REMOTE READY IMPORTANT: This direct-vent burner system must be installed into approved Comfort Glow cast iron stove bodies, models CISGA series and CISCA series ONLY. See page 3 of this manual.
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
This appliance may be installed in an aftermarket* permanently located, manufactured (mobile) home, where not prohibited by state or local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
Save this manual for future reference. Save this manual for future reference.



PRODUCT IDENTIFICATION

5. This stove reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Stove will remain hot for a time after shutdown. Allow sur- faces to cool before touching. 6. Carefully supervise young children when they are in the room with stove. 7. Do not modify the burner or stove under any circumstances. Any parts removed for servicing must be replaced prior to op- erating burner system. 8. Turn burner system off and let cool before servicing, install- ing, or repairing. Only a qualified service person should in- stall, service, or repair the stove or burner system. Have burner system inspected annually by a qualified service person. 9. You must keep control compartments, burners, and circulat- ing air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding mate- rial, pet hair, etc. Turn off the gas valve and pilot light before cleaning stove or burner system. 10. Have venting system inspected annually by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 28. 11. Keep the area around your stove clear of combustible materi- als, gasoline, and other flammable vapor and liquids. Do not run burner system where these are used or stored. Do not place items such as clothing or decorations on or around stove. 12. Do not use this stove to cook food or burn paper or other objects. 13. Never place anything on top of stove. 14. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this stove. Use only the gas type indicated on burner system nameplate. 15. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Ca- nadian Electrical Code, CSA C22.1. 16. Do not obstruct the flow of combustion and ventilation air in any way. Provide adequate clearances around air openings into the combustion chamber along with adequate accessibility clearance for servicing and proper operation. 17. Do not install stove directly on carpeting, vinyl tile, or any com- bustible material other than wood. The stove must set on a metal or wood panel extending the full width and depth of the stove. 18. Do not use stove or burner system if any part has been ex- posed to or under water. Immediately call a qualified service person to arrange for replacement of the unit. 19. Do not operate burner system if any log is broken. 20. Do not use a blower insert, heat exchanger insert, or other ac- cessory not approved for use with this stove. 21 . Do not operate burner system with glass door removed, cracked, or broken.
Figure 1 - Comfort Glow Direct-Vent Burner System Shown Installed in Approved Comfort Glow Cast Iron Stove Body Models CISGA Series and CISCA Series Only
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Grate Assembly · Glowing Embers · Lava Rock


LOCAL CODES PRODUCT FEATURES GLOSSARY OF TERMS PRE-INSTALLATION PREPARATION
LOCAL CODES Install and use stove and burner system with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI Z223.1/NFPA 54* (USA) or the current CSA- B149.1 Installation Code (Canada).

*Available from:
American National Standards Institute, Inc.
1430 Broadway New York, NY 10018
CAUTION: This stove with burner system creates warm air currents. These currents move heat to wall surfaces next to stove. Installing stove next to vinyl or cloth wall coverings or operating stove where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269
LOCATION AND SPACE REQUIREMENTS
This cast iron stove with burner system is clean burning and vents easily through outside walls or vertically using outside air for combustion. Heat is generated by both realistic flames and glowing embers. When used without the blower accessory, the stove with burner system requires no electricity making it ideal for emergency backup heat.
Determine the safest and most efficient location for your Comfort Glow cast iron stove. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows, or doors. Figure 2 shows some common locations. Read all venting information in this manual. Be aware of all restrictions and precau- tions before deciding the exact location for your stove.
When deciding the location of your stove, follow these rules: 1. Do not connect this stove and burner system to a chimney flue serving a separate solid-fuel burning fireplace or appliance. 2. Due to high temperatures, do not locate this stove in high traf- fic areas or near furniture or draperies. 3. Proper clearances must be maintained, see Figures 3 and 4 on page 5. 4. This stove is a freestanding unit designed to set directly on the floor. If your stove is to be installed directly on carpeting, vi- nyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the stove. See Figure 5, page 5.
This burner system has a piezo ignitor. This system requires no matches, batteries, or other sources to light burner system.
Chase - A boxlike enclosure to protect venting from the elements when the venting run is on the outside of a structure.
Mastic - A pliable sealant for use around the vent terminal.
Snorkel Termination - A box that raises the horizontal termination above ground level clearances.
Vent Terminal - Mounted on an outside wall or roof to separate the inlet and outlet of the vent system and protect it from weather.
Vinyl Siding Standoff - A metal box that separates the vent cap from vinyl siding.
On Wall with Horizontal Termination

Wall Thimble/Firestop - A metal plate used to secure the vent pipe when it passes through a wall or ceiling.
On Wall with Vertical Termination Through Ceiling Corner Installation Figure 2 - Common Stove Locations
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com




Figure 4 - Clearance for Corner Installation

Must contain a minimum of 1" clearance to combustibles

Figure 5 - Stove with Burner System Bottom Dimensions

Figure 3 - Clearances for Standard Installation
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Ceiling · Floor


STOVE BODY ASSEMBLY 1. Lift off corrugated box enclosing stove body crating. 2. Remove all screws fastening the wood frame enclosure. Spread wood frame open and lift away from plastic-bagged stove body. The bottom pieces of pallet wood will remain bolted to the stove body. 3. Remove plastic bag from stove body. 4. Remove back panel from stove (see Figure 6). Use an adjust- able wrench or a 10 mm socket. Remove six (6) bolts and wash- ers. Keep bolts and washers to reattach back panel later. 5. Remove all contents from inside stove cavity. Contents include: (1) - Stove bottom (Discard. Not used in this application.) (4) - Legs with leg leveler bolts (1) - Bottom door (1) - Top grate (1) - Hardware kit bag with fasteners 6. Carefully lay stove body on back to attach bottom components to stove body (see Figure 7). Rest stove on drop cloth or blan- ket to avoid scratching stove edges. 7. Remove remaining pallet wood attached to bottom of stove body (see Figure 8). Use an adjustable wrench to remove bolts.
8. Fasten each leg to stove with four (4) M8 x 1.25 - 20mm bolts. Use a flat washer and lock washer with each bolt. Tighten bolts into threaded holes on stove body (see Figures 9 and 10). Use an adjustable wrench or a 12mm socket. 9. Attach stove door by inserting step bolt through door hinge pivot hole and into threaded hole in stove body (see Figure 9 and Figure 11 on page 7). Use an adjustable wrench or a 12mm socket to fasten step bolt. Tighten step bolt until snug. Make sure door moves freely.
Bottom Of Stove Unit
Figure 8 - Removing Pallet Wood from the Bottom of the Stove
Door Catch Bolt With Adjustable Hex Nuts Hole
Door Hinge Step Bolt Hole

Bolt Product Identification Label Back Stove Panel
Bottom Of Stove Unit
Figure 6 - Removing Back Panel
Figure 9 - Locating Threaded Holes for Legs, and Door Attachment Top of Stove Unit


Pallet Wood Bolted to Bottom of Stove Body
Figure 7 - Laying Stove On Side
Figure 10 - Attaching Stove Legs
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


Stove Body Assembly (Cont.) Installing Direct-Vent Burner System Into Stove Body
10. Install door catch bolt (M8 x 1.25-55mm with two M8 hex nuts) into threaded hole on stove body (see Figure 9, page 6). Use an adjustable wrench or a 12mm socket. The catch bolt has two hex nuts attached to it (see Figure 12). The top nut is a bolt stop and the bottom nut is for door leveling adjustment. 11. Check general catch bolt alignment with door claw. Make fi- nal adjustment and door leveling after stove is in normal stand- ing position. 12. Carefully lift stove back up on its four attached legs. 13. Set top grate into stove top.
INSTALLING DIRECT-VENT BURNER SYSTEM INTO STOVE BODY 1. Carefully lift burner system and place into stove body from the rear of stove. 2. Using screws provided, attach burner system to back of stove.

Figure 13 - Installing Burner System Into Cast Iron Stove Body
Figure 12 - Catch Bolt and Door Claw Orientation
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Door Hinge · Step Bolt · Door


Installing GA3750/CDA3620T Blowers 1. Align the holes in the top mounting tabs of blower with holes in wall of rear cover (see Figure 15). Using the 4 screws pro- vided, mount blower and tighten screws securely. Note: For CDA3620T, make sure the thermal switch has been properly installed to fit against the back of the burner system. 2. Make sure all wire connections to terminals on blower motor (and thermal switch where applicable) are securely attached and that the screw retaining the green ground wire is tight. 3. Place speed control on back wall inside of rear cover and push the plastic control shaft through opening (see Figure 15). 4. While supporting speed control, secure control shaft with lock nut by pushing and turning lock nut with pliers clockwise until tight against the side of rear cover. Place control knob provided onto shaft (see Figure 15). 5. Plug in blower power cord. 6. Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign objects in blower wheel. Turn blower on and check for operation. Turn blower off by rotating knob fully counterclockwise before continuing.

When installing the CDA3620T thermostatically-controlled blower accessory, you must first secure the thermal switch to the blower. 1. Remove the two hex head screws on the blower assembly as shown in Figure 14. 2. Place the green wire between the bottom hole on the thermal switch bracket and the bottom hole on the blower assembly. Insert one of the hex screws into all three pieces and tighten. 3. Insert the top screw through the thermal switch bracket and into the blower assembly. Tighten screw. 4. Connect the blue wire on the blower assembly to the right side of the thermal switch. 5. Connect the black wire to the left side of the thermal switch.
Black Wire White Wire

Thermal Switch with Bracket
Mounting Screws (Included in Hardware Pack)

Figure 14 - Attaching Thermal Switch to CDA3620T Thermostatically-Controlled Blower Accessory
Figure 15 - Installing Optional Blower Accessory (Thermostat Model CDA3610T Shown)
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Speed Control · Wiring Diagram Decal · Rear Cover


GENERAL VENTING
These models are approved for use with Simpson Dura-Vent 6 5/8" direct-vent pipe components and terminations as well as both flex and rigid Comfort Glow vent components.

INSTALLING REAR COVER 1. Lift rear panel over vent pipe connection on burner system. Rear cover will rest on the bottom ledge of the stove body. 2. Using screws provided, attach rear cover to back of stove body. See Figure 16. IMPORTANT: This rear cover must be securely in place be- fore venting pipes are installed.

When locating vent termination, it is important to observe the minimum clearances shown in Figure 17, page 10.
*Check with local codes or with the current CAN/CGA B149[.1 or .2] Installation Codes for Canada or the USA Installations follow the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
Figure 16 - Installing Rear Cover
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com



TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA (TERMINATION PROHIBITED) A = clearance above grade, veranda, porch, deck, or balcony
I = clearance to service regulator vent outlet [*72 inches (182.9cm)
[*12 inches (30.5cm) minimum] B = clearance to window or door that may be opened
minimum] J = clearance to non-mechanical air supply inlet to building or the
[12 inches (30.5cm) minimum] C = clearance to permanently closed window [minimum 12 inches
combustion air inlet to any other fireplace [*12 inches (30.5cm) minimum] K = clearance to a mechanical air supply inlet [*72 inches (182.9cm)
(30.5cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal
minimum] L = clearance above paved side-walk or a paved driveway located on
within a horizontal distance of 24 inches (61cm) from the center-line of the terminal [18 inches (45.7cm) minimum] E = clearance to unventilated soffit [12 inches (30.5cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within
public property [*84 inches (213.4cm) minimum] M = clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ] N = clearance above a roof shall extend a minimum of 24 inches (61cm)
above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (45.7cm)
36 inches (91.4cm) horizontally from the center-line of the regulator
vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow the current National Fuel Gas Code, ANSI Z223.1 Note: Local codes or regulations may require different clearances
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Outside Corner Recessed Location


Balcony with No Side Wall
Balcony with Perpendicular Side Wall
recessed location D = Minimum width for back wall of
recessed location - Combustible - 38" (96.5cm) Noncombustible - 24" (61cm) E = Clearance from corner in
Combustible & Noncombustible H = 24" (61cm) J = 20" (50.8cm)
recessed location- Combustible - 6" (15.2cm) Noncombustible - 2" (5.1cm)
G = Combustible 24" (61cm)
Noncombustible 18" (45.7cm)
Figure 17 - Minimum Clearances for Vent Terminations
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Inside Corner



It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness.
For Horizontal Termination: Select the amount of vertical rise desired. The horizontal run of venting must have 1/4" rise for every 12" of run towards the termination.
You may use one or two 90° elbows in this vent configuration. See Horizontal Termination Configurations on page 14.
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this stove and burner system manual and vent kit instructions.
For Vertical Termination: Measure the distance from the burner system flue outlet to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roofline. You may use one or two 90° elbows in this vent configuration. See Vertical Termination Configurations on pages 16 and 17.
For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required (see Figure 29, page 15).
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase, page 12.
Your Comfort Glow stove with direct-vent burner system has been tested for a maximum 17" wall thickness when using a 60º elbow directly off the back of the stove. The maximum horizontal run is 20' with 8' vertical rise (see Installation for Horizontal Termination, pages 12 through 14). The maximum vertical run is 30' (see Installation for Vertical Termination, pages 15 through 17).

It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com



A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is not required for such venting.

INSTALLATION FOR HORIZONTAL TERMINATION 1. Determine the route your horizontal venting will take. Note: The location of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed.
Figure 18 - Snorkel Termination

Snorkel terminations are available (see page 18) for 14" and 36" terminations requiring a vertical rise on the exterior of the building (see Figures 18 and 19). Follow the same installation procedures used for standard horizontal terminations. If install- ing the snorkel termination below grade (basement applications), you must provide proper drainage to prevent water from enter- ing the snorkel termination (see Figure 19). Do not back fill around the snorkel termination. 2. Rigid vent pipes and fittings have special twist-lock connec- tions. Assemble the desired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor.
Twist-lock Procedure: The female ends of the pipes and fit- tings have four locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes and fittings. (All connections must be sealed with high temperature silicone sealant as specified in the second warn- ing statement on page 11.) Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. See Figure 20, page 13. Note: Horizontal runs of vent must be supported every three feet. Use wall straps for this purpose.
Figure 19 - Snorkel Termination with Drainage Pipe
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Snorkel · Adequate drainage


3. Attach vent pipe assembly to the fireplace. Set fireplace in front of it’s permanent location to insure minimum clearances. Mark the wall for a 10" square hole (for noncombustible ma- terial such as masonry block or concrete, a 7 1/2" diameter hole is acceptable). See Figure 21. The center of the hole should line up with the center-line of the horizontal rigid vent pipe. Cut a 10"x10" (25.4cm x 25.4cm) square hole through combustible exterior wall (7 1/2" [19.1cm] diameter hole if noncombustible). Frame as necessary (see Figure 21). 4. Noncombustible Exterior Wall: Apply a bead of non-harden- ing mastic around the outside edge of the vent cap. Position the vent cap in the center of the 7 1/2" hole on the exterior wall with the arrow on the vent cap pointing up. Attach the vent cap with four wood screws provided (see Figure 22). Note: Replace the wood screws with appropriate fasteners for stucco, brick, con- crete, or other types of siding.
5. Conbustible Exterior Wall Only: Slide the interior wall firestop over the vent pipe before connecting the horizontal run to the vent cap (see Figure 24). 6. Carefully move the stove with vent assembly attached toward the wall and insert the vent pipe into the horizontal termina- tion. The pipe overlap should be a minimum of 1 1/4". Apply silicone to the connection. Fasten all vent connections with screws provided. 7. Conbustible Exterior Wall Only: Slide the wall firestop against the interior wall surface and attach with screws provided (see Figure 24).

Combustible Exterior Wall: For vinyl siding, stucco, or wood exteriors, a siding standoff must be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging siding materials. Siding materials must be cut to accommodate standoff. Bolt the vent cap to the stand- off. Apply non-hardening mastic around outside edge of the standoff. Position the standoff/cap assembly in the center of the 10" square hole and attach to exterior wall with wood screws provided (see Figure 23). The siding standoff must sit flush against the exterior fascia material.
Figure 22 - Installing Horizontal Vent Cap (Noncombustible Exterior)
Vinyl Siding Standoff (Apply Mastic to All Four Sides)
Figure 23- Installing Vinyl Siding Standoff (Combustible Exterior)

Figure 20 - Vent Pipe Connections

Vent Cap (Horizontal Termination)
Figure 24 - Connecting Vent Cap with Horizontal Vent Pipe
Figure 21 - Vent Opening Requirements
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


Figures 25 through 28 show different configurations for venting with horizontal termination. Each figure includes a chart with vertical minimum/maximum and horizontal maximum dimensions which must be met. Seal all connections with high temperature silicone sealant (outer pipe only) as specified in the second warning statement on page 11. All horizontal terminations require 1/4" rise per 12" of horizontal run.
Vertical (V) Horizontal (H1) Horizontal (H1) +
Vertical (V) Horizontal (H)
Horizontal (H2)
35" min. 20" max.
5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' min. 20' max. 20' max. 8' max. 20' max.
Figure 25 - Horizontal Termination Configuration for Rigid Venting

Figure 27 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows

42" min. 32" max. (30° elbow with 6" adaptor, 90° elbow, no vertical pipe)
53" min. 44" max. (30° elbow with 6" adaptor, 1' vertical pipe, 90° elbow)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. 20' max. 20' max.
60" min. 60" max. 72" min. 84" max. 89" min. 20' max. Note: This configuration for use with corner installation.
Figure 28 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows with Termination at 90° with Stove
Figure 26 - Horizontal Termination Configuration for Rigid Venting Using One 90° Elbow
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


2. Assemble the desired lengths of pipe and elbows necessary to reach from the burner system flue up through the firestop. All connections must be sealed with high temperature silicone seal- ant as specified in the second warning statement on page 11. Be sure all pipe and elbow connections are fully twist-locked (see Figure 20, page 13). 3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10"x10" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible mate- rials. Frame the opening as shown in Figure 21 on page 13. 4. Connect a section of pipe and extend up through the hole. Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 29). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air. 5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and fram- ing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 29. There must be a 1" clearance from the vent pipe to combustible materials. 6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 17 on page 10. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem. 7. Twist-lock the vent cap onto the last section of vent pipe and seal outer pipe connection with high temperature silicone seal- ant as specified in the second warning statement on page 11. Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allowable clearances to combustibles. Do not fill any of the required air spaces with insulation.
1. Determine the route your vertical venting will take. If ceiling joists, roof rafters, or other framing will obstruct the venting system, consider an offset (see Figure 29) to avoid cutting loadbearing members. Note: Pay special attention to these in- stallation instructions for required clearances (air space) to com- bustibles when passing through ceilings, walls, roofs, enclo- sures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shown in Figure 17 on page 10. 2. Set the stove in desired location. Drop a plumb line down from the ceiling to the position of the burner system exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point. Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Figure 29 - Offset with Wall Strap and 45° Elbows
If area above is not a room, install firestop below framed hole. If area above is a room, install firestop above framed hole.
Flat Ceiling Installation 1. Cut a 10" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10"x10" (25.4cm x 25.4cm) inside dimensions, as shown in Figure 21 on page 13 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 30).

Figure 30 - Installing Firestop
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Roof Flashing · Wall Strap · 45° Elbow


Cathedral Ceiling Installation 1. Remove shingles or other roof covering as necessary to cut the rectangular hole for the support box. Mark the outline of the cathedral ceiling support box on the roof sheathing using the locating hole as a center point. 2. Cut the hole 1/8" larger than the support box outline (see Fig- ure 31). 3. Lower the support box through the hole in the roof until the bottom of the box extends at least 2" below the ceiling (see Figure 31). Align the support box vertically and horizontally using a level. Temporarily tack the support box in place through the inside walls and into the roof sheathing. 4. Using tin snips, cut the support box from the top corners down to the roofline and fold the resulting flaps over the roof sheath- ing (see Figure 32). Apply a bead of non-hardening mastic around the top edges of the support box to make a seal be- tween the box and the roof. Nail in place with roofing nails. Remove any combustible material that might be inside of the support box. 5. Complete the cathedral ceiling installation by following the same procedures outlined in steps 2 through 7 for Flat Ceiling Installation, page 15.
Figures 33 and 34 and Figures 35 and 36 on page 17 show four different configurations for vertical termination. All connections must be sealed with high temperature silicone sealant as specified in the second warning statement on page 11.

Venting with One 90° Elbow
Vertical (V) Horizontal (H)
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.

Figure 33 - Vertical Rigid Venting Configuration Using One 90° Elbow

Horizontal (H2)
2" minimum below finished ceiling
5' min. 2' max. 6' min. 4' max. 7' min. 6' max. 8' min. 8' max. 20' max. 8' max.
Cut hole 1/8" larger than support box when projected onto roofline
Figure 31 - Cathedral Ceiling Support Box Installation
Nonhardening Mastic under all edges of support box before nailing
Figure 32 - Installed Cathedral Ceiling Support Box
Figure 34 - Vertical Rigid Venting Configuration Using Two 90° Elbows with Two Horizontal Runs
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Level


High Altitude Installation Parts Lists For Venting Kits And Components

Venting with Two 90° Elbows
Your Comfort Glow cast iron stove and direct-vent burner system has been CSA tested and approved for operation at altitudes in the USA from 0-2000 ft. and in Canada from 0-4500 ft.
Vertical (V1) Horizontal (H)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max. Note: Vertical (V1) + Vertical (V2) = 20' max.
When installing this stove at an elevation above 2000 feet (in the USA), you may need to decrease the input rating by changing the existing burner orifice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orifice size identification.
When installing this stove at an elevation above 4500 feet (in Canada), check with local authorities.
Consult your local gas company to help determine the proper orifice for your location
For assistance with any high altitude installation contact DESA International’s Technical Service Department at 1-866-672-6040.
Number Description P-47-12-K 12" Black Coaxial Pipe (1 pk) P-47-24-K 24" Black Coaxial Pipe (1 pk) P-47-48-K 48" Black Coaxial Pipe (1 pk) PA47-712-K 7"-12" Black Coaxial Pipe (1 pk) P-47-6-K 6" Black Coaxial Pipe (1 pk) E47-60-K 60° Elbow (1 pk) E47-30-K 30° Elbow (1 pk) E47-90-K 90° Elbow (1 pk) E47-45-K 45° Elbow (1 pk) PA-47-6-K 6" Adaptor Collar, Black (1 pk) WS-47 Wall Strap (1 pk) SC-47 Storm Collar (1 pk) VT-47 Vertical Round Termination (1 pk) WF-47 Wall Firestop (1 pk) VR-47 Vertical Restrictor (1 pk) FP-47 Firestop Plate (1 pk) HTS-47 Horizontal Square Termination (1 pk) CS-47 Cathedral Ceiling Support Box (1 pk) RF-47-6 Roof Flashing 0 to 6/12 Pitch (1 pk) RF-47-12 Roof Flashing 6/12 to 12/12 Pitch (1 pk) S-47 Vinyl Siding Standoff (1 pk) TP-47 Trim Plate, Black (1 pk) HT-47 Horizontal Round Termination (1 pk) ST-47-14 14" Snorkel Termination (1 pk) ST-47-36 36" Snorkel Termination (1 pk)
Figure 35 - Vertical Rigid Venting Configuration Using Two 90° Elbows

V = 40' max.
Figure 36 - Vertical Rigid Venting Configuration With No Horizontal Run
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Vertical Venting · RVKBK Kit Shown


Check Gas Type Installing Gas Piping To Stove/Burner System Location

Use proper gas type for the burner system unit you are installing. If you have conflicting gas types, do not install burner system. See dealer where you purchased the stove and burner system for proper burner system according to your gas type.
Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from burner system (see Figure 38, page 19).
Check your building codes for any special requirements for locating equipment shutoff valve to stoves.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves.
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 36.
Figure 37 - External Regulator with Vent Pointing Down (Propane/LP Only)
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regu- lator with the vent pointing down as shown in Figure 37. Pointing the vent down protects it from freezing rain or sleet.
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Propane/LP Supply Tank · External Regulator · Vent Pointing Down



We recommend that you install a sediment trap in supply line as shown in Figure 38. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into burner system gas controls. If sediment trap is not installed or is installed wrong, burner system may not run properly.
Flexible Gas Line from Equipment Shutoff Valve Provided by Installer
Natural - To Gas Supply Propane/LP - To External Regulator
CSA Design-Certified Equipment Shutoff Valve with 1/8" NPT Tap*

Figure 39 - Flexible Gas Line
Propane/LP - From External Regulator (11" W.C. to 14" W.C. Pressure)

Natural - From Gas Meter (5" W.C. to 10.5" W.C. Pressure)
Cap Pipe Tee Nipple Joint
Figure 38 - Gas Connection
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) 1. Disconnect burner system and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage burner system gas regulator. 2. Cap off open end of gas pipe where equipment shutoff valve was connected. 3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas burner system or open- ing main gas valve located on or near gas meter for natural gas burner system, or using compressed air. 4. Check all joints of gas supply piping system. Apply a noncor- rosive leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once. 5. Reconnect burner system and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
* The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your dealer.
Installation Items Needed
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Equipment Shutoff Valve · Sediment Trap


Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa) 1. Close equipment shutoff valve (see Figure 40). 2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas burner system or open- ing main gas valve located on or near gas meter for natural gas burner system, or using compressed air. 3. Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 41 for propane/LP or Fig- ure 42 for natural). Apply a noncorrosive leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Burner System Gas Connections 1. Open equipment shutoff valve (see Figure 40). 2. Open propane/LP supply tank valve for propane/LP burner system or main gas valve located on or near gas meter for natu- ral gas burner system. 3. Make sure control knob of burner system is in the OFF position. 4. Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 41 for propane/LP or Figure 42 for natu- ral). Apply a noncorrosive leak test solution to all gas joints. Bubbles forming show a leak. Correct all leaks at once. 5. Light burner system (see Operating Stove with Burner System, pages 23 through 26). Check all other internal joints for leaks. 6. Turn off burner system (see To Turn Off Gas to Appliance, page 24).
Figure 41 - Checking Gas Joints for Propane/LP Gas Burner System

Figure 42 - Checking Gas Joints for Natural Gas Burner System
Figure 40 - Equipment Shutoff Valve
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Open · Equipment Shutoff Valve · Closed


STOVE AND DIRECT-VENT BURNER SYSTEM INSTALLATION Installing Optional Wireless Hand-held Remote Control Accessories - CGHRC and CGHRCTA Series
Installing Remote Receiver 1. Open bottom door on stove body and locate the switch plate on the left of the valve bracket. 2. Unscrew switch plate (see Figure 43). 3. Disconnect wires from THTP and TH on control valve that lead to the switch (see Figure 44). Discard switch plate, screws, and nuts. 4. Install battery into receiver battery clip and connect to termi- nals (see Figure 45). 5. Place receiver into valve bracket and align holes (see Figure 46). 6. Use push-in fasteners included with receiver to secure to bracket. 7. Connect the wires from the receiver to the valve at TH and THTP (see Figure 44).
Figure 46 - Installing Remote Receiver
Installing 9-Volt Battery in Hand-Held Remote Control Unit 1. Remove battery cover on back of remote control unit 2. Attach terminal wires to a 9-volt battery (not included). Place battery into the battery housing. 3. Replace battery cover onto remote control unit.
Terminal Wires Battery Cover 9-Volt Battery

Figure 43 - Removing Switch Plate
Figure 47 - Installing Battery in Hand-Held Remote Control Unit
To Control Switch or Optional Accessory
You must remove glass door to install logs, lava rock, and ember material. To remove glass door, you must first remove the front panel on stove body.

Figure 44 - Control Valve Terminals

Figure 45 - Installing Battery in Receiver
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


Removing/Replacing Glass Door (Cont.) Installing Logs, Lava Rock and Glowing Embers
4. Place log #3 (left piece) onto the front left part of the grate. Make sure it is seated properly over the prong of the grate as shown in Figure 52. 5. Place log #4 (right piece) onto the front right part of the grate making sure the notches fit over the prong of the grate (see Figure 53). 6. Place lava rock along sides and front of inside of burner system bottom. It is not necessary to use all of the lava rock provided.


Figure 48 - Removing Front Panel from Stove

Figure 50 - Installing Log No. 1
Figure 51 - Installing Log No. 2
Figure 49 - Removing Glass Door from Burner System Insert


Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with freestanding burner system. Do not use if any log(s) are broken (see Replacement Parts, page 31). 1. Remove glass door. See Removing/Replacing Glass Door, pages 21 and 22. 2. Place log #1 (back log) on top of grate. Make sure the notches in the bottom of the log fit over the grate (see Figure 50). 3. Rest log #2 (large front log) on the pins on the front part of the grate (see Figure 51).
Figure 52 - Installing Log No. 3 Figure 53 - Installing Log No. 4
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Screw


OPERATING STOVE WITH BURNER SYSTEM

7. Pull ember material apart into pieces no larger than a dime. Place these pieces loosely and sparingly directly onto the ex- posed section of the front burner and along the space between the burner and grate prongs (see Figure 54). This will create the glowing ember appearance as the flame touches the ember material. Do not block air slots by using too much ember ma- terial in one area. It is not necessary to use all of the ember material provided. 8. Replace the glass door and stove front. See Removing/Replac- ing Glass Door, pages 21 and 22.

Figure 54 - Placing Ember Material on Burner
to “OFF”. 6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Fol- low “B” in the safety information above. If you don't smell gas, go to the next step. 7. The pilot is located by the main burner and should not require accessing for lighting.
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


LIghting Instructions (Cont.) To Turn Gas Off To Appliance Manual Lighting Procedure Optional Remote Operation
PROCEDURE
OPERATION
TO APPLIANCE
Thermostat Control Operation
(Optional CGHRCTA Only) The thermostat control setting on the remote control unit can be set to any comfort level between HI and LO. The burners will turn on and off automatically to maintain the comfort level you select. The ideal comfort setting will vary by household depending upon the amount of space to be heated, the output of the central heating system, etc.
1. After lighting, let pilot flame burn for about one minute. Turn gas control knob on the control valve to ON position. Turn variable control knob anywhere between HI and LO. Slide the selector switch to the REMOTE position. Note: The burners may light if hand-held remote ON button was on when selector switch was last turned off. You can now turn the burners on and off with either optional hand-held remote control unit. IMPORTANT: Do not leave the selector switch in the RE- MOTE position when the pilot is not lit. This will drain the battery. IMPORTANT: Be sure to press the ON/OFF buttons on the hand-held remote control unit for up to 3 seconds to assure proper operation.
You may shut off the burners and keep the pilot lit by doing one of the following: 1. Turn gas control knob clockwise to the PILOT position. 2. Set selector switch in the OFF position.
Variable Control Knob Piezo Ignitor

Figure 55 - Control Valve
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Gas Control Knob


CGHRC Series Operation: 2a. Press the ON/OFF button to turn the burners on and off. When turning burners off, the pilot will remain lit.

The Log Heater will Automatically Cycle between Pilot and the Heat Setting that has been Selected
Turns Burners On or Off and Allows You to Choose the Auto Setting
Figure 57 - Hand-Held Thermostat Remote Control Unit Selections (CGHRCTA Only)
Locate the blower controls by opening the lower door on the stove. Blower controls are located on the left side of the switch bracket to the left just inside the door.
Both the GA3700 manual blower and the DA3610T thermo- statically-controlled blower have an ON setting and an OFF setting. The blower will only run when the switch is in the ON position. In the OFF position, the blower will not operate.
Note for DA3610T Only: If you are using DA3610T blower with optional thermostat (wall mount or remote control) for the burner system, your burner system and blower will not turn on and off at the same time. The burner system may run for several minutes before the blower turns on. After the burner system modulates to the pilot position, the blower will continue to run. The blower will shut off after the burner system temperature decreases.
Selector Switch in Remote Position (Optional Remote Control)
Variable Control Knob Gas Control Knob in On Position
LO
IN OUT
The blower helps distribute heated air from the burner system. Periodically check the air passageways of the burner system and remove any dust, dirt, or other obstructions that will hinder the flow of air.
Figure 56 - Setting the Selector Switch, Gas Control Knob, and Variable Control Knob for Remote Operation
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com




Light the burner system as instructed in Lighting Instructions on pages 23 and 24. Set wall thermostat to desired temperature.
This thermostat has been electronically calibrated at the factory and requires no adjustment or leveling. Upon installation, the thermostat must be allowed to stabilize at room temperature for a minimum of 30 minutes for proper operation. To turn the burner system off, adjust thermostat to the lowest setting and turn the gas control knob back to PILOT. The pilot will remain lit.
Figure 58 - Pilot Assembly
Burner flames will be steady; not lifting or floating. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent configuration is installed incorrectly, the flames will lift or "ghost". This can be dangerous. Inspect the flames after installa- tion to ensure proper installation and performance.
Check pilot flame pattern and burner flame patterns often.
The pilot assembly is factory preset for the proper flame height. Alterations may have occurred during shipping and handling. Call a qualified service person to readjust the pilot if necessary.

The height of the thermopile must be 3/8" to 1/2" above the pilot flame as shown in Figure 58. The thermocouple must be at a height of about 1/8" above the pilot flame. The flame from the pilot burner must extend beyond both the thermocouple and thermopile.
Figure 59 - Typical Flame Pattern
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


If glass has been broken, carefully remove glass door (see Remov- ing/Replacing Glass Door, pages 21 and 22). Vacuum all glass pieces with a shop vac.

Use only the ceramic glass door replacement intended for this burner system (see Replacement Parts, page 31 for detail on ordering). No substitutions may be made. See Removing/Replacing Glass Door, pages 21 and 22 for instructions for replacing glass door.

Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust, and other airborne particles to cling to the glass surface. During initial start-up a slight film may form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, non- abrasive household cleaner and warm water after the first two weeks of operation. Thereafter, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door on pages 21 and 22 of this manual when removing glass door for cleaning.
Conduct annual inspection of the venting system following these guidelines: 1. Check areas of venting system that are exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced immediately by a qualified service person. 2. Remove the vent cap and shine a flashlight into the vent. Re- move any foreign material. 3. Check for evidence of excessive condensation. Continuous condensation can cause corrosion of caps, pipes, and fittings and can be caused by having excessive lateral runs, too many elbows, or exterior portions of the system being exposed to cold weather. 4. Inspect joints to verify that no pipe section or fitting has been disturbed and loosened. Check mechanical supports such as wall straps for rigidity.

105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com



POSSIBLE CAUSE
REMEDY
When ignitor button is pressed, there is no spark at pilot
When ignitor button is pressed, there is spark at pilot but no ignition
Pilot lights but flame goes out when control knob is released
B) Clean pilot (see Cleaning and Maintenance, page 27) or replace pilot assembly
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


POSSIBLE CAUSE
REMEDY
Burner does not light after pilot is lit
Burner backfiring during combustion
Slight smoke or odor during initial operation
Burner system produces a whistling noise when burner is lit
Burner system produces a clicking/ticking noise just after burners are lit or shut off
Remote does not function
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Delayed ignition burner · Glass soots



POSSIBLE CAUSE
REMEDY
Burner system produces unwanted odors
Burner system shuts off in use

Gas odor even when control knob is in OFF position
Dark residue on logs or inside of burner system
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


REPLACEMENT PARTS

Variable Fan Switch Fan Switch

Figure 60 - Blower Wiring Diagram for Thermostat-Controlled Models

Stove and Burner System* 26 1/2" x 25" x 25 5/8" 26 1/2" x 25" x 25 5/8" 673.1 x 635 x 650.7mm 673.1 x 635 x 650.7mm Carton (Insert Only) 23 1/4" x 33 1/4" x 23 1/2" 23 1/4" x 33 1/4" x 23 1/2" 590.5 x 844.5 x 596.9mm 590.5 x 844.5 x 596.9mm Weight, lbs/kg
Burner System 70 lbs/31.8 kg 70 lbs/31.8 kg Shipping 75 lbs/34 kg 75 lbs/34 kg
* When installed in Comfort Glow cast iron stove body (CISGA Series and CISCA Series).
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com



105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


This list contains replaceable parts used in your burner system. When ordering parts, follow the instructions listed under Replace- ment Parts on page 31 of this manual.
KEY NO. PART NUMBER DESCRIPTION QTY.
1 ** Firebox Assembly 1 2 M11084-26 Screw, Hex 2 3 27129 Rear Cover 1 4 M11084-39 Screw, Hex 12 5 103587-02 Switch Plate 1 6 099998-01 On/Off Switch 1 7 103284-04 Wire Harness 1 8 104491-01 Relief Cover 1 9 104518-01 Relief Cover Gasket 1 10 104527-01 Relief Spring 2 11 104528-01 Relief Washer 2 12 H5C4-20B Hex Head Cap Screw 2 13 NTC-4C Locknut 2 14 105468-02 Valve Bracket 1 15 14389 Valve, Natural 1 14390 Valve, Propane/LP 1 16 14561 Pilot Assembly, Natural 1 14562 Pilot Assembly, Propane/LP 1 17 102445-01 Ignitor, Piezo 1 18 102334-01 Palnut Fastener 1 19 105523-01 Burner, Natural 1 105523-02 Burner, Propane/LP 1 20 104506-01 Orifice, Natural 1 104506-02 Orifice, Propane/LP 1 21 14528 Brass Elbow 1 22 901056-01 Brass Elbow 2 23 105493-01 Aluminum Tubing Assy 1 24 105795-01 Glass Door Assy 1 25 105325-01 Air Deflector 1 26 14585 Log Set 1 26-1 105773-01 Rear Log 1 26-2 105773-02 Front Log 1 26-3 105773-03 Left Log Piece 1 26-4 105773-04 Right Log Piece 1 27 M10908-2 Screw 18 28 11107 Screw 4 29 M12461-62 Screw 2 30 104555-03CJ Grate Assembly 1 31 105483-01 Burner Bracket 1
GA6060 Lava Rock 1 14250 Ember Material 1 M11084-3 Hex Screw for Blower Bracket 4
** Not a field replaceable part.
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com



105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


This list contains replaceable parts used in your stove. When ordering parts, follow the instructions listed under Replacement Parts on page 31 of this manual.
KEY PART NO. NO. DESCRIPTION QTY.
1 104968-01 Stove Back Panel (Black Only) 1 2 104969-01 Bottom Door (Charcoal) 1 104969-02 Bottom Door (Forest Green) 1 3 104174-03 Stove Dropped Bottom 1 4 104970-01 One Leg (Charcoal) (4 Total Per Stove) 1 104970-02 One Leg (Forest Green) (4 Total Per Stove) 1 5 104971-01 Hardware Kit 1 5-1 * Door Hinge Step Bolt With Shoulder (1 Per Unit) 1 5-2 * Door Catch Bolt M8 x 1.25 - 55mm Long With Two M8 Hex Nuts (1 Per Unit) 1 5-3 * Bottom Floor Bolts M6 x 1 - 25mm Long With Flat Washer And Lock Washer (4 Per Unit) 1 5-4 * Leg Attachment Stud, Headless, Slotted, M10 x 1.5 - 40mm Long 4 7 104178-01 Back Panel Bolts M6 x 1 - 20mm Long With Flat Washer And Lock Washer (6 Per Unit) 1
104108-08 Touch-up Spray Paint 12 oz Can (Charcoal) 1 104108-05 Touch-up Spray Paint 12 oz Can (Forest Green) 1
* Included In Hardware Kit
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


You may have further questions about installation, operation, or troubleshooting. If so, contact DESA International’s Customer Service Department at 1-866-672-6040. When calling, please have your model and serial numbers of your heater ready.
You can also visit DESA International’s technical service web site at www.desatech.com.
For all models. Allows the burner system to be turned on and off conveniently.
AUTO
COOLER
TEMP
OFF
ON
If you feel your gas pressure is too low or gas quality is bad, contact your local natural or propane/LP gas supplier.
ACCESSORIES
Purchase these stove and burner system accessories from your local dealer. If they can not supply these accessories, call DESA International’s Sales Department at 1-866-672-6040. for informa- tion. You can also write to the address listed on the back page of this manual.
For all models. Allows the burner system to be operated in a manually or thermostatically-controlled mode. You can adjust your heat settings and turn the burner system on or off without leaving the comfort of your easy chair. (Requires part no. 103284-04 wire harness included with burner system.)
For all models. Manual-variable control blower accessory for both the CDVBN(A) and CDVBP(A) Series burner systems.
For all models. Provides better heat distribution. Blower turns off and on automatically, as needed. Complete installation and opera- tion instructions included in this manual.
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com

In order to provide better customer service for this and future purchases, we recommend that you register your product with us. You can register online at www.desatech.com. If access to our website is not available to you, please complete this Owner’s Registration Form and mail to the address on the back of this owner’s manual. Please provide the following product information:
Date Purchased: Note: Keep receipt for warranty verification.
Serial Number: 7 or 9 digit number located on product or identification tag.
Address:
E-Mail:
Please answer the following questions to register your product with DESA International:
❍ Living/Family Room ❍ Office/Warehouse ❍ Utility Shed/Outbuilding ❍ Garage ❍ Bedroom ❍ Bathroom ❍ Other
❍ 100,000 to 250,000 ❍ Over 250,000
❍ Fireplace or Hearth Shop ❍ Farm Store ❍ Other
❍ Emergency Back-Up Heat ❍ Heater was on Sale ❍ Energy Savings/High Efficiency ❍ Construction Project ❍ Other
❍ $50,000 to $74,999 ❍ $75,000 to $99,999 ❍ $100,000 and Over
Not Important Somewhat Important Very Important
Availability Price Brand Name Overall Quality Heat Output Made in USA Warranty Local Service Value for Price Prior Brand Experience Controls Location Thermostat, Remote, or Manual Operation Ease of Operation Special Features Salesperson’s Recommendation Friend/Relative’s Recommendation Portability Quiet Operation
❍
❍
❍
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com


2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004

105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
Postage Required


105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com



Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
COMFORT GLOW LIMITED WARRANTY DIRECT-VENT BURNER SYSTEM AND STOVE CHASSIS
DESA International warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this stove and burner system to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The stove and burner system MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective stove and burner system will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com
105501-01 Rev. G 02/03
105501-01G For more information, visit www.desatech.com For more information, visit www.desatech.com
105501 01
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.