Liebert Interceptor II

31 pages·1.6 MB·Surge Protector·PDF·ENDEFRITNLJA
Liebert Interceptor II
Table of Contents 80 sections For Business-Critical Continuity ™ · PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Products · Surge Protection · Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar, · … ShowHide
For Business-Critical Continuity ™p.1PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Productsp.1Surge Protectionp.1Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar,p.1Installation, Operation and Maintenance Manualp.1To maximize system performance locate unit asp.4close as possible to protected circuit and keep inter-p.4EQUIPMENT PERFORMANCE!!p.4Warnings Defi nedp.4INSTALLATION INSTRUCTIONSp.4UNPACKING AND INSTALLATIONp.4Unpacking and Preliminary Inspectionp.4Handling Considerationsp.4Location Considerationsp.4Storagep.4ELECTRICAL CONNECTIONSp.5For maximum system performance, the unit must bep.5located as close to the protected circuit as practicalp.5Voltage Ratings and Power Source Confi gurationsp.5DE-ENERGIZED AND LOCKED OUT BEFOREp.5VERIFY THAT ALL POWER CIRCUITS AREp.5150 L-N 120Sp.6320 L-N 240S 240, 277 240, 277 480p.6347 347 600 420 L-N 347Sp.6N/A 208 208 250 L-L 208Dp.6240Dp.6400Dp.6480Dp.6N/A 600 600 580 L-L 600Dp.6120/240/120 120/240/120 240 150 L-N 240Np.6240/480/240 240/480/240 480 250 L-N 480Hp.6120Yp.6127Yp.6230Yp.6254Yp.6277Yp.6347Yp.6VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONSp.6150 L-Np.6320 L-Np.6420 L-Np.6150 L-Gp.6320 L-Gp.6420 L-Gp.6275 L-Np.6130 L-Lp.6150 L-Lp.6275 L-Lp.6420 L-Lp.6320 L-Lp.6580 L-Lp.6L-N L-G L-Lp.6100 100 N/Ap.6110 110 N/Ap.6120 120 N/Ap.6230 230 N/Ap.6277 277 N/Ap.6N/A 208 208p.6N/A 240 240p.6N/A 400 400p.6N/A 480 480p.6N/A 600 600p.6N/A 380 380p.6N/A 415 415p.6N/A 120 208p.6N/A 127 220p.6N/A 220 380p.6N/A 230 400p.6N/A 254 440p.6N/A 277 480p.6N/A 347 600p.6Source Confi gurationsp.6G Np.6Typical Parallel Connections (without Internal Rotary Disconnect)p.7Typical Parallel Connections (with Internal Rotary Disconnect)p.7FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IFp.8PROVIDED), MUST BE RELIABLY CONNECTED TO THEp.8NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABLEp.8NEUTRAL CONNECTION MAY RESULT IN MODULE FAILURE!p.8SPD Monitoringp.8
Page 1 of the Liebert Interceptor II user manual — Installation, Operation and Maintenance Manual
Page 1 · click to enlarge
Page 1
Liebert Interceptor II — For Business-Critical Continuity ™ diagram (page 1)
Fig. 1 · For Business-Critical Continuity ™

For Business-Critical Continuity ™

PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Products

Surge Protection

Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar,

Installation, Operation and Maintenance Manual

Page 2 of the Liebert Interceptor II user manual — For Business-Critical Continuity ™
Page 2 · click to enlarge
Page 2
Page 2 of the Liebert Interceptor II user manual — For Business-Critical Continuity ™
Page 3 of the Liebert Interceptor II user manual — For Business-Critical Continuity ™
Page 3 · click to enlarge
Page 3
Page 3 of the Liebert Interceptor II user manual — For Business-Critical Continuity ™
Page 4 of the Liebert Interceptor II user manual — Storage
Page 4 · click to enlarge
Page 4

The installer should perform the following steps to assure a

quality installation. The entire installation manual should be

read before starting installation. These instructions do not

replace national or local electrical codes. Check applicable

electrical codes to ensure compliance. Installation of the Liebert

SPD system should only be performed by qualifi ed personnel.

For optimum transient surge protection, coordinated surge

suppression should be applied at the service entrance and all

other electrical connections to the building (telephone, CATV,

etc.), at known surge generating loads within the building

(large motors, arc welders, switched capacitors, etc.), as well

as at sensitive electronic loads (such as computers, electronic

appliances, solid state motor drives, etc.). For interconnected

electronic loads (such as by way of data cabling), transient surge

suppression should also be applied to the interconnecting

Mounting — Unit is intended to be wall mounted. Refer to

individual instruction sheet or unit submittal drawings for

hazardous situation that, if not

avoided, will result in death or

serious injury. This signal word

is to be limited to the most

hazardous situation that, if not

avoided, could result in death or

hazardous situation that, if not

avoided, may result in minor or

moderate injury. It may also be used

To maximize system performance locate unit as

close as possible to protected circuit and keep inter-

to alert against unsafe practices.

EQUIPMENT PERFORMANCE!!

extreme situations.

typical mounting dimensions and weight.

serious injury.

connecting wiring less than 5 ft.

wiring (data cables).

Warnings Defi ned

INSTALLATION INSTRUCTIONS

UNPACKING AND INSTALLATION

The Liebert Surge Protective Devices (SPDs) are high quality,

high energy surge current diversion systems designed to

protect sensitive equipment from damaging transient voltage

surges. Proper installation is required for maximum system

1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit.
2. Remove any securing bands and cardboard packing and inspect the unit for any obvious shipping damages.
3. If any damage as a result of shipping is observed, immediately fi le a claim with the shipping agency and forward a copy to

Larger units are bolted to a shipping pallet to facilitate handling

by forklift or pallet jack. Check the size and weight. Refer to

The unit should be stored in a clean, dry environment. Storage

temperature range is -55ºC (-67ºF) to +85ºC (+185ºF). Care

should be taken to avoid condensation. All packing and

shipping materials should be left intact until the unit is ready

for fi nal installation. If the unit has been stored for an extended

period of time, the unit should be cleaned and carefully

Environment — The unit is designed for operation indoors in

ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) with

The unit is provided in an industrial use enclosure, which is

dust-tight and drip-tight and should not be installed in areas

with excessive dust, corrosive vapors, fl ammable materials or

Audible Noise — The audible noise of the unit is less than

40 dB at 5 feet, which allows its placement within almost any room if desired.

Service Clearances — Service clearance is needed for units with

hinged doors on the front that are capable of being opened.

Thirty-six inches (36 in/914 mm) minimum is recommended.

a relative humidity of 0% to 95% (non-condensing).

Unpacking and Preliminary Inspection

your local Liebert Sales Representative.

the cabinet data furnished with the unit.

inspected before placing into service.

Handling Considerations

Location Considerations

explosive atmospheres.

performance.

Storage

Page 5 of the Liebert Interceptor II user manual — EQUIPMENT PERFORMANCE!!
Page 5 · click to enlarge
Page 5

The following is from the National Electric Code 2002 Edition.

285.21 Connection. Where a TVSS is installed, it shall be connected as follows:

(1) Service Supplied Building or Structure. The transient

voltage surge suppressor shall be connected on the

load side of a service disconnect overcurrent device

(2) Feeder Supplied Building or Structure. The transient

voltage surge suppressor shall be connected on the

load side of the fi rst overcurrent device at the building

Exception to (1) and (2)Where the TVSS is also listed as a surge

(3) Separately Derived System. The TVSS shall be

connected on the load side of the fi rst overcurrent

Disconnect Switch (If Provided) — All SPD units must still be

connected to the load side of the main service disconnect, or

Surge Voltage Ratings — To obtain the suppression voltage

ratings (SVRs), as obtained by Underwriters Laboratory,

Incorporated, in accordance with the Standard for Safety,

Transient Voltage Surge Suppressors (TVSS), Standard 1449,

Second Edition, dated August 15, 1996, marked on this

product, the wire size listed for each product must be utilized

to connect the unit to your facilities’ power grid. Connections

made with conductors other than the wire size listed may

Circuit Ampacity Limitations — Representative samples

of these products have been investigated by Underwriters

Laboratories, Incorporated to withstand, without exposing

live circuits or components at system voltages and fault

currents ranging from 14,000 AIC up to 200,000 AIC, as

described in the Standard for Safety, Transient Voltage Surge

Suppressor (TVSS), Standard 1449, Second Edition, dated

August 15, 1996. Verify each products fault current rating on

arrestor, the connection shall be as permitted by Article 280.

load side of a protected circuit’s disconnecting means.

device in a separately derived system.

the individual installation pages that follow.

required in 230.91.

result in different SVRs.

or structure.

ELECTRICAL CONNECTIONS

(A) Location.

All electrical connections should be installed by a qualifi ed

(licensed) electrician only. All wiring must comply with the

Before making connections to the unit, verify that the unit

model number and nameplate voltage rating are appropriate

for connection to the intended power source. See the chart

on page 4 for voltage rating applications with typical power

To reduce the wiring impedance to surge currents, it is

recommended that the phase, neutral (if required), and ground

conductors are twisted together and routed in the same

Wire Sizing — With parallel connection, the size of the

wiring to the SPD unit is independent of the protected

circuit’s ampacity. For suggested wire size refer to individual

NEC Article 285-21(B) requires surge suppressor connecting

Overcurrent Protection — The SPD unit conducts practically

no current under normal operation and only conducts very

For maximum system performance, the unit must be

located as close to the protected circuit as practical

raceway (conduit). Avoid any sharp bends in the conductors.

National Electrical Code (NEC) and applicable local codes.

Voltage Ratings and Power Source Confi gurations

conductors to be at least #14 copper or #12 aluminum.

DE-ENERGIZED AND LOCKED OUT BEFORE

VERIFY THAT ALL POWER CIRCUITS ARE

MAKING ELECTRICAL CONNECTIONS.

to minimize interconnecting wiring length.

EQUIPMENT PERFORMANCE!!

Parallel Connection (see Figures on page 5)

short duration transient surge currents.

source confi gurations.

product sheet.

Page 6 of the Liebert Interceptor II user manual — G
Page 6 · click to enlarge
Page 6

Maximum Continuous Model Voltage Code

(Found in part number)

120 N or 120-

120 N or 120-

120 N or 120-

230 N or 230-

277 N or 277-

347 347 N/A 420 L-N 347 N or 347-

150 L-N 120S

320 L-N 240S 240, 277 240, 277 480

347 347 600 420 L-N 347S

N/A 208 208 250 L-L 208D

240D

400D

400D

400D

480D

N/A 600 600 580 L-L 600D

120/240/120 120/240/120 240 150 L-N 240N

240/480/240 240/480/240 480 250 L-N 480H

120Y

127Y

230Y

230Y

254Y

277Y

347Y

VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS

150 L-N

150 L-N

320 L-N

320 L-N

320 L-N

320 L-N

420 L-N

150 L-G

150 L-G

320 L-G

320 L-G

320 L-G

320 L-G

420 L-G

150 L-N

150 L-N

150 L-N

275 L-N

320 L-N

130 L-L

150 L-L

275 L-L

275 L-L

420 L-L

320 L-L

580 L-L

580 L-L

580 L-L

580 L-L

120 120 208, 240

L-N L-G L-L

100 100 N/A

110 110 N/A

120 120 N/A

230 230 N/A

277 277 N/A

N/A 208 208

N/A 240 240

N/A 400 400

N/A 480 480

N/A 600 600

N/A 240 240

N/A 380 380

N/A 400 400

N/A 415 415

N/A 480 480

N/A 120 208

N/A 127 220

N/A 220 380

N/A 230 400

N/A 254 440

N/A 277 480

N/A 347 600

N

G

N

G

G

Three Phase Wye, 3 W + G No Neutral

A

N

B

G

Source Confi gurations

A

B

G

Three Phase Delta Hi Leg, 4 W + G

B

A

G N

A

B

G

Single Phase L-N, 2 W + G

Three Phase Delta, 3 W + G

Three Phase Wye, 4 W + G

Single Phase L-L, 2 W + G

Single Phase, 3 W + G

G

N

G

N

G

VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS Source Confi gurationsNominal Operating Voltage L-N L-G L-LMaximum ContinuousModel Voltage Code (Found in part number) 100 100 N/A150 L-N120 N or 120- 110 110 N/A150 L-N120 N or 120-
Show 13 more labels / short text on this page
208L or 208- · 240L or 240- · 400L or 400- · 480L or 480- · 600L or 600- · 120 120 208 · 127 127 220 · 220 220 380 · 230 230 400 · 254 254 440 · 277 277 480 · 347 347 600 · Nominal Operating Voltage
Page 7 of the Liebert Interceptor II user manual — Typical Parallel Connections (without Internal Rotary Disconnect)
Page 7 · click to enlarge
Page 7

Typical Parallel Connections (without Internal Rotary Disconnect)

Typical Parallel Connections (with Internal Rotary Disconnect)

Panel Wire should be

less than 5 feet

Panel Wire should be

less than 5 feet

Show 40 more labels / short text on this page
Protected · Loads · Protected · To · To · Loads · Liebert · Protective · Device · Surge · Protective · Liebert · Surge · Device · Phase(s) · Transient · Ground · Safety · Ground · Neutral · Neutral · Phase(s) · Transient · Ground · Ground · Safety · Disconnect · Rotary · and straight · as possible · and straight · as possible · Neutral · Neutral · Protected · Phases · Protected · Phases · Ground · Ground
Page 8 of the Liebert Interceptor II user manual — System Grounding and Bonding
Page 8 · click to enlarge
Page 8

FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF

PROVIDED), MUST BE RELIABLY CONNECTED TO THE

NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABLE

External Status Indicators — These indicators provide a

summary of the status of the surge SPD module. For normal

conditions, the green “OK” LED is illuminated and the red

“Service” LED is extinguished. If the surge SPD module

requires replacement, the green “OK” LED is turned off and

Summary Alarm Contact (if applicable) — Summary alarm

Form C (1 N.O. and 1 N.C.) relay contacts may be provided for

Contacts are rated 5 amps at 250 VAC maximum with a power

factor of 1.0. For units with Summary Alarm Contacts, access

to the contacts are typically provided via contact terminals

located on the printed circuit board mounted on the inside of

Transient Counter (if applicable) – Transient counters are

provided for transient voltage surge monitoring. The counter

The transient counter monitors line transient voltages. The

circuit counts all surges that deviate from the line sine wave.

The factory setting is 30% over nominal line voltage. Other

Swell Counter (if applicable) — The swell counter monitors

line to line & line to neutral voltages. It is factory set to record

whenever the peak voltage on any normal mode exceeds the

nominal voltage of the TVSS for more than 10ms. This counter

records temporary line over voltages that may result from

Audible Alarm (if applicable) — If the surge SPD module

requires replacement, an audible alarm is activated to draw

the system to normal operation. An audible alarm disable is

provided to silence the alarm. The system will automatically

reset itself after repair. The audible alarm switch and “Service”

LED can be tested by activating the “Test” switch on the

system monitor panel. For information on the AccuVar Series

NEUTRAL CONNECTION MAY RESULT IN MODULE FAILURE!

totalizes surges monitored since the last counter reset.

remote indication of the failed surge SPD module.

utility switching, line regulation problems, etc.

settings include 50%, 70%, and 100%.

the red “Service” LED illuminated.

Alarm, see page 16.

SPD Monitoring

the unit’s cover.

The performance and safety of any SPD system is dependent

on proper grounding and bonding. Grounding is required for

safety. Correct implementation also enhances equipment

performance. Incorrect grounding can reduce or impede the

All electrical circuits to the SPD must include an equipment-

grounding conductor as required by the NEC and local codes.

An insulated grounding conductor is required in addition to any

metallic raceway, which may be used as a grounding conductor.

For parallel-connected SPDs, the grounding conductor should

be the same wire size as the associated power conductors.

Grounding conductors must be routed with the associated

When metallic raceways are used, adequate electrical

continuity must be maintained at all raceway connections,

particularly raceway terminations to the electrical enclosures.

The use of isolating bushings or other means to interrupt a

metallic conduit run is a potential safety hazard and is not

Grounding Electrode — Surge protective devices do not

discharge all surges to ground (earth). Surge protective

devices divert the surge current back to its source to complete

In the case of lightning whose potential is developed with

respect to the earth, the SPD diverts the surge current to

the grounding electrode (earth connection). However, for

most transient surges that are developed by switching loads,

the SPD diverts the surge current back to its source without

For proper SPD performance, the service entrance grounding

electrode system must comply with the NEC by having all

available electrodes (building steel, metal water pipe, driven

rods, concrete encased electrodes, etc.) properly bonded

The use of a separate grounding electrode to ground the SPD

defeats the effectiveness of the SPD, is a potential safety hazard,

may cause equipment damage, is an NEC violation (reference

together and connected to the power system grounding.

NEC 250-51 and 250-54), and is not recommended.

power conductors in the same raceway (conduit).

involving the grounding electrode.

System Grounding and Bonding

the electrical circuit.

SPD’s operation.

recommended.

Page 9 of the Liebert Interceptor II user manual — 607-724-2484.)
Page 9 · click to enlarge
Page 9

The Liebert SPD is designed for years of trouble-free operation.

However, even the most reliable equipment may fail under

Diagnostic indicators are provided to indicate when the unit

needs replacement (see individual SPD operation of this

manual for details). To ensure continuity of surge protection,

failed units should be replaced at the earliest convenient

When replacing surge modules, other components should

be inspected for damage and replaced if necessary. Standard

electrical troubleshooting procedures should be used to

isolate problems other than failed surge current diverter

When replacing components, for continued proper operation

and safety, replace only with identically rated components.

Periodic system inspections, cleaning, and connection checks

are recommended to ensure reliable system performance and

It is diffi cult to establish a schedule for preventative

maintenance since conditions vary from site to site. Inspections

for failed surge modules using available diagnostics should be

Please contact factory for information on replacement parts.

Preventative Maintenance (Inspection and Cleaning)

continued surge transient protection.

done routinely (weekly or monthly).

Troubleshooting / Servicing / Maintenance

Corrective Maintenance

abnormal conditions.

service opportunity.

modules.

If status failure indication occurs or Form C relay has changed

states, a qualifi ed electrician shall fi rst determine if the

If the SPD remains in an alarm condition once the electrician

is satisfi ed that the electrical system and its connections are

normal, the unit should be repaired. At this point consult the

  • Unit identifi cation number – (refers to the model and serial numbers detailed on the data label and is located on the front
  • Nature of problem – (including status of all status indicators and alarms).

ONLY QUALIFIED PERSONNEL SHOULD PERFORM

HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT

ELECTRICAL SAFETY PRE-CAUTIONS MUST BE FOLLOWED

TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND

LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE

(For servicing assistance, contact your local Liebert

Sales Representative or Liebert at 800-288-6169 or

factory, having available the following information:

systems voltage and proper phasing exists.

or upper left [hinge] side of the enclosure.)

MAINTENANCE ON THE SYSTEM.

DURING NORMAL OPERATIONS.

WHEN SERVICING THIS UNIT.

Troubleshooting

SERVICING UNIT.

607-724-2484.)

Servicing

Page 10 of the Liebert Interceptor II user manual — Interceptor II Series
Page 10 · click to enlarge
Page 10
1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections.
2. The SPD is provided in the enclosure type listed below. NEMA 12 enclosures are suitable for use in indoor installations. NEMA 3R, NEMA 4 or NEMA 4X enclosures are suitable for use in indoor or outdoor installations.
3. Determine where the SPD is to be mounted, allowing for minimum length of wire between itself and the input power terminals of the service panel. Punch or cut the proper hole size in the side of the SPD closest to the knockout to be utilized in the service

panel. Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the

Circuit Ampacity Limitations. Representative samples of these products have been investigated by Underwriters Laboratories,

Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents of up to the rating

shown above, as described in the Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition,

Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 10)
Fig. 2

PowerSure Medium Exposure Series AccuVar Series PowerSure Low Exposure Series

SPD Standard Enclosure Optional Enclosures SPD Standard Enclosure Optional Enclosures

Type SI 200,000 Symmetrical Amperes Type ACV/AII 200,000 Symmetrical Amperes Type H 200,000 Symmetrical Amperes Type LPM 65,000 Symmetrical Amperes

Type SS 65,000 Symmetrical Amperes Type LPL 14,000 Symmetrical Amperes

SPD Short Circuit Current Rating SPD Short Circuit Current Rating

Type H Type SS Series Type LM Series

Type H NEMA 12 NEMA 3R, 4, 4X Type LPM NEMA 12 NEMA 3R, 4, 4X

Type SS NEMA 4X N/A Type LPL ABS Plastic 94V-0 NEMA 1

tables on the “Dimensional Information” pages in this manual. Mount surge suppressor using the hardware listed.

Type SI NEMA 4 NEMA 4X Type ACV/AII NEMA 4X N/A

SPD Mounting Hardware SPD Mounting Hardware

Type LM NEMA 12 NEMA 3R, 4, 4X

Type LPM Type ACV & AII Type LPL

Type H (Page 16) 3/8" Type LPM (Page 20) #10

Type SI (Page 15) 3/8" Type ACV/AII (Page 16) #8

Type SS (Page 18) 1/4" Type LPL (Page 21) #6

Type LM (Page 19) 1/4"

Typical Parallel Installations

Surge Protective Devices (SPD)

4. The SPD has obtained the short circuit current rating shown below.

Type SI Hybrid Advantage Series

Type LM 200,000 Symmetrical Amperes

Interceptor II Series

Installation Instructions

dated August 15, 1996.

Page 11 of the Liebert Interceptor II user manual — If the SPD model is a Wye confi gured unit (4W+G),
Page 11 · click to enlarge
Page 11
7. An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below

(also indicated on the “Dimensional Information” pages in this manual). The SPD shall be connected in accordance with all

5. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground) marked G, of the SPD using the wire range listed below. To yield the best performance of the SPD within the electrical
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 11)
Fig. 3

Surge Voltage Ratings. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated,

in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August

15, 1996, marked on this product, the suggested wire size must be utilized to connect the unit to your facilities power grid. Connections made with conductors other than the size provided may result in different SVRs.

6. Connection to Form ‘C’ contacts shall be with #18 – 22 AWG. The ratings of the Form ‘C’ contacts are 5 amps at 250 VAC maximum with a power factor of 1.0. For additional information on Interceptor II connections, see page 15.
7. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are illuminated. If the GREEN LEDs are extinguished or a RED LED is illuminated, check to ensure that power is applied to the SPD.

If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection

8. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
9. The protection modules in these SPDs may be replaceable, contact Liebert/Emerson Network Power Surge Protection for replacement. (Note: ACV, LPM, & LPL units do not have replaceable modules).

Wire Size With Disconnect Without Disconnect With Disconnect Without Disconnect

60 Amp 80 Amp 80 Amp 100 Amp 60 Amp 80 Amp 80 Amp 80 Amp 80 Amp 40 Amp 40 Amp 100 Amp 30 Amp

and a Neutral connection is not available, please contact factory.

If the SPD model is a Wye confi gured unit (4W+G),

distribution system, keep all conductors as short as possible and avoid sharp bends.

15A – 150A 15A – 175 A 15A – 175A 15A – 175A 15A – 150A 15A – 175A 15A – 175A 15A – 175A N/A

15A – 150A 15A – 175A 15A – 175A N/A

at 1-800-288-6169 or 1-607-724-2484.

national and local electrical codes.

Page 12 of the Liebert Interceptor II user manual — Installation Instructions
Page 12 · click to enlarge
Page 12
1. Ampacity: The fi lter’s maximum continuous current (Ampere) rating must be greater than or equal to the protected load’s full load amps or overcurrent protection (Circuit Breaker) rating.
2. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections.
3. The SPD is provided in a NEMA 3R, NEMA 4, NEMA 4X or NEMA 12 enclosure. The SPD is suitable for use in indoor (NEMA 12) or outdoor (NEMA 3R, 4, 4X) installations.
4. Determine where the SPD is to be mounted. Punch or cut proper hole size in the side of the SPD closest to the knockout to be utilized in the service panel. Wall Mounted Units: Drill mounting holes in wall at location picked for SPD next to service panel
5. Units up to 225 amps are suitable for short circuit current ratings up to 25,000 amps. For short circuit currents up to 50,000 amps, Class RK5 fuses sized up to 125% of the fi lter’s continuous current rating are required. Units rated at 400 to 800 amps

are suitable for available symmetrical short circuit currents up to 50,000 amps. For short circuit currents up to 100,000 amps,

Class L Fuses sized up to 125% of the fi lter’s continuous current rating are required. Units 1200 amps and above are suitable for

6. For best performance, keep input and output wiring separated as much as practical to eliminate input-to-output coupling of noise and transients. Do not route input and output wiring in the same raceway. If practical, terminate input and output
7. The Liebert Active Tracking Filter System is wired in-line (in series) with the protected load(s). See Figures on the following page.
8. Terminals are provided inside the Liebert Active Tracking Filter System for the line (phase), neutral (if used), transient ground, and equipment safety ground connections. See page 11 for terminal wire size ranges.
9. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground) marked G, of the SPD using the wire range listed in the table on page 12 in accordance with the National Electric Code (NEC)

Article 285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, avoid sharp

10. Connection to the Form ‘C’ contacts shall be with #18 – 22 AWG. Contacts are rated 5 amps at 250 VAC maximum with a power factor of 1.0.
11. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are illuminated. If the GREEN LEDs are extinguished or the RED LED is illuminated, check to ensure that power is applied to

the SPD. If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge

12. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
13. The protection modules in these SPDs are replaceable, contact Liebert/Emerson Network Power Surge Protection for replacement.

raceways (conduits) at opposite ends of the active tracking fi lter enclosure (input near the top and output near the bottom).

using mounting dimension from the tables on page 17. Mount surge suppressor using 3/8-16 hardware or equivalent.

Liebert Active Tracking Filter Series — Type F

Surge Protective Device (SPD)

Liebert Interceptor II — Surge Protective Device (SPD) diagram (page 12)
Fig. 4 · Surge Protective Device (SPD)

available symmetrical short circuit currents up to 200,000 amps.

Protection at 1-800-288-6169 or 1-607-724-2484.

Installation Instructions

bends.

Page 13 of the Liebert Interceptor II user manual — (required)
Page 13 · click to enlarge
Page 13

Typical Series Connections for Wye (4 Wire + Ground) or Single Phase (3 Wire + Ground) System

Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 13)
Fig. 5

“Protected”

“Protected”

Load (s) }

To

To

CURRENT RATING NEUTRAL TERMINALS GROUND TERMINAL GROUND TERMINAL

400 A # 6 – 250 kcmil (2) # 6 – 250 kcmil (2) # 6 – 250 kcmil (4)

800 A 2.75 x .50 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (4)

1200 A (2x) 6.0 x .25 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (4)

2000 A (3x) 6.0 x .25 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (2)

4000 A (5x) 6.0 x .25 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (2)

30 –100 A # 14 – 2/0 (1) # 14 – 2/0 (5) # 14 - # 4 (4)

225 A # 6 – 250 kcmil (1) # 14 – 2/0 (5) # 10 – 1/0 (4)

FILTER CONTINUOUS PHASE AND TRANSIENT SAFETY

Liebert Interceptor II — FILTER CONTINUOUS PHASE AND TRANSIENT SAFETY diagram (page 13)
Fig. 6

Typical Series Connections for Delta (3 Wire + Ground) System

Liebert Interceptor II — Typical Series Connections for Delta (3 Wire + Ground) System diagram (page 13)
Fig. 7 · Typical Series Connections for Delta (3 Wire + Groun…

TERMINAL WIRE SIZE RANGE

Active Tracking

3. Units must be installed with Busbar(s) only! Wire lugs are not U.L. approved.

Filter System

Active Tracking

Filter System

Liebert

Liebert

1. Single lug with single connection for Input and Output.
2. Single lug with dual connection for Input and Output.
4. Single lug with single connection.
5. Single lug with dual connection.

(required)

Neutral

Ground

’s

’s

NOTES:

Page 14 of the Liebert Interceptor II user manual — Installation Instructions
Page 14 · click to enlarge
Page 14
1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections
3. The unit is to be wall mounted in an area where suffi cient access and working space around the cabinet can be assured. (See NEC Section 110-16.) Position the SPD opposite the incoming feed to the panelboard. For example, if the panelboard is
4. Knockouts for connection of the suppressor to the panelboard back box are provided on top, bottom, and sides of the unit’s enclosure. The diameters of the knockouts vary to accommodate conduit / collar diameters of 1/2 in. to 1 1/4 in. The proper

size busing (diameter and length) must be selected to protect the conductors as they transition from the SPD to the panelboard

5. When connecting the SPD to the panelboard, it is important that the panelboards interior and the SPD are protected from any metal shavings, which may result. An inspection and cleaning of the LPGE should be performed before applying power.
6. Representative samples of this product have been investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents of up to 200,000 AIC, as described in the
7. An external circuit breaker is not necessary for over-current protection. However, it is recommended that the SPD be connected in series with a 30A circuit breaker. The SPD shall be connected in accordance with all national and local electrical codes.
8. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August 15, 1996,

marked on this product, #8 AWG wire must be utilized to connect the unit to your facilities power grid. Connections made

9. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground) marked G, of the SPD using the wire range listed in the table below in accordance with the National Electric Code (NEC) Article

285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, keep all conductors as short as possible and avoid sharp bends.

10. Connection to the Form ‘C’ contacts shall be with #18 – 22 AWG. Contacts are rated 5 amps at 250 VAC maximum with a power factor of 1.0.
11. Apply power. The surge protector is fully operational when the GREEN LEDs are illuminated. If the GREEN LEDs are extinguished, check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact
12. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
13. The protection modules in these SPDs are replaceable, contact Liebert/Emerson Network Power Surge Protection for replacement.
2. The unit is provided in a NEMA 1 rated industrial-use enclosure and should be installed in areas only appropriate for NEMA 1.

Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition, dated August 15, 1996.

conductor, and to maintain the cosmetic integrity of the Liebert LPGE Series Surge Protection Device.

Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.

supplied through the top of its enclosure, mount the SPD at the bottom of the panelboard.

Liebert PanelGuard Series - Type LPGE

Surge Protective Device (SPD)

Liebert Interceptor II — Surge Protective Device (SPD) diagram (page 14)
Fig. 8 · Surge Protective Device (SPD)

with conductors other that #8 AWG may result in different SVRs.

Installation Instructions

Page 15 of the Liebert Interceptor II user manual — Installation Instructions
Page 15 · click to enlarge
Page 15

All electrical connections shall be installed by a qualifi ed (licensed) electrician. All wiring must comply with the National Electrical

NEC 240.21 Location in Circuit. Over current protection shall be provided in each ungrounded circuit conductor and shall

be located at the point where the conductors receive their supply except as specifi ed in 240.21(A) through (G). No conductor

supplied under the provisions of 240.21(A) through (G) shall supply another conductor under those provisions, except through

(A) Branch-Circuit Conductors. Branch-circuit tap conductors meeting the requirements specifi ed in 210.19 shall be

(B) Feeder Taps. Conductors shall be permitted to be tapped, without over current protection at the tap, to a feeder as

(1) Taps Not Over 3 m (10 ft) Long. Where the length of the tap conductors does not exceed 3 m (10 ft) and the tap

b. Not less than the rating of the device supplied by the tap conductors or not less than the rating of the over

(2) The tap conductors do not extend beyond the switchboard, panelboard, disconnecting means, or control devices

(3) Except at the point of connection to the feeder, the tap conductors are enclosed in a raceway, which shall extend

from the tap to the enclosure of an enclosed switchboard, panelboard, or control devices, or to the back of an

(4) For fi eld installations where the tap conductors leave the enclosure or vault in which the tap is made, the rating

of the over current device on the line side of the tap conductors shall not exceed 10 times the Ampacity of the

(2) Taps Not Over 7.5 m (25 ft) Long. Where the length of the tap conductors does not exceed 7.5 m (25 ft) and the tap

(1) The Ampacity of the tap conductors is not less than one-third of the rating of the over current device protecting the

(2) The tap conductors terminate in a single circuit breaker or a single set of fuses that will limit the load to the

Ampacity of the tap conductors. This device shall be permitted to supply any number of additional over current

Flexible liquid tight non-metallic conduit in lengths greater than six feet must be installed in accordance with NEC 351-27.

The National Electrical Code Article 240-21 details specifi c tap rules that should be considered before installation.

a. Not less than the combined computed loads on the circuits supplied by the tap conductors, and

(3) The tap conductors are suitably protected from physical damage or are enclosed in a raceway.

Liebert AccuGuide Series — Type ACG

permitted to have over current protection located as specifi ed in that section.

current protective device at the termination of the tap conductors.

SPD Interconnect Assembly

(1) The Ampacity of the tap conductors (25 Amps in our case) is

an over current protective device meeting the requirements of 240.4.

feeder conductors (75 Amp maximum in our case).

(5) Outside Taps of Unlimited Length. Not Applicable

(3) Taps Supplying a Transformer. Not Applicable

(4) Taps Over 7.5 m (25 ft) Long. Not Applicable

conductors comply with all of the following:

conductors comply with all of the following:

National Electrical Code (NEC) Considerations

specifi ed in 240.21(B)(1) through (5).

Code (NEC) and applicable local codes.

devices on its load side.

open switchboard.

tap conductor.

they supply.

Installation Instructions

Page 16 of the Liebert Interceptor II user manual — Connection
Page 16 · click to enlarge
Page 16

The AccuGuide assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an

additional fi ve feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of

the pigtail is based on the SPD lug size. See chart below for units and acceptable wire ranges. An additional 10 gauge-grounding

The ideal SPD installation locates the suppression as close to the protected bus as possible. This product was designed to address

those instances when a close installation is not possible. However, while the voltage drop experienced with an AccuGuide

Each end of the AccuGuide assembly is shipped with fi ve-foot pigtails. The length is offered as a worst-case need for the panel or

The AccuGuide assembly is sold without conduit. If conduit housing is required, the following conduit and fi tting sizes apply:

switchgear end (our SPD will be much less than 5 feet). We recommend cutting the pigtail to the shortest length possible.

body when pulling the assembly through conduit. Do not pull AccuGuide assembly using the pigtails or damage

assembly is signifi cantly reduced, care should be taken to keep connection lengths to a minimum.

conductor is provided with the AccuGuide assembly for use as an equipment ground.

Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 16)
Fig. 9

Interceptor II Units Acceptable Wire Range

LM Units Acceptable Wire Range

No. of Conductors Conduit Size (in.)

All Units - No Disconnect #14 – 2/O

SI032-100 – With Disconnect #14 – 2/O

LM100-250 – With Disconnect #14 – 2/O

SI016-025 – With Disconnect #8 – 1/O

All Units - No Disconnect #14 – #2

LM060-080 – With Disconnect #8 – 1/O

1 Coax Cable, 1 GND 1 2 Coax Cable, 1 GND 1-1/4 3 Coax Cable, 1 GND 1-1/4 4 Coax Cable, 1 GND 1 1/4 5 Coax Cable, 1 GND 1 1/2 6 Coax Cable, 1 GND 1 1/2 7 Coax Cable, 1 GND 1 1/2

Equipment Performance

may occur.

Connection

Conduit

Page 17 of the Liebert Interceptor II user manual — SI016
Page 17 · click to enlarge
Page 17
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 17)
Fig. 10

#14 – 1/O

#14 – 2/O

#14 – 2/O

#14 – 2/O

Liebert Interceptor II — #14 – 1/O diagram (page 17)
Fig. 11

15A – 150A

15A – 175A

15A – 175A

15A – 175A

Interceptor II Series - Type SI

Dimensional Information

100 A

60 A

80 A

80 A

Liebert Interceptor II — 15A – 150A diagram (page 17)
Fig. 12
Liebert Interceptor II — 15A – 150A diagram (page 17)
Fig. 13

SI016

SI025

SI032

SI040

SI050

SI060

SI075

SI100

Show 9 more labels / short text on this page
Disconnect/Main · Neutral Buss · Ground Buss · Breaker for · Panel · #6 · #4 · #4 · #2
Page 18 of the Liebert Interceptor II user manual — (AWG)
Page 18 · click to enlarge
Page 18
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 18)
Fig. 14

*Alarm ENABLED Alarm DISABLED Audible Alarm — AccuVar Series

Alarm Enable/Disable Feature

Jumper Jumper Alarm Alarm

Jumper located next to alarm

15A – 150A 15A – 175A 15A – 175A 15A – 175A

Hybrid Advantage Series — Type H

AccuVar Series – Type ACV & AII

8 30A #10 15A-30A #14- #10

STATUS

Loads to be Protected

AccuVar Series

Liebert Interceptor II — AccuVar Series diagram (page 18)
Fig. 15 · AccuVar Series

(AWG)

Show 22 more labels / short text on this page
*Factory Setting · Disconnect/Main · Breaker for · Neutral Buss · Ground Buss · Panel · Phase L2/B · Phase L3/C · / · Wire Range · Range Allowable · Service Panel for · Dedicated · Disconnect · (Optional) · Allowable · Breaker · Suggested · Wire Size · (lbs) Suggested · Breaker Size · Weight
Page 19 of the Liebert Interceptor II user manual — D
Page 19 · click to enlarge
Page 19

A B C D E F Lbs Kg

FxxxN/L30 Single Phase 24.0 20.0 9.0 21.25 10.0 .44 35 15.9 FxxxS30 Split Phase 24.0 20.0 9.0 25.25 14.0 .44 45 20.4 FxxxD30 Three Phase Delta 24.0 20.0 9.0 25.25 14.0 .44 50 22.7 FxxxY30 Three Phase Wye 24.0 20.0 9.0 25.25 14.0 .44 60 27.2 FxxxN/L60 Single Phase 24.0 20.0 9.0 21.25 10.0 .44 35 15.9 FxxxS60 Split Phase 24.0 20.0 9.0 25.25 14.0 .44 45 20.4 FxxxD60 Three Phase Delta 24.0 20.0 9.0 25.25 14.0 .44 50 22.7 FxxxY60 Three Phase Wye 24.0 20.0 9.0 25.25 14.0 .44 60 27.2 FxxxN/L100 Single Phase 30.0 24.0 9.0 25.25 14.0 .44 60 27.2 FxxxS100 Split Phase 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxD100 Three Phase Delta 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxY100 Three Phase Wye 30.0 24.0 9.0 31.25 18.0 .44 80 36.3 FxxxN/L225 Single Phase L – N 30.0 24.0 9.0 25.25 14.0 .44 60 27.2 FxxxS225 Split Phase 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxD225 Three Phase Delta 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxY225 Three Phase Wye 30.0 24.0 9.0 31.25 18.0 .44 80 36.3 FxxxD400 Three Phase Delta 48.0 36.0 12.0 49.25 30.0 .44 275 125 FxxxY400 Three Phase Wye 48.0 36.0 12.0 49.25 30.0 .44 300 136

Current Model Dimensions (Inches) Weight

A B C Lbs Kg

FxxxD800 Three Phase Delta 60.0 48.0 12.0 500 227 FxxxY800 Three Phase Wye 60.0 48.0 12.0 530 241 FxxxD1200 Three Phase Delta 60.0 48.0 20.0 700 318 FxxxY1200 Three Phase Wye 60.0 48.0 20.0 750 340 FxxxD2000 Three Phase Delta 60.0 48.0 20.0 875 397 FxxxY2000 Three Phase Wye 60.0 48.0 20.0 950 431 FxxxD4000 Three Phase Delta 60.0 48.0 20.0 1175 533 FxxxY4000 Three Phase Wye 60.0 48.0 20.0 1300 590

Typical Cabinet Data (30 to 400Amps) Typical Cabinet Data (800 to 4000Amps)

A

E B 2.0” Max.

Active Tracking Filter Series - Type F

Small Bezel .50” Max. (No Options)

Large Bezel 2.0” Max. (Options)

Rating XXX = VOLTAGE Application

D

XXX = VOLTAGE

A

F

B

800A

1200A

2000A

4000A

30A

60A

100A

225A

400A

Show 5 more labels / short text on this page
Dimensions (Inches) Weight · 12” · Application · Rating Model · Current
Page 20 of the Liebert Interceptor II user manual — Type SS Series
Page 20 · click to enlarge
Page 20

D

Liebert Interceptor II — D diagram (page 20)
Fig. 16

#4 15A – 175A 15A – 175A #14 – 2/O

F

Liebert Interceptor II — F diagram (page 20)
Fig. 17

1 Phase 3 Phase 13.32 17.32 6.6 9.6 14.75 18.75 10 12 0.32 0.32 26 43 80 A 80 A #4

Type SS Series

Service Panel For

Page 21 of the Liebert Interceptor II user manual — LM060
Page 21 · click to enlarge
Page 21
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 21)
Fig. 18

15A –150A #14 – 1/O 16

#14 – 2/O

#14 – 2/O

15A –175A

15A –175A

Liebert Interceptor II — 15A –150A #14 – 1/O 16 diagram (page 21)
Fig. 19

100 A

40 A

40 A

Type LM Series

Liebert Interceptor II — 100 A diagram (page 21)
Fig. 20

LM060

LM080

LM100

LM125

LM150

LM200

LM225

LM250

Show 8 more labels / short text on this page
Disconnect/Main · Neutral Buss · Ground Buss · Breaker for · Panel · #8 · #8 · #2
Page 22 of the Liebert Interceptor II user manual — .31 (4X)
Page 22 · click to enlarge
Page 22
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 22)
Fig. 21
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 22)
Fig. 22

PowerSure Medium Exposure Series — Type LPM 160

be Protected Phase L3/C

Liebert Interceptor II — PowerSure Medium Exposure Series — Type LPM 160 diagram (page 22)
Fig. 23 · PowerSure Medium Exposure Series — Type LPM 160

6.000 Phase A Phase B Phase C

8.750 8.000

0.375 3.500

Liebert Interceptor II — PowerSure Medium Exposure Series — Type LPM 160 diagram (page 22)
Fig. 24 · PowerSure Medium Exposure Series — Type LPM 160
Liebert Interceptor II — PowerSure Medium Exposure Series — Type LPM 160 diagram (page 22)
Fig. 25 · PowerSure Medium Exposure Series — Type LPM 160

.31 (4X)

Show 11 more labels / short text on this page
Disconnect · (Optional) · Service Panel · for Loads to · Dedicated · Phase L2/B · Phase L1/A · Ground Buss · Neutral Buss · Disconnect/Main · Breaker for Panel
Page 23 of the Liebert Interceptor II user manual — 1/2” Offset Conduit Nipple
Page 23 · click to enlarge
Page 23

Disconnect/Main

Neutral Buss

Ground Buss Dedicated

Breaker for

Panel

Unit is equipped with Summary

Alarm Contacts. The #18 wires

Phase L1/A

Phase L2/B

Phase L3/C

are designated as follows:

YELLOW = Normally Open

BLUE = Normally Closed

ORANGE = COMMON

PowerSure Low Exposure Series - Type LPL

Service Panel

for Loads to

be Protected

Disconnect

5.250 5.700

.188 (4X)

connection. It is REQUIRED that a 30A circuit

breaker or less be used for installation.

Unit is supplied from the factory with a

minimum length of 18” of #12 wire for

1/2” Offset Conduit Nipple

3.00 Max.

Status · Status

Page 24 of the Liebert Interceptor II user manual — Contacts Inside
Page 24 · click to enlarge
Page 24

Summary Alarm

(Remove Cover for Access)

Contacts Inside

3 Pole, 30 Amp Circuit

Breaker

Module

PanelGuard Series — Type LPGE

Customer

Supplied

PanelBoard

Sliding Trim

Proper Fit

Neutral Bar

Uninsulated

Ground Bar

Slots for

To Ensure

Conduit

Collar Conduit

Collar

Supplied

LPGE Unit

Liebert

Page 25 of the Liebert Interceptor II user manual — Example Installations
Page 25 · click to enlarge
Page 25
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 25)
Fig. 26
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 25)
Fig. 27

Example Installations

Page 26 of the Liebert Interceptor II user manual — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF
Page 26 · click to enlarge
Page 26
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 26)
Fig. 28
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 26)
Fig. 29
Page 27 of the Liebert Interceptor II user manual — LIEBERT PRODUCTS COVERED:
Page 27 · click to enlarge
Page 27

This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser’s business.

Liebert Corporation products and systems are in our opinion the fi nest available. We take pride in our products and are pleased that you have chosen

Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain

Interceptor® Transient Voltage Surge Suppressors, Interceptor® Active Tracking® Filters, Hybrid Advantage Transient Voltage Surge Suppressors,

As provided herein, the Liebert product is warranted to be free of defects in material and workmanship for a period of ten (10) years from the date

of product shipment from Liebert. The shipment date will be determined only from the Liebert bill of lading. If any part or portion of the Liebert

product fails to conform to the warranty within the warranty period, Liebert, at its option, will furnish new or factory remanufactured parts for

This Warranty is extended to the fi rst person, fi rm, association or corporation for whom the Liebert product specifi ed herein is originally installed

for use (the “User”) in the fi fty United States (excluding territories) or Canada. This Warranty is not transferable or assignable without the prior

Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of the Liebert product and which are

assignable, but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any

Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the certifi ed drawings, if any,

applicable thereto, to Liebert’s fi nal invoices, and to applicable Liebert product brochures and manuals current as of the date of product shipment

(“Descriptions”). Liebert does not control the installation and use of any Liebert product. Accordingly, it is understood that the Descriptions are

Within a reasonable time, but in no case to exceed thirty (30) days, after User’s discovery of a defect, User shall contact Liebert at 1-800-LIEBERT

(543-2378) and request a return authorization number. User shall ship the product, with proof of purchase, to Liebert freight prepaid. Liebert

products shipped to Liebert without a return authorization number will be refused and returned freight collect to User at User’s expense. Liebert

products shipped by User to Liebert which have incurred freight damage due to User’s improper packaging of the product will not be covered by

this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned

Subject to the limitations specifi ed herein, Liebert will repair or replace, at its option, without charge for Liebert labor or materials, subsequent

to its inspection F.O.B. Liebert’s facility, the Liebert product warranted hereunder which does not conform to the Warranty. Replacement parts,

components or products shipped to User prior to Liebert’s receipt and inspection of the product claimed to be defective shall be invoiced in the

full current price amount and shipped freight collect F.O.B. Liebert’s facility. Warranty coverage will be extended only after Liebert’s receipt of

the claimed defective product within thirty (30) days of shipment of any replacement parts, components or products, if applicable, and only if

Liebert’s inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of

It is Liebert’s practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate

with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects

in the product components. Accordingly, Liebert may utilize third parties in the performance of Warranty work, including repair or replacement

hereunder, where, in Liebert’s opinion, such work can be performed in less time, with less expense, or in closer proximity to the Liebert product.

them. Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship.

matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components.

this Warranty. All defective products and component parts replaced under this Warranty become the property of Liebert.

TEN YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP

NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.

AccuVar® Transient Voltage Surge Suppressors, and Type SS Transient Voltage Surge Suppressors.

Limited Warranty

Warranty Extends to First Purchaser for Use, Non-transferable:

Warranty Performance of Component Manufacturers:

Obtaining Performance Under This Warranty:

repair or replacement of that part or portion.

performance under this Warranty.

LIEBERT PRODUCTS COVERED:

written permission of Liebert.

Assignment of Warranties:

Drawings, Descriptions:

freight collect to User.

Terms of Warranty:

General:

Page 28 of the Liebert Interceptor II user manual — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF
Page 28 · click to enlarge
Page 28

THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or

connection, negligence, inappropriate on site operating conditions, corrosive atmosphere, repair by non-Liebert designated personnel, accident

in transit, tampering, alterations, a change in location or operating use, exposure to the elements, Acts of God, theft or installation contrary to

Liebert’s recommendations or specifi cations, or in any event if the Liebert serial number has been altered, defaced or removed. Notwithstanding

the foregoing, the following Acts of God are covered: lightning-induced surges, which are transients, spikes or other sub-cycle, discontinuous

events impinging on normally applied voltage as defi ned by reference data in the latest version of IEEE C62.41 and the Liebert product performance

THIS WARRANTY DOES NOT COVER shipping costs, installation costs, circuit breaker resetting or maintenance or service items and further, except

as provided herein, does NOT include labor costs or transportation charges arising from the replacement of the Liebert product or any part thereof

THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Liebert product in combination with any electrical or electronic

components, circuits, systems, assemblies, or other materials not furnished by Liebert. Liebert does NOT warrant the suitability for use or the

THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT DESIGNED FOR USE IN THE FOLLOWING APPLICATIONS: (i) ANY NUCLEAR OR RELATED

  • THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
  • IF USER’S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION, LIEBERT’S RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED THE NET PRODUCT PURCHASE PRICE.
  • IN NO EVENT SHALL LIEBERT ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION, LOST PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED
  • NO SALESPERSON, EMPLOYEE OR AGENT OF LIEBERT IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY. Warranty terms may be modifi ed, if at all, only in a writing signed by a Liebert offi cer.
  • Liebert obligations under this warranty are conditioned upon Liebert timely receipt of full payment of the product purchase price and any other amounts due. Liebert reserves the right to supplement or change the terms of this Warranty in any subsequent warranty offering to User or
  • In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and provisions shall continue in full force and effect.
  • This Warranty shall be governed by, and construed under, the laws of the State of Ohio, without reference to the confl ict of laws principles thereof.
  • This Warranty represents the entire agreement between Liebert and User with respect to the subject matter herein and supersedes all prior or contemporaneous oral or written communications, representations, understandings or agreements relating to this subject.

REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD.

APPLICATIONS; AND (ii) LIFE SUPPORT AND PATIENT-CONNECTED AND APPLIED MEDICAL AND DENTAL APPLICATIONS.

  • USER’S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE LIEBERT PRODUCT AS SET FORTH HEREIN.

UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT OR OTHERWISE.

results of the Liebert product in combination with the products of others.

or charges to remove or reinstall same at any premises of the User.

Items Not Covered By Warranty:

Miscellaneous:

specifi cations.

Limitations:

others.

Page 29 of the Liebert Interceptor II user manual — Limited Warranty
Page 29 · click to enlarge
Page 29
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 29)
Fig. 30

Limited Warranty

Page 30 of the Liebert Interceptor II user manual — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF
Page 30 · click to enlarge
Page 30
Liebert Interceptor II — FOR PROPER AND SAFE OPERATION, THE NEUTRAL, (IF diagram (page 30)
Fig. 31

Items Not Covered By Warranty:

Page 31 of the Liebert Interceptor II user manual — Liebert Corporation
Page 31 · click to enlarge
Page 31

responsibility and disclaims all liability for damages resulting from use

© 2006 Liebert Corporation All rights reserved throughout the world.

The global leader in enabling Business-Critical Continuity™. Emerson Network Power.com

Racks and Integrated Cabinets

While every precaution has been taken to ensure the accuracy and

® Liebert and the Liebert logo are registered trademarks of Liebert

completeness of this literature, Liebert Corporation assumes no

Corporation. All names referred to are trademarks or registered

SL-22085 (11/06) Rev. 2 82290 Printed in USA

Surge Protection

Emerson Network Power, the Emerson Network Power logo and Business-Critical Continuity are trademarks and service marks of Emerson Electric Co.

of this information or for any errors or omissions.

Specifi cations subject to change without notice.

Emerson Network Power Asia Pacifi c

7/F., Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong

trademarks of their respective owners.

614 888 0246 (Outside U.S.) 614 841 6022 FAX

Liebert Corporation

35028 Piove Di Sacco (PD) Italy

Via Leonardo Da Vinci 8

39 049 9719 111 Phone 39 049 5841 257 FAX

607 724 2484 Phone 607 722 8713 FAX 800 288 6169 Toll-Free

1050 Dearborn Drive P.O. Box 29186

800 877 9222 Phone (US & Canada Only)

852 25722201 Phone 852 28029250 FAX

Power Switching & Controls

Liebert.com

Emerson Network Power.

©2006 Emerson Electric Co.

Show 12 more labels / short text on this page
Services · Zona Industriale Tognana · Columbus, OH 43229 · Technical Support · Precision Cooling · Outside Plant · Embedded Computing · Embedded Power · Monitoring · Connectivity · DC Power · AC Power
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Liebert Interceptor II

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert Interceptor II

Be the first to ask — other owners or our team will answer.

Original document

Liebert Interceptor II manual PDF

31 pages·1.6 MB·Surge Protector·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…