PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Products
Surge Protection
Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar,





The installer should perform the following steps to assure a
quality installation. The entire installation manual should be
read before starting installation. These instructions do not
replace national or local electrical codes. Check applicable
electrical codes to ensure compliance. Installation of the Liebert
SPD system should only be performed by qualifi ed personnel.
For optimum transient surge protection, coordinated surge
suppression should be applied at the service entrance and all
other electrical connections to the building (telephone, CATV,
etc.), at known surge generating loads within the building
(large motors, arc welders, switched capacitors, etc.), as well
as at sensitive electronic loads (such as computers, electronic
appliances, solid state motor drives, etc.). For interconnected
electronic loads (such as by way of data cabling), transient surge
suppression should also be applied to the interconnecting
Mounting — Unit is intended to be wall mounted. Refer to
individual instruction sheet or unit submittal drawings for
hazardous situation that, if not
avoided, will result in death or
serious injury. This signal word
is to be limited to the most
hazardous situation that, if not
avoided, could result in death or
hazardous situation that, if not
avoided, may result in minor or
moderate injury. It may also be used
close as possible to protected circuit and keep inter-
to alert against unsafe practices.
extreme situations.
typical mounting dimensions and weight.
serious injury.
connecting wiring less than 5 ft.
wiring (data cables).
INSTALLATION INSTRUCTIONS
UNPACKING AND INSTALLATION
The Liebert Surge Protective Devices (SPDs) are high quality,
high energy surge current diversion systems designed to
protect sensitive equipment from damaging transient voltage
surges. Proper installation is required for maximum system
Larger units are bolted to a shipping pallet to facilitate handling
by forklift or pallet jack. Check the size and weight. Refer to
The unit should be stored in a clean, dry environment. Storage
temperature range is -55ºC (-67ºF) to +85ºC (+185ºF). Care
should be taken to avoid condensation. All packing and
shipping materials should be left intact until the unit is ready
for fi nal installation. If the unit has been stored for an extended
period of time, the unit should be cleaned and carefully
Environment — The unit is designed for operation indoors in
ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) with
The unit is provided in an industrial use enclosure, which is
dust-tight and drip-tight and should not be installed in areas
with excessive dust, corrosive vapors, fl ammable materials or
Audible Noise — The audible noise of the unit is less than
40 dB at 5 feet, which allows its placement within almost any room if desired.
Service Clearances — Service clearance is needed for units with
hinged doors on the front that are capable of being opened.
Thirty-six inches (36 in/914 mm) minimum is recommended.
a relative humidity of 0% to 95% (non-condensing).
your local Liebert Sales Representative.
the cabinet data furnished with the unit.
inspected before placing into service.
Location Considerations
explosive atmospheres.
performance.

The following is from the National Electric Code 2002 Edition.
285.21 Connection. Where a TVSS is installed, it shall be connected as follows:
(1) Service Supplied Building or Structure. The transient
voltage surge suppressor shall be connected on the
load side of a service disconnect overcurrent device
(2) Feeder Supplied Building or Structure. The transient
voltage surge suppressor shall be connected on the
load side of the fi rst overcurrent device at the building
(3) Separately Derived System. The TVSS shall be
connected on the load side of the fi rst overcurrent
Disconnect Switch (If Provided) — All SPD units must still be
connected to the load side of the main service disconnect, or
Surge Voltage Ratings — To obtain the suppression voltage
ratings (SVRs), as obtained by Underwriters Laboratory,
Incorporated, in accordance with the Standard for Safety,
Transient Voltage Surge Suppressors (TVSS), Standard 1449,
Second Edition, dated August 15, 1996, marked on this
product, the wire size listed for each product must be utilized
to connect the unit to your facilities’ power grid. Connections
made with conductors other than the wire size listed may
Circuit Ampacity Limitations — Representative samples
of these products have been investigated by Underwriters
Laboratories, Incorporated to withstand, without exposing
live circuits or components at system voltages and fault
currents ranging from 14,000 AIC up to 200,000 AIC, as
described in the Standard for Safety, Transient Voltage Surge
Suppressor (TVSS), Standard 1449, Second Edition, dated
August 15, 1996. Verify each products fault current rating on
arrestor, the connection shall be as permitted by Article 280.
load side of a protected circuit’s disconnecting means.
device in a separately derived system.
the individual installation pages that follow.
required in 230.91.
result in different SVRs.
or structure.
(A) Location.
All electrical connections should be installed by a qualifi ed
(licensed) electrician only. All wiring must comply with the
Before making connections to the unit, verify that the unit
model number and nameplate voltage rating are appropriate
for connection to the intended power source. See the chart
on page 4 for voltage rating applications with typical power
To reduce the wiring impedance to surge currents, it is
recommended that the phase, neutral (if required), and ground
conductors are twisted together and routed in the same
Wire Sizing — With parallel connection, the size of the
wiring to the SPD unit is independent of the protected
circuit’s ampacity. For suggested wire size refer to individual
NEC Article 285-21(B) requires surge suppressor connecting
Overcurrent Protection — The SPD unit conducts practically
no current under normal operation and only conducts very
located as close to the protected circuit as practical
raceway (conduit). Avoid any sharp bends in the conductors.
National Electrical Code (NEC) and applicable local codes.
conductors to be at least #14 copper or #12 aluminum.
VERIFY THAT ALL POWER CIRCUITS ARE
MAKING ELECTRICAL CONNECTIONS.
to minimize interconnecting wiring length.
Parallel Connection (see Figures on page 5)
short duration transient surge currents.
source confi gurations.
product sheet.

Maximum Continuous Model Voltage Code
(Found in part number)
120 N or 120-
120 N or 120-
120 N or 120-
230 N or 230-
277 N or 277-
347 347 N/A 420 L-N 347 N or 347-
320 L-N 240S 240, 277 240, 277 480
347 347 600 420 L-N 347S
N/A 208 208 250 L-L 208D
240D
400D
400D
400D
480D
N/A 600 600 580 L-L 600D
120/240/120 120/240/120 240 150 L-N 240N
240/480/240 240/480/240 480 250 L-N 480H
120Y
127Y
230Y
230Y
254Y
277Y
347Y
VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS
150 L-N
150 L-N
320 L-N
320 L-N
320 L-N
320 L-N
420 L-N
150 L-G
150 L-G
320 L-G
320 L-G
320 L-G
320 L-G
420 L-G
150 L-N
150 L-N
150 L-N
275 L-N
320 L-N
130 L-L
150 L-L
275 L-L
275 L-L
420 L-L
320 L-L
580 L-L
580 L-L
580 L-L
580 L-L
120 120 208, 240
100 100 N/A
110 110 N/A
120 120 N/A
230 230 N/A
277 277 N/A
N/A 208 208
N/A 240 240
N/A 400 400
N/A 480 480
N/A 600 600
N/A 240 240
N/A 380 380
N/A 400 400
N/A 415 415
N/A 480 480
N/A 120 208
N/A 127 220
N/A 220 380
N/A 230 400
N/A 254 440
N/A 277 480
N/A 347 600
N
G
N
G
G
Three Phase Wye, 3 W + G No Neutral
N
B
G
Source Confi gurations
A
B
G
Three Phase Delta Hi Leg, 4 W + G
A
G N
A
B
G
Single Phase L-N, 2 W + G
Three Phase Delta, 3 W + G
Three Phase Wye, 4 W + G
Single Phase L-L, 2 W + G
Single Phase, 3 W + G
N
G
N
G

Typical Parallel Connections (with Internal Rotary Disconnect)
Panel Wire should be
less than 5 feet
Panel Wire should be
less than 5 feet

PROVIDED), MUST BE RELIABLY CONNECTED TO THE
NEUTRAL OF THE SOURCE. FAILURE TO PROVIDE A RELIABLE
External Status Indicators — These indicators provide a
summary of the status of the surge SPD module. For normal
conditions, the green “OK” LED is illuminated and the red
“Service” LED is extinguished. If the surge SPD module
requires replacement, the green “OK” LED is turned off and
Summary Alarm Contact (if applicable) — Summary alarm
Form C (1 N.O. and 1 N.C.) relay contacts may be provided for
Contacts are rated 5 amps at 250 VAC maximum with a power
factor of 1.0. For units with Summary Alarm Contacts, access
to the contacts are typically provided via contact terminals
located on the printed circuit board mounted on the inside of
Transient Counter (if applicable) – Transient counters are
provided for transient voltage surge monitoring. The counter
The transient counter monitors line transient voltages. The
circuit counts all surges that deviate from the line sine wave.
The factory setting is 30% over nominal line voltage. Other
Swell Counter (if applicable) — The swell counter monitors
line to line & line to neutral voltages. It is factory set to record
whenever the peak voltage on any normal mode exceeds the
nominal voltage of the TVSS for more than 10ms. This counter
records temporary line over voltages that may result from
Audible Alarm (if applicable) — If the surge SPD module
requires replacement, an audible alarm is activated to draw
the system to normal operation. An audible alarm disable is
provided to silence the alarm. The system will automatically
reset itself after repair. The audible alarm switch and “Service”
LED can be tested by activating the “Test” switch on the
system monitor panel. For information on the AccuVar Series
totalizes surges monitored since the last counter reset.
remote indication of the failed surge SPD module.
utility switching, line regulation problems, etc.
settings include 50%, 70%, and 100%.
the red “Service” LED illuminated.
Alarm, see page 16.
the unit’s cover.
The performance and safety of any SPD system is dependent
on proper grounding and bonding. Grounding is required for
safety. Correct implementation also enhances equipment
performance. Incorrect grounding can reduce or impede the
All electrical circuits to the SPD must include an equipment-
grounding conductor as required by the NEC and local codes.
An insulated grounding conductor is required in addition to any
metallic raceway, which may be used as a grounding conductor.
For parallel-connected SPDs, the grounding conductor should
be the same wire size as the associated power conductors.
Grounding conductors must be routed with the associated
When metallic raceways are used, adequate electrical
continuity must be maintained at all raceway connections,
particularly raceway terminations to the electrical enclosures.
metallic conduit run is a potential safety hazard and is not
Grounding Electrode — Surge protective devices do not
discharge all surges to ground (earth). Surge protective
devices divert the surge current back to its source to complete
In the case of lightning whose potential is developed with
respect to the earth, the SPD diverts the surge current to
the grounding electrode (earth connection). However, for
most transient surges that are developed by switching loads,
the SPD diverts the surge current back to its source without
For proper SPD performance, the service entrance grounding
electrode system must comply with the NEC by having all
available electrodes (building steel, metal water pipe, driven
rods, concrete encased electrodes, etc.) properly bonded
The use of a separate grounding electrode to ground the SPD
defeats the effectiveness of the SPD, is a potential safety hazard,
may cause equipment damage, is an NEC violation (reference
together and connected to the power system grounding.
NEC 250-51 and 250-54), and is not recommended.
power conductors in the same raceway (conduit).
involving the grounding electrode.
the electrical circuit.
SPD’s operation.
recommended.

The Liebert SPD is designed for years of trouble-free operation.
However, even the most reliable equipment may fail under
Diagnostic indicators are provided to indicate when the unit
needs replacement (see individual SPD operation of this
manual for details). To ensure continuity of surge protection,
failed units should be replaced at the earliest convenient
When replacing surge modules, other components should
be inspected for damage and replaced if necessary. Standard
electrical troubleshooting procedures should be used to
isolate problems other than failed surge current diverter
When replacing components, for continued proper operation
and safety, replace only with identically rated components.
Periodic system inspections, cleaning, and connection checks
are recommended to ensure reliable system performance and
It is diffi cult to establish a schedule for preventative
maintenance since conditions vary from site to site. Inspections
for failed surge modules using available diagnostics should be
Please contact factory for information on replacement parts.
continued surge transient protection.
done routinely (weekly or monthly).
abnormal conditions.
service opportunity.
modules.
If status failure indication occurs or Form C relay has changed
states, a qualifi ed electrician shall fi rst determine if the
If the SPD remains in an alarm condition once the electrician
is satisfi ed that the electrical system and its connections are
normal, the unit should be repaired. At this point consult the
HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT
ELECTRICAL SAFETY PRE-CAUTIONS MUST BE FOLLOWED
TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND
LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE
(For servicing assistance, contact your local Liebert
Sales Representative or Liebert at 800-288-6169 or
factory, having available the following information:
systems voltage and proper phasing exists.
or upper left [hinge] side of the enclosure.)
MAINTENANCE ON THE SYSTEM.
DURING NORMAL OPERATIONS.
WHEN SERVICING THIS UNIT.
SERVICING UNIT.
Servicing

panel. Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the
Circuit Ampacity Limitations. Representative samples of these products have been investigated by Underwriters Laboratories,
Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents of up to the rating
shown above, as described in the Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition,

SPD Standard Enclosure Optional Enclosures SPD Standard Enclosure Optional Enclosures
Type SI 200,000 Symmetrical Amperes Type ACV/AII 200,000 Symmetrical Amperes Type H 200,000 Symmetrical Amperes Type LPM 65,000 Symmetrical Amperes
Type SS 65,000 Symmetrical Amperes Type LPL 14,000 Symmetrical Amperes
SPD Short Circuit Current Rating SPD Short Circuit Current Rating
Type H NEMA 12 NEMA 3R, 4, 4X Type LPM NEMA 12 NEMA 3R, 4, 4X
Type SS NEMA 4X N/A Type LPL ABS Plastic 94V-0 NEMA 1
tables on the “Dimensional Information” pages in this manual. Mount surge suppressor using the hardware listed.
Type SI NEMA 4 NEMA 4X Type ACV/AII NEMA 4X N/A
SPD Mounting Hardware SPD Mounting Hardware
Type LM NEMA 12 NEMA 3R, 4, 4X
Type H (Page 16) 3/8" Type LPM (Page 20) #10
Type SI (Page 15) 3/8" Type ACV/AII (Page 16) #8
Type SS (Page 18) 1/4" Type LPL (Page 21) #6
Type LM (Page 19) 1/4"
Type LM 200,000 Symmetrical Amperes
Installation Instructions
dated August 15, 1996.

(also indicated on the “Dimensional Information” pages in this manual). The SPD shall be connected in accordance with all

Surge Voltage Ratings. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated,
in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August
15, 1996, marked on this product, the suggested wire size must be utilized to connect the unit to your facilities power grid. Connections made with conductors other than the size provided may result in different SVRs.
If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection
Wire Size With Disconnect Without Disconnect With Disconnect Without Disconnect
60 Amp 80 Amp 80 Amp 100 Amp 60 Amp 80 Amp 80 Amp 80 Amp 80 Amp 40 Amp 40 Amp 100 Amp 30 Amp
and a Neutral connection is not available, please contact factory.
distribution system, keep all conductors as short as possible and avoid sharp bends.
15A – 150A 15A – 175 A 15A – 175A 15A – 175A 15A – 150A 15A – 175A 15A – 175A 15A – 175A N/A
15A – 150A 15A – 175A 15A – 175A N/A
at 1-800-288-6169 or 1-607-724-2484.
national and local electrical codes.

are suitable for available symmetrical short circuit currents up to 50,000 amps. For short circuit currents up to 100,000 amps,
Class L Fuses sized up to 125% of the fi lter’s continuous current rating are required. Units 1200 amps and above are suitable for
Article 285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, avoid sharp
the SPD. If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge
raceways (conduits) at opposite ends of the active tracking fi lter enclosure (input near the top and output near the bottom).
using mounting dimension from the tables on page 17. Mount surge suppressor using 3/8-16 hardware or equivalent.

available symmetrical short circuit currents up to 200,000 amps.
Protection at 1-800-288-6169 or 1-607-724-2484.
bends.

Typical Series Connections for Wye (4 Wire + Ground) or Single Phase (3 Wire + Ground) System

“Protected”
Load (s) }
To
To
CURRENT RATING NEUTRAL TERMINALS GROUND TERMINAL GROUND TERMINAL
400 A # 6 – 250 kcmil (2) # 6 – 250 kcmil (2) # 6 – 250 kcmil (4)
800 A 2.75 x .50 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (4)
1200 A (2x) 6.0 x .25 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (4)
2000 A (3x) 6.0 x .25 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (2)
4000 A (5x) 6.0 x .25 Cu Busbar (3) # 6 – 250 kcmil (2) # 6 – 250 kcmil (2)
30 –100 A # 14 – 2/0 (1) # 14 – 2/0 (5) # 14 - # 4 (4)
225 A # 6 – 250 kcmil (1) # 14 – 2/0 (5) # 10 – 1/0 (4)


Active Tracking
Filter System
Liebert
Liebert
Neutral
Ground
’s
’s
NOTES:

size busing (diameter and length) must be selected to protect the conductors as they transition from the SPD to the panelboard
marked on this product, #8 AWG wire must be utilized to connect the unit to your facilities power grid. Connections made
285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, keep all conductors as short as possible and avoid sharp bends.
Standard for Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition, dated August 15, 1996.
conductor, and to maintain the cosmetic integrity of the Liebert LPGE Series Surge Protection Device.
Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
supplied through the top of its enclosure, mount the SPD at the bottom of the panelboard.

with conductors other that #8 AWG may result in different SVRs.

All electrical connections shall be installed by a qualifi ed (licensed) electrician. All wiring must comply with the National Electrical
NEC 240.21 Location in Circuit. Over current protection shall be provided in each ungrounded circuit conductor and shall
be located at the point where the conductors receive their supply except as specifi ed in 240.21(A) through (G). No conductor
supplied under the provisions of 240.21(A) through (G) shall supply another conductor under those provisions, except through
(A) Branch-Circuit Conductors. Branch-circuit tap conductors meeting the requirements specifi ed in 210.19 shall be
(B) Feeder Taps. Conductors shall be permitted to be tapped, without over current protection at the tap, to a feeder as
(1) Taps Not Over 3 m (10 ft) Long. Where the length of the tap conductors does not exceed 3 m (10 ft) and the tap
b. Not less than the rating of the device supplied by the tap conductors or not less than the rating of the over
(2) The tap conductors do not extend beyond the switchboard, panelboard, disconnecting means, or control devices
(3) Except at the point of connection to the feeder, the tap conductors are enclosed in a raceway, which shall extend
from the tap to the enclosure of an enclosed switchboard, panelboard, or control devices, or to the back of an
(4) For fi eld installations where the tap conductors leave the enclosure or vault in which the tap is made, the rating
of the over current device on the line side of the tap conductors shall not exceed 10 times the Ampacity of the
(2) Taps Not Over 7.5 m (25 ft) Long. Where the length of the tap conductors does not exceed 7.5 m (25 ft) and the tap
(1) The Ampacity of the tap conductors is not less than one-third of the rating of the over current device protecting the
(2) The tap conductors terminate in a single circuit breaker or a single set of fuses that will limit the load to the
Ampacity of the tap conductors. This device shall be permitted to supply any number of additional over current
Flexible liquid tight non-metallic conduit in lengths greater than six feet must be installed in accordance with NEC 351-27.
The National Electrical Code Article 240-21 details specifi c tap rules that should be considered before installation.
a. Not less than the combined computed loads on the circuits supplied by the tap conductors, and
(3) The tap conductors are suitably protected from physical damage or are enclosed in a raceway.
permitted to have over current protection located as specifi ed in that section.
current protective device at the termination of the tap conductors.
(1) The Ampacity of the tap conductors (25 Amps in our case) is
an over current protective device meeting the requirements of 240.4.
feeder conductors (75 Amp maximum in our case).
(5) Outside Taps of Unlimited Length. Not Applicable
(3) Taps Supplying a Transformer. Not Applicable
(4) Taps Over 7.5 m (25 ft) Long. Not Applicable
conductors comply with all of the following:
conductors comply with all of the following:
specifi ed in 240.21(B)(1) through (5).
Code (NEC) and applicable local codes.
devices on its load side.
open switchboard.
tap conductor.
they supply.

The AccuGuide assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an
additional fi ve feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of
the pigtail is based on the SPD lug size. See chart below for units and acceptable wire ranges. An additional 10 gauge-grounding
The ideal SPD installation locates the suppression as close to the protected bus as possible. This product was designed to address
those instances when a close installation is not possible. However, while the voltage drop experienced with an AccuGuide
Each end of the AccuGuide assembly is shipped with fi ve-foot pigtails. The length is offered as a worst-case need for the panel or
The AccuGuide assembly is sold without conduit. If conduit housing is required, the following conduit and fi tting sizes apply:
switchgear end (our SPD will be much less than 5 feet). We recommend cutting the pigtail to the shortest length possible.
body when pulling the assembly through conduit. Do not pull AccuGuide assembly using the pigtails or damage
assembly is signifi cantly reduced, care should be taken to keep connection lengths to a minimum.
conductor is provided with the AccuGuide assembly for use as an equipment ground.

LM Units Acceptable Wire Range
No. of Conductors Conduit Size (in.)
All Units - No Disconnect #14 – 2/O
SI032-100 – With Disconnect #14 – 2/O
LM100-250 – With Disconnect #14 – 2/O
SI016-025 – With Disconnect #8 – 1/O
All Units - No Disconnect #14 – #2
LM060-080 – With Disconnect #8 – 1/O
1 Coax Cable, 1 GND 1 2 Coax Cable, 1 GND 1-1/4 3 Coax Cable, 1 GND 1-1/4 4 Coax Cable, 1 GND 1 1/4 5 Coax Cable, 1 GND 1 1/2 6 Coax Cable, 1 GND 1 1/2 7 Coax Cable, 1 GND 1 1/2
may occur.
Conduit


#14 – 2/O
#14 – 2/O
#14 – 2/O

15A – 175A
15A – 175A
15A – 175A
Interceptor II Series - Type SI
Dimensional Information
100 A
60 A
80 A
80 A


SI025
SI032
SI040
SI050
SI060
SI075
SI100


Alarm Enable/Disable Feature
Jumper Jumper Alarm Alarm
Jumper located next to alarm
15A – 150A 15A – 175A 15A – 175A 15A – 175A
AccuVar Series – Type ACV & AII
STATUS
Loads to be Protected


A B C D E F Lbs Kg
FxxxN/L30 Single Phase 24.0 20.0 9.0 21.25 10.0 .44 35 15.9 FxxxS30 Split Phase 24.0 20.0 9.0 25.25 14.0 .44 45 20.4 FxxxD30 Three Phase Delta 24.0 20.0 9.0 25.25 14.0 .44 50 22.7 FxxxY30 Three Phase Wye 24.0 20.0 9.0 25.25 14.0 .44 60 27.2 FxxxN/L60 Single Phase 24.0 20.0 9.0 21.25 10.0 .44 35 15.9 FxxxS60 Split Phase 24.0 20.0 9.0 25.25 14.0 .44 45 20.4 FxxxD60 Three Phase Delta 24.0 20.0 9.0 25.25 14.0 .44 50 22.7 FxxxY60 Three Phase Wye 24.0 20.0 9.0 25.25 14.0 .44 60 27.2 FxxxN/L100 Single Phase 30.0 24.0 9.0 25.25 14.0 .44 60 27.2 FxxxS100 Split Phase 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxD100 Three Phase Delta 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxY100 Three Phase Wye 30.0 24.0 9.0 31.25 18.0 .44 80 36.3 FxxxN/L225 Single Phase L – N 30.0 24.0 9.0 25.25 14.0 .44 60 27.2 FxxxS225 Split Phase 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxD225 Three Phase Delta 30.0 24.0 9.0 31.25 18.0 .44 70 31.8 FxxxY225 Three Phase Wye 30.0 24.0 9.0 31.25 18.0 .44 80 36.3 FxxxD400 Three Phase Delta 48.0 36.0 12.0 49.25 30.0 .44 275 125 FxxxY400 Three Phase Wye 48.0 36.0 12.0 49.25 30.0 .44 300 136
Current Model Dimensions (Inches) Weight
A B C Lbs Kg
FxxxD800 Three Phase Delta 60.0 48.0 12.0 500 227 FxxxY800 Three Phase Wye 60.0 48.0 12.0 530 241 FxxxD1200 Three Phase Delta 60.0 48.0 20.0 700 318 FxxxY1200 Three Phase Wye 60.0 48.0 20.0 750 340 FxxxD2000 Three Phase Delta 60.0 48.0 20.0 875 397 FxxxY2000 Three Phase Wye 60.0 48.0 20.0 950 431 FxxxD4000 Three Phase Delta 60.0 48.0 20.0 1175 533 FxxxY4000 Three Phase Wye 60.0 48.0 20.0 1300 590
A
E B 2.0” Max.
Small Bezel .50” Max. (No Options)
Large Bezel 2.0” Max. (Options)
Rating XXX = VOLTAGE Application
XXX = VOLTAGE
A
F
B
800A
1200A
2000A
4000A
30A
60A
100A
225A
400A


#4 15A – 175A 15A – 175A #14 – 2/O

1 Phase 3 Phase 13.32 17.32 6.6 9.6 14.75 18.75 10 12 0.32 0.32 26 43 80 A 80 A #4
Service Panel For


#14 – 2/O
#14 – 2/O
15A –175A
15A –175A

40 A
40 A
Type LM Series

LM080
LM100
LM125
LM150
LM200
LM225
LM250



be Protected Phase L3/C

6.000 Phase A Phase B Phase C
8.750 8.000
0.375 3.500



Neutral Buss
Ground Buss Dedicated
Breaker for
Panel
Unit is equipped with Summary
Alarm Contacts. The #18 wires
Phase L2/B
Phase L3/C
are designated as follows:
YELLOW = Normally Open
BLUE = Normally Closed
PowerSure Low Exposure Series - Type LPL
Service Panel
for Loads to
be Protected
Disconnect
5.250 5.700
.188 (4X)
connection. It is REQUIRED that a 30A circuit
breaker or less be used for installation.
Unit is supplied from the factory with a
minimum length of 18” of #12 wire for
3.00 Max.
Status · Status

(Remove Cover for Access)
3 Pole, 30 Amp Circuit
Breaker
Module
PanelGuard Series — Type LPGE
Customer
Supplied
PanelBoard
Sliding Trim
Proper Fit
Neutral Bar
Uninsulated
Ground Bar
Slots for
To Ensure
Conduit
Collar Conduit
Collar
Supplied
LPGE Unit
Liebert







This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser’s business.
Liebert Corporation products and systems are in our opinion the fi nest available. We take pride in our products and are pleased that you have chosen
Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain
Interceptor® Transient Voltage Surge Suppressors, Interceptor® Active Tracking® Filters, Hybrid Advantage Transient Voltage Surge Suppressors,
As provided herein, the Liebert product is warranted to be free of defects in material and workmanship for a period of ten (10) years from the date
of product shipment from Liebert. The shipment date will be determined only from the Liebert bill of lading. If any part or portion of the Liebert
product fails to conform to the warranty within the warranty period, Liebert, at its option, will furnish new or factory remanufactured parts for
This Warranty is extended to the fi rst person, fi rm, association or corporation for whom the Liebert product specifi ed herein is originally installed
for use (the “User”) in the fi fty United States (excluding territories) or Canada. This Warranty is not transferable or assignable without the prior
Liebert assigns to User any warranties which are made by manufacturers and suppliers of components of the Liebert product and which are
assignable, but Liebert makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any
Liebert warrants for the period and on the terms of the Warranty set forth herein that the Liebert product will conform to the certifi ed drawings, if any,
applicable thereto, to Liebert’s fi nal invoices, and to applicable Liebert product brochures and manuals current as of the date of product shipment
(“Descriptions”). Liebert does not control the installation and use of any Liebert product. Accordingly, it is understood that the Descriptions are
Within a reasonable time, but in no case to exceed thirty (30) days, after User’s discovery of a defect, User shall contact Liebert at 1-800-LIEBERT
(543-2378) and request a return authorization number. User shall ship the product, with proof of purchase, to Liebert freight prepaid. Liebert
products shipped to Liebert without a return authorization number will be refused and returned freight collect to User at User’s expense. Liebert
products shipped by User to Liebert which have incurred freight damage due to User’s improper packaging of the product will not be covered by
this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned
Subject to the limitations specifi ed herein, Liebert will repair or replace, at its option, without charge for Liebert labor or materials, subsequent
to its inspection F.O.B. Liebert’s facility, the Liebert product warranted hereunder which does not conform to the Warranty. Replacement parts,
components or products shipped to User prior to Liebert’s receipt and inspection of the product claimed to be defective shall be invoiced in the
full current price amount and shipped freight collect F.O.B. Liebert’s facility. Warranty coverage will be extended only after Liebert’s receipt of
the claimed defective product within thirty (30) days of shipment of any replacement parts, components or products, if applicable, and only if
Liebert’s inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of
It is Liebert’s practice, consistent with its desire to remedy Warranty defects in the most prompt and effective manner possible, to cooperate
with and utilize the services of component manufacturers and their authorized representatives in the performance of work to correct defects
in the product components. Accordingly, Liebert may utilize third parties in the performance of Warranty work, including repair or replacement
hereunder, where, in Liebert’s opinion, such work can be performed in less time, with less expense, or in closer proximity to the Liebert product.
them. Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship.
matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components.
this Warranty. All defective products and component parts replaced under this Warranty become the property of Liebert.
TEN YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP
NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
AccuVar® Transient Voltage Surge Suppressors, and Type SS Transient Voltage Surge Suppressors.
Warranty Extends to First Purchaser for Use, Non-transferable:
Warranty Performance of Component Manufacturers:
Obtaining Performance Under This Warranty:
repair or replacement of that part or portion.
performance under this Warranty.
written permission of Liebert.
Assignment of Warranties:
Drawings, Descriptions:
freight collect to User.
Terms of Warranty:
General:

THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or
connection, negligence, inappropriate on site operating conditions, corrosive atmosphere, repair by non-Liebert designated personnel, accident
in transit, tampering, alterations, a change in location or operating use, exposure to the elements, Acts of God, theft or installation contrary to
Liebert’s recommendations or specifi cations, or in any event if the Liebert serial number has been altered, defaced or removed. Notwithstanding
the foregoing, the following Acts of God are covered: lightning-induced surges, which are transients, spikes or other sub-cycle, discontinuous
events impinging on normally applied voltage as defi ned by reference data in the latest version of IEEE C62.41 and the Liebert product performance
THIS WARRANTY DOES NOT COVER shipping costs, installation costs, circuit breaker resetting or maintenance or service items and further, except
as provided herein, does NOT include labor costs or transportation charges arising from the replacement of the Liebert product or any part thereof
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Liebert product in combination with any electrical or electronic
components, circuits, systems, assemblies, or other materials not furnished by Liebert. Liebert does NOT warrant the suitability for use or the
THE PRODUCTS LISTED IN THIS WARRANTY ARE NOT DESIGNED FOR USE IN THE FOLLOWING APPLICATIONS: (i) ANY NUCLEAR OR RELATED
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD.
APPLICATIONS; AND (ii) LIFE SUPPORT AND PATIENT-CONNECTED AND APPLIED MEDICAL AND DENTAL APPLICATIONS.
UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT OR OTHERWISE.
results of the Liebert product in combination with the products of others.
or charges to remove or reinstall same at any premises of the User.
Items Not Covered By Warranty:
Miscellaneous:
specifi cations.
Limitations:
others.




Items Not Covered By Warranty:

responsibility and disclaims all liability for damages resulting from use
© 2006 Liebert Corporation All rights reserved throughout the world.
The global leader in enabling Business-Critical Continuity™. Emerson Network Power.com
Racks and Integrated Cabinets
While every precaution has been taken to ensure the accuracy and
® Liebert and the Liebert logo are registered trademarks of Liebert
completeness of this literature, Liebert Corporation assumes no
Corporation. All names referred to are trademarks or registered
SL-22085 (11/06) Rev. 2 82290 Printed in USA
Emerson Network Power, the Emerson Network Power logo and Business-Critical Continuity are trademarks and service marks of Emerson Electric Co.
of this information or for any errors or omissions.
Specifi cations subject to change without notice.
Emerson Network Power Asia Pacifi c
7/F., Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong
trademarks of their respective owners.
614 888 0246 (Outside U.S.) 614 841 6022 FAX
35028 Piove Di Sacco (PD) Italy
Via Leonardo Da Vinci 8
39 049 9719 111 Phone 39 049 5841 257 FAX
607 724 2484 Phone 607 722 8713 FAX 800 288 6169 Toll-Free
1050 Dearborn Drive P.O. Box 29186
800 877 9222 Phone (US & Canada Only)
852 25722201 Phone 852 28029250 FAX
Power Switching & Controls
Emerson Network Power.
©2006 Emerson Electric Co.