Line Interactive Network Protection
Pure Sine Wave Output UPS
Regular models600A/800A/1000A/1250A
1500A/2000A/2500A/3000A & Extended Run-Time Models
1000AL/2000AL/3000AL
USER’S MANUAL
Printed in USA

Thank you for selecting this uninterruptible power system (UPS). It provides you
with better protection for connected equipment.
This manual provides safety, installation and operating instructions that will help
you derive the fullest performance and service life that the UPS has to offer.
It includes important instructions for the safe use of this UPS and for obtaining
factory service should the proper operation of the UPS come into question.
The UPS‘ s shipping materials were designing with great care to provide
protection from transportation related damage. These materials are invaluable if
you ever have to return the UPS for service. Damage sustained during transit is
not covered under the warranty.



The product is line interactive UPS with the newest technology and powerful function. The LINE INTERACTIVE UPS is with AVR function allows input voltage range from 75% to 125%, including on line voltage boost-up & buck down. An ideal protection equipment for critical connected loads. It is based on microprocessor controls, with utility power connected, the charging is ongoing, no need to switch ON the UPS and at back-up mode, UPS can be automatically turned OFF if none of the connected loads is operating to save the battery energy. The indicator will be ON when battery needs replacement and a cyclic self-testing function is included in order to verify both the operation of the UPS and the condition of the battery.
In addition, This UPS provides advanced single telephone line or modem surge suppression through the modular connectors on the back panel.
The LINE INTERACTIVE UPS and RUPS seies monitoring software (optional kits) makes your computer operate intelligent and provides you with the ability of perfect protection of your critical devices.
connect the equipment to an outlet on a circuit different from that to which the receiver is connected
increase the separation between the equipment and the receiver reorient the receiving antenna

∨ To reduce the risk of electric shock, disconnect the UPS from the mains supply before installing a computer interface signal cable. Reconnect the power cord only after signaling interconnections have been made.
∨ The internal energy source(the battery) cannot be de-energized by the user. The output may be energized when the unit is not connected to a mains supply.
∨ The right way to de-energize the UPS properly in an emergency is to move the I/O switch to the OFF position and disconnect the power cord from the mains supply.
∨ The socket-outlet shall be installed near the equipment and easily accessible.
∨Attention, hazardous through electric shock. Also with disconnection of this unit the main, hazardous voltage still may be accessible through supply from battery. The battery supply should be therefore disconnected in the plus and minus pole when maintenance of service work inside the UPS is considered.
∨ Do not dispose of batteries in a fire, the battery may explore.
∨ Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
∨ A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries - Remove watches, rings or other metal objects. - Use tools with insulated handles.
3.1 "ON/TEST" button With the UPS plugged in, press the ON/TEST button to turn on the UPS and

power the loads. ON/TEST also activates the UPS's self-test and utility line voltage displays.
3.2 " OVERLOAD" indicator (RED LED) The LED lights when the loads connected to the UPS exceed the UPS's capacity. See Section 6.3.
3.3 "BACK UP" indicator (GREEN LED) The LED illuminates when the UPS is supplying battery power to the loads.
3.4 "REPLACE BATTERY" indicator (RED LED)
The LED illuminates when the UPS's battery is no longer useful and must be replaced. See section 9.
3.5 "BUCK AVR (VOLTAGE REDUCTION)" indicator (YELLOW LED) The LED illuminates when the UPS is correcting a high utility voltage condition. The loads receive normal power.
3.6 "LINE NORMAL" indicator (GREEN LED) The LED illuminates when the line input voltage is normal.
3.7 "BOOST AVR (VOLTAGE BOOST)" indicator (YELLOW LED) The LED illuminates when the UPS is correcting a low utility voltage condition. The loads receive normal power.
3.8 LOAD bar graph The display shows the power being drawn by the load.
3.9 POWER bar graph (BATTERY CHARGE/LINE VOLTAGE) The display shows the present battery charge as a percentage of battery capacity. It also display the voltage of utility line.
3.10 "OFF" button Press the OFF button to turn off the UPS and the loads.
3.11 TEL./MODEM SURGE PROTECTION Surge protection for telephone and modem line to have the complete safety connection for INTERNET service.
3.12 EXTERNAL BATTERY PACK CONNECTOR (optional) Caution: Use only factory supplied or authorized connecting cable for external

3.13 SNMP INTERFACE PORT (optional) Provide the SNMP adapters for 10-BaseT Ethernet and Token Ring connectors. Through RS232 communication port, the SNMP adapter make your UPS becomes "SNMP manageable", provide a real time UPS and power status information for the network manager.
3.15 AC INPUT POWER RECEPTACLE
3.16 INPUT CIRCUIT BREAKER It trips when the connected loads exceed the protected receptacle's capacity, The center plungers of the circuit breakers extend when tripped.
3.17 SITE WIRING FAULT INDICATORS (RED LED) It comes on when the UPS is connected to an improperly wired AC power outlet. Note: This device is available on 110 Vac model only.
3.18 COMPUTER INTERFACE Provide both RS-232 and relay signal to support NOVELL, UNIX, DOS, WINDOWS and other operating systems.
4.0 Inspection Inspect the UPS upon receipt. The packaging is recyclable; save it for reuse or dispose of it properly.
4.1 Placement Install the UPS in a protected area with adequate air flow and free of excessive dust. Do not operate the UPS where the temperature and humidity is outside the specified limits.
4.2 Connect Computer Interface (optional)
battery !

RUPS series software (or other power management software) and an interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9 pin computer interface port on the back panel of the UPS.
4.3 Connect external battery pack (optional) Before connecting, make sure the external battery pack and the connector cable are compatible with this UPS.
4.4 Connect the telephone/modem lines Connect a single line telephone or a modem line into the telephone/modem surge protection sockets on the back of the UPS. The RJ-45/RJ-11 modular sockets accept standard single line telephone connections. This connection will require another length of telephone cable (supplied).
4.5 Connect to Utility Connect the AC input power connector to utility power to power up the UPS.
4.6 Charge the battery The UPS charges its battery whenever it is connected to utility power. For best results, charge the battery for 4 hours in the initial use.
4.7 Connect the loads Plug the loads into the output connectors on the rear of the UPS. To use the UPS as a master on/off switch, make sure all of the loads are switched on.

computer equipment. A laser printer or plotter periodically draws significantly more power than when idle, and may overload the UPS.
4.8 Check the Site Wiring Fault Indicator After plugging in the loads and the UPS, check the site wiring fault indicator on the rear panel. See section 3.17 for location of the indicator on the back panel. It lights if the UPS is plugged into an improperly wired AC power outlet. Wiring faults detected include ground, hot-neutral polarity reversal, and overloaded neutral circuit.
2.5cm (1 in )

5.1 Switch on With the UPS plugged in, press ON/TEST button less than 1 second to switch the UPS on. The UPS will perform self-testing each time when it is switched on.
5.2 Switch off By pressing and holding OFF button until the "LINE NORMAL" or "BACK UP" LED off.

5.3 Self-test Use the self-test to verify both the operation of the UPS and the condition of the battery. In normal utility power, push the ON/TEST button more than 1 second and UPS performs a self-test function. During the self-test, the UPS operates a back up mode.
Note: During the self-test, the UPS briefly operates the loads on-battery (the on-battery LED comes on). If the UPS passes the self-test, it returns to on-line operation. The on-battery L E D d o e s o f f a n d t h e o n - l i n e L E D g o e s o n s t e a d y . If the UPS fails the self-test it immediately returns to on-line operation and lights the replace battery LED. The loads are not affected. Recharge the battery overnight and perform the self-test again. If the replace battery LED is still on, ask our nearest dealer to replace battery.
5.4 Silence In "BACK UP" mode, push ON/TEST more than 1 second to silence the audible alarm. (The function is void when under condition of "LOW BATTERY" or "OVERLOAD")
5.5 Load bar graph The 5-LED display (See section 3.8 for location of the indicator on the front panel) shows the power drawn from the UPS by load. The display indicates the percentage of the UPS's rated capacity. For example. If three LEDs are lit, the load is drawing between 50% and 67% of the UPS's capacity. If the UPS is overloaded, the overload LED lights and alarm sounds. See section 6.3
5.6 Bttery charge bar graph The 5-LED display (see section 3.9 for location of the indicator on the front panel) shows the present charge of the UPS's battery as a percentage of the battery capacity. When all five LEDs light, the battery is fully charged. When only two LED lights, the battery can supply less than two minutes of run time for the load.
5.7 Cold start When the UPS is off and there is no utility power, use the cold start feature to apply power to the loads from UPS's battery. Press the ON/TEST button (see section 3.1 for location of the indicator on the front panel) until the UPS beeps.
5.8 Shutdown mode In shutdown mode the UPS stops supplying power to the load, waiting for return of utility power. If there is no utility power present, external devices (e.g., servers) connected to the computer interface can command the UPS to shutdown. This is normally done to preserve battery capacity after the graceful shutdown of protected servers. The UPS will scroll the front panel indicators sequentially in shutdown mode.

6.1 "BACK UP" (slow alarm) When in BACK UP mode, the YELLOW LED illuminates and the UPS sounds an audible alarm. The alarm stops when the UPS returns to LINE NORMAL operation. Press the ON/TEST button during on-battery alarms to stop the beeping.
6.2 "LOW BATTERY" (rapid alarm) In BACK UP mode, when the battery energy runs low, the UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to LINE NORMAL operation.
6.3 "OVERLOAD" (continuous alarm) When the UPS is overloaded (the connected loads exceed the maximum rated capacity) the UPS emits continuous alarm to warn a overload condition. Disconnect nonessential load equipment from UPS to eliminate the overload.
6.4 "REPLACE BATTERY" (continuous alarm) The UPS emits continuous beeps and the REPLACE BATTERY LED illuminates if the battery fails the self-test. See section 9 to replace battery by yourself or call your dealer for services.
7.1 Power Monitoring Software The RUPS series software (or other power monitoring software) is applied standard RS-232 interface to perform monitoring functions, and then provides an orderly shutdown of a computer in the event of power failure. Moreover, RUPS displays all the diagnostic symptoms on monitor, such as Voltage, Frequency, Battery level and so on..
The software is available for DOS, Windows 3.1x, Windows 95, Windows NT V3.5 or later, Novell Netware and others. Call your dealer for more information on computer OS compatible solutions.
7.2 Interface Kits A series of interface kits is available for operation systems that provide UPS monitoring. Each interface kit includes the special interface cable required to convert status signals from the UPS into signals which individual operating system recognize. The interface cable at UPS side must be connected to REMOTE PORT , at computer side can be either COM 1 or COM 2. The other installation instructions and powerful features please refer to READ.ME file.

1. Keep the unit clean and vacuum the ventilation intake periodically. 2. Wipe with soft loose and damp cloth. 3. Check for loose and bad connections monthly. 4. Never leave the unit on an uneven surface. 5. Position the unit to allow at least 10 cm clearance between the rear panel and the wall. Keep the ventilation intake open. 6. Avoid direct sunlight, rain. And high humidity. 7. Stay away from fire and extremely hot location. 8. Do not stack materials on top of the unit. 9. The unit should not be exposed to corrosive air. 10. The normal operating temperature is 0-40 .
The computer interface port has the following characteristics: The communication port on the back of the UPS may be connected to host computer. This port allows the computer to monitor the status of the UPS and control the operation of the UPS in some cased. Its major functions normally include some or all of the following:
to broadcast a warning when power fails. to close any open file before the battery reserves are exhausted. to turn of the UPS. Some computers are equipped with a special connector to link with the communication port. In addition, special plug-in card may be needed. Some computers may need a special UPS monitoring software. Contact your dealer for the details on the various interface Kits. The computer interface port has the following characteristics: 1. Pin 5 and 2 are open collector outputs which must be pulled up to a common referenced supply no greater than +40 Vdc. The transistors are capable of a maximum nonconductive load of 25 mAdc, Use only pin 7 as the common.


Your battery should run any where from 3-5 years before eve needing to be replaced. Please follow the instructions below for easy battery replacement. 1) Unplug unit from AC power source and disconnect all connected equipment. 2) Disconnect AC power cord from unit.. 3) Turn unit upside down and using a phillips screw driver, unscrew the 4 screws holding the top of the unit to the bottom. Put screws in a safe place for reconnection. 4) Holding the top together firmly with the bottom, turn the entire unit right side up. 5) Carefully lift top cover off and place to the side. The connecting wires and electronics will be exposed. Be careful not to touch any inner components when changing the battery. 6) Remove the 2 connecting wires from the battery. 7) You can now easily remove the battery from the unit Caution: Do not dispose of battery in fire. Caution: Do not attempt to open the battery. Caution: The following precautions should be taken when replacing the battery ∨remove watches, rings, etc… ∨use tools with insulated handles

10.1 Storage conditions Store the UPS covered and upright in a cool , dry location, with its battery fully charged. Before storing, charger the UPS for at least 4 hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessary draining the battery.
10.2 Extended storage During extended storage in environments where the ambient temperature is -15 to +30 (+5 to +86 ), charge the UPS‘ s battery every 6 months. During extended storage in environments where the ambient temperature is +30 to +45 (+86 to +113 ), charge the UPS‘ s battery every 3 months.
PROBLEM POSSIBLE ACTION TO TAKE On/test button not pushed or push too short
Press the on/test button to power the UPS and the load
UPS input circuit break tripped
Reduce the load on the UPS by unplugging equipment and reset the circuit breaker by pressing the plunger back in
UPS will not turn on
Very low or no utility voltage
Check the AC power supply to the UPS with multimeter
Computer interface of accessory problem Push on/test or off button too short
Disconnect the computer interface or accessory. If the UPS now works normally, check the interface cable, the attached computer and the accessory
UPS will not turn on or off
UPS operates on- battery even though normal line voltage is
UPS’ s input circuit breaker tripped
Reduce the load on the UPS by unplugging equipment and reset the circuit breaker
UPS beeps occasionally Normal UPS operation Normal condition UPS does not provide The UPS’ s battery is Charge the battery

The UPS is overloaded Check the UPS’ s load display Remove nonessential equipments Front panel indicators flash sequentially
The UPS has been shut down by remote control
None. The UPS will restart automatically when utility power returns.
All indicators are flash And the UPS emits a Constant tone
Internal UPS fault Do not attempt to use the UPS. Turn the UPS off and have it service immediately
The UPS operates normally, but the site wiring fault indicator is lit.
Building wire error such as missing ground or hot to neutral wire reversal
Have a qualified electrician correct the building wiring
The UPS is shut down and the battery is discharged and exhausted.
None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.
Low battery light is on and all LED is off.
Weak batteries The batteries to recharge for at least four hours. If the problem still exists after recharging, replace with batteries.
The replace battery light is lit
Install up to 8 battery packs per xxxA(L) model UPS following the instruction below.


To install additional battery packs, repeat this procedure using the battery pack connectors on the battery packs. Note: Do not stack battery packs.

MODEL SMK 600A 800A 1000A 1250A 1500A 2000A Capacity 600VA 800VA 1000VA 1250VA 1500VA 2000VA Voltage 100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Single phase INPUT
Frequency 50 or 60Hz +/-5% (auto sensing) Voltage (on battery)
AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output voltage
15% below input voltage if+9% to +25% of nominal
Spike Protection 320 Joules, 2ms Unit Input Fuse for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz Overload Protection
UPS automatic shutdown if overload exceeds 110% of nominal at
Short Circuit UPS output cut off immediately or input fuse protection Type Hot swappable, Sealed, Maintenance-free lead acid BATTERY


indicator Back - up Time 10 - 30 minutes (depending on computer load) Net Weight
Receptacles NEMA 5-15R (115V)/IEC 320 female appliance coupler (230V) Battery Back-Up
Overload Continue beeping sound INTERFACE RS-232 I t f
Bi-directional communication port Safety cUL, TUV, CE, meet FCC Surge Meet IEEE 587 standard CONFORMANCE
6,000 meters max. elevation, 0-95% humidity non-condensing 0-40 deg C Audible noise
MODEL SMK 800A RM 1250A RM 1500A RM 2000A RM 2500A RM 3000A RM Capacity 800VA 1250VA 1500VA 2000VA 2500VA 3000VA Voltage +/-25% at line input , Single phase INPUT
Frequency 50 or 60Hz +/-5% (auto sensing) Voltage (on battery)
Pure sine wave output at +/-5% of nominal, -10% after low battery
50 or 60Hz +/-0.5%
AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output voltage 15% below input
voltage if+9% to +25% of nominal
Spike Protection 320 Joules, 2ms Unit Input Fuse for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz Overload Protection
UPS automatic shutdown if overload exceeds 110% of nominal at 20
second and 125% at 2 seconds.
Transfer Time 2/4 milliseconds, including detection time
Short Circuit UPS output cut off immediately or input fuse / breaker protection Type Hot swappable, Sealed, Maintenance-free lead acid , with 3-6 years
4 hours (to 90% of full capacity)
Voltage Regulation AVR · lifetime BATTERY · Typical Recharge Time

Protection Automatic self-test & discharge protection, Replace battery indicator
Back - up Time 10 - 30 minutes (depending on computer load) Net Weight
57.8 (127.1) Shipping Weight Kg(lbs)
18.0 (39.6)
23.5 (51.7)
26.1 (57.4)
28.4 (62.4)
55.2 (121.4)
60.0 (132.0) Dimension(mm) WxDxH 483 x 381 x 130 483 x 508 x 221
19.5 (42.9)
25.0 (55.0)
27.7 (60.9)
30.0 (66.0)
58.0 (127.6)
Input Inlet IEC 320 power inlet
Receptacles NEMA 5-15R (115V)/IEC 320 female appliance coupler (230V) Battery Back-Up
Slow beeping sound (about 0.25Hz)
Battery Low Rapid beeping sound (about 1.00Hz)
Overload Continue beeping sound INTERFACE Support both RS232 &dry contact signal
Provide power management & diagnostic functions including power status, battery low, schedule UPS ON/OFF, battery/load level display and more. Compatible with Windows 95/98/NT, Novell, Unix and other
popular systems.
3,500 meters max. elevation, 0-95% humidity non-condensing 0-40 deg C Audible noise
15000 meters max. elevation

MODEL SMK 2500A 3000A 1000AL 2000AL 3000AL Capacity 2500VA 3000VA 1000VA 2000VA 3000VA Voltage +/-25% at line input, Single phase INPUT
Frequency 50 or 60Hz +/-5% (auto sensing) Voltage (on battery)
Pure sine wave at +/-5% of nominal, -10% after low battery
AVR automatically increase output voltage 15% above input voltage if -9% to-25% of nominal. AVR decrease output voltage
15% below input voltage if+9% to +25% of nominal
Unit Input Breaker for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz Overload Protection
UPS automatic shutdown if overload exceeds 110% of nominal at
Short Circuit UPS output cut off immediately or input fuse protection Type Hot swappable, Sealed, Maintenance-free lead acid ,with 3-6
Kg(lbs) · Ambient operation · Storage condition


indicator Back - up Time 10 - 30 minutes (depending on computer load) Net Weight (Kg) (220V)30 (110V)
26.8 Shipping Weight (Kg) 32 22.7 21 11 21 29.3
Safety cUL, TUV, CE, FCC Surge Meet IEEE 587 standard CONFORMANCE
6,000 meters max. elevation, 0-95% humidity non-condensing 0-40 deg C Audible noise


Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS will not turn on | Press the on/test button to power the UPS and the load | p.14 | |
| UPS will not turn on | Reduce the load on the UPS by unplugging equipment and reset the circuit breaker by pressing the plunger back in | p.14 | |
| UPS will not turn on | Check the AC power supply to the UPS with multimeter | p.14 | |
| UPS will not turn on or off | Disconnect the computer interface or accessory. If the UPS now works normally, check the interface cable, the attached computer and the accessory | p.14 | |
| UPS operates on- battery even though normal line voltage is | Reduce the load on the UPS by unplugging equipment and reset the circuit breaker | p.14 | |
| UPS beeps occasionally | Normal condition | p.14 | |
| UPS does not provide | Charge the battery | p.14 |