Important Safety Instructionsp.7Figure 1 Model number nomenclaturep.81.0 Product Descriptionp.91.1 General Product Informationp.91.1.1 Product/System Descriptionp.9Figure 2 Liebert XDP componentsp.91.1.2 Minimum Loadp.9Table 1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H) loadp.91.2 Equipment Inspectionp.91.3 Equipment Handlingp.101.3.1 Handling the Liebert XDP While it is on Skid and Packagedp.101.3.2 Unpacking the Liebert XDPp.11Figure 3 Unpacking the Liebert XDPp.111.3.3 Removing the Unit from the Skid Using a Forkliftp.11Figure 4 Use a forklift to remove the Liebert XDP from the skidp.121.3.4 Removing the Unit from the Skid using Riggingp.12Figure 5 Removing the unit from the skid using riggingp.131.3.5 Moving the Liebert XDP Using Piano Jacksp.13Figure 6 Securing the Liebert XDP to piano jacksp.141.3.6 Removing the Unit from the Piano Jacksp.142.0 Installationp.152.1 Mechanical Considerationsp.152.1.1 Positioning the Liebert XDPp.15Figure 7 Dimensionsp.15Table 2 Liebert XDP dimensionsp.15Figure 8 Piping access pointsp.16Table 3 Unit piping outlet connection sizes, inches, OD Cup.162.2 Electrical Considerationsp.162.2.1 Connecting High-Voltage Cablesp.17Figure 9 Front view of Liebert XDP and electrical enclosurep.17Figure 10 Electrical enclosure knockout location for hazardous voltage wiringp.18Figure 11 High voltage connections—60Hzp.18Figure 12 High voltage connections—50Hzp.192.2.2 Extra Low Voltage (ELV) Connectionsp.19Figure 13 Electrical enclosure knockout locations for Extra Low Voltagep.19Figure 14 Connecting the remote temperature/humidity sensorsp.202.2.3 DIP Switch and Jumper Settings for Remote Sensorsp.21Figure 15 DIP switch and jumper settingsp.21Figure 16 Unit-to-unit networking connectionsp.212.3 Field Connections—Optional for All Unitsp.22Figure 17 Liebert XDP extra low voltage field connections pointsp.222.4 Remote Sensor Installation—Proper Placementp.23Figure 18 Suggested remote sensor placementp.233.0 Pipingp.243.1 European Union Fluorinated Greenhouse Gas Requirementsp.243.2 Connection Sizesp.243.2.1 Recommended Pipe Sizep.24Table 4 Supply, return pipe sizes for refrigerant loopp.243.3 Liebert XDP Interconnection with Liebert XD Cooling Modulesp.25Figure 19 Liebert XD system diagramp.253.4 Piping Installation Methodsp.253.4.1 Piping Installation—R-134a Pumped Circuitp.253.4.2 Piping Mainsp.263.4.3 Bypass Flow Controllerp.26Table 5 Bypass flow controllers for a Liebert XDP-based systemp.26Figure 20 Bypass flow controller details, dimensionsp.26Figure 21 Bypass flow controller arrangementp.27Figure 22 Bypass flow controller pipingp.273.5 Piping Details—Shutoff/Isolation Valvesp.27Figure 23 General piping detailsp.283.5.1 Evacuation and Leak Check—R-134a Pumped Circuitp.283.5.2 Insulationp.283.6 Filling the Pumped Circuit—R-134ap.29Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 7 System refrigerant charge for the supply and return mainsp.29Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 9 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDRp.303.6.1 Calculating Refrigerant Charge—Examplep.30Table 10 Calculating refrigerant charge—examplep.30Table 11 Worksheet to calculate refrigerant chargep.303.7 Checklist for Proper Installationp.314.0 Liebert iCOM Control—Firmware Version XP1.00.010.STDp.324.1 Liebert iCOM Components and Functionsp.32Figure 24 Liebert iCOM display componentsp.32Table 12 Keyboard icons and functionsp.334.2 Display Lamp Indicatorsp.334.3 Navigating Through the Liebert iCOM Displayp.34Figure 25 Liebert iCOM default home screenp.344.3.1 Accessing Menus and Settingsp.34Viewing Datap.344.3.2 Cooling Module Overviewp.35Figure 26 Cooling module overview, first 10 modulesp.354.3.3 Entering the Passwordp.36Figure 27 Entering the passwordp.364.4 Changing Liebert iCOM’s Display Settingsp.37Figure 28 Display setup screenp.374.5 Changing Operational Settingsp.374.6 Graphical Data Recordp.384.7 Liebert iCOM User Menu Icons and Legendp.38Figure 29 Liebert iCOM User Menu iconsp.38Figure 30 Liebert XDP User Menu screenp.394.8 Liebert iCOM User Menu Screensp.40Figure 31 Setpoints screenp.40Spare Partsp.40Event Logp.40Figure 32 Set Alarms screenp.41Figure 33 Sensor Data screen, page 1 of 2p.42Figure 34 Sensor Data screen, page 2 of 2p.43Figure 35 Display Setup screenp.44Figure 36 Module Status screen, page 1 of 20p.45Figure 37 Liebert XDV Smart Module Status screenp.45Figure 38 Liebert XDH Smart Module Status screen—each bank shown separatelyp.46Figure 39 Liebert XDO Smart Module Status screenp.46Figure 40 Total Run Hours screenp.474.9 Liebert iCOM Service Menu Icons and Legendp.47Figure 41 Liebert iCOM Service Menu iconsp.47Figure 42 Liebert XDP Service Menu screenp.484.10 Liebert iCOM Service Menu Screensp.48Figure 43 Setpoints screenp.48Figure 44 Maintenance—Basic Settings screen, page 1 of 7p.50Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7p.51Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7p.52Figure 47 Maintenance screens, pages 4 through 7p.52Figure 48 Diagnostics/Service Mode screen, page 1 of 6p.53Figure 49 Diagnostics/Service Mode screen, page 2 of 6p.53Figure 50 Diagnostics/Service Mode screen, page 3 of 6p.54Figure 51 Diagnostics/Service Mode screen, page 4 of 6p.54Figure 52 Diagnostics/Service Mode screen, page 5 of 6p.55Figure 53 Diagnostics/Service Mode screen, page 6 of 6p.55Figure 54 Set Alarms screen, page 1 of 7p.56Figure 55 Set Alarms screen, page 2 of 7p.57Figure 56 Set Alarms screen, page 3 of 7p.58Figure 57 Set Alarms screen, page 4 of 7p.59Figure 58 Set Alarms screens, pages 5 and 6p.60Figure 59 Set Alarms screen, page 7 of 7p.60Figure 60 Sensor Calibration/Setup screen, page 1 of 3p.61Figure 61 Sensor Calibration/Setup screen, page 2 of 3p.62Figure 62 Sensor Calibration/Setup screen, page 3 of 3p.62Figure 63 System/Network Setup screen—System, page 1 of 2p.63Figure 64 System/Network Setup screen—System, page 2 of 2p.64Figure 65 System/Network Setup screen—Unit, page 1 of 2p.65Figure 66 System/Network Setup screen—Unit, page 2 of 2p.66Figure 67 Options Setup screen, page 1 of 2p.67Figure 68 Options Setup screen, page 2 of 2p.68Figure 69 Module Setup screen, page 1 of 20p.68Figure 70 Module Setup screen, page 1 of 20p.695.0 Start the Liebert XDP with Liebert iCOMp.705.1 Checklist for Liebert XDP Startupp.70Table 13 Liebert XDP pump light indicator—208V and 400V unitsp.705.2 Starting the Liebert XDP with Liebert iCOM Controllerp.71Figure 71 System R-134a liquid level at 160kW loadp.716.0 Alarm Descriptions and Solutionsp.726.1 Alarm Descriptionsp.726.2 Warning Descriptionsp.746.3 System Shutdown Causesp.74Unit Is Off By Refrig Sens Failp.74Unit Is Off By High CW Tempp.74Unit Is Off By Pump Short Cyclep.74Unit Is Off By Low Refrig Tempp.747.0 Troubleshootingp.75Table 14 Troubleshooting the Liebert XDPp.758.0 Maintenancep.778.1 Fluorinated Greenhouse Gas Requirementsp.779.0 Specificationsp.78Table 15 Liebert XDP160 specificationsp.78
Page 1 of the Liebert XDP160RC user manual — Liebert ® XDP ™ with Liebert ® iCOM ® Control
Page 1 · click to enlarge
Page 1
Liebert XDP160RC diagram (page 1)
Fig. 1

Liebert ® XDP ™ with Liebert ® iCOM ® Control

Page 2 of the Liebert XDP160RC user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Liebert XDP160RC user manual
Page 3 of the Liebert XDP160RC user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Important Safety Instructionsp.7Figure 1 Model number nomenclaturep.81.0 Product Descriptionp.91.1 General Product Informationp.91.1.1 Product/System Descriptionp.9Figure 2 Liebert XDP componentsp.91.1.2 Minimum Loadp.9Table 1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H) loadp.91.2 Equipment Inspectionp.91.3 Equipment Handlingp.101.3.1 Handling the Liebert XDP While it is on Skid and Packagedp.101.3.2 Unpacking the Liebert XDPp.11Figure 3 Unpacking the Liebert XDPp.111.3.3 Removing the Unit from the Skid Using a Forkliftp.11Figure 4 Use a forklift to remove the Liebert XDP from the skidp.121.3.4 Removing the Unit from the Skid using Riggingp.12Figure 5 Removing the unit from the skid using riggingp.131.3.5 Moving the Liebert XDP Using Piano Jacksp.13Figure 6 Securing the Liebert XDP to piano jacksp.141.3.6 Removing the Unit from the Piano Jacksp.142.0 Installationp.152.1 Mechanical Considerationsp.152.1.1 Positioning the Liebert XDPp.15Figure 7 Dimensionsp.15Table 2 Liebert XDP dimensionsp.15Figure 8 Piping access pointsp.16Table 3 Unit piping outlet connection sizes, inches, OD Cup.162.2 Electrical Considerationsp.162.2.1 Connecting High-Voltage Cablesp.17Figure 9 Front view of Liebert XDP and electrical enclosurep.17Figure 10 Electrical enclosure knockout location for hazardous voltage wiringp.18Figure 11 High voltage connections—60Hzp.18Figure 12 High voltage connections—50Hzp.192.2.2 Extra Low Voltage (ELV) Connectionsp.19Figure 13 Electrical enclosure knockout locations for Extra Low Voltagep.19Figure 14 Connecting the remote temperature/humidity sensorsp.202.2.3 DIP Switch and Jumper Settings for Remote Sensorsp.21Figure 15 DIP switch and jumper settingsp.21Figure 16 Unit-to-unit networking connectionsp.212.3 Field Connections—Optional for All Unitsp.22Figure 17 Liebert XDP extra low voltage field connections pointsp.222.4 Remote Sensor Installation—Proper Placementp.23Figure 18 Suggested remote sensor placementp.233.0 Pipingp.243.1 European Union Fluorinated Greenhouse Gas Requirementsp.243.2 Connection Sizesp.243.2.1 Recommended Pipe Sizep.24Table 4 Supply, return pipe sizes for refrigerant loopp.243.3 Liebert XDP Interconnection with Liebert XD Cooling Modulesp.25Figure 19 Liebert XD system diagramp.253.4 Piping Installation Methodsp.253.4.1 Piping Installation—R-134a Pumped Circuitp.253.4.2 Piping Mainsp.263.4.3 Bypass Flow Controllerp.26Table 5 Bypass flow controllers for a Liebert XDP-based systemp.26Figure 20 Bypass flow controller details, dimensionsp.26Figure 21 Bypass flow controller arrangementp.27Figure 22 Bypass flow controller pipingp.273.5 Piping Details—Shutoff/Isolation Valvesp.27Figure 23 General piping detailsp.283.5.1 Evacuation and Leak Check—R-134a Pumped Circuitp.283.5.2 Insulationp.283.6 Filling the Pumped Circuit—R-134ap.29Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 7 System refrigerant charge for the supply and return mainsp.29Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 9 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDRp.303.6.1 Calculating Refrigerant Charge—Examplep.30Table 10 Calculating refrigerant charge—examplep.30Table 11 Worksheet to calculate refrigerant chargep.303.7 Checklist for Proper Installationp.314.0 Liebert iCOM Control—Firmware Version XP1.00.010.STDp.324.1 Liebert iCOM Components and Functionsp.32Figure 24 Liebert iCOM display componentsp.32Table 12 Keyboard icons and functionsp.334.2 Display Lamp Indicatorsp.334.3 Navigating Through the Liebert iCOM Displayp.34Figure 25 Liebert iCOM default home screenp.344.3.1 Accessing Menus and Settingsp.34Viewing Datap.344.3.2 Cooling Module Overviewp.35Figure 26 Cooling module overview, first 10 modulesp.354.3.3 Entering the Passwordp.36Figure 27 Entering the passwordp.364.4 Changing Liebert iCOM’s Display Settingsp.37Figure 28 Display setup screenp.374.5 Changing Operational Settingsp.374.6 Graphical Data Recordp.384.7 Liebert iCOM User Menu Icons and Legendp.38Figure 29 Liebert iCOM User Menu iconsp.38Figure 30 Liebert XDP User Menu screenp.394.8 Liebert iCOM User Menu Screensp.40Figure 31 Setpoints screenp.40Spare Partsp.40Event Logp.40Figure 32 Set Alarms screenp.41Figure 33 Sensor Data screen, page 1 of 2p.42Figure 34 Sensor Data screen, page 2 of 2p.43Figure 35 Display Setup screenp.44Figure 36 Module Status screen, page 1 of 20p.45Figure 37 Liebert XDV Smart Module Status screenp.45Figure 38 Liebert XDH Smart Module Status screen—each bank shown separatelyp.46Figure 39 Liebert XDO Smart Module Status screenp.46Figure 40 Total Run Hours screenp.474.9 Liebert iCOM Service Menu Icons and Legendp.47Figure 41 Liebert iCOM Service Menu iconsp.47Figure 42 Liebert XDP Service Menu screenp.484.10 Liebert iCOM Service Menu Screensp.48Figure 43 Setpoints screenp.48Figure 44 Maintenance—Basic Settings screen, page 1 of 7p.50Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7p.51Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7p.52Figure 47 Maintenance screens, pages 4 through 7p.52Figure 48 Diagnostics/Service Mode screen, page 1 of 6p.53Figure 49 Diagnostics/Service Mode screen, page 2 of 6p.53Figure 50 Diagnostics/Service Mode screen, page 3 of 6p.54Figure 51 Diagnostics/Service Mode screen, page 4 of 6p.54Figure 52 Diagnostics/Service Mode screen, page 5 of 6p.55Figure 53 Diagnostics/Service Mode screen, page 6 of 6p.55Figure 54 Set Alarms screen, page 1 of 7p.56Figure 55 Set Alarms screen, page 2 of 7p.57Figure 56 Set Alarms screen, page 3 of 7p.58Figure 57 Set Alarms screen, page 4 of 7p.59Figure 58 Set Alarms screens, pages 5 and 6p.60Figure 59 Set Alarms screen, page 7 of 7p.60Figure 60 Sensor Calibration/Setup screen, page 1 of 3p.61Figure 61 Sensor Calibration/Setup screen, page 2 of 3p.62Figure 62 Sensor Calibration/Setup screen, page 3 of 3p.62Figure 63 System/Network Setup screen—System, page 1 of 2p.63Figure 64 System/Network Setup screen—System, page 2 of 2p.64Figure 65 System/Network Setup screen—Unit, page 1 of 2p.65Figure 66 System/Network Setup screen—Unit, page 2 of 2p.66Figure 67 Options Setup screen, page 1 of 2p.67Figure 68 Options Setup screen, page 2 of 2p.68Figure 69 Module Setup screen, page 1 of 20p.68Figure 70 Module Setup screen, page 1 of 20p.695.0 Start the Liebert XDP with Liebert iCOMp.705.1 Checklist for Liebert XDP Startupp.70Table 13 Liebert XDP pump light indicator—208V and 400V unitsp.705.2 Starting the Liebert XDP with Liebert iCOM Controllerp.71Figure 71 System R-134a liquid level at 160kW loadp.716.0 Alarm Descriptions and Solutionsp.726.1 Alarm Descriptionsp.726.2 Warning Descriptionsp.746.3 System Shutdown Causesp.74Unit Is Off By Refrig Sens Failp.74Unit Is Off By High CW Tempp.74Unit Is Off By Pump Short Cyclep.74Unit Is Off By Low Refrig Tempp.747.0 Troubleshootingp.75Table 14 Troubleshooting the Liebert XDPp.758.0 Maintenancep.778.1 Fluorinated Greenhouse Gas Requirementsp.779.0 Specificationsp.78Table 15 Liebert XDP160 specificationsp.78
Page 4 of the Liebert XDP160RC user manual
Page 4 · click to enlarge
Page 4

4.3 Navigating Through the Liebert iCOM Display 28 4.3.1 Accessing Menus and Settings 28 4.3.2 Cooling Module Overview 29 4.3.3 Entering the Password 30

4.4 Changing Liebert iCOM’s Display Settings 31

4.5 Changing Operational Settings 31

4.6 Graphical Data Record 32

4.7 Liebert iCOM User Menu Icons and Legend 32

4.8 Liebert iCOM User Menu Screens 34

4.9 Liebert iCOM Service Menu Icons and Legend 41

4.10 Liebert iCOM Service Menu Screens 42

5.0 START THE LIEBERT XDP WITH LIEBERT ICOM 64

5.1 Checklist for Liebert XDP Startup 64

5.2 Starting the Liebert XDP with Liebert iCOM Controller 65

6.0 ALARM DESCRIPTIONS AND SOLUTIONS 66

6.1 Alarm Descriptions 66

6.2 Warning Descriptions 68

6.3 System Shutdown Causes 68

7.0 TROUBLESHOOTING 69

8.0 MAINTENANCE 71

8.1 Fluorinated Greenhouse Gas Requirements 71

9.0 SPECIFICATIONS 72 COMPLIANCE WITH EUROPEAN UNION DIRECTIVES INSIDE BACK COVER

Page 5 of the Liebert XDP160RC user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

Important Safety Instructionsp.7Figure 1 Model number nomenclaturep.81.0 Product Descriptionp.91.1 General Product Informationp.91.1.1 Product/System Descriptionp.9Figure 2 Liebert XDP componentsp.91.1.2 Minimum Loadp.9Table 1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H) loadp.91.2 Equipment Inspectionp.91.3 Equipment Handlingp.101.3.1 Handling the Liebert XDP While it is on Skid and Packagedp.101.3.2 Unpacking the Liebert XDPp.11Figure 3 Unpacking the Liebert XDPp.111.3.3 Removing the Unit from the Skid Using a Forkliftp.11Figure 4 Use a forklift to remove the Liebert XDP from the skidp.121.3.4 Removing the Unit from the Skid using Riggingp.12Figure 5 Removing the unit from the skid using riggingp.131.3.5 Moving the Liebert XDP Using Piano Jacksp.13Figure 6 Securing the Liebert XDP to piano jacksp.141.3.6 Removing the Unit from the Piano Jacksp.142.0 Installationp.152.1 Mechanical Considerationsp.152.1.1 Positioning the Liebert XDPp.15Figure 7 Dimensionsp.15Table 2 Liebert XDP dimensionsp.15Figure 8 Piping access pointsp.16Table 3 Unit piping outlet connection sizes, inches, OD Cup.162.2 Electrical Considerationsp.162.2.1 Connecting High-Voltage Cablesp.17Figure 9 Front view of Liebert XDP and electrical enclosurep.17Figure 10 Electrical enclosure knockout location for hazardous voltage wiringp.18Figure 11 High voltage connections—60Hzp.18Figure 12 High voltage connections—50Hzp.192.2.2 Extra Low Voltage (ELV) Connectionsp.19Figure 13 Electrical enclosure knockout locations for Extra Low Voltagep.19Figure 14 Connecting the remote temperature/humidity sensorsp.202.2.3 DIP Switch and Jumper Settings for Remote Sensorsp.21Figure 15 DIP switch and jumper settingsp.21Figure 16 Unit-to-unit networking connectionsp.212.3 Field Connections—Optional for All Unitsp.22Figure 17 Liebert XDP extra low voltage field connections pointsp.222.4 Remote Sensor Installation—Proper Placementp.23Figure 18 Suggested remote sensor placementp.233.0 Pipingp.243.1 European Union Fluorinated Greenhouse Gas Requirementsp.243.2 Connection Sizesp.243.2.1 Recommended Pipe Sizep.24Table 4 Supply, return pipe sizes for refrigerant loopp.243.3 Liebert XDP Interconnection with Liebert XD Cooling Modulesp.25Figure 19 Liebert XD system diagramp.253.4 Piping Installation Methodsp.253.4.1 Piping Installation—R-134a Pumped Circuitp.253.4.2 Piping Mainsp.263.4.3 Bypass Flow Controllerp.26Table 5 Bypass flow controllers for a Liebert XDP-based systemp.26Figure 20 Bypass flow controller details, dimensionsp.26Figure 21 Bypass flow controller arrangementp.27Figure 22 Bypass flow controller pipingp.273.5 Piping Details—Shutoff/Isolation Valvesp.27Figure 23 General piping detailsp.283.5.1 Evacuation and Leak Check—R-134a Pumped Circuitp.283.5.2 Insulationp.283.6 Filling the Pumped Circuit—R-134ap.29Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 7 System refrigerant charge for the supply and return mainsp.29Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 9 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDRp.303.6.1 Calculating Refrigerant Charge—Examplep.30Table 10 Calculating refrigerant charge—examplep.30Table 11 Worksheet to calculate refrigerant chargep.303.7 Checklist for Proper Installationp.314.0 Liebert iCOM Control—Firmware Version XP1.00.010.STDp.324.1 Liebert iCOM Components and Functionsp.32Figure 24 Liebert iCOM display componentsp.32Table 12 Keyboard icons and functionsp.334.2 Display Lamp Indicatorsp.334.3 Navigating Through the Liebert iCOM Displayp.34Figure 25 Liebert iCOM default home screenp.344.3.1 Accessing Menus and Settingsp.34Viewing Datap.344.3.2 Cooling Module Overviewp.35Figure 26 Cooling module overview, first 10 modulesp.354.3.3 Entering the Passwordp.36Figure 27 Entering the passwordp.364.4 Changing Liebert iCOM’s Display Settingsp.37Figure 28 Display setup screenp.374.5 Changing Operational Settingsp.374.6 Graphical Data Recordp.384.7 Liebert iCOM User Menu Icons and Legendp.38Figure 29 Liebert iCOM User Menu iconsp.38Figure 30 Liebert XDP User Menu screenp.394.8 Liebert iCOM User Menu Screensp.40Figure 31 Setpoints screenp.40Spare Partsp.40Event Logp.40Figure 32 Set Alarms screenp.41Figure 33 Sensor Data screen, page 1 of 2p.42Figure 34 Sensor Data screen, page 2 of 2p.43Figure 35 Display Setup screenp.44Figure 36 Module Status screen, page 1 of 20p.45Figure 37 Liebert XDV Smart Module Status screenp.45Figure 38 Liebert XDH Smart Module Status screen—each bank shown separatelyp.46Figure 39 Liebert XDO Smart Module Status screenp.46Figure 40 Total Run Hours screenp.474.9 Liebert iCOM Service Menu Icons and Legendp.47Figure 41 Liebert iCOM Service Menu iconsp.47Figure 42 Liebert XDP Service Menu screenp.484.10 Liebert iCOM Service Menu Screensp.48Figure 43 Setpoints screenp.48Figure 44 Maintenance—Basic Settings screen, page 1 of 7p.50Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7p.51Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7p.52Figure 47 Maintenance screens, pages 4 through 7p.52Figure 48 Diagnostics/Service Mode screen, page 1 of 6p.53Figure 49 Diagnostics/Service Mode screen, page 2 of 6p.53Figure 50 Diagnostics/Service Mode screen, page 3 of 6p.54Figure 51 Diagnostics/Service Mode screen, page 4 of 6p.54Figure 52 Diagnostics/Service Mode screen, page 5 of 6p.55Figure 53 Diagnostics/Service Mode screen, page 6 of 6p.55Figure 54 Set Alarms screen, page 1 of 7p.56Figure 55 Set Alarms screen, page 2 of 7p.57Figure 56 Set Alarms screen, page 3 of 7p.58Figure 57 Set Alarms screen, page 4 of 7p.59Figure 58 Set Alarms screens, pages 5 and 6p.60Figure 59 Set Alarms screen, page 7 of 7p.60Figure 60 Sensor Calibration/Setup screen, page 1 of 3p.61Figure 61 Sensor Calibration/Setup screen, page 2 of 3p.62Figure 62 Sensor Calibration/Setup screen, page 3 of 3p.62Figure 63 System/Network Setup screen—System, page 1 of 2p.63Figure 64 System/Network Setup screen—System, page 2 of 2p.64Figure 65 System/Network Setup screen—Unit, page 1 of 2p.65Figure 66 System/Network Setup screen—Unit, page 2 of 2p.66Figure 67 Options Setup screen, page 1 of 2p.67Figure 68 Options Setup screen, page 2 of 2p.68Figure 69 Module Setup screen, page 1 of 20p.68Figure 70 Module Setup screen, page 1 of 20p.695.0 Start the Liebert XDP with Liebert iCOMp.705.1 Checklist for Liebert XDP Startupp.70Table 13 Liebert XDP pump light indicator—208V and 400V unitsp.705.2 Starting the Liebert XDP with Liebert iCOM Controllerp.71Figure 71 System R-134a liquid level at 160kW loadp.716.0 Alarm Descriptions and Solutionsp.726.1 Alarm Descriptionsp.726.2 Warning Descriptionsp.746.3 System Shutdown Causesp.74Unit Is Off By Refrig Sens Failp.74Unit Is Off By High CW Tempp.74Unit Is Off By Pump Short Cyclep.74Unit Is Off By Low Refrig Tempp.747.0 Troubleshootingp.75Table 14 Troubleshooting the Liebert XDPp.758.0 Maintenancep.778.1 Fluorinated Greenhouse Gas Requirementsp.779.0 Specificationsp.78Table 15 Liebert XDP160 specificationsp.78
Page 6 of the Liebert XDP160RC user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

Important Safety Instructionsp.7Figure 1 Model number nomenclaturep.81.0 Product Descriptionp.91.1 General Product Informationp.91.1.1 Product/System Descriptionp.9Figure 2 Liebert XDP componentsp.91.1.2 Minimum Loadp.9Table 1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H) loadp.91.2 Equipment Inspectionp.91.3 Equipment Handlingp.101.3.1 Handling the Liebert XDP While it is on Skid and Packagedp.101.3.2 Unpacking the Liebert XDPp.11Figure 3 Unpacking the Liebert XDPp.111.3.3 Removing the Unit from the Skid Using a Forkliftp.11Figure 4 Use a forklift to remove the Liebert XDP from the skidp.121.3.4 Removing the Unit from the Skid using Riggingp.12Figure 5 Removing the unit from the skid using riggingp.131.3.5 Moving the Liebert XDP Using Piano Jacksp.13Figure 6 Securing the Liebert XDP to piano jacksp.141.3.6 Removing the Unit from the Piano Jacksp.142.0 Installationp.152.1 Mechanical Considerationsp.152.1.1 Positioning the Liebert XDPp.15Figure 7 Dimensionsp.15Table 2 Liebert XDP dimensionsp.15Figure 8 Piping access pointsp.16Table 3 Unit piping outlet connection sizes, inches, OD Cup.162.2 Electrical Considerationsp.162.2.1 Connecting High-Voltage Cablesp.17Figure 9 Front view of Liebert XDP and electrical enclosurep.17Figure 10 Electrical enclosure knockout location for hazardous voltage wiringp.18Figure 11 High voltage connections—60Hzp.18Figure 12 High voltage connections—50Hzp.192.2.2 Extra Low Voltage (ELV) Connectionsp.19Figure 13 Electrical enclosure knockout locations for Extra Low Voltagep.19Figure 14 Connecting the remote temperature/humidity sensorsp.202.2.3 DIP Switch and Jumper Settings for Remote Sensorsp.21Figure 15 DIP switch and jumper settingsp.21Figure 16 Unit-to-unit networking connectionsp.212.3 Field Connections—Optional for All Unitsp.22Figure 17 Liebert XDP extra low voltage field connections pointsp.222.4 Remote Sensor Installation—Proper Placementp.23Figure 18 Suggested remote sensor placementp.233.0 Pipingp.243.1 European Union Fluorinated Greenhouse Gas Requirementsp.243.2 Connection Sizesp.243.2.1 Recommended Pipe Sizep.24Table 4 Supply, return pipe sizes for refrigerant loopp.243.3 Liebert XDP Interconnection with Liebert XD Cooling Modulesp.25Figure 19 Liebert XD system diagramp.253.4 Piping Installation Methodsp.253.4.1 Piping Installation—R-134a Pumped Circuitp.253.4.2 Piping Mainsp.263.4.3 Bypass Flow Controllerp.26Table 5 Bypass flow controllers for a Liebert XDP-based systemp.26Figure 20 Bypass flow controller details, dimensionsp.26Figure 21 Bypass flow controller arrangementp.27Figure 22 Bypass flow controller pipingp.273.5 Piping Details—Shutoff/Isolation Valvesp.27Figure 23 General piping detailsp.283.5.1 Evacuation and Leak Check—R-134a Pumped Circuitp.283.5.2 Insulationp.283.6 Filling the Pumped Circuit—R-134ap.29Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 7 System refrigerant charge for the supply and return mainsp.29Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDRp.29Table 9 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDRp.303.6.1 Calculating Refrigerant Charge—Examplep.30Table 10 Calculating refrigerant charge—examplep.30Table 11 Worksheet to calculate refrigerant chargep.303.7 Checklist for Proper Installationp.314.0 Liebert iCOM Control—Firmware Version XP1.00.010.STDp.324.1 Liebert iCOM Components and Functionsp.32Figure 24 Liebert iCOM display componentsp.32Table 12 Keyboard icons and functionsp.334.2 Display Lamp Indicatorsp.334.3 Navigating Through the Liebert iCOM Displayp.34Figure 25 Liebert iCOM default home screenp.344.3.1 Accessing Menus and Settingsp.34Viewing Datap.344.3.2 Cooling Module Overviewp.35Figure 26 Cooling module overview, first 10 modulesp.354.3.3 Entering the Passwordp.36Figure 27 Entering the passwordp.364.4 Changing Liebert iCOM’s Display Settingsp.37Figure 28 Display setup screenp.374.5 Changing Operational Settingsp.374.6 Graphical Data Recordp.384.7 Liebert iCOM User Menu Icons and Legendp.38Figure 29 Liebert iCOM User Menu iconsp.38Figure 30 Liebert XDP User Menu screenp.394.8 Liebert iCOM User Menu Screensp.40Figure 31 Setpoints screenp.40Spare Partsp.40Event Logp.40Figure 32 Set Alarms screenp.41Figure 33 Sensor Data screen, page 1 of 2p.42Figure 34 Sensor Data screen, page 2 of 2p.43Figure 35 Display Setup screenp.44Figure 36 Module Status screen, page 1 of 20p.45Figure 37 Liebert XDV Smart Module Status screenp.45Figure 38 Liebert XDH Smart Module Status screen—each bank shown separatelyp.46Figure 39 Liebert XDO Smart Module Status screenp.46Figure 40 Total Run Hours screenp.474.9 Liebert iCOM Service Menu Icons and Legendp.47Figure 41 Liebert iCOM Service Menu iconsp.47Figure 42 Liebert XDP Service Menu screenp.484.10 Liebert iCOM Service Menu Screensp.48Figure 43 Setpoints screenp.48Figure 44 Maintenance—Basic Settings screen, page 1 of 7p.50Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7p.51Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7p.52Figure 47 Maintenance screens, pages 4 through 7p.52Figure 48 Diagnostics/Service Mode screen, page 1 of 6p.53Figure 49 Diagnostics/Service Mode screen, page 2 of 6p.53Figure 50 Diagnostics/Service Mode screen, page 3 of 6p.54Figure 51 Diagnostics/Service Mode screen, page 4 of 6p.54Figure 52 Diagnostics/Service Mode screen, page 5 of 6p.55Figure 53 Diagnostics/Service Mode screen, page 6 of 6p.55Figure 54 Set Alarms screen, page 1 of 7p.56Figure 55 Set Alarms screen, page 2 of 7p.57Figure 56 Set Alarms screen, page 3 of 7p.58Figure 57 Set Alarms screen, page 4 of 7p.59Figure 58 Set Alarms screens, pages 5 and 6p.60Figure 59 Set Alarms screen, page 7 of 7p.60Figure 60 Sensor Calibration/Setup screen, page 1 of 3p.61Figure 61 Sensor Calibration/Setup screen, page 2 of 3p.62Figure 62 Sensor Calibration/Setup screen, page 3 of 3p.62Figure 63 System/Network Setup screen—System, page 1 of 2p.63Figure 64 System/Network Setup screen—System, page 2 of 2p.64Figure 65 System/Network Setup screen—Unit, page 1 of 2p.65Figure 66 System/Network Setup screen—Unit, page 2 of 2p.66Figure 67 Options Setup screen, page 1 of 2p.67Figure 68 Options Setup screen, page 2 of 2p.68Figure 69 Module Setup screen, page 1 of 20p.68Figure 70 Module Setup screen, page 1 of 20p.695.0 Start the Liebert XDP with Liebert iCOMp.705.1 Checklist for Liebert XDP Startupp.70Table 13 Liebert XDP pump light indicator—208V and 400V unitsp.705.2 Starting the Liebert XDP with Liebert iCOM Controllerp.71Figure 71 System R-134a liquid level at 160kW loadp.716.0 Alarm Descriptions and Solutionsp.726.1 Alarm Descriptionsp.726.2 Warning Descriptionsp.746.3 System Shutdown Causesp.74Unit Is Off By Refrig Sens Failp.74Unit Is Off By High CW Tempp.74Unit Is Off By Pump Short Cyclep.74Unit Is Off By Low Refrig Tempp.747.0 Troubleshootingp.75Table 14 Troubleshooting the Liebert XDPp.758.0 Maintenancep.778.1 Fluorinated Greenhouse Gas Requirementsp.779.0 Specificationsp.78Table 15 Liebert XDP160 specificationsp.78
Page 7 of the Liebert XDP160RC user manual — NOTICE
Page 7 · click to enlarge
Page 7

I MPORTANT S AFETY I NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert XDP. Read this manual thoroughly before attempting to install or operate this unit. Only qualified personnel should move, install or service this equipment. Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions. Follow all local codes.

! WARNING Risk of arc flash and electric shock. Can cause property damage, injury or death. Disconnect all local and remote electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM control. The line side of the disconnect switch on the front of the unit contains live high-voltage. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local codes. ! WARNING Risk of unit falling over. Can cause property damage, injury or death. The XDP is top-heavy. Use extreme caution and care when moving and installing this unit. ! CAUTION Risk of piping and component rupture. Can cause injury or equipment damage. System is pressurized. Relieve pressure through access valve before working on unit.Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves. System is pressurized. Relieve pressure through access valve before working on unit

NOTICE

Risk of leaking chilled water lines. Can cause equipment and building damage. Lines and joints must be inspected regularly. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Emerson Network Power recommends installing monitored leak detection equipment for the unit and supply and return lines.

Page 8 of the Liebert XDP160RC user manual — Example: XDP160RA– –4
Page 8 · click to enlarge
Page 8

Figure 1 Model number nomenclature

Example: XDP160RA– –4

XD P 160 – *

R

A

Liebert X-treme heat Density system

A = 460V-3ph-60Hz (voltage-phase-frequency)

C = 208V-3ph-60Hz M = 380/415-3ph-50Hz

Show 8 more labels / short text on this page
Pumping · Pump Redundancy · Place holder · Revision · unit · level · 160kW nominal capacity · Place holder
Page 9 of the Liebert XDP160RC user manual — 1.2 Equipment Inspection
Page 9 · click to enlarge
Page 9

1.0 P RODUCT D ESCRIPTION

1.1 General Product Information

1.1.1 Product/System Description Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP is rated for 160kW (546,000BTU/H) of cooling. The Liebert XDP consists of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls, valves and piping. The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the refrigerant being pumped to the cooling modules at a temperature above the room’s dew point. All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are automatic.

Figure 2 Liebert XDP components

Liebert XDP Unit

Control Valve Liebert XD Cooling Modules

Chilled Water

Heat Exchanger

Receiver Pumps

1.1.2 Minimum Load

The Liebert XDP's minimum recommended operating load is 30% of system nominal capacity. The Liebert XDP160 is rated for 160kW (546,000BTU/H) of cooling, therefore the system's minimum recommended load is 48kW (163,800BTU/H). Loading below this value can unfavorably affect system operation. Consult the factory for any loading below this recommendation.

To achieve the minimum recommended load, the capacity of all connected modules must total at least 48kW (163,800BTU/H). See Table 1.

Table 1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H) load

Liebert XD Module Type XDCF10XDV8XDV10XDO16XDO20XDH20XDH32XDR20 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800BTU/H) load56533323

1.2 Equipment Inspection

When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Emerson and to your sales representative.

Product Description

Page 10 of the Liebert XDP160RC user manual — NOTICE
Page 10 · click to enlarge
Page 10

1.3 Equipment Handling

! WARNING Risk of unit falling over. Can cause injury or death. The Liebert XDP is top-heavy. Use extreme caution and care when moving and installing this unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified rating organization. See Table 15 for unit weights. Unit weights are specified in section 9.0 Personnel should be properly trained and certified to move and rig equipment

! CAUTION Risk of sharp edges, splinters and exposed fasteners. Can cause injury.

Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.

1.3.1 Handling the Liebert XDP While it is on Skid and Packaged

  • Always keep the unit upright, indoors and protected from damage.
  • If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In either case, do NOT press on the top edges of the packaging.
  • If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
  • When moving the skidded unit with a forklift truck, do not lift the unit any higher than 6" (152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift point of the unit.

NOTICE

Risk of structural interference. Can cause equipment or building damage. While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard doorway. Any attempt to move the unit, while skidded, through a standard doorway will cause damage to the unit and to the building. NOTICE

Risk of damage from forklift. Can cause unit damage.

Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage. NOTICE

Risk of improper storage. Can cause unit damage.

Keep the Liebert XDP upright, indoors and protected from dampness, freezing temperatures and contact damage. NOTICE

Risk of overtightening securing straps. Can cause damage to panels. Place a protective material between the straps of the piano jacks and the unit. Ensure that the straps are not tightened to a point of damaging panels.

Product Description

Page 11 of the Liebert XDP160RC user manual — 1.3.2 Unpacking the Liebert XDP
Page 11 · click to enlarge
Page 11

1.3.2 Unpacking the Liebert XDP 1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and side packaging planks. 2. Remove and set aside filter dryer kit. 3. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The bag may remain in place for dust and panel protection or removed for immediate unit installation. 4. Remove the bag from the unit when ready to remove the skid for installation.

Figure 3 Unpacking the Liebert XDP

Liebert XDP160RC — 1.3.2 Unpacking the Liebert XDP diagram (page 11)
Fig. 2 · 1.3.2 Unpacking the Liebert XDP
Liebert XDP160RC — 1.3.2 Unpacking the Liebert XDP diagram (page 11)
Fig. 3 · 1.3.2 Unpacking the Liebert XDP
Liebert XDP160RC — 1.3.2 Unpacking the Liebert XDP diagram (page 11)
Fig. 4 · 1.3.2 Unpacking the Liebert XDP

Remove Stretch Wrap Remove Filter Dryer Kit Remove Packaging Planks

1.3.3 Removing the Unit from the Skid Using a Forklift 1. Align the forklift with either the front or rear side of the unit. Make sure the tines of the forklift are locked to the widest position. Use the center of gravity indicators to determine the entry points for the tines. The tines must be equally spaced on either side of the center of gravity indicator. 2. Insert the tines of the forklift under the unit. Make sure the tines are level. The tines must be low enough to fit under the unit without damaging it. Make sure the tines extend beyond the opposite side of the unit. 3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.

4. Lift the unit to a height that it is not being support by the skid. 5. Move the skid from under the unit.
Show 5 more labels / short text on this page
Product Description · Stretch · Wrap · Filter Dryer · Kit
Page 12 of the Liebert XDP160RC user manual — Figure 4 Use a forklift to remove the Liebert XDP from the skid
Page 12 · click to enlarge
Page 12

Figure 4 Use a forklift to remove the Liebert XDP from the skid

Liebert XDP160RC — Figure 4 Use a forklift to remove the Liebert XDP from the skid diagram (page 12)
Fig. 5 · Figure 4 Use a forklift to remove the Liebert XDP fr…
Liebert XDP160RC — Figure 4 Use a forklift to remove the Liebert XDP from the skid diagram (page 12)
Fig. 6 · Figure 4 Use a forklift to remove the Liebert XDP fr…

The forklift tines must be equally spaced on either side of the center of gravity indicator.

Move the forklift forward until the tines are fully under the unit.

Fit the forklift tines under the Liebert XDP.

1.3.4 Removing the Unit from the Skid using Rigging 1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally spaced on either side of the center of gravity indicator. Refer to Figure 5. 2. Place slings under the unit using spaces provided between the skid deck boards.

3. Use spreader bars or an equivalent method to ensure proper protection of the unit. 4. Ensure that the panels, if attached, are well protected from the slings.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the unit. 7. Remove the skid from under the unit.

Product Description

Page 13 of the Liebert XDP160RC user manual — Figure 5 Removing the unit from the skid using rigging
Page 13 · click to enlarge
Page 13

Figure 5 Removing the unit from the skid using rigging

Cushioning material not shown for clarity.

Liebert XDP160RC — Figure 5 Removing the unit from the skid using rigging diagram (page 13)
Fig. 7 · Figure 5 Removing the unit from the skid using riggi…
Liebert XDP160RC — Figure 5 Removing the unit from the skid using rigging diagram (page 13)
Fig. 8 · Figure 5 Removing the unit from the skid using riggi…

Center of Gravity Symbols

If rigging will be used to transport the Liebert XDP, place one or two horizontal straps around the unit and the vertical staps about this height.

1.3.5 Moving the Liebert XDP Using Piano Jacks 1. Elevate the Liebert XDP with a lifting mechanism, such as a forklift or rigging. 2. Position one piano jack at each end of the Liebert XDP. 3. Lower the unit to a height suitable for placing it on the piano jacks. 4. Put protective material between the Liebert XDP and the piano jacks and straps. 5. Secure the Liebert XDP to the piano jacks. 6. Release the the Liebert XDP from the straps securing it to the lifting mechanism and move the mechanism away from the unit.

Using the piano jacks, at least two properly trained and qualified personnel can move the unit.

Show 4 more labels / short text on this page
Product Description · Spreader · Bars · Bracket
Page 14 of the Liebert XDP160RC user manual — Figure 6 Securing the Liebert XDP to piano jacks
Page 14 · click to enlarge
Page 14

Figure 6 Securing the Liebert XDP to piano jacks

Liebert XDP160RC — Figure 6 Securing the Liebert XDP to piano jacks diagram (page 14)
Fig. 9 · Figure 6 Securing the Liebert XDP to piano jacks
Liebert XDP160RC — Figure 6 Securing the Liebert XDP to piano jacks diagram (page 14)
Fig. 10 · Figure 6 Securing the Liebert XDP to piano jacks
Liebert XDP160RC — Figure 6 Securing the Liebert XDP to piano jacks diagram (page 14)
Fig. 11 · Figure 6 Securing the Liebert XDP to piano jacks

Using a forklift to put a Liebert XDP on piano jacks

Using rigging to put a Liebert XDP on piano jacks

1.3.6 Removing the Unit from the Piano Jacks 1. Lower the Liebert XDP as far as the piano jacks will allow. 2. Undo all strapping holding the piano jacks to the unit. 3. Lift one end of the Liebert XDP off one piano jack with a pry bar or similar device, taking care not to damage the unit’s cabinet. 4. Repeat Step 3 to remove the piano jack from under the opposite end of the Liebert XDP. 5. Remove all material used to protect the unit from the piano jacks and strapping.

Product Description · Liebert XDP Secured · to piano jacks

Page 15 of the Liebert XDP160RC user manual — 2.1 Mechanical Considerations
Page 15 · click to enlarge
Page 15

2.0 I NSTALLATION

2.1 Mechanical Considerations

2.1.1 Positioning the Liebert XDP Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.

The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.

For additional technical information, refer to the System Design and Configuration Document for the Liebert XD™ System, SL-16655. The document is available in electronic format at Liebert’s Web site, www.liebert.com, as well as from your local Emerson representative.

Liebert XDP160RC — 2.1 Mechanical Considerations diagram (page 15)
Fig. 12 · 2.1 Mechanical Considerations

The shaded area indicates a recommended clearance of 36" (914mm) for component access.

Table 2 Liebert XDP dimensions

Dimensional Data, inches (mm) Shipping Weight, lb. (kg)

A B* C D E H Domestic Export

XDP160 38 (965) 34 (864) 33-1/8 (841) 33 (838) 36 (914) 78 (1981) 1020(462) 1083 (491)

* The dimension does not include the bezel of the disconnect switch.

Installation · Figure 7 Dimensions · Model 50/60Hz

Page 16 of the Liebert XDP160RC user manual — XDP160 2-1/8 1-1/8 2-5/8 2-5/8
Page 16 · click to enlarge
Page 16

Figure 8 Piping access points

Liebert XDP160RC — Figure 8 Piping access points diagram (page 16)
Fig. 13 · Figure 8 Piping access points

To first cooling module or bypass flow controller **

Install replaceable filter dryer assembly in liquid supply line B.

Emerson recommends field-installation of shutoff valves at these points to permit isolating the Liebert XDP for maintenance

Dimensions are approximate and subject to change without notice.

* Allow 8" (204mm) clearance for filter replacement. ** To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly between the discharge line of the Liebert XDP and the first bypass flow controller or the first Liebert XD cooling module.

D - Chilled Water Return To Chilled Water Source

C - Chilled Water Supply From Chilled Water Source

Table 3 Unit piping outlet connection sizes, inches, OD Cu

Model Pipe Connection Point

50/60 Hz A B C D

XDP160 2-1/8 1-1/8 2-5/8 2-5/8

2.2 Electrical Considerations

Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated on the Liebert XDP’s rating plate. The unit must be installed in accordance with national wiring regulations.

Connect cables for high voltage supply to the electrical box in the Liebert XDP according to Figure 11 and make sure that the phases are correctly connected.

! WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within the unit.

Installation

Page 17 of the Liebert XDP160RC user manual — 2.2.1 Connecting High-Voltage Cables
Page 17 · click to enlarge
Page 17

! WARNING Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment damage, injury or death.

Damage to wiring or components can make unit unsafe to operate.

Use caution when installing wiring to prevent damage to factory wiring.

Install protective bushings in wiring knockouts as required to protect wiring from sharp edges.

Do not disturb factory wiring or route field-installed wiring over electrical terminals.

Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.

Check and retighten all wiring connections before starting the unit.

2.2.1 Connecting High-Voltage Cables 1. Turn the Liebert XDP’s disconnect switch to the Off position (see Figure 9). Open the front doors and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.

Figure 9 Front view of Liebert XDP and electrical enclosure

Liebert XDP160RC — 2.2.1 Connecting High-Voltage Cables diagram (page 17)
Fig. 14 · 2.2.1 Connecting High-Voltage Cables
2. Determine which knockouts in the electrical enclosure will be used and remove them (see Figure 10 ).

Installation

Page 18 of the Liebert XDP160RC user manual — Figure 10 Electrical enclosure knockout location for hazardous voltage wiring
Page 18 · click to enlarge
Page 18

Figure 10 Electrical enclosure knockout location for hazardous voltage wiring

Liebert XDP160RC — Figure 10 Electrical enclosure knockout location for hazardous voltage wiring diagram (page 18)
Fig. 15 · Figure 10 Electrical enclosure knockout location for…
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see Figure 10 ) to the disconnect switch L1, L2 and L3 (see Figures 11 and 12 ). Observe proper phasing. 4. Connect the ground wire to the ground lug (see Figures 11 and 12 ), which is in the middle left of the enclosure.

Figure 11 High voltage connections—60Hz

Liebert XDP160RC — Figure 10 Electrical enclosure knockout location for hazardous voltage wiring diagram (page 18)
Fig. 16 · Figure 10 Electrical enclosure knockout location for…

Installation

Page 19 of the Liebert XDP160RC user manual — Figure 12 High voltage connections—50Hz
Page 19 · click to enlarge
Page 19

Figure 12 High voltage connections—50Hz

Liebert XDP160RC — Figure 12 High voltage connections—50Hz diagram (page 19)
Fig. 17 · Figure 12 High voltage connections—50Hz

2.2.2 Extra Low Voltage (ELV) Connections Extra Low Voltage power output is 30V and 100VA or less. 1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this equipment (refer to Figure 13). 2. Route low voltage electrical connections through the appropriate knockouts as indicated below.

Figure 13 Electrical enclosure knockout locations for Extra Low Voltage

Liebert XDP160RC — Figure 12 High voltage connections—50Hz diagram (page 19)
Fig. 18 · Figure 12 High voltage connections—50Hz

Liebert XD Module Condensate Connections (optional; depends on features supplied with Liebert XD Module)

Installation

Page 20 of the Liebert XDP160RC user manual — P32
Page 20 · click to enlarge
Page 20

Figure 14 Connecting the remote temperature/humidity sensors

P66 P67

P66 P67

Liebert XD Cooling Module

Liebert XD Cooling Module

CAN Ground Coupler CAN Ground Coupler

P2 P4

P3 P1

See Note 5 See Note 5

P66 P64 P67

P66 P67 P66 P67

Remote T/H Sensor B Remote T/H Sensor A

Unit Display (Rear View)

Red Crossover Ethernet Cable

Crossover Coupler See Note 6

P41

P11 P12

P13 P7

E5

P43

E4

P24

OFF ON

E3

P66 P67

3 P78

2 1 4 3 6 5 SW 2

E2

E1

P64

P63

P68

P51 TB1

E1

P61

P45

P65

P4

P4

P18

P54

Liebert iCOM Microprocessor and I/O Board

P22 P38 P39 P53 P52

P1

P2

P65

See Table for Plug Assignments

P40

P3

P8

P34

P35

Liebert IntelliSlot Power Supply

P32

P33

P36

1. See unit electrical schematic, installation and user manuals. 2. Cables “A” and “B” provided with each unit. Only one is used as follows: Liebert IntelliSlot-based communications - Cable “A” is preconnected to P65 on microprocessor and input/output board and P65 on Liebert IntelliSlot power supply non-Liebert IntelliSlot-based communications - Vable “B” is pre-connected to Terminals 77 and 78 but must be exchanged with Cable “A” at P65 on the microprocessor and input/output board. 3. Install applicable Liebert IntelliSlot cards. 4. Both cables (P64 and P66) are required. 5. It is not necessary to connect ground coupling on end of cable connected to Sensor “A” or Sensor “B.”

6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug the red cable from P64 on the microprocessor and input/output board and connect to one side of the crossover coupler. The first customer connection point is to P64 on the microprocessor and input/output board. The second customer connection point is to the other side of the crossover coupler. This connects the microprocessor and input/output board and display to the private U2U network. 7. The remote sensors are interchangeable as to which connects to the Liebert XD cooling module and which connects to P2 on CAN Iso. 8. Field-install cables with factory-installed ferrite beads (when provided, typical two places). Each cable must make three passes through the ferrite bead. Locate the ferrite bead on top of the electric box. See instruction sheet provided with the cable assembly. 9. Factory-installed ferrite bead (when provided). Cable passes through ferrite bead three times

302211 Rev. 2

Show 24 more labels / short text on this page
Installation · See Note 8 · CAN Cable · CAN Iso Adapter · See Note 4 · See Note 8 · Termination Plug · See Note 4 · See Note 9 · See Note 7 · T6 Isolation Transformer · T1 Unit Control · 24VAC Nominal · Transformer · See Note 3 · Liebert IntelliSlot 1 · Liebert IntelliSlot 2 · Control · Fuse Board · Not Used · Ribbon Cables · Cable A · See Note 2 · Cable B
Page 21 of the Liebert XDP160RC user manual — 2.2.3 DIP Switch and Jumper Settings for Remote Sensors
Page 21 · click to enlarge
Page 21

2.2.3 DIP Switch and Jumper Settings for Remote Sensors The Liebert XDP is shipped with jumpers and DIP switch settings for normal operation. See Figure 15. Figure 15 DIP switch and jumper settings

Liebert XDP160RC — 2.2.3 DIP Switch and Jumper Settings for Remote Sensors diagram (page 21)
Fig. 19 · 2.2.3 DIP Switch and Jumper Settings for Remote Sens…

OFF ON 1 2 3 4 5 6 7 8 9 10

2 5 6 7 8 Jumpers on 1-2, 5-6

SW3 1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

3 2 1 Jumper on 2-3 302211 Rev. 2

Figure 16 Unit-to-unit networking connections

Liebert XDP160RC — 2.2.3 DIP Switch and Jumper Settings for Remote Sensors diagram (page 21)
Fig. 20 · 2.2.3 DIP Switch and Jumper Settings for Remote Sens…
1. Both cables (P64 and P66) are required. 2. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug the red cable from P64 on the microprocessor and I/O board and connect to one side of the crossover coupler. The first customer connection point is to P64 on the microprocessor and I/O board.

The second customer connection point is to the other side of the crossover coupler. This connects the microprocessor and I/O board and display to the private U2U network.

Installation

Page 22 of the Liebert XDP160RC user manual — 2.3 Field Connections—Optional for All Units
Page 22 · click to enlarge
Page 22

2.3 Field Connections—Optional for All Units

  • Connect field wiring from the optional Liebert XD cooling module condensation detection circuit to terminal strip locations COMM. (24) and H2O (51).
  • Connect optional field wiring from remote devices to remote alarm device, common alarm outputs, site monitor and remote shutdown, if applicable. See terminal strip descriptions in Figure 17 .

Figure 17 Liebert XDP extra low voltage field connections points

Liebert XDP160RC — 2.3 Field Connections—Optional for All Units diagram (page 22)
Fig. 21 · 2.3 Field Connections—Optional for All Units

To P66 on Liebert iCOM Control Board To P64 on Liebert iCOM Control Board Red Ethernet Cable

To Liebert XD Cooling Module(s) and Remote T/H Sensor B

Control wiring must be Class 2 and installed in accordance with the National Electrical Code (NEC).

Installation

Page 23 of the Liebert XDP160RC user manual — 2.4 Remote Sensor Installation—Proper Placement
Page 23 · click to enlarge
Page 23

2.4 Remote Sensor Installation—Proper Placement

Placement of the two remote temperature/humidity sensors is critical to effective cooling of the conditioned space.

The remote sensors must be installed in areas where conditions are representative of the space conditioned by the Liebert XDP. Emerson recommends installing the sensors in different areas near the cooling modules served by the Liebert XDP. If the return air side of the primary air mover, such as a Liebert DS, represents the conditions where the Liebert XD cooling modules are located, one sensor could be placed there. Emerson suggests placing the other sensor on the wall opposite the heat load area (see Figure 18 for guidance).

Do not install the sensors where ambient air might cause false readings, for example, near unsealed doors or windows, or areas with stagnant air.

1. Unpack the two remote temperature/humidity sensors and cables. One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable; each bears labels indicating Sensor End and Unit End. 2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure 14). 3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM input/output board inside the Liebert XDP. Secure the ring terminal on the cable shield to the electric box adjacent to P67 (see Figure 14). 4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 14). 5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 14). Secure the ring terminal on the cable shield to the grounding screw adjacent to P67.

Figure 18 Suggested remote sensor placement

Liebert XDP160RC — 2.4 Remote Sensor Installation—Proper Placement diagram (page 23)
Fig. 22 · 2.4 Remote Sensor Installation—Proper Placement

Installation

Page 24 of the Liebert XDP160RC user manual — 3.2 Connection Sizes
Page 24 · click to enlarge
Page 24

3.0 P IPING

3.1 European Union Fluorinated Greenhouse Gas Requirements

Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f- gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F- gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.

The F-Gas Regulation requires operators to use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas before disposing of equipment, as well as during service and maintenance.

Refer to the full regulation for additional details.

3.2 Connection Sizes

The copper pipe connections on the Liebert XDP are:

Building Chilled Water Supply 2-5/8" OD

Building Chilled Water Return 2-5/8" OD

Refrigerant Supply 1-1/8" OD

Refrigerant Return 2-1/8" OD

3.2.1 Recommended Pipe Size Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to site specific documentation and the configuration guide for the Liebert XD system. Elbows and restrictions must be minimized to get good fluid flow.

Table 4 Supply, return pipe sizes for refrigerant loop

Pipe Function Size / Equivalent Pipe Length

Liebert XDP supply line, from Liebert XDP supply to farthest Liebert XD cooling module

1-1/8" OD for lengths up to 60 feet

1-3/8" OD for lengths over 60 but less than 175 feet

Liebert XDP return line, from farthest Liebert XD cooling module to Liebert XDP return

2-1/8" OD for lengths up to 60 feet

2-5/8" OD for lengths over 60 but less than 175 feet

1/2" OD for lengths up to 10 feet

From any model Liebert XDO/Liebert XDH supply to supply line of Liebert XDP

7/8" OD for lengths over 10 but less than 25 feet

From any model Liebert XDO/Liebert XDH return to return line of Liebert XDP

7/8" OD for lengths up to 10 feet

1-1/8" OD for lengths over 10 but less than 25 feet

From any model Liebert XDV/Liebert XDCF supply to supply line of Liebert XDP

1/2" OD for lengths up to 10 feet

5/8" OD for lengths over 10 but less than 35 feet

5/8" OD for lengths up to 10 feet

From any model Liebert XDV/Liebert XDCF return to return line of Liebert XDP

7/8" OD for lengths over 10 but less than 35 feet

Piping

Page 25 of the Liebert XDP160RC user manual — 3.4.1 Piping Installation—R-134a Pumped Circuit
Page 25 · click to enlarge
Page 25

3.3 Liebert XDP Interconnection with Liebert XD Cooling Modules

All piping must be ASTM (American Society for Testing and Materials) Type ACR copper pipe. The Liebert XDP may be connected to Liebert XD cooling modules with either Liebert’s XD prefabricated piping assembly or with rigid, off-the-shelf piping. In either setup, piping for the Liebert XD system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling modules are connected in parallel between main return and supply pipes going to and from the Liebert XDP/Liebert XDC. Figure 19 represents a typical configuration. For piping details, refer to Liebert’s XD System Design Manual, SL-16655, available at Liebert’s Web site: www.liebert.com. The guidelines provided for pipe size must be strictly followed. Failure to size the main lines and connection lines adequately may result in reduced cooling capacity. The critical aspects of pipe sizing are related to refrigerant volume and pressure drop. Each must be minimized.

Figure 19 Liebert XD system diagram

Liebert XDP160RC — 3.3 Liebert XDP Interconnection with Liebert XD Cooling Modules diagram (page 25)
Fig. 23 · 3.3 Liebert XDP Interconnection with Liebert XD Cool…

All supply and return mains must be level with or above the top of all Liebert XD modules

SLOPE—The main supply and return lines to and from the Liebert XDP must be sloped downward toward the Liebert XDP at a rate of 1-2" per 20 feet (25.4-51mm per 6m) of pipe run.

3.4 Piping Installation Methods

The assembly and connection means used for piping in the Liebert XD system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft soldering is not recommended.

During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.

Insulate all piping lines to prevent condensation in applications where the dew point approaches the R-134a refrigerant temperature.

Emerson recommends venting the pressure relief valve for the R-134a outside the conditioned space where it is open to the atmosphere. The R-134a side relief valve is inside the Liebert XDP unit at the top of the receiver.

3.4.1 Piping Installation—R-134a Pumped Circuit

Emerson recommends venting the relief pressure valve of the Liebert XDP (located at the top of the receiver) outside of the conditioned space where it is open to the atmosphere.

Piping

Page 26 of the Liebert XDP160RC user manual — 3.4.3 Bypass Flow Controller
Page 26 · click to enlarge
Page 26

3.4.2 Piping Mains

All refrigeration piping mains connected to the Liebert XD cooling module, both supply and return, should be installed with a downward pitch toward the Liebert XDP of 1-2" for every 20 feet (25.4-51mm per 6m) of pipe run.

Install a 20-40 mesh strainer on the chilled water supply to the Liebert XDP. The strainer is required to prevent particles in the chilled water from entering the Liebert XDP’s heat exchanger. The maximum distance from the strainer to the Liebert XDP is 10 feet (3m).

NOTICE

Risk of particles in chilled water. Can cause equipment damage and reduced cooling. Failure to install a strainer in the supply line to the Liebert XDP can result in damage to the unit’s heat exchanger.

3.4.3 Bypass Flow Controller

Three bypass flow controllers are required to ensure that the Liebert XDP pumps operate within the optimum range. These devices are added to the field piping and simulate the flow of additional cooling modules.

Each bypass flow controller must be installed with one shutoff valve to allow the controller to be disabled when cooling modules are added to a Liebert XD system.

Bypass flow controllers should be connected between the main supply and the main return lines of the field piping. The connection points to the main supply and return lines should be in a convenient and accessible location between the Liebert XDP/Liebert XDC and the first Liebert XD module in the circuit. See Figures 20 and 21 for piping details of the bypass flow controller.

Refer to Table 5 to determine the number of bypass flow controllers that must be open to provide proper refrigerant flow based on the total nominal cooling capacity of the cooling modules in each Liebert XD system.

Table 5 Bypass flow controllers for a Liebert XDP-based system

Liebert XDP160RC — 3.4.3 Bypass Flow Controller diagram (page 26)
Fig. 24 · 3.4.3 Bypass Flow Controller

Figure 20 Bypass flow controller details, dimensions

Liebert XDP160RC — 3.4.3 Bypass Flow Controller diagram (page 26)
Fig. 25 · 3.4.3 Bypass Flow Controller

Piping

Page 27 of the Liebert XDP160RC user manual — 3.5 Piping Details—Shutoff/Isolation Valves
Page 27 · click to enlarge
Page 27

Figure 21 Bypass flow controller arrangement

Liebert XDP160RC — Figure 21 Bypass flow controller arrangement diagram (page 27)
Fig. 26 · Figure 21 Bypass flow controller arrangement

Main 7/8" Refrigerant Grade Full Port Ball Valve Field-Supplied and Field-Installed

Figure 22 Bypass flow controller piping

Liebert XDP160RC — Figure 21 Bypass flow controller arrangement diagram (page 27)
Fig. 27 · Figure 21 Bypass flow controller arrangement

3.5 Piping Details—Shutoff/Isolation Valves

Isolation valves must be installed on the Liebert XDP’s refrigerant circuit to permit maintenance on the unit (see Figure 23).

Piping

Page 28 of the Liebert XDP160RC user manual — 3.5.2 Insulation
Page 28 · click to enlarge
Page 28

Figure 23 General piping details

Liebert XDP160RC — Figure 23 General piping details diagram (page 28)
Fig. 28 · Figure 23 General piping details

Emerson recommends field-installation of shutoff valves at these points to permit isolating the Liebert XDP for maintenance.

3.5.1 Evacuation and Leak Check—R-134a Pumped Circuit 1. Open all service valves, including those outside the Liebert XDP. 2. Attach a jumper hose from one of the Schrader valve fittings on a pump outlet before the check valve to a Schrader valve fittings after the check valve. 3. Place 150psig (1034kPa; 10.34 bars) of dry nitrogen with a tracer of R-134a in the system.

NOTICE

Risk of overpressurization. Can cause equipment damage. Do not exceed 150 psig (1034 kPa; 10.34 bars) in the R-134a circuit.

4. Check the system for leaks with a suitable leak finder on the pumps’ suctions lines. 5. After completion of the leak testing, release the test pressure (per local code) and connect to vacuum pump(s) at the Schrader valves. 6. After pulling a deep vacuum for four hours, check the vacuum level and, if it has not changed, break the vacuum with dry nitrogen. 7. Pull a second vacuum to 250 microns or less. Recheck the vacuum level after 2 hours.

3.5.2 Insulation

Insulate all piping between the Liebert XDP and its connected cooling modules to prevent condensation where the piping passes through non-conditioned areas.

Piping

Page 29 of the Liebert XDP160RC user manual — 3.6 Filling the Pumped Circuit—R-134a
Page 29 · click to enlarge
Page 29

3.6 Filling the Pumped Circuit—R-134a

Using a refrigerant pump or cylinder heater pads will speed the charging process.

1. Connect a charging manifold to the service port of the receiver outlet valve or to the suction and discharge side of the pump. 2. Purge the hoses. 3. Calculate the amount of R-134a refrigerant needed to charge the system, using the values in Tables 6, 7, 8 and 9; for assistance, refer to 3.6.1 - Calculating Refrigerant Charge— Example. The section includes a worksheet to calculate system refrigerant charge requirements. 4. Weigh in the calculated charge. 5. After adding the calculated charge, allow the system to sit 15 to 30 minutes to reach equilibrium. Observe the refrigerant level through the sight glasses of the receiver. The level should be above the second sight glass at a minimum when the Liebert XDP is off. 6. If the refrigerant level is improper, the charge must be adjusted. If the level is too high or too low, recalculate the required charge and reduce or increase the amount as needed to reach the proper level.

Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR

Per Liebert XD Unit (Excludes Connector Lines to and from Liebert XD Cooling Module) 1.41 lb. (0.64kg) Liebert XDCF 5.32 lb. (2.41kg) Liebert XDH 3.55 lb. (1.61kg) Liebert XDO 157 lb. (71.2kg) Liebert XDP 4 lb. (1.8kg) Liebert XDR 2.32 lb. (1.05kg) Liebert XDV

Refrigerant Charge, lb. (kg)

Table 7 System refrigerant charge for the supply and return mains

lb/foot (kg/m) Supply/Return Main Length and Diameter 0.45 (0.67) Main supply actual length per 1-1/8" OD copper tubing 0.68 (1.01) Main supply actual length per 1-3/8" OD copper tubing 0.28 (0.42) Main return actual length per 2-1/8" OD copper tubing 0.43 (0.64) Main return actual length per 2-5/8" OD copper tubing

Before beginning, verify that the system is not equipped with pre-charged Liebert XD Flex Pipe.

Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR

Refrigerant Charge, lb/foot (kg/m) Hard-Piped Connector Length and Diameter

0.08 (0.12) 1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDR supply connector actual length 0.13 (0.19) 5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length 0.26 (0.39) 7/8" OD Liebert XDO/Liebert XDH/Liebert XDR supply connector actual length 0.02 (0.03) 5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length 0.04 (0.06) 7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length 0.04 (0.06) 7/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XDR return connector actual length 0.07 (0.1) 1-1/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XDR return connector actual length

Piping · Refrigerant Charge,

Page 30 of the Liebert XDP160RC user manual — 3.6.1 Calculating Refrigerant Charge—Example
Page 30 · click to enlarge
Page 30

Table 9 R-134a refrigerant charge for Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDR

lb. (kg) Metal Flex Pipe Connector Length

Supply Line Diameter 1/2"

0.3 lb. (0.14) 4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

0.5 lb. (0.23) 6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

0.7 lb. (0.32) 8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

0.8 lb. (0.36) 10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply/Liebert XDR

Return Line Diameter 5/8"

0.01 lb. (0.01) 4 ft. Flex Pipe existing Liebert XDV systems

0.02 lb. (0.01) 6 ft. Flex Pipe existing Liebert XDV systems

0.03 lb. (0.01) 8 ft. Flex Pipe existing Liebert XDV systems

0.03 lb. (0.01) 10 ft. Flex Pipe existing Liebert XDV systems

Return Line Diameter 1"

0.13 lb. (0.06) 4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

0.2 lb. (0.09) 6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

0.27 lb. (0.12) 8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

0.33 lb. (0.15) 10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply

3.6.1 Calculating Refrigerant Charge—Example

Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20 Liebert XDV8 cooling modules.

Table 10 Calculating refrigerant charge—example

Number of Units or Piping Length, feet

Pounds Per Component Total, lb.

Liebert XDP 1 157 157

Liebert XDV8 Cooling Modules 20 2.32 46.4

Supply Main, 1-1/8" 100 0.45 45

Return Main, 2-1/8" 100 0.28 28

Liebert XDV 1/2" supply Liebert XD Flex Pipes 20 0.8 16

Liebert XDV 5/8" return Liebert XD Flex Pipes 20 0.03 0.6

Table 11 Worksheet to calculate refrigerant charge

Number of Units or Piping Length

Pounds Per Component Total

Show 6 more labels / short text on this page
Piping · Refrigerant Charge · Components · Total 293 · Components · Total
Page 31 of the Liebert XDP160RC user manual — 3.7 Checklist for Proper Installation
Page 31 · click to enlarge
Page 31

3.7 Checklist for Proper Installation ___ 1. Unpack and check received material 2. Position the Liebert XDP and secure it to the floor 3. Wire high voltage connections 4. Wire low voltage connections 5. Connect the building chilled water piping to the Liebert XDP.44Connect the Liebert XD cooling module piping to the Liebert XDP with slope 6. Check the system for leaks 7. Hold a vacuum on the system 8. Charge the system with refrigerant 9. Make sure that all piping has proper insulation.

Piping

Page 32 of the Liebert XDP160RC user manual — ESC
Page 32 · click to enlarge
Page 32

4.0 L IEBERT I COM C ONTROL —F IRMWARE V ERSION XP1.00.010.STD

4.1 Liebert iCOM Components and Functions

The Liebert iCOM controller layout is shown in Figure 24; the keyboard functions are defined in Table 12.

Figure 24 Liebert iCOM display components

Liebert XDP160RC — 4.1 Liebert iCOM Components and Functions diagram (page 32)
Fig. 29 · 4.1 Liebert iCOM Components and Functions

Liquid Crystal Display screen

LED Status Indicators (top LED is red or flashing red; bottom LED is green or amber)

LEDs (see Table 12 for

?

Left Arrow Key Right Arrow Key Enter Key

ESC

Escape Key Down Arrow Key

Show 6 more labels / short text on this page
Keypad · meanings) · Alarm Key · Up Arrow Key · On/Off Key · Help Key
Page 33 of the Liebert XDP160RC user manual — 4.2 Display Lamp Indicators
Page 33 · click to enlarge
Page 33

Table 12 Keyboard icons and functions

Icon Key Name Function

On/Off Key Controls the operational state of the cooling unit.

Alarm Key Silences an alarm.

?

Help Key Accesses integrated Help menus.

ESC

ESCape Key Returns to the previous display view.

Enter Key Confirms all selections and selects icons or text.

Increase Key (Up Arrow) Moves upward in a menu or increases the value of a selected parameter.

Decrease Key (Down Arrow) Moves downward in a menu or reduces the value of a selected parameter.

Left and Right Arrow Keys Navigates through text and sections of the display.

Blinking Red—Active, unacknowledged alarm exists

Solid Red—Active, acknowledged alarm exists

Amber—Power is available to the unit; unit is NOT operating

Green—Unit is operating with no alarms

4.2 Display Lamp Indicators

  • The Green lamp will be On only when the Liebert XDP is On and running with no alarms.
  • The Red lamp will be On if the unit is On and running with an active alarm, or if the unit is shut down because of an alarm.
  • The Red lamp will flash while an alarm is being annunciated. The Red lamp will stop flashing and the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.
  • The Amber lamp will be On if the Liebert XDP has been shut down at the I/O switch or if the unit has been shut down by an alarm condition.

Upper LED · Lower LED

Page 34 of the Liebert XDP160RC user manual — 4.3.1 Accessing Menus and Settings
Page 34 · click to enlarge
Page 34

4.3 Navigating Through the Liebert iCOM Display

Liebert iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The Liebert iCOM’s home screen is shown in Figure 25.

Figure 25 Liebert iCOM default home screen

Pump Operation represented by animated refrigerant lines

Sensor A Room Data

Sensor B Room Data

Liebert XDP160RC — 4.3 Navigating Through the Liebert iCOM Display diagram (page 34)
Fig. 30 · 4.3 Navigating Through the Liebert iCOM Display
Sensor A B Temp74°F 72°F Hum: 50% 50% Dew Pt: 55°F 54°F

Available only with Liebert XD Smart Modules

28.02.20 12 14:07(01) UNIT ON 28.02.20 12 14:07(01) UNIT ON

press : for next /prev unit for unit /system view press : for menu ; ESC for prev screen ; ? for help

4.3.1 Accessing Menus and Settings

Viewing Data

No password is required to view data or settings.

To view data:

1. From the home screen, press the Enter key to view the User Menu (see Figure 29 ). 2. Press Enter again to highlight the first icon. 3. Use the keyboard’s arrow keys to move to the icon for the data you wish to view. 4. Once that icon is highlighted, press Enter again to open that menu.
  • If a password is required, see 4.3.3 - Entering the Password .
  • If a menu has more than one screen, the Liebert iCOM display will have text at the top simi lar to this: (page 1 of 2) . 5. Press Enter to select the first line of data. 6. Use the Up and Down arrow keys to scroll to the desired data point. 7. Press ESC to move back to higher level menus.
Show 7 more labels / short text on this page
Unit Name · Refrigerant Temperature · Next Scheduled Maintenance · Date and Time · Unit Status · Alarm/Event History · Navigation Prompts
Page 35 of the Liebert XDP160RC user manual — 8/4/2012 14:13:54 ALARM OFF
Page 35 · click to enlarge
Page 35

4.3.2 Cooling Module Overview

The Liebert iCOM will display an overview of all connected cooling modules. It does not display a system view, which would include units other than the cooling modules.

To display an overview of all connected cooling modules:

1. At the default home screen on the Liebert iCOM, press the down arrow. This will display the first 10 modules’ outlet temperature and capacity levels. Press ESC to return to the unit view.

Figure 26 Cooling module overview, first 10 modules

UNIT 1

Air Temp Liebert XDP

OFF 9/2013 100% 212°F Max XD Supply

°F 70 72 74 76 75 73 74 71 77 72

AA01AA01

8/4/2012 14:13:54 ALARM OFF

(01) 8/2/2012 08:33 RST General Alarm (01) 8/2/2012 08:20 ACK HIGH CHILLED WATER TEMP

? for help for next/previous unit for system view ESC for previous screen for menu

2. Press the down arrow button again to display the next 10 modules’ outlet temperature and capacity levels. 3. Press ESC to return to the default home screen.
Page 36 of the Liebert XDP160RC user manual — ???? 68.0°F
Page 36 · click to enlarge
Page 36

4.3.3 Entering the Password

Most settings in the Liebert iCOM are protected by a factory-set password, 1490. To enter the password:

1. From the home screen, press the Enter key to view the User Menu (see Figure 29). 2. Press Enter again to highlight the first icon. 3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change. 4. Once that icon is highlighted, press Enter again to open that menu. 5. Press Enter to highlight the Password line. 6. With the Password line highlighted, press Enter to highlight the first digit in the password 7. Enter the password, 1490. Use the Up and Down arrow keys to select a numeral for the first digit of the password. Move to the next digit of the password with the Right arrow key. Select the numerals for all four digits with the same process. 8. After all four digits of the password have been entered, press the Enter key.

Figure 27 Entering the password

After highlighting the Password command line, press Enter again to highlight the first digit. Use the Up and Down arrow keys to change the first digit. Move to the next digit in the Password with the right arrow.

Password command line—highlight by pressing Enter

SETPOINTS

UNIT 01

U101 U102 U103 U104 U105 U106 U107 U108 U109 U110 U111

PASSWORD (Actual Level 0) Min Room Temperature Setpoint

68.0°F

to change parameter to confirm to select parameter for next/previous unit then

Page 37 of the Liebert XDP160RC user manual — 4.5 Changing Operational Settings
Page 37 · click to enlarge
Page 37

4.4 Changing Liebert iCOM’s Display Settings

No password is required to change the way Liebert iCOM displays data. The Display Setup controls how the unit shows data, such as temperature, date and time.

To change the display settings:

1. From the home screen, press the Enter key to view the User Menu (see Figure 29). 2. Press Enter again to highlight the first icon. 3. Use the keyboard’s arrow keys to move to the Display Setup icon. 4. Once that icon is highlighted, press Enter again to open that menu. 5. Press the Enter key to select the first setting. Either change that setting or navigate to another setting with the Up and Down arrow keys. 6. Once the desired setting is highlighted, press the Enter key to access that parameter’s display setting options. 7. Use the Up and Down arrow keys to make changes. 8. Press the Enter key to accept the changes. 9. Press the ESC key twice to return to Liebert iCOM’s user menu.

Figure 28 Display setup screen

DISPLAY SETUP

SYSTEM

U401 U402 U403 U404 U405 U406 U407 U408 U409 U410 U411

Language Date Time Temperature Indication Display Contrast Buzzer Frequency Backlite Off after Screen

ENGLISH (US)

8/27/2012 15:03:17 °C

Highlight the setting to be changed by pressing Enter.

Display Colors Date Format

to change parameter to confirm to select parameter for next/previous unit then

4.5 Changing Operational Settings

Changes to the Liebert XDP’s operation settings in the Set Alarms and Setpoints menus require a password.

1. From the home screen, press the Enter key to view the User Menu (see Figure 29). 2. Press Enter again to highlight the first icon. 3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change. 4. Once that icon is highlighted, press Enter again to open that menu. If a password is required, see 4.3.3 - Entering the Password. 5. After entering the password, use the Up and Down arrow keys to scroll to and highlight the operational setting to be changed. 6. Press Enter to highlight the values for that setting. 7. Use the Up and Down arrow keys to change the value. 8. Press Enter to accept the change. (The value will no longer be highlighted.) 9. Press ESC to deselect the operational setting. (The setting will no longer be highlighted.) 10. Press ESC again to move to previous screens.

50 Off/ 50 · 5 min XDP · Normal mm/dd/yyyy

Page 38 of the Liebert XDP160RC user manual — 4.7 Liebert iCOM User Menu Icons and Legend
Page 38 · click to enlarge
Page 38

4.6 Graphical Data Record

The Graphical Data Record charts the average temperature from Sensors A and B and the supply refrigerant temperature.

The temperature scales can be changed to expand or compress the data.

The time scale also can be altered to any of several selectable values.

4.7 Liebert iCOM User Menu Icons and Legend

Figure 29 Liebert iCOM User Menu icons

Liebert XDP160RC — 4.7 Liebert iCOM User Menu Icons and Legend diagram (page 38)
Fig. 31 · 4.7 Liebert iCOM User Menu Icons and Legend

Displays average temperature from Sensors A and B, the average dew point from

Page 39 of the Liebert XDP160RC user manual — Figure 30 Liebert XDP User Menu screen
Page 39 · click to enlarge
Page 39

Figure 30 Liebert XDP User Menu screen

Liebert XDP160RC — Figure 30 Liebert XDP User Menu screen diagram (page 39)
Fig. 32 · Figure 30 Liebert XDP User Menu screen

ESC to unselect to change level to open requested menu

Page 40 of the Liebert XDP160RC user manual — ???? 68.0°F
Page 40 · click to enlarge
Page 40

4.8 Liebert iCOM User Menu Screens

User menus report general cooling unit operations and status. User menu screens employ a coding that begins with “U” and is followed by parameters and information, such as settings. Gaining access to some User menu screens requires entering a password; the User Menu password is 1490.

Check www.liebert.com for the latest Liebert iCOM user manual updates, SL-18835.

Figure 31 Setpoints screen

SETPOINTS

UNIT 01

U101 U102 U103 U104 U105 U106 U107 U108 U109 U110 U111

PASSWORD (Actual Level 0) Min Room Temperature Setpoint

68.0°F

to change parameter to confirm to select parameter for next/previous unit then

Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, the unit will raise the refrigerant temperature to reduce the amount of cooling.

The setting is intended to keep the room temperature above the setpoint. Without a proper setpoint, the Liebert XDP can lower the room temperature too much, depending on the room dew point and load. This setpoint will reduce the cooling to keep the room temperature above this desired temperature.

The default setting is 60°F (15.6°C). The range is 50-80°F (10-27°C). For optimal cooling performance, the minimum temperature setpoint should be 1-2° below the expected temperature at the remote sensors, which may affect placement of the remote sensors. If the minimum temperature setpoint is set above the typical remote temperature sensor reading, it will reduce the Liebert XD cooling output and, in extreme cases, cause erratic Liebert XD performance.

Spare Parts Spare Parts—The spare parts lists contains a detailed description and part number that can be used to order parts for the unit. These part numbers are specific to each model and option installed on the unit.

Event Log Event Log—The event log displays all events and actions that have been generated by the unit. When multiple units are networked you will see the event log of the whole system. Each event shows the unit that generated the alarm, time and date stamp, a description and the event type.

Page 41 of the Liebert XDP160RC user manual — 60.0°F
Page 41 · click to enlarge
Page 41

Figure 32 Set Alarms screen

SET ALARMS (page 1 of 1)

UNIT 01

U201 U202 U203 U204 U205 U206 U207 U208 U209 U210 U211

PASSWORD (Actual Level 0) High Room Air Temperature Low Room Air Temperature High Room Dewpoint High Refrigerant Temperature

80.0°F 55.0°F 65.0°F 80.0°F

High Chilled Water Temperature

60.0°F

to change parameter to confirm to select parameter for next/previous unit then

High Room Air Temperature—Sets the threshold where a high room temperature alarm will occur, based on the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C). Low Room Air Temperature—Sets the threshold where a low room temperature alarm will occur, based on the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C). High Room Dewpoint—Sets the threshold where a high room dew point alarm will occur, based on the calculated values from either remote Sensor A or remote Sensor B. The range for the high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C). High Refrigerant Temperature—Sets the threshold where a high refrigerant temperature alarm will occur based on the actual reading from the supply refrigerant sensor. The supply refrigerant temperature is from the Liebert XDP to the modules. The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C). High Chilled Water Temperature—Sets the threshold where a high chilled water temperature alarm will occur based on the actual reading from the supply chilled water sensor. The range for the high chilled water temperature is from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).

Page 42 of the Liebert XDP160RC user manual — Figure 33 Sensor Data screen, page 1 of 2
Page 42 · click to enlarge
Page 42

Figure 33 Sensor Data screen, page 1 of 2

SENSOR DATA (page 1 of 2) UNIT 01

U301 U302 U303 U304 U305 U306 U307 U308 U309 U310 U311 U312

Sensor A Temperature 62.8°F Sensor A Humidity 42.20% Sensor A Dew Point 39.4°F Sensor B Temperature 71.2°F Sensor B Humidity 29.60°% Sensor B Dew Point 37.8°F Supply Refrigerant Temperature 55.0°F

Supply Chilled Water Temperature 55.0°F

This window is READ ONLY

Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor designated as Sensor A.

Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated as Sensor A.

Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated as Sensor A.

Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor designated as Sensor B.

Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated as Sensor B.

Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated as Sensor B.

Supply Refrigerant Temperature—Displays the actual supply refrigerant temperature from the Liebert XDP to the modules.

Supply Chilled Water Temperature—Displays the actual the Supply Chilled Water temperature to the Liebert XDP.

Page 43 of the Liebert XDP160RC user manual — Figure 34 Sensor Data screen, page 2 of 2
Page 43 · click to enlarge
Page 43

Figure 34 Sensor Data screen, page 2 of 2

SENSOR DATA (page 2 of 2) UNIT 01

U313 U314 U315 U316 U317 U318 U319 U320 U321 U322 U323 U324

Daily High Temperature 07:49:57 72°F Daily Low Temperature 07:11:30 64°F Daily High Humidity 11:31:46 45% Daily Low Humidity 07:56:18 34% Daily High Dew Point 07:47:26 45°F Daily Low Dew Point 08:02:20 37°F Daily High Refrigerant Temp 13:01:25 69°F Daily Low Refrigerant Temp 13:01:11 69°F Daily High CW Temp 14:01:33 55°F Daily Low CW Temp 14:01:45 55°F

This window is READ ONLY

Daily High Temperature—Shows the highest temperature in a rolling 24 hour period for either remote Sensor A or remote Sensor B.

Daily Low Temperature—Shows the lowest temperature in a rolling 24 hour period for either remote Sensor A or remote Sensor B.

Daily High Humidity—Shows the highest humidity in a rolling 24 hour period for either remote Sensor A or remote Sensor B.

Daily Low Humidity—Shows the lowest humidity in a rolling 24 period for either remote Sensor A or remote Sensor B.

Daily High Dew Point—Shows the highest dew point in a rolling 24 hour period for either remote Sensor A or remote Sensor B.

Daily Low Dew Point—Shows the lowest dew point in a 24 hour period for either remote Sensor A or remote Sensor B.

Daily High Refrigerant Temperature—Shows the highest supply refrigerant temperature in a rolling 24 hour period from the Liebert XDP to the modules.

Daily Low Refrigerant Temperature—Shows the lowest supply refrigerant temperature in a rolling 24 hour period from the Liebert XDP to the modules.

Daily High Chilled Water Temperature—Shows the highest chilled water supply temperature being delivered to the Liebert XDP in a rolling 24 hour period.

Daily Low Chilled Water Temperature—Shows the lowest chilled water return temperature being delivered to the Liebert XDP in a rolling 24 hour period.

Page 44 of the Liebert XDP160RC user manual — ENGLISH (US)
Page 44 · click to enlarge
Page 44

Figure 35 Display Setup screen

DISPLAY SETUP

SYSTEM

U401 U402 U403 U404 U405 U406 U407 U408 U409 U410 U411

Language Date Time Temperature Indication Display Contrast Buzzer Frequency Backlite Off after Screen

ENGLISH (US)

8/27/2012 15:03:17 °F 30 Off/ 50

5 min Unit View

Display Colors Date Format

to change parameter to confirm to select parameter for next/previous unit then

Language—Sets the language on the display. Changing this setting changes all menu parameters to the selected language.

Date—Sets the internal date of the unit. If this unit is connected to other units with the unit-to-unit network connection, each unit will reflect the last date set.

Time—Sets the internal time of the unit. If this unit is connected to other units with the unit-to-unit network connection each unit will reflect the last time set.

Temperature Indication—Selects the actual and setpoint temperature scale. Selecting C will set the unit to display in Celsius and F will set the unit to display in Fahrenheit.

Display Contrast—Changes the contrast of the display to adjust for different viewing angles, low light and bright light conditions. As the display ages, the contrast may require adjustment for viewing.

Buzzer Frequency—Changes the audible noise frequency of the built-in buzzer. The buzzer will sound when its frequency is being adjusted, easing selection of a frequency easily detected when an alarm occurs.

Backlite Off After—Controls how long the back-light remains active when the display is unused. When the buttons on the front display have not been pressed for the time selected in this parameter, the back-light will turn Off, extending the life of the display and saving energy.

Screen—Controls the screen layout. The Liebert XDP has one view, Unit View.

Display Colors—Selects the background color. Inverted sets the display to show white font with blue background and Normal sets a white background with blue font.

Date Format—Date format changes the month, day and year arrangement shown on the front display and on event time stamps.

Normal mm/dd/yyyy

Page 45 of the Liebert XDP160RC user manual — NODE 81 AZ81
Page 45 · click to enlarge
Page 45

Figure 36 Module Status screen, page 1 of 20

MODULE STATUS (page 1 of 20) UNIT 01

U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913

NODE 81 AZ81

ONLINE

57°F

92°F

XDV

66°F

65°F

Model / Capacity XDV8SK 8 KW Left Fan Status ON Right Fan Status ON

Module Node ID—The location within the CANbus. Each module’s ID is factory-set to 80 and is automatically changed during setup; requires no user action.

Module Labels—A four-character label consisting of two letters and two numerals. This is the standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or both labels can be used and are entered using the Module Setup found in the Service menu (S910).

Module Status—Indicates whether the smart module is connected to the CANbus.

Figure 37 Liebert XDV Smart Module Status screen

MODULE STATUS (page 1 of 20) UNIT 01

U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913

NODE 81 AZ81

ONLINE

57°F

92°F

XDV

66°F

65°F

Model / Capacity XDV8SK 8 KW Left Fan Status ON Right Fan Status ON

U905—Displays the temperature of the air entering the Liebert XDV.

U908—Displays the temperature of the air leaving the right and left fan of the Liebert XDV.

U911—Displays the module type and calculated local module capacity; possible module types are XDV8SK, XDV8SS, XDV8ST, XDV10SK, XDV10SS and XDV10ST.

U912—Displays the left fan status; possible values are ON and OFF.

U913—Displays the right fan status; possible values are ON, OFF and ON ECON. ON ECON indicates that only one fan is On.

Page 46 of the Liebert XDP160RC user manual — ONLINE NODE 81 AF01
Page 46 · click to enlarge
Page 46

Figure 38 Liebert XDH Smart Module Status screen—each bank shown separately

MODULE STATUS (page 1 of 20) UNIT 01

U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913

NODE 82 AA82

ONLINE

57°F

98°F

73°F XDH TOP/

98°F

BOTTOM

Model / Capacity XDH32SK 15 KW Middle Fan Status ON Top and Bottom Fan Status ON

U904—Displays the temperature of the air entering the top of the bank of the Liebert XDH.

U905—Displays the temperature of the air leaving the Liebert XDH.

U907—Displays the temperature of the air entering the bottom of the bank of the Liebert XDH.

U911—Displays the module type and calculated local module capacity; possible module types are XDH20SK, XDH20SS, XDH32SK and XDH32SS.

U912—Displays the middle fan status; possible values are ON and OFF.

U913—Displays the top and bottom fans’ status; possible values are ON, OFF and ON ECON. (ON ECON indicates that two fans have been turned On.)

Figure 39 Liebert XDO Smart Module Status screen

MODULE STATUS (page 1 of 20) UNIT 01

U901 U902 U903 U904 U905 U906 U907 U908 U909 U910 U911 U912 U913

ONLINE NODE 81 AF01

57°F

XDO

92°F 92°F

68°F

Model / Capacity XDO20SK 20 KW Fan Status ON

U907—Displays the temperature of the air entering from the right and left of the Liebert XDO.

U910—Displays the temperature of the air leaving the Liebert XDO.

U911—Displays the module type and calculated local module capacity; possible module types XDO16SK, XDO16SS and XDO20SS.

U912—Displays the fan status; possible values are ON and OFF.

Page 47 of the Liebert XDP160RC user manual — 4.9 Liebert iCOM Service Menu Icons and Legend
Page 47 · click to enlarge
Page 47

Figure 40 Total Run Hours screen

Liebert XDP160RC — Figure 40 Total Run Hours screen diagram (page 47)
Fig. 33 · Figure 40 Total Run Hours screen

U501 U502 U503 U504 U505 U506 U507 U508 U509 U510 U511

Actual Hours Limit Pump 1 454 0 Pump 2 413 0

The parameter shows the actual hours Pump 1 and Pump 2 have operated and the maximum time Pump 1 can operate before the next maintenance.

4.9 Liebert iCOM Service Menu Icons and Legend

Figure 41 Liebert iCOM Service Menu icons

Liebert XDP160RC — 4.9 Liebert iCOM Service Menu Icons and Legend diagram (page 47)
Fig. 34 · 4.9 Liebert iCOM Service Menu Icons and Legend

Smart Module Setup of alarms and events. Set temperature limits

Page 48 of the Liebert XDP160RC user manual — 4.10 Liebert iCOM Service Menu Screens
Page 48 · click to enlarge
Page 48

Figure 42 Liebert XDP Service Menu screen

Liebert XDP160RC — Figure 42 Liebert XDP Service Menu screen diagram (page 48)
Fig. 35 · Figure 42 Liebert XDP Service Menu screen

to select parameter to change level to open requested menu ESC to unselect

4.10 Liebert iCOM Service Menu Screens

Service menus allow customized settings for site operations. Service Menu screens employ a coding that begins with “S” and is followed by parameters and information, such as settings. Gaining access to most Service Menus requires entering a password; the Service Menu password is 5010; see 4.3.3 - Entering the Password for assistance. The Liebert iCOM control firmware is being updated constantly. As a result, the Service Menu parameters in this manual may be slightly different from what is shown on a cooling unit’s display. Check www.liebert.com for the latest Liebert iCOM user manual updates.

Figure 43 Setpoints screen

Liebert XDP160RC — 4.10 Liebert iCOM Service Menu Screens diagram (page 48)
Fig. 36 · 4.10 Liebert iCOM Service Menu Screens

S101 S102 S103 S104 S105 S106 S107 S108 S109 S110 S111

PASSWORD (Actual Level 0) Min Room Temperature Setpoint Temperature Control Type Temperature Proportional Band Temperature Integration Tiime Temperature Derivative Dewpoint Margin Minimum Control Point Min Percent Cooling Setpoint

Page 49 of the Liebert XDP160RC user manual — Figure 42 Liebert XDP Service Menu screen
Page 49 · click to enlarge
Page 49

Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, unit will raise the refrigerant temperature to reduce the amount of cooling. Adjustable from 50 to 80°F (10.0 to 26.7°C), the factory default setting is 60°F (15.6°C).

Temperature Control Type—Selects the type of control the system will use to activate cooling. The Liebert iCOM control has three temperature control types: Proportional, PI and Intelligent. The factory default is Intelligent.

Proportional—If Proportional Control is selected, the percent cooling requirement is determined by the difference between the air temperature sensor reading and the temperature setpoint. As the air temperature rises above the temperature setpoint, the percent cooling required increases proportionally (from 0 to 100%) over half the programmable temperature proportional band. The percent heating requirement (0 to 100%) is determined the same way when the air temperature falls below the setpoint. PI—If PI Control is selected, the percent cooling requirement is calculated by adding together two individual terms, proportional and integral. The proportional term is calculated in a manner similar to the previously described Proportional control. The integral term (sometimes called reset action) is calculated by measuring how much and for how long the air temperature has been above or below the setpoint. If the actual air temperature is above the setpoint, the percent requirement is slowly but continuously increased until the total is sufficient to bring the return room air back to the setpoint. Intelligent—If Intelligent Control is selected, the air temperature is controlled at or near the setpoint. The percent temperature adjustment required is calculated based on logic that is programmed into the control. These rules simulate the actions that would be taken by a human operator manually controlling the system.

Temperature Proportional Band—Adjusts the activation points of compressors or rate of change based on the actual sensor values deviation from setpoint. The smaller this number the faster the compressors and valve(s) will increase capacity. Too small of a number may cause the unit to short cycle the compressors or excessively reposition the valve. This parameter is adjustable from 1.8 to 54.0°F (1.0 to 30.0°C). The factory default setting is 7.0°F (3.9°C).

Temperature Integration Time—Temperature integration takes into consideration the amount of time the actual temperature has deviated from the setpoint. The larger this deviation is the longer the unit will wait before corrective action is taken to achieve the setpoint. This parameter is adjustable from 0 to 15 minutes. The factory default is 0.

Temperature Derivative Time—Monitors the rate of change and will reduce or increase the amount of corrective action based on the actual temperature increasing or decreasing toward the temperature setpoint. This parameter is adjustable from 0-900 seconds. The factory default is 0.

Dewpoint Margin—Selects the difference between the room dew point and the refrigerant temperature control point. This parameter is adjustable from 4.0 to 10.0°F (2.2 to 6.0°C). The factory default setting is 4.0°F (2.2°C).

Minimum Control Point—Sets the minimum supply refrigerant temperature the Liebert XDP will maintain. This parameter is adjustable from 40 to 80°F (4.4 to 27.0°C). The factory default is 55°F (12.8°C).

Min Percent Cooling Setpoint—Selects the lowest percent call for cooling during normal operations. Whenever the unit is not in startup mode or OFF, the percent call for cooling cannot go below this value. The parameter is adjustable from 5 to 30%. The factory default is 15%.

Page 50 of the Liebert XDP160RC user manual — Figure 44 Maintenance—Basic Settings screen, page 1 of 7
Page 50 · click to enlarge
Page 50

Figure 44 Maintenance—Basic Settings screen, page 1 of 7

Basic Settings (page 1 of 7) SYSTEM

S001 S002 S003 S004 S005 S006 S007 S008 S009 S010 S011

PASSWORD (Actual Level 0) Maintenance Frequency Per Year 1 Max Bonus 0 Max Penalty 0 Last Maintenance 08/25/2011 Service Engineer NOBODY Confirm PM No Calculated Next Maintenance 08/2014

to confirm for next/previous unit then

Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year time span.

Max Bonus—Increases the time until the next required maintenance. Service personnel should assign a bonus when a service visit finds all components working optimally.

Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign a penalty when a service visit finds excessive wear on components.

Last Maintenance—Date set during the service call. It also indicates to other service personnel the date of the last visit.

Service Engineer—Provides a label for the service representative to list either the company name or representative’s name.

Confirm PM—Confirms that the service representative has completed the preventive maintenance and resets the next maintenance date.

Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty or bonus set in the Liebert iCOM control.

to select parameter · to change parameter

Page 51 of the Liebert XDP160RC user manual — Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7
Page 51 · click to enlarge
Page 51

Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7

Pump 1 Settings (page 2 of 7) UNIT 1

S012 S013 S014 S015 S016 S017 S018 S019 S020 S021 S022

PASSWORD (Actual Level 0) Number of Starts 31 Run Hours 453hrs Average Run Time 876min Starts per Day Best 1 Starts per Day Worst 24 Number of Alarms 1 Actual Bonus 0

to confirm for next/previous unit then

Number of Starts—Shows the number of starts for the unit’s Pump 1.

Run Hours—Shows the number of run hours for the unit’s Pump 1.

Average Run Time—Shows the average run time of the unit’s Pump 1.

Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1.

Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1.

Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1.

Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will always take the value from the worst component for the next maintenance indication.

to select parameter · to change parameter

Page 52 of the Liebert XDP160RC user manual — Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7
Page 52 · click to enlarge
Page 52

Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7

Liebert XDP160RC — Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7 diagram (page 52)
Fig. 37 · Figure 46 Maintenance—Pump 2 Settings screen, page 3…

Pump 2 Settings (page 3 of 7) UNIT 1

S023 S024 S025 S026 S027 S028 S029 S030 S031 S032 S033

PASSWORD (Actual Level 0) Number of Starts 2 Run Hours 0hrs Average Run Time 0min Starts per Day Best 1 Starts per Day Worst 24 Number of Alarms 1 Actual Bonus 0

Number of Starts—Shows the number of starts for the unit’s Pump 2. Run Hours—Shows the number of run hours for the unit’s Pump 2. Average Run Time—Shows the average run time of the unit’s Pump 2. Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 2. Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 2. Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 2 Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 2. The unit will always take the value from the worst component for the next maintenance indication.

Figure 47 Maintenance screens, pages 4 through 7

Liebert XDP160RC — Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7 diagram (page 52)
Fig. 38 · Figure 46 Maintenance—Pump 2 Settings screen, page 3…

Compressor 1A Settings (page 4 of 7) UNIT 1

Compressor 1B Settings (page 5 of 7) UNIT 1

S034 S035 S036 S037 S038 S039 S040 S041 S042 S043 S044

S045 S046 S047 S048 S049 S050 S051 S052 S053 S054 S055

Compressor 2A Settings (page 6 of 7) UNIT 1

Compressor 2B Settings (page 7 of 7) UNIT 1

S067 S068 S069 S070 S071 S072 S073 S074 S075 S076 S077

S056 S057 S058 S059 S060 S061 S062 S063 S064 S065 S066

Pages 4 through 7 apply only to the Liebert XDC. No Liebert XDP parameters are present.

Page 53 of the Liebert XDP160RC user manual — Figure 48 Diagnostics/Service Mode screen, page 1 of 6
Page 53 · click to enlarge
Page 53

Figure 48 Diagnostics/Service Mode screen, page 1 of 6

DIAGNOSTICS/SERVICE MODE (page 1 of 6) UNIT 01

S301 S302 S303 S304 S305 S306 S307 S308 S309 S310 S311

PASSWORD (Actual Level 0)

to confirm for next/previous unit then

Page 1 applies to the Liebert XDC only. No Liebert XDP parameters are present.

Figure 49 Diagnostics/Service Mode screen, page 2 of 6

DIAGNOSTICS/SERVICE MODE (page 2 of 6) UNIT 01

S312 S313 S314 S315 S316 S317 S318 S319 S320 S321 S322

PASSWORD (Actual Level 0) Manual Mode No Pump 1 Off Pump 2 Off

3P Start Completed/Active No No 3P Actuator Input Request 30.00% 3P Actuator Position 30% 3P Actuator Open Off 3P Actuator Close Off Valve Feedback 30%

to confirm for next/previous unit then

Manual Mode—Used to place the Liebert iCOM control in manual mode. This is the initial setting necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each service menu item shows the current status of each parameter.

Pump 1—Starts the unit’s Pump 1.

Pump 2—Starts the unit’s Pump 2.

3P Start Active/Complete—Displays if the startup routine is active, and if it is completed.

3P Actuator Input Request—Shows the % call for cooling.

3P Actuator Position—Sets the position of the actuator 0-100% in manual mode.

3P Actuator Open—Opens the 3P actuator when set to ON in manual mode.

3P Actuator Close—Closes the 3P actuator when set to ON in manual mode

Valve Feedback—Opens the valve % in manual mode.

Show 4 more labels / short text on this page
to select parameter · to change parameter · to select parameter · to change parameter
Page 54 of the Liebert XDP160RC user manual — Figure 50 Diagnostics/Service Mode screen, page 3 of 6
Page 54 · click to enlarge
Page 54

Figure 50 Diagnostics/Service Mode screen, page 3 of 6

DIAGNOSTICS/SERVICE MODE (page 3 of 6) UNIT 01

S323 S324 S325 S326 S327 S328 S329 S330 S331 S332 S333

PASSWORD (Actual Level 0)

to confirm for next/previous unit then

Page 3 applies to the Liebert XDC only. No Liebert XDP parameters are present.

Figure 51 Diagnostics/Service Mode screen, page 4 of 6

DIAGNOSTICS/SERVICE MODE (page 4 of 6) UNIT 01

S334 S335 S336 S337 S338 S339 S340 S341 S342 S343 S344

PASSWORD (Actual Level 0)

Manual Mode Control Type Full Manual Deviation 12% Analog Output Ramp 1 30% Analog Output Ramp 2 0% Analog Output Ramp 3 60% Analog Output Ramp 4 58% Alarm Relay Off Warning Relay Off

to confirm for next/previous unit then

Manual Mode Control Type—Not currently used.

Manual Deviation—Not currently used.

Analog Output Ramp 1—Sets the value of Analog Output 1 value as a percentage. The factory default for the Liebert XDP is the Valve % Open.

Analog Output Ramp 2—Sets the value of Analog Output 2 value as a percentage. The factory default for the Liebert XDP is the Call for Cooling.

Analog Output Ramp 3—Sets the value of Analog Output 3 value as a percentage. The factory default for the Liebert XDP is the CW Temp.

Analog Output Ramp 4—Sets the value of Analog Output 4 value as a percentage. The factory default for the Liebert XDP is the refrigerant temperature.

Alarm Relay—Used to activate the Liebert iCOM’s common alarm relay output.

Show 4 more labels / short text on this page
to select parameter · to change parameter · to select parameter · to change parameter
Page 55 of the Liebert XDP160RC user manual — Figure 52 Diagnostics/Service Mode screen, page 5 of 6
Page 55 · click to enlarge
Page 55

Figure 52 Diagnostics/Service Mode screen, page 5 of 6

DIAGNOSTICS/SERVICE MODE (page 5 of 6) UNIT 01

S345 S346 S347 S348 S349 S350 S351 S352 S353 S354 S355

PASSWORD (Actual Level 0) Status Remote Shutdown o–o On Status Fan Failure o/o Ok Status Diff Press Switch 1 o/o Act

Status Customer Input 1 o/o Ok Status Condensation Detect o/o Ok Status Unit Ready o–o On

to confirm for next/previous unit then

Status Remote Shutdown—Displays the status of the unit’s remote shutdown input.

Status Fan Failure—Displays the status of the dry contact to communicate fan failure at a module. (The dry contacts are not used to communicate a fan failure alarm when using CANbus.)

Status Diff Press Switch 1—Displays the status of the differential pressure switch.

Status Customer Input 1—Displays the status of the customer input 1 alarm.

Status Condensation Detect—Displays the status of the dry contact to communicate condensate detection at a module.

Status Unit Ready—Shows unit status when a secondary device, such as a fire detection system, is employed.

Figure 53 Diagnostics/Service Mode screen, page 6 of 6

DIAGNOSTICS/SERVICE MODE (page 6 of 6) UNIT 01

S356 S357 S358 S359 S360 S361 S362 S363 S364 S365 S366

PASSWORD (Actual Level 0)

to confirm for next/previous unit then

Page 6 applies to the Liebert XDC only. No Liebert XDP parameters are present.

Show 4 more labels / short text on this page
to select parameter · to change parameter · to select parameter · to change parameter
Page 56 of the Liebert XDP160RC user manual — Figure 54 Set Alarms screen, page 1 of 7
Page 56 · click to enlarge
Page 56

Figure 54 Set Alarms screen, page 1 of 7

SET ALARMS (page 1 of 7) UNIT 01

S201 S202 S203 S204 S205 S206 S207 S208 S209 S210 S211

PASSWORD (Actual Level 0) High Room Air Temperature 88.0°F Low Room Air Temperature 55.0°F High Room Dewpoint 65.0°F High Refrigerant Temperature 80.0°F

High Chilled Water Temperature 60.0°F

to confirm for next/previous unit then

High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).

Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).

High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).

High Refrigerant Temperature—Sets the threshold for a high a refrigerant temperature alarm. The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).

High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high chilled water temperature alarm. The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).

to select parameter · to change parameter

Page 57 of the Liebert XDP160RC user manual — Figure 55 Set Alarms screen, page 2 of 7
Page 57 · click to enlarge
Page 57

Figure 55 Set Alarms screen, page 2 of 7

SET ALARMS (page 2 of 7) UNIT 01

S212 S213 S214 S215 S216 S217 S218 S219 S220 S221 S222

PASSWORD (Actual Level 0) Customer Input 1 Water Alarm Customer Input 1 active when Closed

to confirm for next/previous unit then

Customer Input 1—Selects the device and operation of the customer input. Each event reflects a different alarm and possible action to the unit. Selectable options are:

Call Service C-Input Water Smoke

Customer Input 1 active when—Selects whether the Customer Input 1 input is normally closed or normally open.

Reset Disabled Alarms—Resets disabled events.

The Set Alarm Screens (Figure 56 through 60) permit setting the operation of an active alarm. Each event can be enabled or disabled and can be set to operate as an alarm, warning or message. The delay is the time the control waits before reporting the event.

Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes the red LED on the display. Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event viewer / front display and flashes the red LED on the display. Message: Shows the event in the event viewer and on the front display.

to select parameter · to change parameter

Page 58 of the Liebert XDP160RC user manual — ???? TYPE
Page 58 · click to enlarge
Page 58

Figure 56 Set Alarms screen, page 3 of 7

SET ALARMS (page 3 of 7) UNIT 01

S223 S224 S225 S226 S227 S228 S229 S230 S231 S232 S233 S234 S235

PASSWORD (Actual Level 0)

TYPE

DELAY

EN-DIS ENABLE

HIGH TEMP SENSOR A LOW TEMP SENSOR A HIGH TEMP SENSOR B LOW TEMP SENSOR B HIGH DEWPOINT SENSOR A FAILURE SENSOR B FAILURE HIGH CHILLED WATER TEMP SUPPLY CW SENSOR FAILURE

30

ALM

to confirm for next/previous unit then

HIGH TEMP SENSOR A—Enables or disables the High Temperature Sensor A event, which occurs when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. LOW TEMP SENSOR A—Enables or disables the Low Temperature Sensor A event, which occurs when the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. HIGH TEMP SENSOR B—Enables or disables the High Temperature Sensor B event, which occurs when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is reported as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. LOW TEMP SENSOR B—Enables or disables the Low Temperature Sensor B event, which occurs when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. HIGH DEWPOINT—Enables or disables the High Dewpoint event, which occurs when the calculated dew point at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. SENSOR A FAILURE—Enables or disables the Sensor A Failure event, which occurs when the control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. SENSOR B FAILURE—Enables or disables the Sensor B Failure event, which occurs when the control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. HIGH CHILLED WATER TEMP—Enables or disables the High Chilled Water Temp event, which occurs when the reading from Supply Chilled Water Sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. SUPPLY CW SENSOR FAILURE—Enables or disables the Supply CW Sensor Failure Failure event, which occurs when the control no longer senses a signal from Supply CW Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

to select parameter · to change parameter

Page 59 of the Liebert XDP160RC user manual — ALM ALM ALM ALM ALM ALM
Page 59 · click to enlarge
Page 59

Figure 57 Set Alarms screen, page 4 of 7

SET ALARMS (page 4 of 7) UNIT 01

S236 S237 S238 S239 S240 S241 S242 S243 S244 S245 S246 S247 S248

PASSWORD (Actual Level 0)

TYPE

DELAY

EN-DIS ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE

HIGH REFRIGERANT TEMP LOW REFRIGERANT TEMP SUPPLY REFRIGERANT SENSOR LOSS OF FLOW PUMP 1 LOSS OF FLOW PUMP 2 PUMP SHORT CYCLE

ALM

CONTROL VALVE FAILURE

ENABLE

ALM

to confirm for next/previous unit then

HIGH REFRIGERANT TEMP—Enables or disables the High Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOW REFRIGERANT TEMP—Enables or disables the Low Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SUPPLY REFRIGERANT SENSOR—Enables or disables the Supply Refrigerant Sensor event, which occurs when the control no longer senses a signal from the Supply Refrigerant Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF FLOW PUMP 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when Pump 1 is commanded to run and the differential pressure switch does not sense differential pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF FLOW PUMP 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when Pump 2 is commanded to run and the differential pressure switch does not sense differential pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

PUMP SHORT CYCLE—Enables or disables the Pump Short Cycle event, which occurs when flow is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

CONTROL VALVE FAILURE—Enables or disables the Control Valve Failure event, which occurs when the chilled water control valve has been commanded by the control to open or close and no change is detected by the valve position signal. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

to select parameter · to change parameter

Page 60 of the Liebert XDP160RC user manual — Figure 58 Set Alarms screens, pages 5 and 6
Page 60 · click to enlarge
Page 60

Figure 58 Set Alarms screens, pages 5 and 6

Liebert XDP160RC — Figure 58 Set Alarms screens, pages 5 and 6 diagram (page 60)
Fig. 39 · Figure 58 Set Alarms screens, pages 5 and 6

PASSWORD (Actual Level 0) S259 S250 S251 S252 S253 S254 S255 S256 S257 S258 S259 S260 S261

PASSWORD (Actual Level 0) S262 S263 S264 S265 S266 S267 S268 S269 S270 S271 S272 S273 S274

Pages 5 and 6 apply to the Liebert XDC only. No Liebert XDP parameters are present.

Figure 59 Set Alarms screen, page 7 of 7

Liebert XDP160RC — Figure 58 Set Alarms screens, pages 5 and 6 diagram (page 60)
Fig. 40 · Figure 58 Set Alarms screens, pages 5 and 6

S275 S276 S277 S278 S279 S280 S281 S282 S283 S284 S285 S286 S287

CONDENSATION DETECTED FAN FAILURE CUSTOMER INPUT 1 SMOKE DETECTED WATER UNDER FLOOR UNIT X DISCONNECTED WORKING HRS EXCEEDED CALL SERVICE LOSS OF POWER

ENABLE

CONDENSATION DETECTED—Enables or disables the Condensation Detected event, which occurs when water is detected at a Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. FAN FAILURE—Enables or disables the Fan Failure event, which occurs when a fan failure occurs at a Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. CUSTOMER INPUT 1—Enables or disables the Customer Input 1 event, which occurs when 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event. SMOKE DETECTED—Enables or disables the Smoke Detected event, which occurs when the Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

Page 61 of the Liebert XDP160RC user manual — Figure 60 Sensor Calibration/Setup screen, page 1 of 3
Page 61 · click to enlarge
Page 61

WATER UNDER FLOOR—Enables or disables the Water Under Floor event, which occurs when the Customer Input 1 is configured for “Water Under Floor” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

UNIT X DISCONNECTED—Not currently used.

WORKING HOURS EXCEEDED—Enables or disables the Working Hrs Exceeded event, which occurs when a component has exceeded the user-specified limit. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

CALL SERVICE—Enables or disables the Call Service event, which occurs when the Customer Input 1 is configured for “Call Service” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF POWER—Enables or disables the Loss of Power event, which occurs when the unit is On and operational and the 24VAC power to the control is lost. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

Figure 60 Sensor Calibration/Setup screen, page 1 of 3

SENSOR CALIBRATION/SETUP (page 1 of 3) UNIT 01

S601 S602 S603 S604 S605 S606 S607 S608 S609 S610 S611

PASSWORD (Actual Level 0) Temperature Sensor A Calibrated Temperature Sensor A Humidity Sensor A Calibrated Humidity Sensor A Temperature Sensor B Calibrated Temperature Sensor B Humidity Sensor B Calibrated Humidity Sensor B

+0.0°F 70.3°F +0.0°F 38.3% +0.0°F 72.3°F +0.0°F 35.6%

to confirm for next/previous unit then

Temperature Sensor A—Adjusts the temperature reading from the actual remote CAN Temp Humidity sensor designated as Sensor A to compensate for any error of the sensor or to match other sensors in the room.

Calibrated Temperature Sensor A—Displays the adjusted temperature value of the remote CAN Temp Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus the offset Temperature Sensor A.

Humidity Sensor A—Adjusts the humidity reading from the actual remote CAN Temp Humidity sensor designated as Sensor A to compensate for any error of the sensor or to match other sensors in the room.

Calibrated Humidity Sensor A—Displays the adjusted humidity value of the remote CAN Temp Humidity sensor designated as Sensor A. This value is the actual sensor reading plus or minus the offset Humidity Sensor A.

Temperature Sensor B—Adjusts the temperature reading from the actual remote CAN Temp Humidity sensor designated as Sensor B to compensate for any error of the sensor or to match other sensors in the room.

Calibrated Temperature Sensor B—Displays the adjusted temperature value of the remote CAN Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the offset Temperature Sensor B.

to select parameter · to change parameter

Page 62 of the Liebert XDP160RC user manual — ???? 30.0°F 90.0°F
Page 62 · click to enlarge
Page 62

Humidity Sensor B—Adjusts the humidity reading from the actual remote sensor designated as Sensor B to compensate for any error of the sensor or to match other sensors in the room.

Calibrated Humidity Sensor B—Displays the adjusted humidity value of the remote CAN Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the offset Humidity Sensor B.

Figure 61 Sensor Calibration/Setup screen, page 2 of 3

SENSOR CALIBRATION/SETUP (page 2 of 3) UNIT 01

S612 S613 S614 S615 S616 S617 S618 S619 S620 S621 S622

PASSWORD (Actual Level 0) Supply Refrigerant Sensor Calibrated Supply Refrigerant Sensor

+0.0°F 58.5°F

Supply Chilled Water Sensor Calibrated Supply Chilled Water Sensor

+0.0°F 60.1°F

to confirm for next/previous unit then

to select parameter to change parameter

Supply Refrigerant Sensor—Adjusts the temperature reading from the actual supply refrigerant sensor to compensate for any error of the sensor. Calibrated Supply Refrigerant Sensor—Displays the adjusted temperature value of the supply refrigerant sensor. This value is the actual sensor reading plus or minus the offset Supply Refrigerant Sensor. Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled water sensor to compensate for any error of the sensor. Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water Sensor.

Figure 62 Sensor Calibration/Setup screen, page 3 of 3

SENSOR CALIBRATION/SETUP (page 3 of 3) UNIT 01

S623 S624 S625 S626 S627 S628 S629 S630 S631 S632 S633

PASSWORD (Actual Level 0) Supply Refrigerant Sensor 0% Supply Refrigerant Sensor 100%

30.0°F 90.0°F

to confirm for next/previous unit then

to select parameter to change parameter

Page 63 of the Liebert XDP160RC user manual — Figure 63 System/Network Setup screen—System, page 1 of 2
Page 63 · click to enlarge
Page 63

Supply Refrigerant Sensor 0%—Allows the sensor reading to be calibrated at the lowest reading of the sensor. This calibration changes the start point of the sensor reading.

Supply Refrigerant Sensor 100%—Allows the sensor reading to be calibrated at the highest reading of the sensor. This calibration changes the end point of the sensor reading.

Figure 63 System/Network Setup screen—System, page 1 of 2

SYSTEM/NETWORK SETUP (page 1 of 2) SYSTEM

S801 S802 S803 S804 S805 S806 S807 S808 S809 S810 S811

PASSWORD (Actual Level 0) Number of Connected Units

Configuration Safe Network Safe SW Version

No No OK OK XP1.00.010.STD

to confirm for next/previous unit then

Number of Connected Units—Shows the number of displays connected. This is always 1.

Configuration Safe—Saves or loads configuration settings for the display that have been modified from the factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service Tool. Selecting Save will write the settings to the internal storage file and selecting Load will write the settings from the internal storage file to the application software. The internal file is updated automatically every 12 hours.

Network Safe—Saves or loads network settings for the display that have been modified from the factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service Tool. Selecting Save will write the settings to the internal storage file and selecting Load will write the settings from the internal storage file to the application software.

SW Version—Contains the application software version loaded onto the Liebert iCOM display.

· to select parameter · to change parameter

Page 64 of the Liebert XDP160RC user manual — ???? 192.168.254.003 255.255.255.000 0.000.000.000 00:00:68:19:40:C7 GBP
Page 64 · click to enlarge
Page 64

Figure 64 System/Network Setup screen—System, page 2 of 2

SYSTEM/NETWORK SETUP (page 2 of 2) SYSTEM

S812 S813 S814 S815 S816 S817 S818 S819 S820 S821 S822

PASSWORD (Actual Level 0) IP Address Netmask Gateway MAC U2U Protocol U2U Address U2U Group

192.168.254.003 255.255.255.000 0.000.000.000 00:00:68:19:40:C7 GBP

IP Address—Contains the network address of the display. This address must be unique on the network. The factory default is 192.168.254.003.

Netmask—Defines which part of the IP address is used for the network. The factory default is 255.255.255.000.

Gateway—A network point that acts as an entrance to another network. The factory default is 0.000.000.000.

MAC—A unique hardware identifier for the Ethernet device. The following parameters (U2U Protocol, U2U Address and U2U Group) are for displaying other networked Liebert XDPs. The Liebert XDP does not perform Teamwork Operations.

U2U Protocol—This is always set to GBP.

U2U Address—A unique identifier for each display on the network. Display addresses range from 33 to 64. Each display on the U2U network must have a different U2U address. Not currently used.

U2U Group—Used to create zones or groups within a U2U network. Once a group number is selected, the display will see only other devices with the same group number. The group number can be changed to view other devices in different groups. Not currently used.

Bootloader Variables—Indicates the bootloader has changed since it was last loaded. This parameter should only be activated by an authorized service person.

Bootloader Variables · No OK

Page 65 of the Liebert XDP160RC user manual — UNIT
Page 65 · click to enlarge
Page 65

Figure 65 System/Network Setup screen—Unit, page 1 of 2

SYSTEM/NETWORK SETUP (page 1 of 2)

UNIT 01

S823 S824 S825 S826 S827 S828 S829 S830 S831 S832 S833

PASSWORD (Actual Level 0) Monitoring Address

UNIT

Configuration Safe Network Safe SW Verson

No No OK OK XP1.00.008.STD

to confirm for next/previous unit then

Monitoring Address—Sets the address used by the Liebert IntelliSlot® cards. This is set to 3 at the factory and should not be changed.

Unit Name—Identifies the unit from the local or remote display. This label will show at the top right of every screen that has monitoring or configuration of that unit

Configuration Safe—Saves or loads configuration settings for the control board that have been modified from the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load” will write the settings from the internal storage file to the application software. The internal file is updated every 12 hours automatically.

Network Safe—Saves or loads network settings for the control board that have been modified from the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load” will write the settings from the internal storage file to the application software.

SW Version—Contains the application software version loaded onto the Liebert iCOM.

Show 4 more labels / short text on this page
???? · Unit Name · to select parameter · to change parameter
Page 66 of the Liebert XDP160RC user manual — UNIT 01
Page 66 · click to enlarge
Page 66

Figure 66 System/Network Setup screen—Unit, page 2 of 2

SYSTEM/NETWORK SETUP (page 2 of 2)

UNIT 01

S834 S835 S836 S837 S838 S839 S840 S841 S842 S843 S844

PASSWORD (Actual Level 0) Monitoring Protocol IP Address Netmask Gateway MAC U2U Protocol U2U Address U2U Group Bootloader Variables Static RAM

Velocity V4 192.168.254.003 255.255.255.000 0.000.000.000 00:00:68:19:9B:42 GBP

1 1 No No OK OK

Monitoring Protocol—Selects the monitoring protocol. Velocity V4 is the factory default which will provide communications to the Liebert IntelliSlot housing. IGMnet will activate the 77/78 terminals for communication to the Liebert SiteLink(-E). Liebert Hironet is only used on Liebert HPM units.

IP Address—Contains the network address of the display. This address must be unique to every other device on the network. The factory default is 192.168.254.003.

Netmask—Defines which part of the IP address is used for the network. The factory default is 255.255.255.000.

Gateway—A gateway is a network point that acts as an entrance to another network. The factory default is 0.000.000.000.

MAC—The MAC address is a unique hardware identifier of the Ethernet device.

The following parameters (U2U Protocol, U2U Address and U2U Group) are for displaying other Liebert XDPs that are networked. The Liebert XDP does not perform Teamwork Operations.

U2U Protocol—Always set to GBP.

U2U Address—Unique identifier for each display on the network. Display addresses range from 1 to 32. Each display on the U2U network must have a different U2U address. Not currently used.

U2U Group—Creates zones or groups within a U2U network. Once a group number is selected the display will only see other devices with the same group number. The group number can be changed to view other devices in different groups. Not currently used.

Bootloader Variables—Indicates if there has been a change to the boot loader since it was last loaded. This parameter should only be activated by authorized service personnel.

Static RAM—Allows service personnel to clear and reboot the RAM of the control board. Only Emerson service personnel should perform this function.

Page 67 of the Liebert XDP160RC user manual — UNIT 01
Page 67 · click to enlarge
Page 67

Figure 67 Options Setup screen, page 1 of 2

OPTIONS SETUP (page 1 of 2)

UNIT 01

S401 S402 S403 S404 S405 S406 S407 S408 S409 S410 S411

PASSWORD (Actual Level 0) Autorestart Enabled Single Unit Auto Restart Unit Start Sequence Delay Control Delay Time Pump Start Time Delay Pump Wait Time Delay Pump Off Time Delay

5sec 1sec 1sec 10sec 10sec 5sec

Pump Short Cycle Delay

to confirm for next/previous unit then

Autorestart Enabled—Restarts the unit after a power cycle when set to Yes. When this parameter is set to No, the unit will not restart after a power cycle.

Single Unit Auto Restart—Sets a time delay for the unit to restart when the Auto Restart Enabled is set to Yes. The delay begins once the boot process has completed. This parameter allows units to be staggered On to reduce the amount of simultaneous power consumption after a loss of power.

Unit Start Sequence Delay—Not currently used.

Control Delay Time—Not currently used.

Pump Start Time Delay—Sets a time delay to ensure that refrigerant begins flowing when the pump starts. If refrigerant does not begin flowing before the user-set delay expires, the pump will be turned Off.

Pump Wait Time Delay—Sets the pump wait time delay to prevent the pump from continuing to run when refrigerant is not flowing. If a pump is running normally and refrigerant flow is lost, the pump will stay On for the specified time trying to re-establish refrigerant flow. If refrigerant flow resumes during the specified interval, the pump will continue operating. If the wait time expires and refrigerant flow has not resumed, the pump will shut down.

Pump Off Time Delay—Sets the length of time a pump will remain off when refrigerant flow is interrupted or stops. After the time delay has expired, the control will try to restart the pump.

Lead Pump—Sets which pump is the active pump. It can be set to PUMP 1 or PUMP 2. The control will operate the respective pump unless a loss of flow condition occurs. On a LOSS OF FLOW condition, the control will switch to the standby pump after the LOSS OF FLOW alarm time delay has elapsed and the LOSS OF FLOW alarm has been annunciated. The default is PUMP 1.

Pump Short Cycle Delay—Sets the time to lock Off the unit if it is unable to establish refrigerant flow within this set amount of time.

Show 4 more labels / short text on this page
???? Yes · 30min · to select parameter · to change parameter
Page 68 of the Liebert XDP160RC user manual — XXX.XX.XXX
Page 68 · click to enlarge
Page 68

Figure 68 Options Setup screen, page 2 of 2

OPTIONS SETUP (page 2 of 2)

UNIT 01

S412 S413 S414 S415 S416 S417 S418 S419 S420 S421 S422

PASSWORD (Actual Level 0) Valve Start Open Valve Start TD 3P Actuator Runtime 3P Actuator Direction Unit Off Valve % Open

30% 90sec 70sec Direct

to confirm for next/previous unit then

to select parameter to change parameter

Valve Start Open—Sets position of the valve when the unit starts.

Valve Start TD—Sets a time interval for the unit to complete startup and enter into normal operation.

3P Actuator Runtime—If Valve Control is selected for “Time” then this parameter sets the travel time of the valve to determine the full open and closed position of the valve. This parameter is set at the factory, based on the valve manufacturer’s specifications.

3P Actuator Direction—Sets if the valve is a “Direct” or “Reverse” acting valve.

Unit Off Valve % Open—Sets the valve position when the unit is Off.

Figure 69 Module Setup screen, page 1 of 20

MODULE SETUP (page 1 of 20) UNIT 01

S901 S902 S903 S904 S905 S906 S907 S908 S909 S910 S911 S912 S913

PASSWORD (Actual Level 0) NODE ID 81 CONDENSATION DETECTED LOCAL MODULE SHUTDOWN SENSOR FAILURE FAN FAILURE FAN CONTROL MODE DISABLE LOCAL BUTTON FLASH LED AT MODULE SET MODULE LABEL SUPPLY AIR TEMP LIMITS RETURN AIR TEMP LIMITS FIRMWARE VERSION

TYPE

DELAY

EN-DIS ENABLE ENABLE ENABLE ENABLE

15 15 30 30

ALM ALM ALM

OFF NO NO

A Z 81 High 80 Low 50 °F High 120 Low 60 °F

XXX.XX.XXX

30%

Page 69 of the Liebert XDP160RC user manual — XXX.XX.XXX
Page 69 · click to enlarge
Page 69

This screen selects the operation of an active alarm for each smart module. Each event can be enabled or disabled and can be set to operate as an alarm, a warning or a message. The delay is the time the control waits before reporting the event.

Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes the red LED on the display. Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event viewer/front display and flashes the red LED on the display. Message: Shows the event in the event viewer and on the front display.

Fan Control Type—Sets the fan control mode. Values can be OFF, ON, ON ALL and TEMP CNTL.

Disable Local Button—Disables the push button on the front of the smart module. To disable the push button, set the parameter to YES. To re-enable the push button, set the parameter to NO.

Flash LED at Module—Flashes the LED on the smart module when set to Yes.

Set Module Label—A four-character label consisting of two letters and two numerals. This is the standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or both labels can be used and are entered using this screen.

Supply Air Temp Limit—Sets the high and low supply air temperature to from the module. An alarm will occur if the temperature falls outside the limits.

Return Air Temp Limit—Sets the high and low return air temperature to from the module. An alarm will occur if the temperature falls outside the limits.

Firmware Version—Displays the firmware version installed on the smart module.

Figure 70 Module Setup screen, page 1 of 20

MODULE SETUP (page 1 of 20) UNIT 01

S901 S902 S903 S904 S905 S906 S907 S908 S909 S910 S911 S912 S913

PASSWORD (Actual Level 0) NODE ID 81 CONDENSATION DETECTED LOCAL MODULE SHUTDOWN SENSOR FAILURE FAN FAILURE FAN CONTROL MODE DISABLE LOCAL BUTTON FLASH LED AT MODULE SET MODULE LABEL SUPPLY AIR TEMP LIMITS RETURN AIR TEMP LIMITS FIRMWARE VERSION

TYPE

DELAY

EN-DIS ENABLE ENABLE ENABLE ENABLE

15 15 30 30

ALM ALM ALM

OFF NO NO

A Z 81 High 80 Low 50 °F High 120 Low 60 °F

XXX.XX.XXX

Page 70 of the Liebert XDP160RC user manual — 5.1 Checklist for Liebert XDP Startup
Page 70 · click to enlarge
Page 70

Start the Liebert XDP with Liebert iCOM

5.0 S TART THE L IEBERT XDP WITH L IEBERT I COM

5.1 Checklist for Liebert XDP Startup

! CAUTION Risk of piping and component rupture. May cause equipment damage or injury.

Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves.

NOTE The Liebert XDP160 requires a minimum load of 48kW (163,800BTU/H) before the system can be commissioned. This load can be supplied by actual user load in racks, by independent load banks or by the “Load Bank Testing” service of Emerson Network Power Liebert Services. To achieve the minimum load requirements, the capacity of all connected modules must total at least 48kW (163,800BTU/H). See Table 1.

1. Verify that bypass flow controllers were installed (if applicable), see Table 5. 2. Verify that the minimum load level of 48kW (163,800BTU/H) is present. 3. Check all isolation ball valves in the Liebert XDP and Liebert XD cooling module and verify that all are open. 4. Check rotation of the Liebert XDP’s pumps. On 460V units only—Hold the rotation device provided against the pump housing at the inspection screw prior to energizing the pumps. Counterclockwise indicates proper rotation; clockwise indicates incorrect rotation. On 208V and 400V units only, view the LED indicator on the pump. Green indicates proper rotation; Green and Red indicate incorrect rotation.

Table 13 Liebert XDP pump light indicator—208V and 400V units

Off Off The electricity supply has been switched Off or the pump has been cut out by the thermal switch.

On Off The electricity supply has been switched On. Normal operation.

On On The electricity supply has been switched On. The direction of rotation is wrong.

5. Check rotation of fans on Liebert XD cooling module units. 6. Verify that air is being discharged into the cold aisle. 7. Confirm that the total calculated refrigerant R-134a amount has been properly charged into the system (see 3.6 - Filling the Pumped Circuit—R-134a ). 8. Confirm that the remote temperature/humidity sensors provided have been installed in optimal locations (see 2.4 - Remote Sensor Installation—Proper Placement )

The Liebert XDP system is now ready to be turned ON.

Indicator Lights · Description Green Red

Page 71 of the Liebert XDP160RC user manual — 5.2 Starting the Liebert XDP with Liebert iCOM Controller
Page 71 · click to enlarge
Page 71

Start the Liebert XDP with Liebert iCOM

5.2 Starting the Liebert XDP with Liebert iCOM Controller

The Liebert XDP is started, stopped and controlled through the Liebert iCOM controller. Figure 24 shows the Liebert iCOM keypad.

1. Turn the Liebert XDP On with the user interface (I/O button). The factory-setting defaults Liebert XD module fans to On. When the Liebert XDP is turned On, the Liebert XD modules’ fans will turn On. Allow the system to attempt to start for at least 2 minutes. If the Liebert XDP pump cannot maintain flow and continues to switch over due to starting difficulties, refer to 7.0 - Troubleshooting. After remedying the problem, proceed to Step 2. 2. If constant flow is established, wait until the Liebert XDP has been operating for 10-15 minutes, then verify that the refrigerant level in the receiver sight glass is between the second and third level (see Figure 71). Add or remove charge, if necessary. 3. Check pressure differential functionality: The Liebert XDP system should be On. If it is Off: a. Turn the Liebert XDP On via user interface (I/O button). The factory-setting defaults Liebert XD module fans to On. When the Liebert XDP is turned On, the Liebert XD modules’ fans will turn On. If no “Loss of Flow” alarm is present—This suggests that there is flow. Test the pressure differential by closing the ball valve on either the suction line or discharge line to stop the flow. This should prompt an alarm for “loss of flow on P1.” This alarm confirms that the switch has opened on low pressure (below 6 psi; 41kPa; 0.41 bars). If a “Loss of Flow” alarm is present—This suggests that there is no flow. Verify that this is correctly annunciated by looking at the sight glass in the receiver. If a true no-flow condi tion exists, the level will not move. However, if there is flow, but the differential reading is faulty, the level will slowly drop, indicating flow, while the loss of flow alarm is annunciated. Check the pressure differential physically by making sure that the electrical connections are properly connected. Then check the pressure differential electrically by making sure that the unit has 24VAC across it.

Figure 71 System R-134a liquid level at 160kW load

Operation above sight glass #3 can make the system operate erratically and reduce cooling capacity. Reduce charge to recommended level.

For lightly loaded systems, the recommended operating level is sight glass #2.

Operation below sight glass #1 may cause loss of flow or cooling. Add charge to reach recommended level.

Sight Glasses 1, 2 & 3

Recommended operating level · Acceptable operating level

Page 72 of the Liebert XDP160RC user manual — 6.1 Alarm Descriptions
Page 72 · click to enlarge
Page 72

Alarm Descriptions and Solutions

6.0 A LARM D ESCRIPTIONS AND S OLUTIONS

6.1 Alarm Descriptions

CALL SERVICE—Activated when Customer Input 1 is configured for “Call Service” and 24VAC is applied to the input. This alarm is reset when the 24VAC is removed.

CONDENSATION DETECTED (optional)—Activated when water is detected at a cooling module. A 24VAC signal is applied to the condensation input on the control board using a pair of twisted wires or the alarm is sent via CANbus communication. When this alarm is active, the control will raise its refrigerant control point by 4°F (2.2°C). This alarm will reset when the alarms is acknowledged and the signal stops being sent from CANbus or condensation input. The alarm can also be reset by cycling the power. The main power must be cycled to remove the 4°F (2.2°C) offset.

CONTROL VALVE FAILURE—Activated when the chilled water control valve has been commanded to open or close by the control and no change is detected by the valve position signal. The alarm is reset when the main power is cycled.

CUSTOMER INPUT 1—Activated when a 24VAC signal is applied to the customer alarm input on the control board. This alarm will reset when the 24VAC signal stops being sent from the customer alarm input. WATER UNDER FLOOR, SMOKE DETECTED, CALL SERVICE, and COMP LOCK PD are possible designations for this alarm; they are set with the Unit Code.

FAN FAILURE (optional)—Activated when a 24VAC signal is applied to the fan failure input on the control board using a twisted pair of wires or the alarm is sent via CANbus communication. This alarm will reset when the alarms is acknowledged and the signal stops being sent from CANbus or fan failure input. The alarm can also be reset by cycling the power.

HIGH CW TEMP—Activated when the Supply CW sensor reads the chilled water temperature above the user-specified alarm setpoint. This alarm will reset when the reading from the refrigerant temperature sensor drops 5°F (2.8°C) below the user-specified setpoint and the alarm has been acknowledged.

HIGH DEW POINT—Activates when the calculated dew point at either Sensor A or B exceeds the user-specified alarm setpoint. The alarm will reset when the calculated room dew point from both Sensor A and Sensor B is 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.

HIGH REFRIGERANT TEMP—Activated when the refrigerant temperature sensor reads the refrigerant temperature above the user-specified alarm setpoint. This alarm will reset when the reading from the refrigerant temperature sensor drops 2°F (1.1°C) below the user-specified setpoint and the alarm has been acknowledged.

HIGH TEMP SENSOR A—Activated when the reading from Sensor A is above the user-specified alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.

HIGH TEMP SENSOR B—Activated when the reading from Sensor A is above the user-specified alarm setpoint. The alarm will reset when the reading from Sensor A drops 2°F (1.1°C) below the setpoint and the alarm has been acknowledged.

LOSS OF FLOW PUMP 1—Activated when Pump 1 is commanded to run and the differential pressure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting to start Pump 1 three times, the Liebert XDP will automatically switch to the other pump to establish flow. This alarm will reset when flow has been established on Pump 1 and the alarm has been acknowledged.

LOSS OF FLOW PUMP 2—Activated when Pump 2 is commanded to run and the differential pressure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting to start Pump 2 three times, the Liebert XDP will automatically switch to the other pump to establish flow. This alarm will reset when flow has been established on Pump 2 and the alarm has been acknowledged.

Page 73 of the Liebert XDP160RC user manual — 6.0 Alarm Descriptions and Solutions
Page 73 · click to enlarge
Page 73

Alarm Descriptions and Solutions

LOW MEMORY—Activated when the control board is low in memory resources. This alarm rests automatically as soon as memory consumption falls below the threshold.

LOW REFRIGERANT TEMP—Activated when the supply refrigerant temperature sensor temperature reading drops below the higher of the two calculated dew points, assuming that neither Sensor A or Sensor B has a sensor failure alarm. This alarm will reset when the refrigerant temperature sensor reads the refrigerant temperature above both of the two calculated dew points and the alarm has been acknowledged. This alarm can lock the unit Off. If this occurs, the main power must be cycled, or the Low Refrig Temp Alarm Code in the Service Diagnostics menu must be reset to 0.

LOW TEMP SENSOR A—Activated when the reading from Sensor A drops below the user-specified alarm setpoint. The alarm will reset when the reading from Sensor A rises 2°F (1.1°C) above the setpoint and the alarm has been acknowledged.

LOW TEMP SENSOR B—Activated when the reading from Sensor B drops below the user-specified alarm setpoint. The alarm will reset when the reading from Sensor B rises 2°F (1.1°C) above the setpoint and the alarm has been acknowledged.

NODEX CONDENSATION DETEC—Activated when condensation is detected on a smart module at CAN node ID X, where X is a value ranging from 81 to 100. This alarm resets when condensate is no longer detected. The main power must be cycled off to remove the 4°F (2.2°C) offset value.

NODEX FAN FAILURE—Activated when a fan failure occurs on a smart module at CAN node ID X, where X is a value ranging from 81 to 100. The alarm will rest when the fan returns to normal operation.

NODEX LOCAL SHUT DOWN—Activated when a smart module at CAN node ID X, where X is a value ranging from 81 to 100, has been shut down by an external signal. This alarm will reset when the remote shutdown input is deactivated.

NODEX RETURNAIR TEMPLIMT—Activated when the return air temperature (entering air temperature to the module) exceeds the user-specified return air temperature range on a smart module at CAN node ID X, where X is a value ranging from 81 to 100. This alarm will reset when the return air temperature return to with the user-specified range.

NODEX SENSOR FAILURE—Activated when a smart module at CAN node ID X, where X is a value ranging from 81 to 100, stops receiving a signal from one or more of its supply air, return air, or refrigerant temperature sensors. This alarm will reset when signals are detected from the module’s sensors.

NODEX SUPPLYAIR TEMPLIMT—Activated when the supply air temperature (temperature of the air leaving the module) exceeds the user-specified supply air temperature range on a smart module at CAN node ID X, where X is a value ranging from 81 to 100. This alarm will reset when the return air temperature return to with the user-specified range.

PUMP SHORT CYCLE—Activated when the Liebert XDP is trying to establish flow (differential pressure) and is unable to do so. The Liebert XDP will attempt three times to establish flow on a pump before trying the other pump. The control will keep cycling three times on one pump, then three times on the other pump until it is able to establish flow (differential pressure). If this cycling occurs for 30 minutes and the Liebert XDP still does not establish flow, a PUMP SHORT CYCLE alarm will be present. This alarm will shut down the Liebert XDP. To reset this alarm, the main power must be cycled.

RAM/BATTERY FAIL—Activated when the RAM backup battery or the RAM itself has failed. This requires a hardware replacement.

SENSOR A FAILURE—Activated when the controls no longer senses a signal from Sensor A. This alarm will reset when the signal is returned and the alarms has been acknowledged.

SENSOR B FAILURE— Activated when the controls no longer senses a signal from Sensor B. This alarm will reset when the signal is returned and the alarm has been acknowledged.

Page 74 of the Liebert XDP160RC user manual — Unit Is Off By Low Refrig Temp
Page 74 · click to enlarge
Page 74

Alarm Descriptions and Solutions

SMOKE DETECTED—Activated when the Customer Input 1 is configured for “Smoke” and 24VAC is applied to the input. This alarm is reset when the 24VAC is removed.

SUPPLY CW SENSOR FAILURE—Activated when the control no longer senses a signal from the Supply CW sensor. This alarm will reset when the signal is returned.

SUPPLY REFRIGERANT SENSOR FAILURE—Activated when the control no longer senses a signal from the supply refrigerant sensor. This alarm will reset when the signal is returned.

UNIT CODE MISSING—Activated when a valid unit code has not been entered and saved. To reset, enter valid unit code, save and execute.

WATER UNDER FLOOR—Activated when Customer Input 1 is configured for “Water Alarm” and 24VAC is applied to the input. This alarm is reset when the 24VAC is removed.

6.2 Warning Descriptions

LOSS OF POWER—Activated when the unit is On and operational and 24VAC power to the control is lost. This alarm will be emitted when power is restored to the control. The Liebert XDP will restart at a user-defined time delay after power is restored. Once activated, the alarm will remain activated for 30 minutes.

PUMP 1 HRS EXCEED—Activated when the Pump 1 Actual Hours exceeds the user-specified limit. To reset, Actual Hours must be reset to 0.

PUMP 2 HRS EXCEED—Activated when the Pump 2 Actual Hours exceeds the user-specified limit. To reset, Actual Hours must be reset to 0.

6.3 System Shutdown Causes

Unit Is Off By Refrig Sens Fail

The control has lost its signal from the refrigerant temperature sensor. The control has no way of controlling the refrigerant temperature, so the unit is shut off. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.

Unit Is Off By High CW Temp

The entering chilled water temperature is too high to keep the refrigerant pump(s) running normally. If a HIGH CW TEMP alarm occurs and the refrigerant pump loses flow (differential pressure), then the Liebert XDP will go into a pre-chill mode. The Liebert XDP can attempt to start again only if the entering chilled water temperature drops below the HIGH CW TEMP setpoint.

Unit Is Off By Pump Short Cycle

The control was unable to get a pump started upon startup or after a loss of differential pressure. The control looks at the SHORT CYCLE time delay. If it cannot establish differential pressure within that amount of time, the unit is shut down. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.

Unit Is Off By Low Refrig Temp

The control was unable to raise the refrigerant temperature to the calculated refrigerant temperature control point. The unit is shut down because if the control cannot raise the refrigerant temperature to the calculated refrigerant temperature control point, water may condense on the refrigerant piping and receiving coils. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.

Page 75 of the Liebert XDP160RC user manual — 7.0 T ROUBLESHOOTING
Page 75 · click to enlarge
Page 75

7.0 T ROUBLESHOOTING

Table 14 Troubleshooting the Liebert XDP

Symptom Possible Cause Check or Remedy

No main power Check L1, L2 and L3 for rated voltage.

Loose electrical connections Tighten connections.

Pump Will Not Energize

Overloads tripped Allow pump to cool. Check amp draw. Tripped circuit breaker Check circuit breaker to pump(s).

Incorrect phase wiring See Table 13.

No chilled water Check and verify that there is supply chilled water to the Liebert XDP.

Isolation valve(s) on pump suction and/or discharge is closed. Open all isolation valves completely during normal operation.

Pump Will Not Start or Run

Check and verify that the chilled water temperature setpoint is at 50°F (10°C) or lower and that there is flow on the chilled water side.

Supply chilled water is too high

Liebert XD cooling modules are Off Check Liebert XD cooling modules to make sure that they are On prior to starting the Liebert XDP.

Check alarm(s) history on Liebert XDP. The Liebert XDP was operating below the dew point for a significant amount of time. Check humidity in conditioned space, lower humidity if necessary to allow Liebert XDP to operate at a lower temperature. (Disconnect must be switched to Off then back On to allow Liebert XDP to reset itself).

Low Refrigerant Temperature (high dew point)

Check both differential pressure settings. If not within 6 psi, ± 1 psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then manually change accordingly.

Pressure switch not making contact

Not enough charge See 5.1 - Checklist for Liebert XDP Startup.

Pump Will Not Start Chilled water valve not closing completely.

Wait at least 10 minutes before calibrating. Access the Advanced Menu>Factory Settings>Calibrate Actuator. Contact Liebert Services for assistance, 1-800-543-2778.

Cavitation due to vapor in pump Check for adequate charge in system, refer to the User's Manual. 5.1 - Checklist for Liebert XDP Startup

Worn motor bearings Replace pump

Pump is rotating in reverse See Table 13.

1. Check humidity of the room along with the location of remote sensors. Make sure that the sensors are not in a cold area where there is insufficient air flow for accurate, representative readings. 2. Chilled Water temperature is too cold. 3. Load is too light.

Loss of power When power is restored, the Liebert XDP will automatically restart.

Liebert XDP (Pump) Suddenly Stops

Clogged filter dryer and/or impeller Clean out debris

Leak in system - loss of charge Check the entire system for leaks with a refrigerant sniffer. Repair as necessary.

Low chilled water temperature alarm and loss of flow Pump X alarm Check supply chilled water temperature.

Supply refrigerant sensor failure alarm

Check wiring.

Call service. Clogged Filter Dryer and/or Impeller

Debris or other contaminants in refrigerant Replace.

Pipe Rattle Loose pipe connections Check pipe connections.

Motor operates but valve won't open Check linkage for adjustment and be sure that it is tight on the valve.

No 24 VAC power to motor Check for 24 VAC between P52-1 and P52-4. No signal from control Check 24 VAC at P22-1 (close) or P22-3 (open).

Chilled Water Valve Not Working

Unplug P22 from the board. Jumper P22-5 to P52-4 for grounding, then jumper P22-1 to P52-1 to drive close. Remove jumper to close and then jumper P22-3 to P52-1 to drive open. If motor fails to work, replace it.

Show 4 more labels / short text on this page
Troubleshooting · Pump Noisy · Low refrigerant temperature · Motor not operating
Page 76 of the Liebert XDP160RC user manual — 7.0 Troubleshooting
Page 76 · click to enlarge
Page 76

Table 14 Troubleshooting the Liebert XDP (continued)

Symptom Possible Cause Check or Remedy

Check control panel for welded contactor contacts or welded overload contacts

Replace defective components.

Main 24VAC Fuse Trips Shorts or loose connections Check the wiring connections of the 24 VAC circuit. Faulty circuit board Replace the circuit board.

R-134a pump loop overcharged While pump is running R-134a receiver level must be within recommended levels (see Figure 71). R-134a pump loop undercharged

Filter dryer clogged See Clogged Filter Dryer and/or Impeller symptom and remedy.

Liebert XDP is Off Check status of the Liebert XDP at the user interface. Turn system On at I/O button if system is Off.

Check temperature and relative humidity (RH) of room. Lower RH setpoint if necessary to lower dew point. At normal room temperature of 68°F (20°C), the RH should be set to 50% or lower.

Room Becomes Too Warm

Liebert XD cooling modules are Off Check Liebert XD cooling modules to make sure that they are On before starting the Liebert XDP.

Minimum room temperature setpoint is too high

Check the setpoint in the User Setpoints menu (see Figure 43).

Temperature/humidity sensors incorrectly placed

Place the sensor on the return air side of the primary air mover (eg., Liebert DS). Do not install the sensor near unsealed doors, windows or similar areas.

Clogged strainer Clean or replace strainer

Reduced Chilled Water Flow Rate

Fouled heat exchanger (no strainer installed) Replace heat exchanger and install 20-40 mess strainer

Clogged strainer Clean or replace strainer

Fouled heat exchanger (no strainer installed) Replace heat exchanger and install 20-40 mess strainer

Show 5 more labels / short text on this page
Troubleshooting · Motor Burnout · Unstable Pump Operation · High dew point · Increased Refrigerant Temperature
Page 77 of the Liebert XDP160RC user manual — 8.1 Fluorinated Greenhouse Gas Requirements
Page 77 · click to enlarge
Page 77

8.0 M AINTENANCE

The Liebert XD system components require little maintenance when proper fluid levels are maintained and proper startup and operation procedures are followed. The following tasks should be performed at the intervals stated:

1. Clean or replace chilled water strainer annually. Adjust accordingly based on purity of chilled water. 2. Check sight glass level of receiver every 4-6 weeks. During normal operation, the level should be at or above the second sight glass. 3. Check system for leaks every 4-6 weeks.

8.1 Fluorinated Greenhouse Gas Requirements

Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f- gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F- gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.

The F-Gas Regulation requires operators to use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas during equipment service and maintenance and before disposing of equipment.

Refer to the full regulation for additional details.

Maintenance

Page 78 of the Liebert XDP160RC user manual — 9.0 S PECIFICATIONS
Page 78 · click to enlarge
Page 78

9.0 S PECIFICATIONS

Table 15 Liebert XDP160 specifications

Models XDP160RC--4 XDP160RA--4 XDP160RM--4

160kW / 46 Tons, 60Hz 140kW / 40 Tons, 50Hz

Each capacity is based on 45ºF (7ºC) entering water temperature and 140gpm (530lpm) water flow rate. Capacity is reduced when glycol mixtures are used in place of 100% water.

Minimum Load 30% of nominal system capacity or 48kW (163,800BTU/H)

Input 208V/3ph/60Hz 460V/3/ph60Hz 380/415V/3ph/50Hz

Full Load Amps 4A 2.1A 2.3A

Height – Unit only 78 (1981)

Height – As shipped 83 (2108)

Unit only 821 (372)

Shipping weight Domestic990 (449); Export: 1067 (484)

Installed, with refrigerant and

chilled water 1038 (471)

Refrigerant supply to Liebert XD

cooling module 1-1/8" OD, Cu

Refrigerant return from Liebert XD

cooling module 2-1/8" OD, Cu

Chilled water supply and return 2-5/8" OD, Cu

Control valve 2-way, 2" nominal; 35 PSIG close-off pressure rating; 150 PSIG maximum allowable pressure

Pressure Drop – Chilled Water Side

20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate, control valve fully open

Temperature Rise – Chilled Water Side at rated flow, °F (°C) 8.0 (4.4) 6.9 (3.8)

Number of Liebert XD cooling units connected, maximum (minimum)

Liebert XDCF10 16 (5)

Liebert XDH20 8 (3)

Liebert XDH32 5 (2)

Liebert XDV8 20 (6)

Liebert XDV10 16 (5)

Liebert XDO16 10 (3)

Liebert XDO20 8 (3)

Liebert XDR20 8 (3)

Cabinet Exterior Finish Black, matte finish, heat-fused powder coat

Operating Ambient Temperature, Maximum, °F (°C) 86 (30)

Approvals CSA 60Hz CE 50Hz

Show 9 more labels / short text on this page
Specifications · Cooling Capacity, Nominal · Electrical Requirements · Dimensions, inches (mm) · Width 38 (965) · Depth 34 (864) · Weight, lb (kg) · Pipe Connections · Agency
Page 79 of the Liebert XDP160RC user manual — 2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC
Page 79 · click to enlarge
Page 79

C OMPLIANCE WITH E UROPEAN U NION D IRECTIVES

Liebert XDP160RC — C OMPLIANCE WITH E UROPEAN U NION D IRECTIVES diagram (page 79)
Fig. 41

Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 USA

Il Produttore dichiara che, se munito di marchio CE, il prodotto è conforme alle direttive dell'Unione europea: The Manufacturer hereby declares that this product, when bearing the CE mark, conforms to the European Union directives: Der Hersteller erklärt hiermit, dass das vorliegende Produkt, sollte es die CE-Kennzeichnung tragen, den folgenden Richtlinien der Europäischen Union entspricht: Le fabricant déclare par la présente que ce produit, portant la marque CE, est conforme aux directives de l'Union européenne : El fabricante declara por la presente que si este producto lleva el marcado CE es conforme con las directivas de la Unión Europea: O fabricante declara por este meio que este produto, quando ostenta a marca CE, está em conformidade com as directivas da União Europeia: Tillverkaren tillkännager härmed att den här produkten, när den är CE-märkt, överensstämmer med EU:s direktiv: De fabrikant verklaart hierbij dat dit product, indien het van de CE-markering is voorzien, conform de EU-richtlijnen is: Valmistaja vakuuttaa täten, että mikäli tuotteessa on CE-merkintä, se täyttää seuraavien EU-direktiivien vaatimukset: Produsenten erklærer herved at dette produktet, når det er CE-merket, er i samsvar med EU-direktiver: Producenten erklærer hermed, at dette produkt overholder EU's direktiver, når det bærer CE-mærket: Ο Κατασκευαστής δηλώνει ότι το προϊόν αυτό, το οποίο φέρει σήμανση CE, είναι σύμμορφο με τις οδηγίες της Ε.Ε.:

2006/42/EC; 2004/108/EC; 2006/95/EC; 97/23/EC

Page 80 of the Liebert XDP160RC user manual — SL-16644_REV04_01-12
Page 80 · click to enlarge
Page 80

Ensuring The High Availability Of Mission-Critical Data And Applications.

Technical Support / Service

Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™

Web Site www.liebert.com

from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.

Monitoring liebert.monitoring@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Single-Phase UPS & Server Cabinets

liebert.upstech@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Three-Phase UPS & Power Systems

800-543-2378 Outside North America614-841-6598
800-543-2778 Outside the United States614-888-0246

Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center

Philippines +63 2 687 6615 Fax: +63 2 730 9572

SL-16644_REV04_01-12

Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com

Embedded Computing Embedded Power

Racks & Integrated Cabinets Services

Power Switching & Controls Precision Cooling

Infrastructure Management & Monitoring

Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2008 Emerson Electric Co.

Show 6 more labels / short text on this page
Environmental Systems · Pasig City 1605 · AC Power Connectivity · Outside Plant · DC Power · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
XDIO Smart Module Setup of alarms and events. Set temperature limits for supply and return sensors. Label smart modules, view firmware version p.47
XDIO Smart Module Setup of alarms and events. Set temperature limits for supply and return sensors. Label smart modules, view firmware version p.47
Pump Will Not EnergizeNo main powerCheck L1, L2 and L3 for rated voltage. p.75
Pump Will Not EnergizeLoose electrical connectionsTighten connections. p.75
Pump Will Not EnergizeOverloads trippedAllow pump to cool. Check amp draw. p.75
Pump Will Not EnergizeTripped circuit breakerCheck circuit breaker to pump(s). p.75
Pump Will Not EnergizeIncorrect phase wiringSee Table 13. p.75
Pump Will Not Start or RunNo chilled waterCheck and verify that there is supply chilled water to the Liebert XDP. p.75
Pump Will Not Start or RunIsolation valve(s) on pump suction and/or discharge is closed.Open all isolation valves completely during normal operation. p.75
Pump Will Not Start or RunSupply chilled water is too highCheck and verify that the chilled water temperature setpoint is at 50°F (10°C) or lower and that there is flow on the chilled water side. p.75
Pump Will Not Start or RunLiebert XD cooling modules are OffCheck Liebert XD cooling modules to make sure that they are On prior to starting the Liebert XDP. p.75
Pump Will Not Start or RunLow Refrigerant Temperature (high dew point)Check alarm(s) history on Liebert XDP. The Liebert XDP was operating below the dew point for a significant amount of time. Check humidity in conditioned space, lower humidity if necessary to allow Liebert XDP to operate at a lower temperature. (Disconnect must be switched to Off then back On to allow Liebert XDP to reset itself). p.75
Pump Will Not Start or RunPressure switch not making contactCheck both differential pressure settings. If not within 6 psi, ± 1 psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then manually change accordingly. p.75
Pump Will Not Start or RunNot enough chargeSee 5.1 - Checklist for Liebert XDP Startup. p.75
Pump Will Not StartChilled water valve not closing completely.Wait at least 10 minutes before calibrating. Access the Advanced Menu>Factory Settings>Calibrate Actuator. Contact Liebert Services for assistance, 1-800-543-2778. p.75
Pump NoisyCavitation due to vapor in pumpCheck for adequate charge in system, refer to the User's Manual. 5.1 - Checklist for Liebert XDP Startup p.75
Pump NoisyWorn motor bearingsReplace pump p.75
Pump NoisyPump is rotating in reverseSee Table 13. p.75
Liebert XDP (Pump) Suddenly StopsLow refrigerant temperature1. Check humidity of the room along with the location of remote sensors. Make sure that the sensors are not in a cold area where there is insufficient air flow for accurate, representative readings. 2. Chilled Water temperature is too cold. 3. Load is too light. p.75
Liebert XDP (Pump) Suddenly StopsLoss of powerWhen power is restored, the Liebert XDP will automatically restart. p.75
Liebert XDP (Pump) Suddenly StopsClogged filter dryer and/or impellerClean out debris p.75
Liebert XDP (Pump) Suddenly StopsLeak in system - loss of chargeCheck the entire system for leaks with a refrigerant sniffer. Repair as necessary. p.75
Liebert XDP (Pump) Suddenly StopsLow chilled water temperature alarm and loss of flow Pump X alarmCheck supply chilled water temperature. p.75
Liebert XDP (Pump) Suddenly StopsSupply refrigerant sensor failure alarmCheck wiring. p.75
Liebert XDP (Pump) Suddenly StopsCall service. p.75
Clogged Filter Dryer and/or ImpellerDebris or other contaminants in refrigerantReplace. p.75
Pipe RattleLoose pipe connectionsCheck pipe connections. p.75
Chilled Water Valve Not WorkingMotor operates but valve won't openCheck linkage for adjustment and be sure that it is tight on the valve. p.75
Chilled Water Valve Not WorkingNo 24 VAC power to motorCheck for 24 VAC between P52-1 and P52-4. p.75
Chilled Water Valve Not WorkingNo signal from controlCheck 24 VAC at P22-1 (close) or P22-3 (open). p.75
Chilled Water Valve Not WorkingMotor not operatingUnplug P22 from the board. Jumper P22-5 to P52-4 for grounding, then jumper P22-1 to P52-1 to drive close. Remove jumper to close and then jumper P22-3 to P52-1 to drive open. If motor fails to work, replace it. p.75
Motor BurnoutCheck control panel for welded contactor contacts or welded overload contactsReplace defective components. p.76
Main 24VAC Fuse TripsShorts or loose connectionsCheck the wiring connections of the 24 VAC circuit. p.76
Main 24VAC Fuse TripsFaulty circuit boardReplace the circuit board. p.76
Unstable Pump OperationR-134a pump loop overchargedWhile pump is running R-134a receiver level must be within recommended levels (see Figure 71). p.76
Unstable Pump OperationR-134a pump loop undercharged p.76
Unstable Pump OperationFilter dryer cloggedSee Clogged Filter Dryer and/or Impeller symptom and remedy. p.76
Room Becomes Too WarmLiebert XDP is OffCheck status of the Liebert XDP at the user interface. Turn system On at I/O button if system is Off. p.76
Room Becomes Too WarmHigh dew pointCheck temperature and relative humidity (RH) of room. Lower RH setpoint if necessary to lower dew point. At normal room temperature of 68°F (20°C), the RH should be set to 50% or lower. p.76
Room Becomes Too WarmLiebert XD cooling modules are OffCheck Liebert XD cooling modules to make sure that they are On before starting the Liebert XDP. p.76
Room Becomes Too WarmMinimum room temperature setpoint is too highCheck the setpoint in the User Setpoints menu (see Figure 43). p.76
Room Becomes Too WarmTemperature/humidity sensors incorrectly placedPlace the sensor on the return air side of the primary air mover (eg., Liebert DS). Do not install the sensor near unsealed doors, windows or similar areas. p.76
Reduced Chilled Water Flow RateClogged strainerClean or replace strainer p.76
Reduced Chilled Water Flow RateFouled heat exchanger (no strainer installed)Replace heat exchanger and install 20-40 mess strainer p.76
Increased Refrigerant TemperatureClogged strainerClean or replace strainer p.76
Increased Refrigerant TemperatureFouled heat exchanger (no strainer installed)Replace heat exchanger and install 20-40 mess strainer p.76

Ask about the Liebert XDP160RC

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert XDP160RC

Be the first to ask — other owners or our team will answer.

Original document

Liebert XDP160RC manual PDF

80 pages·2.8 MB·Refrigerator·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…