! WARNING Risk of electric shock. Can cause injury or death. Disconnect local and remote power supplies before working within. Before proceeding with installation of XD cooling unit’s, read all instructions, verify that all the parts are included, and check the nameplate to be sure the XD cooling unit’s voltage matches available utility power. Follow all local codes.
! WARNING Risk of unit falling over when installed on top of cabinet. Can cause property damage, injury or death. The XDV is top-heavy. Use extreme caution and care when moving and installing this unit.
! WARNING Risk of explosive discharge. Can cause equipment damage, injury or death. Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without follow recommended procedures for repair, maintenance and replacement of components. Installing pressure relief valves in field piping that may become isolated by service valves.
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo- sphere.
The F-Gas Regulation also requires operators to use use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.


6.8 Connecting Liebert XD Flex Pipe to Liebert XDV Modules 25
6.9 Connecting a Liebert XDV with Liebert Flex Pipe to an Operational Liebert XD System 26
6.10 Disconnecting a Liebert XDV With Liebert Flex Pipe From a Liebert XD System 28
6.11 Insulation 29
7.0 ELECTRICAL 30
7.1 Connecting High Voltage Cables for CSA/C-US Certified Units 30
7.2 Connecting Low Voltage Wiring—Optional 32
8.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP 33
8.1 Checklist for Proper Installation 33
8.2 Charging with Refrigerant and Starting the Liebert XD System 33
9.0 OPERATION 34
9.1 Start the Liebert XDV 34
10.0 MAINTENANCE 35
10.1 Fluorinated Greenhouse Gas Requirements 35
10.2 Internal Access 35 10.2.1 Accessing Internal Electrical Components 36
11.0 SPECIFICATIONS 38




Liebert XDV Component Locations and Model Number Nomenclature
1.0 LIEBERT XDV COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATURE
Figure 1 Liebert XDV component locations

Figure 2 Liebert XDV model number nomenclature
XD V B K —
*
S= 230V, 1ph-50Hz T=208-240V-1ph-60Hz,
Packaging E = Export
level B = Base unit D = Unit with
— = Hard Piped P = Pre-charged (one-shot) Coupling) R = Removable Coupling

This document must be used together with site specific documentation and documentation for other parts of the system.
Each Liebert XDV module is to be securely mounted either on the top of a computer cabinet or rack or above the heat-producing equipment. Mounting the Liebert XDV above the rack requires Liebert’s optional mounting kit. The units are designed to be mounted without modification on Liebert Foundation™ cabinets. Mount- ing clips included with the Liebert XDV permit installation on other manufacturers’ cabinets and racks. The clips also can be used with the Foundation for stronger attachment. Determine whether the Liebert XDV includes the condensate detection option (factory-installed). This option will require separate low voltage connections to a monitoring unit. To minimize the possibility of condensation, insulate all piping between the Liebert XDV and the Lie- bert XDP or Liebert XDC.
Table 1 Application limits
2.4.1 Room Preparation The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either rubber or plastic.
Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly controlled. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site. Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.
Installation

The Liebert XDV cooling system is designed to be attached to the top of a computer cabinet or rack containing heat dissipating equipment. Two fans draw hot air exhausted from the equipment or from the hot aisle, pass it through a cooling coil and discharge cool air back down to the cold aisle, where the equipment's air intake is located. The Liebert XDV comes from the factory ready to draw heated air through a perforated grille on the back of the unit. The Liebert XDV is easily modified to draw hot air through the bottom of the unit, should that cooling method be better suited to your application.
The complete system consists of Liebert XDV modules, Liebert XDP or Liebert XDC coolant distribu- tion units, power and signal cabling and interconnecting piping, see Figure 3 below.
A condensate detection option gives notification if any condensation occurs in the Liebert XDV.
Figure 3 Liebert XDV hydraulic diagram
Liebert XD Cooling Module *
Liebert XD Cooling Module *
Liebert XD Cooling Module *
Liebert XD Cooling Module *
* Liebert XDCF, XDH, XDO or XDV
When the Liebert XDV is delivered, inspect all items for either visible or concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative. If you later find any concealed damage, report it to the shipping company and your local Liebert representative.
Check to be sure all required assemblies and parts have been received.
The Liebert XDV is shipped in a protective carton and secured to a pallet (see Figures 5 and 6). Do not remove these protective items from the Liebert XDV before it is at the installation location. When unpacking and handling the Liebert XDV, exercise extra care to prevent damage.

Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the bill of lading. Carefully inspect all items for either visible or concealed damage. Damage should be immedi- ately reported to the carrier and a damage claim filed with a copy sent to Liebert Corporation or to your sales representative.
! CAUTION Risk of sudden refrigerant discharge. Can cause loss of charge and minor injury. If the optional pre-charged option is chosen, the Liebert XDV unit is shipped with a full charge of R-134a refrigerant under pressure. Do not remove the pipe caps or plugs before the unit is ready for connection to Liebert XD Piping. Supply and return fittings on the pre-charged Liebert XDV units are one-shot connections. Do not disconnect one-shot connections after they have been connected. Disconnection will release pressurized R-134a refrigerant from the Liebert XDV.
R
All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
! WARNING Risk of improper handling. Can cause equipment damage, injury or death. Read all of the following instructions before attempting to move, lift, remove packaging from, or preparing unit for installation. ! CAUTION Risk of sharp edges, splinters and exposed fasteners can cause injury. Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from, or prepare unit for installation.
Risk of unit damage if improperly stored. Keep the unit indoors and protected from dampness, freezing temperatures and contact damage. NOTICE
Risk of damage from forklift. Improper handling with the forklift can cause exterior and/or underside damage. Keep tines of the forklift level and at a height suitable to fit below the skid.
Figure 4 Recommended unit handling equipment
General product information · Forklift Pallet Jack

If possible, transport the unit using a forklift or pallet jack.
Domestic Packaging 1. Remove outer packaging when ready to install the Liebert XDV. 2. Keep the Liebert XDV covered by the unit bag until removal from pallet.
Figure 5 Removing domestic shipping package
Plastic bag used for shipping not shown for clarity.
Do not use unit piping to lift or move the Liebert XDV

Export Packaging 1. Unbend all metal tabs as indicated in Step 1 in Figure 6. 2. Remove outer packaging when ready to install the Liebert XDV. 3. Keep the Liebert XDV covered by the unit bag until removal from pallet. 4. Do not use unit piping to lift or move the Liebert XDV.
Figure 6 Removing export shipping package
Plastic bag used for shipping not shown for clarity.

Do not use unit piping to lift or move the Liebert XDV
General product information

Removing the Liebert XDV from the Pallet 1. Unfold the unit bag to expose the Liebert XDV. 2. Verify the nameplate information found on the Liebert XDV against the bill of lading. If the information does not match the product specified, contact your local Liebert sales representative. 3. At least two properly trained personnel may lift the Liebert XDV off the pallet and onto a flat surface. 4. To protect the Liebert XDV’s paint, lay non-abrasive material, longer than the unit, on the flat surface before moving the Liebert XDV.
Figure 7 Removing Liebert XDV from shipping pallet
Removing the Liebert XDV from its shipping pallet requires two people.
General product information

Liebert XDVs should be placed above or on top of the cabinets that generate the greatest amount of heat. If heat loads are dispersed evenly throughout the room, the Liebert XDV modules may be spread out accordingly. The Liebert XDV is engineered to fit atop computer enclosure cabinets. Figure 8, below, illustrates the unit’s dimensions and the location of pipes, the fan tray and power connections. (An optional kit is available to permit suspending the Liebert XDV from either Unistruts or from the overhead struc- ture; see 5.2 - Suspended Mounting Method.).
Figure 8 Liebert XDV dimensions


Liebert XDV With Pre-charged Option (all dimensions except piping height are the same as for the hard-piped setup, see Table 2) Liebert XDV With Hard-piped Arrangement
Table 2 Dimensional data

Mechanical Considerations

The Liebert XDV comes from the factory with the air intake on the rear of the unit. If required for your application, this can be changed so that the Liebert XDV takes in heated air from the bottom. This is done more easily and safely before the unit is mounted on a computer cabinet.
! WARNING Risk of high-speed moving parts. Can cause death, injury and equipment damage. Before opening the Liebert XDV, shut the unit off and disconnect all electrical power. Wait for the Liebert XDV’s fans to stop rotating before beginning to open the unit.
To change the air intake:
1. Loosen the six screws holding the grille on the rear of the Liebert XDV (see Figure 9). 2. Remove the grille and lay it aside for use later. 3. Remove the channel bracket holding the two solid metal plates to the bottom of the Liebert XDV. It is secured with two screws, one on either end. 4. Lift the two solid plates out of the bottom of the Liebert XDV. 5. Optional—replace the channel bracket, securing it with the two screws removed in Step 3. 6. Lay the perforated grille down with the screws pointing up 7. Lay the two solid plates on the grille with the screws through the matching holes of the plates. 8. Hold the grille and plates together and attach the assembly to the rear of the Liebert XDV with the screws.
Figure 9 Changing the Liebert XDV’s air intake location

Remove rear inlet grille, taking care not to loosen the screws. Remove screws and channel bracket from base of unit, remove solid plates. Using the screws from the rear grille, reinstall the solid plates on the exterior rear of the unit. Place rear grille in a secure area for future use.
Mechanical Considerations

Mounting the Liebert XDV
The Liebert XDV module must be securely attached to the top of the computer cabinet or, alterna- tively, suspended above the cabinet. For mounting atop the computer cabinet, see 5.1 - Mounting the Liebert XDV on Top of the Cabinet; to hang the Liebert XDV above the computer cabinet, refer to 5.2 - Suspended Mounting Method. Be sure to follow all applicable codes.
! WARNING Risk of top-heavy cabinet falling. Can cause equipment damage, injury or death. A lightly loaded cabinet may become top-heavy after a Liebert XDV is mounted on it, causing the cabinet to tip over, possibly resulting in serious injury.
Before beginning to place the Liebert XDV on the cabinet, ascertain whether the cabinet or rack requires additional stabilization, and secure the cabinet to the floor if necessary to prevent tip- over.
Always use at least two persons to mount the Liebert XDV on top of a cabinet.
The Liebert XDV may be installed on a computer cabinet by securing it with either the two included bolts, the two included clips or both the bolts and clips. The Liebert XDV has mounting holes below the fans that match holes in the Liebert Foundation com- puter system cabinet. Other cabinets may require that holes be drilled to accommodate the bolts or the clips.
5.1.1 Bolting Liebert XDV to Top of Cabinet To mount the Liebert XDV: 1. With at least one additional person, lift the Liebert XDV and set it down on top of the cabinet. The front edge of the Liebert XDV should be even with the front edge of the cabinet. See Figure 10.
Figure 10 Positioning the Liebert XDV
CORRECT Liebert XDV is flush with
INCORRECT
is too far from front edge
2. If your cabinet has mounting holes matching those on the Liebert XDV, align the Liebert XDV properly and insert the bolts from the bottom of the cabinet and secure them to the factory- installed cage nuts (see Figure 11). Tighten the bolts. If your cabinet’s mounting holes do not match those on the Liebert XDV, drill holes as required. To prevent metal shavings and particles from falling into the equipment in the cabinet or into the Liebert XDV, use a vacuum or other method to collect them while drilling the holes. After drilling the holes, insert bolts from the bottom of the cabinet and secure them to the factory- installed cage nuts (see Figure 11). Tighten the bolts. If also using mounting clips in conjunction with bolting method above, see 5.1.2 - Using Sup- plied Clips for Mounting.

Mounting the Liebert XDV
Figure 11 Mounting hole locations—standard mounting method

Fan tray removed to show mounting location(s) of 1/4" - 20 bolts
Figure 12 Mounting hole locations—alternate mounting points


Mounting the Liebert XDV
5.1.2 Using Supplied Clips for Mounting 1. Attach the mounting clips to the back of the Liebert XDV by fitting them into the machined slots. Tighten the bolts. 2. If your cabinet has mounting holes in position for the clips, align the Liebert XDV properly and insert the bolts from the bottom of the cabinet and secure them with the included lock washers and nuts (see Figure 13). Tighten the nuts. If your cabinet’s mounting holes do not match the clips, drill holes as required. To prevent- ing metal shavings and particles from falling into the equipment in the cabinet or into the Liebert XDV, use a vacuum or other method to collect them while drilling the holes. After drilling the holes, insert bolts from the bottom of the cabinet and secure them with lock washers and nuts (see Figure 13). Tighten the nuts and bolts. If also using mounting clips in conjunction with bolting method above, see 5.1.1 - Bolting Lie- bert XDV to Top of Cabinet.
Figure 13 Mounting clip placement

Liebert Foundation shown without panels for clarity. Mounting holes shown may not match all cabinets.

Mounting the Liebert XDV
The Liebert XDV also may be mounted above the cabinet by suspending it either from overhead com- ponents or from Unistruts above the cabinets (see Figures 15 and 16). An optional kit available from Liebert will simplify mounting the Liebert XDV above the computer cabinet.
Each suspended-mounting method requires that the supporting components be strong enough to sup- port the Liebert XDV’s weight with coolant, 79 lb. (36kg). Each method also requires that the Liebert XDV’s placement above the computer cabinet meets the criteria in Figure 10.
To ensure efficient cooling, a baffle or similar object must be installed between the suspended Liebert XDV and the computer cabinet (see Figure 16). The baffle’s purpose is to prevent the Liebert XDV from drawing in the cooled air that it has just discharged.
Figure 14 Dimensions—optional external hanging brackets
2-1/2" (64mm)
7/16" (11mm) 3" (76mm)
H
7/8" (22mm)
4" (102mm)
DPN000770 Pg. 10, Rev. 5 Front View , Left Side
Table 3 Suspension hardware and bracket dimensional data
Bracket Kit Part # "H"
to be Suspended Brackets in Kit
180427G11, 180427G15 34-5/16 (872) 1 4
180427G22* 18-11/16 (474) 2 8 33 (838)
* Bracket kit for double-stacked Liebert XDVs
Liebert XDV Units

Mounting the Liebert XDV
The Liebert XDV may be bolted to customer-supplied Unistruts. The height of the Unistruts above the computer cabinet must be adequate to accommodate the combined height of the Liebert XDV and the baffle.
To suspend the Liebert XDV from a Unistrut system:
Figure 15 Suspending Liebert XDV from Unistruts

Bolt 3/8" -16; nut and washer provided in kit
Bolt a bracket to each corner of the Liebert XDV
To suspend the Liebert XDV from the overhead structure using the optional overhead mounting kit and field-supplied all-thread bolts:
1. Bolt the hangers to each corner of the Liebert XDV, inserting the Liebert-supplied bolts into factory-fabricated holes in the bottom of the Liebert XDV. 2. Tighten all bolts firmly, taking care not to overtighten the bolts. 3. Install the field-supplied all-thread bolts into the overhead structure, securing them to components so they will match the layout of the brackets 4. Using a lifting mechanism, raise the Liebert XDV inserting the all-thread bolts through the bolt holes in the brackets 5. Install field-supplied nuts and washers, on the all-thread bolts, placing them on the bolts at the level desired for hanging the Liebert XDV. 6. Again using field-supplied nuts and washers, secure the Liebert XDV to the all-thread bolts. 7. Tighten the nuts until the Liebert XDV is level and well-secured.

Mounting the Liebert XDV
Figure 16 Suspending Liebert XDV from the overhead structure

To prevent bypass air from recirculating through the Liebert XDV without it passing through the cabinet, this space between the hanging XDV and the cabinet must be blocked.

Mounting the Liebert XDV
Liebert designed the Liebert XDV to permit mounting the units in a stacked arrangement to increase the system’s heat-removal. Stacking may be done either during the original system or added later to an existing configuration.
Stacking Liebert XDVs is possible when suspending units from either Unistruts or from the overhead structure. Hanger brackets are available in two lengths to ease hanging Liebert XDVs in a stacked arrangement.
The upper Liebert XDV must be positioned forward of the front of its companion Liebert XDV for effi- cient heat removal (see Figure 17).
Figure 17 Stacking configuration offset
Hanging brackets suspend stacked Liebert XDVs from either Unistruts or from roof structure
Rear of Liebert XDVs
Upper Liebert XDV must line up with front edge of lower Liebert XDV
Lower Liebert XDV must line up with front edge of the cabinet (space between Liebert XDV and cabinet must be blocked to prevent recirculation of cooled air FRONT
For details on preventing recirculation, see Figure 16.

Mounting the Liebert XDV
Because the upper Liebert XDV in a stacked arrangement must be positioned farther forward than the lower Liebert XDV, two sets of Unistruts are required. The second set of Unistruts must be installed 9-7/8 inches (251mm) forward of the first set. This arrangement positions the stacked Lie- bert XDVs so that they meet the air-intake criteria shown in Figure 10 and Figure 17.
After installing the Unistruts at the proper location, hang the Liebert XDVs as outlined in 5.2.1 - Suspending the Liebert XDV from Unistruts.
Figure 18 Attach hanger brackets to Liebert XDV for stacked arrangement

Attach hanger brackets to each corner of each Liebert XDV. This arrangement permits mounting from either Unistruts or from overhead structure.
1/4 - 20 x 5/8" length typical, 2; factory-supplied
Figure 19 Stacked Liebert XDVs suspended from Unistruts

Unistrut field-supplied upper Liebert XDV: 1 lower Liebert XDV: 2 Bolt 3/8"- 16, nut and washer factory-supplied

Mounting the Liebert XDV
Because the upper Liebert XDV in a stacked arrangement must be positioned farther forward than the lower Liebert XDV, the place where the hangers attach to the overhead structure must be offset accordingly. The second row of attachment locations must be 9-7/8 inches (251mm) forward of the first row of hanger mounting locations. This arrangement positions the stacked Liebert XDVs so that they meet the air-intake criteria shown in Figure 10 and Figure 17.
After determining the proper for attachment to the overhead structure, hang the Liebert XDVs as outlined in 5.2.2 - Suspending the Liebert XDV from Overhead Structures.
Figure 20 Stacked Liebert XDVs ready for suspension from overhead structure

3/8"-16 All-thread bolts, field-supplied (four required per Liebert XDV)

Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo- sphere.
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.
If possible, connect the Liebert XDV modules to Liebert XDPs or Liebert XDCs in an interlaced config- uration (see Figure 21). In an interlaced configuration, half the cooling units in an aisle are con- nected to one Liebert XDP or Liebert XDC and the other half in that aisle are connected to another Liebert XDP or Liebert XDC. Such interlaced piping will keep half the Liebert XDV units operating and maintain even cooling in the conditioned space should one of the Liebert XDP or Liebert XDC units fail. However, in a system with just one Liebert XDP or Liebert XDC, connect Liebert XDV modules in a non-interlaced configuration (see Figure 22).
Figure 21 Typical Liebert XDV piping—interlaced connections
A
B
A
B
A
B
A

Figure 22 Typical Liebert XDV piping—non-interlaced connection
A
A
A
6.2.1 Piping Connections to Liebert XDP or Liebert XDC
Refer to site specific drawings for general locations of the piping connections. For Liebert XDV con- nection locations, refer to Figures 1 and 24.
The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination. All piping must be ASTM Type "L" copper pipe.
For hard-piped Liebert XDVs, the supply piping connection is 1/2" OD copper pipe, and the return piping connection is 5/8" OD copper. For Liebert XDVs with the pre-charged option, both supply and return fittings are one-shot connections. These fittings contain pressurized R-134a refrigerant inside the Liebert XDV.

Figure 23 Hard-piped connection diagram
Return Main (seen from end ) 2-1/8" O.D. or 2-5/8" O.D. Recommended Arc
Supply Main (seen from end ) 1-1/8" O.D. or 1-3/8" O.D.
5/8” Refrigerant-Grade Full-Port Ball Valve Field-Supplied and Field-Installed
1/2” Refrigerant-Grade Full-Port Ball Valve Field-Supplied and Field- Installed
Copper Tubing Total length of each line from Liebert XDV to Main; not to exceed 72" (1829mm)
Refer to Table 4 for details.
Top of Liebert XDV
Right Side of Liebert XDV
Piping · Acceptable Arc

Supply piping connection is 1/2" OD copper pipe and return piping connection is 5/8" OD copper.
The Liebert XDV in hard-piped configuration is shipped with a low-pressure holding charge (about 30 psi) of nitrogen to prevent oxidation and moisture. This must be vented before removing the caps on the ends of the supply and return piping.
To vent the holding charge:
Figure 24 Piping location and connection sizes—hard-piped units
SUPPLY (IN)
RETURN (OUT)
Rear of Liebert XDV
DPN000770 Page 4, Rev. 5

Figure 25 Schrader valve location for venting holding charge
Top of Liebert XDV
Schrader Valve
SCHRADER VALVE
SUPPLY ( IN)
RETURN (OUT)
Supply pipe connection (1/2" OD)
Return pipe connection (5/8" OD)
Rear of XDV
6.4.2 Brazing Preparations—Hard-Piped Units After the holding charge for a hard-piped Liebert XDV has been vented, a torch can be used to remove the caps over the ends of the supply and return lines. During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrig- eration piping.
NOTICE
To minimize the amount of refrigerant required, do NOT oversize the piping.
Connect the main pipes between the Liebert XDV branch piping and the Liebert XDP or Liebert XDC according to Table 4. Elbows and restrictions must be minimized to ensure good fluid flow.
Please see Table 4 below for recommended pipe sizes and Figure 3 for piping segment locations.
Piping

Table 4 Branch piping sizes for refrigerant loop
Pipe Function Size / Equivalent Pipe Length
Liebert XDP/Liebert XDC supply line, from Liebert XDP/Liebert XDC supply to farthest Liebert XDV
1-1/8" OD (1.025" ID) for lengths up to 60 feet (18m) 1-3/8" OD (1.265" ID) for lengths over 60 but less than 175 feet (18 to 53m)
Liebert XDP/Liebert XDC return line, from farthest Liebert XDV to Liebert XDP/Liebert XDC return
2-1/8" OD (1.985" ID) for lengths up to 60 feet (18m) 2-5/8" OD (2.465" ID) for lengths over 60 but less than 175 feet (18 to 53m)
From Liebert XDV supply to supply line of Liebert XDP/Liebert XDC
1/2" OD (0.430" ID) for lengths up to 6 feet (1.8m) 5/8" OD (0.545" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)
5/8" OD (0.545" ID) for lengths up to 6 feet (1.8m) 7/8" OD (0.785" ID) for lengths over 6 feet but less than 35 feet (1.8-10.6m)
From Liebert XDV return to return line of Liebert XDP/Liebert XDC
The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination.
Both supply and return fittings may be supplied with optional, one-shot connections. These fittings contain pressurized R-134a refrigerant inside the Liebert XDV.
! CAUTION Risk of sudden refrigerant discharge. Can cause injury and loss of charge. If the optional pre-charged option is chosen, the Liebert XDV unit is shipped with a full charge of R-134a refrigerant under pressure. Do not remove the pipe caps or plugs before the unit is ready for connection to Liebert XD Piping. Supply and return fittings on the pre-charged Liebert XDV units are one-shot connections. Do not disconnect one-shot connections after they have been connected. Disconnection will release pressurized R-134a refrigerant from the Liebert XDV.
If the unit includes the optional, factory-installed, one-shot style connections, proceed with 6.7 - Field Installation of Liebert Flex Pipe Kit on Liebert XDV and see Figure 26.
If the unit does not include flex piping, refer to 6.4.1 - Holding Charge—Hard-Piped Units.
Figure 26 Piping location and connection sizes—pre-charged units with one-shot connections

Piping

Liebert XDVs with the pre-charged option are equipped with one-shot connections on the supply and return fittings. These contain a charge of R-134a refrigerant under pressure within the unit. This charge must not be vented.
Do not remove the pipe caps or plugs before the unit is ready for connection to Liebert XD Piping. Do not disconnect one-shot connections after they have been connected.
If you are not performing a service installation or a field-retrofit, skip this section and proceed with the instructions in 6.8 - Connecting Liebert XD Flex Pipe to Liebert XDV Modules.
Liebert Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters). Connec- tion style to the unit end may be straight or 90 degrees. Connection to the prefab piping assembly is a threaded coupler. For data on acquiring the correct kit for your installation, see Table 7.
Figure 27 Liebert XD Flex Pipe dimensions—straight and 90-degree connections
Connection to Prefabricated Piping assembly
Connection to Prefabricated Piping assembly
Length 4, 6, 8 or 10 feet (1.2, 1.8, 2.4 or 3 meters)
Length 4, 6, 8 or 10 feet (1.2, 1.8, 2.4 or 3 meters)
90° Connection to XD Cooling Unit (One-Shot Coupling)
Connection to XD Cooling Unit (One-Shot Coupling) DPN000780 Pg. 1, Rev. 1
DPN000780 Pg. 2, Rev. 1
6.8 Connecting Liebert XD Flex Pipe to Liebert XDV Modules 1. Remove the caps on the supply and return lines on the top of the Liebert XDV. 2. Lubricate the threads, diaphragm and O-ring with one or two drops of mineral oil. 3. Connect the line-set coupling finger-tight. 4. Make sure the Schrader valve is properly oriented; refer to the label on the top of the Liebert XDV. 5. Hold the backup hex nut with a wrench while tightening the swivel nut. 6. Tighten the swivel nut on the female coupling until it is seated or a definite resistance is felt. 7. Once a definite bottoming resistance is felt (as in metal to metal), place a mark lengthwise from the swivel nut to the backup hex and tighten the swivel nut on the female coupling an additional 1/4 turn. 8. Tighten both the supply fittings and the return fittings to 35-45ft/lb (47-61Nm). 9. Mark the female and male coupler with for future reference.
Piping · 90-Degree Connection · Straight Connection

6.9 Connecting a Liebert XDV with Liebert Flex Pipe to an Operational Liebert XD System
Before connecting the Liebert XDV with Liebert Flex Pipe to the prefabricated piping mains, check the whole system for leaks. Check the Liebert XDV to ensure that the unit has no refrigerant leaks. Read all instructions before beginning installation.
Figure 28 Liebert XD prefabricated piping assembly
Supply Main Service Valve, typical (all ports)
5. Use system refrigerant to lubricate the face of the male coupling half, including the poppet valve face and the stainless steel delta ring. 6. Thread the return couplers together, the larger of the two couplers (Liebert Flex Pipe and return main). 7. Use one of the adjustable wrenches to hold the fixed side of the female coupler on the Liebert XDV stationary. With the other adjustable wrench, tighten the collar onto the coupler. Tighten these only until the force required to tighten abruptly increases. See Figure 29.
Do not overtighten the couplers. Overtightening of couplers will damage the couplers.
Piping · Return Main · Threaded Cap (Typical)

Figure 29 Detail view of Liebert XD Flex Pipe and prefabricated piping port
Service Valve Note: Make sure the valve is closed before attaching flex pipe to the system.
Tighten collar with wrench. DO NOT OVERTIGHTEN!
Supply Side Torque Range for 1/2" coupler is 22.1 to 25.8 lb/ft (30-35Nm)
Return Side Torque Range for 1" coupler is 59 to 62.7 lb/ft (80-85Nm)
Hold threaded coupler here with a wrench to keep the pipe stationary while tightening collar with another wrench.
8. Repeat Steps 6 and 7 for the smaller coupler (supply line). 9. Once the supply and return connections are completed, check to make sure the Liebert XDV fan power switches are Off, then connect the power cords to their power sources. 10. Turn the fan switches on. Ensure that the fans operate. 11. Open the return service valve first, then open the supply service valve. With the fans running, cool air is discharged from the front of the Liebert XDV.
Figure 30 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe
Return Service Valve Make sure valve is open after system leak check
Supply Service Valve. Make sure valve is open after system leak check
Return Liebert Flex Pipe from XDV unit
Supply Liebert Flex Pipe from Liebert XDV unit

6.10 Disconnecting a Liebert XDV With Liebert Flex Pipe From a Liebert XD System
! CAUTION Risk of sudden discharge of pressurized refrigerant. Can cause equipment damage or injury. Do not disconnect threaded refrigerant couplers at the unit cabinet end without relieving system pressure. Reclaim any refrigerant during removal of unit from system.
Before uninstalling a Liebert XDV with Liebert Flex Pipe from the prefabricated piping mains: With the fans running, close the supply service valve, wait approximately two minutes, then close the return service valve. Removing a Liebert XDV from above a cabinet will require two people. Read all instructions before beginning.
Figure 31 Profile view of the Liebert XD system with one-shot connections

Liquid Sensing (optional) Disconnect wiring prior to moving XDV
Piping

Figure 32 Piping mains without Liebert XDV and Liebert Flex Pipe
Risk of permanent damage to the flex pipes. Do not fold or bend flex pipe tightly. 13. Carefully unbolt the Liebert XDV from the cabinet or hanging bracket, if applicable. 14. With the help of another person, carefully lower the Liebert XDV from the cabinet or hanging bracket onto a stable surface.
To minimize the possibility of condensation, insulate all piping between the Liebert XDV and the Lie- bert XDP or Liebert XDC.
Piping

The unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial tag for electrical requirements. Refer to Table 5 for details.
Replacement of any wiring or supply cord must be performed only by the manufacturer, the manufac- turer’s service agent or a similarly qualified person.
! WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within the unit.
Connect IEC power cords to each receptacle on the Liebert XDV and to power sources. If only one power source is available, then only the power connection labeled “SECONDARY” should be con- nected to the power source. See Figures 33 and 34 for location of power connections.
Figure 33 Liebert XDV electrical connections for CSA-approved units

60Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP TO BE N.E.C. CLASS 2
50Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP FOR SAFETY EXTRA LOW VOLTAGE CIRCUITS
60Hz MODELS ONLY Field wiring connections at terminal strip to be NEC Class 2. Use switch contacts
with 75VA minimum rating.
50Hz MODELS ONLY Field wiring connections at terminal strip for safety extra
low voltage circuits only. Use
switch contacts rated 75VA minimum, 24VAC maximum.
Electrical

Figure 34 Liebert XDV electrical connections for CE-approved units
60Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP TO BE N.E.C. CLASS 2
USE SWITCH CONTACTS WITH 75 V.A.
50Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP FOR SAFETY EXTRA LOW VOLTAGE CIRCUITS
CONTACTS RATED
75 V.A. MINIMUM, 24 VOLTS AC MAXIMUM.
60Hz MODELS ONLY Field wiring connections at terminal strip to be NEC Class 2. Use switch contacts
with 75VA minimum rating.
Condensate Detection Dry Contacts – Low Voltage Connections
50Hz MODELS ONLY Field wiring connections at terminal strip for safety extra
Knockout for Optional Wiring
low voltage circuits only. Use
switch contacts rated 75VA minimum, 24VAC maximum.
Primary and Secondary Power Cords
1774241P1
FACTORY-SUPPLIED
POWER CORDS (straight-on and profile)
If the factory-supplied power cords do not match with the user’s electrical outlets, a suitable adapter must be field-provided.
Electrical

Low voltage connections to the Liebert XDV are available only on units with the optional condensate detection feature. The low voltage connections are on the right side of the electrical connections box, just above the power connections (see Figure 35). These dry contacts can to be connected to a moni- toring unit, such as Liebert’s SiteScan®.
For units equipped with condensate detection, make low voltage connections according to site-specific drawings. The unit must be installed in accordance with national wiring regulations.
Figure 35 Low voltage connections
60Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP TO BE N.E.C. CLASS 2
USE SWITCH CONTACTS WITH 75 V.A.
MINIMUM RATING.
50Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP FOR SAFETY EXTRA LOW VOLTAGE CIRCUITS
CONTACTS RATED
75 V.A. MINIMUM, 24 VOLTS AC MAXIMUM.
60Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP TO BE N.E.C. CLASS 2
USE SWITCH CONTACTS WITH 75 V.A.
MINIMUM RATING.
50Hz MODELS ONLY. FIELD WIRING CONNECTIONS AT TERMINAL STRIP FOR SAFETY EXTRA LOW VOLTAGE CIRCUITS
75 V.A. MINIMUM, 24 VOLTS AC MAXIMUM.
Electrical

Installation Checklist and System Fill for Startup
8.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP
___ 1. Liebert XDV module is properly mounted, secured either to the cabinet, overhead structure or to the Unistruts.
___ 2. Power cords connected to electrical supply.
___ 3. Low voltage wiring to optional condensate detection on Liebert XDV.
___ 4. Piping from Liebert XDP to Liebert XDV, with isolation valves piped to each Liebert XDV. a. Hard-piped units connected to prefabricated headers b. Flex piping connections to prefabricated header assembly, if flex piping is used.
___ 5. Piping insulated.
___ 6. Start the Liebert XDV to ensure proper operation (see 9.1 - Start the Liebert XDV).
___ 7. Shut down the Liebert XDV.
The Liebert XD System must be completely installed before it is charged with refrigerant. After installation is complete, refer to the Liebert XDP or Liebert XDC user manual for instructions on charging the Liebert XD modules with refrigerant and starting the system. The complete Liebert XD system includes all cooling modules, a Liebert XDC or Liebert XDP unit and any other connected equipment.

The Liebert XDV’s fan controls are on the front of the unit, near the fans, for easy access. Each switch controls the operation of one fan (see Figure 36). The separate switches permit the use of only one fan at a time, reducing the airflow if the Liebert XDV’s full cooling capacity is not needed.
The Liebert XDV’s primary and secondary circuit breakers are also on the front of the unit. They are at the top left when facing the Liebert XDV (see Figure 36).
One of the Liebert XDV’s fans must be operating at all times that the Liebert XDP or Liebert XDC is operating. Operating either the Liebert XDP or the Liebert XDC without at least one of the Liebert XDV’s fans rotating may cause a system malfunction.
Figure 36 Fan switches

The Liebert XDV fans must be on before starting the Liebert XDP or Liebert XDC that will supply coolant to the Liebert XDVs.
To start the Liebert XDV, press either of the rocker switches to turn on one or both of the Liebert XDV’s fans.
Operation

Minimal maintenance is required to keep the Liebert XDV operating at optimal levels. The unit should be cleaned and checked for damage and worn parts. Suggested maintenance includes:
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo- sphere.
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas during equipment service and maintenance and before disposing of equipment.
Refer to the full regulation for additional details.
The conditions required for sensitive electronic equipment should preclude the accumulation of appre- ciable amounts of dust in the Liebert XDV. Most of that small amount should be found on the rear coils, near the air inlet. The rear covers and the fan tray on the front of the Liebert XDV are easily removed for maintenance. (A wiring diagram is provided on the inside of the fan tray.) To remove the rear grille: 1. Loosen the six screws holding the grille on the rear of the Liebert XDV. 2. Remove the grille and lay it aside for reinstallation.
Maintenance

10.2.1 Accessing Internal Electrical Components 1. Disconnect all power inputs. 2. Remove five screws to remove the front electrical panel cover. SeeFigure 37 and 12 of 13 3. Lift off the panel.

Maintenance

To remove the fan tray:
1. Remove the front electrical panel cover as described in 10.2.1 - Accessing Internal Electrical Components. 2. Disconnect the 12-pin connector. Take care not to stretch or stress the electrical wires to the fans. 3. Remove the four screws holding the fan tray on the Liebert XDV. 4. Support the fan tray when removing the last screw to keep it from falling. 5. Set the screws aside for reinsertion after maintenance is completed. 6. Then lift the fan tray up and set it on top of the Liebert XDV or on a nearby surface.
Figure 38 Removing the fan tray

To reattach the fan tray: 1. Clean the fan tray to prevent debris from being blown into the computer cabinet. 2. Reconnect the 12-pin connector. 3. Lift the fan tray and fit it against the base of the Liebert XDV housing (see Figure 38). 4. Holding the fan tray against the Liebert XDV housing, insert the screws extracted when removing the fan tray. 5. Tighten the screws securely. 6. Reconnect power to the Liebert XDV.
Maintenance

Table 5 Liebert XDV10 specifications
XDV10BT--*; XDV10DT--* XDV10BTP-*; XDV10DTP-* XDV10BT-E*; XDV10DT-E* XDV10BTPE*; XDV10DTPE*
XDV10BS--*; XDV10DS--* XDV10BSP-*; XDV10DSP-* XDV10BS-E*; XDV10DS-E* XDV10BSPE*; XDV10DSPE*
XDV10BKR-*; XDV10BKRE* XDV10DKR-*; XDV10DKRE*
XDV10BTR-*; XDV10BTRE* XDV10DTR-*; XDV10DTRE*
XDV10BSR-*; XDV10BSRE* XDV10DSR-*; XDV10DSRE*
60 Hz 60 Hz 50 Hz 50 Hz
Cooling Capacity Nominal (98ºF [37ºC] EAT): 10kW / 2.8 Tons Maximum (106ºF [41ºC] EAT): 11.8kW/3.4 Tons
Conditions Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Input power connections 2 power connections, each model
nominal, watts 180 190 190 190
Height – unit only 14 (355) not including pipe connections
Height – including hard
pipe connections 18-5/8 (473)
Height – including one-
shot connections 19-5/8 (498)
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Unit only 77 (35)
Shipping weight 125 (57)
Installed, with refrigerant 79 (36)
Number of fans 2
1000 (1699) with rear inlet. Bottom inlet airflow may be less, depending on restrictions inside
833 (1415) with rear inlet. Bottom inlet airflow may be less, depending on restrictions inside
Airflow, Nominal, ft3/ min (m3/ hr)
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
Refrigerant supply from Liebert XDP/ XDC 1/2" OD, Cu, (optional 1/2" threaded coupler flex piping)
Refrigerant return to Liebert XDP/ XDC 5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
(factory-installed) Dry contact outgoing signal
Pre-Charged Refrigerant R-134a Refrigerant, one-shot connections
Approvals CSA 60Hz CSA 50Hz CE 50Hz
* = Revision level of unit

Table 6 Liebert XDV8 specifications
XDV8BK--*; XDV8DK--* XDV8BKP-*; XDV8DKP-* XDV8BK-E*; XDV8DK-E* XDV8BKPE*;XDV8DKPE* XDV8BKR-*; XDV8BKRE* XDV8DKR-*; XDV8DKRE*
XDV8BS--*; XDV8DS--* XDV8BSP-*; XDV8DSP-* XDV8BS-E*; XDV8DS-E* XDV8BSPE*; XDV8DSPE*
XDV8BTR-*; XDV8BTRE* XDV8DTR-*; XDV8DTRE*
XDV8BSR-*; XDV8BSRE* XDV8DSR-*; XDV8DSRE*
60 Hz 60 Hz 50 Hz 50 Hz
Cooling Capacity Nominal (98°F [37°C] EAT): 8.8kW / 2.5 Tons Maximum (95°F [35°C] EAT): 8.8kW / 2.5 Tons
Conditions Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Input power connections 2 power connections, each model
nominal, watts 180 190 190 190
Height – unit only 14 (355) not including pipe connections
Height – including pipe
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Unit only 77 (35)
Shipping weight 125 (57)
Number of Fans 2
833 (1415) with rear inlet. Bottom inlet airflow may be less, depending on restrictions inside
Airflow, Nominal, ft3/ min (m3/ hr)
1000 (1699) with rear inlet. Bottom inlet airflow may be less, depending on restrictions inside cabinet
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
from Liebert XDP/Liebert XDC
1/2" OD Cu, (optional 1/2" threaded coupler flex piping)
Refrigerant Return to Liebert XDP/Liebert
5/8" OD Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
(factory-installed) Dry contact outgoing signal
Pre-Charged R-134a Refrigerant, one-shot connections
Approvals CSA 60Hz CSA 50Hz CE 50Hz
* = Revision level of unit

Table 7 Liebert XD Liebert Flex Pipe assemblies, supply and return
Liebert P/N Straight Connection
Liebert P/N 90-Degree Connection Assembly
7 (178) 8 (203) 186568G2 186567G2 10 (3.0)
186568G3 186567G3 8 (2.5)
186568G4 186567G4 4 (1.2)



Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
Technical Support / Service
Web Site www.liebert.com
Monitoring 800-222-5877 monitoring@emersonnetworkpower.com
800-222-5877 upstech@emersonnetworkpower.com
800-543-2378 powertech@emersonnetworkpower.com
800-543-2778 Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250
EmersonNetworkPower.com Emerson Network Power. The global leader in enabling Business-Critical Continuity.
Embedded Computing Embedded Power Power Switching & Controls
Services Racks & Integrated Cabinets Outside Plant
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.