Liebert GXT3

44 pages·2.7 MB·Surge Protector·PDF·ENDEFRITNLJA
Liebert GXT3
Table of Contents 122 sections Important Safety Precautions · Save These Instructions · UPS Safety Notes · Battery Safety · … ShowHide
Important Safety Precautionsp.7Save These Instructionsp.7UPS Safety Notesp.7Battery Safetyp.8Information for the Protection of the Environmentp.8Glossary of Symbolsp.91.0 Product Descriptionp.101.1 Featuresp.101.2 Available Modelsp.10Table 1 UPS models, power ratingsp.101.3 Appearance and Componentsp.111.3.1 Appearancep.11Figure 1 Liebert GXT3-700RT230 - GXT3-3000RT230 UPSp.111.3.2 Rear Panel Featuresp.11Figure 2 Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA modelsp.11Figure 3 Rear panel components, Liebert GXT3 230V 2000VA modelsp.11Figure 4 Rear panel components, Liebert GXT3 230V 3000VA modelsp.121.4 Major Componentsp.12Figure 5 Operating principle diagramp.12Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filtersp.12Rectifier/Power Factor Correction (PFC) Circuitp.13Inverterp.13Battery Chargerp.13DC-to-DC Converterp.13Batteryp.13Dynamic Bypassp.131.5 Operating Modep.131.5.1 Mains (AC) Modep.131.5.2 Manual Bypass Modep.141.5.3 Battery Modep.141.5.4 Battery Recharge Modep.141.5.5 Frequency Converter Modep.142.0 Installationp.152.1 Unpacking and Inspectionp.152.2 What’s Includedp.152.3 Preparation for Installationp.152.3.1 Installation Environmentp.15Installation Clearancesp.152.4 Mechanical Installationp.162.4.1 Tower Installationp.16Figure 6 Support basesp.16Figure 7 Remove the front plastic bezel coverp.16Figure 8 Rotate the operation and display panelp.17Figure 9 Tower installationp.172.4.2 Rack Installationp.18Figure 10 Pulling inner member from each bracket assemblyp.18Figure 11 Installing rear member of each bracket assemblyp.19Figure 12 Installing front member of each bracket assemblyp.19Figure 13 Fastening rear member and front member togetherp.19Figure 14 Installing inner membersp.20Figure 15 Installing rack-mount earsp.20Figure 16 Insert the UPSp.202.5 Cable Connectionp.212.5.1 Connecting to AC Mains and Loadsp.21Table 2 Specification of input circuit breakerp.212.5.2 Connecting Battery Cablesp.212.6 Connecting Communication Cablesp.222.6.1 Connecting USB Communication Cablesp.222.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cablesp.223.0 Operation and Display Panelp.23Figure 17 Operation and display panelp.233.1 Control Buttonsp.233.1.1 On/Alarm Silence/Manual Battery Test buttonp.23Table 3 Functions of the On/Alarm Silence/Manual Battery Test buttonp.233.1.2 Standby/Manual Bypass buttonp.23Table 4 Functions of the Standby/Manual Bypass buttonp.233.2 Indicatorsp.243.2.1 Level Indicatorsp.24Battery Level Indicatorsp.24Figure 18 Battery level indicatorsp.24Load Level Indicatorsp.24Figure 19 Load level indicatorsp.243.2.2 UPS Status Indicatorsp.25Table 5 UPS status indicatorsp.254.0 Operationp.264.1 Startup Checklist for the Liebert GXT3p.264.2 Starting the UPSp.264.3 Manual Battery Testp.264.4 Manual Bypassp.264.5 Shut Down the Liebert GXT3p.274.6 Disconnecting Input Power from the Liebert GXT3p.275.0 Communicationp.285.1 Liebert IntelliSlot Communication Cardsp.285.1.1 Liebert MultiLinkp.285.2 USB Port Communicationp.295.2.1 Configuration Programp.29Table 6 Output voltage option, all modelsp.295.3 Terminal Block Communicationp.30Figure 20 Terminal Block Communication pin layoutp.305.3.1 Any Mode Shutdownp.305.3.2 Battery Mode Shutdownp.315.3.3 On Batteryp.315.3.4 Low Batteryp.316.0 Maintenancep.326.1 Replacing the Internal Battery Packp.32Table 7 Replacement battery pack model numbersp.326.1.1 Battery Replacement Proceduresp.32Figure 21 Removing the front plastic bezel cover and battery doorp.32Figure 22 Disconnecting the battery plug and battery connector (front view)p.33Figure 23 Pulling out the batteryp.336.2 Battery Chargingp.336.3 Precautionsp.346.4 Checking UPS Statusp.346.5 Checking UPS Functionsp.347.0 Troubleshootingp.357.1 UPS Symptomsp.357.1.1 Indicatorsp.35Figure 24 Battery level indicatorp.35Table 8 Indicator descriptionsp.357.1.2 Audible Alarmp.36Table 9 Audible alarm descriptionp.367.2 Troubleshootingp.36Table 10 Troubleshooting tablep.368.0 Battery Cabinetp.38Figure 25 Battery cabinetp.389.0 Specificationsp.39Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPSp.39Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230p.40Table 13 Battery cabinet specificationsp.41Table 14 Operating temperature parametersp.41Table 15 Battery run timesp.429.1 Product Warranty Registrationp.43
Page 1 of the Liebert GXT3 user manual
Page 1 · click to enlarge
Page 1
Liebert GXT3 diagram (page 1)
Fig. 1
Page 2 of the Liebert GXT3 user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Liebert GXT3 user manual
Page 3 of the Liebert GXT3 user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Important Safety Precautionsp.7Save These Instructionsp.7UPS Safety Notesp.7Battery Safetyp.8Information for the Protection of the Environmentp.8Glossary of Symbolsp.91.0 Product Descriptionp.101.1 Featuresp.101.2 Available Modelsp.10Table 1 UPS models, power ratingsp.101.3 Appearance and Componentsp.111.3.1 Appearancep.11Figure 1 Liebert GXT3-700RT230 - GXT3-3000RT230 UPSp.111.3.2 Rear Panel Featuresp.11Figure 2 Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA modelsp.11Figure 3 Rear panel components, Liebert GXT3 230V 2000VA modelsp.11Figure 4 Rear panel components, Liebert GXT3 230V 3000VA modelsp.121.4 Major Componentsp.12Figure 5 Operating principle diagramp.12Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filtersp.12Rectifier/Power Factor Correction (PFC) Circuitp.13Inverterp.13Battery Chargerp.13DC-to-DC Converterp.13Batteryp.13Dynamic Bypassp.131.5 Operating Modep.131.5.1 Mains (AC) Modep.131.5.2 Manual Bypass Modep.141.5.3 Battery Modep.141.5.4 Battery Recharge Modep.141.5.5 Frequency Converter Modep.142.0 Installationp.152.1 Unpacking and Inspectionp.152.2 What’s Includedp.152.3 Preparation for Installationp.152.3.1 Installation Environmentp.15Installation Clearancesp.152.4 Mechanical Installationp.162.4.1 Tower Installationp.16Figure 6 Support basesp.16Figure 7 Remove the front plastic bezel coverp.16Figure 8 Rotate the operation and display panelp.17Figure 9 Tower installationp.172.4.2 Rack Installationp.18Figure 10 Pulling inner member from each bracket assemblyp.18Figure 11 Installing rear member of each bracket assemblyp.19Figure 12 Installing front member of each bracket assemblyp.19Figure 13 Fastening rear member and front member togetherp.19Figure 14 Installing inner membersp.20Figure 15 Installing rack-mount earsp.20Figure 16 Insert the UPSp.202.5 Cable Connectionp.212.5.1 Connecting to AC Mains and Loadsp.21Table 2 Specification of input circuit breakerp.212.5.2 Connecting Battery Cablesp.212.6 Connecting Communication Cablesp.222.6.1 Connecting USB Communication Cablesp.222.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cablesp.223.0 Operation and Display Panelp.23Figure 17 Operation and display panelp.233.1 Control Buttonsp.233.1.1 On/Alarm Silence/Manual Battery Test buttonp.23Table 3 Functions of the On/Alarm Silence/Manual Battery Test buttonp.233.1.2 Standby/Manual Bypass buttonp.23Table 4 Functions of the Standby/Manual Bypass buttonp.233.2 Indicatorsp.243.2.1 Level Indicatorsp.24Battery Level Indicatorsp.24Figure 18 Battery level indicatorsp.24Load Level Indicatorsp.24Figure 19 Load level indicatorsp.243.2.2 UPS Status Indicatorsp.25Table 5 UPS status indicatorsp.254.0 Operationp.264.1 Startup Checklist for the Liebert GXT3p.264.2 Starting the UPSp.264.3 Manual Battery Testp.264.4 Manual Bypassp.264.5 Shut Down the Liebert GXT3p.274.6 Disconnecting Input Power from the Liebert GXT3p.275.0 Communicationp.285.1 Liebert IntelliSlot Communication Cardsp.285.1.1 Liebert MultiLinkp.285.2 USB Port Communicationp.295.2.1 Configuration Programp.29Table 6 Output voltage option, all modelsp.295.3 Terminal Block Communicationp.30Figure 20 Terminal Block Communication pin layoutp.305.3.1 Any Mode Shutdownp.305.3.2 Battery Mode Shutdownp.315.3.3 On Batteryp.315.3.4 Low Batteryp.316.0 Maintenancep.326.1 Replacing the Internal Battery Packp.32Table 7 Replacement battery pack model numbersp.326.1.1 Battery Replacement Proceduresp.32Figure 21 Removing the front plastic bezel cover and battery doorp.32Figure 22 Disconnecting the battery plug and battery connector (front view)p.33Figure 23 Pulling out the batteryp.336.2 Battery Chargingp.336.3 Precautionsp.346.4 Checking UPS Statusp.346.5 Checking UPS Functionsp.347.0 Troubleshootingp.357.1 UPS Symptomsp.357.1.1 Indicatorsp.35Figure 24 Battery level indicatorp.35Table 8 Indicator descriptionsp.357.1.2 Audible Alarmp.36Table 9 Audible alarm descriptionp.367.2 Troubleshootingp.36Table 10 Troubleshooting tablep.368.0 Battery Cabinetp.38Figure 25 Battery cabinetp.389.0 Specificationsp.39Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPSp.39Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230p.40Table 13 Battery cabinet specificationsp.41Table 14 Operating temperature parametersp.41Table 15 Battery run timesp.429.1 Product Warranty Registrationp.43
Page 4 of the Liebert GXT3 user manual
Page 4 · click to enlarge
Page 4

4.0 OPERATION 20

4.1 Startup Checklist for the Liebert GXT3 20

4.2 Starting the UPS 20

4.3 Manual Battery Test 20

4.4 Manual Bypass 20

4.5 Shut Down the Liebert GXT3 21

4.6 Disconnecting Input Power from the Liebert GXT3 21

5.0 COMMUNICATION 22

5.1 Liebert IntelliSlot Communication Cards 22 5.1.1 Liebert MultiLink 22

5.2 USB Port Communication 23 5.2.1 Configuration Program 23

5.3 Terminal Block Communication 24 5.3.1 Any Mode Shutdown 24 5.3.2 Battery Mode Shutdown 25 5.3.3 On Battery 25 5.3.4 Low Battery 25

6.0 MAINTENANCE 26

6.1 Replacing the Internal Battery Pack 26 6.1.1 Battery Replacement Procedures 26

6.2 Battery Charging 27

6.3 Precautions 28

6.4 Checking UPS Status 28

6.5 Checking UPS Functions 28

7.0 TROUBLESHOOTING 29

7.1 UPS Symptoms 29 7.1.1 Indicators 29 7.1.2 Audible Alarm 30

7.2 Troubleshooting 30

8.0 BATTERY CABINET 32

9.0 SPECIFICATIONS 33

9.1 Product Warranty Registration 37

Page 5 of the Liebert GXT3 user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

Important Safety Precautionsp.7Save These Instructionsp.7UPS Safety Notesp.7Battery Safetyp.8Information for the Protection of the Environmentp.8Glossary of Symbolsp.91.0 Product Descriptionp.101.1 Featuresp.101.2 Available Modelsp.10Table 1 UPS models, power ratingsp.101.3 Appearance and Componentsp.111.3.1 Appearancep.11Figure 1 Liebert GXT3-700RT230 - GXT3-3000RT230 UPSp.111.3.2 Rear Panel Featuresp.11Figure 2 Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA modelsp.11Figure 3 Rear panel components, Liebert GXT3 230V 2000VA modelsp.11Figure 4 Rear panel components, Liebert GXT3 230V 3000VA modelsp.121.4 Major Componentsp.12Figure 5 Operating principle diagramp.12Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filtersp.12Rectifier/Power Factor Correction (PFC) Circuitp.13Inverterp.13Battery Chargerp.13DC-to-DC Converterp.13Batteryp.13Dynamic Bypassp.131.5 Operating Modep.131.5.1 Mains (AC) Modep.131.5.2 Manual Bypass Modep.141.5.3 Battery Modep.141.5.4 Battery Recharge Modep.141.5.5 Frequency Converter Modep.142.0 Installationp.152.1 Unpacking and Inspectionp.152.2 What’s Includedp.152.3 Preparation for Installationp.152.3.1 Installation Environmentp.15Installation Clearancesp.152.4 Mechanical Installationp.162.4.1 Tower Installationp.16Figure 6 Support basesp.16Figure 7 Remove the front plastic bezel coverp.16Figure 8 Rotate the operation and display panelp.17Figure 9 Tower installationp.172.4.2 Rack Installationp.18Figure 10 Pulling inner member from each bracket assemblyp.18Figure 11 Installing rear member of each bracket assemblyp.19Figure 12 Installing front member of each bracket assemblyp.19Figure 13 Fastening rear member and front member togetherp.19Figure 14 Installing inner membersp.20Figure 15 Installing rack-mount earsp.20Figure 16 Insert the UPSp.202.5 Cable Connectionp.212.5.1 Connecting to AC Mains and Loadsp.21Table 2 Specification of input circuit breakerp.212.5.2 Connecting Battery Cablesp.212.6 Connecting Communication Cablesp.222.6.1 Connecting USB Communication Cablesp.222.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cablesp.223.0 Operation and Display Panelp.23Figure 17 Operation and display panelp.233.1 Control Buttonsp.233.1.1 On/Alarm Silence/Manual Battery Test buttonp.23Table 3 Functions of the On/Alarm Silence/Manual Battery Test buttonp.233.1.2 Standby/Manual Bypass buttonp.23Table 4 Functions of the Standby/Manual Bypass buttonp.233.2 Indicatorsp.243.2.1 Level Indicatorsp.24Battery Level Indicatorsp.24Figure 18 Battery level indicatorsp.24Load Level Indicatorsp.24Figure 19 Load level indicatorsp.243.2.2 UPS Status Indicatorsp.25Table 5 UPS status indicatorsp.254.0 Operationp.264.1 Startup Checklist for the Liebert GXT3p.264.2 Starting the UPSp.264.3 Manual Battery Testp.264.4 Manual Bypassp.264.5 Shut Down the Liebert GXT3p.274.6 Disconnecting Input Power from the Liebert GXT3p.275.0 Communicationp.285.1 Liebert IntelliSlot Communication Cardsp.285.1.1 Liebert MultiLinkp.285.2 USB Port Communicationp.295.2.1 Configuration Programp.29Table 6 Output voltage option, all modelsp.295.3 Terminal Block Communicationp.30Figure 20 Terminal Block Communication pin layoutp.305.3.1 Any Mode Shutdownp.305.3.2 Battery Mode Shutdownp.315.3.3 On Batteryp.315.3.4 Low Batteryp.316.0 Maintenancep.326.1 Replacing the Internal Battery Packp.32Table 7 Replacement battery pack model numbersp.326.1.1 Battery Replacement Proceduresp.32Figure 21 Removing the front plastic bezel cover and battery doorp.32Figure 22 Disconnecting the battery plug and battery connector (front view)p.33Figure 23 Pulling out the batteryp.336.2 Battery Chargingp.336.3 Precautionsp.346.4 Checking UPS Statusp.346.5 Checking UPS Functionsp.347.0 Troubleshootingp.357.1 UPS Symptomsp.357.1.1 Indicatorsp.35Figure 24 Battery level indicatorp.35Table 8 Indicator descriptionsp.357.1.2 Audible Alarmp.36Table 9 Audible alarm descriptionp.367.2 Troubleshootingp.36Table 10 Troubleshooting tablep.368.0 Battery Cabinetp.38Figure 25 Battery cabinetp.389.0 Specificationsp.39Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPSp.39Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230p.40Table 13 Battery cabinet specificationsp.41Table 14 Operating temperature parametersp.41Table 15 Battery run timesp.429.1 Product Warranty Registrationp.43
Page 6 of the Liebert GXT3 user manual
Page 6 · click to enlarge
Page 6
Page 6 of the Liebert GXT3 user manual
Page 7 of the Liebert GXT3 user manual — UPS Safety Notes
Page 7 · click to enlarge
Page 7

I MPORTANT S AFETY P RECAUTIONS

! WARNING Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to properly trained and qualified service personnel. Do not attempt to service this product yourself. Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Never work alone.

SAVE THESE INSTRUCTIONS

This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or operate this UPS.

UPS Safety Notes

The UPS contains no user-serviceable parts except the internal battery pack. Do not remove the cover. Removing the cover may result in electric shock and will invalidate any implied warranty.

The UPS has an internal battery, so the output receptacles of the UPS may carry live voltage even if the UPS is not connected to mains input power.

Before moving or rewiring the UPS, disconnect mains input power and the battery and make sure that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard.

To ensure human safety and normal UPS operation, the UPS must be properly grounded before use.

When the UPS is connected to an IT power distribution system, the short-circuit protection device must be installed on the neutral line.

Install and use the UPS in the following environments:

  • Temperature: 0°C to 40°C (32 - 104°F); relative humidity: 0% to 95%, non-condensing)
  • Out of direct sunlight
  • Away from heat source
  • Stable surface, not subject to vibrations or shocks
  • Away from dust and other particulates
  • Away from corrosive substances, salts and flammable gases

Keep the air inlet and outlet of the UPS unobstructed. Poor ventilation will increase the UPS internal temperature and can shorten the life of the UPS and its batteries.

Keep liquid and other foreign objects away from the UPS.

In case of fire, use a dry chemical fire extinguisher to put out the fire. Using a fluid fire extinguisher may cause electric shock.

This UPS is not intended for use with life support and other designated critical devices. Maximum load must not exceed that shown on the UPS rating label. This UPS is designed for data processing equipment. If uncertain, consult your local dealer or Emerson Network Power® representative.

Page 8 of the Liebert GXT3 user manual — Information for the Protection of the Environment
Page 8 · click to enlarge
Page 8

Battery Safety

! CAUTION Do not dispose of the battery in a fire. The battery may explode. Do not open or damage the battery. Released electrolyte is toxic and is harmful to skin and eyes. If electrolyte comes into contact with the skin, wash the affected area immediately with plenty of clean water and get medical attention.

  • ! CAUTION A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
  • Remove watches, rings and other metal objects.
  • Use tools with insulated handles.
  • Wear rubber gloves and boots.
  • Do not lay tools or metal parts on top of batteries.
  • Disconnect charging source prior to connecting or disconnecting battery terminals.
  • Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded supply circuit).

ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 series complies with the limits for a Class A digital device. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.

The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson®.

Information for the Protection of the Environment

UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers.

The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE).

For information regarding the scrapping of this equipment, please browse http://www.eu.emersonnetworkpower.com (“Products session” or “Contact us” session) or call our worldwide technical support.

  • Toll Free: 00 80011554499
  • Toll Number Based in Italy: +39 0298250222
Page 9 of the Liebert GXT3 user manual — R
Page 9 · click to enlarge
Page 9

G LOSSARY OF S YMBOLS

Risk of electrical shock

!

Indicates caution followed by important instructions

Requests the user to consult the manual

Indicates the unit contains a valve-regulated lead acid battery

R

WEEE

Show 10 more labels / short text on this page
AC input · AC output · PbH2SO4 - + · Recycle · DC voltage · Equipment grounding conductor · Bonded to ground · AC voltage · ON/Alarm Silence/Battery Test · OFF/Bypass
Page 10 of the Liebert GXT3 user manual — 1.2 Available Models
Page 10 · click to enlarge
Page 10

1.0 P RODUCT D ESCRIPTION

The Liebert GXT3 is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers and other sensitive electronic equipment with clean sine wave input power, 700VA to 3000VA at 230V.

Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and damage equipment.

The Liebert GXT3 protects equipment from these disturbances. The Liebert GXT3 continuously charges its batteries from the mains, enabling it to supply power to connected loads, even when the mains fail.

This section describes the UPS, its features, models, appearance and components, operating principles and operating mode.

1.1 Features

The UPS includes the following features:

  • Intelligent battery management to extend the battery life
  • Operation and display panel with LED for monitoring load percentage and battery capacity independently
  • Flexible network management with Liebert MultiLink ® software
  • Fan fault self-inspection and automated diagnostic function
  • Intelligent fan operation, automatically changing rotation speed depending on system requirements, to decrease power consumption and noise
  • Input circuit breaker to ease recovery from overloads
  • CE mark and safety approval from CE
  • Communication options: USB port, Liebert IntelliSlot ® port and terminal block communication
  • Dry contacts for remote monitoring
  • Input power factor greater than 0.99
  • Output voltage selection function

1.2 Available Models

Available models of the UPS are shown in Table 1:

Table 1 UPS models, power ratings

ModelNominal Power Rating GXT3-700RT230700VA/630W GXT3-1000RT2301000VA/900W GXT3-1500RT2301500VA/1350W GXT3-2000RT2302000VA/1800W GXT3-3000RT2303000VA/2700W

Product Description

Page 11 of the Liebert GXT3 user manual — 1.3.2 Rear Panel Features
Page 11 · click to enlarge
Page 11

1.3 Appearance and Components

1.3.1 Appearance

The Liebert GXT3 rack/tower models in various power ratings have the same general appearance, controls and features (see Figure 1). The various rack/tower models differ largely in the type of receptacles each has.

Figure 1 Liebert GXT3-700RT230 - GXT3-3000RT230 UPS

Liebert GXT3 — 1.3 Appearance and Components diagram (page 11)
Fig. 2 · 1.3 Appearance and Components

Operation and Display Panel Ventilation Slots

1.3.2 Rear Panel Features

The rear panel of the Liebert GXT3 has these features:

  • USB port
  • Cooling fan
  • C19 output receptacle (GXT3-3000RT230 only)
  • Six C13 output receptacles
  • Input circuit breaker
  • Liebert IntelliSlot ®
  • Communication terminal block
  • Input receptacle

Figure 2 Rear panel components, Liebert GXT3 230V 700VA, 1000VA and 1500VA models

Liebert IntelliSlot Port USB Port

Liebert GXT3 — 1.3.2 Rear Panel Features diagram (page 11)
Fig. 3 · 1.3.2 Rear Panel Features

Figure 3 Rear panel components, Liebert GXT3 230V 2000VA models

Liebert IntelliSlot Port USB Port

Liebert GXT3 — 1.3.2 Rear Panel Features diagram (page 11)
Fig. 4 · 1.3.2 Rear Panel Features

External Battery Connector Cooling Fan C13 Output Receptacles

Show 7 more labels / short text on this page
Product Description · Input Circuit Breaker · C14 Input Receptacle · Terminal Block Communication · Input Circuit Breaker · C20 Input Receptacle · Terminal Block Communication
Page 12 of the Liebert GXT3 user manual — Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
Page 12 · click to enlarge
Page 12

Figure 4 Rear panel components, Liebert GXT3 230V 3000VA models

Liebert IntelliSlot Port USB Port

C20 Input Receptacle Output Circuit Breakers

Liebert GXT3 — Figure 4 Rear panel components, Liebert GXT3 230V 3000VA models diagram (page 12)
Fig. 5 · Figure 4 Rear panel components, Liebert GXT3 230V 30…

Cooling Fan C13 Output Receptacles

1.4 Major Components

The operating principle of the UPS is shown in Figure 5.

Figure 5 Operating principle diagram

Liebert GXT3 — 1.4 Major Components diagram (page 12)
Fig. 6 · 1.4 Major Components

The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output.

Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters

The Liebert GXT3 has surge protection and filters that protect the connected load from power surges and sags, electromagnetic interference (EMI) and radio frequency interference (RFI). These features can minimize any surges or interference present in the mains power. The filters also prevent surges or interference generated by the UPS from adversely affecting other devices connected on the same branch as the UPS.

Show 5 more labels / short text on this page
Product Description · Input Circuit Breaker · Terminal Block Communication · External Battery Connector · C19 Output Receptacle
Page 13 of the Liebert GXT3 user manual — 1.5.1 Mains (AC) Mode
Page 13 · click to enlarge
Page 13

Rectifier/Power Factor Correction (PFC) Circuit

In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts mains power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current achieves two objectives:

  • Efficient power use by the UPS
  • Reduced reflected harmonics

This results in cleaner power being available to other devices in the building that are not protected by the UPS.

Inverter

In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC circuit to produce precise, regulated sine wave AC power. When mains power fails, the inverter receives DC power from the battery through the DC-to DC converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise, regulated AC output power.

Battery Charger

The battery charger utilizes energy from the mains power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is plugged in, even when the UPS is not turned On.

DC-to-DC Converter

The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, increasing reliability.

Battery

The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the Liebert GXT3 in an ambient temperature of 0°C to 25°C (32°F to 77°F).

Optional external battery cabinets are available to extend battery run times.

Dynamic Bypass

The Liebert GXT3 provides an alternate path for mains power to the connected loads in the unlikely event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature, or UPS failure condition, the UPS automatically transfers the connected loads to bypass.

NOTE The bypass power path does not protect the connected loads from disturbances on the mains.

1.5 Operating Mode

The UPS operation modes include the following: Mains (AC) Mode, Bypass Mode, Battery Mode, Battery Recharge Mode and Frequency Converter Mode.

For the descriptions of operation mode indicators and control buttons, refer to 3.0 - Operation and Display Panel.

1.5.1 Mains (AC) Mode

During Mains (AC) Mode, the mains provides energy to the Liebert GXT3. The filters, PFC circuit and inverter process this power to provide high-level power to connected loads. Meanwhile, the UPS maintains the batteries in a fully charged state.

Product Description

Page 14 of the Liebert GXT3 user manual — 1.5.5 Frequency Converter Mode
Page 14 · click to enlarge
Page 14

1.5.2 Manual Bypass Mode

Manual Bypass Mode occurs when the Standby/Manual Bypass button is pressed and held for about 2 seconds while the Liebert GXT3 is in Mains (AC) Mode. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting). During Bypass Mode, mains power bypasses the inverter and provides energy to the connected load.

NOTICE

Turning Off the UPS in Bypass Mode will result in loss of output power.

1.5.3 Battery Mode

The Liebert GXT3 enters Battery Mode when mains power fails or is outside acceptable values. The battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the connected loads.

When the Liebert GXT3 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low (this Low Battery Warning is user-configurable).

In Battery Mode, the AC Input indicator is Off and the Battery Level indicators illuminate to warn that a mains problem has occurred. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 7.0 - Troubleshooting.

For approximate battery run times, refer to Table 15.

NOTICE

Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power. If the UPS is turned Off manually, it must be manually restarted after mains power returns. If the UPS is turned Off by a communication signal or because the batteries are depleted, it will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 - Configuration Program).

1.5.4 Battery Recharge Mode

Once mains power is applied to the Liebert GXT3, the Battery Charger begins charging the batteries.

1.5.5 Frequency Converter Mode

All models of the Liebert GXT3 are capable of frequency conversion. Frequency Conversion Mode can be selected using the configuration program. Allowable frequency operating modes include:

  • Auto Sensing - 50Hz or 60 Hz – Bypass Enabled
  • Auto Sensing - 50Hz or 60 Hz – Bypass Disabled
  • Frequency Converter - 50Hz – Bypass Disabled
  • Frequency Converter - 60Hz – Bypass Disabled

! CAUTION Do not touch the AC input receptacle when the UPS is operating. AC input voltages may still be present even when the AC input indicator is Off.

Product Description

Page 15 of the Liebert GXT3 user manual — Installation Clearances
Page 15 · click to enlarge
Page 15

2.0 I NSTALLATION

2.1 Unpacking and Inspection

Unpack the UPS and conduct the following checks:

  • Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer or Emerson ® representative immediately.
  • Check the accessories against the delivery list. If there is any discrepancy, contact your local dealer or your Emerson representative immediately.

2.2 What’s Included

  • Terminal Block Communication terminals
  • Compact Disk with:
  • Liebert MultiLink ®
  • Configuration Program
  • User Manual
  • USB Cable: one, 2m (6-1/2 ft.) long
  • Mounting hardware, including screws and handles
  • Plastic tower stand sets: 2 (four pieces)
  • Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
  • for 700VA - 1500VA: (2) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long
  • for 2000VA - 3000VA:
  • (3) 10A IEC C13 C14 Output Cable, 2m (6-1/2 ft.) long
  • (1) CEE 7/7 (Schuko) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long
  • (1) BS1363 (UK) to IEC C20 Input Cable, 2.5m (8-1/5 ft.) long

2.3 Preparation for Installation

2.3.1 Installation Environment

  • Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off. The installation environment should meet the specifications in 9.0 - Specifications .
  • Place the UPS in an area where airflow around the unit is unrestricted and away from water, flammable liquids, gases, corrosives and conductive contaminants. Avoid direct sunlight.

Installation Clearances

Maintain a clearance of at least 100mm (4 inches) in the front and rear of the Liebert GXT3. Do not obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the Liebert GXT3.

Installation · With GXT3 UPS

Page 16 of the Liebert GXT3 user manual — 2.4.1 Tower Installation
Page 16 · click to enlarge
Page 16

2.4 Mechanical Installation

The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery cabinets.

2.4.1 Tower Installation

To install the Liebert GXT3 as a tower:

1. Take out support bases from the accessories (see Figure 6 ).

Figure 6 Support bases

Liebert GXT3 — 2.4.1 Tower Installation diagram (page 16)
Fig. 7 · 2.4.1 Tower Installation
Liebert GXT3 — 2.4.1 Tower Installation diagram (page 16)
Fig. 8 · 2.4.1 Tower Installation

2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the spacers delivered with the battery cabinet. 3. Connect the spacers and the support bases as shown in Figure 6. Each Liebert GXT3 needs two assembled support bases, one in the front and one in the rear. 4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3. a. Remove the front plastic bezel cover (see Figure 7).

Figure 7 Remove the front plastic bezel cover

Liebert GXT3 — 2.4.1 Tower Installation diagram (page 16)
Fig. 9 · 2.4.1 Tower Installation

b. Pull the operation and display panel, rotate it 90 degrees clockwise and snap it back into position (see Figure 8).

Show 5 more labels / short text on this page
Installation · Spacers Connectors · Support Bases · Front Plastic · Bezel Cover
Page 17 of the Liebert GXT3 user manual — Figure 8 Rotate the operation and display panel
Page 17 · click to enlarge
Page 17

Figure 8 Rotate the operation and display panel

Liebert GXT3 — Figure 8 Rotate the operation and display panel diagram (page 17)
Fig. 10 · Figure 8 Rotate the operation and display panel

Operation and Display Panel Rotated Clockwise 90 Degrees

c. Pull the logo on the front plastic bezel cover, rotate it 90 degrees clockwise and snap it back into position. The rotated front plastic bezel cover is shown in Figure 9. d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation and display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing for users. 5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs four support bases, as shown in Figure 9.

Figure 9 Tower installation

Liebert GXT3 UPS and External Battery Cabinet

Liebert GXT3 — Figure 8 Rotate the operation and display panel diagram (page 17)
Fig. 11 · Figure 8 Rotate the operation and display panel
Liebert GXT3 — Figure 8 Rotate the operation and display panel diagram (page 17)
Fig. 12 · Figure 8 Rotate the operation and display panel

Rotated for Tower Operation

Support Bases Support Bases

Show 4 more labels / short text on this page
Installation · Liebert GXT3 UPS · Operation and · Display Panel
Page 18 of the Liebert GXT3 user manual — 2.4.2 Rack Installation
Page 18 · click to enlarge
Page 18

2.4.2 Rack Installation

  • NOTE
  • When the Liebert GXT3 is installed in a rack, the UPS must be supported by a shelf, brackets, or slide rails on each side. The factory-supplied rack-mount ears cannot support the weight of the UPS. They are used to move the UPS into and out of the rack and attach the UPS to the rack.
  • Mounting hardware and slide rails are sold separately. Contact your local dealer or Emerson ® representative for these options and any assistance.

To install a Liebert GXT3 UPS in a rack:

1. Unpack the two bracket assemblies and mounting hardware from the rack-mounting kit (P/N: RMKIT18-32). Bracket assembly includes inner member, front member and rear member. They are interchangeable between left-hand and right-hand. Mounting hardware includes M4 screws and M5 screws. 2. Remove inner member of each bracket assembly by extending it to its outermost position, depressing the retaining latch and then pulling the inner member from the bracket assembly (see Figure 10 ).

Figure 10 Pulling inner member from each bracket assembly

Liebert GXT3 — 2.4.2 Rack Installation diagram (page 18)
Fig. 13 · 2.4.2 Rack Installation
3. Determine the desired height and mounting position of the Liebert GXT3 inside the rack’s vertical rails.

! CAUTION Reduce risk of tipping the rack by installing the Liebert GXT3 in the lowest possible rack position.

4. Attach the rear member of each bracket assembly to the rack’s vertical rails with two factorysupplied M5 screws (see Figure 11 ).

Installation

Page 19 of the Liebert GXT3 user manual — Figure 11 Installing rear member of each bracket assembly
Page 19 · click to enlarge
Page 19

Figure 11 Installing rear member of each bracket assembly

M5 screw (4 pcs)

5. Extend bracket assembly by sliding the front member forward until it touches the rack’s front vertical rails (adjustable length: 18 inches to 32 inches). 6. Use two M5 screws to attach each front member onto the front vertical rails through the installation holes. Make sure that the bracket assemblies are at the same mounting height on all four of the rack’s vertical rails (see Figure 12 .)

Figure 12 Installing front member of each bracket assembly

M5 screw (4 pcs)

7. Fasten the rear and front members together using four M4 screws and four M4 nuts (M4 nuts have been installed on the rear member before delivery) per bracket assembly, as shown in Figure 13 .

Figure 13 Fastening rear member and front member together

M4 screw (8 pcs) Rear member

M4 nut (8 pcs)

Show 9 more labels / short text on this page
Installation · Vertical pole · Rear member · Front member · Slide · Front vertical pole · Front member · Rear member · Front member
Page 20 of the Liebert GXT3 user manual — Figure 14 Installing inner members
Page 20 · click to enlarge
Page 20
8. Fasten inner members pulled from the bracket assemblies in Step 2 to the UPS on both sides with eight M4 screws provided in this kit. Make sure that the retaining latch is near the rear of the UPS, as shown in Figure 14 .

Figure 14 Installing inner members

Liebert GXT3 — Figure 14 Installing inner members diagram (page 20)
Fig. 14 · Figure 14 Installing inner members
9. Use M4 screws to install ears of accessories on both sides of the UPS, as shown in Figure 15 .
10. Insert the UPS, with inner members attached, into bracket assemblies by inserting top and bottom edges of inner members into the top and bottom curved tracks of front members and sliding the UPS into the rack, as shown in Figure 16 .
Liebert GXT3 — Figure 14 Installing inner members diagram (page 20)
Fig. 15 · Figure 14 Installing inner members

The UPS should move smoothly into the bracket assemblies. If not, recheck alignment of front and rear members from Steps 4 through 7.

Installation

Page 21 of the Liebert GXT3 user manual — 2.5.1 Connecting to AC Mains and Loads
Page 21 · click to enlarge
Page 21
11. Through the rack-mount ears, use M5 screws provided in this kit to secure the front of the UPS to the rack’s vertical rails to prevent the UPS from sliding out of position. 12. If optional Liebert external battery cabinets will be connected to the UPS, they can be placed all on one side of the UPS or stacked beneath the UPS. The installation procedures are the same as those for the UPS .

2.5 Cable Connection

The Liebert GXT3 rear panel has an input receptacle and output receptacles. Refer to 1.3.2 - Rear Panel Features for details. The battery cables are supplied with the battery cabinet.

2.5.1 Connecting to AC Mains and Loads

Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local electrical codes. The wall receptacle must be grounded.

Emerson® recommends installing an upstream circuit breaker of the same series as the Liebert GXT3’s input circuit breaker. The upstream breaker should have a higher capacity than the UPS input circuit breaker.

The specification of input circuit breaker on the rear panel of the UPS is given in Table 2.

Table 2 Specification of input circuit breaker

Liebert GXT3 — 2.5.1 Connecting to AC Mains and Loads diagram (page 21)
Fig. 16 · 2.5.1 Connecting to AC Mains and Loads
1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.
3. Plug the input receptacle of the Liebert GXT3 into the input power connection .

2.5.2 Connecting Battery Cables 1. Switch Off the input breaker of the battery cabinet. 2. Take out the battery cable included with the battery cabinet. 3. Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect the other end to any battery port on the rear panel of the battery cabinet. 4. Switch On the battery breaker on the rear of the external battery cabinet. 5. Use the Configuration Program included with the UPS to specify the number of external battery cabinets connected to the Liebert GXT3. See Table 15 for approximate battery run times.

Installation

Page 22 of the Liebert GXT3 user manual — 2.6 Connecting Communication Cables
Page 22 · click to enlarge
Page 22

2.6 Connecting Communication Cables

Communication cable connection includes USB and option card cables.

2.6.1 Connecting USB Communication Cables 1. Remove the USB communication cables from the accessories box. 2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert GXT3 (see Figure 2). 3. Insert the other end of the USB communication cable to the USB port of the computer.

2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables 1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT3 and set it aside. 2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws. 3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided with the card.

To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual. Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site: www.liebert.com

Installation

Page 23 of the Liebert GXT3 user manual — 3.1.2 Standby/Manual Bypass button
Page 23 · click to enlarge
Page 23

Operation and Display Panel

3.0 O PERATION AND D ISPLAY P ANEL

The operation and display panel, shown in Figure 17, is on the front panel of the Liebert GXT3 (see Figure 1).

Figure 17 Operation and display panel

Liebert GXT3 — 3.0 O PERATION AND D ISPLAY P ANEL diagram (page 23)
Fig. 17

3.1 Control Buttons

The operation and display panel has two control buttons: the On/Alarm Silence/Manual Battery Test button and the Standby/Manual Bypass button.

3.1.1 On/Alarm Silence/Manual Battery Test button

The On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and has three functions (see Table 3).

Table 3 Functions of the On/Alarm Silence/Manual Battery Test button

Liebert GXT3 — 3.1.1 On/Alarm Silence/Manual Battery Test button diagram (page 23)
Fig. 18 · 3.1.1 On/Alarm Silence/Manual Battery Test button

ON Press the button once for 3 seconds To start up the UPS

Alarm silence 1 Press the button for at least half a second To silence alarms 2

Manual Battery Test Press the button for at least half a second while operating in Mains (AC) Mode with no alarms present. To initiate a manual battery test

1. The low battery and bypass reminder alarms cannot be silenced. 2. After the alarm is silenced, UPS will reactivate the alarm system to alert of additional problems.

3.1.2 Standby/Manual Bypass button

The Standby/Manual Bypass button controls output power to connected load(s) and has two functions (see Table 4).

Table 4 Functions of the Standby/Manual Bypass button

Liebert GXT3 — 3.1.2 Standby/Manual Bypass button diagram (page 23)
Fig. 19 · 3.1.2 Standby/Manual Bypass button

Manual Bypass Press the button once and hold it for about 2 seconds. 1 To initiate a manual transfer of the connected loads to the internal bypass, if available

Standby Press the button twice within four seconds while the UPS is in Manual Bypass or Battery Mode. 2 To shut down the UPS and shut Off all power to the connected loads

1. If the bypass is not available due to voltage or frequency, pressing this button once will be ignored. 2. Perform all necessary shutdown procedures on connected loads before turning Off the Liebert GXT3.
Page 24 of the Liebert GXT3 user manual — Load Level Indicators
Page 24 · click to enlarge
Page 24

Operation and Display Panel

3.2 Indicators

The operation and display panel has seven indicators (see Figure 16). The indicators can be divided into two groups according to their applications: level indicators and UPS status indicators.

3.2.1 Level Indicators

Battery Level Indicators

The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%). The battery level indicators will illuminate as shown in Figure 18.

Figure 18 Battery level indicators

Liebert GXT3 — 3.2.1 Level Indicators diagram (page 24)
Fig. 20 · 3.2.1 Level Indicators

Load Level Indicators

The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in Figure 19.

Figure 19 Load level indicators

Liebert GXT3 — Load Level Indicators diagram (page 24)
Fig. 21 · Load Level Indicators
Page 25 of the Liebert GXT3 user manual — 3.2.2 UPS Status Indicators
Page 25 · click to enlarge
Page 25

Operation and Display Panel

3.2.2 UPS Status Indicators

UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator, inverter indicator and bypass indicator. Table 5 shows the symbols and their meanings.

Table 5 UPS status indicators

Indicator Icon Color Description

Fault Indicator Red On if the UPS has detected a fault; Off if there is no fault

AC input Indicator Green On when the mains input power is normal; Off during mains failure; flashing when mains power is outside specifications

Battery Indicator Amber On when the battery is supplying power; Off when the battery is not supplying power

Inverter Indicator Green On when the inverter is supplying power; Off when the inverter is not supplying power

On when the bypass is supplying power; Off when the bypass is not supplying power; flashing when mains power is outside specifications

UPS Status · Bypass Indicator Amber

Page 26 of the Liebert GXT3 user manual — 4.4 Manual Bypass
Page 26 · click to enlarge
Page 26

4.0 O PERATION

This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the UPS.

4.1 Startup Checklist for the Liebert GXT3

Before starting the UPS, perform these checks:

___ 1. Check that the input plugs and loads are connected properly and reliably.

___ 2. Check that the battery cable is connected properly.

___ 3. Check that the communication cables are connected properly.

4.2 Starting the UPS 1. Turn On the input circuit breaker (see Figure 2 for its position). 2. Turn On the UPS by pressing the On/Alarm Silence/Manual Battery Test button for three seconds. After the button is pressed, the LEDs on the display will signal that the unit has initiated the startup process. 3. Once the inverter LED has been illuminated, turn On the connected loads. 4. Check the status indicators to determine whether the Liebert GXT3 is operating normally. 5. Check the load level indicators to verify that the connected load does not exceed the UPS’s rated capacity.

The UPS is now providing conditioned power to the loads.

4.3 Manual Battery Test

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from mains power with no alarm conditions present.

  • If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.
  • Retest the batteries after 24 hours of charging.
  • After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact your local Emerson ® representative or Emerson Network Power Channel Support.
  • If none of the five Battery LEDs illuminate during a manual battery test, check the battery connection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery test again.
  • If none of the five Battery LEDs illuminate during the second manual battery test, replace batteries and contact your local Emerson representative or Emerson Channel Support.

4.4 Manual Bypass

Press the Standby/Manual Bypass button once while the UPS is in Mains (AC) Mode and hold it for about 2 seconds. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of mains power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to 7.0 - Troubleshooting.)

Operation

Page 27 of the Liebert GXT3 user manual — 4.5 Shut Down the Liebert GXT3
Page 27 · click to enlarge
Page 27

4.5 Shut Down the Liebert GXT3 1. Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding it for about 2 seconds. If manual bypass is not available, disregard the first step. 2. Press the Standby/Manual Bypass button twice within four seconds, each time holding it for about two seconds, to shut down the UPS. The UPS will shut down about 30 seconds after the button is pressed.

Power to the connected loads is now Off.

4.6 Disconnecting Input Power from the Liebert GXT3 1. After the UPS has been shut down as detailed in 4.5 - Shut Down the Liebert GXT3, disconnect the input cable plug. 2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete. 3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering Off the UPS, the UPS ceases output and the load is powered Off.

Operation

Page 28 of the Liebert GXT3 user manual — 5.1.1 Liebert MultiLink
Page 28 · click to enlarge
Page 28

5.0 C OMMUNICATION

This section describes UPS communication over the three types of communication connections on the rear of the Liebert GXT3:

  • Liebert IntelliSlot port
  • USB port (standard B-type)
  • Terminal Block Communication

! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables.

5.1 Liebert IntelliSlot Communication Cards

The Liebert IntelliSlot port accepts three optional cards:

  • Liebert IntelliSlot SNMP Card
  • Liebert IntelliSlot Relay Card
  • Liebert IntelliSlot 485 Card.

The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.

The Liebert IntelliSlot 485 Card is used to connect the UPS and a BMS.

Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at:

multilink.liebert.com

5.1.1 Liebert MultiLink

Liebert MultiLink monitors the UPS continuously and can shut down the computer or server in the event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.

Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot SNMP Card or Liebert IntelliSlot Web Card is installed in the UPS. An optional Liebert MultiLink License Kit permits shutting down the UPS over a network.

For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert MultiLink License Kits, visit the Liebert Web site (www.liebert.com) or contact your local Emerson® representative.

Communication

Page 29 of the Liebert GXT3 user manual — NOTICE
Page 29 · click to enlarge
Page 29

5.2 USB Port Communication

The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert MultiLink®. The configuration program can be completed through the communication port.

5.2.1 Configuration Program

Accessing the Configuration Program via USB is a new feature of the Liebert GXT3. For most users, the factory default settings will be adequate. This section illustrates the features available for modification, as well as the factory default setting.

The USB configuration program allows these features of the Liebert GXT3 to be changed:

  • Enable/Disable Auto-Restart
  • Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass disabled
  • Set the Low Battery Warning alarm time from 2 to 30 minutes
  • Enable/Disable the Auto-Battery test
  • Enable/Disable Auto-Restart after removing Remote shutdown
  • Set the wiring mode of Remote shutdown
  • Set the Auto-Enable output
  • Set the Auto-Battery test to 7, 14, 21 or 28 days
  • Select the number of external battery cabinets connected to the UPS to adjust the remaining run time calculated by Emerson ® software products
  • Select one of multiple output voltages to match various voltages (see Table 6 ).

Table 6 Output voltage option, all models

Factory Default Setting Output Voltage Option

230VAC 220VAC, 230VAC and 240VAC

NOTICE

The output voltage settings cannot be changed while the UPS is On and powering connected loads.

  • NOTE
  • This program is compatible with UPS models beginning with ‘GXT3,’ as in ‘GXT3-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.
  • A computer running Windows 2000 ® , XP ® or Vista ® is required to set up and run the configuration program.

Communication

Page 30 of the Liebert GXT3 user manual — 5.3.1 Any Mode Shutdown
Page 30 · click to enlarge
Page 30

5.3 Terminal Block Communication

The Terminal Block includes eight pins, as shown in Figure 20.

Figure 20 Terminal Block Communication pin layout

Liebert GXT3 — 5.3 Terminal Block Communication diagram (page 30)
Fig. 22 · 5.3 Terminal Block Communication

5.3.1 Any Mode Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.

Any Mode Shutdown can be operated locally or remotely:

  • Local Any Mode Shutdown can be performed by shorting Pin 1 and Pin 2.
  • Remote Any Mode Shutdown can be performed using a switch connected to Pin 1 and Pin 2 and mounted at a remote location.

A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS.

The connection to the UPS for remote connection will be via terminal block connector.

Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.

! WARNING When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the Liebert GXT3’s output can turn On automatically and without warning if the Pin 1 and Pin 2 connection is changed.

Communication

Page 31 of the Liebert GXT3 user manual — 5.3.4 Low Battery
Page 31 · click to enlarge
Page 31

5.3.2 Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

  • Local Battery Mode shutdown can be performed by shorting Pin3 and Pin4.
  • Remote Battery Mode Shutdown can be performed using a switch connected to Pin3 and Pin4 and mounted at remote location.

A current-limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.

The connection to the Liebert GXT3 for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the mains power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

5.3.3 On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

5.3.4 Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

  • Rated Voltage: 30V (AC or DC)
  • Rated Current: 300mA

Communication

Page 32 of the Liebert GXT3 user manual — 6.1 Replacing the Internal Battery Pack
Page 32 · click to enlarge
Page 32

6.0 M AINTENANCE

This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s status and checking UPS functions.

  • ! WARNING The battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the battery pack:
  • Remove rings, watches and other metal objects.
  • Use tools with insulated handles.
  • Do not lay tools or other metal objects on the batteries.
  • If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson ® representative immediately.
  • Do not dispose of batteries in a fire. The batteries may explode.
  • Handle, transport and recycle batteries in accordance with local regulations.

6.1 Replacing the Internal Battery Pack

The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Refer to Table 7 for internal battery pack part numbers for Liebert GXT3 UPS:

Table 7 Replacement battery pack model numbers

Liebert GXT3-700RT230 GXT3-5A48BATKIT 1

Liebert GXT3-1000RT230 GXT3-5A48BATKIT 1

Liebert GXT3-1500RT230 GXT3-7A48BATKIT 1

Liebert GXT3-2000RT230 GXT3-9A48BATKIT 1

Liebert GXT3-3000RT230 GXT3-9A72BATKIT 1

Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to obtain the part number and pricing of the appropriate replacement battery pack.

6.1.1 Battery Replacement Procedures 1. Gently remove the front plastic bezel cover from the UPS. 2. Loosen and remove the six screws on the battery door, as shown in Figure 21. 3. Lay the battery door and screws aside for reassembly.

Figure 21 Removing the front plastic bezel cover and battery door

Liebert GXT3 — 6.1 Replacing the Internal Battery Pack diagram (page 32)
Fig. 23 · 6.1 Replacing the Internal Battery Pack
4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in Figure 22 .
Show 8 more labels / short text on this page
Maintenance · Replacement Internal Battery · Quantity Required · UPS Model Number · Pack Model Number · Battery Door · Screws, 6 · Front Bezel
Page 33 of the Liebert GXT3 user manual — 6.2 Battery Charging
Page 33 · click to enlarge
Page 33

Figure 22 Disconnecting the battery plug and battery connector (front view)

Liebert GXT3 — Figure 22 Disconnecting the battery plug and battery connector (front view) diagram (page 33)
Fig. 24 · Figure 22 Disconnecting the battery plug and battery…

Battery Connector Battery Connector

5. Grasp the battery handle and pull the internal battery pack out of the UPS, as shown in Figure 23 .

Figure 23 Pulling out the battery

Liebert GXT3 — Figure 22 Disconnecting the battery plug and battery connector (front view) diagram (page 33)
Fig. 25 · Figure 22 Disconnecting the battery plug and battery…

Pull Out with Battery Handle

6. Unpack the new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson® representative or Emerson Channel Support. 7. Line up and slide in the new internal battery pack. 8. Reconnect the battery plug and battery receptacle 9. Gently push the battery wire and internal battery pack back into the UPS. 10. Reattach the front battery door with the six screws. 11. Reattach the front plastic bezel cover to the UPS.

Do not replace the battery while the UPS is in Battery Mode. This will result in a loss of output power and will drop the connected load.

6.2 Battery Charging

The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert GXT3 charges the batteries continuously when it is connected to the mains input power.

If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.

Maintenance · Internal Battery Pack · Battery Handle

Page 34 of the Liebert GXT3 user manual — 6.5 Checking UPS Functions
Page 34 · click to enlarge
Page 34

6.3 Precautions

Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:

  • Turn Off and unplug the Liebert GXT3 before cleaning it.
  • Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
  • Never block or insert any objects into the ventilation holes or other openings of the UPS.
  • Do not place the Liebert GXT3 power cord where it might be damaged.

6.4 Checking UPS Status

Emerson® recommends checking the UPS operation status every six months.

  • Check whether the UPS is faulty: Is the Fault Indicator On? Is the UPS sounding an alarm?
  • Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support.
  • Check whether the battery is discharging. When the mains input is normal, the battery should not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson Channel Support.

6.5 Checking UPS Functions

Emerson recommends checking the UPS functions once every six months.

Back up the load data before conducting the UPS functions check. Procedures are as follows:

1. Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal. 2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators are On and the UPS is operating normally. 3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode. The UPS should initiate a battery self-test. Check to determine whether the battery is operating normally. If not, stop and contact your local Emerson representative or Emerson Channel Support

Maintenance

Page 35 of the Liebert GXT3 user manual — A B C D E
Page 35 · click to enlarge
Page 35

7.0 T ROUBLESHOOTING

This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.

7.1 UPS Symptoms

The following symptoms indicate the Liebert GXT3 is malfunctioning:

  • The relative indicators illuminate, indicating the UPS has detected a problem.
  • An alarm buzzer sounds, alerting the user that the UPS requires attention.

7.1.1 Indicators

In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 24. The descriptions are listed in Table 8.

Figure 24 Battery level indicator

A B C D E

Table 8 Indicator descriptions

A - E On bypass from output overload (half-second beep every half-second)

A On bypass due to overtemperature condition (1-second beep every 4 seconds)

B On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

C On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)

D On bypass due to PFC failure (1-second beep every 4 seconds)

E On bypass due to inverter failure (1-second beep every 4 seconds)

A&B UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarm

A&C UPS failed battery test (2-second beep every 60 seconds)

A&E Bypass feedback (1-second beep every 4 seconds)

B&E Short circuit on the output

C&E UPS shutdown by command from communication (USB port or Liebert IntelliSlot® port) (no audible)

Utility LED flash L-N reverse

Internal battery not connected (continuous horn); check battery connection, power down and restart UPS

Bypass Indicator Flashing Mains power voltage or frequency is out of tolerance; bypass is unavailable

A - E indicators are shown in Figure 24. If the UPS experiences an overload, the UPS will transfer from bypass back to inverter approximately 5 minutes after the overload ends.

Troubleshooting · Indicator Diagnosis/Audible alarm · Battery Indicator Flashing

Page 36 of the Liebert GXT3 user manual — 7.2 Troubleshooting
Page 36 · click to enlarge
Page 36

7.1.2 Audible Alarm

An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in Table 9.

Table 9 Audible alarm description

Battery discharge Half-second beep every 10 seconds

Low battery Two half-second beeps every 5 seconds

UPS fault, load on bypass 1-second beep every 4 seconds

UPS fault, no power to load Continuous

Overload Half-second beep every half second

Battery replacement 2-second beep every 60 seconds

Wiring problem (loss of proper grounding for UPS) Continuous

Bypass reminder 1-second beep every 2 minutes

7.2 Troubleshooting

In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the fault persists, contact Emerson® Channel Support.

Table 10 Troubleshooting table

UPS fails to start when the On/Alarm Silence/Manual Battery Test button is pressed

Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.

UPS is short-circuited or overloaded

UPS is not plugged in UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle.

UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.

UPS input protection fuse has blown/opened

Battery indicator is illuminated

UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS.

Mains power is out of tolerance

Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries.

UPS is overloaded Check load level indicator and reduce the load on the UPS.

UPS has reduced battery backup time

Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit.

Batteries may not be able to hold a full charge due to age

Fault and Bypass indicators and all LED segments of battery level indicator are illuminated

Check load level indicator and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load for faults.

UPS is overloaded or load is faulty

Ensure UPS is not overloaded, ventilation holes are not blocked and room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS cannot restart, contact your local dealer, Emerson® representative or Emerson Channel Support.

Fault and Bypass indicators and diagnostic A indicator are illuminated

UPS has been shut down due to temperature condition; load is on bypass power

Fault and Bypass indicators and diagnostic B indicator are illuminated

UPS internal DC bus overvoltage

UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.

Show 4 more labels / short text on this page
Troubleshooting · Condition Alarm · Battery loss Continuous · Problem Cause Solution
Page 37 of the Liebert GXT3 user manual — 7.1.2 Audible Alarm
Page 37 · click to enlarge
Page 37

Table 10 Troubleshooting table (continued)

Fault and Bypass indicators and diagnostic C indicator are illuminated

UPS DC/DC fault UPS requires service. Contact your local dealer, Emerson® representative or Emerson Channel Support.

Fault indicator and diagnostic D indicator are illuminated

UPS PFC (Power Factor Correction Circuit) fault

UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.

Fault and Bypass indicators and diagnostic E indicator are illuminated

UPS inverter fault UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.

Fault indicator and diagnostic A and C indicators are illuminated

UPS failed the battery test Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support.

Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Emerson representative or Emerson Channel Support.

Fault and Bypass indicators and diagnostic C and E indicators are illuminated

UPS has been shut down by a command from the communications port(s)

UPS failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarm

Fault indicator and diagnostic A and B indicators are illuminated

Ensure fan is not blocked up. If the fault is not removed, contact your local dealer, Emerson representative or Emerson Channel Support.

UPS detected a line-to-neutral reversal or a loss of proper grounding for UPS; continuous horn and UPS cannot start up in standby status. This is active only when power is first applied to the input. Once the UPS is running, the AC input indicator will flash, unless the input wiring is correctly changed.

AC input indicator is flashing.

Contact a qualified electrician to verify site wiring.

Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.

Battery indicator is flashing. Battery source is not available; continuous horn.

The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable.

Because the voltage or frequency is outside acceptable limits, the bypass is disabled.

Bypass indicator is flashing.

When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the top panel of the Liebert GXT3.

Troubleshooting · Problem Cause Solution

Page 38 of the Liebert GXT3 user manual — 8.0 B ATTERY C ABINET
Page 38 · click to enlarge
Page 38

8.0 B ATTERY C ABINET

Optional battery cabinets are available for the Liebert GXT3. The external battery connector and input breaker are on the battery cabinet’s rear panel, as shown in Figure 25. For battery cabinet specifications, refer to Table 13.

Figure 25 Battery cabinet

Liebert GXT3 — 8.0 B ATTERY C ABINET diagram (page 38)
Fig. 26

! WARNING Do not contact the external battery connector and ground without wearing protective gloves and clothing and taking other precautions against electrical shock. The battery loop and AC input are not insulated, which may cause a dangerous voltage between the external battery connector and ground.

Battery Cabinet · Input Breaker · External Battery Connector

Page 39 of the Liebert GXT3 user manual — GXT3-700RT230 GXT3-1000RT230
Page 39 · click to enlarge
Page 39

9.0 S PECIFICATIONS

The specifications of the Liebert GXT3 are listed in Table 11 and Table 12.

Table 11 Specifications of GXT3-700RT230 and GXT3-1000RT230 UPS

GXT3-700RT230 GXT3-1000RT230

Model Rating 700VA/630W 1000VA/900W

Dimensions, D x W x H, mm (in)

Unit 497 x 430 x 85 (19.6 x 16.9 x 3.3)

Shipping 617 x 570 x 262 (24.3 x 22.4 x 10.3)

Unit 16.8 (37)

Voltage Range (typical) 230VAC nominal; variable based on output load

90% ~ 100% loading 177VAC/280VAC

70% ~ 90% loading 168VAC/280VAC

30% ~ 70% loading 150VAC/280VAC

0 ~ 30% loading 115VAC/280VAC

Frequency 40Hz ~ 70Hz; Auto Sensing

Input Power Receptacle C14

AC-AC Efficiency > 88% AC-AC, minimum

Output Receptacles C13 × 6

Voltage 220/230/240VAC (user configurable); ±3%

Frequency 50Hz or 60Hz

Mains (AC) Mode Overload 200% for 2 seconds; 150% for 1 minute with transfer to bypass

Charger Current 1.3

Type Valve-regulated, nonspillable, lead acid

Qty × V× Rating 4 × 12V × 5.0Ah

Battery Mfr/Part# YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245

Backup Time See Table 15 - Battery run times

Recharge Time 3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)

Operating Temp 0ºC to +40ºC (+32ºF to +104ºF); Table 14 - Operating temperature parameters

Storage Temp -15ºC to +50ºC (5ºF to 122ºF)

Relative Humidity 0%RH to 95%RH, non-condensing

Operating Elevation Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating

Storage Elevation 15,240 (50,000 ft.) maximum

Audible Noise < 46 dBA, at 1 meter (3.2ft) from the rear < 43 dBA, at 1 meter (3.2ft) from the front or sides

Safety IEC/EN/AS 62040-1:2008, GS mark

RFI/EMI IEC/EN/AS 62040-2 2nd Ed (Category C2) = CISPR22 Class A

Surge Immunity IEC/EN 62040-2 2nd Ed (IEC/EN 61000-4-5)

Transportation ISTA Procedure 1A

Show 12 more labels / short text on this page
Specifications · Product model · Parameters · Weight, kg (lb) · Shipping 20 (44) · Input AC · Output AC · Waveform Sine wave · Internal Battery Charger · Battery · Environmental Requirements · Agency
Page 40 of the Liebert GXT3 user manual — CSB/ GP 1272
Page 40 · click to enlarge
Page 40

Table 12 Specifications of the Liebert GXT3-1500RT230, GXT3-2000RT230 and GXT3-3000RT230

GXT3-1500RT230 GXT3-2000RT230 GXT3-3000RT230

Model Rating 1500VA/1350W 2000VA/1800W 3000VA/2700W

Dimensions, D x W x H, mm (in)

Unit 497 × 430 × 85 (19.6 x 16.9 x 3.3)

602 × 430 × 85 (23.7 x 16.9 x 3.3)

Shipping 617 x 570 x 262 (24.3 x 22.4 x 10.3)

717 x 570 x 262 (28.2 x 22.4 x 10.3)

Unit 23.2 (51.1) 25.5 (56.1) 32.4 (71.4)

Shipping 26 (57.3) 28 (61.7) 35 (77.2)

Voltage Range (typical) 230VAC nominal; variable based on output load

90% ~ 100% loading 177VAC/280VAC 196VAC/280VAC

70% ~ 90% loading 168VAC/280VAC 184VAC/280VAC

30% ~ 70% loading 150VAC/280VAC 161VAC/280VAC

0 ~ 30% loading 115VAC/280VAC 115VAC/280VAC

Frequency 40Hz ~ 70Hz; Auto Sensing

Input Power Receptacle C14 C20

AC-AC Efficiency > 88% AC-AC, minimum

Output Receptacles C13 x 6 C13 x 6; C19 x 1

Voltage 220/230/240VAC (user configurable); ±3%

Frequency 50Hz or 60Hz

Mains (AC) Mode Overload 200% for 2 seconds; 150% for 50 seconds 200% for 2 seconds; 150% for 55 seconds

Charger Current 1.88 2.71 2.5 Battery

Type Valve-regulated, nonspillable, lead acid

Qty × V× Rating 4 × 12V × 7.2Ah 4 × 12V × 9.0Ah 6 × 12V × 9.0Ah

CSB/ GP 1272

CSB/ HR 1234W F2

Backup Time See Table 15 - Battery run time

Recharge Time 3 hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)

Operating Temp 0ºC to 40ºC (32ºF to 104ºF); Table 14 - Operating temperature parameters

Storage Temp -15ºC to +50ºC (5ºF to 122ºF)

Relative Humidity 0%RH to 95%RH, non-condensing

Operating Elevation Up to 3000m (10,000 ft.) at 25ºC (77ºF) without derating

Storage Elevation 15000m (50,000 ft.) maximum

Audible Noise < 45 dBA max. at 1 meter (3.2ft.) front and side

< 48 dBA max. at 1 meter (3.2ft.) front and side

< 46 dBA, at 1 meter (3.2ft.) rear

< 48 dBA, at 1 meter (3.2ft.) rear

Safety IEC/EN/AS 62040-1:2008, GS mark

RFI/EMI IEC/EN/AS 62040-2 2nd Ed. (Category C2) = CISPR22 Class A

Surge Immunity IEC/EN 62040-2 2nd Ed. (IEC/EN 61000-4-5)

Transportation ISTA Procedure 1A

Show 12 more labels / short text on this page
Specifications · Product model · Parameters · Weight, kg (lb) · Input AC · Output AC · Waveform Sine wave · Internal Battery Charger · Battery Mfr/Part# Panasonic/UP-RW1236 · Panasonic/UP-RW1245 · Environmental Requirements · Agency
Page 41 of the Liebert GXT3 user manual — GXT3-48VBATT GXT3-72VBATT
Page 41 · click to enlarge
Page 41

Table 13 Battery cabinet specifications

GXT3-48VBATT GXT3-72VBATT

GXT3-700RT230, GXT3-1000RT230, GXT3-1500RT230, GXT3-2000RT230 GXT3-3000RT230

Dimensions, D x W x H, mm (in)

Unit 497 × 430 × 85 (19.7 x 16.9 x 3.3)

602 × 430 × 85 (23.6 x 16.9 x 3.3)

Shipping 617 x 570 x 262 (24.3x 22.4 x 10.3)

717 x 570 x 262 (28.2 x 22.4 x 10.3)

Unit 32 (70.5) 42 (92.6)

Shipping 35 (77.2) 46 (101.4)

Type Valve-regulated, nonspillable, lead acid

Qty × V× Rating 2 × 4 × 12V × 9.0Ah 2 × 6 × 12V × 9.0Ah

Battery Mfr/Part# Panasonic/UP-RW1245 CSB/HR 1234W F2

Backup Time See Table 15 - Battery run times

Operating Temperature 0ºC to 40ºC (32ºF to 104ºF)

Storage Temperature -15ºC to +40ºC (19ºF to 104ºF)

Relative Humidity 0% to 95%, non-condensing

Operating Elevation Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating

Storage Elevation 15000m (50,000 ft.) maximum

Safety IEC/EN/AS 62040-1:2008, GS mark

RFI/EMI FCC Part 15, Class A=CISPR22 Class B

Surge Immunity IEC 62040-2 2nd Ed.: 2006

Transportation ISTA Procedure 1A

Table 14 Operating temperature parameters

Ambient Temperature, °C (°F) 25-30 (77-86) 30-35 (86-95) 35-40 (95-104)

Maximum Output Power Factor Derating @ Maximum Load

Show 9 more labels / short text on this page
Specifications · Model Number · Parameter · Used w/UPS Model · Weight, kg (lb) · Battery parameters · Environmental · Agency · 100%-93% 93%-86% 86%-79%
Page 42 of the Liebert GXT3 user manual — 700VA 1000VA 1500VA 2000VA 3000VA
Page 42 · click to enlarge
Page 42

Table 15 Battery run times

700VA 1000VA 1500VA 2000VA 3000VA

10% 105 91 75 73 77

20% 62 38 35 33 37

30% 37 31 22 21 21

40% 32 23 16 15 15

50% 27 17 11 11 11

60% 22 14 10 8 8

70% 18 11 6 6 6

80% 15 9 5 5 5

90% 13 8 4 4 4

100% 11 6 4 3 3

10% 307 214 194 166 182

20% 183 153 131 121 123

30% 150 124 96 79 79

40% 131 100 72 41 53

Internal Battery + 1 External Battery Cabinet

50% 109 79 41 38 46

60% 98 66 38 34 38

70% 81 41 35 30 31

80% 72 38 32 25 26

90% 63 36 27 21 21

100% 41 34 23 17 18

10% 374 337 310 306 311

20% 314 216 185 159 160

30% 212 166 148 133 134

40% 186 152 126 105 105

Internal Battery + 2 External Battery Cabinets

50% 160 136 103 81 81

60% 149 121 83 67 68

70% 139 104 72 40 52

80% 128 93 62 38 47

90% 112 79 40 36 43

100% 105 71 38 33 38

10% 480 480 339 331 335

20% 341 322 225 202 205

30% 319 219 184 157 157

40% 225 191 154 138 139

Internal Battery + 3 External Battery Cabinets

50% 206 161 139 120 120

60% 187 151 123 99 100

70% 163 140 105 80 81

80% 155 128 93 70 71

90% 148 112 79 60 62

100% 141 105 71 40 51

Show 6 more labels / short text on this page
Specifications · Run Time, Minutes · Number of Batteries/Cabinets · Load Percent · of Capacity · Internal Battery
Page 43 of the Liebert GXT3 user manual — 9.1 Product Warranty Registration
Page 43 · click to enlarge
Page 43

Table 15 Battery run times (continued)

700VA 1000VA 1500VA 2000VA 3000VA

10% 480 480 480 346 480

20% 480 340 315 301 303

30% 338 316 215 186 187

40% 322 220 184 156 156

Internal Battery + 4 External Battery Cabinets

50% 305 198 157 141 141

60% 217 166 145 126 127

70% 202 158 133 107 108

80% 186 149 120 95 97

90% 164 141 105 79 81

100% 159 133 96 72 73

The times above are approximate. They are based on new, fully charged batteries with 100% resistive loads and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle computers and monitors) or add optional external battery cabinets.

9.1 Product Warranty Registration

To register for warranty protection, visit the Quick Links section of the Liebert Web site at:

http://www.liebert.com

Click on Product Warranty Registration and fill in the form.

If you have any questions, contact Emerson® Channel Applications Engineering at:

North America800-222-5877 Outside North America: 00-800-1155-4499 liebert.upstech@ emerson.com
Show 5 more labels / short text on this page
Specifications · Run Time, Minutes · Number of Batteries/Cabinets · Load Percent · of Capacity
Page 44 of the Liebert GXT3 user manual — SLI-23180_REV5_06-13
Page 44 · click to enlarge
Page 44

Ensuring The High Availability Of Mission-Critical Data And Applications.

Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™

Technical Support / Service

Web Site www.liebert.com

from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.

Monitoring liebert.monitoring@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Single-Phase UPS & Server Cabinets

liebert.upstech@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Three-Phase UPS & Power Systems

800-543-2378 Outside North America614-841-6598
800-543-2778 Outside the United States614-888-0246

Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center

Philippines +63 2 687 6615 Fax: +63 2 730 9572

SLI-23180_REV5_06-13

Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com

Embedded Computing Embedded Power

Racks & Integrated Cabinets Services

Power Switching & Controls Precision Cooling

Infrastructure Management & Monitoring

Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.

Show 6 more labels / short text on this page
Environmental Systems · Pasig City 1605 · AC Power Connectivity · Outside Plant · DC Power · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
UPS fails to start when the On/Alarm Silence/Manual Battery Test button is pressedUPS is short-circuited or overloadedEnsure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally. p.36
Battery indicator is illuminatedUPS is not plugged inUPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle. p.36
Battery indicator is illuminatedUPS input protection fuse has blown/openedUPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS. p.36
Battery indicator is illuminatedMains power is out of toleranceUPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS. p.36
UPS has reduced battery backup timeBatteries are not fully chargedKeep UPS plugged in continuously at least 24 hours to recharge batteries. p.36
UPS has reduced battery backup timeUPS is overloadedCheck load level indicator and reduce the load on the UPS. p.36
UPS has reduced battery backup timeBatteries may not be able to hold a full charge due to ageReplace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit. p.36
Fault and Bypass indicators and all LED segments of battery level indicator are illuminatedUPS is overloaded or load is faultyCheck load level indicator and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load for faults. p.36
Fault and Bypass indicators and diagnostic A indicator are illuminatedUPS has been shut down due to temperature condition; load is on bypass powerEnsure UPS is not overloaded, ventilation holes are not blocked and room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS cannot restart, contact your local dealer, Emerson® representative or Emerson Channel Support. p.36
Fault and Bypass indicators and diagnostic B indicator are illuminatedUPS internal DC bus overvoltageUPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. p.36
Fault and Bypass indicators and diagnostic C indicator are illuminatedUPS DC/DC faultUPS requires service. Contact your local dealer, Emerson® representative or Emerson Channel Support. p.37
Fault indicator and diagnostic D indicator are illuminatedUPS PFC (Power Factor Correction Circuit) faultUPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. p.37
Fault and Bypass indicators and diagnostic E indicator are illuminatedUPS inverter faultUPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. p.37
Fault indicator and diagnostic A and C indicators are illuminatedUPS failed the battery testReplace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support. p.37
Fault and Bypass indicators and diagnostic C and E indicators are illuminatedUPS has been shut down by a command from the communications port(s)Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Emerson representative or Emerson Channel Support. p.37
Fault indicator and diagnostic A and B indicators are illuminatedUPS failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarmEnsure fan is not blocked up. If the fault is not removed, contact your local dealer, Emerson representative or Emerson Channel Support. p.37
AC input indicator is flashing.UPS detected a line-to-neutral reversal or a loss of proper grounding for UPS; continuous horn and UPS cannot start up in standby status. This is active only when power is first applied to the input. Once the UPS is running, the AC input indicator will flash, unless the input wiring is correctly changed.Contact a qualified electrician to verify site wiring. p.37
Battery indicator is flashing.Battery source is not available; continuous horn.Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed. p.37
Bypass indicator is flashing.Because the voltage or frequency is outside acceptable limits, the bypass is disabled.The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable. p.37

Ask about the Liebert GXT3

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert GXT3

Be the first to ask — other owners or our team will answer.

Original document

Liebert GXT3 manual PDF

44 pages·2.7 MB·Surge Protector·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…