Liebert 100-1000A

152 pages·5.2 MB·Surge Protector·PDF·ENDEFRITNLJA
Liebert 100-1000A
Table of Contents 277 sections Important Safety Instructions · Overview of Manual · 1.0 Safety Precautions · 2.0 Unpacking and Inspections · … ShowHide
Important Safety Instructionsp.9Overview of Manualp.101.0 Safety Precautionsp.112.0 Unpacking and Inspectionsp.122.1 External Inspectionsp.122.2 Unloading and Handlingp.122.2.1 Handling Considerationsp.132.2.2 Unit Preparationp.132.3 Internal Inspectionsp.133.0 Location Considerationsp.143.1 Recommended Minimum Service Clearancesp.143.2 Heat Outputp.14Table 1 Heat outputp.143.3 Operating Environmentp.143.4 Altitudep.15Figure 1 Recommended derating for high altitude operationp.15Figure 2 Maximum ambient temperature for full load operation at higher altitudesp.154.0 Locating the Liebert STS2p.164.1 Leveling and Anchoring the Unit to the Floorp.164.2 Leveling of the Static Switch Without Anchoringp.164.3 Leveling and Anchoring the Static Switch Using Floor Standp.165.0 Power and Control Wiringp.175.1 Input And Output Power Connectionsp.17Figure 3 Typical static transfer switch one-line diagramp.18Table 2 Input/output conduit plate specificationsp.185.2 Input Junction Box Installation—Optionalp.18Table 3 Input junction box dimensionsp.19Table 4 Input junction box terminal wire size rangep.195.3 System Groundingp.20Figure 4 Typical one-line diagram of two PDUs and a Liebert STS2p.205.4 Control Wiring Connectionsp.205.5 Remote Source Selection Wiringp.21Table 5 Remote source selection terminal blockp.215.6 Power Supplyp.21Table 6 Terminal block 1 and terminal block 2 wire connectionsp.216.0 Optionsp.226.1 Programmable Relay Boardp.22Table 7 Programmable relay board pinoutp.226.2 Optimized Transferp.226.3 Distribution Cabinet With I-Line Panelboard—100-600A Units Onlyp.236.4 Input Contact Isolator Boardp.236.5 Comms Boardp.236.6 Liebert IntelliSlot® SNMP/Web/Modbus 485 Cardp.236.7 LED Displayp.246.8 Remote Source Selectionp.246.9 Key Lockout Switchp.246.10 Redundant Output Breakerp.246.11 Transfer Inhibitp.246.12 Input Junction Boxes and Cablesp.256.13 Seismic Floor Anchorsp.256.14 Seismic Floor Standp.257.0 Installation Drawingsp.26Figure 5 Outline drawing: 100 – 250 amp Liebert STS2p.26Figure 6 Outline drawing: 400 – 600 amp Liebert STS2p.27Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2p.28Figure 8 Outline drawing: 100 – 250amp Liebert STS2 with a key lockout switch optionp.29Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch optionp.30Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch optionp.31Figure 11 Seismic anchor drawing: 100 – 250 amp Liebert STS2p.32Figure 12 Seismic anchor drawing: 400 – 600 amp Liebert STS2p.33Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS2p.34Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breakerp.35Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakersp.36Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breakerp.37Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakersp.38Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breakerp.39Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakersp.40Figure 20 Liebert STS2 non-automatic circuit breaker schedulep.41Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2p.42Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2p.43Figure 23 Control wiring for remote source selection optionp.44Figure 24 Control wiring for the programmable relay board optionp.45Figure 25 Control wiring for the input contact isolator board optionp.46Figure 26 Control wiring for comms boardp.47Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 cardp.48Figure 28 Control wiring for the RS-232 portp.49Figure 29 Outline drawing for input junction boxp.50Figure 30 Color LCD touch screen displayp.51Figure 31 LED displayp.52Figure 32 Installation drawing, seismic floor stand 100-250Ap.53Figure 33 Installation drawing, seismic floor stand 100-250Ap.54Figure 34 Installation drawing, seismic floor stand 100-250Ap.55Figure 35 Installation drawing, seismic floor stand 100-250Ap.56Figure 36 Installation drawing, seismic floor stand 400-600Ap.57Figure 37 Installation drawing, seismic floor stand 400-600Ap.58Figure 38 Installation drawing, seismic floor stand 400-600Ap.59Figure 39 Installation drawing, seismic floor stand 400-600Ap.60Figure 40 Installation drawing, seismic floor stand 800-1000Ap.61Figure 41 Installation drawing, seismic floor stand 800-1000Ap.62Figure 42 Installation drawing, seismic floor stand 800-1000Ap.63Figure 43 Installation drawing, seismic floor stand 800-1000Ap.648.0 Introduction to Liebert STS2 Operationsp.658.1 System Descriptionp.658.1.1 Redundancyp.658.1.2 Reliability and Agency Requirementsp.668.1.3 Factory Backup and Service Assistancep.668.2 Modes of Operationp.668.2.1 Normal (Preferred Source)p.668.2.2 Transferp.668.2.3 Transfer Inhibitp.668.2.4 Bypassp.678.3 Operator Controlsp.67Figure 44 Liebert STS2 touch screen displayp.679.0 Theory of Operationp.689.1 General Descriptionp.689.1.1 Liebert STS2 Static Transfer Switchp.689.1.2 Source Transferp.689.1.3 Automatic Transfer/Retransferp.68Automatic Retransfer Inhibitedp.689.1.4 Emergency Transferp.699.1.5 Load Current Transfer Inhibitp.699.1.6 SCR Failurep.699.1.7 On/Off Sequencep.699.2 Detailed Component Descriptionp.709.2.1 Controlsp.70Operator Interfacep.70Hardwarep.70Firmwarep.709.2.2 Circuit Breakersp.719.2.3 SCRsp.719.2.4 Logic Modulesp.719.2.5 Audible Alarmp.719.2.6 RS-232 Portp.7110.0 Operating Instructions for the Touch Screen Interfacep.7210.1 Normal System Startupp.73Figure 45 Liebert STS2 touch screen displayp.7310.2 Manual Transfer / Preferred Source Selectionp.74Figure 46 Source transfer screenp.7410.3 Enabling Remote Source Selectionp.7510.4 Maintenance Bypassp.75Figure 47 Gate board viewing slot locationsp.7610.4.1 Bypass Procedures for Source 1p.7710.4.2 Bypass Procedures for Source 2p.7810.5 Normal System Shutdownp.7810.5.1 Shutdown in Static Transfer Switch Modep.7810.5.2 Shutdown in Maintenance Bypass Modep.7811.0 Alarm and Faultsp.7911.1 Event Maskp.7911.2 Event and History Logsp.8011.2.1 Event Logp.8011.2.2 History Logp.8011.3 Alarm Notesp.8111.4 List of Messagesp.81Table 8 Event messagesp.8212.0 Communication Interfacesp.8412.1 Using the RS-232 Portp.8412.1.1 Connecting and Using a Terminalp.85Table 9 Terminal commandsp.8512.1.2 Configuring the Liebert STS2 via the Terminalp.86Groups Parameterp.86Item Parameterp.86Value Parameterp.87Table 10 Value typesp.87Table 11 Group settings and valuesp.8712.1.3 Setting Bitpacked Options with the Terminalp.89Table 12 Binary-hexadecimal conversionsp.90Putting the Terminal Command Togetherp.9112.1.4 Setting Event Masks with the Terminalp.92Examples of Event Mask Settingsp.9213.0 Liebert STS2 Touch Screen Displayp.9313.1 Display Overviewp.93Figure 48 Liebert STS2 touch screen displayp.9313.2 Menu Overviewp.94Figure 49 Menusp.94Figure 50 Keyboard and keypad displaysp.9413.2.1 Securityp.95Using the Optional Key Lockout Switchp.95Figure 51 Key lockout switch.p.95Using the Passwordp.9513.3 Mimic Displayp.9613.4 Event Controlsp.9613.5 Event Displayp.9613.6 Menu Barp.9613.7 Configuration Menup.9613.7.1 System Ratingsp.9613.7.2 Event Masksp.96Figure 52 Event mask dialog boxp.9713.7.3 User Settingsp.97Figure 53 User settings dialog boxp.98Source Set Pointsp.98Figure 54 Source setpointsp.99Table 13 Sepoint parametersp.9913.7.4 System Settingsp.10113.8 Comm Optionsp.101Figure 55 Comm options dialog boxp.10113.8.1 Configuring the Modemp.102Figure 56 Modem dialog boxp.10213.8.2 Configuring Pager Supportp.10313.8.3 Configuring the Input Contact Isolator Settingsp.104Figure 57 Input contact isolator dialog boxp.10413.8.4 Configuring the Programmable Relay Board Settingsp.105Table 14 Standard settings for programmable relaysp.105Figure 58 Programmable relay board dialog boxp.10613.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Cardp.10613.8.6 Liebert SiteScan® Configurationp.10713.8.7 Saving Your Communications Configurationsp.10713.9 System Optionsp.107Figure 59 System optionsp.107Dual Output Breakerp.107PDUp.1074-Pole Transfer Switchp.108Shuntp.108Wye Output Transformerp.108Remote Source Selectionp.10813.10 System IDp.10813.11 Logsp.10913.11.1 Event Logp.109Figure 60 Event logp.10913.11.2 History Logp.109Figure 61 History logp.10913.12 Source Transfersp.11013.13 Startup Procedurep.11013.14 Bypass Procedurep.11013.15 Helpp.11013.16 Logop.11013.17 Cleaning the LCD Touch Screenp.11014.0 Operating the Liebert STS2 LED Displayp.11114.1 LEDs and Buttons and Key Lockout Switchp.11114.1.1 Front Panel Controlsp.111Figure 62 LED displayp.11114.1.2 LED and Push Button Descriptionp.112Table 15 LED and push button descriptionp.11214.1.3 Event Controlsp.11314.1.4 Key Lockout Switchp.113Figure 63 Key lockout switch.p.11314.2 Operationsp.11414.2.1 Normal System Startupp.11414.2.2 Manual Transfer / Preferred Source Selectionp.11514.2.3 Maintenance Bypassp.116Bypass Procedures for Source 1p.116Bypass Procedures for Source 2p.11714.2.4 Normal System Shutdownp.118Shutdown in Static Transfer Switch Modep.118Shutdown in Maintenance Bypass Modep.11815.0 Specificationsp.11915.1 System Configurationp.11915.1.1 Frequencyp.11915.1.2 Input/Output Voltagep.119Table 16 Input/output voltagep.11915.1.3 System Current Ratingsp.119Table 17 System current ratingsp.11915.1.4 Groundingp.12015.1.5 Electrical Requirementsp.120Table 18 Electrical requirementsp.120Table 19 Unit short circuit withstand capabilityp.12015.1.6 Input Surge Suppressionp.12015.1.7 Response Timep.12015.1.8 Environmental Requirementsp.12015.2 System Componentsp.12115.2.1 Frame and Enclosurep.121Table 20 Frame sizesp.12115.2.2 Casters, Leveling and Seismic Anchoringp.12115.2.3 Coolingp.12115.2.4 Accessp.12215.2.5 Circuit Breakersp.12215.2.6 Cable Entrancep.12215.2.7 Doorsp.12215.2.8 Color Graphical Display or LED Displayp.12215.2.9 RS-232 Portp.12315.2.10 Terminal Port Connectionsp.123Table 21 MTA plug pinoutp.123Table 22 DB9 pinoutp.12315.2.11 RS-232 Interface Parametersp.124Table 23 RS-232 settingsp.12415.2.12 Maintenance Bypassp.12415.2.13 Fuseless Designp.12415.2.14 Optionsp.12416.0 Event Message Help Textp.125Key:p.12517.0 Maintenancep.14617.1 Proper Tightening of Nuts and Boltsp.146Table 24 Torque tighteningp.14617.2 Testing the Liebert STS2p.14617.3 Changing the Air Filterp.146Support Informationp.147Programmable Relay Board Settings Recordp.148Input Contact Isolator Settings Recordp.150
Page 1 of the Liebert 100-1000A user manual
Page 1 · click to enlarge
Page 1
Liebert 100-1000A diagram (page 1)
Fig. 1
Page 2 of the Liebert 100-1000A user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Liebert 100-1000A user manual
Page 3 of the Liebert 100-1000A user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Important Safety Instructionsp.9Overview of Manualp.101.0 Safety Precautionsp.112.0 Unpacking and Inspectionsp.122.1 External Inspectionsp.122.2 Unloading and Handlingp.122.2.1 Handling Considerationsp.132.2.2 Unit Preparationp.132.3 Internal Inspectionsp.133.0 Location Considerationsp.143.1 Recommended Minimum Service Clearancesp.143.2 Heat Outputp.14Table 1 Heat outputp.143.3 Operating Environmentp.143.4 Altitudep.15Figure 1 Recommended derating for high altitude operationp.15Figure 2 Maximum ambient temperature for full load operation at higher altitudesp.154.0 Locating the Liebert STS2p.164.1 Leveling and Anchoring the Unit to the Floorp.164.2 Leveling of the Static Switch Without Anchoringp.164.3 Leveling and Anchoring the Static Switch Using Floor Standp.165.0 Power and Control Wiringp.175.1 Input And Output Power Connectionsp.17Figure 3 Typical static transfer switch one-line diagramp.18Table 2 Input/output conduit plate specificationsp.185.2 Input Junction Box Installation—Optionalp.18Table 3 Input junction box dimensionsp.19Table 4 Input junction box terminal wire size rangep.195.3 System Groundingp.20Figure 4 Typical one-line diagram of two PDUs and a Liebert STS2p.205.4 Control Wiring Connectionsp.205.5 Remote Source Selection Wiringp.21Table 5 Remote source selection terminal blockp.215.6 Power Supplyp.21Table 6 Terminal block 1 and terminal block 2 wire connectionsp.216.0 Optionsp.226.1 Programmable Relay Boardp.22Table 7 Programmable relay board pinoutp.226.2 Optimized Transferp.226.3 Distribution Cabinet With I-Line Panelboard—100-600A Units Onlyp.236.4 Input Contact Isolator Boardp.236.5 Comms Boardp.236.6 Liebert IntelliSlot® SNMP/Web/Modbus 485 Cardp.236.7 LED Displayp.246.8 Remote Source Selectionp.246.9 Key Lockout Switchp.246.10 Redundant Output Breakerp.246.11 Transfer Inhibitp.246.12 Input Junction Boxes and Cablesp.256.13 Seismic Floor Anchorsp.256.14 Seismic Floor Standp.257.0 Installation Drawingsp.26Figure 5 Outline drawing: 100 – 250 amp Liebert STS2p.26Figure 6 Outline drawing: 400 – 600 amp Liebert STS2p.27Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2p.28Figure 8 Outline drawing: 100 – 250amp Liebert STS2 with a key lockout switch optionp.29Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch optionp.30Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch optionp.31Figure 11 Seismic anchor drawing: 100 – 250 amp Liebert STS2p.32Figure 12 Seismic anchor drawing: 400 – 600 amp Liebert STS2p.33Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS2p.34Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breakerp.35Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakersp.36Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breakerp.37Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakersp.38Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breakerp.39Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakersp.40Figure 20 Liebert STS2 non-automatic circuit breaker schedulep.41Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2p.42Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2p.43Figure 23 Control wiring for remote source selection optionp.44Figure 24 Control wiring for the programmable relay board optionp.45Figure 25 Control wiring for the input contact isolator board optionp.46Figure 26 Control wiring for comms boardp.47Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 cardp.48Figure 28 Control wiring for the RS-232 portp.49Figure 29 Outline drawing for input junction boxp.50Figure 30 Color LCD touch screen displayp.51Figure 31 LED displayp.52Figure 32 Installation drawing, seismic floor stand 100-250Ap.53Figure 33 Installation drawing, seismic floor stand 100-250Ap.54Figure 34 Installation drawing, seismic floor stand 100-250Ap.55Figure 35 Installation drawing, seismic floor stand 100-250Ap.56Figure 36 Installation drawing, seismic floor stand 400-600Ap.57Figure 37 Installation drawing, seismic floor stand 400-600Ap.58Figure 38 Installation drawing, seismic floor stand 400-600Ap.59Figure 39 Installation drawing, seismic floor stand 400-600Ap.60Figure 40 Installation drawing, seismic floor stand 800-1000Ap.61Figure 41 Installation drawing, seismic floor stand 800-1000Ap.62Figure 42 Installation drawing, seismic floor stand 800-1000Ap.63Figure 43 Installation drawing, seismic floor stand 800-1000Ap.648.0 Introduction to Liebert STS2 Operationsp.658.1 System Descriptionp.658.1.1 Redundancyp.658.1.2 Reliability and Agency Requirementsp.668.1.3 Factory Backup and Service Assistancep.668.2 Modes of Operationp.668.2.1 Normal (Preferred Source)p.668.2.2 Transferp.668.2.3 Transfer Inhibitp.668.2.4 Bypassp.678.3 Operator Controlsp.67Figure 44 Liebert STS2 touch screen displayp.679.0 Theory of Operationp.689.1 General Descriptionp.689.1.1 Liebert STS2 Static Transfer Switchp.689.1.2 Source Transferp.689.1.3 Automatic Transfer/Retransferp.68Automatic Retransfer Inhibitedp.689.1.4 Emergency Transferp.699.1.5 Load Current Transfer Inhibitp.699.1.6 SCR Failurep.699.1.7 On/Off Sequencep.699.2 Detailed Component Descriptionp.709.2.1 Controlsp.70Operator Interfacep.70Hardwarep.70Firmwarep.709.2.2 Circuit Breakersp.719.2.3 SCRsp.719.2.4 Logic Modulesp.719.2.5 Audible Alarmp.719.2.6 RS-232 Portp.7110.0 Operating Instructions for the Touch Screen Interfacep.7210.1 Normal System Startupp.73Figure 45 Liebert STS2 touch screen displayp.7310.2 Manual Transfer / Preferred Source Selectionp.74Figure 46 Source transfer screenp.7410.3 Enabling Remote Source Selectionp.7510.4 Maintenance Bypassp.75Figure 47 Gate board viewing slot locationsp.7610.4.1 Bypass Procedures for Source 1p.7710.4.2 Bypass Procedures for Source 2p.7810.5 Normal System Shutdownp.7810.5.1 Shutdown in Static Transfer Switch Modep.7810.5.2 Shutdown in Maintenance Bypass Modep.7811.0 Alarm and Faultsp.7911.1 Event Maskp.7911.2 Event and History Logsp.8011.2.1 Event Logp.8011.2.2 History Logp.8011.3 Alarm Notesp.8111.4 List of Messagesp.81Table 8 Event messagesp.8212.0 Communication Interfacesp.8412.1 Using the RS-232 Portp.8412.1.1 Connecting and Using a Terminalp.85Table 9 Terminal commandsp.8512.1.2 Configuring the Liebert STS2 via the Terminalp.86Groups Parameterp.86Item Parameterp.86Value Parameterp.87Table 10 Value typesp.87Table 11 Group settings and valuesp.8712.1.3 Setting Bitpacked Options with the Terminalp.89Table 12 Binary-hexadecimal conversionsp.90Putting the Terminal Command Togetherp.9112.1.4 Setting Event Masks with the Terminalp.92Examples of Event Mask Settingsp.9213.0 Liebert STS2 Touch Screen Displayp.9313.1 Display Overviewp.93Figure 48 Liebert STS2 touch screen displayp.9313.2 Menu Overviewp.94Figure 49 Menusp.94Figure 50 Keyboard and keypad displaysp.9413.2.1 Securityp.95Using the Optional Key Lockout Switchp.95Figure 51 Key lockout switch.p.95Using the Passwordp.9513.3 Mimic Displayp.9613.4 Event Controlsp.9613.5 Event Displayp.9613.6 Menu Barp.9613.7 Configuration Menup.9613.7.1 System Ratingsp.9613.7.2 Event Masksp.96Figure 52 Event mask dialog boxp.9713.7.3 User Settingsp.97Figure 53 User settings dialog boxp.98Source Set Pointsp.98Figure 54 Source setpointsp.99Table 13 Sepoint parametersp.9913.7.4 System Settingsp.10113.8 Comm Optionsp.101Figure 55 Comm options dialog boxp.10113.8.1 Configuring the Modemp.102Figure 56 Modem dialog boxp.10213.8.2 Configuring Pager Supportp.10313.8.3 Configuring the Input Contact Isolator Settingsp.104Figure 57 Input contact isolator dialog boxp.10413.8.4 Configuring the Programmable Relay Board Settingsp.105Table 14 Standard settings for programmable relaysp.105Figure 58 Programmable relay board dialog boxp.10613.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Cardp.10613.8.6 Liebert SiteScan® Configurationp.10713.8.7 Saving Your Communications Configurationsp.10713.9 System Optionsp.107Figure 59 System optionsp.107Dual Output Breakerp.107PDUp.1074-Pole Transfer Switchp.108Shuntp.108Wye Output Transformerp.108Remote Source Selectionp.10813.10 System IDp.10813.11 Logsp.10913.11.1 Event Logp.109Figure 60 Event logp.10913.11.2 History Logp.109Figure 61 History logp.10913.12 Source Transfersp.11013.13 Startup Procedurep.11013.14 Bypass Procedurep.11013.15 Helpp.11013.16 Logop.11013.17 Cleaning the LCD Touch Screenp.11014.0 Operating the Liebert STS2 LED Displayp.11114.1 LEDs and Buttons and Key Lockout Switchp.11114.1.1 Front Panel Controlsp.111Figure 62 LED displayp.11114.1.2 LED and Push Button Descriptionp.112Table 15 LED and push button descriptionp.11214.1.3 Event Controlsp.11314.1.4 Key Lockout Switchp.113Figure 63 Key lockout switch.p.11314.2 Operationsp.11414.2.1 Normal System Startupp.11414.2.2 Manual Transfer / Preferred Source Selectionp.11514.2.3 Maintenance Bypassp.116Bypass Procedures for Source 1p.116Bypass Procedures for Source 2p.11714.2.4 Normal System Shutdownp.118Shutdown in Static Transfer Switch Modep.118Shutdown in Maintenance Bypass Modep.11815.0 Specificationsp.11915.1 System Configurationp.11915.1.1 Frequencyp.11915.1.2 Input/Output Voltagep.119Table 16 Input/output voltagep.11915.1.3 System Current Ratingsp.119Table 17 System current ratingsp.11915.1.4 Groundingp.12015.1.5 Electrical Requirementsp.120Table 18 Electrical requirementsp.120Table 19 Unit short circuit withstand capabilityp.12015.1.6 Input Surge Suppressionp.12015.1.7 Response Timep.12015.1.8 Environmental Requirementsp.12015.2 System Componentsp.12115.2.1 Frame and Enclosurep.121Table 20 Frame sizesp.12115.2.2 Casters, Leveling and Seismic Anchoringp.12115.2.3 Coolingp.12115.2.4 Accessp.12215.2.5 Circuit Breakersp.12215.2.6 Cable Entrancep.12215.2.7 Doorsp.12215.2.8 Color Graphical Display or LED Displayp.12215.2.9 RS-232 Portp.12315.2.10 Terminal Port Connectionsp.123Table 21 MTA plug pinoutp.123Table 22 DB9 pinoutp.12315.2.11 RS-232 Interface Parametersp.124Table 23 RS-232 settingsp.12415.2.12 Maintenance Bypassp.12415.2.13 Fuseless Designp.12415.2.14 Optionsp.12416.0 Event Message Help Textp.125Key:p.12517.0 Maintenancep.14617.1 Proper Tightening of Nuts and Boltsp.146Table 24 Torque tighteningp.14617.2 Testing the Liebert STS2p.14617.3 Changing the Air Filterp.146Support Informationp.147Programmable Relay Board Settings Recordp.148Input Contact Isolator Settings Recordp.150
Page 4 of the Liebert 100-1000A user manual
Page 4 · click to enlarge
Page 4

7.0 INSTALLATION DRAWINGS 18

8.0 INTRODUCTION TO LIEBERT STS2 OPERATIONS 57 8.1 System Description 57 8.1.1 Redundancy 57 8.1.2 Reliability and Agency Requirements 58 8.1.3 Factory Backup and Service Assistance 58 8.2 Modes of Operation 58 8.2.1 Normal (Preferred Source) 58 8.2.2 Transfer 58 8.2.3 Transfer Inhibit 58 8.2.4 Bypass 59 8.3 Operator Controls 59

9.0 THEORY OF OPERATION 60 9.1 General Description 60 9.1.1 Liebert STS2 Static Transfer Switch 60 9.1.2 Source Transfer 60 9.1.3 Automatic Transfer/Retransfer 60 9.1.4 Emergency Transfer 61 9.1.5 Load Current Transfer Inhibit 61 9.1.6 SCR Failure 61 9.1.7 On/Off Sequence 61 9.2 Detailed Component Description 62 9.2.1 Controls 62 9.2.2 Circuit Breakers 63 9.2.3 SCRs 63 9.2.4 Logic Modules 63 9.2.5 Audible Alarm 63 9.2.6 RS-232 Port 63 10.0 OPERATING INSTRUCTIONS FOR THE TOUCH SCREEN INTERFACE 64 10.1 Normal System Startup 65

10.2 Manual Transfer / Preferred Source Selection 66

10.3 Enabling Remote Source Selection 67

10.4 Maintenance Bypass 67 10.4.1 Bypass Procedures for Source 1 69 10.4.2 Bypass Procedures for Source 2 70 10.5 Normal System Shutdown 70 10.5.1 Shutdown in Static Transfer Switch Mode 70 10.5.2 Shutdown in Maintenance Bypass Mode 70 11.0 ALARM AND FAULTS 71 11.1 Event Mask 71

11.2 Event and History Logs 72 11.2.1 Event Log 72 11.2.2 History Log 72 11.3 Alarm Notes 73

11.4 List of Messages 73

Page 5 of the Liebert 100-1000A user manual
Page 5 · click to enlarge
Page 5

12.0 COMMUNICATION INTERFACES 76 12.1 Using the RS-232 Port 76 12.1.1 Connecting and Using a Terminal 77 12.1.2 Configuring the Liebert STS2 via the Terminal 78 12.1.3 Setting Bitpacked Options with the Terminal 81 12.1.4 Setting Event Masks with the Terminal 84 13.0 LIEBERT STS2 TOUCH SCREEN DISPLAY 85 13.1 Display Overview 85

13.2 Menu Overview 86 13.2.1 Security 87 13.3 Mimic Display 88

13.4 Event Controls 88

13.5 Event Display 88

13.6 Menu Bar 88

13.7 Configuration Menu 88 13.7.1 System Ratings 88 13.7.2 Event Masks 88 13.7.3 User Settings 89 13.7.4 System Settings 93 13.8 Comm Options 93 13.8.1 Configuring the Modem 94 13.8.2 Configuring Pager Support 95 13.8.3 Configuring the Input Contact Isolator Settings 96 13.8.4 Configuring the Programmable Relay Board Settings 97 13.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Card 98 13.8.6 Liebert SiteScan® Configuration 99 13.8.7 Saving Your Communications Configurations 99 13.9 System Options 99

13.10 System ID 100

13.11 Logs 101 13.11.1 Event Log 101 13.11.2 History Log 101 13.12 Source Transfers 102

13.13 Startup Procedure 102

13.14 Bypass Procedure 102

13.15 Help 102

13.16 Logo 102

13.17 Cleaning the LCD Touch Screen 102

Page 6 of the Liebert 100-1000A user manual
Page 6 · click to enlarge
Page 6

14.0 OPERATING THE LIEBERT STS2 LED DISPLAY 103 14.1 LEDs and Buttons and Key Lockout Switch 103 14.1.1 Front Panel Controls 103 14.1.2 LED and Push Button Description 104 14.1.3 Event Controls 105 14.1.4 Key Lockout Switch 105 14.2 Operations 106 14.2.1 Normal System Startup 106 14.2.2 Manual Transfer / Preferred Source Selection 107 14.2.3 Maintenance Bypass 108 14.2.4 Normal System Shutdown 110 15.0 SPECIFICATIONS 111 15.1 System Configuration 111 15.1.1 Frequency 111 15.1.2 Input/Output Voltage 111 15.1.3 System Current Ratings 111 15.1.4 Grounding 112 15.1.5 Electrical Requirements 112 15.1.6 Input Surge Suppression 112 15.1.7 Response Time 112 15.1.8 Environmental Requirements 112 15.2 System Components 113 15.2.1 Frame and Enclosure 113 15.2.2 Casters, Leveling and Seismic Anchoring 113 15.2.3 Cooling 113 15.2.4 Access 114 15.2.5 Circuit Breakers 114 15.2.6 Cable Entrance 114 15.2.7 Doors 114 15.2.8 Color Graphical Display or LED Display 114 15.2.9 RS-232 Port 115 15.2.10 Terminal Port Connections 115 15.2.11 RS-232 Interface Parameters 116 15.2.12 Maintenance Bypass 116 15.2.13 Fuseless Design 116 15.2.14 Options 116 16.0 EVENT MESSAGE HELP TEXT 117

17.0 MAINTENANCE 138 17.1 Proper Tightening of Nuts and Bolts 138

17.2 Testing the Liebert STS2 138

17.3 Changing the Air Filter 138

SUPPORT INFORMATION 139

PROGRAMMABLE RELAY BOARD SETTINGS RECORD 140

INPUT CONTACT ISOLATOR SETTINGS RECORD 142

Page 7 of the Liebert 100-1000A user manual — Table of contents
Page 7 · click to enlarge
Page 7

Table of contents

Important Safety Instructionsp.9Overview of Manualp.101.0 Safety Precautionsp.112.0 Unpacking and Inspectionsp.122.1 External Inspectionsp.122.2 Unloading and Handlingp.122.2.1 Handling Considerationsp.132.2.2 Unit Preparationp.132.3 Internal Inspectionsp.133.0 Location Considerationsp.143.1 Recommended Minimum Service Clearancesp.143.2 Heat Outputp.14Table 1 Heat outputp.143.3 Operating Environmentp.143.4 Altitudep.15Figure 1 Recommended derating for high altitude operationp.15Figure 2 Maximum ambient temperature for full load operation at higher altitudesp.154.0 Locating the Liebert STS2p.164.1 Leveling and Anchoring the Unit to the Floorp.164.2 Leveling of the Static Switch Without Anchoringp.164.3 Leveling and Anchoring the Static Switch Using Floor Standp.165.0 Power and Control Wiringp.175.1 Input And Output Power Connectionsp.17Figure 3 Typical static transfer switch one-line diagramp.18Table 2 Input/output conduit plate specificationsp.185.2 Input Junction Box Installation—Optionalp.18Table 3 Input junction box dimensionsp.19Table 4 Input junction box terminal wire size rangep.195.3 System Groundingp.20Figure 4 Typical one-line diagram of two PDUs and a Liebert STS2p.205.4 Control Wiring Connectionsp.205.5 Remote Source Selection Wiringp.21Table 5 Remote source selection terminal blockp.215.6 Power Supplyp.21Table 6 Terminal block 1 and terminal block 2 wire connectionsp.216.0 Optionsp.226.1 Programmable Relay Boardp.22Table 7 Programmable relay board pinoutp.226.2 Optimized Transferp.226.3 Distribution Cabinet With I-Line Panelboard—100-600A Units Onlyp.236.4 Input Contact Isolator Boardp.236.5 Comms Boardp.236.6 Liebert IntelliSlot® SNMP/Web/Modbus 485 Cardp.236.7 LED Displayp.246.8 Remote Source Selectionp.246.9 Key Lockout Switchp.246.10 Redundant Output Breakerp.246.11 Transfer Inhibitp.246.12 Input Junction Boxes and Cablesp.256.13 Seismic Floor Anchorsp.256.14 Seismic Floor Standp.257.0 Installation Drawingsp.26Figure 5 Outline drawing: 100 – 250 amp Liebert STS2p.26Figure 6 Outline drawing: 400 – 600 amp Liebert STS2p.27Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2p.28Figure 8 Outline drawing: 100 – 250amp Liebert STS2 with a key lockout switch optionp.29Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch optionp.30Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch optionp.31Figure 11 Seismic anchor drawing: 100 – 250 amp Liebert STS2p.32Figure 12 Seismic anchor drawing: 400 – 600 amp Liebert STS2p.33Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS2p.34Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breakerp.35Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakersp.36Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breakerp.37Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakersp.38Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breakerp.39Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakersp.40Figure 20 Liebert STS2 non-automatic circuit breaker schedulep.41Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2p.42Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2p.43Figure 23 Control wiring for remote source selection optionp.44Figure 24 Control wiring for the programmable relay board optionp.45Figure 25 Control wiring for the input contact isolator board optionp.46Figure 26 Control wiring for comms boardp.47Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 cardp.48Figure 28 Control wiring for the RS-232 portp.49Figure 29 Outline drawing for input junction boxp.50Figure 30 Color LCD touch screen displayp.51Figure 31 LED displayp.52Figure 32 Installation drawing, seismic floor stand 100-250Ap.53Figure 33 Installation drawing, seismic floor stand 100-250Ap.54Figure 34 Installation drawing, seismic floor stand 100-250Ap.55Figure 35 Installation drawing, seismic floor stand 100-250Ap.56Figure 36 Installation drawing, seismic floor stand 400-600Ap.57Figure 37 Installation drawing, seismic floor stand 400-600Ap.58Figure 38 Installation drawing, seismic floor stand 400-600Ap.59Figure 39 Installation drawing, seismic floor stand 400-600Ap.60Figure 40 Installation drawing, seismic floor stand 800-1000Ap.61Figure 41 Installation drawing, seismic floor stand 800-1000Ap.62Figure 42 Installation drawing, seismic floor stand 800-1000Ap.63Figure 43 Installation drawing, seismic floor stand 800-1000Ap.648.0 Introduction to Liebert STS2 Operationsp.658.1 System Descriptionp.658.1.1 Redundancyp.658.1.2 Reliability and Agency Requirementsp.668.1.3 Factory Backup and Service Assistancep.668.2 Modes of Operationp.668.2.1 Normal (Preferred Source)p.668.2.2 Transferp.668.2.3 Transfer Inhibitp.668.2.4 Bypassp.678.3 Operator Controlsp.67Figure 44 Liebert STS2 touch screen displayp.679.0 Theory of Operationp.689.1 General Descriptionp.689.1.1 Liebert STS2 Static Transfer Switchp.689.1.2 Source Transferp.689.1.3 Automatic Transfer/Retransferp.68Automatic Retransfer Inhibitedp.689.1.4 Emergency Transferp.699.1.5 Load Current Transfer Inhibitp.699.1.6 SCR Failurep.699.1.7 On/Off Sequencep.699.2 Detailed Component Descriptionp.709.2.1 Controlsp.70Operator Interfacep.70Hardwarep.70Firmwarep.709.2.2 Circuit Breakersp.719.2.3 SCRsp.719.2.4 Logic Modulesp.719.2.5 Audible Alarmp.719.2.6 RS-232 Portp.7110.0 Operating Instructions for the Touch Screen Interfacep.7210.1 Normal System Startupp.73Figure 45 Liebert STS2 touch screen displayp.7310.2 Manual Transfer / Preferred Source Selectionp.74Figure 46 Source transfer screenp.7410.3 Enabling Remote Source Selectionp.7510.4 Maintenance Bypassp.75Figure 47 Gate board viewing slot locationsp.7610.4.1 Bypass Procedures for Source 1p.7710.4.2 Bypass Procedures for Source 2p.7810.5 Normal System Shutdownp.7810.5.1 Shutdown in Static Transfer Switch Modep.7810.5.2 Shutdown in Maintenance Bypass Modep.7811.0 Alarm and Faultsp.7911.1 Event Maskp.7911.2 Event and History Logsp.8011.2.1 Event Logp.8011.2.2 History Logp.8011.3 Alarm Notesp.8111.4 List of Messagesp.81Table 8 Event messagesp.8212.0 Communication Interfacesp.8412.1 Using the RS-232 Portp.8412.1.1 Connecting and Using a Terminalp.85Table 9 Terminal commandsp.8512.1.2 Configuring the Liebert STS2 via the Terminalp.86Groups Parameterp.86Item Parameterp.86Value Parameterp.87Table 10 Value typesp.87Table 11 Group settings and valuesp.8712.1.3 Setting Bitpacked Options with the Terminalp.89Table 12 Binary-hexadecimal conversionsp.90Putting the Terminal Command Togetherp.9112.1.4 Setting Event Masks with the Terminalp.92Examples of Event Mask Settingsp.9213.0 Liebert STS2 Touch Screen Displayp.9313.1 Display Overviewp.93Figure 48 Liebert STS2 touch screen displayp.9313.2 Menu Overviewp.94Figure 49 Menusp.94Figure 50 Keyboard and keypad displaysp.9413.2.1 Securityp.95Using the Optional Key Lockout Switchp.95Figure 51 Key lockout switch.p.95Using the Passwordp.9513.3 Mimic Displayp.9613.4 Event Controlsp.9613.5 Event Displayp.9613.6 Menu Barp.9613.7 Configuration Menup.9613.7.1 System Ratingsp.9613.7.2 Event Masksp.96Figure 52 Event mask dialog boxp.9713.7.3 User Settingsp.97Figure 53 User settings dialog boxp.98Source Set Pointsp.98Figure 54 Source setpointsp.99Table 13 Sepoint parametersp.9913.7.4 System Settingsp.10113.8 Comm Optionsp.101Figure 55 Comm options dialog boxp.10113.8.1 Configuring the Modemp.102Figure 56 Modem dialog boxp.10213.8.2 Configuring Pager Supportp.10313.8.3 Configuring the Input Contact Isolator Settingsp.104Figure 57 Input contact isolator dialog boxp.10413.8.4 Configuring the Programmable Relay Board Settingsp.105Table 14 Standard settings for programmable relaysp.105Figure 58 Programmable relay board dialog boxp.10613.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Cardp.10613.8.6 Liebert SiteScan® Configurationp.10713.8.7 Saving Your Communications Configurationsp.10713.9 System Optionsp.107Figure 59 System optionsp.107Dual Output Breakerp.107PDUp.1074-Pole Transfer Switchp.108Shuntp.108Wye Output Transformerp.108Remote Source Selectionp.10813.10 System IDp.10813.11 Logsp.10913.11.1 Event Logp.109Figure 60 Event logp.10913.11.2 History Logp.109Figure 61 History logp.10913.12 Source Transfersp.11013.13 Startup Procedurep.11013.14 Bypass Procedurep.11013.15 Helpp.11013.16 Logop.11013.17 Cleaning the LCD Touch Screenp.11014.0 Operating the Liebert STS2 LED Displayp.11114.1 LEDs and Buttons and Key Lockout Switchp.11114.1.1 Front Panel Controlsp.111Figure 62 LED displayp.11114.1.2 LED and Push Button Descriptionp.112Table 15 LED and push button descriptionp.11214.1.3 Event Controlsp.11314.1.4 Key Lockout Switchp.113Figure 63 Key lockout switch.p.11314.2 Operationsp.11414.2.1 Normal System Startupp.11414.2.2 Manual Transfer / Preferred Source Selectionp.11514.2.3 Maintenance Bypassp.116Bypass Procedures for Source 1p.116Bypass Procedures for Source 2p.11714.2.4 Normal System Shutdownp.118Shutdown in Static Transfer Switch Modep.118Shutdown in Maintenance Bypass Modep.11815.0 Specificationsp.11915.1 System Configurationp.11915.1.1 Frequencyp.11915.1.2 Input/Output Voltagep.119Table 16 Input/output voltagep.11915.1.3 System Current Ratingsp.119Table 17 System current ratingsp.11915.1.4 Groundingp.12015.1.5 Electrical Requirementsp.120Table 18 Electrical requirementsp.120Table 19 Unit short circuit withstand capabilityp.12015.1.6 Input Surge Suppressionp.12015.1.7 Response Timep.12015.1.8 Environmental Requirementsp.12015.2 System Componentsp.12115.2.1 Frame and Enclosurep.121Table 20 Frame sizesp.12115.2.2 Casters, Leveling and Seismic Anchoringp.12115.2.3 Coolingp.12115.2.4 Accessp.12215.2.5 Circuit Breakersp.12215.2.6 Cable Entrancep.12215.2.7 Doorsp.12215.2.8 Color Graphical Display or LED Displayp.12215.2.9 RS-232 Portp.12315.2.10 Terminal Port Connectionsp.123Table 21 MTA plug pinoutp.123Table 22 DB9 pinoutp.12315.2.11 RS-232 Interface Parametersp.124Table 23 RS-232 settingsp.12415.2.12 Maintenance Bypassp.12415.2.13 Fuseless Designp.12415.2.14 Optionsp.12416.0 Event Message Help Textp.125Key:p.12517.0 Maintenancep.14617.1 Proper Tightening of Nuts and Boltsp.146Table 24 Torque tighteningp.14617.2 Testing the Liebert STS2p.14617.3 Changing the Air Filterp.146Support Informationp.147Programmable Relay Board Settings Recordp.148Input Contact Isolator Settings Recordp.150
Page 8 of the Liebert 100-1000A user manual — Table of contents
Page 8 · click to enlarge
Page 8

Table of contents

Important Safety Instructionsp.9Overview of Manualp.101.0 Safety Precautionsp.112.0 Unpacking and Inspectionsp.122.1 External Inspectionsp.122.2 Unloading and Handlingp.122.2.1 Handling Considerationsp.132.2.2 Unit Preparationp.132.3 Internal Inspectionsp.133.0 Location Considerationsp.143.1 Recommended Minimum Service Clearancesp.143.2 Heat Outputp.14Table 1 Heat outputp.143.3 Operating Environmentp.143.4 Altitudep.15Figure 1 Recommended derating for high altitude operationp.15Figure 2 Maximum ambient temperature for full load operation at higher altitudesp.154.0 Locating the Liebert STS2p.164.1 Leveling and Anchoring the Unit to the Floorp.164.2 Leveling of the Static Switch Without Anchoringp.164.3 Leveling and Anchoring the Static Switch Using Floor Standp.165.0 Power and Control Wiringp.175.1 Input And Output Power Connectionsp.17Figure 3 Typical static transfer switch one-line diagramp.18Table 2 Input/output conduit plate specificationsp.185.2 Input Junction Box Installation—Optionalp.18Table 3 Input junction box dimensionsp.19Table 4 Input junction box terminal wire size rangep.195.3 System Groundingp.20Figure 4 Typical one-line diagram of two PDUs and a Liebert STS2p.205.4 Control Wiring Connectionsp.205.5 Remote Source Selection Wiringp.21Table 5 Remote source selection terminal blockp.215.6 Power Supplyp.21Table 6 Terminal block 1 and terminal block 2 wire connectionsp.216.0 Optionsp.226.1 Programmable Relay Boardp.22Table 7 Programmable relay board pinoutp.226.2 Optimized Transferp.226.3 Distribution Cabinet With I-Line Panelboard—100-600A Units Onlyp.236.4 Input Contact Isolator Boardp.236.5 Comms Boardp.236.6 Liebert IntelliSlot® SNMP/Web/Modbus 485 Cardp.236.7 LED Displayp.246.8 Remote Source Selectionp.246.9 Key Lockout Switchp.246.10 Redundant Output Breakerp.246.11 Transfer Inhibitp.246.12 Input Junction Boxes and Cablesp.256.13 Seismic Floor Anchorsp.256.14 Seismic Floor Standp.257.0 Installation Drawingsp.26Figure 5 Outline drawing: 100 – 250 amp Liebert STS2p.26Figure 6 Outline drawing: 400 – 600 amp Liebert STS2p.27Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2p.28Figure 8 Outline drawing: 100 – 250amp Liebert STS2 with a key lockout switch optionp.29Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch optionp.30Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch optionp.31Figure 11 Seismic anchor drawing: 100 – 250 amp Liebert STS2p.32Figure 12 Seismic anchor drawing: 400 – 600 amp Liebert STS2p.33Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS2p.34Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breakerp.35Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakersp.36Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breakerp.37Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakersp.38Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breakerp.39Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakersp.40Figure 20 Liebert STS2 non-automatic circuit breaker schedulep.41Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2p.42Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2p.43Figure 23 Control wiring for remote source selection optionp.44Figure 24 Control wiring for the programmable relay board optionp.45Figure 25 Control wiring for the input contact isolator board optionp.46Figure 26 Control wiring for comms boardp.47Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 cardp.48Figure 28 Control wiring for the RS-232 portp.49Figure 29 Outline drawing for input junction boxp.50Figure 30 Color LCD touch screen displayp.51Figure 31 LED displayp.52Figure 32 Installation drawing, seismic floor stand 100-250Ap.53Figure 33 Installation drawing, seismic floor stand 100-250Ap.54Figure 34 Installation drawing, seismic floor stand 100-250Ap.55Figure 35 Installation drawing, seismic floor stand 100-250Ap.56Figure 36 Installation drawing, seismic floor stand 400-600Ap.57Figure 37 Installation drawing, seismic floor stand 400-600Ap.58Figure 38 Installation drawing, seismic floor stand 400-600Ap.59Figure 39 Installation drawing, seismic floor stand 400-600Ap.60Figure 40 Installation drawing, seismic floor stand 800-1000Ap.61Figure 41 Installation drawing, seismic floor stand 800-1000Ap.62Figure 42 Installation drawing, seismic floor stand 800-1000Ap.63Figure 43 Installation drawing, seismic floor stand 800-1000Ap.648.0 Introduction to Liebert STS2 Operationsp.658.1 System Descriptionp.658.1.1 Redundancyp.658.1.2 Reliability and Agency Requirementsp.668.1.3 Factory Backup and Service Assistancep.668.2 Modes of Operationp.668.2.1 Normal (Preferred Source)p.668.2.2 Transferp.668.2.3 Transfer Inhibitp.668.2.4 Bypassp.678.3 Operator Controlsp.67Figure 44 Liebert STS2 touch screen displayp.679.0 Theory of Operationp.689.1 General Descriptionp.689.1.1 Liebert STS2 Static Transfer Switchp.689.1.2 Source Transferp.689.1.3 Automatic Transfer/Retransferp.68Automatic Retransfer Inhibitedp.689.1.4 Emergency Transferp.699.1.5 Load Current Transfer Inhibitp.699.1.6 SCR Failurep.699.1.7 On/Off Sequencep.699.2 Detailed Component Descriptionp.709.2.1 Controlsp.70Operator Interfacep.70Hardwarep.70Firmwarep.709.2.2 Circuit Breakersp.719.2.3 SCRsp.719.2.4 Logic Modulesp.719.2.5 Audible Alarmp.719.2.6 RS-232 Portp.7110.0 Operating Instructions for the Touch Screen Interfacep.7210.1 Normal System Startupp.73Figure 45 Liebert STS2 touch screen displayp.7310.2 Manual Transfer / Preferred Source Selectionp.74Figure 46 Source transfer screenp.7410.3 Enabling Remote Source Selectionp.7510.4 Maintenance Bypassp.75Figure 47 Gate board viewing slot locationsp.7610.4.1 Bypass Procedures for Source 1p.7710.4.2 Bypass Procedures for Source 2p.7810.5 Normal System Shutdownp.7810.5.1 Shutdown in Static Transfer Switch Modep.7810.5.2 Shutdown in Maintenance Bypass Modep.7811.0 Alarm and Faultsp.7911.1 Event Maskp.7911.2 Event and History Logsp.8011.2.1 Event Logp.8011.2.2 History Logp.8011.3 Alarm Notesp.8111.4 List of Messagesp.81Table 8 Event messagesp.8212.0 Communication Interfacesp.8412.1 Using the RS-232 Portp.8412.1.1 Connecting and Using a Terminalp.85Table 9 Terminal commandsp.8512.1.2 Configuring the Liebert STS2 via the Terminalp.86Groups Parameterp.86Item Parameterp.86Value Parameterp.87Table 10 Value typesp.87Table 11 Group settings and valuesp.8712.1.3 Setting Bitpacked Options with the Terminalp.89Table 12 Binary-hexadecimal conversionsp.90Putting the Terminal Command Togetherp.9112.1.4 Setting Event Masks with the Terminalp.92Examples of Event Mask Settingsp.9213.0 Liebert STS2 Touch Screen Displayp.9313.1 Display Overviewp.93Figure 48 Liebert STS2 touch screen displayp.9313.2 Menu Overviewp.94Figure 49 Menusp.94Figure 50 Keyboard and keypad displaysp.9413.2.1 Securityp.95Using the Optional Key Lockout Switchp.95Figure 51 Key lockout switch.p.95Using the Passwordp.9513.3 Mimic Displayp.9613.4 Event Controlsp.9613.5 Event Displayp.9613.6 Menu Barp.9613.7 Configuration Menup.9613.7.1 System Ratingsp.9613.7.2 Event Masksp.96Figure 52 Event mask dialog boxp.9713.7.3 User Settingsp.97Figure 53 User settings dialog boxp.98Source Set Pointsp.98Figure 54 Source setpointsp.99Table 13 Sepoint parametersp.9913.7.4 System Settingsp.10113.8 Comm Optionsp.101Figure 55 Comm options dialog boxp.10113.8.1 Configuring the Modemp.102Figure 56 Modem dialog boxp.10213.8.2 Configuring Pager Supportp.10313.8.3 Configuring the Input Contact Isolator Settingsp.104Figure 57 Input contact isolator dialog boxp.10413.8.4 Configuring the Programmable Relay Board Settingsp.105Table 14 Standard settings for programmable relaysp.105Figure 58 Programmable relay board dialog boxp.10613.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Cardp.10613.8.6 Liebert SiteScan® Configurationp.10713.8.7 Saving Your Communications Configurationsp.10713.9 System Optionsp.107Figure 59 System optionsp.107Dual Output Breakerp.107PDUp.1074-Pole Transfer Switchp.108Shuntp.108Wye Output Transformerp.108Remote Source Selectionp.10813.10 System IDp.10813.11 Logsp.10913.11.1 Event Logp.109Figure 60 Event logp.10913.11.2 History Logp.109Figure 61 History logp.10913.12 Source Transfersp.11013.13 Startup Procedurep.11013.14 Bypass Procedurep.11013.15 Helpp.11013.16 Logop.11013.17 Cleaning the LCD Touch Screenp.11014.0 Operating the Liebert STS2 LED Displayp.11114.1 LEDs and Buttons and Key Lockout Switchp.11114.1.1 Front Panel Controlsp.111Figure 62 LED displayp.11114.1.2 LED and Push Button Descriptionp.112Table 15 LED and push button descriptionp.11214.1.3 Event Controlsp.11314.1.4 Key Lockout Switchp.113Figure 63 Key lockout switch.p.11314.2 Operationsp.11414.2.1 Normal System Startupp.11414.2.2 Manual Transfer / Preferred Source Selectionp.11514.2.3 Maintenance Bypassp.116Bypass Procedures for Source 1p.116Bypass Procedures for Source 2p.11714.2.4 Normal System Shutdownp.118Shutdown in Static Transfer Switch Modep.118Shutdown in Maintenance Bypass Modep.11815.0 Specificationsp.11915.1 System Configurationp.11915.1.1 Frequencyp.11915.1.2 Input/Output Voltagep.119Table 16 Input/output voltagep.11915.1.3 System Current Ratingsp.119Table 17 System current ratingsp.11915.1.4 Groundingp.12015.1.5 Electrical Requirementsp.120Table 18 Electrical requirementsp.120Table 19 Unit short circuit withstand capabilityp.12015.1.6 Input Surge Suppressionp.12015.1.7 Response Timep.12015.1.8 Environmental Requirementsp.12015.2 System Componentsp.12115.2.1 Frame and Enclosurep.121Table 20 Frame sizesp.12115.2.2 Casters, Leveling and Seismic Anchoringp.12115.2.3 Coolingp.12115.2.4 Accessp.12215.2.5 Circuit Breakersp.12215.2.6 Cable Entrancep.12215.2.7 Doorsp.12215.2.8 Color Graphical Display or LED Displayp.12215.2.9 RS-232 Portp.12315.2.10 Terminal Port Connectionsp.123Table 21 MTA plug pinoutp.123Table 22 DB9 pinoutp.12315.2.11 RS-232 Interface Parametersp.124Table 23 RS-232 settingsp.12415.2.12 Maintenance Bypassp.12415.2.13 Fuseless Designp.12415.2.14 Optionsp.12416.0 Event Message Help Textp.125Key:p.12517.0 Maintenancep.14617.1 Proper Tightening of Nuts and Boltsp.146Table 24 Torque tighteningp.14617.2 Testing the Liebert STS2p.14617.3 Changing the Air Filterp.146Support Informationp.147Programmable Relay Board Settings Recordp.148Input Contact Isolator Settings Recordp.150
Page 9 of the Liebert 100-1000A user manual — I MPORTANT S AFETY I NSTRUCTIONS
Page 9 · click to enlarge
Page 9

I MPORTANT S AFETY I NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during the installation and maintenance of the Liebert STS2.

! WARNING The unit is supplied by more than one power source. The unit contains hazardous voltages if any of the input sources are ON, even when the unit is in bypass. To isolate the unit, turn OFF and lock out ALL input power sources.

Verify that all input power sources are de-energized and locked out before making connections inside unit.

Lethal voltages exist inside the unit during normal operation. Only qualified service personnel should perform maintenance on the static switch.

Emerson Network Power neither recommends nor knowingly sells this product for use with life support or other FDA-designated “critical” devices.

The Liebert STS2 is suitable for indoor use only. Protect the unit from excessive moisture and install the unit in an area free from flammable liquids, gases, or corrosive substances.

The unit is designed to operate from solidly grounded AC power sources only. Provide input over-current protection in accordance with the unit ratings. Wire and ground the unit according to national and local electrical safety codes. All wiring should be installed by a qualified electrician.

Before unit is placed into service for the first time, after equipment relocation, or after the unit has been de-energized for an extended period of time, a thorough equipment inspection and supervised startup by qualified service personnel are strongly recommended.

! CAUTION This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.

! WARNING Locate the center of gravity symbols and determine the unit’s weight before handling the cabinet.

Page 10 of the Liebert 100-1000A user manual — O VERVIEW OF M ANUAL
Page 10 · click to enlarge
Page 10

O VERVIEW OF M ANUAL

The Liebert STS2 Installation, Operation and Maintenance Manual is organized in a logical progression so that you can follow the procedures in the order provided to get your Liebert STS2 installed and running.

Read the entire manual before proceeding with the unpacking and installation of the Liebert STS2.

The major sections are as follows:

Support Information—a blank table in which you can enter pertinent data, such as the serial and part numbers, needed when calling Emerson for technical support.

Programmable Relay Board Settings Record—a blank table in which you can document your Programmable Relay Board settings.

Input Contact Isolator Settings Record—a blank table in which you can document your Input Contact Isolator settings.

1.0 - Safety Precautions—provides safety warnings that you must review before proceeding.

2.0 - Unpacking and Inspections—provides instructions for inspecting, unloading, handling and removing the Liebert STS2 from the shipping pallet.

3.0 - Location Considerations—provides information regarding environmental considerations for where the Liebert STS2 is installed.

4.0 - Locating the Liebert STS2—provides instructions for leveling the Liebert STS2 and anchoring the unit to the floor, should that be required.

5.0 - Power and Control Wiring—provides instructions wiring the Liebert STS2 for power and control connections.

6.0 - Options—lists the options available for the Liebert STS2.

7.0 - Installation Drawings—provides outline, seismic and electrical field connection drawings required for installing the Liebert STS2.

8.0 - Introduction to Liebert STS2 Operations—provides a system description.

9.0 - Theory of Operation—provides an overview of how the unit works, plus a brief overview of some of the components.

10.0 - Operating Instructions for the Touch Screen Interface—provides instructions for turning the system on and off, completing a maintenance bypass and selecting a preferred source.

11.0 - Alarm and Faults—provides a list of event messages.

12.0 - Communication Interfaces—discusses the communication ports and provides a list of terminal and modem commands.

13.0 - Liebert STS2 Touch Screen Display—provides instructions for using the HMI touch screen interface for monitoring and managing the Liebert STS2.

14.0 - Operating the Liebert STS2 LED Display—provides instructions for operating the LED Display unit without the touch screen display.

15.0 - Specifications—provides specifications for the Liebert STS2.

16.0 - Event Message Help Text—provides the help text for the various system event messages. This help is also available through the touch screen interface.

17.0 - Maintenance—briefly discusses routine maintenance, provides proper torque settings for nuts and bolts, and provides the Emerson contact information for technical support.

Page 11 of the Liebert 100-1000A user manual — ! CAUTION Risk of unit damage
Page 11 · click to enlarge
Page 11

1.0 S AFETY P RECAUTIONS

Read this manual thoroughly before working with the Liebert STS2.

Be sure to review the warning under Important Safety Instructions on page 1.

Refer to the Handling Considerations on page 5 before attempting to move the unit.

Under typical operation and with the doors closed, only normal safety precautions are necessary. The area around the Liebert STS2 should be kept free from puddles of water, excess moisture and debris. The vent grate in the front of the system should not be obstructed in order to ensure a smooth air flow through the unit for cooling.

ONLY qualified service personnel should perform maintenance on the Liebert STS2. When performing maintenance on any part of the equipment under power, service personnel and test equipment should be located on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor.

Unless all power is removed from the input sources to the unit, one person should never work alone. A second person should be on hand to assist and summon help, should an accident occur.

Three types of messages are used throughout this manual to stress important text. Carefully read the information below each Warning, Caution and Note and use professional skills and prudent care when performing the actions described in that text.

A Warning indicates the presence of a possible serious, life-threatening condition. For example:

! WARNING The unit is supplied by more than one power source. The Unit contains hazardous voltages if any of the input sources is ON, even when the unit is in bypass. To isolate the unit, turn OFF and lock out ALL input power sources.

Verify that all input power sources are de-energized and locked out before making connections inside unit.

Lethal voltages exist inside the unit during normal operation. only qualified service personnel should perform maintenance on the static switch.

A Caution indicates a condition that could seriously damage the equipment and possibly injure personnel. For example:

! CAUTION Risk of unit damage

The input sources to the static switch must be grounded-wye sources. input sources other than solidly grounded-wye sources may cause damage to the switch.

A Note emphasizes important text. If the instructions are not properly followed, the equipment could be damaged or may not properly operate. For example:

Safety Precautions

Page 12 of the Liebert 100-1000A user manual — 2.2 Unloading and Handling
Page 12 · click to enlarge
Page 12

2.0 U NPACKING AND I NSPECTIONS

A high-quality installation begins on the receiving dock. The Liebert STS2 and its packaging should be inspected when the unit is delivered. If the packaging is not damaged, unpack the unit and conduct an internal inspection before beginning the installation process. This section discusses the inspecting and unpacking of the Liebert STS2.

2.1 External Inspections 1. While the Liebert STS2 is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. 2. Upon receipt and before unpacking, inspect the shipping crate for damage or mishandling. Check the Shock-Watch™ indicator.

  • If the indicator is red, note on shipper’s receipt and check for concealed damage.
  • If any damage as a result of shipping is observed, file a damage claim with the shipper within 24 hours and contact Emerson Network Power Liebert Services at 1-800-543-2378 or your local Emerson representative to inform them of the damage claim and the condition of the equipment. 3. Locate the bag containing the keys for the front access door. The bag is attached to the cabinet. 4. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and to Liebert Services immediately. 5. Check the nameplate on the cabinets to verify that the model numbers correspond with the one specified. Record the model numbers and serial numbers in the front of this installation manual. A record of this information is necessary should servicing be required. 6. If unit is to be stored before installation, it is recommended to store the unit in a dry environment with temperatures in the range of -40°F (-40°C) to 176°F (80°C). Use original packing materials or other suitable means to keep the unit clean. When opening the shipping crate, use care not to puncture the container with sharp objects.

2.2 Unloading and Handling

! CAUTION Risk of unit damage.

When moving the unit by forklift, lift the unit from the rear so as to protect the front panel.

Do not exceed a 15 degree tilt with the forklift.

Also, if you are moving the unit by forklift or pallet jack after it has been removed from the pallet, be aware of the location of the casters and leveling feet so as not to damage them.

Most Liebert STS2 models are contained in one cabinet. The 800–1000 amp units are contained in two cabinets that are connected together and shipped on one pallet.

Because the weight distribution in the cabinet is uneven, use extreme care during handling and transporting.

The unit can be moved by forklift or pallet jack.

See 2.2.2 - Unit Preparation on page 5 for instruction on removing the Liebert STS2 from the pallet.

Unpacking and Inspections

Page 13 of the Liebert 100-1000A user manual — 2.3 Internal Inspections
Page 13 · click to enlarge
Page 13

2.2.1 Handling Considerations

The static switch is bolted to a wooden shipping pallet to allow handling by forklift equipment or a pallet jack.

Easily Moved — The unit is furnished with integral castors that allow the unit to be rolled into place after it has reached its location and is removed from the pallet.

! WARNING Exercise extreme care when handling static switch cabinets to avoid equipment damage or injury to personnel.

The cabinet can be safely tilted 15 degrees in any direction by forklift.

If moving the unit up a ramp on its casters or a pallet jack, ensure that the incline does not exceed fifteen (15) degrees.

Locate the center of gravity symbols and determine the unit’s weight before handling the cabinet.

Check the unit size and weight — Refer to the cabinet drawings furnished with the unit for size and weight. Typical cabinet dimensions are shown in Figures 5 through 7. Typical unit weights are:

100-250 amp 780 lb. (354 kg)

400-600 amp 1200 lb. (544 kg)

800-1000 amp 2500 lb. (1134 kg)

Plan the route — Review the route over which the unit will be transported to its installation location to ensure that all passages are large enough to accommodate the unit and support the weight. Check for any non-negotiable corners or offsets in hallways. Before moving the unit to the intended location, review 3.0 - Location Considerations.

2.2.2 Unit Preparation

The unit can be removed from the pallet before it is moved to its location.

Complete the following steps to properly remove the Liebert STS2 from the shipping pallet:

1. Set the pallet in a level area with enough room to maneuver and remove the unit. 2. Remove the bolts holding the unit to the shipping pallet (located in the base of the unit). 3. Remove the shipping blocks from under the frame of the unit. 4. Use a forklift to raise the unit off the pallet and onto the floor. Ensure that the forklift is clear of the unit’s casters and leveling feet. Lift the unit from the rear. 5. Conduct an internal inspection of the unit. See the list below of inspection items.

2.3 Internal Inspections

After the Liebert STS2 has been unpacked, conduct an internal inspection:

1. Verify that all items have been received. 2. If spare parts were ordered, verify their arrival. 3. After the Liebert STS2 has been removed from the pallet, open the door and remove cabinet panels to check for shipping damage to internal components. 4. Check for loose connections or unsecured components in the cabinet(s). 5. Check for any unsafe condition that may be a potential safety hazard.

After the Liebert STS2 has been inspected and no problems are found, the unit can be moved to its installation location. If using a forklift, remember to lift the unit from the rear.

Unpacking and Inspections

Page 14 of the Liebert 100-1000A user manual — 3.3 Operating Environment
Page 14 · click to enlarge
Page 14

3.0 L OCATION C ONSIDERATIONS

The Liebert STS2 should be placed in a clean, cool and dry location. The Liebert STS2 requires only front access for installation and maintenance. Back or side access is not required. Adequate space is required above the unit for conduit (if configured as such) and cooling air flow. This section provides specific information for these considerations.

The unit is designed with top and bottom cable terminations to allow maximum flexibility in its installation. If bottom cable entry is used, sufficient cable bending space must be provided by a raised floor or a floor stand.

For dimensions of each unit, see Figures 5, 6 and 7 in section 7.0 - Installation Drawings on page 18. If your unit is equipped with an optional key lockout switch, see Figures 8 through 10 for location of that switch.

3.1 Recommended Minimum Service Clearances

The recommended service clearances are at the front of the unit. The minimum service clearance required by the National Electrical Code (NEC) Article 110-26 is 36 in. (91 cm) for units with voltages up to 150V to ground and 42 in. (107 cm) for units with voltages over 150V to ground. Clearance of at least 18 in. (46 cm) is required above the unit for cooling air flow.

3.2 Heat Output

The unit produces minimal heat during normal operation.

Table 1 Heat output

Heat Output BTU/Hr (kW)

100 amp 2,711 (0.80)

250 amp 4,680 (1.37)

400 amp 6,972 (2.04)

600 amp 10,520 (3.08)

800 amp 13,777 (4.03)

1000 amp 17,390 (5.09)

3.3 Operating Environment

The unit is designed to be installed indoors under the following environmental conditions:

  • Storage Temperature Range: -40° to +80°C (-40° to 176°F).
  • Operating Temperature Range: 0° to 40°C (32° to 104°F).
  • Relative Humidity: 0 to 95% without condensation.
  • Operating Altitude: Up to 4000 ft. (1200m) above sea level without derating. Above 4000 ft. (1200m), output current is derated by 6% per 1000 ft. (18% per 1000m).
  • Storage/Transport Altitude: Up to 40,000 ft. (12,200m) above sea level.
  • Audible Noise: Less than 55 dBA at 5 ft. (1.5m) with audible alarm off.

Location Considerations · Switch Size

Page 15 of the Liebert 100-1000A user manual — Altitude, Feet (M) Above Sea Level
Page 15 · click to enlarge
Page 15

3.4 Altitude

The standard units are designed for full load operation up to 4000 feet (1200m) above sea level. See Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200m).

Figure 1 Recommended derating for high altitude operation

Rating (%)

Altitude, Feet (M) Above Sea Level

Operation at full load at a higher altitude can be accommodated in ambient temperatures less than 104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load operation at altitudes above 4000 feet (1200 m).

Figure 2 Maximum ambient temperature for full load operation at higher altitudes

104.0 (40)

102.2 (39)

Temperature, °F (°C)

Maximum Ambient

100.4 (38)

98.6 (37)

96.8 (36)

95.0 (35)

93.2 (34)

94.1 (33)

89.6 (32)

87.8 (31)

86.0 (30)

Altitude, Feet (M) Above Sea Level

Show 27 more labels / short text on this page
Location Considerations · 4000 (1200) · 4500 (1372) · 5000 (1524) · 5500 (1676) · 6000 (1829) · 6500 (1981) · 7000 (2134) · 7500 (2286) · 8000 (2438) · 8500 (2591) · 9000 (2743) · 9500 (2896) · 10,000 (3048) · 4000 (1200) · 4500 (1372) · 5000 (1524) · 5500 (1676) · 6000 (1829) · 6500 (1981) · 7000 (2134) · 7500 (2286) · 8000 (2438) · 8500 (2591) · 9000 (2743) · 9500 (2896) · 10,000 (3048)
Page 16 of the Liebert 100-1000A user manual — 4.3 Leveling and Anchoring the Static Switch Using Floor Stand
Page 16 · click to enlarge
Page 16

Locating the Liebert STS2

4.0 L OCATING THE L IEBERT STS2

This section provides instructions for leveling the Liebert STS2 and anchoring the unit to the floor, should that be required.

For leveling feet details, see Figures 5 through 10.

4.1 Leveling and Anchoring the Unit to the Floor

The Liebert STS2 can be anchored to the concrete floor to ensure stability for the unit in the event of seismic activity.

The seismic brackets are an option for the Liebert STS2 and are shipped separately from the unit when ordered.

See Figures 11 through 13 for instructions and details for installing seismic anchoring.

4.2 Leveling of the Static Switch Without Anchoring

The Liebert STS2 is furnished with casters and leveling feet. After final positioning of the unit, adjust the leveling feet located in each corner of the frame base to level and stabilize the unit.

4.3 Leveling and Anchoring the Static Switch Using Floor Stand

The Liebert STS2 can be installed using the optional floor stand to support the unit instead of using the raised floor. The Liebert STS2 can be rolled or placed using a lift on to the floor stand.

After final positioning of the unit, adjust the leveling feet located in each corner of the frame base to level and stabilize the unit.

The floor stand can also be used to ensure the unit’s stability in the event of seismic activity by anchoring the Liebert STS2 to the floor stand and to the concrete floor.

The seismic floor stand is shipped separately from the unit when ordered.

See Figures 32 through 43 for instructions and details for installing seismic floor stand.

Page 17 of the Liebert 100-1000A user manual — 5.0 P OWER AND C ONTROL W IRING
Page 17 · click to enlarge
Page 17

Power and Control Wiring

5.0 P OWER AND C ONTROL W IRING

All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes. Unless otherwise labeled, use the recommended tightening torque as shown in Table 24 - Torque tightening. The busbars are accessible through the front of the Liebert STS2 and designed to allow one-handed tightening. Cables can be installed through the top or bottom of the unit through removable conduits plates. See Figures 5 through 10 for wiring entrance locations. Input wiring also can be installed under a raised floor to optional input junction boxes and cables, when used. 5.1 Input And Output Power Connections

If the unit is furnished with input junction boxes, the input power connections are made to the input power terminals located in the junction boxes. Input power cables, furnished with the input junction boxes, are shipped unattached to the unit for connection between the junction boxes and the bus bars provided inside the unit. Input junction box installation is discussed in 5.2 - Input Junction Box Installation—Optional on page 10. If input junction boxes are not furnished, the input power connections are made to the bus bars provided inside the unit. These bus bars are accessible through the front of the unit. Output power connections also are made to the bus bars provided inside the unit. These bus bars are accessible through the front of the unit. See Figures 14 to 19 for details on the bus bars.

! WARNING Risk of electric shock Verify that all input power and control circuits are de-energized and locked out before making connections inside unit.

The two input power feeds (sources) to the Liebert STS2 should be from two independent sources to avoid a common source failure. To ensure proper operation of the Liebert STS2, the two input sources must be the same nominal voltage level and phase rotation. For uninterrupted automatic transfer, the two input sources should be synchronized within 15 degrees.

! CAUTION Risk of unit damage. The input sources to the static switch must be grounded-wye sources. Input sources other than solidly grounded-wye sources may cause damage to the switch.

The Liebert STS2 is designed for operation with 3- or 4-wire, solidly grounded sources only. For 4-wire operation, the common source neutral must be connected to the Liebert STS2. See Figure 3 on page 10 for a typical one-line diagram. Refer to Figures 14 to 19 for electrical field connections on all units, with both single and dual output breakers.

Page 18 of the Liebert 100-1000A user manual — 5.2 Input Junction Box Installation—Optional
Page 18 · click to enlarge
Page 18

Power and Control Wiring

Figure 3 Typical static transfer switch one-line diagram

SOURCE 1 SOURCE 2

STS2 STS1

CB1

CB2

K2 K1

K1 K3 K2 K3 CB4 CB5

CB3

OUTPUT

The input and output power wire size should be based on the upstream overcurrent protection device, observing the NEC and local codes.

The molded case switches contained in the Liebert STS2 are typically non-automatic circuit breakers that rely on the upstream and/or load overcurrent protection. Upstream overcurrent protection should be rated equal to or less than the rating of the Liebert STS2 molded case switches.

The Liebert STS2 input and output power and ground and neutral bus bars accommodate a wide range of wire sizes. The Liebert STS2 bus bars accommodates standard 2 hole lugs.

Table 2 Input/output conduit plate specifications

Rating Max. number and size

100-250A 6 — 3" conduit

400-600A 9 — 4" conduit

800-1000A 12 — 4" conduits

5.2 Input Junction Box Installation—Optional

The input junction box option is available to simplify input connections to the Liebert STS2. Two input junction boxes and the associated flexible 10 foot long (3 meter) input cables are provided with this option.

This option is available only with bottom cable entrance, typically when the unit is located on a raised floor.

If the input junction boxes will be used, they may be shipped either with the unit or in advance to be installed during the rough-in stage of construction.

Locate the junction boxes a maximum of 8 feet (2.4 meters) from the planned location of the Liebert STS2.

Due to a lack of clearance for the cables below the unit, the cables are also shipped loose from the unit for installation at the site. The input cables connect from the input junction boxes to the input power bus bars inside the Liebert STS2.

The standard configuration for the input junction boxes and cables is for 3-wire-plus-ground feeds. If the input neutral is required, special 4-wire-plus-ground input cables and junction boxes are required. See Figure 29 for wiring details.

Page 19 of the Liebert 100-1000A user manual — Table 3 Input junction box dimensions
Page 19 · click to enlarge
Page 19

Power and Control Wiring

For preparation purposes, the following tables provide the dimensions and wire sizes for the input junction boxes.

Table 3 Input junction box dimensions

100 amp 16 (406) 14 (356) 6 (152)

250 to 600 amp 30 (762) 16 (406) 6 (152)

Table 4 Input junction box terminal wire size range

Switch Rating Power and Ground Lug Wire Range

100 amp #6 to #2/0 AWG

250 to 600 amp (2) #6 AWG to (2) 500 kcmil

Show 4 more labels / short text on this page
Length Inches (mm) · Width Inches (mm) · Height Inches (mm) · Switch Rating
Page 20 of the Liebert 100-1000A user manual — 5.4 Control Wiring Connections
Page 20 · click to enlarge
Page 20

Power and Control Wiring

5.3 System Grounding

Equipment grounding — Grounding is primarily for equipment and personnel safety, although proper grounding also enhances equipment performance.

All input and output power feeds must include an equipment grounding means as required by the NEC and local codes.

An insulated equipment ground conductor is recommended to run with each input and output power feed. The equipment ground conductors should be at least the minimum size conductor per the NEC based on the upstream overcurrent protection device.

! WARNING If conduit is used as a grounding means, adequate electrical continuity must be maintained at all conduit connections. The use of isolating bushings with a metal conduit can be a safety hazard and is not recommended.

4-Wire-Plus-Ground Systems — When 4-wire-plus-ground input feeds are utilized, the input power sources must be properly grounded. Because the neutral is not switched by the Liebert STS2, the neutrals of the two power sources are solidly interconnected. The NEC prohibits grounding a power source at more than one point. Connecting the neutrals of two grounded power sources together effectively grounds each of the sources at more than one point, which allows neutral current to flow on the ground system, defeats ground fault protection, creates a safety hazard, and violates the NEC.

Where possible, the two power sources should be located in close proximity and a single neutral-to-ground bond made (as shown in Figure 4 on page 12 or as is typical with a double- ended substation).

Figure 4 Typical one-line diagram of two PDUs and a Liebert STS2

Liebert 100-1000A — 5.3 System Grounding diagram (page 20)
Fig. 2 · 5.3 System Grounding

5.4 Control Wiring Connections

No control wiring is needed on the standard Liebert STS2. Only certain options require external control wiring. See 6.0 - Options on page 14 for details

Page 21 of the Liebert 100-1000A user manual — F2 TB1-YY
Page 21 · click to enlarge
Page 21

Power and Control Wiring

5.5 Remote Source Selection Wiring

An optional Remote Source Selection board may be installed in your Liebert STS2. This board is installed in the same bay as the communications options. See Figures 21 and 22 for the location of these options. See Figure 23 for information on the control wiring for the Remote Source Selection option.

The Remote Source Selection allows you choose the preferred input source from a remote location. Terminal connections allow the customer to remotely select a source to be the preferred source in the same process as the local source transfer selection.

The unit’s preferred source selection and Remote Source Selection are active at the same time, with the Liebert STS2 following the last request for a preferred source change, regardless of whether it was from the local or Remote Source Selection controls.

A six pin terminal block provides the Remote Source Selection connections. Two pairs of wires are used from the switch to trigger the source selection. You can select the type of switch used for this remote control. Connections are made to four of the connections, using Form A dry contacts. The contacts are numbered left to right:

Table 5 Remote source selection terminal block

5 DO NOT USE

6 DO NOT USE

See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source Selection option.

5.6 Power Supply

The Liebert STS2 is supplied with redundant power supplies that are designed to operate from a voltage range of 200V to 600V. The unit is set at the factory to match the nameplate voltage. Field adjustments are not necessary. If the unit needs to operate at a voltage other than what is listed on the nameplate, contact Liebert Services or your local Emerson representative. Table 6 provides transformer tap information.

Table 6 Terminal block 1 and terminal block 2 wire connections

Jumper Between F1 TB1-XX

F2 TB1-YY

F3 TB2-XX

F4 TB2-YY

200 1 9 1 9 1-7

208 1 10 1 10 1-7

220 2 12 2 12 6-8

240 1 11 1 11 1-7

380 1 8 1 8 2-7

400 1 9 1 9 3-7

415 1 10 1 10 4-7

480 1 11 1 11 5-7

600 1 12 1 12 6-7 ! CAUTION Using Table 6, ensure that the wiring for the control transformers matches the input voltage for the unit. Improper wiring could result in blown fuses.

Show 7 more labels / short text on this page
Contact Connection · 1 Source 1 · 2 Isolated ground · 3 Source 2 · 4 Isolated Ground · Connect t Connect · Voltage
Page 22 of the Liebert 100-1000A user manual — 6.2 Optimized Transfer
Page 22 · click to enlarge
Page 22

6.0 O PTIONS

This section discusses the options available for the Liebert STS2. The communications options are also discussed in 12.0 - Communication Interfaces.

6.1 Programmable Relay Board

The Programmable Relay Board (PRB) provides a means to trigger an external device when an event occurs in the Liebert STS2. Each PRB has eight channels. Each channel has two sets of Form-C dry contacts, rated 1 Amp @ 30 VDC or 250 mAmp @ 125VAC.

Any alarm/event can be programmed to any channel or channels. Up to ten (10) events can be programmed to a relay. If multiple events are grouped to one relay, group the events logically to simplify troubleshooting when an event is triggered. The same alarm/event can be programmed to more than one channel. Up to two Programmable Relay Boards can be installed in the Liebert STS2 for a total of 16 channels. Programming is performed through the touch screen display.

See Configuring the Programmable Relay Board Settings on page 97 for default settings and instructions for reconfiguring the relays. See Figures 21 and 22 for the location of the PRB. See Figure 24 for wiring details. Table 7 provides the PRB pinout.

Table 7 Programmable relay board pinout

Channel Pin No. C N.C. N.O.

A 1-3 1 2 3

CH1

B 4-6 4 5 6

TB1

A 7-9 7 8 9

CH2

B 10-12 10 11 12

A 13-15 13 14 15

CH3

B 1-3 1 2 3

A 4-6 4 5 6

CH4

TB2

B 7-9 7 8 9

A 10-12 10 11 12

CH5

B 13-15 13 14 15

A 1-3 1 2 3

CH6

B 4-6 4 5 6

TB3

A 7-9 7 8 9

CH7

B 10-12 10 11 12

A 13-15 13 14 15

CH8

TB4 B 1-3 1 2 3

Key: N.O. = Normally Open; N/C. = Normally Closed; C = Common Note: Pin 16 not used on TB1, TB2, and TB3.

6.2 Optimized Transfer

When the Liebert STS2 is used as a primary-side switch—on the primary of an isolation transformer—optimized transfer greatly reduces the transformer magnetization current during automatic transfers through a new transfer control algorithm. The Liebert algorithm optimizes the transfer timing so that the volt-seconds applied to the downstream transformer primary is balanced, minimizing peak saturation current.

The volt-second balance is achieved by directly computing the volt-second applied to the transformer during transfer events and determining the optimum time to turn on the alternate source SCRs in order to balance the volt-second within specified tolerance.

Optimized transfer also seeks to minimize the voltage disturbances while still maintaining transformer flux balance. This unique flux balance algorithm does not just wait for the balance point to occur, but will pulse fire the SCRs as soon as possible to minimize the voltage disruption. This results in far superior voltage waveforms applied to the load.

Options

Page 23 of the Liebert 100-1000A user manual — 6.6 Liebert IntelliSlot ® SNMP/Web/Modbus 485 Card
Page 23 · click to enlarge
Page 23

6.3 Distribution Cabinet With I-Line Panelboard—100-600A Units Only

A distribution cabinet with a Square D I-Line panelboard offers space to plug in up to 10 three-pole branch circuit breakers (100A-250A). The panelboard is rated at 600A with an overall short-circuit rating of 100,000 AIC.

The full-height cabinet mounts on either the right or left side of the Liebert STS2 and is fully enclosed with a keylock door and an accent cover that permits access to the panelboard without exposing other portions of the Liebert STS2.

6.4 Input Contact Isolator Board

The Input Contact Isolator Board (ICI) provides an Liebert STS2 module interface for up to eight external user alarm or message inputs to be routed through the Liebert STS2’s alarm network. The eight contacts are normally open dry contacts. When a contact closes, an event is triggered.

The Input Contact Isolator options are configured through the Input Contact Isolator dialog box, which is accessed from the Comm Option dialog box on the touch screen display. You also can program the alarm messages through this dialog box. See Configuring the Input Contact Isolator Settings on page 96 for instructions on configuring the connections.

See Figures 21 and 22 for the location of the ICI. See Figure 25 for wiring details.

6.5 Comms Board

The Comms Board provides a communication interface to Liebert SiteScan, a site monitoring product and/or an external modem. Liebert SiteLink™-12 or Liebert SiteLink-4 is required for Liebert SiteScan to communicate with the Liebert STS2.

The Comms Board is equipped with an RS-422 communication port for communication to a Liebert SiteScan monitoring system using a 2-wire twisted pair for reliable communication up to 1000 meters (3281 feet). Information available from the RS-422 port includes the present switch status information, all monitoring parameters, and all active alarms.

The Comms Board is equipped with a modem interface for remote reporting of the present switch status information, alarm history information, and the history of status screens that are triggered upon a major alarm event. The monitoring system software also supports an auto-dial feature that allows the system to automatically dial programmed phone numbers by way of the modem to report designated alarm conditions.

Programming the Comms Board is performed through the touch screen display. See Comm Options on page 93 for details.

See Figures 21 and 22 for the location of the Comms Board.

See Figure 26 for information on the control wiring.

6.6 Liebert IntelliSlot ® SNMP/Web/Modbus 485 Card

A Liebert IntelliSlot SNMP/Web/Modbus 485 card enables the Liebert STS2 to communicate to a network management system (NMS). The card provides the internal hardware and software to communicate, via SNMP/Web (HTTP), to any IP-based Ethernet network through an RJ-45 connector using Category 5 cabling.

The Liebert SNMP/Web/Modbus 485 card provides redundant paths for communications that make it possible to connect to a Building Management System (BMS) using Modbus, while simultaneously communicating to a NMS through SNMP/Web (HTTP). A terminal block provides the connection to Modbus.

See Figures 21 and 22 for the location of the Liebert SNMP/Web/Modbus 485 card. See Figure 27 control wiring information.

If you have questions about the Liebert SNMP/Web/Modbus 485 card, refer to the user guide, SL-52615, available at the Liebert Web site, www.liebert.com

Options

Page 24 of the Liebert 100-1000A user manual — 6.11 Transfer Inhibit
Page 24 · click to enlarge
Page 24

6.7 LED Display

A light-emitting diode display is available to replace the standard liquid crystal display touch screen control. The display provides monitoring and control throuh a series of LEDs and buttons. LEDs alert you when a problem occurs. A PC running terminal emulation software connected to the RS-232 port is needed to access the data and configuration settings.

6.8 Remote Source Selection

The Remote Source Selection allows the preferred input source to be chosen from a remote location. A user supplied normally open dry contact allows the user to remotely select a source to be the preferred source in the same process as the local source transfer selection.

The unit’s preferred source selection and Remote Source Selection are active at the same time, with the Liebert STS2 following the last request for a preferred source change, regardless of whether it was from the local or Remote Source Selection controls.

See 10.3 - Enabling Remote Source Selection for instructions on enabling the Remote Source Selection.

See Figures 21 and 22 for the location of the Remote Source Selection option.

See 5.5 - Remote Source Selection Wiring on page 13 and Figure 23 for information on the control wiring.

6.9 Key Lockout Switch

The key lockout switch activates a software lockout of the touch screen display to prevent manual transfers and configuration changes. When locked out, the touch screen becomes a read only display. A key is needed to do manual transfers or change settings.

The alarm silence button is not disabled when in the lockout position.

The switch is located behind the front door but can be operated without opening the front door. See Figures 8 to 10 for the key lockout location on each unit.

See 14.1.4 - Key Lockout Switch for instructions on using the key lockout switch.

6.10 Redundant Output Breaker

An output plug-in, non-automatic circuit breaker is provided which allows redundancy in the output power path. The breaker is connected in parallel with the output plug-in non-automatic circuit breaker.

6.11 Transfer Inhibit

Transfer Inhibit prevents the Liebert STS2 from transferring under certain conditions. When a customer-supplied closed dry contact is provided, the Liebert STS2 will not transfer and remain on its present source even if the source is no longer supplying power.

This option requires an Input Contact Isolator board (see 6.4 - Input Contact Isolator Board).

Options

Page 25 of the Liebert 100-1000A user manual — 6.14 Seismic Floor Stand
Page 25 · click to enlarge
Page 25

6.12 Input Junction Boxes and Cables

Two input power junction boxes and interconnecting cables provide under floor connection for the two input power feeds. Power terminal blocks are provided in each junction box for the connection of the input power conductors and a parity-sized ground conductor. The junction boxes are NEMA 1 enclosures. A main input cable assembly is provided for connection between the unit and the junction box. The cable length between the unit and junction box is 10 feet (3 meters) long.

See 5.2 - Input Junction Box Installation—Optional on page 10 for more information and specifications. See Figure 29 for wiring details.

6.13 Seismic Floor Anchors

Seismic anchors are available for anchoring the unit to a concrete floor to meet seismic Zone 4 requirements. See 4.1 - Leveling and Anchoring the Unit to the Floor on page 8 for more information. Installation details are provided in Figures 11 through Figure 13 on page 26.

6.14 Seismic Floor Stand

Seismic floor stands in four heights—18", 24", 30" and 36" (457mm, 610mm, 762mm and 914mm)— are available for the Liebert STS2. The stands can be fastened to the floor to meet seismic Zone 4 requirements. See 4.0 - Locating the Liebert STS2 and Figures 32 through 43 for instructions and details for installing seismic floor stands.

Options

Page 26 of the Liebert 100-1000A user manual — 7.0 I NSTALLATION D RAWINGS
Page 26 · click to enlarge
Page 26

7.0 I NSTALLATION D RAWINGS

Figure 5 Outline drawing100 – 250 amp Liebert STS2

32.1" (815)

Center Of Gravity Center Of Gravity

36.7" (932)

18.8 (477) 19.2" (488)

23.4" (594) Caster Centers

24.4" (620)

8.4 (213) 11.1 (280) 4.6 (116)

9.4 (238)

13.5" (343)

29" (736) (12mm centers) 21.6" (548) Caster Centers

12.8" (326)

21.5 (546)

24.4 (619)

.47" (12)

5.1 (130) 29.8" (756)

Notes: 1. All dimensions are in inches and (millimeters). 2. 18" (457mm) min. clearance above unit required for air exhaust. 3. Clearance of 36" (914mm) minimum is required in the front for installation and service access. 4. Heat output: 2710 btu/hr (0.80 kW/hr) max. for 100A switch. 4680 btu/hr (1.37 kW/hr) max. for 250A switch. 5. Weight: 780 lb. (354 kg) 6. Unit bottom is structurally adequate for forklift handling. 7. Keep cabinet within 15 degrees of vertical while handling. 8. Color - IBM off-white. 9. Open door to replace air filter, disposable type, size 1x25x25. 10.Threaded mounting holes (see detail a) are provided for seismic anchoring or floor stand. Mounting bolts must be threaded into the unit mounting holes from underneath the unit base. If floor stand is used, the casters must rest on the floor stand to support the weight of the unit.

2.75" (69.8) typ.

.47" (12) dia. threaded mounting

hole; 4 typ. see Note 10

DETAIL A Front of Unit Without Side Panel

PS211100 Rev. 03

Show 5 more labels / short text on this page
Installation Drawings · 30" (762) · 77" (1956) · centers · Leveler
Page 27 of the Liebert 100-1000A user manual — Figure 6 Outline drawing: 400 – 600 amp Liebert STS2
Page 27 · click to enlarge
Page 27
Figure 6 Outline drawing400 – 600 amp Liebert STS2
Liebert 100-1000A — Figure 6 Outline drawing: 400 – 600 amp Liebert STS2 diagram (page 27)
Fig. 3 · Figure 6 Outline drawing: 400 – 600 amp Liebert STS2

Installation Drawings

Page 28 of the Liebert 100-1000A user manual — Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2
Page 28 · click to enlarge
Page 28
Figure 7 Outline drawing800 – 1000 amp Liebert STS2
Liebert 100-1000A — Figure 7 Outline drawing: 800 – 1000 amp Liebert STS2 diagram (page 28)
Fig. 4 · Figure 7 Outline drawing: 800 – 1000 amp Liebert STS…

Installation Drawings

Page 29 of the Liebert 100-1000A user manual — Figure 8 Outline drawing: 100 – 250amp Liebert STS2 with a key lockout switch option
Page 29 · click to enlarge
Page 29
Figure 8 Outline drawing100 – 250amp Liebert STS2 with a key lockout switch option

Notes: 1. All dimensions are in inches and (millimeters). 2. 18" (457mm) min. clearance above unit required for air exhaust. 3. Clearance of 36" (914mm) minimum is required in the front for installation and service access. 4. Heat output: 2710 btu/hr (0.80 kW/hr) max. for 100A switch. 4680 btu/hr (1.37 kW/hr) max. for 250A switch. 5. Weight: 780 lb. (354 kg) 6. Unit bottom is structurally adequate for forklift handling. 7. Keep cabinet within 15 degrees of vertical while handling. 8. Color - IBM off-white. 9. Open door to replace air filter, disposable type, size 1x25x25. 10.Threaded mounting holes (see detail a) are provided for seismic anchoring or floor stand. Mounting bolts must be threaded into the unit mounting holes from underneath the unit base. If floor stand is used, the casters must rest on the floor stand to support the weight of the unit.

PS211101 Rev. 02

Installation Drawings

Page 30 of the Liebert 100-1000A user manual — Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch option
Page 30 · click to enlarge
Page 30
Figure 9 Outline drawing400 – 600 amp Liebert STS2 with a key lockout switch option
Liebert 100-1000A — Figure 9 Outline drawing: 400 – 600 amp Liebert STS2 with a key lockout switch option diagram (page 30)
Fig. 5 · Figure 9 Outline drawing: 400 – 600 amp Liebert STS2…

Installation Drawings

Page 31 of the Liebert 100-1000A user manual — Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch option
Page 31 · click to enlarge
Page 31
Figure 10 Outline drawing800 – 1000 amp Liebert STS2 with the key lockout switch option
Liebert 100-1000A — Figure 10 Outline drawing: 800 – 1000 amp Liebert STS2 with the key lockout switch option diagram (page 31)
Fig. 6 · Figure 10 Outline drawing: 800 – 1000 amp Liebert ST…

Installation Drawings

Page 32 of the Liebert 100-1000A user manual — FRONT FLOOR
Page 32 · click to enlarge
Page 32
Figure 11 Seismic anchor drawing100 – 250 amp Liebert STS2

PS211105

FLOOR LINE

FRONT CABINET

Rev. 0

BASE BRACKET

7. IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM DISTANCE FROM EITHER SIDE WALL IS REQUIRED.

REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH

6. MARK HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL FLOOR BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS.
8. REAR AND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINET BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.

FIGURE 3 FIGURE 2

BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT

5. MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OF FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR

CABINET BASE BRACKET BUT DO NOT FULLY TIGHTEN HARDWARE.

SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

FRONT FLOOR

FRONT DOOR

BRACKET

OF CABINET

FLOOR ANCHOR

NOT SUPPLIED

HARDWARE

SUPPLIED

HARDWARE

APPROX 1/2"

REAR FLOOR

BASE BRACKET BACK

WALL

BRACKET

FLOOR ANCHOR

(NOT SUPPLIED)

HARDWARE

REAR CABINET

FLOOR LINE

REAR FLOOR

SEE NOTE (2)

FOR SPACING

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

4. INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH BENT FLANGE FACING FRONT.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

BRACKET

2. POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75" FROM BACK WALL. MARK LOCATION AND DRILL HOLES (FIG. 1) TO
1. RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD SELF DRILLING ANCHOR, ICBO #ER-1372 OR EQUIVALENT (NOT
3. INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.

(146 MM)

BACK WALL

5.75"

SYSTEM SEISMIC ANCHORING, FIGURE 1

(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

(107 MM)

A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

4.2"

(335 MM)

13.2" 13.2"

TOP VIEW

FRONT

(107 MM) (256 MM)

10.1" 4.2"

(335 MM)

BRACKET IS SECURED.

BRACKET IS SECURED.

FRONT FLOOR

NOTES:

BRACKET

SIDE WALL

32.75" (832 MM)

SEE NOTE (7)

FOR SPACING

Installation Drawings

Page 33 of the Liebert 100-1000A user manual — FRONT FLOOR
Page 33 · click to enlarge
Page 33
Figure 12 Seismic anchor drawing400 – 600 amp Liebert STS2

FLOOR LINE

BASE BRACKET FRONT CABINET

BASE BRACKET

7. IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM DISTANCE FROM EITHER SIDE WALL IS REQUIRED.

REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH

PS211405

6. MARK HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL FLOOR BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS.
8. REAR AND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINET BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.

FIGURE 3

BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT

Rev. 0

5. MOVE CABINET INTO POSITION WITH REAR TABS INTO SLOTS OF FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR

CABINET BASE BRACKET BUT DO NOT FULLY TIGHTEN HARDWARE.

SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

BRACKET FRONT FLOOR

FRONT DOOR

OF CABINET

FLOOR ANCHOR

NOT SUPPLIED REAR FLOOR

HARDWARE

SUPPLIED

HARDWARE

APPROX 1/2"

BACK

WALL

BRACKET

FLOOR ANCHOR

(NOT SUPPLIED)

HARDWARE

FIGURE 2

REAR CABINET

FLOOR LINE

REAR FLOOR

SEE NOTE (2)

FOR SPACING

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

4. INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH BENT FLANGE FACING FRONT.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

BRACKET

(146 MM)

2. POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75" FROM BACK WALL. MARK LOCATION AND DRILL HOLES (FIG. 1) TO

5.75" (107 MM)

1. RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD SELF DRILLING ANCHOR, ICBO #ER-1372 OR EQUIVALENT (NOT
3. INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.

BACK WALL

SYSTEM SEISMIC ANCHORING, FIGURE 1

(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

4.2"

A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

(335 MM) (335 MM)

13.2" 13.2"

TOP VIEW

FRONT

(462 MM)

18.2" (107 MM)

BRACKET IS SECURED.

BRACKET IS SECURED.

NOTES:

4.2"

FRONT FLOOR

BRACKET

SIDE WALL

32.75" (832 MM)

SEE NOTE (7)

FOR SPACING

Installation Drawings

Page 34 of the Liebert 100-1000A user manual — 13.2" (335 MM)
Page 34 · click to enlarge
Page 34
Figure 13 Seismic anchor drawing800 – 1000 amp Liebert STS2

FLOOR LINE

FRONT CABINET

BASE BRACKET

PS211805

FIGURE 3

Rev. 0

FRONT FLOOR

7. IF SIDE WALLS ARE PRESENT, 5.0 INCH MINIMUM D ISTANCE FROM EITHER SIDE WALL IS REQUIRED.

APPROX 1/2"

FRONT DOOR

BRACKET

REINSTALL FRONT FLOOR BRACKETS TO FRONT CABINET BRACKETS WITH

BRACKET REAR FLOOR

OF CABINET

8. REAR A ND FRONT FLOOR BRACKETS, AND REAR AND FRONT CABINE T

FLOOR ANCHOR

NOT SUPPLIED

6. MARK HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL FLOOR BRACKETS. UNIT DOOR CAN BE REMOVED FOR BETTER ACCESS.

BACK

WALL

HARDWARE

BRACKET (FIG. 2). THEN ATTACH FRONT FLOOR BRACKETS TO FRONT

SUPPLIED

HARDWARE

5. MOVE CABINET INTO P OSITION W ITH REAR TABS INTO S LOTS OF FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR

CABINET BASE BRACKET BUT DO N OT FULLY TIGHTEN HARDWARE.

(NOT SUPPLIED )

BASE BRACKETS ARE 1010 STEEL AND APPROX. .25 INCH THICK.

FLOOR ANCHOR

HARDWARE

FIGURE 2

SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

REAR CABINET

BASE BRACKET

FLOOR LINE

SEE NOTE (2)

(144 MM)

REAR FLOOR

FOR SPACING

5.7"

BRACKET

4.2" 4.2" (107 MM)

13.2" 15.6" (335 MM) (396 MM)

FOR SPACING BACK WALL

SYSTEM SEISMIC ANCHORING, FIGURE 1

32.2" (817 MM)

FRONT

13.2" (335 MM)

1. RECOMMENDED FLOOR ANCHOR: 1/2" ITW RAMSET/RED HEAD

FROM BACK WALL. MARK LOCATION A ND DRILL HOLES (FIG. 1) TO

TOP VIEW

SELF DRILLING ANCHOR, ICBO #ER-1372 OR EQUIVALENT (NOT

2. POSITION REAR FLOOR BRACKETS ON FLOOR AT LEAST .75"
3. INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING
4. INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING

(107 MM)

HOLES ON U NDERSIDE OF UNIT WITH BENT FLANGE FACING FRONT.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.

11.4" (289 MM)

(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

4.2" (107 MM)

13.2" (335 MM)

4.2"

(310 MM)

12.2"

BRACKET IS SECURED.

BRACKET IS SECURED.

13.2" (335 MM)

(107 MM)

NOTES:

FRONT FLOOR

SIDE WALL

BRACKET

SEE NOTE (7)

32.75" (832 MM)

Installation Drawings

Page 35 of the Liebert 100-1000A user manual — Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breaker
Page 35 · click to enlarge
Page 35

Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breaker

Liebert 100-1000A — Figure 14 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with single output breaker diagram (page 35)
Fig. 7 · Figure 14 Electrical field connections drawing: 100…

CONDUIT SIZE, AND REPLACE. REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

3. CONTROL WIRING AND POWER WIRING MUST BE RUN
5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL
7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS 428 INCH-LBS. (48 N-m).

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES. IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT 6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,

Installation Drawings

Page 36 of the Liebert 100-1000A user manual — Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakers
Page 36 · click to enlarge
Page 36

Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakers

Liebert 100-1000A — Figure 15 Electrical field connections drawing: 100 – 250 amp Liebert STS2 with dual output breakers diagram (page 36)
Fig. 8 · Figure 15 Electrical field connections drawing: 100…

Installation Drawings

Page 37 of the Liebert 100-1000A user manual — Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breaker
Page 37 · click to enlarge
Page 37

Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breaker

Liebert 100-1000A — Figure 16 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with single output breaker diagram (page 37)
Fig. 9 · Figure 16 Electrical field connections drawing: 400…

CONDUIT SIZE, AND REPLACE. REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

3. CONTROL WIRING AND POWER WIRING MUST BE RUN
5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL

428 INCH-LBS. (48 N-m). 7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES. IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT 6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,

Installation Drawings

Page 38 of the Liebert 100-1000A user manual — Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakers
Page 38 · click to enlarge
Page 38

Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakers

Liebert 100-1000A — Figure 17 Electrical field connections drawing: 400 – 600 amp Liebert STS2 with dual output breakers diagram (page 38)
Fig. 10 · Figure 17 Electrical field connections drawing: 400…

Installation Drawings

Page 39 of the Liebert 100-1000A user manual — Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breaker
Page 39 · click to enlarge
Page 39

Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breaker

Liebert 100-1000A — Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breaker diagram (page 39)
Fig. 11 · Figure 18 Electrical field connections drawing: 800…

CONDUIT SIZE, AND REPLACE. REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL
7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS 428 INCH-LBS. (48 N-m).
3. CONTROL WIRING AND POWER WIRING MUST BE RUN

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES. IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT 6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,

Installation Drawings

Page 40 of the Liebert 100-1000A user manual — Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakers
Page 40 · click to enlarge
Page 40
Figure 19 Electrical field connections800 – 1000 amp Liebert STS2 with dual output breakers
Liebert 100-1000A — Figure 19 Electrical field connections: 800 – 1000 amp Liebert STS2 with dual output breakers diagram (page 40)
Fig. 12 · Figure 19 Electrical field connections: 800 – 1000 a…

Installation Drawings

Page 41 of the Liebert 100-1000A user manual — 100K 65K 25K
Page 41 · click to enlarge
Page 41

Figure 20 Liebert STS2 non-automatic circuit breaker schedule

Ampere Rating, A Vendor Type Ampacity, A Voltage

100 ABB T4L 250 200-240V 380-480V 600V

125K 100K 50K

250 ABB T4L 250 200-240V 380-480V 600V

125K 100K 50K

400 ABB T5L 400 200-240V 380-480V 600V

150K 100K 25K

600 ABB T5L 600 200-240V 380-480V 600V

150K 100K 25K

800 ABB T6H 800 200-240V 380-480V 600V

125K 65K 25K

1000 Square D PJ 1200 200-240V 380-480V 600V

100K 65K 25K

1. The Liebert STS2 non-automatic breakers are 3-pole, 600VAC rated with magnetic trip only. 2. Upstream devices (by others) must be used to provide overcurrent protection. Upstream overcurrent protection should have ampacity equal to or less than the ampere rating of the static switch.
Show 4 more labels / short text on this page
Installation Drawings · Liebert STS2 · Withstand · Current
Page 42 of the Liebert 100-1000A user manual — FRONT VIEW WITH FRONT D OOR R EMOVED CONTROL WIRING
Page 42 · click to enlarge
Page 42

Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2

Liebert 100-1000A — Figure 21 Control connection location diagram: 100 – 600 amp Liebert STS2 diagram (page 42)
Fig. 13 · Figure 21 Control connection location diagram: 100 –…
2. MAXIMUM OF TWO (2) PROGRAMMABLE RELAY BOARDS CAN BE USED.

FRONT VIEW WITH FRONT D OOR R EMOVED CONTROL WIRING

Installation Drawings

Page 43 of the Liebert 100-1000A user manual — Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2
Page 43 · click to enlarge
Page 43

Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2

Liebert 100-1000A — Figure 22 Control connection location diagram: 800 – 1000 amp Liebert STS2 diagram (page 43)
Fig. 14 · Figure 22 Control connection location diagram: 800 –…

RELAY BOARDS CAN BE USED. 2. MAXIMUM OF TWO (2) PROGRAMMABLE

FRONT VIEW WITH FRONT D OOR R EMOVE D CONTROL WIRING

Installation Drawings

Page 44 of the Liebert 100-1000A user manual — PS213007 Rev. 02
Page 44 · click to enlarge
Page 44

Figure 23 Control wiring for remote source selection option

See Note 1

S2 S1 GND GND

1 2 3 4 6 5

TB50

Remote Source Selection

NOTES 1. Customer-provided normally open dry contacts. Rating 10mA at 30VDC. 2. Maximum cable length 500 ft. (152m) with #16 AWG, 300V minimum flexible stranded cable. 3. All control wiring (by others) must be run separate from power wiring . Control wiring runs should not be combined in the same conduit. 4. Refer to Static Transfer Switch control diagram for location of remote source selection opt. 5. All wiring must be in accordance with national and local electrical codes.

PS213007 Rev. 02

Installation Drawings · Source 1 Preferred · Source 2 Preferred

Page 45 of the Liebert 100-1000A user manual — A
Page 45 · click to enlarge
Page 45

Figure 24 Control wiring for the programmable relay board option

(C=COMMON, NC=NORMALLY CLOSED, NO=NORMALLY OPENED)

DIAGRAM FOR LOCATION OF PROGRAM RELAY BOARD OPTION. 5. REFER TO STATIC TRANSFER SWITCH CONTROL CONNECTION

TERMINAL BLOCKS 1 THROUGH 15. 1. CUSTOMER CONTROL WIRING CONNECTION POINTS ARE

SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS 4. ALL CONTROL WIRING (BY OTHERS) MUST BE RUN

SIGNAL CHANNELS WITH (2) FORM-C DRY CONTACTS PER 2. PROGRAMMABLE RELAY BOARD OPTION INCLUDES 8

3. REFER TO INSTALLATION, OPERATION & MAINTENANCE

MANUAL FOR CONFIGURING THE PROGRAMMABLE RELAY

8. ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL
6. CONTACT RATINGS: 1AMP @ 30VDC, 200mA @125VAC.

#16AWG FLEXIBLE STRANDED CABLE. 7. MAXIMUM CABLE LENGTH 500 FT. (152 METERS) WITH

SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

PS213001

Rev. 2

AND LOCAL ELECTRICAL CODES.

CHANNEL. SEE TABLE.

BOARD OPTION.

NOTES:

J71

J72

J73 J74

NO

2 1 3 4 5 7 6 8 9 10 1112 13 14 15 16

2 1 3 4 5 7 6 8 9 10 1112 13 14 15 16

2 1 3 4 5 7 6 8 9 10 1112 13 14 15 16

PROGRAMMABLE RELAY BOARD

NC

2 5 8 11

11 14 2 5

B 1

13 13 - 15 A

PIN NO. CHANNEL

10. 12
13. 15 10 - 12 7 - 9 4 - 6 1 - 3 13 - 15 10 - 12 7 - 9 4 - 6 1 - 3

TABLE

4. 6 7 - 9

A

A

B

B

A

B

A

B

A

B

A J73

B

J74 A

B

CH1

CH2

CH3

CH4

CH5

CH6

CH7

CH8

J71

J72

Installation Drawings

Page 46 of the Liebert 100-1000A user manual — Figure 25 Control wiring for the input contact isolator board option
Page 46 · click to enlarge
Page 46

Figure 25 Control wiring for the input contact isolator board option

Liebert 100-1000A — Figure 25 Control wiring for the input contact isolator board option diagram (page 46)
Fig. 15 · Figure 25 Control wiring for the input contact isola…

2 1 5 3 4 6 7 14 11 9 8 10 1213 1516

NOTES: 1. Customer control wiring connection points are Terminals 1 through 16 (see Table J51). 2. Customer-provided, normally open, dry contacts for user alarm messages. 3. Refer to installation, operation and maintenance manual for configuring the Input Contact Isolator board option. 4. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit. 5. Refer to static transfer switch control connection diagram (Figure 21 or 22) for location of Input Contact Isolator board option. 6. Signal voltage: 100mA @ 12VDC. 7. Maximum cable length 500 ft. (152 m) with #16 AWG flexible, stranded cable. 8. All wiring must be in accordance with national and local electrical codes. 9. When the Transfer Inhibit option is supplied, connect a N.O. dry contact (customer-supplied) to Input Contact 8 (Pins 15 and 16). When the customer contact closes, transfers will be inhibited as long as the contact remains closed. Input Contact 8 is factory-set so no setup is required. The Transfer Inhibit option prevents Input Contact 8 from being used for any other input.

Liebert 100-1000A — Figure 25 Control wiring for the input contact isolator board option diagram (page 46)
Fig. 16 · Figure 25 Control wiring for the input contact isola…

Installation Drawings · Table J51

Page 47 of the Liebert 100-1000A user manual — DETAIL A
Page 47 · click to enlarge
Page 47

Figure 26 Control wiring for comms board

EXTERNAL MODEM

SEE DETAIL A

J81

J1A

TB55 TB56 TB51

LIEBERT SITESCAN SEE DETAIL B

“NO CUSTOMER

“NO CUSTOMER

CONNECTION”

CONNECTION”

COMMS BOARD

02-810015-XX

CUSTOMER-SUPPLIED INTERCONNECTING CABLE

CUSTOMER-SUPPLIED INTERCONNECTING CABLE

TO EXTERNAL MODEM

TO LIEBERT SITESCAN

SEE NOTE 2

SEE NOTES 1 & 2

DCD

GND

DSR

DTR

RTS

CTS

RX

TX

RI

9 1 2 3 4 5 6 7 8

J81

TB 55

PS213003 Rev. 02

DETAIL A

DETAIL B

NOTES 1. Maximum cable length 1000 feet (300 meters) with twisted pair cable #22 AWG 300V minimum. 2. Signal voltage 5VDC, current 10mA. 3. Refer to installation, operation and maintenance manual for configuring the COMMS board. 4. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit. 5. Refer to control connection location diagram (Figure 21 or 22) for location of COMMS board. 6. All wiring must be in accordance with national and local electrical codes.

Installation Drawings

Page 48 of the Liebert 100-1000A user manual — TB3 TB2 TB1
Page 48 · click to enlarge
Page 48

Figure 27 Control wiring for the Liebert IntelliSlot SNMP/Web/Modbus 485 card

2. Maximum cable length 1000 feet (300 meters) with twisted pair cable #22 AWG minimum. Signal
3. Refer to the Liebert Intellislot Web/485 Card’s installation, operation & maintenance manual for
4. All control wiring (by others) must be run separate from power wiring. Control wiring runs
1. Wire size and type: 10/100 base-T ethernet cable with RJ-45 plug connector. The length is
6. All wiring must be in accordance with national and local electrical codes.

should not be combined in the same conduit.

5. Refer to control connection location diagram of static transfer switch for location of Liebert

See Notes 1 and 2 Customer-Supplied

Intellislot Web/485 card option.

limited by internet standards.

voltage 5VDC, current 10mA.

PS213008

configuration details.

Rev. 02

TB3 TB2 TB1

TB3

DB-9 J3

for setup only. Uses standard

computer serial port cable

Show 14 more labels / short text on this page
Installation Drawings · Interconnection Cable · Ethernet Network · RF-45 Connector · No customer · connection · interconnection cable · Customer-supplied · See Note 2 · to Modbus · + - · RS-232 (DB-9 connector) · No customer · connection
Page 49 of the Liebert 100-1000A user manual — TXD RXD GND
Page 49 · click to enlarge
Page 49

Figure 28 Control wiring for the RS-232 port

LCD DISPLAY

6 7 8 9

1 2 3 4 5

TXD RXD GND

Front View Upper Half of Unit

PS213006 Rev. 01

Show 5 more labels / short text on this page
Installation Drawings · See Detail A · DB9 Connector · Detail A · With Door Open
Page 50 of the Liebert 100-1000A user manual — Figure 29 Outline drawing for input junction box
Page 50 · click to enlarge
Page 50

Figure 29 Outline drawing for input junction box

Liebert 100-1000A — Figure 29 Outline drawing for input junction box diagram (page 50)
Fig. 17 · Figure 29 Outline drawing for input junction box
Liebert 100-1000A — Figure 29 Outline drawing for input junction box diagram (page 50)
Fig. 18 · Figure 29 Outline drawing for input junction box

Wire Size Range A B C D E F G H

100A 16 (406) 14 (356) 6 (152) 17-1/2 (445) 12 (305) 16-3/4 (426) 5/16 (8) 1 (25) #6 AWG to #2/0 AWG

250A - 600A 16 (406) 30 (762) 6 (152) 33 (830) 10 (254) 32 (813) 7/16 (11) 3 (76) (2) #6 AWG to (2)

Installation Drawings

Page 51 of the Liebert 100-1000A user manual — Figure 30 Color LCD touch screen display
Page 51 · click to enlarge
Page 51

Figure 30 Color LCD touch screen display

Liebert 100-1000A — Figure 30 Color LCD touch screen display diagram (page 51)
Fig. 19 · Figure 30 Color LCD touch screen display

LOGS CONFIG SOURCE XFERS STARTUP PROC. BYP. PROC. HELP LOGO

Installation Drawings

Page 52 of the Liebert 100-1000A user manual — LED DISPLAY LEGEND
Page 52 · click to enlarge
Page 52

Figure 31 LED display

Liebert 100-1000A — Figure 31 LED display diagram (page 52)
Fig. 20 · Figure 31 LED display

LED DISPLAY LEGEND

Liebert 100-1000A — LED DISPLAY LEGEND diagram (page 52)
Fig. 21

H Green Push Button to Select Source 1 as the Preferred Source

I Green Push Button to Select Source 2 as the Preferred Source

L Symbol to Indicate the K and M Must Be pushed at the Same Time to Reset Alarm

Installation Drawings

Page 53 of the Liebert 100-1000A user manual — TABLE
Page 53 · click to enlarge
Page 53

Figure 32 Installation drawing, seismic floor stand 100-250A

PS215000 REV. NO. 0

P/N OF FLOOR STANDHEIGHT HEIGHT MAX: HEIGHT MIN:

SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. RETIGHTEN LEVELER FEET NUTS.

2. INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS215001). USE M12-1.75X40mm CAP SCREW,

OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS215001). USE M12-1.75X40mm CAP

523401G1 18.0" 19.25" 16.75" 523402G1 24.0" 25.25" 22.75" 523403G1 30.0" 31.25" 28.75"

523404G1 36.0" 37.25" 34.75"

(FIG 1 AND FIG 2, PS215001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE

6. INSTALL THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS215002). ATTACH BRACKET TO STS2 USING M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 31 FT-LBS.

JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS215000). FLOOR STAND MUST BE LEVEL AND ALL FEET

3. LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS215001). INSTALL REAR UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT

TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS AND

5. ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) FIT INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH

HARDWARE TORQUE CHART

MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD TRUBOLTS

ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND

1.0" NUT 320 FT - LBS

M8 - 1.25 16FT - LBS

M10 - 1.5 31 FT - LBS

M12 - 1.75 53 FT -LBS

4. FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS215000).

HEIGHT TABLE

1. CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.

SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS.

EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.

FLOOR STAND BRACKET (FIG. 2, DWG PS215002).

FLAT WASHER AND TORQUE TO 53 FT-LBS

ISOMETRIC VIEW 250A FLOOR STAND

INSTALLATION NOTES:

B

JAM NUT

NUT

NUT

INSTALLATION DRAWING FOR

SEISMIC FLOOR STAND

100-250A STS2

FOOT DETAIL A

FOOT DETAIL B

MOUNTING PLATE AS SHOWN 29.44" TYP.

ALIGN FOOT PARALLEL TO

MOUNTING PLATE

17.48" TYP. 2.47" TYP .625" DIA x 2

BOTTOM VIEW

TOP VIEW

FRONT VIEW

29.9"

A

6" TYP.

36.9"

SEE HEIGHT

2.47" TYP.

TABLE

TYP.

Installation Drawings

Page 54 of the Liebert 100-1000A user manual — Figure 33 Installation drawing, seismic floor stand 100-250A
Page 54 · click to enlarge
Page 54

Figure 33 Installation drawing, seismic floor stand 100-250A

Liebert 100-1000A — Figure 33 Installation drawing, seismic floor stand 100-250A diagram (page 54)
Fig. 22 · Figure 33 Installation drawing, seismic floor stand…

Installation Drawings

Page 55 of the Liebert 100-1000A user manual — Figure 34 Installation drawing, seismic floor stand 100-250A
Page 55 · click to enlarge
Page 55

Figure 34 Installation drawing, seismic floor stand 100-250A

Liebert 100-1000A — Figure 34 Installation drawing, seismic floor stand 100-250A diagram (page 55)
Fig. 23 · Figure 34 Installation drawing, seismic floor stand…

Installation Drawings

Page 56 of the Liebert 100-1000A user manual — Figure 35 Installation drawing, seismic floor stand 100-250A
Page 56 · click to enlarge
Page 56

Figure 35 Installation drawing, seismic floor stand 100-250A

Liebert 100-1000A — Figure 35 Installation drawing, seismic floor stand 100-250A diagram (page 56)
Fig. 24 · Figure 35 Installation drawing, seismic floor stand…

Installation Drawings

Page 57 of the Liebert 100-1000A user manual — FRONT SIDE
Page 57 · click to enlarge
Page 57

Figure 36 Installation drawing, seismic floor stand 400-600A

P/N OF FLOOR STANDHEIGHT HEIGHT MAX: HEIGHT MIN:

523405G1 18.0" 19.25" 16.75"

523406G1 24.0" 25.25" 22.75" 523407G1 30.0" 31.25" 28.75" 523408G1 36.0" 37.25" 374.75"

PS216000 Rev.0

2. INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS216001). USE M12-1.75X40mm CAP SCREW,

OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS216001). USE M12-1.75X40mm CAP

SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. RETIGHTEN LEVELER FEET NUTS.

(FIG 1 AND FIG 2, PS216001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE

6. INSTALL THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS216002). ATTACH BRACKET TO STS2 USING M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 31 FT-LBS.

HARDWARE TORQUE CHART

JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS216000). FLOOR STAND MUST BE LEVEL AND ALL FEET

1.0" NUT 320 FT - LBS

M8 - 1.25 16FT - LBS

M10 - 1.5 31 FT - LBS

M12 - 1.75 53 FT -LBS

3. LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS216001). INSTALL REAR UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT

TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS AND

5. ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) FIT INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH

MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD TRUBOLTS

ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND

4. FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS216000).

HEIGHT TABLE

1. CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.

SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS.

EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.

FLOOR STAND BRACKET (FIG. 2, DWG PS216002).

FLAT WASHER AND TORQUE TO 53 FT-LBS

ISOMETRIC VIEW #1

INSTALLATION NOTES:

JAM NUT

B

NUT

NUT

FOOT DETAIL A

FOOT DETAIL B

MOUNTING PLATE AS SHOWN

ALIGN FOOT PARALLEL TO

MOUNTING PLATE

HEIGHT

TABLE

B

SEE

2.47" TYP

25.59" TYP. 2.47" TYP .625" DIA x 2

FRONT SIDE

BOTTOM VIEW

FRONT VIEW

TOP VIEW

A

29.44" TYP.

6" TYP.

36.9"

TYP.

Installation Drawings · 38"

Page 58 of the Liebert 100-1000A user manual — Figure 37 Installation drawing, seismic floor stand 400-600A
Page 58 · click to enlarge
Page 58

Figure 37 Installation drawing, seismic floor stand 400-600A

Liebert 100-1000A — Figure 37 Installation drawing, seismic floor stand 400-600A diagram (page 58)
Fig. 25 · Figure 37 Installation drawing, seismic floor stand…

Installation Drawings

Page 59 of the Liebert 100-1000A user manual — CAP SCREW M10-1.5X30MM SPLIT
Page 59 · click to enlarge
Page 59

Figure 38 Installation drawing, seismic floor stand 400-600A

SEE DWGS PS216000, PS216001, AND PS216003

PS216002 Rev. 0

REAR UPPER STS2 BRACKET

REAR LOWER STS2 BRACKET

UPPER REAR BRACKET TABS TO

LOCK WASHER M10 FLAT WASHER M10

FOR DETAILS.

CAP SCREW M10-1.5X30MM SPLIT

SLIDE INTO LOWER REAR

CAP SCREW M12-1.75X40MM

NOTE:

SPLIT LOCK WASHER M12

LOWER FRONT BRACKET

BRACKET SLOTS

FLAT WASHER M12

(2 PLACES)

(2 PLACES)

REAR RIGHT ISOMETRIC VIEW

FIG. 2

2 PLACES DETAIL A

FRONT LEFT ISOMETRIC VIEW

A

RIGHT SIDE VIEW

FIG. 1

FIG. 3

Installation Drawings

Page 60 of the Liebert 100-1000A user manual — Figure 39 Installation drawing, seismic floor stand 400-600A
Page 60 · click to enlarge
Page 60

Figure 39 Installation drawing, seismic floor stand 400-600A

Liebert 100-1000A — Figure 39 Installation drawing, seismic floor stand 400-600A diagram (page 60)
Fig. 26 · Figure 39 Installation drawing, seismic floor stand…

Installation Drawings

Page 61 of the Liebert 100-1000A user manual — SEE HEIGHT
Page 61 · click to enlarge
Page 61

Figure 40 Installation drawing, seismic floor stand 800-1000A

31 FT-LBS. ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER,

USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS.

AND ALL FEET MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD

5. ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) FIT INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH
3. LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS217001). INSTALL REAR UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT
6. INSTALL THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS217002). ATTACH BRACKET TO STS2 USING M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO

UNDERSIDE OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS217001).

TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS

PS217000 Rev. 0

4. FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS217000).

AND JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS217000). FLOOR STAND MUST BE LEVEL

(FIG 1 AND FIG 2, PS217001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON

2. INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS217001).

USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO

ISOMETRIC VIEW

1. CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.

TRUBOLTS EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.

B

FLOOR STAND BRACKET (FIG. 2, DWG PS217002).

AND FLAT WASHER AND TORQUE TO 53 FT-LBS

53 FT-LBS. RETIGHTEN LEVELER FEET NUTS.

P/N OF FLOOR STANDHEIGHT HEIGHT MAX: HEIGHT MIN:

523409G1 18.0" 19.25" 16.75" 523410G1 24.0" 25.25" 22.75" 523411G1 30.0" 31.25" 28.75"

523412G1 36.0" 37.25" 34.75" 6" TYP.

HARDWARE TORQUE CHART

INSTALLATION NOTES:

1.0" NUT 320 FT - LBS

M10 - 1.5 31 FT - LBS

M8 - 1.25 16FT - LBS

M12 - 1.75 53 FT -LBS

HEIGHT TABLE

RIGHT SIDE VIEW

FOOT DETAIL A

FOOT DETAIL B

NUT

NUT

JAM NUT

71.55" TYP. 2.47" TYP

TO MOUNTING PLATE AS

ALIGN FOOT PARALLEL

MOUNTING

BOTTOM VIEW

FRONT VIEW

PLATE

SHOWN

TOP VIEW

83.9"

A

36.9"

SEE HEIGHT

TABLE

2.47" TYP.

29.44" TYP.

Installation Drawings

Page 62 of the Liebert 100-1000A user manual — Figure 41 Installation drawing, seismic floor stand 800-1000A
Page 62 · click to enlarge
Page 62

Figure 41 Installation drawing, seismic floor stand 800-1000A

Liebert 100-1000A — Figure 41 Installation drawing, seismic floor stand 800-1000A diagram (page 62)
Fig. 27 · Figure 41 Installation drawing, seismic floor stand…

Installation Drawings

Page 63 of the Liebert 100-1000A user manual — Figure 42 Installation drawing, seismic floor stand 800-1000A
Page 63 · click to enlarge
Page 63

Figure 42 Installation drawing, seismic floor stand 800-1000A

Liebert 100-1000A — Figure 42 Installation drawing, seismic floor stand 800-1000A diagram (page 63)
Fig. 28 · Figure 42 Installation drawing, seismic floor stand…

Installation Drawings

Page 64 of the Liebert 100-1000A user manual — NOTE:
Page 64 · click to enlarge
Page 64

Figure 43 Installation drawing, seismic floor stand 800-1000A

SEE DWGS PS217000, PS217001, AND PS217002

PS217003 Rev. 0

FRONT VIEW RIGHT SIDE VIEW

FOR DETAILS.

32.1"

NOTE:

ISOMETRIC VIEW

RAISED FLOOR

77.0"

Installation Drawings · 32" 52" · 84"

Page 65 of the Liebert 100-1000A user manual — 8.1.1 Redundancy
Page 65 · click to enlarge
Page 65

Introduction to Liebert STS2 Operations

8.0 I NTRODUCTION TO L IEBERT STS2 O PERATIONS

8.1 System Description

A Liebert STS2 provides an automatic, seamless transfer between input power sources to an output load. The Liebert STS2 monitors the input sources, to ensure each source is operating within set parameters, as well as ensure that each source is within acceptable tolerances for a transfer between sources to be completed.

The Liebert STS2 contains two static transfer switches in one enclosure to allow the unit to transfer its load between the two input sources without an interruption of power to the load longer than 1/4 cycle.

If a problem is detected with a primary (Preferred) input source and defined trigger points are reached, the Liebert STS2 automatically switches the input to the other (Alternate) input source. The Liebert STS2 continues to monitor both sources and can automatically transfer the load back to the preferred source, if so configured, when that source returns to acceptable operating parameters.

The system control logic automatically monitors the input sources and power output to ensure that they are operating within acceptable tolerances. The system logic manages the transfer between sources.

The Liebert STS2 front panel contains either a Color Graphical Display on an LCD touch screen or an LED display.

The Color Graphical Display provides a menu-driven operator interface, and a display of system information, status information, a one-line diagram (Mimic) of the Liebert STS2, active alarms, and alarm history information.

The menu selections provide control of the preferred source, manual transfer initiation. Buttons provide for audible alarm silence and reset.

Through the touch screen, specific voltage, current and environmental parameters can be configured to trigger events that can sound an alarm, write to a history log and either transfer sources or inhibit a transfer.

In units not equipped with the touch screen, LEDs provide the user with the ability to monitor the Liebert STS2 and quickly assess problems.

Preferred input source selection, alarm reset and alarm silencing are done through buttons on the touch screen, or push buttons with the LED display.

Communication options can be installed in the Color Graphical Display (LCD) unit only. These options provide external communication with the Liebert STS2 through a modem, a network card, a programmable relay board, a contact isolator, or an RS-422 port to Liebert SiteScan.

8.1.1 Redundancy

Redundancy within the Liebert STS2 prevents one component from being a single point of failure, should a problem occur. Redundant circuits and components are used to eliminate single points of failure.

Since the Liebert STS2 has two input sources, no single component failure can cause a loss of power to the load. Redundant power supplies are provided which feed a DC dual-bus used throughout the unit to prevent any single-point power supply failure modes.

Three separate redundant control logic modules are built into the system. Each contains the logic necessary to run the Liebert STS2, and control all transfers.

Redundant fans are provided if a primary fan fails. The redundant fans turn on to prevent overheating inside of the unit.

Should the front panel interface fail, either touch screen or LEDs, the control logic continues to operate and the unit would transfer should a problem be detected on the preferred source. Information on the monitoring parameters would be available through the remote communication options, if available, or the DB9 (RS-232) connector located next to the LCD display behind the front door. See Figure 28 on page 41 for details.

Page 66 of the Liebert 100-1000A user manual — 8.2.3 Transfer Inhibit
Page 66 · click to enlarge
Page 66

Introduction to Liebert STS2 Operations

8.1.2 Reliability and Agency Requirements

The Liebert STS2 is designed for high reliability and high availability with a critical bus Mean Time Between Failure (MTBF) exceeding 1,000,000 hours.

The Liebert STS2, Control/Power Module and all its options are designed, tested and certified, where applicable, to meet agency requirements as follows:

  • UL 1008: Transfer Switch Equipment, for UL and ULc listing
  • UL1459: Telephone equipment (Modem)
  • NEC
  • FCC Part 15 EMI emission limits for Class A computing devices.

The Liebert STS2 uses conservatively rated components, minimizing the need to go to maintenance bypass. All maintenance and repair work can be done through the front panel of the unit. This access makes repairs and maintenance easier.

Gating and control logic are partitioned so that failure of one source’s gating or sensing logic does not prevent the switch from transferring to the other source.

All control and logic components are mounted separate from the power components. The Liebert STS2 is designed to minimize the exposure of hazardous voltages to allow safe servicing of the unit while the load is energized.

All electrical components requiring normal maintenance are replaceable without de-energizing the load, as long as one source is available. Solid-state switching devices are packaged to allow safe repair of those devices without having to de-energize the load. All non-automatic switches or circuit breakers are the plug-in or draw-out type to allow replacement without de-energizing the load. All solid-state power switching devices are rated to prevent hazardous device failure in power systems with available fault currents up to the defined limits, as listed in 15.1.5 - Electrical Requirements.

8.1.3 Factory Backup and Service Assistance

Because improper installation can cause a system to fail, a Liebert Services service technician should thoroughly inspect the unit to ensure it is properly installed and its operating parameters are properly configured.

Once the Liebert STS2 is properly installed, you, as the on-site operator, can easily monitor the unit’s operation utilizing the touch screen or LEDs.

If you need assistance, or have questions, contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

8.2 Modes of Operation

8.2.1 Normal (Preferred Source)

Under normal operating conditions, the Liebert STS2 routes power from the preferred input source to the output load. The unit monitors the voltage current and phase of each source to ensure that both are operating within set tolerances, and that the alternate source is available, should a transfer be required

8.2.2 Transfer

Should the preferred source fail or be outside acceptable voltage limits, the Liebert STS2 transfers the input to the alternate source until the problem is rectified in the preferred source. The unit can be set to automatically transfer the input back to the preferred source, or only allow the transfer to be done manually.

8.2.3 Transfer Inhibit

For a transfer to be completed between input sources, the sources must meet certain parameters, or the transfer cannot take place. Uninterrupted transfer between sources is inhibited due to input source failure, sources out of sync, switch failure, or the unit is in bypass mode.

Page 67 of the Liebert 100-1000A user manual — 8.3 Operator Controls
Page 67 · click to enlarge
Page 67

Introduction to Liebert STS2 Operations

8.2.4 Bypass

The static transfer switch can be manually bypassed to allow the power from a source to directly flow to the output load. This bypass allows the unit’s electronics to be serviced without dangerous voltages being present.

The Liebert STS2 includes key-interlocked maintenance bypass breakers that allow either input source’s electronics to be bypassed for maintenance without interruption of power to the load. The maintenance bypass allows all electronics to be isolated from the input, output, and bypass connections. Bypass instructions are available from the touch screen and are discussed later in this manual.

8.3 Operator Controls

The Liebert STS2 is equipped with an interface to configure and monitor the unit either locally or remotely. The Color Graphical Display is a touch screen LCD that provides a color diagram (Mimic) that displays the current status of the unit. System parameters are displayed and help is available to define events. See Figure 44 below and Figure 30. The touch screen menus allow the operator to initiate source transfers, view event and history logs, and view bypass and other operational instructions.

Figure 44 Liebert STS2 touch screen display

Liebert 100-1000A — 8.3 Operator Controls diagram (page 67)
Fig. 29 · 8.3 Operator Controls

Display Panel and Help Screen

Touch screen control buttons allow you to reset alarms, silence the audible alarm, review configurations, event and history logs, preferred source, startup and bypass procedures, and the help menu. Qualified personnel, with a password, can use these menus to configure parameters, select a preferred source and do manual source transfers.

LED display units do not have the color LCD touch screen. Instead of the touch screen, these units are monitored by a series of LEDs and controlled by a series of push buttons.

Both units can be accessed from a terminal, or a PC running terminal emulation software, that is attached to the unit. Through the RS-232 access, you can monitor and configure the unit, plus remotely select a preferred source. See 12.1 - Using the RS-232 Port on page 76 for instructions on using the RS-232 interface.

Show 4 more labels / short text on this page
Mimic · Event controls · Event Display · Menu Options
Page 68 of the Liebert 100-1000A user manual — Automatic Retransfer Inhibited
Page 68 · click to enlarge
Page 68

9.0 T HEORY OF O PERATION

9.1 General Description

The Liebert STS2 contains all the equipment necessary to prevent an interruption in power flow to the AC load, should your primary source fail.

9.1.1 Liebert STS2 Static Transfer Switch

The Liebert STS2 is a 3-pole, double-throw, solid state automatic transfer switch that is fed from two sources. The Preferred source is the input source that normally carries the load when both sources are available. The preferred source is selectable by the user from the LCD panel or an optional Remote Source Selection. The unselected source is referred to as the Alternate source and carries the load if the preferred source should fail or if a manual transfer is initiated.

The unit uses Silicon Controlled Rectifiers (SCRs) connected in parallel, opposing pairs to function as an AC switch configuration. Three pairs of SCRs connect the AC load to the selected preferred input source as long as the preferred source is available. A second set of SCRs stands ready to transfer the AC load to the alternate input source should the preferred source fail. The switching action is a very fast, break-before-make without an interruption of power to the load longer than 1/4 cycle.

During static switch transfers and retransfers, the conduction state of the SCRs is carefully monitored and controlled to prevent a current path from one source to the other. This technique prevents a faulted source from feeding into the other good source.

9.1.2 Source Transfer

The Liebert STS2 allows manually initiated transfers between the two sources. On units without the Optimized Transfer option the alternate source must be within acceptable voltage limits and phase tolerances with the preferred source. You begin a manual transfer by selecting the inactive source as the preferred source. On a manual transfer, the Liebert STS2 transfers between the two sources with less than one (1) millisecond interruption of power to the load. The transfer can only be completed when both sources are available and synchronized within the user-adjustable phase synchronization window. For sources where the two frequencies are not exactly in phase, manually initiated transfers are delayed by the Liebert STS2 until the two sources are within the defined phase synchronization window.

The Liebert STS2 with Optimized Transfer option allows manually initiated transfer at any phase difference, does not require synchronization, as long as the alternate source is within acceptable voltage limits with the preferred source. Transfer is not delayed if the two frequencies are not in phase.

Source selection can also be done remotely using the Remote Source Selection option, if installed.

9.1.3 Automatic Transfer/Retransfer

If the preferred source is out of voltage and/or frequency limits, the load is automatically transferred to the alternate source. The default transfer voltage limits comply with the limits of the IEEE Std. 446-1995 computer voltage tolerance envelope.

If the unit is so configured, the load is retransferred automatically to the preferred source after the preferred source returns to within the acceptable voltage and frequency limits for at least the defined retransfer time delay, and is in phase with the alternate source. You can enable and disable automatic retransfer to the preferred source through a user configuration setting.

Automatic Retransfer Inhibited

If the system makes five transfers from the preferred source to the alternate source in a five minute period, automatic retransfers back to the preferred source is disabled.

To clear this alarm condition, you must assign the alternate source as the preferred source.

Also, the UV detection thresholds may need adjustment. See Source Set Points on page 90 for instructions on setting the UV detection.

Theory of Operation

Page 69 of the Liebert 100-1000A user manual — 9.1.7 On/Off Sequence
Page 69 · click to enlarge
Page 69

This alarm also is cleared if the unit transfers to the preferred source due to an alternate source AC volt failure (i.e., an emergency transfer.)

9.1.4 Emergency Transfer

To ensure that power remains connected to the load, the Liebert STS2 automatically performs an emergency transfer from one input source to the other when an outage occurs on the existing source. The automatic transfer takes place if the other source’s voltage is within acceptable limits, and regardless of the phase difference between the two sources.

Emergency transfers occur without an interruption of power to the load longer than 4 ms.

Emergency transfers from the alternate source to the preferred source are not affected by the Auto Retransfer Enabled/Disabled or Retransfer Delay user settings.

9.1.5 Load Current Transfer Inhibit

The Liebert STS2 senses the load current. If the load current exceeds the preset level deemed to represent a load inrush or fault condition, the unit’s logic disables manual and automatic transfers, even if the selected source’s input voltage is outside the acceptable limits. This event triggers an I- Peak alarm. If so configured, the Load Current Transfer Inhibit is automatically reset 100 milliseconds after the current and voltage return to within normal parameters. This reset provides continued protection against a source failure. The Load Current Transfer Inhibit also can be programmed to require a manual reset. See step 14. on page 92 under the Source Set Points heading for details.

9.1.6 SCR Failure

The Liebert STS2 continuously monitors the status of the SCR switching devices for proper operation. In the event of a shorted SCR on the input source powering the load, the Liebert STS2 automatically triggers an alarm and trips open the other source isolation breaker. In the event of a shorted SCR on the other input source, the Liebert STS2 automatically triggers an alarm and trips open the other source isolation breaker.

In the event of an open SCR, the switch automatically triggers an alarm and transfers the load to the other source. All open and shorted SCR alarm conditions are latched and require the system to be repaired and reset to restore normal operation.

9.1.7 On/Off Sequence

The Liebert STS2 contains no master On/Off push button control. When connected to the input sources, the unit’s logic power comes on automatically. The touch screen display (if so equipped) is active as long as at least one input source is energized and the Control Power Disconnect (located inside the static switch) is on.

Theory of Operation

Page 70 of the Liebert 100-1000A user manual — Firmware
Page 70 · click to enlarge
Page 70

9.2 Detailed Component Description

9.2.1 Controls

Operator Interface

The Liebert STS2 Color Graphical Display unit contains a touch screen color LCD to provide the operator interface to control and configure the operation of the unit and quickly diagnose problems. A password and an optional keylock, if installed, are provided for security.

The LED Display unit includes push buttons for source transfer, alarm reset and audible alarm silence.

Hardware

  • The Liebert STS2 operator interface in the Color Graphical Display unit is designed to provide all of the information required to configure and monitor the unit’s operation.
  • The control logic performs automatic operations with minimal operator interface.
  • Each Liebert STS2 unit is equipped with either a color LCD touch screen or a panel of LEDs and push buttons.
  • The Liebert STS2 can have optional communication ports installed. See 6.0 - Options and 12.0 - Communication Interfaces on page 76 for more information on communication options.
  • On LED Display units, the RS-232 interface is used for configuration and status and event log monitoring. The RS-232 interface can also be used with the Color Graphical Display units, if necessary.

Firmware

The operator interface enables you to monitor the Liebert STS2, to configure set points for transfers, monitor system parameters and access event and history logs. The firmware is accessible through the LCD touch screen (if installed) or the RS-232 interface. The firmware includes:

  • View and set the preferred source.
  • View and configure setpoints.
  • View alarms, faults and status.

Additionally, the Color Graphical Display unit provides:

  • The mimic graphical representation of the systems operation.
  • Menu driven monitoring and configuration.
  • Step-by-step instructions to assist you in the startup, shutdown and bypass operations.
  • Help on event messages.
  • Touch screen alarm reset and silence buttons.

Events in the system, both faults and alarms, are detected and displayed on the LCD. See 11.0 - Alarm and Faults on page 71 for more information on events.

  • A set of event masks can be configured through the LCD to trigger a system response to an event. See 11.1 - Event Mask .
  • Report event conditions from other components of the system.
  • Monitor and report changes in event condition states. If the event condition’s state changes from inactive to active , a new event is detected. If the transition is from active to inactive , the event condition has cleared.
  • Process new faults and alarms, and clear inactive alarms.
  • Provide the alarm reset and silence options.

Theory of Operation

Page 71 of the Liebert 100-1000A user manual — 9.2.6 RS-232 Port
Page 71 · click to enlarge
Page 71

9.2.2 Circuit Breakers

Three circuit breakers provide total isolation of the solid-state switching devices with an input breaker for each source and a load isolation breaker. Two breakers provide for maintenance bypassing of the solid-state switching devices to either input source.

All switches in the Liebert STS2 are plug-in types, which allows any switch to be replaced without de- energizing the output bus. The breakers have an interlock in the plug-in base, which prevents the switch from being withdrawn in the CLOSED position. The switch trips OPEN before it disconnects from the plug-in base.

See 15.2.5 - Circuit Breakers for specifications and more information pertaining to the circuit breakers. See Figure 14 to Figure 19 for circuit breaker locations. The circuit breaker schedule is provided in Figure 20.

9.2.3 SCRs

Brick-type SCRs are used rated to carry the full 100% rated load. Because the unit is a fuseless design with non-automatic circuit breakers, overcurrent protection is provided by upstream circuit breakers.

9.2.4 Logic Modules

The logic contains three separate redundant logic modules. The modules contain the logic necessary to run the Liebert STS2 and control transfers and shunt trips under all circumstances, without any outside assistance once set-up and started properly.

9.2.5 Audible Alarm

An audible alarm is installed on the control board. This alarm is triggered by an alarm condition detected on the unit. The alarm can be turned off from the touch screen (Color Graphical Display units) or by a push button (LED Display units). Turning off the audible alarm does not clear or reset the condition that triggered the alarm.

9.2.6 RS-232 Port

An RS-232 serial port is provided to allow an external terminal to be connected as another user interface. See 12.1 - Using the RS-232 Port on page 76 for more information on using the RS-232 port.

Theory of Operation

Page 72 of the Liebert 100-1000A user manual — 10.0 Operating Instructions for the Touch Screen Interface
Page 72 · click to enlarge
Page 72

Operating Instructions for the Touch Screen Interface

10.0 OPERATING INSTRUCTIONS FOR THE TOUCH SCREEN INTERFACE

! CAUTION Before the unit is placed into service for the first time, after equipment relocation, or after the equipment has been de-energized for an extended period of time, a thorough equipment inspection and supervised startup by qualified personnel are strongly recommended. Contact your local Emerson Network Power representative or Liebert Services at 1-800-543-2378 to arrange for equipment inspection and startup.

After the initial equipment startup, the following operating guidelines can be used for standard equipment operation. These guidelines should be reviewed for any special equipment modifications, special site conditions, or company policies that may require changes to the standard equipment operation.

All programmable functions are preset at the factory to enable the unit to be brought up without the need to enter all selectable parameters.

This section refers to the LCD touch screen display. This display is discussed in more detail later in the manual. See 13.0 - Liebert STS2 Touch Screen Display.

See Figures 14 - 19 for circuit breaker locations.

Page 73 of the Liebert 100-1000A user manual — 10.1 Normal System Startup
Page 73 · click to enlarge
Page 73

Operating Instructions for the Touch Screen Interface

10.1 Normal System Startup

1. Ensure that all Liebert STS2 breakers—CB1, CB2, CB3, CB3A (if supplied), CB4, and CB5—are in the OFF position. a. Ensure that the key interlocks for CB1 and CB2 have their bolts retracted. b. Ensure that the key interlocks for CB4 and CB5 have their bolts extended, thus preventing CB4 or CB5 from being turned ON. 2. Source/input power should be applied to both Liebert STS2 inputs. The touch screen control panel should become active and operate properly when at least one of the inputs is energized is closed. 3. Verify that nominal input voltages are applied to both inputs (Source 1 and Source 2). The input voltages, selected preferred source, breaker and switch status, and alarms are indicated on the Mimic screen.

Figure 45 Liebert STS2 touch screen display

4. Close CB1. 5. Verify that Source 1 voltages are nominal and CB1 breaker status is correctly indicated on the Monitor/Mimic screen. 6. Close CB2. 7. Verify that Source 2 voltages are nominal and CB2 breaker status is correctly indicated on the Mimic screen. 8. Verify that boxes for the preferred source and corresponding static transfer switch are highlighted on the Mimic screen, indicating which side of the Liebert STS2 is on. 9. Close Output Breaker CB3 (and CB3A in redundant output configurations). 10. Verify CB3, the Output box, and the Load box are highlighted, indicating that CB3 is closed and the Output and Load are energized.

11. Press the RESET button on the touch screen to reset any previous alarms. 12. Verify in the Event Display and the Mimic that there are no active alarms. If any active alarms are displayed, refer to 11.0 - Alarm and Faults for a description of the alarms and possible causes. All active alarm conditions should be corrected before proceeding. 13. Turn on the load equipment following the load equipment manufacturer’s recommendations.
Show 5 more labels / short text on this page
Mimic · Sources · Static Transfer Switch · Event controls · Event display
Page 74 of the Liebert 100-1000A user manual — 10.2 Manual Transfer / Preferred Source Selection
Page 74 · click to enlarge
Page 74

Operating Instructions for the Touch Screen Interface

10.2 Manual Transfer / Preferred Source Selection

The Source Transfer option (Source Xfers) in the touch screen menu allows you to select a preferred source. Transfers are only permitted when the voltage and current are within their proper operating range and the sources are synchronized on units without Optimized Transfer. Units with the Optimized Transfer option do not require the sources to be synchronized to make a manual transfer. The Source Transfer screen indicates the synchronization between the two sources, while the voltage and frequency are displayed on the Mimic. See Figure 46. Transfer is inhibited if the deviation exceeds the parameter set in the Source Set Points. See User Settings on page 89

NOTE If one source will be de-energized for an extended period (hours or days), set the unit to bypass mode for the remaining source. Without using bypass, if a failure occurs in the switch components for remaining source, the Liebert STS2 does not have a second source to switch to and the load would not receive power. See Maintenance Bypass on page 67 for bypass instructions.

If your system contains the LED front panel instead of the LCD touch screen, refer to 14.2.2 - Manual Transfer / Preferred Source Selection for instructions on this procedure.

Figure 46 Source transfer screen

Liebert 100-1000A — 10.2 Manual Transfer / Preferred Source Selection diagram (page 74)
Fig. 30 · 10.2 Manual Transfer / Preferred Source Selection
Page 75 of the Liebert 100-1000A user manual — 10.4 Maintenance Bypass
Page 75 · click to enlarge
Page 75

Operating Instructions for the Touch Screen Interface

To manually select the preferred source:

1. Verify that the input breakers CB1 and CB2 are closed. 2. Select SOURCE XFERS from the menu bar. The Select Preferred Source screen is displayed in the Event Display. 3. Check the Mimic to verify that Source 1 and Source 2 input voltages are correct. 4. Select SOURCE 1 or SOURCE 2 as your preferred source. When conditions are correct, the switch transfers the load to the alternate source by selecting the alternate source as the preferred source. This source is now monitored as the preferred source throughout the various configurations set up through the touch screen. 5. Verify that the correct source is designated as the preferred source and that the input source changes to the desired source.

The Mimic is updated to indicate the new preferred source. The source is now highlighted with blue and that source is labeled as the preferred source.

If the Transfer Inhibit message is displayed, check for alarm messages on the Active Status window. Correct alarm conditions before attempting a source transfer.

10.3 Enabling Remote Source Selection

If your system is equipped with the optional Remote Source Selection option, it must be enabled.

If you your system includes the Color Graphical Display:

1. Select CONFIG from the menu bar. 2. Select SYSTEM SETTINGS from the Configuration menu. 3. Select SYSTEM OPTIONS from the System Settings menu. 4. Select YES for the REMOTE SOURCE SELECT choice.

If your system contains the LED display or you are configuring the system from the RS-232 port, see 12.1 - Using the RS-232 Port on page 76 for instructions on using the that interface.

10.4 Maintenance Bypass

The Liebert STS2 is equipped with two key-interlocked, bypass breakers, CB4 and CB5, to allow manual bypass of the switch electronics for either input source in the event of switch failure or for maintenance of the switch. Refer to the static transfer switch one-line diagram (Figure 3). While operating on maintenance bypass, all voltages are removed from the Liebert STS2 electronics to facilitate safe repair, without de-energizing the load using a make-before-break switching sequence.

However, the unit can be bypassed using a make-before-break switching sequence only to the same source to which that the switch is connected, as indicated by the highlighted static transfer switch box on the Mimic screen.

In the event of source or switch failure, the unit should be bypassed only to the current input source. For convenience, instructions for the bypass procedure can be displayed on the touch screen by selecting the BYP. PROC option from the menu bar.

The Mimic is used to verify the status of the unit during the bypass procedures. In the unlikely event that the Color Graphical Display is not available, open the front door and look through the slots in the control door. If you can see green LEDs on the gate driver board through that slot, then the unit is connected to the source referenced on the label below that slot. See Figure 47.

Page 76 of the Liebert 100-1000A user manual — Figure 47 Gate board viewing slot locations
Page 76 · click to enlarge
Page 76

Operating Instructions for the Touch Screen Interface

Figure 47 Gate board viewing slot locations

Liebert 100-1000A — Figure 47 Gate board viewing slot locations diagram (page 76)
Fig. 31 · Figure 47 Gate board viewing slot locations

Viewing Slot for the Source 1 Gate Drive Board

Viewing Slot for the Source 2 Gate Drive Board

GREEN LEDS ON THE GATE DRIVER BOARD ARE VIEWABLE THROUGH THIS SLOT INDICATE THAT THE STS IS ON SOURCE 1

GREEN LEDS ON THE GATE DRIVER BOARD ARE VIEWABLE THROUGH THIS SLOT INDICATE THAT THE STS IS ON SOURCE 1

GREEN LEDS ON THE GATE DRIVER BOARD ARE VIEWABLE THROUGH THIS SLOT INDICATE THAT THE STS IS ON SOURCE 2

If the Color Graphical Display is not available, you can still use the following bypass procedures, ignore the steps to check the display and check the LEDs.

If your system contains the LED display, see 14.2.3 - Maintenance Bypass.

Page 77 of the Liebert 100-1000A user manual — 10.4.1 Bypass Procedures for Source 1
Page 77 · click to enlarge
Page 77

Operating Instructions for the Touch Screen Interface

10.4.1 Bypass Procedures for Source 1 To bypass the switch for Source 1:

1. Verify that Source 1 is supplying power via the Mimic.
  • If the Color Graphical Display is not available, check the gate driver board LEDs through the slots in the control panel. See Figure 47 . 2. Remove the interlock key from CB5 and place it in the CB4 interlock. 3. Open the alternate source input breaker CB2. 4. Rotate and remove the CB2 interlock key. 5. Insert the key in the CB4 bypass breaker interlock. 6. Rotate the interlock keys in the CB4 bypass breaker interlock to retract the interlock. 7. Close bypass breaker CB4. 8. Verify the breaker status on the Mimic screen. 9. Open source input breaker CB1. 10. Rotate the CB1 interlock key and remove it to lock out the breaker. 11. Secure the key according to your site’s lockout/tagout procedure. 12. Open output breakers CB3 and CB3A (if supplied) to remove power and isolate the static switch from the load.

To return to normal mode:

1. Insert the key in the CB1 breaker interlock. 2. Rotate the key to retract the interlock. 3. Close source input breaker CB1. 4. Verify Source 1 and CB1 breaker status on the Mimic screen. 5. Select the SOURCE 1 button in the SOURCE XFERS menu. 6. Close output breakers CB3 and CB3A (if supplied). 7. Verify CB3 and CB3A breaker status. 8. Verify that STS SOURCE 1 and OUTPUT boxes are highlighted on the Mimic screen. 9. Open bypass breaker CB4. 10. Rotate the keys in the CB4 interlock to extend the interlock. 11. Remove the proper key from the CB4 interlock and insert it in the CB2 breaker interlock. 12. Rotate the key to retract the CB2 breaker interlock. 13. Close source input breaker CB2. 14. Verify the STS SOURCE 2 box and CB2 breaker status on the Mimic screen. • If the Color Graphical Display is not available, check the gate driver board LEDs through the slots in the control panel. See Figure 47.

Page 78 of the Liebert 100-1000A user manual — 10.5 Normal System Shutdown
Page 78 · click to enlarge
Page 78

Operating Instructions for the Touch Screen Interface

10.4.2 Bypass Procedures for Source 2 To bypass the switch for Source 2:

1. Verify that Source 2 is supplying power via the Mimic.
  • If the Color Graphical Display is not available, check the gate driver board LEDs through the slots in the control panel. See Figure 47 . 2. Remove the interlock key from CB4 and place it in the CB5 interlock. 3. Open the alternate source input breaker CB1. 4. Rotate and remove the CB1 interlock key. 5. Insert the key in the CB5 bypass breaker interlock. 6. Rotate the interlock keys in the CB5 bypass breaker interlock to retract the interlock. 7. Close bypass breaker CB5. 8. Verify the breaker status on the Mimic screen. 9. Open source input breaker CB2. 10. Rotate the CB2 interlock key and remove it to lock out the breaker. 11. Secure the key according to your site’s lockout/tagout procedure. 12. Open output breakers CB3 and CB3A (if supplied) to remove power and isolate the static switch from the load. To return to normal mode: 1. Insert the key in the CB2 breaker interlock. 2. Rotate the key to retract the interlock. 3. Close source input breaker CB2. 4. Verify Source 2 and CB2 breaker status on the Mimic screen. 5. Select the SOURCE 2 button in the SOURCE XFERS menu. 6. Close output breakers CB3 and CB3A (if supplied). 7. Verify CB3 and CB3A breaker status. 8. Verify that STS SOURCE 2 and OUTPUT boxes are highlighted on the Mimic screen. 9. Open bypass breaker CB5. 10. Rotate the keys in the CB5 interlock to extend the interlock. 11. Remove the proper key from the CB5 interlock and insert it in the CB1 breaker interlock. 12. Rotate the key to retract the CB1 breaker interlock. 13. Close source input breaker CB1. 14. Verify the STS SOURCE 1 box and CB1 breaker status on the Mimic screen.
  • If the Color Graphical Display is not available, check the gate driver board LEDs through the slots in the control panel. See Figure 47 .

10.5 Normal System Shutdown

The Liebert STS2 can be shut down from either the static switch mode or the bypass mode. 10.5.1 Shutdown in Static Transfer Switch Mode When the Liebert STS2 is operating on static transfer switch mode (not maintenance bypass mode): 1. Turn off the load equipment per manufacturer’s recommendations. 2. Open CB3 to turn off the static switch output.

  • Open CB3A if the static transfer switch has a redundant output configuration. 3. Open the input switches CB1 and CB2. 4. To completely de-energize the unit, turn OFF power to both inputs to the Liebert STS2. 10.5.2 Shutdown in Maintenance Bypass Mode When the Liebert STS2 is operating on bypass: 1. Turn off the load equipment per manufacturer’s recommendations. 2. Open the bypass switch (CB4 or CB5) to turn off the static transfer switch output. 3. To completely de-energize the unit, turn OFF the power to both inputs to the Liebert STS2.
Page 79 of the Liebert 100-1000A user manual — 11.1 Event Mask
Page 79 · click to enlarge
Page 79

11.0 A LARM AND F AULTS

Alarms and faults are events that are triggered when the operation of the Liebert STS2 falls outside the defined parameters. These events can also be triggered by: user actions, such as changing configurations, clearing logs, etc.; failed components such as a fan failure, an SCR that is open or closed, etc.; and system status, such as open circuit breakers, load on alternate source, etc. These events can provide a warning or trigger the system to make a change, such as switch sources or the recording of a history log.

The Liebert STS2 monitoring system detects and annunciates a comprehensive set of fault and alarm conditions. Faults and alarm messages are can be viewed on the LCD touch screen or via the RS-232 port.

On the LCD touch screen, the events are shown in the Status Display panel in the lower left corner of the touch screen and written to the Event log. You can touch a message to view a definition of an event and a tip for troubleshooting. See 13.0 - Liebert STS2 Touch Screen Display for more information on the touch screen.

If you are monitoring the system through the RS-232 port, see Table 9 - Terminal commands on page 77 for the commands to view event logs, and alarm and fault lists.

Event actions can be triggered by the settings configured from the Event Masks. See 11.1 - Event Mask for more information.

Faults — A fault indicates that a component of the Liebert STS2 has failed or has been damaged. In the Event Display, faults are indicated in red.

Alarms — An alarm is an event caused by a significant abnormal system condition. In the Event Display, alarms are indicated in yellow. The setpoints for many of the alarms are configurable through the User Settings. Many alarms clear themselves when the condition is resolved. If an alarm event mask is set to latch, the alarm messages remain active until the alarm condition has been corrected and the RESET button is pushed. See 11.1 - Event Mask for more information on latching.

When the system is furnished with an external modem and a telephone line is connected to the modem, the system can be programmed to automatically dial out upon occurrence of any of certain designated alarms. The auto-dial feature can be configured for alarms using the Event Mask option in the touch screen. See Configuring the Modem on page 94 for instructions on for setting up your modem.

11.1 Event Mask

The Liebert STS2 gathers, processes and reports faults and alarms, collectively referred to below as events. The Event Mask dialog box allows you to set the system’s response for specific alarms and faults that are generated. The following mask types are available for each event:

  • Latch — If a latch is enabled for the selected event, that event remains active even if the originating event condition clears. A latched event may only be cleared by pushing the RESET button (ALRMRST on the LED units).
  • Dial Out — If the selected event is triggered, the system automatically calls the specified telephone numbers through a modem. For example, a page could be sent or an event could be sent to a external terminal, via a modem. See Communication Interfaces on page 76 for more information on configuring communications options.
  • Event Log — The selected event is date/time stamped and recorded to the Event Log when the event is triggered.
  • Audible — If the selected event is triggered, an audible beeper or horn is sounded by the Liebert STS2. The beeper continues while this event is active or latched, or until the SILENCE button (NOAUD on the LED units) is pushed. This button must be pushed with the ALRMRST button on the LED units. See Event Masks on page 88 for instructions on setting the mask type via the touch screen display. See the 12.1.4 - Setting Event Masks with the Terminal on page 84 for instructions on configuration using the RS-232 port.

Alarm and Faults

Page 80 of the Liebert 100-1000A user manual — 11.2.2 History Log
Page 80 · click to enlarge
Page 80

11.2 Event and History Logs

The system tracks events through the Events Log and tracks significant events through the History Logs. These logs allow you to quickly spot trends or diagnose problems that the unit may have had. Both logs are written in nonvolatile memory.

The logs can be accessed from the touch screen menu or the RS-232 port. See 13.11 - Logs for more instructions on viewing the logs from the touch screen. See Table 9 - Terminal commands on page 77 for the RS-232 interface commands used to access the logs.

11.2.1 Event Log

The events are tracked in sequence of occurrence. The sequence of occurrence is identified by date, time, and frame number. The last 512 events are stored in a nonvolatile memory and can be viewed from the Event Log.

Event logs wrap, meaning when the log is full, the oldest event is deleted when a new event is written to the log.

The Event Log tracks:

  • # — the sequence number in which the event occurred since the log was last cleared.
  • Message — the event that occurred, such as Ambient Overtemp., Source 1 Fail, etc.
  • Type — either a Fault or Alarm. See 11.0 - Alarm and Faults on page 71 for further details on these events.
  • ID — the event identifier.
  • Date and Time — when the event occurred.
  • Faults — the number of fault events logged.
  • Alarms — the number of alarm events logged.
  • User Alarms — the number of alarm events logged that were triggered by user-created alarms, such as those alarms created with the Input Contact Isolator settings.
  • Total — the sum of all the events currently logged.

11.2.2 History Log

When a designated major alarm occurs, the History Status buffer is frozen, capturing 64 sequential frames before and after the alarm condition. When the History Status buffer is frozen, a History Log is created.

Two History Logs are available to track major alarms. This log includes the triggering event plus the surrounding events, and the system voltages, currents, frequency, power, source selection and breaker positions at the time of the event. The History Log displays the 64 sequential frames, in 4-millisecond intervals, of the Present Status screens surrounding the event.

If you are viewing the log from the touch screen, the Mimic and the Event Display show the data that was present as the alarm was triggered. The data is displayed as frames are played.

The History Log allows you to replay the events leading up to the alarm and the events right after the alarm to see the status of the switch at that time and diagnose the cause of the alarm. The History Log is triggered when certain events are tripped that have the Freeze option enabled.

You can run through the frames sequentially. The sequence of the events is identified by date, time, and frame number. The History Log frames are stored in a nonvolatile memory buffer that is continuously overwritten until a designated fault condition occurs. When the fault occurs to trigger a freeze, the History Log stores the next 23 frames, then freezes until it is reset. The History Log then keeps 40 frames before the fault, the frame where the fault occurred, plus the next 23 frames.

The History Log should not be reset until the fault condition that caused the buffer to freeze is reviewed and investigated by a qualified service technician. After the alarm condition has been corrected, the History Log can be cleared.

Alarm and Faults

Page 81 of the Liebert 100-1000A user manual — 11.4 List of Messages
Page 81 · click to enlarge
Page 81

The History Log has the following fields:

  • Replay Rate — indicates how long it takes for the replay to play. Use the UP and DOWN buttons to set the time.
  • Status — the status of the Liebert STS2 at the point of the current frame in the replay. The History log has three statuses: Frozen , Not Frozen and Retrieving Data, please stand by .
  • Critical Event — The event which triggered this log to be written. The event is indicated in red on the bar graph.
  • Frame Number — the current frame in the replay. A negative number indicates the replay is at a point before the triggering event occurred.

11.3 Alarm Notes

The I-PK on Source 1 and I-PK on Source 2 alarms inhibit automatic transfer due to an overload or load fault. These alarms can be set for either auto or manual alarm reset.

In the auto reset mode, the alarm is reset 100 milliseconds after the load current and source voltage return to normal, and transfers are no longer inhibited. In manual mode, the alarm remains active and transfers are inhibited until the conditions return to normal and the user manually presses the RESET button (ALRMRST button on LED units). In either case, the cause of the Source 1 or Source 2 I-Peak overload should be investigated and resolved (such as by reducing the overload condition or clearing the output fault) before returning the switch to normal operation.

SCR fault events indicate a device failure. The device must be replaced and the system must be restarted for the fault to clear. A shorted SCR automatically trips open a source input switch (CB1 or CB2) to prevent transfers in the event of an SCR failure. The SCR failure must be investigated and repaired before returning the switch to normal operation. Both source input switches must be opened (such as when the unit is placed in maintenance bypass for servicing) before a shorted or open SCR alarm can be reset.

11.4 List of Messages

Table 8 lists available event messages, a definition of the event, and the functions that are activated with the event by default. The functions are indicated as follows:

D — The indicated event initiates the Auto-Dial sequence through a modem. A — The indicated event activates the Audible alarm. F — The indicated event triggers a Freeze of the History Log. L — The indicated event Latches. A latched alarm remains displayed until the alarm condition has cleared and the RESET (ALRMRST) button has been pressed. E — By default, all faults and alarms are written to the Event Log. Changing this setting is only available for the LED units and is set through the RS-232 port. See Setting Event Masks with the Terminal on page 84

All of these functions, except Freeze, can be reconfigured to trigger for each event, using the Event Mask option. See 11.1 - Event Mask on page 71. The Freeze function is hard-coded and cannot be changed for an event.

If the front panel of your Liebert STS2 has LEDs and push buttons instead of the touch screen interface, you can view these messages via the RS-232 port. See 12.1.1 - Connecting and Using a Terminal on page 77 for the commands to view the event messages on a PC terminal.

An LED is used to indicate the presence of any active fault or alarm. Refer to 14.0 - Operating the Liebert STS2 LED Display for more information about the LEDs.

Alarm and Faults

Page 82 of the Liebert 100-1000A user manual — Table 8 Event messages
Page 82 · click to enlarge
Page 82

Table 8 Event messages

ID Alarm Message Description/Cause Action

001 S1 SCR SHORT One or more of the SCRs for Source 1 have shorted and failed. D, F, A, E

002 S2 SCR SHORT One or more of the SCRs for Source 2 have shorted and failed. D, F, A, E

003 S1 SCR OPEN One or more of the SCRs for Source 1 is open. D, F, A, E

004 S2 SCR OPEN One or more of the SCRs for Source 2 is open. D, F, A, E

005 PRIMARY FAN FAIL A primary cooling fan has failed and the unit is now being cooled by a secondary fan, which is not monitored. D, A, E

006 CONTROL MODULE FAIL Control logic module has failed. D, A, E

007 PWR SPLY DC A FAIL Power supply DC bus A has failed. D, A, E

008 PWR SPLY DC B FAIL Power supply DC bus B has failed. D, A, E

009 PWR SPLY S1 AC FAIL Power supply Source 1 AC has failed. D, A, E

010 PWR SPLY S2 AC FAIL Power supply Source 2 AC has failed. D, A, E

011 PWR SPLY LOGIC FAIL A power supply module has failed. D, A, E

012 OUT VOLT SENSE FAIL The output volt sense module failed D, A, E

013 S1 VOLT SENSE FAIL The Source 1 volt sense module failed. D, A, E

014 S2 VOLT SENSE FAIL The Source 2 volt sense module failed. D, A, E

015 S1 SCR SENSE FAIL The Source 1 SCR sense module failed. D, A, E

016 S2 SCR SENSE FAIL The Source 2 SCR sense module failed. D, A, E

017 S1 CURR SENSE FAIL The Source 1 SCR current module failed. D, A, E

018 S2 CURR SENSE FAIL The Source 2 SCR current module failed. D, A, E

019 S1 GATE DRIVE FAIL The Source 1 gate drive module failed. D, A, E

020 S2 GATE DRIVE FAIL The Source 2 gate drive module failed. D, A, E

021 INTERNAL COMM FAIL Internal CAN communications failed. D, A, E

022 EXTERNAL COMM FAIL Options CAN communications failed. A, E

023 CB1 SHUNT TRIP FAIL CB1 shunt trip failed. A, E

024 CB2 SHUNT TRIP FAIL CB2 shunt trip failed. D, A, E

064 HEATSINK OVERTEMP Heatsink has exceeded the recommended temperature. A, E

067 S1 UV Source 1 under voltage, fast detection. A, E

068 S1 UV (RMS) Source 1 under voltage, slow detection. L, A, E

069 S1 OV Source 1 over voltage A, E

070 S1 OF/UF Source 1 over frequency/under frequency A, E

071 S1 FAIL Source 1 failure. A, E

072 S2 UV Source 2 under voltage, fast detection. A, E

073 S2 UV (RMS) Source 2 under voltage, slow detection. A, E

074 S2 OV Source 2 over voltage. A, E

075 S2 OF/UF Source 2 over frequency/under frequency. A, E

076 S2 FAIL Source 2 failure. A, E

077 S1 OVERCURRENT Source 1 over current. A, E

078 S2 OVERCURRENT Source 2 over current. A, E

079 S1 I-PEAK I-PK on Source 1. A, F, E

080 S2 I-PEAK I-PK on Source 2. A, F, E

081 SOURCES OUT OF SYNC Source 1 and Source 2 are out of synchronization. A, E

082 LOAD ON ALT SOURCE The output load is running on the alternate source. A, E

083 AUTO REXFER INHIBIT Automatic retransfer is inhibited. A, E

084 CB1 (S1) OPEN Source 1, Circuit Breaker 1 is open. A, E

Alarm and Faults

Page 83 of the Liebert 100-1000A user manual — A, E
Page 83 · click to enlarge
Page 83

Table 8 Event messages (continued)

ID Alarm Message Description/Cause Action

085 CB2 (S2) OPEN Source 2, Circuit Breaker 2 is open. A, E

086 CB4 (S1 BYP) CLOSED Source 1 on bypass, Circuit Breaker 4 is closed. A, E

087 CB5 (S2 BYP) CLOSED Source 2 on bypass, Circuit Breaker 5 is closed. A, E

088 CB3 (OUTPUT) OPEN Output circuit breaker (CB3) is open. A, E

089 CB3A (OUTPUT) OPEN Output circuit breaker (CB3A) is open. A, E

090 S1 PHASE ROT ERROR Source 1 phase rotation error. A, E

091 S2 PHASE ROT ERROR Source 2 phase rotation error. A, E

092 TRANSFER INHIBITED Transfer inhibited. A, E

093 OUTPUT UV Output is under voltage. D, F, A, E

120 121 122 123 124 125 126 127

INPUT CONTACT #1 INPUT CONTACT #2 INPUT CONTACT #3 INPUT CONTACT #4 INPUT CONTACT #5 INPUT CONTACT #6 INPUT CONTACT #7 INPUT CONTACT #8

Input Contact # x is an optional alarm input. The alarm name can be programmed with an alarm name from the Input Contactor Isolator settings option under the Comm Options. See Configuring the Input Contact Isolator Settings on page 96. The alarm is sent to Monitor DSP. The LCD logs the alarm with the programmed name. Monitor DSP logs it with the generic name which is how it is reported to the SVT query.

A, E

128 CONFIG MODIFIED A set point configuration has changed. A, E

129 PASSWORD CHANGED The password for touch screen access has been modified and saved. A, E

130 TIME REPROGRAMMED The system’s time has been reset and saved. A, E

131 DATE REPROGRAMMED The system’s date has been reset and saved. A, E

132 EVENT LOG CLEARED The event log has been erased. A, E

133 HIST LOGS CLEARED Both History Logs have been erased. A, E

134 HIST LOGS FULL Both History Logs have been written and no more history logs can be written without clearing one of the logs. A, E

Alarm and Faults

Page 84 of the Liebert 100-1000A user manual — 12.1 Using the RS-232 Port
Page 84 · click to enlarge
Page 84

12.0 C OMMUNICATION I NTERFACES

The Liebert STS2 monitoring system offers several choices for communications.

The RS-232 terminal port is standard on all units. The port is located inside the front door, to the left of the touch screen/LED front panel mounting as shown in Figure 28. This port is primarily used as an alternate user interface to configure, control, and diagnose the system, especially for systems that do not include the HMI touch screen. Commands for the RS-232 port are shown in Table 9.

Several other communications options are also available. Those options are located a Communications compartment to the right of the touch screen/LED front panel and are accessible when the front panel door is open. See Figures 21 and 22 for the location of the communications options.

Connections to the communication ports are made by wiring to terminal boards located in the Communications compartment. The communications options listed below reference the control wiring drawing for each option.

  • Liebert IntelliSlot SNMP/Web/Modbus 485 card (optional) — the card provides connectivity to any TCP/IP-based Ethernet network to allow the device to communicate with network management systems (NMS) via SNMP/Web(HTTP). Events can be transmitted to the NMS to provide remote status monitoring, plus fault and alarm detection. The card includes an RJ-45 port for an Ethernet connection, via Category 5 cable. The Liebert SNMP/Web/Modbus 485 card can also integrate the system with an existing Building Management System (BMS) or out-of-band monitoring, using Modbus, a standard multi-drop protocol. The card has redundant communication paths that make it possible to connect to a BMS using Modbus while simultaneously communicating to an NMS through SNMP/Web(HTTP). See Figure 27 for more information on the Liebert SNMP/Web/Modbus 485 card. If you have questions about the card, refer to the user guide, SL-52615, available at the Liebert Web site, <a href="http://www.liebert.com" rel="nofollow noopener" target="_blank">www.liebert.com</a>
  • Input Contact Isolator (ICI) Board (optional) — provides an interface for up to eight user inputs. External messages and alarms can be routed to the unit, via the ICI. See Configuring the Input Contact Isolator Settings on page 96 for instructions on configuring the connections. See Figure 25 for wiring details.
  • Programmable Relay Board (PRB) (optional) — up to two PRBs can be installed in the Liebert STS2 to route Liebert STS2 events to external devices. See Configuring the Programmable Relay Board Settings on page 97 for default settings and instructions for reconfiguring the relays. See Figure 24 for wiring details.
  • Comms Board (optional) — includes a terminal block to provide a DTE connection to an external modem. This board also provides a direct connection to a Liebert SiteScan terminal, via an RS-422. Liebert SiteLink-12 or Liebert SiteLink-4 is required for Liebert SiteScan to communicate with the Liebert STS2. See Figure 26 for wiring details.

Data link requirements are Full Duplex Asynchronous RS-232 format.

Communications options are also discussed in 6.0 - Options.

12.1 Using the RS-232 Port

The RS-232 port is configured with a baud rate of 9600 with 8 data bits, 1 stop bit, no parity, and no hardware handshaking.

Communication Interfaces

Page 85 of the Liebert 100-1000A user manual — 12.1.1 Connecting and Using a Terminal
Page 85 · click to enlarge
Page 85

12.1.1 Connecting and Using a Terminal

An RS-232 connection can be used to connect the Liebert STS2 to either a terminal or a PC running terminal emulation software. If you are unsure of the cable pin out, see 15.2.10 - Terminal Port Connections.

1. Connect the terminal to the Liebert STS2 by plugging the cable from the terminal into the RS-232 port. This connection can be made at any time. 2. After making the connection, verify the communications link by pressing on the terminal keyboard. The interface communications system responds as indicated below:

Repeating command --> Illegal command! or displays the RS-232 command set or displays specific help for the command SVTP-Control >

The SVTP-Control > prompt indicates that RS-232 communications are established.

  • If you receive no response or prompt, verify that the connector is properly plugged into the port and the PC or terminal serial interface is working properly. 3. Enter the desired commands, as listed in Table 9 .

For additional help type or

Refer to the corresponding menu options in the 13.0 - Liebert STS2 Touch Screen Display for more details about the commands.

Some terminal commands require a password to function. Use the PWD command and a valid password to gain access.

Table 9 Terminal commands

? Displays this help menu or specific help with a command AA? Displays active alarms AF? Displays active faults CEL Clears the event log CHL Clears the history logs DATE? Displays current system date DATE Sets system date EL? Displays the entire event log HELP? Displays this help menu or specific help with a command HLn? Displays the history log #n, if frozen LOGOUT Logs user out of unprotected mode PS? Displays the preferred source PS n Sets the preferred source to #n PWD Allows users to access protected commands QUIT Modem only. Ends the session and hangs up the modem. SH Silences the horn SPT? Displays all current setpoints

SPTx Displays current setpoints for group x. See 12.1.2 - Configuring the Liebert STS2 via the Terminal for a description of groups. SR? Displays status reports TIME? Displays current system time TIME Sets system time UPMDR? Displays metering data VER? Displays firmware versions

Communication Interfaces · Keys Function

Page 86 of the Liebert 100-1000A user manual — Item Parameter
Page 86 · click to enlarge
Page 86

12.1.2 Configuring the Liebert STS2 via the Terminal

The SPT command is used to configure the systems setpoints. The SVT syntax for the setpoints consists for four parameters:

SPT [group] [item] [value] where the parameters are:

  • SPT — is the terminal command that is used to configure setpoints.
  • group — the group under the setpoint command which contains the desired settings.
  • item — the item number within the selected group.
  • value — the desired value for this item.

Only the specific options words listed in this section use a hexadecimal value. Other settings, depending on what they are, use other input types. For example, System ID uses a text string, nominal voltages and currents use standard numeric integers, and modem baud rate uses an enumeration where 0 = 2400, 1 = 9600, & 2 = 19200 bps.

This section provides instructions for setting these parameters, with an example of building an SPT command for System and User settings.

Groups Parameter

The setpoints are grouped for ease of configuration. For example, Event Masks are Group 4 and System Settings are Group 2. The numbers shown below are entered for the group parameter. For example, start of a System Settings command is SPT 2.

The group parameters are:

1 = System Ratings 2 = System Settings 3 = User Settings 4 = Event Mask Settings

For example, the start of a System Settings command is SPT 2, where SPT is the system setpoints command and 2 is the group parameter for System Settings.

See 12.1.4 - Setting Event Masks with the Terminal on page 84 for instructions on configuring Event Mask parameters.

Item Parameter

Each setting within the group is indexed by an item number as shown below in Table 11. These item numbers are also displayed on the terminal when you list the configuration setting for a particular group.

Continuing with the example, to configure an Options_1 setting under System Settings, the command would begin with SPT 2 6 where 6 is the value Options_1. Note the space between each parameter.

Communication Interfaces

Page 87 of the Liebert 100-1000A user manual — Value Parameter
Page 87 · click to enlarge
Page 87

Value Parameter

Item settings, depending on what they are, use various value types. Table 10 provides a list of the possible value types and their description.

Table 10 Value types

Numeric An integer numeric value in the units indicated by the item name. For example, a System Voltage Rating of 480 would indicate 480 volts.

Scaled Similar to the Numeric, this value type is an integer that has been scaled, usually to remove decimal points that would normally appear within the value. In this case, a value of 2.5 may actually be input as simply 25. For all Scaled types, the scaling appears in Table 11.

String Certain settings are represented by alphanumeric character strings, such as setting the System Model Number to Liebert STS2.

Enumeration This type uses an indexed list to represent possible choices. One example is the Modem Baud Rate which uses a value of 0 to select 2400 bps, 1 for 9600 bps, and 2 for 19200 bps.

Bit-packed This type of value uses a hexadecimal binary word, where each of the sixteen bits in the word has the value of 1 (True) or 0 (False). Although somewhat difficult to use, it packs a large amount of data within a single entry. A detailed description of this type appears in section 12.1.3 - Setting Bitpacked Options with the Terminal on page 81.

Event Masks This type is a specially formatted and is used to customize the behavior of each fault and alarm in the system. See 12.1.4 - Setting Event Masks with the Terminal on page 84 for instructions on configuring Event Mask parameters.

Table 11 shows the various groups, the settings contained within, and the type of value it requires.

Table 11 Group settings and values

Group ItemDescription Value Type Value Notes

1 Input Volts (PDU) Integer Set per system spec.

Group 1System Ratings

2 Volts Integer Set per system spec.

3 Current Integer Set per system spec.

4 Frequency Scaled Desired freq. x 10 (600 = 60 Hz)

1 Language Enumeration [Not supported at this time]

2 System Model Number String 14 Character max.

3 System ID Number String 8 Character max.

4 System Tag Number String 8 Character max.

5 System Order Number String 8 Character max.

6 Options_1 Bitpacked 14 Character max.

7 Autodial Primary Line String 20 Character max.

Group 2System Settings

8 Autodial Secondary Line String 20 Character max.

9 Autodial Pager Number String 20 Character max.

10 Autodial Pager PIN String 10 Character max.

11 Modem Init String String 20 Character max.

12 Modem Baud Rate Enumeration 0 = 2400, 1 = 9600, & 2 = 19200 bps

13 Modem LGS Check - Day Bitpacked

14 Modem LGS Check - Time Bitpacked

15 Comms Options 1 Bitpacked See section 12.1.3.

16 Comms Options 2 Bitpacked See section 12.1.3.

Communication Interfaces · Type Definition

Page 88 of the Liebert 100-1000A user manual — Value Parameter
Page 88 · click to enlarge
Page 88

Table 11 Group settings and values (continued)

Group ItemDescription Value Type Value Notes

1 SCR1 Fast Undervoltage Setpoint Integer In % of nominal below nominal

Group 3User Settings

2 SCR1 Slow Undervoltage Setpoint Integer In % of nominal below nominal

3 SCR1 Slow Undervoltage Detect Delay Integer In number of lines cycles

4 SCR1 Overvoltage Setpoint Integer In % of nominal above nominal

5 SCR1 Overvoltage Detect Delay Integer In 1/4 lines cycles

6 SCR1 I peak Transfer Setpoint Integer x 10

7 SCR2 Fast Undervoltage Setpoint Integer In % of nominal below nominal

8 SCR2 Slow Undervoltage Setpoint Integer In % of nominal below nominal

9 SCR2 Slow Undervoltage Detect Delay Integer In number of lines cycles

10 SCR2 Overvoltage Setpoint Integer In % of nominal above nominal

11 SCR2 Overvoltage Detect Delay Integer In 1/4 lines cycles

12 SCR2 I peak Transfer Setpoint Integer x 10

13 Max. Transfer Phase Angle Integer In degrees

14 Output Frequency Deviation Integer Freq. in Hz x 10

15 ReTransfer Delay Time Integer In seconds

16 Horn Volume Integer Range1-10

17 Critical Option Enabling Bitpacked See section 12.1.3.

18 Non-Critical Option Enabling Bitpacked See section 12.1.3.

1 to 63 Event Mask settings for faults Event Mask See section 12.1.4.

Group 4Event Mask Settings

64 to 143 Event Mask settings for alarms Event Mask See section 12.1.4.

Communication Interfaces

Page 89 of the Liebert 100-1000A user manual — 12.1.3 Setting Bitpacked Options with the Terminal
Page 89 · click to enlarge
Page 89

12.1.3 Setting Bitpacked Options with the Terminal

Five sets of options and features settings are available through the terminal to control the system operation.

Under System Settings for the SPT command, these items denote which options are INSTALLED:

  • 6 — Options_1
  • 14 — Comms Options 1
  • 15 — Comms Options 2

Under User Settings, for the SPT command, these items denote which features are ENABLED:

  • 17 — Critical Option Enabling
  • 18 — Non-Critical Option Enabling

The value parameter settings are in the form of a bit-packed word (in hexadecimal notation). In other words, each bit indicates a particular setting for the option or feature. The bit assignments for the options and features are as follows:

bit0 — HasDualOutputBreaker bit1 — HasPDU bit2 — Has4PoleTransferSwitch bit3 — HasShuntTrip bit4 — HasWyeOutputXfmr bit5 — HasExternalPrecisionTimeSource bit6 — HasSFA bit7 — HasRemoteSourceSelect bit8 through bit15 — not used (set to 0)

bit0 — HasIntModem bit1 — HasExtModem bit2 — HasNIC bit3 — not used (set to 0) bit4 — HasSiteScan bit5 — not used (set to 0) bit6 — not used (set to 0) bit7 — HasOpenCommsDigitalInputBrd bit8 — HasOpenCommsDigitalOutputBrd_1 bit9 — HasOpenCommsDigitalOutputBrd_2 bit10 — HasRemoteStatusPanelBrd_1 bit11 — not used (set to 0) bit12 — not used (set to 0) bit13 — not used (set to 0) bit14 — EnableDialIn bit15 — EnableDialOut

bit0 — EnablePager bit1 — EnableOCDINormallyClosed bit2-3 — OCDO1Assignment (0=User Defined, 1=Standard Set or 2=AS400) bit4-5 — OCDO2Assignment (0=User Defined, 1=Standard Set or 2=AS400) bit6 through bit15 — not used (set to 0)

Show 4 more labels / short text on this page
Communication Interfaces · Options_1 · Comms Options 1 · Comms Options 2
Page 90 of the Liebert 100-1000A user manual — 0000 0 A 1010
Page 90 · click to enlarge
Page 90

bit0—EnableManual_IPeakReset bit1—EnableAutoRestart bit2 through bit15 - not used (set to 0)

bit0 — EnableAutoReXfer bit1 through bit15 — not used (set to 0)

The bits are set in reverse order, from bit 15 on the left to bit 0 (zero) on the right. The bits are grouped in four sets of four bits each, as such:

0000 | | bit 15 bit 0

Since each bit represents a setting, a bit can be enabled or disabled:

  • 1 = installed option or enabled feature – or –
  • 0 = option not installed or feature not enabled

Enabling or disabling the bits in each group creates a binary value for that group. For example, if the fourth bit in a group is set to 1, the group group’s binary value is 0001.

Each group is translated into a hexadecimal equivalent. The group with the value of 0001 has a hex equivalent of 1.

You can use this table to help with the conversion:

Table 12 Binary-hexadecimal conversions

Hex Equivalent Binary value

0000 0 A 1010

0001 1 B 1011

0010 2 C 1100

0011 3 D 1101

0100 4 E 1110

0101 5 F 1111

The hex value for each group is entered in the command as four digits.

To summarize the procedure:

1. Set each bit position. 2. Convert the binary value each group into its hex equivalent. 3. Enter the hex values for each group, in order, into the command for the value parameter.

The following example explains how the conversion is completed.

Show 5 more labels / short text on this page
Communication Interfaces · Critical Option Enabling · Non-Critical Option Enabling · Hex Equivalent · Binary value
Page 91 of the Liebert 100-1000A user manual — SPT 2 6 0081
Page 91 · click to enlarge
Page 91

Putting the Terminal Command Together

For example, a unit only has the Remote Source Selection and Dual-Output Breaker options installed.

Checking the bits list under Options_1 on page 81, bits 7 and 0 each must be set to 1 to indicate that these options are installed.

The bit setting is as follows, starting with bit 15 on the left and going down to bit 0:

0000 0000 1000 0001

With the bits combined in groups of four, the binary settings can be translated into hexadecimal values.

The first two groups in the sample equal zero (0). In the third group, 1000 in binary translates to 8 in hex. In the fourth group, 0001 in binary translates to 1 in hex.

In hex this equates to (digits in the value parameter cannot have spaces between them):

So your command to indicate that the Remote Source Selection and the Dual-Output Breaker are installed would be:

SPT 2 6 0081

Communication Interfaces

Page 92 of the Liebert 100-1000A user manual — Examples of Event Mask Settings
Page 92 · click to enlarge
Page 92

12.1.4 Setting Event Masks with the Terminal

The event masks can be customized via a terminal. The command SPT4? displays all faults and alarms, along with their associated event masks. A plus sign (+) means that particular event mask is enabled, while a minus sign (-) means that mask is disabled.

Refer to 11.1 - Event Mask on page 71 for more information on event masks and their associated flags.

Unlike the System and User Settings, mask values are set by designated letters, not hex values. However, as with other RS-232 interface settings, four parameters are passed. See 12.1.2 - Configuring the Liebert STS2 via the Terminal on page 78 for more details about the parameters.

The syntax for configuring event masks is:

SPT 4 ID ±D±L±S±E±A

  • SPT — is the terminal command used to configure setpoints.
  • 4 — setting (group parameter) for event masks, under System Settings.
  • ID — event ID. The ID is the item parameter for this command. The ID numbers for each event are listed with the events in Table 8 on page 74.
  • D,L,S,E,A — the event masks: Dial , Latch , Summary , Event log , and Audible . The masks are the value parameter for the command. Each mask type must be preceded by a plus sign (+) to enable it, or a minus sign (-) to disable it.

Only the mask that is passed (enabled) is applied when the event occurs.

To set the event masks for a particular event:

1. Enter the command. Examples and descriptions are provided below. 2. Press ENTER.

After the new settings are entered, the new results for that event ID are displayed.

Examples of Event Mask Settings

  • To latch event #001, S1 SCR SHORT, use SPT 4 1 +L.
  • To disable event #128, CONFIG MODIFIED, from sounding the horn, use SPT 4 100 -A.
  • To enable event #012, OUT VOLT SENSE FAIL, to Dial and go into the Event Log, use SPT 4 12 +D+E.
  • To disable all masks for event #120, INPUT CONTACT #1, use SPT 4 120 -D-L-S-E-A.

To breakdown this syntax for the last example:

  • SPT — SVT command
  • 4 — group parameter, identifying System Setting group under which the Event Mask settings reside.
  • 120 — item parameter. In this command, that is the event ID.
  • -D-L-S-E-A — value parameter. In this case, the minus sign (-)disables all masks for the INPUT CONTACT #1 event.

Communication Interfaces

Page 93 of the Liebert 100-1000A user manual — 13.1 Display Overview
Page 93 · click to enlarge
Page 93

Liebert STS2 Touch Screen Display

13.0 L IEBERT STS2 T OUCH S CREEN D ISPLAY

The Liebert STS2 can be configured with a Color Graphical LCD touch screen that allows you to quickly check the status of the unit and identify problems.

A touch screen LCD is available through the front of the Liebert STS2. This screen provides a graphical (Mimic) display of the switch’s operation, plus system information including system parameters, alarms and faults.

The LCD provides a color, back-lit touch screen as a user interface. In addition to the Mimic and the system parameters, the screen provides a series of menus to allow you to configure the Liebert STS2, including the control of the preferred source, auto/manual retransfer selection, alarm notification, and other system setpoints. The touch screen also provides buttons to reset alarms and turn off audible alarms, such as a horn.

13.1 Display Overview

The Liebert STS2 Color Graphical Display provides three areas of information, plus buttons and a series of menu choices.

The Color Graphical Display contains the following features:

  • Mimic — a graphical diagram of the status of the unit.
  • Event controls — allow you to reset alarms and turn off audible alarms.
  • Event Display — displays any active alarm or fault condition, in real-time.
  • Menus — provide choices and configuration settings in dialog boxes or information in the display panel.
  • Display panel — provides additional information, depending on the menu choice that was last selected. This information includes event help text and startup and bypass procedures.

Figure 48 Liebert STS2 touch screen display

Show 5 more labels / short text on this page
Mimic · Event Controls · Display Panel · Event Display · Menu Options
Page 94 of the Liebert 100-1000A user manual — 13.2 Menu Overview
Page 94 · click to enlarge
Page 94

Liebert STS2 Touch Screen Display

13.2 Menu Overview

The touch screen menu provides access to configuration settings and more device information.

The CONFIG (Configuration) and LOGS menus provide multiple choices through pop-up menus. The SOURCE XFER menu selection allows you to select the preferred source. The other menu choices provide information in the display panel. The menu choices are discussed later in this manual.

All programmable functions are preset at the factory to default settings. These settings enable the unit to be brought up without the need to enter all selectable parameters. The menus allow the settings to be customized.

Click OK to save the data that you have entered.

Use the back arrow button (

Figure 50 Keyboard and keypad displays

Liebert 100-1000A — 13.2 Menu Overview diagram (page 94)
Fig. 32 · 13.2 Menu Overview
Liebert 100-1000A — 13.2 Menu Overview diagram (page 94)
Fig. 33 · 13.2 Menu Overview
Show 15 more labels / short text on this page
Figure 49 Menus · Config menu · Logs · System Rating · Event Log · Event Masks · History Log 1 · User Settings · History Log 2 · System Settings · Comm Options · System Options · System ID · Backspace · Backspace
Page 95 of the Liebert 100-1000A user manual — Using the Password
Page 95 · click to enlarge
Page 95

Liebert STS2 Touch Screen Display

13.2.1 Security

Because the Liebert STS2 Color Graphical Display provides access to various configuration and monitoring choices, a password or key lockout switch may be used to protect access to certain changes, including:

  • Change configuration settings.
  • Clear logs.
  • Make a source transfer.
  • Reset an alarm.

Without entering the password or enabling changes with the key lockout switch, you still can:

  • View the display, including the mimic, status and event help.
  • View logs.
  • View the startup and bypass procedures.
  • Use the SILENCE button to turn off the audible alarm.

Using the Optional Key Lockout Switch

An optional key lockout switch for the Liebert STS2 enables or disables the ability to make changes on the Liebert STS2. The key lockout switch is mounted on the front door. See Figures 8 through 10 for location of the key lockout switch.

  • To disable the changes, turn the key to the top of the switch, toward the closed padlock.
  • To enable changes turn the key to the horizontal position, toward the open padlock.

Figure 51 Key lockout switch.

Using the Password

If the unit is not equipped with a keylock, a password is required when you attempt to:

  • Save changes in the CONFIG menu choices.
  • Transfer sources.
  • Reset active alarms.
  • Clear logs.

When a password is requested, a keyboard is displayed on the touch screen. After you enter the password, select OK.

The password is case-sensitive. Password access times out after ten (10) minutes, and must be re-entered to save changes. The time-out period cannot be changed.

To set or reset the password:

1. Select SYSTEM SETTINGS from the CONFIG menu. 2. Select SYSTEM ID form the SYSTEM SETTINGS menu. 3. Click PASSWORD. A keyboard is displayed. 4. Enter a password. The password must be four (4) alpha-numeric characters and is case sensitive. 5. Click OK.

Changes disabled · Changes enabled

Page 96 of the Liebert 100-1000A user manual — 13.7.2 Event Masks
Page 96 · click to enlarge
Page 96

Liebert STS2 Touch Screen Display

13.3 Mimic Display

The Mimic display provides a color diagram of the operation of the Liebert STS2. This display imitates the power flow through the static transfer switch and indicates source status, breaker status, switch status, source voltage and current readings, output power measurements, and active alarm messages. See Figure 48 on page 85.

13.4 Event Controls

The Liebert STS2 detects events when certain thresholds are passed or certain problems occur. The alarm controls allow you to acknowledge the existence of these events.

  • RESET — All latched events whose conditions have cleared are removed from the Event Display. Faults and alarms that remain active, or are not recoverable, are not affected when this button is selected. This button is also used to perform manual I-Peak resets and manual retransfers.
  • SILENCE — turns off the audible alarm (horn or beeper) without resetting the triggering event. This setting does not permanently turn off the horn. The alarm sounds again when the next event with an audible alarm setting is triggered.

Active events are shown in the Event Display, whereas cleared events can be reviewed via the Event Log.

13.5 Event Display

The Event Display lists the condition of the Liebert STS2 in real-time. Both nominal system parameters and alarm messages are displayed in the Event Display. You can touch any message in the Event Display to display more information in the Display Panel to the left. The selected status is displayed in bold type.

13.6 Menu Bar

As previously mentioned, the menu bar provides both configuration choices and information. The choices under the Config and Log menus access additional dialog boxes, while the other menu choices only show information in the display panel.

13.7 Configuration Menu

When you select the CONFIG (Configuration) menu choice, a pop-up menu is displayed with four choices.

Liebert 100-1000A — 13.7 Configuration Menu diagram (page 96)
Fig. 34 · 13.7 Configuration Menu
  • System Ratings — used to configure frequency, voltage and currents settings for the Liebert STS2.
  • Event Mask — allows you to configure system’s response for events.
  • User Settings — allows you to configure operations for the Liebert STS2.
  • System Settings — accesses another pop-up menu to configure communication and system choices and the system ID.

Each of these choices accesses a separate dialog box.

13.7.1 System Ratings

The System Ratings menu is used to set the nominal line frequency, nominal voltage and nominal current at which the system operates when it is installed. These settings are configured when the system is initialized at the factory or under maintenance and should not be changed by the user.

13.7.2 Event Masks

The Liebert STS2 gathers, processes and reports faults and alarms, collectively referred to below as events. The Event Mask dialog box allows you to set the system’s response for specific alarms and faults that are generated. See 11.0 - Alarm and Faults for more information on events and 11.1 - Event Mask for the definitions of the Event Mask types.

Page 97 of the Liebert 100-1000A user manual — 13.7.3 User Settings
Page 97 · click to enlarge
Page 97

Liebert STS2 Touch Screen Display

To set the event masks:

1. Access the Event Mask dialog box: a. Select CONFIG. b. Select EVENT MASK from the pop-up menu. The Event Mask dialog box is displayed. See Figure 52 . 2. Select the mask settings for each fault and alarm. a. Select YES to enable the setting, – or – b. Select NO to disable the setting. 3. Select SAVE to keep the settings.

Figure 52 Event mask dialog box

Liebert 100-1000A — Figure 52 Event mask dialog box diagram (page 97)
Fig. 35 · Figure 52 Event mask dialog box

13.7.3 User Settings

The User Settings choice allows you to adjust the user-accessible switch settings. Access is limited to qualified personnel via system security.

To access the User Settings dialog box:

1. Select CONFIG. 2. Select USER SETTINGS from the pop-up menu.

The User Settings dialog box is displayed. See Figure 53. The top six buttons access a series of secondary dialog boxes to configure the various settings.

Page 98 of the Liebert 100-1000A user manual — Source Set Points
Page 98 · click to enlarge
Page 98

Liebert STS2 Touch Screen Display

Figure 53 User settings dialog box

Liebert 100-1000A — Figure 53 User settings dialog box diagram (page 98)
Fig. 36 · Figure 53 User settings dialog box

Source Set Points

The Source 1/2 Set Points allows you to configure trigger points for each input source (1 or 2) for the Liebert STS2 via a keypad dialog or HI/LO dialog box. The source numbers do not designate the source as the preferred or alternate source. The numbers simply identify the input source. See 10.2 - Manual Transfer / Preferred Source Selection to set the preferred source.

The Set Points are based on values in relation to the nominal voltage required for the Liebert STS2. UV refers to under voltage, meaning the amount of voltage below the nominal voltage. OV refers to over voltage, or the amount of voltage over the nominal voltage.

  • Fast UV Setting (%) — if the voltage drops below this set percentage of the nominal voltage, the Liebert STS2 transfers from the current source to the opposite source.
  • Slow UV Setting (%) — if the voltage remains this set percentage below the nominal voltage for the period of the slow detection delay, the Liebert STS2 transfers from the current source to the opposite source.
  • Slow UV detection delay — the number of cycles that the source must remain below the Slow UV Setting before the Liebert STS2 transfers.
  • OV Setting (%) — if the voltage exceeds this set percentage of the nominal voltage for the period of the OV detection delay, the Liebert STS2 transfers from the current source to the opposite source.
  • OV Detection Delay — the number of cycles that the source must remain above the OV Setting before the Liebert STS2 transfers sources.
  • I-PK Xfer Lockout — if current from the source exceeds this threshold, the Liebert STS2 disables source transfers, and has to be reset either manually or automatically. The type of reset is configured under the User Settings.
Page 99 of the Liebert 100-1000A user manual — Figure 54 Source setpoints
Page 99 · click to enlarge
Page 99

Liebert STS2 Touch Screen Display

To configure the setpoints for each source:

1. Select SOURCE 1/2 Set Points from the User Settings dialog box. The Source 1/2 Set Points dialog is displayed.

Figure 54 Source setpoints

Liebert 100-1000A — Figure 54 Source setpoints diagram (page 99)
Fig. 37 · Figure 54 Source setpoints
2. Select 1 to configure the settings for Source 1. 3. Configure the settings using the keypad or dialog box that is displayed when you touch a button.

Table 13 Sepoint parameters

Button Range Default Comments

Fast UV Setting (%) -10 to -30% of Nominal voltage rating -20% Set in increments of 1%.

Slow UV Setting (%) -5 to -20% -10% Set in increments of 1%.

Slow UV detection delay 1-60 cycles 5 cycles Units: Line Cycle

OV Setting (%) +5% to +20% +10% Set in increments of 1%.

OV Detection Delay 1-255 cycles 3 cycles Units: 1/4 Line Cycle

I-peak xfer lockout detection point. Units: Amps RMS. Select the HI or LO buttons to configure your setting.

I-PK Xfer Lockout 0 – 3.0 multiplied by the unit current rating.

1.5 * Unit Current Rating

4. Select 2 for Source 2. 5. Configure the settings, as described in Step 3. 6. Select SAVE to keep the settings for both sources. The Set Points dialog is closed and the User Settings dialog is displayed. 7. Select MANUAL MAX XFER PHASE ANGLE. A keypad is displayed. This setting configures the maximum allowed phase difference between the sources and applies to all manual transfers as well as any auto retransfer. a. Configure this setting with a range of ± 1-30 degrees. The default setting is ±15 degrees and the resolution is 1 deg. b. Select OK to save the setting. The setting is now displayed in the adjacent field in the User Settings dialog box.

Page 100 of the Liebert 100-1000A user manual — Figure 54 Source setpoints
Page 100 · click to enlarge
Page 100

Liebert STS2 Touch Screen Display

8. Select FREQUENCY TRIP POINT. A keypad is displayed. This choice verifies that the source is running at the proper frequency. This choice sets the frequency deviation in the frequency that triggers the frequency trip point alarm. The frequency deviation setting is the allowable frequency variation from nominal (60.0 or 50.0 Hz) before activating the frequency deviation alarm. The frequency setting applies to both input sources. a. Configure this setting with a range of 0.1 – 3.0 Hz The default setting is 3 and the resolution is 0.1. b. Select OK to save the setting. 9. Select RETRANSFER DELAY. A keypad is displayed. With the secondary source being used, this setting sets the length of time the switch waits until attempting to transfer back to the preferred source. a. Configure this setting with a range of 1 to 60 seconds. The default setting is three (3) seconds and the resolution is 1 second. b. Select OK to save the setting. The setting is now displayed in the adjacent field in the User Settings dialog box. 10. Select AUDIO LEVEL. A dialog box is displayed with HI and LO settings. This choice sets the loudness of the horn or beeper that is sounded for audible alarms. a. Configure this setting with a range of 1–10 (ten). The default setting is 5. The settings have an increment of 1 (one). b. Select OK to save the setting. The setting is now displayed in the adjacent field in the User Settings dialog box. You can select TEST to briefly sound the alarm to judge its volume. 11. Select DISPLAY BRIGHTNESS. A dialog box is displayed with HI and LO settings. This choice sets the brightness for the touch screen. a. Configure the Contrast and Brightness settings with a range of 1 – 10 (ten). b. Select OK to save the settings. 12. Set the AUTO REXFER ENABLE choice. The auto retransfer enable setting determines whether the switch automatically returns the preferred source after that source is restored.

  • Select YES to enable the automatic transfer.
  • Select NO to disable the automatic transfer. The setting requires transfers be done manually. 13. Set the AUTO RESTART ENABLE choice. This setting determines whether the Liebert STS2 can be started automatically when power is restored after it has been lost.
  • Select YES to enable the automatic restart.
  • Select NO to disable the automatic restart. This settings requires a manual restart of the Liebert STS2. 14. Select a setting for the I-PEAK RESET.
  • Select AUTO to configure the Liebert STS2 to automatically reset when a fault clears and the voltage and current are normal.
  • Select MAN to require a manual reset of the Liebert STS2 when fault clears and the voltage and current are normal.
  • The default setting is Manual. ! CAUTION Risk of equipment damage and personnel injury. Use of Auto Restart is site specific. Do not enable auto restart unless the infrastructure is designed for unattended operation and there is no chance of equipment or personnel harm by automatic re-energizing of the system. Consult with your Emerson site engineer as to whether Auto restart should be enabled.
Page 101 of the Liebert 100-1000A user manual — 13.8 Comm Options
Page 101 · click to enlarge
Page 101

Liebert STS2 Touch Screen Display

13.7.4 System Settings

The System Settings choice under the Config menu displays another pop-up menu with three choices:

  • Comm Options (see Section 13.8 )
  • System Options (see Section 13.9 )
  • System ID (see Section 13.10 )

To access the System Settings menu:

1. Select CONFIG from the menu bar. 2. Select SYSTEM SETTINGS from the Config menu.

13.8 Comm Options

The Comm Options dialog box allows you to configure the communications settings for the Liebert STS2.

  • Select COMM OPTIONS from the System Settings Menu. (If needed, see 13.7.4 - System Settings to access the System Settings menu.) The Comm Options dialog box is displayed. See Figure 55 .
  • An option can be enabled by selecting YES.
  • An option can be disabled by selecting NO.
  • An option can be configured by selecting the adjacent option button to display a separate configuration dialog box.

The instructions for configuring the communications options are provided in this section:

Option Refer to:

Modem 13.8.1 - Configuring the Modem

Pager 13.8.2 - Configuring Pager Support

Input Contact Isolator 13.8.3 - Configuring the Input Contact Isolator Settings

Prog. Relay Board 13.8.4 - Configuring the Programmable Relay Board Settings

Network Interface Card 13.8.5 - Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Card

Site Scan 13.8.6 - Liebert SiteScan® Configuration

Modem 13.8.4 - Configuring the Programmable Relay Board Settings

Figure 55 Comm options dialog box

Liebert 100-1000A — 13.8 Comm Options diagram (page 101)
Fig. 38 · 13.8 Comm Options

Option buttons

Page 102 of the Liebert 100-1000A user manual — 13.8.1 Configuring the Modem
Page 102 · click to enlarge
Page 102

Liebert STS2 Touch Screen Display

13.8.1 Configuring the Modem

The Modem dialog box allows you to configure the optional external modem that is connected to the Liebert STS2.

The dialog box contains a series of choices that access either a keypad or a secondary dialog to configure settings. Auto dial can also be configured for the modem to be triggered by events, as set up in the Event Mask choices.

Designated major alarms activate the auto dial modem sequence. Automatic dial attempts are made to the first number three times, at 30 seconds between attempts. If connection is not established in that time period, the system automatically rolls over to the second number. Auto dial attempts are made again three more times at 30 seconds between attempts. The process is repeated until a successful connection is made. Upon successful connection, the system transmits a present status data, including all active alarms messages. After transmission, the modem automatically hangs up and returns to the auto-answer mode.

To configure the modem:

1. Select MODEM from the Comm Options menu. The Modem dialog box is displayed.

Figure 56 Modem dialog box

Liebert 100-1000A — 13.8.1 Configuring the Modem diagram (page 102)
Fig. 39 · 13.8.1 Configuring the Modem
2. Select the type of modem that the Liebert STS2 will be using:
  • Select INT internal modem not available.
  • Select EXT if the Liebert STS2 will be communicating via an external modem. 3. Select the PRIMARY LINE choice to enter the primary telephone number for the modem to dial when an alarm is triggered. 4. Enter the number in the keypad dialog box. 5. Select OK to save the telephone number. The number is displayed in the field adjacent to the Primary Line choice. 6. Select the SECONDARY LINE choice to enter the secondary telephone number for the modem to dial when an alarm is triggered. 7. Enter the number in the keypad dialog box. 8. Select OK to save the telephone number. The number is displayed in the field adjacent to the Secondary Line choice.
Page 103 of the Liebert 100-1000A user manual — 13.8.2 Configuring Pager Support
Page 103 · click to enlarge
Page 103

Liebert STS2 Touch Screen Display

9. Select INIT. STRING to configure the initialization string. This string configures the parameters of the modem.
  • Check your modem’s documentation for this setting. 10. Select BAUD RATE to display a dialog with the baud rate choices:
  • For an external modem, select from 2400 bps, 9600 bps or 19200 bps. 11. Configure the MODEM HEALTH CHECK. The Health Check verifies that the modem is working properly. This setting allows you to enable the check and set when it is run. a. Select the button to display the Modem Health Check dialog box, from which you can access further dialogs to set the time and days that the check is run. b. Select SAVE to keep the settings. The Health Check dialog box is closed and the Modem dialog box is again active. c. Select YES in the Modem dialog box to activate the Modem Health Check. If you select NO, the Modem Health Check is not run. 12. Configure AUTO DIAL IN. Auto Dial In allows a user to dial into the Liebert STS2 through the modem to check status and access the system via a hyperterminal connection. a. Select YES to activate the dial in feature. b. Select NO to deactivate the dial in feature. 13. Configure AUTO DIAL OUT. Auto Dial Out allows the Liebert STS2 to automatically dial out to a system to notify a user of an event or status. a. Select YES to activate the dial out feature. b. Select NO to deactivate the dial out feature. 14. Select SAVE to keep the modem configuration settings. 15. Select YES in the Comm Options dialog box to activate the settings.

You are returned to the Comm Options dialog box.

13.8.2 Configuring Pager Support

Pager support will be implemented in an upcoming update of the system. This support will trigger the system to call a pager when specified events occur. This menu choice will allow you to enter the telephone number and PIN for the pager that you want the system to call.

Page 104 of the Liebert 100-1000A user manual — 13.8.3 Configuring the Input Contact Isolator Settings
Page 104 · click to enlarge
Page 104

Liebert STS2 Touch Screen Display

13.8.3 Configuring the Input Contact Isolator Settings

The Input Contact Isolator (ICI) is an optional, eight-channel input board for up to eight external user alarm or message inputs to be routed to the Liebert STS2’s alarm network. If the Transfer Inhibit option is supplied, the ICI will accommodate up to seven external user alarm or message inputs.

The contact is set to either be normally open or normally closed. When a contact closes or opens, an event is triggered. See 6.4 - Input Contact Isolator Board for more information on the ICI.

The Input Contact Isolator options are configured through the Input Contact Isolator dialog box, which is accessed from the Comm Options dialog box. The Input Contact Isolator dialog box contains eight choices to match the eight channel input board. You can label each button to identify the event associated with the contact. When the dialog box is accessed, each button flashes to display the Input Contact Isolator number and the user entered label. This label also appears in the Display Panel when an event related to an Input Isolator Connector is triggered.

The Input Contact Isolator dialog box allows you to:

  • Label the input contact assignments for your setup.
  • Set the delay for an external event triggering an alarm.
  • Review the isolator contact assignments, once the labels are entered.

The delay allows you to set the number of seconds which a condition needs to persist to trigger an alarm.

These input alarms can also be configured to activate a programmable relay output, which is discussed in Configuring the Programmable Relay Board Settings on page 97.

When the Transfer Inhibit option is supplied, connect a N.O. dry contact (customer-supplied) to Input Contact 8 (Pins 15 and 16). When the customer contact closes, transfers will be inhibited as long as the contact remains closed. Input Contact 8 is factory-set so no setup is required. The Transfer Inhibit option prevents Input Contact 8 from being used for any other input.

To configure the Input Contact Isolator relays:

1. Select INPUT CONTACT ISOLATOR from the Comm Options menu. The Input Contact Isolator dialog box is displayed.

Figure 57 Input contact isolator dialog box

Liebert 100-1000A — 13.8.3 Configuring the Input Contact Isolator Settings diagram (page 104)
Fig. 40 · 13.8.3 Configuring the Input Contact Isolator Settin…
2. Select INPUT CONTACT 1.
Page 105 of the Liebert 100-1000A user manual — 13.8.4 Configuring the Programmable Relay Board Settings
Page 105 · click to enlarge
Page 105

Liebert STS2 Touch Screen Display

A keyboard is displayed to allow you to enter the name of the alarm. 3. Enter the name of the alarm set for that input. For example, a fan problem could be indicated by naming the button FAN. 4. Select OK on the keyboard to keep your label. 5. Select DELAY. A keypad is displayed prompting you for a delay time, in seconds, for a condition to exist before the alarm is triggered. 6. Enter the delay value. The range for the values are from 0 (zero) to 99.9 seconds. 7. Select OK on the keypad to keep your setting. The value you entered is displayed in the field adjacent to the corresponding input contact. 8. Repeat steps 2 to 7 for each input contact. 9. Select SAVE after you have configured all input contacts. Be sure to select Save even if you have accessed this dialog only to change a setting. 10. Enter the settings in Input Contact Isolator Settings Record on page 142. This information is not saved if control power is removed. 11. Select OK in the Comm Options dialog box to activate the settings.

13.8.4 Configuring the Programmable Relay Board Settings

The Liebert STS2 can contain up to two Programmable Relay Boards (PRB) that can trigger an external device when an event occurs in the Liebert STS2. For example, if Source 1 fails, an external light flashes.

See 6.1 - Programmable Relay Board for more information on the PRBs.

The Programmable Relay Board dialog box with two options: STANDARD SET and USER DEFINED SET. The STANDARD SET are the factory-configured settings.

The STANDARD SET for the Programmable Relay Board settings are:

Table 14 Standard settings for programmable relays

1 SOURCE 1 FAIL Source 1 failure.

2 SOURCE 2 FAIL Source 2 failure.

3 BYPASS CB4 CLOSED Switch (CB4) is closed, Source 1 is bypassed.

4 BYPASS CB5 CLOSED Switch (CB 5) is closed, Source 2 is bypassed.

5 TRANSFER INHIBIT A transfer between Source 1 and Source 2 is being restrained.

6 OUT OF SYNC The phase difference between sources 1 and 2 exceeds the allowable threshold for transfer,

7 EQUIP OVER TEMP The ambient temperature of the Liebert STS2 exceeds the recommended threshold for operation.

8 blank No setting.

The USER DEFINED SET allows you to assign faults and alarms to each contact on the relay boards.

Utilizing the USER DEFINED SET, you can also select Input Contact Isolators to associate with a programmable relay.

In addition individual events, three other assignment choices are available:

  • SELECT ALL sends a summary event to the selected relay whenever any event occurs. If this setting is selected for a relay, no other event needs to be assigned for that relay.
  • ON SOURCE 1 or ON SOURCE 2 can be assigned to a relay to send a notification when that source is being used by the load.

Once configured, the Liebert STS2 continuously checks the status of the items defined for each contact and updates the state of the relay.

Relay Setting Definition

Page 106 of the Liebert 100-1000A user manual — 13.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Card
Page 106 · click to enlarge
Page 106

Liebert STS2 Touch Screen Display

To configure your programmable relay boards for user defined settings:

1. Select PROG. RELAY BOARD # x from the Comm Options dialog box, where x is the corresponding board number. The Prog. Relay Board dialog box is displayed.

Figure 58 Programmable relay board dialog box

Liebert 100-1000A — Figure 58 Programmable relay board dialog box diagram (page 106)
Fig. 41 · Figure 58 Programmable relay board dialog box
2. Select your configuration settings.
  • Select STANDARD SET to use the settings configured at the factory. See Go to step 4 .
  • Select USER DEFINED SET to configure your own settings. Go to step 3 . If you enter a user-defined setting, record the setting in Programmable Relay Board Settings Record on page 140 . If for some reason the control board is replaced, it will be necessary to reprogram the Programmable Relay Board with this information. 3. To define your relay board settings: a. Select a Programming Relay. b. Select an event you want associated with the relay. That fault is placed in the Relay column. You can associate up to ten (10) events with one relay. If you do so, you should group the events logically to simplify troubleshooting when an event is triggered. 4. Select SAVE to keep the settings. 5. Select OK for the applicable Programmable Options Board option in the Comm Options dialog box to activate the settings.

13.8.5 Configuring the Liebert IntelliSlot SNMP/Web/Modbus 485 Card

An optional Liebert IntelliSlot SNMP/Web/Modbus 485 card can be installed in the Liebert STS2 to provide Ethernet connectivity via an RJ-45 port.

Ethernet cabling is the responsibility of the customer. Category 5 cabling is required.

See 6.6 - Liebert IntelliSlot® SNMP/Web/Modbus 485 Card for more information on the Liebert IntelliSlot SNMP/Web/Modbus 485 card. See the card’s user guide, SL-52615, for configuration instructions. The guide is available at the Liebert Web site, www.liebert.com

If the optional Liebert IntelliSlot SNMP/Web/Modbus 485 card is installed in the Liebert STS2:

  • Select YES for the Liebert IntelliSlot SNMP/Web/Modbus 485 card option in the Comm Options dialog box to activate the card.
Page 107 of the Liebert 100-1000A user manual — PDU
Page 107 · click to enlarge
Page 107

Liebert STS2 Touch Screen Display

13.8.6 Liebert SiteScan ® Configuration

An optional RS-422 port, contained in the Comms Board, can be installed in the Liebert STS2 to provide communications with Liebert SiteScan. Liebert SiteScan is system monitoring software that allows you to utilize a PC to monitor the Liebert STS2’s status and check alarms. See 6.5 - Comms Board for more information on this board.

If the Liebert STS2 will be connected to Liebert SiteScan:

  • Select YES for the Liebert SiteScan choice in the Comm Options dialog box to activate the card.

13.8.7 Saving Your Communications Configurations

To save you communications configuration settings:

1. When you have completed the Comm Options configurations, ensure you have selected YES for all the settings that you want activated. 2. Select SAVE to keep the settings.

Whenever you make modifications to the any of the Comm Options, select SAVE to keep the changes.

13.9 System Options

Most System Options are configured at the factory. However, you may need to set two of the choices after the unit is installed: Wye Output Transformer and Remote Source Selection.

  • Select SYSTEM OPTIONS from the System Settings Menu. (If needed, see 13.7.4 - System Settings to access the System Settings menu.) The System Options dialog box is displayed.
  • An option is enabled by selecting YES.
  • An option is disabled by selecting NO.

Figure 59 System options

Liebert 100-1000A — 13.9 System Options diagram (page 107)
Fig. 42 · 13.9 System Options

Dual Output Breaker

This selection is set at the factory. The choice is set to YES to enable both output breakers (CB3 and CB3A) when two are installed in the unit. If only one output breaker (CB3) is installed, the setting is set to NO.

PDU

This selection is set at the factory. This setting allows the LCD to draw the Mimic accordingly and display PDU specific metering and alarm information.

Page 108 of the Liebert 100-1000A user manual — 13.10 System ID
Page 108 · click to enlarge
Page 108

Liebert STS2 Touch Screen Display

4-Pole Transfer Switch

This option is not available (factory-set to No).

Shunt

This selection is set at the factory.

Wye Output Transformer

The Wye Output Transformer controls the firing of the SCRs on startup, which minimizes the inrush into PDU transformers. Output breakers and PDU input breakers have to be closed when you start up the system. Based on whether the input side of the PDU transformer is configured as a Wye or Delta changes the firing sequence of the SCRs.

If the Liebert STS2 is connected to a PDU configured as a Wye:

  • Select YES for the Wye Output Transformer choice in the System Options dialog box.

Remote Source Selection

If your system is configured with the optional Remote Source Selection, it must be enabled from the System Options menu. See 5.5 - Remote Source Selection Wiring for more information.

If the system is utilizing Remote Source Selection:

  • Select YES for the Remote Source Selection choice in the System Options dialog box to activate the option.

13.10 System ID

Most of the settings for System ID are set by Emerson either at the factory or when the unit is installed.

Order No., System Tag No., System ID No. and Model No. are the numbers used to identify and track the system.

Language, Time and Date are synchronized with the location of the unit.

The only configurable field is the Password. See Using the Password on page 87 for more information on configuring and using the password.

Page 109 of the Liebert 100-1000A user manual — 13.11.2History Log
Page 109 · click to enlarge
Page 109

Liebert STS2 Touch Screen Display

13.11 Logs

Two types of logs are kept by the Liebert STS2: Event Log and History Log.

13.11.1Event Log

The Event Log tracks the alarms and faults of the Liebert STS2.

See 11.0 - Alarm and Faults for more information on these events and see 11.2.1 - Event Log for more information on the Event Log and definitions of the fields displayed in the Event Log screen.

Figure 60 Event log

Liebert 100-1000A — 13.11.1Event Log diagram (page 109)
Fig. 43 · 13.11.1Event Log

To use the Event Log:

1. Select LOGS from the menu bar to open the Logs menu. 2. Select EVENT LOG from the menu. 3. Use the UP and DOWN buttons to scroll through the event list. 4. Select OK to close the Event Log. The data remains in the log.

13.11.2History Log

Two History Logs are available to track major alarms. If so configured, an alarm freezes the history buffer. When the History Status buffer is frozen, a History Log is created that can be accessed from the HISTORY LOG x choices in the LOGS menu.

See 11.2.2 - History Log for more information on the History Logs and definitions of the fields displayed in the History Log screen.

Figure 61 History log

Liebert 100-1000A — 13.11.2History Log diagram (page 109)
Fig. 44 · 13.11.2History Log
Page 110 of the Liebert 100-1000A user manual — 13.17 Cleaning the LCD Touch Screen
Page 110 · click to enlarge
Page 110

Liebert STS2 Touch Screen Display

To use the History Log:

1. Select LOGS from the menu bar to open the Logs menu. 2. Select either HISTORY LOG 1 or HISTORY LOG 2 from the menu. 3. Select the appropriate buttons to replay the log:
  • Select PREV to go to the previous frame in the sequence.
  • Select NEXT to go to the next frame in the sequence.
  • Move the green cursor to the location from which you would like to play the sequence of events.
  • Select REPLAY to play the frames automatically from the point of the cursor.
  • Select STOP to halt the replay.
  • Select RESET to return to the first frame in the log. 4. Select EXIT to close the History Log. The data remains in the log.
  • Use CLEAR HLOGS to remove the data from both history logs.

13.12 Source Transfers

The Source Transfer choice (SOURCE XFERS) allows you to manually select a preferred source.

To switch the primary source, refer to the instructions in 10.2 - Manual Transfer / Preferred Source Selection.

13.13 Startup Procedure

You can access instructions for starting the Liebert STS2 from the menu bar.

  • From the menu bar, select STARTUP PROC.

These instructions are also provided on 10.1 - Normal System Startup for Color Graphical display units and 14.2.1 - Normal System Startup for LED Display units.

13.14 Bypass Procedure

You can access instructions for bypassing the static transfer switch from the menu bar.

  • From the menu bar, select BYP. PROC.

The instructions are provided in the display panel.

Bypass procedures are also discussed in 10.4 - Maintenance Bypass for Color Graphical display units and 14.2.3 - Maintenance Bypass for LED Display units.

13.15 Help

You can select an event in the Event Display to display more information about that event in the Display Panel. This same help is also available in 16.0 - Event Message Help Text.

13.16 Logo

The Logo menu choice shows the Emerson logo in the Display panel.

13.17 Cleaning the LCD Touch Screen

If the touch screen requires cleaning, use a pre-moistened towelette designed for cleaning CRTs, or dampen a soft, non-abrasive cloth with a very mild cleaning solution.

Do not spray the cleaner directly onto the touch screen, as drips may run down into the screen and damage the equipment.

Close all menus and dialog boxes before cleaning the touch screen.

Page 111 of the Liebert 100-1000A user manual — (E)
Page 111 · click to enlarge
Page 111

Operating the Liebert STS2 LED Display

14.0 O PERATING THE L IEBERT STS2 LED D ISPLAY

Certain models of the Liebert STS2 do not include the LCD Color Graphical Display with the touch screen interface. This display is replaced by an LED front panel to allow you to monitor the unit and alert you when a problem occurs. The LED panel can be replaced with the Color Graphical Display, if desired. Instructions for using the LCD are in 13.0 - Liebert STS2 Touch Screen Display.

You can use a PC running terminal emulation software connected to the RS-232 port to access the data and configuration settings that are available in the Color Graphical Display touch screen.

See 12.1 - Using the RS-232 Port for instructions on setting up and using a terminal with the unit.

14.1 LEDs and Buttons and Key Lockout Switch

The LED Display unit is monitored and controlled through a series of LEDs and buttons and an optional key lockout switch. This section includes illustrations of the LEDs, buttons and key lockout switch, plus tables providing definitions of these components.

14.1.1 Front Panel Controls

The front panel contains the LEDs to monitor the Liebert STS2, plus selection buttons to choose the preferred source. Figure 62 provides a breakdown of the front panel.

Table 15 on page 104 defines the LEDs and the push buttons on the display.

Figure 62 LED display

(E)

1 (C) 1 (A)

(H)

(J)

(G)

3A

(B) 2 (D)

(F)

(L)

(K) (M)

(N) PS211002 Rev. 0

!

Page 112 of the Liebert 100-1000A user manual — 14.1.2 LED and Push Button Description
Page 112 · click to enlarge
Page 112

Operating the Liebert STS2 LED Display

14.1.2 LED and Push Button Description

The following table defines the LEDs and push buttons in the LED display:

Table 15 LED and push button description

Symbol LED Description Action

A green LED is lit if the Source 1 input power is present. This LED only indicates that power is present to the power supply; it does not indicate if the power is within the programmed tolerances of the unit.

A Green Source 1 power is present

A green LED is lit if the Source 2 input power is present. This LED only indicates that power is present to the power supply; it does not indicate if the power is within the programmed tolerances of the unit.

B Green Source 2 power is present

C Green Source 1 within tolerance A green LED is lit if Source 1 power is within the programmed tolerance for all phases.

D Green Source 2 within tolerance A green LED is lit if Source 2 power is within the programmed tolerance for all phases.

E Green Source 1 SCRs on A green LED is lit when the SCRs for Source 1 are closed.

F Green Source 2 SCRs on A green LED is lit when the SCRs for Source 2 are closed.

A yellow (amber) LED is lit when source transfers are inhibited (locked out) by a hardware condition. Connect a PC terminal to the Liebert STS2 to locate the exact cause. See 12.0 - Communication Interfaces for PC terminal commands.

G Yellow Source transfer inhibited

H Green Push button to select Source 1 as the preferred source

A green LED is lit if the button has been pushed to set Source 1 as the preferred source.

I Green Push button to select Source 2 as the preferred source

A green LED is lit if the button has been pushed to set Source 2 as the preferred source.

J Green Output power is present A green LED is lit to indicate that power is present on the output load.

Push this button to turn off the horn that is sounded for an alarm. This button does not reset an alarm condition, unless pushed simultaneously with “M” button.

K Alarm silence button

Symbol to indicate the K and M must be pushed at the same time to reset alarm

Push this button simultaneously with the “K” button to reset an alarm condition. An alarm can only be reset if the hardware condition permits a reset.

M Alarm reset push button

A red LED is lit when an alarm condition is present in the Liebert STS2. Connect a PC terminal to the Liebert STS2 to locate the exact cause. See 12.0 - Communication Interfaces for PC terminal commands.

N Red Alarm present

1 Green CB1 closed A green LED is lit if CB1 is closed, indicating power is flowing to the static transfer switch from Source 1.

2 Green CB2 closed A green LED is lit if CB2 is closed, indicating power is flowing to the static transfer switch from Source 2.

3 Green CB3 closed A green LED is lit if the output breaker/switch is closed.

3A Green CB3A closed A green LED is lit if the output breaker/switch is closed. CB3A is installed on units with dual output breakers.

4 Yellow CB4 closed A yellow LED is lit if the Source 1 bypass breaker/switch is closed.

5 Yellow CB5 closed A yellow LED is lit if the Source 2 bypass breaker/switch is closed.

Page 113 of the Liebert 100-1000A user manual — 14.1.4 Key Lockout Switch
Page 113 · click to enlarge
Page 113

Operating the Liebert STS2 LED Display

14.1.3 Event Controls

When an alarm is triggered, a red LED is lit in the control panel. A pair of buttons allows you to turn off the horn and reset the alarm.

14.1.4 Key Lockout Switch

An optional key lockout switch for the Liebert STS2 enables or disables all push button inputs, except for the alarm silence button. The key lockout switch is mounted on the front of the unit. See Figures 8 to 10 for the key lockout switch location on each unit.

  • To disable the buttons, turn the key to the top of the switch, toward the closed padlock icon.
  • To enable all of the buttons, except the alarm silence, turn the key to the horizontal position, toward the open padlock icon.

Figure 63 Key lockout switch.

Changes disabled · Changes enabled

Page 114 of the Liebert 100-1000A user manual — 14.2.1 Normal System Startup
Page 114 · click to enlarge
Page 114

Operating the Liebert STS2 LED Display

14.2 Operations

This section discusses the system startup, shutdown and bypass procedures for the LED-based Liebert STS2.

If your unit has an LCD touch screen, see10.0 - Operating Instructions for the Touch Screen Interface for instructions these procedures.

14.2.1 Normal System Startup

This section provides instructions to start up the Liebert STS2. The LEDs provide the basic information required to ensure proper operation. To monitor metering data, use a PC terminal.

1. Ensure that all Liebert STS2 breakers—CB1, CB2, CB3A (if supplied), CB3, CB4, and CB5—are in the OFF (open) position. a. Ensure that the key interlocks for CB1 and CB2 have their bolts retracted. b. Ensure that the key interlocks for CB4 and CB5 have their bolts extended, thus preventing CB4 or CB5 from being turned ON. c. Ensure that the circuit breakers respective LEDs are off. 2. Source/input power should be applied to both Liebert STS2 inputs. Check that the green LEDs for each source are lit. 3. Verify that nominal input voltages are applied to both inputs (Source 1 and Source 2). Check that the green LEDs monitoring the sources are lit indicating the sources are within acceptable tolerances.

4. Close CB1. The green LED monitoring CB1 turns on. 5. Close CB2. The green LED for CB2 turns on. 6. Verify that the preferred source LED (green) (LED_PREFx) is lit for the source that you want the switch to be using. 7. Verify that the green LED for the corresponding SCR (Liebert STS1 or Liebert STS2) is lit, indicating that the SCR is closed. 8. Close Output Breaker CB3 (and CB3A in a redundant output configuration). 9. Verify that CB3 LED is lit, indicating that CB3 is closed and the output and load are energized.

  • In a redundant output configuration, verify the CB3A LED is lit, indicating that CB3A is closed and the output and load are energized 10. Press the Reset and Silence buttons simultaneously to reset any previous alarms. 11. Verify that no red or yellow (amber) LEDs are lit indicating an active alarm, transfer is inhibited or a bypass circuit breaker is closed. If the alarm LED remains lit, check the PC terminal to identify the alarm. Refer to 11.0 - Alarm and Faults for a description of the alarms and possible causes. All active alarm conditions should be corrected before proceeding. 12. If the unit is supplied with an output distribution cabinet, close output breakers as required. 13. Turn on the load equipment following the load equipment manufacturer’s recommendations.
Page 115 of the Liebert 100-1000A user manual — 14.2.2 Manual Transfer / Preferred Source Selection
Page 115 · click to enlarge
Page 115

Operating the Liebert STS2 LED Display

14.2.2 Manual Transfer / Preferred Source Selection

The preferred source buttons allow you to change the preferred source. Transfers are only permitted when the voltage and current are within their proper operating range and the sources are synchronized. Transfer is inhibited if the deviation exceeds the parameter set in the Source Set Points.

NOTE If one source will be de-energized for an extended period (hours or days), set the unit to bypass mode for the remaining source. Without using bypass, if a failure occurs in the switch components for remaining source, the Liebert STS2 does not have a second source to switch to and the load would not receive power. See 14.2.3 - Maintenance Bypass on page 108 for bypass instructions.

To manually select the preferred source:

1. Ensure that the Transfer Inhibit (NOXF) LED is not lit. If the Transfer Inhibit LED is lit:
  • Check to see if the red alarm LED is lit.
  • If the alarm LED is lit, check the alarm messages on a PC terminal.
  • Correct alarm conditions before attempting a source transfer.
2. Verify that the LEDs are lit for both sources, indicating power is present and within acceptable tolerances. 3. Verify that the LEDs for the SCRs (Liebert STS1 and Liebert STS2) are lit. 4. Verify that the input breakers CB1 and CB2 are closed.
  • Verify that their respective LEDs are lit. 5. Push the Preferred Source button for the desired source. See Table 15 on page 104. The Preferred Source (LED_PREF x ) LED turns on for that source. When conditions are correct, the switch transfers the load to the alternate source by selecting the alternate source as the preferred source. This source is now monitored as the preferred source throughout the various configurations set up through the PC terminal. 6. Check the LEDs to verify that the correct source is designated as the preferred source and that the input source changes to the desired source and the output (OUT) LED remains lit.
Page 116 of the Liebert 100-1000A user manual — 14.2.3 Maintenance Bypass
Page 116 · click to enlarge
Page 116

Operating the Liebert STS2 LED Display

14.2.3 Maintenance Bypass The Liebert STS2 is equipped with two key-interlocked, bypass breakers, CB4 and CB5, to allow manual bypass of the switch electronics for either input source in the event of switch failure or for maintenance of the switch. Refer to the static transfer switch one-line diagram (Figure 3). While operating on maintenance bypass, all voltages are removed from the Liebert STS2 electronics to facilitate safe repair, without de-energizing the load using a make-before-break switching sequence. However, the unit can be bypassed using a make-before-break switching sequence only to the same source to which that the switch is connected. In the event of source or switch failure, the unit should be bypassed only to the current input source. The LED display is used to verify the status of the unit during the bypass procedures. In the unlikely event that the LED display is not available, open the front door and look through the slots in the control door. If you can see green LEDs on the gate driver board through that slot, then the unit is connected to the source referenced on the label below that slot. See Figure 47. Bypass Procedures for Source 1 To bypass the switch for Source 1:

1. Verify that Source 1 is supplying power via the LED display.
  • If the LED Display is not available, check the gate driver board LEDs through the slots in the control panel. See Figure 47 . 2. Remove the interlock key from CB5 and place it in the CB4 interlock. 3. Open the alternate source input breaker CB2. Verify that CB2 LED is off. 4. Rotate and remove the CB2 interlock key. 5. Insert the key in the CB4 bypass breaker interlock. 6. Rotate the interlock keys in the CB4 bypass breaker interlock to retract the interlock. 7. Close bypass breaker CB4. Verify that CB4 LED is on. 8. Open source input breaker CB1. Verify that CB1 LED is off. 9. Rotate the CB 1 interlock key and remove it to lock out the breaker. 10. Secure the key according to your site’s lockout/tagout procedure. 11. Open output breakers CB3 and CB3A (if supplied) to remove power and isolate the static switch from the load. Verify that CB3 and CB3A LEDs (if supplied) are off. 12. Verify that the output LED is on. Power is now flowing directly from the source to the load, without passing through the static transfer switch. To return to normal mode: 1. Verify that the LED for Source 1 is on, indicating that the source is supplying power and is operating within acceptable tolerances. 2. Insert the key in the CB1 breaker interlock. 3. Rotate the key to retract the interlock. 4. Close source input breaker CB1. Verify that CB1 LED is on. 5. Select the SOURCE 1 button in the SOURCE XFERS menu. 6. Close output breakers CB3 and CB3A (if supplied). Verify that CB3 and CB3A LEDs are on. 7. Verify that STS SOURCE 1 and OUTPUT LEDs are on. 8. Open bypass breaker CB4. Verify that CB4 LED is off. 9. Rotate the keys in the CB4 interlock to extend the interlock. 10. Remove the proper key from the CB4 interlock and insert it in the CB2 breaker interlock. 11. Rotate the key to retract the CB2 breaker interlock. 12. Close source input breaker CB2. Verify that CB2 LED is on.
Page 117 of the Liebert 100-1000A user manual — Bypass Procedures for Source 2 To bypass the switch for Source 2:
Page 117 · click to enlarge
Page 117

Operating the Liebert STS2 LED Display

Bypass Procedures for Source 2 To bypass the switch for Source 2:

1. Verify that Source 2 is supplying power via the LED display.
  • If the LED Display is not available, check the gate driver board LEDs through the slots in the control panel. See Figure 47 . 2. Remove the interlock key from CB4 and place it in the CB5 interlock. 3. Open the alternate source input breaker CB1. Verify that CB1 LED is off. 4. Rotate and remove the CB1 interlock key. 5. Insert the key in the CB5 bypass breaker interlock. 6. Rotate the interlock keys in the CB5 bypass breaker interlock to retract the interlock. 7. Close bypass breaker CB5. Verify that CB5 LED is on. 8. Open source input breaker CB2. Verify that CB2 LED is off. 9. Rotate the CB2 interlock key and remove it to lock out the breaker. 10. Secure the key according to your site’s lockout/tagout procedure. 11. Open output breakers CB3 and CB3A (if supplied) to remove power and isolate the static switch from the load. Verify that CB3 and CB3A LEDs (if supplied) are off. 12. Verify that the output LED is on.

Power is now flowing directly from the source to the load, without passing through the static transfer switch.

To return to normal mode:

1. Verify that the LEDs for Source 2 are on, indicating that the source is supplying power and is operating within acceptable tolerances. 2. Insert the key in the CB2 breaker interlock. 3. Rotate the key to retract the interlock. 4. Close source input breaker CB2. Verify that CB2 LED is on. 5. Select the SOURCE 2 button in the SOURCE XFERS menu. 6. Close output breakers CB3 and CB3A (if supplied). Verify that CB3 and CB3A LEDs are on. 7. Verify that STS SOURCE 2 and OUTPUT LEDs are on. 8. Open bypass breaker CB5. Verify that CB5 LED is off. 9. Rotate the keys in the CB5 interlock to extend the interlock. 10. Remove the proper key from the CB5 interlock and insert it in the CB1 breaker interlock. 11. Rotate the key to retract the CB1 breaker interlock. 12. Close source input breaker CB1. Verify that CB1 LED is on.

Page 118 of the Liebert 100-1000A user manual — Shutdown in Maintenance Bypass Mode
Page 118 · click to enlarge
Page 118

Operating the Liebert STS2 LED Display

14.2.4 Normal System Shutdown

The Liebert STS2 can be shut down from either the static switch mode or the bypass mode.

Shutdown in Static Transfer Switch Mode

When the Liebert STS2 is operating in static transfer switch mode (not maintenance bypass mode):

1. Turn off the load equipment per manufacturer’s recommendations. 2. Open CB3 to turn off the static switch output.
  • Open CB3A if the static transfer switch is a redundant output configuration. The LEDs for CB3 and CB3A (if supplied) and the output (OUT) are turned off. 3. Open the input switches CB1 and CB2. The LEDs for CB1 and CB2 are turned off. 4. To completely de-energize the unit, turn OFF the power to both inputs to the Liebert STS2.

Shutdown in Maintenance Bypass Mode

When the Liebert STS2 is operating on bypass:

1. Turn off the load equipment per manufacturer’s recommendations. 2. Open the bypass switch (CB4 or CB5) to turn off the Liebert STS2 output. The LED for the bypass switch is turned off. The output (OUT) LED is turned off. 3. To completely de-energize the unit, turn OFF the power to both inputs to the Liebert STS2.
Page 119 of the Liebert 100-1000A user manual — [L-L/L-N] [L-L/L-N]
Page 119 · click to enlarge
Page 119

15.0 S PECIFICATIONS

This section provides the specifications for the Liebert STS2.

15.1 System Configuration

The Liebert STS2 can be set in several different configurations, according to the model and location. The configuration is set at the factory and does not need to be changed by the customer. These configurations apply to both units, the Color Graphical Display and an LED Display.

15.1.1 Frequency

The Liebert STS2 accepts input frequencies of 50 Hz and 60 Hz. The frequency shall be within ± 0.5Hz of the nominal frequency.

15.1.2 Input/Output Voltage

The Liebert STS2 models are available to handle various voltages.

The input voltage must be three-phase AC (3 or 4 wire-plus-ground). The Liebert STS2 is designed to accept an input neutral from each source. The neutral is switched in the 4-pole Liebert STS2 only.

The voltage shall be within ± 10% of the nominal voltage.

The output voltage shall be three-phase AC (3 or 4 wire-plus-ground). Nominal output voltage shall be same as input voltage.

The following table provides nominal voltages, listed according to frequency.

Table 16 Input/output voltage

[L-L/L-N] [L-L/L-N]

200/115V 200/115V

208/120V 208/120V

220/127V 220/127V

240/139V 240/139V

380/220V 380/220V

400/230V 400/230V

415/240V 415/240V

480/277V

600/346V

15.1.3 System Current Ratings

These ratings are based upon continuous switch current rating. These ratings are for all voltages and frequencies. All units are 100% continuous current rated.

Table 17 System current ratings

Specifications · 60Hz 50 Hz · Current

Page 120 of the Liebert 100-1000A user manual — 15.1.8 Environmental Requirements
Page 120 · click to enlarge
Page 120

15.1.4 Grounding

Refer to 5.3 - System Grounding for specifications and instructions regarding grounding.

15.1.5 Electrical Requirements

Table 18 Electrical requirements

Maximum Continuous Current 100, 250, 400, 600, 800, 1000 amps

Load Power Factor Range 0.75 to 1.0, leading or lagging

Load Crest Factor Up to 3.5

Source Voltage Distortion Up to 10% THD with notches and ringing transients

125% for 30 minutes 100A-400A

125% for 10 minutes 600A-1000A

150% for 2 minutes

500% for 0.25 sec.

Table 19 Unit short circuit withstand capability

Unit Voltage Unit Amps Withstand Capability

208-240V

380-480V

15.1.6 Input Surge Suppression

The Liebert STS2 is equipped with transient voltage surge suppression on each input for maximum surge suppression. The surge suppression is capable of protecting the Liebert STS2 from operating outside of tolerances due to surges as defined by IEC 1000-4-5 (1.2/50uS surge, 2kV CM and 1kV DM) as required under EN 50091-2.

15.1.7 Response Time

A dual level fast/slow transfer threshold is used for under voltage detection to allow the Liebert STS2 to be compatible with UPSs and generators. The voltage thresholds and the slow transfer delay time is user-adjustable. The fast transfer delay time is less than 4 ms.

The over voltage detection uses a single threshold, with programmable level and delay time.

See User Settings on page 89 for instructions on configuring these settings.

15.1.8 Environmental Requirements

See 3.0 - Location Considerations for details concerning environmental requirements for the Liebert STS2.

Show 12 more labels / short text on this page
Specifications · Item Requirement · Overload Capability · 100-250A 125kA · 400-600A 150kA · 800-1000A 100kA · 100-250A 100kA · 400-600A 100kA · 800-1000A 65kA · 100-250A 50kA · 400-600A 25kA · 800-1000A 25kA
Page 121 of the Liebert 100-1000A user manual — 15.2.3 Cooling
Page 121 · click to enlarge
Page 121

15.2 System Components

All Liebert STS2 models provide two static transfer switches within one enclosure, with the ability to transfer between two input sources to a single output.

All Liebert STS2s are configured with either an LCD Color Graphical Interface touch screen display or LEDs for monitoring and configuring the unit.

This section lists the common components and the differences for both types of units.

15.2.1 Frame and Enclosure

The complete Liebert STS2 is housed in a freestanding enclosure. The cabinet is a NEMA type 1 enclosure and meets IP20 requirements. The cabinet is structurally designed to handle lifting from the base. The frame is designed to accommodate floor stands.

Table 20 Frame sizes

Rating Width Depth Height

100. 250A 3 pole 30 in (76 cm) 32 in (81 cm) 76.77 in (195 cm)
400. 600A 3 pole 38 in (96 cm) 32 in (81 cm) 76.77 in (195 cm)
800. 1000A 3 pole 84 in (213 cm) 32 in (81 cm) 76.77 in (195 cm)

The distributed floor weight for Liebert STS2 is less than 150 lbs./sq. ft. (660kg/m²).

The required service access is only from the front of the unit.

The Liebert STS2 can be tipped 15° in any direction without falling over.

15.2.2 Casters, Leveling and Seismic Anchoring

The frame includes heavy-duty swivel casters for ease of installation, plus permanent leveling feet for final installation.

The unit also can be fastened to the floor using optional seismic anchors to meet seismic Zone 4 requirements. See 4.0 - Locating the Liebert STS2 and Figures 11 through 13 for instructions and details for installing seismic anchoring.

15.2.3 Cooling

The Liebert STS2 100 – 600A units utilize convection air cooling for the enclosure with forced air cooling of the heat sinks. The 800-1000A units are fan cooled using low-velocity fans to minimize audible noise. All fans are redundant so that a single fan failure cannot cause temperatures to increase beyond acceptable limits.

Air intake is through screened protective openings in the front of the unit. A standard furnace filter is installed behind the openings.

By opening the front door, the filter can be changed easily without exposing personnel to high voltage.

The size of the filter is 1 in. x 25 in. x 25 in. (2.54 cm x 63.5 cm x 63.5 cm).

The air exhaust is through the top of the unit.

Specifications

Page 122 of the Liebert 100-1000A user manual — 15.2.8 Color Graphical Display or LED Display
Page 122 · click to enlarge
Page 122

15.2.4 Access

The Liebert STS2 is designed so all repairs and maintenance can be done from the front or top of the unit. All components that may need repair or replacement during routine field maintenance are safely accessed with the units in bypass without removing power from the unit. These components include:

  • All electronic PCB assemblies
  • Power supply assemblies
  • All fuses
  • All circuit breaker plug-in modules
  • Fans
  • SCRs

All power connections are designed to maintain proper connection torque over the lifetime of the unit without any maintenance. The integrity of the connections can be checked via infrared scanning safely from the front or top of the unit.

All other components including power cables and connections, circuit breaker bases, etc. are replaceable from the front or top of the unit only, but this requires all power to be removed from the unit for safety. Although routine re-torquing of the power connections is not required, if maintenance of these connections is needed, complete removal of power is required from the unit for safety reasons.

! WARNING Lethal voltages exist inside the unit during normal operation. Only qualified service personnel should perform maintenance on the static switch.

The unit is supplied by more than one power source. The unit contains hazardous voltages if any of the input sources is ON, even when the unit is in bypass. To isolate the unit, turn OFF and lock out ALL input power sources.

Verify that all input power sources are de-energized and locked out before making connections inside unit.

15.2.5 Circuit Breakers

The Liebert STS2 is equipped with five molded-case, plug-in, non-automatic circuit breakers. The breakers are UL-listed for use up to 600 VAC and CE-marked. The plug-in feature of the breaker includes an interlock, which prevents the breaker from being unplugged without being in the OFF (open) position.

Mechanical interlocks are provided on the breakers to prevent improper maintenance bypassing of the solid-state switch. A bypass breaker cannot be closed unless the solid-state switch is connected to the same input source and only one bypass breaker can be closed at a time. All breakers are equipped with N.O. and N.C. auxiliary switches for monitoring of the breaker positions. The two input breakers for the solid-state switching devices also are equipped with 48 VDC shunt trips to allow for control by the Liebert STS2 logic. See Figure 20 - Liebert STS2 non-automatic circuit breaker schedule.

15.2.6 Cable Entrance

Removable conduit termination plates are provided in the top and bottom of the Liebert STS2 for termination of the two source input conduits or raceways and/or the output conduits or raceways.

15.2.7 Doors

A removable key lock hinged front door provides access to the circuit breakers.

15.2.8 Color Graphical Display or LED Display

The display is located in the front of the unit. Front panel display is either an LCD touch screen display for monitoring and configuring the unit, or an LED panel to monitor the unit’s status.

See Figure 30 for a drawing of the touch screen display. See Figure 62 for the layout of the LED display.

Specifications

Page 123 of the Liebert 100-1000A user manual — 15.2.10 Terminal Port Connections
Page 123 · click to enlarge
Page 123

15.2.9 RS-232 Port

The unit is equipped with an RS-232 port for connecting a terminal or PC. See Figure 28 for the port’s location.

See 12.1 - Using the RS-232 Port for instructions on using a PC terminal with the unit.

15.2.10 Terminal Port Connections

The system has an asynchronous serial port configured as Data Terminal Equipment for terminal access only (half duplex). The CPU services the terminal port with no handshaking. The serial port conforms to RS-232 levels with a data format of 9600 Baud, 1 start bit, 8 data bits, and no parity bits. The serial port is 1000VDC isolated (non-SELV) and ESD protected to 15kV air discharge. The connector is a 6 Pin MTA plug with connections shown below.

Table 21 MTA plug pinout

Pin Signal Name Function / Comments

1 ISO_GND Isolated service terminal ground

2 ISO_TXD Isolated service terminal transmit output

3 ISO_RXD Isolated service terminal receive input

4 NC No Connection

5 NC No Connection

6 NC No Connection

A DB9 male connector is added and connected parallel to the 6 position header. It is configured as DTE.

Table 22 DB9 pinout

Pin Signal Name Function / Comments

1 NC No Connection

2 ISO_RXD Isolated service terminal transmit output

3 ISO_TXD Isolated service terminal receive input

4 NC No Connection

5 ISO_GND Isolated service terminal ground

6 NC No Connection

7 NC No Connection

8 NC No Connection

9 NC No Connection

Specifications

Page 124 of the Liebert 100-1000A user manual — 15.2.14 Options
Page 124 · click to enlarge
Page 124

15.2.11 RS-232 Interface Parameters

The service terminal interface parameters are the following settings and cannot be changed.

Table 23 RS-232 settings

Interface RS-232 Using EIA Voltage Levels

Number of Data Bits 8

Number of Stop Bits 1

Hardware Flow Control Off

15.2.12 Maintenance Bypass

The Liebert STS2 is configured to allow the unit’s electronics to be bypassed to either input source for maintenance without interruption of power to the load.

The Liebert STS2 is furnished with key-interlocked maintenance bypass breakers to configure the bypass.

Liebert STS2 units have all electronics isolated from the input, output, and bypass connections to allow safe servicing of any components without access to hazardous voltages when the unit is in maintenance bypass.

See 10.4 - Maintenance Bypass on page 67 for instructions using the Color LCD Graphical Display unit and 14.2.3 - Maintenance Bypass on page 108 for instructions using the LED units.

15.2.13 Fuseless Design

All Liebert STS2 units are fuseless and are UL rated for use with upstream circuit breakers only.

15.2.14 Options

The following options are available for the Liebert STS2:

Programmable Relay Board Remote Source Selection

Optimized Transfer Key Lockout Switch

Distribution Cabinet With I-Line Panelboard Redundant Output Breaker

Input Contact Isolator Board Transfer Inhibit

Comms Board w/Liebert SiteScan and Modem Interface Input Junction Boxes and Cable

Liebert IntelliSlot SNMP/Web/Modbus 485 Card Seismic Floor Anchors

LED Display Seismic Floor Stand - 18", 24", 30" and 36"

See 6.0 - Options for more information.

Show 8 more labels / short text on this page
Specifications · Parameter Setting · Baud Rate 9600 · Parity None · Terminator <CR> <LF> · Handshaking Not supported · Structure Full duplex · Local Echo Off
Page 125 of the Liebert 100-1000A user manual — S1 SCR OPEN
Page 125 · click to enlarge
Page 125

Event Message Help Text

16.0 E VENT M ESSAGE H ELP T EXT

Key: ALL CAPS = event message displayed in the Event Display panel in the lower left corner of the LCD display.

Indented text = help text shown in the Display Panel in the lower right corner of LCD display. BOLD = commands that are sent through the RS-232 port.

S1 SCR SHORT

Source 1 SCR Short.

One or more of the SCRs for Source 1 has shorted. Transferring between sources has been inhibited.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

S2 SCR SHORT

Source 2 SCR Short.

One or more of the SCRs for Source 2 has shorted. Transferring between sources has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

S1 SCR OPEN

Source 1 SCR Open.

One or more SCRs on Source 1 is open. Transferring between sources has been inhibited.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Liebert STS2 output has been transferred to Source 2.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

Page 126 of the Liebert 100-1000A user manual — CONTROL MODULE FAIL
Page 126 · click to enlarge
Page 126

Event Message Help Text

S2 SCR OPEN

Source 2 SCR Open.

One or more SCRs on Source 2 is open. Transferring between sources has been inhibited.

Liebert STS2 output has been transferred to Source 1.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

PRIMARY FAN FAIL

Primary Fan Failure.

One of the primary cooling fans for the Liebert STS2 has failed. The alternate fans are now running. The alternate fans are not monitored.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

CONTROL MODULE FAIL

Control logic module has failed.

One of the control modules on the control board has failed.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 127 of the Liebert 100-1000A user manual — PWR SPLY S1 AC FAIL
Page 127 · click to enlarge
Page 127

Event Message Help Text

PWR SPLY DC A FAIL

Power Supply DC Bus A Failed.

The primary power supply is no longer providing DC power to the control board and the touch screen.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

PWR SPLY DC B FAIL

Power Supply DC Bus B Failed.

The secondary power supply is no longer providing DC power to the control board and CAN options.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

PWR SPLY S1 AC FAIL

Power Supply Source 1 AC Failed.

The AC input power to the power supplies from Source 1 has failed. The power supplies are now operating on AC power from Source 2. The AC input from Source 1 is still good.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 128 of the Liebert 100-1000A user manual — OUT VOLT SENSE FAIL
Page 128 · click to enlarge
Page 128

Event Message Help Text

PWR SPLY S2 AC FAIL

Power Supply Source 2 AC Failed.

The AC input power to the power supplies from Source 2 has failed. The power supplies are now operating on AC power from Source 1. The AC input from Source 2 is still good.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

PWR SPLY LOGIC FAIL

Power Supply Module Failed.

The power supply logic module contained in the primary power supply has failed.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, is so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

OUT VOLT SENSE FAIL

Output Voltage Sense Module Failed.

The module contained on the snubber monitoring the output voltage has failed.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 129 of the Liebert 100-1000A user manual — S1 SCR SENSE FAIL
Page 129 · click to enlarge
Page 129

Event Message Help Text

S1 VOLT SENSE FAIL

Source 1 Voltage Sense Module Failed.

The module contained on the snubber monitoring the input voltage from Source 1 has failed.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S2 VOLT SENSE FAIL

Source 2 Voltage Sense Module Failed.

The module contained on the snubber monitoring the input voltage from Source 2 has failed.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2 system from a terminal, type CA and press RETURN on your keyboard.

S1 SCR SENSE FAIL

Source 1 SCR Sense Module Failed.

The module contained on the snubber monitoring the SCRs for Source 1 has failed.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2 system from a terminal, type CA and press RETURN on your keyboard.

Page 130 of the Liebert 100-1000A user manual — S1 GATE DRIVE FAIL
Page 130 · click to enlarge
Page 130

Event Message Help Text

S2 SCR SENSE FAIL

Source 2 SCR Sense Module Failed.

The module contained on the snubber monitoring the SCRs for Source 2 has failed.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2 system from a terminal, type CA and press RETURN on your keyboard.

S1 CURR SENSE FAIL

Source 1 Current Sense Failure.

The module monitoring the current from Source 1 has failed. This module is contained on the left side gate driver board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Events Log, is so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2 system from a terminal, type CA and press RETURN on your keyboard.

S2 CURR SENSE FAIL

Source 2 Current Sense Failure.

The module monitoring the current from Source 2 has failed. This module is contained on the right side gate driver board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Events Log, is so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2 system from a terminal, type CA and press RETURN on your keyboard.

S1 GATE DRIVE FAIL

Source 1 Gate Drive Failure.

The gate drive module for an SCR for Source 1 has failed. This module is contained on the right side gate driver board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the Liebert STS2 system from a terminal, type CA and press RETURN on your keyboard.

Page 131 of the Liebert 100-1000A user manual — EXTERNAL COMM FAIL
Page 131 · click to enlarge
Page 131

Event Message Help Text

S2 GATE DRIVE FAIL

Source 1 Gate Drive Failure.

The gate drive module for an SCR for Source 2 has failed. This module is contained on the left side gate driver board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INTERNAL COMM FAIL

Internal CAN Communications Failed.

Communications have failed in the CAN bus between the control board and the touch screen control.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

EXTERNAL COMM FAIL

External Communications Failed.

Communications have failed between the control board and the CAN options.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the unit from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 132 of the Liebert 100-1000A user manual — HEAT SINK OVERTEMP
Page 132 · click to enlarge
Page 132

Event Message Help Text

CB1 SHUNT TRIP FAIL

Circuit Breaker 1 Shunt Trip Failure.

Circuit Breaker 1 failed to trip open when the control issued a command for the circuit breaker to trip.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

CB2 SHUNT TRIP FAIL

Circuit Breaker 2 Shunt Trip Failure.

Circuit Breaker 2 failed to trip open when the control issued a command for the circuit breaker to trip.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

Contact Liebert Services for technical support at 1-800-LIEBERT (800-543-2378).

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

HEAT SINK OVERTEMP

Heat Sink Over Temperature.

The system heat sink temperature has exceeded the design limits.

Take immediate steps to cool the unit. Remove obstructions from the air inlet in the front of the unit. Remove and replace the air filter behind the front door. A standard furnace filter can be used.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

Page 133 of the Liebert 100-1000A user manual — S1 OV
Page 133 · click to enlarge
Page 133

Event Message Help Text

S1 UV

Source 1 Under Voltage (fast detection).

The input voltage from Source 1 dropped below a set percentage of the nominal voltage, as set in the Fast UV set point under the User Settings. An S1 Fail alarm was also issued and source transfer has been inhibited.

The load of the Liebert STS2 has been transferred to Source 2.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S1 UV (RMS)

Source 1 Under Voltage (slow detection).

The input voltage from Source 1 remained below a set percentage of the nominal voltage for a designated period, as set in the Slow UV Setting and Slow UV Detection Delay set points configured under the User Settings. An S1 Fail alarm was also issued and source transfer has been inhibited.

The load of the Liebert STS2 has been transferred to Source 2.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The alarm is latched and must be reset after the voltage returns to the nominal voltage. If the Reset option is not configured for AUTO (automatic reset), then the reset action must be done manually. When the voltage is within acceptable parameters, touch the RESET button on the touch screen. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

S1 OV

Source 1 Over Voltage.

The input voltage from Source 1 exceeded a set percentage of the nominal voltage, as set in the OV Setting and OV Detection Delay set points configured under the User Settings. An S1 Fail alarm was also issued and source transfer has been inhibited.

The load of the Liebert STS2 has been transferred to Source 2.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 134 of the Liebert 100-1000A user manual — S2 UV
Page 134 · click to enlarge
Page 134

Event Message Help Text

S1 OF/UF

Source 1 Over Frequency/Under Frequency.

The frequency for Source 1 is running outside the acceptable operating range, as set in the Frequency Trip Point under User Settings. An S1 Fail alarm was also issued and source transfer has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S1 FAIL

Source 1 Failure.

Source 1 has failed due to under voltage (UV), over voltage (OV), or running over or under frequency (OF/UF). This alarm is a companion to S1 UV, S1 UV (RMS), S1 OV and S1 OF/UF.

The load of the Liebert STS2 has been transferred to Source 2.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event has been written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S2 UV

Source 2 Under Voltage (fast detection).

The input voltage from Source 2 dropped below a set percentage of the nominal voltage, as set in the Fast UV setpoint under the User Settings. An S2 Fail alarm was also issued and source transfer has been inhibited.

The load of the Liebert STS2 has been transferred to Source 1.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 135 of the Liebert 100-1000A user manual — S2 UF/OF
Page 135 · click to enlarge
Page 135

Event Message Help Text

S2 UV (RMS)

Source 2 Under Voltage (slow detection).

The input voltage from Source 2 remained below a set percentage of the nominal voltage for a designated period, as set in the Slow UV Setting and Slow UV Detection Delay set points configured under the User Settings. An S2 Fail alarm was also issued and source transfer has been inhibited.

The load of the Liebert STS2 has been transferred to Source 1.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The alarm is latched and must be reset after the voltage returns to the nominal voltage. If the Reset option is not configured for AUTO (automatic reset), then the reset action must be done manually. When the voltage is within acceptable parameters, touch the RESET button on the touch screen. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

This event was written to the Event Log, if so configured.

S2 OV

Source 2 Over Voltage.

The input voltage from Source 2 exceeded a set percentage of the nominal voltage, as set in the OV Setting and OV Detection Delay set points configured under the User Settings. An S2 Fail alarm was also issued and source transfer has been inhibited.

The load of the Liebert STS2 has been transferred to Source 1.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S2 UF/OF

Source 2 Under Frequency/Over Frequency.

The frequency for Source 2 is running outside the acceptable operating range, as set in the Frequency Trip Point under User Settings. An S2 Fail alarm was also issued and source transfer has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 136 of the Liebert 100-1000A user manual — S2 OVERCURRENT
Page 136 · click to enlarge
Page 136

Event Message Help Text

S2 FAIL

Source 2 Failure.

Source 2 has failed due to under voltage (UV), over voltage (OV), or running with an over or under frequency (OF/UF). This alarm is a companion to S2 UV, S2 UV (RMS), S2 OV and S2 OF/UF.

The load of the Liebert STS2 has been transferred to Source 1.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S1 OVERCURRENT

Source 1 Overcurrent.

Liebert STS2 is running on Source 1 and an overload condition has occurred on one or more phases.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S2 OVERCURRENT

Source 1 Overcurrent.

Liebert STS2 is running on Source 2 and an overload condition has occurred on one or more phases.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 137 of the Liebert 100-1000A user manual — SOURCES OUT OF SYNC
Page 137 · click to enlarge
Page 137

Event Message Help Text

S1 I-PEAK

Current Peak on Source 1.

The peak current from Source 1 has exceeded the set point as defined in the I-PK Xfer Lockout setting under User Settings.

Transferring to Source 2 has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

If this alarm is configured to automatically reset under the set points for User Settings, the alarm clears itself when the I- Peak condition clears.

If this alarm is set for manual reset mode, the alarm continues to show as active after the current returns to nominal, still inhibiting transfers. You will need to manually reset the alarm. If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

The alarm has triggered a message to be sent to the modem, if so configured.

S2 I-PEAK

Current Peak on Source 2.

The peak current from Source 2 has exceeded the set point as defined in the I-PK Xfer Lockout setting under User Settings.

Transferring to Source 1 has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

If this alarm is configured to automatically reset under the set points for User Settings, the alarm clears itself when the I- Peak condition clears.

If this alarm is set for manual reset mode, the alarm continues to show as active after the current returns to nominal, still inhibiting transfers. You will need to manually reset the alarm. If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

The alarm has triggered a message to be sent to the modem, if so configured.

SOURCES OUT OF SYNC

Sources out of synchronization.

The phase difference between Source 1 and Source 2 has exceeded the deviation as set for MANUAL MAX XFER PHASE ANGLE under User Settings.

A manual transfer cannot take place while the sources are not synchronized.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 138 of the Liebert 100-1000A user manual — CB1 (S1) OPEN
Page 138 · click to enlarge
Page 138

Event Message Help Text

LOAD ON ALT SOURCE

Liebert STS2 load on the alternate source.

The static transfer switch is running on the alternate power source. Check the Event Log to determine the reason for the transfer from the preferred source.

Another event has caused the system to transfer to the alternate source. The system returns the load to the preferred source either automatically or manually, depending on how the system is configured.

In automatic reset mode, the Liebert STS2 automatically retransfers to the preferred source after the causal condition clears.

In manual reset mode, the system remains on the alternate source after the causal event clears until you select RESET from the touchscreen, or enter CA (Clear Alarms) from a service terminal.

Pressing the RESET button to returns the unit to the preferred source. Ensure that the condition that triggered the switch has been rectified before returning to the preferred source.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

AUTO REXFER INHIBIT

Automatic Retransfer Inhibited.

The system made five transfers from the preferred source to the alternate source in the last five minutes. As a result, automatic retransfers back to the preferred source is now disabled.

To clear this alarm condition, assign the alternate source as the preferred source.

This alarm also is cleared if the unit transfers to the preferred source due to an alternate source AC volt failure (i.e., an emergency transfer).

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

CB1 (S1) OPEN

Circuit Breaker 1 (for Source 1) Open.

Circuit Breaker 1 is not closed.

Check that the Circuit Breaker 1 switch is in the desired position.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 139 of the Liebert 100-1000A user manual — CB3 (OUTPUT) OPEN
Page 139 · click to enlarge
Page 139

Event Message Help Text

CB2 (S2) OPEN

Circuit Breaker 2 (for Source 2) Open.

Circuit Breaker 2 is not closed.

Check that the Circuit Breaker 2 switch is in the desired position.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

CB4 (S1 BYP) CLOSED

Circuit Breaker 4 (Source 1 Bypass Breaker) Closed.

Circuit breaker 4 is not open. The input from Source 1 is bypassing the static transfer switch.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

CB5 (S1 BYP) CLOSED

Circuit Breaker 5 (Source 2 Bypass Breaker) Closed.

Circuit breaker 5 is not open. The input from Source 2 is bypassing the static transfer switch.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

CB3 (OUTPUT) OPEN

Circuit Breaker 3 (Output breaker) Open.

Circuit breaker 3 is not closed. This circuit breaker is assigned to the output load. The power flow to the load cannot flow through the static transfer switch.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 140 of the Liebert 100-1000A user manual — S2 PHASE ROT ERROR
Page 140 · click to enlarge
Page 140

Event Message Help Text

CB3A (OUTPUT) OPEN

Circuit Breaker 3A (Output breaker) is Open (Optional).

Circuit breaker 3A is not closed. This circuit breaker is assigned to the output load. The power flow to the load cannot flow through the static transfer switch.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S1 PHASE ROT ERROR

Source 1 Phase Rotation Error.

A phase rotation error condition exists on Source 1. Check the phase sequence (ABC) of Source 1.

Transferring to Source 1 has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

S2 PHASE ROT ERROR

Source 2 Phase Rotation Error.

A phase rotation error condition exists on Source 2. Check the phase sequence (ABC) of Source 2.

Transferring to Source 1 has been inhibited.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 141 of the Liebert 100-1000A user manual — INPUT CONTACT #1
Page 141 · click to enlarge
Page 141

Event Message Help Text

TRANSFER INHIBITED

Transfer Inhibited.

Uninterrupted transfer between sources is inhibited due to input source failure, sources out of sync, switch failure, or the unit is in bypass mode.

Check the Event Log for the event or events that may have caused the alarm.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

OUTPUT UV

Output Undervoltage.

The voltage being supplied to the load has dropped below the acceptable nominal voltage. Check the input voltage from both sources.

This event and the system status surrounding it have been written to a History Log if the History Logs were not already full. This event was also written to the Event Log, if so configured.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INPUT CONTACT #1

Input Contact Isolator #1.

Occurrence of the indicated external event has been detected by Input Contact Isolator #1 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 142 of the Liebert 100-1000A user manual — INPUT CONTACT #5
Page 142 · click to enlarge
Page 142

Event Message Help Text

INPUT CONTACT #2

Input Contact Isolator #2.

Occurrence of the indicated external event has been detected by Input Contact Isolator #2 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INPUT CONTACT #3

Input Contact Isolator #3.

Occurrence of the indicated external event has been detected by Input Contact Isolator #3 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INPUT CONTACT #4

Input Contact Isolator #4.

Occurrence of the indicated external event has been detected by Input Contact Isolator #4 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INPUT CONTACT #5

Input Contact Isolator #5.

Occurrence of the indicated external event has been detected by Input Contact Isolator #5 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 143 of the Liebert 100-1000A user manual — INPUT CONTACT #8
Page 143 · click to enlarge
Page 143

Event Message Help Text

INPUT CONTACT #6

Input Contact Isolator #6.

Occurrence of the indicated external event has been detected by Input Contact Isolator #6 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INPUT CONTACT #7

Input Contact Isolator #7.

Occurrence of the indicated external event has been detected by Input Contact Isolator #7 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

INPUT CONTACT #8

Input Contact Isolator #8.

Occurrence of the indicated external event has been detected by Input Contact Isolator #8 of the Open Comms Digital Input option board.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event, with its assigned name, was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 144 of the Liebert 100-1000A user manual — DATE REPROGRAMMED
Page 144 · click to enlarge
Page 144

Event Message Help Text

CONFIG MODIFIED

Configuration Modified.

A set point has been updated and saved.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

PASSWORD CHANGED

Access Password Changed.

The password for accessing the HMI (touch screen) options has been updated and saved.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The alarm has triggered a message to be sent to the modem, if so configured.

The event was written to the Event Log, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

TIME REPROGRAMMED

System Time Reprogrammed.

The system’s time setting has been updated and saved.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

DATE REPROGRAMMED

System Date Reprogrammed.

The system’s date setting has been updated and saved.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 145 of the Liebert 100-1000A user manual — HIST LOGS FULL
Page 145 · click to enlarge
Page 145

Event Message Help Text

EVENT LOG CLEARED

Event Log Cleared.

All past alarms and faults are no longer recorded in the system’s event log.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

This event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

HIST LOGS CLEARED

History Logs Cleared.

Both History Logs have been erased and the logs are now available to record future events.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

HIST LOGS FULL

History Logs Full.

The history buffer has reached its capacity for both history logs. No further history logs can be written until the logs are cleared. The History Logs were frozen by the occurrence of two designated faults or alarms.

Both history logs have been frozen by significant events. These logs contain valuable diagnostic data regarding those events which may be useful if service is required. Once the logs have been analyzed and the causes for freezing them have been resolved, the history logs should be cleared to make them available for capturing future events.

To clear the History Logs, select the CLEAR HLOG button under the LOGS > HISTORY LOG 1 or LOGS > HISTORY LOG 2 menus to clear the History Status buffer after the alarms have been resolved.

If you are accessing the unit from a terminal, type CHL and press RETURN to clear the History Logs.

Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2 system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.

The event was written to the Event Log, if so configured.

The alarm has triggered a message to be sent to the modem, if so configured.

If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and press RETURN on your keyboard.

Page 146 of the Liebert 100-1000A user manual — 17.3 Changing the Air Filter
Page 146 · click to enlarge
Page 146

17.0 M AINTENANCE

! WARNING Only qualified service personnel should perform maintenance on the static switch.

Lethal voltages exist inside the unit during normal operation.

The unit is supplied by multiple AC power sources. Disconnect and lock-out all power sources before working inside unit.

Minimal periodic maintenance of the Liebert STS2 is required. As with all electrical distribution components, the system should be regularly inspected for electrical connection integrity, signs of excessive temperatures, dirt accumulation, and proper system operation.

17.1 Proper Tightening of Nuts and Bolts

The recommended tightening torque for all nuts and bolts is as shown below, unless otherwise labeled. All power connections are designed to remain at proper torque throughout the lifetime of the unit.

Table 24 Torque tightening

Grade 5 -Imperial Grade 8.8 -Metric

Electrical Connections With Belleville Washers

in-lb N-m in-lb N-m

10-32 25 3 35 4

1/4-20 53 6 80 9.0

5/16-18 107 12 180 20.4

3/8-16 192 22 240 27.1

1/2-13 428 48 480 54.3

17.2 Testing the Liebert STS2

The Liebert STS2 includes comprehensive system alarms and fault detection to identify operational problems. To increase the degree of confidence of proper system operation, periodic transfer tests can be easily performed. For instructions for changing the preferred source and switching sources:

  • For a Color Graphical Display unit, see 10.2 - Manual Transfer / Preferred Source Selection on page 66.
  • For an LED-equipped unit, see 14.2.2 - Manual Transfer / Preferred Source Selection on page 107.

17.3 Changing the Air Filter

A standard furnace filter is installed behind the air intake in the front door. The air intake allows air to circulate to cool the unit. Replace the filter when it becomes dirty and impedes air flow. The frequency of changing or cleaning the filter depends on the location in which the unit is located. The size of the filter is 1 in. x 25 in. x 25 in. (2.54 cm x 63.5 cm x 63.5 cm).

Maintenance · Bolt Shaft · Size

Page 147 of the Liebert 100-1000A user manual — S UPPORT I NFORMATION
Page 147 · click to enlarge
Page 147

S UPPORT I NFORMATION

To contact Emerson Network Power Liebert Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services is available to assure fast repair of your unit with minimal downtime. Liebert Services offers a complete range of startup services, repair services, preventive maintenance plans, and service contracts. For repair or maintenance service outside the 48 contiguous states, contact Liebert Services, if available in your area. For areas not covered by Liebert Services, the authorized distributor is responsible for providing qualified factory-authorized service. Additional telephone numbers and E-mail contact information is on the back page of this manual.

Please have the following information available.

Part Number:

Serial Number:

Date Purchased:

Date Installed:

Location:

Current Rating:

Frequency:

Voltage:

Maintenance

Page 148 of the Liebert 100-1000A user manual — P ROGRAMMABLE R ELAY B OARD S ETTINGS R ECORD
Page 148 · click to enlarge
Page 148

P ROGRAMMABLE R ELAY B OARD S ETTINGS R ECORD

The optional Programmable Relay Board (PRB) has eight channels to report events to an external device. Up to ten (10) events can be programmed to each channel. See 6.1 - Programmable Relay Board for more information on the PRB.

If your Liebert STS2 has the PRB option installed, list the settings below for future reference. If control power is lost in the Liebert STS2, the settings are not saved.

Channel 1:

Channel 2:

Channel 3:

Channel 4:

Channel 5:

Channel 6:

Channel 7:

Maintenance

Page 149 of the Liebert 100-1000A user manual — Programmable Relay Board Settings Record
Page 149 · click to enlarge
Page 149

Channel 8:

Channel 9:

Channel 10:

PRB Notes:

Maintenance

Page 150 of the Liebert 100-1000A user manual — I NPUT C ONTACT I SOLATOR S ETTINGS R ECORD
Page 150 · click to enlarge
Page 150

I NPUT C ONTACT I SOLATOR S ETTINGS R ECORD

The Input Contact Isolator board (ICI) provides an Liebert STS2 module interface for up to eight external user alarm or message inputs to be routed through the Liebert STS2’s alarm network. See 6.4 - Input Contact Isolator Board for more information on the ICI.

If your Liebert STS2 has the ICI option installed, list the settings below for future reference. If control power is lost in the Liebert STS2, the settings are not saved.

Channel 1:

Channel 2:

Channel 3:

Channel 4:

Channel 5:

Channel 6:

Channel 7:

Channel 8:

Maintenance

Page 151 of the Liebert 100-1000A user manual — Input Contact Isolator Settings Record
Page 151 · click to enlarge
Page 151
Page 151 of the Liebert 100-1000A user manual — Input Contact Isolator Settings Record
Page 152 of the Liebert 100-1000A user manual — SL-20620_REV8_05-11
Page 152 · click to enlarge
Page 152

Ensuring The High Availability Of Mission-Critical Data And Applications.

Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™

Technical Support / Service

Web Site www.liebert.com

from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.

Monitoring liebert.monitoring@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Single-Phase UPS & Server Cabinets

liebert.upstech@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Three-Phase UPS & Power Systems

800-543-2378 Outside North America614-841-6598
800-543-2778 Outside the United States614-888-0246

Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center

Philippines +63 2 687 6615 Fax: +63 2 730 9572

SL-20620_REV8_05-11

Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com

Embedded Computing Embedded Power

Racks & Integrated Cabinets Services

Power Switching & Controls Precision Cooling

Infrastructure Management & Monitoring

Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.

Show 6 more labels / short text on this page
Environmental Systems · Pasig City 1605 · AC Power Connectivity · Outside Plant · DC Power · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
RS-422Liebert SiteLink-12 or Liebert SiteLink-4 is required for Liebert SiteScan to p.84

Ask about the Liebert 100-1000A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert 100-1000A

Be the first to ask — other owners or our team will answer.

Original document

Liebert 100-1000A manual PDF

152 pages·5.2 MB·Surge Protector·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…