FTB-350A 24V TEST BOX

Frymaster, L.L.C., 8700 Line Avenue
Shreveport, LA 71106 TEL 318-865-1711 FAX 318-868-5987
*8196797*
24-Hour Service Hotline · 1-800-551-8633



INTRODUCTION The FTB-350A Test Box is a tester designed to test the F3000 Frymaster cooking controller for correct operating and controlling functions. WARNING: This test box should not be hooked up to 12V controllers.
PARTS ORDERING Parts orders must be placed directly with your local Factory Authorized Servicer. If you do not have a Factory Authorized Servicer list, please contact Frymaster Service Department at 1-800-551-8633 or 1-318-865-1711. To speed up your order, the following information is required: Model Number:



CONTROL PANEL

F3000 TEST PROCEDURE FOR LEGACY FRYMASTER FRYERS (KJ3, 118G, H55, MJ45, 118E/RE80 and FPRE114/117)
Ensure the controller is set to LEGACY-FRYMASTER using code 7628 in tech mode. With the Controller displaying OFF press and hold the check button until PRODUCT SETUP is displayed. Press the right arrow to tech mode. Enter 7628. Set LOCALE to NON-CE. Press the right arrow. Set system type to LEGACY-FRYMASTER. Press the right arrow. Set ENERGY to ELEC or GAS. Press the right arrow. Set TYPE to fryer type desired. Press the right arrow. Set FRESH OIL to NONE. Press the right arrow. Set WASTE OIL to NONE. Press the right arrow. Press the check button at EXIT.
1. Press controller ON/OFF switch to ON. 2. Set FTB-350A PROBE switches (6 & 7) to 3°C/37°F. (a) RELAY POWER indicator (3) illuminates. (b) HEAT indicators (2 & 4) should cycle on and off. “MLT-CYCL” is displayed on the controllers alternating with setpoint on the left and actual temperature on the right. 3. Set FTB-350A PROBE switches (6 & 7) to 97°C/206°F. (a) HEAT indicators (2 & 4) should illuminate continuously. (b) Setpoint is displayed on the left and actual temperature on the right.
function and only VARIABLE knob (9) will function. 4. Turn power off by pressing and holding the ON/OFF switch on the controller.

indicates a temperature. (c) Rotate VARIABLE knob (8 & 9) slowly clockwise until controller indicates DROP. (d) Press Temperature button on controller. Controller should indicate a temperature from one (1) to (4) degrees +/- set point (340°F/171°C). If not, rotate the VARIABLE knobs (8 & 9) counterclockwise very slowly until HEAT indicators (2 & 4) cycles ON. DROP band is 338°F/170°C-344°F/173°C. (e) HEAT indicators (2 & 4) should now cycle ON and OFF very slowly.
the alarm sounding. (c) RELAY POWER indicator (3) is no longer illuminated. (d) Turn off FTB-350A POWER switch (10).
“DISCONNECT POWER” and the alarm sounding. (c) RELAY POWER indicator (3) is no longer illuminated. (d) Turn off FTB-350A POWER switch (10). (e) Controller test is now complete.

Ensure the controller is set to HENNY PENNY 580/590/290 FULL using code 7628 in tech mode. Press and hold the check button until PRODUCT SETUP is displayed. Press the right arrow to tech mode. Enter 7628. Set LOCALE to NON-CE. Press the right arrow. Set system type to HENNY PENNY. Press the right arrow. Set ENERGY to ELEC. Press the right arrow. Set TYPE to HP580/590. Press the right arrow. Set FRESH OIL to NONE. Press the right arrow. Set WASTE OIL to NONE. Press the right arrow. Press the check button at EXIT.
A. INITIAL TEST SET-UP See page 6 for instructions to run initial test set-up. B. TEST POWER TO FRYER INTERFACE BOARD See page 6 for instructions to test power to fryer interface board. C. TEST MELT-CYCLE FUNCTION See page 6 for instructions to test melt-cycle function. D. TEST CONTROLLING FUNCTION See page 7 for instructions to test controlling function. G. TEST CONTROLLER HIGH LIMIT See page 7 for instructions to test controller high limit. H. TEST PROBE FAILURE MALFUNCTION See page 7 for instructions to test probe failure malfunction. I. TEST PRESSURE SOLENOID ACTIVATION 1. Ensure controller is set to OFF. 2. Set up a product opening and closing pressure solenoids. a) Press and hold the check button until PRODUCT SETUP is displayed. b) Press the check (9) button. c) Enter 3228 d) Select and press a button that is not illuminated. e) Enter TEST as LONG NAME (using the down arrow to scroll to next
letter). Press the right (X) arrow. f) Enter TEST as SHORT NAME (using the down arrow to scroll to next
letter). Press the right (X) arrow. g) Ensure COOKING MODE is set to MULTIPLE SETPOINT. If not press
the down (T) arrow. Press the right (X) arrow. h) Enter 1:00 at 1 TIME. Press the right (X) arrow. i) Leave 1 TEMPR at setpoint of 340°F/171°C. Press the right (X)
arrow. j) Leave 1 FLEX at 0. Press the right (X) arrow. k) Set 1 PRESSURE SOLENOID to CLOSE. Press the right (X) arrow. l) Enter 00:30 at 2 TIME. Press the right (X) arrow. m) Leave 2 TEMPR at setpoint of 340°F/171°C. Press the right (X)
arrow.

n) Leave 2 FLEX at 0. Press the right (X) arrow. o) Leave 2 PRESSURE SOLENOID to OPEN. Press the right (X) arrow. p) Leave :00 at 3 TIME. Press the right (X) arrow. q) Leave 1 ALARM TIME at :00. Press the right (X) arrow. r) Leave AFTER COOKING to COOL. Press the right (X) arrow. s) Leave FILTER LOCKOUT to 0. Press the right (X) arrow. t) Leave QUANTITY? to NO. Press the right (X) arrow. u) Leave HEAD COUNT to .0. Press the right (X) arrow. v) Leave INSTANT ON to 0. Press the right (X) arrow. w) Press check (9) button at EXIT. x) Press the SCAN button two times to OFF. 3. Press controller ON/OFF switch to ON (set point = 340°F/171°C). 4. Press the product button programmed in step 2 to start a cook. 5. The PRESSURE SOLENOID indicator (5) illuminates. After 30 seconds the pressure SOLENOID indicator (5) turns off. 6. Press the product button with blinking LED when DONE is displayed. 7. Controller test is now complete.
Ensure the controller is set to HENNY PENNY 690/390 FULL using code 7628 in tech mode. Press and hold the check button until PRODUCT SETUP is displayed. Press the right arrow to tech mode. Enter 7628. Set LOCALE to NON-CE. Press the right arrow. Set system type to HENNY PENNY. Press the right arrow. Set ENERGY to GAS. Press the right arrow. Set TYPE to HP690/390 FULL. Press the right arrow. Set FRESH OIL to NONE. Press the right arrow. Set WASTE OIL to NONE. Press the right arrow. Press the check button at EXIT.
1. Set-up FTB-350A as follows: (a) Set POWER switch (10) to OFF. (b) Set PROBE switch (7) to Variable. (c) Connect 120/24V transformer to 120VAC outlet or 240/24V transformer to 240VAC outlet. 2. Set controller up as follows: (a) Set POWER switch to OFF. (b) Connect FTB-350A 16-pin connector to rear of controller. (c) Plug 4-pin drain switch into connector. (d) Switch the HP690 POWER switch (11) to ON. (e) Switch the HP690 ALARM switch (12) to OFF. 3. Set FTB-350A POWER switch (10) to ON (a) Program the set point to 340°F/171°C.

knob (9) will function. 4. Turn power off by switching the HP690 POWER switch (11) to OFF.
1. Switch the HP690 POWER switch (11) to ON (set point = 340°F/171°C). 2. Set FTB-350A PROBE switch (7) to VARIABLE. (a) RELAY POWER indicator (3) illuminates. (b) Rotate VARIABLE knob (9) counterclockwise until controller indicates a temperature. (c) Rotate VARIABLE knob (9) slowly clockwise until controller indicates DROP. (d) Press Temperature button on controller. Controller should indicate a temperature from one (1) to (4) degrees +/- set point (340°F/171°C). If not, rotate the VARIABLE knob (9) counterclockwise very slowly until HEAT indicator (4) cycles ON. DROP band is 338°F/170°C- 344°F/173°C. (e) HEAT indicator (4) should now cycle ON and OFF very slowly. E. TEST CONTROLLER HIGH LIMIT
the alarm sounding. (c) RELAY POWER indicator (3) is no longer illuminated. (d) Turn off FTB-350A POWER switch (10).

“DISCONNECT POWER” and the alarm sounding. (c) RELAY POWER indicator (3) is no longer illuminated. (d) Turn off FTB-350A POWER switch (10). G. TEST ALARM FUNCTION
“CHECK HI-LIMIT - DRAIN VALVE - VACUUM SWITCH - BLOWER MOTOR” with alarm sounding. 5. Set HP 690 ALARM switch (12) OFF. 6. Controller resumes normal operation. H. TEST PRESSURE SOLENOID ACTIVATION See page 8 for instructions to test solenoid activation. I. TEST STRATIFY FUNCTION
1. Turn on FTB-350A POWER switch (10) (set point = 340°F/171°C). 2. Set FTB-350A PROBE switch (7) to variable. 3. Set HP 690 ALARM switch (12) ON. (a) RELAY POWER indicator (3) illuminates. (b) Rotate VARIABLE knob (9) slowly clockwise until controller indicates DROP. (c) Press Temperature button on controller. Controller should indicate a temperature from one (1) to (4) degrees +/- set point (340°F/171°C). 4. Start a cook on the controller. At the end of the cook (DONE), press the
product button. 5. Let the controller set idle for 30 minutes. 6. At the end of 30 minutes, the STRATIFY indicator (1) will illuminate for
approximately 15 seconds. Controller test is now complete.

F3000 TEST PROCEDURE FOR PITCO FRYERS (18WKS FULL, SG18 FULL, SSH75 FULL, SG6H FULL, 14WKS FULL, 7WKS FULL, 7- 2WKS SPLIT, E18WKS FULL, SE18 17 KW FULL and SE 22KW FULL)
Ensure the controller is set to PITCO using code 7628 in tech mode. With the Controller displaying OFF press and hold the check button until PRODUCT SETUP is displayed. Press the right arrow to tech mode. Enter 7628. Set LOCALE to NON-CE. Press the right arrow. Set system type to PITCO. Press the right arrow. Set ENERGY to ELEC or GAS. Press the right arrow. Set TYPE to fryer type desired. Press the right arrow. Set FRESH OIL to NONE. Press the right arrow. Set WASTE OIL to NONE. Press the right arrow. Press the check button at EXIT.
A. INITIAL TEST SET-UP See page 6 for instructions to run initial test set-up. B. TEST POWER TO FRYER INTERFACE BOARD See page 6 for instructions to test power to fryer interface board. C. TEST MELT-CYCLE FUNCTION See page 6 for instructions to test melt-cycle function. D. TEST CONTROLLING FUNCTION See page 7 for instructions to test controlling function. E. TEST CONTROLLER HIGH LIMIT See page 7 for instructions to test controller high limit. F. TEST PROBE FAILURE MALFUNCTION See page 7 for instructions to test probe failure malfunction. Controller test is now complete.




TEL 1-318-865-1711 FAX (Parts) 1-318-219-7140
FAX (Tech Support) 1-318-219-7135
PRINTED IN THE UNITED STATES SERVICE HOTLINE