YELLOW FLAME DESIGN UNVENTED (VENT-FREE) PROPANE/LP GAS LOG HEATER (Manually-Controlled Models Also Designed Certified as Vented Decorative Appliance)
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer OWNER’S OPERATION AND INSTALLATION MANUAL
18", 24", and 30" Variable ManuallyControlled
Controlled Model
CGD3924PT
Models
CGD3018P CGD3924P CGD3930P
flammable vapors and liquids in the vicinity of this or any other appliance. — WHAT TO DO IF YOU SMELL GAS
formed by a qualified installer, service agency, or the gas supplier.
Save this manual for future reference.
®


Figure 1 - Vent-Free Gas Log Heater LOCAL CODES Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223, also known as NFPA 54*. *Available from: American National Standards Institute, Inc.
1430 Broadway New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269
UNPACKING 1. Remove logs and heater base assembly from carton. Note: Do not pick up heater base assembly by burners. This could damage heater. Always handle base assembly by grate. 2. Remove all protective packaging applied to logs and heater for shipment. 3. Check all items for any shipping damage. If damaged, promptly inform dealer where you bought heater.
Operation This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by realistic dancing, yellow flames. This heater is designed for vent-free operation with flue damper closed. State and local codes in some areas prohibit the use of vent-free heaters. You can operate heater as a vented product by opening flue damper.
Safety Device This heater has a pilot with an Oxygen Depletion Sensor Shutoff System (ODS). The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
Piezo Ignition System This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.

WARNING ICON G 001 WARNING
This heater shall not be installed in a confined space unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible. While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation. Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION The following is exerpts from National Fuel Gas Code. NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation. All spaces in homes fall into one of the three following ventilation classifications: 1. Unusually Tight Contruction; 2. Unconfined Space; 3. Confined Space. The information on pages 5 through 7 will help you classify your space and provide adequate ventilation. Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where: a. walls and ceilings exposed to the outside atmosphere have a continu-
ous water vapor retarder with a rating of one perm or less with open- ings gasketed or sealed and b. weather stripping has been added on openable windows and doors and c. caulking or sealants are applied to areas such as joints around window
and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings. If your home meets all of the three criteria above, you must provide addi- tional fresh air. See Ventilation Air From Outdoors, page 7. If your home does not meet all of the three criteria above, proceed to page 6.
Unconfined Space The National Fuel Gas Code, ANSIZ223.1, 1992, Section 5.3 defines uncon- fined space as having a minimum air volume of 50 cubic feet (127 cubic cm) for each 1000 Btu/Hr input rating of all appliances in the space (cubic feet equals length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms. Confined Space The National Fuel Gas Code, ANSIZ223.1, 1992, Section 5.3 defines confined space as having an air volume of less than 50 cubic feet (127 cubic cm) for each 1000 Btu/Hr input rating of all appliances in the space (cubic feet equals length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms.

Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
Length x Width x Height = cu. ft. (volume of space) Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
Vent-free heater Btu/Hr Gas water heater* Btu/Hr Gas furnace Btu/Hr Vented gas heater Btu/Hr Gas fireplace logs Btu/Hr Other gas appliances* + Btu/Hr Total = Btu/Hr
Example: Gas water heater 40,000 Btu/Hr Vent-free heater + 39,000 Btu/Hr Total = 79,000 Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides
an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
Ventilation Grills Into Adjoining Room,
Or Remove Door into Adjoining
Figure 2 - Ventilation Air from Inside Building
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.
Inlet Air Ventilated Crawl Space
Figure 3 - Ventilation Air from Outdoors

INSTALLING NOTICE A qualified service person must install heater. Follow all local codes.
CHECK GAS TYPE Use only propane gas. If your gas supply is not propane, do not install heater. Call dealer where you bought heater for proper type heater.

Carefully follow the instructions below. This will ensure safe installation into a masonry or U.L. listed manufactured fireplace.
Minimum Wall and Ceiling Clearances (see Figure 4) A. Clearances from the side of the fireplace opening to any combustible wall
should not be less than 16 inches. B. Clearances from the top of the fireplace opening to the ceiling should not be
less than 42 inches.
16" Left and Right
Figure 4 - Minimum Clearance to Wall and Ceiling
42" · Sides

NOTICE
You may use this heater as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, non-combustible material above fire- place opening is not needed. Go to Installing Damper Clamp Accessory for Vented Operation, page 13.
If Not Using Mantel Note: If using a mantel, go to page 11. If not using a mantel, follow the informa- tion on this page.
You must have non combustible material(s) above the fireplace opening. Non combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible material must extend at least 8" up (for all models). If non combus- tible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See chart below and Figure 5 for minimum clearances.
Non-Combustible Requirements for Material Distance (A) Safe Installation
12" or more Non combustible material okay.
Between 8" and 12" 24" or 30" Models: Install fireplace hood acessory (GA6050 or GA6052, see Accessories, page 33). 18" Model: Non combustible material okay.
Less than 8" Non combustible material must be extended to at least 8". See Between 8" and 12", above. If you cannot extend material, you must operate heater with flue damper open.
Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace
Heat Resistant Material

You must have non combustible material(s) above the fireplace opening. Non combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible material must extend at least 8 inches up (for all models). If non combustible material is less than 12", you must install the fireplace hood acces- sory (24" and 30" models only). Even if non combustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See chart below and Figures 6 and 7 for minimum clearances.
Mantel Clearances If you meet minimum clearance between mantel shelf and top of fireplace open- ing, a hood is not required (see Figure 6).
Underside of Mantel Shelf
2 1/2"
All minimum distances are in inches
Log Set 24"/30" Models
20" 241/2" 271/2" 30"
8" 14" 163/4" 181/2" 20" 18" Model
Top of Fireplace Opening
Minimum Non- Combustible Material Height
Distances to Underside of Mantel
Figure 6 - Minimum Mantel Clearances Without Using Hood
If above minimum clearances are not met, you must have a hood. Follow minimum clearances shown in Figure 7 when using hood.

Underside of Mantel Shelf
2 1/2"
All minimum distances are in inches
Minimum Non- Combustible Material 8" Min.
18", 24", 30" Models 20"
Top of Fireplace Opening
Distances to Underside of Mantel
Figure 7 - Minimum Mantel Clearances When Using Hood
Floor Clearances A. If installing appliance on the floor level, you must maintain the minimum
distance of 14" to combustibles (see Figure 8).
14" Min.
Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level
B. If combustible materials are less than 14" to the fireplace, you must install
appliance at least 5" above the combustible flooring (see Figure 9).
5" Min.
Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring

INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION Note: When used as a vented heater, appliance must be installed only in a solid- fuel burning fireplace with a working flue and constructed of non combustible material. If your heater is a manually controlled model, you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode. 1. The fireplace does not meet the clearance to combustibles requirements for vent-free operation. 2. State or local codes do not permit vent-free operation. 3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 33). This will insure vented operation (see Figure 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.
See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.
Chimney Minimum Permanent Height (ft.) Flue Opening (sq. ins.)
6' to 15' 39 sq. inches 15' to 30' 29 sq. inches
Area of Various Standard Round Flues
Diameter (ins.) Area (sq. ins.)
5" 20 sq. inches 6" 29 sq. inches 7" 39 sq. inches 8" 51 sq. inches
Manufactured Fireplace Masonry Fireplace
Continued Figure 10 - Attaching Damper Clamp

1. Apply pipe joint sealant lightly to male threads of the fitting to be threaded into gas regulator. Connect approved flexible gas hose to gas regulator of heater (see Figure 11). IMPORTANT: Hold gas regulator with wrench when connecting flexible gas hose. 2. Locate masonary screws in hardware package. 3. Position heater base assembly in fireplace. 4. Mark screw locations through holes in mounting brackets (see Figure 12, page 15). If installing in a brick-bottom fireplace, mark screw locations in mortar joint of bricks. 5. Remove heater base from fireplace. 6. Drill holes at marked locations using 3/16" drill bit. 7. Attach base assembly to fireplace floor using two masonry screws (in hardware package) (see Figure 12, page 15). 8. Connect to gas supply. See Connecting To Gas Supply, page 15.
Flexible Gas Hose (if allowed by local codes)
Figure 11 - Attaching Flexible Gas Hose to Heater Gas Regulator
Heater Gas Regulator · Fitting

Figure 12 - Attaching Base Assembly to Fireplace Floor
Installation Items Needed Before installing heater, make sure you have the items listed below.
* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 33.
Masonry Screw · Mounting Bracket

The installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.
Figure 13 - External Regulator With Vent Pointing Down
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14, page 17).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
Install sediment trap in supply line as shown in Figure 14, page 17. Locate sedi- ment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
Propane Supply Tank · External Regulator · Vent Pointing Down

A.G.A. Design-Certified Manual Shutoff Valve With 1/8" NPT Tap*
From Gas Meter (5" W.C.** to
Approved Flexible Gas Hose (if allowed by local codes)
10.5" W.C. Pressure)
Figure 14 - Gas Connection
* Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 33. ** Minimum inlet pressure for purpose of input adjustment.
Pressure Testing gas Supply Piping system Test Pressures In Excess Of 1/2 PSIG 1. Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator. 2. Cap off open end of gas pipe where manual shutoff valve was connected.

Test Pressures Equal To or Less Than 1/2 PSIG 1. Close manual shutoff valve (see Figure 15). 2. Pressurize supply piping system by either using compressed air or opening propane supply tank valve. 3. Check all joints from propane supply tank to manual shutoff valve (see Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak. 4. Correct all leaks at once.
Pressure Testing Heater Gas Connections 1. Open manual shutoff valve (see Figure 15). 2. Open propane supply tank valve. 3. Make sure control knob of heater is in the OFF position. 4. Check all joints from manual shutoff valve to control valve (see Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak. 5. Correct all leaks at once. 6. Light heater (see Operating Heater, pages 20 through 22 [manually-controlled models] or pages 22 through 24 [thermostatically-controlled model]). Check all other internal joints for leaks. 7. Turn off heater (see To Turn Off Gas to Appliance, page 21 [manually-con- trolled models]) or page 24 [thermostatically-controlled model].).
OFF POSITION
Figure 15 - Manual Shutoff Valve
Manual Shutoff Valve Propane Supply Tank
Thermostat Gas Valve or Control Valve Location
Figure 16 - Checking Gas Joints
Open · Manual Shutoff Valve · Closed

Continued WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury.
Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with heater. 1. Locate pegs on the bottom of back log (#1). Slide these pegs into the holes in the grate base behind the burner (see Figure 17). 2. Place the base of the middle log (#2) in the U-shaped slots of the grate base in front of the back log. The cutout on the right of the middle log should fit over the burner (see Figure 18). Make sure the front of the middle log is resting on the tabs of the grate base and the cutout area is centered over the burner “U” bend. 3. Locate the recesses on the back of the front log (#3). Fit these recesses between the posts of the grate base (see Figure 19). 4. Locate the notches in the bottom of the crossover log (#4). Place the crossover log on top of the middle log and front log. Make sure the notches of the cross- over log lines up with rectangular knobs on top of the middle and front logs (see Figure 20).
Peg Hole in Grate Base
Figure 17 - Installing Back Log (#1) Figure 18 - Installing Middle Log (#2)
Crossover Log (#1) Notches
Figure 19 - Installing Front Log (#3) Figure 20 - Installing Crossover Log (#4)

HEATER
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
Note: Homeowners generally prefer to operate their heater with the chimney damper closed. This will put all the heat into the room. However there may be times you will desire the full flames of the Hi heat setting but will find the heat output excessive. You can open the chimney damper (if you have one) fully or partially to release some of the heat. WARNING: Damper handle will be hot if heater has been running.
Control Knob Ignitor Button
PILOT
OFF
LO
Figure 21 - Control Knob and Ignitor Button Location 4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the next step.

Figure 22 - Pilot
The variable control valve can be set to any heat setting and flame height desired, by simply turning the control knob until that setting is attained. Even the lowest setting provides realistic, dancing yellow flames. Selecting higher settings produces greater heat output. This results in increased heating comfort.
TO TURN OFF GAS TO APPLIANCE Shutting Off Heater 1. Press in and turn control knob clockwise Clockwise to the HIGH position. 2. Turn control knob clockwise Clockwise to the pilot position. 3. Press in control knob and turn clockwise Clockwise to the OFF position.
Shutting Off Burners Only (pilot stays lit) 1. Turn control knob clockwise Clockwise to the HIGH position. 2. Press in and turn control knob clockwise Clockwise to the pilot position.
Thermocouple · Ignitor Electrode · Pilot Burner

MANUAL LIGHTING PROCEDURE 1. Follow steps 1 through 5 under Lighting Instructions, pages 20 and 21. 2. Depress control knob and light pilot with match. 3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow step 8 on page 21.
OPERATING
HEATER Thermostatically-
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS
Note: Homeowners generally prefer to operate their heater with the chimney damper closed. This will put all the heat into the room. However there may be times you will desire the full flames of the Hi heat setting but will find the heat output excessive. You can open the chimney damper (if you have one) fully or partially to release some of the heat. WARNING: Damper handle will be hot if heater has been running.

HI
LO
Control Knob Ignitor Button
Figure 23 - Control Knob and Ignitor Button Location
Figure 24 - Pilot

HEATER Thermostatically-
Shutting Off Heater 1. Turn control knob clockwise Clockwise to the OFF position.
Shutting Off Burners Only (pilot stays lit) 1. Turn control knob clockwise Clockwise to the PILOT position.
THERMOSTAT CONTROL OPERATION
The thermostat control knob can be set to any comfort level between Hi and Lo. The thermostat will gradually modulate the heat output and flame height from higher to lower settings, or pilot, in order to maintain the comfort level you select. The ideal comfort setting will vary by household depending upon the amount of space to be heated, the output of the central heating system, etc.
Check pilot flame pattern and burner flame patterns often.
PILOT FLAME PATTERN Figure 25 shows a correct pilot flame pattern. Figure 26 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down.
Figure 25 - Correct Pilot
Figure 26 - Incorrect Pilot
Flame Pattern If pilot flame pattern is incorrect, as shown in Figure 24
Thermocouple Pilot Burner · Pilot Burner Thermocouple · Flame Pattern

listed in order of
operation.
POSSIBLE CAUSE
REMEDY
When ignitor button is pressed, there is no spark at ODS/pilot

POSSIBLE CAUSE
REMEDY
When ignitor button is pressed, there is spark at ODS/pilot but no ignition
ODS/pilot lights but flame goes out when control knob is released
B) Clean ODS/pilot (see Cleaning and Mainte- nance, page 25) or replace ODS/pilot assembly

POSSIBLE CAUSE
REMEDY
Burner does light after ODS/pilot is lit
Delayed ignition of burner
Burner backfiring during combustion
Slight smoke or odor during initial operation
Moisture/condensa- tion noticed on windows
Heater produces a whistling noise when burner is lit

WARNING If you smell gas
POSSIBLE CAUSE
REMEDY
Heater produces a clicking/ticking noise just after burner is lit or shut off
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
Gas odor during combustion
Logs set cycles to pilot, but room temperature drops to a lower than ideal level before log set comes back on

If your log set cycles to pilot, but the room temperature drops to a lower than ideal comfort level before the log set comes back on, you may want to reposition the thermostat sensing bulb.
The thermostat sensing bulb is located near the gas valve assembly on the mounting bracket. This location allows the thermostat to keep the room temperature at an ideal comfort level for most fireplace applications. For positioning the thermostat sensing bulb elsewhere, an adhesive-backed mounting clip has been provided.
Figure 27 - Location of Gas Valve Assembly and Thermostat Sensing Bulb
Figure 28 - Adhesive-backed Mounting Clip
Retaining Clamp Thermostat Sensing Bulb
Figure 29 - Removing Thermostat Sensing Bulb

OF THERMOSTAT SENSING BULB For Masonry and
Figure 30 - Locating Thermostat Sensing Bulb on Masonry Fireplace
If you have a factory-built metal fireplace, see Figure 31 for location.
¢ Adhesive-backed Mounting Clip
Q
Q
Figure 31 - Locating Thermostat Sensing Bulb on Factory-built Metal Fireplace
If your fireplace has glass doors, position sensing bulb directly behind door gap on right bottom side (see Figure 32).
Q
Q
Q
Q
Q
Q
Q ¢
Q
Figure 32 - Installing Thermostat Sensing Bulb behind Glass Doors
5. The mounting clip must be a minimum of 3" from bottom of fireplace to prevent crimping of capillary. Once you have decided on a location, clean the area thoroughly. Remove the paper backing from the adhesive on back of mounting clip. Press the clip into the new location so that the thermostat sensing bulb will be positioned vertically with the capillary at the bottom (see Figure 33). Slide the thermostat sensing bulb into the clip. IMPORTANT: Do not crimp capillary.
Do Not Crimp Capillary
Figure 33 - Positioning the Thermostat Sensing Bulb in the Vertical
Position with the Capillary at the Bottom

You may have further questions about installation, operation, or troubleshooting. If so, contact DESA International’s Technical Service Department at 1-800-DESA LOG (1-800-337-2564).
SPECIFICATIONS 18" Model 24" Models 30" Model
Btu (Variable) 16,000/30,000 20,000/39,000 20,000/39,000
Type Gas Propane Only Propane Only Propane Only
Ignition Piezo Piezo Piezo
Manifold Pressure 8.0" W.C. 8.0" W.C. 8.0" W.C.
Inlet Gas Pressure (in. of water)
Maximum 14" 14" 14" Minimum* 11" 11" 11"
Shipping Weight 28 lbs. 30 lbs. 32 lbs.
* For the purpose of input adjustment
You may feel your gas pressure is too low or gas quality is bad. If so, contact your local propane gas supplier.

Parts Under Warranty Contact authorized dealers of this product. If they can’t supply original replace- ment part(s), call DESA International’s Technical Service Department at 1-800-DESA LOG (1-800-337-2564).
When calling DESA International, have ready
Parts Not Under Warranty Contact authorized dealers of this product. If they can’t supply original replace- ment part(s), call DESA International’s Parts Department at 1-800-972-7879 for referral information.
When calling DESA International, have ready
These Parts Centrals are privately owned businesses. They have agreed to support our customer’s needs by providing original replacement parts and accessories.
Baltimore Electric 1348 Dixwell Avenue Hamden, CT 06514 1-800-397-7553 203-248-7553 Parts Department
Washer Equipment Co. 1715 Main Street Kansas City, MO 64108 KS, MO, AR 816-842-3911
Dayton Hardware P.O. Box 275 North Dayton Station Dayton, OH 45404 All States 513-258-3721 OH 1-800-762-3426
East Coast Energy Products 833 Broadway W. Long Branch, NJ 07764 908-870-8809 1-800-755-8809
Portable Heater Parts 342 N. County Rd. 400 East Valparaiso, IN 46383 All States 219-462-7441 1-800-362-6951
Halco Enterprises 208 Carter Drive, Unit 21 West Chester, PA 19382 215-696-2670 1-800-368-0803
FBD 601 Hope Street Bowling Green, KY 42101 502-796-8406 1-800-654-8534
Tarantin Tank Co. P.O. Box 6129 Freehold, NJ 07728 908-780-9340 1-800-922-0724
LA Porte’s Parts & Service 2444 N. 5th Street Hartsville, SC 29550 803-332-0191 Parts Department
Four Flags Power Products 1115 Stateline Road Niles, MI 49120 616-684-2697 Parts Only
Albany Ladder 1586-90 Central Avenue Albany, NY 12205 NY, MA, VT 518-869-5335 1-800-354-7368
Cans Unlimited, Inc. P.O. Box 645 Taylor, SC 29687 All States 803-879-3009 1-800-845-5301
Master Service Center 1184 Wilson NW Walker, MI 49504 616-791-4760 1-800-446-1446

ACCESSORIES Purchase these fireplace accessories from your local dealer. If they can not supply these accessories, call DESA International’s Sales Department at 1-800-472-7879 for referral information. You can also write to the address listed on the back page of this manual.
MANUAL SHUTOFF VALVE - GA5010 For all models. Manual shutoff valve with 1/8" NPT tap. Fits 1/2" NPT pipe.
BLACK FIREPLACE HOOD - GA6050 For all models. Helps deflect heat away from mantel or wall above fireplace.
BRASS FIREPLACE HOOD - GA6052 For all models. Helps deflect heat away from mantel or wall above fireplace.
DAMPER CLAMP - GA6080 For variably controlled models. Permanently opens chimney flue damper for vented operation.
LAVA ROCK - GA6060 For all models. Order when additional rock is desired. (3 lb. bag)



This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 33 of this manual. PARTS LIST
KEY CGD3018P CGD3924P CGD3930P NO. PART NUMBER PART NUMBER PART NUMBER DESCRIPTION QTY.
1 103008-02 103008-01 103008-03 Back Log (#1) 1 2 103009-02 103009-01 103009-03 Middle Log (#2) 1 3 103010-02 103010-01 103010-03 Front Log (#3) 1 4 103011-02 103011-01 103011-03 Crossover Log (#4) 1 5 102774-04BR 102774-01BR 102774-03BR Painted Base Assembly 1 6 102844-02 102844-01 102844-01 Lower Bracket 1 7 102966-02 102966-01 102966-01 Upper Bracket 1 8 098867-10 098867-10 098867-10 Gas Regulator 1 9 102798-01 102798-01 102798-01 Inlet Tube 1 10 102779-04 102779-02 102779-02 Outlet Burner Tube 1 11 099056-19 099056-17 099056-17 Burner Orifice Injector 1 12 102843-01 102843-01 102843-01 Burner Clip 1 13 102980-01 102772-01 102772-01 Burner 1 14 102568-08 102568-06 102568-06 Control Valve 1 15 098508-01 098508-01 098508-01 Valve Retainer Nut 1 16 098354-01 098354-01 098354-01 Control Knob 1 17 102445-01 102445-01 102445-01 Piezo Ignitor 1 18 099387-08 099387-08 099387-08 Pilot Tube 1 19 098271-07 098271-07 098271-07 Ignitor Cable 1 20 099059-02 099059-02 099059-02 ODS Pilot 1 20-1 099594-01 099594-01 099594-01 Ignitor Electrode 1 20-2 098593-01 098593-01 098593-01 Thermocouple 1 21 M11084-38 M11084-38 M11084-38 Regulator Screw 2 22 098304-03 098304-03 098304-03 Black Screw, PPH #8-18 9 23 098276-01 098276-01 098276-01 Hex Head Plug, 1/8 NPT 1 24 098249-01 098249-01 098249-01 Nut, M5 2 25 099553-01 099553-01 099553-01 Pilot Shield 1
100563-01 100563-01 100563-01 Warning Plate 1 101055-02 101055-02 101055-02 Lighting Instructions Plate 1 100565-01 100565-01 100565-01 Warning Plate Fastener 1 100639-01 100639-01 100639-01 Caution Decal 1 101449-04 101449-04 101449-04 Control Position Decal 1 101137-02 101137-02 101137-02 Hardware Kit 1 101416-18 101416-18 101416-18 Information Video 1 GA6060 GA6060 GA6060 Lava Rock 1



This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 33 of this manual. PARTS LIST
KEY CGD3924PT NO. PART NUMBER DESCRIPTION QTY.
1 103008-01 Back Log (#1) 1 2 103009-01 Middle Log (#2) 1 3 103010-01 Front Log (#3) 1 4 103011-01 Crossover Log (#4) 1 5 102774-05BR Painted Base Assembly 1 6 102844-01 Lower Bracket 1 7 102966-01 Upper Bracket 1 8 098867-10 Gas Regulator 1 9 102981-01 Inlet Tube 1 10 102983-02 Outlet Burner Tube 1 11 099056-17 Burner Orifice Injector 1 12 102843-01 Burner Clip 1 13 102772-01 Burner 1 14 101329-19 Thermostat Gas Valve Assembly 1 15 102979-01 Thermostat Bracket 1 16 098544-01 Thermobulb Clip 1 17 102445-01 Piezo Ignitor 1 18 099387-09 Pilot Tube 1 19 098271-07 Ignitor Cable 1 20 099059-02 ODS Pilot 1 20-1 099594-01 Ignitor Electrode 1 20-2 098593-01 Thermocouple 1 21 M11084-38 Regulator Screw 2 22 098304-03 Black Screw, PPH #8-18 13 23 099553-01 Pilot Shield 1 24 098249-01 Nut, M5 2 25 099211-01 Hex Screw, 10-16 x 2.50 2
100563-01 Warning Plate 1 101054-01 Lighting Instructions Plate 1 100565-01 Warning Plate Fastener 1 100639-01 Caution Decal 1 101137-02 Hardware Kit 1 101416-18 Information Video 1 GA6060 Lava Rock 1



Serial No.
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
DESA International warrants this product to be free from defects in materials and components for one (1) year from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MER- CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO ONE (1) YEAR ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004
102991-01 Rev. A 06/96