Evco S.p.A. • Codice 104K802E04 EVK802 Digital controller for quick coolers management version 1.04

E ENGLISH 1 PREPARATIONS 1.1 Important Please read these instructions carefully prior to installation and use, and follow all the precautions for installation and electrical connections; keep these instructions with the device for future consultation. 1.2 Installation Per panel, using the snap-on brackets supplied; the dimensions are given in mm.

  • ensure that the voltage, frequency and operational power of the device are compatible with the local power supply
  • disconnect the power prior to proceeding with any kind of maintenance operation
  • do not use the device as a safety device
  • for repairs and any information relating to the device, contact the Evco dealer network. 2 USER INTERFACE 2.1 Introductory information The device has the following operational states:
  • "on" (the device is switched on and an operating cycle is running)
  • "stand-by" (the device is switched on but no operating cycle is running)
  • "off" (the device is not switched on). If power is interrupted during a timed blast chilling operation, when power is restored, chilling will continue from the time point at which the interruption occurred (with a maximum error of 10 minutes). If power is interrupted during a set-temperature blast chilling operation, when power is restored, chilling will start again from the beginning. If power is interrupted during a storage operation, when power is restored the storage operation will be reset. If power is interrupted while in "stand-by" mode, when power is restored the device will be in the same state. 2.2 The display In the "on" state, during normal operation, the display shows:
  • the amount of time remaining for a timed blast chilling operation, if this is ongoing
  • the temperature measured by the pin probe if a set-temperature chilling operation is ongoing
  • the temperature of the cabinet, if storage is ongoing. In "stand-by" mode, during normal operation, the display shows the temperature of the cabinet for ½ s every 3 s. 2.3 Defrosting and the evaporator fan The service controlled by relay K2 depends on parameter u0:
  • if u0 = 0, the service controlled by relay K2 will be defrosting (electrical defrosting; the evaporator fan is not controlled)
  • if u0 = 1, the service controlled by relay K2 will be evaporator fan (defrost stopping the compressor): - during blast chilling, operation of the evaporator fan depends on
  • press

within 60 s: in the case of a timed cycle, the display will show the duration of the blast chilling step (in minutes) or in the case of a set-temperature cycle, the set target tempera- ture •press

  • 3.4 Set-temperature positive blast chilling and storage cycle To start the cycle:
  • ensure the device is in "stand-by" mode and no procedures are running
  • press

Prior to starting the cycle: •the test is run in order to check correct pin probe insertion (see para- graph 3.6): - if the outcome of the test is positive, the cycle will be started - if the outcome of the test is negative, the cycle will be started in timed

  • To access the first level:
  • ensure the device is in "stand-by" mode and no procedures are running
  • press
  • for 4 s: the display will show “PA” To access the second level:
  • access the first level
  • press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value r1, r2, r3 or r4 is restored) •press

to select "PoS" and ensure the LED

  • mode During chilling:
  • the display shows the temperature measured by the pin probe
  • the LED
within 15 sthe display will show the blast chilling endpoint temperature •press

to select “PA” • press

  • within 15 s: the cycle will be activated. 3.2 Timed positive blast chilling and storage cycle To start the cycle:
  • ensure the device is in "stand-by" mode and no procedures are running
  • press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r3 is reset) •press

  • is on
  • the parameter r4 sets the chilling endpoint temperature
  • the parameter r6 sets the maximum chilling time duration
  • the parameter r8 sets the operational setpoint
  • press
  • press

within 15 s to set “-19” • press

or leave for 15 s • press

for4 sthe display will show “CA1”. To select a parameter: • press

: the display will show the chilling operational setpoint (in °C/°F) and the LED

to select "PoS" and ensure the LED

  • several times to: - display the maximum residual chilling time remaining - display the message "nEg" - flashing display the cabinet temperature - exit the procedure, or leave for 15 s. If the temperature measured by the pin probe reaches the chilling endpoint temperature prior to expiry of the maximum chilling time duration:
  • the device will switch to storage mode
  • the display will show the message "End"
  • the buzzer will sound for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message "End". If the temperature measured by the pin probe does not reach the chilling endpoint temperature prior to expiry of the maximum chilling time duration:
  • chilling will continue
  • the LED
within 15 sthe display will show the duration of the blast chilling step (in minutes) •press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r7 is restored) •press

To modify a parameter• press
DIMENS. MINIMUM TYPICAL MAXIMUM A 71,0 71,0 71,8 B 29,0 29,0 29,8

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r1 is restored) •press

  • press

within 15 s • press

within 15 s: the cycle will be activated. Also look at parameters rb and E0. Prior to starting the cycle: •the test is run in order to check correct pin probe insertion (see para- graph 3.6): - if the outcome of the test is positive, the cycle will be started - if the outcome of the test is negative, the cycle will be started in timed

or leave for 15 s. To exit the procedure: • press

: the display will show the chilling operational setpoint (in °C/°F) and the LED

  • for 4 s, or leave for 60 s. IInterrupt the device power supply after altering the parameters. 4.3 Resetting configuration parameter default values
  • ensure the device is in "stand-by" mode and no procedures are running
  • press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r7 is restored) •press

  • within 15 s: the cycle will be activated. Also look at parameters rb and E0. During chilling:
  • the display shows the residual chilling time remaining
  • the LED
  • mode. During chilling:
  • the display shows the temperature measured by the pin probe
  • the LED
for 4 sthe display will show “PA” • press
  • is on
  • the parameter r3 sets the blast chilling endpoint temperature
  • the parameter r5 sets the maximum chilling time duration
  • the parameter r7 sets the operational setpoint
  • press
  • press

within 15 s to set “743” • press

  • is on
  • parameter r1 sets the chilling time duration
  • parameter r7 sets the operational setpoint
  • press

or leave for 15 s • press

per 4 sthe display will show “dEF” • press
  • will be on
  • the buzzer will sound
  • press

will flash and the LED

  • several times to: - display the message "PoS" - display the cabinet temperature - exit the procedure, or leave for 15 s. Once the chilling period has elapsed:
  • the device switches to storage mode
  • the display shows the message "End"
  • the buzzer sounds for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message "End". During storage:
  • the display shows the cabinet temperature
  • the LEDs
  • several times to: - display the maximum residual chilling time remaining - display the message "PoS" - display the flashing cabinet temperature - exit the procedure, or leave for 15 s. If the temperature measured by the pin probe reaches the chilling endpoint temperature prior to expiry of the maximum chilling time duration:
  • the device will switch to storage mode
  • the display will show the message "End"
  • the buzzer will sound for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message "End". If the temperature measured by the pin probe does not reach the chilling endpoint temperature prior to expiry of the maximum chilling time duration:
  • chilling will continue
  • the LED
  • press

within 15 s to set “149” • press

several times to: - mute the buzzer - display the time elapsed since the maximum chilling time expired - display the cabinet temperature - display the message "nEg" - exit the procedure, or leave for 15 s •when the temperature measured by the pin probe reaches the chill- ing endpoint temperature: - the device will switch to storage mode - the LED

  • Recommendations for installation:
  • the maximum depth with screw terminal blocks is 59.0
  • the maximum depth with removable terminal blocks is 83.0
  • the panel thickness must not exceed 8,0 mm
  • ensure that the operating conditions (operating temperature, humidity, etc.) are within the limits indicated in the technical data sheets
  • do not install the device near to any sources of heat (heating elements, hot air conduits, etc.), equipment containing powerful magnets (large diffusers, etc.), areas affected by direct sunlight, rain, humidity, excessive dust, mechanical vibration or shock
  • in compliance with safety regulations, the device must be installed correctly, and in such a way as to protect against any contact with electrical parts; all safety devices must be fixed so that they cannot be removed without the use of tools. 1.3 Electrical connections With reference to the electrical circuit diagram:
  • the service controlled by relay K2 depends on parameter u0
  • the serial port (available on request) is the port used for communicating with the monitoring system (by means of a serial interface, via TTL, using the MODBUS communication protocol) or with the programming key; the port must not be used for both purposes simultaneously.
5.1 Signals LEDMESSAGE timed chilling LED • if on and the LED is off, a timed chilling operation is ongoing • if on and the LED is also on, a post timed-chilling storage operation is ongoing • if flashing, a timed chilling and storage cycle will have been selected set-temperature chilling LED • if on and the LED is off, a set-temperature chilling operation is ongoing • if on and the LED is also on, a post set-temperature chilling storage operation will be ongoing • if flashing, a set-temperature chilling and storage cycle will have been selected • if it is on for ½ s every 3 s, the test to verify correct pin probe insertion will be ongoing • if flashing, and the LED is on, then the test to verify correct pin probe insertion will have had a negative outcome (parameters rc and rd) and the cycle will have been started in timed mode; see paragraph 3.6 • if flashing, and the LED is on, the chilling stage will have had a negative outcome, and so this will continue • if flashing, and the LEDs and are on, the chilling stage will have had a negative outcome, the device will have switched to storage mode and this will be ongoing storage LED • if on, a storage operation will be ongoing • if flashing, then the operational setpoint will be being modified while a storage operation is ongoing (see paragraph 4.1) °C °alarm LED if on, an alarm is ongoing degree Celsius LED if on, the unit of measurement for temperature is degrees Celsius (parameter P2) Fdegree Fahrenheit LED if on, the unit of measurement for temperature is degrees Fahrenheit (parameter P2) decimal pointminute LED if flashing, the unit of measurement of magnitude displayed is the minute CODEMESSAGE

parameter F0 - during storage, operation of the evaporator fan depends on param-

will continue to stay on - the display will show the message "End" - the buzzer will sound for the period of time set by parameter AA - press any key to mute the buzzer; press once more to cancel the

will continue to flash and the LED

  • eter F2 - the evaporator fan is started during defrosting. In "stand-by" mode it is only possible to activate manual defrosting; if the service controlled by relay K2 is the evaporator fan (parameter u0 = 1), during defrosting the evaporator fan will be switched on, and during drip-draining, this will be switched off. To start defrosting in manual mode:
  • ensure no procedure is running
  • press
  • are on
  • the parameter r9 sets the operational setpoint
  • press

several times to: - display the message "PoS" - exit the procedure, or leave for 15 s. To interrupt the cycle: •press

  • message "End". During storage:
  • the display shows the cabinet temperature
  • if chilling had a positive outcome, the LEDs
  • will be on
  • the buzzer will sound
  • press

will flash and the LED

  • for 2 s. 3.3 Timed negative chilling and storage cycle To start the cycle:
  • ensure the device is in "stand-by" mode and no procedures are running
  • press

and will be on; if chilling had a negative outcome, the LEDs

several times to: - mute the buzzer - display the time elapsed since the maximum chilling time expired - display the cabinet temperature - display the message "PoS" - exit the procedure, or leave for 15 s •when the temperature measured by the pin probe reaches the chill- ing endpoint temperature: - the device switches to storage mode - the LED

will be on and the LED

  • for 4 s. Defrosting is never activated during blast-chilling. Defrosting occurs periodically during storage; it is possible to start defrosting manually. 2.4 Viewing the status of the compressor and the evaporator fan To view the compressor status:
  • ensure no procedure is running
  • press
  • will flash
  • the parameter rA sets the operational setpoint
  • press

several times to: - display the message "nEg" - exit the procedure, or leave for 15 s. To interrupt the cycle: •press

to select "nEg" and ensure the LED

within 15 sthe display will show the duration of the blast chilling step (in minutes) •press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r2 is restored) •press

  • for2 s. 3.6 Test to check correct pin probe insertion Set-temperature cycles are preceded by a test step in order to check correct pin probe insertion. The test has two stages:
  • if the outcome of the first stage is positive, the second will not be run
  • if the outcome of the first stage is negative, the second will be run. The outcome of the first stage is positive if "the temperature measured by the pin probe - the temperature of the cabinet" is greater than the value set by parameter rc at least 3 times out of 5 (the comparison is made every 10 s); if parameter rc is set to 0, neither the first nor second stages will be run. The outcome of the second stage is positive if the difference "temperature measured by the pin probe - temperature of the cabinet" is greater by at least 1ºC/1ºF (with respect to the previous comparison) at least 6 times out of 8 (the comparison is made every "rd/8 s"). If the outcome of the test is positive:
  • the cycle will be activated. the cycle will be activated:
  • the cycle will be started in timed mode
  • the LED

: the display will show the first available label: - if the display shows "C-1", the compressor will be switched-on - if the display shows "C-0", the compressor will be switched off - if the display shows "C-P", compressor protection will be ongoing

will stay on - the display will show the message "End" - the buzzer will sound for the period of time set by parameter AA - press any key to mute the buzzer; press once more to cancel the

will continue to flash and the LED

: the display will show the chilling operational setpoint (in °C/°F) and the LED

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r8 is restored) •press

  • (parameters C0, C1, C2 and i7). To view the status of the evaporator fan:
  • ensure no procedure is running
  • press
  • message "End". During storage:
  • the display shows the cabinet temperature
  • if chilling had a positive outcome, the LEDs
  • within 15 s: the cycle will be activated. Also look at parameters rb and E0. During chilling:
  • the display shows the residual chilling time remaining
  • the LED

twice: the display will show the first available label: - if the display shows "F-1", the evaporator fan will be switched on - if the display shows "F-0", the evaporator fan will be switched off - if the display shows "F-P", then evaporator fan deferred activation will

and will be on; if chilling had a negative outcome, the LEDs

will be on and the LED

  • will flash
  • the parameter r9 sets the operational setpoint
  • press
  • is on
  • parameter r2 sets the chilling time duration
  • parameter r8 sets the operational setpoint
  • press

be ongoing (parameter F8). To exit the procedure: • press

several times to: - display the message "PoS" - exit the procedure, or leave for 15 s. To interrupt the cycle: •press

  • until the display shows the ongoing status value (see paragraph 2.2), or leave for 15 s. If the service controlled by relay K2 is defrosting (parameter u0 = 0), labels "F-1", "F-0" and "F-P" will not be displayed. 2.5 Buzzer mute
  • ensure no procedure is running
  • press any key (the first key press does not trigger the associated effect). 3 OPERATIONAL CYCLES 3.1 Introductory information The device has the following operational cycles:
  • timed positive chilling and storage
  • timed negative chilling and storage
  • set-temperature positive chilling and storage
  • set-temperature negative chilling and storage. Set-temperature cycles are preceded by a test step in order to check correct insertion of the pin probe (see paragraph 3.6). To re-start using the same settings as the last cycle run:
  • ensure that the device is in "stand-by" mode, that no procedures are running and that another cycle has not been selected
  • press
  • several times to: - display the message "nEg" - display the cabinet temperature - exit the procedure, or leave for 15 s. Once the chilling period has elapsed:
  • the device switches to storage mode
  • the display shows the message "End"
  • the buzzer sounds for the period of time set by parameter AA
  • press any key to mute the buzzer; press once more to cancel the message "End". During storage:
  • the display shows the cabinet temperature
  • the LEDs
  • for2 s. 3.5 Set-temperature negative chilling and storage cycle To start the cycle:
  • ensure the device is in "stand-by" mode and no procedures are running
  • press
  • will flash. If power is interrupted during the test, when power is restored, the test will start again from the beginning. 4 SETTINGS 4.1 Temporary setting of operational setpoint during storage
  • ensure the device is in "stand-by" mode and no procedures are running
  • press

to select "nEg" and ensure the LED

within 15 sthe display will show the blast chilling endpoint temperature •press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r4 is restored) •press

  • are on
  • the parameter rA sets the operational setpoint
  • press

: the display will show the chilling operational setpoint (in °C/°F) and the LED

: the LED

  • Points to note for connecting to the electricity supply
  • do not use electric or pneumatic screw-wrenches on the terminal board
  • if the device has been moved from a cold to a warm environment, condensation may have formed inside; please wait approx. one hour prior to switching on

several times to: - display the message "nEg" - exit the procedure, or leave for 15 s. To interrupt the cycle: •press

within 15 s to change the value (the setting re- mains active until another cycle is selected, when the value assigned by parameter r8 is restored) •press

or leave for 15 s. The setting remains active until another operational cycle is selected, when the value assigned by parameter r9 or ra is restored. 4.2 Setting the configuration parameters The parameters are arranged on two levels.

for 2 s.

within 15 s: the cycle will be activated. Also look at parameters rb and E0.

2 sthe display will show the label of the last cycle run
Show 37 more labels / short text on this page
and · or · is flashing •press · or · or · or · and · is flashing •press · will flash •press · or · or · or · or · and · will flash •press · or · and · or · and · or · and · and · and · is flashing •press · or · will flash •press · or · and · and · is flashing •press · or · and · will flash •press · will flash •press · within15 s •press · or · or
Page 2 of the EVCO Digital Controller (EVK802) user manual — 104K802E04
Page 2 · click to enlarge
Page 2
  • operation will continue Consequences if the error occurs during a storage operation:
  • parameter C11 is set to 0, the compressor activity will depend on parameters C4, C5 and C6
  • if parameter C11 is set to 1, the pin probe will function as the cabinet probe and the storage operation will continue Pr2 Pin probe error Remedies:
  • the same as for the previous case, but in relation to the pin probe Consequences if the error occurs while in "stand-by" mode:
  • only timed operation cycles will be allowed to start Consequences if the error occurs during a timed chilling operation:
  • chilling will continue Consequences if the error occurs during a set-temperature chilling operation:
  • chilling will continue in timed mode Consequences if the error occurs during storage mode:
  • storage will continue 8 TECHNICAL DATA 8.1 Technical data Case: grey self-extinguishing. Front panel protection classification (use copper conductors only): IP 65. Connections: Screw terminal blocks (power supply, inputs and outputs), 6 pin connector (serial port; available on request); extractable terminal block (power supply, inputs and outputs) available on request. Operating temperature: from 0 to 55 ºC (10 ... 90% relative humidity, without condensation). Power supply: 230 VAC, 50/60 Hz, 3 VA (nominal); 115 VAC or 12-24 VAC/DC or 12 VAC/DC by request. Insulation class: 2. Alarm buzzer: integrated. Sensor inputs: 2 (cabinet probe and pin probe) for PTC/NTC probes. Digital inputs: 1 (door switch/multifunction) for NA/NC contact (clean contact, 5 V 1 mA). Sensor range: from -50.0 to 150.0 ºC for PTC probes, from -40.0 to 105.0 ºC for NTC probes. Sensitivity: 0.1ºC/1ºC/1ºF. Digital outputs: 2 relays:
r7 -99,0 99,0 °C/°F (1) 0,0 positive blast chilling operational setpoint (cabinet temperature) i2 -1 120 min 30 door switch input alarm activation delay (solo se i0 = 0 o 1) r8 -99,0 99,0 °C/°F (1) -40,0 negative blast chilling operational setpoint (cabinet temperature) -1= the alarm will not sound r9 -99,0 99,0 °C/°F (1) 2,0 post positive blast chill storage operational setpoint (cabinet temperature) i3 -1 120 min 15 door switch input activation effect maximum duration (only if i0 = 0 or 1) rA -99,0 99,0 °C/°F (1) -20,0 post negative blast chill storage operational setpoint (cabinet temperature) -1= the effect will last until the input will be disabled rb 0 2 - - - 1 kind of cycle enabled i7 0 120 min 0 compressor protection deactivation compressor delay (only if i0 = 2) 0 = positive chilling PARAM. MIN. MAX. M.U. DEF. DIGITAL OUTPUTS 1 = positive chilling and negative chilling u0 0 1 - - - 1 service controlled by relay K2 (see paragraph 2.3) 2 = negative chilling 0 = defrosting rc 0,0 99,0 °C/°F (1) 5,0 "temperature detected by the pin probe - temperature of the cabinet" difference for the first stage of the 1 = evaporator fan test to check correct pin probe insertion (see paragraph 3.6) PARAM. MIN. MAX. M.U. DEF. SERIAL NETWORK (MODBUS) 0 = test will not be performed (neither the first nor second stages) LA 1 247 - - - 247 device address rd 1 99 s 60 duration of the second stage of the test to check correct pin probe insertion (see paragraph 3.6) Lb 0 3 - - - 2 baud rate PARAM. MIN. MAX. M.U. DEF. COMPRESSOR PROTECTION 0 = 2.400 baud C0 0 240 min 0 operational cycle deferred compressor start-up; deferred compressor power restoration also follow1 = 4.800 baud ing a power interruption during an operational cycle 2 = 9.600 baud C1 0 240 min 5 minimum elapsed time period between two consecutive compressor start-up operations 3 = 19.200 baud C2 0 240 min 3 minimum compressor shut-down time LP 0 2 - - - 2 parity C3 0 240 s 0 minimum compressor start-up time 0 = none (no parity) C4 0 240 min 10 storage cabinet probe error compressor shut-down duration; see also C5 and C6 (only if C11 = 0) 1 = odd C5 0 240 min 10 positive storage cabinet probe error compressor start-up duration; see also C4 (only if C11 = 0) 2 = even C6 0 240 min 20 negative storage cabinet probe error compressor start-up duration; see also C4 (only if C11 = 0) PARAM. MIN. MAX. M.U. DEF. ENABLING C11 0 1 - - - 0 pin probe operation during cabinet probe error E0 0 3 - - - 1 quantity modifiable quickly before starting the cycle 0 = pin probe 0 = no quantity IF THE ERROR OCCURS IN "STAND-BY" MODE - it will not be possible to start any of the cycles 1 = if you have selected a timed chilling cycle, the chilling duration IF THE ERROR OCCURS DURING A TIMED OR SET TEMPERATURE BLAST CHILLING OPERATION - the if you have selected a set-temperature chilling cycle, the chilling end-point temperature cycle will be interrupted 2 = if you have selected a timed chilling cycle, the chilling duration and the chilling operational IF THE ERROR OCCURS DURING A STORAGE OPERATION - compressor activity will depend on setpoint parameters C4, C5 and C6 if you have selected a set-temperature chilling cycle, the chilling operational setpoint 1 = both pin probe and cabinet probe 3 = if you have selected a timed chilling cycle, the chilling duration and the chilling operational IF THE ERROR OCCURS WHILE IN "STAND-BY" MODE - the pin probe will operate as a cabinet probe setpoint and it will only be possible to start timed cycles if you have selected a set-temperature chilling cycle, the chilling end-point temperature and the IF THE ERROR OCCURS DURING TIMED BLAST CHILLING - the pin probe will operate as a cabinet chilling operational setpoint probe and chilling will continue E9 0 1 - - - 1 reserved IF THE ERROR OCCURS DURING SET-TEMPERATURE BLAST CHILLING - the pin probe will operate as (1) the unit of measurement depends on parameter P2 both a pin probe and as a cabinet probe and chilling will continue; it is recommended to (2) set the parameters relating to the controllers appropriately after altering parameter P2 set the i0 parameter to 2 (COMPRESSOR PROTECTION) (3) the device stores the defrost interval count every 30 minutes; altering parameter d0 has effect of concluding the previous defrost interval or IF THE ERROR OCCURS DURING A STORAGE OPERATION - the pin probe will operate as a cabinet manual defrost activation probe and storage will continue (4) the temperature alarm functions are only enabled during storage operations PARAM. MIN. MAX. M.U. DEF. DEFROST (5) the parameter differential is 2.0 ºC/4 ºF d0 0 99 h 8 defrost interval (3) (6) there are no temperature alarms during defrosting and drip draining, if they occur following defrost activation 0 = regular periodic defrosting will never be enabled (7) there is no maximum temperature alarm while door switch input is enabled, if occurring after input activation d3 0 99 min 30 defrost duration (8) the evaporator fan will be shut down providing defrosting is not ongoing 0 = defrosting will never be enabled (9) the compressor and/or ventilator fan are shut down 10 s after input activation d7 0 15 min 2 drip-drain duration (10) the compressor is shut down 10 s after input activation. PARAM. MIN. MAX. M.U. DEF. TEMPERATURE ALARMS (4) A1 0,0 99,0 °C/°F (1) 10,0 the temperature below which the minimum temperature alarm is activated; see also A2 (5) The device must be disposed of in accordance with local regulations pertaining to the collection of electrical and electronic appliances. A2 0 1 - - - 1 minimum temperature alarm type 0 = no alarm 1 = depending on parameters r9 and rA (or "r9 - A1" and "rA - A1") A4 0,0 99,0 °C/°F (1) 10,0 the temperature above which the maximum temperature alarm is activated; see also A5 (5) A5 0 1 - - - 1 maximum temperature alarm type 0 = no alarm 1 = depending on parameters r9 and rA (or "r9 + A4" and "rA + A4") A6 0 240 min 15 storage operation start-up temperature alarm delay A7 0 240 min 15 temperature alarm delay A8 0 240 min 15 drip-drain end maximum temperature alarm delay (6) A9 0 240 min 15 door switch input deactivation maximum temperature alarm delay (only if i0 = 0 or 1) (7) AA 0 240 s 5 blast chill completion buzzer duration PARAM. MIN. MAX. M.U. DEF. EVAPORATOR FAN (only if u0 = 1) F0 0 2 - - - 2 evaporator fan activity during chilling 0 = off 1 = on 2 = in parallel with the compressor F2 0 2 - - - 1 evaporator fan activity during storage 0 = off 1 = on 2 = in parallel with the compressor F8 0 99 min 0 evaporator fan start-up delay following defrost cycle start PARAM. MIN. MAX. M.U. DEF. DIGITAL INPUTS i0 0 4 - - - 1 digital input operation 0 = DOOR SWITCH INPUT - in this case parameters i1, i2 and i3 assume significance; enabling input will cause the evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) (8) (9) 1 = DOOR SWITCH INPUT - in this case parameters i1, i2 and i3 assume significance; enabling input will cause the compressor and evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) (8) (9) 2 = COMPRESSOR PROTECTION - in this case, parameters i1 and i7 assume significance; the compressor will be shut-down, the display will flash code "iA" and the buzzer will be activated (until the input will be deactivated) 3 = DOOR SWITCH INPUT - in this case parameters i1, i2 and i3 assume significance; enabling input will cause the evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) (8) 4 = DOOR SWITCH INPUT - in this case parameters i1, i2 and i3 assume significance; enabling input will cause the compressor and evaporator fan to be shut down (at most for the period of time set by i3 or until input will be disabled) (8) (10) i1 0 2 - - - 2 digital input contact type 0 = NA (input active with contact closed) 1 = NC (input active with contact open) 2 = no input-1120min30door switch input alarm activation delay (solo se i0 = 0 o 1) -1= the alarm will not sound -1120min15door switch input activation effect maximum duration (only if i0 = 0 or 1) -1= the effect will last until the input will be disabled 0120min0compressor protection deactivation compressor delay (only if i0 = 2) PARAM.MIN.MAX.M.U.DEF.DIGITAL OUTPUTS 01- - -1service controlled by relay K2 (see paragraph 2.3) 0 = defrosting 1 = evaporator fan PARAM.MIN.MAX.M.U.DEF.SERIAL NETWORK (MODBUS) 1247- - -247device address 03- - -2baud rate 0 = 2.400 baud 1 = 4.800 baud 2 = 9.600 baud 3 = 19.200 baud 02- - -2parity 0 = none (no parity) 1 = odd 2 = even PARAM.MIN.MAX.M.U.DEF.ENABLING 03- - -1quantity modifiable quickly before starting the cycle 0 = no quantity 1 = if you have selected a timed chilling cycle, the chilling duration if you have selected a set-temperature chilling cycle, the chilling end-point temperature 2 = if you have selected a timed chilling cycle, the chilling duration and the chilling operational setpoint if you have selected a set-temperature chilling cycle, the chilling operational setpoint 3 = if you have selected a timed chilling cycle, the chilling duration and the chilling operational setpoint if you have selected a set-temperature chilling cycle, the chilling end-point temperature and the chilling operational setpoint 01- - -1reserved
-99,099,0°C/°F (1)0,0 -99,099,0°C/°F (1)-40,0 -99,099,0°C/°F (1)2,0 -99,099,0°C/°F (1)-20,0 02- - -1 0,099,0°C/°F (1)5,0 199s60 PARAM.MIN.MAX.M.U.DEF.COMPRESSOR PROTECTION 0240min0 0240min5 0240min3 0240s0 0240min10 0240min10 0240min20 01- - -0 PARAM.MIN.MAX.M.U.DEF.DEFROST 099h8 099min30 015min2 PARAM.MIN.MAX.M.U.DEF.TEMPERATURE ALARMS (4) 0,099,0°C/°F (1)10,0 01- - -1 0,099,0°C/°F (1)10,0 01- - -1 0240min15 0240s5 PARAM.MIN.MAX.M.U.DEF.EVAPORATOR FAN (only if u0 = 1) 02- - -2 02- - -1 099min0 PARAM.MIN.MAX.M.U.DEF.DIGITAL INPUTS 04- - -1 02- - -2
6.1 Alarms CODEMESSAGE ALMinimum temperature alarm Remedies: •check the cabinet temperature •check parameters A1 and A2 Consequences: •the device will continue to function normally AHMaximum temperature alarm Remedies: •check the cabinet temperature •check parameters A3 and A4 Consequences: •the device will continue to function normally idMicro-port input alarm (only in "stand-by" mode and if parameter i0 is set to 0 or 1) Remedies: •check the causes which activated the input •check parameters i0 and i1 Consequences: •the outcome set by parameter i0 iACompressor protection input alarm (only if parameter i0 is set to 2) Remedies: •check the causes which activated the input •check parameters i0 and i1 Consequences:
7.1 Internal diagnostics CODEMESSAGE Pr1Cabinet probe error Remedies: •see P0 parameter •check probe integrity •check probe-device connection •check the cabinet temperature Consequences if the error occurs while in "stand-by" mode: •if parameter C11 is set to 0, it will not be possible to start any of the cycles •if parameter C11 is set to 1, the pin probe will function as the cabinet probe and only timed cycles will be allowed to start Consequences if the error occurs during a timed chilling operation: •if parameter C11 is set to 0, the cycle will be interrupted •if parameter C11 is set to 1, the pin probe will function as the cabinet probe and the chilling operation will continue Consequences if the error occurs during a set-temperature chilling operation: •if parameter C11 is set to 0, the cycle will be interrupted •if parameter C11 is set to 1, the pin probe will function as both the cabinet probe and pin probe and the chilling
  • compressor relay: 16 A res. @250 VAC, 5 FLA, 30 LRA (NA contact) versions with 12 VAC/DC and 12-24 VAC/DC; 8 A res. @ 250 VAC, 2 FLA, 12 LRA otherwise
  • defrosting/evaporator fan relay: 8 A res. @250 VAC, 2 FLA, 12 LRA (exchange contacts). The maximum permitted current on loads is 10 A. Serial port: port for communicating with the monitoring system (by means of a serial interface, via TTL, using the MODBUS communication protocol) or with the programming key; available on request.
9.1 First level configuration parameters PARAM.MIN.MAX.M.U.DEF.MAIN CONTROLLER r00,115,0°C/°F (1)2,0parameter r7, r8, r9 and Ra differential r11600min90timed positive blast chilling duration r21600min240timed negative blast chilling duration r3-99,099,0°C/°F (1)3,0positive blast chill end-point temperature (temperature detected by the pin probe) r4-99,099,0°C/°F (1)-18,0negative blast chill end-point temperature (temperature detected by the pin probe) r51600min90set-temperature positive blast chilling maximum duration r61600min240set-temperature negative blast chilling maximum duration r7-99,099,0°C/°F (1)0,0positive blast chilling operational setpoint (cabinet temperature) r8-99,099,0°C/°F (1)-40,0negative blast chilling operational setpoint (cabinet temperature) r9-99,099,0°C/°F (1)2,0post positive blast chill storage operational setpoint (cabinet temperature) rA-99,099,0°C/°F (1)-20,0post negative blast chill storage operational setpoint (cabinet temperature)
PARAM.MIN.MAX.M.U.DEF.SENSOR INPUTS CA1-25,025,0°C/°F (1)0,0cabinet probe offset CA2-25,025,0°C/°F (1)0,0pin probe offset P001- - -0probe type 0 = PTC 1 = NTC P101- - -1degree Celsius decimal point (for the quantity displayed during normal operation) 1 = YES P201- - -0unit of temperature measurement (2) 0 = °C 1 = °F P301- - -1pin probe enabling 1 = YES PARAM.MIN.MAX.M.U.DEF.MAIN CONTROLLER r00,115,0°C/°F (1)2,0parameter r7, r8, r9 and Ra differential r11600min90timed positive blast chilling duration r21600min240timed negative blast chilling duration r3-99,099,0°C/°F (1)3,0positive blast chill end-point temperature (temperature detected by the pin probe) r4-99,099,0°C/°F (1)-18,0negative blast chill end-point temperature (temperature detected by the pin probe) r51600min90set-temperature positive blast chilling maximum duration r61600min240set-temperature negative blast chilling maximum duration
  • EVCO S.p.A. This document belongs to Evco; unless you are authorized by Evco, you can not publish it. Via Mezzaterra 6, 32036 Sedico Belluno ITALY Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use. Phone +39-0437-852468
  • Fax +39-0437-83648 Evco does not take any responsibility about damages coming by the non-observance of the additional information. [email protected]
  • <a href="http://www.evco.it" rel="nofollow noopener" target="_blank">www.evco.it</a> Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the EVCO Digital Controller (EVK802)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the EVCO Digital Controller (EVK802)

Be the first to ask — other owners or our team will answer.

Original document

EVCO Digital Controller (EVK802) manual PDF

8 pages·510 KB·Controller·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…