The EPcolor series is an elegant range of programmable remote user interfac-
es.
The 3.5 inch (EPcolor S), 5 inch (EPcolor M) or 7 inch (EPcolor L) TFT graphic
display is fully touch-screen.
The EPcolor series is ideal for setting up user interfaces for applications devel-
oped on c-pro 3 programmable controllers. Thanks to the MODBUS protocol,
they can also interact with third-party devices.
Highly evolved user interfaces can be set up using a wide range of predefined
library graphics and templates. Moreover, the ability to automatically import
fonts, load bitmaps and text translation files from a USB flash drive simplifies
the human-machine interface personalisation process.



Measurements are expressed in mm (inches).
Models to be fitted to a panel (with elastic holding flaps).

The metal panel must be between 0.8 and 1.5 mm (1/32 and 1/16 in) thick, while the plastic panel must be between 0.8 and 3.4 mm (1/32 and 1/8 in).
Models to be mounted on the wall (with fixing screws and plugs) or in regular built-in boxes (with fixing screws).

2.1 Wall installation:
2.1.1 Rest the back cover on the wall in a place suitable for allowing the connection cables to feed through the opening.
2.1.2 Use the slots in the back cover as a guide for drilling the 4 holes with a diameter suitable for the plug.
We recommend using 5 mm (3/16 inch) diameter plugs.
2.1.3 Insert the plugs into the holes drilled in the wall.
2.1.4 Fit the back cover to the wall with 4 screws.
We recommend using flat countersunk screws.
2.2 Installation in a built-in box: fit the back cover to the box with 4 screws.
We recommend using flat countersunk screws.

Measurements are expressed in mm (inches).
Models to be fitted to a panel (with elastic holding flaps).

The metal panel must be between 0.8 and 1.5 mm (1/32 and 1/16 in) thick, while the plastic panel must be between 0.8 and 3.4 mm (1/32 and 1/8 in)
Models to be installed from behind (using threaded studs).


Measurements are expressed in mm (inches).
Models to be fitted to a panel (with elastic holding flaps).

The metal panel must be between 0.8 and 1.5 mm (1/32 and 1/16 in) thick, while the plastic panel must be between 0.8 and 3.4 mm (1/32 and 1/8 in)
Models to be installed from behind (using threaded studs).


- ensure that the working conditions are within the limits stated in the TECHNICAL SPECIFICATIONS section
- do not install the device close to heat sources, equipment with a strong magnetic field, in places subject to direct sunlight, rain, damp, excessive dust, me-
- in compliance with safety regulations, the device must be installed properly to ensure adequate protection from contact with electrical parts. All protective
parts must be fixed in such a way as to need the aid of a tool to remove them


- use cables of an adequate section for the current running through them
- to reduce any electromagnetic interference, connect the power cables as far away as possible from the signal cables and, if necessary, connect to a RS-
485 MODBUS network and/or a CAN network by using a twisted pair
- for the CAN port of EPcolor S and EPcolor M use a ferrite (for example Essentra RKCF-08-A5) to which the conductors of the shielded cable must be wound
4.1.1 Connectors
Models to be fitted to a panel.


USB port to programme the device.
- to fit the termination resistor of the RS-485 MODBUS port
- to fit the termination resistor of the CAN port.

Models to be mounted on the wall.

3 device power supply (24 VAC/ 12... 30 VDC); if the device is powered by direct current connect the negative terminal
4 device power supply (24 VAC/ 12... 30 VDC); if the device is powered by direct current connect the positive terminal
USB port to programme the device.
- to fit the termination resistor of the RS-485 MODBUS port
- to fit the termination resistor of the CAN port.
Connector 1 · Connector 2 · Micro-switch

4.1.2 Example of electrical connection
Models to be fitted to a panel with an independent power source.

Do not power another device with the same transformer
Models for panel installation powered by another device.

Make sure the current generated by the controller is enough to power the device
4.1.3 Fitting the termination resistor of the RS-485 port and the CAN port
To fit the termination resistor of the RS-485 MODBUS port, place micro-switch 1 in the ON position.
To fit the termination resistor of the CAN port, place micro-switch 2 in the ON position.
The micro-switch is on the back of the device (first remove the back cover from the front).

Models to be fitted to a wall with an independent power source.

Do not power another device with the same transformer
Models for wall installation powered by another device.

Make sure the current generated by the controller is enough to power the device

4.2.1 Connectors



36 device power supply and RS-485 MODBUS master port GND reference


USB port to programme the device.
- to fit the termination resistor of the RS-485 MODBUS master port
- to fit the termination resistor of the RS-485 MODBUS slave port.
To fit the termination resistor of the CAN port.

4.2.2 Example of electrical connection

Do not power another device with the same transformer
4.2.3 Fitting the termination resistor of the RS-485 ports and the CAN port
To fit the termination resistor of the RS-485 MODBUS master port, place dip 1 of micro-switch 1 in the ON position.
To fit the termination resistor of the RS-485 MODBUS slave port, place dip 2 of micro-switch 1 in the ON position.
To fit the termination resistor of the CAN port, place micro-switch 2 in the ON position.

4.3.1 Connectors

USB port to programme the device.



33 device power supply and RS-485 MODBUS master port GND reference

To fit the termination resistor of the CAN port.
To fit the termination resistor of the RS-485 MODBUS slave port.
To fit the termination resistor of the RS-485 MODBUS master port.

4.3.2 Example of electrical connection

Do not power another device with the same transformer
4.3.3 Fitting the termination resistor of the RS-485 ports and the CAN port
To fit the termination resistor of the CAN port, place micro-switch 1 in the ON position.
To fit the termination resistor of the RS-485 MODBUS port, place micro-switch 2 in the ON position.
To fit the termination resistor of the RS-485 MODBUS port, place micro-switch 3 in the ON position.

- if using an electrical or pneumatic screwdriver, adjust the tightening torque
- if the device is moved from a cold to a warm place, humidity may cause condensation to form inside. Wait for about an hour before switching on the power
- make sure that the supply voltage, electrical frequency and power are within the set limits. See the section TECHNICAL SPECIFICATIONS
- disconnect the power supply before carrying out any type of maintenance
- do not use the device as a safety device
- for repairs and further information, contact the EVCO sales network

Purpose of the control device Function controller
Construction of the control device Built-in electronic device
Category of heat and fire resistance D
111.4 x 76.4 x 25.0 mm (4 3/8 x 3 x 1 in) for panel installation models 111.4 x 76.4 x 18.5 mm (4 3/8 x 3 x 3/ 4 in) for wall installation models
Mounting methods for the control device According to the model, panel (with elastic holding flaps), wall (with fixing plugs and screws) or in regular
built-in boxes (with fixing screws)
Degree of protection provided by the casing IP30 (IP65 in the event of panel installation)
Plug-in screw terminal blocks for wires up to 1 mm² for panel installation models Fixed screw terminal blocks for wires up to 1 mm² for wall mounted models
Maximum permitted length for connection cables
CAN port:
- 1,000 m (3,280 ft), baud rate: 20,000 baud
- 500 m (1,640 ft), baud rate: 50,000 baud
- 250 m (820 ft), baud rate: 125,000 baud
- 50 m (164 ft), baud rate: 500,000 baud
Over 10 m (32.8 ft) use a screened cable
Operating temperature From -10 to 55 °C (from 14 to 131 °F)
Storage temperature From -20 to 70 °C (from -4 to 158 °F)
Operating humidity Relative humidity without condensate from 5 to 95%
Pollution status of the control device 2
RoHS 2011/65/EC WEEE 2012/19/EU REACH (EC) Regulation no. 1907/2006
Power supply 24 VAC (±15%), 50/60 Hz (±3 Hz), max. 4 VA not insulated or 12... 30 VDC, max. 2 W not insulated (inde-
pendent power source or power generated by a controller)
Earthing methods for the control device None
Rated impulse-withstand voltage 330 V
Software class and structure A
Clock Built-in secondary lithium battery
Clock drift ≤ 55 s/month at 25 °C (77 °F)
Clock battery autonomy in the absence of a power
> 6 months at 25 °C (77 °F)
Clock battery charging time 24 h (the battery is charged by the power supply of the device)
Displays 3.5-inch capacitive TFT touch-screen graphic display, 320x240 px, 256 colours
Incorporated sensors Temperature (according to the model)
Incorporated sensors working range From 0 to 40 °C (from 32 to 104 °F)
Programme memory 1 MB

1 RS-485 MODBUS master/slave port 1 CAN port
For communications ports · 1 USB port

Purpose of the control device Function controller
Construction of the control device Built-in electronic device
Category of heat and fire resistance D
Mounting methods for the control device According to the model, to be installed from behind using threaded studs or to a panel with elastic holding
Degree of protection provided by the casing IP40 (IP65 in the event of panel installation)
Connection method Plug-in screw terminal blocks for wires up to 1 mm²
Maximum permitted length for connection cables
CAN port:
- 1,000 m (3,280 ft), baud rate: 20,000 baud
- 500 m (1,640 ft), baud rate: 50,000 baud
- 250 m (820 ft), baud rate: 125,000 baud
- 50 m (164 ft), baud rate: 500,000 baud
Over 10 m (32.8 ft) use a screened cable
Operating temperature From 0 to 55 °C (from 32 to 131 °F)
Storage temperature From -20 to 70 °C (from -4 to 158 °F)
Operating humidity Relative humidity without condensate from 5 to 95%
Pollution status of the control device 2
RoHS 2011/65/EC WEEE 2012/19/EU REACH (EC) Regulation no. 1907/2006
Power supply 24 VAC (±15%), 50/60 Hz (±3 Hz), max. 6.5 VA not insulated or 12... 30 VDC, max. 3 W not insulated
Earthing methods for the control device None
Rated impulse-withstand voltage 330 V
Software class and structure A
Clock Built-in secondary lithium battery
Clock drift ≤ 55 s/month at 25 °C (77 °F)
Clock battery autonomy in the absence of a power
> 6 months at 25 °C (77 °F)
Clock battery charging time 24 h (the battery is charged by the power supply of the device)
Displays 5-inch capacitive TFT touch-screen graphic display, 800x480 px, 65K colours
Programme memory 1 MB
1 RS-485 MODBUS master port 1 RS-485 MODBUS slave port
1 CAN port 1 USB port

Purpose of the control device Function controller
Construction of the control device Built-in electronic device
Category of heat and fire resistance D
216.0 x 156.0 x 50.0 mm (8 1/2 x 6 1/8 x 2 in) for models to be installed from
192.95 x 131.95 x 47.0 mm (7 5/8 x 5 3/16 x 1 7/8 in) for panel installation
Mounting methods for the control device According to the model, to be installed from behind using threaded studs or to a panel with elastic holding
Degree of protection provided by the casing IP40 (IP65 in the event of panel installation)
Connection method Plug-in screw terminal blocks for wires up to 1 mm²
Maximum permitted length for connection cables
CAN port:
- 1,000 m (3,280 ft), baud rate: 20,000 baud
- 500 m (1,640 ft), baud rate: 50,000 baud
- 250 m (820 ft), baud rate: 125,000 baud
- 50 m (164 ft), baud rate: 500,000 baud
Over 10 m (32.8 ft) use a screened cable
Operating temperature From 0 to 55 °C (from 32 to 131 °F)
Storage temperature From -20 to 70 °C (from -4 to 158 °F)
Operating humidity Relative humidity without condensate from 5 to 95%
Pollution status of the control device 2
RoHS 2011/65/EC WEEE 2012/19/EU REACH (EC) Regulation no. 1907/2006
Power supply 24 VAC (±15%), 50/60 Hz (±3 Hz), max. 10 VA not insulated or 12... 30 VDC, max. 4.6 W not insulated
Earthing methods for the control device None
Rated impulse-withstand voltage 330 V
Software class and structure A
Clock Built-in secondary lithium battery
Clock drift ≤ 55 s/month at 25 °C (77 °F)
Clock battery autonomy in the absence of a power
> 6 months at 25 °C (77 °F)
Clock battery charging time 24 h (the battery is charged by the power supply of the device)
Displays 7-inch capacitive TFT touch-screen graphic display, 800x480 px, 65K colours
Programme memory 1 MB
1 RS-485 MODBUS master port 1 RS-485 MODBUS slave port
1 CAN port 1 USB port

Programmable remote user interfaces (with Gui-PRO graphic tool)
This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual Property Rights Code (CPI). EVCO
imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of EVCO. The customer (manufacturer,
installer or end user) assumes all responsibility for the configuration of the device. EVCO accepts no liability for any possible errors in this document and reserves the
right to make any changes at any time without prejudice to the essential functional and safety features of the equipment.
EPcolor · Code 144PCOLORE204

EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
phone +39 0437 8422 fax +39 0437 83648
email [email protected] web www.evco.it
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.