The Intrinsically Safe Optical Smoke Detector SLR-E-IS uses the scattered light principle and was developed for the detection of smoke particles in explosion-prone rooms. The modern design of the sensing chamber al- lows to reliably evaluate the characteristics of fi re.
Ex classifi cation. The two LEDs with 360° visibility indi- cate the activated condition of the detector. By means of an auxiliary module, the connection to an ADM loop is possible.
A detector function test can be conducted by using test gas. The detector is attached to the IS Detector Base YBN-R/4IS.
Conventional technology is used for alarm transmission to the fi re detection control panel. In conjunction with the Safety Barrier ES58-2, the detector reaches the given

Ignition protection intrinsically safe
Ex classifi cation EEx ia IIC T5
Current consumption at 24V typ. 50µA (quiescent)
Ambient temperature -10°C to +55°C
Relative humidity 10 – 95% (no condensation)
Dimensions ø × H (incl. base) 100 × 46 (mm)
Approval BAS01ATEX1281 LPCB 164a
Order name IS Optical Smoke Detector/Conv. SLR-E-IS
SLR-E-IS_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.
Colour cream · Weight 115g · Order number 241090

Ambient temperature -10°C to +55°C (no condensation or icing)
Relative humidity 10 – 95% (no condensation)
Dimensions ø × H 100 × 15 (mm)
Order name IS Detector Base/Conv. YBN-R/4IS
SLR-E-IS_DBL_LST_EN_0804.PDF • PAGE 2 A Building Safety. Building Security.