The response delay of the detector can be selected in 4 steps between 1 and 8s. An alarm and a fault conditi- on is signalled via two dry relay contacts. Conventional technology is used for alarm transmission to the fi re detection control panel. The detector can be integra- ted into an ADM loop by means of a conventional zone module.
A simple test of the detector can be carried out by means of the integrated optical self test function, which does not require additional tools. During this self test, a built-in infrared source simulates a fi re situation which activates the detector.
With three independent infrared sensors for different wavelengths and with an intelligent evaluation logic, the detector can safely distinguish between alarm situati- ons and deceptive alarms. Therefore, it is particularly insensitive to disturbance sources such as sunlight, fl uorescent lamps or electric arcs.
The detector has been designed for indoor and outdoor use. The optional Detector Mounting Bracket 7127 al- lows stepless horizontal and vertical adjustment for the easy adaptation of the detector to the required monito- ring area. For use in explosion-hazardous areas, an Ex version of the fl ame detector is available on request.
The detector complies with EN 54-10, Class 1, which means it is suitable to detect fl ames up to a distance of 25m.
IR3-16589_DBL_LST_EN_0850.PDF • PAGE 1 A Building Safety. Building Security.


Operating voltage 14 – 30VDC
Current consumption at 24VDC max. 8mA (quiescent), 14mA (alarm)
Range max. 25m
Spectral sensitivity 0.75 – 2.7µm
Contact rating of relay outputs max. 1A at 50VDC
Ambient temperature -10°C to +55°C
Dimensions W × H × D 108 × 142 × 82 (mm)
Colour sky blue, RAL 5015
Approvals LPCB 729a/01 0832-CPD-0595
Order name Flame Detector/IR3 16589
Adjustment range vertical 0 to -45°
Adjustment range horizontal ±45°
Dimensions W × H × D 82 × 98 × 90 (mm)
Order name Detector Mounting Bracket/Flame Detector 7127