EN
Official user manual

LST Fire Alarm Control Panel (16589)

2 pages·116 KB·Smoke Alarm·PDF·ENDEFRITNLJA
LST Fire Alarm Control Panel (16589)
Table of Contents 4 sections Flame Detector IR · Description · 0832–CPD–0595 · Specifi cations ShowHide
Page 1 of the LST Fire Alarm Control Panel (16589) user manual — 0832–CPD–0595
Page 1 · click to enlarge
Page 1
LST Fire Alarm Control Panel (16589) — Flame Detector IR diagram (page 1)
Fig. 1 · Flame Detector IR

Flame Detector IR

LST Fire Alarm Control Panel (16589) — Flame Detector IR diagram (page 1)
Fig. 2 · Flame Detector IR
LST Fire Alarm Control Panel (16589) — Flame Detector IR diagram (page 1)
Fig. 3 · Flame Detector IR
LST Fire Alarm Control Panel (16589) — Flame Detector IR diagram (page 1)
Fig. 4 · Flame Detector IR
LST Fire Alarm Control Panel (16589) — Flame Detector IR diagram (page 1)
Fig. 5 · Flame Detector IR
  • Triple infrared sensor according to EN 54-10, Class 1
  • Detection of open fl ames through fl ickering infrared radiation
  • Very high immunity to deceptive alarms
  • Selectable response delay
  • Relay contacts for alarm and fault
  • Integrated optical test function
LST Fire Alarm Control Panel (16589) — Flame Detector IR diagram (page 1)
Fig. 6 · Flame Detector IR

Description

  • The Flame Detector 16589 responds to the fl ickering infrared radiation of open fl ames. Therefore, it is extremely well suitable for the detection of fi res which are diffi cult to detect with common smoke detectors – for example, alcoholic fi res or gas fl ames. The detector is ideal for the following applications:
  • Pharmaceutical industry
  • Paint shops
  • Warehouses
  • Nuclear facilities
  • Tunnels

The response delay of the detector can be selected in 4 steps between 1 and 8s. An alarm and a fault conditi- on is signalled via two dry relay contacts. Conventional technology is used for alarm transmission to the fi re detection control panel. The detector can be integra- ted into an ADM loop by means of a conventional zone module.

A simple test of the detector can be carried out by means of the integrated optical self test function, which does not require additional tools. During this self test, a built-in infrared source simulates a fi re situation which activates the detector.

With three independent infrared sensors for different wavelengths and with an intelligent evaluation logic, the detector can safely distinguish between alarm situati- ons and deceptive alarms. Therefore, it is particularly insensitive to disturbance sources such as sunlight, fl uorescent lamps or electric arcs.

The detector has been designed for indoor and outdoor use. The optional Detector Mounting Bracket 7127 al- lows stepless horizontal and vertical adjustment for the easy adaptation of the detector to the required monito- ring area. For use in explosion-hazardous areas, an Ex version of the fl ame detector is available on request.

The detector complies with EN 54-10, Class 1, which means it is suitable to detect fl ames up to a distance of 25m.

0832–CPD–0595

IR3-16589_DBL_LST_EN_0850.PDF • PAGE 1 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED
Page 2 of the LST Fire Alarm Control Panel (16589) user manual — Specifi cations
Page 2 · click to enlarge
Page 2
LST Fire Alarm Control Panel (16589) — Specifi cations diagram (page 2)
Fig. 7 · Specifi cations

Specifi cations

Operating voltage 14 – 30VDC

Current consumption at 24VDC max. 8mA (quiescent), 14mA (alarm)

Range max. 25m

Spectral sensitivity 0.75 – 2.7µm

Contact rating of relay outputs max. 1A at 50VDC

Ambient temperature -10°C to +55°C

Dimensions W × H × D 108 × 142 × 82 (mm)

Colour sky blue, RAL 5015

Approvals LPCB 729a/01 0832-CPD-0595

Order name Flame Detector/IR3 16589

Adjustment range vertical 0 to -45°

Adjustment range horizontal ±45°

Dimensions W × H × D 82 × 98 × 90 (mm)

Order name Detector Mounting Bracket/Flame Detector 7127

IR3-16589_DBL_LST_EN_0850.PDF • PAGE 2 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED
Show 8 more labels / short text on this page
Monitored angle 90° · Weight 2kg · Protection class IP65 · Order number 243011 · Detector Mounting Bracket · Material stainless steel · Weight 650g · Order number 249141
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the LST Fire Alarm Control Panel (16589)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the LST Fire Alarm Control Panel (16589)

Be the first to ask — other owners or our team will answer.

Original document

LST Fire Alarm Control Panel (16589) manual PDF

2 pages·116 KB·Smoke Alarm·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…