Operating manual System operation for user
Fire & Security Products
Siemens Building Technologies Group
Phase 4

Data and design subject to change without notice. / Supply subject to availability. Copyright by Siemens Building Technologies AG
Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder ausserhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
Nous nous réservons tous les droits sur ce document, ainsi que sur l’objet y figurant. La partie recevant ce document reconnaît ces droits et elle s’engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l’employer à des fins autres que celles pour lesquelles il lui a été remis.
Ci riserviamo ogni diritto relativo al presente documento e sull’oggetto illustrato in esso. La parte che riceve il documento si impegna a non renderlo accessibile a terzi, né per intero né in parte, senza la nostra previa autorizzazione scritta ed a non usarlo per altri scopi di quello per il quale è stato rilasciato.

Introduction 1
About this operation manual 2
Fundamentals 3
Control console layout 4
Floor panel 5
Overview operating menu 6
Fundamental operation 9
Normal operation 10
Operating access 11
Operating “manned” and “unmanned” 13
Alarm 15
Cerberus Alarm Concept (CAC) 16
Alarm 18
Disable/Enable System Parts 21
Temporary isolation of a detector zone 22
Temporary isolation of a single detector 26
Remote Transmission 28
Alarm devices 30
Faults 31
Faults 32
Maintenance 33
Detector test 34
Lamp test 38
Battery load test 39
Test of acoustic alarm devices 40
Test of Remote Transmission (RT) 41
Other Functions 43
Printer disabling/enabling 44
Paper replacement with logging printer B2Q191 45
Poll alarm counter 46
Poll event memory 47
Poll user text of zones or elements 48
Poll system status 49
Poll configuration data 50
Printout 51
Set time and date 52
06.2003

06.2003

02.2004

This operation manual describes the use and the operation of the control console FC330A. It contains all information for the normal user with access level 2 who has to react to alarms, disa- ble and enable parts of the system, etc. This document contains the following:
This operation manual uses several symbols to guide the user through the manual. The meanings in detail are:
Single step actions are marked with a triangle.
The result of an action is marked with an arrow. In body text you will find quotations like display texts, keys or LED−fields or LEDS. Frequently used keys are shown as they look like on the console, e.g. ok .
02.2004

02.2004

ALARM
NORMAL OPERATION
MON 04.01.99 09:13
Remote alarm fault / off
Remote alarm active Alarm delay off
Alarm horn fault / off
FC330A
ALARM LED bar Red LED’s blinking when an alarm signal is pending.
Text display Displays selection menus as well as alarm and fault messages.
Scroll key Allows scrolling of alarm messages in the text display.
Acknowledge key Confirms an alarm or a message (2 variants possible).
Variant 1:
Variant 2:
1st activation Alarm horns and buzzer
1st activation Buzzer off
2nd activation Alarm horns off
2nd activation Reactivation alarm horns
3rd activation Reactivation alarm horns
Reset key Resets alarm and fault messages.
Display fields Indicates the operating state by an LED.
Command fields Possess a button to change the operating mode and may have an LED to indicate the operating state.
Alarm delay off Cancels alarm delay. Remote alarm is given immediately.
Toggles between “manned” and “unmanned” operating mode.
Function keypad Keys for menu−orientated operation and password input.
St Start/Stop key Open and close menus.
F1 F2 Function keys Usage depends on context.
ok Execution key Starts the selected menu function.
Move up/down key Selects menu items upwards/downwards.
hm Home key Returns to the previous menu.
del Delete key Deletes the character left of the cursor.
Keylock switch Gives access to user operating level 2 without password. Only when keylock switch is installed.
02.2004

The floor panel is a typical local indication terminal. It mainly serves to display alarm events re- motely. Secondary it is also an operating terminal to acknowledge and reset the control console from remote. Two types of panels are available:

ALARM zone ###/## / ###### 1( 1) 1st floor office 101 ALARM zone ###/## / ###### 1( 1) 1st floor office 101
Scroll key Allows scrolling of alarm messages in the text display.
Also to initiate lamp test (press key 3 sec).
Acknowledge key Confirms an alarm or a message.
Display fields Indicates the operating state by an LED.
Keylock switch Gives access to user operating level 2 without password.
The display of the floor panel indicates the same event text as shown at the control console. It only displays one message at a time.
02.2004

After getting operating access, the start menu appears. From the main menu, all menus can be selected ( page 9, fundamental operation). With access level 2 all menu points exept other functions − configuration can be selected. The passwort for access level 2 is:
ENabling: 1. detector ’zone’ (1.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’
Enable detector zones 1...256 Enable detector elements within zone Enable control zones 1...64
Enable all control zones
Enable control lines 1...4 for alarm horns Enable alarm contacts 1...4 Enable remote transmission ALARM
Enable remote transmission FAULT
Enable only event logging or all messages
ENable printout messages: 1. log ALL (old: #) 2. only ALARMS 3. log NONE Enable only alarms or none
Disable detector zones 1...256 disabling permanent or for a set time 1...98h
DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’
Disable detector ELEMENTS within zone disabling permanent or for a set time 1...98h Disable conTrol zones 1 64
Disable all control zones
Disable control line 1..4 for alarm horns Disable alarm contacts 1...4 Disable remote transmission ALARM
Disable remote transmission FAULT
Disable only alarms or none ENable printout messages: 1. log ALL (old: #) 2. only ALARMS 3. log NONE
Disable only event logging or all messages
View fault messages View turned off system components View pre-alarm messages View ELEMENT states
View reviewing event list View number of alarms and remote alarms
INFO: 1. configuration system (3.3) 2. configuration coll line 3. user text detector zn/elem 4. user text ConTrol zone
View general parameter settings View parameter settings coll. lines View user texts detector zones/elements View user texts control zones
View parameter settings detector zones View parameter settings addr. lines View parameter settings LON-bus
02.2004

Switching manned unmanned via menu Set or adjust time and date
Activate all ’horns’ for 30 sec Activate all ’alarm contacts’ for 30 sec. Activate ’remote alarm’ for 30 sec. Activate ’remote fault’ for 30 sec.
Activate all LEDs and LCD for 10 sec. Load battery for 10 sec.
SYSTEM TEST: 1. single zone test (4.2.3) 2. zone range test 3. set control zones Set control zone to ’control zone Test’ X..Y
Set detectors to ’Detector test’ per zone
Set detectors to ’Detector test’ zone X...Y
Print current fault messages Print current turned off system components Print current information messages Print current ELEMENT states
Print event memory list Print alarm counter readings
Print general parameter settings Print parameter settings coll. lines Print user texts detector zones / elements Print user texts control zones
PRINT: 1. configuration system (4.3.3) 2. configuration coll. line 3. user text detector zn/elem 4. user text ConTrol zone
Print parameter settings detector zones Print parameter settings addr. lines Print parameter settings LON-bus
02.2004
page 8

FUNCTIONS: 1. function (4) 2. system TEST 3. printout 4. configuration CONFIGURATION: 1. user functions (4.4) 2. user text 3. service functions 4. erase functions
direct setting user parameters direct definition user texts
Level SERVICE FUNCTIONS > enter password?
engineer
SERVICE 1. addr. line −> CONNECT level : 2. addr. line −> DISCON. (4.4.3) 3. test AI−LED’s ON/OFF 4. reconfigure addr. lines
connect addressable loop disconnect addressable loop for TEST LEDs to reconfigure addr. lines
to activate horn briefly with each det. TEST alarm enable / disable ’visualizer’
to start automatic configuration of LON- Bus
Level SERVICE FUNCTIONS > enter password?
ERASE data: 1. ERASE alarm counter (4.4.4) 2. ERASE event memory 3. ERASE conf + sys data 4. ERASE element status
(locked with switch ’S2’) (not locked)
only for specialized personell
to erase ’non−alarm’ events
02.2004
for COMMON disabling

To choose a menu item in the display of the console:

Access level page 11 SELECT: 1. ENabling (main menu) 2. DISabling 3. INFO polling 4. other functions
Enter the number of the menu option on the numeric keypad (e. g. option 2.). Display shows
Press hm to return to the previous menu.
The following description is an example for choosing the Disable elements menu.
Enter “2”. Display shows
Enter “1”. Display shows

DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’
Enter “2”. Display shows
In this operation manual, selecting a menu item will be described from now on in a short form as follows:
02.2004

The system is ready to receive danger messages (alarm) from the detectors.
No fault messages are pending.
The green LED in the display field System on is on.
The illumination of the text display may be turned off, but turns on as soon as any key is
pressed or an alarm, fault or status is issued.
WED 21.7.99 15:00
Mains interruption
In case of a mains interruption the fire detection system is powered by an internal battery. No fault message is issued in the text display and the normal operation will continue , until a preset default time is expired When the system is powered by the internal battery the green LED in the display field System on is blinking.
The delay is min Standard default: 10 min

02.2004

Three main access levels are defined allowing different privileges for the operation of the fire detection system. Access is provided by a four digit password for the higher access levels, re- spectively.
After 3 consecutive incorrect password entries the operation access is disabled for 15 minu- tes.
Overview of the access levels

(password required or key−lock switch, if instal- led)
Automatic timeout The access by password is automatically cancelled if no key is operated for:
5 min during state of “normal operation“
30 sec during condition “alarm“
Enter the password on the keypad as described below.
Turn the keylock switch in horizontal position.
Access with level user operating 2 is provided as long as the key is left in horizontal position.

02.2004
Acknowledge messages · or

The passwords are defined and released to the operators by the service engineer. In case of misskeying the password, use del to cancel keying errors.
START system operating > enter password?
Log out There is no log out procedure, because the operating access expires automatically if no key is pressed within a certain time ( page 11, Automatic timeout).
02.2004
Log in

i SPECIAL Alarm Concept used: Yes No
The operating states “manned” and “unmanned” are defined in a SPECIAL Alarm Concept, where signals from automatic fire detectors and manual call points are processed differently (for details page 16). The switchover from the operating states “manned” to “unmanned” and vice versa is either done manually by the operating personnel or automatically as programmed by the service engineer.
The operating person, responsible for the surveillance of the system and the alarm investiga-
tion, is present on the premises.
The LED in the display field Premises manned is on.
The LED in the display field Isolation is on (depends on system configuration).
The responsible operating person is not present on the premises.
The LED in the display field Premises manned is off.
Remote alarm fault / off
Remote alarm active Alarm delay off
Alarm horn fault / off
FC330A
Manual switching between the operating states “manned” and “unmanned”
Manual switching between the operating states “manned” and “unmanned” is only possible during defined working hours ( page 14, Automatic switchover).
Toggle between “manned” and “unmanned” via menu which is described next page.
WED 21.7.99 15:00
NORMAL OPERATION mode ’manned’
02.2004

mode ’manned’ until ##:##, 1.> unmanned sel. #, 2.> manned 3.extra time
If mode ”manned” is selected Display shows for a few seconds
mode ’manned’ TERMINATED > system is set to NORMAL OPERATION
The automatic switchover is used for example, to prevent the system status “manned” during nighttime when no operating personnel is present: The system switches automatically to status “unmanned” at a defined time (e. g. after the office hours). The same scheme can be used for unattended times during weekends or holidays. The automatic switchover scheme is defined by the service engineer. No user action is required.
Automatic switchover from “manned” to “unmanned”: at p.m.
Automatic switchover from “unmanned” to “manned”: at a.m.
The function “extra time” allows to set the system to manned operation for a preset time, after the automatic switchover to unmanned has taken place.
activated not activated
mode ’unmanned’ 2. > ’manned’ (hm = INTERRUPT) 3. extra time
The actual display depends on the initial mode, here e. g. mode unmanned (i. e. after
17:00).
EXTRA TIME h/min? (max. ##:##)
hm: back to menu Stop: end operating Extra time max.
The time until the system is set to manned mode is displayed.
02.2004
Toggle via menu · Function extra time

02.2004

To prevent the unnecessary turn out of the fire department for minor incidents a SPECIAL Alarm Concept was developed. It involves operating personnel in the alarming sequence and relies on two operating states:
“unmanned” mode while the operating personnel is not present on the premises.
“manned” mode while the operating personnel is present on the premises.
“unmanned” mode When the system operates in “unmanned” mode, the fire brigade is called immediately when an alarm signal is issued.
“manned” mode When the system operates in “manned” mode, manual call points and automatic detectors trig- ger different actions in the event of an alarm:
Manual call point is actuated The fire brigade is summoned immediately.
Automatic fire detector responds The fire brigade is summoned only after a preprogrammed time in which the operating personnel performs following alarm response procedure:
Emergency Actuate the nearest manual call point immediately!
or Press the Alarm delay off key on the control console! The fire brigade is summoned immediately.
Minor incident Reset the system before expiration of the alarm investigation time V2 by pressing the Reset key.
The system is in the normal operation mode again.
i The times V1 and V2 are only relevant, when the remote transmission is installed.
02.2004
Event Action

V1 = min.
Alarm acknowledgement time V1
The alarm acknowledgement time is active for automatic detectors when the system opera-
tes in “manned” mode.
The system checks whether someone acknowledges the alarm message within this prepro-
grammed time.
An alarm must be acknowledged before V1 expires, otherwise the alarm is transmitted to the
fire department.
The remaining time is indicated on the text dis-
play in minutes and seconds.
ALARM zone ###/## / ######
1:27 min
V2 = min.
Alarm investigation time V2
The alarm investigation time is active for automatic detectors when the system operates in
“manned” mode.
It limits the time for investigating the fire location to an preprogrammed length.
On expiration of this time the alarm is transmitted to the fire department.
In case of minor incidents, an alarm must be reset before V2 expires.
The remaining time is indicated on the text dis-
play in minutes and seconds.
ALARM zone ###/## / ######
2:27 min
02.2004
1 ( 1) · 1 ( 1)

An alarm is issued by the system if an automatic detector has responded or a manual call point was actuated. The alarm is indicated by:
−blinking of the red LED alarm bar on the control console −alarm message on the text display
−buzzer of the control console −attached signal horns As described in the SPECIAL Alarm Concept, the operating personnel is involved into the alarm scheme only if the system is in “manned” mode. In all other cases, i. e. SPECIAL Alarm Concept is not activated (used) or the system operates in “unmanned” mode, the alarm is transmitted immediately to the fire brigade.
During alarm other states such as faults etc. are not shown at the display. However, it is possible to make them visible via the menu “Info polling” (For details page 49).

ALARM zone ###/## / ###### 1st floor canteen 1( 1)
02.2004
optical signals · acoustic signals

A single alarm message on the text display consists of 2 lines as shown in the example to the right.The first line tells that the alarm was given in zone 5 by the element 1 of this zone, which was an automatic fire detector. The numbers at the end of the line tell, that this is the first of in total 3 alarm messages. The se- cond line gives the explicit location of the re- sponding detector. The 3. and the 4. line hold the same information for the last alarm message issued. In this case a manual call point was actuated in zone 3 of the building, which is located in the ground floor main entrance.
ALARM zone ###/## / ###### 1st floor canteen
ALARM zone ###/## / ###### ground floor main entrance

Scrolling alarm messages Additional pending messages can be retrieved using the scroll key.
Press the scroll key below the text display.
The first two lines are superseeded with the subsequent alarm message.
Retrieving supplementary informations Supplementary informations to the alarm messages can be retrieved by using F1 and F2 :
F1 tells the type of the responding device, e. g. automatic detector.
F2 tells the cabling address and the type number of the responding device (device address).
Press F1 (or F2 ).
The second line in the text display is superseeded with the supplementary information.
Press the scroll key to retrieve supplementary information of subsequent alarm messages.

If a manual call point was activated while the alarm, insert a new front glass in the actual call
02.2004
1( 3) · 3( 3)

02.2004

02.2004

The detectors and manual call points of the fire detection system are grouped into zones, which are defined according to geographical aspects of the building. Zones may be all self-contained areas of a building, for example
adjacent rooms (no doors between the rooms)

In that way, a zone represents a “room address”. Each zone contains one or more automatic fire detector devices or manual call points.
Assignment of zones to building areas For each zone a descriptive user text (e. g. room designation and floor no.) is defined in the sy- stem. Only in case of an alarm, this text is displayed on the text display together with the zone and device number of the responding detector.
It is recommended to prepare a list holding the assignment of zone numbers to actual rooms and building-areas.
In exceptional situations zones have to be isolated from the system, to prevent unintended alarm. An exceptional situation depends on the kind of the detector and exists for zones with:
smoke detectors, if smoke or dust is produced by unusual work
heat detectors, if heat or steam is produced by unusual work
manual call points, if there is a possibility of inadvertent activation
02.2004
single rooms · corridors · staircases

Display shows Now you can disable single zones, a range of detector zones or all zones as described be- low:
zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)
zone ### SELECTED > hours DISABLED? (99=permanent)
Permanent disabling zone ### permanent DISABLED (hm = end) new zone no.?
Enter the desired disabling time in full
Disabling for a few
hours zone ### DISABLED for ## hours (hm = end) new zone no.?
hours (e. g. 2). Display shows
Enter another single zone number to disable.
parts of system DISABLED total:###
Display shows The yellow LED isolation is on.
Disable a range of zones
zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###) _
zone ### − ### SELECTED > hours DISABLED? (99=permanent)
Permanent disabling zones ### − ### permanent DISABLED (hm = end) new zone no.?

Disabling for a few
Enter the desired disabling time in full
hours zones ### − ### DISABLED for ## hours (hm = end) new zone no.?
hours (e. g. 2). Display shows
Enter another zone number to disable. Display shows The yellow LED isolation is on.
parts of system DISABLED total:###
02.2004
Disable single zones · or · or


zone ### − ### SELECTED > hours DISABLED? (99=permanent)
Permanent disabling zone ### permanent DISABLED (hm = end) new zone no.?
Disabling for a few
Enter the desired disabling time in full

hours zone ### DISABLED for ## hours (hm = end) new zone no.?
hours (e. g. 2). Display shows
Display shows The yellow LED isolation is on.

After last zone has been displayed, sy-
stem turns back to overview. Display shows
parts of system DISABLED total:###
Display shows The yellow LED isolation is off.
02.2004
Disable all zones · or · Several zones disabled

MONITORING zone ###, wait. (F1 /hm = enabling) next zone?
Display shows With a running timeout after which the
zone is automatically enabled.
Display shows for a few seconds or
ENabling: 1. detector ’zone’ (1.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’
Enable a range of zones

ENable zone range ### to ### > confirm LAST zone no.?
MONITORING zones ###−###, wait (F1 /hm = enabling) > LAST zone
Display shows With a running timeout after which the
zone range is automatically enabled.
Display shows for a few seconds or
DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’
Enable all disabled zones
MONITORING zone ###, wait (F1 /hm = enabling) > LAST zone
Display shows With a running timeout after which all
zones are automatically enabled.
Display shows for a few seconds or
DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’
02.2004
Enable single zones

Exceptional situations may occur, where it is preferable to isolate only single detector devices instead of the whole detector zone. Such situations may be for example:
Construction work with smoke or heat development at a particular location within a large
zone with a lot of detectors
Malfunction of a detector in a zone with several detector devices
If a single detector should be isolated the detector has to be identified clearly! If the detector cannot be identified clearly, the whole detector zone should be isolated. A wrong isolation of a detector can cause an unwelcome call of the fire brigade!
zone ### SELECTED > element no.? (range ## − ##)
zone ### element ## SELECTED > hours disabled? (99=permanent)
zone ### elem. ## permanent DISABLED > new element no.? (range ## − ##)
Display shows The yellow LED isolation is on.
02.2004

ENABLE element: (zone range ### − ###) > zone no.?
ENABLE single element in zone ###: > element no.? (range ## − ##)
MONIT. zone ### elem. ##, WAIT (F1 /hm = enabling) next elem.?
02.2004

Remote transmission provided: No Yes Alarm to: Fault transmission provided: No Yes Alarm to:
The remote transmission facility establishes a transmission path to the fire department in the event of a fire alarm issued by the fire detection system. Depending on the alarm concept, the alarm is transmitted immediately to the fire department, or after a certain delay, giving time for investigation by operating personnel. In single cases a separate transmission path for fault messages is established.
Under normal conditions the remote alarm transmission facility is enabled to ensure minimal alarming times. The remote transmission facility is disabled only in special cases to prevent un- necessary turn out of the fire brigade. The transmission facility should be disabled for:
Test of the fire detection system
Maintenance and conversion works on the fire detection system
Display shows for a few seconds
The remote fire alarm transmission is disabled. The yellow LEDs of the display fields Isolation and Remote alarm/fault off are on. The text display indicates that no alarm message is pending.
Display shows for a few seconds
The remote fire alarm transmission is enabled. The yellow LEDs of the display fields Isolation and Remote alarm/fault off are off, if no other
parts of the system are isolated.
02.2004
RT−alarm permanent DISABLED · RT−alarm ENABLED

Display shows for a few seconds
The remote fault transmission is disabled. The yellow LED of the display field Isolation is on. The text display indicates that no alarm message is pending.
Display shows for a few seconds
The remote fault transmission is enabled. The yellow LED of the display filed Isolation is off, if no other parts of the system are isola-
ted.
02.2004
RT−fault DISABLED · RT−alarm ENABLED

Under normal conditions the alarm devices (e. g. horns or sirens) operate in active stand−by. They are only disabled for:
Test of the fire detection system.
Maintenance and conversion works on the fire detection system.
Normally all acoustic devices are disabled together. Single devices or lines are only disa- bled in exceptional cases. For the alarm devices there are always 2 lines, in some cases 4 lines, but max. 6 lines possible.

Display shows for a few seconds
Press St to finish the procedure. The desired alarm devices are disabled. The yellow LEDs of the display fields Isolation and Alarm horn fault/off are on. The text display indicates that no alarm message is pending.

Display shows for a few seconds
Press St to finish the procedure. The desired alarm devices are enabled. The yellow LEDs of the display fields Isolation and Alarm horn fault/off are off, if no other
parts of the system are isolated.
02.2004

02.2004

Fault messages are issued on the text display if a malfunction in the system, the cabling or the attached devices is detected. Additionally the LED in the fault display field is blinking.
The yellow LED in the fault display field changes from blinking to constant on.
Only a few faults can be remedied by the user. These are listed below. For all other faults call the SIEMENS service organization.
Defective or missing detector
Broken glass on manual call point
Display shows Manual call point with broken glass is
If a detector is missing, insert a detector of
the same type into the detector base.
If a detector is damaged, replace it with a detector of the same type and order a new reserve
detector from the SIEMENS service organization.
If a manual call point has been operated and the glass is broken, replace it, then press the key
Reset.
If the public power supply is down, no action is required. The emergency battery supplies the
system for several hours (according to local requirements at least 12 h, max. 72 h), depen- ding on the size of the emergency battery.
If the outage is not in the public power supply:
Printer out of paper
Insert a new paper roll ( page 45, Printer: Paper replenishing).
02.2004
or · flashing · Mains POWER OFF

02.2004

For function tests of the automatic fire detectors and the manual call points, zones of the fire detection system are set into the “detector test mode”. In the detector test mode a responding detector or manual call point triggers only a test alarm. This allows individual on−site function tests, where automatic fire detectors deliberately are trig- gered by means of special detector test equipement. Manual call points are triggered either with a special test key or by opening the cover and actua- ting the button.
Test alarm A test alarm generates no danger message on the control console. Acoustic alarm devices, the remote alarm transmission or any other control functions are not activated. A test alarm is indicated on the text display of the control console as test−ALARM ZONE #. It is recorded in the event memory and automatically logged, if a printer is connected.
Frequency Visual control of detectors and manual call points: Once a year. Testing of all detectors and manual call points: Once every two years.
Perform the function tests periodically. The frequency of function tests is determined by the
service engineer.
Switch only the fire detectors of a few zones at a time to detector test mode, never the entire
building.
For manual call points the function test needs to be performed only according to a sampling
plan, designed by the service engineer.
Test automatic fire detectors and manual call points separately. Never switch them to detec-
tor test mode simultaneously.
No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)
02.2004

Display shows for a few seconds
The selected detector zones are set
into detector test mode. Display shows The yellow LED of the display field de-
tector test mode are on.

No ’DET.TEST’ mode, set range ### − ###: > zone no.? (555=all, 0=end)
zone range ### − ### in ’DET. TEST’ mode Outputs NOT activated
Display shows for a few seconds

zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)
Display shows The selected zone range is set into de-
tector test mode. Display shows
No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)
’DET. TEST’ mode TERMINATED
Display shows for a few seconds
The detector test mode is terminated for
all detector zones.

No ’DET.TEST’ mode, set range ### − ###: > zone no.? (555=all, 0=end)
Display shows for a few seconds
The detector test mode is terminated for
all detector zones.
02.2004

Required equipement There are basically two kinds of automatic fire detectors: heat detectors and smoke detectors. For heat detectors the detector tester RE6T is required, which simulates the temperatur rise with a hot air blower. Smoke detectors exist also as the variation multisensor smoke detector. Both are tested with the detector tester RE6, which also can be used as tool for the detector exchange. Smoke is detec- ted by its light scattering, which is optically simulated by the detector tester RE6.
Identification of detectors Smoke detectors, multisensor smoke detectors and heat detectors can be identified by their housing, see illustration.
If the tested detector did not respond, exchange the detector unit.

Test procedure for detector tester RE6
The functional testing is completed.
If the tested detector did not respond, check the gas can inside the detector tester RE6 or the
battery inside the tester DZ1193. If defective detectors are found call the SIEMENS service organization.
Detector tester RE6 (gas)
Test procedure for detector tester RE6T

The functional testing is completed.
If the tested detector did not respond, exchange the detector unit.
02.2004
Multisensor smoke detector · Heat detector · Detector tester RE6T

Test procedure for type KAC
A test alarm is simulated.
The functional testing is completed.
If the tested manual call point did not respond, call the SIEMENS service organization.
Test procedure for type DIN (indirect activation)
A test alarm is simulated.
The functional testing is completed.
If the tested manual call point did not respond, call the SIEMENS service organization.
mode ’detector TEST’ ACTIVE > test−ALARM zone ###/##
Each test alarm is indicated in the display for a few seconds and also registered in the event
memory.
02.2004

Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis- play fields, the text display and the alarm buzzer of the control console. To check the correct function of these parts the lamp test can be initiated: All visual and audible devices of the control console are activated for a few seconds.
Frequency The lamps have to be tested at least once a year.
To initiate the lamp test. Display shows
TESTING lamps and display: > remaining time (→← ↓↑)
If one or more devices are malfunctional, call the SIEMENS service organization.
i Lamp test on local indication and control panels page 5.
02.2004

In case of mains interruption the power supply of the fire detection system relies on an internal battery pack. The capacity of the battery pack is sufficent to keep the system for a couple of hours operating ( page 32, Faults). As the lifetime of batteries is limited, a battery load test has to be performed periodically to ensure a good condition of the battery pack: For 10 seconds the battery is highly loaded and the battery voltage is monitored. If the voltage drop is beyond a cer- tain value, the battery pack has to be replaced.
Frequency The batterie test is automatically performed by the system every 24 hours. If the battery is dama- ged, or provides only an insufficent capacity, a fault messages is displayed. Once a year the battery test has to be performed manually.
To initiate the battery load test. Display shows
If the battery test is completed, the sy-
RESULT battery test: > battery OK.
stem shows the result. Display shows for a few seconds
If the battery load test yields insufficent battery capacity, call the SIEMENS service organization to replace the battery.
02.2004

The fire detection system is equipped with acoustic alarm devices distributed throughout the building to alarm the fire brigade in case of fire. The function of the acoustic alarm devices has to be checked periodically. The “horn test” activates all acoustic alarm devices for 30 seconds.
Frequency The acoustic alarm devices have to be tested at least once a year.
To initiate the horn test. Display shows The horn test runs for 30 seconds. The remaining time is indicated. After the test has finished, the submenu is displayed again.
If an acoustic device did not respond in the test, call the SIEMENS service organization for repla- cement or repair.
The horn test can be stopped before expiration of the 30 seconds by pressing hm .
02.2004

In test mode the function of the remote transmission can be tested without activating an alarm device or a manual call point. The function of the remote transmission facility has to be checked periodically. The remote alarm transmission and the remote fault transmission can be tested separately.
Frequency The acoustic alarm devices have to be tested at least once a year.
To initiate the remote ALARM test. Display shows
Display shows The test runs for 30 sec. The remaining
time is indicated. After the test has finished, the submenu is displayed again.
If the remote alarm did not arrive at the fire departement, call the SIEMENS service organization for repair.
The test can be stopped before expiration of the 30 seconds by pressing hm .
To initiate the remote FAULT test. Display shows
The test runs for 30 sec. The remaining
time is indicated. After the test has finished, the submenu is displayed again.
If the fault message did not arrive at the remote location, call the SIEMENS service organization for repair.
The test can be stopped before expiration of the 30 seconds by pressing hm .
02.2004

02.2004

02.2004

i Printer connected: Yes No
Under normal conditions the printer operates in active stand-by. It is only disabled in special ca- ses e. g. for change of paper or repair.
Display shows for a few seconds The printer is disabled. The yellow LED of the display field Isolation is on.
Display shows for a few seconds The printer is enabled. The yellow LED of the display field Isolation is off, if no other parts of the system are isola-
ted.
02.2004
printer DISABLED

Before changing the printer paper disable the printer by the control panel menu ( page 44).

B2Q101
H
Change of printer paper
After changing the printer paper, enable the printer by the control panel menu ( page 44).
Following types of paper rolls are available for the printer:
part no. 279 977 (4 pieces)
HOSHU PS 65 B1
MITSUBISHI F − 200 U7X
Print intensity
If the print intensity is too low, call the SIEMENS service organization.
02.2004

The alarm counter allows to get information about the number of alarms and remote alarms in the past.
Display shows for a few seconds The submenu is displayed.
02.2004

The event memory allows to get information about events registered by the fire detection system in the past. Always the last 200 events are registered by the system.
The first line tells the event number and
the date and time of its occurance, the second line reproduces the correspon- ding event message. Display shows
viewing EVENT no ##: ##.##.## ##:##:## event text
02.2004

The assignment of the zone numbers to the descriptive user text is stored in the memory of the fire detection system and can be displayed on the text display of the control console.
display of USER TEXT for ### ZONES/ELEM: (key: ↓ = forward / ↑ = backward)
The first line tells the zone number, the
second and third line reproduces the corresponding user text. Display shows
display USER text of zone ###: zone ###/ −: ###### ground floor main entrance ↓: forward ↑: backwards
02.2004

After acknowledging messages from various system states differing from “normal operation” as “isolation” or “fault”, detailed information may be no longer visible on the text display. Only the LEDs of the display fields and a more general message like “parts of the system isolated” on the text display indicate a special system state. More detailed informations e. g. which zones are isolated, or which elements are faulty can be retrieved by polling the system status at any time.
A scroll page for the selected item is dis-
played, here for example for “fault“. Display shows
display FAULT messages: total:## fault messages
02.2004

The polling of configuration data is only relevant for the service engineer, for controlling user functions without the configuration tool.

ZONE ### selected. ok = single ZONE Second ZONE No.? (range ### − ###)
Zn ###:###### tst:######dis:######## el ele ## name=###### type=###### al=###### incr=###### dr=###### trouble=###### ln ## dev ##


LINE ## selected. ok = single line Second line no.? (range ## − ##)
line ###: ######, ### devices device ### name=###### type=###### al=###### incr=###### dr=###### trouble=###### zn ### el ##
02.2004

All informations that can be polled also can be printed, if a printer is connected.
PRINTOUT in process:
PRINTOUT in process:
PRINT: 1. configuration system (4.3.3) 2. configuration coll. line 3. user text detector zn/elem 4. user text ConTrol zone
PRINTOUT in process:
PRINTOUT in process:
02.2004

i Changeover summertime to wintertime: manually automatically
Time and date are set by the service engineer when the system is put into service. Under normal conditions there is no need to correct time and date. The changeover from summertime to wintertime and vice versa is performed automatically for Central European Time. Central European Time is valid for Western Europe, most of Eastern Europe an parts of Russia. The switchover from summertime to wintertime is performed at the last sunday in March, vise versa at the last sunday in October. Differing automatic switching ti- mes are not possible. Only due to an electronical distortion or a complete power failure (mains and battery interrupted) the system sets time and date to “default”.
Log in with at least ”access level 2”.
START system operating > enter password?
set TIME: ##:##:## > new time: hour.min.sec.?
set DATE: ##.##.## > new date: day.mon.year?
Time and date are set to the current va-
lues. Display shows
02.2004

Back 02.2004

Siemens Building Technologies AG
CH-8708 Männedorf Alte Landstrasse 411
Tel. Fax www.cerberus.ch
+41 1 − 922 61 11 +41 1 − 922 64 50
Fire & Security Products Siemens Building Technologies Group Document no.
Back 02.2004
02.2004
Manual FD-M · Edition · Section 8