Siemens Fire Alarm Control Panel (FC330A)

58 pages·543 KB·Smoke Alarm·PDF·ENDEFRITNLJA
Siemens Fire Alarm Control Panel (FC330A)
Table of Contents 80 sections Synova ® FC330A Fire detection system · Operating manual System operation for user · Fire & Security Products · Introduction · … ShowHide
Synova ® FC330A Fire detection systemp.1Operating manual System operation for userp.1Fire & Security Productsp.1Introductionp.5About this operation manualp.6How to use this operation manualp.6How to read this operation manualp.6Fundamentalsp.7Control console layoutp.8Control console FC330Ap.8ALARMp.8NORMAL OPERATIONp.8MON 04.01.99 09:13p.8F1p.8F2p.8FC330Ap.8Floor panelp.9Overview operating menup.10only for servicep.12engineerp.12Fundamental operationp.13How to operate the control consolep.13Examplep.13Actions in the operation manualp.13What is “normal operation”?p.14WED 21.7.99 15:00p.14Mains interruptionp.14Operating accessp.15Possible access levelsp.15How do I get operating access?p.15Operating access via passwordp.16Operating “manned” and “unmanned”p.17i SPECIAL Alarm Concept used: Yes No p.17Basic rulesp.17Manual switching between the operating states “manned” and “unmanned”p.17Automatic switchoverp.18Extra timep.18SPECIAL Alarm Conceptp.20Purpose and principlep.20Principlep.22How are alarm messages shown on the text display?p.23Disable/Enable System Partsp.25Temporary isolation of a detector zonep.26What is a detector zone?p.26When has a detector zone to be isolated?p.26Zone isolation procedurep.27WED 21.7.00 15:00p.27Viewing disabled zonesp.28Zone reactivation procedurep.28Temporary isolation of a single detectorp.30When has a single detector to be isolated?p.30Single detector isolation procedurep.30Detector reactivation procedurep.31Remote Transmissionp.32What is “remote transmission”?p.32When has the remote transmission to be disabled?p.32Disabling the remote alarm transmission facilityp.32Enabling the remote alarm transmission facilityp.32Disabling the remote fault transmission facilityp.33Enabling the remote fault transmission facilityp.33Alarm devicesp.34When have alarm devices to be disabled?p.34Disabling the alarm devicesp.34Enabling alarm devicesp.34Faultsp.35How do I respond to fault messages?p.36What remedies are available to the user?p.36TUE 27.7.99 10:35p.36Maintenancep.37Detector testp.38i Differing national or local regulations always have priority!p.38Recommendations for function testsp.38Setting single detector zones into detector test modep.38Setting a zone range or all detectors into detector test modep.39Terminating the detector test mode for single zonesp.39Terminating the detector test mode for a zone rangep.39Functional testing of automatic AlgoRex-detectorsp.40Functional test of manual call pointsp.41Lamp testp.42Purpose of the lamp testp.42
Page 1 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Synova ® FC330A Fire detection system
Page 1 · click to enlarge
Page 1
Siemens Fire Alarm Control Panel (FC330A) — Synova ® FC330A Fire detection system diagram (page 1)
Fig. 1 · Synova ® FC330A Fire detection system

Synova ® FC330A Fire detection system

Operating manual System operation for user

Fire & Security Products

Siemens Building Technologies Group

Phase 4

Page 2 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Synova ® FC330A Fire detection system
Page 2 · click to enlarge
Page 2

Data and design subject to change without notice. / Supply subject to availability. Copyright by Siemens Building Technologies AG

Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder ausserhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.

We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.

Nous nous réservons tous les droits sur ce document, ainsi que sur l’objet y figurant. La partie recevant ce document reconnaît ces droits et elle s’engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l’employer à des fins autres que celles pour lesquelles il lui a été remis.

Ci riserviamo ogni diritto relativo al presente documento e sull’oggetto illustrato in esso. La parte che riceve il documento si impegna a non renderlo accessibile a terzi, né per intero né in parte, senza la nostra previa autorizzazione scritta ed a non usarlo per altri scopi di quello per il quale è stato rilasciato.

Page 3 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Synova ® FC330A Fire detection system
Page 3 · click to enlarge
Page 3

Introduction 1

About this operation manual 2

Fundamentals 3

Control console layout 4

Floor panel 5

Overview operating menu 6

Fundamental operation 9

Normal operation 10

Operating access 11

Operating “manned” and “unmanned” 13

Alarm 15

Cerberus Alarm Concept (CAC) 16

Alarm 18

Disable/Enable System Parts 21

Temporary isolation of a detector zone 22

Temporary isolation of a single detector 26

Remote Transmission 28

Alarm devices 30

Faults 31

Faults 32

Maintenance 33

Detector test 34

Lamp test 38

Battery load test 39

Test of acoustic alarm devices 40

Test of Remote Transmission (RT) 41

Other Functions 43

Printer disabling/enabling 44

Paper replacement with logging printer B2Q191 45

Poll alarm counter 46

Poll event memory 47

Poll user text of zones or elements 48

Poll system status 49

Poll configuration data 50

Printout 51

Set time and date 52

06.2003

Page 4 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Synova ® FC330A Fire detection system
Page 4 · click to enlarge
Page 4

06.2003

Page 5 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Introduction
Page 5 · click to enlarge
Page 5

Introduction

02.2004

Page 6 of the Siemens Fire Alarm Control Panel (FC330A) user manual — How to read this operation manual
Page 6 · click to enlarge
Page 6

About this operation manual

How to use this operation manual

This operation manual describes the use and the operation of the control console FC330A. It contains all information for the normal user with access level 2 who has to react to alarms, disa- ble and enable parts of the system, etc. This document contains the following:

ChapterContentsPage Introduction− General information about this operation manual − How to use this manual1 FundamentalsFundamental information on the console: − Description of the control console, functions of the keys − Description of the floor panels, functions of the keys − Overview of the menu structure − Fundamental operation of the console − What is normal operation − How to get access for operation − Manned and unmanned operation3 Alarm− Organisation of the SPECIAL Alarm Concept − How to read an alarm message − How to react in an alarm situation15 Disable/Enable System Parts− Temporary isolation of a detector zone/single detectors, i. e. for repair works − Disabling/Enabling remote transmission − Disabling/Enabling alarm devices21 Faults− How to react to a fault message − Remedies by the user31 MaintenanceMaintenance works carried out by the user e.g.: − Testing detectors − Testing lamps, batteries, alarm devices, remote transmission33 Other functions− Disabling/Enabling the printer, paper replacement − Printing information − Polling information, i. e. alarm counter, event memory, user texts, system status, configuration data − Setting time and date43

How to read this operation manual

This operation manual uses several symbols to guide the user through the manual. The meanings in detail are:

1. Multi step actions are marked with numbers.

Single step actions are marked with a triangle.

The result of an action is marked with an arrow. In body text you will find quotations like display texts, keys or LED−fields or LEDS. Frequently used keys are shown as they look like on the console, e.g. ok .

02.2004

Page 7 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Fundamentals
Page 7 · click to enlarge
Page 7

Fundamentals

02.2004

Page 8 of the Siemens Fire Alarm Control Panel (FC330A) user manual — F2
Page 8 · click to enlarge
Page 8

Control console layout

Control console FC330A

ALARM

NORMAL OPERATION

MON 04.01.99 09:13

Remote alarm fault / off

Remote alarm active Alarm delay off

F1

Fault Isolation

Alarm horn fault / off

F2

FC330A

ALARM LED bar Red LED’s blinking when an alarm signal is pending.

Text display Displays selection menus as well as alarm and fault messages.

Scroll key Allows scrolling of alarm messages in the text display.

Acknowledge key Confirms an alarm or a message (2 variants possible).

Variant 1:

Variant 2:

1st activation Alarm horns and buzzer

1st activation Buzzer off

2nd activation Alarm horns off

2nd activation Reactivation alarm horns

3rd activation Reactivation alarm horns

Reset key Resets alarm and fault messages.

Display fields Indicates the operating state by an LED.

Command fields Possess a button to change the operating mode and may have an LED to indicate the operating state.

Alarm delay off Cancels alarm delay. Remote alarm is given immediately.

Toggles between “manned” and “unmanned” operating mode.

Function keypad Keys for menu−orientated operation and password input.

St Start/Stop key Open and close menus.

F1 F2 Function keys Usage depends on context.

ok Execution key Starts the selected menu function.

Move up/down key Selects menu items upwards/downwards.

hm Home key Returns to the previous menu.

del Delete key Deletes the character left of the cursor.

Keylock switch Gives access to user operating level 2 without password. Only when keylock switch is installed.

02.2004

Show 13 more labels / short text on this page
Acknowledge · Silence/resound horn · Reset · System on · Start/ · Stop · Premises manned · ok · System fault · Detector test mode · hm 0 del · off · Premises manned key
Page 9 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Floor panel
Page 9 · click to enlarge
Page 9

Floor panel

The floor panel is a typical local indication terminal. It mainly serves to display alarm events re- motely. Secondary it is also an operating terminal to acknowledge and reset the control console from remote. Two types of panels are available:

Siemens Fire Alarm Control Panel (FC330A) — Floor panel diagram (page 9)
Fig. 2 · Floor panel

ALARM zone ###/## / ###### 1( 1) 1st floor office 101 ALARM zone ###/## / ###### 1( 1) 1st floor office 101

Scroll key Allows scrolling of alarm messages in the text display.

Also to initiate lamp test (press key 3 sec).

Acknowledge key Confirms an alarm or a message.

Display fields Indicates the operating state by an LED.

Keylock switch Gives access to user operating level 2 without password.

The display of the floor panel indicates the same event text as shown at the control console. It only displays one message at a time.

02.2004

Page 10 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Overview operating menu
Page 10 · click to enlarge
Page 10

Overview operating menu

After getting operating access, the start menu appears. From the main menu, all menus can be selected ( page 9, fundamental operation). With access level 2 all menu points exept other functions − configuration can be selected. The passwort for access level 2 is:

ENABLE1. Detector/ConTrol ZONES (1) 2. horn/RT/alarm contacts 3. printer

ENabling: 1. detector ’zone’ (1.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’

Enable detector zones 1...256 Enable detector elements within zone Enable control zones 1...64

Enable all control zones

ENabling1. horn (1.2) 2. alarm contacts 3. RT−alarm 4. RT−fault

Enable control lines 1...4 for alarm horns Enable alarm contacts 1...4 Enable remote transmission ALARM

Enable remote transmission FAULT

Enable only event logging or all messages

ENable printout messages: 1. log ALL (old: #) 2. only ALARMS 3. log NONE Enable only alarms or none

Disable detector zones 1...256 disabling permanent or for a set time 1...98h

DISabling1. detector/ConTrol ZONES (2) 2. horn/RT/alarm contacts 3. printer

DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’

Disable detector ELEMENTS within zone disabling permanent or for a set time 1...98h Disable conTrol zones 1 64

Disable all control zones

DISabling1. horn (2.2) 2. alarm contacts 3. RT−alarm 4. RT−fault

Disable control line 1..4 for alarm horns Disable alarm contacts 1...4 Disable remote transmission ALARM

Disable remote transmission FAULT

Disable only alarms or none ENable printout messages: 1. log ALL (old: #) 2. only ALARMS 3. log NONE

Disable only event logging or all messages

View fault messages View turned off system components View pre-alarm messages View ELEMENT states

INFO1. system status (3) 2. event memory/alarm counter 3. configuration/user text 4. configuration zone/line/LON
STATUS1. fault (3.1) 2. isolation 3. pre−alarm 4. techn.alarm /element status
MEMORY1. event memory (3.2) 2. alarm counter

View reviewing event list View number of alarms and remote alarms

INFO: 1. configuration system (3.3) 2. configuration coll line 3. user text detector zn/elem 4. user text ConTrol zone

View general parameter settings View parameter settings coll. lines View user texts detector zones/elements View user texts control zones

View parameter settings detector zones View parameter settings addr. lines View parameter settings LON-bus

INFO1. configuration det. zones (3.4) 2. configuration addr. lines 3. configuration LON devices

02.2004

Page 11 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Overview operating menu
Page 11 · click to enlarge
Page 11
FUNCTIONS1. function (4) 2. system TEST 3. printout 4. configuration
FUNCTIONS1. switching alarm org. (4.1) 2. set time / date

Switching manned unmanned via menu Set or adjust time and date

SYSTEM TEST1. horn/ al.co ntact/RT (4.2) 2. lamps/battery 3. fire and contr.zones

Activate all ’horns’ for 30 sec Activate all ’alarm contacts’ for 30 sec. Activate ’remote alarm’ for 30 sec. Activate ’remote fault’ for 30 sec.

SYSTEM TEST1. horn (4.2.1) 2. alarm contacts 3. RT−alarm 4. RT−fault
SYSTEM Test1. lamps/display (4.2.2) 2. battery

Activate all LEDs and LCD for 10 sec. Load battery for 10 sec.

SYSTEM TEST: 1. single zone test (4.2.3) 2. zone range test 3. set control zones Set control zone to ’control zone Test’ X..Y

Set detectors to ’Detector test’ per zone

Set detectors to ’Detector test’ zone X...Y

PRINT1. system status (4.3) 2. event memory/alarm counter 3. configuration/user text 4. configuration zone/line/LON
PRINT1. fault (4.3.1) 2. isolation 3. pre−alarm 4. techn.alarm /element status

Print current fault messages Print current turned off system components Print current information messages Print current ELEMENT states

PRINT1. event memory (4.3.2) 2. alarm counter

Print event memory list Print alarm counter readings

Print general parameter settings Print parameter settings coll. lines Print user texts detector zones / elements Print user texts control zones

PRINT: 1. configuration system (4.3.3) 2. configuration coll. line 3. user text detector zn/elem 4. user text ConTrol zone

Print parameter settings detector zones Print parameter settings addr. lines Print parameter settings LON-bus

PRINT1. configuration det. zones (4.3.4) 2. configuration addr. lines 3. configuration LON devices

02.2004

page 8

Page 12 of the Siemens Fire Alarm Control Panel (FC330A) user manual — only for service
Page 12 · click to enlarge
Page 12

FUNCTIONS: 1. function (4) 2. system TEST 3. printout 4. configuration CONFIGURATION: 1. user functions (4.4) 2. user text 3. service functions 4. erase functions

direct setting user parameters direct definition user texts

Level SERVICE FUNCTIONS > enter password?

only for service

engineer

SERVICE 1. addr. line −> CONNECT level : 2. addr. line −> DISCON. (4.4.3) 3. test AI−LED’s ON/OFF 4. reconfigure addr. lines

connect addressable loop disconnect addressable loop for TEST LEDs to reconfigure addr. lines

5. horn/ctrl/RT −> OFF 6. TEST−alarm −> HORN 7. Visualizer ON/OFF 8. re−parametrise LON

to activate horn briefly with each det. TEST alarm enable / disable ’visualizer’

to start automatic configuration of LON- Bus

Level SERVICE FUNCTIONS > enter password?

ERASE data: 1. ERASE alarm counter (4.4.4) 2. ERASE event memory 3. ERASE conf + sys data 4. ERASE element status

(locked with switch ’S2’) (not locked)

only for specialized personell

to erase ’non−alarm’ events

02.2004

for COMMON disabling

Page 13 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Actions in the operation manual
Page 13 · click to enlarge
Page 13

Fundamental operation

How to operate the control console

To choose a menu item in the display of the console:

Siemens Fire Alarm Control Panel (FC330A) — How to operate the control console diagram (page 13)
Fig. 3 · How to operate the control console

Access level page 11 SELECT: 1. ENabling (main menu) 2. DISabling 3. INFO polling 4. other functions

2. Enter the password and press ok .
3. Select the menu item with the and keys and press ok . or

Enter the number of the menu option on the numeric keypad (e. g. option 2.). Display shows

DISabling1. detector/ConTrol ZONES (2) 2. horn/RT/alarm contacts 3. printer
4. Repeat the selection until the required menu is displayed.
5. Follow the instructions on the display.
6. Finish the operation by pressing St . or

Press hm to return to the previous menu.

Example

The following description is an example for choosing the Disable elements menu.

2. Log in.
3. Select option 2. with the and keys and press ok . or

Enter “2”. Display shows

DISabling1. detector/ConTrol ZONES (2) 2. horn/RT/alarm contacts 3. printer
4. Select option 1. with the and keys and press ok . or

Enter “1”. Display shows

Siemens Fire Alarm Control Panel (FC330A) — Example diagram (page 13)
Fig. 4 · Example

DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’

5. Select option 2. with the and keys and press ok . or

Enter “2”. Display shows

DISABLE element> zone no.? (range ### − ###)

Actions in the operation manual

In this operation manual, selecting a menu item will be described from now on in a short form as follows:

DISABLE element> zone no.? (range ### − ###)

02.2004

Page 14 of the Siemens Fire Alarm Control Panel (FC330A) user manual — NORMAL OPERATION
Page 14 · click to enlarge
Page 14

Normal operation

What is “normal operation”?

The system is ready to receive danger messages (alarm) from the detectors.

No fault messages are pending.

The green LED in the display field System on is on.

The illumination of the text display may be turned off, but turns on as soon as any key is

pressed or an alarm, fault or status is issued.

NORMAL OPERATION

WED 21.7.99 15:00

Mains interruption

In case of a mains interruption the fire detection system is powered by an internal battery. No fault message is issued in the text display and the normal operation will continue , until a preset default time is expired When the system is powered by the internal battery the green LED in the display field System on is blinking.

The delay is min Standard default: 10 min

Siemens Fire Alarm Control Panel (FC330A) — NORMAL OPERATION diagram (page 14)
Fig. 5

02.2004

Page 15 of the Siemens Fire Alarm Control Panel (FC330A) user manual — How do I get operating access?
Page 15 · click to enlarge
Page 15

Operating access

Possible access levels

Three main access levels are defined allowing different privileges for the operation of the fire detection system. Access is provided by a four digit password for the higher access levels, re- spectively.

After 3 consecutive incorrect password entries the operation access is disabled for 15 minu- tes.

Overview of the access levels

Siemens Fire Alarm Control Panel (FC330A) — Possible access levels diagram (page 15)
Fig. 6 · Possible access levels
possiblewith access level 1 with access level 2

(password required or key−lock switch, if instal- led)

Automatic timeout The access by password is automatically cancelled if no key is operated for:

5 min during state of “normal operation“

30 sec during condition “alarm“

How do I get operating access?

Enter the password on the keypad as described below.

Turn the keylock switch in horizontal position.

Access with level user operating 2 is provided as long as the key is left in horizontal position.

Siemens Fire Alarm Control Panel (FC330A) — How do I get operating access? diagram (page 15)
Fig. 7 · How do I get operating access?

02.2004

Acknowledge messages · or

Page 16 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Operating access via password
Page 16 · click to enlarge
Page 16

Operating access via password

The passwords are defined and released to the operators by the service engineer. In case of misskeying the password, use del to cancel keying errors.

START system operating > enter password?

hm /Stopend operating
2. Enter the password and press ok .
3. Proceed operating (access is now provided)

Log out There is no log out procedure, because the operating access expires automatically if no key is pressed within a certain time ( page 11, Automatic timeout).

02.2004

Log in

Page 17 of the Siemens Fire Alarm Control Panel (FC330A) user manual — WED 21.7.99 15:00
Page 17 · click to enlarge
Page 17

Operating “manned” and “unmanned”

i SPECIAL Alarm Concept used: Yes No

Basic rules

The operating states “manned” and “unmanned” are defined in a SPECIAL Alarm Concept, where signals from automatic fire detectors and manual call points are processed differently (for details page 16). The switchover from the operating states “manned” to “unmanned” and vice versa is either done manually by the operating personnel or automatically as programmed by the service engineer.

The operating person, responsible for the surveillance of the system and the alarm investiga-

tion, is present on the premises.

The LED in the display field Premises manned is on.

The LED in the display field Isolation is on (depends on system configuration).

The responsible operating person is not present on the premises.

The LED in the display field Premises manned is off.

Remote alarm fault / off

Remote alarm active Alarm delay off

F1

Alarm horn fault / off

F2

FC330A

Manual switching between the operating states “manned” and “unmanned”

Manual switching between the operating states “manned” and “unmanned” is only possible during defined working hours ( page 14, Automatic switchover).

1. Log in with ”access level 2”.
2. Press the Premises manned key on the control panel to toggle between the operating states “manned” (yellow LED is on) and “unmanned” (yellow LED is off). or

Toggle between “manned” and “unmanned” via menu which is described next page.

NORMAL OPERATION

WED 21.7.99 15:00

NORMAL OPERATION mode ’manned’

WED 21.7.99 15:00

02.2004

Show 14 more labels / short text on this page
Operating state “manned” · Operating state “unmanned” · System on · Start/ · Stop · Fault · Premises manned · Isolation · System fault · ok · Detector test mode · hm 0 del · Operating state ”unmanned” · Operating state ”manned”
Page 18 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Extra time
Page 18 · click to enlarge
Page 18

mode ’manned’ until ##:##, 1.> unmanned sel. #, 2.> manned 3.extra time

3. If the operating state has to be changed to − “manned”: select option 1. − “unmanned”: select option 2.

If mode ”manned” is selected Display shows for a few seconds

mode ’manned’ TERMINATED > system is set to NORMAL OPERATION

timeout /hmmenu Stop: end operating

Automatic switchover

The automatic switchover is used for example, to prevent the system status “manned” during nighttime when no operating personnel is present: The system switches automatically to status “unmanned” at a defined time (e. g. after the office hours). The same scheme can be used for unattended times during weekends or holidays. The automatic switchover scheme is defined by the service engineer. No user action is required.

Automatic switchover from “manned” to “unmanned”: at p.m.

Automatic switchover from “unmanned” to “manned”: at a.m.

Extra time

The function “extra time” allows to set the system to manned operation for a preset time, after the automatic switchover to unmanned has taken place.

activated not activated

mode ’unmanned’ 2. > ’manned’ (hm = INTERRUPT) 3. extra time

The actual display depends on the initial mode, here e. g. mode unmanned (i. e. after

17:00).

EXTRA TIME h/min? (max. ##:##)

hm: back to menu Stop: end operating Extra time max.

4. Enter the extra time.

The time until the system is set to manned mode is displayed.

02.2004

Toggle via menu · Function extra time

Page 19 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Alarm
Page 19 · click to enlarge
Page 19

Alarm

02.2004

Page 20 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Purpose and principle
Page 20 · click to enlarge
Page 20

SPECIAL Alarm Concept

Purpose and principle

To prevent the unnecessary turn out of the fire department for minor incidents a SPECIAL Alarm Concept was developed. It involves operating personnel in the alarming sequence and relies on two operating states:

“unmanned” mode while the operating personnel is not present on the premises.

“manned” mode while the operating personnel is present on the premises.

“unmanned” mode When the system operates in “unmanned” mode, the fire brigade is called immediately when an alarm signal is issued.

“manned” mode When the system operates in “manned” mode, manual call points and automatic detectors trig- ger different actions in the event of an alarm:

Manual call point is actuated The fire brigade is summoned immediately.

Automatic fire detector responds The fire brigade is summoned only after a preprogrammed time in which the operating personnel performs following alarm response procedure:

1. Confirm the alarm within the alarm acknowledgement time V1 (press the Acknowledge key).
2. Read the alarm locations on the text display.
3. Go to these locations immediately.
4. Decide at the face whether this is an emergency or a minor incident.

Emergency Actuate the nearest manual call point immediately!

or Press the Alarm delay off key on the control console! The fire brigade is summoned immediately.

Minor incident Reset the system before expiration of the alarm investigation time V2 by pressing the Reset key.

The system is in the normal operation mode again.

i The times V1 and V2 are only relevant, when the remote transmission is installed.

02.2004

Event Action

Page 21 of the Siemens Fire Alarm Control Panel (FC330A) user manual — SPECIAL Alarm Concept
Page 21 · click to enlarge
Page 21

V1 = min.

Alarm acknowledgement time V1

The alarm acknowledgement time is active for automatic detectors when the system opera-

tes in “manned” mode.

The system checks whether someone acknowledges the alarm message within this prepro-

grammed time.

An alarm must be acknowledged before V1 expires, otherwise the alarm is transmitted to the

fire department.

The remaining time is indicated on the text dis-

play in minutes and seconds.

ALARM zone ###/## / ######

1:27 min

V2 = min.

Alarm investigation time V2

The alarm investigation time is active for automatic detectors when the system operates in

“manned” mode.

It limits the time for investigating the fire location to an preprogrammed length.

On expiration of this time the alarm is transmitted to the fire department.

In case of minor incidents, an alarm must be reset before V2 expires.

The remaining time is indicated on the text dis-

play in minutes and seconds.

ALARM zone ###/## / ######

2:27 min

02.2004

1 ( 1) · 1 ( 1)

Page 22 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Principle
Page 22 · click to enlarge
Page 22

Alarm

Principle

An alarm is issued by the system if an automatic detector has responded or a manual call point was actuated. The alarm is indicated by:

−blinking of the red LED alarm bar on the control console −alarm message on the text display

−buzzer of the control console −attached signal horns As described in the SPECIAL Alarm Concept, the operating personnel is involved into the alarm scheme only if the system is in “manned” mode. In all other cases, i. e. SPECIAL Alarm Concept is not activated (used) or the system operates in “unmanned” mode, the alarm is transmitted immediately to the fire brigade.

During alarm other states such as faults etc. are not shown at the display. However, it is possible to make them visible via the menu “Info polling” (For details page 49).

Siemens Fire Alarm Control Panel (FC330A) — Principle diagram (page 22)
Fig. 8 · Principle

ALARM zone ###/## / ###### 1st floor canteen 1( 1)

02.2004

optical signals · acoustic signals

Page 23 of the Siemens Fire Alarm Control Panel (FC330A) user manual — How are alarm messages shown on the text display?
Page 23 · click to enlarge
Page 23

How are alarm messages shown on the text display?

A single alarm message on the text display consists of 2 lines as shown in the example to the right.The first line tells that the alarm was given in zone 5 by the element 1 of this zone, which was an automatic fire detector. The numbers at the end of the line tell, that this is the first of in total 3 alarm messages. The se- cond line gives the explicit location of the re- sponding detector. The 3. and the 4. line hold the same information for the last alarm message issued. In this case a manual call point was actuated in zone 3 of the building, which is located in the ground floor main entrance.

ALARM zone ###/## / ###### 1st floor canteen

ALARM zone ###/## / ###### ground floor main entrance

Siemens Fire Alarm Control Panel (FC330A) — How are alarm messages shown on the text display? diagram (page 23)
Fig. 9 · How are alarm messages shown on the text display?
1. alarm message zone 5, element 1 ”1st floor canteen”
3. alarm message zone 3, element 1 ”ground floor main entrance”

Scrolling alarm messages Additional pending messages can be retrieved using the scroll key.

Press the scroll key below the text display.

The first two lines are superseeded with the subsequent alarm message.

Retrieving supplementary informations Supplementary informations to the alarm messages can be retrieved by using F1 and F2 :

F1 tells the type of the responding device, e. g. automatic detector.

F2 tells the cabling address and the type number of the responding device (device address).

Press F1 (or F2 ).

The second line in the text display is superseeded with the supplementary information.

Press the scroll key to retrieve supplementary information of subsequent alarm messages.

Siemens Fire Alarm Control Panel (FC330A) — How are alarm messages shown on the text display? diagram (page 23)
Fig. 10 · How are alarm messages shown on the text display?

If a manual call point was activated while the alarm, insert a new front glass in the actual call

02.2004

1( 3) · 3( 3)

Page 24 of the Siemens Fire Alarm Control Panel (FC330A) user manual — How are alarm messages shown on the text display?
Page 24 · click to enlarge
Page 24

02.2004

Page 25 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Disable/Enable System Parts
Page 25 · click to enlarge
Page 25

Disable/Enable System Parts

02.2004

Page 26 of the Siemens Fire Alarm Control Panel (FC330A) user manual — When has a detector zone to be isolated?
Page 26 · click to enlarge
Page 26

Temporary isolation of a detector zone

What is a detector zone?

The detectors and manual call points of the fire detection system are grouped into zones, which are defined according to geographical aspects of the building. Zones may be all self-contained areas of a building, for example

adjacent rooms (no doors between the rooms)

Siemens Fire Alarm Control Panel (FC330A) — What is a detector zone? diagram (page 26)
Fig. 11 · What is a detector zone?

In that way, a zone represents a “room address”. Each zone contains one or more automatic fire detector devices or manual call points.

Assignment of zones to building areas For each zone a descriptive user text (e. g. room designation and floor no.) is defined in the sy- stem. Only in case of an alarm, this text is displayed on the text display together with the zone and device number of the responding detector.

It is recommended to prepare a list holding the assignment of zone numbers to actual rooms and building-areas.

When has a detector zone to be isolated?

In exceptional situations zones have to be isolated from the system, to prevent unintended alarm. An exceptional situation depends on the kind of the detector and exists for zones with:

smoke detectors, if smoke or dust is produced by unusual work

heat detectors, if heat or steam is produced by unusual work

manual call points, if there is a possibility of inadvertent activation

02.2004

single rooms · corridors · staircases

Page 27 of the Siemens Fire Alarm Control Panel (FC330A) user manual — WED 21.7.00 15:00
Page 27 · click to enlarge
Page 27

Zone isolation procedure

Display shows Now you can disable single zones, a range of detector zones or all zones as described be- low:

DISable zones(range ### to ###) > zone no.? (555 = all)
1. Enter the desired zone number (e. g. 2).

zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)

2. Press ok to disable the single zone.

zone ### SELECTED > hours DISABLED? (99=permanent)

Permanent disabling zone ### permanent DISABLED (hm = end) new zone no.?

3. Enter 99 for permanent disabling.

Enter the desired disabling time in full

Disabling for a few

hours zone ### DISABLED for ## hours (hm = end) new zone no.?

hours (e. g. 2). Display shows

4. Press St to finish the zone disabling procedure. or

Enter another single zone number to disable.

parts of system DISABLED total:###

Display shows The yellow LED isolation is on.

WED 21.7.00 15:00

Disable a range of zones

1. Enter the first zone number of the range of zones to be disabled (e. g. 2).

zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###) _

2. Enter the last zone number of the range of zones to be disabled (e. g. 5).

zone ### − ### SELECTED > hours DISABLED? (99=permanent)

Permanent disabling zones ### − ### permanent DISABLED (hm = end) new zone no.?

3. Enter 99 for permanent disabling.
Siemens Fire Alarm Control Panel (FC330A) — WED 21.7.00 15:00 diagram (page 27)
Fig. 12

Disabling for a few

Enter the desired disabling time in full

hours zones ### − ### DISABLED for ## hours (hm = end) new zone no.?

hours (e. g. 2). Display shows

4. Press St to finish the zone disabling procedure. or

Enter another zone number to disable. Display shows The yellow LED isolation is on.

parts of system DISABLED total:###

WED 21.7.00 15:00

02.2004

Disable single zones · or · or

Page 28 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Zone reactivation procedure
Page 28 · click to enlarge
Page 28
1. Enter 555 to disable all zones in the building.
Siemens Fire Alarm Control Panel (FC330A) — Viewing disabled zones diagram (page 28)
Fig. 13 · Viewing disabled zones

zone ### − ### SELECTED > hours DISABLED? (99=permanent)

Permanent disabling zone ### permanent DISABLED (hm = end) new zone no.?

2. Enter 99 for permanent disabling.

Disabling for a few

Enter the desired disabling time in full

Siemens Fire Alarm Control Panel (FC330A) — Viewing disabled zones diagram (page 28)
Fig. 14 · Viewing disabled zones

hours zone ### DISABLED for ## hours (hm = end) new zone no.?

hours (e. g. 2). Display shows

3. Press St to finish the zone disabling procedure.

Display shows The yellow LED isolation is on.

Viewing disabled zones

Siemens Fire Alarm Control Panel (FC330A) — Viewing disabled zones diagram (page 28)
Fig. 15 · Viewing disabled zones
1. Press key F1 to open list.
display ISOLATIONStotal:### (key: ↓ = forward / ↑ = backward)
2. Press key to view details.
display ISOLATIONStotal:### zone ### − ### permanent DISABLED

After last zone has been displayed, sy-

stem turns back to overview. Display shows

parts of system DISABLED total:###

WED 21.7.00 15:00

Zone reactivation procedure

ENable zone(range ### to ###) > zone no.? (555 = all)

Display shows The yellow LED isolation is off.

02.2004

Disable all zones · or · Several zones disabled

Page 29 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Viewing disabled zones
Page 29 · click to enlarge
Page 29
1. Enter the number of a zone to be enabled (e. g. 2).

MONITORING zone ###, wait. (F1 /hm = enabling) next zone?

Display shows With a running timeout after which the

zone is automatically enabled.

2. Enter another zone number to enable or press F1 to enable the zone before the timeout has expired.
ENable zones> all zones ENABLED

Display shows for a few seconds or

timeout /hmmenu Stop: end operating
3. Press hm to go back to the submenu.

ENabling: 1. detector ’zone’ (1.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’

Enable a range of zones

1. Enter the first number of a zone range to be enabled (e. g. 2).
Siemens Fire Alarm Control Panel (FC330A) — Viewing disabled zones diagram (page 29)
Fig. 16 · Viewing disabled zones

ENable zone range ### to ### > confirm LAST zone no.?

2. Enter the last number of the zone range (e. g. 5).

MONITORING zones ###−###, wait (F1 /hm = enabling) > LAST zone

Display shows With a running timeout after which the

zone range is automatically enabled.

3. Press F1 to enable all zones before the timeout has expired.
ENable zones> all zones ENABLED

Display shows for a few seconds or

timeout /hmmenu Stop: end operating
4. Press hm to go back to the submenu.

DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’

Enable all disabled zones

1. Enter 555 to enable all disabled zones, no matter if all zones, a range of zones or single zones were disabled.

MONITORING zone ###, wait (F1 /hm = enabling) > LAST zone

Display shows With a running timeout after which all

zones are automatically enabled.

2. Press F1 to enable all zones before the timeout has expired.
ENable zones> all zones ENABLED

Display shows for a few seconds or

timeout /hmmenu Stop: end operating
3. Press hm to go back to the submenu.

DISabling: 1. detector ’zone’ (2.1) 2. detector ’element’ 3. ConTrol ’zone’ 4. All Fire Ctrl ’zones’

02.2004

Enable single zones

Page 30 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Single detector isolation procedure
Page 30 · click to enlarge
Page 30

Temporary isolation of a single detector

When has a single detector to be isolated?

Exceptional situations may occur, where it is preferable to isolate only single detector devices instead of the whole detector zone. Such situations may be for example:

Construction work with smoke or heat development at a particular location within a large

zone with a lot of detectors

Malfunction of a detector in a zone with several detector devices

If a single detector should be isolated the detector has to be identified clearly! If the detector cannot be identified clearly, the whole detector zone should be isolated. A wrong isolation of a detector can cause an unwelcome call of the fire brigade!

Single detector isolation procedure

DISABLE element> zone no.? (range ### − ###)
3. Enter the desired zone number.

zone ### SELECTED > element no.? (range ## − ##)

4. Enter the desired element number.

zone ### element ## SELECTED > hours disabled? (99=permanent)

5. Enter the desired disabling time in full hours or 99 for permanent disabling.

zone ### elem. ## permanent DISABLED > new element no.? (range ## − ##)

Display shows The yellow LED isolation is on.

6. Press hm to finish the element disabling procedure or enter a new zone number to disable another single element.

02.2004

Page 31 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Detector reactivation procedure
Page 31 · click to enlarge
Page 31

Detector reactivation procedure

ENABLE element: (zone range ### − ###) > zone no.?

3. Enter the desired zone number.

ENABLE single element in zone ###: > element no.? (range ## − ##)

timeout /hmmenu Stop: end operating
4. Enter the desired element number.

MONIT. zone ### elem. ##, WAIT (F1 /hm = enabling) next elem.?

5. Enter another element number to enable or
6. Press F1 to enable the element before the timeout has expired. or
7. Press hm to go back to the submenu.

02.2004

Page 32 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Enabling the remote alarm transmission facility
Page 32 · click to enlarge
Page 32

Remote Transmission

Remote transmission provided: No Yes Alarm to: Fault transmission provided: No Yes Alarm to:

What is “remote transmission”?

The remote transmission facility establishes a transmission path to the fire department in the event of a fire alarm issued by the fire detection system. Depending on the alarm concept, the alarm is transmitted immediately to the fire department, or after a certain delay, giving time for investigation by operating personnel. In single cases a separate transmission path for fault messages is established.

When has the remote transmission to be disabled?

Under normal conditions the remote alarm transmission facility is enabled to ensure minimal alarming times. The remote transmission facility is disabled only in special cases to prevent un- necessary turn out of the fire brigade. The transmission facility should be disabled for:

Test of the fire detection system

Maintenance and conversion works on the fire detection system

Disabling the remote alarm transmission facility

DISABLE RT−alarm> hours DISABLED? (99=permanent)
3. Enter the desired disabling time or 99 for permanent disabling.

Display shows for a few seconds

timeout /hmmenu Stop: end operating

The remote fire alarm transmission is disabled. The yellow LEDs of the display fields Isolation and Remote alarm/fault off are on. The text display indicates that no alarm message is pending.

Enabling the remote alarm transmission facility

Display shows for a few seconds

timeout /hmmenu Stop: end operating

The remote fire alarm transmission is enabled. The yellow LEDs of the display fields Isolation and Remote alarm/fault off are off, if no other

parts of the system are isolated.

02.2004

RT−alarm permanent DISABLED · RT−alarm ENABLED

Page 33 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Enabling the remote fault transmission facility
Page 33 · click to enlarge
Page 33

Disabling the remote fault transmission facility

Display shows for a few seconds

timeout /hmmenu Stop: end operating

The remote fault transmission is disabled. The yellow LED of the display field Isolation is on. The text display indicates that no alarm message is pending.

Enabling the remote fault transmission facility

Display shows for a few seconds

timeout /hmmenu Stop: end operating

The remote fault transmission is enabled. The yellow LED of the display filed Isolation is off, if no other parts of the system are isola-

ted.

02.2004

RT−fault DISABLED · RT−alarm ENABLED

Page 34 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Enabling alarm devices
Page 34 · click to enlarge
Page 34

Alarm devices

When have alarm devices to be disabled?

Under normal conditions the alarm devices (e. g. horns or sirens) operate in active stand−by. They are only disabled for:

Test of the fire detection system.

Maintenance and conversion works on the fire detection system.

Normally all acoustic devices are disabled together. Single devices or lines are only disa- bled in exceptional cases. For the alarm devices there are always 2 lines, in some cases 4 lines, but max. 6 lines possible.

Disabling the alarm devices

Siemens Fire Alarm Control Panel (FC330A) — Disabling the alarm devices diagram (page 34)
Fig. 17 · Disabling the alarm devices
3. Enter the desired horn number or 555 for disabling all horns.

Display shows for a few seconds

4. Enter the number of a further device to disable. or

Press St to finish the procedure. The desired alarm devices are disabled. The yellow LEDs of the display fields Isolation and Alarm horn fault/off are on. The text display indicates that no alarm message is pending.

Enabling alarm devices

Siemens Fire Alarm Control Panel (FC330A) — Enabling alarm devices diagram (page 34)
Fig. 18 · Enabling alarm devices
3. Enter the desired horn number or 555 to enable all horns.

Display shows for a few seconds

4. Enter the number of a further device to disable. or

Press St to finish the procedure. The desired alarm devices are enabled. The yellow LEDs of the display fields Isolation and Alarm horn fault/off are off, if no other

parts of the system are isolated.

02.2004

Page 35 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Faults
Page 35 · click to enlarge
Page 35

Faults

02.2004

Page 36 of the Siemens Fire Alarm Control Panel (FC330A) user manual — TUE 27.7.99 10:35
Page 36 · click to enlarge
Page 36

Faults

How do I respond to fault messages?

Fault messages are issued on the text display if a malfunction in the system, the cabling or the attached devices is detected. Additionally the LED in the fault display field is blinking.

1. Confirm the message by pressing the Acknowledge key.

The yellow LED in the fault display field changes from blinking to constant on.

2. Read the fault message on the display and decide, whether the fault can be remedied by the user (see next paragraph: What remedies are available to the user).
3. To cancel the fault message after the fault is remedied, press the Reset key.

What remedies are available to the user?

Only a few faults can be remedied by the user. These are listed below. For all other faults call the SIEMENS service organization.

Defective or missing detector

FAULT message(s)total:### zone ### elem. ##: dev. DEFECTIVE

TUE 27.7.99 10:35

FAULT message(s)total:### zone ### elem. ##: NO RESPONSE

TUE 27.7.99 10:35

Broken glass on manual call point

FAULT message(s)total:### zone ### elem ##: Broken glass

Display shows Manual call point with broken glass is

TUE 27.7.99 10:35

If a detector is missing, insert a detector of

the same type into the detector base.

If a detector is damaged, replace it with a detector of the same type and order a new reserve

detector from the SIEMENS service organization.

If a manual call point has been operated and the glass is broken, replace it, then press the key

Reset.

FAULT message(s)total:### EARTH FAULT to 24V

TUE 27.7.99 10:35

Emergency power supplyh

If the public power supply is down, no action is required. The emergency battery supplies the

system for several hours (according to local requirements at least 12 h, max. 72 h), depen- ding on the size of the emergency battery.

If the outage is not in the public power supply:

1. Check the power fuse at the main distribution panel of the building.
2. If the fuse is blown, replace the fuse.

Printer out of paper

Insert a new paper roll ( page 45, Printer: Paper replenishing).

02.2004

or · flashing · Mains POWER OFF

Page 37 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Maintenance
Page 37 · click to enlarge
Page 37

Maintenance

02.2004

Page 38 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Setting single detector zones into detector test mode
Page 38 · click to enlarge
Page 38

Detector test

Purpose and Principle

For function tests of the automatic fire detectors and the manual call points, zones of the fire detection system are set into the “detector test mode”. In the detector test mode a responding detector or manual call point triggers only a test alarm. This allows individual on−site function tests, where automatic fire detectors deliberately are trig- gered by means of special detector test equipement. Manual call points are triggered either with a special test key or by opening the cover and actua- ting the button.

Test alarm A test alarm generates no danger message on the control console. Acoustic alarm devices, the remote alarm transmission or any other control functions are not activated. A test alarm is indicated on the text display of the control console as test−ALARM ZONE #. It is recorded in the event memory and automatically logged, if a printer is connected.

Frequency Visual control of detectors and manual call points: Once a year. Testing of all detectors and manual call points: Once every two years.

i Differing national or local regulations always have priority!

Recommendations for function tests

Perform the function tests periodically. The frequency of function tests is determined by the

service engineer.

Switch only the fire detectors of a few zones at a time to detector test mode, never the entire

building.

For manual call points the function test needs to be performed only according to a sampling

plan, designed by the service engineer.

Test automatic fire detectors and manual call points separately. Never switch them to detec-

tor test mode simultaneously.

Setting single detector zones into detector test mode

No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)

3. Enter the desired zone numbers (e. g. 1 and 2; max. 4 zones). Use the ok key to separate the numbers and the del key to cancel keying errors.

02.2004

Page 39 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Terminating the detector test mode for a zone range
Page 39 · click to enlarge
Page 39
4. After entering the last number press ok twice.
Mode ’DET. TEST’ zones###,###,###,### Outputs NOT activated

Display shows for a few seconds

timeout /hmmenu Stop: end operating

The selected detector zones are set

into detector test mode. Display shows The yellow LED of the display field de-

Mode ’DET. TEST’ zones###,###,###,### Mode ’DET. TEST’ range: ### − ###

TUE 27.7.99 10:35

tector test mode are on.

Setting a zone range or all detectors into detector test mode

Siemens Fire Alarm Control Panel (FC330A) — Setting a zone range or all detectors into detector test mode diagram (page 39)
Fig. 19 · Setting a zone range or all detectors into detector…

No ’DET.TEST’ mode, set range ### − ###: > zone no.? (555=all, 0=end)

3. Enter the first number of the desired zone range (e. g. 2) or 555 for testing all zones.

zone range ### − ### in ’DET. TEST’ mode Outputs NOT activated

Display shows for a few seconds

4. Enter the last number of the desired zone range (e. g. 5).
Siemens Fire Alarm Control Panel (FC330A) — Setting a zone range or all detectors into detector test mode diagram (page 39)
Fig. 20 · Setting a zone range or all detectors into detector…

zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)

Display shows The selected zone range is set into de-

tector test mode. Display shows

Mode ’DET. TEST’ zones###,###,###,### Mode ’DET. TEST’ range: ### − ###

Terminating the detector test mode for single zones

No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)

3. Press del to delete all displayed zone numbers and enter “0” (zero) instead.
4. Press ok twice.

’DET. TEST’ mode TERMINATED

Display shows for a few seconds

timeout /hmmenu Stop: end operating

The detector test mode is terminated for

all detector zones.

Terminating the detector test mode for a zone range

Siemens Fire Alarm Control Panel (FC330A) — Terminating the detector test mode for a zone range diagram (page 39)
Fig. 21 · Terminating the detector test mode for a zone range

No ’DET.TEST’ mode, set range ### − ###: > zone no.? (555=all, 0=end)

3. Enter “0” (zero) and press ok .

Display shows for a few seconds

The detector test mode is terminated for

all detector zones.

02.2004

Page 40 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Functional testing of automatic AlgoRex-detectors
Page 40 · click to enlarge
Page 40

Functional testing of automatic AlgoRex-detectors

Required equipement There are basically two kinds of automatic fire detectors: heat detectors and smoke detectors. For heat detectors the detector tester RE6T is required, which simulates the temperatur rise with a hot air blower. Smoke detectors exist also as the variation multisensor smoke detector. Both are tested with the detector tester RE6, which also can be used as tool for the detector exchange. Smoke is detec- ted by its light scattering, which is optically simulated by the detector tester RE6.

Identification of detectors Smoke detectors, multisensor smoke detectors and heat detectors can be identified by their housing, see illustration.

If the tested detector did not respond, exchange the detector unit.

Siemens Fire Alarm Control Panel (FC330A) — Functional testing of automatic AlgoRex-detectors diagram (page 40)
Fig. 22 · Functional testing of automatic AlgoRex-detectors

Test procedure for detector tester RE6

1. Set the desired zone into detector test mode ( page 34).
2. Set the detector tester onto the detector and press for 1 second.
3. Wait until the response indicator (red LED) located in the detector housing flashes.
4. Possibly press again after 15 − 20 seconds for 1 second.
5. Remove the detector tester.

The functional testing is completed.

If the tested detector did not respond, check the gas can inside the detector tester RE6 or the

battery inside the tester DZ1193. If defective detectors are found call the SIEMENS service organization.

Detector tester RE6 (gas)

Test procedure for detector tester RE6T

Siemens Fire Alarm Control Panel (FC330A) — Functional testing of automatic AlgoRex-detectors diagram (page 40)
Fig. 23 · Functional testing of automatic AlgoRex-detectors
1. Set the desired zone into detector tes mode ( page 34).
2. Set the detector tester onto the detector.
3. Wait until the response indicator (red LED) located in the detector housing flashes.
4. Remove the detector tester.

The functional testing is completed.

If the tested detector did not respond, exchange the detector unit.

02.2004

Multisensor smoke detector · Heat detector · Detector tester RE6T

Page 41 of the Siemens Fire Alarm Control Panel (FC330A) user manual — WED 21.7.99 15:00
Page 41 · click to enlarge
Page 41

Functional test of manual call points

Test procedure for type KAC

1. Set the desired zone into detector test mode ( page 34).
2. Insert the test key into the opening at the lower left side of the housing.

A test alarm is simulated.

3. Observe, whether the response indicator near the upper right corner of the housing flashes.
4. Remove the test key.

The functional testing is completed.

If the tested manual call point did not respond, call the SIEMENS service organization.

Test procedure for type DIN (indirect activation)

1. Set the desired zone into detector test mode ( page 34).
2. Open the housing of the manual call point with the key.
3. Press down the button completely.

A test alarm is simulated.

4. Observe, whether the response indicator, a red LED to the right of the button, flashes.
5. Close the housing.

The functional testing is completed.

If the tested manual call point did not respond, call the SIEMENS service organization.

mode ’detector TEST’ ACTIVE > test−ALARM zone ###/##

WED 21.7.99 15:00

Each test alarm is indicated in the display for a few seconds and also registered in the event

memory.

02.2004

Show 8 more labels / short text on this page
Response · indicator · Test− · key · Response · indicator · Button · Control console
Page 42 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Lamp test procedure
Page 42 · click to enlarge
Page 42

Lamp test

Purpose of the lamp test

Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis- play fields, the text display and the alarm buzzer of the control console. To check the correct function of these parts the lamp test can be initiated: All visual and audible devices of the control console are activated for a few seconds.

Frequency The lamps have to be tested at least once a year.

Lamp test procedure

To initiate the lamp test. Display shows

TESTING lamps and display: > remaining time (→← ↓↑)

3. Check: − all LEDs on? − buzzer audible? − missing segments in text display?

If one or more devices are malfunctional, call the SIEMENS service organization.

i Lamp test on local indication and control panels page 5.

02.2004

Page 43 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Battery load test procedure
Page 43 · click to enlarge
Page 43

Battery load test

Purpose and principle

In case of mains interruption the power supply of the fire detection system relies on an internal battery pack. The capacity of the battery pack is sufficent to keep the system for a couple of hours operating ( page 32, Faults). As the lifetime of batteries is limited, a battery load test has to be performed periodically to ensure a good condition of the battery pack: For 10 seconds the battery is highly loaded and the battery voltage is monitored. If the voltage drop is beyond a cer- tain value, the battery pack has to be replaced.

Frequency The batterie test is automatically performed by the system every 24 hours. If the battery is dama- ged, or provides only an insufficent capacity, a fault messages is displayed. Once a year the battery test has to be performed manually.

Battery load test procedure

To initiate the battery load test. Display shows

TESTING battery> remaining time for load test
hmstop test Stop: end operating

If the battery test is completed, the sy-

RESULT battery test: > battery OK.

stem shows the result. Display shows for a few seconds

timeout /hmmenu Stop: end operating

If the battery load test yields insufficent battery capacity, call the SIEMENS service organization to replace the battery.

02.2004

Page 44 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Horn test procedure
Page 44 · click to enlarge
Page 44

Test of acoustic alarm devices

Purpose and principle

The fire detection system is equipped with acoustic alarm devices distributed throughout the building to alarm the fire brigade in case of fire. The function of the acoustic alarm devices has to be checked periodically. The “horn test” activates all acoustic alarm devices for 30 seconds.

Frequency The acoustic alarm devices have to be tested at least once a year.

Horn test procedure

To initiate the horn test. Display shows The horn test runs for 30 seconds. The remaining time is indicated. After the test has finished, the submenu is displayed again.

TESTING horn> remaining active time
hmstop test Stop: end operating

If an acoustic device did not respond in the test, call the SIEMENS service organization for repla- cement or repair.

The horn test can be stopped before expiration of the 30 seconds by pressing hm .

02.2004

Page 45 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Test procedure for remote fault transmission
Page 45 · click to enlarge
Page 45

Test of Remote Transmission (RT)

Purpose and principle

In test mode the function of the remote transmission can be tested without activating an alarm device or a manual call point. The function of the remote transmission facility has to be checked periodically. The remote alarm transmission and the remote fault transmission can be tested separately.

Frequency The acoustic alarm devices have to be tested at least once a year.

i Before the remote alarm transmission is tested, inform the fire brigade!

Test procedure for remote alarm transmission

1. Inform the fire brigade before a remote alarm transmission test will be performed.

To initiate the remote ALARM test. Display shows

4. If the fire brigade is informed, press ok .
TESTING remote transm. ALARM (RT−alarm)> remaining active time

Display shows The test runs for 30 sec. The remaining

time is indicated. After the test has finished, the submenu is displayed again.

hmstop test Stop: end operating

If the remote alarm did not arrive at the fire departement, call the SIEMENS service organization for repair.

The test can be stopped before expiration of the 30 seconds by pressing hm .

Test procedure for remote fault transmission

To initiate the remote FAULT test. Display shows

TESTING remote transm. FAULT (RT−fault)> remaining active time

The test runs for 30 sec. The remaining

hmstop test Stop: end operating

time is indicated. After the test has finished, the submenu is displayed again.

If the fault message did not arrive at the remote location, call the SIEMENS service organization for repair.

The test can be stopped before expiration of the 30 seconds by pressing hm .

02.2004

Page 46 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Lamp test
Page 46 · click to enlarge
Page 46

02.2004

Page 47 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Other Functions
Page 47 · click to enlarge
Page 47

Other Functions

02.2004

Page 48 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Enabling the printer
Page 48 · click to enlarge
Page 48

Printer disabling/enabling

i Printer connected: Yes No

When has the printer to be disabled?

Under normal conditions the printer operates in active stand-by. It is only disabled in special ca- ses e. g. for change of paper or repair.

Disabling the printer

2. Select option 2. 3. 3. (to disable the printing of all messages)

Display shows for a few seconds The printer is disabled. The yellow LED of the display field Isolation is on.

timeout /hmmenu Stop: end operating

Enabling the printer

printer ACTIVElog ALL messages

Display shows for a few seconds The printer is enabled. The yellow LED of the display field Isolation is off, if no other parts of the system are isola-

timeout /hmmenu Stop: end operating

ted.

02.2004

printer DISABLED

Page 49 of the Siemens Fire Alarm Control Panel (FC330A) user manual —  JUJU TP 50KS − A
Page 49 · click to enlarge
Page 49

Paper replacement with logging printer B2Q191

Switch off the printer

Before changing the printer paper disable the printer by the control panel menu ( page 44).

Siemens Fire Alarm Control Panel (FC330A) — Switch off the printer diagram (page 49)
Fig. 24 · Switch off the printer

G

B2Q101

H

Change of printer paper

1. Remove the screws on the right − hand side or open the hinged cover with the key.
2. Swing out the printer unit.
3. Undo the clamp H and remove the used paper roll (see picture IV).
4. Lift the paper flap A and attach the a new paper roll on the spindle B. Assure that the moving direction of the paper roll is clockwise (see picture I).
5. Press the leading edge of the paper tape lightly against the flap A and feed it through slot C into the printer (see picture II).
6. Press down the release lever D and shove the paper tape through the printer (see picture III).
7. Relinquish release lever D. The paper can now be transported by means of the knurled wheel E (see picture III).
8. Feed the paper tape through slot F.
9. Thread the leading edge of the paper around the take − up roller G and fix it with clamp H (see pictures IV and V).
10. Press the winding up key J (see picture III) to wind up the paper and to reset of the “End of paper” fault.

Enable the printer

After changing the printer paper, enable the printer by the control panel menu ( page 44).

Spare paper rolls

Following types of paper rolls are available for the printer:

part no. 279 977 (4 pieces)

JUJU TP 50KS − A

HOSHU PS 65 B1

MITSUBISHI F − 200 U7X

Print intensity

If the print intensity is too low, call the SIEMENS service organization.

02.2004

Page 50 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Polling the alarm counter
Page 50 · click to enlarge
Page 50

Poll alarm counter

Purpose of polling the alarm counter

The alarm counter allows to get information about the number of alarms and remote alarms in the past.

Polling the alarm counter

ALARM COUNTERalarms: ### remote alarms: ###

Display shows for a few seconds The submenu is displayed.

timeout /hmmenu Stop: end operating
3. Use St to terminate the alarm counter polling.

02.2004

Page 51 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Polling the event memory
Page 51 · click to enlarge
Page 51

Poll event memory

Purpose of polling the event memory

The event memory allows to get information about events registered by the fire detection system in the past. Always the last 200 events are registered by the system.

Polling the event memory

viewing EVENT MEMORYtotal events ### (key: ↓ = forward / ↑ = backward)
3. Use and to scroll through the events.

The first line tells the event number and

the date and time of its occurance, the second line reproduces the correspon- ding event message. Display shows

viewing EVENT no ##: ##.##.## ##:##:## event text

↓forward ↑ : backwards
4. Use hm to go back to the submenu or St to terminate the event memory polling.

02.2004

Page 52 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Polling user text of zones or elements
Page 52 · click to enlarge
Page 52

Poll user text of zones or elements

Purpose

The assignment of the zone numbers to the descriptive user text is stored in the memory of the fire detection system and can be displayed on the text display of the control console.

Polling user text of zones or elements

display of USER TEXT for ### ZONES/ELEM: (key: ↓ = forward / ↑ = backward)

3. Use and to scroll through the zones.

The first line tells the zone number, the

second and third line reproduces the corresponding user text. Display shows

display USER text of zone ###: zone ###/ −: ###### ground floor main entrance ↓: forward ↑: backwards

4. Use hm to go back to the submenu or St to terminate the user text polling.

02.2004

Page 53 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Polling the system status
Page 53 · click to enlarge
Page 53

Poll system status

Purpose

After acknowledging messages from various system states differing from “normal operation” as “isolation” or “fault”, detailed information may be no longer visible on the text display. Only the LEDs of the display fields and a more general message like “parts of the system isolated” on the text display indicate a special system state. More detailed informations e. g. which zones are isolated, or which elements are faulty can be retrieved by polling the system status at any time.

Polling the system status

STATUS1. fault (3.1) 2. isolation 3. pre−alarm 4. techn.alarm /element status

A scroll page for the selected item is dis-

played, here for example for “fault“. Display shows

display FAULT messagestotal:## (key: ↓ = forward / ↑ = backward)
4. Use and to scroll through the messages.

display FAULT messages: total:## fault messages

↓forward ↑ : backwards
5. Use hm to go back to the submenu or St to terminate the system status polling.

02.2004

Page 54 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Polling configuration data of address lines
Page 54 · click to enlarge
Page 54

Poll configuration data

Purpose

The polling of configuration data is only relevant for the service engineer, for controlling user functions without the configuration tool.

Polling configuration data of detector zones

Siemens Fire Alarm Control Panel (FC330A) — Polling configuration data of detector zones diagram (page 54)
Fig. 25 · Polling configuration data of detector zones
Select ZONES(range ### to ###) Enter ZONE no.? (555 = all)
3. Enter the desired zone number or 555 to select all zones and press ok .
ZONE information for ### ZONES/ELEM↓ : forward ↑ : backwards
4. Press ok to select only a single zone or enter the number of the last zone of the desired range and press ok .

ZONE ### selected. ok = single ZONE Second ZONE No.? (range ### − ###)

5. Use and to scroll through the configuration data of each selected zone.

Zn ###:###### tst:######dis:######## el ele ## name=###### type=###### al=###### incr=###### dr=###### trouble=###### ln ## dev ##

6. Use hm to go back to the submenu or St to terminate the configuration data polling.

Polling configuration data of address lines

Siemens Fire Alarm Control Panel (FC330A) — Polling configuration data of address lines diagram (page 54)
Fig. 26 · Polling configuration data of address lines
Select LINES(range ## to ##) Enter line no.? (555 = all)
3. Enter the desired line number or 555 to select all lines and press ok .
LINE information for ## LINES↓ : forward ↑ : backwards
4. Press ok to select only a single line or enter the number of the last line of the desired range and press ok .
Siemens Fire Alarm Control Panel (FC330A) — Polling configuration data of address lines diagram (page 54)
Fig. 27 · Polling configuration data of address lines

LINE ## selected. ok = single line Second line no.? (range ## − ##)

5. Use and to scroll through the configuration data of each device of the selected line.

line ###: ######, ### devices device ### name=###### type=###### al=###### incr=###### dr=###### trouble=###### zn ### el ##

6. Use hm to go back to the submenu or St to terminate the configuration data polling.

02.2004

Page 55 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Print configuration zone/line/LON
Page 55 · click to enlarge
Page 55

Printout

All informations that can be polled also can be printed, if a printer is connected.

Print system status

PRINT1. fault (4.3.1) 2. isolation 3. pre−alarm 4. techn.alarm /element status
3. Select the information to be printed.

PRINTOUT in process:

hmstop print Stop: end operating

Print event memory/alarm counter

PRINT1. event memory (4.3.2) 2. alarm counter
3. Select the information to be printed.

PRINTOUT in process:

hmstop print Stop: end operating

Print configuration/user text

PRINT: 1. configuration system (4.3.3) 2. configuration coll. line 3. user text detector zn/elem 4. user text ConTrol zone

3. Select the information to be printed.

PRINTOUT in process:

hmstop print Stop: end operating

Print configuration zone/line/LON

PRINT1. configuration det. zones (4.3.4) 2. configuration addr. lines 3. configuration LON devices
3. Select the information to be printed.

PRINTOUT in process:

hmstop print Stop: end operating

02.2004

Page 56 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Set time and date
Page 56 · click to enlarge
Page 56

Set time and date

i Changeover summertime to wintertime: manually automatically

Purpuse and Principle

Time and date are set by the service engineer when the system is put into service. Under normal conditions there is no need to correct time and date. The changeover from summertime to wintertime and vice versa is performed automatically for Central European Time. Central European Time is valid for Western Europe, most of Eastern Europe an parts of Russia. The switchover from summertime to wintertime is performed at the last sunday in March, vise versa at the last sunday in October. Differing automatic switching ti- mes are not possible. Only due to an electronical distortion or a complete power failure (mains and battery interrupted) the system sets time and date to “default”.

Set time and date

Log in with at least ”access level 2”.

START system operating > enter password?

hm /Stopend operating
2. Enter the password and press ok .

set TIME: ##:##:## > new time: hour.min.sec.?

4. Enter the current time and press ok .

set DATE: ##.##.## > new date: day.mon.year?

5. Enter the current date and press ok .

Time and date are set to the current va-

lues. Display shows

FUNCTIONS1. switching alarm org. (4.1) 2. set time / date
6. Use St to terminate the time and date setting.

02.2004

Page 57 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Lamp test
Page 57 · click to enlarge
Page 57

Back 02.2004

Page 58 of the Siemens Fire Alarm Control Panel (FC330A) user manual — Lamp test
Page 58 · click to enlarge
Page 58

Siemens Building Technologies AG

CH-8708 Männedorf Alte Landstrasse 411

Tel. Fax www.cerberus.ch

+41 1 − 922 61 11 +41 1 − 922 64 50

Fire & Security Products Siemens Building Technologies Group Document no.

Back 02.2004

02.2004

Manual FD-M · Edition · Section 8

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Siemens Fire Alarm Control Panel (FC330A)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Siemens Fire Alarm Control Panel (FC330A)

Be the first to ask — other owners or our team will answer.

Original document

Siemens Fire Alarm Control Panel (FC330A) manual PDF

58 pages·543 KB·Smoke Alarm·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…