The Thermal ROR Detector GD-55000-127 reacts to temperature changes within defi ned periods of time, up to a maximum temperature of 78°C. The intelligent evaluation of these data allows the early detection of spreading fi res. The detector complies with Class BR and can be used up to a room height of 6m.
means of the optional Address Module NG60-1, each detector can be addressed individually. With that, the activated detector can also be safely identifi ed directly on the control panel.
The detector can be attached to various bases and it can be protected against theft.
Addressable conventional technology is used for alarm transmission to the fi re detection control panel. By

Operating voltage Supply through the detector line voltage
Current consumption typ. 45µA (quiescent)
Alarm temperature 78°C (maximum-heat component)
Operating temperature max. +65°C
Ambient temperature -20°C to +90°C (no condensation or icing)
Relative humidity 0 – 95% (no condensation)
Dimensions ø × H 100 × 42 (mm)
Order name Thermal ROR Detector/Conv./65/Apo GD-55000-127
GD-55000-127_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.