The Fire Brigade Interface FWI2-1 by means of dry contacts allows for the connection of two independent transmitting devices for the direct interconnection with a designated alarm respondent (e.g., the fi re brigade) as well as the connection of a country-specifi c fi re bri- gade control unit to fi re detection control panels Series BC216.
The parameters of the nine inputs and eight outputs can also be freely set and thus are available for general con- trol tasks. Optionally, the Fire Brigade Interface Additio- nal Board (FWZ2-1) can be attached to the Fire Brigade Interface. This unit allows for the connection of two independent, line-monitored transmitting devices. The surveillance current can be adjusted in three levels.

FWI2-1_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.


Current consumption at 24V typ. 4mA
Switching power per contact 60V/1A/30W
Contact life 3 × 105
Ambient temperature -5°C to +50°C
Dimensions L × W × H 132 × 74 × 10 (mm)
Part No. 214022
Order name Fire Brigade Interface FWI2-1
Current consumption at 24V typ. 4mA (both outputs not connected) max. 28mA (both outputs connected)
Ambient temperature -5°C to +50°C
Dimensions L × W × H 117 × 74 × 10 (mm)
Part No. 214023
Order name Fire Brigade Interface Additional Board FWZ2-1
FWI2-1_DBL_LST_EN_0804.PDF • PAGE 2 A Building Safety. Building Security.
Weight 70g · Weight 70g