The Optical-Thermal Detector ECO1002 uses both the scattered light principle as well as a separate thermal detection unit. It was developed to detect the charac- teristics of fi re in a wide range of applications, and to avoid deceptive alarms. The modern design of both measurement systems and the analysis of the parame- ters by means of a special algorithm allow to reliably evaluate the characteristics of fi re. This makes it an all-rounder that is used in virtually all fi elds of fi re de- tection. An internal drift compensation adjusts the alarm thres- hold by continually evaluating the contamination of the
detector. With that, the sensitivity of the detector is kept constant for a long time.
Addressable conventional technology is used for alarm transmission to the fi re detection control panel. By means of the Address Module NG58-1, each detector can be addressed individually.
A test activation of the detector can be carried out using the Remote Test Unit ECO1000RTU. The detec- tor can be attached to various detector bases and it can be protected against theft.

Operating voltage Supply through the detector line voltage
Current consumption typ. 80µA (quiescent)
Alarm temperature 58°C (maximum-heat component)
Operating temperature max. +45°C
Ambient temperature -30°C to +70°C
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 102 × 40.5 (mm)
Order name Optical-Thermal Detector/Conv./1000/SS ECO1002