EN
Official user manual

LST 5451EIS

1 pages·100 KB·Smoke Alarm·PDF·ENDEFRITNLJA
LST 5451EIS
Table of Contents 4 sections IS Thermal ROR Detector · 5451EIS for Hazardous Areas · Description · Specifi cations ShowHide
Page 1 of the LST 5451EIS user manual — Specifi cations
Page 1 · click to enlarge
Page 1
LST 5451EIS — IS Thermal ROR Detector diagram (page 1)
Fig. 1 · IS Thermal ROR Detector

IS Thermal ROR Detector

LST 5451EIS — IS Thermal ROR Detector diagram (page 1)
Fig. 2 · IS Thermal ROR Detector
LST 5451EIS — IS Thermal ROR Detector diagram (page 1)
Fig. 3 · IS Thermal ROR Detector
LST 5451EIS — IS Thermal ROR Detector diagram (page 1)
Fig. 4 · IS Thermal ROR Detector

5451EIS for Hazardous Areas

LST 5451EIS — 5451EIS for Hazardous Areas diagram (page 1)
Fig. 5 · 5451EIS for Hazardous Areas
  • Conventional technology
  • Maximum temperature 60°C
  • Up to 20 detectors can be connected to one safety barrier
  • Function testable with magnet
  • ATEX certifi ed
LST 5451EIS — 5451EIS for Hazardous Areas diagram (page 1)
Fig. 6 · 5451EIS for Hazardous Areas

Description

The Intrinsically Safe Thermal ROR Detector 5451EIS uses the rate-of-rise heat detection principle and was developed for the fi re detection in hazardous areas. The detector, which is a combined maximum/rate-of- rise heat detector, is assigned to class A1R and can be used up to a maximum room height of 7.5m.

the Safety Barrier ES58-2, the detector reaches the given Ex classifi cation. The two LEDs with 360° visibility indicate the activated condition of the detector.

A detector function test can be conveniently conducted using a magnet or a detector test device. The detector can be attached to various bases and it can be protec- ted against theft.

Conventional technology is used for alarm transmission to the fi re detection control panel. In conjunction with

LST 5451EIS — Description diagram (page 1)
Fig. 7 · Description

Specifi cations

Ignition protection intrinsically safe

Ex classifi cation EEx ia IIB T5

Current consumption typ. 100µA (quiescent)

Alarm temperature 60°C (maximum-heat component)

Ambient temperature -10°C to +43°C (continuous operation)

Relative humidity 10 – 93% (no condensation)

Dimensions ø × H 104 × 54 (mm)

Approval BASEEFA03ATEX0155X VdS G296050

Order name IS Thermal ROR Detector/Conv./400/SS 5451EIS

5451EIS_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED

Colour cream · Weight 80g · Order number 242015

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the LST 5451EIS

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the LST 5451EIS

Be the first to ask — other owners or our team will answer.

Original document

LST 5451EIS manual PDF

1 pages·100 KB·Smoke Alarm·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…