The Thermal Max Detector 4351E recognises a maxi- mum temperature of 78°C as sign of fi re. It complies with Class BS and can be used up to a room height of 6m.
is displayed on the Zonal Display Unit S300ZDU.
The detector can be attached to various detector ba- ses and it can be protected against theft.

Operating voltage Supply through the detector line voltage
Current consumption typ. 85µA (quiescent)
Ambient temperature -30°C to +70°C (continuous operation)
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 102 × 43 (mm)
Order name Thermal Max Detector/Conv./300/SS 4351E
4351E_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.