EN
Official user manual

LST 2251EIS

2 pages·133 KB·Smoke Alarm·PDF·ENDEFRITNLJA
LST 2251EIS
Table of Contents 9 sections Devices for Hazardous Areas · for the System Sensor/200 Loop · fi g. A · fi g. B · … ShowHide
Page 1 of the LST 2251EIS user manual — Specifi cations
Page 1 · click to enlarge
Page 1
LST 2251EIS — Devices for Hazardous Areas diagram (page 1)
Fig. 1 · Devices for Hazardous Areas

Devices for Hazardous Areas

LST 2251EIS — Devices for Hazardous Areas diagram (page 1)
Fig. 2 · Devices for Hazardous Areas
LST 2251EIS — Devices for Hazardous Areas diagram (page 1)
Fig. 3 · Devices for Hazardous Areas
LST 2251EIS — Devices for Hazardous Areas diagram (page 1)
Fig. 4 · Devices for Hazardous Areas

for the System Sensor/200 Loop

LST 2251EIS — for the System Sensor/200 Loop diagram (page 1)
Fig. 5 · for the System Sensor/200 Loop
LST 2251EIS — for the System Sensor/200 Loop diagram (page 1)
Fig. 6 · for the System Sensor/200 Loop
LST 2251EIS — for the System Sensor/200 Loop diagram (page 1)
Fig. 7 · for the System Sensor/200 Loop
  • Optical smoke detector
  • Safety barrier with galvanic isolation

fi g. A

  • Protocol interface for communication with the fi re detection control panel
  • ATEX certifi ed

fi g. B

fi g. C

LST 2251EIS — fi g. B diagram (page 1)
Fig. 8 · fi g. B

IS Optical Smoke Detector 2251EIS

The addressable Intrinsically Safe Optical Smoke Detec- tor 2251EIS (fi g. A) uses the scattered light principle and was developed for the detection of smoke particles in hazardous areas. The modern design of the sensing chamber allows to reliably evaluate the characteristics of fi re.

of the next maintenance. Thus the alarm threshold is automatically adjusted within the permissible range, de- pending on the contamination. With that, the constant response sensitivity of the detector is ensured for a long time.

The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is selec- ted with two decadic rotary switches, thus allowing to change the detector without additional tools.

The proven ADM loop technology with System Sen- sor/200 protocol establishes a permanent communica- tion between the fi re detection control panel and the detector. That ensures a periodical function testing of the detector. In the control panel all types of fi res are detected by continuously comparing fi re patterns. Intelligent evaluation algorithms use the current condi- tion of the sensing chamber to predict the likely time

A detector function test can be conveniently conducted using a magnet or test gas. The detector can be pro- tected against theft.

LST 2251EIS — IS Optical Smoke Detector 2251EIS diagram (page 1)
Fig. 9 · IS Optical Smoke Detector 2251EIS

Specifi cations

Ignition protection intrinsically safe

Ex classifi cation EEx ia IIB T5

Operating voltage Supply through loop voltage

Current consumption at 24V 330µA

Ambient temperature -25°C to +70°C

Relative humidity 5 – 95% (no condensation)

Dimensions ø × H 103 × 43 (mm)

Approval BASEEFA03ATEX0157X LPCB 199m

Ex-Sys200_DBL_LST_EN_0804.PDF • PAGE 1 A Building Safety. Building Security.

Order name IS Optical Smoke Detector/Anal./200/SS 2251EIS

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED

Colour cream · Weight 110g · Order number 241025

Page 2 of the LST 2251EIS user manual — Specifi cations
Page 2 · click to enlarge
Page 2
LST 2251EIS — Safety Barrier Y72221 diagram (page 2)
Fig. 10 · Safety Barrier Y72221

Safety Barrier Y72221

The Safety Barrier Y72221 (fi g. B) is used for intrinsi- cally safe electric circuits. The built-in zener barrier and the safe galvanic isolation allow the connecton of fi re

detectors in hazardous areas. Due to the galvanic isola- tion, the earth leakage monitoring can remain activated in the fi re detection control panel.

LST 2251EIS — Safety Barrier Y72221 diagram (page 2)
Fig. 11 · Safety Barrier Y72221

Specifi cations

Ignition protection intrinsically safe

Ex classifi cation EEx ia IIC T5

Operating voltage Supply through the detector line voltage

Ambient temperature -20°C to +60°C

Dimensions W × H × D 20 × 110 × 107.5 (mm)

Mounting TS35 DIN rail

Approval BASEEFA Nr.: BAS00ATEX7087

Order name Safety Barrier/Anal./200/SS Y72221

LST 2251EIS — Specifi cations diagram (page 2)
Fig. 12 · Specifi cations

Protocol Interface IST200

The Protocol Interface IST200 (fi g. C) serves for the design of an intrinsically safe electric circuit in ADM loop technology. It allows the bidirectional data traffi c between fi re detection control panel and fi re detectors in hazardous areas via an ADM loop with System Sen-

sor/200 protocol. The interface is always used toge- ther with the Safety Barrier Y72221. The Surface Moun- ting Box SMB500 is required for mounting the protocol interface.

LST 2251EIS — Protocol Interface IST200 diagram (page 2)
Fig. 13 · Protocol Interface IST200

Specifi cations

Ignition protection intrinsically safe

Operating voltage Supply through loop voltage

Current consumption at 24V 14mA

Ambient temperature 0°C to +60°C

Relative humidity 5 – 95% (no condensation)

Dimensions W × H × D (without attaching sheet) 70 × 70 × 32 (mm)

Order name Protocol Interface/Anal./200/SS IST200

Ex-Sys200_DBL_LST_EN_0804.PDF • PAGE 2 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED
Show 5 more labels / short text on this page
Colour green · Weight 100g · Order number 228006 · Weight 155g · Order number 228007
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the LST 2251EIS

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the LST 2251EIS

Be the first to ask — other owners or our team will answer.

Original document

LST 2251EIS manual PDF

2 pages·133 KB·Smoke Alarm·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…