ý Table 1 Power Wiring Terminals - Factory Supplied
Connection Type
UPS Module Rating
kVA AC Input AC Output Battery Neutral Ground
Bus bars for connecting hardware (1/2” on 1-3/4” centers) are provided. A field supplied lug is required.
Use 75ƒC copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this manual) and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacturer.
Nut and Bolt Combinations
Grade 2 Standard
Electrical Connections with Belleville Washers
Bolt Shaft Size
Lb-in N-m Lb-in N-m
1/4 53 6.0 46 5.2
5/16 107 12 60 6.8
3/8 192 22 95 11
1/2 428 48 256 29
Current Rating Lb-in N-m
AWG Wire Size or Range Lb-in N-m
#22 - #14 3.5 to 5.3 0.4 to 0.6
Use the values in this table unless the equipment is labeled with a different torque value.

Table 3 Table 310-16 Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)1
Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F)
Size Temperature Rating of Conductor. See Table 310-13. Size
75°C (167°F)
90°C (194°F)
60°C (140°F)
75°C (167°F)
90°C (194°F)
Types TBS, SA, SIS,FEP†, FEPB†,MI, RHH†, RHW-2 THHN†,THHW†, THW-2,THWN-2,
TW†
TBS, SA,SIS, THHN†, THHW†, THW-2, THWN-2,
UF†
UF†
THHW†,
THHW†,
THW†, THWN†, XHHW†,
THW†, THWN†, XHHW†, USE†, ZW†
USE†
RHH†, RHW-2,
USE-2, XHH,
USE-2, XHH, XHHW†, XHHW-2, ZW-2
XHHW† XHHW-2,ZW-2
Copper Aluminum or Copper-Clad Aluminum
18 16 14 12 10 8
14 18 25† 30† 40† 55
20† 25† 30 40
20† 25† 35† 50
6 4 3 2 1
55 70 85 95 110
65 85 100 115 130
75 95 110 130 150
40 55 65 75 85
50 65 75 90 100
60 75 85 100 115
6 4 3 2 1
1/0 2/0 3/0 4/0
125 145 165 195
150 175 200 230
170 195 225 260
100 115 130 150
120 135 155 180
135 150 175 205
1/0 2/0 3/0 4/0
250 300 350 400 500
215 240 260 280 320
255 285 310 335 380
290 320 350 380 430
170 190 210 225 260
205 230 250 270 310
230 255 280 305 350
250 300 350 400 500
600 700 750 800 900
355 385 400 410 435
420 460 475 490 520
475 520 535 555 585
285 310 320 330 355
340 375 385 395 425
385 420 435 450 480
600 700 750 800 900
1000 1250 1500 1750 2000
455 495 520 545 560
545 590 625 650 665
615 665 705 735 750
375 405 435 455 470
445 485 520 545 560
500 545 585 615 630
1000 1250 1500 1750 2000
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown
above by the appropriate factor shown below.
21-25 26-30 31-35 36-40 41-45 46-50 51-55 56-60 61-70 71-80
1.08 1.00 .91 .82 .71 .58 .41
1.05 1.00 .94 .88 .82 .75 .67 .58 .33
1.04 1.00 .96 .91 .87 .82 .76 .71 .58 .41
1.08 1.00 .91 .82 .71 .58 .41
1.05 1.00 .94 .88 .82 .75 .67 .58 .33
1.04 1.00 .96 .91 .87 .82 .76 .71 .58 .41
70-77 78-86 87-95 96-104 105-113 114-122 123-131 132-140 141-158 159-176
† Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (†) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. 1 Reprinted with permission from NFPA 70-1993, the National Electrical Code®, Copyright 1996, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.





































Figure 23 Base Mounting Details, 400 and 500 kVA, 208 VAC, Rectifier and Inverter Sections


Figure 24 Base Mounting Details, 400 and 500 kVA, 208 VAC, Control and Output Sections


Figure 25 Base Mounting Details, 625 kVA and 750 kVA (High Link - 240 Cells)


Figure 26 Base Mounting Details, 750 kVA (Low Link - 180 Cells) and 1000 kVA, Rectifier and Inverter


Figure 27 Base Mounting Details, 750 kVA (Low Link - 180 Cells) and 1000 kVA, Control Section


Figure 28 Base Mounting Patterns, System Control Cabinets (SCCB) 640 to 3000 Amps




Figure 30 Base Mounting Patterns, System Control Cabinets (SCCP) 200 to 480 Amps


Figure 31 Base Mounting Patterns, System Control Cabinets (SCCP) 560 to 2000 Amps


Figure 32 Base Mounting Patterns, System Control Cabinets (SCCA) 1600 to 4000 Amps












Figure 38 Shipping Split Detail, 750 kVA (Low Link - 180 Cells) and 1000 kVA






























































* Rectifier AC Input Current
Battery Current at End of Discharge
Approx.
Lbs./ Sq.Ft.
BTU/hr.
Lb.
kVA kW Nom Max Nom Max Amperes Amperes
338 270 420 525 406 507 1000 993 92 80131 128x38x78 8300 246
400 320 504 630 481 601 1200 1170 92 94970 164x38x78 9900 229
400 360 560 700 481 601 1200 1316 92 106842 164x38x78 9900 229
500 400 630 788 601 752 1600 1463 92 118713 164x38x78 10600 245
500 450 700 875 601 752 1600 1646 92 133552 164x38x78 10600 245
625 500 778 973 752 940 2000 1828 92 148391 164x41x78 12300 263
750HL 600 934 1167 902 1128 1600 1644 92 178070 164x41x78 13925 298
750LL 600 934 1167 902 1128 2000 2194 92 178070 177x44x82 14600 270
1000 800 1217 1522 1203 1504 2500 2169 93 205514 177x44x82 16555 306
1000 900 1369 1712 1203 1504 2500 2440 93 231203 177x44x82 16555 306
Applicable Notes:
1,4,5,7,8, 9,11,12 2,5,7,8, 9,11,12 6 6,8,9, 11,12 — — 13 13 —
For explanation of notes, see referenced numbers in 10.1 - Notes
* Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load.
HL - 750 kVA module with 240 battery cells
LL - 750 kVA module with 180 battery cells
Table 5 338-1000 kVA Multi-Module Unit, 480 Volt - Standard Module With Optional Low Distortion Input Filter
* Rectifier AC Input Current
Battery Current at End of Discharge
Approx.
Lb./ Sq.Ft.
BTU/hr.
Lb.
kVA kW Nom Max Nom Max Amperes Amperes
338 270 380 474 406 507 1000 993 92 80131 128x38x78 8700 258
400 320 455 568 481 601 1200 1170 92 94970 164x38x78 10300 238
400 360 512 639 481 601 1200 1316 92 106842 164x38x78 10300 238
500 400 562 703 601 752 1600 1463 92 118713 164x38x78 11150 258
500 450 633 791 601 752 1600 1646 92 133552 164x38x78 11150 258
625 500 711 888 752 940 2000 1828 92 148391 164x41x78 12950 277
750HL 600 853 1066 902 1128 1600 1644 92 178070 164x41x78 14200 304
750LL 600 853 1066 902 1128 2000 2194 92 178070 177x44x82 15450 286
1000 800 1125 1406 1203 1504 2500 2169 93 205514 177x44x82 17400 322
1000 900 1265 1582 1203 1504 2500 2440 93 231203 177x44x82 17400 322
Applicable Notes:
1,4,5,7,8, 9,11,12 2,5,7,8, 9,11,12 6 6,8,9, 11,12 — — 13 13 —
For explanation of notes, see referenced numbers in 10.1 - Notes
* Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load.
HL - 750 kVA module with 240 battery cells
LL - 750 kVA module with 180 battery cells
86 Appendix A - Series 600 UPS Site Planning Data

* Rectifier AC Input Current
Battery Current at End of Discharge
Approx.
Lb./ Sq.Ft.
BTU/hr.
Lb.
kVA kW Nom Max Nom Max Amperes Amperes
338 270 980 1226 937 1171 1000 998 92 91138 128x38x78 8600 255
400 320 1170 1462 1110 1388 1200 1176 92 101457 218x38x78 10250 214
400 360 1300 1625 1110 1388 1200 1323 92 114140 218x38x78 10250 214
500 400 1462 1827 1388 1735 1600 1470 92 126822 218x38x78 10950 228
500 450 1625 2031 1388 1735 1600 1654 92 142675 218x38x78 10950 228
Applicable Notes:
1,4,5,7,8, 9,11,12 2,5,7,8, 9,11,12 6 6,8,9, 11,12 — — 13 13 —
For explanation of notes, see referenced numbers in 10.1 - Notes
* Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load.
Table 7 338-500 kVA Multi-Module Unit, 208 Volt - Standard Module With Optional Low Distortion Input Filter
* Rectifier AC Input Current
Battery Current at End of Discharge
Approx.
Lb./ Sq.Ft.
BTU/hr.
Lb.
kVA kW Nom Max Nom Max Amperes Amperes
338 270 895 1119 937 1171 1000 998 92 91138 128x38x78 9100 270
400 320 1055 1319 1110 1388 1200 1176 92 101457 218x38x78 10750 224
400 360 1187 1484 1110 1388 1200 1323 92 114140 218x38x78 10750 224
500 400 1333 1667 1388 1735 1600 1470 92 126822 218x38x78 11650 243
500 450 1500 1875 1388 1735 1600 1654 92 142675 218x38x78 11650 243
Applicable Notes:
1,4,5,7,8, 9,11,12 2,5,7,8, 9,11,12 6 6,8,9, 11,12 — — 13 13 —
For explanation of notes, see referenced numbers in 10.1 - Notes
* Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load.
Appendix A - Series 600 UPS Site Planning Data 87

* Rectifier AC Input Current
Battery Current at End of Discharge
Approx.
Lb./ Sq.Ft.
BTU/hr.
Lb.
kVA kW Nom Max Nom Max Amperes Amperes
338 270 336 420 325 406 1000 993 92 80131 128x38x78 8300 246
400 320 403 504 385 481 1200 1170 92 94970 164x38x78 9900 229
400 360 448 560 385 481 1200 1316 92 106842 164x38x78 9900 229
500 400 504 630 481 601 1600 1463 92 118713 164x38x78 10600 245
500 450 567 709 481 601 1600 1646 92 133552 164x38x78 10600 245
625 500 630 788 601 752 2000 1828 92 148391 164x41x78 12300 263
750HL 600 747 934 722 902 1600 1644 92 178070 164x41x78 13925 298
750LL 600 747 934 722 902 2000 2194 92 178070 177x44x82 14600 270
1000 800 974 1217 962 1203 2500 2169 93 205514 177x44x82 16555 306
1000 900 1096 1369 962 1203 2500 2440 93 231203 177x44x82 16555 306
Applicable Notes:
1,4,5,7,8, 9,11,12 2,5,7,8, 9,11,12 6 6,8,9, 11,12 — — 13 13 —
For explanation of notes, see referenced numbers in 10.1 - Notes
* Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load.
HL - 750 kVA module with 240 battery cells
LL - 750 kVA module with 180 battery cells
Table 9 338-1000 kVA Multi-Module Unit, 600 Volt - Standard Module With Optional Low Distortion Input Filter
* Rectifier AC Input Current
Battery Current at End of Discharge
Approx.
Lb./ Sq.Ft.
BTU/hr.
Lb.
kVA kW Nom Max Nom Max Amperes Amperes
338 270 307 384 325 406 1000 993 92 80131 128x38x78 8700 258
400 320 360 450 385 481 1200 1170 92 94970 164x38x78 10300 238
400 360 405 506 385 481 1200 1316 92 106842 164x38x78 10300 238
500 400 460 575 481 601 1600 1463 92 118713 164x38x78 11150 258
500 450 517 647 481 601 1600 1646 92 133552 164x38x78 11150 258
625 500 575 718 601 752 2000 1828 92 148391 164x41x78 12950 277
750HL 600 682 853 722 902 1600 1644 92 178070 164x41x78 14200 304
750LL 600 682 853 722 902 2000 2194 92 178070 177x44x82 15450 286
1000 800 890 1113 962 1203 2500 2169 93 205514 177x44x82 17400 322
1000 900 1012 1265 962 1203 2500 2440 93 231203 177x44x82 17400 322
Applicable Notes:
1,4,5,7,8, 9,11,12 2,5,7,8, 9,11,12 6 6,8,9, 11,12 — — 13 13 —
For explanation of notes, see referenced numbers in 10.1 - Notes
* Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load.
HL - 750 kVA module with 240 battery cells
LL - 750 kVA module with 180 battery cells
88 Appendix A - Series 600 UPS Site Planning Data


338 kVA to 1000 kVA; 60 Hz
Technical Support
U.S.A. 1-800-222-5877
Outside the U.S.A. 614-841-6755
France +33 1 4 87 51 52
Germany +49 89 99 19 220
Italy +39 2 98250 1
Netherlands +00 31 475 503333
E-mail upstech@liebert.com
Web site http://www.liebert.com
‡ (QYLURQPHQWDOýV\VWHPVãýFORVHðFRQWUROýDLUýFRQGLWLRQLQJýIURPýìïèýWRýçíýWRQVï ‡ 3RZHUýFRQGLWLRQLQJýDQGý836ýZLWKýSRZHUýUDQJHVýIURPýëèíý9$ýWRýPRUHýWKDQýìíííýN9$ï ‡ ,QWHJUDWHGýV\VWHPVýWKDWýSURYLGHýERWKýHQYLURQPHQWDOýDQGýSRZHUýSURWHFWLRQýLQýDýVLQJOHñýIOH[LEOHý
SDFNDJHï ‡ 0RQLWRULQJýDQGýFRQWUROý¦ýRQðVLWHýRUýUHPRWHý¦ýIURPýV\VWHPVýRIýDQ\ýVL]HýRUýORFDWLRQ
6HUYLFHýDQGýVXSSRUWñýWKURXJKýPRUHýWKDQýìííýVHUYLFHýFHQWHUVýDURXQGýWKHýZRUOGñýDQGýDýëéðKRXU &XVWRPHUý5HVSRQVHý&HQWHUï
:KLOHýHYHU\ýSUHFDXWLRQýKDVýEHHQýWDNHQýWRýHQVXUHýDFFXUDF\ýDQGýFRPSOHWHQHVVýRIýWKLVýOLWHUDWXUHñý /LHEHUWý&RUSRUDWLRQýDVVXPHVýQRýUHVSRQVLELOLW\ñýDQGýGLVFODLPVýDOOýOLDELOLW\ýIRUýGDPDJHVýUHVXOWLQJý IURPýXVHýRIýWKLVýLQIRUPDWLRQýRUýIRUýDQ\ýHUURUVýRUýRPLVVLRQVïý
‹ýìääåý/LHEHUWý&RUSRUDWLRQïý$OOýULJKWVýUHVHUYHGýWKURXJKRXWýWKHýZRUOGïýý6SHFLILFDWLRQVýVXEMHFWýWRý FKDQJHýZLWKRXWýQRWLFHïý
Šý/LHEHUWýDQGýWKHý/LHEHUWýORJRýDUHýUHJLVWHUHGýWUDGHPDUNVýRIý/LHEHUWý&RUSRUDWLRQïýý$OOýQDPHVý UHIHUUHGýWRýDUHýWUDGHPDUNVýRUýUHJLVWHUHGýWUDGHPDUNVýRIýWKHLUýUHVSHFWLYHýRZQHUVïý
3ULQWHGýLQý8ï6ï$ïý
6/ðëééäè
5HYLVHGãý-XO\ýìääç
Worldwide FAX · 614-841-5471 · tech support
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.