- Monitors tanks levels for oil and anti-freeze mixtures -
Part No. 256285 Use with Graco Matrix 3.0 Software only.

The Matrix Tank Level Monitor contains an RF device with the following approvals:
Industry Canada Statement The term “IC” before the certification/registra- tion number only signifies that the Industry Canada technical specifications were met. ✓
US Patent D484,819

The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama- tion point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. Refer back to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where applicable.

There are 8 Network ID's and 8 Transceiver ID's possi- ble by changing the position of the dipswitches. The eight positions are identified as 1, 2, 3, 4, 5, 6, 7 and 8. See FIG. 2 and FIG. 3 on pages 4 and 5.
Setting the S1 and S2 Dipswitches (Unless otherwise indicated, for the following instruc- tions Refer to FIG. 1 and FIG. 2)

The TLM has two, 4 - position dipswitches labeled S1 and S2. TLM dipswitches must be set to match those of the transceiver the TLM will be communicating with. The factory default setting for all TLM’s is (‘1’ ‘1’). The first ‘1’ refers to the Network ID and the second ‘1’ refers to the Transceiver ID.
Wait at least 30 seconds after the dipswitch settings are made before installing the batteries. If you do not wait the 30 seconds, the software will not recognize the new settings.
Set Up

Make sure the cover screws are tightened securely (18-22 in-lb) to avoid water leakage into the TLM electronics. If a torque wrench is not used, verify there are no gaps under the screw heads and no gaps under the cover flange. This will ensure proper compression of the gasket for a water-tight seal.
It will take about 30 seconds for the monitor to dis- play information after pressing the Display button on the initial power-up. This time will decrease thereafter to a few seconds
Make sure the gasket (2) is not damaged and is in the correct location.

Set Up

See FIG. 3 for dipswitch setting configurations.
The batteries must be disconnected and removed before changing dipswitch settings or the TLM will not be able to communicate with the PC software.
1 - default
on 2
on 3
on 4
1 2 3 4 S2
1 2 3 4 S2
1 2 3 4 S2
on 5
on 6
on 8
1 2 3 4 S2
1 2 3 4 S2
1 2 3 4 S2
1 2 3 4 S2
8 S1 Network ID
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
S1
S1
S1
S1
S1
S1
S1

Graco recommends registering TLM prior to installa- tion.
See FIG. 4 for display messages you will see during Registration Mode.
The TLM operating parameters are controlled by the Matrix PC Software and setup by the System Adminis- trator. See the Matrix 3 Software instruction manual for the PC setup instructions.

To register the TLM:
Set Up

(See FIG. 6, page 8)
Fluid Volume -Volume of fluid remaining in the tank, based on the tank geometry defined during setup. The TLM can be programmed to display in either gallons or liters during programming of the TLM.
TLM ID - Unique number assigned to the TLM to distin- guish it from other TLM’s in the system.
Battery Life - Remaining life of the unit’s batteries. Sys- tem Administrator on Matrix PC Software determines when Low Battery Warning message is generated.
Vertical tanks use this capacity figure to calculate tank volume. Obround and cylindrical tanks use the tank dimensions to calculate tank volume.
Battery life is dependent on the number of readings taken per day.
No RF Signal - Displays when the TLM is not receiving an RF ACK signal from the PC transceiver. If the tank level monitor is receiving an ACK signal or the signal is re-established, this screen will not appear.
Network ID and Transceiver ID - Shows the Network ID and Transceiver ID TLM is using (also see page 3).
If the message “No RF Signal” appears, the fluid volume and battery life data is not transmitted or updated at the PC. This message may take up to 15 seconds to display.
Firmware - Current version of operating software con- trolling TLM operation.
Fluid Level - Depth of fluid remaining in the tank pro- vided in either inches or centimeters as defined during setup.
No PC Signal - Displays when the TLM is not receiving a response from the Matrix PC software (i.e, PC is off or software is not installed). If the TLM receives a response from the PC, this information will not appear.
If the message “NO PC SIGNAL” appears, the fluid vol- ume and battery life data will not be updated at the PC. This message may take up to 15 seconds to display.
TLM Display


Press & Hold DISPLAY button


TX ID

MODE


Transceiver No Ack received from



TLM ID


VERSION
xx.xx.xx
xx.xx.xx








TLM must be mounted with- in 2° from perpendicular to the surface of the fluid.

Do not install the TLM in the tank’s fill port. Repeated removal of the TLM will damage the unit and void the warranty.
Graco recommends that the height of the tank fitting should not exceed 1/2 in. (1.27 cm). The fitting height can be up to 2 in. (5.08 cm), provided the fit- ting is within 2 degrees of the surface of the fluid. Also, the taller the tank, the more critical the 2 degree specification becomes. See FIG. 6.
Port (D) is not to be used as a fill hole for oil deliveries. See FIG. 7.
The tank’s breather port might be the only available location for mounting the TLM. The horizontal 2 in. npt port (D) can be used to accommodate the breather. The breather should be mounted in an upright position using a 90° elbow fitting.

Do not use the horizontal port for routing pressure relief return tubes. This can result in inaccurate readings.
- Fluid in the tank is agitated (i.e. filling a tank with oil or anti-freeze). Be sure to take all TLM readings when the fluid in the tank is calm.

- TLM is mounted next to the tank wall or in a cor- ner.
- If there is any structural bracing or obstruction between the TLM and the surface of fluid in tank.
- If the down tube is not the Graco-supplied down tube.
Installation

After a tank is refilled from an oil distributor or a waste oil tank is emptied by a waste oil service provider, press the Display button on the TLM to ensure the TLM will maintain the most current tank volume status. If button is not pushed, the TLM will automatically read correctly at the next scheduled tank reading.

The PC software automatically changes the PC time when daylight saving time changes occur (Spring and Fall).
The first TLM reading will be 1 hour earlier or later (depending on the Spring or Fall daylight saving time change), but all subsequent TLM reading will be accurate.
Press and release the Display button (A). Data appears on display (B); each screen lasting a few seconds before going on to the next. See FIG. 8.
Tank Level data can be viewed remotely at the PC, using the Matrix software.

Viewing Data

Troubleshooting

Troubleshooting

Once the Tank Level Monitor has been installed, no additional maintenance or service is necessary, with the excep- tion of replacing batteries.
Always replace both batteries with two new 9-volt alkaline batteries whenever you change batteries in the TLM.
Sparking can occur when changing batteries. Only replace the battery in a non-hazardous location, away from flammable fluids or fumes.
Service


Remove protective cover used for shipping before programming.
Do not remove. This is required to maintain intrinsic safety approval.
Ref. No. Part No. Description Qty
1 BATTERY, 9 volt (purchased locally) 2 2 126752 GASKET, sensor, ultrasonic 1 3 117467 SCREW, self tapping, HI-LO, #10-16 x 9/16 4 4 117743 FOAM, insulator 1 5 117259 ENCLOSURE 1 6 15T814 LABEL, overlay 1 7 15A962 COVER 1 8 117469 HOLDER, battery 2 9 15U731 DOWN TUBE 1 10 119391 PLUG
Parts

Ultrasonic Tank Depth Measurement range 0 - 30 ft. (0 - 9 m) Not for use in pressurized tanks.
Fluid Level Measurement Accuracy +/- 0.5%
Mounting Standard 2 in. (npt) bung.
Height above tank for TLM and tube mount- ing
15 in. (30.48 cm).
TLM Mounting Tube and Tank Vent Graco recommends venting the tank separately from the TLM. If not possible, the TLM mounting and vent function can be combined if required for tanks with one hole in tank. Be sure TLM is not mounted close to tank edges or corner.
Weight (with batteries installed) 2.34lb. (1.06 g)
RF Communication 2.4 GHz
Operating Temperature Range -22° F to 185° F (- 30° C to 85° C) Note: Display will not function below 32°F (0°C).
Storage Temperature Range -40°F to 185°F (-40°C to 85°C)
Batteries Two 9V alkaline
Battery Life 1.5 years
RF Communication 2.4 GHz
Obstructed RF Communication Range (based on building construction and RF envi- ronment)
250-300 ft (76.2 - 91.0 m)
Tank Geometry Vertical walled tanks, cylindrical tanks, and obround tanks.
Approvals FCC, Industry Canada (IC), C-Tick, CE
Technical Data · Enclosure IP65

A 9.1 in (231 mm)
B 4.9 in. (124 mm)
A
1-1/2 in. npt
2 in. npt
Dimensions

Vertical Tank: • Maximum Volume = 999, 999 gallons or liters.

Maximum Height 30 ft. (360 in.)
Tank Geometry

Cylindrical Tank: • Maximum Volume = 999, 999 gallons or liters.

Maximum Height 30 ft. (360 in)
30 ft. (360 in)
Tank Geometry · Maximum Length

Obround Tank: • Maximum Volume = 999, 999 gallons or liters.

Maximum Height 30 ft. (360 in)
Maximum Width 30 ft. (360 in.)
30 ft. (360 in)
Tank Geometry · Maximum Length

Graco warrants all equipment manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twenty four months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco's written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco's sole obligation and buyer's sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale Graco makes no warranty, and disclaims all implied warranties of merchantability and fitness for a particular purpose in connection with accessories, equipment, materials or components sold but not manufactured by Graco. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise.
The parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés à la suite de ou en rapport, directement ou indirectement, avec les procedures concernées.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor.
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.
For patent information, see www.graco.com/patents
Original Instructions. This manual contains English. MM 312964
Copyright 2008, Graco Inc. is registered to I.S. EN ISO 9001
www.graco.com Revised September 2012
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Brand new monitor’s dis- play is very dim. | Unit is shipped with protective coat- ing over display. | Remove protective coating. | p.11 |
| Monitor displays “Invalid Reading”. | The TLM reading is outside of the programmed size parameters. | Verify the programmed parameters and re-program the TLM if necessary. | p.11 |
| Monitor will not register. | Transceiver is not powered-up. | Verify transceiver is powered-up | p.11 |
| Monitor will not register. | Attempt to program while red lights on transceiver are lit. | Wait until red lights on transceiver go blank before attempting to register. | p.11 |
| Monitor will not register. | Transceiver NET ID and TRANS ID not set correctly | Ensure NET ID and TRANS ID are set for appropriate commu- nication cable. | p.11 |
| Monitor will not register. | TLM dipswitches settings do not match transceiver settings. | Verify settings with Transceiver (see page. 5 for dipswitch set- ting instructions). | p.11 |
| Monitor will not register. | Weak or dead batteries. | Replace batteries. See Replacing Batteries, page 13. | p.11 |
| Monitor will not register. | Microprocessor not completely shut down before installing new batteries. | After you have removed old batteries, wait 30 seconds to ensure the microprocessor has completely shut down, before installing new batteries. | p.11 |
| Monitor will not register. | USB cable or RS-422 not connected | Be sure cable are properly connected between Transceiver and PC | p.11 |
| Monitor has intermittent RF communication | Out of RF range. RF obstruction. | Reposition Transceiver until TLM has good RF communication or add a transceiver. | p.11 |
| Monitor has intermittent RF communication | Weak or dead batteries. | Replace batteries. See Replacing Batteries, page 13. | p.11 |
| Monitor is not reporting scheduled readings. | Out of RF range. RF obstruction. | Reposition Transceiver until TLM has good RF communication. | p.11 |
| Monitor is not reporting scheduled readings. | Two TLMs are programmed to the same address. | Verify that each TLM is correctly programmed to a unique address. | p.11 |
| Monitor is not reporting scheduled readings. | Weak or dead batteries. | Replace batteries. See Setting the S1 and S2 Dipswitches, page 3. | p.11 |
| Monitor is not reporting scheduled readings. | Microprocessor not completely shut down before installing new batteries. | After you have removed old batteries, wait 30 seconds to ensure the microprocessor has completely shut down, before installing new batteries. | p.11 |
| Monitor is not reporting scheduled readings. | Tank Level Monitor was not associ- ated with profile after scheduled times were entered into software. | Reregister Tank Level Monitor and associate Tank Level Moni- tor with profile ID. | p.11 |
| Monitor is not reporting scheduled readings. | Reading is scheduled when pump is operating. | Ensure readings are scheduled at times that the pump is not operating. | p.11 |
| Monitor is not reporting scheduled readings. | Clock was changed on PC but the tank level monitor was not resychro- nized. | The monitor’s internal clock is synchronized with the PC clock upon register or reading. Manipulating the scheduled reporting time by changing the PC clock will cause a false indication that the monitor is not reporting at the scheduled reporting times. | p.11 |
| Monitor will not take read- ing when Display button is pressed. | Weak or dead batteries. | Replace batteries. See Replacing Batteries, page 13. | p.11 |
| Monitor will not take read- ing when Display button is pressed. | Batteries are not correctly seated. | Ensure the batteries fully engage the mounting clips by push- ing on the bottom of each battery with your thumbs. | p.11 |
| Monitor will not take read- ing when Display button is pressed. | Microprocessor not completely shut down before installing new batteries. | After you have removed old batteries, wait 30 seconds to ensure the microprocessor has completely shut down, before installing new batteries. | p.11 |
| Monitor will not take read- ing when Display button is pressed. | Monitor display is cracked. | Replace monitor display. | p.11 |
| Monitor will not take read- ing when Display button is pressed. | PC is not running | Turn on PC. In order for TLM readings to be logged, PC must be running. | p.11 |
| Monitor readings are inaccurate. | Tank geometry incorrectly defined. | See Tank Level Monitor Software Guide or PC Software Guide for details. | p.12 |
| Monitor readings are inaccurate. | Tank Level Monitor has not been updated with latest adjustments made within The profile ID on the PC. | Manually push DISPLAY button on TLM | p.12 |
| Monitor readings are inaccurate. | Two TLMs are programmed to the same address. | Verify that each TLM is correctly programmed to a unique address. | p.12 |
| Monitor readings are inaccurate. | Fluid surface is moving while reading is being taken. | Ensure pump is not operating and that nothing is disturbing the surface of the fluid during readings. | p.12 |
| Monitor readings are inaccurate. | Pipe adapters installed in the tank bung. | Ensure there are no adapters installed in the tank bung. | p.12 |
| Monitor readings are inaccurate. | Tank Level Monitor is not perpendic- ular to top of fluid. | Level tank so that it is perpendicular to top of the fluid and/or realign Tank Level Monitor. | p.12 |
| Monitor readings are inaccurate. | Inside tank obstruction. | Install in different tank bung to avoid tank obstruction. | p.12 |