Emerson XDF

60 pages·13.8 MB·Surge Protector·PDF·ENDEFRITNLJA
Emerson XDF
Table of Contents 147 sections Important Safety Instructions · SAVE THESE INSTRUCTIONS · 1.0 Glossary of Symbols · 2.0 Product Description · … ShowHide
Important Safety Instructionsp.7SAVE THESE INSTRUCTIONSp.71.0 Glossary of Symbolsp.82.0 Product Descriptionp.92.1 Operational Overview-Self-Contained, Air Cooled Modelp.9Figure 1 Component location, general operational layout of self-contained, air cooled modelp.92.2 Operational Overview - Water/Glycol Cooled Modelp.10Figure 2 Component location of water/glycol cooled modelp.10Figure 3 Component location, rear of XDFp.11Figure 4 Dimensional data, self-contained, air cooled modelp.12Figure 5 Dimensional data, water/glycol cooled modelp.13Figure 6 Dimensional data, all models-top, bottom and cable entry cutoutsp.143.0 XDF Componentsp.153.1 Standard Components-Self-Contained, Air Cooled and Water/Glycol Cooled Modelsp.153.1.1 Framep.153.1.2 Enclosurep.153.1.3 Doorsp.153.1.4 Side Panelsp.153.1.5 Environmental Controlp.16Heat Removal-Self-Contained, Air Cooled XDFp.16Heat Removal-Water/Glycol Cooled XDFp.16Figure 7 Cooling system components-self-contained, air cooled modelsp.16Figure 8 Cooling system components-water cooled modelsp.173.1.6 Control-Liebert’s iCOM Controllerp.18Figure 9 XDF with iCOM controllerp.183.2 Coolant Source-Water/Glycol Modelsp.193.2.1 Closed-Loop Water Systemp.19Figure 10 Water/glycol XDF supplied by closed-loop water systemp.193.2.2 Drycooler Loopp.20Figure 11 Water/glycol cooled general arrangement with drycooler as coolant sourcep.203.3 Optional Equipmentp.213.3.1 General Enclosure Optionsp.213.3.2 Power Optionsp.21MP Advanced Power Strips and Controllersp.21Uninterruptible Power Supplyp.21Figure 12 Optional power equipment, examplesp.214.0 Installationp.224.1 Inspectionp.22Packing Materialp.224.2 Recommended Setup Equipmentp.224.3 Unloading the XDFp.224.3.1 Handling the Unit While It is Packagedp.23Figure 13 Recommended unit handling equipmentp.234.3.2 Unpack the XDFp.23Figure 14 Removing XDF packagingp.234.3.3 Removing the XDF from Skidp.24Figure 15 Remove lag bolts and bracketsp.24Figure 16 Roll XDF off the shipping skidp.254.4 XDF Site Preparationp.26Figure 17 XDF clearancesp.264.5 Voltage Requirementsp.274.5.1 Voltage Input Requirementsp.27Changing Condenser Fan Power Source-Self-Contained, Air Cooled Unitsp.27Figure 18 Alternate condenser fan power connectionp.274.5.2 Uninterruptible Power Supply-Optionalp.284.5.3 MP Advanced Power Strips-Optionalp.284.5.4 Condensate Drain Connectionp.28Table 1 Optional condensate pump performancep.28Figure 19 Condensate drain connection and adapterp.284.6 Drycooler Installation-Water/Glycol Cooled Modelp.284.7 Equipment Layoutp.29Figure 20 Recommended equipment arrangementp.294.8 Frame and Enclosure Configurationsp.304.8.1 Internal Mounting Railsp.304.8.2 Rear-Mount Rails-Positionp.304.9 Mounting Hardwarep.304.10 Door-Removep.314.10.1 Remove the Doorp.314.10.2 Quick Door Removalp.314.11 Side Panels-Remove and Replacep.314.11.1 Remove the Left Panelp.314.11.2 Remove the Right Panelp.324.11.3 Replace a Panelp.325.0 Piping Considerations-Water/Glycol Models Onlyp.335.1 Generalp.335.2 Closed Loop Water Systemp.33Table 2 Water supply flow ratesp.335.2.1 Expansion Tanks, Fluid Relief Valves and Other Devicesp.345.2.2 Corrosion Protectionp.345.2.3 Freeze Protection-Coolant Type and Insulationp.345.3 Drycooler Loop Systemp.355.3.1 Glycol Solutionsp.35Table 3 Ethylene glycol concentrationsp.35Table 4 Glycol supply flow ratesp.35Table 5 Drycooler selectionp.356.0 Filling the XDF with Coolant-Water or Glycolp.366.1 Preparing the System for Fillingp.366.1.1 XDF Water/Glycol Cooled Unit Volumep.36Table 6 Volume in standard Type “L” copper pipingp.366.1.2 Filling the System with Water or Glycolp.367.0 Electrical Connectionsp.37Figure 21 Customer electrical connections and cable entry points-self-contained, air cooled unitsp.37Figure 22 Customer electrical connections and cable entry points-water/glycol cooled unitsp.387.1 Utility Power Supplyp.397.1.1 Route Input Power Cables Through the XDF’s Topp.39Figure 23 Route input power cords through XDF topp.398.0 Cable Management Optionsp.408.1 Cable Management Considerationsp.408.2 Cable Managementp.40Figure 24 Cable rings, Velcro straps on XDF railsp.408.3 Cable Accessp.418.3.1 Top Cover and Backp.418.4 Optional Cable Management Channelp.41Figure 25 Cable Management Channel lengthsp.41Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spoolsp.42Figure 27 Cable management accessories: Cable Trayp.429.0 Startupp.439.1 XDF Startup Inspection Checklistp.439.1.1 Site Conditionsp.439.2 Starting the XDFp.44Figure 28 iCOM controller keysp.4410.0 Operationp.4510.1 Environmental Controlp.45Remote Communications-Building Management Systems, Liebert SiteScanp.4510.2 iCOM Components and Functionsp.45Figure 29 iCOM display componentsp.45Table 7 Keyboard icons and functionsp.4610.3 Navigating Through the iCOM Displayp.47Figure 30 iCOM graphical display default screen componentsp.47Figure 31 iCOM simple display default screen componentsp.4710.3.1 Accessing Menus and Settingsp.48Viewing Datap.48Figure 32 iCOM user menu, Page 1 of 6p.48Figure 33 Accessing additional menu linesp.4810.3.2 Entering the Passwordp.4810.4 Changing Operational Settingsp.49Table 8 User menu iconsp.5010.5 Changing iCOM’s Display Settingsp.51Figure 34 Display setup screenp.5110.6 Changing the XDF’s Default Operating Temperaturep.5110.7 Operation With the Door Openp.5210.8 Backup Ventilation Systemp.53Figure 35 Airflow pattern, backup ventilation operationp.5310.9 XDF Compressorp.5310.10 Uninterruptible Power Supplyp.5311.0 Maintenancep.54Table 9 Troubleshootingp.5411.1 Periodic Maintenancep.5412.0 Specificationsp.55Figure 36 XDF model numbersp.55Table 10 Physical specificationsp.55Table 11 Electrical specificationsp.56Table 12 Total heat rejectionp.5612.1 Optional Power Systemsp.57Table 13 UPS performance datap.5712.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mountp.58Table 14 MP Advanced Power Strip specificationsp.58
Page 1 of the Emerson XDF user manual
Page 1 · click to enlarge
Page 1
Emerson XDF diagram (page 1)
Fig. 1
Page 2 of the Emerson XDF user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Emerson XDF user manual
Page 3 of the Emerson XDF user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Important Safety Instructionsp.7SAVE THESE INSTRUCTIONSp.71.0 Glossary of Symbolsp.82.0 Product Descriptionp.92.1 Operational Overview-Self-Contained, Air Cooled Modelp.9Figure 1 Component location, general operational layout of self-contained, air cooled modelp.92.2 Operational Overview - Water/Glycol Cooled Modelp.10Figure 2 Component location of water/glycol cooled modelp.10Figure 3 Component location, rear of XDFp.11Figure 4 Dimensional data, self-contained, air cooled modelp.12Figure 5 Dimensional data, water/glycol cooled modelp.13Figure 6 Dimensional data, all models-top, bottom and cable entry cutoutsp.143.0 XDF Componentsp.153.1 Standard Components-Self-Contained, Air Cooled and Water/Glycol Cooled Modelsp.153.1.1 Framep.153.1.2 Enclosurep.153.1.3 Doorsp.153.1.4 Side Panelsp.153.1.5 Environmental Controlp.16Heat Removal-Self-Contained, Air Cooled XDFp.16Heat Removal-Water/Glycol Cooled XDFp.16Figure 7 Cooling system components-self-contained, air cooled modelsp.16Figure 8 Cooling system components-water cooled modelsp.173.1.6 Control-Liebert’s iCOM Controllerp.18Figure 9 XDF with iCOM controllerp.183.2 Coolant Source-Water/Glycol Modelsp.193.2.1 Closed-Loop Water Systemp.19Figure 10 Water/glycol XDF supplied by closed-loop water systemp.193.2.2 Drycooler Loopp.20Figure 11 Water/glycol cooled general arrangement with drycooler as coolant sourcep.203.3 Optional Equipmentp.213.3.1 General Enclosure Optionsp.213.3.2 Power Optionsp.21MP Advanced Power Strips and Controllersp.21Uninterruptible Power Supplyp.21Figure 12 Optional power equipment, examplesp.214.0 Installationp.224.1 Inspectionp.22Packing Materialp.224.2 Recommended Setup Equipmentp.224.3 Unloading the XDFp.224.3.1 Handling the Unit While It is Packagedp.23Figure 13 Recommended unit handling equipmentp.234.3.2 Unpack the XDFp.23Figure 14 Removing XDF packagingp.234.3.3 Removing the XDF from Skidp.24Figure 15 Remove lag bolts and bracketsp.24Figure 16 Roll XDF off the shipping skidp.254.4 XDF Site Preparationp.26Figure 17 XDF clearancesp.264.5 Voltage Requirementsp.274.5.1 Voltage Input Requirementsp.27Changing Condenser Fan Power Source-Self-Contained, Air Cooled Unitsp.27Figure 18 Alternate condenser fan power connectionp.274.5.2 Uninterruptible Power Supply-Optionalp.284.5.3 MP Advanced Power Strips-Optionalp.284.5.4 Condensate Drain Connectionp.28Table 1 Optional condensate pump performancep.28Figure 19 Condensate drain connection and adapterp.284.6 Drycooler Installation-Water/Glycol Cooled Modelp.284.7 Equipment Layoutp.29Figure 20 Recommended equipment arrangementp.294.8 Frame and Enclosure Configurationsp.304.8.1 Internal Mounting Railsp.304.8.2 Rear-Mount Rails-Positionp.304.9 Mounting Hardwarep.304.10 Door-Removep.314.10.1 Remove the Doorp.314.10.2 Quick Door Removalp.314.11 Side Panels-Remove and Replacep.314.11.1 Remove the Left Panelp.314.11.2 Remove the Right Panelp.324.11.3 Replace a Panelp.325.0 Piping Considerations-Water/Glycol Models Onlyp.335.1 Generalp.335.2 Closed Loop Water Systemp.33Table 2 Water supply flow ratesp.335.2.1 Expansion Tanks, Fluid Relief Valves and Other Devicesp.345.2.2 Corrosion Protectionp.345.2.3 Freeze Protection-Coolant Type and Insulationp.345.3 Drycooler Loop Systemp.355.3.1 Glycol Solutionsp.35Table 3 Ethylene glycol concentrationsp.35Table 4 Glycol supply flow ratesp.35Table 5 Drycooler selectionp.356.0 Filling the XDF with Coolant-Water or Glycolp.366.1 Preparing the System for Fillingp.366.1.1 XDF Water/Glycol Cooled Unit Volumep.36Table 6 Volume in standard Type “L” copper pipingp.366.1.2 Filling the System with Water or Glycolp.367.0 Electrical Connectionsp.37Figure 21 Customer electrical connections and cable entry points-self-contained, air cooled unitsp.37Figure 22 Customer electrical connections and cable entry points-water/glycol cooled unitsp.387.1 Utility Power Supplyp.397.1.1 Route Input Power Cables Through the XDF’s Topp.39Figure 23 Route input power cords through XDF topp.398.0 Cable Management Optionsp.408.1 Cable Management Considerationsp.408.2 Cable Managementp.40Figure 24 Cable rings, Velcro straps on XDF railsp.408.3 Cable Accessp.418.3.1 Top Cover and Backp.418.4 Optional Cable Management Channelp.41Figure 25 Cable Management Channel lengthsp.41Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spoolsp.42Figure 27 Cable management accessories: Cable Trayp.429.0 Startupp.439.1 XDF Startup Inspection Checklistp.439.1.1 Site Conditionsp.439.2 Starting the XDFp.44Figure 28 iCOM controller keysp.4410.0 Operationp.4510.1 Environmental Controlp.45Remote Communications-Building Management Systems, Liebert SiteScanp.4510.2 iCOM Components and Functionsp.45Figure 29 iCOM display componentsp.45Table 7 Keyboard icons and functionsp.4610.3 Navigating Through the iCOM Displayp.47Figure 30 iCOM graphical display default screen componentsp.47Figure 31 iCOM simple display default screen componentsp.4710.3.1 Accessing Menus and Settingsp.48Viewing Datap.48Figure 32 iCOM user menu, Page 1 of 6p.48Figure 33 Accessing additional menu linesp.4810.3.2 Entering the Passwordp.4810.4 Changing Operational Settingsp.49Table 8 User menu iconsp.5010.5 Changing iCOM’s Display Settingsp.51Figure 34 Display setup screenp.5110.6 Changing the XDF’s Default Operating Temperaturep.5110.7 Operation With the Door Openp.5210.8 Backup Ventilation Systemp.53Figure 35 Airflow pattern, backup ventilation operationp.5310.9 XDF Compressorp.5310.10 Uninterruptible Power Supplyp.5311.0 Maintenancep.54Table 9 Troubleshootingp.5411.1 Periodic Maintenancep.5412.0 Specificationsp.55Figure 36 XDF model numbersp.55Table 10 Physical specificationsp.55Table 11 Electrical specificationsp.56Table 12 Total heat rejectionp.5612.1 Optional Power Systemsp.57Table 13 UPS performance datap.5712.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mountp.58Table 14 MP Advanced Power Strip specificationsp.58
Page 4 of the Emerson XDF user manual
Page 4 · click to enlarge
Page 4

4.11 Side Panels—Remove and Replace 25

4.11.1 Remove the Left Panel 25 4.11.2 Remove the Right Panel 26 4.11.3 Replace a Panel 26

5.0 PIPING CONSIDERATIONS—WATER/GLYCOL MODELS ONLY 27

5.1 General 27

5.2 Closed Loop Water System 27

5.2.1 Expansion Tanks, Fluid Relief Valves and Other Devices 28 5.2.2 Corrosion Protection 28 5.2.3 Freeze Protection—Coolant Type and Insulation 28 5.3 Drycooler Loop System 29

5.3.1 Glycol Solutions 29

6.0 FILLING THE XDF WITH COOLANT—WATER OR GLYCOL 30

6.1 Preparing the System for Filling 30

6.1.1 XDF Water/Glycol Cooled Unit Volume 30 6.1.2 Filling the System with Water or Glycol 30

7.0 ELECTRICAL CONNECTIONS 31

7.1 Utility Power Supply 33

7.1.1 Route Input Power Cables Through the XDF’s Top 33

8.0 CABLE MANAGEMENT OPTIONS 34

8.1 Cable Management Considerations 34

8.2 Cable Management 34

8.3 Cable Access 35

8.3.1 Top Cover and Back 35 8.4 Optional Cable Management Channel 35

9.0 STARTUP 37

9.1 XDF Startup Inspection Checklist 37

9.1.1 Site Conditions 37 9.2 Starting the XDF 38

10.0 OPERATION 39

10.1 Environmental Control 39

10.2 iCOM Components and Functions 39

10.3 Navigating Through the iCOM Display 41

10.3.1 Accessing Menus and Settings 42 10.3.2 Entering the Password 42 10.4 Changing Operational Settings 43

10.5 Changing iCOM’s Display Settings 45

10.6 Changing the XDF’s Default Operating Temperature 45

10.7 Operation With the Door Open 46

10.8 Backup Ventilation System 47

10.9 XDF Compressor 47

Page 5 of the Emerson XDF user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

Important Safety Instructionsp.7SAVE THESE INSTRUCTIONSp.71.0 Glossary of Symbolsp.82.0 Product Descriptionp.92.1 Operational Overview-Self-Contained, Air Cooled Modelp.9Figure 1 Component location, general operational layout of self-contained, air cooled modelp.92.2 Operational Overview - Water/Glycol Cooled Modelp.10Figure 2 Component location of water/glycol cooled modelp.10Figure 3 Component location, rear of XDFp.11Figure 4 Dimensional data, self-contained, air cooled modelp.12Figure 5 Dimensional data, water/glycol cooled modelp.13Figure 6 Dimensional data, all models-top, bottom and cable entry cutoutsp.143.0 XDF Componentsp.153.1 Standard Components-Self-Contained, Air Cooled and Water/Glycol Cooled Modelsp.153.1.1 Framep.153.1.2 Enclosurep.153.1.3 Doorsp.153.1.4 Side Panelsp.153.1.5 Environmental Controlp.16Heat Removal-Self-Contained, Air Cooled XDFp.16Heat Removal-Water/Glycol Cooled XDFp.16Figure 7 Cooling system components-self-contained, air cooled modelsp.16Figure 8 Cooling system components-water cooled modelsp.173.1.6 Control-Liebert’s iCOM Controllerp.18Figure 9 XDF with iCOM controllerp.183.2 Coolant Source-Water/Glycol Modelsp.193.2.1 Closed-Loop Water Systemp.19Figure 10 Water/glycol XDF supplied by closed-loop water systemp.193.2.2 Drycooler Loopp.20Figure 11 Water/glycol cooled general arrangement with drycooler as coolant sourcep.203.3 Optional Equipmentp.213.3.1 General Enclosure Optionsp.213.3.2 Power Optionsp.21MP Advanced Power Strips and Controllersp.21Uninterruptible Power Supplyp.21Figure 12 Optional power equipment, examplesp.214.0 Installationp.224.1 Inspectionp.22Packing Materialp.224.2 Recommended Setup Equipmentp.224.3 Unloading the XDFp.224.3.1 Handling the Unit While It is Packagedp.23Figure 13 Recommended unit handling equipmentp.234.3.2 Unpack the XDFp.23Figure 14 Removing XDF packagingp.234.3.3 Removing the XDF from Skidp.24Figure 15 Remove lag bolts and bracketsp.24Figure 16 Roll XDF off the shipping skidp.254.4 XDF Site Preparationp.26Figure 17 XDF clearancesp.264.5 Voltage Requirementsp.274.5.1 Voltage Input Requirementsp.27Changing Condenser Fan Power Source-Self-Contained, Air Cooled Unitsp.27Figure 18 Alternate condenser fan power connectionp.274.5.2 Uninterruptible Power Supply-Optionalp.284.5.3 MP Advanced Power Strips-Optionalp.284.5.4 Condensate Drain Connectionp.28Table 1 Optional condensate pump performancep.28Figure 19 Condensate drain connection and adapterp.284.6 Drycooler Installation-Water/Glycol Cooled Modelp.284.7 Equipment Layoutp.29Figure 20 Recommended equipment arrangementp.294.8 Frame and Enclosure Configurationsp.304.8.1 Internal Mounting Railsp.304.8.2 Rear-Mount Rails-Positionp.304.9 Mounting Hardwarep.304.10 Door-Removep.314.10.1 Remove the Doorp.314.10.2 Quick Door Removalp.314.11 Side Panels-Remove and Replacep.314.11.1 Remove the Left Panelp.314.11.2 Remove the Right Panelp.324.11.3 Replace a Panelp.325.0 Piping Considerations-Water/Glycol Models Onlyp.335.1 Generalp.335.2 Closed Loop Water Systemp.33Table 2 Water supply flow ratesp.335.2.1 Expansion Tanks, Fluid Relief Valves and Other Devicesp.345.2.2 Corrosion Protectionp.345.2.3 Freeze Protection-Coolant Type and Insulationp.345.3 Drycooler Loop Systemp.355.3.1 Glycol Solutionsp.35Table 3 Ethylene glycol concentrationsp.35Table 4 Glycol supply flow ratesp.35Table 5 Drycooler selectionp.356.0 Filling the XDF with Coolant-Water or Glycolp.366.1 Preparing the System for Fillingp.366.1.1 XDF Water/Glycol Cooled Unit Volumep.36Table 6 Volume in standard Type “L” copper pipingp.366.1.2 Filling the System with Water or Glycolp.367.0 Electrical Connectionsp.37Figure 21 Customer electrical connections and cable entry points-self-contained, air cooled unitsp.37Figure 22 Customer electrical connections and cable entry points-water/glycol cooled unitsp.387.1 Utility Power Supplyp.397.1.1 Route Input Power Cables Through the XDF’s Topp.39Figure 23 Route input power cords through XDF topp.398.0 Cable Management Optionsp.408.1 Cable Management Considerationsp.408.2 Cable Managementp.40Figure 24 Cable rings, Velcro straps on XDF railsp.408.3 Cable Accessp.418.3.1 Top Cover and Backp.418.4 Optional Cable Management Channelp.41Figure 25 Cable Management Channel lengthsp.41Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spoolsp.42Figure 27 Cable management accessories: Cable Trayp.429.0 Startupp.439.1 XDF Startup Inspection Checklistp.439.1.1 Site Conditionsp.439.2 Starting the XDFp.44Figure 28 iCOM controller keysp.4410.0 Operationp.4510.1 Environmental Controlp.45Remote Communications-Building Management Systems, Liebert SiteScanp.4510.2 iCOM Components and Functionsp.45Figure 29 iCOM display componentsp.45Table 7 Keyboard icons and functionsp.4610.3 Navigating Through the iCOM Displayp.47Figure 30 iCOM graphical display default screen componentsp.47Figure 31 iCOM simple display default screen componentsp.4710.3.1 Accessing Menus and Settingsp.48Viewing Datap.48Figure 32 iCOM user menu, Page 1 of 6p.48Figure 33 Accessing additional menu linesp.4810.3.2 Entering the Passwordp.4810.4 Changing Operational Settingsp.49Table 8 User menu iconsp.5010.5 Changing iCOM’s Display Settingsp.51Figure 34 Display setup screenp.5110.6 Changing the XDF’s Default Operating Temperaturep.5110.7 Operation With the Door Openp.5210.8 Backup Ventilation Systemp.53Figure 35 Airflow pattern, backup ventilation operationp.5310.9 XDF Compressorp.5310.10 Uninterruptible Power Supplyp.5311.0 Maintenancep.54Table 9 Troubleshootingp.5411.1 Periodic Maintenancep.5412.0 Specificationsp.55Figure 36 XDF model numbersp.55Table 10 Physical specificationsp.55Table 11 Electrical specificationsp.56Table 12 Total heat rejectionp.5612.1 Optional Power Systemsp.57Table 13 UPS performance datap.5712.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mountp.58Table 14 MP Advanced Power Strip specificationsp.58
Page 6 of the Emerson XDF user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

Important Safety Instructionsp.7SAVE THESE INSTRUCTIONSp.71.0 Glossary of Symbolsp.82.0 Product Descriptionp.92.1 Operational Overview-Self-Contained, Air Cooled Modelp.9Figure 1 Component location, general operational layout of self-contained, air cooled modelp.92.2 Operational Overview - Water/Glycol Cooled Modelp.10Figure 2 Component location of water/glycol cooled modelp.10Figure 3 Component location, rear of XDFp.11Figure 4 Dimensional data, self-contained, air cooled modelp.12Figure 5 Dimensional data, water/glycol cooled modelp.13Figure 6 Dimensional data, all models-top, bottom and cable entry cutoutsp.143.0 XDF Componentsp.153.1 Standard Components-Self-Contained, Air Cooled and Water/Glycol Cooled Modelsp.153.1.1 Framep.153.1.2 Enclosurep.153.1.3 Doorsp.153.1.4 Side Panelsp.153.1.5 Environmental Controlp.16Heat Removal-Self-Contained, Air Cooled XDFp.16Heat Removal-Water/Glycol Cooled XDFp.16Figure 7 Cooling system components-self-contained, air cooled modelsp.16Figure 8 Cooling system components-water cooled modelsp.173.1.6 Control-Liebert’s iCOM Controllerp.18Figure 9 XDF with iCOM controllerp.183.2 Coolant Source-Water/Glycol Modelsp.193.2.1 Closed-Loop Water Systemp.19Figure 10 Water/glycol XDF supplied by closed-loop water systemp.193.2.2 Drycooler Loopp.20Figure 11 Water/glycol cooled general arrangement with drycooler as coolant sourcep.203.3 Optional Equipmentp.213.3.1 General Enclosure Optionsp.213.3.2 Power Optionsp.21MP Advanced Power Strips and Controllersp.21Uninterruptible Power Supplyp.21Figure 12 Optional power equipment, examplesp.214.0 Installationp.224.1 Inspectionp.22Packing Materialp.224.2 Recommended Setup Equipmentp.224.3 Unloading the XDFp.224.3.1 Handling the Unit While It is Packagedp.23Figure 13 Recommended unit handling equipmentp.234.3.2 Unpack the XDFp.23Figure 14 Removing XDF packagingp.234.3.3 Removing the XDF from Skidp.24Figure 15 Remove lag bolts and bracketsp.24Figure 16 Roll XDF off the shipping skidp.254.4 XDF Site Preparationp.26Figure 17 XDF clearancesp.264.5 Voltage Requirementsp.274.5.1 Voltage Input Requirementsp.27Changing Condenser Fan Power Source-Self-Contained, Air Cooled Unitsp.27Figure 18 Alternate condenser fan power connectionp.274.5.2 Uninterruptible Power Supply-Optionalp.284.5.3 MP Advanced Power Strips-Optionalp.284.5.4 Condensate Drain Connectionp.28Table 1 Optional condensate pump performancep.28Figure 19 Condensate drain connection and adapterp.284.6 Drycooler Installation-Water/Glycol Cooled Modelp.284.7 Equipment Layoutp.29Figure 20 Recommended equipment arrangementp.294.8 Frame and Enclosure Configurationsp.304.8.1 Internal Mounting Railsp.304.8.2 Rear-Mount Rails-Positionp.304.9 Mounting Hardwarep.304.10 Door-Removep.314.10.1 Remove the Doorp.314.10.2 Quick Door Removalp.314.11 Side Panels-Remove and Replacep.314.11.1 Remove the Left Panelp.314.11.2 Remove the Right Panelp.324.11.3 Replace a Panelp.325.0 Piping Considerations-Water/Glycol Models Onlyp.335.1 Generalp.335.2 Closed Loop Water Systemp.33Table 2 Water supply flow ratesp.335.2.1 Expansion Tanks, Fluid Relief Valves and Other Devicesp.345.2.2 Corrosion Protectionp.345.2.3 Freeze Protection-Coolant Type and Insulationp.345.3 Drycooler Loop Systemp.355.3.1 Glycol Solutionsp.35Table 3 Ethylene glycol concentrationsp.35Table 4 Glycol supply flow ratesp.35Table 5 Drycooler selectionp.356.0 Filling the XDF with Coolant-Water or Glycolp.366.1 Preparing the System for Fillingp.366.1.1 XDF Water/Glycol Cooled Unit Volumep.36Table 6 Volume in standard Type “L” copper pipingp.366.1.2 Filling the System with Water or Glycolp.367.0 Electrical Connectionsp.37Figure 21 Customer electrical connections and cable entry points-self-contained, air cooled unitsp.37Figure 22 Customer electrical connections and cable entry points-water/glycol cooled unitsp.387.1 Utility Power Supplyp.397.1.1 Route Input Power Cables Through the XDF’s Topp.39Figure 23 Route input power cords through XDF topp.398.0 Cable Management Optionsp.408.1 Cable Management Considerationsp.408.2 Cable Managementp.40Figure 24 Cable rings, Velcro straps on XDF railsp.408.3 Cable Accessp.418.3.1 Top Cover and Backp.418.4 Optional Cable Management Channelp.41Figure 25 Cable Management Channel lengthsp.41Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spoolsp.42Figure 27 Cable management accessories: Cable Trayp.429.0 Startupp.439.1 XDF Startup Inspection Checklistp.439.1.1 Site Conditionsp.439.2 Starting the XDFp.44Figure 28 iCOM controller keysp.4410.0 Operationp.4510.1 Environmental Controlp.45Remote Communications-Building Management Systems, Liebert SiteScanp.4510.2 iCOM Components and Functionsp.45Figure 29 iCOM display componentsp.45Table 7 Keyboard icons and functionsp.4610.3 Navigating Through the iCOM Displayp.47Figure 30 iCOM graphical display default screen componentsp.47Figure 31 iCOM simple display default screen componentsp.4710.3.1 Accessing Menus and Settingsp.48Viewing Datap.48Figure 32 iCOM user menu, Page 1 of 6p.48Figure 33 Accessing additional menu linesp.4810.3.2 Entering the Passwordp.4810.4 Changing Operational Settingsp.49Table 8 User menu iconsp.5010.5 Changing iCOM’s Display Settingsp.51Figure 34 Display setup screenp.5110.6 Changing the XDF’s Default Operating Temperaturep.5110.7 Operation With the Door Openp.5210.8 Backup Ventilation Systemp.53Figure 35 Airflow pattern, backup ventilation operationp.5310.9 XDF Compressorp.5310.10 Uninterruptible Power Supplyp.5311.0 Maintenancep.54Table 9 Troubleshootingp.5411.1 Periodic Maintenancep.5412.0 Specificationsp.55Figure 36 XDF model numbersp.55Table 10 Physical specificationsp.55Table 11 Electrical specificationsp.56Table 12 Total heat rejectionp.5612.1 Optional Power Systemsp.57Table 13 UPS performance datap.5712.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mountp.58Table 14 MP Advanced Power Strip specificationsp.58
Page 7 of the Emerson XDF user manual — I MPORTANT S AFETY I NSTRUCTIONS
Page 7 · click to enlarge
Page 7

I MPORTANT S AFETY I NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that must be closely followed during installation and maintenance of this unit to maintain compliance with agency listings. Read all safety and operating instructions before attempting to operate the XDF. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.

This product is designed for commercial / industrial use only. This product is not intended for use with life support or other U.S. FDA designated “critical” devices. Maximum loads must not exceed those shown on the Liebert XDF serial tag.

Operate this product in an indoor environment at an ambient temperature between 35°F and 104°F (1.6°C to 40°C). Install in a clean environment, free from moisture, flammable liquids, gases and cor- rosive substances.

This product must be connected to and powered by suitable AC supplies, rated in accordance with the unit’s serial tag. It must be suitably grounded and protected by circuit breakers or fuses.

Power extension cables, if used, must be rated for the load and must not exceed 20 ft. (6.1m) in length.

Liebert recommends using shielded cables for all external communication interfaces.

Ensure that the XDF has proper ventilation. Never block or insert objects into the ventilation holes or other openings. Maintain a minimum clearance of 36 in. (915mm) in front, behind, on the right side and above the self-contained, air cooled XDF for proper airflow and service. The water/glycol cooled XDF requires 36 in. (915mm) clearance in front, behind and on the right side. It does not require top clearance.

Page 8 of the Emerson XDF user manual — 1.0 G LOSSARY OF S YMBOLS
Page 8 · click to enlarge
Page 8

1.0 G LOSSARY OF S YMBOLS

Hazardous Voltage Present Note following instructions Consult user manual for additional information Indicates weight Indicates ground connection Indicates alternating current

Glossary of Symbols

Page 9 of the Emerson XDF user manual — 2.1 Operational Overview—Self-Contained, Air Cooled Model
Page 9 · click to enlarge
Page 9

2.0 P RODUCT D ESCRIPTION

Congratulations on purchasing a Liebert XDF. The XDF is an integrated equipment cabinet with built-in cooling and intelligent control to protect mission-critical enterprise systems from extreme heat. The XDF provides an organized, secure, controlled environment for your sensitive electronic equipment. The unit is available in a variety of configurations to suit your electronic equipment’s environmental requirements. The self-contained, air cooled Liebert XDF is intended for installation in open areas. Installation in closed-in areas, such as in a closet, alcove or similar space, requires field-supplied ducting, an exter- nal booster fan and sufficient makeup air. Contact your local Liebert representative before installing the XDF in an area that might inhibit heat dissipation. The water/glycol cooled unit, however may be installed in closed-in areas, subject to clearances of three feet in the front, rear and right side. See Figure 6. This is possible because heat rejected from the XDF cabinet is carried away in the coolant.

2.1 Operational Overview—Self-Contained, Air Cooled Model

The self-contained, air cooled XDF model employs a compressorized, direct expansion cooling system rated at 14kW to supply cooling air to rack-mounted equipment. A bank of fans circulates this cooling air through the electronic equipment in the XDF (see Figure 1). An evaporator coil extracts heat from the circulating air. That heat is transferred to a condenser at the top of the XDF and exhausted into the room. The XDF’s backup ventilation system operates automatically if power fails or if any XDF cooling sys- tem component fails.

Figure 1 Component location, general operational layout of self-contained, air cooled model

Condenser Coil transfers heat extracted from electronic equipment cabinet to incoming air

Emerson XDF — 2.1 Operational Overview—Self-Contained, Air Cooled Model diagram (page 9)
Fig. 2 · 2.1 Operational Overview—Self-Contained, Air Cooled…

Condenser Air Entry Point

Condenser Air Entry Point

Condenser Coil - 1 of 2

Evaporator Coil extracts heat from air circulated through the rack equipment compartment Rack-Mount Equipment Compartment (isolated from external air and top condenser section)

Backup Ventilation Air Intake

Evaporator Fans circulate cooling air

Product Description · Heated Air Exhaust · iCOM Controller

Page 10 of the Emerson XDF user manual — 2.2 Operational Overview - Water/Glycol Cooled Model
Page 10 · click to enlarge
Page 10

2.2 Operational Overview - Water/Glycol Cooled Model

The water/glycol cooled XDF model employs a single-stage cooling system rated at 14kW to supply cooling air to the rack-mounted equipment. A bank of fans circulates this cooling air through the elec- tronic equipment in the XDF (see Figure 1).

An evaporator coil extracts heat from the circulating air. That heat is transferred to a brazed plate condenser at the top of the XDF, transferred to the cooling water or glycol solution and is piped out of the unit.

Coolant is piped through the back of the XDF through supply and return pipes with 1" female NPT connections (refer to Figure 2 or Figure 6).

The XDF’s backup ventilation system operates automatically if power fails or if any XDF cooling sys- tem component fails.

If water is used as the coolant, Liebert recommends employing a closed system connected to an exter- nal condensing unit. A closed water supply system protects the XDF from particles and other contam- inants that might reduce cooling efficiency and damage the XDF.

Figure 2 Component location of water/glycol cooled model

Brazed Plate Condenser (behind grille)

Coolant Return - in rear

Emerson XDF — 2.2 Operational Overview - Water/Glycol Cooled Model diagram (page 10)
Fig. 3 · 2.2 Operational Overview - Water/Glycol Cooled Model

Coolant Supply - in rear

Evaporator Coil extracts heat from air circulated through the rack equipment compartment

Rack-Mount Equipment Compartment (isolated from external air)

Backup Ventilation Air Intake

Evaporator Fans circulate cooling air

Product Description · iCOM Controller

Page 11 of the Emerson XDF user manual — WATER/GLYCOL COOLED MODEL
Page 11 · click to enlarge
Page 11

Figure 3 Component location, rear of XDF

Condenser fan (removable to reduce height temporarily)

SELF-CONTAINED AIR COOLED MODEL

Emerson XDF — SELF-CONTAINED AIR COOLED MODEL diagram (page 11)
Fig. 4

Condenser air intakes, perforated grilles

Service access for gauges to be inserted for testing

Three-phase electrical cord, 10 feet (3m)

Single-phase electrical cord, 10 feet (3m)

Casters Stabilizing foot (one of four)

WATER/GLYCOL COOLED MODEL

Emerson XDF — WATER/GLYCOL COOLED MODEL diagram (page 11)
Fig. 5

Supply Line (1" female, NPT)

Service access for gauges to be inserted for testing

Three-phase electrical cord, 10 feet (3m)

Single-phase electrical cord, 10 feet (3m)

Show 10 more labels / short text on this page
Product Description · Door handle · Rear door · Condensate drain · Door handle · Rear door · Condensate drain · Stabilizing foot · (one of four) · Casters
Page 12 of the Emerson XDF user manual — Figure 4 Dimensional data, self-contained, air cooled model
Page 12 · click to enlarge
Page 12

Figure 4 Dimensional data, self-contained, air cooled model

Emerson XDF — Figure 4 Dimensional data, self-contained, air cooled model diagram (page 12)
Fig. 6 · Figure 4 Dimensional data, self-contained, air coole…

Single-Phase Power Cord Entrance; factory-supplied, 10' (3m) NEMA 5-15P

3-Phase Power Cord Entrance; factory-supplied, 10' (3m) NEMA L21-30P

Product Description

Page 13 of the Emerson XDF user manual — Figure 5 Dimensional data, water/glycol cooled model
Page 13 · click to enlarge
Page 13

Figure 5 Dimensional data, water/glycol cooled model

Emerson XDF — Figure 5 Dimensional data, water/glycol cooled model diagram (page 13)
Fig. 7 · Figure 5 Dimensional data, water/glycol cooled model

Single-Phase Power Cord Entrance; factory-supplied, 10' (3m) NEMA 5-15P

3-Phase Power Cord Entrance; factory-supplied, 10' (3m) NEMA L21-30P

Product Description

Page 14 of the Emerson XDF user manual — Figure 6 Dimensional data, all models-top, bottom and cable entry cutouts
Page 14 · click to enlarge
Page 14

Figure 6 Dimensional data, all models—top, bottom and cable entry cutouts

Emerson XDF — Figure 6 Dimensional data, all models-top, bottom and cable entry cutouts diagram (page 14)
Fig. 8 · Figure 6 Dimensional data, all models-top, bottom an…
Emerson XDF — Figure 6 Dimensional data, all models-top, bottom and cable entry cutouts diagram (page 14)
Fig. 9 · Figure 6 Dimensional data, all models-top, bottom an…

A - Rack-Mount Width

Self-contained, air cooled model shown; water cooled unit dimensions are identical; water cooled unit does not have condenser fan.

EIA Nominal19" (483mm) Inside Dimension: 17-13/16 (452) B - Adjustable Mounting Depth
Minimum24" (620mm) Maximum: 32-11/32 (821)

Product Description · Front

Page 15 of the Emerson XDF user manual — 3.1.4 Side Panels
Page 15 · click to enlarge
Page 15

3.0 XDF C OMPONENTS

3.1 Standard Components—Self-Contained, Air Cooled and Water/Glycol Cooled Models

3.1.1 Frame

The self-contained, air cooled XDF is 82-1/4 inches (2089mm) tall; the water/glycol cooled unit, 79-3/4 (2026) tall. The self-contained, air cooled XDF has 36U (63 inches) of usable rack height. The water/glycol cooled XDF has 42U (73-1/2 inches) of usable rack height. Both the self-contained, air cooled and water/glycol cooled XDF units have a standard EIA rack width of 19 inches (483mm).

The XDF frame consists of heavy-duty, riveted, 12-gauge steel. The unit has fixed front rails and adjustable rear rails with square holes for installing rack-mount equipment. The front and rear verti- cal frame members accommodate internal mounting rail options and provide space to route and man- age cabling.

Cutouts in the top (front and rear) permit customer cable entry (Figure 6). All units have casters, stabilizing feet and a grounding lug.

3.1.2 Enclosure

The XDF is equipped with seals to maintain a separate air volume inside the equipment compart- ment.

3.1.3 Doors

The front and rear doors are framed from sheet metal and are removable. A multi-point latch with key lock is provided for security. The front door may be either solid sheet metal or have a Plexiglas™ window for viewing installed equipment. The rear door is solid, full-height sheet metal.

3.1.4 Side Panels

Side panels are constructed of sheet metal and use special fasteners to permit removal for mainte- nance. Insulation is included to provide improved thermal and sound insulation, as well as to prevent condensate formation on the outside of the unit.

XDF Components

Page 16 of the Emerson XDF user manual — 3.1.5 Environmental Control
Page 16 · click to enlarge
Page 16

3.1.5 Environmental Control The XDF supplies cooling air—68°F to 77°F (20-25°C)—to electronic equipment in the rack-mount equipment compartment. In normal operation, six fans at the right front corner of the XDF circulate cooling air through the equipment compartment. The laterally circulating air absorbs heat generated by the electronic equip- ment and transfers the heat to an evaporator coil at the right rear of the XDF. The heat is removed differently in the self-contained, air cooled and water/glycol cooled units.

Heat Removal—Self-Contained, Air Cooled XDF Heat removed from the self-contained, air cooled XDF cabinet is transferred to condenser coils at the top of the XDF, in a section separated from the equipment compartment. The condenser fan on top of the self-contained, air cooled XDF draws ambient air through the condenser coils and exhausts the heat-laden air into the room.

Heat Removal—Water/Glycol Cooled XDF The water/glycol cooled XDF transfers the heat captured by the evaporator coil to a brazed plate con- denser at the top of the unit, also separate from the equipment compartment. That heat is then car- ried away by the cooling water or glycol to a condenser or drycooler.

Figure 7 Cooling system components—self-contained, air cooled models

Emerson XDF — 3.1.5 Environmental Control diagram (page 16)
Fig. 10 · 3.1.5 Environmental Control

Condenser Air Intake Vent for Normal Operation

Backup Ventilation Intake Vent (exhaust vent is on rear)

Evaporator Coil (behind damper) extracts heat from circulated air

Show 4 more labels / short text on this page
XDF Components · Condenser Fan · Condenser Coil · Rear Front
Page 17 of the Emerson XDF user manual — Figure 8 Cooling system components-water cooled models
Page 17 · click to enlarge
Page 17

Figure 8 Cooling system components—water cooled models

Emerson XDF — Figure 8 Cooling system components-water cooled models diagram (page 17)
Fig. 11 · Figure 8 Cooling system components-water cooled mode…

Backup Ventilation Intake Vent (exhaust vent is on rear)

Evaporator Coil (behind damper) extracts heat from cir- culated air

Show 5 more labels / short text on this page
XDF Components · Coolant Return Connection · Brazed Plate Condenser · Coolant Supply Connection · Rear Front
Page 18 of the Emerson XDF user manual — ESC
Page 18 · click to enlarge
Page 18

3.1.6 Control—Liebert’s iCOM Controller The XDF is equipped with Liebert’s iCOM controller for all programming functions on the XDF. The menu-driven, 128 x 64 dot matrix graphic display shows the status of the conditioned space, set- points, alarm status and settings, event histories and the time. Refer to 10.2 - iCOM Components and Functions and 10.3 - Navigating Through the iCOM Display for details or call 800-543-2778.

Figure 9 XDF with iCOM controller

Emerson XDF — 3.1.6 Control-Liebert’s iCOM Controller diagram (page 18)
Fig. 12 · 3.1.6 Control-Liebert’s iCOM Controller
Emerson XDF — 3.1.6 Control-Liebert’s iCOM Controller diagram (page 18)
Fig. 13 · 3.1.6 Control-Liebert’s iCOM Controller
Emerson XDF — 3.1.6 Control-Liebert’s iCOM Controller diagram (page 18)
Fig. 14 · 3.1.6 Control-Liebert’s iCOM Controller
Emerson XDF — 3.1.6 Control-Liebert’s iCOM Controller diagram (page 18)
Fig. 15 · 3.1.6 Control-Liebert’s iCOM Controller

ESC

XDF Components · ? · Liebert iCOM controller

Page 19 of the Emerson XDF user manual — 3.2.1 Closed-Loop Water System
Page 19 · click to enlarge
Page 19

3.2 Coolant Source—Water/Glycol Models

The XDF water/glycol cooled models may be connected to either of two types of coolant sources:

  • a closed-loop water system (cooling tower)
  • a drycooler loop

3.2.1 Closed-Loop Water System

A closed water supply system is required for efficiency and to protect the equipment from particles and other contaminants that might obstruct the system’s piping.

! CAUTION Risk of dirt and debris contamination. May cause condenser clogging.

Do not install the XDF on an open-loop water supply system. Debris carried by the fluid will clog the XDF’s brazed plate condenser.

Figure 10 Water/glycol XDF supplied by closed-loop water system

Emerson XDF — 3.2.1 Closed-Loop Water System diagram (page 19)
Fig. 16 · 3.2.1 Closed-Loop Water System
Emerson XDF — 3.2.1 Closed-Loop Water System diagram (page 19)
Fig. 17 · 3.2.1 Closed-Loop Water System
Emerson XDF — 3.2.1 Closed-Loop Water System diagram (page 19)
Fig. 18 · 3.2.1 Closed-Loop Water System
Show 7 more labels / short text on this page
XDF Components · Closed-Loop Water System · XDF Supply · Line · XDF Return · Hose Bibs · Line
Page 20 of the Emerson XDF user manual — 3.2.2 Drycooler Loop
Page 20 · click to enlarge
Page 20

3.2.2 Drycooler Loop

The water/glycol cooled XDF model requires an external supply of coolant, either water or glycol, to remove heat extracted from the XDF.

Contact the factory for drycooler requirements when connecting multiple XDF units. For information on setting up a drycooler system, contact your local Liebert representative.

Figure 11 Water/glycol cooled general arrangement with drycooler as coolant source

Emerson XDF — 3.2.2 Drycooler Loop diagram (page 20)
Fig. 19 · 3.2.2 Drycooler Loop
Emerson XDF — 3.2.2 Drycooler Loop diagram (page 20)
Fig. 20 · 3.2.2 Drycooler Loop
Emerson XDF — 3.2.2 Drycooler Loop diagram (page 20)
Fig. 21 · 3.2.2 Drycooler Loop

Expansion Tank (install at highest point in system)

Show 8 more labels / short text on this page
XDF Components · Supply · Line · Drycooler · Pump · XDF Water/Glycol · Return Line · Cooled
Page 21 of the Emerson XDF user manual — AC INPUT BATTERY UPS ON BYPASS
Page 21 · click to enlarge
Page 21

3.3 Optional Equipment

3.3.1 General Enclosure Options

  • Sealed entrance cable bundle
  • Cable tray
  • Cable Management Channels
  • Cable rings
  • Velcro cable management straps
  • Fixed shelves, vented, 250lb (113kg) capacity
  • Pullout shelves, vented, 130lb (59kg) capacity
  • Fixed rails, 150lb (68kg) capacity
  • Internal keyboard tray
  • Mounting clip nuts and screws 10-32 or M6 thread
  • Condensate Pump

3.3.2 Power Options

MP Advanced Power Strips and Controllers

Power distribution to equipment in your XDF may be eased with optional Liebert MP Advanced Power Strips. These power strips are available in single- and three-phase power options; some units offer remote monitoring and individual receptacle control. For details, see Table 14 - MP Advanced Power Strip specifications or refer to the MP Advanced Power Strip user manual, SL-28015.

MP Advanced Power Strips may be monitored and controlled with these Liebert units:

MP Advanced Access Servers—Monitors and controls up to 32 MP Advanced Power Strips. This unit permits control of the full strip or single outlets to reboot or turn equipment On or Off. It also sets parameters for alarms and status notifications. OpenComms EM——Monitors and controls up to two MP Advanced Power Strips. This unit per- mits control of the full strip or single outlets to reboot or turn equipment On or Off. It also sets parameters for alarms and status notifications.

Uninterruptible Power Supply

An Uninterruptible Power Supply (UPS) can provide your electronic equipment with surge protection and suppression, as well as voltage and frequency regulation, preventing damage to the hardware. A UPS provides time to perform a controlled shutdown of your operating system, allowing you to save valuable data. Liebert online, double-conversion UPS systems also condition utility power, eliminat- ing damaging power transients.

The following Liebert UPS models are available for installation in the XDF:

  • GXT2 - 500, 700, 1000, 1500, 2000, 2700 and 3000RT120
  • GXT2-6000RT208, GXT2-10000RT208
  • PS1000, 1440, 2200 and 3000RT2-120

Refer to the UPS user manual for further details.

Figure 12 Optional power equipment, examples

Emerson XDF — Uninterruptible Power Supply diagram (page 21)
Fig. 22 · Uninterruptible Power Supply
Emerson XDF — Uninterruptible Power Supply diagram (page 21)
Fig. 23 · Uninterruptible Power Supply

AC INPUT BATTERY UPS ON BYPASS

GXT2U UPS and Additional Battery Cabinet

GXT2-10000RT208 UPS and Additional Battery Cabinet

Show 6 more labels / short text on this page
XDF Components · On-Line UPS Systems · Line Interactive Systems · UPStation GXT · Liebert · + –
Page 22 of the Emerson XDF user manual — ! CAUTION
Page 22 · click to enlarge
Page 22

4.0 I NSTALLATION

4.1 Inspection

Upon arrival of the unit, and before unpacking it, verify that the delivered equipment matches the bill of lading. Examine the packaging for any signs of mishandling or damage. Inspect all items for dam- age, visible or concealed. Report any damage immediately to the carrier and file a damage claim. Send a copy to Liebert Corporation or to your sales representative.

Packing Material

All material used to package this unit is recyclable. Please save the material for future use or dispose of it appropriately.

4.2 Recommended Setup Equipment

  • pallet jack or forklift
  • utility knife
  • 3/8" ratchet or wrench

4.3 Unloading the XDF

! WARNING Risk of top-heavy unit falling over. Can cause death, injury and equipment damage.

Read all of the following instructions before attempting to move, lift or remove packaging from the unit.

! CAUTION Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.

Only trained personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift or remove packaging from the unit or prepare the unit for installation.

! CAUTION

Risk of overhead interference. Can damage the unit and structure.

The unit may be too tall to fit through a doorway while on the skid. Measure the unit and doorway heights and refer to the installation plans to verify clearances before moving the unit.

! CAUTION Risk of frozen fluids. Can cause equipment damage.

Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.

Installation

Page 23 of the Emerson XDF user manual — 4.3.1 Handling the Unit While It is Packaged
Page 23 · click to enlarge
Page 23

4.3.1 Handling the Unit While It is Packaged

  • If possible, transport the XDF using a forklift or pallet jack. Otherwise use a crane with belts or cables and spreader bars to protect the XDF’s sides from damage.
  • If using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest distance that fit under the skid. Also, ensure the fork length is suitable for the unit length.
  • When moving the packaged XDF, do not lift it any higher than 6" (152mm) off the ground. Exercise great care if the XDF must be lifted higher than 6" (152mm); any personnel not directly involved in lifting the XDF must be at least 20' (5m) from the unit.

Figure 13 Recommended unit handling equipment

Fork Lift Pallet Jack

4.3.2 Unpack the XDF 1. Remove the exterior stretch-wrap packaging material from around the XDF, exposing the protective corner and side packaging planks (see Figure 14). 2. Remove the corner and side packaging planks from the XDF, exposing the bag over the unit. The bag may remain in place to protect the XDF from dust and scratches or removed for immedi- ate unit installation. Ensure the metal ramps stay with the XDF for removal from the skid. 3. Remove the bag from the XDF when ready to remove the skid and install the unit.

Figure 14 Removing XDF packaging

Emerson XDF — 4.3.1 Handling the Unit While It is Packaged diagram (page 23)
Fig. 24 · 4.3.1 Handling the Unit While It is Packaged

Self-contained, air cooled unit shown; steps apply to all XDF units

Installation

Page 24 of the Emerson XDF user manual — 4.3.3 Removing the XDF from Skid
Page 24 · click to enlarge
Page 24

4.3.3 Removing the XDF from Skid

This unit is on casters—to prevent it from rolling, ensure that the skid is on a flat surface before removing the XDF from the skid.

1. Remove eight lag bolts from the unit tie-down brackets on the controls side of the unit. 2. Remove the four tie-down brackets from the controls side of the unit (see Figure 15). 3. Find the ramps that were shipped with the unit. 4. Insert the two tabs on each ramp into the holes on the skid. 5. Remove eight lag bolts from the unit tie-down brackets on the side opposite the controls. 6. Remove the four tie-down brackets from the side opposite the controls. Unit weight when empty is 710 lb (322kg). Weight may differ if optional equipment has been installed. Refer to the packing slip for the unit’s exact weight. 7. Remove the XDF by rolling it off of the ramp using an appropriate number of personnel and rigging based on the unit weight (see Figure 16).

Once off of the skid, the unit can be rolled to the installation site.

Figure 15 Remove lag bolts and brackets

Right front corner detail

(controls side of XDF)

Four (4) Lag Bolts and Two Brackets Per Corner

Installation

Page 25 of the Emerson XDF user manual — Figure 16 Roll XDF off the shipping skid
Page 25 · click to enlarge
Page 25

Figure 16 Roll XDF off the shipping skid

Emerson XDF — Figure 16 Roll XDF off the shipping skid diagram (page 25)
Fig. 25 · Figure 16 Roll XDF off the shipping skid

Fit tabs on ramps into holes on front of skid

Self-contained, air cooled unit shown; steps apply to all XDF units

... off the skid onto level surface and roll unit to installation location

Installation

Page 26 of the Emerson XDF user manual — 4.4 XDF Site Preparation
Page 26 · click to enlarge
Page 26

4.4 XDF Site Preparation

When deciding where to place your Liebert XDF, keep in mind these factors:

  • electricity is required to operate the compressor (208V-3ph-60Hz) and the controls and evaporator fans (120V-1ph-60Hz)
  • adequate ventilation and makeup air are necessary for proper equipment operation and protection
  • service clearance must be provided
  • the XDF must be on a level surface to ensure proper operation
  • condensate must be drained, either by gravity-fed drain or optional condensate pump
  • water/glycol cooled units require connection to a water or drycooler loop Liebert’s self-contained, air cooled XDF is intended for installation in open areas. Field-supplied ducting, an external booster fan and sufficient makeup air are required for installing a self-contained, air cooled model in closed-in areas, such as in a closet, alcove or similar space. Contact your local Liebert representative before installing the XDF in an area that might inhibit heat dissipation.

Note the dimensions of your XDF to determine the space required. The self-contained, air cooled XDF requires clearance of 36 in. (915mm) at the top, front, back and right side for equipment access and service (see Figure 17). The water/glycol XDF requires clearance of 36 in. (915mm) at the front, back and right side for equipment access and service; no top clearance is required.

Figure 17 XDF clearances

Emerson XDF — 4.4 XDF Site Preparation diagram (page 26)
Fig. 26 · 4.4 XDF Site Preparation

Self-Contained, Air Cooled model shown. Water/Glycol models do not require top clearance.

Installation

Page 27 of the Emerson XDF user manual — Changing Condenser Fan Power Source—Self-Contained, Air Cooled Units
Page 27 · click to enlarge
Page 27

4.5 Voltage Requirements

All XDF systems require two input power circuits. Each power cord is 10 feet (3m) long. For the full load amp requirements of each option, refer to 12.1 - Optional Power Systems or the component’s user manual.

4.5.1 Voltage Input Requirements

The first input connection provides power—120V-1ph-60Hz, line-to-neutral—to the controls, evapora- tor fans and condenser fan. This input’s power cord has a NEMA 5-15P plug. This power cord should be connected to a UPS-protected power source.

The second input connection on 60Hz XDF units provides power—208V-3ph-60Hz, with neutral—to the compressor, optional condensate pump and an alternate connection for the condenser fan. (The alternate connection for the condenser fan permits reducing the load on the UPS-protected power source.) The 208V power cord has a NEMA L21-30P locking plug.

Changing Condenser Fan Power Source—Self-Contained, Air Cooled Units

! WARNING Risk of electric shock. Can cause death or injury.

Disconnect all local and remote electric power before working within and/or installing equipment.

To change the power source connections:

1. Open the front door panel and look for two screws with Torx heads that secure the hinged corner panel. The Torx-head screws are on the front doorjamb. 2. Extract the two screws and swing the panel open. 3. Remove the protective covering over the electrical connections (see Figure 18). The cover is secured with two screws. 4. Find the connectors (see Figure 18) and pull apart the snap connection made at the factory. 5. Connect the alternate power source connector to the supply that feeds the condenser fan. 6. Reinstall the protective cover over the electrical connections. 7. Close the outer panel and reinsert the two Torx screws. 8. Close the front door.

Figure 18 Alternate condenser fan power connection

Emerson XDF — Changing Condenser Fan Power Source—Self-Contained, Air Cooled Units diagram (page 27)
Fig. 27 · Changing Condenser Fan Power Source—Self-Contained,…

Power supply to condenser fan

Emerson XDF — Changing Condenser Fan Power Source—Self-Contained, Air Cooled Units diagram (page 27)
Fig. 28 · Changing Condenser Fan Power Source—Self-Contained,…

Default circuit connector (connection made at factory)

Protective cover over high voltage electrical connections

Alternate circuit connector to condenser fan

Installation

Page 28 of the Emerson XDF user manual — 4.6 Drycooler Installation—Water/Glycol Cooled Model
Page 28 · click to enlarge
Page 28

4.5.2 Uninterruptible Power Supply—Optional

If your XDF is equipped with a UPS, it will require connection to a dedicated electrical circuit. Review the UPS’s user manual before connecting utility power to the unit.

4.5.3 MP Advanced Power Strips—Optional

MP Advanced Power Strips are available in several power ranges. Consult Table 14 in 12.0 - Specifi- cations or the MP Advanced Power Strip user manual, SL-28015, for your model’s power require- ments.

4.5.4 Condensate Drain Connection

The XDF cooling process removes humidity from the air inside the cabinet. The moisture is collected in a pan and must be removed from the cabinet. The condensate may be fed into a gravity drain or pumped away with an optional, factory-installed condensate pump.

The gravity-fed drain line must be pitched a minimum of 1/8" per foot (11mm per meter).

Table 1 Optional condensate pump performance

60Hz 18 (5.49)

50Hz 14 (4.27)

The standard XDF condensate drain is a 1/2" NPT female pipe connector. A factory-supplied adapter permits connecting a 3/4" hose, the same size as a standard garden hose. The adapter is shipped with the cabinet (see Figure 19).

Figure 19 Condensate drain connection and adapter

Emerson XDF — 4.5.4 Condensate Drain Connection diagram (page 28)
Fig. 29 · 4.5.4 Condensate Drain Connection

Condensate Drain Connection 1/2” NPT female connector or 3/4” garden hose with adapter (as shipped)

Bottom Right Rear Corner of XDF

4.6 Drycooler Installation—Water/Glycol Cooled Model

For details on installing the drycooler, contact your local Liebert representative.

Show 4 more labels / short text on this page
Installation · Maximum Head, · Model · feet (m)
Page 29 of the Emerson XDF user manual — 4.7 Equipment Layout
Page 29 · click to enlarge
Page 29

4.7 Equipment Layout

! WARNING Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power before working within and/or installing equipment. Before installing or rearranging equipment, ensure the equipment and the UPS are switched off. Ensure that all electrical sources are disconnected.

The lateral, circular flow of cooling air permits arranging equipment as required for stability if the XDF is filled or nearly filled with equipment. Install heavier equipment first, placing it in the lower racks of the XDF. This keeps the XDF from having a high center of gravity, which could make it eas- ier to tip over (see Figure 20). The XDF may be filled to capacity as long as the maximum heat load of 14kW is not exceeded. If the XDF will not be filled with equipment, the equipment should be installed with a 1U space above and below each unit. Again, install heavier equipment first, placing it in the bottom racks. After all equipment has been installed, any remaining spaces larger than 5U at the top of the XDF should be closed with optional blanking panels. (Panels are available in 1U, 2U, 3U, 4U, 5U and 10U.) This arrangement prevents large, open expanses in the equipment compartment that would reduce cooling efficiency by channeling airflow around the electronic gear. Figure 20 Recommended equipment arrangement

Emerson XDF — 4.7 Equipment Layout diagram (page 29)
Fig. 30 · 4.7 Equipment Layout

Blanking Panels in empty spaces larger than 5U

Large expanses channel airflow around equipment

Equipment spaced 1U apart

RECOMMENDED SPACING Regular spacing of equipment 1U apart and blanking panels enhance cooling air distribution. Heavier equipment at bottom promotes stability

INEFFICIENT SPACING Irregular equipment spacing prevents proper airflow for cooling. Heavier equipment too high for best stability

! CAUTION Risk of top-heavy unit falling over. Can cause death, injury and equipment damage. Read all of the following instructions before attempting to move, lift or remove packaging from the unit.

Installation

Page 30 of the Emerson XDF user manual — 4.9 Mounting Hardware
Page 30 · click to enlarge
Page 30

4.8 Frame and Enclosure Configurations

4.8.1 Internal Mounting Rails

The XDF can accommodate rack-mounted or free-standing computer and network equipment. The unit features 19-inch (483mm) rear-mount rack rails. These internal mounting rails are designed in accordance with the EIA 310D rack standard. The rails are adjustable for equipment of different sizes.

Liebert offers these optional mounting hardware kits: fixed shelf, fixed rails, pullout shelf, 19-inch (483mm) rack rail adapters and keyboard trays. Each kit includes installation hardware.

4.8.2 Rear-Mount Rails—Position

Emerson XDF — 4.8.2 Rear-Mount Rails—Position diagram (page 30)
Fig. 31 · 4.8.2 Rear-Mount Rails—Position

The XDF’s front rails are fixed into position, while rear-mount rails are secured by carriage bolts that pass through horizontal slots in the frame. These slots permit you to change the front-to-rear distance between the rails as your application requires.

To position the rails:

1. Determine the proper location of the rails. 2. Loosen the bolts securing a rail to the frame. 3. Move the rail to the desired position (be sure to get the rail square). 4. Tighten the bolts securing the rails to the frame. 5. Repeat for the other rail. 6. Install your rack-mounted equipment or the shelves to hold your freestanding equipment.

4.9 Mounting Hardware

Optional mounting clip nuts and screws are available for mounting equipment to the mounting rails. Clip nuts are metal clips with captive nuts that fit over vertical rack rail holes, allowing individual placement of the mounting hard- ware. Each clip nut and screw package includes 10 clip nuts (Type 10/32 or M6 threads) and screws.

Installation

Page 31 of the Emerson XDF user manual — 4.11.1 Remove the Left Panel
Page 31 · click to enlarge
Page 31

4.10 Door—Remove

The XDF’s doors are removable for convenience when installing equipment.

4.10.1 Remove the Door 1. Remove the bolts securing the lower half of each two-piece hinge to the door. 2. Remove the lower half of each hinge. 3. Lift the door straight up until the pins clear the hinges. 4. Set the door in a safe place.

4.10.2 Quick Door Removal

Remove this bolt first

For minimum-security installations that also require frequent and fast removal of the door, the lower half of the hinge assembly may be perma- nently removed. This allows for quick removal of an open door by lifting the door straight up until the pins clear the hinge mount.

4.11 Side Panels—Remove and Replace

XDF side panels are simple to remove and replace, making it easier to install equipment and to ser- vice the XDF. Panel removal also improves access for equipment maintenance and replacement.

4.11.1 Remove the Left Panel

! WARNING Risk of electric shock. Can cause injury or death.

Disconnect all local and remote electric power before working within and/or installing equipment.

To remove the left panel from the XDF:

1. The left panel is secured with two internal security quarter-turn fasteners and four panel retainers. Open the doors and locate the internal security quarter-turn fasteners on the left side panel. The security fasteners are at the top front and top rear corners of the panel. 2. Using the factory-supplied T-handle Allen wrench, turn the internal security fasteners counterclockwise 90 degrees. 3. Locate the four panel retainers on the outside of the left XDF panel. One retainer is in each corner of the panel. 4. Using the factory-supplied T-handle Allen wrench, turn the panel retainers counterclockwise 90 degrees.

! CAUTION Risk of heavy panel falling off. Can cause injury and/or equipment damage.

Support the panel when removing it. Unlocking the security fasteners and removing the panel retainers will allow unsupported panel to fall.

5. Lift the panel off the lip at the bottom of the XDF and set it in a safe location.

Installation

Page 32 of the Emerson XDF user manual — 4.11.2 Remove the Right Panel
Page 32 · click to enlarge
Page 32

4.11.2 Remove the Right Panel

! WARNING Risk of electric shock. Can cause injury or death.

Disconnect all local and remote electric power before working within and/or installing equipment.

To remove the right panel from the XDF:

1. Locate the four panel retainers on the outside of the right XDF panel. One retainer is in each corner of the panel. 2. Using the factory-supplied T-handle Allen wrench, turn the panel retainers counterclockwise 90 degrees.

! CAUTION Risk of heavy panel falling off. Can cause injury and/or equipment damage.

Support the panel when removing it. Unlocking the security fasteners and removing the panel retainers will allow unsupported panel to fall.

3. Lift the panel off the lip at the bottom of the XDF and set it in a safe location.

4.11.3 Replace a Panel 1. Set the panel on the lip at the bottom of the XDF frame. 2. Using the factory-supplied T-handle Allen wrench, turn each of the four panel retainers clockwise 90 degrees. 3. Left panel only: Using the factory-supplied T-handle Allen wrench, turn the internal security fasteners clockwise 90 degrees.

Installation

Page 33 of the Emerson XDF user manual — EWT
Page 33 · click to enlarge
Page 33

Piping Considerations—Water/Glycol Models Only

5.0 PIPING CONSIDERATIONS—WATER/GLYCOL MODELS ONLY

The XDF’s supply and return fittings are on the upper portion of the rear of the unit (see Figure 6). The 1-1/8" diameter pipes have one-inch female NPT fittings. The pipes are capped at the factory. Pip- ing connections to the XDF should be done by qualified personnel. All work must be done in compli- ance with all national and local regulations.

5.1 General

Equipment damage and personal injury can result from improper piping installation, leak checking, fluid chemistry and fluid maintenance.

  • Follow local piping codes, safety codes and Liebert unit installation and maintenance instructions.
  • Qualified personnel must install and inspect system piping.
  • Contact a local water consultant regarding water quality, corrosion protection and freeze protection requirements.

! CAUTION Risk of dirt and debris contamination. May cause condenser clogging.

Do not install the XDF on an open-loop water supply system. Debris carried by the fluid will clog the XDF’s brazed plate condenser.

! CAUTION Risk of piping stress. Can cause leaks and equipment damage.

To help prevent piping failures, supply and return lines must be supported so that their weight does not bear on the XDF’s piping, on the drycooler or on the pumps.

5.2 Closed Loop Water System

Where water will be used as a coolant medium, Liebert recommends use of a closed-loop water system with a cooling tower or similar heat dissipation method. For flow rates for the XDF water/glycol unit, see Table 2.

Table 2 Water supply flow rates

Entering Water Temp.

Saturated Cond. Temp.

EWT

SCT

65°F (18°C) 105°F (41°C) 15.0 (.95) 4.6 (13.8)

75°F (24°C) 105°F (41°C) 15.0 (.95) 4.6 (13.8)

85°F (29°C) 110°F (43°C) 15.0 (.95) 4.6 (13.8)

Table assumes 95°F ambient, 77°F discharge air, 10°F temperature rise on the heat transfer media.

Show 4 more labels / short text on this page
Flow Rate · Pressure Drop · GPM (l/s) · ft (kPa)
Page 34 of the Emerson XDF user manual — 5.2.3 Freeze Protection—Coolant Type and Insulation
Page 34 · click to enlarge
Page 34

Piping Considerations—Water/Glycol Models Only

5.2.1 Expansion Tanks, Fluid Relief Valves and Other Devices

An expansion tank must be provided for expansion and contraction of the fluid due to temperature change in this closed system. Vents are required at system high points to vent trapped air when fill- ing the system. A relief valve is also necessary.

Depending on the complexity of the system, various other devices may be specified. Pressure gauges, flow switches, automatic air separator, tempering valves, standby pumps, sensors for electrical con- trols and flow switches are just a few of these devices.

Manual shutoff valves should be installed on the supply and return lines. In addition, multiple pump packages require a check valve at the discharge of each pump to prevent back-flow through the standby pump(s). These check valves permit isolating units for routine maintenance or in an emer- gency.

Liebert also recommends installing these items in the system:

  • cleanable, 60 mesh filters—These filters will trap the particles in the coolant supply line and extend the service life of the water cooled condenser.
  • floor drains with wet traps or a leak-detection system, such as Liebert’s Liqui-tect
  • hose bibs at the lowest point of the system to facilitate filling
  • relief valve—to protect against burst water pipes

5.2.2 Corrosion Protection

Read and follow individual unit installation instructions for precautions regarding fluid system design, material selection and use of field-provided devices. Liebert systems contain iron and copper alloys that require appropriate corrosion protection.

Contact a local water consultant regarding water quality, corrosion and freeze protection require- ments. Water chemistry varies greatly by location, as do the required additives, called inhibitors that reduce the corrosive effect of the fluids on the piping systems and components. The chemistry of the water used must be considered because water may contain corrosive elements that reduce the effec- tiveness of the inhibited formulation.

Surface waters that are classified as soft and are low in chloride and sulfate ion content (less than 100 parts per million each) should be used. Proper inhibitor maintenance must be performed to prevent corrosion of the system. Consult glycol manufacturer for testing and maintenance of inhibitors.

Commercial ethylene glycol, when pure, is generally less corrosive to the common metals of construc- tion than water itself. It will, however, assume the corrosivity of the water from which it is prepared and may become increasingly corrosive with use if not properly mixed with corrosion inhibitors. For further details on corrosion prevention, see 5.3.1 - Glycol Solutions.

Idle fluid allows the collection of sediment and that prevents the formation of a protective oxide layer on the inside of tubes. Keep the unit switched On and the system pump operating.

5.2.3 Freeze Protection—Coolant Type and Insulation

Glycol solutions should be considered for use as a coolant to protect the coil against freezing and cor- rosion from water.

! CAUTION Risk of frozen fluid. Can cause piping rupture and equipment damage.

When the field piping or unit can be exposed to freezing temperatures, charge the system with the proper percentage of glycol and water for the coldest design ambient to prevent freezing.

! CAUTION Risk of frozen fluid. Can cause piping rupture and equipment damage.

Immediately after using water for leak testing or system cleaning, charge the tested system with the proper percentage of glycol and water for your coldest design ambient. Complete system drain-down cannot be ensured and damage to the system could result from freezing of residual water.

The minimum coolant temperature to be supplied to the XDF will determine whether the supply and return lines require insulation to prevent condensation.

Page 35 of the Emerson XDF user manual — °F (°C)
Page 35 · click to enlarge
Page 35

Piping Considerations—Water/Glycol Models Only

5.3 Drycooler Loop System

5.3.1 Glycol Solutions

The percentage of glycol to water must be determined by using the lowest design outdoor temperature in which the system is operating. Table 3 indicates the solution freeze point at several concentration levels of ethylene glycol. Propylene glycol concentrations should be 1% higher than the ethylene glycol table val- ues to find the freeze point. For example, 41% propylene glycol freezes at -10°F (-12°C).

Table 3 Ethylene glycol concentrations

% Glycol by Volume 0 * 10 20 30 40 50 Freezing Point °F (°C) 32 (0) 25 (-3.9) 16 (-8.9) 5 (-15.0) -10 (-23.3) -32 (-35.5) Apparent Specific Gravity @ 50°F (10°C) 1 1.014 1.028 1.042 1.057 1.071

* A minimal amount of glycol should be considered for inhibitive coil protection.

The user must determine whether the planned use of glycol complies with national, state and local regulations.

! CAUTION Risk of material reaction. Can cause piping damage.

Galvanized pipe must not be used in or with systems or units that contain glycol. Phosphates in the inhibitor can react with zinc in the galvanized pipe, precipitating an insoluble material that can foul the system.

NOTE When mishandled, glycol products pose a threat to the environment. Before using any glycol products, review the latest Material Safety Data Sheets and ensure that you can use the product safely. For Material Safety Data Sheets and other product safety information, contact the nearest supplier. Glycol manufacturers request that the customer read, understand and comply with the information on the product packaging and in the current Material Safety Data Sheets. Make this information available to anyone responsible for operation, maintenance and repair of the drycooler and related equipment.

Typical inhibited formula ethylene glycol and propylene glycol manufacturers and suppliers are Union Carbide (Ucartherm) or Dow Chemical (Dowtherm SR-1, Dowfrost). These glycols are supplied with corrosion inhibitors and do not contain a silicone anti-leak formula. Do not use glycols with sili- cone anti-leak additives because they reduce cooling performance. Commercial ethylene glycol, when pure, is generally less corrosive to the common metals of construction than water itself. Aqueous solu- tions of these glycols, however, assume the corrosivity of the water from which they are prepared and may become increasingly corrosive with use if not mixed with corrosion inhibitors.

Table 4 Glycol supply flow rates

Saturated Cond. Temperature (SCT)

Ethylene (40%) 115°F (46°C) 135°F (57°C) 15.0 (.95) 11.6 (34.6) Propylene (40%) 115°F (46°C) 135°F (57°C) 15.0 (.95) 18.5 (55.4)

Table assumes 95°F ambient, 77°F discharge air, 10°F temperature rise on the heat transfer media. Table 5 Drycooler selection

High Head Pump Model

1-Phase (57 ft @ 15GPM)

3-Phase (70 ft @ 15GPM)

°F (°C)

HP

95 (35.0) D** 092A 3/4 P13-0030 P02-0340

105 (40.6) D** 174A 3/4 P13-0030 P02-0340

110 (43.3) D** 225A 16 3/4 P13-0030 P02-0340

Show 12 more labels / short text on this page
Entering Coolant · Flow Rate · Pressure Drop · Glycol Type · Temperature · GPM (l/s) · ft (kPa) · Ambient Temperature, · Standard Pump Model · Drycooler · Glycol Pump · Model
Page 36 of the Emerson XDF user manual — 6.1.1 XDF Water/Glycol Cooled Unit Volume
Page 36 · click to enlarge
Page 36

Filling the XDF with Coolant—Water or Glycol

6.0 FILLING THE XDF WITH COOLANT—WATER OR GLYCOL

6.1 Preparing the System for Filling

It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping in order to prevent contamination of the coolant and fouling of the drycooler piping (IF USED). The system should be flushed thoroughly using a mild cleaning solution or high-quality water and then completely drained before charging with coolant.

Cleaning new systems is just as important as cleaning old ones. New systems might be coated with oil or a protective film; dirt and scale are also common. Any residual contaminants could adversely affect the heat transfer stability and performance of your system. In many cases, in both old and new sys- tems, special cleaners are needed to remove scale, rust and hydrocarbon foulants from pipes, mani- folds and passages. Clean heat transfer surfaces are important in maintaining the integrity of the cooling system. For more information on cleaners and degreasers, contact your sales representative.

Calculate the internal volume of the system as closely as possible. See Table 6 and Table 3 for unit volumes. Use volume in Table 6 for glycol piping volumes.

6.1.1 XDF Water/Glycol Cooled Unit Volume

The water/glycol cooled XDF’s coolant capacity is 0.56 of a gallon (2.1 liters). In closed systems, addi- tional coolant will be required for the piping. Refer to Table 6 for required amounts for various piping sizes.

Table 6 Volume in standard Type “L” copper piping

Diameter (in.) Volume

Outside Inside Gal/Ft L/M

1/2 0.123 0.008 0.01

5/8 0.555 0.012 0.15

3/4 0.666 0.018 0.22

7/8 0.785 0.025 0.31

1-1/8 1.025 0.043 0.53

6.1.2 Filling the System with Water or Glycol When filling the XDF with either water or glycol, keep air to a minimum. Air in glycol turns to foam and is difficult and time-consuming to remove. (Anti-foam additives are available and may be consid- ered.) 1. Open all operating systems to the loop. 2. With the top vent(s) open, fill the system from the bottom of the loop. This will allow the coolant to push the air out of the top of the system, minimizing trapped air. 3. Fill to approximately 80% of calculated capacity. Fill slowly from this point, checking fluid levels until the system is full.

Page 37 of the Emerson XDF user manual — 7.0 E LECTRICAL C ONNECTIONS
Page 37 · click to enlarge
Page 37

7.0 E LECTRICAL C ONNECTIONS

Power is supplied to the XDF through two factory-connected power cords (120V and 208V). For more information, refer to 4.5.1 - Voltage Input Requirements

Additional electrical connections required for operation depend on the equipment installed in the XDF and remote communications desired.

The XDF has slots for two communication cards, such as Liebert’s Intellislot card, and two alarm/warning hardwire connections. These connections are at the top left corner of the self-con- tained, air cooled XDF, inside the area housing the condenser coil (see Figure 21). For details, see 10.1 - Environmental Control. Water cooled XDF units have the connections on the top of the unit, near the middle of the compartment (see Figure 22).

Alarm and warning contacts may be connected to monitoring equipment, such as Liebert’s Universal Monitor and SiteLink equipment, as well as to building management systems. Consult the monitor- ing equipment’s user manual for details.

Figure 21 Customer electrical connections and cable entry points—self-contained, air cooled units

Emerson XDF — 7.0 E LECTRICAL C ONNECTIONS diagram (page 37)
Fig. 32

Customer Connections: 75 & 76 Customer Alarm Contacts 94 & 95 Customer Warning Contacts 37 & 38 Remote Shutdown Contacts (all contacts rated 1A, 24VAC maximum)

Communication Card Slots (cards provided when option is selected)

Move plate to back panel for alternate power cable routing

Dashed line delineates equipment compartment

Electrical Connections

Page 38 of the Emerson XDF user manual — Figure 22 Customer electrical connections and cable entry points-water/glycol cooled units
Page 38 · click to enlarge
Page 38

Figure 22 Customer electrical connections and cable entry points—water/glycol cooled units

Emerson XDF — Figure 22 Customer electrical connections and cable entry points-water/glycol cooled units diagram (page 38)
Fig. 33 · Figure 22 Customer electrical connections and cable…

Customer Connections: 37 & 38 Remote Shutdown Contacts 75 & 76 Customer Alarm Contacts 94 & 95 Customer Warning Contacts

(Contacts listed from top to bottom; All contacts rated 1A, 24VAC maximum)

Communication Card Slots (cards provided when option is selected)

Move plate to back panel for alternate power cord routing (see also Figure 23)

Power connection locations (refer to Figure 21 for details)

Electrical Connections

Page 39 of the Emerson XDF user manual — 7.1.1 Route Input Power Cables Through the XDF’s Top
Page 39 · click to enlarge
Page 39

7.1 Utility Power Supply

The XDF’s 120V and 208V input power cords are stored for shipment in a compartment at the bottom left of the rear of the XDF. The 10 feet (3m) cords may be routed to power outlets on the floor or wall.

If the power connections are overhead, the cables may be routed inside the unit and out the top. Lie- bert recommends pulling the cables across the floor of the rack-mounted equipment compartment and up the right rear side. This permits securing cables to the cable management cutouts along the inside of the XDF.

! WARNING Before beginning any work inside the XDF, disconnect all power inputs to the XDF and installed equipment.

7.1.1 Route Input Power Cables Through the XDF’s Top

To route the factory-supplied input power cables inside the unit and out the top:

1. Open the rear door, revealing the back of the rack-mount equipment compartment. 2. Remove the six Phillips screws securing the small metal plate at the bottom left (inside the rack- mount equipment compartment; see Figures 21 and 23). 3. Remove the cable entry snap bushing at the top right side of the rack-mount equipment compartment to access the condenser coil compartment. 4. Remove the cable entry snap bushing from the top of the XDF. 5. Attach an optional cable bundle to the top of the panel that separates the rack-mount equipment compartment from the condenser compartment. 6. Feed the input power cords through the opening at the bottom of the XDF and route them through the optional cable bundle and out the top (see Figure 23). 7. Secure the cable bundle seal around the input power cords. 8. Secure the input power cables to the side of the XDF with optional Velcro ties or cable rings. 9. Install the small plate removed in Step 2 on the back of the XDF just above the condensate drain (see Figure 23). 10. Connect the input power cables to appropriate utility supplies.

Figure 23 Route input power cords through XDF top

Emerson XDF — 7.1.1 Route Input Power Cables Through the XDF’s Top diagram (page 39)
Fig. 34 · 7.1.1 Route Input Power Cables Through the XDF’s Top
Emerson XDF — 7.1.1 Route Input Power Cables Through the XDF’s Top diagram (page 39)
Fig. 35 · 7.1.1 Route Input Power Cables Through the XDF’s Top

Attach optional cable bundle to upper side of cable entry cutout

Secure input power cables to side panel

Route input power cables across bottom of XDF to right rear side Plate moved from inside rack-mount equipment area

Electrical Connections

Page 40 of the Emerson XDF user manual — 8.2 Cable Management
Page 40 · click to enlarge
Page 40

8.0 C ABLE M ANAGEMENT O PTIONS

The XDF is able to host many of the components of the Foundation cable management products. These optional items deliver a flexible solution to rack-enclosure cable problems by utilizing a patent pending platform to provide adaptive equipment and cabling support. Cable and equipment mounting options are available to meet changing requirements.

8.1 Cable Management Considerations

When designing the equipment layout in the XDF, consider how cables must be run for each configu- ration and how cable runs affect cooling, access and operational factors. Separate power and commu- nication cables to reduce electromagnetic interference. Good cable management contributes to:

  • Effective airflow for cooling
  • Easier cable identification
  • Improved access
  • Reduced electromagnetic interference
  • Proper bend radii, particularly for fiber optic cables
  • Adequate support for large cables and heavy cable bundles Several Foundation options are designed to facilitate structured cable management. These are described in 8.4 - Optional Cable Management Channel .

8.2 Cable Management

Once your equipment has been installed, you are ready to connect cables for power and communica- tion. Before making any connections, check the equipment to ensure that all power switches are in the OFF position. Numerous cable entrances and management provisions are built into the XDF to ease cable installa- tion. Optional cable rings and Velcro straps, along with some components for routing cables, can be used with the XDF. These help not only to keep your cables organized but also separate power and commu- nications cables, reducing electromagnetic interference. A wide area is provided on the left rear side of the frame to mount cable rings, Velcro straps and cable trays. This location contributes to cooling effi- ciency by keeping equipment cables out of the cooling air pattern (see Figure 26).

Figure 24 Cable rings, Velcro straps on XDF rails

Emerson XDF — 8.2 Cable Management diagram (page 40)
Fig. 36 · 8.2 Cable Management

Cable Rings Mounted on Rail

Emerson XDF — 8.2 Cable Management diagram (page 40)
Fig. 37 · 8.2 Cable Management

Rear Strap Optional Velcro Strap Positioning on Rails Front

Cable Management Options · Front Strap · or Rear

Page 41 of the Emerson XDF user manual — 8.4 Optional Cable Management Channel
Page 41 · click to enlarge
Page 41

8.3 Cable Access

8.3.1 Top Cover and Back

Optional sealed entrance cable bundles (cone-shaped seals and clamps) permit use of the round openings on the top of the XDF for cable entry.

Emerson XDF — 8.3 Cable Access diagram (page 41)
Fig. 38 · 8.3 Cable Access

To bring cable through these holes:

1. Replace the plug with a sealed entrance cable bundle. 2. Pull the cable through the bundle. 3. The cable bundle can be trimmed to accommodate various quantities of cables. 4. Use the clamp to secure the bundle around the cables.

8.4 Optional Cable Management Channel

The optional Foundation Cable Management Channel (CMC) combines with other optional items to permit the user to route cables in an organized, efficient manner.

CMCs are available in 1U, 2U and 3U sizes and are adjustable for side-to-side or front-to-rear orienta- tions.

Refer to Figures 26 and 27 for various cable management configurations and options.

Figure 25 Cable Management Channel lengths

Emerson XDF — 8.4 Optional Cable Management Channel diagram (page 41)
Fig. 39 · 8.4 Optional Cable Management Channel

Cable Management Channel bracket on back side of panel (both ends)

23" (584mm) CMC Panel Typical - Flanges facing toward you

CMC Panel Typical - Flanges facing toward you. Long tabs of CMC brackets

CMC brackets can be inverted, with the flanges facing away, for an open-end channel.

Cable Management Options · Sealed Entrance · Cable Bundle

Page 42 of the Emerson XDF user manual — Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spools
Page 42 · click to enlarge
Page 42

Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spools

Emerson XDF — Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spools diagram (page 42)
Fig. 40 · Figure 26 Cable management mounting locations and op…
Emerson XDF — Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spools diagram (page 42)
Fig. 41 · Figure 26 Cable management mounting locations and op…

Cable Management Option Mounting Areas (inside rails and frame)

Figure 27 Cable management accessoriesCable Tray
Emerson XDF — Figure 26 Cable management mounting locations and options: Velcro cable straps, Cable Spools diagram (page 42)
Fig. 42 · Figure 26 Cable management mounting locations and op…

Cable Management Options

Page 43 of the Emerson XDF user manual — 9.1 XDF Startup Inspection Checklist
Page 43 · click to enlarge
Page 43

9.0 S TARTUP

Before plugging in your electronic equipment, make sure that all power switches are in the OFF posi- tion.

  • Be certain there are no obstructions, wire bundles, manuals, trash, etc., in front of or on either side of the XDF. Make sure all doors are shut and sealed properly.
  • Plug the XDF’s 120V power cord into a dedicated utility circuit.
  • Plug the XDF’s 208V power cord into a dedicated utility circuit.

9.1 XDF Startup Inspection Checklist

9.1.1 Site Conditions

___ 1. Confirm at least 36 in. (915mm) clearance in front of the XDF, on the right side and behind the unit. No left-side clearance required.

___ 2. Confirm at least 36 in. (915mm) clearance above the unit (self-contained, air cooled units only; water/glycol units do not require clearance above).

___ 3. Confirm site ventilation provisions: ___ Sufficient ambient space to dissipate heat rejected by the XDF (self-contained, air cooled units) Ambient temperature range is 35°F to 104°F (1.6 to 40°C).

___ 4. Ensure that the XDF is level.

___ 5. Confirm condensate drain tube is connected to a drain and will drain properly.

___ 6. Secure all electrical connections inside the XDF.

___ 7. Confirm that the dedicated circuits for the XDF’s compressor and fans are separate from the circuit for the UPS (not same duplex) XDF requires a 120V/60Hz/15A, single-phase, 2-wire plus ground circuit Record the fan working input voltage 120VAC (±10%): XDF requires a 208V/60Hz/30A, three-phase, 4-wire plus ground circuit Record the compressor working input voltage 208VAC (±10%): Check UPS (if provided) nameplate for input electrical requirements.

___ 8. Examine the positioning of equipment inside the cabinet Prevent short cycling of airflow - no spaces larger than 1U between electronic devices Spaces larger than 5U at top of rack are covered with blanking panels Heaviest equipment installed near the bottom of the cabinet.

___ 9. Check cabinet seals—No gaps, loose cables, air leaks: ___ Door gaskets intact / free of damage. Close front and rear doors and confirm no visible seal violations Side panels and the frame have uniform sealing Cable entrance points are sealed.

___ 10. Determine whether the UPS, if one is installed in the XDF, has fully charged batteries.

To charge the UPS batteries before using the unit, you can apply power to the UPS module while installing equipment or making adjustments.

Refer to the UPS manual for preparation for startup, details of UPS operation and the meaning of LED indicators.

Startup

Page 44 of the Emerson XDF user manual — ESC
Page 44 · click to enlarge
Page 44

9.2 Starting the XDF

The XDF is started, stopped and controlled with Liebert’s iCOM controller. Figure 28 shows the iCOM keypad.

Figure 28 iCOM controller keys

?

Left Arrow Key Right Arrow Key Enter Key

ESC

Escape Key Down Arrow Key

To start the XDF:

1. Press the On/Off key on the iCOM controller. 2. Confirm internal airflow: Inside enclosure, (evaporator fan discharge). 3. Confirm cooling air begins circulating. 4. Power up the UPS (if provided). 5. Close the XDF’s doors, if open.
Show 5 more labels / short text on this page
Startup · Alarm Key · Up Arrow Key · On/Off Key · Help Key
Page 45 of the Emerson XDF user manual — 10.2 iCOM Components and Functions
Page 45 · click to enlarge
Page 45

10.0 O PERATION

The XDF is intended for operation with its doors closed and latched. This increases efficiency and keeps out dust and humidity.

With the doors closed, the XDF will achieve full capacity in ambient conditions up to 95°F (35°C) and 40 percent relative humidity. The XDF’s cooling efficiency is reduced if it is operated in higher ambi- ent temperatures and humidity. The reduction varies according to the heat load from the installed equipment and the external temperature and humidity.

The XDF may be operated for short periods with its doors open. Refer to Figure 10.7 - Operation With the Door Open.

10.1 Environmental Control

The XDF’s cooling functions are controlled by Liebert’s iCOM control module. This section describes the iCOM’s basic functions, such as start-up and navigation. For further details on setting up and using your iCOM, refer to 10.2 - iCOM Components and Functions and 10.3 - Navigating Through the iCOM Display or call 800-543-2778.

The menu-driven iCOM display is used for programming each cooling function. The screen shows the status of the conditioned space, setpoints, alarm status and settings, event histories and the current time.

Remote Communications—Building Management Systems, Liebert SiteScan

The iCOM controller on the XDF may be remotely accessed with Liebert’s SiteScan systems, Modbus or with SNMP.

Each XDF is equipped with Intellislot bays for use with optional communication cards:

  • OpenComms 485—enables the XDF to communicate via Modbus or BACnet protocols to Liebert’s SiteScan or third-party building management systems
  • OpenComms Web—enables the XDF to communicate via SNMP

10.2 iCOM Components and Functions

The iCOM controller layout is shown in Figure 29.

Figure 29 iCOM display components

Emerson XDF — 10.2 iCOM Components and Functions diagram (page 45)
Fig. 43 · 10.2 iCOM Components and Functions

Liquid Crystal Display screen

LED Status Indicators (top LED is red or flashing red; bottom LED is green or amber)

Operation · Keypad

Page 46 of the Emerson XDF user manual — ESC
Page 46 · click to enlarge
Page 46

Table 7 Keyboard icons and functions

Icon Key Name Function

On/Off Key Controls the operational state of the cooling unit.

Alarm Key Silences an alarm.

?

Help Key Accesses integrated help menus.

ESC

ESCape Key Returns to the previous display view.

Enter Key Confirms all selections and selects icons or text.

Increase Key (Up Arrow) Moves upward in a menu or increases the value of a selected parameter.

Decrease Key (Down Arrow) Moves downward in a menu or reduces the value of a selected parameter.

Left and Right Arrow Keys Navigates through text and sections of the display.

Blinking Red—Active, unacknowledged alarm exists

Solid Red—Active, acknowledged alarm exists

Amber—Power is available to the unit, unit is NOT operating

Green—Power is available to the unit, unit is operating

Operation · Upper LED · Lower LED

Page 47 of the Emerson XDF user manual — 10.3 Navigating Through the iCOM Display
Page 47 · click to enlarge
Page 47

10.3 Navigating Through the iCOM Display

iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. The iCOM’s default screen may be either graphical or simple (no bar graphs).

Figure 30 iCOM graphical display default screen components

Actual Ambient Relative Humidity

Emerson XDF — 10.3 Navigating Through the iCOM Display diagram (page 47)
Fig. 44 · 10.3 Navigating Through the iCOM Display

Actual Internal Cabinet Temperature

Backup Ventilation (shows only when operating)

Open Door Operation (only one icon shows at a time)

Optional Load Monitor Readout (amount of energy consumption by internal equipment)

Figure 31 iCOM simple display default screen components

Actual Ambient Relative Humidity

Emerson XDF — 10.3 Navigating Through the iCOM Display diagram (page 47)
Fig. 45 · 10.3 Navigating Through the iCOM Display

Actual Internal Cabinet Temperature

Next Scheduled Maintenance Open Door Operation (only one icon shows at a time)

Backup Ventilation (shows only when operating)

Optional Load Monitor Readout (energy con- sumption by internal equipment)

Active Alarms (not displayed when there are no active alarms)

Show 8 more labels / short text on this page
Operation · Actual Ambient Temperature · Internal Cabinet Setpoint · Evaporator Fans · Percent Cooling · Next Scheduled Maintenance · Actual Ambient Temperature · Evaporator Fan Operation
Page 48 of the Emerson XDF user manual — DISPLAY SETUP
Page 48 · click to enlarge
Page 48

10.3.1 Accessing Menus and Settings

Viewing Data

No password is required to view data or settings.

To view data:

1. From the default screen, press the Enter key to view the opening page of the six-page user menu (see Figure 32). 2. Press Enter again to highlight the password line. 3. Use the Down arrow to scroll to the icon for the data you wish to view. 4. Once that icon is highlighted, press Enter again to display the data. If there are lines above or below what is shown on the screen, small arrows in the top right corner and bottom right corner will be displayed (see Figure 33). 5. Press Enter to select the first line of data. 6. Use the Up and Down arrow keys to scroll to the desired data point. 7. Press ESC to move back to higher level menus.

Figure 32 iCOM user menu, Page 1 of 6

USER MENUS 1/6

Up and Down Arrows show additional pages are above and below the current page. Left and Right Arrows show additional screens and menus are available. Note: Although Service and Advanced menus may be viewed, changes may be made only by factory-authorized service personnel.

PASSWORD LEVEL0

C / F % RH

SETPOINTS

SET Password command line—highlight by pressing Enter

Figure 33 Accessing additional menu lines

DISPLAY SETUP

U404 TEMP F / C °F U405 CONTRAST 50% U406 BUZ FREQ 50%

Arrows show there are additional lines above and below

10.3.2 Entering the Password 1. From the default screen, press the Enter key to access the opening page of the six-page user menu (see Figure 32). 2. Press Enter to highlight the Password command line. 3. With the password line highlighted, press Enter to highlight the first digit in the password; enter the password, 1490. 4. Use the Up and Down arrow keys to select a numeral for the first digit of the password. 5. Move to the next digit of the password with the Right arrow key. 6. Select the numerals for all four digits with the same process. 7. After all four digits of the password have been entered, press the Enter key.

Operation

Page 49 of the Emerson XDF user manual — 10.4 Changing Operational Settings
Page 49 · click to enlarge
Page 49

10.4 Changing Operational Settings

Changes to the XDF’s operation settings in the Set Alarms and Setpoints menus require a pass- word.

1. From the default screen, press the Enter key to view the opening page of the six-page user menu. 2. Press Enter again to highlight the password line. 3. Enter the password (for help, see 10.3.2 - Entering the Password) 4. After entering the password, use the Up and Down arrow keys to scroll to the icon containing the operational setting to be changed. 5. Press Enter to display the data for that icon. 6. Press Enter to highlight the first line of commands. 7. Use the Up and Down arrow keys to scroll to the command line to be changed. 8. Press Enter to highlight the setting. 9. Change the setting by using the Up and Down arrow keys. 10. Press Enter to accept the change. (The setting will no longer be highlighted.) 11. Press ESC to deselect the command line. (The command line will no longer be highlighted.) 12. Press ESC again to move to previous screens.

Operation

Page 50 of the Emerson XDF user manual — 1234h
Page 50 · click to enlarge
Page 50

Table 8 User menu icons

°C / °F

Setpoints View and change internal cabinet temperature setpoint (humidity setpoint inactive on XDF)

% RH

SET

EVENT

Event Log Contains last 400 events

LOG

Graphic Data Record Displays temperature and humidity graphs

View Network Shows status of all connected units (inactive on XDF)

SET ALARMS

Set Alarms Allows enable, disable and settings for alarms

Sensor Data Shows readings of sensors

1 2 3 9 6 SET

Display Setup Change settings for display: language, time, simple or graphic display

Total Run Hours Records the run time of all components and allows setting of limits on run time

1234h

1 2 3 9 6

Sleep Mode Allows setback settings for non-peak operation

Service Contacts Contains key contact information for local service, including names and phone numbers

Operation · Icon Name Description

Page 51 of the Emerson XDF user manual — 10.6 Changing the XDF’s Default Operating Temperature
Page 51 · click to enlarge
Page 51

10.5 Changing iCOM’s Display Settings

No password is required to change the way iCOM displays data. The Display Setup submenus control how such data as temperature, date and time is shown.

To change the display settings:

1. From the default screen, press the Enter key (see Figure 28) to access the user menu. 2. Press the Enter key again to highlight the password command line. 3. Use the Up and Down arrow keys to navigate to the Display Setup icon. 4. Press the Enter key again to access the Display Setup submenu (see Figure 34). 5. Press the Enter key to select the first command. Either change that setting or navigate to another setting with the Up and Down arrow keys. 6. Once the desired command line is highlighted, press the Enter key to access that parameter’s display setting options. 7. Use the Up and Down arrow keys to make changes. 8. Press the Enter key to accept the changes. 9. Press the ESC key twice to return to iCOM’s user menu.

Figure 34 Display setup screen

DISPLAY SETUP

U404 TEMP F / C °F U405 CONTRAST 50% U406 BUZ FREQ 50%

Highlight the setting to be changed by pressing Enter.

10.6 Changing the XDF’s Default Operating Temperature

The XDF’s internal temperature is set at the factory at 72°F (22°C). This setpoint is adjustable from 65°F to 80°F (18-27°C). To change this setpoint:

1. From the default screen, press the Enter key (see Figure 28) to access the user menu. 2. Press Enter a second time to select and highlight the Password line. 3. Enter the password (see 10.3.2 - Entering the Password). 4. Use the Down arrow key highlight the Setpoints icon. 5. Press the Enter key to enter the setpoints submenu. 6. Press the Enter key to highlight TEMP SET command line. 7. Press Enter again to access the setpoint adjustment. 8. Use the Up and Down arrow keys to select the desired setpoint. 9. Press the Enter key to accept the selected setpoint. 10. Press the ESC key twice to return to the iCOM’s user menu.

For further details about the iCOM controller, see 10.2 - iCOM Components and Functions and 10.3 - Navigating Through the iCOM Display. For more complete information about the iCOM controller, call 800-543-2778.

Operation

Page 52 of the Emerson XDF user manual — OK
Page 52 · click to enlarge
Page 52

10.7 Operation With the Door Open

If the external ambient dew point exceeds the XDF’s internal tempera- ture, the iCOM control will flash a warning that condensation may form inside the enclosure if a door is opened. The warning is an icon of a door with an “X” on top of it. The word NO appears beside the icon.

NO

If a warning is flashing, the XDF’s doors may be opened safely while the unit is operating by following these steps:

1. From the default screen, press the Enter key (see Figure 28) to access the user menu. 2. Press Enter a second time to select and highlight the Password line. 3. Use the Down arrow to scroll to the Setpoints icon. 4. Press the Enter key again to access the Setpoints submenu. 5. Press Enter again to highlight the first command line. 6. Using the Down arrow key to highlight the DOOR OP command line. 7. Hit the Enter key to highlight the setting adjustment. 8. Use the Up and Down arrow keys to change the status to YES. 9. Press Enter to accept the change. 10. Hit the ESC key four times to return to the default screen. 11. The iCOM control will begin reducing cooling until the XDF’s internal temperature is high enough that condensation will not occur if the door is opened. 12. Once the internal temperature reaches this point, the “Door Open Wait Timer” starts counting down. The XDF may be opened without internal condensation when the default screen removes the “X” from the door icon and the word OK appears beside the icon.

OK

The XDF will keep the temperature at the level required for opening the door for two minutes. If a door is not opened within two minutes, the XDF will return to the normal operating point.

If a door is opened, the XDF will remain in “Open Door Operation” sta- tus until all doors are closed. After all doors are closed, a two-minute delay is initiated before the unit returns to its normal operating setpoint. If a door is opened again within the two-minute delay, the timer is reset and will restart when the door is closed.

Operation

Page 53 of the Emerson XDF user manual — 10.10 Uninterruptible Power Supply
Page 53 · click to enlarge
Page 53

10.8 Backup Ventilation System

The XDF is equipped with a backup ventilation system that circulates ambient air through the XDF should any component of the cooling system fail or if power is lost. The backup ventilation system begins operating only after the internal temperature exceeds the ambient external temperature.

If powered by a UPS, evaporator fans circulate ambient air until the XDF returns to normal opera- tion.

Emerson XDF — 10.8 Backup Ventilation System diagram (page 53)
Fig. 46 · 10.8 Backup Ventilation System

Figure 35 Airflow pattern, backup ventilation operation

Self-contained, air cooled XDF shown; vents and operation apply to all XDF models

Evaporator Fans circulate cooling air if powered by a UPS Backup Ventilation Air Intake Vent

Backup Ventilation Air Exhaust Vent

10.9 XDF Compressor

The iCOM automatically adjusts the cooling capacity of the digital scroll compressor depending on the heat load in the cabinet.

Sensors near the evaporator fans monitor the cooling airflow and send the data to the iCOM. These sensors have setpoints that may be adjusted with the iCOM control unit to raise or lower the internal cabinet temperature. For information on changing the setpoints, refer to 10.6 - Changing the XDF’s Default Operating Temperature or call 800-543-2778.

If the return air temperature drops below the setpoint, iCOM reduces the compressor’s cooling output accordingly. The evaporator fans will continue to circulate internal cabinet air throughout the enclo- sure.

10.10 Uninterruptible Power Supply

The XDF may be supplied with any of several Liebert UPS units or with no UPS. For inte- grated/matched models, the UPS and the equipment installed in the XDF are sized with matched capacities. A larger UPS, with more battery time, can be obtained, but the connected electronics load should not exceed the XDF’s cooling capacity.

For XDF units equipped with a UPS, refer to the UPS manual for UPS operation and specifications.

Operation · Heated air returns

Page 54 of the Emerson XDF user manual — 11.1 Periodic Maintenance
Page 54 · click to enlarge
Page 54

11.0 M AINTENANCE

No Power Confirm unit is plugged in and the building breaker has not tripped.

Clogged condenser coil Clean coil. See 11.1 - Periodic Maintenance.

XDF system not cooling

Hot Gas bypass valve set incorrectly Contact Liebert Technical Support at 800-543-2378.

Refrigerant loss Verify leak. If refrigerant system needs repaired, contact Liebert Technical Support at 800-543-2378.

Remove airflow obstructions from the front and rear of the enclosure. Ensure the cabinet has at least 36" (915mm) front, rear and overhead clearance. (Water/glycol models do not require overhead clearance.) Open XDF’s doors and let compressor cool. Plug in XDF and verify compressor is energized.

Airflow is blocked at the intake or exhaust.

Fans blowing warm air

Compressor trips on thermal overload

Open XDF doors and let compressor cool. Plug in XDF and verify compressor is energized.

Faulty Compressor Contact Liebert Technical Support at 800-543-2378.

Ensure that the enclosure rests on a level surface. The cabinet must be level to ensure proper operation. Verify condensate drain is attached to drain and the drain line has the proper pitch (see 4.5.4 - Condensate Drain Connection).

Water leaking from inside the cabinet

Cabinet not level or internal drain line clogged

Excessive vibration or noise

Defective motor in blower or shipping damage Contact Liebert Technical Support at 800-543-2378.

Electronic equipment not positioned for optimum cabinet airflow

Rearrange the equipment as illustrated in 4.7 - Equipment Layout.

Verify the UPS load does not exceed XDF’s capacity. If no UPS, verify equipment load does not exceed the XDF’s rating.

Cabinet is excessively hot

Heat not rejected from room Verify that XDF is in room with air circulation and heat rejected from unit is sufficiently removed.

XDF system not cooling Confirm unit is plugged in and the building breaker has not tripped. Check setpoints on iCOM controller.

Check cable entry points, and verify doors and side panels are closed. Reposition wires to prevent air leak, or fix or replace damaged gaskets.

Silence alarm on the iCOM module. See solutions for “XDF system not cooling,” “Fans blowing warm air” and “Cabinet is excessively hot causes” to determine course of action.

Audible alarm and cabinet is excessively hot

iCOM control module has detected an abnormal condition

11.1 Periodic Maintenance

The Liebert XDF requires very little maintenance. The XDF’s condenser coil must be inspected peri- odically to determine the necessary cleaning interval based on conditions at the installation site. Depending on site conditions, the coil may require cleaning as often as twice a month or as seldom as twice per year. If the coil becomes dirty and clogged, it should be vacuumed with a soft bristle brush or cleaned with compressed air.

Show 5 more labels / short text on this page
Maintenance · Table 9 Troubleshooting · Problem Cause Solution · Compressor is overloaded · Cabinet not sealed
Page 55 of the Emerson XDF user manual — XDF S 14 1 0 1 0
Page 55 · click to enlarge
Page 55

12.0 S PECIFICATIONS

Figure 36 XDF model numbers

Enclosure Total Load Monitoring

XDF S 14 1 0 1 0

Liebert Extreme Heat Density Foundation Enclosure

0 = None 1 = Module Included 0 = None 1 = Module Included

1 = 120V-1ph-60HzkW and 208V-3ph-60Hz

Air Cooled W = Water Cooled 0 = None A = GXT2-1000 B = GXT2-1500 C = GXT2-2000 D = GXT2-3000 E = GXT2-700 F = PS1000RT2

G = PS1440RT2 H = PS2200RT2 I = PS3000RT2 K = GXT2-2700 (*) L = GXT2-6000 (*) M = GXT2-10000 (*) (*) 208VAC models

Table 10 Physical specifications

Height, In. (mm)

Overall 82-1/4 (2089) 79-3/4 (2026)

Cabinet Only 79-3/4 (2026) 79-3/4 (2026)

Fan Guard 2-1/2 (57) N/A

Equipment Rack Area 36U 42U

Width, In. (mm)

EIA Nominal 19 (483)

Inside Dimension 17-13/16 (452)

Depth, In. (mm)

Mounting Depth, adjustable, minimum 24-3/8 (620)

Mounting Depth, adjustable, maximum 32-11/32 (821)

Weight, Lb. (kg)

Cabinet Only 710 (322) 668 (303)

Equipment Capacity 1200 (544)

Show 15 more labels / short text on this page
Specifications · Cooling Capacity · Input Power UPS · Condensate · Pump · Model Model Type · = 14kW · S = Self-Contained, · XDFS141 Self- Contained, · XDFW141 Water/Glycol · Dimensions · Air Cooled XDF · Cooled XDF · Overall 34-1/8 (867) · Overall 49-1/2 (1257)
Page 56 of the Emerson XDF user manual — °F (°C)
Page 56 · click to enlarge
Page 56

Table 11 Electrical specifications

Control & Fan Supply

Unit FLA 8.3 5.0

Max Fuse or Circuit Breaker Amps 15 15

Min. Supply Circuit Ampacity 9.2 5.2

Receptacle required NEMA 5-15R NEMA 5-15R

Unit FLA 15.7 15.7

Max Fuse or Circuit Breaker Amps 35 35

Min. Supply Circuit Ampacity 19.6 19.6

Receptacle required NEMA L21-30R NEMA L21-30R

Condensate Pump Amps (Optional) 0.72 0.72

Table 12 Total heat rejection

Total Heat Rejection, kW

°F (°C)

°F (°C) Load, kW

95 (35) 77 (25) 14.1 20

Show 16 more labels / short text on this page
Specifications · Self- Contained, · Water/Glycol · Electrical Data · Air Cooled XDF · Cooled XDF · Voltage 120 120 · Ph 1 1 · Hz 60 60 · Compressor Supply · Voltage 208 208 · Ph 3 3 · Hz 60 60 · Rating Point, · Supply Air Temperature, · Ambient
Page 57 of the Emerson XDF user manual — 12.1 Optional Power Systems
Page 57 · click to enlarge
Page 57

12.1 Optional Power Systems

Table 13 UPS performance data

Input Power (1 ph)

Model Number VA / Watts

Height In (mm) U

Volts OPD (A) Plug

GXT2-700RT120 700 / 490 3.5 (89) 2 120 15 NEMA 5-15P

GXT2-1000RT120 1000 / 700 3.5 (89) 2 120 15 NEMA 5-15P

GXT2-1500RT120 1500 / 1050 3.5 (89) 2 120 15 NEMA 5-15P

GXT2-2000RT120 2000 / 1400 3.5 (89) 2 120 20 NEMA 5-20P

GXT2-3000RT120 3000 / 2100 3.5 (89) 2 120 30 NEMA L5-30P

GXT2-700RT230 700 / 490 3.5 (89) 2 230 10 IEC-C14 *

GXT2-1000RT230 1000 / 700 3.5 (89) 2 230 10 IEC-C14 *

GXT2-1500RT230 1500 / 1050 3.5 (89) 2 230 10 IEC-C14 *

GXT2-2000RT230 2000 / 1400 3.5 (89) 2 230 10 IEC-C14 *

GXT2-3000RT230 3000 / 2100 3.5 (89) 2 230 16 IEC-C20 *

GXT2-6000RT-208 6000 / 4200 7 (178) 4 208/120 30 NEMA L14-30P

GXT2-10000RT-208 10000 / 8000 10.5 (267) 6 208/120 60 Hard-Wired

PS1000RT2-120 1000 / 750 3.5 (89) 2 120 15 NEMA 5-15P

PS1440RT2-120 1440 / 1080 3.5 (89) 2 120 15 NEMA 5-15P

PS2200RT2-120 2200 / 1650 3.5 (89) 2 120 15 NEMA L5-30P

PS3000RT2-120 3000 / 2250 3.5 (89) 2 120 15 NEMA L5-30P

PS1000RT2-230 1000 / 750 3.5 (89) 2 230 15 IEC-C14 *

PS1440RT2-230 1440 / 1080 3.5 (89) 2 230 15 IEC-C14 *

PS2200RT2-230 2200 / 1650 3.5 (89) 2 230 15 IEC-C20 *

PS3000RT2-230 3000 / 2250 3.5 (89) 2 230 15 IEC-C20 *

* All 230V models are equipped with input sockets for use with detachable cords. Input cords are not provided, however, each unit does include two 1.8m 10A load cords.

Specifications · or Hard-Wired

Page 58 of the Emerson XDF user manual — 12.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mount
Page 58 · click to enlarge
Page 58

12.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mount

MP Advanced Power Strips are available in 19" rack-mount and vertical-mount form to accommodate different installation requirements. See Mounting Method & Size in Table 14 for specific configu- rations.

Table 14 MP Advanced Power Strip specifications

Envir.

Ft. (m)

Remote Monitoring and Control

MP-C5120 Rckmnt/1U 120V-15A-1ph 5-15P (1) 6 (1.8) 120V-15A-1ph 5-15/20R (8) 0

MP-C5121 Rckmnt /1U 120V-20A-1ph 5-20P (1) 6 (1.8) 120V-20A-1ph 5-15/20R (8) 0

MP-C5122 Rckmnt/1U 120V-20A-1ph L5-20P (1) 6 (1.8) 120V-20A-1ph 5-15/20R (8) 0

MP-C5123 Rckmnt/1U 120V-30A-1ph L5-30P (1) 6 (1.8) 120V-30A-1ph 5-15/20R (8) 2

MP-C5124 Rckmnt/1U 200/240V-20A-1ph L6-20P (1) 6 (1.8) 200/240V-20A-1ph IEC320 C13 (8) 0

MP-C5125 Rckmnt/1U 200/240V-30A-1ph L6-30P (1) 6 (1.8) 200/240V-30A-1ph IEC320 C13 (8) 2

MP-M5109 Rckmnt/1U 120V-15A-1ph 5-15P (1) 6 (1.8) 120V-15A-1ph 5-15/20R (10) 2

MP-M5110 Rckmnt/1U 120V-20A-1ph 5-20P (1) 6 (1.8) 120V-20A-1ph 5-15/20R (10) 2

MP-M5111 Rckmnt/1U 120V-20A-1ph L5-20P (1) 6 (1.8) 120V-20A-1ph 5-15/20R (10) 2

MP-M5112 Rckmnt/1U 120V-30A-1ph L5-30P (1) 6 (1.8) 120V-30A-1ph 5-15/20R (10) 2

MP-M5113 Rckmnt/1U 200/240V-20A-1ph L6-20P (1) 6 (1.8) 200/240V-20A-1ph IEC320 C13 (10) 2

MP-M5114 Rckmnt/1U 200/240V-30A-1ph L6-30P (1) 6 (1.8) 200/240V-30A-1ph IEC320 C13 (10) 2

MP-M5115 Vert/33.25" 120V-15A-1ph 5-15P (1) 10 (3) 120V-15A-1ph 5-15/20R (12) 2

MP-M5116 Vert/33.25" 120V-20A-1ph 5-20P (1) 10 (3) 120V-20A-1ph 5-15/20R (12) 2

MP-M5117 Vert/33.25" 120V-20A-1ph L5-20P (1) 10 (3) 120V-20A-1ph 5-15/20R (12) 2

MP-M5118 Vert./50.75" 120V-20A-1ph 5-20P (1) 10 (3) 120V-20A-1ph 5-15/20R (24) 2

MP-M5034 Vert./50.75" 120V-20A-1ph L5-20P (1) 10 (3) 120V-20A-1ph 5-15/20R (24) 2

MP-M5035 Vert./50.75" 120V-30A-1ph L5-30P (1) 10 (3) 120V-30A-1ph 5-15/20R (24) 2

MP-M5036 Vert./57.75" 200/240V-20A-1ph L6-20P (1) 10 (3) 200/240V-20A-1ph IEC320 C13 (24) 2

MP-M5037 Vert./57.75" 200/240V-30A-1ph L6-30P (1) 10 (3) 200/240V-30A-1ph IEC320 C13 (24) 2

* Twenty switchable receptacles; one receptacle is always On.

Show 15 more labels / short text on this page
Specifications · Input Output · Mounting · Voltage- Current (A)- · Cord Length, · Voltage- Current (A)- · Method · Connection Type (Quan) · Connection Type(s) (Quan) · Liebert PN · & Size · Phase · Phase · Port · Remote Monitoring Only
Page 59 of the Emerson XDF user manual — 12.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mount
Page 59 · click to enlarge
Page 59
Page 59 of the Emerson XDF user manual — 12.2 Optional Managed Power - Advanced Power Strips, Verticalor Horizontal-Mount
Page 60 of the Emerson XDF user manual — SL-17010_REV4_ 12/06
Page 60 · click to enlarge
Page 60

Ensuring The High Availability 0f Mission-Critical Data And Applications.

Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.

Technical Support / Service

Web Site www.liebert.com

Monitoring 800-222-5877 monitoring@emersonnetworkpower.com

Outside the US614-841-6755

800-222-5877 upstech@emersonnetworkpower.com

Outside the US614-841-6755

800-543-2378 powertech@emersonnetworkpower.com

800-543-2778 Outside the United States

614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250

SL-17010_REV4_ 12/06

EmersonNetworkPower.com Emerson Network Power. The global leader in enabling Business-Critical Continuity™.

Embedded Computing Embedded Power Power Switching & Controls

Services Racks & Integrated Cabinets Outside Plant

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.

©2006 Emerson Electric Co.

Show 8 more labels / short text on this page
Single-Phase UPS · Three-Phase UPS · Environmental Systems · AC Power Connectivity · DC Power · Monitoring · Precision Cooling · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
XDF system not coolingNo PowerConfirm unit is plugged in and the building breaker has not tripped. p.54
XDF system not coolingClogged condenser coilClean coil. See 11.1 - Periodic Maintenance. p.54
XDF system not coolingHot Gas bypass valve set incorrectlyContact Liebert Technical Support at 800-543-2378. p.54
XDF system not coolingRefrigerant lossVerify leak. If refrigerant system needs repaired, contact Liebert Technical Support at 800-543-2378. p.54
Fans blowing warm airAirflow is blocked at the intake or exhaust.Remove airflow obstructions from the front and rear of the enclosure. Ensure the cabinet has at least 36" (915mm) front, rear and overhead clearance. (Water/glycol models do not require overhead clearance.) Open XDF’s doors and let compressor cool. Plug in XDF and verify compressor is energized. p.54
Fans blowing warm airCompressor trips on thermal overloadOpen XDF doors and let compressor cool. Plug in XDF and verify compressor is energized. p.54
Fans blowing warm airFaulty CompressorContact Liebert Technical Support at 800-543-2378. p.54
Water leaking from inside the cabinetCabinet not level or internal drain line cloggedEnsure that the enclosure rests on a level surface. The cabinet must be level to ensure proper operation. Verify condensate drain is attached to drain and the drain line has the proper pitch (see 4.5.4 - Condensate Drain Connection). p.54
Excessive vibration or noiseDefective motor in blower or shipping damageContact Liebert Technical Support at 800-543-2378. p.54
Cabinet is excessively hotElectronic equipment not positioned for optimum cabinet airflowRearrange the equipment as illustrated in 4.7 - Equipment Layout. p.54
Cabinet is excessively hotCompressor is overloadedVerify the UPS load does not exceed XDF’s capacity. If no UPS, verify equipment load does not exceed the XDF’s rating. p.54
Cabinet is excessively hotHeat not rejected from roomVerify that XDF is in room with air circulation and heat rejected from unit is sufficiently removed. p.54
Cabinet is excessively hotXDF system not coolingConfirm unit is plugged in and the building breaker has not tripped. Check setpoints on iCOM controller. p.54
Cabinet is excessively hotCabinet not sealedCheck cable entry points, and verify doors and side panels are closed. Reposition wires to prevent air leak, or fix or replace damaged gaskets. p.54
Audible alarm and cabinet is excessively hotiCOM control module has detected an abnormal conditionSilence alarm on the iCOM module. See solutions for “XDF system not cooling,” “Fans blowing warm air” and “Cabinet is excessively hot causes” to determine course of action. p.54

Ask about the Emerson XDF

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson XDF

Be the first to ask — other owners or our team will answer.