6.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE) 6.1 Silence Alarm (Service Terminal Interface) 24 6.2 Back Up Log Files (Service Terminal Interface only) 25
7.0 SYSTEM AND CONTROL OPTIONS 7.1 Login 27 7.2 Setup System - Overview 29 7.3 Setup System - Setup Inputs 29 7.3.1 Change Label (Name of Input) 30 7.3.2 Define Input as Normally Open or Normally Closed 30 7.3.3 Define Input as Alarmable or Event 30 7.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode 31 7.3.5 Set Up Delay Time 31 7.4 Setup System - Setup Common Alarm 32 7.5 Setup System - Setup Zones 33 7.5.1 Set Up a Zone 33 7.6 Setup System - Setup Outputs 34 7.6.1 Define Output as Normally Open or Normally Closed 34 7.6.2 Define Operating or Standby Mode 35 7.6.3 Enable or Disable an Output Device in Alarm Status 35 7.6.4 Configure Output for Loss of Power (“Fail-Safe”) 35 7.7 Setup System - Setup System Info 36 7.7.1 Change Password 36 7.7.2 Set Date & Time/Automatic Daylight Saving Time 37 7.7.3 Setup Site ID 37 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) 38 7.7.5 Factory Defaults 41 7.7.6 Perform Firmware Update (Service Terminal Interface only) 41 7.8 Setup Operation 43 7.8.1 Turn Automatic Sequencing On or Off 44 7.8.2 Turn Standby Testing On or Off 45 7.8.3 Specify Failed Standby Response 45 7.8.4 Specify Hold Delay Time 46 7.8.5 Specify Restart Time 46 7.9 Override Output 47 7.10 Clear Alarms & Logs 48 7.10.1 Clear Active Alarms 48 7.10.2 Clear the Alarm Log 48 7.10.3 Clear the Event Log 48
8.0 SPECIFICATIONS 8.1 Liebert AC4 Specifications 49

APPENDIX A - SERVICE TERMINAL INTERFACE 51 A.1 Comparison of Functions: LCD and Service Terminal Interface 51 A.2 Connecting to the Service Terminal Interface 52 A.2.1 Create a Connection 53 A.2.2 Connect to the Service Terminal Interface 55 A.3 Overview of Menus 56 A.3.1 View Status Overview 56 A.3.2 Silence Alarm and Backup Log Files 56 A.3.3 Setup Menu Overview 56 A.4 View Status Menus 57 A.4.1 View Active Alarms 57 A.4.2 View Alarm Log 58 A.4.3 View Event Log 59 A.4.4 View Input Status 59 A.4.5 View Output Status 60 A.5 Silence Alarm & Back Up Log Files (Service Terminal Interface only) 61 A.5.1 Silence Alarm (Service Terminal Interface only) 61 A.5.2 Back Up Log Files (Service Terminal Interface only) 62 A.6 Setup Menu 63 A.6.1 Setup Inputs 65 A.6.2 Setup Common Alarm 66 A.6.3 Setup Zones 66 A.6.4 Setup Outputs 67 A.6.5 Setup System Info 68 A.6.6 Setup Operation 73 A.6.7 Override Output 76 A.6.8 Clear Alarms & Logs 77


The Liebert AC4 is ideal for coordinated control of systems with redundant equipment, such as multiple environmental units or pumps. When the Liebert AC4 controller detects an alarm in an operating device, the Liebert AC4 enables a standby device and controls the device in alarm as configured, either leaving that device operating or disabling it.
The Liebert AC4 controller can also balance usage of devices by rotating units through Operating and Standby modes according to a user-defined schedule. This helps keep redundant equipment operating efficiently and only when needed. The Liebert AC4 can perform routine testing of standby devices and alert personnel if a standby device fails an operating test and requires attention.
Another capability of the Liebert AC4 is monitoring the status of connected devices and keeping personnel apprised through local alarming.
The Liebert AC4 controller can interface with anything that closes an electrical contact. To improve process efficiency and troubleshooting, the controller tracks data in two types of logs: alarm and event. The Liebert AC4 has a local LCD interface and an RS232 interface.
When an alarm condition arises, the Liebert AC4 displays alarm information, sounds an audible alarm, changes the state of the common alarm relay and turns connected devices on or off according to user configuration. See 1.5 Typical Configuration for a more detailed example.
The Liebert AC4 features access through two interfaces that allow users to configure the unit, silence alarms, back up logs, and perform many other functions to keep a large or small operation running smoothly and safely.
These interfaces permit easy access and configuration of the Liebert AC4, allowing users to view data, silence alarms and have full access to information stored in the controller, including logs of alarms and events.
The two types of data logs—alarm history and event history—can be viewed on the LCD on the front of the Liebert AC4 or the Service Terminal Interface. The logs may also be downloaded to a computer through the Service Terminal Interface.
The alarms available with the Liebert AC4 are:
Introduction

The Liebert AC4 controller board comes in an enclosure that is 2-3/4" deep and has a built-in liquid crystal display (LCD) and a key lock, as shown in Figure 1. The enclosure is made of metal to accommodate secure conduit fittings and protect components against environmental debris.
Figure 1 Liebert AC4 enclosure—external features

LCD for configuration and operation
The enclosure has knockouts and access slots on top and bottom for cables and wires.
The enclosure must be secured to a wall, either flush-mounted or recessed in the wall, as described in 2.0 Installation. Knockouts and access slots on the top and bottom allow easy connection of wires and cables (see 3.0 Wiring and Connections) with either mounting type.
Figure 2 Liebert AC4 enclosure—internal features

Knockouts and access slots (top and bottom)
Ground wire for LCD

Figure 3 shows an example of external devices connected to the Liebert AC4 controller board. There may be up to four devices connected to the four digital inputs and four digital outputs. Remote access is available through the Service Terminal Interface.
Figure 3 Typical Configuration

Introduction

The Liebert AC4 controller board has connectors for four digital inputs and four digital outputs, as shown below. The board comes complete with light emitting diodes (LEDs) to display the status of connected devices, a serial communications port, a power connection and other features necessary to control your operation.
A - Power On/Off switch
D - Common Alarm connectors C - Audible horn jumper B - Audible horn

P - 24VAC power connector
E - Digital output status LEDs
O - LCD contrast adjustment
F - Manual Override Switch (outputs)
G - Digital output connectors
N - LCD connector
H - Status LEDs
M - DIP switch 1
I - Digital output loss-of-power jumper
J - Digital input connectors
L - Serial interface connector (RS232/EIA574)
K - Digital input status LEDs
Table 1 Controller board components
Introduction

Table 1 Controller board components (continued)
Introduction

The Liebert AC4 controller board has LED indicators that show the status of inputs, outputs and the common alarm

OUTPUT2 OUTPUT3 OUTPUT4 OUTPUT5 OUTPUT6 OUTPUT7 OUTPUT8 CTRLLOCK SENLOCK CMN ALR
Table 2 LED indicators summary


Figure 4 shows a typical sequence of how the Liebert AC4 functions after detecting a change in a monitored device. Many responses depend on configuration settings. This example shows what happens when a digital input changes state—assuming the input is defined as alarmable—and when the condition returns to normal.
Figure 4 Example of typical sequence

ALARM CONDITION DETECTED A device connected to the Liebert AC4 changes state.
RETURN TO NORMAL The device that triggered the alarm returns to its normal state.
The alarm is cleared (automatically if Unlatched; must be cleared manually if Latched)
The horn sounds (audible horn on the controller board—silence horn by pressing any key on the LCD keypad)
The horn stops sounding (if user hasn’t silenced it)
The LCD flashes (except during setup)
The LCD stops flashing
ESC ESC
User setup determines output control (for example, the device in alarm might be disabled and a standby device set to operate)
DEVICE_1 ALARM CONTACT CLOSED 30-SEP-04 16:23:04 Entry in Alarm Log Condition (ALARM) & state (CONTACT CLOSED)
30-SEP-04 16:24:04 Entry in Alarm Log (ALARMS CLEARED)
Entry in Active Alarm Log Condition (ALARM) & state (CONTACT CLOSED)
Entry in Event Log Status change (DEVICE_4 STARTED)
Entry in Event Log Actions in response to event (DEVICE_1 STARTED, DEVICE_4 OFF)
DEVICE_1 STARTED DEVICE_2 STARTED DEVICE_3 STARTED DEVICE_4 OFF 30-SEP-04 16:24:06
Introduction

The Liebert AC4 must be installed indoors and may be mounted on the surface of a wall or flush- mounted, depending on the user’s application, the location of equipment to be connected and the type of wall the unit will be mounted on.
The Liebert AC4 should be mounted where it can be easily accessed. On-site personnel would access the unit through the LCD on its front cover or the service terminal connected to the RS232 port.
In addition to the communications connections, the site also must have electrical service and must permit connecting the unit’s four digital inputs and four digital outputs.
The wall material must be capable of supporting the weight of the Liebert AC4: see 8.0 Specifications.
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Table 3 Packing manifest
Liebert AC4 controller board in enclosure
Keys (2) to panel door lock

After determining where to place the unit, check to ensure that you have all the hardware required to install the panel on the surface of a wall. Obtain the needed tools and material.
! WARNING Risk of electric shock. Can cause property damage, injury and death.
Check building plans and other relevant documents to determine whether mounting the Liebert AC4 at the selected location might cause cutting or otherwise damaging electrical or communication wiring or pipes.
1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5). 2. Drill holes, if required, to install the four #10 screws that will secure the Liebert AC4 to the wall. Clean up the debris. 3. If the wall material is not strong enough to hold the screws securely, use wall anchors. 4. Install the top two screws—the screw heads must be small enough to slip through the larger, bottom portion of the pear-shaped mounting slot in the Liebert AC4 (see inset in Figure 5). The screws must also be large enough to extend over the edges of the top of the mounting slot. 5. Hang the Liebert AC4 on the screws, letting the panel slip down until the screws are in the smaller, upper portion of the slot. 6. Tighten the screws until they are snug. 7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.
Figure 5 Mounting dimensions

0.213" (5.4mm) Bottom hole diameter
Installation · Mounting Slot

The rectangular access doors on the top and bottom of the Liebert AC4 must be reversed so they slide the opposite direction. Leaving the doors as shipped from the factory prevents them from being opened when the panel is flush mounted in a wall.
The Liebert AC4 may be flush mounted according to company practices—either with screws through the sides of the panel into wall supports or with hanging hardware that attaches to the back of the panel. After determining how and where to place the unit, check to ensure that you have all the hardware required to install the panel in the wall. Obtain the needed tools.
! WARNING Risk of electric shock. Can cause property damage, injury and death.
Check building plans and other relevant documents to determine whether mounting the Liebert AC4 at the selected location might cause cutting or otherwise damaging electrical or communication wiring or pipes.
1. Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template. 2. Drill a pilot hole for the saw blade, if required. 3. Use the saw to cut out the marked section of the wall (if not new construction). 4. Rest the Liebert AC4 in the wall and mark where mounting screws will be inserted into the wall studs or other support member. 5. Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the debris. 6. Reverse the slide direction of the rectangular access doors on the top and bottom of the Liebert AC4. Leaving the doors as shipped from the factory prevents them from being opened when the panel is flush mounted in a wall. 7. Attach any field-supplied mounting hardware. 8. Reinsert the assembly into the wall. 9. Insert and tighten the screws or wall anchors.
Installation

The Liebert AC4 requires 24VAC for proper operation. Liebert recommends using the optional Transformer Module manufactured by Liebert or another UL-approved class 2 power unit to obtain proper voltage. If the power unit is not a class 2 circuit, it must be protected with an IEC 5 x 20mm time lag 2A fuse. For information, consult your local dealer, Emerson representative or the Emerson Network Power Liebert Worldwide Support Group.
! WARNING Risk of electric shock. Can cause property damage, injury and death. Check that power is removed from wires prior to installation. This unit should be installed only by properly trained and qualified personnel.
! CAUTION Risk of electric shock. Can cause property damage, injury and death. The Liebert AC4 is designed for use on properly grounded (earthed) 24VAC power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground terminal (stud located next to the 24VAC terminal block). This equipment is intended to be installed by a qualified and certified electrician who must review and approve customer supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections to ensure compliance with technical standards and national and local electrical codes.
! WARNING Risk of electric shock. Can cause property damage, injury and death.
Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit. The switch is in the top left corner of the unit, just below the battery pack.
To connect electrical power:
Figure 6 Electrical connections to panel
External wiring through knockout






24VAC input connector 24VAC wiring (red & white)

! WARNING Risk of electric shock. Can cause property damage, injury and death.
Switch Off electric power to the Liebert AC4 before installing any wiring to the unit or changing input or output connections. The Power On/Off switch is in the top left corner of the unit.
Input and output connections to the Liebert AC4 may be made in any order—it is not necessary, for example, to make all input connections before making any output connections. Use copper conductors only for all wiring.
Table 4 Wiring specifications
Connection Supported Wire Type Maximum Wire Length Rating
18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740
750 ft. (225m) Dry Contact (24VDC, 10 mA)
18 AWG* (recommended) 20 AWG 22 AWG
18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740
24VAC @3A @3A 50 ft. (15m) @2A 100 ft. (30m) @1A 200 ft. (60m)
@3A 40 ft. (12m) @2A 60 ft. (18m) @1A 100 ft. (30m)
@3A 25 ft. (7m) @2A 35 ft. (10m) @1A 75 ft. (23m)
18 AWG* (recommended) 20 AWG 22 AWG
18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740
24VAC @3A @3A 50 ft. (15m) @2A 100 ft. (30m) @1A 200 ft. (60m)
@3A 40 ft. (12m) @2A 60 ft. (18m) @1A 100 ft. (30m)
@3A 25 ft. (7m) @2A 35 ft. (10m) @1A 75 ft. (23m)
RS232 Null Modem Cable 50 ft. (15m) N/A
18-22 AWG Stranded & Shielded 18 AWG* (recommended) Non Plenum - Belden 8770 Plenum - Belden 88770
150 ft. (45m) 24VAC @1.3A

The digital inputs and outputs are on the lower right side of the Liebert AC4 printed wiring assembly board. This section describes how to connect devices to the Liebert AC4’s inputs and outputs.
Each input is tied to an output with the same number:
Up to four devices may be connected to the Liebert AC4. Each device must be connected to an input and an output with the same number.
To determine the proper wire size, see Table 4 Wiring specifications.
After making the connections, push the removed piece back into the portion attached to the printed wiring assembly until the terminal block pieces lock together.
For Liebert Precision Cooling units, follow these steps (be sure to connect the same device to inputs and outputs with the same number (Input 1 and Output 1, Input 2 and Output 2, and so on):

3.2.1 Connecting Digital Inputs The four digital inputs are on the lower right side of the Liebert AC4, just below the output terminal blocks, as shown at right. These inputs are numbered 1 through 4.
OUTPUT TERMINAL BLOCKS Note numbering keys to right of terminal blocks; outputs are numbered from bottom (1) to top (4)
To connect an input: 1. Turn Off electrical power to the Liebert AC4. 2. If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure. 3. Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.
INPUT TERMINAL BLOCKS Note numbering keys to right of terminal blocks; inputs are numbered from bottom (1) to top (4)
Wiring and Connections · Numbering keys

The four digital outputs are found on the lower right side of the Liebert AC4 just above the input terminal blocks, as shown at right. These outputs are numbered 1 through 4.
To connect an output: 1. Turn OFF electrical power to the Liebert AC4. 2. If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure. 3. Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.
! CAUTION To reduce the risk of fire or electric shock, do not interconnect the outputs of different class 2 circuits.

Each digital output has an associated jumper to define its operation when power is interrupted. This puts the Liebert AC4 in a fail-safe mode and ensures proper functioning when the board has no power.
The Liebert AC4 comes from the factory with all digital output jumpers in the OFF position (normally open). The jumper setting for each digital output can be changed to ON (normally closed). The settings are shown in Table 5.
Table 5 Digital output jumper settings
To change the output jumper setting:


The common alarm relay, found in the top right corner of the Liebert AC4, permits the user to connect auxiliary notification equipment, such as lights, horns and sirens, to the Liebert AC4. To determine the proper wire size, see Table 4 Wiring specifications.
There are two connectors for the common alarm output. However, the connectors are not individual relay outputs. The connectors should be treated as a double-pole, double-throw (DPDT) relay.
The common alarm relay is energized whenever an alarm occurs.
To connect an output:

Serial interface connector (RS232/EIA5 74)
The Liebert AC4’s Service Terminal Interface offers full configuration and monitoring capability via the RS232 port (see A.2 - Connecting to the Service Terminal Interface).
The RS232 port requires a null modem cable. Connect one end of the cable to the Liebert AC4’s RS232 port, shown at right, and the other end to the COM1 port of a laptop computer or video terminal.
Wiring and Connections · Common alarm outputs

There are two ways to access the Liebert AC4: the LCD on the front of the enclosure and the Service Terminal Interface, which is accessible through any computer using a communications program. Many viewing and configuration tasks can be performed through either interface, but some are available only through the Service Terminal Interface.
Table 6 lists all Liebert AC4 functions and shows whether they can be performed through the LCD interface and where to find information.
Table 6 Guide to Liebert AC4 functions
Service Terminal screen examples
VIEW STATUS FUNCTIONS
View Active Alarms 4 4 page 19 page 57
View Alarm Log 4 4 page 20 page 58
View Event Log 4 4 page 21 page 59
View Input Status 4 4 page 22 page 59
View Output Status 4 4 page 23 page 60
Silence Alarm (On the LCD, press any key to silence an alarm) 4 4 page 24 page 61
Back Up Log Files — 4 page 25 page 62
Login 4 4 page 27 page 63
Setup System 4 4 page 29 page 64
Setup Inputs 4 4 page 29 page 65
Setup Common Alarm 4 4 page 32 page 66
Setup Zones 4 4 page 33 page 66
Setup Outputs 4 4 page 34 page 67
Setup System Info 4 4 page 36 page 68
Change Password 4 4 page 36 page 68
Set Date & Time/Automatic Daylight Saving Time 4 4 page 37 page 69
Setup Site ID 4 4 page 37 page 69
Backup and Upload Configuration File — 4 page 38 page 70
Factory Defaults 4 4 page 41 page 71
Perform Firmware Update — 4 page 41 page 72
Setup Operation 4 4 page 43 page 73
Override Output 4 4 page 47 page 76
Clear Alarms & Logs 4 4 page 48 page 77
Clear Active Alarms 4 4 page 48 page 77
Clear the Alarm Log 4 4 page 48 page 77
Clear the Event Log 4 4 page 48 page 78

The Liebert AC4 displays the Opening Screen at startup, as shown in Figure 7.
If no alarms are present, the Main Menu appears.
The Main Menu offers access to all functions within the panel. As shown in Table 7, the functions are organized into three sections with step-by-step instructions.
Table 7 Primary Functions Overview
5.0 - View Status Options (both LCD and Service Terminal Interface)
7.0 - System and Control Options (some functions available via Service Terminal Interface only)
Figure 7 shows an overview of the initial screens available through the LCD interface. For comparable information about the Service Terminal Interface screens, see A.3 - Overview of Menus.
Figure 7 LCD Menu overview
(If any alarms detected) Current Alarm screen (see 5.1 View Active Alarms)
VIEW STATUS SYSTEM AND CONTROL
↑↓ =NEXT ↵ =SELECT
“View Status” selected See Section “System & Control” selected See Section > VIEW STATUS
SYSTEM AND CONTROL
↑↓ =NEXT ↵ =SELECT
↑↓ =NEXT ↵ =SELECT
View Status Menu (All users - no password) See Section
System & Control Menu (Password required) See Section VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS
5.1 5.2 5.3 5.4 5.5
7.2 7.9 7.10

The View Status menu allows any user to view currently active alarms, data stored in the alarm and event logs and the status of all inputs and outputs. The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item.
This section presents step-by-step instructions for each of the following options:
Figure 8 shows the main options available from the View Status menu.
Figure 8 Menu overview - View Status menu
VX.XXX.X PRESS ↵=STATUS/SETUP Main Menu
SYSTEM AND CONTROL
↑↓=NEXT ↵=SELECT View Status
VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS
View Active Alarms View Alarm Log View Event Log

> ALARM RECORD 99/99 DEVICE_1 ALARM CONTACT CLOSED 30-JUN-04 09:29:10 NO STANDBY AVAILABLE
> EVENT RECORD 99/99 SYSTEM USER LOGIN 19-MAY-04 10:07:00 DEVICE_1 HW FORCE ON CONTACT CLOSED 18-MAY-04 06:47:03 DEVICE_4 FORCE OFF CONTACT OPEN 18-MAY-04 05:22:17 DEVICE_3 AUTO CONTACT OPEN 18-MAY-04 04:32:11
INPUT / STATUS > DEVICE_1 ALARM DEVICE_2 NORMAL DEVICE_3 NORMAL DEVICE_4 NORMAL
OUTPUT / STATUS > DEVICE_1 ALARM DEVICE_2 OPERATING DEVICE_3 OPERATING DEVICE_4 OPERATING
See Section 5.5
View Status Options · Opening Screen · View Status options

The Active Alarm screen displays all alarms that are occurring, up to a maximum of 40.
SYSTEM AND CONTROL
A Current Alarm screen appears automatically whenever an alarm occurs—except during setup. This screen can display only the two most recent active alarms. To view any other active alarms, use the View Active Alarms feature.
View Status Menu > VIEW ACTIVE ALARMS
You may view active alarms at any time by using the following steps:
VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS
Active Alarms > ACTIVE ALARM 01/40 DEVICE_1 ALARM CONTACT CLOSED
The Active Alarms screen displays up to 40 records; it shows any active alarm and any Latched alarm that has not been cleared. Examples of alarms include inputs in alarm status and failure of a standby device. When any alarms are present, the Active Alarms screen shows descriptive details for each alarm:
If there are no active alarms, the screen displays the message:
Viewing Additional Screens
There may be up to 40 records of alarm data.
To clear all active alarms, see 7.10 Clear Alarms & Logs. Alarm records are stored in the Alarm Log.
View Status Options · Main Menu

The Alarm Log contains up to 99 records of alarms that have occurred. Records are added to this log as alarms occur.
SYSTEM AND CONTROL
To view the Alarm Log:
VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS
The Alarm Log screen displays up to 99 records showing alarm data, including inputs and outputs in alarm status and failure of a standby device. If the log contains any alarm records, the Alarm Log screen displays details for each alarm:
Alarm Log > ALARM RECORD 99/99 DEVICE_1 ALARM CONTACT CLOSED 30-JUN-04 09:29:10 NO STANDBY AVAILABLE
Table 8 shows conditions that the alarm log records for digital inputs and in the panel itself.
Table 8 Alarm log conditions
SOURCE Digital Input Panel
LOSS OF POWER ALARM SILENCED ALARMS CLEARED STNDBY DEVICE FAILED NO STANDBY AVAILABLE NO RESTART AVAILABLE
CONDITIONS RECORDED
If there are no alarms in the log, the screen displays the message:
Viewing Additional Screens
There may be up to 99 records of alarm data.
The alarm log is stored as a file in the Liebert AC4; it can hold no more than 99 records. When the log is full, the oldest records are deleted from the end of the file as new alarm records are added at the beginning.
You may back up the alarm log file to a remote computer using the Service Terminal Interface, as described in 6.2 Back Up Log Files (Service Terminal Interface only).
To delete all records in the alarm log, see 7.10 Clear Alarms & Logs.
View Status Options · Main Menu · View Status Menu

In addition to alarms, the Liebert AC4 tracks other changes in the Event Log to assist users with verifying operational and troubleshooting problems. Events reflect changes in the status of an input that is defined as an event or the change of state of an output (i.e., manually forced ON or OFF). Other events may be informational, such as a user login. The Event Log contains up to 99 records of events, which are added as they occur.
SYSTEM AND CONTROL
↑↓ =NEXT ↵ =SELECT
VIEW ACTIVE ALARMS VIEW ALARM LOG > VIEW EVENT LOG
To view the Event Log:
Event Log > EVENT RECORD 99/99 SYSTEM USER LOGIN 19-MAY-04 10:07:00 DEVICE_1 HW FORCE ON CONTACT CLOSED 18-MAY-04 06:47:03 DEVICE_4 FORCE OFF CONTACT OPEN 18-MAY-04 05:22:17 DEVICE_3 AUTO CONTACT OPEN 18-MAY-04 04:32:11 DATE AND TIME SET 18-MAY-04 03:11:43 DEVICE_4 FORCE ON CONTACT CLOSED 18-MAY-04 02:34:00
The Event Log screen displays up to 99 recent events. If the log contains any event records, the Event Log screen displays details for each event:
Table 9 shows conditions that the event log records for inputs and outputs and in the panel itself.
Table 9 Event log conditions
SOURCE Digital Input Digital Output Panel
STARTED ON OFF HW FORCE ON AUTO FORCE ON FORCE OFF RESTORED
EVENT NORMAL
AVAILABLE NO STANDBY TESTING
DEVICE AVAILABLE TIME & DATE SET USER LOGIN
CONDITIONS RECORDED
If there are no records in the log, the screen displays the message:
Viewing Additional Screens
There may be up to 99 records of event data.
The event log is stored as a file in the Liebert AC4; it can hold no more than 99 records. When the log is full, the oldest records are deleted from the end of the file as new event records are added at the beginning.
You may back up the event log file to a remote computer using the Service Terminal Interface, as described in 6.2 Back Up Log Files (Service Terminal Interface only).
To delete all records in the event log, see 7.10 Clear Alarms & Logs.
View Status Options · Main Menu · View Status Menu

The Input Status option allows you to view the current status of all four digital inputs.
SYSTEM AND CONTROL
To view the Input Status:
VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG > VIEW INPUT STATUS
VIEW OUTPUT STATUS
The Input Status screen displays the status of each digital input.
The following details appear for digital inputs:
There are three possible states for a digital input, as shown in Table 10.
Table 10 Digital input states
State Description NORMAL In normal state ALARM In alarm status (for an input configured as alarmable) EVENT An event has occurred (for an input configured as an event)
All input data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:

The Output Status option allows you to view the current status of all four outputs.
SYSTEM AND CONTROL
To view the Output Status:
VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS > VIEW OUTPUT STATUS
The Output Status screen displays the status of each digital output.
The following details appear for digital outputs:
DEVICE_2 OPERATING DEVICE_3 OPERATING DEVICE_4 OPERATING
There are eight possible states for a digital output, as shown in Table 11.
Table 11 Digital output states
State Description OPERATING Device operating, or ON STANDBY Device in standby mode ALARM Device in alarm FORCE ON Device forced ON by operator FORCE OFF Device forced OFF by operator HW FORCE ON Device forced ON by hardware switch PENDING Pending delay timer NOT USED Device not used
All output data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:

Silence Alarm & Backup Log Files (Service Terminal Interface)
6.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)
This section describes two features that are available in the Service Terminal Interface:
The Silence Alarm menu item allows you to silence the audible alarm and reset the Common Alarm Relay output if the common alarm is configured to reset with silence.
This menu item is available only through the Service Terminal Interface.
To silence the alarm remotely through the Service Terminal Interface:
Silence Alarm (Service Terminal Interface only)
Silence alarm and reset common alarm relay if common alarm relay is configured to reset with silence alarm
SELECT A NUMBER:1
>ALARM HAS BEEN SILENCED

Silence Alarm & Backup Log Files (Service Terminal Interface)
The Liebert AC4 maintains two types of logs—alarm and event—that may be backed up to a remote computer.
This feature is available only through the Service Terminal Interface.
To back up the alarm or event log:
Backup Log Files - Event Log File (Service Terminal Interface only)
Backup alarm and event log files
1=BACKUP ALARM LOG FILE 2=BACKUP EVENT LOG FILE 3=RETURN TO MAIN MENU
>INITIATE A BACKUP OF EVENT LOG-YES(Y) OR NO(N)? >[N] >[
INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG

Silence Alarm & Backup Log Files (Service Terminal Interface)



Enter filename - for example, event.log
INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG
After backing up a log file, you may want to delete all records in the Liebert AC4 log of that type. See 7.10 Clear Alarms & Logs for details.
Enter folder · Select Xmodem

System and Control Options
The System and Control menu allows you to configure the Liebert AC4—setting up inputs and outputs and system features such as date and time. This menu also provides a vehicle for manually changing the state of an output to ON or OFF, clearing active alarms and deleting records from the Liebert AC4’s alarm and event logs.
The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item and enter new information. Table 12 shows characters that may be entered in labels and values.
Table 12 Valid characters for data entry
Alphanumeric Special characters A-Z, 0-9 space [ ] ^ _ ! " # $ % & ( ) * + - / , . ; < = > @
The System and Control options require a password to prevent unauthorized users from making changes to the system.
This section presents step-by-step instructions for each of the following:
Users must enter a password to access any of the system and control options. The password consists of four characters (see Table 12 for valid characters). (To set up or change the password, see 7.7.1 Change Password.) The default password is AAAA.

To log in:
OVERRIDE OUTPUT CLEAR ALARMS & LOGS ↑↓=NEXT ↵=SELECT
The System and Control Menu appears next, with these options that are described in the following sections:
Main Menu

System and Control Options
Figure 9 shows the main options available from the System & Control menu.
Figure 9 Menu overview - System and Control menu

System & Control menu Setup System selected
System & Control menu Override Output selected
System & Control menu Clear Alarms&Logs selected

SETUP SYSTEM OVERRIDE OUTPUT > CLEAR ALARMS & LOGS
SETUP INPUTS SETUP COMMON ALARM SETUP ZONES SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION
OVERRIDE OUTPUT > DEVICE_1 AUTO DEVICE_2 AUTO DEVICE_3 AUTO DEVICE_4 FORCE ON
CLEAR ACTIVE ALARMS CLEAR ALARM LOG CLEAR EVENT LOG
Setup Inputs Setup Common Alarm Setup Zones Setup Outputs
SELECT OUTPUT > DEVICE_1 NO-OP-E DEVICE_2 NO-ST-E DEVICE_3 NO-NU-D DEVICE_4 NO-NU-D
Setup System Info Setup Operation

CHANGE PASSWORD SET DATE & TIME SETUP SITE ID FACTORY DEFAULTS
AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N HOLD DELAY : 10:00 RESTART : 00:06
Change Password Set Date & Time Setup Site ID Factory Defaults
See Section 7.7.1
See Section 7.7.2
SETUP SITE ID See Section 7.7.3
See Section 7.7.5
18-MAY-02 10:56:30
Opening Screen

System and Control Options
The Setup System screen displays six options that allow you to configure input and output devices, the common alarm, and a variety of system details, such as login password and system date and time:
SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION
The Liebert AC4 has four digital input points that may be configured individually. These inputs may have a wide variety of Liebert or other manufacturers’ equipment connected.
To configure a digital input:
Log In and Choose Setup System
DEVICE_2 NO-AL-NL ↑↓=NEXT ↵=SELECT DEVICE_3 NO-AL-NL DEVICE_4 NO-AL-NL
Select a Digital Input to Configure
Table 13 shows the digital input features you may change, along with the default settings: you may change the name of the input, define it as normally open or closed, and specify it as alarmable or as an event.
Use the steps following Table 13 to change the default settings for any digital input.
Table 13 Default settings - digital inputs
Feature Default Other Options
LABEL DEVICE_1 Any name (up to eight characters)
NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)
ALARM/EVENT AL (Alarmable) EV (Event)
LATCHED L (Latched) / Y (Yes)* NL (Unlatched) / N (No)*
DELAY 00:01 (1 second) Any time (in minutes and seconds) from 00:00 to 99:59
* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.
Settings - Select Input Menu (see Section 7.3)
When configuring an input (see Section 7.3.4)
Unlatched NL (Not Latched) N (No, not latched)
Latched L (Latched) Y (Yes, latched)
Setup System Menu · Select Input Menu

System and Control Options
Each input has a default label (Device_1, Device_2, etc.) that you may change to a more descriptive name for ease in recognizing alarms and events associated with the input. The label may consist of up to eight characters (see Table 12 for valid characters).
The device name assigned through this menu is also displayed for the corresponding output.
Table 14 Input and output labels
Label Applies to:
Device_1 Input 1 Output 1 Device_2 Input 2 Output 2 Device_3 Input 3 Output 3 Device_3 Input 3 Output 3
If the input label is changed, the output will change also.
Each input may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all input points is NO (Normally Open).
If you require an input to be a supervised point, define the input as Normally Closed (NC).
Normally Open / Closed
↑↓ =NO/NC ↵ =END
7.3.3 Define Input as Alarmable or Event
Each input may be defined as Alarmable (AL) or as an Event (EV).
For both types (alarmable and event), user setup determines output control—whether the device that changed status is disabled or kept in operating mode and whether a standby device is set to operate.
By default, all inputs are set up as AL (Alarmable).

System and Control Options
Alarmable input points may be set up in Latched mode (Y), which requires the user to clear the Liebert AC4 alarms after an alarm has occurred, or Unlatched mode (N), in which alarms will automatically clear after a return-to-normal state. The default setting for alarmable inputs is Y (Latched). Any input defined as an event is automatically Unlatched.
An input defined as Latched does not reset automatically after an alarm. It will remain in the triggered position even after the monitored device returns to normal. After an alarm, the user must manually reset Latched inputs, as described in 7.10.1 Clear Active Alarms. This also means that any outputs linked to a Latched digital input will remain triggered until the input is manually reset.
↑↓ =Y/N ↵ =END
An input defined as Unlatched will automatically track the status of the monitored device. No action by the user is required.
Message (if input has been defined as an event)
The only way to reset latched alarms is by clearing active alarms. This step is required to return latched points to their normal state. For details, see 7.10.1 Clear Active Alarms.
7.3.5 Set Up Delay Time
Each input may be set up with a specified time delay between the occurrence of an alarm or event—a monitored device changes state— and any response by the Liebert AC4. This feature can prevent needless responses to transient conditions.
This delay is the amount of time that must elapse before the Liebert AC4 acknowledges the change of state in the monitored device and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies only when a monitored device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.
When the monitored device returns to its normal state, the Liebert AC4 acknowledges the change of state after the delay timer ends its countdown.

System and Control Options
The audible alarm sounds after the Liebert AC4 detects an alarm condition in any input that has been defined as alarmable. Once the alarm is silenced, there are two options:
You might want to reset the common alarm with silence if an external alarm—for example, a horn—is connected to the common alarm output contacts.
You might not want to reset the common alarm contacts (let contacts reflect/track alarms) and simply silence the audible horn.
To change the common alarm setting:
Log In and Choose Setup System
Change to Reset (Y) or Not Reset (N)
SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION
Reset Common Alarm RESET COMMON ALARM WITH SILENCE? N
Setup System Menu

System and Control Options
The Liebert AC4 has two zones that may be used to define different areas—rooms or sections of a room. The Liebert AC4 effectively performs as two separate units, controlling each zone separately, for examply, using a different rotation sequence for devices in each zone.
Each zone may have two to four outputs associated with it. By default, Zone 1 has four associated outputs and Zone 2 has none.
To set up zones:
Log In and Choose Setup System
↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION
ZONE 2 0 ↑↓ =NEXT ↵ =SELECT
Table 15 shows the default number of outputs for each zone.
Table 15 Default zones
Zone Default number of outputs
Message (if too few devices entered)
A message appears if you enter too few or too many devices, as shown at right. Press Escape to return to the Setup Zones menu.
Table 16 shows the possible combinations of outputs for each zone. For example, if Zone 1 has four outputs, then Zone 2 may not be used (0 outputs).
Message (if too many devices entered)
Table 16 Possible combinations - outputs per zone
4 or 3 outputs 0 (not used)
2 outputs 0 (not used) or 2 outputs
0 (not used) 2 or 3 or 4 outputs

System and Control Options
The Liebert AC4 has four outputs that may be configured individually. These outputs correspond to the four numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.
The output name is the same as the input name, as described in 7.3.1 Change Label (Name of Input).
SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT > SETUP OUTPUTS
To configure an output:
Log In and Choose Setup System
SELECT OUTPUT > DEVICE_1 NO-OP-E
Select an Output to Configure
DEVICE_2 NO-ST-E ↑↓=NEXT ↵=SELECT DEVICE_3 NO-NU-D DEVICE_4 NO-NU-D
Table 17 shows digital output features and their default settings: you may define an output as normally open or normally closed, set the device’s mode—operating, standby or not used—and specify whether to disable the device when an alarm occurs.
Use the steps following Table 17 to change the default settings for any digital output.
Table 17 Default settings - digital outputs
Feature Default Other Options
NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)
OP (Operating) ST (Standby) NU (Not Used)
OP (Operating) ST (Standby)
IN ALARM E (Enable) D (Disable)
Each output may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all output points is NO (Normally Open).
Change State SET TO NORMAL OPEN OR NORMAL CLOSE? NO
Setup System Menu · Select Output Menu · Setup Outputs Menu

System and Control Options
Each output may be defined as Operating (OP), Standby (ST), or Not Used (NU). This setting takes precedence over any setting in the override menu (see 7.9 Override Output).
↑↓ =NEXT ↵ =SELECT IN ALARM: ENABLE
Default settings are:
To change the mode:
You may choose whether to Enable or Disable an output when the connected device is in alarm status. The default setting for all output points is Enabled.
Change State in Alarm STATE OF DEVICE IN ALARM: DISABLE
7.6.4 Configure Output for Loss of Power (“Fail-Safe”)
Each output has an associated jumper that can help prevent undesired effects when the controller board loses power. For example, without the proper fail-safe jumper setting, a loss of power might close a switch that is Normally Open (NO)—perhaps shutting off an environmental unit or a fan or closing a valve.
This fail-safe jumper setting is unrelated to configuring an output as Normally Open (NO) or Normally Closed (NC), as described in 7.6.1 Define Output as Normally Open or Normally Closed.
To configure a digital output jumper for a loss of power:
For more information, see 3.2.3 Setting the Digital Output Jumpers.
Setup Outputs Menu · Set Mode · Setup Outputs Menu

System and Control Options
The Setup System Info options allow users to:
To change any Setup System Info features:
Log In and Choose Setup System
SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS > SETUP SYSTEM INFO
Select Setup System Info
Setup System Info Menu
A password is required to access the Liebert AC4’s system and control options, as described in 7.1 Login. The password consists of four characters (see Table 12 for valid characters). The default password is AAAA.
SET DATE & TIME ↑↓=NEXT ↵=SELECT SETUP SITE ID FACTORY DEFAULTS
To change the password:
AAAA ↑↓ =SELECT ↵ =NEXT/END
Reset Password to the Factory Default (“AAAA”)
To reset the password to the factory default of AAAA:
The password should now be AAAA.
Setup System Menu · Change Password

System and Control Options
The Liebert AC4 has a built-in real-time clock that is backed up by an encapsulated lithium battery and set up to adjust automatically for daylight saving time twice a year. The Setup System Info menu allows you to set the current date or time or change the automatic adjustment at any time.
To change the daylight saving time setting or to set the current date or time:
Setup System Info Menu
SETUP SYSTEM INFO CHANGE PASSWORD > SET DATE & TIME
↑↓=NEXT ↵=SELECT SETUP SITE ID FACTORY DEFAULTS
Set Date & Time
Date Day (DD) 0-31 Month (MMM) JAN-DEC Year (YY) 00-99 Time Hour (HR) 00-23 Minutes (MM) 00-59 Seconds (SS) 00-59
Setup System Info Menu
You may enter a Site ID to identify the Liebert AC4’s location, using a name that may consist of up to 40 characters (see Table 12 for valid characters). The Site ID will appear with each alarm.
SETUP SYSTEM INFO CHANGE PASSWORD SET DATE & TIME ↑↓=NEXT ↵=SELECT > SETUP SITE ID
To enter or change the Site ID:
↑↓ =SELECT ↵ =NEXT/END
Setup Site ID

System and Control Options
This operation may be performed only through the Service Terminal Interface. It permits the user to make a copy of the Liebert AC4 configuration settings and save it as a file on the computer connected through the RS232 port. Should the need arise, the user can upload the configuration file from the computer to the Liebert AC4, instead of re-entering the settings manually.
To access these options:
Backup & Upload Configuration File - Backup (Service Terminal Interface only)
Backup from panel saves panel configurations Upload to panel restores panel configurations
Select to backup or upload file
1=BACKUP CONFIGURATION FILE 2=UPLOAD CONFIGURATION FILE 3=RETURN TO SETUP SYSTEM INFO MENU 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU
OR 7. Enter 2 to upload the configuration file from the computer to the Liebert AC4 and proceed to Step 13. NOTE: This will replace the current configuration settings in the Liebert AC4 with the most recent backup.

System and Control Options
Back Up the Configuration File
>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[



Enter filename - for example, AC4_CONF.SAV
Enter folder · Select Xmodem

System and Control Options
Upload the Configuration File
>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[

Enter filename - for example, AC4_CONF.SAV

Select Xmodem · Send button

System and Control Options
Setup System Info Menu
At any time, you may restore all default values for settings in the Liebert AC4 as it was shipped.
SETUP SYSTEM INFO CHANGE PASSWORD SET DATE & TIME ↑↓=NEXT ↵=SELECT SETUP SITE ID > FACTORY DEFAULTS
Factory Defaults RESTORE ALL DEFAULTS ARE YOU SURE? N
The password is the sole exception when reverting to the factory default settings. The password can be reset to the factory default of AAAA through the DIP switches. For details, see Change Password on page 36.
This function, which may be performed only through the Service Terminal Interface, upgrades the Liebert AC4’s firmware to the newest version.
Firmware Update (Service Terminal Interface only)
This command will update the existing firmware
1=PERFORM FIRMWARE UPDATE 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
![Page 48 of the Emerson Surge Protector (AC4) user manual — >PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[](/cdn/reader/4e/4e25649545a47c0e0c4a8dbce3dd3bd8dbc41ed0162326692b0c0dd7b55bece9/images/page-48.webp?w=400)
System and Control Options
To perform the update:
![Emerson Surge Protector (AC4) — >PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[ diagram (page 48)](/cdn/reader/4e/4e25649545a47c0e0c4a8dbce3dd3bd8dbc41ed0162326692b0c0dd7b55bece9/images/rimg-15.webp)
Enter filename - prog###.s19 or flash###.s19
![Emerson Surge Protector (AC4) — >PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[ diagram (page 48)](/cdn/reader/4e/4e25649545a47c0e0c4a8dbce3dd3bd8dbc41ed0162326692b0c0dd7b55bece9/images/rimg-16.webp)
b. In the Send File window, as shown above:
Select Xmodem · Send button

System and Control Options
The Liebert AC4 operation features allow you to set up a rotation sequence to alternate which devices are operating and which are placed on Standby, as well as test devices while in Standby mode and specify what to do when a Standby device goes into alarm as it is powered up. You may also specify delay times after an output changes state, directing the Liebert AC4 to wait before acknowledging inputs or turning an output on or off.
SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO > SETUP OPERATION
To change any operation features:
Log In and Choose Setup System
Setup Operation Menu > AUTO SEQUENCING OFF
STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06
Table 18 shows the default settings for operation options: automatic sequencing, standby testing, failed standby, hold delay and restart.
Table 18 Default settings - operation features
Feature Default Other Options
AUTO SEQUENCING OFF (Deactivated) ON (Activated), 12h (Activated for 12-hour intervals)
STANDBY TESTING OFF (Deactivated) ON (Activated)
FAILED STANDBY N (Deactivated) Y (Activated)
HOLD DELAY 10:00 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59
RESTART 00:06 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59
Setup System Menu · Select Setup Operation

System and Control Options
Use automatic sequencing to set up a schedule for rotation of redundant devices. For example, three devices might be in operating mode while a fourth device is in standby mode. Every two days, the Liebert AC4 returns the standby device to operating mode and places one of the operating devices on standby.
When zones are used, the Liebert AC4 manages the rotation sequence for each zone separately, so each zone might have one device in operating mode and one in standby mode.
Auto sequencing is OFF (deactivated) by default. When auto sequencing is activated (ON or 12h, for a 12-hour interval), the Liebert AC4 cycles devices at the specified interval and time of day as follows:
When more than one device is in Standby mode or turned On, the Liebert AC4 performs the operations in a sequence that rotates the order. For example, in a sequence set up to occur every two days:
To change the auto sequencing settings:
1. From the Setup System Operation Menu, use the arrows ↑↓ to choose Auto Sequencing, then press Enter ↵. 2. In the Activate / Deactivate screen, use the arrows ↑↓ to choose one of three options: a. ON for intervals of every 1 to 99 days, then press Enter ↵ and proceed to Step 3. b. 12h for an interval of every 12 hours, then press Enter ↵ and proceed to Step 4. c. OFF to deactivate auto sequencing, then press Enter ↵ to return to the previous menu. 3. Select the interval for how often the sequencing should occur in the Every 03 Days field. The default is 3 days; valid entries range from 0 to 99 days.
STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06
Activate / Deactivate > AUTO SEQUENCING OFF
Set Interval & Start Time (1- to 99-Day Interval) > AUTO SEQUENCING ON
EVERY 03 DAYS AT 00:00 ↑↓=NEXT ↵=EDIT
Set Start Time (12-Hour Interval)
> AUTO SEQUENCING 12h
Setup Operation Menu

System and Control Options
Standby testing permits scheduling an automatic operational check of devices in Standby mode.
When this feature is activated (ON), the Liebert AC4 tests all devices in Standby mode by putting each device in operating mode for a designated time. You may specify the time of day the testing begins, the duration of the test and the interval between tests. Standby testing is OFF (deactivated) by default.
To change the standby testing settings:
FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06
Change Standby Testing > STANDBY TESTING ON
EVERY 03 DAYS AT 00:00 FOR 10 MIN ↑↓=NEXT ↵=EDIT
The Liebert AC4’s Failed Standby feature determines what happens when an operating device fails and a standby device then becomes an operating unit. A subsequent alarm in the newly operating unit (previously the standby device) results in either restarting the previously operating device that was alarmed or not. This feature specifies whether each device remains in its current state or returns to its previous state of operation.
When this feature is activated (Y), each device returns to its previous state, as Table 19 shows: the newly enabled Standby device is disabled and the previously operating device is returned to Operating mode. The default setting is N (deactivated), meaning that each device remains in its current state: the Standby device remains enabled and the previously operating unit remains disabled.
AUTO SEQUENCING OFF STANDBY TESTING OFF > FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06
Table 19 Failed Standby response
Previous Standby Device (alarm after being enabled)
Change Failed Standby > FAILED STANDBY N
Activated (Y) Disabled Returned to Operating mode
Deactivated (N) Remains enabled Remains disabled
To change the Failed Standby settings:

System and Control Options
After an output changes state, the hold delay timer directs the Liebert AC4 to ignore all inputs in the same zone for the specified time.
AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT > HOLD DELAY : 10:00
This delay is the amount of time that must elapse before the Liebert AC4 acknowledges a change of state in any input. The default is 10 minutes (displayed as 10 MIN : 00 SEC).
The time delay applies only when a monitored output device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.
When the output device returns to its normal state, the Liebert AC4 acknowledges any input change of state immediately.
The hold delay timer also takes effect when the Liebert AC4 is powered up. All alarms are ignored until the hold delay time expires.
The restart delay timer directs the Liebert AC4 to wait a specified time before changing the state of an output. This feature can prevent needless responses to transient conditions.
AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 > RESTART : 00:06
If two or more outputs change state simultaneously, the Liebert AC4 begins a new countdown between each output change of state.
The default is 6 seconds (displayed as 00 MIN : 06 SEC).
↑↓ =NEXT ↵ =EDIT

System and Control Options
The Override Output feature allows you to manually change the state of any digital output to ON or OFF, overriding automatic control by the Liebert AC4 (the default setting for all outputs). This menu also allows you to release the manual override, returning any output to automatic control.
There are two ways to override automatic control of outputs:
After an output is forced manually ON or OFF, it remains in that state until returned to automatic control through this menu.
Table 20 summarizes the four types of control, including the abbreviated message that appears on the LCD and in log reports.
Table 20 Automatic / manual control - output points
AUTO Automatic Controlled by Liebert AC4 (default for all outputs)
FORCE ON Manually ON This output has been forced ON (operating) or OFF via the Override Output menu FORCE OFF Manually OFF
All outputs have been forced ON (operating) via the hardware switch on the circuit board (see Item F - Manual Override Switch (outputs) in 1.6 Controller Board Overview)
HW FORCE ON Manually ON (all outputs)
System & Control Menu
To force an output point ON or OFF or return it to automatic control:
Log In and Choose Override Output
OVERRIDE OUTPUT > DEVICE_1 AUTO DEVICE_2 AUTO ↑↓=NEXT ↵=SELECT DEVICE_3 AUTO DEVICE_4 FORCE ON
The Select Output menu, shown at right, displays the current status of all four outputs.
Turn Output ON or OFF / Return to Automatic

System and Control Options
The Clear Alarms & Logs menu allows you to clear active alarms or delete all records from either of the Liebert AC4 alarm and event logs.

To clear alarms or logs:
Log In and Choose Clear Alarms & Logs
SETUP SYSTEM OVERRIDE OUTPUT > CLEAR ALARMS & LOGS
To clear all active alarms:

CLEAR ALARM LOG CLEAR EVENT LOG ↑↓=NEXT ↵=SELECT
Clear Active Alarms CLEAR ACTIVE ALARMS ARE YOU SURE? N
The alarm log contains up to 99 records of alarms that have occurred. You may want to clear the log after backing up the file or simply to free up space.

To delete all records from the alarm log:
Clear Alarm Log CLEAR ALARM LOG ARE YOU SURE? N
The event log contains up to 99 records of events detected by the Liebert AC4. You may want to clear the log after backing up the file or simply to free up space.

CLEAR ACTIVE ALARMS CLEAR ALARM LOG > CLEAR EVENT LOG
Clear Event Log CLEAR EVENT LOG ARE YOU SURE? N
To delete all records from the event log:

24VAC ±10% of nominal 50/60 Hz 1.3A, 30VA
Dimensions W x D x H, in. (mm) 14-1/4 x 2-3/4 x 12 (361.95 x 69.85 x 304.8)
Weight (Assembled) 7.68 lbs (3.48 kg)
Enclosure Type NEMA 1
Liquid Crystal Display (LCD) Four line, 20 character, backlit
Mounting Surface Building Wall or Structural Member
32°F to 104°F (0°C to 40°C) 0% RH to 95% RH (non-condensing)
A/D Resolution (Analog IN) 12 Bit
Clock Type Real-Time Clock
Clock battery backup type Lithium Cell (non-replaceable)
Clock battery life 7 years, constant, no power
FCC Compliance CFR 47 Part 15
Inputs & Outputs (Quantity)
Digital Inputs (4) Dry Contact Closure 24VDC, 10 mA
Digital Outputs (4) 24VAC, 3A
Common Alarm Outputs (2) 24VAC, 3A

Specifications

The Service Terminal Interface allows access to all functions of the Liebert AC4, including some that are not possible through the LCD interface. This interface is accessible through any computer using a communications program such as Microsoft® Windows® HyperTerminal.
This appendix provides directions for connecting to the Service Terminal Interface, an overview of each type of function and sample screens for each menu available through the Service Terminal Inter- face. References to more detailed instructions about each function are provided.
A.1 COMPARISON OF FUNCTIONS: LCD AND SERVICE TERMINAL INTERFACE
Table 21 lists all functions for viewing and configuring the Liebert AC4 and shows whether they can be performed through the LCD interface and where to find information.
Table 21 Guide to Liebert AC4 functions
Service Terminal screen examples
VIEW STATUS FUNCTIONS
View Active Alarms ✔ ✔ page 19 page 57
View Alarm Log ✔ ✔ page 20 page 58
View Event Log ✔ ✔ page 21 page 59
View Input Status ✔ ✔ page 22 page 59
View Output Status ✔ ✔ page 23 page 60
Silence Alarm (On the LCD, press any key to silence an alarm) ✔ ✔ page 24 page 61
Back Up Log Files — ✔ page 25 page 62
Login ✔ ✔ page 27 page 63
Setup System ✔ ✔ page 29 page 64
Setup Inputs ✔ ✔ page 29 page 65
Setup Common Alarm ✔ ✔ page 32 page 66
Setup Zones ✔ ✔ page 33 page 66
Setup Outputs ✔ ✔ page 34 page 67
Setup System Info ✔ ✔ page 36 page 68
Change Password ✔ ✔ page 36 page 68
Set Date & Time/Automatic Daylight Saving Time ✔ ✔ page 37 page 69
Setup Site ID ✔ ✔ page 37 page 69
Backup and Upload Configuration File — ✔ page 38 page 70
Factory Defaults ✔ ✔ page 41 page 71
Perform Firmware Update — ✔ page 41 page 72
Setup Operation ✔ ✔ page 43 page 73
Override Output ✔ ✔ page 47 page 76
Clear Alarms & Logs ✔ ✔ page 48 page 77
Clear Active Alarms ✔ ✔ page 48 page 77
Clear the Alarm Log ✔ ✔ page 48 page 77
Clear the Event Log ✔ ✔ page 48 page 78

Connecting to the Service Terminal Interface
This section describes how to set up and connect to the Service Terminal Interface. To access the Ser- vice Terminal Interface, you will need:
Refer to following sections for step-by-step instructions to set up a connection (one time) and use that connection to access the Service Terminal Interface:
The instructions in this section refer to the HyperTerminal program—they may vary for other com- munications programs.

Connecting to the Service Terminal Interface
Before connecting to the Service Terminal Interface, you must create a connection and specify the method to be used for connection, as described in the following steps.


Enter a name for the connection - for example, AC4

Specify COM Port Connection 5. In the Connect To window, select COM1 from the Connect Using drop-down list. 6. Click OK. This opens the COM1 Properties window.
COM1 Port Setup 7. In the COM1 Properties window, shown at right, make the following selections:

Choose COM1 · COM1 Properties

Connecting to the Service Terminal Interface
Properties Setup 9. Open the Properties window by clicking on File, then on Properties, as shown below left.


ASCII Setup 11. In the Properties window, click on the ASCII Setup button, shown below left.

The setup is now complete. To use the new connection, proceed to the next section, A.2.2 - Connect to the Service Terminal Interface.
Settings tab · ASCII Setup button

Connecting to the Service Terminal Interface
After creating and setting up a connection, use a communications program such as HyperTerminal to access the Liebert AC4’s Service Terminal Interface.
1. Verify communications connections between the remote computer and the Liebert AC4. Connect a null modem cable from the computer’s COM1 port to the Liebert AC4’s RS232 port (for location, see 3.4 - RS232 Connector). 2. Start the HyperTerminal program—click on the Start button, then on Programs, then Accessories, then Communications, and finally HyperTerminal. 3. Open the Liebert AC4 connection created in A.2.1 - Create a Connection. To do this, click on File, then on Open, as shown below.


Click on the file name - for example, AC4.ht
For more information on the Liebert AC4’s options:

The Main Menu offers choices for viewing the status of the Liebert AC4, silencing the audible alarm and backing up the unit’s log files. It also allows access to the System and Control features, which require a password.
The following shows where to find examples of the Main Menu screens:
Main Menu For sample screens, see:
1=VIEW ACTIVE ALARMS A.4 - View Status Menus
3=VIEW EVENT LOG
4=VIEW INPUT STATUS
5=VIEW OUTPUT STATUS
6=SILENCE ALARM A.5 - Silence Alarm & Back Up Log Files (Service Terminal Interface only) 7=BACKUP LOG FILES
0=SETUP SYSTEM-LOGIN REQUIRED A.6 - Setup Menu
The View Status features are available to all users. This permits all personnel to check on the status of any equipment or location being monitored. These options allow any user to:
Two Main Menu options—Silence Alarm and Backup Log Files—are unique to the Service Terminal Interface. As with the View Status options, these features do not require a password:
The Setup Menu options require a password. Authorized users may:
Overview of Menus

The View Status menu allows any user to view currently active alarms, data stored in the alarm and event logs and the status of all inputs and outputs.
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This section presents Service Terminal Interface screens for options 1 through 5:
ALL RIGHTS RESERVED
MAIN MENU
For sample screens, see:
1=VIEW ACTIVE ALARMS Section A.4.1
2=VIEW ALARM LOG Section A.4.2
3=VIEW EVENT LOG Section A.4.3
4=VIEW INPUT STATUS Section A.4.4
5=VIEW OUTPUT STATUS Section A.4.5
7=BACKUP LOG FILES
0=SETUP SYSTEM-LOGIN REQUIRED
SELECT A NUMBER:1
A.4.1 View Active Alarms
For details on this feature, see 5.1 - View Active Alarms.
Input points/hardware presently in an alarm state
1=REFRESH ACTIVE ALARMS 2=RETURN TO MAIN MENU
SELECT A NUMBER:
View Status Menus · Main Menu · View Active Alarms

For details on this feature, see 5.2 - View Alarm Log.
DEVICE_1 ALARM CONTACT CLOSED 29-AUG-02 09:29:10
NO STANDBY AVAILABLE 29-AUG-02 09:20:10
STANDBY DEVICE FAILED 29-AUG-02 09:19:10
NO RESTART AVAILABLE 29-AUG-02 09:19:10
<ENTER>=MORE <ESC>=EXIT <A>=ALL
DEVICE_2 ALARM CONTACT CLOSED 28-AUG-02 09:29:10
1=REFRESH ALARM LOG 2=RETURN TO MAIN MENU
SELECT A NUMBER:
View Status Menus · View Alarm Log · Alarm history

For details on this feature, see 5.3 - View Event Log.
SYSTEM USER LOGIN 07-MAY-02 10:29:10
DEVICE_1 HW FORCE ON CONTACT CLOSED 07-MAY-02 09:50:10
DEVICE_4 FORCE OFF CONTACT OPEN 07-MAY-02 09:20:10
DEVICE_3 AUTO CONTACT OPEN 07-MAY-02 06:20:10
<ENTER>=MORE <ESC>=EXIT <A>=ALL
DATE AND TIME SET 06-MAY-02 07:10:10
DEVICE_4 FORCE OFF CONTACT CLOSED 07-MAY-02 06:20:10
1=REFRESH EVENT LOG 2=RETURN TO MAIN MENU
SELECT A NUMBER:
A.4.4 View Input Status
For details on this feature, see 5.4 - View Input Status.
Input status from device
DEVICE_1 NORMAL DEVICE_2 ALARM DEVICE_3 EVENT DEVICE_4 ALARM
1=REFRESH INPUT 2=RETURN TO MAIN MENU
SELECT A NUMBER:1

For details on this feature, see 5.5 - View Output Status.
Output status to device
***************************************** OPERATING = OPERATING/ON STANDBY = IN STANDBY MODE ALARM = IN ALARM FORCE ON = FORCE ON BY OPERATOR FORCE OFF = FORCE OFF BY OPERATOR HW FORCE ON = FORCE ON BY HARDWARE SWITCH PENDING = PENDING DELAY TIMER NOT USED = DEVICE NOT USED *****************************************
DEVICE_1 ON ALARM 1 DEVICE_2 ON OPERATING 1 DEVICE_3 OFF STANDBY 1 DEVICE_4 OFF ALARM 1
SELECT A NUMBER:
View Status Menus · View Output Status

Silence Alarm & Back Up Log Files (Service Terminal Interface only)
A.5 SILENCE ALARM & BACK UP LOG FILES (SERVICE TERMINAL INTERFACE ONLY)
This section presents two options from the Main Menu that are available via the Service Terminal Interface only.
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This section presents Service Terminal Interface screens for options 6 and 7:
ALL RIGHTS RESERVED
MAIN MENU
1=VIEW ACTIVE ALARMS
2=VIEW ALARM LOG
3=VIEW EVENT LOG
4=VIEW INPUT STATUS
5=VIEW OUTPUT STATUS For sample screens, see:
6=SILENCE ALARM Section A.5.1
7=BACKUP LOG FILES Section A.5.2
SELECT A NUMBER:1
A.5.1 Silence Alarm (Service Terminal Interface only)
For details on this feature, see 6.1 - Silence Alarm (Service Terminal Interface).
Silence alarm and reset common alarm relay if common alarm relay is configured to reset with silence alarm
SELECT A NUMBER:1
>ALARM HAS BEEN SILENCED
Main Menu · Silence Alarm

Silence Alarm & Back Up Log Files (Service Terminal Interface only)
For details on this feature, see 6.2 - Back Up Log Files (Service Terminal Interface only).
Backup Log Files - Alarm Log File
Backup alarm and event log files
1=BACKUP ALARM LOG FILE 2=BACKUP EVENT LOG FILE 3=RETURN TO MAIN MENU
>INITIATE A BACKUP OF ALARM LOG-YES(Y) OR NO(N)? >[N] >[
INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., ALARM.LOG
Back Up Event Log File
Backup Log Files - Event Log File
Backup alarm and event log files
1=BACKUP ALARM LOG FILE 2=BACKUP EVENT LOG FILE 3=RETURN TO MAIN MENU
>INITIATE A BACKUP OF EVENT LOG-YES(Y) OR NO(N)? >[N] >[
INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG

The Setup menu allows the user to configure the Liebert AC4—setting up inputs, outputs and system features such as date and time, as well as operation options such as a rotation sequence and standy testing. This menu also provides a vehicle for manually changing the state of an output to ON or OFF, clearing active alarms and deleting records from the Liebert AC4’s alarm and event logs.
After connecting to the Service Terminal Interface, the Main Menu appears, as shown below.
ALL RIGHTS RESERVED
MAIN MENU
1=VIEW ACTIVE ALARMS 2=VIEW ALARM LOG 3=VIEW EVENT LOG 4=VIEW INPUT STATUS 5=VIEW OUTPUT STATUS 6=SILENCE ALARM 7=BACKUP LOG FILES 0=SETUP SYSTEM-LOGIN REQUIRED
The System and Control options require a password to prevent unauthorized users from making changes to the system. After choosing 0 in the Main Menu above, the Login Menu appears:
YOU MUST LOGIN TO PERFORM SETUP OR TO MAKE CHANGES
>INVALID PASSWORD, ENTER AGAIN >PRESS <ESC> TO EXIT
![Page 70 of the Emerson Surge Protector (AC4) user manual — >CHANGE LABEL(8 CHARACTERS MAX). >[DEVICE_1] >[ >COMMAND SUCCESSFUL](/cdn/reader/4e/4e25649545a47c0e0c4a8dbce3dd3bd8dbc41ed0162326692b0c0dd7b55bece9/images/page-70.webp?w=400)
This section presents Service Terminal Interface screens for each of the following:
1=SETUP INPUTS Section A.6.1 Configure digital inputs
2=SETUP COMMON ALARM Section A.6.2 Set up the common alarm to reset with silence
3=SETUP ZONES Section A.6.3 Define areas with 2-4 devices each
4=SETUP OUTPUTS Section A.6.4 Configure digital outputs
5=SETUP SYSTEM INFORMATION* Section A.6.5 Set up features such as password and date & time*
6=SETUP OPERATION Section A.6.6 Set up rotation sequence, standby testing
7=OVERRIDE OUTPUT Section A.6.7 Manually override automatic control of outputs
8=CLEAR ALARMS&LOGS Section A.6.8 Clear active alarms; clear alarm and event logs
SELECT A NUMBER:
* Setup System Information features are:
Use the following tips when making changes in the Service Terminal Interface:
Values that may be entered shown in parentheses ( ) Current setting shown in brackets [ ]
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)? >[NO] >[ >COMMAND SUCCESSFUL
Setup Menu · Setup Menu

For details on this feature, see 7.3 - Setup System - Setup Inputs.
Setup input of device
Select input to edit
**************************** NO=NORMALLY OPENED NC=NORMALLY CLOSED
1=DEVICE_1 NO-EV-NL-00:01 2=DEVICE_2 NO-AL-L -00:01 3=DEVICE_3 NC-EV-NL-00:01 4=DEVICE_4 NO-AL-L -00:01 5=RETURN TO SETUP MENU 6=RETURN TO MAIN MENU
NL=NOT LATCHED L =LATCHED
SELECT A NUMBER:1
MIN:SEC=DELAY TIME BEFORE
INPUT WILL TRIGGER
NOTE:EVENT CANNOT BE LATCHED ****************************
>CHANGE LABEL(8 CHARACTERS MAX). >[DEVICE_1] >[ >COMMAND SUCCESSFUL
>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)? >[NO] >[ >COMMAND SUCCESSFUL
>IS INPUT AN ALARM(AL) OR EVENT(EV)? >[AL] >[ >COMMAND SUCCESSFUL
>IS ALARM LATCHED-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL
>DELAY TIME BEFORE TRIGGER (MM:SS)? >[00:01] >[ >COMMAND SUCCESSFUL
Setup Menu · Setup Inputs

For details on this feature, see 7.4 - Setup System - Setup Common Alarm.
Select if the common alarm relay contact is to reset with silence alarm CURRENT SETTING
N 1=SETUP COMMON ALARM 2=RETURN TO SETUP MENU 3=RETURN TO MAIN MENU
>RESET COMMON ALARM WITH SILENCE-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL
For details on this feature, see 7.5 - Setup System - Setup Zones.
Select zones and number
of devices in the zone
1=ZONE 1 2 2=ZONE 2 2 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
># DEVICES IN ZONE 1 >[2] >[ >COMMAND SUCCESSFUL
Setup Menu · Setup Common Alarm · Setup Zones

For details on this feature, see 7.6 - Setup System - Setup Outputs.
Setup output of device
Select output to edit
OUTPUT DEFINITION ******************************************* NO=NORMALLY OPENED 1=DEVICE_1 NO-OP-E NC=NORMALLY CLOSED 2=DEVICE_2 NO-ST-E 3=DEVICE_3 NO-NU-D OP=OPERATING/ON 4=DEVICE_4 NO-NU-D ST=STANDBY MODE 5=RETURN TO SETUP MENU NU=NOT USED 6=RETURN TO MAIN MENU D=DISABLE DEVICE ON AN ALARM CONDITION SELECT A NUMBER:1 E=LEAVE DEVICE OPERATING ON ALARM CONDITION *******************************************
>SET TO NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC) >[NO] >[ >COMMAND SUCCESSFUL
>DEVICE_1 TO OPERATING/ON(OP), STANDBY MODE(ST), NOT USED(NU) >[OP] >[ >COMMAND SUCCESSFUL
>DEVICE_1 TO ENABLE(E) OR DISABLE(D) DEVICE ON ALARM >[E] >[ >COMMAND SUCCESSFUL
Setup Menu · Setup Outputs

This section presents Service Terminal Interface screens for choices 1 through 9 in the Setup System Information menu shown below. For details on this topic, see 7.7 - Setup System - Setup System Info.
1=CHANGE PASSWORD
2=SET DATE & TIME
3=SETUP SITE ID
4=BACKUP & UPLOAD CONFIGURATION FILE
5=RESTORE PANEL TO FACTORY DEFAULTS
6=PERFORM FIRMWARE UPDATE
7=RETURN TO SETUP MENU
8=RETURN TO MAIN MENU
SELECT A NUMBER:
For details on this feature, see 7.7.1 - Change Password.
1=CHANGE PASSWORD 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
>ENTER ORIGINAL PASSWORD(MUST BE 4 CHARACTERS). >
>ENTER NEW PASSWORD(MUST BE 4 CHARACTERS). >
>ENTER NEW PASSWORD AGAIN FOR CONFIRMATION. >
>PASSWORD CHANGE SUCCESSFUL

For details on this feature, see 7.7.2 - Set Date & Time/Automatic Daylight Saving Time.
Set Date & Time
CURRENT DATE & TIME DST 28-AUG-04 14:45:10 Y 1=SET DATE & TIME 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
>SET DATE & TIME(DD-MON-YY HR:MM:SS) >[28-AUG-02 14:45:10] >[ >COMMAND SUCCESSFUL
>ENABLE DAYLIGHT SAVINGS TIME-YES(Y) OR NO(N)? >[Y] >[ >COMMAND SUCCESSFUL
For details on this feature, see 7.7.3 - Setup Site ID.
Define name to reference panel
1=SETUP SITE ID 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
>ENTER SITE ID NAME(40 CHARACTERS MAX). >[] >[ >COMMAND SUCCESSFUL
Setup Menu · Setup Site ID

For details on this feature, see 7.7.4 - Backup and Upload Configuration File (Service Termi- nal Interface only).
Backup & Upload Configuration File - Backup
Backup from panel saves panel configurations Upload to panel restores panel configurations
Select to backup or upload file
1=BACKUP CONFIGURATION FILE 2=UPLOAD CONFIGURATION FILE 3=RETURN TO SETUP SYSTEM INFO MENU 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU
>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[
INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME,,E.G., AC4_CONF.SAV
Setup Menu

Backup & Upload Configuration File - Upload
Backup from panel saves panel configurations Upload to panel restores panel configurations
Select to backup or upload file
1=BACKUP CONFIGURATION FILE 2=UPLOAD CONFIGURATION FILE 3=RETURN TO SETUP SYSTEM INFO MENU 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU
>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[
INSTRUCTIONS TO PERFORM UPLOAD: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT SEND FILE - ENTER FILE NAME-CONFIGURATION FILE LOCATION & NAME,E.G., AC4_CONF.SAV - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT SEND BUTTON
Factory Defaults
For details on this feature, see 7.7.5 - Factory Defaults.
This command restores all panel information to factory settings
1=RESTORE FACTORY DEFAULTS 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
>RESTORE THE PANEL TO FACTORY SETTINGS-YES(Y) OR NO(N)? >[N] [ >COMMAND SUCCESSFUL
Setup Menu · Factory Defaults

For details on this feature, see 7.7.6 - Perform Firmware Update (Service Terminal Interface only).
This command will update the existing firmware
1=PERFORM FIRMWARE UPDATE 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU
>PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[
INSTRUCTIONS TO PERFORM FIRMWARE UPDATE: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT SEND FILE - ENTER FILE NAME-FIRMWARE FILE LOCATION & NAME,E.G., PROG####.S19 - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT SEND BUTTON
>CHECKSUM IS >PROGRAM VERSION >WAITING TO SEND FLASH FILE >DONE
Setup Menu · Firmware Update
![Page 79 of the Emerson Surge Protector (AC4) user manual — >AT >[00:00] >[ >COMMAND SUCCESSFUL](/cdn/reader/4e/4e25649545a47c0e0c4a8dbce3dd3bd8dbc41ed0162326692b0c0dd7b55bece9/images/page-79.webp?w=400)
For details on this feature, see 7.8 - Setup Operation.
For details on this feature, see 7.8.1 - Turn Automatic Sequencing On or Off.
Setup Operation - Auto Sequencing
Select operation to edit
1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU
>AUTO SEQUENCING- N FOR ON, F FOR OFF >[N] >[N] >COMMAND SUCCESSFUL
>EVERY ## DAYS (.5 FOR 12 HOUR) >[03] DAYS >[ >COMMAND SUCCESSFUL
Setup Menu
![Page 80 of the Emerson Surge Protector (AC4) user manual — >EVERY ## DAYS >[03] DAYS >[ >COMMAND SUCCESSFUL](/cdn/reader/4e/4e25649545a47c0e0c4a8dbce3dd3bd8dbc41ed0162326692b0c0dd7b55bece9/images/page-80.webp?w=400)
For details on this feature, see 7.8.2 - Turn Standby Testing On or Off.
Setup Operation - Standby Testing
Select operation to edit
1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU
>STANDBY TESTING- N FOR ON, F FOR OFF >[N] >[N] >COMMAND SUCCESSFUL
>AT >[00:00] >[ >COMMAND SUCCESSFUL
>FOR >[10] MIN >[ >COMMAND SUCCESSFUL
Setup Menu

For details on this feature, see 7.8.3 - Specify Failed Standby Response.
Setup Operation - Failed Standby
Select operation to edit
1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU
>IF FAILED STANDBY,IN SAME FAILED ZONE, ENABLE A DISABLED UNIT-YES(Y) OR NO(N)? >[N] >[Y] >COMMAND SUCCESSFUL
For details on this feature, see 7.8.4 - Specify Hold Delay Time.
Setup Operation - Hold Delay
Select operation to edit
1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU
>HOLD DELAY (MM:SS) > [10:00] >[ >COMMAND SUCCESSFUL
Setup Menu

For details on this feature, see 7.8.5 - Specify Restart Time.
Setup Operation - Restart Delay
Select operation to edit
1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU
>DELAY BEFORE STARTUP UNIT(MM:SS)? >[00:06] >[ >COMMAND SUCCESSFUL
A.6.7 Override Output
For details on this feature, see 7.9 - Override Output.
Select output to override
1=DEVICE_1 AUTO ******************************** 2=DEVICE_2 AUTO AUTO = CONTROL BY PANEL 3=DEVICE_3 FORCE ON FORCE ON = FORCE ON BY OPERATOR 4=DEVICE_4 FORCE ON FORCE OFF= FORCE OFF BY OPERATOR 5=RETURN TO SETUP MENU ******************************** 6=RETURN TO MAIN MENU
>OVERRIDE OUTPUT DEVICE_1-AUTO(2),FORCE ON(1),FORCE OFF(0). >[2] >[ >COMMAND SUCCESSFUL

For details on this topic, see 7.10 - Clear Alarms & Logs.
For details on this feature, see 7.10.1 - Clear Active Alarms.
Clear Alarms & Logs - Clear Active Alarms
Clear active alarms or log records
Select the log to clear
1=CLEAR ACTIVE ALARMS 2=CLEAR ALARM LOG 3=CLEAR EVENT LOG 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU
>CLEAR ALL THE ACTIVE ALARMS-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL
For details on this feature, see 7.10.2 - Clear the Alarm Log.
Clear Alarms & Logs - Clear the Alarm Log
Clear active alarms or log records
Select the log to clear
1=CLEAR ACTIVE ALARMS 2=CLEAR ALARM LOG 3=CLEAR EVENT LOG 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU
>CLEAR ALL RECORDS IN THE ALARM LOG-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL
Setup Menu

For details on this feature, see 7.10.3 - Clear the Event Log.
Clear Alarms & Logs - Clear the Event Log
Clear active alarms or log records
Select the log to clear
1=CLEAR ACTIVE ALARMS 2=CLEAR ALARM LOG 3=CLEAR EVENT LOG 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU
>CLEAR ALL RECORDS IN THE EVENT LOG-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL
Setup Menu

Specifications

Specifications

Specifications



Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™
Technical Support / Service
Web Site www.liebert.com
from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Monitoring liebert.monitoring@emerson.com
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
Three-Phase UPS & Power Systems
Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2012 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center
Philippines +63 2 687 6615 Fax: +63 2 730 9572
Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com
Embedded Computing Embedded Power
Racks & Integrated Cabinets Services
Power Switching & Controls Precision Cooling
Infrastructure Management & Monitoring
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2012 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.