Emerson Surge Protector (AC4)

89 pages·2.9 MB·Surge Protector·PDF·ENDEFRITNLJA
Emerson Surge Protector (AC4)
Table of Contents 176 sections 1.0 Introduction · 1.1 Methods of Viewing and Configuring the Liebert AC4 · 1.2 Data Logs · 1.3 Available Alarms · … ShowHide
1.0 Introductionp.71.1 Methods of Viewing and Configuring the Liebert AC4p.71.2 Data Logsp.71.3 Available Alarmsp.71.4 Outside Enclosure Overviewp.8Figure 1 Liebert AC4 enclosure—external featuresp.8Figure 2 Liebert AC4 enclosure—internal featuresp.81.5 Typical Configurationp.9Figure 3 Typical Configurationp.91.6 Controller Board Overviewp.10Table 1 Controller board componentsp.101.7 LED Indicatorsp.12Table 2 LED indicators summaryp.121.8 Typical Sequencep.13Figure 4 Example of typical sequencep.132.0 Installationp.142.1 Installation Considerationsp.142.1.1 Unpacking and Preliminary Inspectionp.14Packing Contentsp.14Table 3 Packing manifestp.142.2 Surface-Mounting the Liebert AC4p.15Required toolsp.152.2.1 Mounting the Panelp.15Figure 5 Mounting dimensionsp.152.3 Flush-Mounting the Liebert AC4p.16Required toolsp.162.3.1 Mounting the Panelp.162.4 Connect Power to the Liebert AC4p.17Figure 6 Electrical connections to panelp.173.0 Wiring and Connectionsp.183.1 Wiring Specificationsp.18Table 4 Wiring specificationsp.183.2 Connecting Digital Inputs and Outputsp.19Connecting Liebert Precision Cooling Unitsp.193.2.1 Connecting Digital Inputsp.193.2.2 Connecting Digital Outputsp.203.2.3 Setting the Digital Output Jumpersp.20Table 5 Digital output jumper settingsp.203.3 Connecting Common Alarm Outputsp.213.4 RS232 Connectorp.214.0 Overview of Menusp.22Table 6 Guide to Liebert AC4 functionsp.224.1 Opening Screen Overviewp.234.2 Main Menu Overviewp.23Table 7 Primary Functions Overviewp.234.3 LCD Menu Overviewp.23Figure 7 LCD Menu overviewp.235.0 View Status Optionsp.24Figure 8 Menu overview - View Status menup.245.1 View Active Alarmsp.255.1.1 Active Alarmsp.25Viewing Additional Screensp.25Clearing Active Alarmsp.255.2 View Alarm Logp.265.2.1 Alarm Logp.26Table 8 Alarm log conditionsp.26Viewing Additional Screensp.265.2.2 Backing Up the Alarm Log (Service Terminal Interface only)p.265.3 View Event Logp.275.3.1 Event Logp.27Table 9 Event log conditionsp.27Viewing Additional Screensp.275.3.2 Backing Up the Event Log (Service Terminal Interface only)p.275.4 View Input Statusp.285.4.1 Input Statusp.28Table 10 Digital input statesp.28Viewing Additional Input Datap.285.5 View Output Statusp.295.5.1 Output Statusp.29Table 11 Digital output statesp.29Viewing Additional Output Datap.296.0 Silence Alarm & Backup Log Files (Service Terminal Interface)p.306.1 Silence Alarm (Service Terminal Interface)p.306.2 Back Up Log Files (Service Terminal Interface only)p.317.0 System and Control Optionsp.33Table 12 Valid characters for data entryp.337.1 Loginp.33Figure 9 Menu overview - System and Control menup.347.2 Setup System - Overviewp.357.3 Setup System - Setup Inputsp.35Table 13 Default settings - digital inputsp.357.3.1 Change Label (Name of Input)p.36Table 14 Input and output labelsp.367.3.2 Define Input as Normally Open or Normally Closedp.367.3.3 Define Input as Alarmable or Eventp.367.3.4 Set Up Alarmable Inputs in Latched or Unlatched Modep.377.3.5 Set Up Delay Timep.377.4 Setup System - Setup Common Alarmp.387.5 Setup System - Setup Zonesp.397.5.1 Set Up a Zonep.39Table 15 Default zonesp.39Table 16 Possible combinations - outputs per zonep.397.6 Setup System - Setup Outputsp.40Table 17 Default settings - digital outputsp.407.6.1 Define Output as Normally Open or Normally Closedp.407.6.2 Define Operating or Standby Modep.417.6.3 Enable or Disable an Output Device in Alarm Statusp.417.6.4 Configure Output for Loss of Power (“Fail-Safe”)p.417.7 Setup System - Setup System Infop.427.7.1 Change Passwordp.42Change the Passwordp.42Reset Password to the Factory Default (“AAAA”)p.427.7.2 Set Date & Time/Automatic Daylight Saving Timep.437.7.3 Setup Site IDp.437.7.4 Backup and Upload Configuration File (Service Terminal Interface only)p.447.7.5 Factory Defaultsp.477.7.6 Perform Firmware Update (Service Terminal Interface only)p.477.8 Setup Operationp.49Table 18 Default settings - operation featuresp.497.8.1 Turn Automatic Sequencing On or Offp.507.8.2 Turn Standby Testing On or Offp.517.8.3 Specify Failed Standby Responsep.51Table 19 Failed Standby responsep.517.8.4 Specify Hold Delay Timep.527.8.5 Specify Restart Timep.527.9 Override Outputp.53Table 20 Automatic / manual control - output pointsp.537.10 Clear Alarms & Logsp.547.10.1 Clear Active Alarmsp.547.10.2 Clear the Alarm Logp.547.10.3 Clear the Event Logp.548.0 Specificationsp.558.1 Liebert AC4 Specificationsp.55Appendix A - Service Terminal Interfacep.57A.1 Comparison of Functions: LCD and Service Terminal Interfacep.57Table 21 Guide to Liebert AC4 functionsp.57A.2 Connecting to the Service Terminal Interfacep.58A.2.1 Create a Connectionp.59Specify COM Port Connectionp.59COM1 Port Setupp.59Properties Setupp.60ASCII Setupp.60A.2.2 Connect to the Service Terminal Interfacep.61A.3 Overview of Menusp.62A.3.1 View Status Overviewp.62A.3.2 Silence Alarm and Backup Log Filesp.62A.3.3 Setup Menu Overviewp.62A.4 View Status Menusp.63Main Menup.63A.4.1 View Active Alarmsp.63A.4.2 View Alarm Logp.64A.4.3 View Event Logp.65A.4.4 View Input Statusp.65A.4.5 View Output Statusp.66A.5 Silence Alarm & Back Up Log Files (Service Terminal Interface only)p.67Main Menup.67A.5.1 Silence Alarm (Service Terminal Interface only)p.67A.5.2 Back Up Log Files (Service Terminal Interface only)p.68Back Up Alarm Log Filep.68Back Up Event Log Filep.68A.6 Setup Menup.69Main Menup.69Login Menup.69Setup Menup.70A.6.1 Setup Inputsp.71A.6.2 Setup Common Alarmp.72A.6.3 Setup Zonesp.72A.6.4 Setup Outputsp.73A.6.5 Setup System Infop.74Change Passwordp.74Set Date & Time/Automatic Daylight Saving Timep.75Setup Site IDp.75Backup and Upload Configuration File (Service Terminal Interface only)p.76Factory Defaultsp.77Firmware Update (Service Terminal Interface only)p.78A.6.6 Setup Operationp.79Auto Sequencingp.79Standby Testingp.80Failed Standbyp.81Hold Delayp.81Restart Delayp.82A.6.7 Override Outputp.82A.6.8 Clear Alarms & Logsp.83Clear Active Alarmsp.83Clear the Alarm Logp.83Clear the Event Logp.84
Page 1 of the Emerson Surge Protector (AC4) user manual
Page 1 · click to enlarge
Page 1
Emerson Surge Protector (AC4) diagram (page 1)
Fig. 1
Page 2 of the Emerson Surge Protector (AC4) user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Emerson Surge Protector (AC4) user manual
Page 3 of the Emerson Surge Protector (AC4) user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

1.0 Introductionp.71.1 Methods of Viewing and Configuring the Liebert AC4p.71.2 Data Logsp.71.3 Available Alarmsp.71.4 Outside Enclosure Overviewp.8Figure 1 Liebert AC4 enclosure—external featuresp.8Figure 2 Liebert AC4 enclosure—internal featuresp.81.5 Typical Configurationp.9Figure 3 Typical Configurationp.91.6 Controller Board Overviewp.10Table 1 Controller board componentsp.101.7 LED Indicatorsp.12Table 2 LED indicators summaryp.121.8 Typical Sequencep.13Figure 4 Example of typical sequencep.132.0 Installationp.142.1 Installation Considerationsp.142.1.1 Unpacking and Preliminary Inspectionp.14Packing Contentsp.14Table 3 Packing manifestp.142.2 Surface-Mounting the Liebert AC4p.15Required toolsp.152.2.1 Mounting the Panelp.15Figure 5 Mounting dimensionsp.152.3 Flush-Mounting the Liebert AC4p.16Required toolsp.162.3.1 Mounting the Panelp.162.4 Connect Power to the Liebert AC4p.17Figure 6 Electrical connections to panelp.173.0 Wiring and Connectionsp.183.1 Wiring Specificationsp.18Table 4 Wiring specificationsp.183.2 Connecting Digital Inputs and Outputsp.19Connecting Liebert Precision Cooling Unitsp.193.2.1 Connecting Digital Inputsp.193.2.2 Connecting Digital Outputsp.203.2.3 Setting the Digital Output Jumpersp.20Table 5 Digital output jumper settingsp.203.3 Connecting Common Alarm Outputsp.213.4 RS232 Connectorp.214.0 Overview of Menusp.22Table 6 Guide to Liebert AC4 functionsp.224.1 Opening Screen Overviewp.234.2 Main Menu Overviewp.23Table 7 Primary Functions Overviewp.234.3 LCD Menu Overviewp.23Figure 7 LCD Menu overviewp.235.0 View Status Optionsp.24Figure 8 Menu overview - View Status menup.245.1 View Active Alarmsp.255.1.1 Active Alarmsp.25Viewing Additional Screensp.25Clearing Active Alarmsp.255.2 View Alarm Logp.265.2.1 Alarm Logp.26Table 8 Alarm log conditionsp.26Viewing Additional Screensp.265.2.2 Backing Up the Alarm Log (Service Terminal Interface only)p.265.3 View Event Logp.275.3.1 Event Logp.27Table 9 Event log conditionsp.27Viewing Additional Screensp.275.3.2 Backing Up the Event Log (Service Terminal Interface only)p.275.4 View Input Statusp.285.4.1 Input Statusp.28Table 10 Digital input statesp.28Viewing Additional Input Datap.285.5 View Output Statusp.295.5.1 Output Statusp.29Table 11 Digital output statesp.29Viewing Additional Output Datap.296.0 Silence Alarm & Backup Log Files (Service Terminal Interface)p.306.1 Silence Alarm (Service Terminal Interface)p.306.2 Back Up Log Files (Service Terminal Interface only)p.317.0 System and Control Optionsp.33Table 12 Valid characters for data entryp.337.1 Loginp.33Figure 9 Menu overview - System and Control menup.347.2 Setup System - Overviewp.357.3 Setup System - Setup Inputsp.35Table 13 Default settings - digital inputsp.357.3.1 Change Label (Name of Input)p.36Table 14 Input and output labelsp.367.3.2 Define Input as Normally Open or Normally Closedp.367.3.3 Define Input as Alarmable or Eventp.367.3.4 Set Up Alarmable Inputs in Latched or Unlatched Modep.377.3.5 Set Up Delay Timep.377.4 Setup System - Setup Common Alarmp.387.5 Setup System - Setup Zonesp.397.5.1 Set Up a Zonep.39Table 15 Default zonesp.39Table 16 Possible combinations - outputs per zonep.397.6 Setup System - Setup Outputsp.40Table 17 Default settings - digital outputsp.407.6.1 Define Output as Normally Open or Normally Closedp.407.6.2 Define Operating or Standby Modep.417.6.3 Enable or Disable an Output Device in Alarm Statusp.417.6.4 Configure Output for Loss of Power (“Fail-Safe”)p.417.7 Setup System - Setup System Infop.427.7.1 Change Passwordp.42Change the Passwordp.42Reset Password to the Factory Default (“AAAA”)p.427.7.2 Set Date & Time/Automatic Daylight Saving Timep.437.7.3 Setup Site IDp.437.7.4 Backup and Upload Configuration File (Service Terminal Interface only)p.447.7.5 Factory Defaultsp.477.7.6 Perform Firmware Update (Service Terminal Interface only)p.477.8 Setup Operationp.49Table 18 Default settings - operation featuresp.497.8.1 Turn Automatic Sequencing On or Offp.507.8.2 Turn Standby Testing On or Offp.517.8.3 Specify Failed Standby Responsep.51Table 19 Failed Standby responsep.517.8.4 Specify Hold Delay Timep.527.8.5 Specify Restart Timep.527.9 Override Outputp.53Table 20 Automatic / manual control - output pointsp.537.10 Clear Alarms & Logsp.547.10.1 Clear Active Alarmsp.547.10.2 Clear the Alarm Logp.547.10.3 Clear the Event Logp.548.0 Specificationsp.558.1 Liebert AC4 Specificationsp.55Appendix A - Service Terminal Interfacep.57A.1 Comparison of Functions: LCD and Service Terminal Interfacep.57Table 21 Guide to Liebert AC4 functionsp.57A.2 Connecting to the Service Terminal Interfacep.58A.2.1 Create a Connectionp.59Specify COM Port Connectionp.59COM1 Port Setupp.59Properties Setupp.60ASCII Setupp.60A.2.2 Connect to the Service Terminal Interfacep.61A.3 Overview of Menusp.62A.3.1 View Status Overviewp.62A.3.2 Silence Alarm and Backup Log Filesp.62A.3.3 Setup Menu Overviewp.62A.4 View Status Menusp.63Main Menup.63A.4.1 View Active Alarmsp.63A.4.2 View Alarm Logp.64A.4.3 View Event Logp.65A.4.4 View Input Statusp.65A.4.5 View Output Statusp.66A.5 Silence Alarm & Back Up Log Files (Service Terminal Interface only)p.67Main Menup.67A.5.1 Silence Alarm (Service Terminal Interface only)p.67A.5.2 Back Up Log Files (Service Terminal Interface only)p.68Back Up Alarm Log Filep.68Back Up Event Log Filep.68A.6 Setup Menup.69Main Menup.69Login Menup.69Setup Menup.70A.6.1 Setup Inputsp.71A.6.2 Setup Common Alarmp.72A.6.3 Setup Zonesp.72A.6.4 Setup Outputsp.73A.6.5 Setup System Infop.74Change Passwordp.74Set Date & Time/Automatic Daylight Saving Timep.75Setup Site IDp.75Backup and Upload Configuration File (Service Terminal Interface only)p.76Factory Defaultsp.77Firmware Update (Service Terminal Interface only)p.78A.6.6 Setup Operationp.79Auto Sequencingp.79Standby Testingp.80Failed Standbyp.81Hold Delayp.81Restart Delayp.82A.6.7 Override Outputp.82A.6.8 Clear Alarms & Logsp.83Clear Active Alarmsp.83Clear the Alarm Logp.83Clear the Event Logp.84
Page 4 of the Emerson Surge Protector (AC4) user manual
Page 4 · click to enlarge
Page 4

6.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE) 6.1 Silence Alarm (Service Terminal Interface) 24 6.2 Back Up Log Files (Service Terminal Interface only) 25

7.0 SYSTEM AND CONTROL OPTIONS 7.1 Login 27 7.2 Setup System - Overview 29 7.3 Setup System - Setup Inputs 29 7.3.1 Change Label (Name of Input) 30 7.3.2 Define Input as Normally Open or Normally Closed 30 7.3.3 Define Input as Alarmable or Event 30 7.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode 31 7.3.5 Set Up Delay Time 31 7.4 Setup System - Setup Common Alarm 32 7.5 Setup System - Setup Zones 33 7.5.1 Set Up a Zone 33 7.6 Setup System - Setup Outputs 34 7.6.1 Define Output as Normally Open or Normally Closed 34 7.6.2 Define Operating or Standby Mode 35 7.6.3 Enable or Disable an Output Device in Alarm Status 35 7.6.4 Configure Output for Loss of Power (“Fail-Safe”) 35 7.7 Setup System - Setup System Info 36 7.7.1 Change Password 36 7.7.2 Set Date & Time/Automatic Daylight Saving Time 37 7.7.3 Setup Site ID 37 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) 38 7.7.5 Factory Defaults 41 7.7.6 Perform Firmware Update (Service Terminal Interface only) 41 7.8 Setup Operation 43 7.8.1 Turn Automatic Sequencing On or Off 44 7.8.2 Turn Standby Testing On or Off 45 7.8.3 Specify Failed Standby Response 45 7.8.4 Specify Hold Delay Time 46 7.8.5 Specify Restart Time 46 7.9 Override Output 47 7.10 Clear Alarms & Logs 48 7.10.1 Clear Active Alarms 48 7.10.2 Clear the Alarm Log 48 7.10.3 Clear the Event Log 48

8.0 SPECIFICATIONS 8.1 Liebert AC4 Specifications 49

Page 5 of the Emerson Surge Protector (AC4) user manual
Page 5 · click to enlarge
Page 5

APPENDIX A - SERVICE TERMINAL INTERFACE 51 A.1 Comparison of Functions: LCD and Service Terminal Interface 51 A.2 Connecting to the Service Terminal Interface 52 A.2.1 Create a Connection 53 A.2.2 Connect to the Service Terminal Interface 55 A.3 Overview of Menus 56 A.3.1 View Status Overview 56 A.3.2 Silence Alarm and Backup Log Files 56 A.3.3 Setup Menu Overview 56 A.4 View Status Menus 57 A.4.1 View Active Alarms 57 A.4.2 View Alarm Log 58 A.4.3 View Event Log 59 A.4.4 View Input Status 59 A.4.5 View Output Status 60 A.5 Silence Alarm & Back Up Log Files (Service Terminal Interface only) 61 A.5.1 Silence Alarm (Service Terminal Interface only) 61 A.5.2 Back Up Log Files (Service Terminal Interface only) 62 A.6 Setup Menu 63 A.6.1 Setup Inputs 65 A.6.2 Setup Common Alarm 66 A.6.3 Setup Zones 66 A.6.4 Setup Outputs 67 A.6.5 Setup System Info 68 A.6.6 Setup Operation 73 A.6.7 Override Output 76 A.6.8 Clear Alarms & Logs 77

Page 6 of the Emerson Surge Protector (AC4) user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

1.0 Introductionp.71.1 Methods of Viewing and Configuring the Liebert AC4p.71.2 Data Logsp.71.3 Available Alarmsp.71.4 Outside Enclosure Overviewp.8Figure 1 Liebert AC4 enclosure—external featuresp.8Figure 2 Liebert AC4 enclosure—internal featuresp.81.5 Typical Configurationp.9Figure 3 Typical Configurationp.91.6 Controller Board Overviewp.10Table 1 Controller board componentsp.101.7 LED Indicatorsp.12Table 2 LED indicators summaryp.121.8 Typical Sequencep.13Figure 4 Example of typical sequencep.132.0 Installationp.142.1 Installation Considerationsp.142.1.1 Unpacking and Preliminary Inspectionp.14Packing Contentsp.14Table 3 Packing manifestp.142.2 Surface-Mounting the Liebert AC4p.15Required toolsp.152.2.1 Mounting the Panelp.15Figure 5 Mounting dimensionsp.152.3 Flush-Mounting the Liebert AC4p.16Required toolsp.162.3.1 Mounting the Panelp.162.4 Connect Power to the Liebert AC4p.17Figure 6 Electrical connections to panelp.173.0 Wiring and Connectionsp.183.1 Wiring Specificationsp.18Table 4 Wiring specificationsp.183.2 Connecting Digital Inputs and Outputsp.19Connecting Liebert Precision Cooling Unitsp.193.2.1 Connecting Digital Inputsp.193.2.2 Connecting Digital Outputsp.203.2.3 Setting the Digital Output Jumpersp.20Table 5 Digital output jumper settingsp.203.3 Connecting Common Alarm Outputsp.213.4 RS232 Connectorp.214.0 Overview of Menusp.22Table 6 Guide to Liebert AC4 functionsp.224.1 Opening Screen Overviewp.234.2 Main Menu Overviewp.23Table 7 Primary Functions Overviewp.234.3 LCD Menu Overviewp.23Figure 7 LCD Menu overviewp.235.0 View Status Optionsp.24Figure 8 Menu overview - View Status menup.245.1 View Active Alarmsp.255.1.1 Active Alarmsp.25Viewing Additional Screensp.25Clearing Active Alarmsp.255.2 View Alarm Logp.265.2.1 Alarm Logp.26Table 8 Alarm log conditionsp.26Viewing Additional Screensp.265.2.2 Backing Up the Alarm Log (Service Terminal Interface only)p.265.3 View Event Logp.275.3.1 Event Logp.27Table 9 Event log conditionsp.27Viewing Additional Screensp.275.3.2 Backing Up the Event Log (Service Terminal Interface only)p.275.4 View Input Statusp.285.4.1 Input Statusp.28Table 10 Digital input statesp.28Viewing Additional Input Datap.285.5 View Output Statusp.295.5.1 Output Statusp.29Table 11 Digital output statesp.29Viewing Additional Output Datap.296.0 Silence Alarm & Backup Log Files (Service Terminal Interface)p.306.1 Silence Alarm (Service Terminal Interface)p.306.2 Back Up Log Files (Service Terminal Interface only)p.317.0 System and Control Optionsp.33Table 12 Valid characters for data entryp.337.1 Loginp.33Figure 9 Menu overview - System and Control menup.347.2 Setup System - Overviewp.357.3 Setup System - Setup Inputsp.35Table 13 Default settings - digital inputsp.357.3.1 Change Label (Name of Input)p.36Table 14 Input and output labelsp.367.3.2 Define Input as Normally Open or Normally Closedp.367.3.3 Define Input as Alarmable or Eventp.367.3.4 Set Up Alarmable Inputs in Latched or Unlatched Modep.377.3.5 Set Up Delay Timep.377.4 Setup System - Setup Common Alarmp.387.5 Setup System - Setup Zonesp.397.5.1 Set Up a Zonep.39Table 15 Default zonesp.39Table 16 Possible combinations - outputs per zonep.397.6 Setup System - Setup Outputsp.40Table 17 Default settings - digital outputsp.407.6.1 Define Output as Normally Open or Normally Closedp.407.6.2 Define Operating or Standby Modep.417.6.3 Enable or Disable an Output Device in Alarm Statusp.417.6.4 Configure Output for Loss of Power (“Fail-Safe”)p.417.7 Setup System - Setup System Infop.427.7.1 Change Passwordp.42Change the Passwordp.42Reset Password to the Factory Default (“AAAA”)p.427.7.2 Set Date & Time/Automatic Daylight Saving Timep.437.7.3 Setup Site IDp.437.7.4 Backup and Upload Configuration File (Service Terminal Interface only)p.447.7.5 Factory Defaultsp.477.7.6 Perform Firmware Update (Service Terminal Interface only)p.477.8 Setup Operationp.49Table 18 Default settings - operation featuresp.497.8.1 Turn Automatic Sequencing On or Offp.507.8.2 Turn Standby Testing On or Offp.517.8.3 Specify Failed Standby Responsep.51Table 19 Failed Standby responsep.517.8.4 Specify Hold Delay Timep.527.8.5 Specify Restart Timep.527.9 Override Outputp.53Table 20 Automatic / manual control - output pointsp.537.10 Clear Alarms & Logsp.547.10.1 Clear Active Alarmsp.547.10.2 Clear the Alarm Logp.547.10.3 Clear the Event Logp.548.0 Specificationsp.558.1 Liebert AC4 Specificationsp.55Appendix A - Service Terminal Interfacep.57A.1 Comparison of Functions: LCD and Service Terminal Interfacep.57Table 21 Guide to Liebert AC4 functionsp.57A.2 Connecting to the Service Terminal Interfacep.58A.2.1 Create a Connectionp.59Specify COM Port Connectionp.59COM1 Port Setupp.59Properties Setupp.60ASCII Setupp.60A.2.2 Connect to the Service Terminal Interfacep.61A.3 Overview of Menusp.62A.3.1 View Status Overviewp.62A.3.2 Silence Alarm and Backup Log Filesp.62A.3.3 Setup Menu Overviewp.62A.4 View Status Menusp.63Main Menup.63A.4.1 View Active Alarmsp.63A.4.2 View Alarm Logp.64A.4.3 View Event Logp.65A.4.4 View Input Statusp.65A.4.5 View Output Statusp.66A.5 Silence Alarm & Back Up Log Files (Service Terminal Interface only)p.67Main Menup.67A.5.1 Silence Alarm (Service Terminal Interface only)p.67A.5.2 Back Up Log Files (Service Terminal Interface only)p.68Back Up Alarm Log Filep.68Back Up Event Log Filep.68A.6 Setup Menup.69Main Menup.69Login Menup.69Setup Menup.70A.6.1 Setup Inputsp.71A.6.2 Setup Common Alarmp.72A.6.3 Setup Zonesp.72A.6.4 Setup Outputsp.73A.6.5 Setup System Infop.74Change Passwordp.74Set Date & Time/Automatic Daylight Saving Timep.75Setup Site IDp.75Backup and Upload Configuration File (Service Terminal Interface only)p.76Factory Defaultsp.77Firmware Update (Service Terminal Interface only)p.78A.6.6 Setup Operationp.79Auto Sequencingp.79Standby Testingp.80Failed Standbyp.81Hold Delayp.81Restart Delayp.82A.6.7 Override Outputp.82A.6.8 Clear Alarms & Logsp.83Clear Active Alarmsp.83Clear the Alarm Logp.83Clear the Event Logp.84
Page 7 of the Emerson Surge Protector (AC4) user manual — 1.3 Available Alarms
Page 7 · click to enlarge
Page 7

1.0 I NTRODUCTION

The Liebert AC4 is ideal for coordinated control of systems with redundant equipment, such as multiple environmental units or pumps. When the Liebert AC4 controller detects an alarm in an operating device, the Liebert AC4 enables a standby device and controls the device in alarm as configured, either leaving that device operating or disabling it.

The Liebert AC4 controller can also balance usage of devices by rotating units through Operating and Standby modes according to a user-defined schedule. This helps keep redundant equipment operating efficiently and only when needed. The Liebert AC4 can perform routine testing of standby devices and alert personnel if a standby device fails an operating test and requires attention.

Another capability of the Liebert AC4 is monitoring the status of connected devices and keeping personnel apprised through local alarming.

The Liebert AC4 controller can interface with anything that closes an electrical contact. To improve process efficiency and troubleshooting, the controller tracks data in two types of logs: alarm and event. The Liebert AC4 has a local LCD interface and an RS232 interface.

When an alarm condition arises, the Liebert AC4 displays alarm information, sounds an audible alarm, changes the state of the common alarm relay and turns connected devices on or off according to user configuration. See 1.5 Typical Configuration for a more detailed example.

1.1 Methods of Viewing and Configuring the Liebert AC4

The Liebert AC4 features access through two interfaces that allow users to configure the unit, silence alarms, back up logs, and perform many other functions to keep a large or small operation running smoothly and safely.

  • LCD —liquid crystal display on the front of the panel
  • Service Terminal Interface —accessible via a computer connected directly to an RS232 port

These interfaces permit easy access and configuration of the Liebert AC4, allowing users to view data, silence alarms and have full access to information stored in the controller, including logs of alarms and events.

1.2 Data Logs

The two types of data logs—alarm history and event history—can be viewed on the LCD on the front of the Liebert AC4 or the Service Terminal Interface. The logs may also be downloaded to a computer through the Service Terminal Interface.

1.3 Available Alarms

The alarms available with the Liebert AC4 are:

  • Discrete input alarm (for each digital input)
  • Loss of power
  • No standby available
  • Standby device failed
  • No restart available

Introduction

Page 8 of the Emerson Surge Protector (AC4) user manual — 1.4 Outside Enclosure Overview
Page 8 · click to enlarge
Page 8

1.4 Outside Enclosure Overview

The Liebert AC4 controller board comes in an enclosure that is 2-3/4" deep and has a built-in liquid crystal display (LCD) and a key lock, as shown in Figure 1. The enclosure is made of metal to accommodate secure conduit fittings and protect components against environmental debris.

Figure 1 Liebert AC4 enclosure—external features

Emerson Surge Protector (AC4) — 1.4 Outside Enclosure Overview diagram (page 8)
Fig. 2 · 1.4 Outside Enclosure Overview

LCD for configuration and operation

The enclosure has knockouts and access slots on top and bottom for cables and wires.

The enclosure must be secured to a wall, either flush-mounted or recessed in the wall, as described in 2.0 Installation. Knockouts and access slots on the top and bottom allow easy connection of wires and cables (see 3.0 Wiring and Connections) with either mounting type.

Figure 2 Liebert AC4 enclosure—internal features

Emerson Surge Protector (AC4) — 1.4 Outside Enclosure Overview diagram (page 8)
Fig. 3 · 1.4 Outside Enclosure Overview

Knockouts and access slots (top and bottom)

Ground wire for LCD

Show 4 more labels / short text on this page
Introduction · Key lock · Back of LCD · Controller Board
Page 9 of the Emerson Surge Protector (AC4) user manual — 1.5 Typical Configuration
Page 9 · click to enlarge
Page 9

1.5 Typical Configuration

Figure 3 shows an example of external devices connected to the Liebert AC4 controller board. There may be up to four devices connected to the four digital inputs and four digital outputs. Remote access is available through the Service Terminal Interface.

Figure 3 Typical Configuration

Emerson Surge Protector (AC4) — 1.5 Typical Configuration diagram (page 9)
Fig. 4 · 1.5 Typical Configuration

Introduction

Page 10 of the Emerson Surge Protector (AC4) user manual — 1.6 Controller Board Overview
Page 10 · click to enlarge
Page 10

1.6 Controller Board Overview

The Liebert AC4 controller board has connectors for four digital inputs and four digital outputs, as shown below. The board comes complete with light emitting diodes (LEDs) to display the status of connected devices, a serial communications port, a power connection and other features necessary to control your operation.

A - Power On/Off switch

D - Common Alarm connectors C - Audible horn jumper B - Audible horn

Emerson Surge Protector (AC4) — 1.6 Controller Board Overview diagram (page 10)
Fig. 5 · 1.6 Controller Board Overview

P - 24VAC power connector

E - Digital output status LEDs

O - LCD contrast adjustment

F - Manual Override Switch (outputs)

G - Digital output connectors

N - LCD connector

H - Status LEDs

M - DIP switch 1

I - Digital output loss-of-power jumper

J - Digital input connectors

L - Serial interface connector (RS232/EIA574)

K - Digital input status LEDs

Table 1 Controller board components

ItemDescriptionFor more information, see: A - Power On/Off switchPower switch for the controller board.2.4: Connect Power to the Liebert AC4 B - Audible hornProvides audible notification when an alarm occurs.N/A C - Audible horn jumperJumper to disable the audible horn (factory default is enabled).N/A D - Common Alarm connectorsThe two common alarm connections are used to conne a secondary warning device such as a horn, light or Building Management System (BMS). When an alarm present, the contacts close and the external warning de is activated/notified. The common alarm contacts may configured to be reset with the Silence button/commanct to 3.0: Wiring and Connections 3.3: Connecting Common Alarm is Outputs vice 7.4: Setup System - Setup Common be Alarm d. E - Digital output status LEDsEach output has an LED to indicate its status: ON/OFF (energized/de-energized).1.7: LED Indicators F - Manual Override Switch (outputs)Placing the switch in the ON position will turn ON, or energize, all four outputs simultaneously. This switch removes all automatic output control from the Liebert A7.9: Override Output C4. G - Digital output connectorsEach of the four output connections is a two-state poin ON/OFF (energized/de-energized). An example of a field digital output is a Liebert Environmental unit’s remote shutdown input.t: 3.0: Wiring and Connections 3.2.2: Connecting Digital Outputs 5.5: View Output Status 7.6: Setup System - Setup Outputs H - Status LEDsIndicates the operational status of the controller board.1.7: LED Indicators

Introduction

Page 11 of the Emerson Surge Protector (AC4) user manual — 1.6 Controller Board Overview
Page 11 · click to enlarge
Page 11

Table 1 Controller board components (continued)

ItemDescriptionFor more information, see: I - Digital output loss-of-power jumperOne of four output jumpers. Each digital output has a jumper to set the fail-safe position of the output point when power fails. The OFF position makes the contact Normally Open (factory default). The ON position makes the contact Normally Closed. Note: The jumper position has no effect on the contact when the Liebert AC4 has power.3.2.3: Setting the Digital Output Jumpers 7.6.4: Configure Output for Loss of Power (“Fail-Safe”) J - Digital input connectorsEach of the four input connections is a two-state point: ON/OFF (energized/de-energized). An example of a field digital input is a Liebert Environmental unit’s common alarm relay output.3.0: Wiring and Connections 3.2.1: Connecting Digital Inputs 5.4: View Input Status 7.3: Setup System - Setup Inputs K - Digital input status LEDsEach input has an LED to indicate its status: ON/OFF (energized/de-energized).1.7: LED Indicators L - Serial interface connector (RS232/EIA574)Connection for laptop or video terminal. Used for configuration and monitoring using the Service Terminal Interface. Requires a null modem cable for connectivity (P/N 201258P1).3.4: RS232 Connector A.2: Connecting to the Service Terminal Interface M - DIP switch 1DIP switch used for resetting password to default.7.7.1: Change Password N - LCD connectorConnection for the LCD on the enclosure door.N/A O - LCD contrast adjustmentAdjustment contrast for the LCD on the enclosure door.N/A P - 24VAC power connectorPower connection for the controller. Requires 24VAC.2.4: Connect Power to the Liebert AC4

Introduction

Page 12 of the Emerson Surge Protector (AC4) user manual — 1.7 LED Indicators
Page 12 · click to enlarge
Page 12

1.7 LED Indicators

The Liebert AC4 controller board has LED indicators that show the status of inputs, outputs and the common alarm

Emerson Surge Protector (AC4) — 1.7 LED Indicators diagram (page 12)
Fig. 6 · 1.7 LED Indicators

OUTPUT2 OUTPUT3 OUTPUT4 OUTPUT5 OUTPUT6 OUTPUT7 OUTPUT8 CTRLLOCK SENLOCK CMN ALR

Table 2 LED indicators summary

LED TypeLEDColorDescription EIA422 LEDs422 TXGreen Liebert AC4 is transmitting information over the EIA422 port 422 RXGreen Liebert AC4 is receiving information over the EIA422 port Output LEDsOUTPUT1Green Not used OUTPUT2Green Not used OUTPUT3Green Not used OUTPUT4Green Not used OUTPUT5Green Indicates output 1is ON or energized OUTPUT6Green Indicates output 2is ON or energized OUTPUT7Green Indicates output 3is ON or energized OUTPUT8Green Indicates output 4is ON or energized CTRLLOCKN/A Not used SENLOCKN/A Not used CMN ALRGreen Indicates output isON or energized Status LEDsMOPIndicates the micr Green Liebert AC4 will fuoprocessor is operating properly (MOP)—must be on before nction FPROGGreen Indicates firmware is being upgraded—lights up during upgrade process 574 TX or 232 TXGreen Liebert AC4 is transmitting information via the RS232 port 574 RX or 232 RXGreen Liebert AC4 is receiving information via the RS232 port 485 RXGreen Not used 485 TXGreen Not used Input LEDsINPUT1Red Not used INPUT2Red Not used INPUT3Red Not used INPUT4Red Not used INPUT5Red Indicates input 1 is ON or energized INPUT6Red Indicates input 2 is ON or energized INPUT7Red Indicates input 3 is ON or energized INPUT8Red Indicates input 4 is ON or energized
Emerson Surge Protector (AC4) — 1.7 LED Indicators diagram (page 12)
Fig. 7 · 1.7 LED Indicators
Show 4 more labels / short text on this page
Introduction · Output LEDs · Status LEDs · Input LEDs
Page 13 of the Emerson Surge Protector (AC4) user manual — 30-SEP-04 16:23:10
Page 13 · click to enlarge
Page 13

1.8 Typical Sequence

Figure 4 shows a typical sequence of how the Liebert AC4 functions after detecting a change in a monitored device. Many responses depend on configuration settings. This example shows what happens when a digital input changes state—assuming the input is defined as alarmable—and when the condition returns to normal.

Figure 4 Example of typical sequence

RESPONSES TO AN ALARM RETURN-TO-NORMAL SEQUENCE

Emerson Surge Protector (AC4) — RESPONSES TO AN ALARM RETURN-TO-NORMAL SEQUENCE diagram (page 13)
Fig. 8

ALARM CONDITION DETECTED A device connected to the Liebert AC4 changes state.

RETURN TO NORMAL The device that triggered the alarm returns to its normal state.

The alarm is cleared (automatically if Unlatched; must be cleared manually if Latched)

The horn sounds (audible horn on the controller board—silence horn by pressing any key on the LCD keypad)

The horn stops sounding (if user hasn’t silenced it)

The LCD flashes (except during setup)

The LCD stops flashing

UNIVERSAL MONITOR 05-SEP-02 14:04:13 V5.100.0 PRESS =STATUS/SETUP

ESC ESC

User setup determines output control (for example, the device in alarm might be disabled and a standby device set to operate)

DEVICE_1 ALARM CONTACT CLOSED 30-SEP-04 16:23:04 Entry in Alarm Log Condition (ALARM) & state (CONTACT CLOSED)

30-SEP-04 16:24:04 Entry in Alarm Log (ALARMS CLEARED)

Entry in Active Alarm Log Condition (ALARM) & state (CONTACT CLOSED)

DEVICE_1 ALARM CONTACT CLOSED

Entry in Event Log Status change (DEVICE_4 STARTED)

Entry in Event Log Actions in response to event (DEVICE_1 STARTED, DEVICE_4 OFF)

DEVICE_4 STARTED

DEVICE_1 STARTED DEVICE_2 STARTED DEVICE_3 STARTED DEVICE_4 OFF 30-SEP-04 16:24:06

30-SEP-04 16:23:10

Introduction

Page 14 of the Emerson Surge Protector (AC4) user manual — Packing Contents
Page 14 · click to enlarge
Page 14

2.0 I NSTALLATION

2.1 Installation Considerations

The Liebert AC4 must be installed indoors and may be mounted on the surface of a wall or flush- mounted, depending on the user’s application, the location of equipment to be connected and the type of wall the unit will be mounted on.

The Liebert AC4 should be mounted where it can be easily accessed. On-site personnel would access the unit through the LCD on its front cover or the service terminal connected to the RS232 port.

In addition to the communications connections, the site also must have electrical service and must permit connecting the unit’s four digital inputs and four digital outputs.

The wall material must be capable of supporting the weight of the Liebert AC4: see 8.0 Specifications.

NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

2.1.1 Unpacking and Preliminary Inspection

  • Before unpacking the Liebert AC4, inspect the shipping carton for damage or signs of mishandling, such as gashes or holes in the carton or severely flattened corners.
  • Open the shipping crates carefully. Use care to avoid puncturing the container with sharp objects that might damage the contents.
  • Inspect the Liebert AC4 and all included components for damage.
  • If any damage from shipping or mishandling is observed, immediately file a damage claim with the shipping agency and forward a copy to:

Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Packing Contents

Table 3 Packing manifest

Liebert AC4 controller board in enclosure

Keys (2) to panel door lock

Show 4 more labels / short text on this page
Installation · Standard Components · User Manual · RS232 Configuration Cable
Page 15 of the Emerson Surge Protector (AC4) user manual — 2.2.1 Mounting the Panel
Page 15 · click to enlarge
Page 15

2.2 Surface-Mounting the Liebert AC4

After determining where to place the unit, check to ensure that you have all the hardware required to install the panel on the surface of a wall. Obtain the needed tools and material.

Required tools

  • Electric drill (if surface is too hard to drive screws without pilot holes)
  • Screwdriver
  • Marker to denote layout of holes
  • Four screws, each #10

2.2.1 Mounting the Panel

! WARNING Risk of electric shock. Can cause property damage, injury and death.

Check building plans and other relevant documents to determine whether mounting the Liebert AC4 at the selected location might cause cutting or otherwise damaging electrical or communication wiring or pipes.

1. Mark the wall for mounting holes, using the back of the unit as a template (see Figure 5). 2. Drill holes, if required, to install the four #10 screws that will secure the Liebert AC4 to the wall. Clean up the debris. 3. If the wall material is not strong enough to hold the screws securely, use wall anchors. 4. Install the top two screws—the screw heads must be small enough to slip through the larger, bottom portion of the pear-shaped mounting slot in the Liebert AC4 (see inset in Figure 5). The screws must also be large enough to extend over the edges of the top of the mounting slot. 5. Hang the Liebert AC4 on the screws, letting the panel slip down until the screws are in the smaller, upper portion of the slot. 6. Tighten the screws until they are snug. 7. Insert the remaining two screws in the bottom holes on the back of the panel and tighten.

Figure 5 Mounting dimensions

Emerson Surge Protector (AC4) — 2.2.1 Mounting the Panel diagram (page 15)
Fig. 9 · 2.2.1 Mounting the Panel

0.213" (5.4mm) Bottom hole diameter

Installation · Mounting Slot

Page 16 of the Emerson Surge Protector (AC4) user manual — 2.3.1 Mounting the Panel
Page 16 · click to enlarge
Page 16

2.3 Flush-Mounting the Liebert AC4

The rectangular access doors on the top and bottom of the Liebert AC4 must be reversed so they slide the opposite direction. Leaving the doors as shipped from the factory prevents them from being opened when the panel is flush mounted in a wall.

The Liebert AC4 may be flush mounted according to company practices—either with screws through the sides of the panel into wall supports or with hanging hardware that attaches to the back of the panel. After determining how and where to place the unit, check to ensure that you have all the hardware required to install the panel in the wall. Obtain the needed tools.

Required tools

  • Saw
  • Electric drill
  • Screwdriver
  • Marker to denote layout of the hole to accommodate the Liebert AC4
  • Trim ring and associated hardware
  • Mounting hardware

2.3.1 Mounting the Panel

! WARNING Risk of electric shock. Can cause property damage, injury and death.

Check building plans and other relevant documents to determine whether mounting the Liebert AC4 at the selected location might cause cutting or otherwise damaging electrical or communication wiring or pipes.

1. Mark the wall for the cutout to accommodate the panel, using the back of the unit as a template. 2. Drill a pilot hole for the saw blade, if required. 3. Use the saw to cut out the marked section of the wall (if not new construction). 4. Rest the Liebert AC4 in the wall and mark where mounting screws will be inserted into the wall studs or other support member. 5. Remove the panel and drill the holes for the mounting screws or wall anchors. Clean up the debris. 6. Reverse the slide direction of the rectangular access doors on the top and bottom of the Liebert AC4. Leaving the doors as shipped from the factory prevents them from being opened when the panel is flush mounted in a wall. 7. Attach any field-supplied mounting hardware. 8. Reinsert the assembly into the wall. 9. Insert and tighten the screws or wall anchors.

Installation

Page 17 of the Emerson Surge Protector (AC4) user manual — 2.4 Connect Power to the Liebert AC4
Page 17 · click to enlarge
Page 17

2.4 Connect Power to the Liebert AC4

The Liebert AC4 requires 24VAC for proper operation. Liebert recommends using the optional Transformer Module manufactured by Liebert or another UL-approved class 2 power unit to obtain proper voltage. If the power unit is not a class 2 circuit, it must be protected with an IEC 5 x 20mm time lag 2A fuse. For information, consult your local dealer, Emerson representative or the Emerson Network Power Liebert Worldwide Support Group.

! WARNING Risk of electric shock. Can cause property damage, injury and death. Check that power is removed from wires prior to installation. This unit should be installed only by properly trained and qualified personnel.

! CAUTION Risk of electric shock. Can cause property damage, injury and death. The Liebert AC4 is designed for use on properly grounded (earthed) 24VAC power, 50Hz or 60Hz. The ground wire for the power lead must be wired to the earth ground terminal (stud located next to the 24VAC terminal block). This equipment is intended to be installed by a qualified and certified electrician who must review and approve customer supplied wiring and circuit breakers, verify correct input and grounded (earthed) connections to ensure compliance with technical standards and national and local electrical codes.

! WARNING Risk of electric shock. Can cause property damage, injury and death.

Be sure that the Power On/Off switch is set to OFF before installing any wiring to this unit. The switch is in the top left corner of the unit, just below the battery pack.

To connect electrical power:

1. Run conduit and electrical wiring from building to the Liebert AC4. 2. Use copper wires only; proper wiring to use for power is 18-22 AWG stranded and shielded (18 AWG is recommended—see Table 4 ). Strip wires 1/2".

Figure 6 Electrical connections to panel

External wiring through knockout

Emerson Surge Protector (AC4) — 2.4 Connect Power to the Liebert AC4 diagram (page 17)
Fig. 10 · 2.4 Connect Power to the Liebert AC4
Emerson Surge Protector (AC4) — 2.4 Connect Power to the Liebert AC4 diagram (page 17)
Fig. 11 · 2.4 Connect Power to the Liebert AC4
Emerson Surge Protector (AC4) — 2.4 Connect Power to the Liebert AC4 diagram (page 17)
Fig. 12 · 2.4 Connect Power to the Liebert AC4
Emerson Surge Protector (AC4) — 2.4 Connect Power to the Liebert AC4 diagram (page 17)
Fig. 13 · 2.4 Connect Power to the Liebert AC4
Emerson Surge Protector (AC4) — 2.4 Connect Power to the Liebert AC4 diagram (page 17)
Fig. 14 · 2.4 Connect Power to the Liebert AC4
Emerson Surge Protector (AC4) — 2.4 Connect Power to the Liebert AC4 diagram (page 17)
Fig. 15 · 2.4 Connect Power to the Liebert AC4

24VAC input connector 24VAC wiring (red & white)

3. Secure the incoming electrical service wires to the Liebert AC4’s 24VAC input by sliding the wires into TB7, the 24VAC input terminal block. There is no polarity requirement when connecting to TB7. The ground wire must be connected to the earth ground terminal located on the side of the panel (see Figure 6 ).
Show 4 more labels / short text on this page
Installation · Power On/Off switch · Ground wire (black) · Earth ground terminal
Page 18 of the Emerson Surge Protector (AC4) user manual — (TB7)
Page 18 · click to enlarge
Page 18

3.0 W IRING AND C ONNECTIONS

! WARNING Risk of electric shock. Can cause property damage, injury and death.

Switch Off electric power to the Liebert AC4 before installing any wiring to the unit or changing input or output connections. The Power On/Off switch is in the top left corner of the unit.

3.1 Wiring Specifications

Input and output connections to the Liebert AC4 may be made in any order—it is not necessary, for example, to make all input connections before making any output connections. Use copper conductors only for all wiring.

Table 4 Wiring specifications

Connection Supported Wire Type Maximum Wire Length Rating

18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740

750 ft. (225m) Dry Contact (24VDC, 10 mA)

18 AWG* (recommended) 20 AWG 22 AWG

18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740

24VAC @3A @3A 50 ft. (15m) @2A 100 ft. (30m) @1A 200 ft. (60m)

@3A 40 ft. (12m) @2A 60 ft. (18m) @1A 100 ft. (30m)

@3A 25 ft. (7m) @2A 35 ft. (10m) @1A 75 ft. (23m)

18 AWG* (recommended) 20 AWG 22 AWG

18-22 AWG Stranded & Unshielded 18 AWG* (recommended) Non Plenum - Belden 9740 Plenum - Belden 89740

24VAC @3A @3A 50 ft. (15m) @2A 100 ft. (30m) @1A 200 ft. (60m)

@3A 40 ft. (12m) @2A 60 ft. (18m) @1A 100 ft. (30m)

@3A 25 ft. (7m) @2A 35 ft. (10m) @1A 75 ft. (23m)

RS232 Null Modem Cable 50 ft. (15m) N/A

18-22 AWG Stranded & Shielded 18 AWG* (recommended) Non Plenum - Belden 8770 Plenum - Belden 88770

150 ft. (45m) 24VAC @1.3A

(TB7)

Show 9 more labels / short text on this page
Wiring and Connections · Digital · Input · Digital Output · Common · Alarm Output · Communication · 24VAC Power Connection · * Recommended
Page 19 of the Emerson Surge Protector (AC4) user manual — Connecting Liebert Precision Cooling Units
Page 19 · click to enlarge
Page 19

3.2 Connecting Digital Inputs and Outputs

The digital inputs and outputs are on the lower right side of the Liebert AC4 printed wiring assembly board. This section describes how to connect devices to the Liebert AC4’s inputs and outputs.

Each input is tied to an output with the same number:

  • Input 1 is tied to Output 1 (default name: Device_1)
  • Input 2 is tied to Output 2 (default name: Device_2)
  • Input 3 is tied to Output 3 (default name: Device_3)
  • Input 4 is tied to Output 4 (default name: Device_4)

Up to four devices may be connected to the Liebert AC4. Each device must be connected to an input and an output with the same number.

To determine the proper wire size, see Table 4 Wiring specifications.

After making the connections, push the removed piece back into the portion attached to the printed wiring assembly until the terminal block pieces lock together.

Connecting Liebert Precision Cooling Units

For Liebert Precision Cooling units, follow these steps (be sure to connect the same device to inputs and outputs with the same number (Input 1 and Output 1, Input 2 and Output 2, and so on):

  • Connect a digital input from the Liebert AC4 to the Common Alarm Relay of the environmental unit: terminals 75/76 or TB1-6,TB1-7.
  • Connect a digital output (numbered the same as the input) from the Liebert AC4 to the Remote Shutdown (Power Control) of the environmental unit: terminal 37/38 or TB1-4, TB1-5.
Emerson Surge Protector (AC4) — Connecting Liebert Precision Cooling Units diagram (page 19)
Fig. 16 · Connecting Liebert Precision Cooling Units

3.2.1 Connecting Digital Inputs The four digital inputs are on the lower right side of the Liebert AC4, just below the output terminal blocks, as shown at right. These inputs are numbered 1 through 4.

OUTPUT TERMINAL BLOCKS Note numbering keys to right of terminal blocks; outputs are numbered from bottom (1) to top (4)

To connect an input: 1. Turn Off electrical power to the Liebert AC4. 2. If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure. 3. Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.

INPUT TERMINAL BLOCKS Note numbering keys to right of terminal blocks; inputs are numbered from bottom (1) to top (4)

Wiring and Connections · Numbering keys

Page 20 of the Emerson Surge Protector (AC4) user manual — 3.2.3 Setting the Digital Output Jumpers
Page 20 · click to enlarge
Page 20

3.2.2 Connecting Digital Outputs

The four digital outputs are found on the lower right side of the Liebert AC4 just above the input terminal blocks, as shown at right. These outputs are numbered 1 through 4.

To connect an output: 1. Turn OFF electrical power to the Liebert AC4. 2. If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure. 3. Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.

! CAUTION To reduce the risk of fire or electric shock, do not interconnect the outputs of different class 2 circuits.

3.2.3 Setting the Digital Output Jumpers

Emerson Surge Protector (AC4) — 3.2.3 Setting the Digital Output Jumpers diagram (page 20)
Fig. 17 · 3.2.3 Setting the Digital Output Jumpers

Each digital output has an associated jumper to define its operation when power is interrupted. This puts the Liebert AC4 in a fail-safe mode and ensures proper functioning when the board has no power.

The Liebert AC4 comes from the factory with all digital output jumpers in the OFF position (normally open). The jumper setting for each digital output can be changed to ON (normally closed). The settings are shown in Table 5.

Table 5 Digital output jumper settings

To change the output jumper setting:

1. Find the respective loss-of-power jumper on the circuit board, as shown above. See Table 1 Controller board components for more information. 2. Decide whether your configuration requires the jumper to be OFF or ON. 3. Set the jumper as needed:
  • Set the jumper to OFF by placing the loss-of-power jumper on the middle and top pins.
  • Set the jumper to ON by placing the black jumper on the middle and bottom pins.
Show 6 more labels / short text on this page
Wiring and Connections · Output status · Setting · (power loss) · OFF Normally open · ON Normally closed
Page 21 of the Emerson Surge Protector (AC4) user manual — 3.4 RS232 Connector
Page 21 · click to enlarge
Page 21

3.3 Connecting Common Alarm Outputs

Emerson Surge Protector (AC4) — 3.3 Connecting Common Alarm Outputs diagram (page 21)
Fig. 18 · 3.3 Connecting Common Alarm Outputs

The common alarm relay, found in the top right corner of the Liebert AC4, permits the user to connect auxiliary notification equipment, such as lights, horns and sirens, to the Liebert AC4. To determine the proper wire size, see Table 4 Wiring specifications.

There are two connectors for the common alarm output. However, the connectors are not individual relay outputs. The connectors should be treated as a double-pole, double-throw (DPDT) relay.

The common alarm relay is energized whenever an alarm occurs.

To connect an output:

1. Turn OFF electrical power to the Liebert AC4. 2. If necessary, remove a conduit knockout to permit wire entry into the Liebert AC4 enclosure. 3. Bring the wire(s) into the Liebert AC4 enclosure through a conduit knockout or access slot. 4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block. 5. Tighten the screw until it holds the wire snugly.

3.4 RS232 Connector

Emerson Surge Protector (AC4) — 3.4 RS232 Connector diagram (page 21)
Fig. 19 · 3.4 RS232 Connector

Serial interface connector (RS232/EIA5 74)

The Liebert AC4’s Service Terminal Interface offers full configuration and monitoring capability via the RS232 port (see A.2 - Connecting to the Service Terminal Interface).

The RS232 port requires a null modem cable. Connect one end of the cable to the Liebert AC4’s RS232 port, shown at right, and the other end to the COM1 port of a laptop computer or video terminal.

Wiring and Connections · Common alarm outputs

Page 22 of the Emerson Surge Protector (AC4) user manual — SYSTEM & CONTROL FUNCTIONS
Page 22 · click to enlarge
Page 22

4.0 O VERVIEW OF M ENUS

There are two ways to access the Liebert AC4: the LCD on the front of the enclosure and the Service Terminal Interface, which is accessible through any computer using a communications program. Many viewing and configuration tasks can be performed through either interface, but some are available only through the Service Terminal Interface.

  • Step-by-step instructions for all functions appear in Sections 5.0 through 7.0 . These instructions use examples of LCD screens to illustrate most functions, except those not available via the LCD.
  • Examples of all Service Terminal Interface screens appear in Appendix A - Service Terminal Interface , along with instructions on how to connect to the Service Terminal Interface.

Table 6 lists all Liebert AC4 functions and shows whether they can be performed through the LCD interface and where to find information.

Table 6 Guide to Liebert AC4 functions

Can be performed viaWhere to find:

Service Terminal screen examples

LCD

VIEW STATUS FUNCTIONS

View Active Alarms 4 4 page 19 page 57

View Alarm Log 4 4 page 20 page 58

View Event Log 4 4 page 21 page 59

View Input Status 4 4 page 22 page 59

View Output Status 4 4 page 23 page 60

SILENCE ALARM & BACK UP LOGS FUNCTIONS

Silence Alarm (On the LCD, press any key to silence an alarm) 4 4 page 24 page 61

Back Up Log Files — 4 page 25 page 62

SYSTEM & CONTROL FUNCTIONS

Login 4 4 page 27 page 63

Setup System 4 4 page 29 page 64

Setup Inputs 4 4 page 29 page 65

Setup Common Alarm 4 4 page 32 page 66

Setup Zones 4 4 page 33 page 66

Setup Outputs 4 4 page 34 page 67

Setup System Info 4 4 page 36 page 68

Change Password 4 4 page 36 page 68

Set Date & Time/Automatic Daylight Saving Time 4 4 page 37 page 69

Setup Site ID 4 4 page 37 page 69

Backup and Upload Configuration File — 4 page 38 page 70

Factory Defaults 4 4 page 41 page 71

Perform Firmware Update — 4 page 41 page 72

Setup Operation 4 4 page 43 page 73

Override Output 4 4 page 47 page 76

Clear Alarms & Logs 4 4 page 48 page 77

Clear Active Alarms 4 4 page 48 page 77

Clear the Alarm Log 4 4 page 48 page 77

Clear the Event Log 4 4 page 48 page 78

Show 5 more labels / short text on this page
Overview of Menus · Service Terminal · Instructions on · Function · using function
Page 23 of the Emerson Surge Protector (AC4) user manual — SETUP SYSTEM OVERRIDE OUTPUT CLEAR ALARMS & LOGS
Page 23 · click to enlarge
Page 23

4.1 Opening Screen Overview

The Liebert AC4 displays the Opening Screen at startup, as shown in Figure 7.

  • If any alarms are active, the Current Alarm screen appears. (Pressing any key on the LCD keypad will silence the audible alarm.)

If no alarms are present, the Main Menu appears.

4.2 Main Menu Overview

The Main Menu offers access to all functions within the panel. As shown in Table 7, the functions are organized into three sections with step-by-step instructions.

Table 7 Primary Functions Overview

  • These features are available to all users. This permits all personnel to check the status of any monitored equipment or location. From this menu, any user may:
  • View active alarms
  • View the current status of digital inputs and outputs
  • View data stored in the alarm and event logs 6.0 - Silence Alarm & Backup Log Files (Service Terminal Interface only)

5.0 - View Status Options (both LCD and Service Terminal Interface)

  • These features—available via the Service Terminal Interface only—allow users to:
  • Silence the audible alarm
  • Back up the alarm and event logs

7.0 - System and Control Options (some functions available via Service Terminal Interface only)

  • These options require a password. Authorized users may:
  • Configure the Liebert AC4
  • Override automatic control of outputs to force an output ON or OFF
  • Clear active alarms and delete all records in the alarm and event logs

4.3 LCD Menu Overview

Figure 7 shows an overview of the initial screens available through the LCD interface. For comparable information about the Service Terminal Interface screens, see A.3 - Overview of Menus.

Figure 7 LCD Menu overview

LIEBERT AC4 DD-MON-YY HR:MM:SS

(If any alarms detected) Current Alarm screen (see 5.1 View Active Alarms)

VX.XXX.X PRESS ↵ =STATUS/SETUP

VIEW STATUS SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

“View Status” selected See Section “System & Control” selected See Section > VIEW STATUS

5.0 VIEW STATUS > SYSTEM AND CONTROL

SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

↑↓ =NEXT ↵ =SELECT

View Status Menu (All users - no password) See Section

System & Control Menu (Password required) See Section VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS

5.1 5.2 5.3 5.4 5.5

SETUP SYSTEM OVERRIDE OUTPUT CLEAR ALARMS & LOGS

7.2 7.9 7.10

Show 4 more labels / short text on this page
Overview of Menus · Section Description · Opening Screen · Main Menu
Page 24 of the Emerson Surge Protector (AC4) user manual — > VIEW STATUS
Page 24 · click to enlarge
Page 24

5.0 V IEW S TATUS O PTIONS

The View Status menu allows any user to view currently active alarms, data stored in the alarm and event logs and the status of all inputs and outputs. The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item.

This section presents step-by-step instructions for each of the following options:

  • View Active Alarms
  • View Alarm Log
  • View Event Log
  • View Input Status
  • View Output Status

Figure 8 shows the main options available from the View Status menu.

Figure 8 Menu overview - View Status menu

LIEBERT AC4 DD-MON-YY HR:MM:SS

VX.XXX.X PRESS ↵=STATUS/SETUP Main Menu

> VIEW STATUS

SYSTEM AND CONTROL

↑↓=NEXT ↵=SELECT View Status

VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS

View Active Alarms View Alarm Log View Event Log

Emerson Surge Protector (AC4) — > VIEW STATUS diagram (page 24)
Fig. 20

> ALARM RECORD 99/99 DEVICE_1 ALARM CONTACT CLOSED 30-JUN-04 09:29:10 NO STANDBY AVAILABLE

> EVENT RECORD 99/99 SYSTEM USER LOGIN 19-MAY-04 10:07:00 DEVICE_1 HW FORCE ON CONTACT CLOSED 18-MAY-04 06:47:03 DEVICE_4 FORCE OFF CONTACT OPEN 18-MAY-04 05:22:17 DEVICE_3 AUTO CONTACT OPEN 18-MAY-04 04:32:11

INPUT / STATUS > DEVICE_1 ALARM DEVICE_2 NORMAL DEVICE_3 NORMAL DEVICE_4 NORMAL

OUTPUT / STATUS > DEVICE_1 ALARM DEVICE_2 OPERATING DEVICE_3 OPERATING DEVICE_4 OPERATING

See Section 5.5

View Status Options · Opening Screen · View Status options

Page 25 of the Emerson Surge Protector (AC4) user manual — Clearing Active Alarms
Page 25 · click to enlarge
Page 25

5.1 View Active Alarms

The Active Alarm screen displays all alarms that are occurring, up to a maximum of 40.

> VIEW STATUS

SYSTEM AND CONTROL

A Current Alarm screen appears automatically whenever an alarm occurs—except during setup. This screen can display only the two most recent active alarms. To view any other active alarms, use the View Active Alarms feature.

↑↓ =NEXT ↵ =SELECT

View Status Menu > VIEW ACTIVE ALARMS

You may view active alarms at any time by using the following steps:

VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS

  • From the Main Menu, use the arrows ↑↓ to choose View Status , as shown at right, and then press Enter ↵ .
  • From the View Status Menu, use the arrows ↑↓ to choose View Active Alarms and press Enter ↵ .

Active Alarms > ACTIVE ALARM 01/40 DEVICE_1 ALARM CONTACT CLOSED

5.1.1 Active Alarms

The Active Alarms screen displays up to 40 records; it shows any active alarm and any Latched alarm that has not been cleared. Examples of alarms include inputs in alarm status and failure of a standby device. When any alarms are present, the Active Alarms screen shows descriptive details for each alarm:

  • the source of the alarm (for example, DEVICE_1 )
  • the status of an input ( CONTACT CLOSED )

If there are no active alarms, the screen displays the message:

NO ALARMS PRESENT

Viewing Additional Screens

There may be up to 40 records of alarm data.

  • To view additional records, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.

Clearing Active Alarms

To clear all active alarms, see 7.10 Clear Alarms & Logs. Alarm records are stored in the Alarm Log.

View Status Options · Main Menu

Page 26 of the Emerson Surge Protector (AC4) user manual — 5.2.2 Backing Up the Alarm Log (Service Terminal Interface only)
Page 26 · click to enlarge
Page 26

5.2 View Alarm Log

The Alarm Log contains up to 99 records of alarms that have occurred. Records are added to this log as alarms occur.

> VIEW STATUS

SYSTEM AND CONTROL

To view the Alarm Log:

↑↓ =NEXT ↵ =SELECT

  • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
  • From the View Status Menu, use the arrows ↑↓ to choose View Alarm Log , then press Enter ↵ .

VIEW ACTIVE ALARMS > VIEW ALARM LOG

VIEW EVENT LOG VIEW INPUT STATUS VIEW OUTPUT STATUS

5.2.1 Alarm Log

The Alarm Log screen displays up to 99 records showing alarm data, including inputs and outputs in alarm status and failure of a standby device. If the log contains any alarm records, the Alarm Log screen displays details for each alarm:

Alarm Log > ALARM RECORD 99/99 DEVICE_1 ALARM CONTACT CLOSED 30-JUN-04 09:29:10 NO STANDBY AVAILABLE

  • the source of the alarm (for example, DEVICE_1 )
  • the status of an input or output ( CONTACT CLOSED ) or a brief description of the problem ( STNDBY DEVICE FAILED )
  • the date and time the alarm occurred

29-JUN-04 10:45:00 STNDBY DEVICE FAILED

Table 8 shows conditions that the alarm log records for digital inputs and in the panel itself.

29-JUN-04 10:39:00 NO RESTART AVAILABLE

Table 8 Alarm log conditions

SOURCE Digital Input Panel

28-JUN-04 06:54:09

LOSS OF POWER ALARM SILENCED ALARMS CLEARED STNDBY DEVICE FAILED NO STANDBY AVAILABLE NO RESTART AVAILABLE

ALARM NORMAL

CONDITIONS RECORDED

If there are no alarms in the log, the screen displays the message:

NO ALARMS

Viewing Additional Screens

There may be up to 99 records of alarm data.

  • To view additional records, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.

5.2.2 Backing Up the Alarm Log (Service Terminal Interface only)

The alarm log is stored as a file in the Liebert AC4; it can hold no more than 99 records. When the log is full, the oldest records are deleted from the end of the file as new alarm records are added at the beginning.

You may back up the alarm log file to a remote computer using the Service Terminal Interface, as described in 6.2 Back Up Log Files (Service Terminal Interface only).

To delete all records in the alarm log, see 7.10 Clear Alarms & Logs.

View Status Options · Main Menu · View Status Menu

Page 27 of the Emerson Surge Protector (AC4) user manual — 5.3.2 Backing Up the Event Log (Service Terminal Interface only)
Page 27 · click to enlarge
Page 27

5.3 View Event Log

In addition to alarms, the Liebert AC4 tracks other changes in the Event Log to assist users with verifying operational and troubleshooting problems. Events reflect changes in the status of an input that is defined as an event or the change of state of an output (i.e., manually forced ON or OFF). Other events may be informational, such as a user login. The Event Log contains up to 99 records of events, which are added as they occur.

> VIEW STATUS

SYSTEM AND CONTROL

↑↓ =NEXT ↵ =SELECT

VIEW ACTIVE ALARMS VIEW ALARM LOG > VIEW EVENT LOG

To view the Event Log:

  • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
  • From the View Status Menu, use the arrows ↑↓ to choose View Event Log , then press Enter ↵ .

VIEW INPUT STATUS VIEW OUTPUT STATUS

Event Log > EVENT RECORD 99/99 SYSTEM USER LOGIN 19-MAY-04 10:07:00 DEVICE_1 HW FORCE ON CONTACT CLOSED 18-MAY-04 06:47:03 DEVICE_4 FORCE OFF CONTACT OPEN 18-MAY-04 05:22:17 DEVICE_3 AUTO CONTACT OPEN 18-MAY-04 04:32:11 DATE AND TIME SET 18-MAY-04 03:11:43 DEVICE_4 FORCE ON CONTACT CLOSED 18-MAY-04 02:34:00

5.3.1 Event Log

The Event Log screen displays up to 99 recent events. If the log contains any event records, the Event Log screen displays details for each event:

  • the event source (for example, DEVICE_1 )
  • the status of an input or output ( CONTACT CLOSED ) or a brief description of the event ( USER LOGIN )
  • the date and time the event occurred

Table 9 shows conditions that the event log records for inputs and outputs and in the panel itself.

Table 9 Event log conditions

SOURCE Digital Input Digital Output Panel

STARTED ON OFF HW FORCE ON AUTO FORCE ON FORCE OFF RESTORED

ALARMS CLEARED ALARM SILENCED NO STANDBY OUTPUTS

EVENT NORMAL

AVAILABLE NO STANDBY TESTING

DEVICE AVAILABLE TIME & DATE SET USER LOGIN

CONDITIONS RECORDED

If there are no records in the log, the screen displays the message:

NO EVENTS

Viewing Additional Screens

There may be up to 99 records of event data.

  • To view additional records, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.

5.3.2 Backing Up the Event Log (Service Terminal Interface only)

The event log is stored as a file in the Liebert AC4; it can hold no more than 99 records. When the log is full, the oldest records are deleted from the end of the file as new event records are added at the beginning.

You may back up the event log file to a remote computer using the Service Terminal Interface, as described in 6.2 Back Up Log Files (Service Terminal Interface only).

To delete all records in the event log, see 7.10 Clear Alarms & Logs.

View Status Options · Main Menu · View Status Menu

Page 28 of the Emerson Surge Protector (AC4) user manual — Viewing Additional Input Data
Page 28 · click to enlarge
Page 28

5.4 View Input Status

The Input Status option allows you to view the current status of all four digital inputs.

> VIEW STATUS

SYSTEM AND CONTROL

To view the Input Status:

↑↓ =NEXT ↵ =SELECT

  • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
  • From the View Status Menu, use the arrows ↑↓ to choose View Input Status , then press Enter ↵ .

VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG > VIEW INPUT STATUS

5.4.1 Input Status

VIEW OUTPUT STATUS

The Input Status screen displays the status of each digital input.

The following details appear for digital inputs:

INPUT / STATUS > DEVICE_1 ALARM

  • the name of the digital input (for example, DEVICE_1 )
  • the current status ( ALARM )—values are updated constantly while being viewed

DEVICE_2 NORMAL DEVICE_3 NORMAL DEVICE_4 NORMAL

There are three possible states for a digital input, as shown in Table 10.

Table 10 Digital input states

State Description NORMAL In normal state ALARM In alarm status (for an input configured as alarmable) EVENT An event has occurred (for an input configured as an event)

Viewing Additional Input Data

All input data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:

  • To view all inputs, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.
Show 4 more labels / short text on this page
View Status Options · Main Menu · View Status Menu · Input Status
Page 29 of the Emerson Surge Protector (AC4) user manual — Viewing Additional Output Data
Page 29 · click to enlarge
Page 29

5.5 View Output Status

The Output Status option allows you to view the current status of all four outputs.

> VIEW STATUS

SYSTEM AND CONTROL

To view the Output Status:

↑↓ =NEXT ↵ =SELECT

  • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
  • From the View Status Menu, use the arrows ↑↓ to choose View Output Status , then press Enter ↵ .

VIEW ACTIVE ALARMS VIEW ALARM LOG VIEW EVENT LOG VIEW INPUT STATUS > VIEW OUTPUT STATUS

5.5.1 Output Status

The Output Status screen displays the status of each digital output.

The following details appear for digital outputs:

  • the name of the output (for example, DEVICE_1 )
  • the current status ( ALARM )—values are updated constantly while being viewed

OUTPUT / STATUS > DEVICE_1 ALARM

DEVICE_2 OPERATING DEVICE_3 OPERATING DEVICE_4 OPERATING

There are eight possible states for a digital output, as shown in Table 11.

Table 11 Digital output states

State Description OPERATING Device operating, or ON STANDBY Device in standby mode ALARM Device in alarm FORCE ON Device forced ON by operator FORCE OFF Device forced OFF by operator HW FORCE ON Device forced ON by hardware switch PENDING Pending delay timer NOT USED Device not used

Viewing Additional Output Data

All output data may be viewed by scrolling beyond the four lines that appear on the LCD at one time:

  • To view all outputs, use the arrows ↑↓ .
  • To return to the previous screen, press the ESC key.
Show 4 more labels / short text on this page
View Status Options · Main Menu · View Status Menu · Output Status
Page 30 of the Emerson Surge Protector (AC4) user manual — 1=SILENCE ALARM 2=RETURN TO MAIN MENU
Page 30 · click to enlarge
Page 30

Silence Alarm & Backup Log Files (Service Terminal Interface)

6.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)

This section describes two features that are available in the Service Terminal Interface:

  • Silence Alarm
  • Backup Log Files

6.1 Silence Alarm (Service Terminal Interface)

The Silence Alarm menu item allows you to silence the audible alarm and reset the Common Alarm Relay output if the common alarm is configured to reset with silence.

This menu item is available only through the Service Terminal Interface.

To silence the alarm remotely through the Service Terminal Interface:

  • Connect to the Liebert AC4 either from a remote computer or through the RS232 port (see A.2 - Connecting to the Service Terminal Interface ).
  • At the Main Menu, enter 6 (Silence Alarm).
  • At the Silence Alarm menu, shown below, enter 1 to silence the audible alarm immediately. (To exit without silencing the alarm, enter 2 or press the Escape key.)

Silence Alarm (Service Terminal Interface only)

SILENCE ALARM

Silence alarm and reset common alarm relay if common alarm relay is configured to reset with silence alarm

1=SILENCE ALARM 2=RETURN TO MAIN MENU

SELECT A NUMBER:1

>ALARM HAS BEEN SILENCED

  • A confirmation message appears: “Alarm has been silenced.”
Page 31 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:2
Page 31 · click to enlarge
Page 31

Silence Alarm & Backup Log Files (Service Terminal Interface)

6.2 Back Up Log Files (Service Terminal Interface only)

The Liebert AC4 maintains two types of logs—alarm and event—that may be backed up to a remote computer.

This feature is available only through the Service Terminal Interface.

To back up the alarm or event log:

1. Connect to the Liebert AC4 through the RS232 port (see A.2 - Connecting to the Service Terminal Interface ). 2. At the Main Menu, enter 7 (Backup Log Files). 3. At the Backup Log Files menu, as shown below, enter a number for the type of file you want to back up:
  • Enter 1 to back up the Alarm Log
  • Enter 2 to back up the Event Log

Backup Log Files - Event Log File (Service Terminal Interface only)

BACKUP LOG FILES

Backup alarm and event log files

1=BACKUP ALARM LOG FILE 2=BACKUP EVENT LOG FILE 3=RETURN TO MAIN MENU

SELECT A NUMBER:2

4. At the prompt to initiate a backup of the selected log file, enter Y (Yes - begin) or N (No - cancel). The current setting appears in brackets—[N] in the following example.

>INITIATE A BACKUP OF EVENT LOG-YES(Y) OR NO(N)? >[N] >[

INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG

Page 32 of the Emerson Surge Protector (AC4) user manual — >BACKUP SUCCESSFUL
Page 32 · click to enlarge
Page 32

Silence Alarm & Backup Log Files (Service Terminal Interface)

5. At the top of the HyperTerminal window, shown below, click on Transfer , then on Receive File .
Emerson Surge Protector (AC4) — 6.2 Back Up Log Files (Service Terminal Interface only) diagram (page 32)
Fig. 21 · 6.2 Back Up Log Files (Service Terminal Interface on…
Emerson Surge Protector (AC4) — 6.2 Back Up Log Files (Service Terminal Interface only) diagram (page 32)
Fig. 22 · 6.2 Back Up Log Files (Service Terminal Interface on…
Emerson Surge Protector (AC4) — 6.2 Back Up Log Files (Service Terminal Interface only) diagram (page 32)
Fig. 23 · 6.2 Back Up Log Files (Service Terminal Interface on…

Enter filename - for example, event.log

6. In the Receive File window, as shown above:
  • In the Place Received File in the Following Folder box, enter the name and location of the folder where the configuration file should be placed—for example, C:\downloads —or click on the Browse button to locate the folder.
  • In the Use Receiving Protocol box, select Xmodem from the drop-down list.
  • Click on the Receive button. (To close the window without backing up the file, click on Close or Cancel .) 7. In the Receive Filename window, enter a name for the log file— Event.log in the example above. 8. When the transfer is complete, a confirmation message appears in the Service Terminal Interface window: “Backup Successful.”

INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG

>BACKUP SUCCESSFUL

9. The display returns to the Backup Log Files menu. You may choose another type of log file to back up (return to Step 3 ) or press 3 (or Escape) to return to the Main Menu.

After backing up a log file, you may want to delete all records in the Liebert AC4 log of that type. See 7.10 Clear Alarms & Logs for details.

Enter folder · Select Xmodem

Page 33 of the Emerson Surge Protector (AC4) user manual — 7.1 Login
Page 33 · click to enlarge
Page 33

System and Control Options

7.0 S YSTEM AND C ONTROL O PTIONS

The System and Control menu allows you to configure the Liebert AC4—setting up inputs and outputs and system features such as date and time. This menu also provides a vehicle for manually changing the state of an output to ON or OFF, clearing active alarms and deleting records from the Liebert AC4’s alarm and event logs.

The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item and enter new information. Table 12 shows characters that may be entered in labels and values.

Table 12 Valid characters for data entry

Alphanumeric Special characters A-Z, 0-9 space [ ] ^ _ ! " # $ % & ( ) * + - / , . ; < = > @

The System and Control options require a password to prevent unauthorized users from making changes to the system.

This section presents step-by-step instructions for each of the following:

  • Login - enter the password
  • Setup System - configure inputs, outputs, system features
  • Override Output - manually override automatic control of outputs; release the override
  • Clear Alarms & Logs - clear active alarms; delete records from the alarm and event logs

7.1 Login

Users must enter a password to access any of the system and control options. The password consists of four characters (see Table 12 for valid characters). (To set up or change the password, see 7.7.1 Change Password.) The default password is AAAA.

Emerson Surge Protector (AC4) — 7.1 Login diagram (page 33)
Fig. 24 · 7.1 Login

To log in:

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ , as shown at right.
  • Use the arrows ↑↓ to choose System and Control , and press Enter ↵ . The Login menu appears.
  • To enter your password:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

OVERRIDE OUTPUT CLEAR ALARMS & LOGS ↑↓=NEXT ↵=SELECT

The System and Control Menu appears next, with these options that are described in the following sections:

  • Setup System ( Section 7.2 - Section 7.7 )
  • Override Output ( Section 7.9 )
  • Clear Alarms & Logs ( Section 7.10 )

Main Menu

Page 34 of the Emerson Surge Protector (AC4) user manual — AAAA
Page 34 · click to enlarge
Page 34

System and Control Options

Figure 9 shows the main options available from the System & Control menu.

Figure 9 Menu overview - System and Control menu

Emerson Surge Protector (AC4) — Figure 9 Menu overview - System and Control menu diagram (page 34)
Fig. 25 · Figure 9 Menu overview - System and Control menu

System & Control menu Setup System selected

System & Control menu Override Output selected

System & Control menu Clear Alarms&Logs selected

Emerson Surge Protector (AC4) — Figure 9 Menu overview - System and Control menu diagram (page 34)
Fig. 26 · Figure 9 Menu overview - System and Control menu

SETUP SYSTEM OVERRIDE OUTPUT > CLEAR ALARMS & LOGS

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION

OVERRIDE OUTPUT > DEVICE_1 AUTO DEVICE_2 AUTO DEVICE_3 AUTO DEVICE_4 FORCE ON

CLEAR ACTIVE ALARMS CLEAR ALARM LOG CLEAR EVENT LOG

Setup Inputs Setup Common Alarm Setup Zones Setup Outputs

SELECT OUTPUT > DEVICE_1 NO-OP-E DEVICE_2 NO-ST-E DEVICE_3 NO-NU-D DEVICE_4 NO-NU-D

SETUP DEVICE_1 LABELDEVICE_1 NORM OPEN/CLOSE: NO ALARM/EVENT: AL LATCHED: N DELAY: 00:01
SETUP DEVICE_1 NORM OPEN/CLOSENO MODE: OPERATING IN ALARM: ENABLE

Setup System Info Setup Operation

Emerson Surge Protector (AC4) — Figure 9 Menu overview - System and Control menu diagram (page 34)
Fig. 27 · Figure 9 Menu overview - System and Control menu

CHANGE PASSWORD SET DATE & TIME SETUP SITE ID FACTORY DEFAULTS

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N HOLD DELAY : 10:00 RESTART : 00:06

Change Password Set Date & Time Setup Site ID Factory Defaults

CHANGE PASSWORD

See Section 7.7.1

SET DATE & TIME DAYLIGHT SVG TIME: Y

See Section 7.7.2

SETUP SITE ID See Section 7.7.3

RESTORE ALL DEFAULTS ARE YOU SURE? N

See Section 7.7.5

AAAA

18-MAY-02 10:56:30

Opening Screen

Page 35 of the Emerson Surge Protector (AC4) user manual — SELECT INPUT > DEVICE_1 NO-AL-NL
Page 35 · click to enlarge
Page 35

System and Control Options

7.2 Setup System - Overview

The Setup System screen displays six options that allow you to configure input and output devices, the common alarm, and a variety of system details, such as login password and system date and time:

  • Setup Inputs
  • Setup Common Alarm
  • Setup Zones
  • Setup Outputs
  • Setup System Info
  • Setup Operation

> SETUP INPUTS

SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION

7.3 Setup System - Setup Inputs

The Liebert AC4 has four digital input points that may be configured individually. These inputs may have a wide variety of Liebert or other manufacturers’ equipment connected.

To configure a digital input:

SELECT INPUT > DEVICE_1 NO-AL-NL

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

DEVICE_2 NO-AL-NL ↑↓=NEXT ↵=SELECT DEVICE_3 NO-AL-NL DEVICE_4 NO-AL-NL

Select a Digital Input to Configure

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Inputs and press Enter ↵ .
  • From the Select Input Menu, choose an input—for example, Device_1 —and press Enter ↵ .

Table 13 shows the digital input features you may change, along with the default settings: you may change the name of the input, define it as normally open or closed, and specify it as alarmable or as an event.

  • Alarmable inputs may be defined as either Unlatched or Latched.
  • Event status allows you to monitor a digital input’s state—and use a change in state to initiate an action through an output, if desired—without triggering an alarm. Events are always Unlatched.
  • You may also specify a time delay before the Liebert AC4 responds to an alarm or event.

Use the steps following Table 13 to change the default settings for any digital input.

Table 13 Default settings - digital inputs

Feature Default Other Options

LABEL DEVICE_1 Any name (up to eight characters)

NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)

ALARM/EVENT AL (Alarmable) EV (Event)

LATCHED L (Latched) / Y (Yes)* NL (Unlatched) / N (No)*

DELAY 00:01 (1 second) Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

Settings - Select Input Menu (see Section 7.3)

When configuring an input (see Section 7.3.4)

Unlatched NL (Not Latched) N (No, not latched)

Latched L (Latched) Y (Yes, latched)

Setup System Menu · Select Input Menu

Page 36 of the Emerson Surge Protector (AC4) user manual — ↑↓ =AL/EV ↵ =END
Page 36 · click to enlarge
Page 36

System and Control Options

7.3.1 Change Label (Name of Input)

Each input has a default label (Device_1, Device_2, etc.) that you may change to a more descriptive name for ease in recognizing alarms and events associated with the input. The label may consist of up to eight characters (see Table 12 for valid characters).

SETUP DEVICE_1 > LABEL: DEVICE_1

NORM OPEN/CLOSENO ALARM/EVENT: AL ↑↓ =NEXT ↵ =SELECT LATCHED: N DELAY: 00:01

The device name assigned through this menu is also displayed for the corresponding output.

Table 14 Input and output labels

Label Applies to:

CHANGE LABEL

Device_1 Input 1 Output 1 Device_2 Input 2 Output 2 Device_3 Input 3 Output 3 Device_3 Input 3 Output 3

DEVICE_1 ↑↓ =SELECT ↵ =NEXT/END

If the input label is changed, the output will change also.

  • From the Setup Inputs Menu, choose Label for the selected input— Label: Device_1 in the example at right—and press Enter ↵ .
  • To change the input’s label, which may consist of up to eight characters:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

7.3.2 Define Input as Normally Open or Normally Closed

Each input may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all input points is NO (Normally Open).

SETUP DEVICE_1 LABEL: DEVICE_1 > NORM OPEN/CLOSE: NO

If you require an input to be a supervised point, define the input as Normally Closed (NC).

ALARM/EVENTAL ↑↓ =NEXT ↵ =SELECT LATCHED: N DELAY: 00:01
  • From the Setup Inputs Menu, choose Norm Open/Close , as shown at right, and press Enter ↵ .
  • To change the normal state for this input, use the arrows ↑↓ to choose NO (Normally Open) or NC (Normally Closed), then press Enter ↵ .

Normally Open / Closed

IS INPUT NORMALLY OPEN OR CLOSED? NO

↑↓ =NO/NC ↵ =END

7.3.3 Define Input as Alarmable or Event

Each input may be defined as Alarmable (AL) or as an Event (EV).

SETUP DEVICE_1 LABELDEVICE_1 NORM OPEN/CLOSE: NO > ALARM/EVENT: AL
  • For an input defined as alarmable , a change in the status of the device triggers these actions: the LCD flashes, the audible horn sounds, a record is entered in the Alarm Log and the common alarm relay is energized.
  • For an input defined as an event , a change in the status of the device is recorded in the Event Log.

↑↓ =NEXT ↵ =SELECT LATCHED: N DELAY: 00:01

For both types (alarmable and event), user setup determines output control—whether the device that changed status is disabled or kept in operating mode and whether a standby device is set to operate.

IS INPUT AN ALARM OR EVENT? AL

By default, all inputs are set up as AL (Alarmable).

↑↓ =AL/EV ↵ =END

  • From the Setup Inputs Menu, choose Alarm/Event , as shown at right, and press Enter ↵ .
  • To change the type of input, use the arrows ↑↓ to choose AL (Alarmable) or EV (Event), then press Enter ↵ .
Show 5 more labels / short text on this page
Setup Inputs Menu · Change Label · Setup Inputs Menu · Setup Inputs Menu · Alarmable / Event
Page 37 of the Emerson Surge Protector (AC4) user manual — DELAY TIME BEFORE TRIGGER?
Page 37 · click to enlarge
Page 37

System and Control Options

7.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode

Alarmable input points may be set up in Latched mode (Y), which requires the user to clear the Liebert AC4 alarms after an alarm has occurred, or Unlatched mode (N), in which alarms will automatically clear after a return-to-normal state. The default setting for alarmable inputs is Y (Latched). Any input defined as an event is automatically Unlatched.

SETUP DEVICE_1 LABELDEVICE_1 NORM OPEN/CLOSE: NO ALARM/EVENT: AL ↑↓ =NEXT ↵ =SELECT > LATCHED: N

DELAY: 00:01

An input defined as Latched does not reset automatically after an alarm. It will remain in the triggered position even after the monitored device returns to normal. After an alarm, the user must manually reset Latched inputs, as described in 7.10.1 Clear Active Alarms. This also means that any outputs linked to a Latched digital input will remain triggered until the input is manually reset.

IS ALARM LATCHED? N

↑↓ =Y/N ↵ =END

An input defined as Unlatched will automatically track the status of the monitored device. No action by the user is required.

  • From the Setup Inputs Menu, choose Latched , as shown above right, and press Enter ↵ .
  • To change this feature, use the arrows ↑↓ to choose Y (Yes - Latched) or N (No - Unlatched), then press Enter ↵ .

Message (if input has been defined as an event)

LATCH NOT ALLOWED WHEN IN EVENT MODE

The only way to reset latched alarms is by clearing active alarms. This step is required to return latched points to their normal state. For details, see 7.10.1 Clear Active Alarms.

ESC=BACK

7.3.5 Set Up Delay Time

Each input may be set up with a specified time delay between the occurrence of an alarm or event—a monitored device changes state— and any response by the Liebert AC4. This feature can prevent needless responses to transient conditions.

SETUP DEVICE_1 LABELDEVICE_1 NORM OPEN/CLOSE: NO ALARM/EVENT: AL ↑↓ =NEXT ↵ =SELECT LATCHED: N DELAY: 00:01

This delay is the amount of time that must elapse before the Liebert AC4 acknowledges the change of state in the monitored device and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).

The time delay applies only when a monitored device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.

DELAY TIME BEFORE TRIGGER?

00 MIN01 SEC ↑↓ =SELECT ↵ =NEXT/END

When the monitored device returns to its normal state, the Liebert AC4 acknowledges the change of state after the delay timer ends its countdown.

  • From the Setup Inputs Menu, choose Delay , as shown at right, and press Enter ↵ .
  • To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
  • For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.
  • Press Enter ↵ to advance to seconds (SEC).
  • For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.
  • When finished, press Enter ↵ again.
Show 4 more labels / short text on this page
Setup Inputs Menu · Latched / Unlatched · Setup Inputs Menu · Delay Time
Page 38 of the Emerson Surge Protector (AC4) user manual — ↑↓ =Y/N ↵ =END
Page 38 · click to enlarge
Page 38

System and Control Options

7.4 Setup System - Setup Common Alarm

The audible alarm sounds after the Liebert AC4 detects an alarm condition in any input that has been defined as alarmable. Once the alarm is silenced, there are two options:

  • By default, the common alarm remains energized until all input alarms are cleared.
  • You may change this setting to de-energize the common alarm automatically once the alarm is silenced.

You might want to reset the common alarm with silence if an external alarm—for example, a horn—is connected to the common alarm output contacts.

You might not want to reset the common alarm contacts (let contacts reflect/track alarms) and simply silence the audible horn.

To change the common alarm setting:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

Change to Reset (Y) or Not Reset (N)

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Common Alarm and press Enter ↵ .
  • By default, the common alarm is set up not to reset automatically when the alarm is silenced (N). To change this setting, use the arrows ↑↓ to choose Y (Yes - reset with silence) or N (No - not reset), then press Enter ↵ .

SETUP INPUTS > SETUP COMMON ALARM

SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION

Reset Common Alarm RESET COMMON ALARM WITH SILENCE? N

↑↓ =Y/N ↵ =END

Setup System Menu

Page 39 of the Emerson Surge Protector (AC4) user manual — TOO MANY DEVICES ESC BACK
Page 39 · click to enlarge
Page 39

System and Control Options

7.5 Setup System - Setup Zones

The Liebert AC4 has two zones that may be used to define different areas—rooms or sections of a room. The Liebert AC4 effectively performs as two separate units, controlling each zone separately, for examply, using a different rotation sequence for devices in each zone.

Each zone may have two to four outputs associated with it. By default, Zone 1 has four associated outputs and Zone 2 has none.

To set up zones:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

SETUP INPUTS SETUP COMMON ALARM > SETUP ZONES

↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO SETUP OPERATION

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Zones and press Enter ↵ .

7.5.1 Set Up a Zone

  • From the Setup Zones Menu, choose a zone—for example, Zone 1 —and press Enter ↵ .
  • On the Number of Devices screen, Use the arrows ↑↓ to select the number of outputs for this zone, then press Enter ↵ . The example at right shows four outputs in Zone 1 .

SETUP ZONES > ZONE 1 4

ZONE 2 0 ↑↓ =NEXT ↵ =SELECT

Table 15 shows the default number of outputs for each zone.

Table 15 Default zones

# DEVICES IN ZONE

Zone Default number of outputs

ZONE 1 4 ↑↓ =SELECT ↵ =NEXT/END

Message (if too few devices entered)

A message appears if you enter too few or too many devices, as shown at right. Press Escape to return to the Setup Zones menu.

MINIMUM OF 2 DEVICES ESC BACK

Table 16 shows the possible combinations of outputs for each zone. For example, if Zone 1 has four outputs, then Zone 2 may not be used (0 outputs).

Message (if too many devices entered)

Table 16 Possible combinations - outputs per zone

If Zone 1 hasZone 2 must have:

4 or 3 outputs 0 (not used)

TOO MANY DEVICES ESC BACK

2 outputs 0 (not used) or 2 outputs

0 (not used) 2 or 3 or 4 outputs

Show 6 more labels / short text on this page
Setup System Menu · Select Setup Zones · Setup Zones · Number of Devices · Zone 1 4 · Zone 2 0
Page 40 of the Emerson Surge Protector (AC4) user manual — ↑↓ =NO/NC ↵ =END
Page 40 · click to enlarge
Page 40

System and Control Options

7.6 Setup System - Setup Outputs

The Liebert AC4 has four outputs that may be configured individually. These outputs correspond to the four numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1.

The output name is the same as the input name, as described in 7.3.1 Change Label (Name of Input).

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT > SETUP OUTPUTS

To configure an output:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

SETUP SYSTEM INFO SETUP OPERATION

SELECT OUTPUT > DEVICE_1 NO-OP-E

Select an Output to Configure

DEVICE_2 NO-ST-E ↑↓=NEXT ↵=SELECT DEVICE_3 NO-NU-D DEVICE_4 NO-NU-D

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Outputs and press Enter ↵ .
  • From the Select Output Menu, choose an output—for example, Device_1 —and press Enter ↵ .

Table 17 shows digital output features and their default settings: you may define an output as normally open or normally closed, set the device’s mode—operating, standby or not used—and specify whether to disable the device when an alarm occurs.

Use the steps following Table 17 to change the default settings for any digital output.

Table 17 Default settings - digital outputs

Feature Default Other Options

NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)

OP (Operating) ST (Standby) NU (Not Used)

MODE Outputs 1-3Output 4:

OP (Operating) ST (Standby)

IN ALARM E (Enable) D (Disable)

7.6.1 Define Output as Normally Open or Normally Closed

Each output may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all output points is NO (Normally Open).

SETUP DEVICE_1 > NORM OPEN/CLOSE: NO

MODEOPERATING ↑↓ =NEXT ↵ =SELECT IN ALARM: ENABLE
  • From the Setup Outputs Menu, shown at right, use the arrows ↑↓ to choose Norm Open/Close and press Enter ↵ .
  • To change the normal state for this output, use the arrows ↑↓ to choose the state:

Change State SET TO NORMAL OPEN OR NORMAL CLOSE? NO

  • NO (Normally Open)
  • NC (Normally Closed)
  • Press Enter ↵ .

↑↓ =NO/NC ↵ =END

Setup System Menu · Select Output Menu · Setup Outputs Menu

Page 41 of the Emerson Surge Protector (AC4) user manual — ↑↓ =E/D ↵ =EDIT
Page 41 · click to enlarge
Page 41

System and Control Options

7.6.2 Define Operating or Standby Mode

Each output may be defined as Operating (OP), Standby (ST), or Not Used (NU). This setting takes precedence over any setting in the override menu (see 7.9 Override Output).

SETUP DEVICE_1 NORM OPEN/CLOSE: NO > MODE: OPERATING

↑↓ =NEXT ↵ =SELECT IN ALARM: ENABLE

Default settings are:

  • Outputs 1, 2 and 3 are in Operating (OP) mode
  • Output 4 is in Standby (ST) mode

To change the mode:

SET MODE: OP

  • From the Setup Outputs Menu, shown at right, use the arrows ↑↓ to choose Mode for the selected output and press Enter ↵ .
  • To change the output’s mode, use the arrows ↑↓ to choose one of these options:

↑↓ =OP/ST/NU ↵ =EDIT

  • OP (Operating)
  • ST (Standby)
  • NU (Not Used)
  • Press Enter ↵ .

7.6.3 Enable or Disable an Output Device in Alarm Status

You may choose whether to Enable or Disable an output when the connected device is in alarm status. The default setting for all output points is Enabled.

SETUP DEVICE_1 NORM OPEN/CLOSENO MODE: OPERATING ↑↓ =NEXT ↵ =SELECT > IN ALARM: ENABLE
  • From the Setup Outputs Menu, choose In Alarm , as shown at right, and press Enter ↵ .
  • To make a change, use the arrows ↑↓ to choose E (Enable) or D (Disable) to determine what happens when an alarm is detected in the device.
  • Press Enter ↵ .

Change State in Alarm STATE OF DEVICE IN ALARM: DISABLE

↑↓ =E/D ↵ =EDIT

7.6.4 Configure Output for Loss of Power (“Fail-Safe”)

Each output has an associated jumper that can help prevent undesired effects when the controller board loses power. For example, without the proper fail-safe jumper setting, a loss of power might close a switch that is Normally Open (NO)—perhaps shutting off an environmental unit or a fan or closing a valve.

This fail-safe jumper setting is unrelated to configuring an output as Normally Open (NO) or Normally Closed (NC), as described in 7.6.1 Define Output as Normally Open or Normally Closed.

To configure a digital output jumper for a loss of power:

  • Set the jumper in the “OFF” position (factory default) to make the output Normally Open (NO).
  • Set the jumper in the “ON” position to make the output Normally Closed (NC).

For more information, see 3.2.3 Setting the Digital Output Jumpers.

Setup Outputs Menu · Set Mode · Setup Outputs Menu

Page 42 of the Emerson Surge Protector (AC4) user manual — CHANGE PASSWORD
Page 42 · click to enlarge
Page 42

System and Control Options

7.7 Setup System - Setup System Info

The Setup System Info options allow users to:

  • Change Password —used for access to system setup functions
  • Set Date & Time/Automatic Daylight Saving Time —used to set the Liebert AC4 date and time and to enable automatic time change for Daylight Saving Time
  • Setup Site ID —the Liebert AC4’s location to differentiate among sites if more than one Liebert AC4 is in use
  • Backup and Upload Configuration File (Service Terminal Interface only) —permits the user to copy the Liebert AC4’s configuration settings and to upload the file to the Liebert AC4
  • Factory Defaults— returns the Liebert AC4 to its factory settings
  • Perform Firmware Update (Service Terminal Interface only) —changes the Liebert AC4’s firmware to newest version

To change any Setup System Info features:

Log In and Choose Setup System

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS > SETUP SYSTEM INFO

Select Setup System Info

SETUP OPERATION

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup System Info and press Enter ↵ .
  • Use the following steps to access any of the Setup System Info options.

7.7.1 Change Password

Setup System Info Menu

A password is required to access the Liebert AC4’s system and control options, as described in 7.1 Login. The password consists of four characters (see Table 12 for valid characters). The default password is AAAA.

SETUP SYSTEM INFO > CHANGE PASSWORD

SET DATE & TIME ↑↓=NEXT ↵=SELECT SETUP SITE ID FACTORY DEFAULTS

Change the Password

To change the password:

  • From the Setup System Info Menu, use the arrows ↑↓ to choose Change Password , then press Enter ↵ .
  • To change your password:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

CHANGE PASSWORD

AAAA ↑↓ =SELECT ↵ =NEXT/END

Reset Password to the Factory Default (“AAAA”)

To reset the password to the factory default of AAAA:

  • Locate DIP switch 1 on the unit’s circuit board (see 1.6 Controller Board Overview ) and move all switches to the OFF position (down).
  • Move the second switch to the ON position, then to the OFF position.
  • Move the seventh switch to the ON position, then to the OFF position.
  • Move the eighth switch to the ON position, then to the OFF position.

The password should now be AAAA.

Setup System Menu · Change Password

Page 43 of the Emerson Surge Protector (AC4) user manual — SETUP SITE ID
Page 43 · click to enlarge
Page 43

System and Control Options

7.7.2 Set Date & Time/Automatic Daylight Saving Time

The Liebert AC4 has a built-in real-time clock that is backed up by an encapsulated lithium battery and set up to adjust automatically for daylight saving time twice a year. The Setup System Info menu allows you to set the current date or time or change the automatic adjustment at any time.

To change the daylight saving time setting or to set the current date or time:

Setup System Info Menu

SETUP SYSTEM INFO CHANGE PASSWORD > SET DATE & TIME

  • From the Setup System Info Menu, use the arrows ↑↓ to choose Set Date & Time , then press Enter ↵ .
  • To change the daylight saving time setting:
  • To the right of Daylight Svg Time , use the arrows ↑↓ to choose Y (Yes - automatically adjust for daylight saving time) or N (No), then press Enter ↵ .
  • The format of the date and time is DD-MMM-YY HR:MM:SS . To set the current date or time:

↑↓=NEXT ↵=SELECT SETUP SITE ID FACTORY DEFAULTS

Set Date & Time

SET DATE & TIME DAYLIGHT SVG TIME: Y

  • Press Enter ↵ to advance to the next character position you want to change.
  • Use the arrows ↑↓ to choose from available entries:

18-MAY-04 10:56:30 ↑↓ =SELECT ↵ =NEXT/END

Date Day (DD) 0-31 Month (MMM) JAN-DEC Year (YY) 00-99 Time Hour (HR) 00-23 Minutes (MM) 00-59 Seconds (SS) 00-59

  • Press Enter ↵ to advance to the next character position.
  • When finished, press Enter ↵ again.

7.7.3 Setup Site ID

Setup System Info Menu

You may enter a Site ID to identify the Liebert AC4’s location, using a name that may consist of up to 40 characters (see Table 12 for valid characters). The Site ID will appear with each alarm.

SETUP SYSTEM INFO CHANGE PASSWORD SET DATE & TIME ↑↓=NEXT ↵=SELECT > SETUP SITE ID

To enter or change the Site ID:

FACTORY DEFAULTS

  • From the Setup System Info Menu, use the arrows ↑↓ to choose Setup Site ID , then press Enter ↵ .
  • To enter a Site ID:
  • Use the arrows ↑↓ to choose a character.
  • Press Enter ↵ to advance to the next character position.
  • If the Site ID is less than 40 characters, you may enter an underscore (_) character to indicate the end of the name.
  • When finished, press Enter ↵ again.

SETUP SITE ID

↑↓ =SELECT ↵ =NEXT/END

Setup Site ID

Page 44 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 44 · click to enlarge
Page 44

System and Control Options

7.7.4 Backup and Upload Configuration File (Service Terminal Interface only)

This operation may be performed only through the Service Terminal Interface. It permits the user to make a copy of the Liebert AC4 configuration settings and save it as a file on the computer connected through the RS232 port. Should the need arise, the user can upload the configuration file from the computer to the Liebert AC4, instead of re-entering the settings manually.

To access these options:

1. Connect to the Liebert AC4 either from a remote computer or through the RS232 port (see A.2 - Connecting to the Service Terminal Interface ). 2. At the Main Menu, enter 0 (zero—Setup System-Login Required). 3. At the Login Menu, enter your password. 4. At the Setup Menu, enter 5 (Setup System Information). 5. At the Setup System Information Menu, enter 4 (Backup & Upload Configuration File). The Backup & Upload Configuration File menu appears, shown below:

Backup & Upload Configuration File - Backup (Service Terminal Interface only)

BACKUP AND UPLOAD CONFIGURATION FILE

Backup from panel saves panel configurations Upload to panel restores panel configurations

Select to backup or upload file

1=BACKUP CONFIGURATION FILE 2=UPLOAD CONFIGURATION FILE 3=RETURN TO SETUP SYSTEM INFO MENU 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU

SELECT A NUMBER:1

6. Enter 1 to back up the configuration file from the Liebert AC4 to the computer and proceed to Step 8 ,

OR 7. Enter 2 to upload the configuration file from the computer to the Liebert AC4 and proceed to Step 13. NOTE: This will replace the current configuration settings in the Liebert AC4 with the most recent backup.

Page 45 of the Emerson Surge Protector (AC4) user manual — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only)
Page 45 · click to enlarge
Page 45

System and Control Options

Back Up the Configuration File

8. At the prompt to Initiate a Backup of Configuration File, enter Y (Yes - begin) or N (No - cancel). The current setting appears in brackets—[N] in the following example.

>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[

9. At the top of the HyperTerminal window, shown below, click on Transfer , then on Receive File .
Emerson Surge Protector (AC4) — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) diagram (page 45)
Fig. 28 · 7.7.4 Backup and Upload Configuration File (Service…
Emerson Surge Protector (AC4) — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) diagram (page 45)
Fig. 29 · 7.7.4 Backup and Upload Configuration File (Service…
Emerson Surge Protector (AC4) — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) diagram (page 45)
Fig. 30 · 7.7.4 Backup and Upload Configuration File (Service…

Enter filename - for example, AC4_CONF.SAV

  • 10. In the Receive File window, as shown above:
  • In the Place Received File in the Following Folder box, enter the name and location of the folder where the configuration file should be placed—for example, C:\downloads —or click on the Browse button to locate the folder.
  • In the Use Receiving Protocol box, select Xmodem from the drop-down list.
  • Click on the Receive button. (To close the window without backing up the file, click on Close or Cancel .) 11. In the Receive Filename window, enter a name for the file—for example, AC4_CONF.SAV. 12. When the transfer is complete, a confirmation message appears in the Service Terminal Interface window: “Backup Successful.”

Enter folder · Select Xmodem

Page 46 of the Emerson Surge Protector (AC4) user manual — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only)
Page 46 · click to enlarge
Page 46

System and Control Options

Upload the Configuration File

13. At the prompt to Initiate an Upload of Configuration File, enter Y (Yes - begin) or N (No - cancel). The current setting appears in brackets—[N] in the following example.

>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[

14. At the top of the HyperTerminal window, shown below, click on Transfer , then on Send File .
Emerson Surge Protector (AC4) — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) diagram (page 46)
Fig. 31 · 7.7.4 Backup and Upload Configuration File (Service…

Enter filename - for example, AC4_CONF.SAV

Emerson Surge Protector (AC4) — 7.7.4 Backup and Upload Configuration File (Service Terminal Interface only) diagram (page 46)
Fig. 32 · 7.7.4 Backup and Upload Configuration File (Service…
  • 15. In the Send File window, as shown above:
  • In the Filename box, enter the full path of the file to be uploaded—for example, AC4_CONF.SAV—or click on the Browse button to locate the file.
  • In the Protocol box, select Xmodem from the drop-down list.
  • Click on the Send button. (To close the window without sending the file, click on Close or Cancel .) 16. When the transfer is complete, a confirmation message—“Upload Successful”—appears in the Service Terminal Interface window and the Liebert AC4 reboots with the new configuration.

Select Xmodem · Send button

Page 47 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 47 · click to enlarge
Page 47

System and Control Options

7.7.5 Factory Defaults

Setup System Info Menu

At any time, you may restore all default values for settings in the Liebert AC4 as it was shipped.

SETUP SYSTEM INFO CHANGE PASSWORD SET DATE & TIME ↑↓=NEXT ↵=SELECT SETUP SITE ID > FACTORY DEFAULTS

Factory Defaults RESTORE ALL DEFAULTS ARE YOU SURE? N

↑↓ =Y/N ↵ =END

The password is the sole exception when reverting to the factory default settings. The password can be reset to the factory default of AAAA through the DIP switches. For details, see Change Password on page 36.

7.7.6 Perform Firmware Update (Service Terminal Interface only)

This function, which may be performed only through the Service Terminal Interface, upgrades the Liebert AC4’s firmware to the newest version.

  • Connect to the Liebert AC4 either from a remote computer or through the RS232 port (see A.2 - Connecting to the Service Terminal Interface ).
  • At the Main Menu, enter 0 (zero—Setup System-Login Required).
  • At the Login Menu, enter your password.
  • At the Setup Menu, enter 5 (Setup System Information).
  • At the Setup System Info menu, enter 6 (Perform Firmware Update).
  • At the Perform Firmware Update menu, shown below, enter 1 to proceed with an update.

Firmware Update (Service Terminal Interface only)

PERFORM FIRMWARE UPDATE

This command will update the existing firmware

1=PERFORM FIRMWARE UPDATE 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

Page 48 of the Emerson Surge Protector (AC4) user manual — >PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[
Page 48 · click to enlarge
Page 48

System and Control Options

To perform the update:

1. At the Perform Firmware Update prompt, enter Y (Yes - begin) or N (No - cancel). The current setting appears in brackets—[N] in the following example.

>PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[

2. The firmware update is a two-step process—this step describes how to upload the file prog###.s19 (where ### is a number—for example, prog118.s19) to the Liebert AC4: a. At the top of the HyperTerminal window, shown below, click on Transfer , then on Send File .
Emerson Surge Protector (AC4) — >PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[ diagram (page 48)
Fig. 33

Enter filename - prog###.s19 or flash###.s19

Emerson Surge Protector (AC4) — >PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[ diagram (page 48)
Fig. 34

b. In the Send File window, as shown above:

  • In the Filename box, enter the full path of the file to be uploaded— prog###.s19 —or click on the Browse button to locate the file.
  • In the Protocol box, select Xmodem from the drop-down list.
  • Click on the Send button. (To close the window without sending the file, click on Close or Cancel .)
  • When the transfer is complete, a confirmation message appears in the Service Terminal Interface window. 3. Next, follow these steps to upload the file flash###.s19 (where ### is a number—for example, flash512.s19) to the Liebert AC4: a. At the top of the HyperTerminal window, shown above, click on Transfer , then on Send File . b. In the Send File window, shown above:
  • In the Filename box, enter the full path of the file to be uploaded— flash###.s19 —or click on the Browse button to locate the file.
  • In the Protocol box, select Xmodem from the drop-down list.
  • Click on the Send button. (To close the window without sending the file, click on Close or Cancel .)
  • When the transfer is complete, a confirmation message—“Firmware Update Successful”— appears in the Service Terminal Interface window and the Liebert AC4 reboots with the new firmware update.

Select Xmodem · Send button

Page 49 of the Emerson Surge Protector (AC4) user manual — 7.8 Setup Operation
Page 49 · click to enlarge
Page 49

System and Control Options

7.8 Setup Operation

The Liebert AC4 operation features allow you to set up a rotation sequence to alternate which devices are operating and which are placed on Standby, as well as test devices while in Standby mode and specify what to do when a Standby device goes into alarm as it is powered up. You may also specify delay times after an output changes state, directing the Liebert AC4 to wait before acknowledging inputs or turning an output on or off.

SETUP INPUTS SETUP COMMON ALARM SETUP ZONES ↑↓=NEXT ↵=SELECT SETUP OUTPUTS SETUP SYSTEM INFO > SETUP OPERATION

To change any operation features:

Log In and Choose Setup System

Setup Operation Menu > AUTO SEQUENCING OFF

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Setup System , then press Enter ↵ .

STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06

  • From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Operation and press Enter ↵ .
  • Use the steps following Table 18 to access any of the Setup Operation options.

Table 18 shows the default settings for operation options: automatic sequencing, standby testing, failed standby, hold delay and restart.

Table 18 Default settings - operation features

Feature Default Other Options

AUTO SEQUENCING OFF (Deactivated) ON (Activated), 12h (Activated for 12-hour intervals)

STANDBY TESTING OFF (Deactivated) ON (Activated)

FAILED STANDBY N (Deactivated) Y (Activated)

HOLD DELAY 10:00 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59

RESTART 00:06 (No delay) Any time (in minutes and seconds) from 00:00 to 99:59

Setup System Menu · Select Setup Operation

Page 50 of the Emerson Surge Protector (AC4) user manual — AT 00:00 ↑↓ =NEXT ↵ =EDIT
Page 50 · click to enlarge
Page 50

System and Control Options

7.8.1 Turn Automatic Sequencing On or Off

Use automatic sequencing to set up a schedule for rotation of redundant devices. For example, three devices might be in operating mode while a fourth device is in standby mode. Every two days, the Liebert AC4 returns the standby device to operating mode and places one of the operating devices on standby.

When zones are used, the Liebert AC4 manages the rotation sequence for each zone separately, so each zone might have one device in operating mode and one in standby mode.

Auto sequencing is OFF (deactivated) by default. When auto sequencing is activated (ON or 12h, for a 12-hour interval), the Liebert AC4 cycles devices at the specified interval and time of day as follows:

  • An output device in Standby mode is returned to Operating mode.
  • An output device that is Operating is put in Standby mode.

When more than one device is in Standby mode or turned On, the Liebert AC4 performs the operations in a sequence that rotates the order. For example, in a sequence set up to occur every two days:

  • Monday: Device 1 is placed on Standby, and Devices 2, 3 and 4 operate.
  • Wednesday: Device 2 is placed on Standby, and Devices 1, 3 and 4 operate.
  • Friday: Device 3 is placed on Standby, and Devices 1, 2 and 4 operate.
  • Sunday: Device 4 is placed on Standby, and Devices 1, 2 and 3 operate.

To change the auto sequencing settings:

1. From the Setup System Operation Menu, use the arrows ↑↓ to choose Auto Sequencing, then press Enter ↵. 2. In the Activate / Deactivate screen, use the arrows ↑↓ to choose one of three options: a. ON for intervals of every 1 to 99 days, then press Enter ↵ and proceed to Step 3. b. 12h for an interval of every 12 hours, then press Enter ↵ and proceed to Step 4. c. OFF to deactivate auto sequencing, then press Enter ↵ to return to the previous menu. 3. Select the interval for how often the sequencing should occur in the Every 03 Days field. The default is 3 days; valid entries range from 0 to 99 days.

> AUTO SEQUENCING OFF

STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06

Activate / Deactivate > AUTO SEQUENCING OFF

↑↓ =NEXT ↵ =EDIT

  • For each digit, use the arrows ↑↓ to choose a number from 0 to 9, then press Enter ↵ to advance to the next digit.
  • When finished, press Enter ↵ to set the time of day. 4. Specify the time of day the sequencing should begin in the At 00:00 field. The format is HH:MM for hours and minutes.

Set Interval & Start Time (1- to 99-Day Interval) > AUTO SEQUENCING ON

EVERY 03 DAYS AT 00:00 ↑↓=NEXT ↵=EDIT

  • Use the arrows ↑↓ to choose from available entries for hours (00-23), then press Enter ↵ to advance to minutes.
  • Use the arrows ↑↓ to select minutes (00-59).
  • When finished, press Enter ↵ again.

Set Start Time (12-Hour Interval)

> AUTO SEQUENCING 12h

AT 00:00 ↑↓ =NEXT ↵ =EDIT

Setup Operation Menu

Page 51 of the Emerson Surge Protector (AC4) user manual — ↑↓ =NEXT ↵ =END
Page 51 · click to enlarge
Page 51

System and Control Options

7.8.2 Turn Standby Testing On or Off

Standby testing permits scheduling an automatic operational check of devices in Standby mode.

When this feature is activated (ON), the Liebert AC4 tests all devices in Standby mode by putting each device in operating mode for a designated time. You may specify the time of day the testing begins, the duration of the test and the interval between tests. Standby testing is OFF (deactivated) by default.

To change the standby testing settings:

  • From the Setup System Operation Menu, use the arrows ↑↓ to choose Standby Testing , then press Enter ↵ .
  • In the Change Standby Testing screen, press Enter ↵ to edit Standby Testing , then use the arrows ↑↓ to choose ON to activate or OFF to deactivate the standby testing feature. Press Enter ↵ .
  • Select the desired interval for how frequently the testing should occur in the Every 03 Days field. The default is 3 days; valid entries range from 0 to 99 days.

AUTO SEQUENCING OFF > STANDBY TESTING OFF

FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06

  • For each digit, use the arrows ↑↓ to choose a number from 0 to 9, then press Enter ↵ to advance to the next digit.
  • When finished, press Enter ↵ to configure the time of day.
  • Specify the time of day the test should begin in the At 00:00 field. The format is HH:MM for hours and minutes.

Change Standby Testing > STANDBY TESTING ON

EVERY 03 DAYS AT 00:00 FOR 10 MIN ↑↓=NEXT ↵=EDIT

  • Use the arrows ↑↓ to choose from available entries for hours (00-23), then press Enter ↵ to advance to minutes.
  • Use the arrows ↑↓ to select minutes (00-59).
  • When finished, press Enter ↵ again.
  • Specify the duration of the test in minutes—the length of time the standby units will be turned On—in the For 10 Min field. Use the arrows ↑↓ to choose a number from 0 to 59 minutes. The default is 10 minutes.
  • When finished, press Enter ↵ .

7.8.3 Specify Failed Standby Response

The Liebert AC4’s Failed Standby feature determines what happens when an operating device fails and a standby device then becomes an operating unit. A subsequent alarm in the newly operating unit (previously the standby device) results in either restarting the previously operating device that was alarmed or not. This feature specifies whether each device remains in its current state or returns to its previous state of operation.

When this feature is activated (Y), each device returns to its previous state, as Table 19 shows: the newly enabled Standby device is disabled and the previously operating device is returned to Operating mode. The default setting is N (deactivated), meaning that each device remains in its current state: the Standby device remains enabled and the previously operating unit remains disabled.

AUTO SEQUENCING OFF STANDBY TESTING OFF > FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 RESTART : 00:06

Table 19 Failed Standby response

Previous Standby Device (alarm after being enabled)

Change Failed Standby > FAILED STANDBY N

Activated (Y) Disabled Returned to Operating mode

Deactivated (N) Remains enabled Remains disabled

To change the Failed Standby settings:

↑↓ =NEXT ↵ =END

  • From the Setup System Operation Menu, use the arrows ↑↓ to choose Failed Standby , then press Enter ↵ .
  • In the Change Failed Standby screen, press use the arrows ↑↓ to choose Y to activate or N to deactivate the feature.
  • Press Enter ↵ .
Show 6 more labels / short text on this page
Setup Operation Menu · Setup Operation Menu · Failed Standby · Previously Operating · Setting · Device
Page 52 of the Emerson Surge Protector (AC4) user manual — RESTART DELAY 00 MIN : 06 SEC
Page 52 · click to enlarge
Page 52

System and Control Options

7.8.4 Specify Hold Delay Time

After an output changes state, the hold delay timer directs the Liebert AC4 to ignore all inputs in the same zone for the specified time.

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT > HOLD DELAY : 10:00

This delay is the amount of time that must elapse before the Liebert AC4 acknowledges a change of state in any input. The default is 10 minutes (displayed as 10 MIN : 00 SEC).

RESTART : 00:06

The time delay applies only when a monitored output device changes from its normal state—for example, the Liebert AC4 detects a closed contact that is defined as Normally Open.

HOLD DELAY 10 MIN : 00 SEC

When the output device returns to its normal state, the Liebert AC4 acknowledges any input change of state immediately.

↑↓ =NEXT ↵ =EDIT

The hold delay timer also takes effect when the Liebert AC4 is powered up. All alarms are ignored until the hold delay time expires.

  • From the Setup Operation Menu, choose Hold Delay , as shown at right, and press Enter ↵ .
  • To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
  • For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.
  • Press Enter ↵ to advance to seconds (SEC).
  • For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.
  • When finished, press Enter ↵ again.

7.8.5 Specify Restart Time

The restart delay timer directs the Liebert AC4 to wait a specified time before changing the state of an output. This feature can prevent needless responses to transient conditions.

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓=NEXT ↵=SELECT HOLD DELAY : 10:00 > RESTART : 00:06

If two or more outputs change state simultaneously, the Liebert AC4 begins a new countdown between each output change of state.

The default is 6 seconds (displayed as 00 MIN : 06 SEC).

  • From the Setup Operation Menu, choose Restart , as shown at right, and press Enter ↵ .
  • To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
  • For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.
  • Press Enter ↵ to advance to seconds (SEC).
  • For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.
  • When finished, press Enter ↵ again.

RESTART DELAY 00 MIN : 06 SEC

↑↓ =NEXT ↵ =EDIT

Show 4 more labels / short text on this page
Setup Operation Menu · Hold Delay Time · Setup Operation Menu · Restart Delay Time
Page 53 of the Emerson Surge Protector (AC4) user manual — FORCE ON ↑↓ =SELECT ↵ =END
Page 53 · click to enlarge
Page 53

System and Control Options

7.9 Override Output

The Override Output feature allows you to manually change the state of any digital output to ON or OFF, overriding automatic control by the Liebert AC4 (the default setting for all outputs). This menu also allows you to release the manual override, returning any output to automatic control.

There are two ways to override automatic control of outputs:

  • Use the Override Output menu, as described in this section, to turn any output ON or OFF.
  • Use the hardware switch on the circuit board to force all four outputs ON at the same time (see Item F - Manual Override Switch (outputs) in 1.6 Controller Board Overview ).

After an output is forced manually ON or OFF, it remains in that state until returned to automatic control through this menu.

Table 20 summarizes the four types of control, including the abbreviated message that appears on the LCD and in log reports.

Table 20 Automatic / manual control - output points

VIEW STATUS > SYSTEM AND CONTROL

AUTO Automatic Controlled by Liebert AC4 (default for all outputs)

↑↓ =NEXT ↵ =SELECT

FORCE ON Manually ON This output has been forced ON (operating) or OFF via the Override Output menu FORCE OFF Manually OFF

All outputs have been forced ON (operating) via the hardware switch on the circuit board (see Item F - Manual Override Switch (outputs) in 1.6 Controller Board Overview)

LOGIN

HW FORCE ON Manually ON (all outputs)

AAAA ↑↓ =SELECT ↵ =NEXT/END

System & Control Menu

To force an output point ON or OFF or return it to automatic control:

SETUP SYSTEM > OVERRIDE OUTPUT

Log In and Choose Override Output

CLEAR ALARMS & LOGS ↑↓ =NEXT ↵ =SELECT

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Override Output , then press Enter ↵ .

OVERRIDE OUTPUT > DEVICE_1 AUTO DEVICE_2 AUTO ↑↓=NEXT ↵=SELECT DEVICE_3 AUTO DEVICE_4 FORCE ON

The Select Output menu, shown at right, displays the current status of all four outputs.

  • Use the arrows ↑↓ to choose the output you want—for example, Device_1 —and press Enter ↵ .

Turn Output ON or OFF / Return to Automatic

SELECT DEVICE_1

  • From the Override Output menu, use the arrows ↑↓ to choose one of these options:

FORCE ON ↑↓ =SELECT ↵ =END

  • AUTO - return to automatic control
  • FORCE ON - manually turn this output ON (operating)
  • FORCE OFF - manually turn this output OFF
  • Press Enter ↵ .
Show 6 more labels / short text on this page
Main Menu · Message Description · Login · Select Output · Select an Output · Override Output
Page 54 of the Emerson Surge Protector (AC4) user manual — 7.10.3 Clear the Event Log
Page 54 · click to enlarge
Page 54

System and Control Options

7.10 Clear Alarms & Logs

The Clear Alarms & Logs menu allows you to clear active alarms or delete all records from either of the Liebert AC4 alarm and event logs.

Emerson Surge Protector (AC4) — 7.10 Clear Alarms & Logs diagram (page 54)
Fig. 35 · 7.10 Clear Alarms & Logs

To clear alarms or logs:

Log In and Choose Clear Alarms & Logs

  • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 7.1 Login for help) .
  • Enter your password at the Login screen.
  • From the System and Control Menu, use the arrows ↑↓ to choose Clear Alarms & Logs , then press Enter ↵ .
  • Use the following steps to clear alarms or delete log records.

7.10.1 Clear Active Alarms

SETUP SYSTEM OVERRIDE OUTPUT > CLEAR ALARMS & LOGS

To clear all active alarms:

  • From the Clear Alarms/Logs Menu, use the arrows ↑↓ to choose Clear Active Alarms , then press Enter ↵ .
  • Use the arrows ↑↓ to choose Y (Yes - clear all active alarms) or N (No - do not clear alarms), then press Enter ↵ .
Emerson Surge Protector (AC4) — 7.10.1 Clear Active Alarms diagram (page 54)
Fig. 36 · 7.10.1 Clear Active Alarms

CLEAR ALARM LOG CLEAR EVENT LOG ↑↓=NEXT ↵=SELECT

Clear Active Alarms CLEAR ACTIVE ALARMS ARE YOU SURE? N

7.10.2 Clear the Alarm Log

The alarm log contains up to 99 records of alarms that have occurred. You may want to clear the log after backing up the file or simply to free up space.

Emerson Surge Protector (AC4) — 7.10.2 Clear the Alarm Log diagram (page 54)
Fig. 37 · 7.10.2 Clear the Alarm Log

To delete all records from the alarm log:

Clear Alarm Log CLEAR ALARM LOG ARE YOU SURE? N

  • From the Clear Alarms/Logs Menu, use the arrows ↑↓ to choose Clear Alarm Log , then press Enter ↵ .
  • Use the arrows ↑↓ to choose Y (Yes - clear the alarm log) or N (No - do not clear the alarm log), then press Enter ↵ .

7.10.3 Clear the Event Log

The event log contains up to 99 records of events detected by the Liebert AC4. You may want to clear the log after backing up the file or simply to free up space.

Emerson Surge Protector (AC4) — 7.10.3 Clear the Event Log diagram (page 54)
Fig. 38 · 7.10.3 Clear the Event Log

CLEAR ACTIVE ALARMS CLEAR ALARM LOG > CLEAR EVENT LOG

Clear Event Log CLEAR EVENT LOG ARE YOU SURE? N

To delete all records from the event log:

  • From the Clear Alarms/Logs Menu, use the arrows ↑↓ to choose Clear Event Log , then press Enter ↵ .
  • Use the arrows ↑↓ to choose Y (Yes - clear the event log) or N (No - do not clear the event log), then press Enter ↵ .
Show 4 more labels / short text on this page
Main Menu · Clear Alarms/Logs Menu · Clear Alarms/Logs Menu · Clear Alarms/Logs Menu
Page 55 of the Emerson Surge Protector (AC4) user manual — UL UL3121
Page 55 · click to enlarge
Page 55

8.0 S PECIFICATIONS

8.1 Liebert AC4 Specifications

24VAC ±10% of nominal 50/60 Hz 1.3A, 30VA

Dimensions W x D x H, in. (mm) 14-1/4 x 2-3/4 x 12 (361.95 x 69.85 x 304.8)

Weight (Assembled) 7.68 lbs (3.48 kg)

Enclosure Type NEMA 1

Liquid Crystal Display (LCD) Four line, 20 character, backlit

Mounting Surface Building Wall or Structural Member

32°F to 104°F (0°C to 40°C) 0% RH to 95% RH (non-condensing)

A/D Resolution (Analog IN) 12 Bit

Clock Type Real-Time Clock

Clock battery backup type Lithium Cell (non-replaceable)

Clock battery life 7 years, constant, no power

UL UL3121

FCC Compliance CFR 47 Part 15

Inputs & Outputs (Quantity)

Digital Inputs (4) Dry Contact Closure 24VDC, 10 mA

Digital Outputs (4) 24VAC, 3A

Common Alarm Outputs (2) 24VAC, 3A

Show 13 more labels / short text on this page
Specifications · Power Requirements · Ambient Operating Environment · Processor Specifics · Model Motorola XC68HC812A4 · Clock speed 16MHz · Total RAM 32Kb · Total FLASH 4M · Total EEPROM 4K · Communications · Local Communications RS232 · Agency Listings · CE Yes
Page 56 of the Emerson Surge Protector (AC4) user manual — 8.0 Specifications
Page 56 · click to enlarge
Page 56

Specifications

Page 57 of the Emerson Surge Protector (AC4) user manual — SYSTEM & CONTROL FUNCTIONS
Page 57 · click to enlarge
Page 57

A PPENDIX A - S ERVICE T ERMINAL I NTERFACE

The Service Terminal Interface allows access to all functions of the Liebert AC4, including some that are not possible through the LCD interface. This interface is accessible through any computer using a communications program such as Microsoft® Windows® HyperTerminal.

This appendix provides directions for connecting to the Service Terminal Interface, an overview of each type of function and sample screens for each menu available through the Service Terminal Inter- face. References to more detailed instructions about each function are provided.

A.1 COMPARISON OF FUNCTIONS: LCD AND SERVICE TERMINAL INTERFACE

Table 21 lists all functions for viewing and configuring the Liebert AC4 and shows whether they can be performed through the LCD interface and where to find information.

Table 21 Guide to Liebert AC4 functions

Can be performed viaWhere to find:

Service Terminal screen examples

LCD

VIEW STATUS FUNCTIONS

View Active Alarms ✔ ✔ page 19 page 57

View Alarm Log ✔ ✔ page 20 page 58

View Event Log ✔ ✔ page 21 page 59

View Input Status ✔ ✔ page 22 page 59

View Output Status ✔ ✔ page 23 page 60

SILENCE ALARM & BACK UP LOGS FUNCTIONS

Silence Alarm (On the LCD, press any key to silence an alarm) ✔ ✔ page 24 page 61

Back Up Log Files — ✔ page 25 page 62

SYSTEM & CONTROL FUNCTIONS

Login ✔ ✔ page 27 page 63

Setup System ✔ ✔ page 29 page 64

Setup Inputs ✔ ✔ page 29 page 65

Setup Common Alarm ✔ ✔ page 32 page 66

Setup Zones ✔ ✔ page 33 page 66

Setup Outputs ✔ ✔ page 34 page 67

Setup System Info ✔ ✔ page 36 page 68

Change Password ✔ ✔ page 36 page 68

Set Date & Time/Automatic Daylight Saving Time ✔ ✔ page 37 page 69

Setup Site ID ✔ ✔ page 37 page 69

Backup and Upload Configuration File — ✔ page 38 page 70

Factory Defaults ✔ ✔ page 41 page 71

Perform Firmware Update — ✔ page 41 page 72

Setup Operation ✔ ✔ page 43 page 73

Override Output ✔ ✔ page 47 page 76

Clear Alarms & Logs ✔ ✔ page 48 page 77

Clear Active Alarms ✔ ✔ page 48 page 77

Clear the Alarm Log ✔ ✔ page 48 page 77

Clear the Event Log ✔ ✔ page 48 page 78

Show 5 more labels / short text on this page
Service Terminal Interface · Service Terminal · Instructions on · Function · using function
Page 58 of the Emerson Surge Protector (AC4) user manual — A.2 C ONNECTING TO THE S ERVICE T ERMINAL I NTERFACE
Page 58 · click to enlarge
Page 58

Connecting to the Service Terminal Interface

A.2 C ONNECTING TO THE S ERVICE T ERMINAL I NTERFACE

This section describes how to set up and connect to the Service Terminal Interface. To access the Ser- vice Terminal Interface, you will need:

  • A null modem cable to connect a computer’s COM1 port to the Liebert AC4’s RS232 port.
  • A communications program, such as HyperTerminal, to connect to the Service Terminal Interface.

Refer to following sections for step-by-step instructions to set up a connection (one time) and use that connection to access the Service Terminal Interface:

  • A.2.1 - Create a Connection
  • A.2.2 - Connect to the Service Terminal Interface

The instructions in this section refer to the HyperTerminal program—they may vary for other com- munications programs.

Page 59 of the Emerson Surge Protector (AC4) user manual — A.2.1 Create a Connection
Page 59 · click to enlarge
Page 59

Connecting to the Service Terminal Interface

A.2.1 Create a Connection

Before connecting to the Service Terminal Interface, you must create a connection and specify the method to be used for connection, as described in the following steps.

1. Start the HyperTerminal program—to do this, click on the Start button, then on Programs , then Accessories , then Communications , and finally HyperTerminal . 2. At the top of the HyperTerminal window, click on File , then on New Connection , as shown below left.
Emerson Surge Protector (AC4) — A.2.1 Create a Connection diagram (page 59)
Fig. 39 · A.2.1 Create a Connection
Emerson Surge Protector (AC4) — A.2.1 Create a Connection diagram (page 59)
Fig. 40 · A.2.1 Create a Connection

Enter a name for the connection - for example, AC4

3. In the Connection Description window, shown above right, enter a name for the connection—for example, AC4 . This becomes the file name (with the extension “ .ht ”). 4. Click OK to close the window. The Connect To window opens, as shown at right.
Emerson Surge Protector (AC4) — A.2.1 Create a Connection diagram (page 59)
Fig. 41 · A.2.1 Create a Connection

Specify COM Port Connection 5. In the Connect To window, select COM1 from the Connect Using drop-down list. 6. Click OK. This opens the COM1 Properties window.

COM1 Port Setup 7. In the COM1 Properties window, shown at right, make the following selections:

  • Bits per second: 9600
  • Data bits: 8
  • Parity: None
  • Stop bits: 1
  • Flow control: None 8. Click OK . When the connection is open, the connection name appears in the title bar of the HyperTerminal window. To complete the setup, continue with Step 9 (next section).
Emerson Surge Protector (AC4) — A.2.1 Create a Connection diagram (page 59)
Fig. 42 · A.2.1 Create a Connection

Choose COM1 · COM1 Properties

Page 60 of the Emerson Surge Protector (AC4) user manual — Properties Setup
Page 60 · click to enlarge
Page 60

Connecting to the Service Terminal Interface

Properties Setup 9. Open the Properties window by clicking on File, then on Properties, as shown below left.

Emerson Surge Protector (AC4) — Properties Setup diagram (page 60)
Fig. 43 · Properties Setup
Emerson Surge Protector (AC4) — Properties Setup diagram (page 60)
Fig. 44 · Properties Setup
  • 10. In the Properties window, above right, click on the Settings tab and choose the following settings:
  • Function, arrow, and ctrl keys act as: Terminal keys
  • Backspace key sends: Ctrl+H
  • Emulation: ANSIW
  • Telnet terminal ID: VT100
  • Backscroll buffer lines: 500
  • Play sound when connecting or disconnecting: Unchecked

ASCII Setup 11. In the Properties window, click on the ASCII Setup button, shown below left.

Emerson Surge Protector (AC4) — Properties Setup diagram (page 60)
Fig. 45 · Properties Setup
  • 12. In the ASCII Setup window, shown above right, choose the following settings:
  • ASCII Sending: place a check mark ( ✔ ) in the Send Line Ends With Line Feeds box.
  • ASCII Receiving: place a check mark ( ✔ ) in the Wrap Lines That Exceed Terminal Width box.
  • Click OK .

The setup is now complete. To use the new connection, proceed to the next section, A.2.2 - Connect to the Service Terminal Interface.

Settings tab · ASCII Setup button

Page 61 of the Emerson Surge Protector (AC4) user manual — A.2.2 Connect to the Service Terminal Interface
Page 61 · click to enlarge
Page 61

Connecting to the Service Terminal Interface

A.2.2 Connect to the Service Terminal Interface

After creating and setting up a connection, use a communications program such as HyperTerminal to access the Liebert AC4’s Service Terminal Interface.

1. Verify communications connections between the remote computer and the Liebert AC4. Connect a null modem cable from the computer’s COM1 port to the Liebert AC4’s RS232 port (for location, see 3.4 - RS232 Connector). 2. Start the HyperTerminal program—click on the Start button, then on Programs, then Accessories, then Communications, and finally HyperTerminal. 3. Open the Liebert AC4 connection created in A.2.1 - Create a Connection. To do this, click on File, then on Open, as shown below.

Emerson Surge Protector (AC4) — A.2.2 Connect to the Service Terminal Interface diagram (page 61)
Fig. 46 · A.2.2 Connect to the Service Terminal Interface
Emerson Surge Protector (AC4) — A.2.2 Connect to the Service Terminal Interface diagram (page 61)
Fig. 47 · A.2.2 Connect to the Service Terminal Interface

Click on the file name - for example, AC4.ht

4. In the Open window, shown above right, select the file name— AC4.ht in this example—and then click on the Open button. 5. Press Enter (or Escape) to initiate communication and bring up the Main Menu.

For more information on the Liebert AC4’s options:

  • See A.3 - Overview of Menus for examples of the Service Terminal Interface screens.
  • See Table 21 to locate step-by-step instructions for each Liebert AC4 function.
Page 62 of the Emerson Surge Protector (AC4) user manual — A.3.3 Setup Menu Overview
Page 62 · click to enlarge
Page 62

A.3 O VERVIEW OF M ENUS

The Main Menu offers choices for viewing the status of the Liebert AC4, silencing the audible alarm and backing up the unit’s log files. It also allows access to the System and Control features, which require a password.

The following shows where to find examples of the Main Menu screens:

Main Menu For sample screens, see:

1=VIEW ACTIVE ALARMS A.4 - View Status Menus

2=VIEW ALARM LOG

3=VIEW EVENT LOG

4=VIEW INPUT STATUS

5=VIEW OUTPUT STATUS

6=SILENCE ALARM A.5 - Silence Alarm & Back Up Log Files (Service Terminal Interface only) 7=BACKUP LOG FILES

0=SETUP SYSTEM-LOGIN REQUIRED A.6 - Setup Menu

A.3.1 View Status Overview

The View Status features are available to all users. This permits all personnel to check on the status of any equipment or location being monitored. These options allow any user to:

  • View active alarms
  • View the current status of all inputs and outputs
  • View data stored in alarm and event logs

A.3.2 Silence Alarm and Backup Log Files

Two Main Menu options—Silence Alarm and Backup Log Files—are unique to the Service Terminal Interface. As with the View Status options, these features do not require a password:

  • Silence Alarm —silence the Liebert AC4’s audible alarm and reset the Common Alarm Relay output.
  • Backup Log Files —make backup copies of the Liebert AC4’s Alarm Log and Event Log and save the copies to a computer.

A.3.3 Setup Menu Overview

The Setup Menu options require a password. Authorized users may:

  • Configure the Liebert AC4—this includes setting up digital inputs and outputs and system features such as setting the date and time Two system features— Backup and Upload Configuration File and Firmware Update —are unique to the Service Terminal Interface.
  • Override automatic control of outputs to force an output ON or OFF
  • Clear active alarms and delete all records in the alarm and event logs

Overview of Menus

Page 63 of the Emerson Surge Protector (AC4) user manual — DEVICE_1 ALARM CONTACT CLOSED
Page 63 · click to enlarge
Page 63

A.4 V IEW S TATUS M ENUS

The View Status menu allows any user to view currently active alarms, data stored in the alarm and event logs and the status of all inputs and outputs.

Main Menu

After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This section presents Service Terminal Interface screens for options 1 through 5:

VX.XXX.X LIEBERT CORPORATION COPYRIGHT 2004

ALL RIGHTS RESERVED

MAIN MENU

For sample screens, see:

1=VIEW ACTIVE ALARMS Section A.4.1

2=VIEW ALARM LOG Section A.4.2

3=VIEW EVENT LOG Section A.4.3

4=VIEW INPUT STATUS Section A.4.4

5=VIEW OUTPUT STATUS Section A.4.5

6=SILENCE ALARM

7=BACKUP LOG FILES

0=SETUP SYSTEM-LOGIN REQUIRED

SELECT A NUMBER:1

A.4.1 View Active Alarms

For details on this feature, see 5.1 - View Active Alarms.

ACTIVE ALARMS

Input points/hardware presently in an alarm state

DEVICE_1 ALARM CONTACT CLOSED

1=REFRESH ACTIVE ALARMS 2=RETURN TO MAIN MENU

SELECT A NUMBER:

View Status Menus · Main Menu · View Active Alarms

Page 64 of the Emerson Surge Protector (AC4) user manual — ALARM LOG
Page 64 · click to enlarge
Page 64

A.4.2 View Alarm Log

For details on this feature, see 5.2 - View Alarm Log.

ALARM LOG

DEVICE_1 ALARM CONTACT CLOSED 29-AUG-02 09:29:10

NO STANDBY AVAILABLE 29-AUG-02 09:20:10

STANDBY DEVICE FAILED 29-AUG-02 09:19:10

NO RESTART AVAILABLE 29-AUG-02 09:19:10

<ENTER>=MORE <ESC>=EXIT <A>=ALL

DEVICE_2 ALARM CONTACT CLOSED 28-AUG-02 09:29:10

1=REFRESH ALARM LOG 2=RETURN TO MAIN MENU

SELECT A NUMBER:

View Status Menus · View Alarm Log · Alarm history

Page 65 of the Emerson Surge Protector (AC4) user manual — INPUT STATUS
Page 65 · click to enlarge
Page 65

A.4.3 View Event Log

For details on this feature, see 5.3 - View Event Log.

EVENT LOG

SYSTEM USER LOGIN 07-MAY-02 10:29:10

DEVICE_1 HW FORCE ON CONTACT CLOSED 07-MAY-02 09:50:10

DEVICE_4 FORCE OFF CONTACT OPEN 07-MAY-02 09:20:10

DEVICE_3 AUTO CONTACT OPEN 07-MAY-02 06:20:10

<ENTER>=MORE <ESC>=EXIT <A>=ALL

DATE AND TIME SET 06-MAY-02 07:10:10

DEVICE_4 FORCE OFF CONTACT CLOSED 07-MAY-02 06:20:10

1=REFRESH EVENT LOG 2=RETURN TO MAIN MENU

SELECT A NUMBER:

A.4.4 View Input Status

For details on this feature, see 5.4 - View Input Status.

INPUT STATUS

Input status from device

INPUT STATUS

DEVICE_1 NORMAL DEVICE_2 ALARM DEVICE_3 EVENT DEVICE_4 ALARM

1=REFRESH INPUT 2=RETURN TO MAIN MENU

SELECT A NUMBER:1

Show 4 more labels / short text on this page
View Status Menus · View Event Log · Event history · View Input Status
Page 66 of the Emerson Surge Protector (AC4) user manual — 1=REFRESH OUTPUT STATUS 2=RETURN TO MAIN MENU
Page 66 · click to enlarge
Page 66

A.4.5 View Output Status

For details on this feature, see 5.5 - View Output Status.

OUTPUT STATUS

Output status to device

OUTPUT STATE MODE ZONE

***************************************** OPERATING = OPERATING/ON STANDBY = IN STANDBY MODE ALARM = IN ALARM FORCE ON = FORCE ON BY OPERATOR FORCE OFF = FORCE OFF BY OPERATOR HW FORCE ON = FORCE ON BY HARDWARE SWITCH PENDING = PENDING DELAY TIMER NOT USED = DEVICE NOT USED *****************************************

DEVICE_1 ON ALARM 1 DEVICE_2 ON OPERATING 1 DEVICE_3 OFF STANDBY 1 DEVICE_4 OFF ALARM 1

1=REFRESH OUTPUT STATUS 2=RETURN TO MAIN MENU

SELECT A NUMBER:

View Status Menus · View Output Status

Page 67 of the Emerson Surge Protector (AC4) user manual — 1=SILENCE ALARM 2=RETURN TO MAIN MENU
Page 67 · click to enlarge
Page 67

Silence Alarm & Back Up Log Files (Service Terminal Interface only)

A.5 SILENCE ALARM & BACK UP LOG FILES (SERVICE TERMINAL INTERFACE ONLY)

This section presents two options from the Main Menu that are available via the Service Terminal Interface only.

Main Menu

After connecting to the Service Terminal Interface, the Main Menu appears, as shown below. This section presents Service Terminal Interface screens for options 6 and 7:

V5.300.2 LIEBERT CORPORATION COPYRIGHT 2004

ALL RIGHTS RESERVED

MAIN MENU

1=VIEW ACTIVE ALARMS

2=VIEW ALARM LOG

3=VIEW EVENT LOG

4=VIEW INPUT STATUS

5=VIEW OUTPUT STATUS For sample screens, see:

6=SILENCE ALARM Section A.5.1

7=BACKUP LOG FILES Section A.5.2

0=SETUP SYSTEM-LOGIN REQUIRED

SELECT A NUMBER:1

A.5.1 Silence Alarm (Service Terminal Interface only)

For details on this feature, see 6.1 - Silence Alarm (Service Terminal Interface).

SILENCE ALARM

Silence alarm and reset common alarm relay if common alarm relay is configured to reset with silence alarm

1=SILENCE ALARM 2=RETURN TO MAIN MENU

SELECT A NUMBER:1

>ALARM HAS BEEN SILENCED

Main Menu · Silence Alarm

Page 68 of the Emerson Surge Protector (AC4) user manual — >BACKUP SUCCESSFUL
Page 68 · click to enlarge
Page 68

Silence Alarm & Back Up Log Files (Service Terminal Interface only)

A.5.2 Back Up Log Files (Service Terminal Interface only)

For details on this feature, see 6.2 - Back Up Log Files (Service Terminal Interface only).

Back Up Alarm Log File

Backup Log Files - Alarm Log File

BACKUP LOG FILES

Backup alarm and event log files

1=BACKUP ALARM LOG FILE 2=BACKUP EVENT LOG FILE 3=RETURN TO MAIN MENU

SELECT A NUMBER:1

>INITIATE A BACKUP OF ALARM LOG-YES(Y) OR NO(N)? >[N] >[

INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., ALARM.LOG

>BACKUP SUCCESSFUL

Back Up Event Log File

Backup Log Files - Event Log File

BACKUP LOG FILES

Backup alarm and event log files

1=BACKUP ALARM LOG FILE 2=BACKUP EVENT LOG FILE 3=RETURN TO MAIN MENU

SELECT A NUMBER:2

>INITIATE A BACKUP OF EVENT LOG-YES(Y) OR NO(N)? >[N] >[

INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME, E.G., EVENT.LOG

>BACKUP SUCCESSFUL

Page 69 of the Emerson Surge Protector (AC4) user manual — LOGIN WITH 4 CHARACTER PASSWORD
Page 69 · click to enlarge
Page 69

A.6 S ETUP M ENU

The Setup menu allows the user to configure the Liebert AC4—setting up inputs, outputs and system features such as date and time, as well as operation options such as a rotation sequence and standy testing. This menu also provides a vehicle for manually changing the state of an output to ON or OFF, clearing active alarms and deleting records from the Liebert AC4’s alarm and event logs.

Main Menu

After connecting to the Service Terminal Interface, the Main Menu appears, as shown below.

VX.XXX.X LIEBERT CORPORATION COPYRIGHT 2004

ALL RIGHTS RESERVED

MAIN MENU

1=VIEW ACTIVE ALARMS 2=VIEW ALARM LOG 3=VIEW EVENT LOG 4=VIEW INPUT STATUS 5=VIEW OUTPUT STATUS 6=SILENCE ALARM 7=BACKUP LOG FILES 0=SETUP SYSTEM-LOGIN REQUIRED

SELECT A NUMBER:0

  • Choose 0 to access the features illustrated in this section.

Login Menu

The System and Control options require a password to prevent unauthorized users from making changes to the system. After choosing 0 in the Main Menu above, the Login Menu appears:

YOU MUST LOGIN TO PERFORM SETUP OR TO MAKE CHANGES

LOGIN WITH 4 CHARACTER PASSWORD

>INVALID PASSWORD, ENTER AGAIN >PRESS <ESC> TO EXIT

  • Enter the password, and the Setup Menu appears, as shown in the following section.
Show 5 more labels / short text on this page
Setup Menu · Main Menu · Login · >**** · >
Page 70 of the Emerson Surge Protector (AC4) user manual — >CHANGE LABEL(8 CHARACTERS MAX). >[DEVICE_1] >[ >COMMAND SUCCESSFUL
Page 70 · click to enlarge
Page 70

Setup Menu

This section presents Service Terminal Interface screens for each of the following:

SETUP MENU SeeDescription

1=SETUP INPUTS Section A.6.1 Configure digital inputs

2=SETUP COMMON ALARM Section A.6.2 Set up the common alarm to reset with silence

3=SETUP ZONES Section A.6.3 Define areas with 2-4 devices each

4=SETUP OUTPUTS Section A.6.4 Configure digital outputs

5=SETUP SYSTEM INFORMATION* Section A.6.5 Set up features such as password and date & time*

6=SETUP OPERATION Section A.6.6 Set up rotation sequence, standby testing

7=OVERRIDE OUTPUT Section A.6.7 Manually override automatic control of outputs

8=CLEAR ALARMS&LOGS Section A.6.8 Clear active alarms; clear alarm and event logs

9=RETURN TO MAIN MENU

SELECT A NUMBER:

* Setup System Information features are:

  • Change Password
  • Set Date & Time/Automatic Daylight Saving Time
  • Setup Site ID
  • Backup and Upload Configuration File (Service Terminal Interface only)
  • Factory Defaults
  • Firmware Update (Service Terminal Interface only) Note that two of these system features— Backup and Upload Configuration File and Firmware Update —are unique to the Service Terminal Interface.

Use the following tips when making changes in the Service Terminal Interface:

  • Data that can be entered is shown in parentheses ( ) in prompt line.
  • The current setting is shown in brackets [ ] in the line below the prompt
  • To accept the current setting, press the Enter key.
  • To change the current setting, enter the value and then press Enter.
  • Pressing Escape will exit the current setup function or take you to the previous menu screen.

Values that may be entered shown in parentheses ( ) Current setting shown in brackets [ ]

>CHANGE LABEL(8 CHARACTERS MAX). >[DEVICE_1] >[ >COMMAND SUCCESSFUL

>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)? >[NO] >[ >COMMAND SUCCESSFUL

Setup Menu · Setup Menu

Page 71 of the Emerson Surge Protector (AC4) user manual — EV=EVENT AL=ALARMABLE
Page 71 · click to enlarge
Page 71

A.6.1 Setup Inputs

For details on this feature, see 7.3 - Setup System - Setup Inputs.

SETUP INPUTS

Setup input of device

Select input to edit

INPUT DEFINITION

**************************** NO=NORMALLY OPENED NC=NORMALLY CLOSED

1=DEVICE_1 NO-EV-NL-00:01 2=DEVICE_2 NO-AL-L -00:01 3=DEVICE_3 NC-EV-NL-00:01 4=DEVICE_4 NO-AL-L -00:01 5=RETURN TO SETUP MENU 6=RETURN TO MAIN MENU

EV=EVENT AL=ALARMABLE

NL=NOT LATCHED L =LATCHED

SELECT A NUMBER:1

MIN:SEC=DELAY TIME BEFORE

INPUT WILL TRIGGER

NOTE:EVENT CANNOT BE LATCHED ****************************

>CHANGE LABEL(8 CHARACTERS MAX). >[DEVICE_1] >[ >COMMAND SUCCESSFUL

>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)? >[NO] >[ >COMMAND SUCCESSFUL

>IS INPUT AN ALARM(AL) OR EVENT(EV)? >[AL] >[ >COMMAND SUCCESSFUL

>IS ALARM LATCHED-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL

>DELAY TIME BEFORE TRIGGER (MM:SS)? >[00:01] >[ >COMMAND SUCCESSFUL

Setup Menu · Setup Inputs

Page 72 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 72 · click to enlarge
Page 72

A.6.2 Setup Common Alarm

For details on this feature, see 7.4 - Setup System - Setup Common Alarm.

SETUP COMMON ALARM

Select if the common alarm relay contact is to reset with silence alarm CURRENT SETTING

N 1=SETUP COMMON ALARM 2=RETURN TO SETUP MENU 3=RETURN TO MAIN MENU

SELECT A NUMBER:1

>RESET COMMON ALARM WITH SILENCE-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL

A.6.3 Setup Zones

For details on this feature, see 7.5 - Setup System - Setup Zones.

SETUP ZONES

Select zones and number

of devices in the zone

ZONE # DEVICES

1=ZONE 1 2 2=ZONE 2 2 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

># DEVICES IN ZONE 1 >[2] >[ >COMMAND SUCCESSFUL

Setup Menu · Setup Common Alarm · Setup Zones

Page 73 of the Emerson Surge Protector (AC4) user manual — SETUP OUTPUTS
Page 73 · click to enlarge
Page 73

A.6.4 Setup Outputs

For details on this feature, see 7.6 - Setup System - Setup Outputs.

SETUP OUTPUTS

Setup output of device

Select output to edit

OUTPUT DEFINITION ******************************************* NO=NORMALLY OPENED 1=DEVICE_1 NO-OP-E NC=NORMALLY CLOSED 2=DEVICE_2 NO-ST-E 3=DEVICE_3 NO-NU-D OP=OPERATING/ON 4=DEVICE_4 NO-NU-D ST=STANDBY MODE 5=RETURN TO SETUP MENU NU=NOT USED 6=RETURN TO MAIN MENU D=DISABLE DEVICE ON AN ALARM CONDITION SELECT A NUMBER:1 E=LEAVE DEVICE OPERATING ON ALARM CONDITION *******************************************

>SET TO NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC) >[NO] >[ >COMMAND SUCCESSFUL

>DEVICE_1 TO OPERATING/ON(OP), STANDBY MODE(ST), NOT USED(NU) >[OP] >[ >COMMAND SUCCESSFUL

>DEVICE_1 TO ENABLE(E) OR DISABLE(D) DEVICE ON ALARM >[E] >[ >COMMAND SUCCESSFUL

Setup Menu · Setup Outputs

Page 74 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 74 · click to enlarge
Page 74

A.6.5 Setup System Info

This section presents Service Terminal Interface screens for choices 1 through 9 in the Setup System Information menu shown below. For details on this topic, see 7.7 - Setup System - Setup System Info.

SETUP SYSTEM INFORMATION

1=CHANGE PASSWORD

2=SET DATE & TIME

3=SETUP SITE ID

4=BACKUP & UPLOAD CONFIGURATION FILE

5=RESTORE PANEL TO FACTORY DEFAULTS

6=PERFORM FIRMWARE UPDATE

7=RETURN TO SETUP MENU

8=RETURN TO MAIN MENU

SELECT A NUMBER:

For details on this feature, see 7.7.1 - Change Password.

CHANGE PASSWORD

1=CHANGE PASSWORD 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

>ENTER ORIGINAL PASSWORD(MUST BE 4 CHARACTERS). >

>ENTER NEW PASSWORD(MUST BE 4 CHARACTERS). >

>ENTER NEW PASSWORD AGAIN FOR CONFIRMATION. >

>PASSWORD CHANGE SUCCESSFUL

Show 4 more labels / short text on this page
Setup Menu · Setup System Info · Change Password · Change Password
Page 75 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 75 · click to enlarge
Page 75

Set Date & Time/Automatic Daylight Saving Time

For details on this feature, see 7.7.2 - Set Date & Time/Automatic Daylight Saving Time.

Set Date & Time

SET DATE & TIME

CURRENT DATE & TIME DST 28-AUG-04 14:45:10 Y 1=SET DATE & TIME 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

>SET DATE & TIME(DD-MON-YY HR:MM:SS) >[28-AUG-02 14:45:10] >[ >COMMAND SUCCESSFUL

>ENABLE DAYLIGHT SAVINGS TIME-YES(Y) OR NO(N)? >[Y] >[ >COMMAND SUCCESSFUL

Setup Site ID

For details on this feature, see 7.7.3 - Setup Site ID.

SETUP SITE ID

Define name to reference panel

CURRENT SITE ID

1=SETUP SITE ID 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

>ENTER SITE ID NAME(40 CHARACTERS MAX). >[] >[ >COMMAND SUCCESSFUL

Setup Menu · Setup Site ID

Page 76 of the Emerson Surge Protector (AC4) user manual — >BACKUP SUCCESSFUL
Page 76 · click to enlarge
Page 76

Backup and Upload Configuration File (Service Terminal Interface only)

For details on this feature, see 7.7.4 - Backup and Upload Configuration File (Service Termi- nal Interface only).

Backup & Upload Configuration File - Backup

BACKUP AND UPLOAD CONFIGURATION FILE

Backup from panel saves panel configurations Upload to panel restores panel configurations

Select to backup or upload file

1=BACKUP CONFIGURATION FILE 2=UPLOAD CONFIGURATION FILE 3=RETURN TO SETUP SYSTEM INFO MENU 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU

SELECT A NUMBER:1

>INITIATE A BACKUP OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[

INSTRUCTIONS TO PERFORM BACKUP: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT RECEIVE FILE - ENTER FOLDER WHERE FILE IS TO BE RECEIVED - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT RECEIVE BUTTON AND ENTER FILE NAME,,E.G., AC4_CONF.SAV

>BACKUP SUCCESSFUL

Setup Menu

Page 77 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 77 · click to enlarge
Page 77

Backup & Upload Configuration File - Upload

BACKUP AND UPLOAD CONFIGURATION FILE

Backup from panel saves panel configurations Upload to panel restores panel configurations

Select to backup or upload file

1=BACKUP CONFIGURATION FILE 2=UPLOAD CONFIGURATION FILE 3=RETURN TO SETUP SYSTEM INFO MENU 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU

SELECT A NUMBER:2

>INITIATE AN UPLOAD OF CONFIGURATION FILE-YES(Y) OR NO(N)? >[N] >[

INSTRUCTIONS TO PERFORM UPLOAD: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT SEND FILE - ENTER FILE NAME-CONFIGURATION FILE LOCATION & NAME,E.G., AC4_CONF.SAV - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT SEND BUTTON

>UPLOAD SUCCESSFUL

Factory Defaults

For details on this feature, see 7.7.5 - Factory Defaults.

RESTORE FACTORY DEFAULTS

This command restores all panel information to factory settings

1=RESTORE FACTORY DEFAULTS 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

>RESTORE THE PANEL TO FACTORY SETTINGS-YES(Y) OR NO(N)? >[N] [ >COMMAND SUCCESSFUL

Setup Menu · Factory Defaults

Page 78 of the Emerson Surge Protector (AC4) user manual — >FIRMWARE UPDATE SUCCESSFUL
Page 78 · click to enlarge
Page 78

Firmware Update (Service Terminal Interface only)

For details on this feature, see 7.7.6 - Perform Firmware Update (Service Terminal Interface only).

PERFORM FIRMWARE UPDATE

This command will update the existing firmware

1=PERFORM FIRMWARE UPDATE 2=RETURN TO SETUP SYSTEM INFO MENU 3=RETURN TO SETUP MENU 4=RETURN TO MAIN MENU

SELECT A NUMBER:1

>PERFORM FIRMWARE UPDATE-YES(Y) OR NO(N)? >[N] >[

INSTRUCTIONS TO PERFORM FIRMWARE UPDATE: ASSUMES USING MICROSOFT WINDOWS HYPERTERMINAL APPLICATION - SELECT TRANSFER FROM THE TOOLBAR - SELECT SEND FILE - ENTER FILE NAME-FIRMWARE FILE LOCATION & NAME,E.G., PROG####.S19 - SELECT XMODEM FROM THE PROTOCOL BOX - SELECT SEND BUTTON

>WAITING TO SEND PROGRAM FILE >DONE

>CHECKSUM IS >PROGRAM VERSION >WAITING TO SEND FLASH FILE >DONE

>FIRMWARE UPDATE SUCCESSFUL

Setup Menu · Firmware Update

Page 79 of the Emerson Surge Protector (AC4) user manual — >AT >[00:00] >[ >COMMAND SUCCESSFUL
Page 79 · click to enlarge
Page 79

A.6.6 Setup Operation

For details on this feature, see 7.8 - Setup Operation.

Auto Sequencing

For details on this feature, see 7.8.1 - Turn Automatic Sequencing On or Off.

Setup Operation - Auto Sequencing

SETUP OPERATION

Select operation to edit

OPERATION STATE

1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU

SELECT A NUMBER:1

>AUTO SEQUENCING- N FOR ON, F FOR OFF >[N] >[N] >COMMAND SUCCESSFUL

>EVERY ## DAYS (.5 FOR 12 HOUR) >[03] DAYS >[ >COMMAND SUCCESSFUL

>AT >[00:00] >[ >COMMAND SUCCESSFUL

Setup Menu

Page 80 of the Emerson Surge Protector (AC4) user manual — >EVERY ## DAYS >[03] DAYS >[ >COMMAND SUCCESSFUL
Page 80 · click to enlarge
Page 80

Standby Testing

For details on this feature, see 7.8.2 - Turn Standby Testing On or Off.

Setup Operation - Standby Testing

SETUP OPERATION

Select operation to edit

OPERATION STATE

1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU

SELECT A NUMBER:2

>STANDBY TESTING- N FOR ON, F FOR OFF >[N] >[N] >COMMAND SUCCESSFUL

>EVERY ## DAYS >[03] DAYS >[ >COMMAND SUCCESSFUL

>AT >[00:00] >[ >COMMAND SUCCESSFUL

>FOR >[10] MIN >[ >COMMAND SUCCESSFUL

Setup Menu

Page 81 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:4
Page 81 · click to enlarge
Page 81

Failed Standby

For details on this feature, see 7.8.3 - Specify Failed Standby Response.

Setup Operation - Failed Standby

SETUP OPERATION

Select operation to edit

OPERATION STATE

1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU

SELECT A NUMBER:3

>IF FAILED STANDBY,IN SAME FAILED ZONE, ENABLE A DISABLED UNIT-YES(Y) OR NO(N)? >[N] >[Y] >COMMAND SUCCESSFUL

Hold Delay

For details on this feature, see 7.8.4 - Specify Hold Delay Time.

Setup Operation - Hold Delay

SETUP OPERATION

Select operation to edit

OPERATION STATE

1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU

SELECT A NUMBER:4

>HOLD DELAY (MM:SS) > [10:00] >[ >COMMAND SUCCESSFUL

Setup Menu

Page 82 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:1
Page 82 · click to enlarge
Page 82

Restart Delay

For details on this feature, see 7.8.5 - Specify Restart Time.

Setup Operation - Restart Delay

SETUP OPERATION

Select operation to edit

OPERATION STATE

1=AUTO SEQUENCING OFF 2=STANDBY TESTING OFF 3=FAILED STANDBY N 4=HOLD DELAY 10:00 5=RESTART DELAY 00:06 6=RETURN TO SETUP MENU 7=RETURN TO MAIN MENU

SELECT A NUMBER:5

>DELAY BEFORE STARTUP UNIT(MM:SS)? >[00:06] >[ >COMMAND SUCCESSFUL

A.6.7 Override Output

For details on this feature, see 7.9 - Override Output.

OVERRIDE OUTPUT

Select output to override

OUTPUT CONTROL

1=DEVICE_1 AUTO ******************************** 2=DEVICE_2 AUTO AUTO = CONTROL BY PANEL 3=DEVICE_3 FORCE ON FORCE ON = FORCE ON BY OPERATOR 4=DEVICE_4 FORCE ON FORCE OFF= FORCE OFF BY OPERATOR 5=RETURN TO SETUP MENU ******************************** 6=RETURN TO MAIN MENU

SELECT A NUMBER:1

>OVERRIDE OUTPUT DEVICE_1-AUTO(2),FORCE ON(1),FORCE OFF(0). >[2] >[ >COMMAND SUCCESSFUL

Show 4 more labels / short text on this page
Setup Menu · Override Output · Manually override · an output point
Page 83 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:2
Page 83 · click to enlarge
Page 83

A.6.8 Clear Alarms & Logs

For details on this topic, see 7.10 - Clear Alarms & Logs.

Clear Active Alarms

For details on this feature, see 7.10.1 - Clear Active Alarms.

Clear Alarms & Logs - Clear Active Alarms

CLEAR ALARMS&LOGS

Clear active alarms or log records

Select the log to clear

1=CLEAR ACTIVE ALARMS 2=CLEAR ALARM LOG 3=CLEAR EVENT LOG 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU

SELECT A NUMBER:1

>CLEAR ALL THE ACTIVE ALARMS-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL

Clear the Alarm Log

For details on this feature, see 7.10.2 - Clear the Alarm Log.

Clear Alarms & Logs - Clear the Alarm Log

CLEAR ALARMS&LOGS

Clear active alarms or log records

Select the log to clear

1=CLEAR ACTIVE ALARMS 2=CLEAR ALARM LOG 3=CLEAR EVENT LOG 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU

SELECT A NUMBER:2

>CLEAR ALL RECORDS IN THE ALARM LOG-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL

Setup Menu

Page 84 of the Emerson Surge Protector (AC4) user manual — SELECT A NUMBER:3
Page 84 · click to enlarge
Page 84

Clear the Event Log

For details on this feature, see 7.10.3 - Clear the Event Log.

Clear Alarms & Logs - Clear the Event Log

CLEAR ALARMS&LOGS

Clear active alarms or log records

Select the log to clear

1=CLEAR ACTIVE ALARMS 2=CLEAR ALARM LOG 3=CLEAR EVENT LOG 4=RETURN TO SETUP MENU 5=RETURN TO MAIN MENU

SELECT A NUMBER:3

>CLEAR ALL RECORDS IN THE EVENT LOG-YES(Y) OR NO(N)? >[N] >[ >COMMAND SUCCESSFUL

Setup Menu

Page 85 of the Emerson Surge Protector (AC4) user manual — NOTES
Page 85 · click to enlarge
Page 85

NOTES

Specifications

Page 86 of the Emerson Surge Protector (AC4) user manual — Clear the Event Log
Page 86 · click to enlarge
Page 86

Specifications

Page 87 of the Emerson Surge Protector (AC4) user manual — Clear the Event Log
Page 87 · click to enlarge
Page 87

Specifications

Page 88 of the Emerson Surge Protector (AC4) user manual — Clear the Event Log
Page 88 · click to enlarge
Page 88
Page 88 of the Emerson Surge Protector (AC4) user manual — Clear the Event Log
Page 89 of the Emerson Surge Protector (AC4) user manual — SL-31210_REV1_02-13
Page 89 · click to enlarge
Page 89

Ensuring The High Availability Of Mission-Critical Data And Applications.

Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™

Technical Support / Service

Web Site www.liebert.com

from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.

Monitoring liebert.monitoring@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Single-Phase UPS & Server Cabinets

liebert.upstech@emerson.com

800-222-5877 Outside North America+00800 1155 4499

Three-Phase UPS & Power Systems

800-543-2378 Outside North America614-841-6598
800-543-2778 Outside the United States614-888-0246

Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2012 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center

Philippines +63 2 687 6615 Fax: +63 2 730 9572

SL-31210_REV1_02-13

Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com

Embedded Computing Embedded Power

Racks & Integrated Cabinets Services

Power Switching & Controls Precision Cooling

Infrastructure Management & Monitoring

Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2012 Emerson Electric Co.

Show 6 more labels / short text on this page
Environmental Systems · Pasig City 1605 · AC Power Connectivity · Outside Plant · DC Power · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson Surge Protector (AC4)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson Surge Protector (AC4)

Be the first to ask — other owners or our team will answer.

Original document

Emerson Surge Protector (AC4) manual PDF

89 pages·2.9 MB·Surge Protector·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…