EN
Emerson logo
Official user manual

Emerson 381333234 E

18 pages·471 KB·Surge Protector·PDF·ENDEFRITNLJA
Emerson 381333234 E
Table of Contents 8 sections 333234e0 · 333234ca · 333234e1 · 333234c2 · … ShowHide
Page 1 of the Emerson 381333234 E user manual — TABLE OF CONTENTS
Page 1 · click to enlarge
Page 1

Operator’s

Series 200 Automatic Transfer Switching Equipment

Manual

D–design 30 through 230 amperes

Nameplate / rating Label

The Series 200 Automatic Transfer Switching Equipment (ATSE) contains a nameplate / rating label which includes data for that specific ATSE. It defines the loads and fault circuit withstand/closing ratings. Refer to the labels on the Transfer Switching device for specific values and use the ATSE only within their limits.

An experienced licensed electrician should install the ATSE.

Do not exceed the values on the rating label. Exceeding the rating can cause person injury or serious equipment damage.

TABLE OF CONTENTS

INSTALLATION 1

SEQUENCE OF OPERATION 2

TESTING & SERVICE 3

ADJUSTMENTS 4

CONTROL FEATURES 5

INDEX back of manual

381333–234 E 50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com

section

Page 2 of the Emerson 381333234 E user manual — N 480 G 277 F 240
Page 2 · click to enlarge
Page 2

A typical Catalog Number is shown below with its elements explained:

Catalog Number Identification Typical D–design Series 200 ATS catalog no. for a solid neutral, 3 pole, 100 amp, 400 V, open type:

D

200 A 3 100 J 5X

5. standard 3 – three Ø 2 – single Ø

D 220 C 208

J 400

B – switching 5X – if

K 415

E 230

150 200 * 230 * * 200 & 230 A are limited to 480 volts

N 480 G 277 F 240

M 460

H 380

Show 8 more labels / short text on this page
design prefix letter · Phase Poles Neutral · Amperes Voltage Controller · A – solid · C – overlapping · accessories · ordered · blank – none
Page 3 of the Emerson 381333234 E user manual — Grounding
Page 3 · click to enlarge
Page 3

SECTION 1 INSTALLATION

The ASCO Series 200 automatic transfer switching equipment (ATSE) consists of a transfer switching device, monitoring and transfer control device (controller), and membrane controls (for door mounting). The ATSE is factory tested. Installation requires mounting the devices into an appropriate size enclosure and connection of power conductors, engine start signal wires, and auxiliary circuits.

Emerson 381333234 E — SECTION 1 INSTALLATION diagram (page 3)
Fig. 1
Emerson 381333234 E — SECTION 1 INSTALLATION diagram (page 3)
Fig. 2
Emerson 381333234 E — SECTION 1 INSTALLATION diagram (page 3)
Fig. 3

Mounting

Emerson 381333234 E — Mounting diagram (page 3)
Fig. 4 · Mounting

The Outline and Mounting Diagram furnished with the ATSE shows all mounting details and instructions.

cut out in enclosure

Protect the automatic transfer switching equipment from construction grit and metal chips to prevent malfunction or shortened life of the transfer switching device.

Mount the transfer switch vertically in the back of the enclosure as shown on the Outline and Mounting Diagram provided. Level all mounting points of the rigid supporting structure by using flat washers behind the holes to avoid forced distortion of the transfer switch.

controller must be within a steel enclosure

Figure 1-1. Membrane controls and controller mount-

ing on inside of enclosure door. Refer to Outline & Mounting Diagram for mounting hardware.

Mount the membrane controls and the controller on the inside of the enclosure door as shown on the Outline and Mounting Diagram provided. The membrane controls must be accessible through a cutout in the door. Connect the membrane controls to the right side of the controller with the ribbon cable provided. Then connect the transfer switching device harness plugs to the left side of the controller. See Figures 1–1 and 1–2.

Emerson 381333234 E — Mounting diagram (page 3)
Fig. 5 · Mounting

An add-on rail is provided for some optional accesso- ries. If provided, mounted it below the controller. Then make the connections shown on the Wiring Diagram.

Grounding

Figure 1-2. Membrane controls with gasket

Grounding (earthing) is accomplished by mounting the automatic transfer switching equipment in a metal enclosure. Connect the control panel grounding wire (lower left side) to equipment (enclosure or clean earth) ground. This wire can be connected to the controller’s lower left mounting stud. Because the controller is mounted on a door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges. See Figure 1–3.

suitable for IP65 enclosure.

Emerson 381333234 E — Grounding diagram (page 3)
Fig. 6 · Grounding

2 plugs for transfer switching device harness

ribbon cable to membrane controls

connections for control features &

Figure 1-3. Controller grounding (clean earth)

wire and other connections.

The controller must be grounded for proper operation.

Show 10 more labels / short text on this page
membrane controls · gasket · ribbon cable · controller · door · enclosure · door · ground wire · mounting stud · options
Page 4 of the Emerson 381333234 E user manual — Auxiliary Circuits
Page 4 · click to enlarge
Page 4

INSTALLATION (continued)

De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.

Three conductor spacers must be located as shown for 150, 200, and 230 ampere transfer switching devices.

Emerson 381333234 E — INSTALLATION (continued) diagram (page 4)
Fig. 7 · INSTALLATION (continued)

Power connections

A Wiring Diagram is furnished with the Series 200 ATSE. All wiring must be made in accordance with the local codes.

Do not run cables in front of the transfer switching device. Conductors can be bundled on the right side of the transfer switching device. Maintain proper electrical clearance between the live metal parts and grounded metal: 13 mm minimum.

Figure 1-4. Required conductor spacers for 150, 200, & 230 amp transfer switching devices.

It is not necessary to remove the barriers from the transfer switching device to install the conductors. If you do remove them, however, be sure to reinstall the barriers carefully.

Engine Starting Contacts

The engine control contact connections (if used) are located on the transfer switching device. Connect signal wires to appropriate terminals as specified in Table A and shown in Figure 1–5.

Connect main source and load conductors to clearly marked power terminals on the transfer switching device. Be careful when stripping insulation from the conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer’s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the terminals to the torque specified on the label on the transfer switching device.

Table A. Engine start connections

When normal source failsTerminals on transfer switching device contact closesTB1 and TB2 contact opensTB1 and TB3
Emerson 381333234 E — Engine Starting Contacts diagram (page 4)
Fig. 8 · Engine Starting Contacts
Emerson 381333234 E — Engine Starting Contacts diagram (page 4)
Fig. 9 · Engine Starting Contacts

Three conductor spacers are included with 150, 200, and 230 ampere transfer switching devices. When installing power conductors, run them through the conductor spacers as shown in Figure 1–4. Position the spacers within 38 mm of the power terminals.

ENGINE STARTING CONTACTS

( SHOWN DE–ENERGIZED )

TOP STUD

TS

MIDDLE

STUD

TB 1

NR

BOTTOM

STUD

TB 2 TB 3

NR

Figure 1-5. Engine starting contact label and location on left side of transfer switching device.

Interconnecting harness

Connect the plug–in harness (two plugs) from the transfer switching device to left side of the controller, if not already connected.

Auxiliary Circuits

Connect auxiliary circuit wires (if necessary) to appropriate terminals by referring to the Wiring Diagram.

conductor spacers · 38 mm approximate · conductor spacer

Page 5 of the Emerson 381333234 E user manual — 1 – Manual Operation
Page 5 · click to enlarge
Page 5

INSTALLATION (continued)

Functional Test

The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.

Position of the transfer switch is indicated here

weight marked N (normal) and E (emergency)

Emerson 381333234 E — INSTALLATION (continued) diagram (page 5)
Fig. 10 · INSTALLATION (continued)

Do these checks in the order presented to avoid damaging the automatic transfer switching equipment.

Read all instructions on the Wiring Diagrams and labels affixed to the ATS. Note the control features that are provided and review their operation before proceeding.

1 – Manual Operation

A detachable manual operator handle is provided on the Transfer Switching device for maintenance purposes only. Manual operation of the transfer switching device must be checked before it is operated electrically.

Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers.

With ALL POWER OFF grasp maintenance handle and turn it quickly with your thumb and fingers.

1. After deenergizing both power sources, open the enclosure door. Locate and the maintenance handle on the left side of the transfer switching device. See Figure 1–6.

Figure 1-6. Maintenance handle and positions.

2. Grasp the attached maintenance handle and turn it with thumb and fingers as shown to manually operate it. The maintenance handle turns the opposite direction of the weight. Turn it up or down as shown to manually operate the transfer switching device. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
3. Return the transfer switching device to the N (normal) position.

Now continue to 2 – Voltage Checks on next page.

maintenance handle · weight · floating weight

Page 6 of the Emerson 381333234 E user manual — 2 – Voltage Checks
Page 6 · click to enlarge
Page 6

INSTALLATION (continued)

Emerson 381333234 E — INSTALLATION (continued) diagram (page 6)
Fig. 11 · INSTALLATION (continued)

Figure 1–7. Standard controls and indicators.

2 – Voltage Checks

1Close the normal source circuit breaker. The Normal Transfer Switch Position and the Normal Source Accepted lights should come on.Source Accepted Normal Emergency 2Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switching device normal source terminals. 3Close the emergency source circuit breaker. (Start generator, if necessary.) The Emergency Source Accepted light should come on.Source Accepted Normal Emergency 4Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switching device emergency source terminals.* 5Use a phase rotation meter to check phase rotation of emergency source; it must be the same as the normal source.U V W 6Shut down the engine–generator, if applicable. The Emergency Source Accepted light should go off. Then put the starting control selector switch (on the generator set) in the automatic position. Close enclosure door.Source Accepted Normal Emergency

First check nameplate on transfer switching device; rated voltage must be the same as normal and emergency line voltages.

Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !

Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–7.

O Black circle means light is on.

P White circle means light is off.

* If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer Switching Equipment will respond only to the rated voltage specified on the Transfer Switching device nameplate.

Also see page 4–1 for the HI–LOW voltage adjust setting in the controller. The LOW setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V.

Now continue to 3 – Electrical Operation on next page.

observe these lights

Page 7 of the Emerson 381333234 E user manual — Transfer Test
Page 7 · click to enlarge
Page 7

INSTALLATION (continued)

Figure 1–8. Standard controls and indicators.

3 – Electrical Operation

1The normal source must be available and the generator must be ready to start. Check that the Normal Source Accepted light is on.Source Accepted Normal Emergency 2Press and hold the Transfer Test button until the engine starts and runs. This should happen within 15 sec.Transfer Test 3The Emergency Source Accepted light should come on.Source Accepted Normal Emergency 4The transfer switching device should transfer to the Emergency position. The Emergency Transfer Switch Position light should come on and the Normal light should go off.Transfer Switch Position Normal Emergency 5If the transfer to emergency delay is used the transfer should occurs after a time delay (up to 5 minutes). For immediate transfer press the Bypass Time Delay button.Bypass Time Delay 6The transfer switching device should transfer back to the Normal position. The Normal Transfer Switch Position light should come on and the Emergency light should go off.Transfer Switch Position Normal Emergency 7If the retransfer to normal delay is used the retransfer should occur after a time delay (up to 30 minutes). For immediate retransfer press the Bypass Time Delay button.Bypass Time Delay 8The unloaded running delay keeps the generator running for 5 minutes (cool–down period). Then the generator should stop and the Emergency Source Accepted light should go off.Source Accepted Normal Emergency

This procedure will check the electrical operation of the Automatic Transfer Switching Equipment.

Close the automatic transfer switching equipment enclosure door and tighten the screws before you test electrical operation.

Transfer Test

Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started in this procedure.

Perform steps 1 through 8 at the right. Observe the status lights. See Figure 1–8.

O Black circle means light is on.

P White circle means light is off.

This completes the Functional Test of the ASCO Series 200 Automatic Transfer Switching Equipment. Leave the engine–generator starting control in the automatic position.

observe these lights · press this button

Page 8 of the Emerson 381333234 E user manual — Retransfer to Normal
Page 8 · click to enlarge
Page 8

SECTION 2 SEQUENCE OF OPERATION

Lights show position of transfer switching device. Lights show the sources accepted.

Transfer To Emergency

Light for built–in engine exercise timer:

The sequence for load transfer to emergency source begins automatically when normal source voltage falls below the preset dropout point or when Transfer Test button is pressed. An under voltage condition on any phase of the normal source is detected by the sensor.

³ blinks rapidly when

button is held 5 sec. while being set

³ blinks slowly when

button is released (set) and during 20 min. exercise period.

³ stays on after engine

When the normal source voltage fails or the Transfer Test button is pressed, the SE relay de-ener- gizes and relay NR begins its timing cycle (1 or 3 seconds, momentary normal source outage delay). The NR relay is provided with atime delay on dropout to override momentary outages and prevent nuisance starting of the engine-driven generator. If the normal source voltage returns above the sensor dropout setting before the time delay expires, the NR relay timing cycle is reset to zero and relay SE energizes.

Hold 15 sec. to start the engine generator and to transfer the load to emergency.

Press to cancel the active exercise period (stops engine now or after cooldown) See page 5–1.

Hold 5 sec. to set 20 min. engine exercise period immediately (engine starts) and weekly thereafter.

Figure 2–1. Membrane controls and indicator lights.

Retransfer to Normal

The sequence for load retransfer to the normal source automatically begins when the voltage sensor detects restoration of the normal source. The voltage level must rise above the preset pickup point on all phases before the sensor will accept the normal source.

When the normal source is accepted by the sensor, relay SE begins its timing cycle (adjustable 1 sec. to 30 min., retransfer to normal delay). For immediate retransfer press Bypass Time Delay button. SE relay is provided with a time delay on pickup to prevent immediate load retransfer to the normal source. The delay insures that the normal source has stabilized before reconnection of vital loads. If the normal source voltagefallsbelow thepresent dropoutpoint beforethe time delay expires, the timing cycle is reset to zero. If the emergency source fails for more than 4 seconds duringthetiming cycle, ER relaydrops outand theload is immediately retransferred to the normal source, if that source is acceptable.

If the normal source voltage does not return above the sensor dropout setting before the time delay expires, the NR relay de-energizes and signals the engine-driven generator to start. At the same time, a voltage and frequency sensor begins monitoring the emergency source. The sensor will accept the emergency source only when both voltage and frequency reach preset pickup points. Usually about ten seconds elapse from dropout of the NR relay to acceptance by the sensor. This time span occurs because the engine-driven generator must crank, start, and run up to nominal pickup points. For this reason, if the Transfer Test button is pressed it must be held for 15 seconds. If the emergency source is available immediately, the sensor may accept it as soon as NRrelay drops out.

SE relay energizes and ER relayis droppedout. TheTS coil is energized, the transfer switching device oper- ates, and all switch contacts (mains, controls, auxilia- ries) reverse position. The transfer switching device is now supplying the load from the normal source again.

When the emergency source is accepted by the sensor, relay ER begins its timing cycle (transfer to emergency delay). ER relay is provided with an adjustable (0 to 5 minutes) time delay on pickup to delay transfer of the load to the emergency source. For immediate transfer press Bypass Time Delay button.

Upon retransfer to the normal source, NR relay begins its timing cycle (unloaded running delay [engine cool- down] ). NR relay is provided with a 5 minute time delay on pickup to keep the engine running for a cool-down period.

ER relay energizes, the TS coil is energized, the transfer switching device operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switch is now supplying the load from the emergency source.

NR relay energizes after the time delay and signals the engine-driven generator to shut down. All circuits are reset for any future normal source failure.

The transfer switching device will remain in the Emergencypositionuntilthenormalsource isrestored. If the Transfer Test button is used, the transfer switching device will remain on emergency until the retransfer to normal delay times out.

Activation of standard control features shown in Section 5 will alter the sequence of operation and introduce additional time delays during transfer operations.

Show 6 more labels / short text on this page
stops (exerciser is · enabled for weekly · operation) · See page 5–1 · for complete · instructions
Page 9 of the Emerson 381333234 E user manual — Transfer Switch Test
Page 9 · click to enlarge
Page 9

SECTION 3 TESTING & SERVICE

PREVENTIVE MAINTENANCE

DISCONNECTING THE CONTROLLER

Reasonable care in preventive maintenance will insure high reliability and long life for the automatic transfer switch.

The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps carefully.

Operate the switch at least once a month. Perform this four step Electrical Operation Test. This is a test with load transfer.

Disconnecting the Plugs

1. Observe the position of the transfer switching device. a. If the transfer switching device is in the Normal

position, place standby engine starting control in the off position. Then open the emergency source circuit breaker. b. If the transfer switching device is in the Emergency

position, open the normal source circuit breaker. Place the engine starting control in the test or run position.

2. Separate the quick disconnect plugs by squeezing the latches. Do not pull on the harness wires.
3. Label, remove, and tape the signal wires connected to the engine start terminals on the transfer switching device: TB1 and TB3, or TB1 and TB2.

Transfer Switch Test

Reconnecting the Plugs

1.Press and hold the door-mounted TRANSFER SWITCH TEST button until the engine starts and runs. This should happen within 15 seconds. 2.The transfer switching device will operate to the Emergency position. If the Transfer To Emergency Delay is used, the transfer will occurafter a time delay (up to 5 minutes). For immediate transfer press BYPASS TIME DELAY button. 3.The transfer switching device will operate back to Normal position after the Retransfer To Normal Delay (up to 30 minutes). For immediate retransfer press BYPASS TIME DELAY button. 4.Unloaded Running (Engine Cooldown) Delay allows engine to run unloaded for 5 minutes.
1. Observe the position of the transfer switching device. a. If the transfer switch is in the Normal position, be

sure that the standby engine starting control is still in the off position. The emergency source circuit breaker still should be open. b. If the transfer switch is in the Emergency position,

normal source circuit breaker still should be open. 2. Reconnect the signal wires connected to the appropriate engine start terminals on the transfer switch. See Section 1, Engine Starting Contacts.

3. The harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until both latches click.

Clean and inspect the switch once a year. De-energize all sources, then brush and vacuum away any excessive dust accumulation. Remove the transfer switch barriers and check contact condition. The non–replaceable main contacts are designed to last the life of the transfer switch. Reinstall the barriers carefully.

4. Restore the opposite source as follows: a. If the transfer switch is in the Normal position,

place the standby engine starting control in the automatic position. Then close the emergency source circuit breaker.

b. If the transfer switch is in the Emergency position,

Maintain transfer switch lubrication. The transfer switch has been properly lubricated, and under normal operating conditions no further lubricating is required. Renew factory lubrication if the switch is subjected to severe dust or abnormal operating conditions. Relubricate the solenoid operator if a coil is replaced. Do not use oil. Order lubrication 625550–001 (Castrol EndurexR 4000 lubricant).

close the normal source circuit breaker. The load will be automatically retransferred to the normal source after the Retransfer to Normal Delay. For immediate retransfer, press BYPASS TIME DELAY button. Place the engine starting control in the automatic position.

Replacement parts. Replacement parts are available in kit form. Whenordering partsprovide theSerial No. and Catalog No. from the transfer switch nameplate. Contact your local ASCO Power Technologies sales office.

Page 10 of the Emerson 381333234 E user manual — TESTING & SERVICE (continued)
Page 10 · click to enlarge
Page 10

TESTING & SERVICE (continued)

MANUAL LOAD TRANSFER This procedure will manually transfer the load if the controller is disconnected.

1. Open normal and emergency source circuit breakers.
2. Use the maintenance handle to manually operate transfer switching device to the opposite source. See page 1–4, Manual Operation Test .
3. If the transfer switching device is in the Emergency position manually start the engine generator and then close the emergency source circuit breaker.

Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers.

TROUBLE-SHOOTING Note the control features that are activated or furnished on the switch and review their operation. Refer to Section 5, Control Features. Proceed with care! The automatic transfer switching equipment is energized. Table 3-1. Trouble-Shooting Checks.

CHECK IN NUMERICAL SEQUENCE PROBLEM1 OPERATION2 GEN-SET3 VOLTAGE Gen-Set does not start when the TRANSFER SWITCH TEST button is pressed and held for 15 seconds or when the normal source fails.Hold the TRANSFER SWITCH TEST button 15 sec. or the outage must be long enough to allow for the 1 or 3 sec. Momentary Normal Source Outage Delay plus engine cranking and starting time.Starting control must be in automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.— Transfer switching device does not transfer the load to emergency source after the gen-set starts.Wait for Transfer to Emergency Delay (0 to 5 min.) to time out. For immediate transfer, press the BYPASS TIME DELAY button. If Motor Load Transfer is active, wait for inphase condition (see below).Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (48 Hz for a 50 Hz system).Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals U2 and W2 (or L1 and L5 for 2 pole switches). * * These are factory settings. Transfer switching device does not transfer the load to normal source when normal returns or when TRANSFER SWITCH TEST button is released.Wait for Retransfer to Normal Delay (1 sec. to 30 min.) to time out. For immediate re– transfer, press BYPASS TIME DELAY button. If Motor Load Transfer is active, wait for inphase condition (see below).—Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switching device terminals V1 and W1, W1 and U1, and U1 and V1 (or L2 and L6 for 2 pole switches). Gen-Set does not stop after load retransfer to the normal source.Wait for the 5 minute Unloaded Running Delay to time out.Starting control must be in automatic position.—

Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–3)

3. Press and hold the Transfer Test button. The load should transfer to emergency source when meter needle is near 0 volts. If transfer does not occur, Motor Load Transfer feature is not operating.

Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !

4. Release the Transfer Test button. The load should retransfer back to the normal source after the Retransfer to Normal Delay , if used. The retransfer should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor Load Transfer feature is not operating.
1. Connect a voltmeter (set for twice system phase–to–phase voltage) between transfer switching device terminals U1 and U2 (for 3 pole) or L1 and L2 (for 2 pole).
2. Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.
5. For immediate retransfer, press the Bypass Time Delay button. Then disconnect the voltmeter.

If the problem is isolated to circuits on the controller or the transfer switching device, call your local ASCO Power Technologies sales office. Furnish Serial No., Bill of Material (BOM) No., & Catalog No. from the transfer switching device nameplate.

Page 11 of the Emerson 381333234 E user manual — Sensor Adjustments
Page 11 · click to enlarge
Page 11

SECTION 4 ADJUSTMENTS

Time Delay Adjustment

To change a setting, follow procedure on page 4-2. Use Table 4-1 as a guide to time delay values and their corre- sponding adjustment DIP switch or potentiometer.

Standard time delays are set to customer specifications (if none specified, standard factory settings are used).

Table 4-1. Time Delay Settings

DESCRIPTIONLABELSFACTORY SETTINGADJUSTMENT RANGES3 DIP SWITCHADJUSTMENT POTENTIOMETER Override Momentary Normal Source OutagesTD ES3 seconds1 secondActuator 1 on1— 3 secondsActuator 1 off1 Transfer to EmergencyTIMER N/E0 minutes (full ccw)0 to 5 minutes——P2 Override Momentary Emergency S. Outages—4 secondsnon-adjustable——— Retransfer to NormalTIMER E/N30 minutes (full cw)1 second to 30 minutes——P1 Unloaded Running (Engine Cooldown)—5 minutesnon-adjustable———
Emerson 381333234 E — Time Delay Adjustment diagram (page 11)
Fig. 12 · Time Delay Adjustment

Sensor Adjustments

Voltage and frequency sensor pickup and dropout points are set to customer specifications (if none specified, standardfactory settingsare used). Tochange a setting, follow procedure on page 4–2. Use Tables 4-2 and 4–3 for settings and corresponding DIP switch actuators.

Any change in these settings may affect the normal operation of the automatic transfer switching equipment. This change could allow the load circuits to remain connected to a low voltage source.

Table 4-2. Voltage and Frequency Settings. ( Shaded DIP switches are standard factory settings).

% of nominalS1 DIP DESCRIPTIONLABELSSETTINGFACT. SETADJ RANGESWITCH Normal Source VoltagePU / NPickup90 %95 % *Actuator 3 off3 90 %Actuator 3 on3 DO / NDropout85 %90 % *Actuator 1 off Actuator 2 off1 2 85 %Actuator 1 on Actuator 2 off1 2 80 %Actuator 1 off Actuator 2 on1 2 70 %Actuator 1 on Actuator 2 on1 2 Emergency Source Voltage– –Pickup90 %non-adjustable– – – –Dropout75 %non-adjustable Emergency Source Frequency– –Pickup95 %non-adjustable– – – –Dropout85 %non-adjustable 60 / 50 Hz60 / 50 Hz60 Hz60 HzActuator 4 off4 50 HzActuator 4 on4 Voltage Phases3 4,1 43 4 / 1 43 43 phaseActuator 6 off6 1 phaseActuator 6 on6

Table 4-3. Transformer Voltage Adjust.

(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)

DESCRIPTIONLABELSFACTORY SETTINGADJUSTMENTS3 DIP SWITCH Voltage Adjust (4. 2%)LOW / HIHILOWActuator 2 off2 HIActuator 2 on2
Page 12 of the Emerson 381333234 E user manual — SW1 SW2 SW3
Page 12 · click to enlarge
Page 12

ADJUSTMENTS (continued)

Emerson 381333234 E — ADJUSTMENTS (continued) diagram (page 12)
Fig. 13 · ADJUSTMENTS (continued)
Emerson 381333234 E — ADJUSTMENTS (continued) diagram (page 12)
Fig. 14 · ADJUSTMENTS (continued)

Do not make any setting changes while the controller is energized.

How to Change a Setting

1. Prevent the transfer switching device from operat- ing by disconnecting one source first, then the other, as follows: a. If the transfer switching device is in the Normal position, open the emergency source circuit breaker. Turn the engine starting control to off. Then open the normal source circuit breaker. b. If the transfer switching device is in the Emergency position, open the normal source circuit breaker. Turn engine starting control to test or run. Then open the emergency source circuit breaker.

hook on left side

Figure 4-1. Controller cover latch.

Emerson 381333234 E — How to Change a Setting diagram (page 12)
Fig. 15 · How to Change a Setting
2. Disconnect both harness plugs from controller by squeezing the latches. Do not pull on the wires.

J5

3. Remove cover from the controller by releasing latch on right side with your thumb. See Figure 4-1.

P1

retransfer to normal time delay

4. Locate the appropriate adjustment potentiometer or DIP switch for the setting that you want to change. Refer to Table 4-1 and Table 4–2 on page 4-1 and Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.

P2

S3 DIP

5. Use a small screwdriver to turn the potentiometer clockwise to increase the time delay or counterclockwise to decrease it. See Figure 4-3.

S1 DIP

S2 DIP

6. Use a ball-point pen (or similar pointed tool) to slide the switch actuators left or right so they match the illustration next tothe setting(left =off, right= on). Recheck the setting. See Figure 4-4.

Figure 4-2. Location of potentiometers, DIP switches, battery, and battery jumper.

Emerson 381333234 E — S1 DIP diagram (page 12)
Fig. 16
7. Install the cover on the controller by hooking it on the left side and latching the right side.

P1 or P2 potentiometer

8. Reconnect both harness plugs to the controller by aligning and pressing straight in until latches click.

Figure 4-3. Changing time delay potentiometers.

Close the automatic transfer switching equipment enclosure door and tighten the screws before restoring power.

Emerson 381333234 E — S1 DIP diagram (page 12)
Fig. 17

SW1 SW2 SW3

9. Closetheenclosuredoor, thenrestore bothsources: a. If the transfer switching device is in the Normal position first close the normal source circuit breaker, then close the emergency source circuit breaker. b. If the transfer switching device is in the Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source. Then close the emergency source circuit breaker.

(8 on each DIP switch)

Figure 4-4. Setting DIP switch actuators.

10. Turn the engine starting control to automatic .
Show 18 more labels / short text on this page
thumb latch cover · 9 volt alkaline · battery · battery on/off jumper · harness · plugs · transfer to emergency · switch · time delay · switch · switch · clockwise to · increase · counterclockwise · to decrease · DIP switches · actuator · on off
Page 13 of the Emerson 381333234 E user manual — TIME DELAY
Page 13 · click to enlarge
Page 13

SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS

These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without load transfer, or they can be completely disabled. The engine-generator should be exercised under load once a week for a minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.

BUILT–IN ENGINE EXERCISER The engine exerciser included in the Series 200 automatic transfer switching device provides a once a week 20–minute exercise period. It occurs immediately when the SET ENGINE EXERCISER push button is pressed (and held for at least 5 seconds), and then at the same time weekly thereafter. A 9 volt alkaline battery (DuracellR MN1604, EverreadyR 522, or PanasonicR 6AM6) is furnished and installed in the controller to maintain the setting. The battery jumper block must be shifted to the ON position. See Figure 4–2 on page 4–2.

DIP Switch Settings

Emerson 381333234 E — DIP Switch Settings diagram (page 13)
Fig. 18 · DIP Switch Settings

Fill in day and time set. Week Day Time

Emerson 381333234 E — DIP Switch Settings diagram (page 13)
Fig. 19 · DIP Switch Settings

Press to cancel an active exercise period (stops generator). Press and hold for 5 sec. or until status light blinks rapidly to set exercise period immediately and every week hereafter (generator starts).

If Exercise with Load is set, retransfers load to Normal, then stops generator after min. cooldown.

If Exerciser with Load is set, transfers load to Emergency.

Figure 5-1. Operator panel pushbuttons and light.

Select below either Exercise without Load or Exercise with Load according to the setting of DIPswitch S1, actuator 8. The load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.

Exercise without Load, DIP Switch S1, Actuator 8 off

How to Set Built–In Timer

Push Button Status Light

1 SET ENGINE

FfFfFf set exercise period Exercise the generator now and every week at this time hereafter.

EXERCISER

hold 5 sec.

2 release blinks slowly

FffFff exercise period now active Generator starts and runs.

TIME DELAY F stays on cancel active exercise period Generator stops.

4 — F stays on generator off Exerciser enabled; repeats every 7 days.

Exercise with Load, DIP Switch S1, Actuator 8 on

How to Set Built–In Timer

Push Button Status Light

1 SET ENGINE

FfFfFf set exercise period Exercise the generator now and every week at this time hereafter.

EXERCISER

hold 5 sec.

2 release blinks slowly

FffFff exercise period now active Generator starts and runs; the load transfers to Emergency.

The load retransfers to Normal; then generator runs for 5 minute cooldown ( light blinks slowly during cooldown ). 4 — F stays on generator off Exerciser enabled; repeats every 7 days.

FffFff cancel active exercise period

TIME DELAY

Show 10 more labels / short text on this page
status light · Step · Function Explanation · blinks rapidly · 3 press BYPASS · Step · Function Explanation · blinks rapidly · 3 press BYPASS · blinks slowly
Page 14 of the Emerson 381333234 E user manual — See next page for instructions on setting the timer.
Page 14 · click to enlarge
Page 14

CONTROL FEATURES (continued)

OPTIONAL PROGRAMMABLE ENGINE EXERCISER (Accessory 11CD)

The optional programmable engine exerciser provides seven days of different exercise periods. The timer is connected and mounted below the controller. A permanent backup battery maintains the setting; when power is lost to timer, output switch deenergizes.

The Accessory 11CD Programmable Engine Exerciser incorporates a 7 day time base, and therefore, each day of the week can be uniquely programmed to test the engine generator set either with or without load. The proper controller settings must be made to determine whether or not the test will be conducted with or without load (refer to page 5–1 for proper selection). For convenience, Block Programming is also provided, whereby up to seven days can be grouped together if the ON and OFF times are the same.

DIP Switch Settings

FUNCTION S1 DIP SWITCH

S2 DIP SWITCH Opt. Timer

Opt. Timer

See next page for instructions on setting the timer.

Shaded DIP switches are standard factory settings.

Show 19 more labels / short text on this page
Actuator · Actuator · Enabled · 7 off · 5 off · Actuator · Actuator · Disabled · 7 off · 5 on · Exercise · Actuator · without · 8 off · Load · Exercise · Actuator · with Load · 8 on
Page 15 of the Emerson 381333234 E user manual — Daylight Savings / Standard Time Change
Page 15 · click to enlarge
Page 15

CONTROL FEATURES (continued)

How to Set Optional Programmable Engine Exerciser (Accessory 11CD)

Emerson 381333234 E — CONTROL FEATURES (continued) diagram (page 15)
Fig. 20 · CONTROL FEATURES (continued)

Proceed with care! The automatic transfer switching equipment is energized.

Setting the Clock (Time and Day)

Emerson 381333234 E — Setting the Clock (Time and Day) diagram (page 15)
Fig. 21 · Setting the Clock (Time and Day)

1 2 3 4 5 6 7 AM 12 00

Figure 5-2. Exerciser display and push buttons

Changing or Checking Time Programs By operating the Prog. button, the individual commands as programmed can, at any time, be broughtconsecutively into the display for revision or checking. Revisions are accomplished byprogramming overthe existingprograms using the steps at the left.

Canceling Time Programs

After the selecting the desired program, use the h and m buttons to set hours and minutes to zero; the ––:–– will be displayed. This program has been made ineffective and will no longer be carried out. To cancel all programs, press the Res. (reset) button. This clears all memory including the time base and program storage.

8 release ¬blinking time & date set,

Programming Engine On-Off Period(s)

Manual Override

Emerson 381333234 E — Programming Engine On-Off Period(s) diagram (page 15)
Fig. 22 · Programming Engine On-Off Period(s)

1 2 3 4 5 6 7 –– : –– begin

Do not manually override the exerciser unless you are sure that the controller has been set for exercise without load (see page 5–2). Failure to do so could result in possible injury if the transfer switch operates while the enclosure door is open.

Emerson 381333234 E — Programming Engine On-Off Period(s) diagram (page 15)
Fig. 23 · Programming Engine On-Off Period(s)

6 Prog. 1 2 3 4 5 6 7 –– : –– begin

Daylight Savings / Standard Time Change

Tochange toDaylight Savingstime (Summertime), pressthe ¦1h button once. Clock advances by one hour and +1h appears in display. To change to Standard Time (Greenwich mean time in UK, Middle European time in Germany), press the ¦1h button again; the clock sets back one hour and +1h disappears.

Show 9 more labels / short text on this page
on/off button · reset button · ±1h button · program button · hour button · display · minute button · clock button · day button
Page 16 of the Emerson 381333234 E user manual — Bypass Transfer Time Delay (CP12–13)
Page 16 · click to enlarge
Page 16

CONTROL FEATURES (continued)

INPHASE MONITOR FOR MOTOR LOAD TRANSFER

LOAD DISCONNECT FEATURE

Connect external circuits to the terminals indicated on the Wiring Diagram provided with the ATSE.

Inphase monitoring logic controls transfer and retransfer of motor loads, so that inrush currents do not exceed normal starting currents. It avoids nuisance tripping of circuit breakers and mechanical damage to motor couplings.

The double throw (Form C) contact is rated for 28 VDC or 120VAC (5amps resistive). Thecontact operatesprior to a selectable 0, 3, 10, or 20 second delay before transfer of the automatic transfer switching device. The contact resets either immediately following transfer or after the same delay as set for pre–signal before transfer.

The Motor Load Transfer feature is built into the controller. DIP switch S1 (actuator 5) activates this feature: right = ON, left = OFF.

Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 (actuators 6, 7, 8) as shown below:

Emerson 381333234 E — INPHASE MONITOR FOR MOTOR LOAD TRANSFER diagram (page 16)
Fig. 24

Delay Before Transfer

Emerson 381333234 E — Delay Before Transfer diagram (page 16)
Fig. 25 · Delay Before Transfer
Emerson 381333234 E — Delay Before Transfer diagram (page 16)
Fig. 26 · Delay Before Transfer

If the Motor Load Transfer feature is enabled, it will be activated following the Load Disconnect Feature Delay Before Transfer delay.

Delay After Transfer*

LD TDAT S2 DIP SWITCH

enable Actuator 6 on

disable Actuator 6 off

*Enabling the Delay After Transfer will cause the control signal to reset after the same delay as set for the Delay Before Transfer.

REMOTE CONTROL FEATURES

These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.

Remote Test (terminals CP6–7)

Remote Transfer to Emergency (CP8–9)

RTSW S2 DIP SWITCH

RT /E S2 DIP SWITCH

disable Actuator 3 on

disable Actuator 2 on

enable Actuator 3 off

enable Actuator 2 off

Bypass Transfer Time Delay (CP12–13)

Inhibit Transfer to Emergency (CP10–11)

TD E/N BYP. S2 DIP SWITCH

N/E INHIB. S2 DIP SWITCH

disable Actuator 1 on

disable Actuator 4 on

enable Actuator 1 off

enable Actuator 4 off

Page 17 of the Emerson 381333234 E user manual — 333234e5
Page 17 · click to enlarge
Page 17
Page 17 of the Emerson 381333234 E user manual — 333234e5
Page 18 of the Emerson 381333234 E user manual — O
Page 18 · click to enlarge
Page 18

INDEX

A

F

P

accessories, 5–2, 5–3, 5–4

features, see control features

frequency, pickup and dropout

B

R

functional test, 1–3, 1–4, 1–5

H

remote control features, 5–4

bypass transfer time delay, 5–4 inhibit transfer to emergency,

5–4 remote test, 5–4 remote transfer to emergency,

HELP

bypass time delay, 1–5, 2–1, 3–1

800–800–2726 (ASCO) customercare@asco.com

S

catalog number, inside cover

800–800–2726 (ASCO) customercare@asco.com

set engine exerciser, 5–1

preparation, 1–2 terminals, 1–2

changing, 4–1 factory, 4–1 frequency, 4–1 phase, 4–1 time delay, 4–1 voltage, 4–1

engine control contact, 1–2 power, 1–2

load disconnect feature, 5–4

load disconnect, 5–4 motor load transfer, 5–4 plant exerciser, 5–1

T

M

test, functional, 1–3, 1–4, 1–5

controller (control panel), 4–1, 4–2

codes, cover cover removal, 4–2 disconnecting, 3–1 time delay potentiometers, 4–2

manual load transfer, 3–2

adjustment, 4–1 gen–set cooldown, 4–1 how to change, 4–2 override momentary outages, 4–1 settings, 4–1 transfer to emergency, 4–1 transfer to normal, 4–1

illustration of, 1–3 warning, 1–3

motor load transfer feature, 5–3

D

N

timer (plant exerciser), how to set,

DIP Switches, 4–1, 4–2, 5–1, 5–2,

transfer switch test, 1–5, 3–1

O

E

electrical, 1–5 manual, 1–3

illustration of, 1–3 warning, 1–3 sequence of, 2–1

engine exerciser, 5–1, 5–2, 5–3

voltage, pickup and dropout set-

engine starting contacts, 1–2

Printed in U.S.A. E 2011 ASCO Power Technologies, L.P.

Show 38 more labels / short text on this page
failure · parts, 3–1 · see trouble-shooting, 3–2 · problem, 3–2 · auxiliary circuits, 1–3 · programmable engine exerciser, · 5–2, 5–3 · settings, 4–1 · barriers, 1–2 · battery, 4–2, 5–1 · harness, 1–1 · disconnect plugs, 3–1 · buttons, push, 3–1 · replacement parts, 3–1 · service · inphase monitor, 5–4 · inspection, 3–1 · cleaning, 3–1 · installation, 1–1 · conductors · settings · labels, · connections · rating, cover · lights, 1–5, 5–1 · control features, 5–1 · lubrication, 3–1 · terminal block, 1–3 · maintenance, preventive, 3–1 · time delay · manual operation, 1–3 · nameplate, cover · trouble–shooting, 3–2 · inphase monitor, 5–4 · operation · electrical operation, 1–5 · voltage, phase, 4–1 · tings, 4–1
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson 381333234 E

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson 381333234 E

Be the first to ask — other owners or our team will answer.

Original document

Emerson 381333234 E manual PDF

18 pages·471 KB·Surge Protector·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…