an add-on device for integration with
panelboards at the jobsite for
enhanced surge suppression.
Liebert PanelGuard Extension minimizes data corruption, errors, system re-boots and component failure. Sine wave tracking circuitry filters high frequency electrical line noise. Patented component level monitoring, including neutral to ground, allows status detection in real time.
Flexible mounting (top or bottom) to virtually any panelboard.
Universal panelboard application — can be used with most major manufacturers.
Surge current capacity levels from 130kA per phase to 200kA per phase.
Standard features include all modes of protection, unit status indicators and isolated form C dry contacts.
Options include: audible alarm, transient counter.


1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX

Minimum Tested Single Pulse Surge Current Capacity Protection Mode Impulses Per Mode Model 100 Model 80 Model 65
Line-to-Neutral > 3,500 > 100,000 A > 80,000 A > 65,000 A
Line-to-Ground > 3,500 > 100,000 A > 80,000 A > 65,000 A
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX
Neutral-to-Ground > 3,500 > 100,000 A > 80,000 A > 65,000 A
Line-to-Line > 3,500 > 100,000 A > 80,000 A > 65,000 A
Per Phase > 7,000 > 200,000 A > 160,000 A > 130,000 A
Duty life cycle tested to survive 20kV, 10kA, IEEE C62.41 Category C3 surge current with less than 5% degradation of clamping voltage.
Emerson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 Gloucester Rd, Wanchai Hong Kong 852 25722201 Phone 852 28029250 FAX

All systems EMI-RFI noise or attenuation rejection values are in compliance with test and evaluation procedures outlined in NEMA LS 1-1992, paragraphs 2.2.11 and 3.11.
Technical Support 800 288 6169 Toll-Free 607 724 2484 Phone 607 722 8713 Fax UL 1449 RATINGS
800 288 6169 Toll-Free 607 721 8865 Phone 607 722 8713 Fax
Line to Line to Line Neutral System Voltage Neutral Ground to Line to Ground
While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
120/208 or 120/240 400 V 400 V 800 V 400 V
© 2008 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
208, 240, 277 or 277/480 800 V 800 V 1500 V 800 V
All names referred to are trademarks or registered trademarks of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
NEMA 1 rated. Surface mount dimensions are 12” x 20” x 6”. Flush mount unit is 12” x 21.5” x 6”. Weight is 15 lbs.
SL-22065 (R06/08) Printed in USA
Emerson Network Power. The global leader in enabling Business-Critical Continuity™.
Phase configuration Code 1 Ph, 3W+G. 120/240 VAC 120S 3 Ph, 4W+G. 120/208 VAC 120Y 3 Ph, 4W+G. 277/480 VAC 277Y
Monitoring options Code Standard Status LEDs only -00 LEDs, Audible Alarm, Counter -01 LEDs, Audible Alarm -02 LEDs, Counter -03
DC Power
Embedded Computing Embedded Power
Other phase configurations available. Please consult factory.
kA per mode/per phase Code 65 kA per mode, 130 kA per phase 65 80 kA per mode, 160 kA per phase 80 100 kA per mode, 200 kA per phase 100
How to construct a Liebert PanelGuard Extension (LPGE) model # Code 1. Liebert PanelGuard Extension LPGE 2. Phase configuration 120S 3. kA per mode/per phase 65 4. Trim type: surface mount S 5. Monitoring options -01
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Trim type Code Surface mount trim S Flush mount trim F
Emerson Network Power.com
Business-Critical Continuity™, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2008 Emerson Electric Co.
Owners and our team usually reply within a day — and your question helps the next person too.