MODELS
FH085D36E FH110D48E FH110D60E FLF085D36E FLF110D48E FLF110D60E FLR085D36E FLR110D48E FLR110D60E FLR140D60E FC085D36E
WARNING
READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION.
THIS INSTALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND THE REQUIREMENTS OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION.
IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS.
FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE, BODILY INJURY OR DEATH.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
THIS FURNACE IS NOT INTENDED FOR USE AS A CONSTRUCTION HEATER. USE OF THIS FURNACE DURING CONSTRUCTION AND FINISHING PHASES OF A STRUCTURE IS CONSIDERED AS "OPERATION IN A CORROSIVE ATMOSPHERE" AND "UNUSUAL, NEGLIGENT OR IMPROPER USE" AND AS SUCH ARE CONSIDERED EXCLUSIONS BY THE BARD MANUFACTURING COMPANY LIMITED WARRANTY.

Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Copyright 2003



These publications can help you install the furnace. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
National Fuel Gas Code ANSI Z223.1/NFPA54
National Electrical Code ANSI/NFPA 70
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
Standard for the Installation ANSI/NFPA 90A of Air Conditioning and Ventilating Systems
Standard for Warm Air ANSI/NFPA 90B Heating and Air Conditioning Systems
ASHRAE American Society of Heating Refrigerating, and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
Standard for Chimneys, Fireplaces, Vents ... NFPA 211 and Solid Fuel Burning Appliances
Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection

LOCATING THE FURNACE
An accurate heating load calculation must be conducted using American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) or Air Conditioning Contractors of America (ACCA) manuals. Do not add a large safety factor above the calculated value. If the calculated heating load requirement exceeds the heating capacity rating of a given model, use only the next larger size available. Never increase by any more than absolutely necessary based upon available equipment heating capacities. Always select based upon heat capacity (output), never use input capacities.
When installing the furnace be sure to provide adequate space for easy service and maintenance. Locate the furnace as close to the chimney as practical, giving consideration to the accessibility of the oil burner, controls, and blower for service. Allow a minimum of 24 inches at front of furnace for servicing oil burner. Allow adequate room for filter and blower maintenance. Clearance from combustible material as stated on the furnace and repeated in Table 1 must be maintained. For damp basement installations, a raised concrete pad is recommended. This will help keep the bottom of the furnace dry and reduce the risk of rusting.
An oil burner must have a generous supply of combustion air to operate properly. The flow of combustion and ventilating air must not be obstructed from reaching the furnace. See “Combustion Air Requirements” section.
obligation of the purchaser to contract a qualified installer to assure that installation is adequate and is in conformance with governing codes and ordinances.
The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.
This unit is not designed for mobile home or trailer installations. Always install furnace in a level position.
For the first three (3) feet from plenum. After three (3) feet, no clearance required. C Combustible flooring NC Noncombustible floor * Maintained on one side or the other to achieve filter access and/or blower service. ** Floor must be noncombustible. For furnace only installation can be installed on combustible flooring only when installed on special base part no. CFB7 available from factory. When air conditioning coil cabinet DCB23-22 is used then use special base part no. CFB23.

. a i D H J e zi S . o N
d e s U
s g n i n e p O n o it c e n o C e u l F s r e tli F ri A 1
r a e R 6 6 5 2 6 . 1 3 5 2 6 . 1 3 5 2 1 . 5 5 2 1 . 5 1 x 0 2 x 6 1 1 x 0 2 x 6 1 1 1
1
E 0 6 D 0 4 1 R L F 6 2 0 5 2 . 0 5 5 2 6 . 7 4 0 2 x 5 2 6 1 x 5 2 r a e R 6 5 2 1 . 2 4 - - - 1 x 5 2 x 0 2 1
1 x 0 2 x 0 2 1 x 0 2 x 0 2 1 x 0 2 x 0 2 1 x 0 2 x 0 2

5 2 1 . 5 5 2 1 . 5 5 2 1 . 5 5 2 1 . 5
5 2 6 . 5 3 5 2 6 . 5 3 5 2 6 . 5 3 5 2 6 . 5 3
n r u t e R n o it a c o L G
6
E 6 3 D 5 8 0 R L F 3 2 3 2 5 2 1 . 8 4 5 2 1 . 8 4 5 2 6 . 6 3 5 2 6 . 6 3 0 2 x 2 2 0 2 x 2 2 4 1 x 2 2 4 1 x 2 2 tn o r F
tn o r F
tn o r F
r a e R
r a e R
Washable type filter 1” nom. thickness
y l p p u S F x D
4 1 x 2 2 4 1 x 2 2 4 1 x 2 2 4 1 x 2 2
t e n i b a C m u n e l P
t h g i e H E x D
0 2 x 2 2 0 2 x 2 2 0 2 x 2 2 0 2 x 2 2
5 2 6 . 0 4 5 2 6 . 0 4 5 2 6 . 0 4 5 2 6 . 0 4
h t p e D C

5 2 1 . 8 4 5 2 1 . 8 4 5 2 1 . 8 4 5 2 1 . 8 4
h t d i W B
A
3 2 3 2 3 2 3 2
E 6 3 D 5 8 0 F L F
E 8 4 D 0 1 1 F L F
E 0 6 D 0 1 1 F L F
E 8 4 D 0 1 1 R L F
E 0 6 D 0 1 1 R L F
r e b m u N
l e d o M
KNOCKOUT
FLF/FLR 085, 110 AND 140
J
SPECIFICATION SHEET
DUCT SUPPLY
DUCT
HIGH VOLTAGE
KNOCKOUT REAR FLUE
LOW VOLTAGE
E F
"FLF" FLUE
OPTIONAL
ENTRANCE
OPTIONAL
ENTRANCE
ENTRANCE
OPTIONAL
ENTRANCE
FRESH AIR
KNOCKOUT
TOP VIEW
OIL
OIL
ON "FLR" MODELS
FILTER
DOOR
G
RETURN
D
H

SPECIFICATION SHEET

LOW VOLTAGE
KNOCKOUT
ENTRANCE
ENTRANCE
ENTRANCE
VOLTAGE
OPTIONAL
FLUE
DOOR
HIGH
OIL
SUPPLY
FH MODELS DIMENSIONS

FRONT VIEW
TOP VIEW
KNOCKOUT
HIGH VOLTAGE
LOW VOLTAGE
KNOCKOUT
OPTIONAL
ENTRANCE
OPTIONAL
ENTRANCE
OPTIONAL
ENTRANCE
ENTRANCE
FRESH AIR
KNOCKOUT
VESTIBULE
FLUE
DOOR
FLUE
OIL
OIL

OPENING
(CUT OUT)
19 1/4" · 16"


FC085 SPECIFICATION
SHEET
TOP VIEW



BOTTOM VIEW

DUCT WORK
The air distribution system should be designed and installed in conformance with manuals published by Air Conditioning Contractors of America (ACCA) as set forth in Manual D, or ASHRAE publications.
It is important that a set of instruments capable of the following requirements be used for the setup of this furnace to ensure proper and safe operation:
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace This is to prevent drawing possible hazardous combustion products into the circulated air.
When the furnace is used in connection with a cooling unit*, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit, unless the damper is in the full heat or cool position.
A typical installation is shown in Figures 4 and 5. All parts of the furnace installation (furnace, oil tank and piping systems, combustion and ventilation air, venting, etc.) must comply with NFPA31, Installation of Oil Burning Equipment -- latest edition. This drawing shows the typical connecting parts needed to correctly install this furnace. Make sure that all parts of the heating system comply with the local codes.
Check the furnace and your load calculation to verify that the unit is properly sized. (Refer to Equipment Selection” section on Page 2.)
* A cooling unit is an air conditioning coil, heat pump coil or chilled water coil.
The correct size of unit needed may be substantially smaller than the unit being replaced due to home improvements and technology advancements since the initial installation.
When installing a cooling unit above an FH or FL (below on an FC) series furnace, the coil must be spaced far enough from the furnace outlet to assure proper operation of the furnace. Bard supplied coils, when used with Bard supplied coil cabinets, are automatically positioned.
For top discharge FH and FL models, when coils are installed without using Bard coil cabinets or coils of another brand are used, the coil drain pan should be located a minimum of two (2) inches above the top of the furnace cabinet. If a greater clearance is specified by the coil manufacturer then it would apply.
Short cycling because of limit control operation can be created by incorrectly designed or installed supply and/ or return air duct systems.
The duct systems must be designed using ASHRAE or ACCA design manuals and the equipment CFM and external static pressure ratings to insure proper air delivery capabilities.
THAN A STEEL PAN PARTICULAR ATTENTION MUST BE GIVEN TO THE INSTALLATION INSTRUCTIONS FOR THE COIL TO MAKE SURE IT IS ACCEPTABLE FOR USE WITH THESE OIL FURNACES HAVING MAXIMUM OUTLET AIR TEMPERATURE OF 200° F.
On replacement installations, particularly if equipment is oversized, the duct systems can easily be undersized. Modifications may be required to assure that the equipment is operating within the approved temperature rise range when under full rated input conditions, and that no short cycling on limit controls is occurring.
See CFM versus static pressure curves on pages 33-36 for additional information.

FACTORY WIRING
All wiring must conform to the National Electrical Code and all local codes. A separate fuse or breaker should be used for the furnace.
All units are fully factory wired. Multispeed blowers are factory wired on high speed for cooling/manual fan operation. Heating speeds are wired for the largest input and may need lower speed for field installed low input nozzle. If replacement wire is necessary, use 105 degrees C minimum. See electrical data, Table 3.

FLF UNIT SHOWN
WARNING
TYPICAL UNIT
ALL WIRING MUST CONFORM TO THE NATIONAL ELECTRIC CODE AND ALL LOCAL
!
CODES.
Inspection door
Left side low voltage (thermostat) entrance
Right side low voltage (thermostat) entrance
Left side oil line entrance for opt. air boot
To thermostat and optional A/C unit
Left side oil line entrance
To power source
Oil line (see burner pump inst. for hookup info.)
Shut off switch (if not fused, power line must include fuse or circuit breaker)
Control panel (junction box in FH units)
Power Wires: Black (HOT) White (NEUTRAL) Green (GROUND)
Right side high voltage (unit power) entrance
Right side oil line entrance

FRONT FLUE LOWBOY MODEL SHOWN
(REPRESENTS ALL MODELS)
INSTALLER NOTE:
Follow all appropriate standards for installing needed venting system.
Draft Regulator (Be sure to follow installation inst. supplied with regulator).
1/4 inch per 1 foot rise
90° Rotatable Flue Box on front flue models (remove appropriate cabinet knockout). Mounting screws located under flue box cover.
h
i m
n e
y
Clean-out Door (keep closed)
Optional Fresh Air Boot (remove rect. knockout).

BECKETT AFG OIL BURNER
First determine whether the pipe system is to be a single line system or a two line system. All connections must be absolutely air tight or you will have a malfunction of the burner. When installing the piping, a good oil filter should be installed close to the burner. A single line system is recommended for gravity feed.
This furnace is equipped with a high static Beckett AFG oil burner which is designed to produce adequate draft in nearly any vertically vented application. The burner employs the latest time tested controls of the highest quality. The controls consist of a high voltage Beckett solid state igniter, a Beckett “CleanCut” oil pump with an integral solenoid valve, and a Beckett R7184B primary control.
A typical single inside tank installations shown in Figure 6. For installation details for this and other tank configurations, refer to NFPA31 -- latest edition. All tank and pipe setups must comply with NFPA31.
Vent Cap
2" Cap
2" Fill Pipe
1-1/4" Vent Pipe Return Line
Guage
Bushing, 2" x 1-1/2" or 1-1/4"
Oil Tank
Gate Valve
3/8" x 4" nipple
3/8" x 3/8" Adapter
3/8" O.D. Copper Fuel Tubing
Bushing Legs (either 1-1/4"x10" or 1-1/2"x10" nipples)
Oil Filter
6"

These controls were selected for their proven high quality, dependability, and serviceability. With proper maintenance this burner assembly will provide many years of reliable service.
This igniter differs from the traditional iron core transformer in that it produces a 14,000 volt spark instead of a 10,000 volt spark of the iron core transformer. This hotter spark provides for cleaner, faster ignitions. Being solid state technology this igniter is less susceptible to problems caused by voltage variations. It also has a greater ability to ignite cold and/or inconsistent oil. The solid state igniter is wired to the primary control the same as an iron core transformer.
All units are shipped with the oil burner installed, and with high rate oil nozzle installed designed for use with No. 1 or No. 2 fuel oil. Inspect firepot refractory before firing to be sure it has not been jarred out of position in shipment. Burner air tube must not extend beyond inside surface of firepot. Burner head should be centered on the combustion chamber opening. See Figures 19 and 20.
WARNING
The R7184B Interrupted Electronic Oil Primary is a line voltage, safety rated, interrupted ignition oil primary control for residential oil burners. The R7184B used with a cad cell flame sensor, operates the oil burner and oil valve. The primary controls fuel oil, senses flame, controls ignition spark and is designed to notify a remote alarm circuit before going into lockout when equipped with a flame monitoring system.
Never attempt to use gasoline in your furnace. Gasoline is more combustible than fuel oil and could result in a serious explosion causing damage, injury or death.
This primary control possesses the latest technology, is a very simple control to operate and provides additional troubleshooting features to ease service and reduce down time. The operational guide for the R7184B primary control is provided following on Page 12.
The following is a detailed explanation of each control included in the Becket AFG Oil Burner, how each operates, how to set up the burner, and how to troubleshoot problems should they occur.
This oil pump is equipped with an oil solenoid valve installed in the pump housing. This feature provides quick cutoffs resulting in reduction in smoke after the burner shuts down. This is a time proven pump design and is capable of both one and two pipe systems. This pump requires a pre-purge style primary control such as the R7184B primary. All installation and set up instructions are outlined in the “Oil Pump Specification” section of the installation instructions manual.

OPERATIONAL GUIDE
Pre-Purge Delay – 15 seconds on delay LED Codes – Flashing 1/2 second on / 1/2 second off – system is locked out or in restricted mode
(hard lockout). – Flashing 2 seconds on / 2 seconds off – control is in recycle mode (soft lockout). – ON – CAD cell is sensing flame – OFF – CAD cell is not sensing flame.
Ignition Trials – On any given call for heat the control will allow three ignition trials. After the three trials the control will go into a soft lockout mode. The LED will flash 2 seconds on and 2 seconds off when in this recycle mode. The control may then be reset by pressing the RED reset button on the control. If within the same original call for heat the control will again allow three ignition trials followed by another soft lockout and a 2 second on / 2 second off LED code. The control my be reset one additional time by pressing the red reset button. This will allow three final ignition trials. If all three of the final ignition trials
fail then the control goes into a hard lockout or Restricted Mode. This series of ignition failures must all occur with the original call for heat in order to reach the Restricted Mode. The LED will now flash 1/2 second on / 1/2 second off indicating the restricted mode. The control can be resurrected from the restricted mode only by pressing and holding the red reset button for approximately 30 seconds until the LED flashes twice. Removing unit power or resetting the thermostat will not reset the control
Checking CAD Cell – With a call for heat and the burner ignited, press and release the red reset button. The LED will go out and then flash 1, 2, 3, or 4 times before returning to the run mode. The CAD cell resistance must be below 1600 ohms for proper operation.
– 1 flash – Less than 400 ohms – 2 flashes – More than 400 and less than 800 ohms – 3 flashes – More than 800 and less than 1600 ohms – 4 flashes – More than 1600 and less than 5000 ohms
Burner Option – Flame Quality Monitor This control is trained to recognize and remember a good flame based on initial burner set up. Control then monitors the flame via the CAD cell signal for deviation in the combustion characteristics of the burner. If the control senses a deviation on the high side or on the low side from the original set up condition for three consecutive cycles, it will trigger an alarm circuit which can be tied to an audible local device to signal the home owner or into the home security system. Upon being notified of the of the
alarm, the security agency will notify the dealer of choice based upon information supplied by the home owner. The system will also be capable of being connected to a phone line that will contact the dealer directly with the alarm. This alarm will typical sound 3 to 5 days prior to the primary control going into lockout giving the service agency a prior notice before a sooting condition or other failure can occur resulting in untold savings. This monitor system is available through your local distributor under the Honeywell part no. QS7100F.
blower on and off timings for both heating and cooling speeds are timed automatically. The heating blower off delay can be selected from four different timings by moving the selection jumper. The timings are as follows:
This furnace is equipped with an Electronic Blower Control (EBC) which controls all comfort air blower operations. This EBC has three relays; one for heating speed, one for cooling speed, and one which isolates the T–T signal from the oil primary control.
Heating Blower ON delay – 75 seconds from a call for heat.
This EBC is designed to be very simple and dependable. This basic control allows for easy troubleshooting and maintenance. As illustrated in Figure 7 all connections are well marked. The
Heating Blower OFF delay – Selectable in seconds: 150, 180. 210 or 240. Factory shipped at 240.
Cooling Blower ON delay – 6 seconds from a call for cooling.
Cooling Blower OFF delay – 60 seconds.

TRANSFORMER 24V SECONDARY CONNECTIONS THERMOSTAT CONNECTIONS
3 AMP FUSE
HEATING BLOWER
OFF DELAY ADJUSTMENT
IN SECONDS.
LINE VOLTAGE CONNECTION (HOT)
HUMIDIFIER CONNECTION
UNUSED BLOWER MOTOR SPEED CONNECTIONS
HEATING BLOWER SPEED CONNECTION
LINE VOLTAGE CONNECTION (COM, L2) ELECTRIC AIR CLEANER CONNECTION

d r a d n a t S d e ll a t s n I e c a n r u F n o it p O d e ll a t s n I d l e i F s
2 g n it a e H
2 g n it a e H
1 e l z z o N
1 e l z z o N
1 e l z z o N
t u p n I
y ti c a p a C
t u p n I
y ti c a p a C
t u p n I
y ti c a p a C
r e b m u N l e d o M
H U T B
H U T B
H U T B
H U T B
H U T B
E 6 3 D 5 8 0 F L F 5 7 . 0 0 0 , 5 0 1 0 0 0 , 5 8 5 6 . 0 0 0 , 1 9 0 0 0 , 4 7 5 5 . 0 0 0 , 7 7 0 0 0 , 3 6
E 6 3 D 5 8 0 R L F 5 7 . 0 0 0 , 5 0 1 0 0 0 , 5 8 5 6 . 0 0 0 , 1 9 0 0 0 , 4 7 5 5 . 0 0 0 , 7 7 0 0 0 , 3 6
E 8 4 D 0 1 1 F L F 0 0 . 1 0 0 0 , 0 4 1 0 0 0 , 3 1 1 5 8 . 0 0 0 , 9 1 1 0 0 0 , 6 9 A N A N A N
E 8 4 D 0 1 1 R L F 0 0 . 1 0 0 0 , 0 4 1 0 0 0 , 3 1 1 5 8 . 0 0 0 , 9 1 1 0 0 0 , 6 9 A N A N A N
E 0 6 D 0 1 1 F L F 0 0 . 1 0 0 0 , 0 4 1 0 0 0 , 3 1 1 5 8 . 0 0 0 , 9 1 1 0 0 0 , 6 9 A N A N A N
E 0 6 D 0 1 1 R L F 0 0 . 1 0 0 0 , 0 4 1 0 0 0 , 3 1 1 5 8 . 0 0 0 , 9 1 1 0 0 0 , 6 9 A N A N A N
E 0 6 D 0 4 1 R L F 5 2 . 1 0 0 0 , 5 7 1 0 0 0 , 2 4 1 0 1 . 1 0 0 0 , 4 5 1 0 0 0 , 5 2 1 A N A N A N
E 6 3 D 5 8 0 C F 5 7 . 0 0 0 , 5 0 1 0 0 0 , 5 8 5 6 . 0 0 0 , 1 9 0 0 0 , 4 7 5 5 . 0 0 0 , 7 7 0 0 0 , 3 6
E 6 3 D 5 8 0 H F 5 7 . 0 0 0 , 5 0 1 0 0 0 , 5 8 5 6 . 0 0 0 , 1 9 0 0 0 , 4 7 5 5 . 0 0 0 , 7 7 0 0 0 , 3 6
E 8 4 D 0 1 1 H F 0 0 . 1 0 0 0 , 0 4 1 0 0 0 , 3 1 1 5 8 . 0 0 0 , 9 1 1 0 0 0 , 6 9 A N A N A N
E 0 6 D 0 1 1 H F 0 0 . 1 0 0 0 , 0 4 1 0 0 0 , 3 1 1 5 8 . 0 0 0 , 9 1 1 0 0 0 , 6 9 A N A N A N
70 degree hollow cone spray pattern, 100 PSIG pump pressure Annual fuel utilization efficiency and heating capacity based upon U.S. Government standard test using D.O.E. isolated combustion rating procedure.
A. Calibrate and Check Operation of
All oil burner installations should be performed by a qualified installer in accordance with regulations of the National Fire Protection Standard for Oil-Burning Equipment, NFPA31 -- latest edition, and in complete compliance with all local codes and authorities having jurisdiction. A qualified installer is an individual or agency who is responsible for the installation and adjustments of the heating equipment and who is properly licensed and experienced to install oil-burning equipment in accordance with all codes and ordinances.
Measuring Equipment Follow manufacturer’s recommended procedures for calibration and equipment check out.
B. Prepare Heating Unit for Testing Drill two
1/4 inch holes in the flue between the heating plant and the barometric draft regulator. If space permits, the holes should be located in a straight section of the flue, at least two flue diameters from the elbow in the flue pipe and at least one diameter from the draft regulator. The purpose of the two holes in the flue pipe is to speed up testing and reduce instrument handling.
The proper installation and adjustment of any oil burner requires technical knowledge and the use of combustion test instruments. The following procedure must be followed to correctly adjust the burner to match the specific characteristics of the installation.
C. Clean and Seal Heating Plant Make sure the
burner blast tube, fan housing, and blower wheel are clear of dirt and lint. Seal any air leaks into the combustion chamber.
Always use combustion test instruments when making burner adjustments and draft gauge when setting the barometric damper. It is virtually impossible to make accurate and reliable adjustments using the “eyeball” method.
D. Nozzle Inspection Annual replacement of
nozzle is recommended. The nozzle size should match the design load . DO NOT OVERSIZE. (Determination of oversizing can be determined prior to your adjustment. If the firing rate should be reduced refer to Table 4.) Short cycles and low percent :on: time result in higher overall pollutant emissions and lower thermal efficiency. An in-line oil filter will reduce service problems due to nozzle clogging.
Check all oil lines and connections for leaks.
Connect pressure gauge by removing bleed fitting and screwing in pressure gauge. See Figure 9.
e zi S · e zi S · e zi S

It should be located as close as possible to the oil burner. Care should be taken to prevent air leakage in the oil suction line. Use continuous runs of copper tubing and use minimum number of joints and fittings. Always use flare fittings.
K. Adjust Air Setting Examine the smoke - CO2
plot and, keeping in mind the curve of Figure 6, note the location of the “knee” where the smoke number begins to rise sharply. Noting the air gate position marks, adjust the air setting to a CO2 level 1/2 to 1 percent lower than the CO2 level at the “knee”. (This provides a tolerance against possible shifts in the setting over a period of time.) Do not increase the air setting any more than necessary on the lower portion of the curve below the “knee”
E. Adjustment of Electrodes Adjust ignition
electrodes as specified in Figure 10.
F. Operate Burner Operate burner, adjust air
setting for good flame by visual observation, and run for at least 10 minutes or until operation has stabilized.
The characteristic curve for some burners may not yield a distinct “knee” in the curve. In such cases, the setting should be made near the minimum smoke, (using judgement).
G. Check Burner Pressure Bleed air from
pump and nozzle piping. Check pump pressure and adjust to 100 psi, if necessary.
Lock the air adjustment and repeat draft, CO2 and smoke measurements to make sure the setting has not shifted.
H. Set Draft Check the draft reading over the
fire with a draft gauge through a hole in the inspection door. The hole is above the flame level. Adjust the barometric draft regulator on the flue to give the over fire of -.02” W.C.
L. Check Performance A well-matched and
well-tuned burner should be capable of operation with smoke not greater than No. 2 and at a CO2 level not less than 10%.
I. Check Smoke Readings After burner has been operating 5 or 10 minutes, make a smoke measurement in the flue, following the smoke tester instructions. Oily or yellow smoke spots on the filter paper are usually a sign of unburned fuel, indicating very poor combustion (and likely high emissions of carbon monoxide and unburned hydrocarbons.) This condition can sometimes be caused by too much air, or by other factors. If this condition cannot be corrected, major renovation or even burner replacement may be necessary.
If this cannot be reached, check the following:
To check for dilution by leakage, measure the CO2 at as high a point as possible over the fire, using a stainless steel tube inserted through the fire door sample hole (as described earlier for overfire draft measurements), and compare this with the CO2 measured in the flue. A difference of more than 1 percent CO2 between the flue and overfire reading usually indicates air entry through leaks that have not been properly sealed.
J. Develop Smoke - CO2 Curve Record measurements of smoke and CO2 from the flue. Then establish the smoke - CO2 curve by taking readings over a range of air settings, as shown in Figure 8.
To do this, start with the air gate set at nearly full open and then take smoke and CO2 readings at progressively lower air settings, as necessary to visualize the general shape of the curve. (The CO2 readings will increase as the air setting is decreased, unless combustion is incomplete.) Do not set the air gate to give a smoke reading above No. 4 or No. 5. Plot the points on graph paper, as in Figure 8. Usually 3 or 4 readings are enough to establish the curve.
Seal between the probe and inspection door sample hole during test. The inspection door hole should be sealed when not being used to avoid leakage of air through it. (See Step H.)
In adjusting each air setting, it is helpful to note the various positions of air gate at which measurements are made so that the final setting can be located quickly.
It may be necessary to replace the combustion head or try different settings.

SHORT FORM ADJUSTMENT PROCEDURE
M. Measure Stack Temperature Operating the
unit at an excessive firing rate will generate more heat than the heat exchanger can utilize and result in unnecessary heat loss up the chimney. Other causes of excessive heat loss are badlysooted heat exchanger surfaces and excessive draft. The temperature of the flue gas provides an indication of these heat losses.
Some burner service organizations may wish to perform a shorter procedure for the adjustment of oil burners. The following is an example of such a short form prepared by the National Association of Oil Heat Service Managers.
Measure flue temperature by subtracting the room air temperature from the thermometer reading. Excessive stack loss is indicated of the net stack temperature during steady operation exceeds 600° F.
2, CHECK DRAFT Set draft regulator, if necessary. Regulator should be adjusted to achieve a -.02” W.C. over fire condition. The more restricted and lengthy the flue, the higher the draft necessary to obtain the accepted over fire conditions.
N. Check Ignition Check operation over repeated
cycles to insure prompt ignition on starting.
O. Check Pump Cutoff Slow pump cutoff at the
end of a firing cycle can cause smoke and other pollutant emissions. Check for prompt pump cutoff by observing flame or by testing smoke at shutdown. If poor cutoff is observed, make sure air is purged from the pump and nozzle line. Air trapped in the pump or nozzle line will expand when heated, thus causing oil to drip into the combustion chamber after shutdown. If poor cutoff persists, repair or replace pump. Also make sure the pump solenoid is working. If not replace.
Follow the instructions of the manufacturer of the smoke tester and take a smoke sample. Adjust the air to obtain a preliminary reading of about No. 3 spot. Then readjust the air to obtain the lowest possible reading, but do not open the air adjustment more than absolutely necessary to obtain a trace or No. 0 spot.
Check CO2 levels. This level should be between 10% and 12%.

Air Settings Low High
CO Curve from plotted points
8 10 12 14 6
Percent CO in Flue Gas 2
0 14 8 10 12 6 Percent CO in Flue Gas 2

Remove Bleed Port to attach pressure guage.

AND RESERVE AIR
n o b r a C
e d i x o i D n e g y x O ri A e v r e s e R
). x o r p p A (
(NET STACK TEMP. DEGREES F)
O % 2 0 0 2 0 5 2 0 0 3 0 5 3 0 0 4 0 5 4 0 0 5 0 5 5 0 0 6 0 5 6 0 0 7 0 5 7 0 0 8 O % 2
1 6 . 9 8 4 . 8 8 3 . 7 8 2 . 6 8 1 . 5 8 0 . 4 8 9 . 2 8 7 . 1 8 6 . 0 8 5 . 9 7 4 . 8 7 3 . 7 7 2 . 6 7 7 . 4 1
2 4 . 9 8 2 . 8 8 0 . 7 8 9 . 5 8 7 . 4 8 6 . 3 8 4 . 2 8 2 . 1 8 1 . 0 8 9 . 8 7 7 . 7 7 6 . 6 7 4 . 5 7 0 . 4 1
3 2 . 9 8 9 . 7 8 7 . 6 8 5 . 5 8 3 . 4 8 1 . 3 8 9 . 1 8 7 . 0 8 4 . 9 7 2 . 8 7 0 . 7 7 8 . 5 7 6 . 4 7 2 . 3 1
4 9 . 8 8 7 . 7 8 4 . 6 8 1 . 5 8 8 . 3 8 6 . 2 8 3 . 1 8 0 . 0 8 7 . 8 7 5 . 7 7 2 . 6 7 9 . 4 7 6 . 3 7 5 . 2 1
5 7 . 8 8 3 . 7 8 0 . 6 8 6 . 4 8 3 . 3 8 0 . 2 8 6 . 0 8 3 . 9 7 9 . 7 7 6 . 6 7 3 . 5 7 9 . 3 7 6 . 2 7 7 . 1 1
6 4 . 8 8 0 . 7 8 5 . 5 8 1 . 4 8 7 . 2 8 3 . 1 8 9 . 9 7 5 . 8 7 0 . 7 7 6 . 5 7 2 . 4 7 8 . 2 7 4 . 1 7 0 . 1 1
7 0 . 8 8 5 . 6 8 0 . 5 8 5 . 3 8 0 . 2 8 5 . 0 8 0 . 9 7 5 . 7 7 0 . 6 7 5 . 4 7 0 . 3 7 5 . 1 7 0 . 0 7 3 . 0 1
d e ll a t s n I y r o t c a F n o it p O d e ll a t s n I d l e i F
e c a n r u F
e l y t S r e n r u B
d n a B
r e tt u h S
d n a B
r e tt u h S
d n a B
r e tt u h S
. o N l e d o M
. o N tr a P
g n itt e S
g n itt e S
g n itt e S
g n itt e S
g n itt e S
g n itt e S
E 6 3 D 5 8 0 H F 6 2 0 - 0 2 0 9 / G F A 5 7 . 0 6 5 6 . 0 5 5 5 . 0 5
E 8 4 D 0 1 1 H F 7 2 0 - 0 2 0 9 / G F A 0 0 . 1 2 0 1 5 8 . 0 8 A N A N A N
E 0 6 D 0 1 1 H F 7 2 0 - 0 2 0 9 / G F A 0 0 . 1 2 0 1 5 8 . 0 8 A N A N A N
E 6 3 D 5 8 0 F L F 6 2 0 - 0 2 0 9 / G F A 5 7 . 0 6 5 6 . 0 5 5 5 . 0 5
E 8 4 D 0 1 1 F L F
E 0 6 D 0 1 1 F L F 7 2 0 - 0 2 0 9 / G F A 0 0 . 1 2 0 1 5 8 . 0 8 A N A N A N
E 6 3 D 5 8 0 R L F 1 3 0 - 0 2 0 9 / G F A 5 7 . 0 6 5 6 . 0 5 5 5 . 0 5
E 8 4 D 0 1 1 R L F
E 0 6 D 0 1 1 R L F 2 3 0 - 0 2 0 9 / G F A 0 0 . 1 2 0 1 5 8 . 0 8 A N A N A N
E 0 6 D 0 4 1 R L F 3 3 0 - 0 2 0 9 / G F A 5 2 . 1 0 8 0 1 . 1 0 6 A N A N A N
E 6 3 D 5 8 0 C F 6 2 0 - 0 2 0 9 / G F A 5 7 . 0 6 5 6 . 0 5 5 5 . 0 5
70 degree hollow cone spray pattern, 100 PSIG pump pressure

COMBUSTION AIR REQUIREMENTS
The electrodes should be spaced 5/32” apart. They should extend 1/16” beyond the end and 5/16” above the center of the nozzle tip as shown in Figure 10.
This furnace must be installed in a location where a sufficient supply of combustion air is available for the complete combustion of the fuel oil. Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil.
The gun assembly can be adjusted in the slot inside of fan housing by loosening screw holding slot cover in position. Nozzle tip should ordinarily be located 1-1/8” behind the front face of the cone.
When structures are constructed too tightly to supply sufficient combustion air, air from outside the structure is required to be brought in directly to the furnace. This furnace has been conveniently designed to accept a combustion air boot which is attached directly to the outdoors by means of a 4” pipe. This pipe can be rigid or flexible, but it is recommended that a metallic material be used. Refer to Figure 11. The air boot used for this design is a Field Controls model number CAS-2B-90E that can be purchased through your local distributor. Follow all installation procedures as specified in the instructions packaged with the air boot kit.
Disconnect the oil line at the fan housing and remove lock nuts on copper tube fitting. Loosen igniter hold down clamps, then swing igniter up and backward. Gun assembly can now be removed through this opening.
5/32 GAP
1/16 NOZZLE
1-1/8 · 5/16

COMBUSTION
AIR BOOT ASSEMBLY
USE THIS KNOCKOUT FOR OIL LINE
INTAKE
AIR TUBE
BURNER ASSEMBLY
REMOVE PUMP TO ASSEMBLE INNER AIR BOOT
REMOVE KNOCKOUT IN LEFT SIDE
INSERT OUTER AIR BOOT AND SECURE FLANGE TO UNIT
MAKE ALL SETTINGS ACCORDING TO MANUAL FOR AIR BOOT.

TABLE 8 SQUARE FEET REQUIRED TO QUALIFY AS UNCONFINED SPACE
In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation, and dilution of flue gases. However, in buildings of unusually tight construction, additional air shall be provided using the method described under “All Air From Outdoors” in Figure 13.
e c a p S d e n if n o c n U
l a t o T
n I a e r A m u m i n i M
t e e F e r a u q S
t u p n I
t h g i e H g n ili e C ' 8
An unconfined space (such as an open basement) must have a minimum volume of 50 cubic feet per 1,000 BTUH of total of all appliances in area. Adjoining rooms may be counted as one area only if there are not doors between the rooms.
0 0 0 , 0 6 0 0 0 , 0 8 5 7 3 0 0 5
0 0 0 , 5 8 0 0 0 , 5 0 1 1 3 5 6 5 6
0 0 0 , 5 1 1 0 0 0 , 0 2 1 9 1 7 0 5 7
Shown in Table 8 are the required minimum areas in square feet to qualify as an unconfined space for various total BTUH input ratings. The table is based on a room(s) with 8 foot ceiling heights.
0 0 0 , 0 4 1 0 0 0 , 5 4 1 5 7 8 6 0 9
0 0 0 , 0 6 1 0 0 0 , 0 0 2 0 0 0 1 0 5 2 1
If the unconfined space is within a building having insufficient air because of tight construction, the air for combustion and ventilation shall be obtained from outdoors or from spaces freely communicating with the outdoors. Under these conditions a permanent opening or openings have a total free area of not less than one square inch per 5,000 BTU per hour (28 square inches per hour ) of total input rating of all appliances shall be provided. For combustion air options see Page 20, “Combustion Air Requirements”.
The confined space shall be provided with two permanent openings, one near the top of the enclosure and one near the bottom. Each opening shall have a free area of not less than one square inch per 1,000 BTU per hour (140 square inches per gallon per hour) of the total input rating of all appliances in the enclosure freely communicating with interior areas having in turn adequate infiltration from the outside. (See Figure 12.) Also see Table 9 on the following page for specific ventilation opening requirements for the furnace only.
IN CONFINED SPACES ALL AIR FROM INSIDE THE BUILDING
The flow of combustion and ventilating air must not be obstructed from reaching the furnace.
not less than one square inch per 1,000 BTU per hour (140 square inches per gallon per hour) of the total input rating of all appliances in the enclosure.

ALL VENTILATION AIR FROM OUTDOORS
A. The confined space shall be provided with two

d e d n e m m o c e R
permanent openings, one in or near the top of the enclosure and one in or near the bottom. The openings shall communicate directly, or by means of ducts with outdoors or to such spaces (crawl or attic) that freely communicate with outdoors. (See Figures 13, 14, & 15.)
n o it a lit n e V . n i M
) d e ri u q e R 2 (
h c n I e r a u q S
e zi S . n I . q S
E 6 3 D 5 8 0 H F 0 4 2 6 1 x 8 8 2 1
E 8 4 D 0 1 1 H F 0 8 2 8 1 x 9 2 6 1
B. When directly communicating with outdoors or by
E 0 6 D 0 1 1 H F 0 8 2 8 1 x 9 2 6 1
means of vertical ducts, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour (35 square inches per gallon per hour) of total input rating of all appliances in the enclosures. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2,000 BTU per hour (70 square inches per gallon per hour) of total input of all appliances in the enclosure.
E 6 3 D 5 8 0 F L F 0 9 2 9 1 x 8 2 5 1
E 6 3 D 5 8 0 R L F 0 9 2 9 1 x 8 2 5 1
E 8 4 D 0 1 1 F L F
E 0 6 D 0 1 1 F L F 0 4 3 9 1 x 9 1 7 1
E 8 4 D 0 1 1 R L F
E 0 6 D 0 1 1 R L F 0 4 3 9 1 x 9 1 7 1
E 0 6 D 0 4 1 R L F 0 6 3 9 1 x 5 . 9 0 8 1
E 6 3 D 5 8 0 C F 0 4 2 6 1 x 8 8 2 1
ALL AIR FROM OUTDOORS

free area of not less than one square inch per 2,000 BTU per hour (70 square inches per gallon per hour) of the total input rating of all appliances in the enclosure.

FIGURE 14 APPLIANCES LOCATED IN CONFINED SPACES ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

shall each have a free area of not less than one square inch per 4,000 BTU per hour (35 square inches per gallon per hour) of the total input rating of all appliances in the enclosure.
ALL AIR FROM OUTDOORS INLET AIR FROM VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC

shall each have a free area of not less than one square inch per 4,000 BTU per hour (35 square inches per gallon per hour) of the total input rating of appliances in the enclosure.

A barometric damper is supplied with the furnace and must be installed in the flue pipe observing the instructions packaged with the damper control. The barometric damper opening must be located in the same atmospheric pressure zone as the combustion air inlet to the furnace. The furnace must not be vented into the same chimney with any solid fuel burning appliance such as a wood burner or pellet burner. Masonry chimneys must be lined with a listed system or other approved material that will resist corrosion, softening or cracking from flue gas temperatures up to 1800° F. See Standard for Installation of Oil Burning Equipment NFPA31 latest edition and Standard for Chimneys NFPA211 latest edition for additional information.
In calculating free area for ventilation and combustion air requirements, consideration shall be given to the blocking effect of louvers, grilles, or screens protecting openings. Screens used shall not be smaller than 1/4 inch (6.3 mm) mesh and shall be readily accessible for cleaning. If the free area through a design of louver or grille is known, it shall be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will have 30-35 percent free area and metal louvers and grilles will have 60-75 percent free area.
This furnace is designed to be vented conventionally into a vertical chimney or horizontally through a side wall with an optional Field Controls side wall power venting system.
This furnace is designed to be horizontally vented through a side wall with an optional side wall power vent. The recommended side wall venter is the Field Controls model number SWG-4HDS for 085 and 110 models, and SWG-5S for 140 models only. This venter can be purchased through your local distributor. Follow all installation instructions packaged with the venter system.
Note that the FH, FC and FLF series furnaces have been designed to allow for bringing the vent system through the cabinet side for increased venting flexibility. To take advantage of this feature, simply remove the desired knockout from either side or top of unit and rotate flue box accordingly by removing four (4) screws under cleanout plate as shown in Figure 4. Make sure smoke pipe gasket is in place before reinstalling flue box screws.
These furnaces are designed to be controlled with any 24V heating or heating/cooling thermostat. The heat/cool thermostats must be designed for independent heat/cool transformer circuits to assure that the 24V transformer built into the oil primary control does not conflict with the main furnace 24V transformer. The heat anticipator should be set at 0.20A. This is a nominal setting. The thermostat circuit should be checked to verify setting.
If the unit is to be vertically vented make sure the flue pipe from the furnace to the chimney is the same size diameter as the flue outlet of the furnace which is 6”. The flue pipe must have no reductions in diameter, be made of a corrosion-resistant material having an upward pitch of 1/4” for every foot of horizontal run, and be made of material capable of handling temperatures up to 1800° F.

AND HEATING BLOWER SPEEDS
m u m i x a M
1 e l z z o N s e g n a R e s i R
ri A t e lt u O
r e w o l B g n it a e H
l e d o M
. p m e T
d e e p S
0 0 1 - 0 7 0 0 1 - 0 7 0 9 - 0 6
0 0 2 0 0 2 0 0 2
E 6 3 D 5 8 0 H F
E 8 4 D 0 1 1 H F 5 8 .
0 0 . 1 0 0 1 - 0 7 0 9 - 0 6 0 0 2 0 0 2 w o L
w o L d e M
E 0 6 D 0 1 1 H F 5 8 .
0 0 . 1 0 9 - 0 6 0 9 - 0 6 0 0 2 0 0 2 w o L
w o L d e M
0 9 - 0 6 0 9 - 0 6 0 9 - 0 6
0 0 2 0 0 2 0 0 2
E 6 3 D 5 8 0 F L F
E 8 4 D 0 1 1 F L F 5 8 .
0 0 . 1 0 9 - 0 6 0 9 - 0 6 0 0 2 0 0 2 w o L d e M
h g i H d e M
E 0 6 D 0 1 1 F L F 5 8 .
0 0 . 1 0 9 - 0 6 0 9 - 0 6 0 0 2 0 0 2 w o L d e M
h g i H d e M
0 9 - 0 6 0 9 - 0 6 0 9 - 0 6
0 0 2 0 0 2 0 0 2
E 6 3 D 5 8 0 R L F
E 8 4 D 0 1 1 R L F 5 8 .
0 0 . 1 0 9 - 0 6 0 9 - 0 6 0 0 2 0 0 2 w o L d e M
h g i H d e M
E 0 6 D 0 1 1 R L F 5 8 .
0 0 . 1 0 9 - 0 6 0 9 - 0 6 0 0 2 0 0 2 w o L d e M
h g i H d e M
E 0 6 D 0 4 1 R L F 0 1 . 1 5 2 . 1 0 9 - 0 6 0 9 - 0 6 0 0 2 0 0 2 w o L d e M
h g i H d e M
0 0 1 - 0 7 0 0 1 - 0 7 0 9 - 0 6
0 0 2 0 0 2 0 0 2
E 6 3 D 5 8 0 C F
70 degree hollow cone spray pattern, 100 PSIG pump pressure

Only Lo-Boy models are shipped with air filters. Filter kits are available from your local distributor for Upflow and Counterflow models. Knockouts are provided in the sides of the FH series models to facilitate the cutting of the return openings.

E 6 3 D 5 8 0 H F
y o B -i H ) 1 ( 1 x 5 2 x 6 1
The upflow filter kit part numbers are FR23 for a 16x25x1 filter size and FR24 for a 20x25x1 filter size. These filter kits come complete with the filter and all necessary brackets for installing on the furnace. Each comes with a washable aluminum mesh filter. When installing a five ton AC unit on the furnace, one FR24 or Two FR23 must be used due to the high airflow requirements. It is important to note that a minimum of one inch spacing is required between the filter and the unit side. Do not exceed 400 fpm for fiberglass (disposable) type filters and 575 fpm for washable type filters. See Figure 16.
E 8 4 D 0 1 1 H F
y o B -i H ) 1 ( 1 x 5 2 x 6 1
E 0 6 D 0 1 1 H F
y o B -i H ) 1 ( 1 x 5 2 x 0 2
E 6 3 D 5 8 0 F L F
E 6 3 D 5 8 0 R L F
) 1 ( 1 x 0 2 x 6 1
E 8 4 D 0 1 1 F L F
E 8 4 D 0 1 1 R L F
E 0 6 D 0 1 1 F L F
) 1 ( 1 x 0 2 x 0 2
E 0 6 D 0 1 1 R L F
The counterflow filter kit part number FR25 comes with two washable filters. If not installing the FR25 kit remember not to exceed 400 fpm for fiberglass (disposable) type filters and 575 for washable type filters. See Figure 17.
E 0 6 D 0 4 1 R L F
y o B - o L ) 1 ( 1 x 5 2 x 0 2
E 6 3 D 5 8 0 C F
w olfr e tn u o C ) 2 ( 1 x 0 2 x 6 1
See Table 11 for filter sizes and quantities.
FIGURE 17 TYPICAL INSTALLATION OF FR25
FR27 FILTER RACKS
FILTER KIT


Lo-boy models have the filter installed in the return air cabinet section of the furnace. It is accessible from the rear of the furnace by removing the blower/filter access door. The electrical switch should be turned “off” prior to removing the access door. Refer to Figure 18 below.
LOWBOY FILTER
UNIT FILTER SIZE FLF/FLR085 16 x 20 x1 FLF/FLR110 20 x 20 x1 FLR140 20 x 25 x 1
STEP 3: SLIDE FILTER OUT TOWARDS BLOWER
DOOR
STEP 2: REMOVE BLOWER DOOR
STEP 1: UNFASTEN SWELL LATCHES BY PULLING
BY PULLING OUT ON SWELL LATCHES AND
HANDLES OUTWARD
TILTING OUTWARDS

B. Ignition Failure – Test by closing oil supply
while burner is off. Run through starting procedure. The primary control will attempt three trials for ignition. After three attempts, the control will lockout. C. Power Failure – Turn off power supply
No lubrication is required for either the burner or the blower motor. Both are permanently lubricated.
Replace filters before each heating season begins. It is recommended that filters also be replaced at least twice during the heating season.
while burner is on. When burner goes out, restore power and burner will restart. D. If operation is not as described, check wiring
and installation first. If trouble appears to be in the control circuit, replace the flame detector. If trouble still persists, refer to “Common Causes of Trouble” section on page 28.
Be sure the new filters are set securely in the filter rack so there can be minimal leakage around them.
Final inspection and test of an installation shall be made to determine that the work has been done in full accordance with regulations and according to the highest standards for safety, performance and appearance. Such an inspection and test should indicate the following as a minimum:
Preventive maintenance is the best way to avoid unnecessary expense, inconvenience, and retain operating efficiency of your furnace. It is advisable to have your heating system and burner inspected at periodic intervals by a qualified serviceman. If trouble develops, follow these simple checks before calling the serviceman.
1. Determine that all parts of the oil storage and circulating system, including tank, piping and burner, are free from oil leaks. Be sure that no oil discharges from the nozzle when burner is not operating. 2. Be sure that the suction line and pump have been entirely vented of air so that the burner has instantaneous oil shutoff at the nozzle and so that the pump operates without an air noise. 3. Check the flame adjustment to determine that the flame is clear, quiet, free of odor and oil nozzle is of proper size for the furnace. 4. Test operation of burner by operating the thermostat. First, set the thermostat above room temperature. Burner should start. Second, set thermostat below room temperature. Burner will stop. 5. Check operation of burner primary control in accordance with manufacturer’s instructions included with the control. Following is the method we recommend in checking the safety switch in this primary control. A. Flame Failure – Simulate by shutting off oil
Reset three (3) times only. More than three resets can cause excessive oil to be pumped into combustion chamber which could result in explosion upon ignition.
supply manual valve while burner is on. Within 9 seconds the control will shut the burner down and flash a diagnostic code of 1/2 second on / 1/2 second off. Ignition and motor stop and oil valve closes

WARNING
The furnace has been designed with a combustion chamber mounting system that enables service personnel to remove the combustion chamber, its mounting system, and burner assembly as one unit for inspection and/or service on the bench. It has also been designed to remove the burner assembly independently from the mounting system to perform basic annual service and inspection. The mounting system is completely adjustable so exact alignment between the burner tube and combustion chamber may be assured prior to installation into the furnace. See Figure 19 and 20.
The procedures described in Figures 19 and 20 should be conducted only by a qualified service technician.
Improper servicing could cause electric shock hazard, fires or explosion resulting in damage, injury or death.
BURNER REMOVAL
DANGER !
INSTRUCTIONS
*ELECTRICAL SHOCK HAZARD *DISCONNECT POWER BEFORE SERVICING.
BURNER ASSEMBLY.

TO REMOVE THE ENTIRE COMBUSTION CHAMBER MOUNTING SYSTEM
Disconnect fuel line, power cord and wires from T, T on primary control. Loosen (3) 1/4 inch bolts securing burner mounting flange. Twist burner counterclockwise and pull straight back away from the furnace. (See Figure 19.)
Disconnect fuel line, power cord and wires from T, T on primary control. Remove (6) 5/16 inch bolts from around front plate. Next remove (2) 5/16 inch nuts from upper right and left hand corners of the front plate. Pull entire assembly straight back away from furnace. BE CAREFUL NOT TO TIP ASSEMBLY UP OR DOWN AS IT MAY DAMAGE THE COMBUSTION CHAMBER. (See Figure 20.)


CAUTION
This may be caused by air in pipes. Check all joints in the oil supply pipe for leaks. Check strainer in pump; if dirty, clean.
To avoid accidents, always open main switch (OFF position) when servicing the burner.
Check limit control setting. It may be that flame is not allowed to stay on long enough to generate sufficient heat in furnace to heat the house properly. If the proper size furnace has been selected according to house requirements and satisfactory heat is not obtained, recheck the heating plant for size and capacity in relation to house. Check for clogged filters.
Check oil level gauge to see that there is sufficient oil in tank or tanks. Check the burner mounted relay control. Do not adjust this control.
Check position of electrodes – incorrect position will cause slow or delayed ignition. Clean electrodes and nozzle. Check and clean strainer in pump. If oil line filter is used, check filter condition.
Check and make sure the heat anticipator on the thermostat is set correctly.
If burner runs but there is no flame the fuel pump may be air bound. Follow instructions for bleeding fuel pump.
This furnace cabinet is made with a very durable and corrosion resistant finish. With normal cleaning it will last for many years.
Check and make sure the solenoid valve on the oil pump is being energized and opening.
Check heat anticipator setting on thermostat.
Under no circumstance should a soot deterioration device be used in the combustion chamber. These products known as “soot busters” or “soot sticks” are comprised of chemicals that burn at very high temperatures which may exceed the temperature rating of the combustion chamber material.
Worn tangential grooves in nozzle. Replace nozzle.
Occasionally with a two-pipe installation there may be a low return line hum. Eliminate hum by installing a special anti-hum valve in the return line near pump.
Use of these products are detrimental to the life expectancy of the combustion chamber and will destroy the chamber. Refer to the “Cleaning of Furnace” section for proper cleaning methods.
HEAVY FIRE OR PULSATING FLAME.
These may occur after burner starts. It may be caused by a slight oil leak in the fuel pump and cannot be corrected except by replacing the pump. This happens only when the burner is started.
All of these units have four clean out plugs for easy cleaning of the heat exchanger. They are accessible from the front and back of these units by removing the clean out access cover in the burner compartment and at the back of unit. The furnace should be checked annually by a qualified service technician.
This noise from motor can usually be traced to where a conduit or BX cable is fixed rigidly or attached to some part of the building. Relieving this strain may eliminate noise.

CHART 4 FLF/FLR085D36E DATA
d e e p S r e w o l B c it a t S r e w o l B
d e e p S r e w o l B c it a t S r e w o l B
w o L 0 1 . 5 1 . 3 2 . 0 3 .
w o L 7 0 . 3 1 . 9 1 . 5 2 .
m u i d e M 6 1 . 4 2 . 4 3 . 3 4 .
m u i d e M 5 1 . 4 2 . 3 3 . 1 4 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .
CHART 2 FH110D48E DATA
d e e p S r e w o l B c it a t S r e w o l B
d e e p S r e w o l B c it a t S r e w o l B
w o L 3 0 . 8 0 . 3 1 . 8 1 .
w o L 5 0 . 9 0 . 5 1 . 0 2 .
w o L m u i d e M 9 0 . 6 1 . 3 2 . 2 3 .
w o L m u i d e M 9 0 . 6 1 . 3 2 . 1 3 .
h g i H m u i d e M 6 1 . 5 2 . 4 3 . 4 4 .
h g i H m u i d e M 5 1 . 4 2 . 4 3 . 2 4 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .
CHART 6 FLF/FLR110D60E DATA
d e e p S r e w o l B c it a t S r e w o l B
d e e p S r e w o l B c it a t S r e w o l B
w o L 6 0 . 2 1 . 7 1 . 1 2 .
w o L 8 0 . 2 1 . 7 1 . 1 2 .
w o L m u i d e M 0 1 . 7 1 . 3 2 . 0 3 .
w o L m u i d e M 0 1 . 6 1 . 2 2 . 8 2 .
h g i H m u i d e M 4 1 . 1 2 . 1 3 . 8 3 .
h g i H m u i d e M 3 1 . 1 2 . 9 2 . 6 3 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .

CHART 8 FC085D36E DATA
d e e p S r e w o l B c it a t S r e w o l B
d e e p S r e w o l B c it a t S r e w o l B
w o L 5 0 . 4 1 . 7 1 . 4 2 .
w o L 8 0 . 4 1 . 0 2 . 6 2 .
w o L m u i d e M 8 0 . 7 1 . 2 2 . 0 3 .
m u i d e M 6 1 . 4 2 . 6 3 . 2 4 .
h g i H m u i d e M 1 1 . 0 2 . 7 2 . 5 3 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .
h g i H 0 2 . 0 3 . 0 4 . 0 5 .


NOTES
PURPLE PURPLE
PRIMARY
CONTROL PANEL HEAT EXCHANGER AREA
IF PRIMARY LIMIT WIRES ARE TO BE REPLACED, USE WIRE WITH INSUL. TEMP. RATING OF 200°C.
BURNER ASS'Y
LIMIT
HEATING SPEED CONNECTION POINT.
COOLING SPEED CONNECTION POINT.
OIL VALVE
ONLY ONE HEATING AND COOLING SPEED CAN BE CONNECTED. ALL OTHER TAPS CONNECT TO "SPARE" TERMINALS.
BURNER MOTOR
BLACK
BLACK
IGNITOR
IGNITOR
WHITE
BLACK
BLACK
BLACK
DASHED LINES REPRESENT FIELD WIRING.
CAD CELL
DANGER !
*ELECTRICAL SHOCK HAZARD *DISCONNECT POWER BEFORE SERVICING.
HOT
WHITE GREEN
GROUND NEUTRAL
PLUG #1 PLUG #2
2 1 1 2 3 4 5 6 7 8 9
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THIS APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMP. RATING OF AT LEAST 105°C EXCEPT PRIMARY LIMIT WIRES. SEE NOTE "1".
PURPLE
BLACK BLACK
BLACK
BLACK
GREEN
DOOR SWITCH
WHITE
GREEN
Y C W Rh Y G Rc
240 210 180 150 R W G Y C
SEC1
COND.
THERMOSTAT
24V. CONN.
TRANSFORMER
HUM
HEAT
COOL
COM
SPR1
SPR2
SPR3
OPTIONAL AIR COND. SETTINGS
OPTIONAL AIR COND. SETTINGS
EAC
A/C TONS UNIT CFM @ .50 WC COOLING BLOWER
A/C TONS UNIT CFM @ .50 WC COOLING BLOWER
NOM.
NOM.
SPEED (COLOR)
SPEED (COLOR)
2 LOW (RED) 730 2 1/2 MED (BLUE) 900 3 HIGH (BLACK) 1160 2 1/2 LOW (RED) 1020 3 MED-LOW (ORANGE) 1280 3 1/2 MED-HIGH (BLUE) 1495 4 HIGH (BLACK) 1640 3 LOW (RED) 1300 3 1/2 MED-LOW (ORANGE) 1460 4 MID-HIGH (BLUE) 1660 5 HIGH (BLACK) 1970
2 LOW (RED) 730 2 1/2 MED (BLUE) 900 3 HIGH (BLACK) 1160 2 1/2 LOW (RED) 1020 3 MED-LOW (ORANGE) 1280 3 1/2 MED-HIGH (BLUE) 1495 4 HIGH (BLACK) 1640 3 LOW (RED) 1300 3 1/2 MED-LOW (ORANGE) 1460 4 MID-HIGH (BLUE) 1660 5 HIGH (BLACK) 1970
FH085D36E
BLACK
2 WHITE WHITE
SEE CHART FOR HEATING AND COOLING WIRE COLORS
FH110D48E
FH110D48E
WHITE
PLUG #3
FH110D60E
FH110D60E
1 2 3 4 5
WHITE RED ORANGE BLUE
FACTORY SETTINGS INPUT
FACTORY SETTINGS INPUT
LOW VOLTAGE
BLACK
TEMP.
TEMP.
GPH UNIT COOLING BLOWER
RATE
RATE
HEATING BLOWER
HEATING BLOWER
RISE RANGE
RISE RANGE
RETURN AREA
SPEED (COLOR)
SPEED (COLOR)
SPEED (COLOR)
SPEED (COLOR)
0.55 LOW (RED) 70°-100° 0.65 LOW (RED) 70°-100° 0.75 MED (BLUE) 60°-90° 0.85 LOW (RED) 70°-100° 1 MED-LOW (ORANGE) 60°-90° 0.85 LOW (RED) 60°-90° 1 MED-LOW (ORANGE) 60°-90°
0.55 LOW (RED) 70°-100° 0.65 LOW (RED) 70°-100° 0.75 MED (BLUE) 60°-90° 0.85 LOW (RED) 70°-100° 1 MED-LOW (ORANGE) 60°-90° 0.85 LOW (RED) 60°-90° 1 MED-LOW (ORANGE) 60°-90°
FH085D36E
HIGH VOLTAGE
BROWN
BROWN
HIGH (BLACK)
HIGH (BLACK)
FH110D48E
FH110D48E
FH110D60E
FH110D60E
FIELD WIRING
BLOWER CAPACITOR RATING
BLOWER CAPACITOR RATING
UNIT MOTOR CAPACITOR FH085D36E 1/3 5/370 FH110D48E 1/2 7.5/370 FH110D60E 3/4 15/370
UNIT MOTOR CAPACITOR FH085D36E 1/3 5/370 FH110D48E 1/2 7.5/370 FH110D60E 3/4 15/370


COLING BLWR.
COLING BLWR.
0.55 LOW (RED) 60°-90° HIGH (BLACK) 0.65 LOW (RED) 60°-90° HIGH (BLACK) 0.75 MED (BLUE) 60°-90° HIGH (BLACK) 0.85 MED. HIGH (BLUE)60°-90° HIGH (BLACK)
0.55 LOW (RED) 60°-90° HIGH (BLACK) 0.65 LOW (RED) 60°-90° HIGH (BLACK) 0.75 MED (BLUE) 60°-90° HIGH (BLACK) 0.85 MED. HIGH (BLUE)60°-90° HIGH (BLACK)
1 MED. HIGH (BLUE)60°-90° HIGH (BLACK)
1.1 MED. HIGH (BLUE)60°-90° HIGH (BLACK)
1.1 MED. HIGH (BLUE)60°-90° HIGH (BLACK)
1.25 MED. HIGH (BLUE)60°-90° HIGH (BLACK) FLR140D60E
1.25 MED. HIGH (BLUE)60°-90° HIGH (BLACK) FLR140D60E
CFM@
.50" WC UNIT NOM. A/C
CFM@
.50" WC UNIT NOM. A/C
4047-119 C
Y C W Rh Y G Rc THERMOSTAT
2 LOW (RED) 775 2.5 MED (BLUE) 1070 3 HIGH (BLACK) 1275 2.5 LOW (RED) 1065 3 MED LOW (ORANGE) 1235 3.5 MED HIGH (BLUE) 1415 4 HIGH (BLACK) 1525 3 LOW (RED) 1190 3.5 MED LOW (ORANGE) 1400 4 MED HIGH (BLUE) 1640 5 HIGH (BLACK) 2250
2 LOW (RED) 775 2.5 MED (BLUE) 1070 3 HIGH (BLACK) 1275 2.5 LOW (RED) 1065 3 MED LOW (ORANGE) 1235 3.5 MED HIGH (BLUE) 1415 4 HIGH (BLACK) 1525 3 LOW (RED) 1190 3.5 MED LOW (ORANGE) 1400 4 MED HIGH (BLUE) 1640 5 HIGH (BLACK) 2250
TEMP. RATING OF 200°C.
REPRESENT FIELD WIRING.
SPEED
IF PRIMARY LIMIT WIRES
ARE TO BE REPLACED,
USE WIRE WITH INSUL.
T87F/Q539A1220
OR EQUIVELANT
CONNECTION POINT.
CONNECTION POINT.
AND COOLING SPEED
CAN BE CONNECTED.
HEATING SPEED
COOLING SPEED
ALL OTHER TAPS
DASHED LINES
(TONS) SPEED (COLOR)
(TONS) SPEED (COLOR)
TERMINALS.
COOLING BLOWER SPEEDS
TEMP.
TEMP.
RISE
1 UNIT MOTOR CAPACITOR
UNIT GPH INPUT HTG. BLWR SPD.
UNIT GPH INPUT HTG. BLWR SPD.
FACTORY SETTINGS
*ELECTRICAL SHOCK HAZARD *DISCONNECT POWER BEFORE SERVICING.
(COLOR)
UNIT MOTOR CAPACITOR
BLOWER CAPACITOR RATING
BLOWER CAPACITOR RATING
FLF/R085D36E 1/3 5/370 FLF/R110D48E 1/2 7.5/370 FLF/R110D60E
FLF/R085D36E 1/3 5/370 FLF/R110D48E 1/2 7.5/370 FLF/R110D60E
FLR140D60E 3/4 15/370
FLR140D60E 3/4 15/370
DANGER !
FLF/R085D36E
FLF/R085D36E
FLF/R110D48E
FLF/R110D48E
FLF/R110D60E
FLF/R110D60E
FLR140D60E
FLR140D60E
FLF/R085D36E
FLF/R085D36E
FLF/R110D48E
FLF/R110D48E
FLF/R110D60E
FLF/R110D60E
COND.
24V. CONN.
HOT
GREEN
BLUE
GREEN WHITE
BLACK
BLACK
WIRING DIAGRAM
HEAT EX. AREA
FLF/R SERIES
SEC1
BLOWER CONTROL T
T
SEC2
TRANSFORMER
COM 120V
BACKUP LIMIT PRIMARY LIMIT
SPR3
SPR1 SPR2
240 210 180 150 R W G Y C
L2 COM
WHITE WHITE WHITE
PURPLE PURPLE
COOL EAC
BLACK
BLACK BLACK
"HEAT" AND "COOL"
SEE CHART FOR
WIRE COLORS.
HUM
T T 1 2
BLOWER CAPACITOR
5 4 3 2 1 BLACK
BLACK
ORANGE
WHITE
BLACK
BLUE
RED
BURNER ASS'Y
OIL VALVE
BURNER
IGNITOR
CAD CELL
BLOWER ASSEMBLY
MOTOR
BROWN
BROWN
BLACK
VALVE
BURNER
IGNITOR
CAD CELL
MOTOR
RETURN AREA


2 LOW (RED) 775 2.5 MED (BLUE) 1070 3 HIGH (BLACK) 1230
2 LOW (RED) 775 2.5 MED (BLUE) 1070 3 HIGH (BLACK) 1230
FC SERIES
240 210 180 150 R W G Y C
BLOWER ASSEMBLY (1/3 HP)
BLOWER CAPACITOR
BURNER ASS'Y
BACKUP LIMIT
OIL VALVE
BURNER
IGNITOR
CAD CELL
MOTOR
BLACK
BROWN
BROWN
VALVE
BURNER
IGNITOR
CAD CELL
MOTOR
SWITCH
DOOR
RETURN AREA
(5/370)