Vented Decorative Appliances) OWNER’S OPERATION AND INSTALLATION MANUAL
CGG3630P
Thermostat and Variably-Controlled Models
WARNING: This appliance is for instal- lation only in a solid-fuel burning ma- sonry or UL127 factory-built fireplace, or in an approved ventless firebox. It is design-certified for these installations in accordance with ANS Z21.11.2. Ex- ception: Do not install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
formed by a qualified installer, ser- vice agency, or the gas supplier.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
Save this manual for future reference.

Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning re- semble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP Gas: Propane/LP gas is odor- less. An odor-making agent is added to the gas. The odor helps you detect a gas leak. How- ever, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
2 103425

PRODUCT FEATURES
Bottom Mid Log (#2)
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by both realistic flames and glowing coals. This heater is designed for vent-free opera- tion. It has been tested and approved to ANS Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters. This heater may also be operated as a vented decorative (ANS Z21.60) product by opening the flue damper (non-thermostat operation only).
This heater has a pilot with an Oxygen Depletion Sensor Shutoff System (ODS). The ODS/pilot is a required feature for vent- free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
Figure 1 - Vent-Free Gas Log Heater
UNPACKING
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANS Z223, also known as NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269

Confined and Unconfined Space
The National Fuel Gas Code (ANS Z223.1, 1992 Section 5.3) defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfining space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in- stalled*, through openings not furnished with doors, are considered a part of the unconfined space.
The following are excerpts from National Fuel Gas Code. NFPA 54/ANS Z223.1, Sec- tion 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications: 1. Unusually Tight Construction 2. Unconfined Space 3. Confined Space
The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.
Today’s homes are built more energy efficient than ever. New materials, increased insula- tion, and new construction methods help re- duce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
This heater shall not be installed in a con- fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
The air that leaks around doors and win- dows may provide enough fresh air for com- bustion and ventilation. However, in build- ings of unusually tight construction, you must provide additional fresh air.
* Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them.
Unusually tight construction is de- fined as construction where: a. walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed and b. weather stripping has been added on openable windows and doors and c. caulking or sealants are applied to areas such as joints around window and door frames, be- tween sole plates and floors, be- tween wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com- bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad- equate fresh air for these appliances. This will insure proper venting of vented fuel- burning appliances.
If your home meets all of the three criteria above, you must provide ad- ditional fresh air. See Ventilation Air From Outdoors, page 6.
If your home does not meet all of the three criteria above, proceed to De- termining Fresh-Air Flow for Heater Location, page 5.
4 103425

Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms. 1. Determine the volume of the space (length x width x height). Length x Width x Height = cu. ft. (volume of space) Example: Space size 20ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space) If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space. 2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support) 3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater Btu/Hr Gas water heater* Btu/Hr Gas furnace Btu/Hr Vented gas heater Btu/Hr Gas fireplace logs Btu/Hr Other gas appliances* + Btu/Hr Total = Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors. 4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used) Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Continued · 5 103425

Ventilation Grills Into Adjoining Room,
Or Remove Door into Adjoining
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op- tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.
Inlet Air Ventilated Crawl Space
Figure 3 - Ventilation Air from Outdoors

NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri- mary heating system. Do not in- stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu- late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace, or listed vent-free firebox.
Minimum Wall and Ceiling Clearances (see Figure 4) A. Clearances from the side of the fireplace opening to any combustible wall should not be less than 16 inches. B. Clearances from the top of the fireplace opening to the ceiling should not be less than 42 inches.
Use only propane/LP gas. If your gas supply is not propane/LP, do not install heater. Call dealer where you bought heater for proper type heater.
16" Left and Right Sides
Figure 4 - Minimum Clearance to Wall and Ceiling
42" · Continued · 7 103425

if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7, page 9, for minimum clearances.
You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). Even
If Not Using Mantel
You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8" up (for all mod- els). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See Figure 5 for minimum clearances.
If Using Mantel · 8 103425

Underside of Mantel Shelf
2 1/2"
In addition to meeting noncombustible mate- rial clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clear- ances listed below, you will need a hood.
All minimum distances are in inches
Log Set 24"/30" Models
If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).
Top of Fireplace Opening
Minimum Non- Combustible Material Height
Distances to Underside of Mantel
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear- ances shown in Figure 7 when using hood.
Figure 6 - Minimum Mantel Clearances Without Using Hood
Underside of Mantel Shelf
2 1/2"
All minimum distances are in inches
Minimum Non- Combustible Material 8" Min.
18", 24", & 30" Models 20"
Top of Fireplace Opening
Distances to Underside of Mantel
FLOOR CLEARANCES A. If installing appliance on the floor level, you must maintain the minimum dis- tance of 14" to combustibles (see Fig- ure 8). B. If combustible materials are less than 14" from the fireplace, you must install appliance at least 5" above the combustible flooring (see Figure 9).
Figure 7 - Minimum Mantel Clearances When Using Hood
14" Min.
5" Min.
Figure 9 - Minimum Fireplace Clearances Above Combustible Flooring Figure 8 - Minimum Fireplace Clearances If Installed at Floor Level

See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.
If your heater is a manually controlled model, you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode. 1. The fireplace does not meet the clearance to combustibles requirements for vent-free operation. 2. State or local codes do not permit vent- free operation. 3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 28). This will insure vented operation (see Figure 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.
Manufactured Fireplace Masonry Fireplace
Figure 10 - Attaching Damper Clamp

Flexible Gas Hose (if allowed by local codes)
Figure 11 - Attaching Flexible Gas Hose to Heater Gas Regulator
Figure 12 - Attaching Heater to Fireplace Floor

Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
Install sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Locate sedi- ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
Figure 13 - External Regulator With Vent Pointing Down
* An CSA design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur- chase the optional CSA design-certified manual shutoff valve from your dealer. See Accessories, page 28.
CSA Design-Certified Manual Shutoff Valve With 1/8" NPT Tap*
From External Regulator (11" W.C.** to 14" W.C. Pressure)
Approved Flexible Gas Hose (if allowed by local codes)
The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom- ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.
Figure 14 - Gas Connection * Purchase the optional CSA design-certified manual shutoff valve from your dealer. See Accessories, page 28. ** Minimum inlet pressure for purpose of input adjustment.

Test Pressures Equal To or Less Than 1/2 PSIG 1. Close manual shutoff valve (see Fig- ure 15). 2. Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve. 3. Check all joints from propane/LP sup- ply tank to manual shutoff valve (see Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak. 4. Correct all leaks at once.
Pressure Testing Heater Gas Connections 1. Open manual shutoff valve (see Fig- ure 15). 2. Open propane/LP supply tank valve. 3. Make sure control knob of heater is in the OFF position. 4. Check all joints from manual shutoff valve to thermostat gas valve (thermo- stat-controlled models) or control valve (variably-controlled models) (see Fig- ure 16). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak. 5. Correct all leaks at once. 6. Light heater (see Operating Heater, pages 15 and 16 [Thermostat- Controlled Models] or pages 16 and 17 [Variable Manually- Controlled Models]). Check all other internal joints for leaks. 7. Turn off heater (see To Turn Off Gas to Appliance, page 16 [Thermostat-Con- trolled Models] or page 17 [Variable Manually-Controlled Models]).
Figure 15 - Manual Shutoff Valve
Test Pressures In Excess Of 1/2 PSIG 1. Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator. 2. Cap off open end of gas pipe where manual shutoff valve was connected. 3. Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve. 4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak. 5. Correct all leaks at once. 6. Reconnect heater and manual shutoff valve to gas supply. Check re- connected fittings for leaks.
Thermostat Gas Valve or Control Valve Location
Figure 16 - Checking Gas Joints

Each log is marked with a number. These numbers will help you identify the log when installing. It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with heater. 1. Slide rear log (#1) into place behind rear burner. Make sure flat areas at bot- tom of log are behind front burner (see Figure 17). 2 . Slide bottom mid log (#2) into place in behind front burner. Make sure tabs at bottom of log are behind rear burner (see Figure 18). 3. Place front log (#3) into place in front of bottom mid log (#2) (see Figure 19). Make sure notches on bottom rest on grate prongs. 4. Finally place top log (#4) over bottom mid log (#2) by matching the notches under log (#4) with the raised blocks of log (#2) (see Figure 20).
Figure 19 - Installing Front Log
Figure 17 - Installing Rear Log
Bottom Mid Log (#2)
Figure 20 - Installing Top Log
Figure 18 - Installing Bottom Mid Log

READ BEFORE
to the PILOT position. Press in control knob for five (5) seconds (see Figure 21). • If control knob does not pop out when released, contact a qualified service person or gas supplier for repairs. Note: You may be running this heater for the first time after hook- ing up to gas supply. If so, the con- trol knob may need to be pressed in for 30 seconds or less. This will allow air to bleed from the gas system. 6. With control knob pressed in, press and release ignitor button. This will light pilot. The pilot is attached to the front burner. If needed, keep pressing igni- tor button until pilot lights. Note: If pilot does not stay lit, con- tact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with match. To light pilot with match, see Manual Light- ing Procedure, page 16. 7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Note: If pilot goes out, repeat steps 3 through 7. This heater has a safety interlock system. Wait one (1) minute for system to reset before lighting pilot again. 8. Turn control knob counterclockwise
Note: Home owners generally prefer to operate their heater with the chimney damper closed. This will put all the heat into the room. However, there may be times you will desire the full flames of the Hi heat setting but will find the heat output excessive. You can open the chim- ney damper (if you have one) fully or partially to release some of the heat.
to desired heating level. The burners should light. Set control knob to any heat level between HI and LO.
PILOT
OFF
LO
Control Knob Ignitor Button
Figure 21 - Control Knob and Ignitor Button Location
Figure 22 - Pilot

FOR YOUR SAFETY READ BEFORE LIGHTING
TO APPLIANCE
Shutting Off Heater
Turn control knob clockwise to the OFF position.
Turn control knob clockwise to the PILOT position.
Models Only)
The thermostat control knob can be set to any comfort level between Hi and Lo. The thermostat will gradually modulate the heat output and flame height from higher to lower settings, or pilot, in order to maintain the comfort level you select. The ideal comfort setting will vary by household depending upon the amount of space to be heated, the output of the central heating system, etc.
Note: Home owners generally prefer to operate their heater with the chimney damper closed. This will put all the heat into the room. However, there may be times you will desire the full flames of the High heat setting but will find the heat output excessive. You can open the chim- ney damper (if you have one) fully or partially to release some of the heat.
PROCEDURE 1. Follow steps 1 through 5 under Light- ing Instructions, page 15. 2. Depress control knob and light pilot with match. 3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow step 8, page 15.
PILOT
OFF
LO
Control Knob Ignitor Button
Figure 23 - Control Knob and Ignitor Button Location
16 103425

INSPECTING BURNERS
OPERATION
The variable control valve can be set to any heat setting and flame height desired between high and low by simply turning the control knob until that setting is at- tained. Even the lowest setting provides realistic flames and glowing embers from two burners. Selecting higher settings pro- duces greater heat output. This results in increased heating comfort.
Check pilot flame pattern and burner flame patterns often.
4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety in- formation, page 16. If you don’t smell gas, go to the next step. 5. Press in control knob and turn counter- clockwise C-clockwise to the PILOT posi- tion. Keep control knob pressed in for five (5) seconds (see Figure 23, page 16). • If control knob does not pop out when released, contact a qualified service person or gas supplier for repairs. Note: You may be running this heater for the first time after hook- ing up to gas supply. If so, the con- trol knob may need to be pressed in for 30 seconds. This will allow air to bleed from the gas system. 6. With control knob pressed in, press and release ignitor button. This will light pilot. The pilot is attached to the front burner. If needed, keep pressing igni- tor button until pilot lights. Note: If pilot does not light, contact a qualified service person or gas sup- plier for repairs. Until repairs are made, light pilot with match. To light pilot with match, see Manual Lighting Procedure. 7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Note: If pilot goes out, repeat steps 3 through 7. 8. Push in and turn control knob coun- terclockwise C-clockwise to the HIGH position. Both burners should light. Set control knob to desired setting.
Figure 25 shows a correct pilot flame pattern. Figure 26 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touch- ing the thermocouple. This will cause the thermocouple to cool. When the thermo- couple cools, the heater will shut down.
TO APPLIANCE
Shutting Off Heater 1. Press in and turn control knob clock- wise Clockwise to the HIGH position. 2. Turn the control knob clockwise
Clockwise to the PILOT position. 3. Press in control knob and turn clock- wise Clockwise to the OFF Position.
Figure 25 - Correct Pilot Flame Pattern
Shutting Off Burners Only (pilot stays lit) 1. Turn the control knob clockwise
Clockwise to the HIGH position. 2. Press in and turn control knob clock- wise Clockwise to the pilot position.
PROCEDURE 1. Follow steps 1 through 5 under Light- ing Instructions, page 16. 2. Depress control knob and light pilot with match. 3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Now follow step 8, column 1.
Figure 26 - Incorrect Pilot Flame Pattern
Figure 24 - Pilot

CLEANING AND MAINTENANCE

Figure 27 shows correct front burner flame pattern. Figure 28 shows incorrect front burner flame pattern. The incorrect burner flame pattern shows yellow tipping at top of blue flame.
Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 30). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.


The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. Keep these holes clear of dust, dirt, and lint. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We rec- ommend that you clean the unit every 2,500 hours of operation or every three months.
We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recom- mend using compressed air no greater than 30 PSI. Your local computer store, hard- ware store, or home center may carry com- pressed air in a can. You can use a vacuum cleaner in the blow position. If using com- pressed air in a can, please follow the direc- tions on the can. If you don't follow direc- tions on the can, you could damage the pilot assembly. 1. Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes. 2. Inspect burner, pilot, and primary air inlet holes on injector holder for dust and dirt (see Figure 29). 3. Blow air through the ports/slots and holes in the burner.
Figure 29 - Injector Holder On Outlet Burner Tube
Figure 27 - Correct Front Burner Flame Pattern Yellow Tipping At Top of Blue Flame
Figure 28 - Incorrect Front Burner Flame Pattern
Injector Holder · 18 103425

TROUBLESHOOTING WARNING: Turn off and un- plug heater and let cool before servicing. Only a qualified ser- vice person should service and repair heater.
POSSIBLE CAUSE
REMEDY
When ignitor button is pressed, there is no spark at ODS/pilot
When ignitor button is pressed, there is spark at ODS/pilot but no ignition
ODS/pilot lights but flame goes out when control knob is released
B) Clean ODS/pilot (see Cleaning and Maintenance, page 18) or replace ODS/ pilot assembly
www.desatech.com Continued
19 103425

POSSIBLE CAUSE
REMEDY
One or both burners do not light after ODS/ pilot is lit
Delayed ignition of one or both burners
Burner backfiring during combustion
Yellow flame in front burner during burner combustion
Slight smoke or odor during initial operation
Moisture/condensation noticed on windows
Heater produces a whistling noise when burners are lit
White powder residue forming within burner box or on adjacent walls or furniture
20 103425

POSSIBLE CAUSE
REMEDY
Heater produces a clicking/ticking noise just after burners are lit or shut off
Heater produces unwanted odors
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
Gas odor during combustion
Log set cycles to pilot, but room tempera- ture drops to a lower than ideal level before log set comes back on
21 103425

4. The mounting clip must be a minimum of 3" from bottom of fireplace to pre- vent crimping of capillary. Once you have decided on a location, clean the area thoroughly. Remove the paper backing from the adhesive on back of mounting clip. Press the clip into the new location so that the thermostat sensing bulb will be positioned vertically with the capillary at the bot- tom (see Figure 37). Slide the thermo- stat sensing bulb into the clip. IMPORTANT: Do not crimp capillary.
Figure 34 - Locating Thermostat Sensing Bulb on Masonry Fireplace
If your log set cycles to pilot, but the room temperature drops to a lower than ideal comfort level before the log set comes back on, you may want to reposition the thermostat sensing bulb.
The thermostat sensing bulb is located on the gas valve assembly. This location al- lows the thermostat to keep the room tem- perature at an ideal comfort level for most fireplace applications. For positioning the thermostat sensing bulb elsewhere, an adhe- sive-backed mounting clip is available.
Q
Figure 35 - Locating Thermostat Sensing Bulb on Factory-built Metal Fireplace
Q
1. Locate the gas valve assembly and ther- mostat sensing bulb (see Figure 31). 2. With 5/16" hex driver or socket, loosen the thermostat screw. Carefully slide the thermostat sensing bulb out of the retaining clamp (see Figure 33). Note: Do not remove the screw. Make sure you tighten the screw after remov- ing the thermostat sensing bulb. IMPORTANT: Do not force or bend the thermostat sensing bulb or capillary. A crimped capillary will not allow ther- mostat to operate properly. It cannot be repaired, the valve must be replaced. 3. The thermostat sensing bulb may be located to the lower right front side of fireplace. Determine location of sens- ing bulb, but do not mount sensing bulb until step 5. If you have a masonry fire- place, see Figure 34 for location. If you have a factory-built metal fire- place, see Figure 35 for location. If your fireplace has glass doors, posi- tion sensing bulb directly behind door gap on right bottom side (see Figure 36).
Q
Figure 31 - Location of Gas Valve Assembly and Thermostat Sensing Bulb
Q
Adhesive- backed Mounting Clip Glass Doors
Q ¢
Q
Figure 32 - Adhesive-backed Mounting Clip
Figure 36 - Installing Thermostat Sensing Bulb behind Glass Doors
Thermostat Sensing Bulb Screw
Do Not Crimp Capillary
Figure 33 - Removing Thermostat Sensing Bulb
Figure 37 - Positioning the Thermostat Sensing Bulb in the Vertical Position with the Capillary at the Bottom

Model CGG3324PT CGG2618P CGG3324P CGG3630P
Btu (Variable) 20,000/33,000 16,000/26,000 20,000/33,000 21,500/36,000
Type Gas Propane/LP Only Propane/LP Only Propane/LP Only Propane/LP Only
Ignition Piezo
Manifold Pressure 7.9" W.C. 7.9" W.C. 7.9" W.C. 7.9" W.C.
Inlet Gas Pressure (in. of water)
Maximum 14" Minimum* 11"
Shipping Weight 38 lbs. 36 lbs. 38 lbs. 40 lbs.
* For purpose of input adjustment
REPLACEMENT PARTS
Contact authorized dealers of this product. If they can’t supply original replacement part(s), call DESA International’s Techni- cal Service Department at 1-800-323-5190.
You may feel your gas pressure is too low or gas quality is bad. If so, contact your local propane/LP gas supplier.
You may have further questions about in- stallation, operation, or troubleshooting.
Usually, we will ask you to return the defec- tive part to the factory.
If so, contact DESA International’s Techni- cal Service Department at 1-800-DESA LOG (1-800-337-2564).
You can also visit DESA International’s Technical Service web site at www.desatech.com
Contact authorized dealers of this product. If they can’t supply original replacement part(s), either contact your nearest Parts Central (see page 28) or call DESA International’s Parts Department at 1-800-972-7879 for referral information.
23 103425


CGG2618P CGG3324P CGG3630P
24 103425

This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 23 of this manual.
CGG2618P CGG3324P CGG3630P
KEY PART NUMBER FOR NO. CGG2618P CGG3324P CGG3630P DESCRIPTION QTY.
1 103681-04 103682-04 103683-04 Rear Log (#1) 1 2 103681-02 103682-02 103683-02 Bottom Mid Log (#2) 1 3 103681-01 103682-01 103683-01 Front Log (#3) 1 4 103681-03 103682-03 103683-03 Top Log (#4) 1 5 098249-01 098249-01 098249-01 Nut 4 6 101006-01 101006-01 101006-01 Pilot Bracket 1 7 101330-01 101330-05 101330-06 Front Burner Assembly 1 7-1 101008-01 101008-01 101008-01 Crossover Burner Gasket 1 7-2 101007-01 101007-01 101007-01 Crossover Burner 1 8 100999-01 100999-02 100999-03 Rear Burner Assembly 1 9 101331-10 101331-08 101331-09 Base Assembly (Includes Decals) 1 10 098271-07 098271-06 098271-06 Ignitor Cable 1 11 102445-01 102445-01 102445-01 Piezo Ignitor 1 12 098867-10 098867-10 098867-10 Gas Regulator 1 13 M11084-38 M11084-38 M11084-38 Screw 2 14 101011-01 101011-02 101011-03 Inlet Tube 1 15 098354-01 098354-01 098354-01 Control Knob 1 16 098462-03 098462-03 098462-03 Control Rod 1 17 098325-01 098325-01 098325-01 Roll Pin 1 18 098508-01 098508-01 098508-01 Valve Retainer Nut 1 19 102568-02 102568-02 102568-02 Gas Valve 1 20 101005-01 101005-01 101005-01 Valve Bracket 1 21 M11084-26 M11084-26 M11084-26 Screw 4 22 101004-10 101004-01 101004-02 Rear Burner Injector 1 23 101004-10 101004-02 101004-06 Front Burner Injector 24 102258-01 102258-01 102258-01 Burner Tube 1 25 099387-08 099387-08 099387-08 Pilot Tube 1 26 098276-01 098276-01 098276-01 1/8” Plug 1 27 099059-02 099059-02 099059-02 O.D.S. Pilot 1 27-1 098594-01 098594-01 098594-01 Ignitor Electrode 1 27-2 098593-01 098593-01 098593-01 Thermocouple 1
100563-01 100563-01 100563-01 Warning Plate 1 101054-01 101054-01 101054-01 Lighting Instructions Plate 1 100565-01 100565-01 100565-01 Warning Plate Fastener 1 100639-01 100639-01 100639-01 Caution Decal 1 101137-03 101137-03 101137-03 Hardware Kit 1 101416-28 101416-28 101416-28 Information Video 1 GA6060 GA6060 GA6060 Lava Rock 1
25 103425


26 103425

This list contains replaceable parts used in your heater. When ordering parts, follow the instructions listed under Replacement Parts on page 23 of this manual.
KEY PART NO. NUMBER DESCRIPTION QTY.
1 103682-04 Rear Log (#1) 1 2 103682-02 Bottom Mid Log (#2) 1 3 103682-01 Front Log (#3) 1 4 103682-03 Top Log (#4) 1 5 102764-01 Heat Shield 1 6 M11084-26 Screw 5 7 099059-02 O.D.S. Pilot 1 7-1 098594-01 Ignitor 1 7-2 098593-01 Thermocouple 1 8 098249-01 Nut 4 9 101006-01 Pilot Bracket 1 10 101330-05 Front Burner Assembly 1 10-1 101008-01 Gasket, Crossover Burner 1 10-2 101007-01 Crossover Burner 1 11 100999-02 Rear Burner Assembly 1 12 101331-08 Base Assembly (with decals) 1 13 098271-06 Ignitor Cable 1 14 102445-01 Piezo Ignitor 1 15 098867-10 Gas Regulator 1 16 M11084-38 Screw 2 17 102810-02 Inlet Tube 1 18 098354-01 Control Knob 1 19 102013-01 Control Rod 1 20 100000-01 Cotter Pin 1 21 101053-01 Adapter 1 22 099211-01 Screw 1 23 098544-01 Thermostat Clamp 1 24 101329-18 Thermostat Gas Valve Assy. 1 25 100994-01 Thermovalve Bracket 1 26 101004-01 Rear Burner Injector 1 27 101004-02 Front Burner Injector 1 28 102811-01 Thermostat Burner Tube 1 29 099387-09 Pilot Tube 1 30 102255-01 Strap
100563-01 Warning Plate 1 101054-01 Lighting Instructions Plate 1 100565-01 Warning Plate Fastener 1 100639-01 Caution Decal 1 101137-03 Hardware Kit 1 101416-28 Information Video 1 GA6060 Lava Rock 1
27 103425

East Coast Energy Products 707 Broadway W. Long Branch, NJ 07764 908-870-8809 1-800-755-8809 Parts Department
These Parts Centrals are privately owned busi- nesses. They have agreed to support our customer’s needs by providing original replace- ment parts and accessories. When calling a Parts Central, ask for the Parts Department.
Purchase these heater accessories from your local dealer. If they can not supply these accessories, call DESA International’s Parts Department at 1-800-972-7879 for infor- mation. You can also write to the address listed on the back page of this manual.
Baltimore Electric 1348 Dixwell Avenue Hamden, CT 06514 1-800-397-7553 203-248-7553 Parts Department
Tarantin Tank Co. P.O. Box 6129 Freehold, NJ 07728 908-780-9340 1-800-922-0724 Parts Department
Albany Ladder 1586-90 Central Avenue Albany, NY 07728 NY, MA, VT 1-800-354-7368 518-869-5335 Parts Department
Portable Heater Parts 342 N. County Rd. 400 East Valparaiso, IN 46383 All States 219-462-7441 1-800-362-6951 Parts Department
For all models. Manual shutoff valve with 1/8" NPT tap. Fits 1/2" NPT pipe.
F B D P. O. Box 1096 1720 Kummer Road Franklin, KY 42134 502-586-1922 1-800-654-8534
Dayton Hardware P.O. Box 275 North Dayton Station Dayton, OH 45404 All States 513-258-3721 OH 1-800-762-3426 Parts Department
Four Flags Power Products 1115 Stateline Road Niles, MI 49120 616-684-2697 Parts Only
Halco Enterprises 208 Carter Drive, Unit 21 West Chester, PA 19382 610-430-7717 US 1-800-368-0803 Parts Department
For all models. Helps deflect heat away from mantel or wall above fireplace.
Master Parts Distributors 1184 Wilson Ave. NW Walker, MI 49504 616-791-0505 US 1-800-446-1446 Fax: 616-791-8270 Parts Department
For variably controlled models. Permanently opens chimney flue damper for vented op- eration. Can be used only with non-thermo- stat accessories.
LA Porte's Parts & Service 2444 North 5th Street Hartsville, SC 29550 803-332-0191 Parts Department
Washer Equipment Co. 1715 Main Street Kansas City, MO 64108 KS, MO, AR 816-842-3911 Parts Department
For all models. Order when additional rock is desired. (3 lb. bag)
Cans Unlimited, Inc. P.O. Box 645 Taylor, SC 29687 All States 803-879-3009 1-800-845-5301 Parts Department
28 103425


Serial No.
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
DESA International warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURA- TION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2) YEARS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUEN- TIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com
103425-01 Rev. D 11/01