323356B-01 May 2003 © 2002–2003 Nationa l Instruments Corp. A ll rights res erved. FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of N ational Instruments Corpo ration. Product and company names ment ioned herein are trademark s or trade names of their respective c ompanies.
FP-PG-522 and cFP-PG-522 2 ni.com Installing the FP-PG-522 The FP-PG-522 mounts on a FieldPoint terminal base (FP-TB- x ), which provides operating po wer to the module. Instal ling the FP-PG-522 onto a po wered termin al base does not disrupt the operation of the bank.
© National Instruments Corp . 3 FP-PG-522 and cFP-PG-522 T o install the cFP-PG-522, refe r to Figure 2 and complete the follow ing steps: 1. Align the capti ve scre ws on th e cFP-PG-522 with the holes on the backplane. The alignment keys on the cFP-PG-522 pre vent backward insertion.
FP-PG-522 and cFP-PG-522 4 ni.com Wiring the [c]FP-PG-522 The FP-TB- x terminal base ha s connections for each of the eight output channels and for an exte rnal power supply to po wer the output channels and field de vices. The cFP-CB- x connector block provides th e same connections.
© National Instruments Corp . 5 FP-PG-522 and cFP-PG-522 T able 1 lists the term inal assign ments for the signals of each channel. T erminal assignments are also listed on the side pane l of the cFP-PG-522 and un der the slide-in card on the front of the FP-PG-522.
FP-PG-522 and cFP-PG-522 6 ni.com T able 2 sho ws some common combinations of output current le v els on sev eral channels. In the ON state, the ef fe cti ve resist ance between V OUT and COM is 0.12 Ω , which causes a v oltage drop. F or example, if the output current is 1 A, the voltage drop is 0.
© National Instruments Corp . 7 FP-PG-522 and cFP-PG-522 A channel set to Continuo us mode must be swit ched to Finite mode in order to stop pulse generation. When switched to Fi nite mode from Continuous mode, a channel finishes generating the current pulse and then stops.
FP-PG-522 and cFP-PG-522 8 ni.com T o calcula te On Time and Off T ime , di vide the desired On or Of f T ime for the pulse b y the Resoluti on. F or examp le, to generate a pulse that is on for 3.5 s and off for 0.25 s using a 100 µ s Resolution, set the On T ime to 35,000 and the Off Time to 2,500 (100 µ s = 0.
© National Instruments Corp . 9 FP-PG-522 and cFP-PG-522 va lues, which reflect the number of pulses each channel has left to generate after the current puls e. When you send the Generate Pulses command to one of these channels, the data immediately changes to reflect the number of pulses that remain.
FP-PG-522 and cFP-PG-522 10 ni.com When the network module recogni zes the [c]FP-PG-52 2, it sends initial conf iguration informat ion to the [c]FP-PG-522. After the [c]FP-PG-522 recei ves this in itial information , the green READY indicator lights and the [c]FP-PG-5 22 is in normal operating mode.
© National Instruments Corp. 1 1 FP-PG-522 and cFP-PG-522 follow ing symbol stamped beside it: . Connect the backplane PE ground terminal to the system safety ground using 14 A WG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal.
FP-PG-522 and cFP-PG-522 12 ni.com Physical Char acteristics Indicators ............ ........... ......... .......... Green POWER and READY indicators, eight green output st ate indicators W eight FP-PG-522 .... ........... ........... ........ 130 g (4.
© National Instruments Corp. 1 3 FP-PG-522 and cFP-PG-522 Operating shock (IEC 60068-2-27)........... ........... ........ 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18.
FP-PG-522 and cFP-PG-522 14 ni.com Mechanical Dimensions Figure 5 sho ws the mechanical dimen sions of the FP-PG-522 installed on a termin al base. If you are using the cFP-PG-522, refer to your Compact FieldPo int controller user manual for the dimensions and cabling clearance require ments of the Compact FieldPoint system.
© National Instruments Corp. 1 5 FP-PG-522 and cFP-PG-522 Czech Republic 420 2 2423 5774, Denmark 45 45 76 26 00, Finland 385 0 9 725 725 11, France 33 0 1 48 14 24 24, Germany 49 0 89 741 31 30, Gre.
An important point after buying a device National Instruments cFP-PG-522 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought National Instruments cFP-PG-522 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data National Instruments cFP-PG-522 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, National Instruments cFP-PG-522 you will learn all the available features of the product, as well as information on its operation. The information that you get National Instruments cFP-PG-522 will certainly help you make a decision on the purchase.
If you already are a holder of National Instruments cFP-PG-522, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime National Instruments cFP-PG-522.
However, one of the most important roles played by the user manual is to help in solving problems with National Instruments cFP-PG-522. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device National Instruments cFP-PG-522 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center