Fire is a permanent threat to life and property. There- fore, immediate response to a fi re is imperative. The main objective of the Fire Detection Control Panel Series BC06 is to alarm and to react in time and, con- sequently, save lives and protect property. For decades LST have focused their aims to undertaking unrivaled efforts in order to realise new innovations in the security area. Research, development and production are loca-
ted within LST premises, thus guaranteeing fl exible and reliable individual solutions.
Using a powerful processor system and a large num- ber of integrated functions, the Fire Detection Control Panels Series BC06 ensure topmost effi ciency and speed – prerequisites for saving lives and minimising damage to property.

Already in the basic version the Fire Detection Control Panels BC06-1 and BC06-2 are equipped with four de- tector lines and, owing to its sophisticated factory set- tings, are immediately ready for operation. This allows for quick and effi cient application of the product.
The optional evacuation function serves for the actu- ation of alarming devices independent from activated alarms. Depending on the parameterisation, different country-specifi c regulations (e.g., NEN 2575) can be fulfi lled.
The conventional technology allows for the connection of automatic and non-automatic fi re detectors as well as a wide range of special detectors with contact output. Alarms from manual call points and from automatic de- tectors that are connected together to one detector line can be differentiated and thus evaluated differently by the fi re detection control panel, by means of an optional coding module. Thanks to the two auxiliary inputs whose parameters can be freely set as well as the eight open-collector outputs with predefi ned function, manifold tasks in the fi eld of fi re alarm technology can be realised.
The Fire Detection Control Panels BC06-1 and BC06-2 provide a slot for the installation of the optional Zone Extension Board ZEB2-1. With this expansion module the control panel can be upgraded from four to six de- tector zones. A printer for the event log can be connected via the optional Serial Interface Module SIM06-1.
The Fire Detection Control Panel BC06-2 differs from the BC06-1 by the additionally integrated 4-digit electro- nic alarm counter.
BC06_DBL_LST_EN_0826.PDF • PAGE 1 A Building Safety. Building Security.


The Fire Detection Control Panels BC06-1 and BC06-2 have been designed for use in small fi re detection sys- tems and already in the basic version they provide the following features:
The extremely fl at wall-mount cabinet allows for an easy mounting in virtually any place of the building. Thanks to its modern, ageless design, architectural requirements and demands of the respective regulations are ideally combined. Thanks to the compact design, the standard case can accommodate batteries with up to 7Ah also in the event of full extension (central processing board, optional zone extension board and an auxiliary module) of the control panel. Series BC06 thus stands for modu- larity and easy expansion.
This product complies with all relevant standards of EN 54 and is tested by the VdS. LST‘s high quality level is secured by a permanently monitored quality manage- ment system certifi ed to ISO 9001.
BC06_DBL_LST_EN_0826.PDF • PAGE 2 A Building Safety. Building Security.

A variety of peripheral devices can be connected to the
Fire Detection Control Panel Series BC06:




BC06_DBL_LST_EN_0826.PDF • PAGE 3 A Building Safety. Building Security.

Mains voltage 230VAC +10/-20%, 47...63Hz
Output/nominal voltage typ. 27.6VDC
Output current max. 2.2A
Output current siren outputs output 1 max. 1A output 2 max. 0.5A (the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Own current consumption at 24V typ. 70mA (without optional componentries, line termination 5.6kΩ) typ. 55mA (without optional componentries, line termination 47µF)
Line voltage typ. 20V (line termination 5.6kΩ) typ. 23V (line termination 47µF)
Line current without fi re detectors typ. 3.7mA (line termination 5.6kΩ) typ. 0mA (line termination 47µF)
Line termination 5.6kΩ or 47µF
Line resistance max. 50Ω per core
Ambient temperature -5°C to +50°C
Relative humidity max. 95% (no condensation)
Dimensions W × H × D 330 × 330 × 90 (mm)
Colour grey-white, RAL 9002
Weight without batteries approx. 3kg
Approval tested according to EN 54-2, EN54-4 VdS approval pending
Fire Detection Control Panel BC06-1
Order name Fire Detection Control Panel BC06-1/INT1
Fire Detection Control Panel BC06-2
Order name Fire Detection Control Panel BC06-2/INT1
BC06_DBL_LST_EN_0826.PDF • PAGE 4 A Building Safety. Building Security.
Order number 210205 · Order number 210209
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.