EN
Official user manual

LST Battery Charger (BC06-1)

4 pages·268 KB·Battery Charger·PDF·ENDEFRITNLJA
LST Battery Charger (BC06-1)
Table of Contents 7 sections Fire Detection Control Panel · BC06-1, BC06-2 · Description · Clear Concept · … ShowHide
Page 1 of the LST Battery Charger (BC06-1) user manual — Description
Page 1 · click to enlarge
Page 1
LST Battery Charger (BC06-1) — Fire Detection Control Panel diagram (page 1)
Fig. 1 · Fire Detection Control Panel

Fire Detection Control Panel

LST Battery Charger (BC06-1) — Fire Detection Control Panel diagram (page 1)
Fig. 2 · Fire Detection Control Panel
LST Battery Charger (BC06-1) — Fire Detection Control Panel diagram (page 1)
Fig. 3 · Fire Detection Control Panel
LST Battery Charger (BC06-1) — Fire Detection Control Panel diagram (page 1)
Fig. 4 · Fire Detection Control Panel

BC06-1, BC06-2

LST Battery Charger (BC06-1) — BC06-1, BC06-2 diagram (page 1)
Fig. 5
  • For application in small systems
  • Up to 6 detector zones in conventional technology
  • Differentiation between the activation of automatic detectors and manual call points on the same detector line
  • Evacuation function (NEN 2575)
  • Tested to EN 54-2, -4 by VdS

Fire is a permanent threat to life and property. There- fore, immediate response to a fi re is imperative. The main objective of the Fire Detection Control Panel Series BC06 is to alarm and to react in time and, con- sequently, save lives and protect property. For decades LST have focused their aims to undertaking unrivaled efforts in order to realise new innovations in the security area. Research, development and production are loca-

ted within LST premises, thus guaranteeing fl exible and reliable individual solutions.

Using a powerful processor system and a large num- ber of integrated functions, the Fire Detection Control Panels Series BC06 ensure topmost effi ciency and speed – prerequisites for saving lives and minimising damage to property.

LST Battery Charger (BC06-1) — BC06-1, BC06-2 diagram (page 1)
Fig. 6

Description

Already in the basic version the Fire Detection Control Panels BC06-1 and BC06-2 are equipped with four de- tector lines and, owing to its sophisticated factory set- tings, are immediately ready for operation. This allows for quick and effi cient application of the product.

The optional evacuation function serves for the actu- ation of alarming devices independent from activated alarms. Depending on the parameterisation, different country-specifi c regulations (e.g., NEN 2575) can be fulfi lled.

The conventional technology allows for the connection of automatic and non-automatic fi re detectors as well as a wide range of special detectors with contact output. Alarms from manual call points and from automatic de- tectors that are connected together to one detector line can be differentiated and thus evaluated differently by the fi re detection control panel, by means of an optional coding module. Thanks to the two auxiliary inputs whose parameters can be freely set as well as the eight open-collector outputs with predefi ned function, manifold tasks in the fi eld of fi re alarm technology can be realised.

The Fire Detection Control Panels BC06-1 and BC06-2 provide a slot for the installation of the optional Zone Extension Board ZEB2-1. With this expansion module the control panel can be upgraded from four to six de- tector zones. A printer for the event log can be connected via the optional Serial Interface Module SIM06-1.

The Fire Detection Control Panel BC06-2 differs from the BC06-1 by the additionally integrated 4-digit electro- nic alarm counter.

BC06_DBL_LST_EN_0826.PDF • PAGE 1 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED
Page 2 of the LST Battery Charger (BC06-1) user manual — Clear Concept
Page 2 · click to enlarge
Page 2
LST Battery Charger (BC06-1) — Clear Concept diagram (page 2)
Fig. 7 · Clear Concept

Clear Concept

The Fire Detection Control Panels BC06-1 and BC06-2 have been designed for use in small fi re detection sys- tems and already in the basic version they provide the following features:

  • The Fire Detection Control Panel BC06-2 includes a 4-digit, non-resettable alarm counter which indicates the total number of alarms by means of an LC display in the operating fi eld.
  • A possible breakdown of the central processing board is securely detected and displayed by the system.
  • The processor-monitored power supply ensures permanent supervision and charging of the batteries. This way, even during a power failure the untroubled and uninterrupted operation (for more than 72 hours depending on the design of the batteries) is guaranteed.
  • Three hierarchised authorization levels for operation and parameterisation provide a high degree of security against unauthorized access.
  • The control panel is easily operated and the parameters are set via the display and operating fi eld. LEDs indicate the current menu and the selected parameter. This facilitates user guidance during commissioning, operation and maintenance.
  • The initial commissioning of the control panel is signifi cantly facilitated by the practical factory settings. This guarantees easy and time-saving commissioning.
  • 4 conventional detector lines permit the connection of automatic detectors and manual call points in conventional technology as well as special detectors with contact output. Each detector line can be individually parameterised as detector zone for fi re alarms or as detector zone for fault messages.
  • If automatic detectors and manual call points are connected together on one detector line, their activations can be differentiated and evaluated differently by the control panel. To this aim, the manual call points must be equipped with a special coding module.
  • A slot for connecting the Zone Extension Board ZEB2-1 is available to facilitate the extension to 6 conventional detector lines. The installation of the zone extension board is auto-
  • matically detected by the control panel and the corresponding parameters are set to initial values.
  • Two individually monitored, separately activated siren outputs with an output current of 1A and 0.5A respectively, allow for the connection of acoustic or optical signalling devices. When parameterised accordingly, the siren outputs can also be operated as evacuation circuits.
  • Dry relay outputs indicate the alarm and fault conditions of the control panel. In addition, 8 open-collector outputs with fi xed preset functions as well as two auxiliary inputs whose parameters can be freely set are available for general control tasks.
  • Logical combinations of detector zones for the activation of external alarming devices allow for a high degree of fl exibility. Thus, no additional expenses arise for external relays or logic gates. Thanks to the wide range of parameterisation possibilities, individual requirements even under the most diffi cult ambient conditions can be combined into a reasonable fi re protection strategy.
  • All events that occur can be output in English via a connected printer or PC. Thus, all system conditions and user operations that occurred are documented in a clearly laid out way.

The extremely fl at wall-mount cabinet allows for an easy mounting in virtually any place of the building. Thanks to its modern, ageless design, architectural requirements and demands of the respective regulations are ideally combined. Thanks to the compact design, the standard case can accommodate batteries with up to 7Ah also in the event of full extension (central processing board, optional zone extension board and an auxiliary module) of the control panel. Series BC06 thus stands for modu- larity and easy expansion.

This product complies with all relevant standards of EN 54 and is tested by the VdS. LST‘s high quality level is secured by a permanently monitored quality manage- ment system certifi ed to ISO 9001.

BC06_DBL_LST_EN_0826.PDF • PAGE 2 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED
Page 3 of the LST Battery Charger (BC06-1) user manual — Evacuation functions
Page 3 · click to enlarge
Page 3

Permanent Connection

A variety of peripheral devices can be connected to the

Fire Detection Control Panel Series BC06:

  • Acoustic and optical signalling devices
  • Fire controls
  • External protocol printer
  • Transmitting devices for alarm transmission – and much more.
LST Battery Charger (BC06-1) — Permanent Connection diagram (page 3)
Fig. 8 · Permanent Connection
LST Battery Charger (BC06-1) — Permanent Connection diagram (page 3)
Fig. 9 · Permanent Connection

Evacuation functions

  • In order to comply with different country-specifi c requirements, the control panel can be equipped with an evacuation function for the manual activation of the alarming devices also without fi re alarm (evacuation alarm). This function is determined by the installer during parameterisation. Two modes of operation are available therefor:
  • With the „Evacuate function“ the undelayed activation of the desired alarming device occurs by pressing the corresponding „Alarming“ button and is indicated by a red LED. Pressing the button once again will silence the alarming device again, regardless of as to whether the evacuation alarm has been triggered by a fi re alarm or manually.
  • For the „Evacuation circuit / NEN 2575“, additional operating buttons for the operation of the evacuation circuit are enabled during commissioning. An optional front foil is used for the labelling of these buttons. This function always acts on both alarming devices. In order to activate the alarming devices, the „Enable“ button must be pressed in addition to the „Activate EV circuit“ button. The alarming devices are silenced again by pressing the „Silence EV circuit“ button. The condition of the alarming devices is indicated via LEDs.
LST Battery Charger (BC06-1) — Evacuation functions diagram (page 3)
Fig. 10 · Evacuation functions
LST Battery Charger (BC06-1) — Evacuation functions diagram (page 3)
Fig. 11 · Evacuation functions

BC06_DBL_LST_EN_0826.PDF • PAGE 3 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED
Page 4 of the LST Battery Charger (BC06-1) user manual — Specifi cations
Page 4 · click to enlarge
Page 4

Specifi cations

Mains voltage 230VAC +10/-20%, 47...63Hz

Output/nominal voltage typ. 27.6VDC

Output current max. 2.2A

Output current siren outputs output 1 max. 1A output 2 max. 0.5A (the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)

Own current consumption at 24V typ. 70mA (without optional componentries, line termination 5.6kΩ) typ. 55mA (without optional componentries, line termination 47µF)

Line voltage typ. 20V (line termination 5.6kΩ) typ. 23V (line termination 47µF)

Line current without fi re detectors typ. 3.7mA (line termination 5.6kΩ) typ. 0mA (line termination 47µF)

Line termination 5.6kΩ or 47µF

Line resistance max. 50Ω per core

Ambient temperature -5°C to +50°C

Relative humidity max. 95% (no condensation)

Dimensions W × H × D 330 × 330 × 90 (mm)

Colour grey-white, RAL 9002

Weight without batteries approx. 3kg

Approval tested according to EN 54-2, EN54-4 VdS approval pending

Fire Detection Control Panel BC06-1

Order name Fire Detection Control Panel BC06-1/INT1

Fire Detection Control Panel BC06-2

Order name Fire Detection Control Panel BC06-2/INT1

BC06_DBL_LST_EN_0826.PDF • PAGE 4 A Building Safety. Building Security.

  • © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH
  • A-1231 WIEN
  • WIEGELESTRASSE 36
  • TEL +43 1 52114-0
  • FAX +43 1 52114-27 [email protected]
  • <a href="http://WWW.LST.AT" rel="nofollow noopener" target="_blank">WWW.LST.AT</a>
  • ALL RIGHTS RESERVED

Order number 210205 · Order number 210209

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the LST Battery Charger (BC06-1)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the LST Battery Charger (BC06-1)

Be the first to ask — other owners or our team will answer.

Original document

LST Battery Charger (BC06-1) manual PDF

4 pages·268 KB·Battery Charger·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…