GXT3 Configuration Program

User Manual

Version V1.0 Revision date September 24, 2009 BOM 31012253

Liebert provides customers with technical support. Users may contact the nearest Liebert local sales office or service center.

Copyright © 2009 by Liebert

All rights reserved. The contents in this document are subject to change without notice.

Homepage: www.liebert.com

Monitoring

Email: [email protected]

Tel: 800-222-5877, +800 1155 4499 (Outside North America)

Single-Phase & Three-Phase UPS

Email: [email protected]

Tel: 800-222-5877, +800 1155 4499(Outside North America)

Locations

United States : 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

EuropeVia Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy

Tel: +39 049 9719 111, Fax: +39 049 5841 257

Asia: 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center Pasig City 1605 Philippines

Tel: +63 2 687 6615, Fax: +63 2 730 9572

Page 2 of the Liebert GXT3 user manual — GXT3 Configuration Program
Page 2 · click to enlarge
Page 2
Page 2 of the Liebert GXT3 user manual — GXT3 Configuration Program
Page 3 of the Liebert GXT3 user manual — GXT3 Configuration Program
Page 3 · click to enlarge
Page 3
Page 3 of the Liebert GXT3 user manual — GXT3 Configuration Program
Page 4 of the Liebert GXT3 user manual — GXT3 Configuration Program
Page 4 · click to enlarge
Page 4
Page 4 of the Liebert GXT3 user manual — GXT3 Configuration Program
Page 5 of the Liebert GXT3 user manual — 1.2 Requirements
Page 5 · click to enlarge
Page 5

Chapter 1 Introduction 1

Chapter 1 Introduction

Welcome to the GXT3 configuration program (program for short). This program is used to modify the settings of the UPS. This program is compatible with UPS models beginning with “GXT3” or “S4K2U”, as in “GXT3-3000RT120” or

“S4K2U1000C”.

This chapter details the features and requirements of this program.

1.1 Features

This program has the following features:

Disable the Line-Neutral-Reversed/Missing-Ground receptacle wiring alarm (120Vac models only)

Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz

Enable or disable the audible alarm

Set the Low Battery Warning alarm time from 2 to 30 minutes

Enable or disable the Auto-Battery test

Enable or disable the Auto Restart function

Set the Auto-Battery test interval to 7, 14, 21, or 28 days

Select the number of external battery cabinets connected to the UPS to provide additional runtime

Modifying the shutdown setting of pin 1 & 2 (Any Mode Shutdown)

1.2 Requirements

This program requires the following elements:

A UPS with its model beginning with “GXT3” or “S4K2U”, as in “GXT3-3000RT120” or “S4K2U1000C”

A configuration program CD (or installation file)

A USB cable included in the UPS accessory package

A host computer with the Windows 2000® -or-later based operating system

Select output voltage · Disable Auto-Restart

Page 6 of the Liebert GXT3 user manual — 2.3 Communicating With The UPS
Page 6 · click to enlarge
Page 6

2 Chapter 2 Communication

Chapter 2 Communication

This chapter details how to establish communication link with the UPS, including connecting the USB cable, starting the program and communicating with the UPS.

2.1 Connecting The USB Cable

A USB cable is included in the UPS accessory package.

To connect the USB cable:

1. Connect one end of the USB cable to the USB port on the UPS.
2. Connect the other end of the USB cable to the USB port on the host computer.

If an optional communication card has been installed in the UPS Intelislot port, the card must be removed while using the program.

2.2 Starting The Program

To start the program:

1. Place the configuration program CD into the CD driver of the host computer.
2. Click the „Emerson UPS GXT3 Tool.exe‟ file in the CD driver to start the program.

2.3 Communicating With The UPS

After starting this program, if a qualified UPS is found, the program window will display the UPS model; if the configuration program fails to read data from a qualified UPS, an error message will be displayed, as shown in Figure

Liebert GXT3 — 2.3 Communicating With The UPS diagram (page 6)
Fig. 1 · 2.3 Communicating With The UPS

Figure 2-1 Communication error

In this case, check the following items:

1. Verify that the USB cable is connected securely between the computer and the UPS..
2. Verify that the UPS is powered.
3. Temporarily remove the webcard or option card from the Intelislot port of the UPS.
4. Verify the USB port is not being used by another program.
5. If installed, stop Multilink software using the stop command.
Page 7 of the Liebert GXT3 user manual — 3.2 Changing UPS Settings
Page 7 · click to enlarge
Page 7

Chapter 3 Operation 3

Chapter 3 Operation

This chapter details how to operate the program, including read/config UPS settings only and changing UPS settings.

3.1 Read/Config UPS Settings Only

This program can monitor the UPS settings while the UPS is operating in any mode. If this program is only used to read/config the present UPS settings, you do not need to use any buttons except the Cancel button to close the

program.

3.2 Changing UPS Settings

To change the UPS settings, there are three conditions: canceling the settings , restore the settings and changing the settings.

3.2.1 Canceling The Settings

If you decide not to change the UPS settings after modifying the displayed settings, close the program using the Cancel button, and the settings are canceled.

3.2.2 Restore The Settings

If you decide to restore the UPS settings after modifying the displayed settings and prior to select OK or Apply button, select the Refresh button to restore the UPS settings to the existing values stored in the UPS.

3.2.3 Changing The Settings

Requirements on the UPS

All UPS settings can be changed when the UPS is in Standby mode (with AC input power available). Pay attention to the following two conditions:

Settings on the UPS Tab and Options Tab can only be changed with the UPS in Standby mode.

Settings on the Battery Tab can be changed with the UPS in Normal or Standby mode.

If the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to place the UPS in Standby mode. This will disconnect all power to the load.

Changing any value or selecting/deselecting any setting in the configuration window will not immediately change the settings in the UPS. You may modify the displayed settings until you are satisfied with the new proposed changes. After that, you can save the values by selecting either the Apply or OK button.

The Apply button sends the new settings to the UPS without closing the program.

The OK button sends the new settings to the UPS and closes the program.

Whenever the value is successfully saved, the message will be displayed, as shown in Figure 3-1.

Liebert GXT3 — 3.2 Changing UPS Settings diagram (page 7)
Fig. 2 · 3.2 Changing UPS Settings

Figure 3-1 The changes are saved

Saving the changes

Page 8 of the Liebert GXT3 user manual — Chapter 3 Operation
Page 8 · click to enlarge
Page 8

4 Chapter 3 Operation

At this time, if the UPS is already ON, you do not need to restart it.

When the Apply or OK button is selected to transmit new settings on the UPS Tab or Options Tab, the UPS must be put in the Standby mode, or the changes will be rejected, and the error message will be displayed, as shown in Figure 3-2.

Liebert GXT3 — Chapter 3 Operation diagram (page 8)
Fig. 3 · Chapter 3 Operation

Figure 3-2 The changes are rejected

At this point, you should put the UPS to the Standby mode. If the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to place the UPS in Standby mode.

If the UPS is not in the Standby mode, and changes from both the Battery Tab and the UPS Tab or Options Tab are selected, the UPS will only save the changes on the Battery Tab. The Partial Save message will be displayed, as shown in Figure 3-3.

Liebert GXT3 — Chapter 3 Operation diagram (page 8)
Fig. 4 · Chapter 3 Operation

Figure 3-3 Partial save

Changes rejected · Partial save

Page 9 of the Liebert GXT3 user manual — 4.1 UPS Tab
Page 9 · click to enlarge
Page 9

This chapter details the four tabs of the program, including the UPS Tab, Options Tab, Battery Tab and About Tab.

4.1 UPS Tab

When the program starts, the UPS Tab will open, displaying the UPS model along with the current UPS settings, as shown in Figure 4-1. The information can be refreshed at any time using the Refresh button.

Liebert GXT3 — 4.1 UPS Tab diagram (page 9)
Fig. 5 · 4.1 UPS Tab

Figure 4-1 UPS Tab

In the UPS Tab, the UPS must be in Standby mode for the setting to take effect.

The output voltage displayed in the Output textbox is the nominal input/output voltage. This is the nominal output setting not a measured value. The drop down box will show the alternate L-N voltages available. Select the voltage

that matches the application, as shown in Figure 4-2.

Liebert GXT3 — 4.1 UPS Tab diagram (page 9)
Fig. 6 · 4.1 UPS Tab

Figure 4-2 Selecting the output L-N voltage

Output voltage selection

Page 10 of the Liebert GXT3 user manual — 4.2 Options Tab
Page 10 · click to enlarge
Page 10
1. For the GXT3 Dual-Inverter models, this sets the L1-N and the L2-N nominal voltage.
2. The L1-L2 voltage is dependent upon the phase angle of the input utility and is auto-detected when power is first applied.
3. For the GXT3 230 volt single inverter model, only those voltages supported by the UPS will be displayed.

The L-N reverse detection is only for the 120V UPS. Proper wiring of the receptacle powering the UPS is critical for safety, EMI suppression, and surge suppression. The UPS checks the outlet when first plugged in.

Enable L-N reverse detection is checked

When the box of Enable L-N Reverse Detection (120V UPS only) is checked, alarm of L-N reverse will be enabled.

If the Line-Neutral is reversed or the ground is missing, the UPS will not start.

If a problem is detected after the UPS is started, the UPS will continue to operate, but the AC INPUT LED will flash.

In this situation, the improperly wired receptacles should be immediately repaired before the UPS is put into service.

Enable L-N reverse detection is unchecked

When the box of Enable L-N Reverse Detection (120V UPS only) is unchecked, alarm of L-N reverse will be disabled.

The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capable of being used as 50Hz or 60Hz systems.

Auto Sensing – 50 or 60Hz – Bypass Enabled or Auto Sensing – 50 or 60Hz – Bypass Disabled should be selected according to the application.

The UPS will auto-sense the utility frequency when first plugged in and set the nominal frequency to match.

For some special applications

For some special applications, the UPS is required to be used as a frequency converter. In this application the following options are available:

Frequency Converter – 50Hz – Bypass Disabled or Frequency Converter – 60Hz – Bypass Disabled.

Frequency Converter – 50Hz – Bypass Disabled mode will provide 50Hz UPS output from any qualified commercial power. Frequency Converter – 60Hz – Bypass Disabled mode will provide 60Hz UPS output from any qualified commercial power.

Frequency Converter – 50Hz – Bypass Disabled or Frequency Converter – 60Hz – Bypass Disabled mode disables the Bypass. If, for any reason, the UPS inverter is unable to power the load, the alternate bypass to utility power will not be available and power will be removed from any load.

Enable Audible Alarm Control, if checked the audible alarms are enabled.

Enable Audible Alarm Control, if unchecked the audible alarms are disabled.

4.2 Options Tab

Select the Options Tab, as shown in Figure 4-3.

Show 4 more labels / short text on this page
L-N reverse detection · Frequence selection · For typical applications · Audible alarm control
Page 11 of the Liebert GXT3 user manual — 4.3 Battery Tab
Page 11 · click to enlarge
Page 11
Liebert GXT3 — 4.3 Battery Tab diagram (page 11)
Fig. 7 · 4.3 Battery Tab

Figure 4-3 Options Tab

In the Options Tab, the UPS must be in Standby mode for the setting to take effect.

Disable output - manual restart only

For particular industrial applications and special computer applications, the UPS may be monitored and controlled using external voltages and relay contact signals.

An Any Mode Shutdown command can be activated on the terminal block of the UPS by operating Pin1 & Pin2.

If selected, the Disable Output – Manual Restart Only setting will require the UPS to be manually restarted by pressing the Start button on the front panel of the UPS after the Any Mode Shutdown signal on the terminal block has been removed.

If the UPS is in a remote location with limited access then the setting should not be used.

For particular industrial applications and special computer applications, the UPS may be monitored and controlled

using external voltages and relay contact signals.

An Any Mode Shutdown command can be activated on the terminal block of the UPS by operating Pin1 & Pin2.

If selected, the Auto-Enable Output Automatically setting will automatically restore the UPS output after Any Mode Shutdown signal on the terminal block has been removed.

Default operation - normally open

The shutdown logic can be configured for normally open or normally closed. This setting defines the configuration of the Any Mode Shutdown.

If selected, the Any Mode Shutdown will operate when Pin1 & Pin2 of the terminal block are connected

Inverted operation - normally closed

The shutdown logic can be configured for normally open or normally closed. This setting defines the configuration of the Any Mode Shutdown.

If selected, the Any Mode Shutdown will operate when Pin1 & Pin2 of the terminal block are disconnected.

4.3 Battery Tab

Select the Battery Tab, as shown in Figure 4-4.

Auto-enable output automatically

Page 12 of the Liebert GXT3 user manual — 4.3 Battery Tab
Page 12 · click to enlarge
Page 12
Liebert GXT3 — 4.3 Battery Tab diagram (page 12)
Fig. 8 · 4.3 Battery Tab

Figure 4-4 Battery Tab

In the Battery Tab, the UPS can be in any mode for the setting to take effect.

Low battery time warning

The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated if the estimated time reaches the Low Battery Time. The value of Low Battery Time Warning can be selected from 2 to 30 minutes.

Auto battery test time

The UPS performs an automated battery test periodically. If enabled, the value of Auto Battery Test Time can be selected from 7, 14, 21, and 28 days.

If additional batteries are attached to the UPS, accurate battery runtime estimates are possible if the number of External Battery Cabinets is entered in the textbox of Battery Cabinets. The UPS is designed to operate with up to

four external battery packs or four long runtime (LRT) battery packs.

In some applications it may be preferable to disable the automated, periodic battery test. Uncheck the Enable Auto Battery Test box to disable the periodic battery test.

The UPS will provide computer grade power during power outages. If input power is unavailable for an extended time, the UPS will shut down when batteries are depleted, or a shutdown signal is sent by the computer operating system to limit battery depletion (communication data or contact closure).

If Auto Restart is enabled (checkmark in the box of Enable Auto Restart), the UPS will restart when input power is restored. If the UPS turns off power to the load for any other reason, manual restart is required (See Options tab for exceptions). Uncheck the Enable Auto Restart box to disable Auto Restart.

If the UPS has reached the Low Battery warning level, the UPS will either continue to shutdown or return to Utility when the Utility power returns, dependent on the setting of Enable Auto Shutdown.

If Enable Auto Shutdown is checked, then the UPS will continue to shutdown even if the Utility power returns.

If Enable Auto Shutdown is unchecked, then UPS will return to Utility when the input power returns.

Show 4 more labels / short text on this page
Battery cabinets · Auto battery test · Auto restart · Auto shutdown
Page 13 of the Liebert GXT3 user manual — 4.4 About Tab
Page 13 · click to enlarge
Page 13

4.4 About Tab

Select the About Tab, as shown in Figure 4-5.

Liebert GXT3 — 4.4 About Tab diagram (page 13)
Fig. 9 · 4.4 About Tab

Figure 4-5 Window of About Tab

The contents of the CD can be seen in the About Tab.

Ask about the Liebert GXT3

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert GXT3

Be the first to ask — other owners or our team will answer.

Original document

Liebert GXT3 manual PDF

13 pages·380 KB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…