PowerSure™ PSA Quick-Start Guide for 350-1000VA; 120V WHAT’S IN THE BOX

* Power ON/OFF/ Alarm Silence

Site Wiring Fault * Indicator (Red)

  • Quick-Start guide
  • PowerSure family user manual on CD (also at <a href="http://www.liebert.com" rel="nofollow noopener" target="_blank">www.liebert.com</a> )
  • Warranty card
  • MultiLink ™ software CD
  • MultiLink serial cable (M3LS9P9S), 10 ft. (3m)
  • RJ-11 cord, 7 ft. (2.1 m)
  • USB cable, 6 ft. (1.8m) For more details, refer to the PowerSure user manual on CD. Para una información más detallada, consulte el manual del usuario de la familia PowerSure en el CD.

* Utility Indicator (Green)

Battery Indicator * (Green/Amber)

** Orange output recep- tacles (battery backup and surge protection) (4 receptacles on 350, 500 and 650VA models)

Data Line *** Protection Connectors

* Fault Indicator (Red/Green)

** Black output receptacles (surge protection only)

For details, see* Controls and Indicators ** Installation *** Communications

Battery cover plate (on bottom for 650&1000VA models) (on rear of 350&500VA models)

6-ft. (1.8m) power cord

I NSTALLATION

Plug computers, monitors & network hubs into orange receptacles

Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or at www.liebert.com before operating the UPS. Adhere to all warnings on the unit and in the manual. 1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambi- ent temperature range of 32°F to 104°F (0°C to 40°C). 2. Plug the PSA’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, refer to the Troubleshooting section. 3. Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black receptacles, which provide surge protection only. 4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors. 5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indi- cator will illuminate (green). 6. Turn on connected equipment.

Plug this type of equipment into black receptacles ONLY

Inkjet printers Scanners Fax machines

C ONTROLS AND I NDICATORS

C OMMUNICATIONS

This button controls output power to the connected load and has three functions:

The PowerSure PSA will communicate with your computer in either of two ways: over its DB-9 port through Lie- bert’s MultiLink™ software or by USB through Microsoft® Windows® operating system features.

  • Turns the PowerSure PSA ON
  • Turns the PowerSure PSA OFF
  • Silences PowerSure PSA alarms

MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shut- down of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status infor- mation and will perform an orderly computer shutdown. Check your computer’s OS features to determine whether it has power management capability.

TURN THE UPS ON: Press and release the main ON/OFF button to start the UPS. An audible alarm will sound briefly.

  • For MultiLink Serial Communications
  • Connect the provided MultiLink serial cable to the DB-9 ports on the rear of the UPS and on the rear of your computer.
  • Install the MultiLink software—the software, installation instructions and the user manual are on the CD included in the PowerSure PSA package. For USB Communications (with operating system power management)
  • Connect the USB cable provided with the UPS to the USB ports on the PSA and your computer. The PSA will work automatically with the built-in power management software on Windows XP and 2000 or later.
  • All USB models are compatible with Microsoft Windows 2000, Windows XP and Macintosh ® OS 10.2 or later.

TURN THE UPS OFF: When the PSA is ON, hold the main ON/OFF button down for more than 2 seconds to shut it down. An audible alarm will sound briefly.

SILENCE AN ALARM: When a UPS alarm is active, press and release the main ON/OFF button to silence the audible alarm (Exceptions: low battery, overload and overtemperature). DO NOT hold the button down for more than 2 seconds or the PSA will shut down.

CHECK THE PSA’S CONDITION: Three status indicators on the front of the UPS illuminate to specify the status of the UPS (see Troubleshooting section for details).

S PECIFICATIONS

Utility Indicator GreenNormal operation Amber: Buck/Boost
Model NumberPSA350MT-120PSA500MT-120PSA650MT-120 Power Rating VA/W 350VA/210W500VA/300W650VA/390W
Liebert 350 — S PECIFICATIONS diagram (page 1)
Fig. 1
Fault Indicator GreenOverload/ Overtemperature Red: UPS fault
Unit WxDxH4.6x7.7x8.7 (116x196x222)4.6x7.7x8.7 (116x196x222)4.6x14.1x8.7 (116x358x222) Shipping WxDxH7.7x12.2x11.5 (196x310x293)7.7x12.2x11.5 (196x310x293)9.5x19.7x12.4 (242x500x316)
Battery Indicator GreenOn battery Amber: Battery

SITE WIRING FAULT INDICATOR (RED)

The Site Wiring Fault Indi- cator on the rear panel, as shown, illuminates red when the UPS detects a line-neutral reversal or a poor neutral-ground. (See Troubleshooting Chart if indicator is illuminated.)

Unit16.8 (7.6)17.2 (7.8)20.7 (9.4) Shipping18.1 (8.2)18.5 (8.4)22.9 (10.4)

Site Wiring Fault Indicator (Red)

78VAC - 150VAC, DIP switch selectable (see “DIP switch settings” on page 1)

Input Power Cord 6 ft. (1.8m) attached, w/ NEMA 5-15 P

TRANSFER VOLTAGE SELECTORS (DIP SWITCHES)

The two-position DIP switch control on the rear panel, shown above, allows the operator to select the utility transfer voltage at which the UPS will switch to battery power. The factory default settings are 100VAC - 135VAC. DIP switch positions for each voltage setting are:

Output Receptacles(4) NEMA 5-15R (orange) Battery backup + surge protection; (2) NEMA 5-15R (black) Surge protection Voltage (Normal mo Voltage (Battery mo Output Current2.9 A4.2 A5.4 A Waveform (Battery Frequency Overload Warning (Normal & Battery Overload Shutdown
Liebert 350 — TRANSFER VOLTAGE SELECTORS (DIP SWITCHES) diagram (page 1)
Fig. 2
DIP switch settings t RightNominal UtilitySetting ↑ Up120VAC85 - 145VAC (default) ↓ Down110VAC78 - 138VAC wn ↑ Up127VAC90 - 150VAC wn ↓ Down120VAC85 - 145VAC
Type QuantityxVoltagexRating (1)x12Vx7Ah(1)x12Vx9Ah(1)x12Vx9Ah Transfer Time Backup Time: Full Load Half Load Recharge Time
Show 7 more labels / short text on this page
*** USB port · PowerSure PSA · *** DB-9 port · DIP switches ** · mode · Rear of UPS · DIP Switches
Page 2 of the Liebert 350 user manual — DISCONTINUED
Page 2 · click to enlarge
Page 2

T ROUBLESHOOTING

T ROUBLESHOOTING C HART

The information below indicates various symptoms a user may encounter in the event the PowerSure PSA experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy.

If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installa- tion section of this manual. If the problem persists, refer to the chart below:

ProblemCauseSolution UPS will not startC U Overload/Short U Circuit F Li Wheck the circuit protector on the rear of the PS. If it is tripped, reset it and restart the PS. or further help, call your local dealer, ebert representative or the Liebert orldwide Support Group. B o dira s it cst he cr ay o r gmd ei ps dlc eo ten ln yected C bheck for proper connection of battery or atteries. UPS starts on battery, but will not switch to ACUPS not plugged in Plug in the power cord securely. Circuit protector R tripped Ueset the circuit protector and restart the PS. Power not available H at utility receptacle elave the utility checked by a qualified ectrician. I bn ep lou wt v to hl rta eg she old W l qeait until the voltage rises to an appropriate vel or have the utility checked by a ualified electrician. W AC overvoltage le qait until voltage lowers to an appropriate vel or have the utility checked by a ualified electrician. UPS shuts down, Fault Indicator litOverload/Short C Circuit U U If th w Internal UPS fault th F Li Wheck the circuit protector on the rear of the PS. If it is tripped, reset it and restart the PS. the problem persists, disconnect some of e equipment from your UPS—the total attage of your equipment must not exceed e capacity of the UPS. or further help, call your local dealer, ebert representative or the Liebert orldwide Support Group. M High temp shutdown to aake sure that the UPS is operating in 32°F 104°F (0°C to 40°C) and that it has dequate ventilation. MultiLink shutdown C yoonsult the MultiLink user manual or contact ur LAN administrator. Site Wiring Fault Indicator illuminatedLine-neutral reversal, H Poor ground el connectionave the utility checked by a qualified ectrician. UPS not providing expected back-up timeOverload Reduce load. Battery not charged due to a recent R outageecharge battery. B rea pt lt ae cry e dneeds to be Replace battery.
1. The Fault indicator illuminates, indicating the UPS detected a problem. 2. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload and overtemperature warning conditions. 3. Utility and/or Battery indicators may be illuminated as a diagnostic aid to the operator, as shown below:

GUIDE TO STATUS INDICATORS

Fault IndicatorUtility IndicatorBattery IndicatorDiagnosis/ Audible Alarm —Green ON—Normal operation with utility power present; no beep. ——Green ONUPS is operating on battery; beep every 10 seconds. ——Green ONBattery test has been initiated; no beep. —Green ONAmber FlashingBattery needs to be replaced; long beep every minute. ——Amber FlashingLow battery warning; beep every half-second. Green FlashingGreen ON—Overload warning, load is >100%; beep every half-second. Green Flashing——Overload shutdown, load exceeds UPS capacity (110%); continuous beep. Green ONGreen ON—Overtemperature (overtemp) warning; beep every 5 seconds (Normal mode). Green ON—Green ONOvertemperature (overtemp) warning; beep every 5 seconds (Battery mode). Green ON——Overtemperature (overtemp) shutdown; long beep every 5 seconds. Red FlashingGreen ON—UPS is on, fault warning; continuous beep. Red ON——UPS has failed & shut down; continuous beep.

M AINTENANCE

B ATTERY R EPLACEMENT

The PowerSure PSA UPS requires very little maintenance. Follow these practices to prevent problems.

Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed.

CLEANING THE UPS

To replace the batteries:

The following will help ensure trouble-free operation for years:

1. Remove the battery cover plate on the back/bottom of the UPS ( Figure 1 ). 2. Pull the white tabs towards you to remove the battery from the UPS ( Figure 2 ).

Figure 1 Figure 2

  • Vacuum dust from the ventilation intake occasionally.
  • Wipe the cover periodically with a dry cloth.

MAINTAINING BATTERIES

The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The UPS continuously charges the batteries when connected to the utility supply, even while the UPS is switched off.

When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.

BATTERY REPLACEMENT

  • CAUTION A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:
  • Remove rings, watches, and other metal objects.
  • Do not lay tools or other metal objects on top of the batteries.
  • If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.
  • Do not dispose of batteries in a fire. The batteries may explode.
  • Dispose of old batteries according to local codes.
3. Disconnect the insulated connectors from the battery terminals ( Figure 3 ). 4. Insert a new battery pack, and push the connectors onto the battery terminals (black to black & red to red) ( Figure 4 ).

Figure 3 Figure 4

!

This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads.

5. Push the battery pack into the UPS ( Figure 5 ). 6. Reattach the battery cover plate ( Figure 6 ).

Figure 5 Figure 6

Liebert 350 — Figure 5 Figure 6 diagram (page 2)
Fig. 3 · Figure 5 Figure 6

DISCONTINUED

PRODUCT

  • To register for warranty protection:
  • Visit the Quick Links section of our Web site at: <a href="http://www.liebert.com" rel="nofollow noopener" target="_blank">http://www.liebert.com</a>
  • Click on Product Warranty Registration and fill in the form.

If you have any questions, please contact us at:

SL-23270QS (9/03) Rev. 0

Utility Indicator · Fault Indicator · Battery Indicator

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
UPS will not startC U Overload/Short U Circuit F Li Wheck the circuit protector on the rear of the PS. If it is tripped, reset it and restart the PS. or further help, call your local dealer, ebert representative or the Liebert orldwide Support Group. p.2
UPS will not startB o dira s it cst he cr ay o r gmd ei ps dlc eo ten ln yected C bheck for proper connection of battery or atteries. p.2
UPS starts on battery, but will not switch to ACUPS not plugged in Plug in the power cord securely. p.2
UPS starts on battery, but will not switch to ACCircuit protector R tripped Ueset the circuit protector and restart the PS. p.2
UPS starts on battery, but will not switch to ACPower not available H at utility receptacle elave the utility checked by a qualified ectrician. p.2
UPS starts on battery, but will not switch to ACI bn ep lou wt v to hl rta eg she old W l qeait until the voltage rises to an appropriate vel or have the utility checked by a ualified electrician. p.2
UPS starts on battery, but will not switch to ACW AC overvoltage le qait until voltage lowers to an appropriate vel or have the utility checked by a ualified electrician. p.2
UPS shuts down, Fault Indicator litOverload/Short C Circuit U U If th w Internal UPS fault th F Li Wheck the circuit protector on the rear of the PS. If it is tripped, reset it and restart the PS. the problem persists, disconnect some of e equipment from your UPS—the total attage of your equipment must not exceed e capacity of the UPS. or further help, call your local dealer, ebert representative or the Liebert orldwide Support Group. p.2
UPS shuts down, Fault Indicator litM High temp shutdown to aake sure that the UPS is operating in 32°F 104°F (0°C to 40°C) and that it has dequate ventilation. p.2
UPS shuts down, Fault Indicator litMultiLink shutdown C yoonsult the MultiLink user manual or contact ur LAN administrator. p.2
Site Wiring Fault Indicator illuminatedLine-neutral reversal, H Poor ground el connectionave the utility checked by a qualified ectrician. p.2
UPS not providing expected back-up timeOverload Reduce load. p.2
UPS not providing expected back-up timeBattery not charged due to a recent R outageecharge battery. p.2
UPS not providing expected back-up timeB rea pt lt ae cry e dneeds to be Replace battery. p.2

Ask about the Liebert 350

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert 350

Be the first to ask — other owners or our team will answer.

Original document

Liebert 350 manual PDF

2 pages·912 KB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…