PowerSure™ PSA Quick-Start Guide for 350-1000VA; 120V WHAT’S IN THE BOX
* Power ON/OFF/ Alarm Silence
Site Wiring Fault * Indicator (Red)
* Utility Indicator (Green)
Battery Indicator * (Green/Amber)
** Orange output recep- tacles (battery backup and surge protection) (4 receptacles on 350, 500 and 650VA models)
Data Line *** Protection Connectors
* Fault Indicator (Red/Green)
** Black output receptacles (surge protection only)
Battery cover plate (on bottom for 650&1000VA models) (on rear of 350&500VA models)
6-ft. (1.8m) power cord
Plug computers, monitors & network hubs into orange receptacles
Read all safety, installation and operating instructions in the PowerSure family user manual on the included CD or at www.liebert.com before operating the UPS. Adhere to all warnings on the unit and in the manual. 1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an ambi- ent temperature range of 32°F to 104°F (0°C to 40°C). 2. Plug the PSA’s power cord into an AC outlet. Check the Site Wiring Fault Indicator on the rear; if it is illuminated, refer to the Troubleshooting section. 3. Plug any computers and monitors into the orange receptacles for battery backup and surge protection; other office machines that do not exceed the capacity of the UPS may be plugged into either of the two (2) black receptacles, which provide surge protection only. 4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors. 5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indi- cator will illuminate (green). 6. Turn on connected equipment.
Plug this type of equipment into black receptacles ONLY
Inkjet printers Scanners Fax machines
C OMMUNICATIONS
This button controls output power to the connected load and has three functions:
The PowerSure PSA will communicate with your computer in either of two ways: over its DB-9 port through Lie- bert’s MultiLink™ software or by USB through Microsoft® Windows® operating system features.
MultiLink supplies useful monitoring data, such as input voltage and battery level, and will perform an orderly shut- down of the computer system. Microsoft Windows XP and 2000 operating system utilities supply UPS status infor- mation and will perform an orderly computer shutdown. Check your computer’s OS features to determine whether it has power management capability.
TURN THE UPS ON: Press and release the main ON/OFF button to start the UPS. An audible alarm will sound briefly.
TURN THE UPS OFF: When the PSA is ON, hold the main ON/OFF button down for more than 2 seconds to shut it down. An audible alarm will sound briefly.
SILENCE AN ALARM: When a UPS alarm is active, press and release the main ON/OFF button to silence the audible alarm (Exceptions: low battery, overload and overtemperature). DO NOT hold the button down for more than 2 seconds or the PSA will shut down.
CHECK THE PSA’S CONDITION: Three status indicators on the front of the UPS illuminate to specify the status of the UPS (see Troubleshooting section for details).

The Site Wiring Fault Indi- cator on the rear panel, as shown, illuminates red when the UPS detects a line-neutral reversal or a poor neutral-ground. (See Troubleshooting Chart if indicator is illuminated.)
Site Wiring Fault Indicator (Red)
78VAC - 150VAC, DIP switch selectable (see “DIP switch settings” on page 1)
Input Power Cord 6 ft. (1.8m) attached, w/ NEMA 5-15 P
The two-position DIP switch control on the rear panel, shown above, allows the operator to select the utility transfer voltage at which the UPS will switch to battery power. The factory default settings are 100VAC - 135VAC. DIP switch positions for each voltage setting are:


T ROUBLESHOOTING C HART
The information below indicates various symptoms a user may encounter in the event the PowerSure PSA experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy.
If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installa- tion section of this manual. If the problem persists, refer to the chart below:
B ATTERY R EPLACEMENT
The PowerSure PSA UPS requires very little maintenance. Follow these practices to prevent problems.
Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed.
To replace the batteries:
The following will help ensure trouble-free operation for years:
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The UPS continuously charges the batteries when connected to the utility supply, even while the UPS is switched off.
When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.
!
This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads.

PRODUCT
If you have any questions, please contact us at:
SL-23270QS (9/03) Rev. 0
Utility Indicator · Fault Indicator · Battery Indicator
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS will not start | C U Overload/Short U Circuit F Li W | heck the circuit protector on the rear of the PS. If it is tripped, reset it and restart the PS. or further help, call your local dealer, ebert representative or the Liebert orldwide Support Group. | p.2 |
| UPS will not start | B o dira s it cst he cr ay o r gmd ei ps dlc eo ten ln yected C b | heck for proper connection of battery or atteries. | p.2 |
| UPS starts on battery, but will not switch to AC | UPS not plugged in Pl | ug in the power cord securely. | p.2 |
| UPS starts on battery, but will not switch to AC | Circuit protector R tripped U | eset the circuit protector and restart the PS. | p.2 |
| UPS starts on battery, but will not switch to AC | Power not available H at utility receptacle el | ave the utility checked by a qualified ectrician. | p.2 |
| UPS starts on battery, but will not switch to AC | I bn ep lou wt v to hl rta eg she old W l qe | ait until the voltage rises to an appropriate vel or have the utility checked by a ualified electrician. | p.2 |
| UPS starts on battery, but will not switch to AC | W AC overvoltage le q | ait until voltage lowers to an appropriate vel or have the utility checked by a ualified electrician. | p.2 |
| UPS shuts down, Fault Indicator lit | Overload/Short C Circuit U U If th w Internal UPS fault th F Li W | heck the circuit protector on the rear of the PS. If it is tripped, reset it and restart the PS. the problem persists, disconnect some of e equipment from your UPS—the total attage of your equipment must not exceed e capacity of the UPS. or further help, call your local dealer, ebert representative or the Liebert orldwide Support Group. | p.2 |
| UPS shuts down, Fault Indicator lit | M High temp shutdown to a | ake sure that the UPS is operating in 32°F 104°F (0°C to 40°C) and that it has dequate ventilation. | p.2 |
| UPS shuts down, Fault Indicator lit | MultiLink shutdown C yo | onsult the MultiLink user manual or contact ur LAN administrator. | p.2 |
| Site Wiring Fault Indicator illuminated | Line-neutral reversal, H Poor ground el connection | ave the utility checked by a qualified ectrician. | p.2 |
| UPS not providing expected back-up time | Overload R | educe load. | p.2 |
| UPS not providing expected back-up time | Battery not charged due to a recent R outage | echarge battery. | p.2 |
| UPS not providing expected back-up time | B rea pt lt ae cry e dneeds to be R | eplace battery. | p.2 |