Service Manual Manuale di Assistenza
Issued by TDS cod. 272014 - rev. 12.01.2001




1.1 - Foreword The following manual describes the installation, opera tion and maintenance of Air Conditioners, series Hiline Slim (see Fig. 1).
1.5 - Inspection On receiving the equipment immediately inspect its condition; report any damage to the transport company at once.
1.6 - Transport Always keep the unit vertically upright. If possible transport the unit using a fork lift truck; otherwise use a crane with belts or cables, avoiding the exerting of pressure on the top edges of the pack ing. Unpack the unit as close as possible to its installation position. Once unpacked, avoid stress being trans mitted to its internal components.
1.2 - Operating limits The units are designed to operate within working ranges (see Tab. 1). These limits are referred to new machines or for those that have been correctly installed and serviced. The warranty clauses are no longer valid for any damage or malfunction that may occur during or due to opera tion outside the application values.
1.7 - Positioning of air conditioner The air conditioner can be installed in any indoor location where it is not exposed to an aggressive ambient. Position the air conditioner so as to ensure optimum air distribution within the area in which it is to oper ate, preventing the creation of unconditioned zones. For the correct positioning of the air conditioner see Fig. 2 at the end of the manual.
1.8 - Service area The unit must be provided with a suitable Service Area, as follows (see Fig. 2): All ordinary maintenance can be performed both from the front side and from the rear side (external) where a minimum area must be left free of obstruc tions.
1.9 - Wall holes Make the holes in the wall of the container next to the unit's position (see Fig. 3).
1.3 - Sound pressure levels Tab. 2 shows, for the internal and the external side, the maximum sound pressure levels of the units in standard configuration, in continuous operation, at 2 m from the front surface of the machine, at 1 m height in free field conditions. The noise levels have the highest values at the front of the unit, on the internal side.
1.4 - Sealing the room To create stable indoor conditions make sure that the room is airtight by sealing all gaps, cable entries, etc...


For a correct installation proceed as follows (Fig. 4): Provide the unit with cornice protection elements (these can be supplied as optional), using the proper holes and the self-tapping screws with 3.5 mm diam eter. In order to avoid that water filters inside the contain er, provide it with an adhesive rubber gasket.
Fix the cornice to the shelter wall by means of M4 screws with anchor. Fix the lower cornice protection element by means of two M4 screws with anchor. Provide the unit roof with the fixing bracket to the wall with two self-tapping screws with 3.5 mm diam eter.
Before performing any operations on the electric parts, make sure that: all electrical components are undamaged; all terminal screws are tight; the supply voltage and frequency are as indicated on the unit; the switch QS1 is in open position (OFF); the automatic switch QS2 on the outer clamps of the inverter (if installed) are off; there are no components under voltage.
Note: For the power supply use a screened cable (minimum section indicated in Tab. 4). It is advisable to keep the mains power supply cable as far as possible from the other cables coming out of the inverter (optional). Connect the 230V/1/50 Hz line to the main switch QS1 placed inside the electrical panel. Concerning the alarm contacts available in the differ ent versions, these can be found on the terminal board in the electrical panel. For the alarm description see Chapter 6 and the manual of the installed control. To connect 2 or more units installed in the same con tainer and provided with the MICROFACE control, with HIROMATIC interface, use the HIROBUS cable (supplied with the unit) by connecting it as shown in the wiring diagram. See the Microface and Hiromatic manual for the configuration of the Stand-by units.
The electrical connections (power supply 230/1/50 and, for emergency power supply (48 and 24 Vdc) will be car ried out from the roof of the unit by means of some pro per holes. Let the electrical power supply cable (not supplied by us), pass through the hole made on the unit roof.


(*) In the following conditions (ARI 520-78):
Condensing temperature 54.4C, Ambient temp. 35C, Evaporation temp. 7.2C, Sub-cooling temp.: 8.3C Overheating temp.: 11C
3.2 - Emergency cooling kit (optional) The emergency cooling kit consists of an inverter and a single-phase transformer installed inside the electric board. Operating as shown in par. 3.1, supply power up to 48 (24) Vdc inside the electrical panel, by means of a screened cable with a minimum section as shown in
Tab. 4. Connect the possible ground line to the positive pole of the 48 Vdc power supply. Connect the cable screening to the metal cable clamp and perform the con nections following the wiring diagram carefully. Attention: Connect the poles correctly. As regards the units with emergency supply through external Inverter, make the connections as specified in the electrical diagram.
4.1 - First start-up (or after a long halt) Before starting the air conditioner do check if the power supply voltage and frequency comply with those indi cated on the identification plate of the unit. After that, the conditioner can be started putting the automatic switch QS1 to ON position. On the units pro vided with this switch also press the ON-OFF push but ton on the Hiromatic interface. Check the electrical input of all components and compare it with the data shown in the Tab. 3. Check that there are no active alarms; wait until the system reaches the standard operation and then make the following checks: check that the fans are working correctly; make sure that the temperature is guaranteed and the compressor and the heaters (optional) work when required; only on versions provided with the Variex option (speed adjustment)make sure that the speed adjuster of the fan of the condensing section is correctly calibrated and controls the fan operation (see chapter 8).
4.2 - Start-up with low outside temperature In case of low outside temperature (
4.3 - Starting and stopping For the units provided with HIROMATIC interface: start the unit by pressing the ON-OFF push button on the Hiromatic (confirmed by SYS.ON on the display); stop the unit by pressing the ON-OFF push button on the Hiromatic (confirmed by SYS.OFF. on the display). Note: turn the main switch QS1 and the QS2 Inverter switch off only if the unit is stopped for a long time. For the units provided with the Microface control, you can switch on/off using the main switch QS1, which is ac cessible by opening the hinged higher panel acting on quick lock system.

The unit operation is completely automatic.The below sequence explains (with the assistance of Fig. 5 - Opera tion diagram) how the unit operates (see also Fig. 6 Refrigerating circuit): 1) The temperature sensor, positioned inside the shel ter, informs the control about the condition of the air to be conditioned. 2) The control compares the received information with the Set Point values (= min. indoor temperature required) and Differential programmed values, pre setting the air conditioner for the air conditioning with the following modes:
The opening degree of the damper is determined as a function of the set point value to be kept and of the intake air temperature (see chapter 6).
5.1 - Adjustment of the condenser fan speed (compulsory for outside temperatures -10 / -30C) A sensor is positioned so as to detect constantly the con densing pressure of the refrigeration gas. On the basis of this information, an electronic device (Variex) adjusts the fan rotation speed in order to keep the condensing pressure within the allowed values. In this way, besides optimizing the compressor operation, you can have a remarkable reduction of the sound pressure level (mainly during the night), an easier start-up of the com pressor at low temperatures and some energy saving. For the calibration of the speed adjuster refer to chapter 8.
Cooling (Fig. 5) The compressor (9) and the fans (6) and (10) are started up when the temperature of the room to be conditioned exceeds the preset value. The intake air from the centrif ugal fan (6) enters the unit through the lower gap (A), goes immediately through the filter (1) and then the evaporator (5). The cool refrigerant flows through the evaporator (5), thus cooling the air passing through it. The conditioned air is conveyed into the conditioned room through the discharge opening (B). The heat taken from the room and the one generated by the conditioner motor operation are disposed through the condenser (11) placed in the lower part of the unit and hit, thanks to the fan (11), by the outside air. The fan operation is managed in ON - OFF mode (or with Variex, see par. 5.1) as a function of the condensing pres sure. For the operation logics of the control see chapter 6.
5.2 - Emergency cooling (optional) This option is available for all those applications where it is mostly important to guarantee air flow inside the shel ter, even in the event of mains current drop. In this case, by an inverter and a transformer, the units can be sup plied by the emergency coils at 24 or 48 V dc (see Fig. 7). The intervention mode of the emergency system depends on the switch QS1 condition: QS1 = ON If the main power supply is not cut out, the emer gency system remains inactive; if there is no voltage on the main power supply line, the inverter is automatically activated and, being sup plied by the emergency coils at 24/48 V dc, by the 24/48 V / 230 V transformer it supplies the fan of the evaporating section and the electronic control. So all functions of the unit are still managed, allowing the inside air to recirculate (or the outside air to come in, if the unit is provided with freecooling) if the temper ature inside the shelter is not within the permitted range. In this operation mode, a relay contact (KM6) signals the activation of the inverter system. If the voltage of the emergency coils goes below the safety value, the inverter system is automatically de- activated. QS1 = OFF In this abnormal condition occurring, for instance, after a short-circuit in the unit the inverter is auto matically de-activated. CAUTION: For safety reasons do disconnect the automatic switch QS2 when you want to stop the unit.
Heating (optional) The air heating is achieved by means of electric heaters (7), located in the air flow and activated according to the logics set on the control (see chapter 6). The manual reset of the safety thermostat (15), placed on the electrical heaters is carried out throught the front after removing the grill panel.
Cooling in Freecooling (optional) - (Fig. 5) When the outside air temperature is lower than the inside air temperature by some degrees, it is possible to use this difference to refresh the shelter inside part by direct intake of the outside air, i.e. without using the compressor. Thus it is possible to achieve a considerable energy saving. When the expected conditions occur, the servo-control (2), managed by the Microface control, opens the mov ing damper (12) separating the flows of the inside air and outside air. In this way the outside air sucked by the fans (6) flows inside the container and is discharged through the openings of the condensing section. The air flows present in this operation mode are shown in Fig. 5).

The machine is available in four different operating con figurations: 1) chill unit only; 2) chill and hot unit; 3) unit with freecooling, chill only; 4) unit with freecooling, chill and hot. All versions are equipped with the new Microface microprocessor control.
ing mode remains de-activated for 1/2 hour. If the inside temperature exceeds the proportional band by more than 50%, the Freecooling mode is immediately de- activated and remains in this condition for 1/2 hour and the cooling by refrigerating compressor intervenes.
6.1.1 - Start-Stop Altogether there are three ways for starting or stopping the unit: a) the isolator switch inside the electrical panel; b) the digital input of the Microface card; c) the ON-OFF push button on the Hiromatic interface
6.1 - Control logic These units are managed by the Microface microproces sor control and may be combined with the Hiromatic control for the complete monitoring of all unit operation parameters (see enclosed manual). The control algorithm is based on a single-stage adjust ment for the heating and cooling with the compressor and on an adjustment of the proportional-integrative type for the cooling in the Freecooling mode, with setting of the set point and proportional band (P) (Fig. d.) The control manages all activation delays of the com pressor, and minimum times, in order to guarantee the proper operation and to extend its life as much as pos sible. The activation of the Freecooling mode occurs as a func tion of the difference (that can be set) between the inside temperature and the outside temperature. This means that if the difference between the 2 temperatures increases beyond a certain value, the unit automatically passes to the Freecooling function: the compressor is de-activated and the analog output controls the 3-point servomotor of the damper. The damper open ing is varied in order to maintain the inside temperature equal to setpoint and as a function of the intake air tem perature, which cannot be lower than a preset safety value.
(optional). Priority: a) b) c) must be considered as 3 series contacts; only if all contacts are on, the unit can operate.
6.1.2 - Alarm control The terminal board of the elertical panel is provided with 2 clean exchange contacts, on standard configuration, used as follows: 1) General alarm: compressor low pressure compressor high pressure (reset on the pressure
switch) sensor fault memory fault fan fault (with optional sensors) 2) General warning - signalling of various failure conditions, among which: high temperature low temperature heater thermostat (reset on the thermostat) Notes: both the alarm and the warning must be reset manu ally on the Microface. An alarm causes the unit to stop and the unit in stand-by (if available) to intervene. If the unit is in stand-alone, the high and low pressure alarms don't stop the machine to allow the operation in Freecool ing mode in the proper conditions. The warning doesn't cause the unit to stop. When the heater safety thermostat intervenes, the reset will be carried out on the thermostat (15) acces sibble by removing the internal fan side panel.
tion
6.1.3 - Optional alarm card Besides the components described for the standard con figuration, on the alarm card - which can be supplied as optional - there are relay contacts to obtain the follow ing alarms separated: 1) compressor high and low pressure 2) Clogged filter alarm 3) Fan fault 4) High temperature 5) Low temperature These alarms cause the unit to stop in the same ways as described in the previous paragraph. For the detailed description of the alarms, see the Micro face manual enclosed.
Set Cooling Heating C
Set Cooling Heating C
If the inside temperature exceeds the proportional band by more than 20% for longer than 10 minutes, the unit passes to the cooling with compressor and the Freecool

6.1.4 - Unit in stand-by The control of the unit in stand-by is completely auto matic thanks to the possibility to connect the Microface control. A unit in stand-by starts in the event of an alarm which stops the main unit; this occurs even if the main unit is switched off or disappears from the system due to a fault on the control connecting bus. The rotation per hour of the units in stand-by occurs automatically every 24 hours, so as to allow a homoge neous wear of the system components. If the system is connected to the Hiromatic interface, it is possible to set a different rotation control. If several units are simultaneously working with the same set point, the temperature used for the control is the average of the detected ones; further, in the operation with compressor, the proportional band is divided in as many parts as twice the number of units belonging to the system, so as to shut the total available refrigerating capacity. The operation in Freecooling mode is homogeneous and simultaneous on all units. Fig. b, shown as an example, describes the operation of a system consisting of 3 units.
Microface control
Set C Cooling Heating
1 1 2 2 3
Set C Cooling Heating
1 = main unit 2 = unit in stand-by 3 = unit in stand-by
THESE OPERATIONS MUST BE PERFORMED BY AN EXPERIENCED REFRIGERATION TECHNI CIAN.
7.1 - Features of the refrigerating fluid R22 At standard temperature and pressure it is a colourless gas with low toxicity, non-flammable, and it has an allowed exposure limit value (AEL/TLV) corresponding to 1000 ppm (average value measured on 8 hours/day). In the event of leakage, air the room before use.
7.3 - Oil charge The oil to be used when topping up is SUNISO 3GS; if SUNISO 3GS is unavailable use an oil with the same characteristics (see Tab. 6). NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE PIPING COMPLETELY BEFORE CHANGING THE TYPE OF OIL USED.
7.2 - Refrigerant charge WHEN REPAIRING THE REFRIGERATION CIR CUIT RECUPERATE ALL REFRIGERANT IN A CON TAINER: DO NOT ALLOW IT TO ESCAPE. 1) Start the unit as described in par. 4.1. 2) Start the compressor manually. 3) Guarantee a constant condensation temperature (preferably 42-45°C); if necessary, partially obstruct the condenser coil surface or limit its ventilating power to obtain these conditions. 4) Charge the unit with the quantity of refrigerant R22 as shown in Tab. 5 and wait until the operating condi tions of the whole refrigeration circuit are normal.
approx. specific weight (at 15C) flash point (C.O.C.) pour point ENGLER viscosity at 50 C viscosity index copper corrosion (100 C, 3 hours) ASTM D130 neutralization value conradson carbon residue dielectric strength
:
0.91 kg/l 170 C -40 C 2.7 E 0 1 0.03 max. 0% > 30 kV

The air conditioner has already been factory-tested and calibrated as described below. For the MICROFACE calibrations refer to the rele vant manual (to avoid wrong operations do not use
temperature and rel. humidity set points/propor tional bands which differ excessively from the stan dard settings).

For safety reasons, clear the unit opening the switches QS1 and QS2 before performing any maintenance operations. If installed: AS THE HIROMATIC/MICROFACE FEATURES AUTOMATIC RESTART (AFTER A SUPPLY INTERRUPTION) IT IS ADVISED TO DISABLE AUTORESTART AND OPEN THE SWITCH QS WHEN PERFORMING ANY MAINTENANCE.
Every day check the Hiromatic/Microface readings for temperature and, if shown, ambient relative humidity. The Maintenance Programme described below should be carried out by a skilled technician, prefer ably working under a maintenance contract.
9.1 - Dismantling the unit The machine has been designed and built to ensure con tinuous operation. The working life of some of the main components, such as the fan and the compressor, depends on their mainte
nance. If the unit has to be dismantled, this must be done by skilled refrigerator technicians. The refrigerating fluid and the lubricating oil in the cir cuit must be disposed of in conformity with the laws in force in your country.

Use the Fault Finding Guide on the right as follows: Begin with "START" and follow the arrows marked both "YES" and 'NO' according to the type of fault. The guide uses the following abbreviations:
check fan operation plus electrical circuit
When an alarm occurs, the buzzer and the display indication can be reset manually pressing the key PRG/mute. For the alarm code the reset is active only if the alarm cause has been removed. The reset for the alarm contact is automatic. The reset of the adjuster operation occurs auto matically when the alarm cause is removed. For better information see the HIR32 manual.
check for high air temperature
or low air flow
The alarms, shown in the guide, are reset as in Fig. f.
correct condi tioner model on
ALARM ON
(alarm LED + buzzer on)
is unit operating correctly?
press RESET
press REPORT:
which alarm has intervened?
using Fault Finding Guide
is normal operation restored?
switch unit main switch off and then on
return to normal operation
verify state of component:
continue if everything is ok


suction pipe heats up when compressor stops: replace compressor


Schema di principio Kit Raffreddamento di emergenza

(*) Optional, only on request Optional, solo su richiesta
QS1 Mains supply automatic switch Interruttore automatico linea principale
TM Transformer 48/230 Vac or 24/230 Vac Trasformatore 48/230 Vac o 24/230 Vac
QS2 230 Vac line automatic switch Interruttore automatico linea 230 Vac
18 pag.




Via Leonardo da Vinci, 8 35028 Piove di Sacco (PD) ITALY
TEL. +39.049.97.19.111
FAX +39.049.58.41.257 Internet: www.Liebert-HIROSS.com