UPStation GXT 2U™
U SER M ANUAL






! WARNING Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS and battery service to qualified service personnel. Do not attempt to service this product yourself. Never work alone.
This manual contains important safety instructions. Read all safety, instal- lation, and operating instructions before operating the Uninterruptible Power System (UPS). Adhere to all warnings on the unit and in this man- ual. Follow all operating and user instructions. Individuals without previ- ous training can install and operate this equipment.
It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 50Hz or 60Hz, 208V supply (programmable for 200, 208, 220, 230, and 240VAC output). Installation instructions and warning notices are located in this manual.
ELECTROMAGNETIC COMPATIBILITY—The GXT 2U™ Series com- plies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient tempera- ture range of 32°F to +104°F (0°C to +40°C). Install it in a clean environ- ment, free from moisture, flammable liquids, gases and corrosive substances.

This UPS contains no user serviceable parts except the internal battery pack. The UPS ON/Standby push buttons do not electrically isolate inter- nal parts. Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accor- dance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unautho- rized personnel away from the batteries. PROPER DISPOSAL OF BAT- TERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other open- ings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand half-wave rectification from the UPS, for example: electric drills, vacuum cleaners, laser printers or hairdryers.
Storing magnetic media on top of the UPS may result in data loss or cor- ruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
When replacing batteries, replace with the same Liebert authorized replacement battery kits.
! CAUTION Do not dispose of battery or batteries in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It may be toxic.

Risk of electrical shock
Indicates caution followed by important instructions
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery

Congratulations on your choice of the Liebert UPStation GXT 2U™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during trans- mission and distribution it may be subject to voltage sags, spikes, or com- plete power failure that may interrupt computer operations, cause data loss, or even damage equipment. The UPStation GXT 2U protects equip- ment from these disturbances.
The UPStation GXT 2U is rated for 2700 VA, 1890 watts. Complete model specifications appear at the end of this manual.
The UPStation GXT 2U is a compact, “on-line” UPS. An on-line UPS con- tinuously conditions and regulates its output voltage, whether utility power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the UPStation GXT 2U features a light-emitting diode (LED) display to indicate either load percentage or battery capacity depending upon the mode of operation. It also provides self-diagnostic tests, a combination ON/Alarm Silence/Manual Battery Test button, a Standby button, user configurable program, and two levels of alarms when the unit is operating on battery.
The UPStation GXT 2U has an interface port for communication between the UPS and a network server or other computer systems. This port pro- vides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ software. MultiLink software can also remotely control UPS operation.


G
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS
These UPS components provide surge protection and filter both electro- magnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected.
In normal operation, the rectifier/power factor correction (PFC) circuit con- verts utility AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
This results in cleaner power being available to other devices in the build- ing not being protected by the UPStation GXT 2U.
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a utility power failure, the inverter receives its required energy from the battery through the DC to DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
Input Output · Dynamic

The battery charger utilizes energy from the utility power and precisely regulates it to continuously “float charge” the batteries. The batteries are being charged whenever the UPStation GXT 2U is plugged in, even when the UPS is not turned on.
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame retar- dant, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional exter- nal battery cabinets are available to extend battery run times.
The UPStation GXT 2U provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass opera- tion is indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the Standby button once.


Output Receptacles (L6-15R)

PREPARATION 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.
! CAUTION The UPS is heavy (see Specifications section). Take proper precautions when lifting or moving it.
When using the GXT 2U in a tower configuration, use the included sup- port base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accommo- date the additional cabinets (shown below, right).


Support base Spacers added to support
base to accommodate additional battery cabinets


Securing hardware and slide rails are sold separately. Contact your local dealer or Liebert representative for these additional options and any assistance needed.

Return flanges · Inner members

! CAUTION Reduce risk of tipping the rack enclosure by placing UPS or battery cabinet in the lowest possible rack position.
Install rear member of each bracket assembly into rack enclosure with two (2) M5 screws provided in this kit. (See figure at right.) Return flanges on bracket assembly fit to the inside of rack mount- ing rails. Insert screws loosely (finger-tight) into top and bot- tom holes of return flange on rear member. Extend bracket assembly by sliding front member forward until it touches the front rack mounting rail. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes of return flange on each front member. Make sure bracket assemblies are at the same mounting height on all four (4) rack mounting rails.
Front rack mounting rails

Rear rack mounting rails
4. Locate eight (8) M4 screws and eight (8) M4 nuts from hardware pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten nut and screw completely to assure locking action. Fasten rear member and front member together using four (4) screws and four (4) nuts per bracket assembly as shown in the fig- ures at right. For maximum support, locate fasteners for each bracket assembly as far apart as possible, depending on rack depth, while still join- ing both members (See fig- ures at right). Check alignment of bracket assemblies and TIGHTEN ALL SCREWS FROM STEPS 3 and 4.



5. Prepare the UPS or battery cab- inet (the “equipment”) for rack mounting by following instruc- tions in the equipment’s user manual. The equipment may require additional parts to be added or parts to be removed for rack mounting. After it is pre- pared, lay equipment in rack- mounting position. Fasten inner members from Step 2 to the equipment on both sides as shown in the figure at right with (8) M4 screws provided in this kit. Make sure retaining latch is near the rear of the equipment as shown in the figure at right. 6. Open grease packet pro- vided in this kit. Apply a 1" long bead of grease four (4) places inside the bot- tom, curved tracks of front members as shown at right. The grease will allow the equipment to slide into the bracket assemblies more easily.

UPS or battery cabinet

UPS or battery cabinet
! CAUTION Lifting equipment into rack may be a two-person job, depending on weight of equipment. See equipment’s user manual.
7. Insert the equipment, with inner members attached from Step 5, into bracket assemblies by inserting top and bottom edges of inner mem- bers into the top and bottom, curved tracks of front members and slid- ing the equipment into rack (see figure in Step 6). Ends of inner members are tapered to allow rear of the equipment to be angled upward before insertion, if space allows. Then the rear, bottom edges of inner members can be placed into front edge of bottom tracks, and the front of the equipment can be tipped up into hori- zontal position to insert the top edges of inner members before sliding the equip- ment into rack (see figure at right). The equipment should move smoothly into bracket assemblies. If not, recheck alignment of front and rear members from Steps 3 and 4.




Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. There is no limit to the number of external battery cabinets that can be used but each cabinet will increase the battery recharge time.
! CAUTION The external battery cabinet(s) are heavy (see Specifications section). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.



All LEDs illuminated for illustrative purposes only.
ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
ON - Pressing this button will start up the UPS in order to provide condi- tioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one sec- ond. After the alarm is silenced, the UPStation GXT 2U will reactivate the alarm system to alert of additional problems.
Manual Battery Test - To initiate a manual battery test, press the ON but- ton for at least one second while operating from utility power with no alarm conditions present.

This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass.
! CAUTION While the UPS is in Normal Mode operation, pressing the Standby/ Manual Bypass button once will put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press the Standby/ Manual Bypass button two distinct times (for about one second each time) to turn off the UPS. Perform all necessary shutdown procedures on connected loads before turning off the UPS.
Load/Battery Level Indicators (4 Green, 1 Amber)
The load/battery level indicators have dual functions. During normal mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote battery test features. The automatic test occurs every 14 days (this option is user configurable) if utility has not been interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to Troubleshooting section). The remote test feature functions with MultiLink 3 software and can remotely initiate the battery test.
Fault Indicator LED (Red)
The Fault indicator LED is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting section).
Bypass Indicator LED (Amber)
The Bypass indicator LED is illuminated when the UPS is operating from bypass power. An alarm will sound indicating the UPS detected a prob- lem, or the manual bypass function has been activated.
UPS ON Indicator LED (Green)
The UPS ON indicator LED is illuminated when the UPS inverter is oper- ating and supplying power to your connected loads.
Battery Indicator LED (Amber)
The Battery indicator LED is illuminated when the UPS is operating on battery.
Standby/Manual Bypass Button

AC Input Indicator LED (Green)
The AC Input indicator LED is illuminated when utility power is available and within the input specifications.
The Output Voltage is user configurable and is designed to allow select- ing or changing the desired output voltage to match the utility via the GXT 2U Configuration Program provided with the UPS. The settings to choose from are 200, 208, 220, 230, and 240 VAC output. The factory default setting is 208 VAC.
! CAUTION Never change the voltage settings while the UPS is ON and powering connected loads.
Output Voltage Selection


During normal operation, util- ity power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state.
Normal Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output. BYPASS MODE OPERATION
Bypass mode occurs when the OFF button is pressed once while the UPS is in Normal Mode. During bypass opera- tion, utility power provides energy to the UPS. The utility power bypasses the inverter and provides power for the connected load.

Bypass Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (26-50% of load shown in the example above) on the UPS output.
! CAUTION Turning OFF the UPS while in bypass mode will result in loss of output power.
Battery mode occurs in event of an extreme input voltage condition or complete utility failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load.

Battery Mode Operation at 80-61%

During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish, and the Battery LED will illuminate to warn that a utility prob- lem has occurred. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to Troubleshooting section.
For approximate battery run times, refer to the Battery Run Times charts in this manual. These times are approximates based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add the optional external battery cabinet.
! CAUTION Turning OFF the UPS while in battery mode will result in loss of output power.
Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.

The UPStation GXT 2U UPS has a standard DB-9 serial port female con- nector located on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows:

4 Remote Shutdown (5-12VDC, 10-24 mA max); battery operation
6 Remote Shutdown (short to pin 5); all modes of operation
* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.
PINS 4 & 5 - REMOTE SHUTDOWN ON BATTERY 1. This pin is functional only when the UPS is in battery mode. If the UPS is being powered by the utility, Pin 4 will ignore any signal on this pin.

Whether the UPS turns back ON when power is restored depends on the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the 2-minute shutdown delay.
PINS 5 & 6 - ANY-MODE SHUTDOWN 1. Pin 6 of the 9-pin communication connector is used for “Any-Mode Shutdown” of the UPS output. This control input may be used in spe- cial applications to disable the UPS output power—both Inverter and Bypass.
! WARNING Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS output can turn on automatically and without warning if the Pin 6 connection is changed.
! WARNING DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to install a normally-closed connection between Pins 5 & 6. This connection must be maintained to use the UPS or to use the configuration program again, including the ability to change the UPS setting back to the default setting using the configuration program via a serial communication link.
If version 1.6 (or later) is used with an earlier GXT 2U model (with an ear- lier UPS firmware version), the Any-Mode Shutdown features cannot be changed.
Auto-Enable Output · Pin 6 Logic

If the configuration program is used with an earlier UPS model (with an earlier UPS firmware version) that does not support the modification of these settings, the Options tab will display a reminder of the factory default settings. These cannot be changed.
The UPStation GXT 2U is equipped with an Intellislot® port to provide advanced communication and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the Intellislot SNMP/Web card is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the network with other computers running MultiLink when you purchase a MultiLink License Kit. For more information about the Intellislot SNMP/Web Card and MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the UPStation GXT 2U. The Intellislot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coordinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom- wired applications and delivers support for built-in shutdown for AS/400 systems.
! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables, where applicable.

This is a new feature included with the new UPStation GXT 2U line. Sev- eral UPS settings that were previously not available or required custom manufacturing may now be modified using this program. For most users, the factory default settings will be adequate. This manual illustrates the features available for modification, as well as the factory default setting.
NOTE The UPS must be turned off—and not powering connected equip- ment—before you make any changes to configuration settings. While the UPS is in Normal Mode operation, press the OFF button once to put the UPS into Bypass Mode. Once the UPS is in Bypass Mode operation, press and release the OFF button two distinct times (for about a second each time) to turn off the UPS.
What You Will Need

In addition to the GXT 2U UPS, you will need the configuration program dis- kette and serial cable (beige or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. The BLACK ML9P9S CONTACT CLOSURE communication cable IS NOT compatible with the configuration program. A Windows 95®, 98®, or NT® computer—desktop or laptop—is also required to set up and run the configuration program.

The UPStation GXT 2U requires very little maintenance. The batteries are valve-regulated, nonspillable, flame retardant, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is recommended to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries.
The UPStation GXT 2U is designed to allow the user to safely replace the internal batteries. Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing.

Internal Battery Replacement Procedures 1. Gently remove the front plastic bezel cover from the UPS.

The information below indicates various symptoms a user may encounter in the event the UPStation GXT 2U develops a problem. Use this informa- tion to determine whether external factors caused the problem and how to remedy the situation.

This example shows the UPS on bypass due to output overload.
BYPASS
D
UPS ON

BATTERY
A
AC INPUT
A B C D E Fault
LOAD/BATTERY LEVEL INDICATORS
LED status Diagnosis/Audible alarm
All LEDs On bypass due to output overload; beep every half-second A LED On bypass due to overtemperature condition; beep every 4 sec. B LED On bypass due to DC bus overvoltage; beep every 4 sec. C LED On bypass due to control power supply failure; beep every 4 sec. D LED On bypass due to PFC failure; beep every 4 sec. E LED On bypass due to inverter failure; beep every 4 sec. A&C LEDs UPS failed battery test; long beep every minute
C&E LEDs UPS shutdown due to command from communication port (SNMP); no beep Battery LED
Internal Battery source not available (continuous horn). Check battery connection, completely power down and reboot UPS. AC LED Flashing
Line-to-neutral reversal in the AC input power supply or a loss of proper grounding; continuous horn and UPS will not start. Bypass LED
Utility power voltage or frequency is out of tolerance; bypass is unavailable.
Fault · Flashing · Flashing

Under fault conditions, the Fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or contact the Liebert Worldwide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.
UPS fails to start when the ON button is pressed.
UPS is short circuited or overloaded.
Ensure UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
Battery indicator LED is illuminated.
UPS not plugged in. UPS is operating from battery mode, make certain UPS is securely plugged into the wall receptacle.
UPS input protection fuse has blown/opened.
UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.
Utility voltage out of UPS input range.
UPS is operating from battery mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS.
UPS has reduced battery time.
Batteries are not fully charged.
Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS is overloaded. Check load level display and reduce the load on the UPS.
Batteries may not be able to hold a full charge due to age.
Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group for replacement battery kit.
Problem Cause Solution

Fault and Bypass indicator LEDs and all load level LEDs are illuminated.
UPS overloaded or load equipment is faulty.
Check load level display and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load equipment for faults.
Fault and Bypass indicator LEDs and diagnostic LED A are illuminated.
UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power.
Ensure UPS is not overloaded, ventilation openings not blocked, or room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS does not restart, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Fault and Bypass indicator LEDs and diagnostic LED B are illuminated.
UPS internal DC bus overvoltage.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Fault and Bypass indicator LEDs and diagnostic LED C are illuminated.
UPS control power supply fault.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Fault and Bypass indicator LEDs and diagnostic LED D are illuminated.
UPS PFC (Power Factor Correction Circuit) fault.
UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Fault and Bypass indicator LEDs and diagnostic LED E are illuminated.
UPS inverter fault. UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group.
Fault indicator LED and diagnostic LED A and C are illuminated.
UPS failed the battery test. Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Problem Cause Solution

Fault and Bypass indicator LEDs and diagnostic LED C and E are illuminated.
UPS shutdown due to a command from the communications port(s).
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
AC LED is flashing.
UPS detected a line-to- neutral reversal or a loss of proper grounding; continuous horn and UPS will not start.This is active only when power is first applied to the input. Once the UPS is running, the AC LED will not start flashing, even if the input wiring is changed.
Contact a qualified electrician to verify site wiring.
Battery LED is flashing.
Battery source is not available; continuous horn.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
Bypass LED is flashing.
Bypass voltage is present, but is disabled for use because the voltage or frequency is outside acceptable limits.
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this LED will flash, indicating that the bypass is unavailable.
Problem Cause Solution

Battery Mode (utility failure)
One short beep every 10 seconds; more than 2 minutes of run time remaining
Low Battery Two short beeps every 5 seconds; less than 2 minutes of run time remaining
One short beep every half second
A one-second beep every 4 seconds
DC Bus Overvoltage (bypass)
A one-second beep every 4 seconds
Control Power Supply Failure (bypass)
A one-second beep every 4 seconds
PFC Failure (bypass) A one-second beep every 4 seconds
Inverter Failure A one-second beep every 4 seconds
Battery Test Failure A 2-second beep every minute
Condition Alarm · Output Overload (bypass) · Overtemperature (bypass)

Model Number GXT2-2700RT208 Model Rating 2700VA/1890W DIMENSIONS: in. (mm)
Unit - W x D x H: in. (mm) 3.5 x 24.2 x 17 (87 x 618 x 430) Shipping - W x D x H: in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585) WEIGHT lbs (kg)
Voltage Range (typical) 208 VAC nominal; variable based on output load 100% - 90% loading 176 VAC/280 VAC 90% - 70% loading 159 VAC/280 VAC 70% - 30% loading 139 VAC/280 VAC 30% - 0% loading 119 VAC/280 VAC Frequency 40 - 70 Hz; Auto Sensing Input Power Cord 10 ft. attached w/ NEMA L6-20 plug OUTPUT AC PARAMETERS
Output Receptacles (2) NEMA L6-15R (1) NEMA L6-20R Voltage 200/208/220/230/240 (user configurable) VAC; ±3% Frequency 50 Hz or 60 Hz Waveform Sinewave Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass BATTERY PARAMETERS
Type Valve-regulated, nonspillable, flame retardant, lead acid Qty x V x Rating 6 x 12V x 9.0 AH Battery Mfg/Part # Panasonic/ UP-VW1245P1 Yuasa/ REW 45-12 FR Back-Up Time See Battery Run Times charts Recharge Time 5 Hours to 95% capacity after full discharge into 100% load (Internal Batteries Only) ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C) Storage Temp +5°F to +122°F (-15°C to +50°C) Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating Storage Elevation 50,000 ft. (15,000 m) maximum Audible Noise
Safety UL 1778, c-UL Listed (Suitable for computer room applications) RFI/EMI FCC Part 15, Subpart B, Class A Surge Immunity IEEE 587 Category A & B Transportation ISTA Procedure 1A

Used w/ UPS Model GXT2-2700RT208
Unit - W x D x H in. (mm) 3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping - W x D x H in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)
Type Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating 2 x 6 x 12V x 9.0 AH
Battery Mfg/Part # Panasonic/UP-VW1245P1 Yuasa/REW 45-12 FR
Back-Up Time See Battery Run Times charts
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A
Model Number GXT2-72VBATT · DIMENSIONS in (mm) · WEIGHT lbs (kg)


10% 91 20% 46 30% 30 40% 21 50% 16 60% 11 70% 9 80% 8 90% 7 100% 5
10% 364 20% 184 30% 120 40% 84 50% 64 60% 44 70% 36 80% 32 90% 28 100% 20
10% 728 20% 368 30% 240 40% 168 50% 128 60% 88 70% 72 80% 64 90% 56 100% 40
10% 1092 20% 552 30% 360 40% 252 50% 192 60% 132 70% 108 80% 96 90% 84 100% 60
10% 1456 20% 736 30% 480 40% 336 50% 256 60% 176 70% 144 80% 128 90% 112 100% 80 Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.

To register for warranty protection:
http://www.liebert.com • Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:





U SER M ANUAL UPStation GXT 2U™
Web Site www.liebert.com
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Monitoring 800-222-5877 monitoring@liebert.com Outside the US: 614-841-6755
800-222-5877 upstech@liebert.com Outside the US: 614-841-6755
800-543-2378 powertech@liebert.com Environmental Systems
800-543-2778 Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax: +39 049 5841 257
Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong +852 2 572 2201 Fax: +852 2 831 0114
© 2003 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23154 (6/03) Rev. 1
Technical Support/Service · Single-Phase UPS · Three-Phase UPS
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS fails to start when the ON button is pressed. | UPS is short circuited or overloaded. | Ensure UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally. | p.30 |
| Battery indicator LED is illuminated. | UPS not plugged in. | UPS is operating from battery mode, make certain UPS is securely plugged into the wall receptacle. | p.30 |
| Battery indicator LED is illuminated. | UPS input protection fuse has blown/opened. | UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS. | p.30 |
| Battery indicator LED is illuminated. | Utility voltage out of UPS input range. | UPS is operating from battery mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS. | p.30 |
| UPS has reduced battery time. | Batteries are not fully charged. | Keep UPS plugged in continuously at least 24 hours to recharge batteries. | p.30 |
| UPS has reduced battery time. | UPS is overloaded. | Check load level display and reduce the load on the UPS. | p.30 |
| UPS has reduced battery time. | Batteries may not be able to hold a full charge due to age. | Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group for replacement battery kit. | p.30 |
| Fault and Bypass indicator LEDs and all load level LEDs are illuminated. | UPS overloaded or load equipment is faulty. | Check load level display and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load equipment for faults. | p.31 |
| Fault and Bypass indicator LEDs and diagnostic LED A are illuminated. | UPS internal fan has a problem or UPS shutdown due to temperature condition. Load is on bypass power. | Ensure UPS is not overloaded, ventilation openings not blocked, or room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS does not restart, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. | p.31 |
| Fault and Bypass indicator LEDs and diagnostic LED B are illuminated. | UPS internal DC bus overvoltage. | UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. | p.31 |
| Fault and Bypass indicator LEDs and diagnostic LED C are illuminated. | UPS control power supply fault. | UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. | p.31 |
| Fault and Bypass indicator LEDs and diagnostic LED D are illuminated. | UPS PFC (Power Factor Correction Circuit) fault. | UPS requires service. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. | p.31 |
| Fault and Bypass indicator LEDs and diagnostic LED E are illuminated. | UPS inverter fault. | UPS requires service. Contact your local dealer, Liebert Representative or the Liebert Worldwide Support Group. | p.31 |
| Fault indicator LED and diagnostic LED A and C are illuminated. | UPS failed the battery test. | Replace batteries. Contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. | p.31 |
| Fault and Bypass indicator LEDs and diagnostic LED C and E are illuminated. | UPS shutdown due to a command from the communications port(s). | Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Liebert representative or the Liebert Worldwide Support Group. | p.32 |
| AC LED is flashing. | UPS detected a line-to- neutral reversal or a loss of proper grounding; continuous horn and UPS will not start.This is active only when power is first applied to the input. Once the UPS is running, the AC LED will not start flashing, even if the input wiring is changed. | Contact a qualified electrician to verify site wiring. | p.32 |
| Battery LED is flashing. | Battery source is not available; continuous horn. | Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed. | p.32 |
| Bypass LED is flashing. | Bypass voltage is present, but is disabled for use because the voltage or frequency is outside acceptable limits. | The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this LED will flash, indicating that the bypass is unavailable. | p.32 |