1.0 About This Documentp.71.1 Purpose of This Documentp.71.2 Applicability of This Documentp.72.0 Introductionp.82.1 Descriptionp.8Figure 1 Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power systemp.8Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power systemp.92.2 Applicationsp.92.3 Control and Distribution Cabinets - Typical Configurationsp.10Figure 3 Typical configurations for Helios DC System 4000/48 control, distribution and rectifier ...p.10Table 1 Rectifier cabinetsp.11Table 2 Control and distribution cabinetsp.11Table 3 Auxiliary distribution cabinetsp.113.0 Specificationsp.123.1 Frameworkp.123.1.1 Mechanical Specifications of a Cabinetp.12Table 4 Mechanical specifications of the cabinet (empty)p.123.1.2 Electrical Specifications of the Cabinetsp.123.2 Conventional Controllerp.133.2.1 Mechanical Specifications of the Conventional Controllerp.13Table 5 Mechanical specifications of the Conventional Controllerp.13Figure 4 Front view of the Conventional Controllerp.133.2.2 Electrical Specifications of the Conventional Controllerp.133.3 Distribution Panelsp.143.3.1 Fuse Panelsp.14Mechanical specifications of the fuse panelsp.14Table 6 Mechanical specifications of the fuse panelsp.14Figure 5 Front view of the 20 QFF 0-5 A fuse panelsp.14Table 7 Fuse sizes available for the (20) QFF 0-5 A fuse panelsp.14Figure 6 Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Table 8 Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Figure 7 Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Table 9 Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Figure 8 Front view of the (8) TPN 5-30 A fuse panelsp.16Table 10 Fuse sizes available for the (8) TPN 5-30 A fuse panelsp.16Figure 9 Front view of the (4) RS100P 70-100 A fuse panelsp.16Table 11 Fuse sizes available for the (4) RS100P 70-100 A fuse panelsp.16Figure 10 Front view of the (4) CRS200P 150-200A/(4) CRS200P 150200A (w/load shunts) fuse pa...p.17Table 12 Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150200A (w/load shunt...p.17Figure 11 Front view of the (4) TPL 225-600 A fuse panelsp.17Table 13 Fuse sizes available for the (4) TPL 225-600 A fuse panelsp.17Figure 12 Front view of the (18) TPS 1-70 A fuse panelp.18Table 14 Fuse sizes available for the (18) TPS 1-70 A fuse panelp.18Electrical specifications of the fuse panelsp.19Table 15 Electrical specifications of the fuse panelsp.193.3.2 Circuit Breaker Panelsp.19Mechanical specifications of the circuit breaker panelsp.19Table 16 Mechanical specifications of the circuit breaker panelsp.19Figure 13 Front view of the (24) Plug-In 1-100 A circuit breaker panelp.20Table 17 Plug-in circuit breakers available for the (24) Plug-In 1-100 A circuit breaker panelp.20Figure 14 Front view of the (4) 70-250 A circuit breaker panelp.21Table 18 Circuit breaker sizes available for the (4) 70-250 A circuit breaker panelp.21Figure 15 Front view of the (2) 400 A circuit breaker panelp.22Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panelp.22Figure 16 Front view of the (1) 600-700 A circuit breaker panelp.22Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panelp.22Electrical specifications of the circuit breaker panelsp.23Table 21 Electrical specifications of the circuit breaker panelsp.233.4 Externally Mounted Battery Return Busbarp.243.4.1 Mechanical Specifications of the External Battery Return Busbarp.24Table 22 Mechanical specifications of a single laminationp.24Figure 17 Top and side views of the external battery return busbarp.243.4.2 Electrical Specifications of the External Battery Return Busbarp.243.5 Terminating Assemblies (Optional)p.25Figure 18 Perspective view of the a terminating assembliesp.253.6 MPS300 and MPA100 Power Shelvesp.263.6.1 Mechanical Specifications of the MPS300 and MPA100 Power Shelvesp.26Table 23 Mechanical specifications of the MPS300 and MPA100 power shelvesp.26Figure 19 Front view of the MPS300 power shelf (shown empty)p.26Figure 20 Front view of the MPA100 power shelf (shown empty)p.273.6.2 Electrical Specifications of the Power Shelvesp.273.7 Rectifiersp.273.7.1 Helios Rectifier 100/48p.27Mechanical specifications of the Helios Rectifier 100/48p.27Table 24 Mechanical specifications of the Helios Rectifier 100/48p.27Figure 21 Front view of the Helios Rectifier 100/48p.27Electrical specifications of the Helios Rectifier 100/48p.28Table 25 Electrical specifications of the Helios Rectifier 100/48p.283.7.2 Helios Rectifiers 200I/48 and 200E/48p.28Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Table 26 Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48p.293.7.3 Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48p.30Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48p.303.7.4 Standardsp.303.8 Helios Monitor 3000/48 (Optional)p.313.8.1 Mechanical Specificationsp.31Table 28 Mechanical specifications of the Helios Monitor 3000/48p.31Figure 23 Front view of the Helios Monitor 3000/48 (without the mounting brackets)p.313.8.2 Electrical Specificationsp.313.9 600A and 1200A Battery Disconnect Unit (Optional)p.31Figure 24 600 A Battery Disconnect Unitp.313.10 AC Junction Boxp.32Figure 25 Front view of the AC junction box (with the front panel open)p.323.10.1 Mechanical Specificationsp.32Table 29 Mechanical specifications of the AC junction boxp.323.10.2 Electrical Specificationsp.323.11 Overall Power System Specificationsp.323.11.1 Standardsp.323.11.2 Mechanical Specifications of Fully Equipped Power Cabinetsp.32Table 30 Mechanical specifications of fully equipped power cabinetsp.323.11.3 Electrical Specificationsp.33Electromagnetic compliance (EMC)p.33Electrostatic discharge (ESD) immunityp.333.11.4 Environmental Specificationsp.33Operatingp.33Transportationp.33Storagep.33Heat dissipationp.333.11.5 Floor and Point Loadingp.33Table 31 Floor and point loadingp.334.0 Operationp.344.1 Generalp.344.2 Conventional Controllerp.344.2.1 Front Panelp.34Figure 26 Front view of the Conventional Controllerp.34Visual indicatorsp.34Table 32 Visual indicatorsp.34Table 33 Transmitted alarmsp.35Potentiometersp.35Table 34 Potentiometersp.35Switchesp.36Table 35 Switchesp.36DIP switchesp.36Table 36 DIP switch modulesp.36Figure 27 Shunt range selection settingsp.36Figure 28 Equalize voltage and duration settingsp.37Fusesp.37Table 37 Fusep.37Test pointsp.37Table 38 Test pointsp.374.2.2 Rear Panelp.38Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controllerp.38Terminal blocksp.38Figure 30 Wiring diagram and pin assignment of terminal blocks TB1 to TB4p.39Figure 31 Wiring diagram and pin assignment of terminal blocks TB5 and TB6, and connectors P1 to P26p.40Connectorsp.404.3 MPS300 and MPA100 Power Shelvesp.404.4 Rectifiersp.414.5 AC Junction Boxp.414.6 Distribution Panelsp.414.7 Terminating Assemblies (Optional)p.414.8 Helios Monitor 3000/48 (Optional)p.424.9 600A and 1200 Battery Disconnect Units (Optional)p.425.0 Maintenancep.435.1 Generalp.435.1.1 Helios Monitor 3000/48p.435.1.2 Controller and Rectifiersp.43Cleaningp.43Calibrationp.43Storagep.43Air filter replacementp.44Fan unit replacementp.445.2 Troubleshootingp.45Table 39 Fault diagnosisp.455.3 Addition / Replacement Proceduresp.465.3.1 Addition or Replacement of a Rectifierp.46Adding a Helios Rectifier 100/48p.47Adding a Helios Rectifier 200I/48 or 200E/48p.47Figure 32 AC connections in a Helios Rectifier 200E/48p.48Figure 33 AC connections in the female receptacle for a Helios Rectifier 200I/48 or a Helios Rect...p.49Figure 34 AC connections inside the junction box (top fed shown) for a Helios Rectifier 200E/48p.49Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed systemp.50Figure 36 AC cable routing for the Helios Rectifiers 200E/48 in a bottom fed systemp.505.3.2 Replacing a Rectifierp.51Replacing a Helios Rectifier 100/48p.51Replacing a Helios Rectifier 200I/48 or 200E/48p.525.3.3 Adding or Replacing a Battery Stringp.535.3.4 Replacement of a Distribution Fuse Block or Circuit Breakerp.54Replacing a distribution circuit breakerp.545.3.5 Replacing a Cabinet Alarm Lampp.546.0 Reference Documentsp.557.0 List of Termsp.56
Page 1 of the Liebert 1500 user manual — User Manual
Page 1 · click to enlarge
Page 1
Liebert 1500 diagram (page 1)
Fig. 1

DC P OWER

Helios DC System 4000/48 1500, 3000, 4000 & 6000 A DC Power System

User Manual

Liebert 1500 — User Manual diagram (page 1)
Fig. 2 · User Manual
Page 2 of the Liebert 1500 user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Liebert 1500 user manual
Page 3 of the Liebert 1500 user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

1.0 About This Documentp.71.1 Purpose of This Documentp.71.2 Applicability of This Documentp.72.0 Introductionp.82.1 Descriptionp.8Figure 1 Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power systemp.8Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power systemp.92.2 Applicationsp.92.3 Control and Distribution Cabinets - Typical Configurationsp.10Figure 3 Typical configurations for Helios DC System 4000/48 control, distribution and rectifier ...p.10Table 1 Rectifier cabinetsp.11Table 2 Control and distribution cabinetsp.11Table 3 Auxiliary distribution cabinetsp.113.0 Specificationsp.123.1 Frameworkp.123.1.1 Mechanical Specifications of a Cabinetp.12Table 4 Mechanical specifications of the cabinet (empty)p.123.1.2 Electrical Specifications of the Cabinetsp.123.2 Conventional Controllerp.133.2.1 Mechanical Specifications of the Conventional Controllerp.13Table 5 Mechanical specifications of the Conventional Controllerp.13Figure 4 Front view of the Conventional Controllerp.133.2.2 Electrical Specifications of the Conventional Controllerp.133.3 Distribution Panelsp.143.3.1 Fuse Panelsp.14Mechanical specifications of the fuse panelsp.14Table 6 Mechanical specifications of the fuse panelsp.14Figure 5 Front view of the 20 QFF 0-5 A fuse panelsp.14Table 7 Fuse sizes available for the (20) QFF 0-5 A fuse panelsp.14Figure 6 Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Table 8 Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Figure 7 Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Table 9 Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Figure 8 Front view of the (8) TPN 5-30 A fuse panelsp.16Table 10 Fuse sizes available for the (8) TPN 5-30 A fuse panelsp.16Figure 9 Front view of the (4) RS100P 70-100 A fuse panelsp.16Table 11 Fuse sizes available for the (4) RS100P 70-100 A fuse panelsp.16Figure 10 Front view of the (4) CRS200P 150-200A/(4) CRS200P 150200A (w/load shunts) fuse pa...p.17Table 12 Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150200A (w/load shunt...p.17Figure 11 Front view of the (4) TPL 225-600 A fuse panelsp.17Table 13 Fuse sizes available for the (4) TPL 225-600 A fuse panelsp.17Figure 12 Front view of the (18) TPS 1-70 A fuse panelp.18Table 14 Fuse sizes available for the (18) TPS 1-70 A fuse panelp.18Electrical specifications of the fuse panelsp.19Table 15 Electrical specifications of the fuse panelsp.193.3.2 Circuit Breaker Panelsp.19Mechanical specifications of the circuit breaker panelsp.19Table 16 Mechanical specifications of the circuit breaker panelsp.19Figure 13 Front view of the (24) Plug-In 1-100 A circuit breaker panelp.20Table 17 Plug-in circuit breakers available for the (24) Plug-In 1-100 A circuit breaker panelp.20Figure 14 Front view of the (4) 70-250 A circuit breaker panelp.21Table 18 Circuit breaker sizes available for the (4) 70-250 A circuit breaker panelp.21Figure 15 Front view of the (2) 400 A circuit breaker panelp.22Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panelp.22Figure 16 Front view of the (1) 600-700 A circuit breaker panelp.22Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panelp.22Electrical specifications of the circuit breaker panelsp.23Table 21 Electrical specifications of the circuit breaker panelsp.233.4 Externally Mounted Battery Return Busbarp.243.4.1 Mechanical Specifications of the External Battery Return Busbarp.24Table 22 Mechanical specifications of a single laminationp.24Figure 17 Top and side views of the external battery return busbarp.243.4.2 Electrical Specifications of the External Battery Return Busbarp.243.5 Terminating Assemblies (Optional)p.25Figure 18 Perspective view of the a terminating assembliesp.253.6 MPS300 and MPA100 Power Shelvesp.263.6.1 Mechanical Specifications of the MPS300 and MPA100 Power Shelvesp.26Table 23 Mechanical specifications of the MPS300 and MPA100 power shelvesp.26Figure 19 Front view of the MPS300 power shelf (shown empty)p.26Figure 20 Front view of the MPA100 power shelf (shown empty)p.273.6.2 Electrical Specifications of the Power Shelvesp.273.7 Rectifiersp.273.7.1 Helios Rectifier 100/48p.27Mechanical specifications of the Helios Rectifier 100/48p.27Table 24 Mechanical specifications of the Helios Rectifier 100/48p.27Figure 21 Front view of the Helios Rectifier 100/48p.27Electrical specifications of the Helios Rectifier 100/48p.28Table 25 Electrical specifications of the Helios Rectifier 100/48p.283.7.2 Helios Rectifiers 200I/48 and 200E/48p.28Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Table 26 Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48p.293.7.3 Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48p.30Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48p.303.7.4 Standardsp.303.8 Helios Monitor 3000/48 (Optional)p.313.8.1 Mechanical Specificationsp.31Table 28 Mechanical specifications of the Helios Monitor 3000/48p.31Figure 23 Front view of the Helios Monitor 3000/48 (without the mounting brackets)p.313.8.2 Electrical Specificationsp.313.9 600A and 1200A Battery Disconnect Unit (Optional)p.31Figure 24 600 A Battery Disconnect Unitp.313.10 AC Junction Boxp.32Figure 25 Front view of the AC junction box (with the front panel open)p.323.10.1 Mechanical Specificationsp.32Table 29 Mechanical specifications of the AC junction boxp.323.10.2 Electrical Specificationsp.323.11 Overall Power System Specificationsp.323.11.1 Standardsp.323.11.2 Mechanical Specifications of Fully Equipped Power Cabinetsp.32Table 30 Mechanical specifications of fully equipped power cabinetsp.323.11.3 Electrical Specificationsp.33Electromagnetic compliance (EMC)p.33Electrostatic discharge (ESD) immunityp.333.11.4 Environmental Specificationsp.33Operatingp.33Transportationp.33Storagep.33Heat dissipationp.333.11.5 Floor and Point Loadingp.33Table 31 Floor and point loadingp.334.0 Operationp.344.1 Generalp.344.2 Conventional Controllerp.344.2.1 Front Panelp.34Figure 26 Front view of the Conventional Controllerp.34Visual indicatorsp.34Table 32 Visual indicatorsp.34Table 33 Transmitted alarmsp.35Potentiometersp.35Table 34 Potentiometersp.35Switchesp.36Table 35 Switchesp.36DIP switchesp.36Table 36 DIP switch modulesp.36Figure 27 Shunt range selection settingsp.36Figure 28 Equalize voltage and duration settingsp.37Fusesp.37Table 37 Fusep.37Test pointsp.37Table 38 Test pointsp.374.2.2 Rear Panelp.38Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controllerp.38Terminal blocksp.38Figure 30 Wiring diagram and pin assignment of terminal blocks TB1 to TB4p.39Figure 31 Wiring diagram and pin assignment of terminal blocks TB5 and TB6, and connectors P1 to P26p.40Connectorsp.404.3 MPS300 and MPA100 Power Shelvesp.404.4 Rectifiersp.414.5 AC Junction Boxp.414.6 Distribution Panelsp.414.7 Terminating Assemblies (Optional)p.414.8 Helios Monitor 3000/48 (Optional)p.424.9 600A and 1200 Battery Disconnect Units (Optional)p.425.0 Maintenancep.435.1 Generalp.435.1.1 Helios Monitor 3000/48p.435.1.2 Controller and Rectifiersp.43Cleaningp.43Calibrationp.43Storagep.43Air filter replacementp.44Fan unit replacementp.445.2 Troubleshootingp.45Table 39 Fault diagnosisp.455.3 Addition / Replacement Proceduresp.465.3.1 Addition or Replacement of a Rectifierp.46Adding a Helios Rectifier 100/48p.47Adding a Helios Rectifier 200I/48 or 200E/48p.47Figure 32 AC connections in a Helios Rectifier 200E/48p.48Figure 33 AC connections in the female receptacle for a Helios Rectifier 200I/48 or a Helios Rect...p.49Figure 34 AC connections inside the junction box (top fed shown) for a Helios Rectifier 200E/48p.49Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed systemp.50Figure 36 AC cable routing for the Helios Rectifiers 200E/48 in a bottom fed systemp.505.3.2 Replacing a Rectifierp.51Replacing a Helios Rectifier 100/48p.51Replacing a Helios Rectifier 200I/48 or 200E/48p.525.3.3 Adding or Replacing a Battery Stringp.535.3.4 Replacement of a Distribution Fuse Block or Circuit Breakerp.54Replacing a distribution circuit breakerp.545.3.5 Replacing a Cabinet Alarm Lampp.546.0 Reference Documentsp.557.0 List of Termsp.56
Page 4 of the Liebert 1500 user manual
Page 4 · click to enlarge
Page 4

3.11 Overall Power System Specifications 26

3.11.1 Standards 26 3.11.2 Mechanical Specifications of Fully Equipped Power Cabinets 26 3.11.3 Electrical Specifications 27 3.11.4 Environmental Specifications 27 3.11.5 Floor and Point Loading 27

4.0 OPERATION 28

4.1 General 28

4.2 Conventional Controller 28

4.2.1 Front Panel 28 4.2.2 Rear Panel 32

4.3 MPS300 and MPA100 Power Shelves 34

4.4 Rectifiers 35

4.5 AC Junction Box 35

4.6 Distribution Panels 35

4.7 Terminating Assemblies (Optional) 35

4.8 Helios Monitor 3000/48 (Optional) 36

4.9 600 A and 1200 Battery Disconnect Units (Optional) 36

5.0 MAINTENANCE 37

5.1 General 37

5.1.1 Helios Monitor 3000/48 37 5.1.2 Controller and Rectifiers 37

5.2 Troubleshooting 39

5.3 Addition / Replacement Procedures 40

5.3.1 Addition or Replacement of a Rectifier 40 5.3.2 Replacing a Rectifier 45 5.3.3 Adding or Replacing a Battery String 47 5.3.4 Replacement of a Distribution Fuse Block or Circuit Breaker 48 5.3.5 Replacing a Cabinet Alarm Lamp 48

6.0 REFERENCE DOCUMENTS 49

7.0 LIST OF TERMS 50

Page 5 of the Liebert 1500 user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

1.0 About This Documentp.71.1 Purpose of This Documentp.71.2 Applicability of This Documentp.72.0 Introductionp.82.1 Descriptionp.8Figure 1 Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power systemp.8Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power systemp.92.2 Applicationsp.92.3 Control and Distribution Cabinets - Typical Configurationsp.10Figure 3 Typical configurations for Helios DC System 4000/48 control, distribution and rectifier ...p.10Table 1 Rectifier cabinetsp.11Table 2 Control and distribution cabinetsp.11Table 3 Auxiliary distribution cabinetsp.113.0 Specificationsp.123.1 Frameworkp.123.1.1 Mechanical Specifications of a Cabinetp.12Table 4 Mechanical specifications of the cabinet (empty)p.123.1.2 Electrical Specifications of the Cabinetsp.123.2 Conventional Controllerp.133.2.1 Mechanical Specifications of the Conventional Controllerp.13Table 5 Mechanical specifications of the Conventional Controllerp.13Figure 4 Front view of the Conventional Controllerp.133.2.2 Electrical Specifications of the Conventional Controllerp.133.3 Distribution Panelsp.143.3.1 Fuse Panelsp.14Mechanical specifications of the fuse panelsp.14Table 6 Mechanical specifications of the fuse panelsp.14Figure 5 Front view of the 20 QFF 0-5 A fuse panelsp.14Table 7 Fuse sizes available for the (20) QFF 0-5 A fuse panelsp.14Figure 6 Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Table 8 Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Figure 7 Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Table 9 Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Figure 8 Front view of the (8) TPN 5-30 A fuse panelsp.16Table 10 Fuse sizes available for the (8) TPN 5-30 A fuse panelsp.16Figure 9 Front view of the (4) RS100P 70-100 A fuse panelsp.16Table 11 Fuse sizes available for the (4) RS100P 70-100 A fuse panelsp.16Figure 10 Front view of the (4) CRS200P 150-200A/(4) CRS200P 150200A (w/load shunts) fuse pa...p.17Table 12 Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150200A (w/load shunt...p.17Figure 11 Front view of the (4) TPL 225-600 A fuse panelsp.17Table 13 Fuse sizes available for the (4) TPL 225-600 A fuse panelsp.17Figure 12 Front view of the (18) TPS 1-70 A fuse panelp.18Table 14 Fuse sizes available for the (18) TPS 1-70 A fuse panelp.18Electrical specifications of the fuse panelsp.19Table 15 Electrical specifications of the fuse panelsp.193.3.2 Circuit Breaker Panelsp.19Mechanical specifications of the circuit breaker panelsp.19Table 16 Mechanical specifications of the circuit breaker panelsp.19Figure 13 Front view of the (24) Plug-In 1-100 A circuit breaker panelp.20Table 17 Plug-in circuit breakers available for the (24) Plug-In 1-100 A circuit breaker panelp.20Figure 14 Front view of the (4) 70-250 A circuit breaker panelp.21Table 18 Circuit breaker sizes available for the (4) 70-250 A circuit breaker panelp.21Figure 15 Front view of the (2) 400 A circuit breaker panelp.22Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panelp.22Figure 16 Front view of the (1) 600-700 A circuit breaker panelp.22Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panelp.22Electrical specifications of the circuit breaker panelsp.23Table 21 Electrical specifications of the circuit breaker panelsp.233.4 Externally Mounted Battery Return Busbarp.243.4.1 Mechanical Specifications of the External Battery Return Busbarp.24Table 22 Mechanical specifications of a single laminationp.24Figure 17 Top and side views of the external battery return busbarp.243.4.2 Electrical Specifications of the External Battery Return Busbarp.243.5 Terminating Assemblies (Optional)p.25Figure 18 Perspective view of the a terminating assembliesp.253.6 MPS300 and MPA100 Power Shelvesp.263.6.1 Mechanical Specifications of the MPS300 and MPA100 Power Shelvesp.26Table 23 Mechanical specifications of the MPS300 and MPA100 power shelvesp.26Figure 19 Front view of the MPS300 power shelf (shown empty)p.26Figure 20 Front view of the MPA100 power shelf (shown empty)p.273.6.2 Electrical Specifications of the Power Shelvesp.273.7 Rectifiersp.273.7.1 Helios Rectifier 100/48p.27Mechanical specifications of the Helios Rectifier 100/48p.27Table 24 Mechanical specifications of the Helios Rectifier 100/48p.27Figure 21 Front view of the Helios Rectifier 100/48p.27Electrical specifications of the Helios Rectifier 100/48p.28Table 25 Electrical specifications of the Helios Rectifier 100/48p.283.7.2 Helios Rectifiers 200I/48 and 200E/48p.28Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Table 26 Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48p.293.7.3 Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48p.30Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48p.303.7.4 Standardsp.303.8 Helios Monitor 3000/48 (Optional)p.313.8.1 Mechanical Specificationsp.31Table 28 Mechanical specifications of the Helios Monitor 3000/48p.31Figure 23 Front view of the Helios Monitor 3000/48 (without the mounting brackets)p.313.8.2 Electrical Specificationsp.313.9 600A and 1200A Battery Disconnect Unit (Optional)p.31Figure 24 600 A Battery Disconnect Unitp.313.10 AC Junction Boxp.32Figure 25 Front view of the AC junction box (with the front panel open)p.323.10.1 Mechanical Specificationsp.32Table 29 Mechanical specifications of the AC junction boxp.323.10.2 Electrical Specificationsp.323.11 Overall Power System Specificationsp.323.11.1 Standardsp.323.11.2 Mechanical Specifications of Fully Equipped Power Cabinetsp.32Table 30 Mechanical specifications of fully equipped power cabinetsp.323.11.3 Electrical Specificationsp.33Electromagnetic compliance (EMC)p.33Electrostatic discharge (ESD) immunityp.333.11.4 Environmental Specificationsp.33Operatingp.33Transportationp.33Storagep.33Heat dissipationp.333.11.5 Floor and Point Loadingp.33Table 31 Floor and point loadingp.334.0 Operationp.344.1 Generalp.344.2 Conventional Controllerp.344.2.1 Front Panelp.34Figure 26 Front view of the Conventional Controllerp.34Visual indicatorsp.34Table 32 Visual indicatorsp.34Table 33 Transmitted alarmsp.35Potentiometersp.35Table 34 Potentiometersp.35Switchesp.36Table 35 Switchesp.36DIP switchesp.36Table 36 DIP switch modulesp.36Figure 27 Shunt range selection settingsp.36Figure 28 Equalize voltage and duration settingsp.37Fusesp.37Table 37 Fusep.37Test pointsp.37Table 38 Test pointsp.374.2.2 Rear Panelp.38Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controllerp.38Terminal blocksp.38Figure 30 Wiring diagram and pin assignment of terminal blocks TB1 to TB4p.39Figure 31 Wiring diagram and pin assignment of terminal blocks TB5 and TB6, and connectors P1 to P26p.40Connectorsp.404.3 MPS300 and MPA100 Power Shelvesp.404.4 Rectifiersp.414.5 AC Junction Boxp.414.6 Distribution Panelsp.414.7 Terminating Assemblies (Optional)p.414.8 Helios Monitor 3000/48 (Optional)p.424.9 600A and 1200 Battery Disconnect Units (Optional)p.425.0 Maintenancep.435.1 Generalp.435.1.1 Helios Monitor 3000/48p.435.1.2 Controller and Rectifiersp.43Cleaningp.43Calibrationp.43Storagep.43Air filter replacementp.44Fan unit replacementp.445.2 Troubleshootingp.45Table 39 Fault diagnosisp.455.3 Addition / Replacement Proceduresp.465.3.1 Addition or Replacement of a Rectifierp.46Adding a Helios Rectifier 100/48p.47Adding a Helios Rectifier 200I/48 or 200E/48p.47Figure 32 AC connections in a Helios Rectifier 200E/48p.48Figure 33 AC connections in the female receptacle for a Helios Rectifier 200I/48 or a Helios Rect...p.49Figure 34 AC connections inside the junction box (top fed shown) for a Helios Rectifier 200E/48p.49Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed systemp.50Figure 36 AC cable routing for the Helios Rectifiers 200E/48 in a bottom fed systemp.505.3.2 Replacing a Rectifierp.51Replacing a Helios Rectifier 100/48p.51Replacing a Helios Rectifier 200I/48 or 200E/48p.525.3.3 Adding or Replacing a Battery Stringp.535.3.4 Replacement of a Distribution Fuse Block or Circuit Breakerp.54Replacing a distribution circuit breakerp.545.3.5 Replacing a Cabinet Alarm Lampp.546.0 Reference Documentsp.557.0 List of Termsp.56
Page 6 of the Liebert 1500 user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

1.0 About This Documentp.71.1 Purpose of This Documentp.71.2 Applicability of This Documentp.72.0 Introductionp.82.1 Descriptionp.8Figure 1 Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power systemp.8Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power systemp.92.2 Applicationsp.92.3 Control and Distribution Cabinets - Typical Configurationsp.10Figure 3 Typical configurations for Helios DC System 4000/48 control, distribution and rectifier ...p.10Table 1 Rectifier cabinetsp.11Table 2 Control and distribution cabinetsp.11Table 3 Auxiliary distribution cabinetsp.113.0 Specificationsp.123.1 Frameworkp.123.1.1 Mechanical Specifications of a Cabinetp.12Table 4 Mechanical specifications of the cabinet (empty)p.123.1.2 Electrical Specifications of the Cabinetsp.123.2 Conventional Controllerp.133.2.1 Mechanical Specifications of the Conventional Controllerp.13Table 5 Mechanical specifications of the Conventional Controllerp.13Figure 4 Front view of the Conventional Controllerp.133.2.2 Electrical Specifications of the Conventional Controllerp.133.3 Distribution Panelsp.143.3.1 Fuse Panelsp.14Mechanical specifications of the fuse panelsp.14Table 6 Mechanical specifications of the fuse panelsp.14Figure 5 Front view of the 20 QFF 0-5 A fuse panelsp.14Table 7 Fuse sizes available for the (20) QFF 0-5 A fuse panelsp.14Figure 6 Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Table 8 Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panelsp.15Figure 7 Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Table 9 Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panelsp.15Figure 8 Front view of the (8) TPN 5-30 A fuse panelsp.16Table 10 Fuse sizes available for the (8) TPN 5-30 A fuse panelsp.16Figure 9 Front view of the (4) RS100P 70-100 A fuse panelsp.16Table 11 Fuse sizes available for the (4) RS100P 70-100 A fuse panelsp.16Figure 10 Front view of the (4) CRS200P 150-200A/(4) CRS200P 150200A (w/load shunts) fuse pa...p.17Table 12 Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150200A (w/load shunt...p.17Figure 11 Front view of the (4) TPL 225-600 A fuse panelsp.17Table 13 Fuse sizes available for the (4) TPL 225-600 A fuse panelsp.17Figure 12 Front view of the (18) TPS 1-70 A fuse panelp.18Table 14 Fuse sizes available for the (18) TPS 1-70 A fuse panelp.18Electrical specifications of the fuse panelsp.19Table 15 Electrical specifications of the fuse panelsp.193.3.2 Circuit Breaker Panelsp.19Mechanical specifications of the circuit breaker panelsp.19Table 16 Mechanical specifications of the circuit breaker panelsp.19Figure 13 Front view of the (24) Plug-In 1-100 A circuit breaker panelp.20Table 17 Plug-in circuit breakers available for the (24) Plug-In 1-100 A circuit breaker panelp.20Figure 14 Front view of the (4) 70-250 A circuit breaker panelp.21Table 18 Circuit breaker sizes available for the (4) 70-250 A circuit breaker panelp.21Figure 15 Front view of the (2) 400 A circuit breaker panelp.22Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panelp.22Figure 16 Front view of the (1) 600-700 A circuit breaker panelp.22Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panelp.22Electrical specifications of the circuit breaker panelsp.23Table 21 Electrical specifications of the circuit breaker panelsp.233.4 Externally Mounted Battery Return Busbarp.243.4.1 Mechanical Specifications of the External Battery Return Busbarp.24Table 22 Mechanical specifications of a single laminationp.24Figure 17 Top and side views of the external battery return busbarp.243.4.2 Electrical Specifications of the External Battery Return Busbarp.243.5 Terminating Assemblies (Optional)p.25Figure 18 Perspective view of the a terminating assembliesp.253.6 MPS300 and MPA100 Power Shelvesp.263.6.1 Mechanical Specifications of the MPS300 and MPA100 Power Shelvesp.26Table 23 Mechanical specifications of the MPS300 and MPA100 power shelvesp.26Figure 19 Front view of the MPS300 power shelf (shown empty)p.26Figure 20 Front view of the MPA100 power shelf (shown empty)p.273.6.2 Electrical Specifications of the Power Shelvesp.273.7 Rectifiersp.273.7.1 Helios Rectifier 100/48p.27Mechanical specifications of the Helios Rectifier 100/48p.27Table 24 Mechanical specifications of the Helios Rectifier 100/48p.27Figure 21 Front view of the Helios Rectifier 100/48p.27Electrical specifications of the Helios Rectifier 100/48p.28Table 25 Electrical specifications of the Helios Rectifier 100/48p.283.7.2 Helios Rectifiers 200I/48 and 200E/48p.28Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Table 26 Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48p.28Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48p.293.7.3 Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48p.30Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48p.303.7.4 Standardsp.303.8 Helios Monitor 3000/48 (Optional)p.313.8.1 Mechanical Specificationsp.31Table 28 Mechanical specifications of the Helios Monitor 3000/48p.31Figure 23 Front view of the Helios Monitor 3000/48 (without the mounting brackets)p.313.8.2 Electrical Specificationsp.313.9 600A and 1200A Battery Disconnect Unit (Optional)p.31Figure 24 600 A Battery Disconnect Unitp.313.10 AC Junction Boxp.32Figure 25 Front view of the AC junction box (with the front panel open)p.323.10.1 Mechanical Specificationsp.32Table 29 Mechanical specifications of the AC junction boxp.323.10.2 Electrical Specificationsp.323.11 Overall Power System Specificationsp.323.11.1 Standardsp.323.11.2 Mechanical Specifications of Fully Equipped Power Cabinetsp.32Table 30 Mechanical specifications of fully equipped power cabinetsp.323.11.3 Electrical Specificationsp.33Electromagnetic compliance (EMC)p.33Electrostatic discharge (ESD) immunityp.333.11.4 Environmental Specificationsp.33Operatingp.33Transportationp.33Storagep.33Heat dissipationp.333.11.5 Floor and Point Loadingp.33Table 31 Floor and point loadingp.334.0 Operationp.344.1 Generalp.344.2 Conventional Controllerp.344.2.1 Front Panelp.34Figure 26 Front view of the Conventional Controllerp.34Visual indicatorsp.34Table 32 Visual indicatorsp.34Table 33 Transmitted alarmsp.35Potentiometersp.35Table 34 Potentiometersp.35Switchesp.36Table 35 Switchesp.36DIP switchesp.36Table 36 DIP switch modulesp.36Figure 27 Shunt range selection settingsp.36Figure 28 Equalize voltage and duration settingsp.37Fusesp.37Table 37 Fusep.37Test pointsp.37Table 38 Test pointsp.374.2.2 Rear Panelp.38Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controllerp.38Terminal blocksp.38Figure 30 Wiring diagram and pin assignment of terminal blocks TB1 to TB4p.39Figure 31 Wiring diagram and pin assignment of terminal blocks TB5 and TB6, and connectors P1 to P26p.40Connectorsp.404.3 MPS300 and MPA100 Power Shelvesp.404.4 Rectifiersp.414.5 AC Junction Boxp.414.6 Distribution Panelsp.414.7 Terminating Assemblies (Optional)p.414.8 Helios Monitor 3000/48 (Optional)p.424.9 600A and 1200 Battery Disconnect Units (Optional)p.425.0 Maintenancep.435.1 Generalp.435.1.1 Helios Monitor 3000/48p.435.1.2 Controller and Rectifiersp.43Cleaningp.43Calibrationp.43Storagep.43Air filter replacementp.44Fan unit replacementp.445.2 Troubleshootingp.45Table 39 Fault diagnosisp.455.3 Addition / Replacement Proceduresp.465.3.1 Addition or Replacement of a Rectifierp.46Adding a Helios Rectifier 100/48p.47Adding a Helios Rectifier 200I/48 or 200E/48p.47Figure 32 AC connections in a Helios Rectifier 200E/48p.48Figure 33 AC connections in the female receptacle for a Helios Rectifier 200I/48 or a Helios Rect...p.49Figure 34 AC connections inside the junction box (top fed shown) for a Helios Rectifier 200E/48p.49Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed systemp.50Figure 36 AC cable routing for the Helios Rectifiers 200E/48 in a bottom fed systemp.505.3.2 Replacing a Rectifierp.51Replacing a Helios Rectifier 100/48p.51Replacing a Helios Rectifier 200I/48 or 200E/48p.525.3.3 Adding or Replacing a Battery Stringp.535.3.4 Replacement of a Distribution Fuse Block or Circuit Breakerp.54Replacing a distribution circuit breakerp.545.3.5 Replacing a Cabinet Alarm Lampp.546.0 Reference Documentsp.557.0 List of Termsp.56
Page 7 of the Liebert 1500 user manual — 1.2 Applicability of This Document
Page 7 · click to enlarge
Page 7

1.0 A BOUT T HIS D OCUMENT

1.1 Purpose of This Document

This document provides all the necessary information to operate and maintain a Helios DC Sys- tem 4000/48 power system.

The installation procedures for the Helios DC System 4000/48 power system are covered in instal- lation manual SL-60034.

1.2 Applicability of This Document

This document applies to Helios DC System 4000/48 power systems having any configuration of equipment.

About This Document 1

Page 8 of the Liebert 1500 user manual — 2.0 I NTRODUCTION
Page 8 · click to enlarge
Page 8

2.0 I NTRODUCTION

2.1 Description

The Helios DC System 4000/48 is a positive ground, -48 V DC nominal power system consisting of one control and distribution cabinet and one or more rectifier cabinets. It is available in capacities of 1500, 3000, 4000 and 6000 A. Auxiliary distribution cabinets can be added as required for addi- tional distribution. Remote monitoring, temperature compensation and battery disconnect options are also available. The 1500, 3000 and 4000 A versions use internal -48 V bussing and external BR+ bussing, while the 6000 A version uses overhead bussing. Figure 1 shows a typical bottom fed 4000 A system, while Figure 2 shows a typical 6000 A system.

Figure 1 Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power system

Liebert 1500 — 2.0 I NTRODUCTION diagram (page 8)
Fig. 3

Aux dist. cabinet Main cabinet 1200 A rectifier cabinets

2 Introduction

Page 9 of the Liebert 1500 user manual — 2.2 Applications
Page 9 · click to enlarge
Page 9

Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power system

Liebert 1500 — Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power system diagram (page 9)
Fig. 4 · Figure 2 Front view of a typical 6000 A Helios DC Sy…

Aux dist. cabinets Main cabinet 1200 A rectifier cabinets

Cables are used for inter-cabinet connections (1500, 3000 and 6000 A systems) or connections to the overhead busbars (6000 A system) for ease of expansion on live systems. In a 1500, 3000 or 4000 A systems, the power system battery return (BR) busbar is mounted externally from the cab- inet to facilitate the connections of the battery return cables. In a 6000 A system, a separate BR busbar dedicated to the battery returns for the loads is mounted externally from the overhead busbar duct to facilitate the connections of the load battery return cables.

The Helios DC System 4000/48 provides a variety of monitoring and alarm features, such as high/ low float and high/low voltage alarm, high voltage shutdown, fuse and breaker alarm and rectifier failure alarms.

The Helios DC System 4000/48 uses Helios Rectifiers 200I/48, Helios Rectifiers 200E/48 or Helios Rectifiers 100/48 connected in parallel as building blocks to reach the maximum capacities. The Helios Rectifiers 200I/48 operate from a 380 V to 415 V three phase, 50 or 60 Hz AC source. The Helios Rectifiers 200I/48 operate from a 480 V three phase, 50 or 60 Hz AC source. The Helios Rectifiers 100/operate from a 208 V to 240 V single phase, 50 or 60 Hz AC source.

The 1200 A rectifier cabinet accepts up to six Helios Rectifiers 200I/48 or 200E/48, while the 1000 A rectifier cabinet accepts up to 10 Helios Rectifiers 100/48.

The control and distribution cabinet and the auxiliary distribution cabinets are available with distribution busbar risers of 2000 A or 3000 A capacity.

The cabinets are seismic qualified to zone 4 (Bellcore) when anchored to a concrete floor whose compressive strength is at least 2.11 kg/mm2 (3000 psi) and when equipped with a seismic kit. The cabinets are seismic qualified to zone 2 without the seismic kit.

The cabinets are equipped with a ventilated, lockable door, a ventilated top cover and two rear ventilated panels.

In many applications, such as with DMS, a consistent single-point ground (SPG) topology must be maintained for all associated equipment. The Helios DC System 4000/48 complies with this requirements for single-point grounding (the isolation kit is required).

2.2 Applications

The Helios DC System 4000/48 is designed to operate with DMS systems or any other telecommu- nication systems whose input is nominal -48 V DC and whose current requirements do not exceed 6000 A capacity.

Introduction 3

Page 10 of the Liebert 1500 user manual — 2.3 Control and Distribution Cabinets - Typical Configurations
Page 10 · click to enlarge
Page 10

2.3 Control and Distribution Cabinets - Typical Configurations

Figure 3 shows the front and side views of typical rectifier and distribution cabinets for a Helios DC System 4000/48 (bottom cabled cabinets are illustrated - top cabled versions are available).

Figure 3 Typical configurations for Helios DC System 4000/48 control, distribution and rectifier cabinets

Liebert 1500 — 2.3 Control and Distribution Cabinets - Typical Configurations diagram (page 10)
Fig. 5 · 2.3 Control and Distribution Cabinets - Typical Conf…

4 Introduction

Page 11 of the Liebert 1500 user manual — Table 3 Auxiliary distribution cabinets
Page 11 · click to enlarge
Page 11

Cabinets are available in a variety of configurations as listed in the following tables. Note that for a 6000 A system, the cabling is always at the top.

Table 1 Rectifier cabinets

Cabinet CapacityRectifierCabled top or bottom TypeQty 1200 AHelios Rectifier 200I6Top 1200 AHelios Rectifier 200I6Bottom 1000 AHelios Rectifier 100/4810Top or bottom 1200 AHelios Rectifier 200E6Top 1200 AHelios Rectifier 200E6Bottom 1200 AHelios Rectifier 200E6Top 1200 AHelios Rectifier 200E6Bottom

Table 2 Control and distribution cabinets

Nominal cabinet capacityShunt capacityRiser busbar capacityCabled top or bottom 1500 A2500 A2000 ATop 3000 A4000 A3000 ATop 4000 A5000 A3000 ATop 1500 A2500 A2000 ABottom 3000 A4000 A3000 ABottom 4000 A5000 A3000 ABottom For a 6000 A system, the charge busbars and the shunt are mounted externally from the control and distribution cabinet.

Table 3 Auxiliary distribution cabinets

Nominal cabinet capacityTop busbar capacityRiser busbar capacityCabled top or bottom 2000 A3000 A2000 ATop 2000 A3000 A2000 ABottom 3000 A4000 A3000 ATop 3000 A4000 A3000 ABottom

Introduction 5

Page 12 of the Liebert 1500 user manual — 3.1.2 Electrical Specifications of the Cabinets
Page 12 · click to enlarge
Page 12

3.0 S PECIFICATIONS

3.1 Framework

The Helios DC System 4000/48 uses cabinet type frameworks. The same cabinet design is used for the main control and distribution cabinet, the auxiliary distribution cabinets and the rectifier cab- inets. The cabinet is always equipped with a front door and door frame (lockable, equipped with ground straps, and easily removable for installation or maintenance access), a ventilated top cover made of non-flammable plastic, and two ventilated rear cover panels (equipped with ground strap and easily removable for installation and maintenance access). Bussing and equipment (controller, rectifiers, distribution panels, etc.) are added as required, depending on the use of the cabinet. Seismic bracing is also available as options.

When using the Cable Trough, overhead cabling cannot enter from the front or rear of the system. It must be confined to the system foot print and enter at the ends of the lineup.

The cabinets may be either top or bottom cabled as determined by the location of the bussing.

3.1.1 Mechanical Specifications of a Cabinet

The mechanical specifications of an empty cabinet are listed in Table 4.

Table 4 Mechanical specifications of the cabinet (empty)

Framework typeHeightDepthWidthWeight Cabinet2134 mm (84.0 in.)600 mm (23.6 in.)600 mm (23.6 in.)114 kg (251 lb)

Refer to Figure 3 for typical views of cabinets.

3.1.2 Electrical Specifications of the Cabinets

The electrical specifications of equipped cabinets are as follows:

  • The main control and distribution cabinet for a 1500 A system has a 2000 A busbar riser and a common equipment panel e/w one 1500 A CHG and DISCH busbar and a 2500 A system shunt.
  • The main control and distribution cabinet for a 3000A system has a 3000 A busbar riser and a common equipment panel e/w two 1500 A CHG and DISCH busbars and a 4000 A system shunt.
  • The main control and distribution cabinet for a 4000A system has a 3000 A busbar riser and a common equipment panel e/w three 1500 A CHG and DISCH busbars and a 5000 A system shunt.
  • A 6000 A system has a 3000 A busbar riser in the main control and distribution cabinet (the CHG and DISCH busbar and the shunt are external).
  • The auxiliary distribution cabinet is available with a 2000 or 3000 A busbar riser.
  • A 1200 A rectifier cabinet has 1500 A busbar risers for the DC output of the rectifiers.
Page 13 of the Liebert 1500 user manual — Figure 4 Front view of the Conventional Controller
Page 13 · click to enlarge
Page 13

3.2 Conventional Controller

3.2.1 Mechanical Specifications of the Conventional Controller

The mechanical specifications of the Conventional Controller are listed in Table 5.

Table 5 Mechanical specifications of the Conventional Controller

Figure Height Depth Width Weight

Figure 4 152 mm (6.0 in.)

76 mm (3.0 in.)

584 mm (23 in.)

4.5 kg (10 lb)

Figure 4 Front view of the Conventional Controller

3.2.2 Electrical Specifications of the Conventional Controller

The operating voltage is -48 V DC. Refer to the 4.0 - Operation and the appropriate user manual listed in 6.0 - Reference Documents for a detailed list of specifications, operating parameters and features of the Conventional Controller.

Page 14 of the Liebert 1500 user manual — QFF1A 1.333 A0205202
Page 14 · click to enlarge
Page 14

3.3 Distribution Panels

3.3.1 Fuse Panels

Mechanical specifications of the fuse panels

The mechanical specifications of the fuse panels are listed in Table 6 below.

Table 6 Mechanical specifications of the fuse panels

Panel description Figure Height Width Weight

(20) QFF 0-5 A

60 A max Figure 5 76.2 mm (3.0 in.)

584 mm (23.0 in.)

3 kg (6.6 lb)

(16) QFF 0-5 A &

Figure 6 76.2 mm (3.0 in.)

584 mm (23.0 in.)

5 kg (11.0 lb)

(12) ABS 5-30 A

(16) QFF 0-5 A &

Figure 7 152.4 mm (6.0 in.)

584 mm (23.0 in.)

7 kg (15.4 lb)

(6) TPN 5-30 A

(8) TPN 5-30 A

250 A max Figure 8 152.4 mm (6.0 in.)

584 mm (23.0 in.)

7 kg (15.4 lb)

(4) RS100P 70-100 A

300 A max Figure 9 152.4 mm (6.0 in.)

584 mm (23.0 in.)

8 kg (17.8 lb)

(4) CRS200P 150-200 A

600 A max Figure 10 228.6 mm (9.0 in.)

584 mm (23.0 in.)

22 kg (48.4 lb)

(4) CRS200P 150-200 A

Figure 10 228.6 mm (9.0 in.)

584 mm (23.0 in.)

24 kg (52.9 lb)

(4) TPL 225-600 A

1600 A max Figure 11 304.8 mm (12.0 in.)

584 mm (23.0 in.)

32 kg (70.4 lb)

(18) TPS 1-70 A

600 A max Figure 12 178 mm (7.0 in.)

584 mm (23.0 in.)

35 kg (77.0 lb)

Figure 5 Front view of the 20 QFF 0-5 A fuse panels

FA

The DC output connections are wire wrap or solder.

Table 7 Fuse sizes available for the (20) QFF 0-5 A fuse panels

Fuse type Current (A) CPC

QFF1A 1.333 A0205202

QFF1B 2 A0205203

QFF1C 3 A0205204

QFF1D 5 A0205205

QFF1E 0.18 A0205206

QFF1F 0.25 A0205207

QFF1G 0.5 A0205208

QFF1H 0.75 A0205209

QFF3A DUMMY A0205210

Show 4 more labels / short text on this page
300 A max · 250 A max · (w/load shunts) · 600 A max
Page 15 of the Liebert 1500 user manual — FA
Page 15 · click to enlarge
Page 15

Figure 6 Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panels

FA

The DC output connections are No. 8-32 studs equipped with two hex nuts.

Table 8 Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panels

Liebert 1500 — FA diagram (page 15)
Fig. 6

Figure 7 Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panels

Liebert 1500 — FA diagram (page 15)
Fig. 7

The DC output connections are 0.250-20 studs equipped with two hex nuts.

Table 9 Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panels

Liebert 1500 — FA diagram (page 15)
Fig. 8
Page 16 of the Liebert 1500 user manual — Figure 9 Front view of the (4) RS100P 70-100 A fuse panels
Page 16 · click to enlarge
Page 16

Figure 8 Front view of the (8) TPN 5-30 A fuse panels

Liebert 1500 — Figure 8 Front view of the (8) TPN 5-30 A fuse panels diagram (page 16)
Fig. 9 · Figure 8 Front view of the (8) TPN 5-30 A fuse panel…

The DC output connections are 0.250-20 studs equipped with two hex nuts.

Table 10 Fuse sizes available for the (8) TPN 5-30 A fuse panels

Liebert 1500 — Figure 8 Front view of the (8) TPN 5-30 A fuse panels diagram (page 16)
Fig. 10 · Figure 8 Front view of the (8) TPN 5-30 A fuse panel…

Figure 9 Front view of the (4) RS100P 70-100 A fuse panels

Liebert 1500 — Figure 9 Front view of the (4) RS100P 70-100 A fuse panels diagram (page 16)
Fig. 11 · Figure 9 Front view of the (4) RS100P 70-100 A fuse…

FA (1) (2) (3) (4) (2) (3) (4) (1)

The DC output connections are 0.375-16 studs equipped with two hex nuts.

Table 11 Fuse sizes available for the (4) RS100P 70-100 A fuse panels

Liebert 1500 — Figure 9 Front view of the (4) RS100P 70-100 A fuse panels diagram (page 16)
Fig. 12 · Figure 9 Front view of the (4) RS100P 70-100 A fuse…
Page 17 of the Liebert 1500 user manual — Figure 11 Front view of the (4) TPL 225-600 A fuse panels
Page 17 · click to enlarge
Page 17

Figure 10 Front view of the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load shunts) fuse panels

Liebert 1500 — Figure 10 Front view of the (4) CRS200P 150-200A/(4) CRS200P 150200A (w/load shunts) fuse pa... diagram (page 17)
Fig. 13 · Figure 10 Front view of the (4) CRS200P 150-200A/…

The DC output connections are 0.50-13 studs equipped with two hex nuts.

Table 12 Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load shunts) fuse panels

Liebert 1500 — Figure 10 Front view of the (4) CRS200P 150-200A/(4) CRS200P 150200A (w/load shunts) fuse pa... diagram (page 17)
Fig. 14 · Figure 10 Front view of the (4) CRS200P 150-200A/…

Figure 11 Front view of the (4) TPL 225-600 A fuse panels

Liebert 1500 — Figure 11 Front view of the (4) TPL 225-600 A fuse panels diagram (page 17)
Fig. 15 · Figure 11 Front view of the (4) TPL 225-600 A fuse p…

The DC output connections are busbar angles that can accept 535MCM or 750MCM cables, or the metric equivalent. The lugs must be for two 1/2” dia. bolts at 1-3/4” c-c.

Table 13 Fuse sizes available for the (4) TPL 225-600 A fuse panels

Liebert 1500 — Figure 11 Front view of the (4) TPL 225-600 A fuse panels diagram (page 17)
Fig. 16 · Figure 11 Front view of the (4) TPL 225-600 A fuse p…
Page 18 of the Liebert 1500 user manual — 1 A0601322
Page 18 · click to enlarge
Page 18

Figure 12 Front view of the (18) TPS 1-70 A fuse panel

MAX FUSE 70A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 UNIT AMPS

FA

LOAD

FUSE PANEL NT6C21XX 600 A MAX PANEL CAPACITY

Can accept maximum 1/0 AWG cables and requires one-hole lugs for 1/4” diameter studs.

Table 14 Fuse sizes available for the (18) TPS 1-70 A fuse panel

Fuse type Current (A) CPC

1 A0601322

3 A0601323

5 A0601325

6 A0601326

10 A0601327

15 A0601328

25 A0601330

30 A0601331

40 A0601332

50 A0601333

60 A0601334

70 A0601335

DC power (TPS)

Page 19 of the Liebert 1500 user manual — Table 16 Mechanical specifications of the circuit breaker panels
Page 19 · click to enlarge
Page 19

Electrical specifications of the fuse panels

The electrical specifications of the fuse panels are described in Table 15.

Table 15 Electrical specifications of the fuse panels

Busbar capacity Quantity Capacity

(20) QFF 0-5 A

60 A max Figure 5 20 0-5 A 60 A

(16) QFF 0-5 A &

Figure 6 16 12 0-5 A 0-30 A 300 A

(12) ABS 5-30 A

(16) QFF 0-5 A &

Figure 7 8 0-30 A 250 A

(6) TPN 5-30 A

(8) TPN 5-30 A

250 A max Figure 8 8 31-60 A 300 A

(4) RS100P 70-100 A

300 A max Figure 9 4 70-100 A 300 A

(4) CRS200P 150-200 A

Figure 10 4 101-200 A 600 A

(4) CRS200P 150-200 A (w/load shunts)

(4) TPL 225-600 A

1600 A max Figure 11 4 225-600 A 1600 A

(18) TPS 1-70 A

600 A max Figure 12 18 0-70 A 600 A

3.3.2 Circuit Breaker Panels

Mechanical specifications of the circuit breaker panels

The mechanical specifications of the circuit breaker panels are described in Table 16.

Table 16 Mechanical specifications of the circuit breaker panels

Panel description Figure Height Width Weight

(24) Plug-In 1-100 A

900 A max Figure 13 165 mm (6.5 in.)

584 mm (23.0 in.)

9.1kg (20 lb.)

(4) 70-250 A 900 A max * Figure 14 178 mm (7.0 in.)

584 mm (23.0 in.)

10.5 kg (25 lb)

(2) 400 A Figure 15 178 mm (7.0 in.)

584 mm (23.0 in.)

10.5 kg (25 lb)

(1) 600-700 A Figure 16 178 mm (7.0 in.)

584 mm (23.0 in.)

10.5 kg (25 lb)

* The 250 A circuit breaker has two poles, thus the panel can accommodate a maximum of two 250 A breakers. An alarm circuit pack with an alarm indication LED is standard on all panels.

Show 6 more labels / short text on this page
Fuses · Panel number Figure · 300 A max · 250 A max · 600 A max · 600 A max
Page 20 of the Liebert 1500 user manual — 1 A A0723076 A0722751
Page 20 · click to enlarge
Page 20

Figure 13 Front view of the (24) Plug-In 1-100 A circuit breaker panel

The DC output connections vary according to the circuit breaker capacity: maximum cable size is 2/0AWG. The lugs must be for 3/8” dia. bolts at 1” c-c.

Refer to Table 21 for the maximum panel capacity.

Table 17 Plug-in circuit breakers available for the (24) Plug-In 1-100 A circuit breaker panel

current CPC Std Trip CPC Mid Trip

1 A A0723076 A0722751

5 A A0723033 A0722752

10 A A0723035 A0722754

15 A A0723037 A0722755

20 A A0723007 A0722695

25 A A0723039 A0722707

30 A A0723040 A0722715

35 A A0723041 A0722717

40 A A0723042 A0722721

45 A A0723069 A0722722

50 A A0723008 A0722726

60 A A0723070 A0722727

65 A A0723071 A0722497

70 A A0723072 A0722732

80 A A0723074 A0722733

90 A A0723077 A0722750

100 A A0723009 A0722496

Nominal

Page 21 of the Liebert 1500 user manual — LOAD
Page 21 · click to enlarge
Page 21

Figure 14 Front view of the (4) 70-250 A circuit breaker panel

CIRCUIT BREAKER PANEL

900A MAX. PANEL CAPACITY

(4) 70-250 A

NT6C12EE

FA

REL ( ) SER NO ( )

UNIT AMPS

225 1 2 3 4

LOAD

The DC output connections can accommodate two 4/0 cables back to back for each circuit breaker. The required lugs can be either for two 3/8” holes at 1” c-c or for two 1/2” holes at 1-3/4” c-c.

Refer to Table 21 for the maximum panel capacity.

Table 18 Circuit breaker sizes available for the (4) 70-250 A circuit breaker panel

70 A (no shunt) A0617079

70 A (with shunt) A0617080

70 A (with relay trip) A0617081

100 A (no shunt) A0616667

100 A (with shunt) A0616668

100 A (with relay trip) A0616669

150 A (no shunt) A0616670

150 A (with shunt) A0616671

150 A (with relay trip) A0616672

200 A (no shunt) A0616673

200 A (with shunt) A0616674

200 A (with relay trip) A0616675

225 A (no shunt) A0605489

225 A (with shunt) A0605490

225 A (with relay trip) A0605492

250 A (no shunt) A0616676

250 A (with shunt) A0616677

250 A (with relay trip) A0616678

The (4) 70-250 A circuit breaker panel can accept up to:

  • four breakers (70 to 225 A) mid trip with or without the metering shunt option (1 pole breakers)
  • two breakers (70 to 225 A) mid trip with the relay trip option (takes a 2 pole space)
  • two breakers (250 A) mid trip with or without the metering shunt option (takes a two pole breaker)
  • one (250 A) breaker mid trip with the relay trip option (takes a 3 pole space)

Nominal current CPC

Page 22 of the Liebert 1500 user manual — Figure 16 Front view of the (1) 600-700 A circuit breaker panel
Page 22 · click to enlarge
Page 22

Figure 15 Front view of the (2) 400 A circuit breaker panel

Liebert 1500 — Figure 15 Front view of the (2) 400 A circuit breaker panel diagram (page 22)
Fig. 17 · Figure 15 Front view of the (2) 400 A circuit breake…

The DC output connections can accommodate two 750 MCM cables back to back for each circuit breaker. The required lugs must be for two 1/2” holes at 1-3/4” c-c.

Refer to Table 21 for the maximum panel capacity.

Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panel

Liebert 1500 — Figure 15 Front view of the (2) 400 A circuit breaker panel diagram (page 22)
Fig. 18 · Figure 15 Front view of the (2) 400 A circuit breake…

The panel accepts up to:

  • two breakers (400 A) mid trip with or without the metering shunt option
  • one breaker (400 A) mid trip with the relay trip option (takes a 3 pole space)

Figure 16 Front view of the (1) 600-700 A circuit breaker panel

Liebert 1500 — Figure 16 Front view of the (1) 600-700 A circuit breaker panel diagram (page 22)
Fig. 19 · Figure 16 Front view of the (1) 600-700 A circuit br…

The DC output connections can accommodate four 750 MCM cables back to back. The lugs must be for two 1/2” bolts at 1-3/4” c-c.

Refer to Table 21 for the available circuit breakers and the maximum panel capacity.

Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panel

600 A (no shunt) P0875700

600 A (e/w shunt) P0875701

600 A (e/w relay trip) P0875702

Nominal current CPC

Page 23 of the Liebert 1500 user manual — (4) 70-250 A
Page 23 · click to enlarge
Page 23

Electrical specifications of the circuit breaker panels

The electrical specifications of the circuit breaker panels are described in Table 21.

Table 21 Electrical specifications of the circuit breaker panels

Busbar capacity Max. Quantity Capacity

(24) Plug-In 1-100 A

900 A max Figure 13 24 1-100 A 900A

(4) 70-250 A

900 A max Figure 14 4 70-250 A 900 A

(2) 400 A Figure 15 2 400 A 900 A

(1) 600-700 A Figure 16 1 600 A 900 A

Circuit breakers · Panel description · Figure

Page 24 of the Liebert 1500 user manual — 3.4.2 Electrical Specifications of the External Battery Return Busbar
Page 24 · click to enlarge
Page 24

3.4 Externally Mounted Battery Return Busbar

The battery return busbar is designed to mount on the overhead racking for 6000 A systems and top cabled 1500, 3000 or 4000 A power systems. It can also be mounted on a wall or on the floor below the raised floor for bottom cabled 1500, 3000 or 4000 A power systems (which are assumed to be installed on a raised, computer type floor).

3.4.1 Mechanical Specifications of the External Battery Return Busbar

The external battery return busbar kit consists of a group of single busbar laminations and attachment hardware assembled as shown in Figure 17 (6000 A shown). The kit can grow verti- cally in such a way as to maintain the 3-ft maximum radius grounding requirement. Laminations are added as required to increase the capacity. The mechanical specifications of a single lamina- tion are listed in Table 22.

Table 22 Mechanical specifications of a single lamination

Figure Length Width Thickness

Figure 17 863.6 mm (34 inches)

152.4 mm (6 inches)

12.7 mm (0.5 inches)

Figure 17 Top and side views of the external battery return busbar

Liebert 1500 — Figure 17 Top and side views of the external battery return busbar diagram (page 24)
Fig. 20 · Figure 17 Top and side views of the external battery…

Side view of the external ground bar installed on

* For a 1500 A system, only the bottom level is provided for the external battery return ground bar.

3.4.2 Electrical Specifications of the External Battery Return Busbar

A single busbar lamination has a current carrying capacity of 3000 A.

Page 25 of the Liebert 1500 user manual — Figure 18 Perspective view of the a terminating assemblies
Page 25 · click to enlarge
Page 25

3.5 Terminating Assemblies (Optional)

The optional terminating assembly allows top access connections for up to six loads. Refer to Figure 18. Each load position is rated at 600 A and can accept up to three lugs having 1” or 1-3/4” c-c hole spacing, for cables up to 777 kcmil.

The terminating assembly is bolted to the top of the main or auxiliary distribution cabinets and, therefore, increase the cabinet height by 12 inches. The weight of the terminating assembly is 12.5 kg (27.6 lb).

An optional Lexan™ protective cover is available to protect the connections of the load cables.

Figure 18 Perspective view of the a terminating assemblies

Liebert 1500 — Figure 18 Perspective view of the a terminating assemblies diagram (page 25)
Fig. 21 · Figure 18 Perspective view of the a terminating asse…
Page 26 of the Liebert 1500 user manual — Figure 19 Front view of the MPS300 power shelf (shown empty)
Page 26 · click to enlarge
Page 26

3.6 MPS300 and MPA100 Power Shelves

The MPS300 and MPA100 power shelves are required for the Helios Rectifier 100/48, which is a plug-in type rectifier. The MPA100 power shelf supports one Helios Rectifier 100/48, while the MPS300 shelf can support up to three Helios Rectifiers 100/48.

3.6.1 Mechanical Specifications of the MPS300 and MPA100 Power Shelves

The mechanical specifications of the power shelves are listed in Table 23.

Table 23 Mechanical specifications of the MPS300 and MPA100 power shelves

Liebert 1500 — Table 23 Mechanical specifications of the MPS300 and MPA100 power shelves diagram (page 26)
Fig. 22 · Table 23 Mechanical specifications of the MPS300 and…

Figure 19 Front view of the MPS300 power shelf (shown empty)

Liebert 1500 — Figure 19 Front view of the MPS300 power shelf (shown empty) diagram (page 26)
Fig. 23 · Figure 19 Front view of the MPS300 power shelf (show…
Page 27 of the Liebert 1500 user manual — Figure 21 Front view of the Helios Rectifier 100/48
Page 27 · click to enlarge
Page 27

Figure 20 Front view of the MPA100 power shelf (shown empty)

Liebert 1500 — Figure 20 Front view of the MPA100 power shelf (shown empty) diagram (page 27)
Fig. 24 · Figure 20 Front view of the MPA100 power shelf (show…

3.6.2 Electrical Specifications of the Power Shelves

Each rectifier position provides interconnection points for AC input (208 to 240 V nominal), DC output (-48 V nominal) and control and alarm signals.

3.7 Rectifiers

The Helios system 4000/48 can be equipped with Helios Rectifiers 100/48 for single phase 208/240 V AC operation, with Helios Rectifiers 200I/48 for three phase 380/415 V AC operation, or with Helios Rectifiers 200E/48 for three phase 480 V AC operation.

3.7.1 Helios Rectifier 100/48

Mechanical specifications of the Helios Rectifier 100/48

The mechanical specifications of the Helios Rectifier 100/48 are listed in Table 24.

Table 24 Mechanical specifications of the Helios Rectifier 100/48

Figure Height Depth Width Weight

Figure 21 178 mm (7.0 in.)

305 mm (12.0 in.)

584 mm (23.0 in.)

22.2 kg (49 lb)

Figure 21 Front view of the Helios Rectifier 100/48

Liebert 1500 — Figure 21 Front view of the Helios Rectifier 100/48 diagram (page 27)
Fig. 25 · Figure 21 Front view of the Helios Rectifier 100/48
Page 28 of the Liebert 1500 user manual — Table 26 Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48
Page 28 · click to enlarge
Page 28

Electrical specifications of the Helios Rectifier 100/48

The electrical specifications of the Helios Rectifier 100/48 are listed in Table 25.

Table 25 Electrical specifications of the Helios Rectifier 100/48

Input voltage208/240 V AC, 1-phase, 47-63 Hz Input voltage range: 176 to 264 V AC

Input current: 31 A nominal at 208 V AC input and -56 V DC, 100 A output

Recommended AC service input:

50 A, two pole AC circuit breaker

Output voltage: Float: -48 to -58 V DC Equalize: 0 to 4 V DC above Float Maximum: -59.5 V DC

Output current: 100 A per rectifier 100 A for a one position shelf 300 A for a three position shelf

Input protection: A two pole / 45 A circuit breaker opens both lines.

Output protection: The rectifier is protected by a 120 A circuit breaker at the output. The output current is limited to a value adjustable from 50% to 105% of the rated capacity of the rectifier. This circuit is factory set to 105 A.

Output regulation: The rectifier output voltage is automatically regulated to remain within ±0.5% of the selected value under all load conditions and within the specified input voltage, frequency, and ambient temperature ranges. And within + 1% for any combinations of specified input, output and environmental conditions.

Efficiency: Efficiency is better than 88% at a nominal input voltage of 208/240 V AC and an output load greater than 40 A.

Power factor: Power factor is 0.99 at a nominal input voltage of 208 V AC and output loads greater than 40 A.

Electromagnetic interference (EMI):

The rectifier meets the FCC requirements for conducted and radiated EMI for Class “A” equipment.

Heat dissipation763 W (2606 Btu/hr)

3.7.2 Helios Rectifiers 200I/48 and 200E/48

Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48

The mechanical specifications of the Helios Rectifier 200I/48 and 200E/48 are listed in Table 26.

Table 26 Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48

Figure Height Depth Width Weight

Figure 22 254 mm (10 in.)

559 mm (22 in.)

521 mm (20.5 in.)

42.3 kg (93 lb)

Parameter Specification

Page 29 of the Liebert 1500 user manual — Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48
Page 29 · click to enlarge
Page 29

Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48

Liebert 1500 — Figure 22 Front view of the Helios Rectifiers 200I/48 and 200E/48 diagram (page 29)
Fig. 26 · Figure 22 Front view of the Helios Rectifiers 200I/4…
Page 30 of the Liebert 1500 user manual — 3.7.4 Standards
Page 30 · click to enlarge
Page 30

3.7.3 Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48

The electrical specifications of the Helios Rectifiers 200I/48 and 200E/48 are listed in Table 27.

Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48

Input voltage Helios Rectifier 200I/48:

380/415 V AC, three phase, 47-63 Hz Input voltage range: 330 to 475 V AC Helios Rectifier 200E/48:

480 V AC, three phase, 47-63 Hz Input voltage range: 430 to 520 V AC

Input current Helios Rectifier 200I/48: 18.3 A RMS nominal at 380 V AC input and -54 V DC, 200 A output (24 A RMS worst case) Helios Rectifier 200E/48: 15 A RMS nominal at 480 V AC input and -54 V DC, 200 A output (17 A RMS worst case)

Input protection A 3 pole / 25 A circuit breaker opens all three lines.

Recommended AC service input

30 A, 3 pole AC circuit breaker

Output voltage Float: -46 to -58 V DC Equalize: 0 to 4 V DC above Float Maximum: -60 V DC

Output current 200 A nominal Adjustable between 100 and 210 A

Output protection The rectifier is protected by a 250 A circuit breaker at the output. The output current is limited to a value adjustable from 50% to 105% of the rated capacity of the rectifier. This circuit is factory set to 205 A.

Output regulation The rectifier output voltage is automatically regulated to remain within ±0.5% of the selected value under all load conditions and within the specified input voltage, frequency, and ambient temperature ranges. And within + 1% for any combinations of specified input, output and environmental conditions.

Efficiency Efficiency is better than 89% at nominal input voltage and an output load greater than 80 A.

Power factor Power factor is better than 0.99 at nominal input voltage and an output load greater than 80 A.

The rectifier meets the FCC requirements for conducted and radiated EMI for Class “B” equipment.

Heat dissipation 1,335 W (4,558 Btu/hr) at -54 V DC, 200 A output

Total harmonic distortion (THD)

THD is less than 5% between half load and full load at nominal input voltage

3.7.4 Standards

The following standards also apply to the rectifiers:

  • ANSI Std. C62.41/IEEE Std. 587-1980, Class A and B lightning surge 6000 V, 3000 A, 1.2 x 50 ms impulse, 10 hits per second
  • ANSI Std. C82.41 oscillatory surge 2500 V, 0.5 ms impulse, 100kHz positive/negative oscillating decay
  • Bellcore TR-TSY-000947
  • IEC-950, VDE EN 60950, EN 41003
  • CISPR 22, Class A
  • CE mark

Parameter Specification · Electromagnetic interference (EMI)

Page 31 of the Liebert 1500 user manual — Figure 24 600 A Battery Disconnect Unit
Page 31 · click to enlarge
Page 31

3.8 Helios Monitor 3000/48 (Optional)

3.8.1 Mechanical Specifications

The mechanical specifications of the Helios Monitor 3000/48 are listed in Table 28.

Table 28 Mechanical specifications of the Helios Monitor 3000/48

Figure Height Depth Width Weight

Figure 23 45 mm (1.75 in.)

222 mm (8.75 in.)

280 mm (11.0 in.)

2.8 kg (6.2 lb)

The above dimensions are without the mounting brackets. The weight may vary slightly depend- ing on the number and type of analog interface modules installed in the unit.

Figure 23 Front view of the Helios Monitor 3000/48 (without the mounting brackets)

Liebert 1500 — Table 28 Mechanical specifications of the Helios Monitor 3000/48 diagram (page 31)
Fig. 27 · Table 28 Mechanical specifications of the Helios Mon…

ROTARY SWITCHES 12 DIGIT ALPHA-NUMERIC DISPLAY 4 PUSH-BUTTON KEYPAD

3.8.2 Electrical Specifications

The input voltage of the Helios Monitor 3000/48 is -48 V DC nominal, with a range of -42 V DC to -60 V DC.

The input current drain is 400 mA. This current drain may vary slightly depending upon the number and type of analog interface modules installed in the unit.

For more detailed electrical specifications of the Helios Monitor 3000/48, refer to the appropriate user manual listed in 6.0 - Reference Documents.

3.9 600 A and 1200 A Battery Disconnect Unit (Optional)

The Battery Disconnect Units are 11 inches high and provides for 500 mm (19 in.) or 600 mm (23 in.) framework mounting or wall mounting. The units are equipped with a heavy duty circuit breaker that can be used to manually or automatically disconnect a battery string. Reconnect is manual only. The breaker is mid trip and equipped with a relay trip feature.

Figure 24 600 A Battery Disconnect Unit

Liebert 1500 — Figure 24 600 A Battery Disconnect Unit diagram (page 31)
Fig. 28 · Figure 24 600 A Battery Disconnect Unit

For more detailed electrical specifications of the Battery Disconnect Unit, refer to the user man- ual, SL-60040.

Page 32 of the Liebert 1500 user manual — 3.11.2 Mechanical Specifications of Fully Equipped Power Cabinets
Page 32 · click to enlarge
Page 32

3.10 AC Junction Box

The AC junction box is required as an AC connection interface in rectifier cabinets where the Helios Rectifier 200E/48 is used.

Figure 25 Front view of the AC junction box (with the front panel open)

Liebert 1500 — 3.10 AC Junction Box diagram (page 32)
Fig. 29 · 3.10 AC Junction Box

Six receptacles to plug the cables from the rectifiers

TB1 TB2 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12

3.10.1 Mechanical Specifications

The junction box is made of zinc plated steel and can accommodate up to six one-inch rigid or flex- ible conduits. The mechanical specifications are listed in Table 29.

Table 29 Mechanical specifications of the AC junction box

Figure Height Depth Width

Figure 25 264 mm (10.4 in.)

284 mm (11.2 in.)

521 mm (20.5 in.)

3.10.2 Electrical Specifications

The junction box is designed to accommodate six 3-phase circuits (3 wires plus ground) at a maxi- mum voltage of 600 V AC and a capacity of 30 A per circuit.

3.11 Overall Power System Specifications

3.11.1 Standards

The Helios DC System 4000/48 meets the following North American and European standards:

  • UL-1801
  • CSA 22.2 (#0.7, #225)
  • TR-TSY-000406
  • CE
  • VDE

3.11.2 Mechanical Specifications of Fully Equipped Power Cabinets

Table 30 Mechanical specifications of fully equipped power cabinets

Liebert 1500 — 3.11.2 Mechanical Specifications of Fully Equipped Power Cabinets diagram (page 32)
Fig. 30 · 3.11.2 Mechanical Specifications of Fully Equipped P…
Page 33 of the Liebert 1500 user manual — Table 31 Floor and point loading
Page 33 · click to enlarge
Page 33

3.11.3 Electrical Specifications Refer to the individual component’s specifications.

Electromagnetic compliance (EMC) The equipment contained in the power system complies with the specifications of FCC, Part 15, Subpart B for class A equipment, CSA 108.8 for class A and CISPR 22 for class A.

Electrostatic discharge (ESD) immunity No equipment damage or malfunctions shall occur when electrostatic discharge voltages of sever- ity level 2 and 4, as specified by IEC-801-2, are applied to exposed parts of the power system.

3.11.4 Environmental Specifications

Operating

Temperature0° to +50°C (32° to 122°F)
Humidity0 to 95% non-condensing
AltitudeSea level to 2134 m (7000 ft)

Transportation

During transportation the equipment may be subjected to the following conditions without damage:

Temperature-50° to +75°C (-58° to +167°F)
Humidity0 to 95% (non condensing) 4kPa max. WVP for 10 days
VibrationTR-NWT-000063 section 5.4.4 Transportation Vibration (packaged equipment)
ShockTR-NWT-000063, Section 5.4.1 Handling Drop Tests, and Section 5.4.3 Installation Shop Tests

Storage

Temperature-50° to +75°C (-58° to +167°F)
Humidity0 to 95% (non condensing) 4kPa max. WVP for 10 days

Heat dissipation A Helios DC System 4000/48 rectifier cabinet equipped with six Helios Rectifier 200I/48 or 200E/ 48 will dissipate a maximum of 8,010 watts or 27,350 Btu/hr.

3.11.5 Floor and Point Loading The floor loading is based on a footprint of 600 mm x 600 mm (23.6 in. x 23.6 in.) plus a 30-inch aisle width (15 inches front and rear). The point loading is based on distributing the cabinet weight over four shims, each with an assumed area of 25.8 cm2 (4 in.2). See Figure 1 for a typical system configuration for floor and point loading calculations.

Table 31 Floor and point loading

Cabinet type Floor loading Point loading

Control and distribution cabinet 41.3 kN/sq m (90.9 lb/sq ft) 34.5 N/sq cm (50 lb/sq in.)

Auxiliary distribution cabinet 32.3 kN/sq m (71 lb/sq ft) 26.9 N/sq cm (39 lb/sq in.)

Rectifier cabinet 50.1 kN/sq m (110.2 lb/sq ft) 41.8 N/sq cm (60.6 lb/sq in.)

Page 34 of the Liebert 1500 user manual — Table 32 Visual indicators
Page 34 · click to enlarge
Page 34

4.0 O PERATION

4.1 General

This chapter describes the control, adjustment and operational features of the Helios DC System 4000/48.

4.2 Conventional Controller

The Conventional Controller monitors the operation of the entire power plant. It monitors all the alarms, and it controls and monitors the rectifiers.

Provision is made on the back of the Conventional Controller to extend any occurring alarm to the alarm center through the facilities provided in the powered equipment.

All of the control switches, potentiometers, operational and alarm visual indications are located at the front of the Conventional Controller.

4.2.1 Front Panel

The front panel of the Conventional Controller is provided with the control, alarm and operational features shown in Figure 26 and described in the following subsections.

Figure 26 Front view of the Conventional Controller

Visual indicators A 4.5 digit red LED readout to display the system current and voltage, and 18 LEDs to display the alarm conditions as described in Table 32. All alarm conditions are also displayed by a red incan- descent cabinet alarm lamp.

Table 32 Visual indicators

RECT FAN Rectifier Fan Failure yellow

EQL Equalize On yellow

FA Fuse Failure Alarm (Internal to the Controller) red

DFA Discharge Fuse Alarm red

CFA (not used) Charge Fuse Alarm red

RFA MIN Rectifier Failure Alarm Minor yellow

RFA MAJ Rectifier Failure Alarm Major red

ACO Alarm cut-off red

HVSD High Voltage Shutdown Alarm red

HV High Voltage Alarm red

LV Low Voltage Alarm red

HF High Float Alarm yellow

LF Low Float Alarm yellow

LVD Low Voltage Disconnect red

BOD Battery On Discharge red

LOP Loss of Phase red

AUX 1 (BDA) Auxiliary Major red

AUX 2 Auxiliary Minor yellow

Designation Description Color · 28 Operation

Page 35 of the Liebert 1500 user manual — Table 34 Potentiometers
Page 35 · click to enlarge
Page 35

Table 33 Transmitted alarms

RECT FAN (1 - Form C contacts)

RFA MIN (1 - Form C contacts)

RFA MAJ (1 - Form C contacts)

H/L FLOAT (2 - Form C contacts)

EQL ALM (1 - Form C contacts)

H/L VOLT (2 - Form C contacts)

FA (1 - Form C contacts)

CHG FUSE (1 - Form C contacts)

DISCH FUSE (1 - Form C contacts)

LVD (1 - Form C contacts)

LOSS OF AC VOLT (1 - Form C contacts)

AUX 1 ALM (2 - Form C contacts)

AUX 2 ALM (2 - Form C contacts)

HVSD (1 - Form C contacts)

BOD (1 - Form C contacts)

MIN VIS (note 2) (2 - Form C contacts)

MAJ VIS (note 2) (2 - Form C contacts)

MIN AUD (2 - Form C contacts)

MAJ AUD (2 - Form C contacts)

MINOR VIS (2) and MAJ VIS (2) are used for the cabinet alarm lamp.

Potentiometers

Twelve potentiometers for the adjustment of alarm and control functions as described in Table 34.

Table 34 Potentiometers

HVSD High Voltage Shutdown

HV High Voltage Alarm

LV Low Voltage Alarm

HF High Float Alarm

LF Low Float Alarm

LVD Low Voltage Disconnect

BOD Battery On Discharge

VOLT ADJ Plant Voltage Adjustment

REF CAL Reference Calibration

METER ADJ Meter Adjustment

AMP ADJ Ampere Adjustment

LVR Low Voltage Reconnect

Alarm Description · Designation Description · Operation 29

Page 36 of the Liebert 1500 user manual — = SWITCH IS ON
Page 36 · click to enlarge
Page 36

Switches

Four switches for the control of functions as described in Table 35.

Table 35 Switches

EQUALIZE MAN/AUTO Used to activate or deactivate the equalize function.

ACO Used to cancel the audible alarm signal.

CALIBRATE NORM/CAL Used to activate or deactivate the calibration function.

CONT rotary switch Six position switch: OFF, AMP, CHG VOLT, BAT VOLT, CAL, TST DISPL

DIP switches

Three DIP switch modules for the setting of functions as described in Table 36 and as shown in Figure 27 and Figure 28.

Table 36 DIP switch modules

SHUNT SELECT To select the shunt size

TIMER To select the duration of the equalize

VOLT To select the equalize voltage

Figure 27 Shunt range selection settings

S1 RANGE AMPS

MIN-MAX

1 2 3 4 5 6

= SWITCH IS ON

Show 12 more labels / short text on this page
Designation Description · Designation Description · 55 to 100 · 100 to 170 · 170 to 340 · 340 to 500 · 500 to 1000 · 1000 to 1700 · 1700 to 3400 · 3400 to 7000 · 7000 to 14000 · 30 Operation
Page 37 of the Liebert 1500 user manual — Table 38 Test points
Page 37 · click to enlarge
Page 37

Figure 28 Equalize voltage and duration settings

TIMER

VOLT

Switch # 1 2 3 4 5 6

Switch # 1 2 3

10 sec.

20 sec.

OFF ON

38 sec.

1.25 h

3.0 h

5.0 h

ON OFF

: switch in the ON position

Fuses

Thirty-four fuses for circuit protection as described in Table 37. Except for the ABS fuse, which is small tube type (9/32” dia x 1-1/4” long), all fuses are of the QFF type.

Table 37 Fuse

ABS 15 A -48 V supply for the office alarm circuit(s)

ABS ALM 1/2 A Alarm fuse for the above ABS fuse

RC1 to RC24 1-1/3 A -48 V sense supply for the rectifiers of the system

CONV 1/2 A Protection for the internal converter in the controller

METER 1/2 A Protection for the meter and selector panel if so equipped

CHG 1/2 A Protection for internal circuitry of the controller when the CONT rotary switch is in the CHG VOLT position

Spare 1 and 2 0 to 5 A For external loads as required (ex.: Helios Monitor)

BAT 1/2 A Protection for internal circuitry of the controller when the CONT rotary switch is in the BAT VOLT position

CONT 1-1/3 A Protection for the internal circuitry of the controller

Plus one unused position

Test points

Three sets of test points for applications as described in Table 38.

Table 38 Test points

CAL OUT + and - To connect an external meter when calibrating the LED readout for current readings

VOLT + and - To connect an external meter when adjusting the BOD, LF, LV, HF, HV, HVSD, LVD and LVR thresholds

PWR EXT + and - The connect an external power supply when adjusting the LVR threshold

Show 4 more labels / short text on this page
LOP enabled · Designation Capacity Description · Designation Description · Operation 31
Page 38 of the Liebert 1500 user manual — Terminal blocks
Page 38 · click to enlarge
Page 38

4.2.2 Rear Panel

The rear panel of the Conventional Controller is provided with the connection interface features shown in Figure 30 and described in the following subsections.

Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controller

Liebert 1500 — 4.2.2 Rear Panel diagram (page 38)
Fig. 31 · 4.2.2 Rear Panel

P2 P10 P8 P6 P4 P16 P14 P12 P22 P20 P18 P24 P26

P1 P9 P7 P5 J1 J2 P3 P15 P13 P11 J3

Terminal blocks

Six terminal blocks to interface with external wiring as follows:

  • TB1: various alarm outputs to the office alarm circuits and the cabinet alarm lamp
  • TB2: various alarm outputs to the office alarm circuits, and remote equalize signal input
  • TB3: various alarm outputs to the office alarm circuits, and charge and discharge fuse alarm inputs
  • TB4: various alarm outputs to the office alarm circuits, and LVD control and alarm
  • TB5: various alarm outputs to the office alarm circuits, remote TR signal input, -48 V supply to cabinet alarm lamp and various small loads, and AUX 1 and AUX 2 alarms inputs
  • TB6: -48 V supply to office alarm circuits if required, VR+ and VRinputs, and -48 V and ground inputs

Refer to Figure 30 and Figure 31 for the pin assignment of terminal blocks TB1 to TB6.

32 Operation

Page 39 of the Liebert 1500 user manual — CHG FUSE ALM
Page 39 · click to enlarge
Page 39

Figure 30 Wiring diagram and pin assignment of terminal blocks TB1 to TB4

NE-1451X cable (or equivalent)

NE-1451X cable (or equivalent)

TB3 TB1

H/L FLOAT ALM (1)

C NC NO

MINOR VIS (1)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2 3 4 5

H/L FLOAT ALM (1)

NC NO C

MINOR VIS (1)

To small internal battery return busbar

H/L FLOAT ALM (2)

C NC NO

BK ALARM VISUAL (C)

H/L FLOAT ALM (2)

NC NO C

6 7 8 9 10

MIN RECT ALM

C NC NO

MAJOR VIS (1)

MIN RECT ALM

NC NO C

MAJOR VIS (1)

MAJ RECT ALM

C NC NO

MAJ RECT ALM

NC NO C

G ALARM VISUAL (NC) To cabinet alarm lamp

11 12 13 14 15 16 17 18 19 20

LVD ALM

C NC NO

MINOR AUD (1)

LVD ALM

MINOR AUD (1)

NC NO C

LOSS OF AC VOLT ALM

C NC NO

MINOR AUD (2)

LOSS OF AC VOLT ALM

NC NO C

MINOR AUD (2)

Input from DISCH fuse alarm circuits

DFA CFA

MAJOR AUD (1)

Input from CHG fuse alarm circuits

NC

MAJOR AUD (1)

NE-1451X cable (or equivalent)

NE-1451X cable (or equivalent)

TB4 TB2

AUX ALM NO.1 (1)

C NC NO

NO C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

MAJOR AUD (2)

AUX ALM NO.1 (1)

NC NO C

MAJOR AUD (2)

AUX ALM NO.1 (2)

C NC NO

AUX ALM NO.1 (2)

FUSE ALM

NC NO C

FUSE ALM

AUX ALM NO.2 (1)

C NC NO

AUX ALM NO.2 (1)

CHG FUSE ALM

NC NO C NC NO C NC NO C NC NO

CHG FUSE ALM

AUX ALM NO.2 (2)

C NC NO

AUX ALM NO.2 (2)

DISCH FUSE ALM

DISCH FUSE ALM

EQUALIZE ALM

C NC NO

EQUALIZE ALM

H/L VOLT ALM (1)

H/L VOLT ALM (1)

HVSD ALM

C NC NO

HVSD ALM

H/L VOLT ALM (2)

H/L VOLT ALM (2)

RLVD LVDA To LVD circuit Input alarm from LVD circuit

Input from office remote circuit REMOTE EQUALIZE START

Show 13 more labels / short text on this page
To office · alarm · circuit · To office · alarm · circuit · To office · alarm · To office · alarm · circuit · circuit · Operation 33
Page 40 of the Liebert 1500 user manual — 4.3 MPS300 and MPA100 Power Shelves
Page 40 · click to enlarge
Page 40

Figure 31 Wiring diagram and pin assignment of terminal blocks TB5 and TB6, and connectors P1 to

P26

22GA 8-conductor shielded cable

P1 TO P24

TB5

To alarm interface board or rectifier interface card as required, or directly to rectifier

To office alarm circuit, If required

EQL ( )

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

ABSF

RG+ ( )

RC- ( )

Input from office remote circuit

TR

TR ( )

RECT FAN

card as required, or directly to rectifier

FAN ( )

RECT FAN To office alarm circuit

NC

HVSD ( )

NO

RFA ( )

NE-1451X cable (or equivalent)

LP (–48V)

To cabinet alarm lamp

22GA 2-conductor shielded cable

–48V (SPARE 2)

To load as required

-48V (METER)

P25

To meter & selector

NC NC SHUNT +

1 2 3 4 5 6 7 8

GRD

Main plant shunt (the shunt wires should be fused near the shunt to prevent fire hazard)

BOD

To office alarm circuit

NC

BOD

SHUNT –

NO

NC NC

NE-1451X cable (or equivalent)

–48 V CHG busbar

NC

AUX1 INPUT (MAJ)

AUX2 INPUT (MIN) GRD alarm signals from auxiliary equipment as required

P26

TB6

To office alarm circuit or alarm reporting circuit, if required

–48 (ABS)

NC NC

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

NC

10 AWG

NC

VR–

NC

VR+

GRD To AC monitor

ALM

GRD

10 AWG

Connectors

Twenty-six connectors to interface with external equipment as follows:

  • P1 to P24: signaling between the controller and the rectifiers
  • P25: interface with the main power system shunt
  • P26: interface with an AC monitoring device

Refer to Figure 31 for the pin assignment of connectors P1 to P26.

Eight connectors (J1 to J8) for the interface between the two circuit boards of the controller (for factory use only).

4.3 MPS300 and MPA100 Power Shelves

The MPS300 power shelf provides the interconnecting points for all the AC, DC and control cabling and wiring for three Helios Rectifier 100/48. The MPA100 power shelf does the same for one Helios Rectifier 100/48.

Refer to the appropriate rectifier user manual listed in 6.0 - Reference Documents for detailed operation information on the MPS300 and MPA100 power shelves.

Show 11 more labels / short text on this page
To · NT6C43PA or NT6C43PB · rectifier · interface · panel (NT6C10AA), · if so equipped · Battery sense leads · Power plant busbars · circuit · such as NT6C18BA · 34 Operation
Page 41 of the Liebert 1500 user manual — 4.7 Terminating Assemblies (Optional)
Page 41 · click to enlarge
Page 41

4.4 Rectifiers

The rectifiers provide isolated, filtered and regulated DC power, from either a single-phase AC source (Helios Rectifier 100/48) or a three-phase AC source (Helios Rectifier 200I/48 or 200E/48), for charging a positive grounded battery.

The nominal output is adjustable over the range of -46 to -59.5 V to float a 23 or 24 cell battery string.

The rectifiers are equipped with AC input and DC output circuit breakers, a digital ammeter, potentiometers for the adjustment of thresholds, and LED indicators for alarm indications.

The rectifiers use high frequency switching technology and forced air-cooling.

Refer to the appropriate rectifier user manual listed in 6.0 - Reference Documents for detailed operation information on the Helios Rectifier 100/48, the Helios Rectifier 200I/48, or the Helios Rectifier 200E/48.

4.5 AC Junction Box

! WARNING PREVENTING ELECTRICAL SHOCKS

WHEN OPENING THE DOOR OR WIRING THE AC INPUT OF THE RECTIFIERS INSIDE THE JUNCTION BOX, ENSURE THAT THE ASSOCIATED AC BREAKERS, LOCATED IN THE AC SERVICE PANEL, ARE IN THE OFF POSITION AND THAT A WARNING TAG CLEARLY INDICATES THAT THESE BREAKERS ARE TO REMAIN OFF UNTIL THE AC WIRING HAS BEEN COMPLETED. DO NOT INSERT FUSES, OR OPERATE CIRCUIT BREAKER OR SWITCHES TO ON UNTIL THE WIRING IS COMPLETED AND YOU ARE INSTRUCTED TO DO SO.

The AC junction box is part of the rectifier cabinet used for the Helios Rectifier 200E/48. It is located at the top of the cabinet for top fed systems, or at the bottom of the cabinet for bottom fed systems.

The AC junction box provides AC connection interface for up to six rectifiers and facilitates the addition and/or replacement of rectifiers in a working system. The AC supply from the AC service panel is hard wired inside the box at the time of the initial installation. Detailed cabling and con- necting guidelines for the AC junction box can be found in 5.0 - Maintenance.

The rectifiers are provided with a factory-installed AC cord equipped with a male connector. This male connector is plugged into a matching female receptacle at the rear of the AC junction box. For the complete procedures for adding or replacing a rectifier, refer to 5.0 - Maintenance. Note that caps are provided to protect the unused female receptacles.

4.6 Distribution Panels

All distribution panels provide local alarm indication on the panel itself, and alarm extension to the controller for additional indication on the controller and the cabinet and further extension to remote alarm facilities.

4.7 Terminating Assemblies (Optional)

Terminating assemblies are optional devices used to facilitate the connecting of loads to distribu- tion fuses or circuit breakers larger than 199 A. These assemblies can be used in top fed systems only (they cannot be used on bottom fed systems). Each terminating assembly provides connection facilities for up to six loads without having to route the cables inside the cabinet during installa- tion.

Two terminating assemblies can be used on an auxiliary distribution cabinet, while only one ter- minating assembly can be used on a main control and distribution cabinet.

Operation 35

Page 42 of the Liebert 1500 user manual — 4.9 600 A and 1200 Battery Disconnect Units (Optional)
Page 42 · click to enlarge
Page 42

4.8 Helios Monitor 3000/48 (Optional)

The Helios Monitor 3000/48 is a microprocessor-based unit used to monitor and record power sys- tems operational data. The recorded data is accessible locally by means of the front panel or the RS-232 port, or remotely through the modem link.

If an Helios Monitor 3000/48 was supplied with your system, refer to the Monitor 3000 user man- ual, SL-60015, for detailed operational characteristics.

4.9 600 A and 1200 Battery Disconnect Units (Optional)

The 600 A and 1200 A Battery Disconnect Units (BDU) are equipped with a circuit breaker that provides for automatic or manual disconnect, but only manual reconnect. The automatic discon- nect is intended to serve the low voltage disconnect function to prevent batteries from deep dis- charge that could damage them. The circuit breaker has industrial grade contacts to connect and disconnect large currents, and it is provided with a relay trip feature.

If battery disconnect unit(s) were supplied with your system, refer to the user manual, SL-60040, for the detailed operational characteristics of the battery disconnect unit.

36 Operation

Page 43 of the Liebert 1500 user manual — Storage
Page 43 · click to enlarge
Page 43

5.0 M AINTENANCE

5.1 General

The following is a list of general preventive maintenance procedures which should be performed periodically as required according to the environmental conditions and customer maintenance policy to ensure trouble free operation of the Helios DC System 4000/48:

  • clean all ventilation openings
  • if these are used, clean or replace the air filters on the rectifiers
  • tighten all electrical connections
  • check for hot fuses or breakers (loose, undersized or overloaded)
  • verify alarms and alarm thresholds
  • verify calibration settings
  • verify rectifier settings

The voltage and alarm settings of the controller and rectifiers are based on the type of batteries used with the power system. The recommended settings for various types of batteries can be found in SL-60026, Voltage Level Limits for Power Plants, Rectifiers and Controllers. If unlisted models of batteries are used, it may be necessary to follow specific customer or manufacturer requirements.

The following is list of the tools and test equipment required to adjust the equipment in the Helios DC System 4000/48:

  • a potentiometer screwdriver, Bourns No. 60 or equivalent
  • a digital voltmeter, Fluke 8050A or equivalent
  • a dummy load, 5 kVA

5.1.1 Helios Monitor 3000/48

If the power system is equipped with a Helios Monitor 3000/48, refer to the user manual, SL-60015, for maintenance and troubleshooting information.

5.1.2 Controller and Rectifiers

The controller and the rectifiers need little maintenance. The following should be checked period- ically in order to ensure trouble free operation.

! WARNING PREVENTING DAMAGE TO THE EQUIPMENT

DO NOT ATTEMPT ANY OTHER REPAIR THAN THOSE LISTED BELOW. IF ANY PROBLEM PERSISTS, CONTACT LIEBERT GLOBAL SERVICES AT 1-800-LIEBERT.

Cleaning

Clean the front panels and the LED display screens with a soft cloth and isopropyl alcohol.

Calibration

Verify the calibration of the alarm and control thresholds at least once a year. Follow the calibra- tion instructions detailed in the appropriate user manual.

Storage

The rectifiers contain aluminum electrolytic capacitors. For this reason, they shall be either kept in operation, or energized once a year for at least two hours in order to maintain the electrolytic capacitors in good condition.

Maintenance 37

Page 44 of the Liebert 1500 user manual — Fan unit replacement
Page 44 · click to enlarge
Page 44

Air filter replacement

In dusty environments, the use of an air filter is strongly recommended. When used, it should be replaced at least once a year. Do not install a wet filter on a rectifier. To remove the filter, simply unscrew it. Install the new one by reversing the operation. Contact your local Liebert representa- tive for ordering information on air filters.

Fan unit replacement

Visually inspect the airflow intake for any obstruction by foreign objects or excessive dust and dirt build-up. Open both AC and DC breakers. If the rectifier is a Helios Rectifier 100/48, remove it from the power shelf. Inspect the air outlet for obstruction by foreign objects. Visually inspect the air outlet of the power shelf (Helios Rectifier 100/48) or the cabinet (Helios Rectifiers 200I/48 and 200E/48). The fan unit is field replaceable. Contact your local Liebert representative for ordering information on replacement fans. To install a new fan unit, refer to the appropriate procedure and associated figures in the maintenance chapter of the applicable rectifier user manual listed in 6.0 - Reference Documents. If a problem is detected inside the rectifier, contact Liebert Glo- bal Services at 1-800-LIEBERT. Do not attempt to open the unit for on-site servicing.

38 Maintenance

Page 45 of the Liebert 1500 user manual — Table 39 Fault diagnosis
Page 45 · click to enlarge
Page 45

5.2 Troubleshooting

Table 39 provides a list of the problems that may occur on the Helios DC System 4000/48, along with their possible causes. Blown fuses and tripped circuit breakers should always be investi- gated before utilizing Table 39.

Table 39 Fault diagnosis

Fault symptom Possible causes

No DC output current Open AC circuit breaker Open DC circuit breaker Faulty connection between the power shelf and the rectifier (Helios Rectifier 100/48) Faulty connection between the rectifier and the power plant Sense leads opened

Incorrect indication of the DC output current

Incorrect meter calibration Loose shunt leads connection

Low float voltage Faulty rectifier(s) Shorted battery cell(s) Prolonged power failure Incorrect float voltage adjustment Sense leads opened

Low recharge voltage Incorrect float voltage adjustment Discharge load greater than the rectifier’s capacity (batteries are recharging or the system is in manual bypass) Sense leads opened

High float or recharge voltage Faulty rectifier(s) Incorrect Float/Equalize adjustment

Failure to generate alarms during alarm conditions

Incorrect connections between the controller and the rectifiers and distribution panels

Failure to generate cabinet alarm during minor or major alarm conditions

Faulty LP fuse on the controller (F31) Faulty cabinet alarm lamp Faulty or loose connection

Failure to generate RFA alarm under appropriate conditions

Faulty rectifier Faulty wiring Faulty RFA LED

Failure to generate FA alarm Faulty wiring Faulty fuse Faulty FA LED Loose connection

HV lamp lit High discharge voltage condition Incorrect HV level adjustment

LV lamp lit Low discharge voltage condition Incorrect LV level adjustment

HF lamp lit High discharge voltage condition Incorrect HF level adjustment

LF lamp lit Low discharge voltage condition Incorrect LF level adjustment

FA lamp lit Blown fuse or extended FA alarm

CFA lamp lit Blown charge fuse

DFA lamp lit Blown distribution fuse

RECT MIN lamp lit One rectifier has failed

RECT MAJ lamp lit Two or more rectifiers have failed

RECT FAN lamp lit Defective rectifier fan(s)

Maintenance 39

Page 46 of the Liebert 1500 user manual — ! WARNING PROTECTING PERSONNEL AGAINST ELECTRICAL SHOCKS
Page 46 · click to enlarge
Page 46

Table 39 Fault diagnosis

Fault symptom Possible causes

LOP lamp lit Loss of one or more phases in the AC supply

HVSD lamp lit High voltage shutdown condition initiated by the controller

LVD lamp lit Low voltage disconnect condition initiated by the controller

AUX 1 lamp lit User defined alarm condition When a Battery Disconnect Unit is present, this lamp will indicate that a battery disconnect alarm is ongoing.

AUX 2 lamp lit User defined alarm condition

BOD lamp lit Low discharge voltage condition Incorrect BOD level adjustment

ACO lamp lit ACO switch has been operated during an alarm condition which is still ongoing

EQL lamp lit The equalize function has been activated

Rectifiers are not sharing the load

Incorrect float or equalize adjustment on one of the rectifiers Sense leads opened on one rectifier Share mode incorrectly set

Meter display is OFF Open meter fuse Meter and display failure Meter and display rotary switch in the OFF position

5.3 Addition / Replacement Procedures

5.3.1 Addition or Replacement of a Rectifier

! WARNING PRECAUTIONS SHALL BE TAKEN TO AVOID SERVICE INTERRUPTIONS

WHEN INSTALLING A RECTIFIER, THE FLOAT AND EQUALIZE VOLTAGES MUST BE SET ACCORDING TO THE TYPE OF BATTERIES USED WITH THE SYSTEM. FAILURE TO SET THESE VOLTAGES PROPERLY MAY RESULT IN BATTERY UNDERCHARGING OR OVERCHARGING AND/OR BATTERY DAMAGE.

! WARNING PROTECTING PERSONNEL AGAINST ELECTRICAL SHOCKS

INPUT VOLTAGES TO THE RECTIFIERS ARE AT A DANGEROUS LEVEL. ENSURE THAT THE CIRCUIT BREAKERS ARE LOCKED IN THE OFF POSITION AT THE AC SERVICE PANEL BEFORE ATTEMPTING TO WORK ON THE RECTIFIERS. DANGEROUS VOLTAGES MAY STILL BE PRESENT AT THE TERMINALS EVEN IF THE RECTIFIERS ARE OFF. USE A VOLTMETER TO VERIFY FOR THE PRESENCE OF SUCH VOLTAGES. DO NOT SWITCH CIRCUIT BREAKERS TO ON UNTIL INSTRUCTED TO DO SO IN THE APPROPRIATE PROCEDURE.

Add a rectifier as described in the following procedure for a Helios Rectifier 100/48 or as in the Adding a Helios Rectifier 200I/48 or 200E/48 procedure, whichever is applicable.

40 Maintenance

Page 47 of the Liebert 1500 user manual — Adding a Helios Rectifier 100/48
Page 47 · click to enlarge
Page 47

Adding a Helios Rectifier 100/48 1. Remove the rectifier blank panel and store it for future use.

Note: Should a rectifier be removed at any time, re-install the blank panel to meet the regulatory requirements. 2. Verify that the AC, DC and signalling cabling for the rectifier shelf has been previously installed and verified. 3. Ensure that the AC and DC circuit breakers on the front panel of the rectifier are in the OFF position. 4. Carefully slide the rectifier into position, making sure that it is fully inserted. 5. Install the left and right side clamping brackets supplied with the rectifier to secure it into position. 6. Operate the AC circuit breaker of the new rectifier to the “ON” position. 7. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 8. Install the corresponding sense fuse (RC) on the front of the controller. 9. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 10. Operate the DC circuit breaker of the rectifier to the “ON” position. 11. Verify that the rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its float and equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents).

Adding a Helios Rectifier 200I/48 or 200E/48 1. Ensure that the AC and DC circuit breakers on the front panel of the rectifier are in the OFF position. 2. Use a manual lift (or at least two people) to lift the rectifier to its position, rest it on the angle guides, and slide it into the cabinet. 3. Align the mounting holes of the rectifier with those of the cabinet uprights and secure the rectifier in place using the eight mounting screws provided.

Note: A star washer must be used on one of the mounting screws. 4. Bring the connectorized AC cord up (top fed) or down (bottom fed) the cabinet and secure as required. 5. Install the required circuit breaker at the AC service panel. 6. Ensure that the circuit breaker installed per Step 5 is locked in the open (OFF) position. 7. Determine the length of cable (or individual wires in conduit) required to bring the AC supply from the AC service panel to the rectifier cabinet. 8. Cut the cable (or wires) to the required lengths then run and secure between the AC service panel and the rectifier cabinet. 9. Strip the sheeting and insulation material away from the ends of the wires to expose the AC leads 10. For a Helios Rectifier 200E/48 without an AC cord, remove the AC protective cover at the rear of the rectifier and connect the AC leads inside the rectifier as shown in Figure 32, then reinstall the AC protective cover. For a Helios Rectifier 200E/48 or a Helios Rectifier 200I/48 equipped with an AC cord, first connect the associated female receptacle supplied with the rectifier to the cable (or wires) incoming from the AC service panel (refer to Figure 33). Then, plug the male connector at the end of the rectifier AC cord into the female receptacle. For a Helios Rectifier 200E/48 equipped with an AC cord, feed the cables through the appro- priate strain relief connector at the top (top fed) or bottom (bottom fed) of the rectifier AC junction box inside the cabinet (refer to Figure 34). Use a flat blade screwdriver to tighten the strain relief connector, then connect the wires to the appropriate terminals inside the junction box as shown in Figure 34. Use plastic cable ties to secure the wires at the tie down points (one for each rectifier position) inside the junction box. Plug the male connector at the

Maintenance 41

Page 48 of the Liebert 1500 user manual — Figure 32 AC connections in a Helios Rectifier 200E/48
Page 48 · click to enlarge
Page 48

end of the rectifier AC cord into the corresponding female receptacle behind the junction box. For the specific AC cable routing to be used with the Helios Rectifier 200E/48, refer to Figure 35 in the case of a top fed system, or to Figure 36 in the case of a bottom fed system. 11. Make the ground and line connections as applicable, at the AC service panel. 12. Install the four bolts for the DC connections to the busbar risers at the rear of the cabinet. 13. Plug one end of the control and signal cable supplied with the rectifier into the DB25 connector at the rear of the rectifier. 14. Plug the other end of the control and signal cable into the corresponding connector on the interface circuit board at the top (top fed system) or bottom (bottom fed system) of the rectifier cabinet. 15. Operate the AC circuit breaker of the new rectifier to the “ON” position. 16. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 17. Install the corresponding sense fuse (RC) on the front of the controller. 18. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 19. Operate the DC circuit breaker of the rectifier to the “ON” position. 20. Verify that the rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its float and equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents).

Figure 32 AC connections in a Helios Rectifier 200E/48

Liebert 1500 — Figure 32 AC connections in a Helios Rectifier 200E/48 diagram (page 48)
Fig. 32 · Figure 32 AC connections in a Helios Rectifier 200E/…

Partial view of the rectifier’s rear panel (right side as viewed from the rear)

42 Maintenance

Page 49 of the Liebert 1500 user manual — 200E/48
Page 49 · click to enlarge
Page 49

Figure 33 AC connections in the female receptacle for a Helios Rectifier 200I/48 or a Helios Rectifier

200E/48

Liebert 1500 — 200E/48 diagram (page 49)
Fig. 33

Figure 34 AC connections inside the junction box (top fed shown) for a Helios Rectifier 200E/48

Liebert 1500 — 200E/48 diagram (page 49)
Fig. 34

TB1 TB2 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12

Six connectors to plug the cables from the rectifiers

Maintenance 43

Page 50 of the Liebert 1500 user manual — Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed system
Page 50 · click to enlarge
Page 50

Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed system

Liebert 1500 — Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed system diagram (page 50)
Fig. 35 · Figure 35 AC cable routing for the Helios Rectifiers…

Enlarged view of routing of the AC cables from behind

Figure 36 AC cable routing for the Helios Rectifiers 200E/48 in a bottom fed system

Liebert 1500 — Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed system diagram (page 50)
Fig. 36 · Figure 35 AC cable routing for the Helios Rectifiers…

Enlarged view of routing of the AC cables from behind

44 Maintenance

Page 51 of the Liebert 1500 user manual — 5.3.2 Replacing a Rectifier
Page 51 · click to enlarge
Page 51

5.3.2 Replacing a Rectifier

Replace a rectifier as described below for a Helios Rectifier 100/48 or as in Replacing a Helios Rectifier 200I/48 or 200E/48, whichever is applicable.

Replacing a Helios Rectifier 100/48 1. Notify the alarm center of incoming alarms during this procedure. 2. Turn OFF the AC and DC circuit breakers on the rectifier. 3. Remove the corresponding sense fuse on the front of the controller. 4. Remove the left and right rectifier retaining bars by loosening the screws. 5. Slide the rectifier out of the shelf carefully. Reuse the shipping carton of the new rectifier to store or ship the removed unit. 6. Ensure that the AC and DC circuit breakers on the new rectifier about to be plugged-in are in the “OFF” position (down). 7. Carefully slide the new rectifier into the shelf, ensuring that it is fully inserted. 8. Reinstall the left and right side clamping brackets removed in Step 4 to secure the rectifier into position. 9. Operate the AC circuit breaker of the new rectifier to the “ON” position. 10. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 11. Reinstall the sense fuse (RC) removed in Step 3. 12. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 13. Operate the DC circuit breaker of the new rectifier to the “ON” position. 14. Verify that the replacement rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its Float and Equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents). 15. Notify the alarm center of the end of the procedure.

Maintenance 45

Page 52 of the Liebert 1500 user manual — Replacing a Helios Rectifier 200I/48 or 200E/48
Page 52 · click to enlarge
Page 52

Replacing a Helios Rectifier 200I/48 or 200E/48 1. Notify the alarm center of incoming alarms during this procedure. 2. Turn OFF the AC and DC circuit breakers on the rectifier to be replaced. 3. Remove the corresponding sense fuse on the front of the controller. 4. At the AC service panel, place the AC circuit breaker associated with this rectifier in the OFF position. 5. For a Helios Rectifier 200E/48 without an AC cord, remove the AC protective cover at the rear of the rectifier and disconnect the AC cable inside the rectifier (refer to Figure 32). For a Helios Rectifier 200I/48 or 200E/48 equipped with an AC cord, unplug the AC cord from the supply receptacle. 6. Remove the four bolts for the DC connections to the busbar risers at the rear of the cabinet. 7. Disconnect the control and signal cable from the DB25 connector at the rear of the rectifier. 8. Remove the mounting screws securing the rectifier to the cabinet. 9. Carefully slide the rectifier out of the cabinet.

CAUTION: Due to the weight of the rectifier (55 kg - 120 lb) a manual lift or at least two persons are required to remove the rectifier. Reuse the shipping carton of the new rectifier to store or ship the removed unit. 10. Ensure that the AC and DC circuit breakers on the front panel of the new rectifier are in the OFF position. 11. Lift the new rectifier to its position, rest it on the angle guides, and slide it into the cabinet. CAUTION: Due to the weight of the rectifier (55 kg - 120 lb) a manual lift or at least two persons are required to install the rectifier. 12. Align the mounting holes of the rectifier with those of the cabinet uprights and secure the rectifier in place using the eight mounting screws provided.

Note: A star washer must be used on one of the mounting screws. 13. Reinstall the four bolts for the DC connections to the busbar risers at the rear of the cabinet (removed in Step 6). 14. Reconnect the control and signal cable into the DB25 connector at the rear of the rectifier (disconnected in Step 7). 15. Reconnect the AC cable disconnected in Step 5 (or the AC cord that was unplugged). 16. At the AC service panel, place the AC circuit breaker associated with the rectifier in the ON position. 17. Operate the AC circuit breaker of the new rectifier to the “ON” position. 18. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 19. Reinstall the sense fuse (RC) removed in Step 3. 20. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 21. Operate the DC circuit breaker of the rectifier to the “ON” position. 22. Verify that the rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its float and equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents). 23. Notify the alarm center of the end of the procedure.

46 Maintenance

Page 53 of the Liebert 1500 user manual — 5.3.3 Adding or Replacing a Battery String
Page 53 · click to enlarge
Page 53

5.3.3 Adding or Replacing a Battery String

For replacements, proceed from Step 1 below. For new installations, go to Step 5 of this proce- dure.

! WARNING THIS PROCEDURE IMPLIES THAT ALL OR PART OF THE BATTERIES WILL BE MOMENTARILY TAKEN OUT OF SERVICE.

THIS WORK SHOULD THEN BE COMPLETED DURING REDUCED TRAFFIC HOURS AND/OR WITH A DIESEL GENERATOR BACKUP AVAILABLE TO ENSURE NO LOSS OF SERVICE DURING A POSSIBLE AC OUTAGE. IF MORE THAN ONE STRING IS TO BE REPLACED, REPLACE ONLY ONE STRING AT A TIME AND DO NOT DISCONNECT THE NEXT STRING BEFORE THE PREVIOUS ONE IS RECONNECTED.

1. Removal of the old string: Notify the alarm center of the possibility of incoming alarms during this procedure. 2. Above the battery stand, or at the top of the main cabinet for a 1500, 3000 or 4000 A system, or at the overhead busbars for a 6000 A system, locate, disconnect and isolate the charge leads (+ and -) coming from the batteries being replaced. 3. Disconnect the inter-cell connectors from the individual battery cells, and insulate each exposed terminal with electrician tape. 4. The removed batteries shall be disposed of in accordance with local, state and national environmental legislation. 5. Installation of the new string: If this is an addition, locate and install the new battery stand according to the specifications and drawings. If this is a replacement, install the new battery string in the space vacated by the removed one. 6. Install the new batteries and use the new connecting material supplied with the batteries to interconnect them. 7. Perform the initial charging of this new battery string according to the battery manufacturer’s specifications using an external power supply. 8. Above the battery stand, or at the top of the main cabinet for a 1500, 3000 or 4000 A system, or at the overhead busbars for a 6000 A system, connect the charge leads (+ and -) coming from the new batteries. 9. Notify the alarm center of the end of the procedure.

Maintenance 47

Page 54 of the Liebert 1500 user manual — 5.3.5 Replacing a Cabinet Alarm Lamp
Page 54 · click to enlarge
Page 54

5.3.4 Replacement of a Distribution Fuse Block or Circuit Breaker

! CAUTION Precautions must be taken to avoid service interruptions.

Use properly insulated tools when working on the power distribution panels.

Replace a distribution fuse block as described below.

1. Notify the alarm center of incoming alarms during this procedure. 2. Remove the fuse from the fuse block to be replaced. 3. Remove the rear panels of the cabinet. 4. Carefully remove and insulate any load and alarm leads connected to the fuse block. 5. Carefully remove the fuse block. 6. Ensure that the fuse is removed from the new fuse block. 7. Carefully install the new fuse block. 8. Reconnect the load and alarm leads disconnected in Step 4. 9. Install the fuse in the fuse block. 10. Notify the alarm center of the end of this procedure.

Replacing a distribution circuit breaker

Replace a distribution circuit breaker as described below.

1. Notify the alarm center of incoming alarms during this procedure. 2. Place the circuit breaker to be replaced in the OFF position. 3. Remove the rear panels of the cabinet. 4. Carefully remove and insulate any load lead and alarm lead connected to the circuit breaker. 5. Carefully remove the circuit breaker. 6. Ensure that the new circuit breaker is in the OFF position before installing it. 7. Carefully install the new circuit breaker. 8. Reconnect the load and alarm leads disconnected in Step 4. 9. Turn on the circuit breaker 10. Notify the alarm center of the end of this procedure.

5.3.5 Replacing a Cabinet Alarm Lamp

Replace a cabinet alarm lamp as described below.

1. Remove the LP fuse on the controller (F31). 2. Unscrew and remove the lens cap on the cabinet alarm lamp unit. 3. Pull the defective light bulb out. 4. Insert the new light bulb. 5. Screw back the lens cap on the cabinet alarm lamp unit. 6. Reinstall the LP fuse on the controller (F31) removed in Step 1.

48 Maintenance

Page 55 of the Liebert 1500 user manual — 6.0 R EFERENCE D OCUMENTS
Page 55 · click to enlarge
Page 55

6.0 R EFERENCE D OCUMENTS

Manual No. Description

SL-60040 600 A and 1200 A Battery Disconnect Unit

SL-60014 TCM48 temperature compensation module

SL-60026 Voltage level limits for rectifiers and controllers

SL-60015 Helios Monitor 3000/48 remote surveillance unit

SL-60033 Helios DC System 4000/48 Installation manual

SL-60012 Helios Rectifier 100/48

SL-60036 Helios Rectifier 200I/48

SL-60037 Helios Rectifier 200E/48

Reference Documents 49

Page 56 of the Liebert 1500 user manual — 7.0 L IST OF T ERMS
Page 56 · click to enlarge
Page 56

7.0 L IST OF T ERMS

A ampere ABS alarm battery supply ABSF alarm battery supply fuse AC or ac alternating current ACO alarm cut-off AD Assembly drawing ADJ adjust or adjustment ALM alarm AMP ampere AUD audible AUX auxiliary AWG American wire gauging BAT battery BAT RTN battery return BDA battery disconnect alarm BDU battery disconnect unit BMU battery management unit BOD battery on discharge BODA battery on discharge alarm BPG building principal ground BR battery return BRR battery return reference CAL calibrate CFA charge fuse alarm CHG charge COM common CONT control CSA Canadian Standard Association CTRL control DC or dc direct current DFA distribution fuse alarm DISCH discharge DSPL display EB earthquake brace EMI electromagnetic interference EQL equalize ESD electrostatic discharge EXT external F fuse FA fuse alarm FG frame ground FGB floor ground bar FS forced sharing ft foot ft-lb foot-pound GRD or GRND ground HF high float HV high voltage HVA high voltage alarm

50 List of Terms

Page 57 of the Liebert 1500 user manual — 7.0 List of Terms
Page 57 · click to enlarge
Page 57

HVSD high voltage shutdown HVSDA high voltage shutdown alarm HVSDR high voltage shutdown reset in. inch in.-lb inch-pound IS interconnect schematic ISG isolated system ground L line lb pound LED light emitting diode LF low float LOP loss of phase LV low voltage LVA low voltage alarm LVD low voltage disconnect LVDA low voltage disconnect alarm LVR low voltage reconnect m meter MAJ major MGB main ground bar MIN minor MNL manual MOP method of procedure MPS modular power shelf mV millivolt NC normally closed N-m Newton-meter NO normally open NORM normal psi pound per square inch PWR power RC Rectifier control RECT rectifier REF reference RFA rectifier failure alarm RPM remote power monitor RST reset SHT shunt SLS slope load share SPG single-point ground (connection) SW switch TB terminal block TCM temperature compensation module TP test point TR temporary release TST test UL Underwriters Laboratories V volt VRLA valve regulated lead acid (batteries) WD wiring diagram WVP water vapor pressure

List of Terms 51

Page 58 of the Liebert 1500 user manual — 7.0 List of Terms
Page 58 · click to enlarge
Page 58

52 List of Terms

Page 59 of the Liebert 1500 user manual — SL-60030
Page 59 · click to enlarge
Page 59
Liebert 1500 — 7.0 List of Terms diagram (page 59)
Fig. 37 · 7.0 List of Terms

Helios DC System 4000/48

1500, 3000, 4000 & 6000 A

DC Power System

Technical Support

U.S.A. 1-800-222-5877

Outside the U.S.A. 614-841-6755

U.K. +44 (0) 1793 553355

France +33 1 4 87 51 52

Germany +49 89 99 19 220

Italy +39 2 98250 1

Netherlands +00 31 475 503333

E-mail upstech@liebert.com

Web site http://www.liebert.com

The Company Behind The Products

With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:

  • Environmental systems: close-control air conditioning from 1.5 to 60 tons.
  • Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA.
  • Integrated systems that provide both environmental and power protection in a single, flexible package.
  • Monitoring and control — on-site or remote — from systems of any size or location

Service and support, through more than 100 service centers around the world, and a 24-hour Customer Response Center.

While every precaution has been taken to ensure accuracy and completeness of this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

© 1998 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Printed in U.S.A.

SL-60030

RevisedJune 1999

Worldwide FAX · 614-841-5471 · tech support

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
No DC output currentOpen AC circuit breaker Open DC circuit breaker Faulty connection between the power shelf and the rectifier (Helios Rectifier 100/48) Faulty connection between the rectifier and the power plant Sense leads opened p.45
Incorrect indication of the DC output currentIncorrect meter calibration Loose shunt leads connection p.45
Low float voltageFaulty rectifier(s) Shorted battery cell(s) Prolonged power failure Incorrect float voltage adjustment Sense leads opened p.45
Low recharge voltageIncorrect float voltage adjustment Discharge load greater than the rectifier’s capacity (batteries are recharging or the system is in manual bypass) Sense leads opened p.45
High float or recharge voltageFaulty rectifier(s) Incorrect Float/Equalize adjustment p.45
Failure to generate alarms during alarm conditionsIncorrect connections between the controller and the rectifiers and distribution panels p.45
Failure to generate cabinet alarm during minor or major alarm conditionsFaulty LP fuse on the controller (F31) Faulty cabinet alarm lamp Faulty or loose connection p.45
Failure to generate RFA alarm under appropriate conditionsFaulty rectifier Faulty wiring Faulty RFA LED p.45
Failure to generate FA alarmFaulty wiring Faulty fuse Faulty FA LED Loose connection p.45
HV lamp litHigh discharge voltage condition Incorrect HV level adjustment p.45
LV lamp litLow discharge voltage condition Incorrect LV level adjustment p.45
HF lamp litHigh discharge voltage condition Incorrect HF level adjustment p.45
LF lamp litLow discharge voltage condition Incorrect LF level adjustment p.45
FA lamp litBlown fuse or extended FA alarm p.45
CFA lamp litBlown charge fuse p.45
DFA lamp litBlown distribution fuse p.45
RECT MIN lamp litOne rectifier has failed p.45
RECT MAJ lamp litTwo or more rectifiers have failed p.45
RECT FAN lamp litDefective rectifier fan(s) p.45
LOP lamp litLoss of one or more phases in the AC supply p.46
HVSD lamp litHigh voltage shutdown condition initiated by the controller p.46
LVD lamp litLow voltage disconnect condition initiated by the controller p.46
AUX 1 lamp litUser defined alarm condition When a Battery Disconnect Unit is present, this lamp will indicate that a battery disconnect alarm is ongoing. p.46
AUX 2 lamp litUser defined alarm condition p.46
BOD lamp litLow discharge voltage condition Incorrect BOD level adjustment p.46
ACO lamp litACO switch has been operated during an alarm condition which is still ongoing p.46
EQL lamp litThe equalize function has been activated p.46
Rectifiers are not sharing the loadIncorrect float or equalize adjustment on one of the rectifiers Sense leads opened on one rectifier Share mode incorrectly set p.46
Meter display is OFFOpen meter fuse Meter and display failure Meter and display rotary switch in the OFF position p.46

Ask about the Liebert 1500

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Liebert 1500

Be the first to ask — other owners or our team will answer.

Original document

Liebert 1500 manual PDF

59 pages·1.2 MB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…