Helios DC System 4000/48 1500, 3000, 4000 & 6000 A DC Power System





3.11 Overall Power System Specifications 26
3.11.1 Standards 26 3.11.2 Mechanical Specifications of Fully Equipped Power Cabinets 26 3.11.3 Electrical Specifications 27 3.11.4 Environmental Specifications 27 3.11.5 Floor and Point Loading 27
4.0 OPERATION 28
4.1 General 28
4.2 Conventional Controller 28
4.2.1 Front Panel 28 4.2.2 Rear Panel 32
4.3 MPS300 and MPA100 Power Shelves 34
4.4 Rectifiers 35
4.5 AC Junction Box 35
4.6 Distribution Panels 35
4.7 Terminating Assemblies (Optional) 35
4.8 Helios Monitor 3000/48 (Optional) 36
4.9 600 A and 1200 Battery Disconnect Units (Optional) 36
5.0 MAINTENANCE 37
5.1 General 37
5.1.1 Helios Monitor 3000/48 37 5.1.2 Controller and Rectifiers 37
5.2 Troubleshooting 39
5.3 Addition / Replacement Procedures 40
5.3.1 Addition or Replacement of a Rectifier 40 5.3.2 Replacing a Rectifier 45 5.3.3 Adding or Replacing a Battery String 47 5.3.4 Replacement of a Distribution Fuse Block or Circuit Breaker 48 5.3.5 Replacing a Cabinet Alarm Lamp 48
6.0 REFERENCE DOCUMENTS 49
7.0 LIST OF TERMS 50



1.1 Purpose of This Document
This document provides all the necessary information to operate and maintain a Helios DC Sys- tem 4000/48 power system.
The installation procedures for the Helios DC System 4000/48 power system are covered in instal- lation manual SL-60034.
This document applies to Helios DC System 4000/48 power systems having any configuration of equipment.
About This Document 1

2.1 Description
The Helios DC System 4000/48 is a positive ground, -48 V DC nominal power system consisting of one control and distribution cabinet and one or more rectifier cabinets. It is available in capacities of 1500, 3000, 4000 and 6000 A. Auxiliary distribution cabinets can be added as required for addi- tional distribution. Remote monitoring, temperature compensation and battery disconnect options are also available. The 1500, 3000 and 4000 A versions use internal -48 V bussing and external BR+ bussing, while the 6000 A version uses overhead bussing. Figure 1 shows a typical bottom fed 4000 A system, while Figure 2 shows a typical 6000 A system.
Figure 1 Front view of a typical bottom fed 4000 A Helios DC System 4000/48 power system

Aux dist. cabinet Main cabinet 1200 A rectifier cabinets
2 Introduction

Figure 2 Front view of a typical 6000 A Helios DC System 4000/48 power system

Aux dist. cabinets Main cabinet 1200 A rectifier cabinets
Cables are used for inter-cabinet connections (1500, 3000 and 6000 A systems) or connections to the overhead busbars (6000 A system) for ease of expansion on live systems. In a 1500, 3000 or 4000 A systems, the power system battery return (BR) busbar is mounted externally from the cab- inet to facilitate the connections of the battery return cables. In a 6000 A system, a separate BR busbar dedicated to the battery returns for the loads is mounted externally from the overhead busbar duct to facilitate the connections of the load battery return cables.
The Helios DC System 4000/48 provides a variety of monitoring and alarm features, such as high/ low float and high/low voltage alarm, high voltage shutdown, fuse and breaker alarm and rectifier failure alarms.
The Helios DC System 4000/48 uses Helios Rectifiers 200I/48, Helios Rectifiers 200E/48 or Helios Rectifiers 100/48 connected in parallel as building blocks to reach the maximum capacities. The Helios Rectifiers 200I/48 operate from a 380 V to 415 V three phase, 50 or 60 Hz AC source. The Helios Rectifiers 200I/48 operate from a 480 V three phase, 50 or 60 Hz AC source. The Helios Rectifiers 100/operate from a 208 V to 240 V single phase, 50 or 60 Hz AC source.
The 1200 A rectifier cabinet accepts up to six Helios Rectifiers 200I/48 or 200E/48, while the 1000 A rectifier cabinet accepts up to 10 Helios Rectifiers 100/48.
The control and distribution cabinet and the auxiliary distribution cabinets are available with distribution busbar risers of 2000 A or 3000 A capacity.
The cabinets are seismic qualified to zone 4 (Bellcore) when anchored to a concrete floor whose compressive strength is at least 2.11 kg/mm2 (3000 psi) and when equipped with a seismic kit. The cabinets are seismic qualified to zone 2 without the seismic kit.
The cabinets are equipped with a ventilated, lockable door, a ventilated top cover and two rear ventilated panels.
In many applications, such as with DMS, a consistent single-point ground (SPG) topology must be maintained for all associated equipment. The Helios DC System 4000/48 complies with this requirements for single-point grounding (the isolation kit is required).
The Helios DC System 4000/48 is designed to operate with DMS systems or any other telecommu- nication systems whose input is nominal -48 V DC and whose current requirements do not exceed 6000 A capacity.
Introduction 3

Figure 3 shows the front and side views of typical rectifier and distribution cabinets for a Helios DC System 4000/48 (bottom cabled cabinets are illustrated - top cabled versions are available).
Figure 3 Typical configurations for Helios DC System 4000/48 control, distribution and rectifier cabinets

4 Introduction

Cabinets are available in a variety of configurations as listed in the following tables. Note that for a 6000 A system, the cabling is always at the top.
Introduction 5

3.1 Framework
The Helios DC System 4000/48 uses cabinet type frameworks. The same cabinet design is used for the main control and distribution cabinet, the auxiliary distribution cabinets and the rectifier cab- inets. The cabinet is always equipped with a front door and door frame (lockable, equipped with ground straps, and easily removable for installation or maintenance access), a ventilated top cover made of non-flammable plastic, and two ventilated rear cover panels (equipped with ground strap and easily removable for installation and maintenance access). Bussing and equipment (controller, rectifiers, distribution panels, etc.) are added as required, depending on the use of the cabinet. Seismic bracing is also available as options.
When using the Cable Trough, overhead cabling cannot enter from the front or rear of the system. It must be confined to the system foot print and enter at the ends of the lineup.
The cabinets may be either top or bottom cabled as determined by the location of the bussing.
The mechanical specifications of an empty cabinet are listed in Table 4.
Refer to Figure 3 for typical views of cabinets.
The electrical specifications of equipped cabinets are as follows:

The mechanical specifications of the Conventional Controller are listed in Table 5.
Figure Height Depth Width Weight
Figure 4 152 mm (6.0 in.)
76 mm (3.0 in.)
584 mm (23 in.)
4.5 kg (10 lb)
3.2.2 Electrical Specifications of the Conventional Controller
The operating voltage is -48 V DC. Refer to the 4.0 - Operation and the appropriate user manual listed in 6.0 - Reference Documents for a detailed list of specifications, operating parameters and features of the Conventional Controller.

Mechanical specifications of the fuse panels
The mechanical specifications of the fuse panels are listed in Table 6 below.
Panel description Figure Height Width Weight
60 A max Figure 5 76.2 mm (3.0 in.)
584 mm (23.0 in.)
3 kg (6.6 lb)
Figure 6 76.2 mm (3.0 in.)
584 mm (23.0 in.)
5 kg (11.0 lb)
(16) QFF 0-5 A &
Figure 7 152.4 mm (6.0 in.)
584 mm (23.0 in.)
7 kg (15.4 lb)
(8) TPN 5-30 A
250 A max Figure 8 152.4 mm (6.0 in.)
584 mm (23.0 in.)
7 kg (15.4 lb)
300 A max Figure 9 152.4 mm (6.0 in.)
584 mm (23.0 in.)
8 kg (17.8 lb)
600 A max Figure 10 228.6 mm (9.0 in.)
584 mm (23.0 in.)
22 kg (48.4 lb)
Figure 10 228.6 mm (9.0 in.)
584 mm (23.0 in.)
24 kg (52.9 lb)
1600 A max Figure 11 304.8 mm (12.0 in.)
584 mm (23.0 in.)
32 kg (70.4 lb)
600 A max Figure 12 178 mm (7.0 in.)
584 mm (23.0 in.)
35 kg (77.0 lb)
FA
The DC output connections are wire wrap or solder.
Table 7 Fuse sizes available for the (20) QFF 0-5 A fuse panels
Fuse type Current (A) CPC
QFF1B 2 A0205203
QFF1C 3 A0205204
QFF1D 5 A0205205
QFF1E 0.18 A0205206
QFF1F 0.25 A0205207
QFF1G 0.5 A0205208
QFF1H 0.75 A0205209
QFF3A DUMMY A0205210

Figure 6 Front view of the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panels
The DC output connections are No. 8-32 studs equipped with two hex nuts.
Table 8 Fuse sizes available for the (16) QFF 0-5 A & (12) ABS 5-30 A fuse panels

Figure 7 Front view of the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panels

The DC output connections are 0.250-20 studs equipped with two hex nuts.
Table 9 Fuse sizes available for the (16) QFF 0-5 A & (6) TPN 5-30 A fuse panels



The DC output connections are 0.250-20 studs equipped with two hex nuts.
Table 10 Fuse sizes available for the (8) TPN 5-30 A fuse panels


FA (1) (2) (3) (4) (2) (3) (4) (1)
The DC output connections are 0.375-16 studs equipped with two hex nuts.
Table 11 Fuse sizes available for the (4) RS100P 70-100 A fuse panels


Figure 10 Front view of the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load shunts) fuse panels

The DC output connections are 0.50-13 studs equipped with two hex nuts.
Table 12 Fuse sizes available for the (4) CRS200P 150-200 A/(4) CRS200P 150-200 A (w/load shunts) fuse panels


The DC output connections are busbar angles that can accept 535MCM or 750MCM cables, or the metric equivalent. The lugs must be for two 1/2” dia. bolts at 1-3/4” c-c.
Table 13 Fuse sizes available for the (4) TPL 225-600 A fuse panels


MAX FUSE 70A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 UNIT AMPS
LOAD
FUSE PANEL NT6C21XX 600 A MAX PANEL CAPACITY
Can accept maximum 1/0 AWG cables and requires one-hole lugs for 1/4” diameter studs.
Table 14 Fuse sizes available for the (18) TPS 1-70 A fuse panel
Fuse type Current (A) CPC
3 A0601323
5 A0601325
6 A0601326
10 A0601327
15 A0601328
25 A0601330
30 A0601331
40 A0601332
50 A0601333
60 A0601334
70 A0601335
DC power (TPS)

The electrical specifications of the fuse panels are described in Table 15.
Busbar capacity Quantity Capacity
60 A max Figure 5 20 0-5 A 60 A
Figure 6 16 12 0-5 A 0-30 A 300 A
(16) QFF 0-5 A &
Figure 7 8 0-30 A 250 A
(8) TPN 5-30 A
250 A max Figure 8 8 31-60 A 300 A
300 A max Figure 9 4 70-100 A 300 A
Figure 10 4 101-200 A 600 A
(4) CRS200P 150-200 A (w/load shunts)
1600 A max Figure 11 4 225-600 A 1600 A
600 A max Figure 12 18 0-70 A 600 A
Mechanical specifications of the circuit breaker panels
The mechanical specifications of the circuit breaker panels are described in Table 16.
Panel description Figure Height Width Weight
(24) Plug-In 1-100 A
900 A max Figure 13 165 mm (6.5 in.)
584 mm (23.0 in.)
9.1kg (20 lb.)
(4) 70-250 A 900 A max * Figure 14 178 mm (7.0 in.)
584 mm (23.0 in.)
10.5 kg (25 lb)
(2) 400 A Figure 15 178 mm (7.0 in.)
584 mm (23.0 in.)
10.5 kg (25 lb)
(1) 600-700 A Figure 16 178 mm (7.0 in.)
584 mm (23.0 in.)
10.5 kg (25 lb)
* The 250 A circuit breaker has two poles, thus the panel can accommodate a maximum of two 250 A breakers. An alarm circuit pack with an alarm indication LED is standard on all panels.

Figure 13 Front view of the (24) Plug-In 1-100 A circuit breaker panel
The DC output connections vary according to the circuit breaker capacity: maximum cable size is 2/0AWG. The lugs must be for 3/8” dia. bolts at 1” c-c.
Refer to Table 21 for the maximum panel capacity.
Table 17 Plug-in circuit breakers available for the (24) Plug-In 1-100 A circuit breaker panel
current CPC Std Trip CPC Mid Trip
5 A A0723033 A0722752
10 A A0723035 A0722754
15 A A0723037 A0722755
20 A A0723007 A0722695
25 A A0723039 A0722707
30 A A0723040 A0722715
35 A A0723041 A0722717
40 A A0723042 A0722721
45 A A0723069 A0722722
50 A A0723008 A0722726
60 A A0723070 A0722727
65 A A0723071 A0722497
70 A A0723072 A0722732
80 A A0723074 A0722733
90 A A0723077 A0722750
100 A A0723009 A0722496
Nominal

CIRCUIT BREAKER PANEL
900A MAX. PANEL CAPACITY
(4) 70-250 A
NT6C12EE
FA
REL ( ) SER NO ( )
UNIT AMPS
225 1 2 3 4
The DC output connections can accommodate two 4/0 cables back to back for each circuit breaker. The required lugs can be either for two 3/8” holes at 1” c-c or for two 1/2” holes at 1-3/4” c-c.
Refer to Table 21 for the maximum panel capacity.
Table 18 Circuit breaker sizes available for the (4) 70-250 A circuit breaker panel
70 A (no shunt) A0617079
70 A (with shunt) A0617080
70 A (with relay trip) A0617081
100 A (no shunt) A0616667
100 A (with shunt) A0616668
100 A (with relay trip) A0616669
150 A (no shunt) A0616670
150 A (with shunt) A0616671
150 A (with relay trip) A0616672
200 A (no shunt) A0616673
200 A (with shunt) A0616674
200 A (with relay trip) A0616675
225 A (no shunt) A0605489
225 A (with shunt) A0605490
225 A (with relay trip) A0605492
250 A (no shunt) A0616676
250 A (with shunt) A0616677
250 A (with relay trip) A0616678
The (4) 70-250 A circuit breaker panel can accept up to:
Nominal current CPC


The DC output connections can accommodate two 750 MCM cables back to back for each circuit breaker. The required lugs must be for two 1/2” holes at 1-3/4” c-c.
Refer to Table 21 for the maximum panel capacity.
Table 19 Circuit breaker kits available for the (2) 400 A circuit breaker panel

The panel accepts up to:

The DC output connections can accommodate four 750 MCM cables back to back. The lugs must be for two 1/2” bolts at 1-3/4” c-c.
Refer to Table 21 for the available circuit breakers and the maximum panel capacity.
Table 20 Circuit breaker kits available for the (1) 600-700 A circuit breaker panel
600 A (no shunt) P0875700
600 A (e/w shunt) P0875701
600 A (e/w relay trip) P0875702
Nominal current CPC

The electrical specifications of the circuit breaker panels are described in Table 21.
Busbar capacity Max. Quantity Capacity
(24) Plug-In 1-100 A
900 A max Figure 13 24 1-100 A 900A
900 A max Figure 14 4 70-250 A 900 A
(2) 400 A Figure 15 2 400 A 900 A
(1) 600-700 A Figure 16 1 600 A 900 A
Circuit breakers · Panel description · Figure

The battery return busbar is designed to mount on the overhead racking for 6000 A systems and top cabled 1500, 3000 or 4000 A power systems. It can also be mounted on a wall or on the floor below the raised floor for bottom cabled 1500, 3000 or 4000 A power systems (which are assumed to be installed on a raised, computer type floor).
The external battery return busbar kit consists of a group of single busbar laminations and attachment hardware assembled as shown in Figure 17 (6000 A shown). The kit can grow verti- cally in such a way as to maintain the 3-ft maximum radius grounding requirement. Laminations are added as required to increase the capacity. The mechanical specifications of a single lamina- tion are listed in Table 22.
Figure Length Width Thickness
Figure 17 863.6 mm (34 inches)
152.4 mm (6 inches)
12.7 mm (0.5 inches)

Side view of the external ground bar installed on
* For a 1500 A system, only the bottom level is provided for the external battery return ground bar.
A single busbar lamination has a current carrying capacity of 3000 A.

The optional terminating assembly allows top access connections for up to six loads. Refer to Figure 18. Each load position is rated at 600 A and can accept up to three lugs having 1” or 1-3/4” c-c hole spacing, for cables up to 777 kcmil.
The terminating assembly is bolted to the top of the main or auxiliary distribution cabinets and, therefore, increase the cabinet height by 12 inches. The weight of the terminating assembly is 12.5 kg (27.6 lb).
An optional Lexan™ protective cover is available to protect the connections of the load cables.


The MPS300 and MPA100 power shelves are required for the Helios Rectifier 100/48, which is a plug-in type rectifier. The MPA100 power shelf supports one Helios Rectifier 100/48, while the MPS300 shelf can support up to three Helios Rectifiers 100/48.
The mechanical specifications of the power shelves are listed in Table 23.




Each rectifier position provides interconnection points for AC input (208 to 240 V nominal), DC output (-48 V nominal) and control and alarm signals.
The Helios system 4000/48 can be equipped with Helios Rectifiers 100/48 for single phase 208/240 V AC operation, with Helios Rectifiers 200I/48 for three phase 380/415 V AC operation, or with Helios Rectifiers 200E/48 for three phase 480 V AC operation.
Mechanical specifications of the Helios Rectifier 100/48
The mechanical specifications of the Helios Rectifier 100/48 are listed in Table 24.
Figure Height Depth Width Weight
Figure 21 178 mm (7.0 in.)
305 mm (12.0 in.)
584 mm (23.0 in.)
22.2 kg (49 lb)


The electrical specifications of the Helios Rectifier 100/48 are listed in Table 25.
Input current: 31 A nominal at 208 V AC input and -56 V DC, 100 A output
Recommended AC service input:
50 A, two pole AC circuit breaker
Output voltage: Float: -48 to -58 V DC Equalize: 0 to 4 V DC above Float Maximum: -59.5 V DC
Output current: 100 A per rectifier 100 A for a one position shelf 300 A for a three position shelf
Input protection: A two pole / 45 A circuit breaker opens both lines.
Output protection: The rectifier is protected by a 120 A circuit breaker at the output. The output current is limited to a value adjustable from 50% to 105% of the rated capacity of the rectifier. This circuit is factory set to 105 A.
Output regulation: The rectifier output voltage is automatically regulated to remain within ±0.5% of the selected value under all load conditions and within the specified input voltage, frequency, and ambient temperature ranges. And within + 1% for any combinations of specified input, output and environmental conditions.
Efficiency: Efficiency is better than 88% at a nominal input voltage of 208/240 V AC and an output load greater than 40 A.
Power factor: Power factor is 0.99 at a nominal input voltage of 208 V AC and output loads greater than 40 A.
Electromagnetic interference (EMI):
The rectifier meets the FCC requirements for conducted and radiated EMI for Class “A” equipment.
Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48
The mechanical specifications of the Helios Rectifier 200I/48 and 200E/48 are listed in Table 26.
Figure Height Depth Width Weight
Figure 22 254 mm (10 in.)
559 mm (22 in.)
521 mm (20.5 in.)
42.3 kg (93 lb)
Parameter Specification



The electrical specifications of the Helios Rectifiers 200I/48 and 200E/48 are listed in Table 27.
Input voltage Helios Rectifier 200I/48:
380/415 V AC, three phase, 47-63 Hz Input voltage range: 330 to 475 V AC Helios Rectifier 200E/48:
480 V AC, three phase, 47-63 Hz Input voltage range: 430 to 520 V AC
Input current Helios Rectifier 200I/48: 18.3 A RMS nominal at 380 V AC input and -54 V DC, 200 A output (24 A RMS worst case) Helios Rectifier 200E/48: 15 A RMS nominal at 480 V AC input and -54 V DC, 200 A output (17 A RMS worst case)
Input protection A 3 pole / 25 A circuit breaker opens all three lines.
Recommended AC service input
30 A, 3 pole AC circuit breaker
Output voltage Float: -46 to -58 V DC Equalize: 0 to 4 V DC above Float Maximum: -60 V DC
Output current 200 A nominal Adjustable between 100 and 210 A
Output protection The rectifier is protected by a 250 A circuit breaker at the output. The output current is limited to a value adjustable from 50% to 105% of the rated capacity of the rectifier. This circuit is factory set to 205 A.
Output regulation The rectifier output voltage is automatically regulated to remain within ±0.5% of the selected value under all load conditions and within the specified input voltage, frequency, and ambient temperature ranges. And within + 1% for any combinations of specified input, output and environmental conditions.
Efficiency Efficiency is better than 89% at nominal input voltage and an output load greater than 80 A.
Power factor Power factor is better than 0.99 at nominal input voltage and an output load greater than 80 A.
The rectifier meets the FCC requirements for conducted and radiated EMI for Class “B” equipment.
Heat dissipation 1,335 W (4,558 Btu/hr) at -54 V DC, 200 A output
Total harmonic distortion (THD)
THD is less than 5% between half load and full load at nominal input voltage
The following standards also apply to the rectifiers:
Parameter Specification · Electromagnetic interference (EMI)

The mechanical specifications of the Helios Monitor 3000/48 are listed in Table 28.
Figure Height Depth Width Weight
Figure 23 45 mm (1.75 in.)
222 mm (8.75 in.)
280 mm (11.0 in.)
2.8 kg (6.2 lb)
The above dimensions are without the mounting brackets. The weight may vary slightly depend- ing on the number and type of analog interface modules installed in the unit.
Figure 23 Front view of the Helios Monitor 3000/48 (without the mounting brackets)

ROTARY SWITCHES 12 DIGIT ALPHA-NUMERIC DISPLAY 4 PUSH-BUTTON KEYPAD
The input voltage of the Helios Monitor 3000/48 is -48 V DC nominal, with a range of -42 V DC to -60 V DC.
The input current drain is 400 mA. This current drain may vary slightly depending upon the number and type of analog interface modules installed in the unit.
For more detailed electrical specifications of the Helios Monitor 3000/48, refer to the appropriate user manual listed in 6.0 - Reference Documents.
The Battery Disconnect Units are 11 inches high and provides for 500 mm (19 in.) or 600 mm (23 in.) framework mounting or wall mounting. The units are equipped with a heavy duty circuit breaker that can be used to manually or automatically disconnect a battery string. Reconnect is manual only. The breaker is mid trip and equipped with a relay trip feature.

For more detailed electrical specifications of the Battery Disconnect Unit, refer to the user man- ual, SL-60040.

The AC junction box is required as an AC connection interface in rectifier cabinets where the Helios Rectifier 200E/48 is used.
Figure 25 Front view of the AC junction box (with the front panel open)

Six receptacles to plug the cables from the rectifiers
TB1 TB2 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
The junction box is made of zinc plated steel and can accommodate up to six one-inch rigid or flex- ible conduits. The mechanical specifications are listed in Table 29.
Figure Height Depth Width
Figure 25 264 mm (10.4 in.)
284 mm (11.2 in.)
521 mm (20.5 in.)
The junction box is designed to accommodate six 3-phase circuits (3 wires plus ground) at a maxi- mum voltage of 600 V AC and a capacity of 30 A per circuit.
The Helios DC System 4000/48 meets the following North American and European standards:
Table 30 Mechanical specifications of fully equipped power cabinets


3.11.3 Electrical Specifications Refer to the individual component’s specifications.
Electromagnetic compliance (EMC) The equipment contained in the power system complies with the specifications of FCC, Part 15, Subpart B for class A equipment, CSA 108.8 for class A and CISPR 22 for class A.
Electrostatic discharge (ESD) immunity No equipment damage or malfunctions shall occur when electrostatic discharge voltages of sever- ity level 2 and 4, as specified by IEC-801-2, are applied to exposed parts of the power system.
Operating
During transportation the equipment may be subjected to the following conditions without damage:
Heat dissipation A Helios DC System 4000/48 rectifier cabinet equipped with six Helios Rectifier 200I/48 or 200E/ 48 will dissipate a maximum of 8,010 watts or 27,350 Btu/hr.
3.11.5 Floor and Point Loading The floor loading is based on a footprint of 600 mm x 600 mm (23.6 in. x 23.6 in.) plus a 30-inch aisle width (15 inches front and rear). The point loading is based on distributing the cabinet weight over four shims, each with an assumed area of 25.8 cm2 (4 in.2). See Figure 1 for a typical system configuration for floor and point loading calculations.
Cabinet type Floor loading Point loading
Control and distribution cabinet 41.3 kN/sq m (90.9 lb/sq ft) 34.5 N/sq cm (50 lb/sq in.)
Auxiliary distribution cabinet 32.3 kN/sq m (71 lb/sq ft) 26.9 N/sq cm (39 lb/sq in.)
Rectifier cabinet 50.1 kN/sq m (110.2 lb/sq ft) 41.8 N/sq cm (60.6 lb/sq in.)

4.1 General
This chapter describes the control, adjustment and operational features of the Helios DC System 4000/48.
The Conventional Controller monitors the operation of the entire power plant. It monitors all the alarms, and it controls and monitors the rectifiers.
Provision is made on the back of the Conventional Controller to extend any occurring alarm to the alarm center through the facilities provided in the powered equipment.
All of the control switches, potentiometers, operational and alarm visual indications are located at the front of the Conventional Controller.
The front panel of the Conventional Controller is provided with the control, alarm and operational features shown in Figure 26 and described in the following subsections.
Visual indicators A 4.5 digit red LED readout to display the system current and voltage, and 18 LEDs to display the alarm conditions as described in Table 32. All alarm conditions are also displayed by a red incan- descent cabinet alarm lamp.
RECT FAN Rectifier Fan Failure yellow
EQL Equalize On yellow
FA Fuse Failure Alarm (Internal to the Controller) red
DFA Discharge Fuse Alarm red
CFA (not used) Charge Fuse Alarm red
RFA MIN Rectifier Failure Alarm Minor yellow
RFA MAJ Rectifier Failure Alarm Major red
ACO Alarm cut-off red
HVSD High Voltage Shutdown Alarm red
HV High Voltage Alarm red
LV Low Voltage Alarm red
HF High Float Alarm yellow
LF Low Float Alarm yellow
LVD Low Voltage Disconnect red
BOD Battery On Discharge red
LOP Loss of Phase red
AUX 1 (BDA) Auxiliary Major red
AUX 2 Auxiliary Minor yellow
Designation Description Color · 28 Operation

RECT FAN (1 - Form C contacts)
RFA MIN (1 - Form C contacts)
RFA MAJ (1 - Form C contacts)
H/L FLOAT (2 - Form C contacts)
EQL ALM (1 - Form C contacts)
H/L VOLT (2 - Form C contacts)
FA (1 - Form C contacts)
CHG FUSE (1 - Form C contacts)
DISCH FUSE (1 - Form C contacts)
LVD (1 - Form C contacts)
LOSS OF AC VOLT (1 - Form C contacts)
AUX 1 ALM (2 - Form C contacts)
AUX 2 ALM (2 - Form C contacts)
HVSD (1 - Form C contacts)
BOD (1 - Form C contacts)
MIN VIS (note 2) (2 - Form C contacts)
MAJ VIS (note 2) (2 - Form C contacts)
MIN AUD (2 - Form C contacts)
MAJ AUD (2 - Form C contacts)
MINOR VIS (2) and MAJ VIS (2) are used for the cabinet alarm lamp.
Twelve potentiometers for the adjustment of alarm and control functions as described in Table 34.
HVSD High Voltage Shutdown
HV High Voltage Alarm
LV Low Voltage Alarm
HF High Float Alarm
LF Low Float Alarm
LVD Low Voltage Disconnect
BOD Battery On Discharge
VOLT ADJ Plant Voltage Adjustment
REF CAL Reference Calibration
METER ADJ Meter Adjustment
AMP ADJ Ampere Adjustment
LVR Low Voltage Reconnect
Alarm Description · Designation Description · Operation 29

Four switches for the control of functions as described in Table 35.
EQUALIZE MAN/AUTO Used to activate or deactivate the equalize function.
ACO Used to cancel the audible alarm signal.
CALIBRATE NORM/CAL Used to activate or deactivate the calibration function.
CONT rotary switch Six position switch: OFF, AMP, CHG VOLT, BAT VOLT, CAL, TST DISPL
Three DIP switch modules for the setting of functions as described in Table 36 and as shown in Figure 27 and Figure 28.
SHUNT SELECT To select the shunt size
TIMER To select the duration of the equalize
VOLT To select the equalize voltage
S1 RANGE AMPS
MIN-MAX
1 2 3 4 5 6

TIMER
VOLT
Switch # 1 2 3 4 5 6
Switch # 1 2 3
10 sec.
20 sec.
38 sec.
1.25 h
3.0 h
5.0 h
: switch in the ON position
Thirty-four fuses for circuit protection as described in Table 37. Except for the ABS fuse, which is small tube type (9/32” dia x 1-1/4” long), all fuses are of the QFF type.
ABS 15 A -48 V supply for the office alarm circuit(s)
ABS ALM 1/2 A Alarm fuse for the above ABS fuse
RC1 to RC24 1-1/3 A -48 V sense supply for the rectifiers of the system
CONV 1/2 A Protection for the internal converter in the controller
METER 1/2 A Protection for the meter and selector panel if so equipped
CHG 1/2 A Protection for internal circuitry of the controller when the CONT rotary switch is in the CHG VOLT position
Spare 1 and 2 0 to 5 A For external loads as required (ex.: Helios Monitor)
BAT 1/2 A Protection for internal circuitry of the controller when the CONT rotary switch is in the BAT VOLT position
CONT 1-1/3 A Protection for the internal circuitry of the controller
Plus one unused position
Three sets of test points for applications as described in Table 38.
CAL OUT + and - To connect an external meter when calibrating the LED readout for current readings
VOLT + and - To connect an external meter when adjusting the BOD, LF, LV, HF, HV, HVSD, LVD and LVR thresholds
PWR EXT + and - The connect an external power supply when adjusting the LVR threshold

The rear panel of the Conventional Controller is provided with the connection interface features shown in Figure 30 and described in the following subsections.
Figure 29 Terminal blocks and connectors layout at the rear of the Conventional Controller

P2 P10 P8 P6 P4 P16 P14 P12 P22 P20 P18 P24 P26
P1 P9 P7 P5 J1 J2 P3 P15 P13 P11 J3
Six terminal blocks to interface with external wiring as follows:
Refer to Figure 30 and Figure 31 for the pin assignment of terminal blocks TB1 to TB6.
32 Operation

Figure 30 Wiring diagram and pin assignment of terminal blocks TB1 to TB4
NE-1451X cable (or equivalent)
NE-1451X cable (or equivalent)
H/L FLOAT ALM (1)
C NC NO
MINOR VIS (1)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5
NC NO C
MINOR VIS (1)
To small internal battery return busbar
C NC NO
BK ALARM VISUAL (C)
H/L FLOAT ALM (2)
NC NO C
6 7 8 9 10
C NC NO
MAJOR VIS (1)
MIN RECT ALM
NC NO C
MAJOR VIS (1)
MAJ RECT ALM
C NC NO
MAJ RECT ALM
NC NO C
G ALARM VISUAL (NC) To cabinet alarm lamp
11 12 13 14 15 16 17 18 19 20
C NC NO
MINOR AUD (1)
LVD ALM
MINOR AUD (1)
NC NO C
LOSS OF AC VOLT ALM
C NC NO
MINOR AUD (2)
LOSS OF AC VOLT ALM
NC NO C
MINOR AUD (2)
Input from DISCH fuse alarm circuits
MAJOR AUD (1)
Input from CHG fuse alarm circuits
MAJOR AUD (1)
NE-1451X cable (or equivalent)
NE-1451X cable (or equivalent)
AUX ALM NO.1 (1)
C NC NO
NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
AUX ALM NO.1 (1)
NC NO C
MAJOR AUD (2)
AUX ALM NO.1 (2)
C NC NO
AUX ALM NO.1 (2)
FUSE ALM
NC NO C
FUSE ALM
AUX ALM NO.2 (1)
C NC NO
AUX ALM NO.2 (1)
CHG FUSE ALM
NC NO C NC NO C NC NO C NC NO
AUX ALM NO.2 (2)
C NC NO
AUX ALM NO.2 (2)
DISCH FUSE ALM
DISCH FUSE ALM
EQUALIZE ALM
C NC NO
EQUALIZE ALM
H/L VOLT ALM (1)
H/L VOLT ALM (1)
HVSD ALM
C NC NO
HVSD ALM
H/L VOLT ALM (2)
H/L VOLT ALM (2)
RLVD LVDA To LVD circuit Input alarm from LVD circuit
Input from office remote circuit REMOTE EQUALIZE START

Figure 31 Wiring diagram and pin assignment of terminal blocks TB5 and TB6, and connectors P1 to
22GA 8-conductor shielded cable
TB5
To alarm interface board or rectifier interface card as required, or directly to rectifier
To office alarm circuit, If required
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
RG+ ( )
RC- ( )
Input from office remote circuit
TR ( )
RECT FAN
card as required, or directly to rectifier
RECT FAN To office alarm circuit
HVSD ( )
NO
RFA ( )
NE-1451X cable (or equivalent)
To cabinet alarm lamp
22GA 2-conductor shielded cable
To load as required
P25
To meter & selector
1 2 3 4 5 6 7 8
Main plant shunt (the shunt wires should be fused near the shunt to prevent fire hazard)
To office alarm circuit
BOD
SHUNT –
NO
NC NC
NE-1451X cable (or equivalent)
–48 V CHG busbar
AUX1 INPUT (MAJ)
AUX2 INPUT (MIN) GRD alarm signals from auxiliary equipment as required
TB6
To office alarm circuit or alarm reporting circuit, if required
NC NC
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
10 AWG
NC
VR–
NC
VR+
GRD To AC monitor
GRD
10 AWG
Connectors
Twenty-six connectors to interface with external equipment as follows:
Refer to Figure 31 for the pin assignment of connectors P1 to P26.
Eight connectors (J1 to J8) for the interface between the two circuit boards of the controller (for factory use only).
The MPS300 power shelf provides the interconnecting points for all the AC, DC and control cabling and wiring for three Helios Rectifier 100/48. The MPA100 power shelf does the same for one Helios Rectifier 100/48.
Refer to the appropriate rectifier user manual listed in 6.0 - Reference Documents for detailed operation information on the MPS300 and MPA100 power shelves.

The rectifiers provide isolated, filtered and regulated DC power, from either a single-phase AC source (Helios Rectifier 100/48) or a three-phase AC source (Helios Rectifier 200I/48 or 200E/48), for charging a positive grounded battery.
The nominal output is adjustable over the range of -46 to -59.5 V to float a 23 or 24 cell battery string.
The rectifiers are equipped with AC input and DC output circuit breakers, a digital ammeter, potentiometers for the adjustment of thresholds, and LED indicators for alarm indications.
The rectifiers use high frequency switching technology and forced air-cooling.
Refer to the appropriate rectifier user manual listed in 6.0 - Reference Documents for detailed operation information on the Helios Rectifier 100/48, the Helios Rectifier 200I/48, or the Helios Rectifier 200E/48.
WHEN OPENING THE DOOR OR WIRING THE AC INPUT OF THE RECTIFIERS INSIDE THE JUNCTION BOX, ENSURE THAT THE ASSOCIATED AC BREAKERS, LOCATED IN THE AC SERVICE PANEL, ARE IN THE OFF POSITION AND THAT A WARNING TAG CLEARLY INDICATES THAT THESE BREAKERS ARE TO REMAIN OFF UNTIL THE AC WIRING HAS BEEN COMPLETED. DO NOT INSERT FUSES, OR OPERATE CIRCUIT BREAKER OR SWITCHES TO ON UNTIL THE WIRING IS COMPLETED AND YOU ARE INSTRUCTED TO DO SO.
The AC junction box is part of the rectifier cabinet used for the Helios Rectifier 200E/48. It is located at the top of the cabinet for top fed systems, or at the bottom of the cabinet for bottom fed systems.
The AC junction box provides AC connection interface for up to six rectifiers and facilitates the addition and/or replacement of rectifiers in a working system. The AC supply from the AC service panel is hard wired inside the box at the time of the initial installation. Detailed cabling and con- necting guidelines for the AC junction box can be found in 5.0 - Maintenance.
The rectifiers are provided with a factory-installed AC cord equipped with a male connector. This male connector is plugged into a matching female receptacle at the rear of the AC junction box. For the complete procedures for adding or replacing a rectifier, refer to 5.0 - Maintenance. Note that caps are provided to protect the unused female receptacles.
All distribution panels provide local alarm indication on the panel itself, and alarm extension to the controller for additional indication on the controller and the cabinet and further extension to remote alarm facilities.
Terminating assemblies are optional devices used to facilitate the connecting of loads to distribu- tion fuses or circuit breakers larger than 199 A. These assemblies can be used in top fed systems only (they cannot be used on bottom fed systems). Each terminating assembly provides connection facilities for up to six loads without having to route the cables inside the cabinet during installa- tion.
Two terminating assemblies can be used on an auxiliary distribution cabinet, while only one ter- minating assembly can be used on a main control and distribution cabinet.
Operation 35

The Helios Monitor 3000/48 is a microprocessor-based unit used to monitor and record power sys- tems operational data. The recorded data is accessible locally by means of the front panel or the RS-232 port, or remotely through the modem link.
If an Helios Monitor 3000/48 was supplied with your system, refer to the Monitor 3000 user man- ual, SL-60015, for detailed operational characteristics.
The 600 A and 1200 A Battery Disconnect Units (BDU) are equipped with a circuit breaker that provides for automatic or manual disconnect, but only manual reconnect. The automatic discon- nect is intended to serve the low voltage disconnect function to prevent batteries from deep dis- charge that could damage them. The circuit breaker has industrial grade contacts to connect and disconnect large currents, and it is provided with a relay trip feature.
If battery disconnect unit(s) were supplied with your system, refer to the user manual, SL-60040, for the detailed operational characteristics of the battery disconnect unit.
36 Operation

5.1 General
The following is a list of general preventive maintenance procedures which should be performed periodically as required according to the environmental conditions and customer maintenance policy to ensure trouble free operation of the Helios DC System 4000/48:
The voltage and alarm settings of the controller and rectifiers are based on the type of batteries used with the power system. The recommended settings for various types of batteries can be found in SL-60026, Voltage Level Limits for Power Plants, Rectifiers and Controllers. If unlisted models of batteries are used, it may be necessary to follow specific customer or manufacturer requirements.
The following is list of the tools and test equipment required to adjust the equipment in the Helios DC System 4000/48:
If the power system is equipped with a Helios Monitor 3000/48, refer to the user manual, SL-60015, for maintenance and troubleshooting information.
The controller and the rectifiers need little maintenance. The following should be checked period- ically in order to ensure trouble free operation.
DO NOT ATTEMPT ANY OTHER REPAIR THAN THOSE LISTED BELOW. IF ANY PROBLEM PERSISTS, CONTACT LIEBERT GLOBAL SERVICES AT 1-800-LIEBERT.
Clean the front panels and the LED display screens with a soft cloth and isopropyl alcohol.
Verify the calibration of the alarm and control thresholds at least once a year. Follow the calibra- tion instructions detailed in the appropriate user manual.
The rectifiers contain aluminum electrolytic capacitors. For this reason, they shall be either kept in operation, or energized once a year for at least two hours in order to maintain the electrolytic capacitors in good condition.
Maintenance 37

In dusty environments, the use of an air filter is strongly recommended. When used, it should be replaced at least once a year. Do not install a wet filter on a rectifier. To remove the filter, simply unscrew it. Install the new one by reversing the operation. Contact your local Liebert representa- tive for ordering information on air filters.
Visually inspect the airflow intake for any obstruction by foreign objects or excessive dust and dirt build-up. Open both AC and DC breakers. If the rectifier is a Helios Rectifier 100/48, remove it from the power shelf. Inspect the air outlet for obstruction by foreign objects. Visually inspect the air outlet of the power shelf (Helios Rectifier 100/48) or the cabinet (Helios Rectifiers 200I/48 and 200E/48). The fan unit is field replaceable. Contact your local Liebert representative for ordering information on replacement fans. To install a new fan unit, refer to the appropriate procedure and associated figures in the maintenance chapter of the applicable rectifier user manual listed in 6.0 - Reference Documents. If a problem is detected inside the rectifier, contact Liebert Glo- bal Services at 1-800-LIEBERT. Do not attempt to open the unit for on-site servicing.
38 Maintenance

Table 39 provides a list of the problems that may occur on the Helios DC System 4000/48, along with their possible causes. Blown fuses and tripped circuit breakers should always be investi- gated before utilizing Table 39.
Fault symptom Possible causes
No DC output current Open AC circuit breaker Open DC circuit breaker Faulty connection between the power shelf and the rectifier (Helios Rectifier 100/48) Faulty connection between the rectifier and the power plant Sense leads opened
Incorrect indication of the DC output current
Incorrect meter calibration Loose shunt leads connection
Low float voltage Faulty rectifier(s) Shorted battery cell(s) Prolonged power failure Incorrect float voltage adjustment Sense leads opened
Low recharge voltage Incorrect float voltage adjustment Discharge load greater than the rectifier’s capacity (batteries are recharging or the system is in manual bypass) Sense leads opened
High float or recharge voltage Faulty rectifier(s) Incorrect Float/Equalize adjustment
Failure to generate alarms during alarm conditions
Incorrect connections between the controller and the rectifiers and distribution panels
Failure to generate cabinet alarm during minor or major alarm conditions
Faulty LP fuse on the controller (F31) Faulty cabinet alarm lamp Faulty or loose connection
Failure to generate RFA alarm under appropriate conditions
Faulty rectifier Faulty wiring Faulty RFA LED
Failure to generate FA alarm Faulty wiring Faulty fuse Faulty FA LED Loose connection
HV lamp lit High discharge voltage condition Incorrect HV level adjustment
LV lamp lit Low discharge voltage condition Incorrect LV level adjustment
HF lamp lit High discharge voltage condition Incorrect HF level adjustment
LF lamp lit Low discharge voltage condition Incorrect LF level adjustment
FA lamp lit Blown fuse or extended FA alarm
CFA lamp lit Blown charge fuse
DFA lamp lit Blown distribution fuse
RECT MIN lamp lit One rectifier has failed
RECT MAJ lamp lit Two or more rectifiers have failed
RECT FAN lamp lit Defective rectifier fan(s)
Maintenance 39

Fault symptom Possible causes
LOP lamp lit Loss of one or more phases in the AC supply
HVSD lamp lit High voltage shutdown condition initiated by the controller
LVD lamp lit Low voltage disconnect condition initiated by the controller
AUX 1 lamp lit User defined alarm condition When a Battery Disconnect Unit is present, this lamp will indicate that a battery disconnect alarm is ongoing.
AUX 2 lamp lit User defined alarm condition
BOD lamp lit Low discharge voltage condition Incorrect BOD level adjustment
ACO lamp lit ACO switch has been operated during an alarm condition which is still ongoing
EQL lamp lit The equalize function has been activated
Rectifiers are not sharing the load
Incorrect float or equalize adjustment on one of the rectifiers Sense leads opened on one rectifier Share mode incorrectly set
Meter display is OFF Open meter fuse Meter and display failure Meter and display rotary switch in the OFF position
! WARNING PRECAUTIONS SHALL BE TAKEN TO AVOID SERVICE INTERRUPTIONS
WHEN INSTALLING A RECTIFIER, THE FLOAT AND EQUALIZE VOLTAGES MUST BE SET ACCORDING TO THE TYPE OF BATTERIES USED WITH THE SYSTEM. FAILURE TO SET THESE VOLTAGES PROPERLY MAY RESULT IN BATTERY UNDERCHARGING OR OVERCHARGING AND/OR BATTERY DAMAGE.
INPUT VOLTAGES TO THE RECTIFIERS ARE AT A DANGEROUS LEVEL. ENSURE THAT THE CIRCUIT BREAKERS ARE LOCKED IN THE OFF POSITION AT THE AC SERVICE PANEL BEFORE ATTEMPTING TO WORK ON THE RECTIFIERS. DANGEROUS VOLTAGES MAY STILL BE PRESENT AT THE TERMINALS EVEN IF THE RECTIFIERS ARE OFF. USE A VOLTMETER TO VERIFY FOR THE PRESENCE OF SUCH VOLTAGES. DO NOT SWITCH CIRCUIT BREAKERS TO ON UNTIL INSTRUCTED TO DO SO IN THE APPROPRIATE PROCEDURE.
Add a rectifier as described in the following procedure for a Helios Rectifier 100/48 or as in the Adding a Helios Rectifier 200I/48 or 200E/48 procedure, whichever is applicable.
40 Maintenance

Adding a Helios Rectifier 100/48 1. Remove the rectifier blank panel and store it for future use.
Note: Should a rectifier be removed at any time, re-install the blank panel to meet the regulatory requirements. 2. Verify that the AC, DC and signalling cabling for the rectifier shelf has been previously installed and verified. 3. Ensure that the AC and DC circuit breakers on the front panel of the rectifier are in the OFF position. 4. Carefully slide the rectifier into position, making sure that it is fully inserted. 5. Install the left and right side clamping brackets supplied with the rectifier to secure it into position. 6. Operate the AC circuit breaker of the new rectifier to the “ON” position. 7. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 8. Install the corresponding sense fuse (RC) on the front of the controller. 9. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 10. Operate the DC circuit breaker of the rectifier to the “ON” position. 11. Verify that the rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its float and equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents).
Adding a Helios Rectifier 200I/48 or 200E/48 1. Ensure that the AC and DC circuit breakers on the front panel of the rectifier are in the OFF position. 2. Use a manual lift (or at least two people) to lift the rectifier to its position, rest it on the angle guides, and slide it into the cabinet. 3. Align the mounting holes of the rectifier with those of the cabinet uprights and secure the rectifier in place using the eight mounting screws provided.
Note: A star washer must be used on one of the mounting screws. 4. Bring the connectorized AC cord up (top fed) or down (bottom fed) the cabinet and secure as required. 5. Install the required circuit breaker at the AC service panel. 6. Ensure that the circuit breaker installed per Step 5 is locked in the open (OFF) position. 7. Determine the length of cable (or individual wires in conduit) required to bring the AC supply from the AC service panel to the rectifier cabinet. 8. Cut the cable (or wires) to the required lengths then run and secure between the AC service panel and the rectifier cabinet. 9. Strip the sheeting and insulation material away from the ends of the wires to expose the AC leads 10. For a Helios Rectifier 200E/48 without an AC cord, remove the AC protective cover at the rear of the rectifier and connect the AC leads inside the rectifier as shown in Figure 32, then reinstall the AC protective cover. For a Helios Rectifier 200E/48 or a Helios Rectifier 200I/48 equipped with an AC cord, first connect the associated female receptacle supplied with the rectifier to the cable (or wires) incoming from the AC service panel (refer to Figure 33). Then, plug the male connector at the end of the rectifier AC cord into the female receptacle. For a Helios Rectifier 200E/48 equipped with an AC cord, feed the cables through the appro- priate strain relief connector at the top (top fed) or bottom (bottom fed) of the rectifier AC junction box inside the cabinet (refer to Figure 34). Use a flat blade screwdriver to tighten the strain relief connector, then connect the wires to the appropriate terminals inside the junction box as shown in Figure 34. Use plastic cable ties to secure the wires at the tie down points (one for each rectifier position) inside the junction box. Plug the male connector at the
Maintenance 41

end of the rectifier AC cord into the corresponding female receptacle behind the junction box. For the specific AC cable routing to be used with the Helios Rectifier 200E/48, refer to Figure 35 in the case of a top fed system, or to Figure 36 in the case of a bottom fed system. 11. Make the ground and line connections as applicable, at the AC service panel. 12. Install the four bolts for the DC connections to the busbar risers at the rear of the cabinet. 13. Plug one end of the control and signal cable supplied with the rectifier into the DB25 connector at the rear of the rectifier. 14. Plug the other end of the control and signal cable into the corresponding connector on the interface circuit board at the top (top fed system) or bottom (bottom fed system) of the rectifier cabinet. 15. Operate the AC circuit breaker of the new rectifier to the “ON” position. 16. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 17. Install the corresponding sense fuse (RC) on the front of the controller. 18. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 19. Operate the DC circuit breaker of the rectifier to the “ON” position. 20. Verify that the rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its float and equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents).

Partial view of the rectifier’s rear panel (right side as viewed from the rear)
42 Maintenance

Figure 33 AC connections in the female receptacle for a Helios Rectifier 200I/48 or a Helios Rectifier

Figure 34 AC connections inside the junction box (top fed shown) for a Helios Rectifier 200E/48

TB1 TB2 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
Six connectors to plug the cables from the rectifiers
Maintenance 43

Figure 35 AC cable routing for the Helios Rectifiers 200E/48 in a top fed system

Enlarged view of routing of the AC cables from behind
Figure 36 AC cable routing for the Helios Rectifiers 200E/48 in a bottom fed system

Enlarged view of routing of the AC cables from behind
44 Maintenance

Replace a rectifier as described below for a Helios Rectifier 100/48 or as in Replacing a Helios Rectifier 200I/48 or 200E/48, whichever is applicable.
Replacing a Helios Rectifier 100/48 1. Notify the alarm center of incoming alarms during this procedure. 2. Turn OFF the AC and DC circuit breakers on the rectifier. 3. Remove the corresponding sense fuse on the front of the controller. 4. Remove the left and right rectifier retaining bars by loosening the screws. 5. Slide the rectifier out of the shelf carefully. Reuse the shipping carton of the new rectifier to store or ship the removed unit. 6. Ensure that the AC and DC circuit breakers on the new rectifier about to be plugged-in are in the “OFF” position (down). 7. Carefully slide the new rectifier into the shelf, ensuring that it is fully inserted. 8. Reinstall the left and right side clamping brackets removed in Step 4 to secure the rectifier into position. 9. Operate the AC circuit breaker of the new rectifier to the “ON” position. 10. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 11. Reinstall the sense fuse (RC) removed in Step 3. 12. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 13. Operate the DC circuit breaker of the new rectifier to the “ON” position. 14. Verify that the replacement rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its Float and Equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents). 15. Notify the alarm center of the end of the procedure.
Maintenance 45

Replacing a Helios Rectifier 200I/48 or 200E/48 1. Notify the alarm center of incoming alarms during this procedure. 2. Turn OFF the AC and DC circuit breakers on the rectifier to be replaced. 3. Remove the corresponding sense fuse on the front of the controller. 4. At the AC service panel, place the AC circuit breaker associated with this rectifier in the OFF position. 5. For a Helios Rectifier 200E/48 without an AC cord, remove the AC protective cover at the rear of the rectifier and disconnect the AC cable inside the rectifier (refer to Figure 32). For a Helios Rectifier 200I/48 or 200E/48 equipped with an AC cord, unplug the AC cord from the supply receptacle. 6. Remove the four bolts for the DC connections to the busbar risers at the rear of the cabinet. 7. Disconnect the control and signal cable from the DB25 connector at the rear of the rectifier. 8. Remove the mounting screws securing the rectifier to the cabinet. 9. Carefully slide the rectifier out of the cabinet.
CAUTION: Due to the weight of the rectifier (55 kg - 120 lb) a manual lift or at least two persons are required to remove the rectifier. Reuse the shipping carton of the new rectifier to store or ship the removed unit. 10. Ensure that the AC and DC circuit breakers on the front panel of the new rectifier are in the OFF position. 11. Lift the new rectifier to its position, rest it on the angle guides, and slide it into the cabinet. CAUTION: Due to the weight of the rectifier (55 kg - 120 lb) a manual lift or at least two persons are required to install the rectifier. 12. Align the mounting holes of the rectifier with those of the cabinet uprights and secure the rectifier in place using the eight mounting screws provided.
Note: A star washer must be used on one of the mounting screws. 13. Reinstall the four bolts for the DC connections to the busbar risers at the rear of the cabinet (removed in Step 6). 14. Reconnect the control and signal cable into the DB25 connector at the rear of the rectifier (disconnected in Step 7). 15. Reconnect the AC cable disconnected in Step 5 (or the AC cord that was unplugged). 16. At the AC service panel, place the AC circuit breaker associated with the rectifier in the ON position. 17. Operate the AC circuit breaker of the new rectifier to the “ON” position. 18. With the DC breaker in the “OFF” position, adjust the float, equalize and high voltage shutdown voltage levels as required. Refer to the appropriate rectifier user manual (see 6.0 - Reference Documents). 19. Reinstall the sense fuse (RC) removed in Step 3. 20. Ensure that the FLS/FS switch on the rectifier is set to the same position as that of the other rectifiers in the power system. 21. Operate the DC circuit breaker of the rectifier to the “ON” position. 22. Verify that the rectifier is sharing the load by observing its ammeter. It should display approximately the same value as the ammeters on the other rectifiers. If not, adjust its float and equalize voltage levels as described in the appropriate rectifier user manual (see 6.0 - Reference Documents). 23. Notify the alarm center of the end of the procedure.
46 Maintenance

For replacements, proceed from Step 1 below. For new installations, go to Step 5 of this proce- dure.
! WARNING THIS PROCEDURE IMPLIES THAT ALL OR PART OF THE BATTERIES WILL BE MOMENTARILY TAKEN OUT OF SERVICE.
THIS WORK SHOULD THEN BE COMPLETED DURING REDUCED TRAFFIC HOURS AND/OR WITH A DIESEL GENERATOR BACKUP AVAILABLE TO ENSURE NO LOSS OF SERVICE DURING A POSSIBLE AC OUTAGE. IF MORE THAN ONE STRING IS TO BE REPLACED, REPLACE ONLY ONE STRING AT A TIME AND DO NOT DISCONNECT THE NEXT STRING BEFORE THE PREVIOUS ONE IS RECONNECTED.
1. Removal of the old string: Notify the alarm center of the possibility of incoming alarms during this procedure. 2. Above the battery stand, or at the top of the main cabinet for a 1500, 3000 or 4000 A system, or at the overhead busbars for a 6000 A system, locate, disconnect and isolate the charge leads (+ and -) coming from the batteries being replaced. 3. Disconnect the inter-cell connectors from the individual battery cells, and insulate each exposed terminal with electrician tape. 4. The removed batteries shall be disposed of in accordance with local, state and national environmental legislation. 5. Installation of the new string: If this is an addition, locate and install the new battery stand according to the specifications and drawings. If this is a replacement, install the new battery string in the space vacated by the removed one. 6. Install the new batteries and use the new connecting material supplied with the batteries to interconnect them. 7. Perform the initial charging of this new battery string according to the battery manufacturer’s specifications using an external power supply. 8. Above the battery stand, or at the top of the main cabinet for a 1500, 3000 or 4000 A system, or at the overhead busbars for a 6000 A system, connect the charge leads (+ and -) coming from the new batteries. 9. Notify the alarm center of the end of the procedure.
Maintenance 47

! CAUTION Precautions must be taken to avoid service interruptions.
Use properly insulated tools when working on the power distribution panels.
Replace a distribution fuse block as described below.
1. Notify the alarm center of incoming alarms during this procedure. 2. Remove the fuse from the fuse block to be replaced. 3. Remove the rear panels of the cabinet. 4. Carefully remove and insulate any load and alarm leads connected to the fuse block. 5. Carefully remove the fuse block. 6. Ensure that the fuse is removed from the new fuse block. 7. Carefully install the new fuse block. 8. Reconnect the load and alarm leads disconnected in Step 4. 9. Install the fuse in the fuse block. 10. Notify the alarm center of the end of this procedure.
Replace a distribution circuit breaker as described below.
1. Notify the alarm center of incoming alarms during this procedure. 2. Place the circuit breaker to be replaced in the OFF position. 3. Remove the rear panels of the cabinet. 4. Carefully remove and insulate any load lead and alarm lead connected to the circuit breaker. 5. Carefully remove the circuit breaker. 6. Ensure that the new circuit breaker is in the OFF position before installing it. 7. Carefully install the new circuit breaker. 8. Reconnect the load and alarm leads disconnected in Step 4. 9. Turn on the circuit breaker 10. Notify the alarm center of the end of this procedure.
Replace a cabinet alarm lamp as described below.
48 Maintenance

Manual No. Description
SL-60040 600 A and 1200 A Battery Disconnect Unit
SL-60014 TCM48 temperature compensation module
SL-60026 Voltage level limits for rectifiers and controllers
SL-60015 Helios Monitor 3000/48 remote surveillance unit
SL-60033 Helios DC System 4000/48 Installation manual
SL-60012 Helios Rectifier 100/48
SL-60036 Helios Rectifier 200I/48
SL-60037 Helios Rectifier 200E/48
Reference Documents 49

A ampere ABS alarm battery supply ABSF alarm battery supply fuse AC or ac alternating current ACO alarm cut-off AD Assembly drawing ADJ adjust or adjustment ALM alarm AMP ampere AUD audible AUX auxiliary AWG American wire gauging BAT battery BAT RTN battery return BDA battery disconnect alarm BDU battery disconnect unit BMU battery management unit BOD battery on discharge BODA battery on discharge alarm BPG building principal ground BR battery return BRR battery return reference CAL calibrate CFA charge fuse alarm CHG charge COM common CONT control CSA Canadian Standard Association CTRL control DC or dc direct current DFA distribution fuse alarm DISCH discharge DSPL display EB earthquake brace EMI electromagnetic interference EQL equalize ESD electrostatic discharge EXT external F fuse FA fuse alarm FG frame ground FGB floor ground bar FS forced sharing ft foot ft-lb foot-pound GRD or GRND ground HF high float HV high voltage HVA high voltage alarm
50 List of Terms

HVSD high voltage shutdown HVSDA high voltage shutdown alarm HVSDR high voltage shutdown reset in. inch in.-lb inch-pound IS interconnect schematic ISG isolated system ground L line lb pound LED light emitting diode LF low float LOP loss of phase LV low voltage LVA low voltage alarm LVD low voltage disconnect LVDA low voltage disconnect alarm LVR low voltage reconnect m meter MAJ major MGB main ground bar MIN minor MNL manual MOP method of procedure MPS modular power shelf mV millivolt NC normally closed N-m Newton-meter NO normally open NORM normal psi pound per square inch PWR power RC Rectifier control RECT rectifier REF reference RFA rectifier failure alarm RPM remote power monitor RST reset SHT shunt SLS slope load share SPG single-point ground (connection) SW switch TB terminal block TCM temperature compensation module TP test point TR temporary release TST test UL Underwriters Laboratories V volt VRLA valve regulated lead acid (batteries) WD wiring diagram WVP water vapor pressure
List of Terms 51

52 List of Terms


DC Power System
Technical Support
U.S.A. 1-800-222-5877
Outside the U.S.A. 614-841-6755
France +33 1 4 87 51 52
Germany +49 89 99 19 220
Italy +39 2 98250 1
Netherlands +00 31 475 503333
E-mail upstech@liebert.com
Web site http://www.liebert.com
With more than 500,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Service and support, through more than 100 service centers around the world, and a 24-hour Customer Response Center.
While every precaution has been taken to ensure accuracy and completeness of this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 1998 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Printed in U.S.A.
Worldwide FAX · 614-841-5471 · tech support
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| No DC output current | Open AC circuit breaker Open DC circuit breaker Faulty connection between the power shelf and the rectifier (Helios Rectifier 100/48) Faulty connection between the rectifier and the power plant Sense leads opened | p.45 | |
| Incorrect indication of the DC output current | Incorrect meter calibration Loose shunt leads connection | p.45 | |
| Low float voltage | Faulty rectifier(s) Shorted battery cell(s) Prolonged power failure Incorrect float voltage adjustment Sense leads opened | p.45 | |
| Low recharge voltage | Incorrect float voltage adjustment Discharge load greater than the rectifier’s capacity (batteries are recharging or the system is in manual bypass) Sense leads opened | p.45 | |
| High float or recharge voltage | Faulty rectifier(s) Incorrect Float/Equalize adjustment | p.45 | |
| Failure to generate alarms during alarm conditions | Incorrect connections between the controller and the rectifiers and distribution panels | p.45 | |
| Failure to generate cabinet alarm during minor or major alarm conditions | Faulty LP fuse on the controller (F31) Faulty cabinet alarm lamp Faulty or loose connection | p.45 | |
| Failure to generate RFA alarm under appropriate conditions | Faulty rectifier Faulty wiring Faulty RFA LED | p.45 | |
| Failure to generate FA alarm | Faulty wiring Faulty fuse Faulty FA LED Loose connection | p.45 | |
| HV lamp lit | High discharge voltage condition Incorrect HV level adjustment | p.45 | |
| LV lamp lit | Low discharge voltage condition Incorrect LV level adjustment | p.45 | |
| HF lamp lit | High discharge voltage condition Incorrect HF level adjustment | p.45 | |
| LF lamp lit | Low discharge voltage condition Incorrect LF level adjustment | p.45 | |
| FA lamp lit | Blown fuse or extended FA alarm | p.45 | |
| CFA lamp lit | Blown charge fuse | p.45 | |
| DFA lamp lit | Blown distribution fuse | p.45 | |
| RECT MIN lamp lit | One rectifier has failed | p.45 | |
| RECT MAJ lamp lit | Two or more rectifiers have failed | p.45 | |
| RECT FAN lamp lit | Defective rectifier fan(s) | p.45 | |
| LOP lamp lit | Loss of one or more phases in the AC supply | p.46 | |
| HVSD lamp lit | High voltage shutdown condition initiated by the controller | p.46 | |
| LVD lamp lit | Low voltage disconnect condition initiated by the controller | p.46 | |
| AUX 1 lamp lit | User defined alarm condition When a Battery Disconnect Unit is present, this lamp will indicate that a battery disconnect alarm is ongoing. | p.46 | |
| AUX 2 lamp lit | User defined alarm condition | p.46 | |
| BOD lamp lit | Low discharge voltage condition Incorrect BOD level adjustment | p.46 | |
| ACO lamp lit | ACO switch has been operated during an alarm condition which is still ongoing | p.46 | |
| EQL lamp lit | The equalize function has been activated | p.46 | |
| Rectifiers are not sharing the load | Incorrect float or equalize adjustment on one of the rectifiers Sense leads opened on one rectifier Share mode incorrectly set | p.46 | |
| Meter display is OFF | Open meter fuse Meter and display failure Meter and display rotary switch in the OFF position | p.46 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.