GE PMCS 6.11a

304 pages·2.7 MB·Network Card·PDF·ENDEFRITNLJA
GE PMCS 6.11a
Table of Contents 297 sections Introduction · Welcome · How should I use this manual? · Conventions · … ShowHide
Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 1 of the GE PMCS 6.11a user manual — Installation Guide GEH-6513
Page 1 · click to enlarge
Page 1

POWER LEADER TM

PMCS 6.11 a Interface Toolkit

Installation Guide GEH-6513

GE Power Management Control System 6.11a

PMCS Interface Toolkit Back to Main Menu • i

Page 2 of the GE PMCS 6.11a user manual — EPM5350P (DMMS350) EPM5000P (DMWH300) EPM9450Q/EPM9650Q
Page 2 · click to enlarge
Page 2

Notice

The information contained in this document is subject to change without notice. GE makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. GE shall not be liable for errors contained herein or incidental consequential damages in connection with the furnishing, performance, or use of this material.

This document contains proprietary information which is protected by copyright. All rights are reserved. No part of this document may be photocopied or otherwise reproduced without consent of GE.

Copyright ©2000 - 2002 by GE. Published in a limited copyright sense, and all rights, including trade secrets, are reserved.

Document Edition - First 5/96

Second 5/97 Third 1/98 Fourth 06/98 Fifth 03/99 Sixth 07/99 Seventh 03/00 Eighth 10/00 Ninth 02/01 Tenth 06/01 Eleventh 01/02 The following are products of General Electric Company:

POWER LEADERTM Meter 239 Motor Protection Relay GE Fanuc Series 90/30 PLC

POWER LEADER Modbus Monitor 269 Plus Motor Management Relay GE Fanuc Series 90/70 PLC

POWER LEADER Electronic Power Meter

369 Motor Management Relay Power Quality Meter (PQM)

Spectra MicroVersaTrip SR469 Motor Management Relay EPM 7300 Electronic Power Meter

EPM 7600 Electronic Power Meter EPM 7500 Electronic Power Meter EPM 7330 Electronic Power Meter

Enhanced MicroVersaTrip-C SR489 Generator Management Relay EPM 7700 Electronic Power Meter

Enhanced MicroVersaTrip-D 565 Feeder Management Relay EPM 3710 Electronic Power Meter

MDP Overcurrent Relay 735 Feeder Relay EPM 3720 Electronic Power Meter

SR750/SR760 Feeder Management Relay SR745 Transformer Management Relay Spectra Electronic Control Module

Universal Relay EPM7430D/EPM7450D Motor Manager II (MMII)

GE-Zenith MX200 (Microprocessor Controller)

GE-Zenith Generator PLC (Series 90- 70) EPM5300P/EPM5200P

EPM5350P (DMMS350) EPM5000P (DMWH300) EPM9450Q/EPM9650Q

Electronic Power Meter 3710 , Electronic Power Meter 3720, Electronic Power Meter 7300, Electronic Power Meter 7330, Electronic Power Meter 7500, Electronic Power Meter 7600, and Electronic Power Meter 7700 are products of Power Measurement Limited.

Multilin 269+ Motor Management Relay® is a registered trademarks of Multilin Inc., and Multilin SR489 Generator Management Relay™ and Multilin SR745 Transformer Management Relay™ are trademarks of Multilin Inc.

Microsoft, Microsoft Access, Microsoft Excel, Microsoft PowerPoint, Microsoft Visual Basic, and MS-DOS are registered trademarks, and Windows NT is a trademark of Microsoft Corporation.

Wonderware is a registered trademark of WonderWare Corporation. Wonderware InTouch and NetDDE are trademarks of WonderWare Corporation.

US Pat Nos 5,768,148; 5,764,155; 5,862,391

ii • Back to Main Menu PMCS Interface Toolkit

Page 3 of the GE PMCS 6.11a user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 4 of the GE PMCS 6.11a user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 5 of the GE PMCS 6.11a user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 6 of the GE PMCS 6.11a user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 7 of the GE PMCS 6.11a user manual — Table of contents
Page 7 · click to enlarge
Page 7

Table of contents

Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 8 of the GE PMCS 6.11a user manual
Page 8 · click to enlarge
Page 8
Page 8 of the GE PMCS 6.11a user manual
Page 9 of the GE PMCS 6.11a user manual — Introduction
Page 9 · click to enlarge
Page 9

Introduction

Welcome

The PMCS Interface Toolkit is a POWER LEADER Power Management Control System (PMCS) version 6.11a tool that provides a custom toolkit to efficiently create flexible, accurate, and friendly user interfaces to your power management data. With the PMCS Wizards (accurate graphical representations of power management devices and other commonly encountered objects), you can create applications to provide a customized interface that accurately represents physical, electrical, and geographical plant layouts. The wizards can significantly cut new system development time, providing results in less than an hour.

The PMCS Interface Toolkit allows you to create one-line diagrams, elevation views, and floor plans that you can combine with tabular data screens and three-dimensional device wizards to create a virtual representation of your facility and equipment. With this graphical user interface, you actually see and control devices on the screen, without having to make a trip out to the meter or trip unit.

The Toolkit, which consists of the Wonderware InTouch development environment coupled with GE’s wizards, is easy to use, taking advantage of state-of-the-art drag- and-drop technology. Wizards are provided for all the devices most commonly used with the PMCS DDE Server. Creating a custom interface is as easy as selecting wizards for the devices installed in a facility and placing them on the screen.

Here’s what you’ll find in this guide:

  • Chapter 2 explains the kinds of PMCS Wizards, their use and configuration – Small Faceplate wizards, Large Faceplate wizards, Tabular Data Screen wizards, OneLine wizards, Elevation wizards, and Floor Plan wizards.
  • Chapter 3 illustrates the use of the GE wizards described in Chapter 2 to create animated displays of the facility floor plan, switchgear elevations, and system oneline diagrams.
  • Chapter 4 gives an example of application development, using the wizards described in Chapters 2 and 3 to create an actual PMCS application.
  • Chapter 5 describes the functions available with each of the GE Large Faceplate wizards. These wizards are accurate graphical representations
Page 10 of the GE PMCS 6.11a user manual — How should I use this manual?
Page 10 · click to enlarge
Page 10

of power management devices, complete with working controls that are linked to the corresponding devices in your facility.

  • Chapter 6 describes the Tabular Data wizards. These wizards list the data and setpoints of power management devices in a tabular format. Simply point and click to select the appropriate tab of information to display and view the related data.

The examples and references in this guide enable you to create custom interfaces for your PMCS system, and allow you to access power management data in the way that best suits you.

How should I use this manual?

How you use this book depends on your level of expertise with Wonderware InTouch. Consult the table below to determine where you should start.

If this describes you…Start here: I’ve never seen this stuff before! What’s Wonderware InTouch? What are “Wizards”?Refer to the documentation that came with your Wonderware InTouch package. Start with the introduction and tutorial sections, which will teach you about Wonderware InTouch and how to use it to create custom applications. When you understand what wizards are and how to use them, come back here. I’ve just opened this package – where do I go first?Go to Chapter 1, Introduction. Chapter 1 explains what the User Screen Configurator is, what it’s good for, and where to go after that. I’m familiar with Wonderware InTouch and I’d like to build a custom application for some GE power management devices.Go to Chapter 1 for installation instructions, then to Chapter 2 for descriptions of the wizards and how to use them. Chapter 4 provides a demo of actual application development. This package contains wizards for the power management devices supported by GE’s PMCS 6.11a software. The GE PMCS Wizards are already installed on my system, I’m already experienced with InTouch, and I’m ready to start building custom applications.Turn to Chapter 2 for information on how to use the GE PMCS Wizards, and Chapter 4 for a quick example of application development. For detailed descriptions of the Large Faceplate wizards or the Tabular Data Screen wizards, refer to Chapters 5 and 6 respectively. Just tell me about the wizards; I’m an old pro and ready to go!Skim through Chapters 2 and 3 for an overview of what’s in the package, then Chapter 4 for a quick example of application development. Chapter 5 describes the GE Large Faceplate wizards and Chapter 6 the associated Tabular Data Screen wizards.
Page 11 of the GE PMCS 6.11a user manual — Installation
Page 11 · click to enlarge
Page 11

Conventions

You will find this book easy to use if you look for these simple conventions:

  • Boldface type indicates the name of an item you need to select.
  • Monospace type indicates an example or text that is displayed on the screen.
  • UPPERCASE type indicates a file name, command name, or acronym.

About the Interface Toolkit

The Interface Toolkit consists of the Wonderware InTouch development environment and a special set of wizards developed for use with the power management devices supported by PMCS.

Installation

To install the Interface Toolkit from the CD-ROM, refer to the instructions provided in GEH-6514, Read This Book First.

When InTouch is successfully installed, you must add the PMCS wizards to InTouch’s library of available wizards.

To add the wizards to InTouch, start InTouch and enter Development mode. Pull down the Special menu and select Configure > Wizard.

GE PMCS 6.11a — Installation diagram (page 11)
Fig. 1 · Installation
Page 12 of the GE PMCS 6.11a user manual — Conventions
Page 12 · click to enlarge
Page 12

From the InTouch Configuration menu, select Install Wizards.

The Wizard Installation dialog displays two list boxes, showing the currently installed wizards and the wizards available for installation. Select the desired wizards from the bottom box and click Install. When the installation is complete, click Done.

GE PMCS 6.11a — Conventions diagram (page 12)
Fig. 2 · Conventions

Exit from the InTouch Configuration dialog box by clicking OK. The PMCS wizards should now be loaded and ready for use.

Page 13 of the GE PMCS 6.11a user manual — Using and Configuring PMCS Wizards
Page 13 · click to enlarge
Page 13

Using and Configuring PMCS Wizards

About the Wizards

The wizards contained in the PMCS Interface Toolkit allow you to quickly build accurate and friendly user interfaces with InTouch. In addition to the various wizards standard with InTouch development systems, the Interface Toolkit provides six types of powerful GE wizards:

  • GE Small Faceplates
  • GE Large Faceplates
  • GE Tabular Screens
  • GE One-Line Tools
  • GE Elevation Wizards
  • GE Floor Plan Wizards

The five-step procedure below outlines how to use InTouch wizards.

1. From InTouch, either create a new window or open an existing window to modify.
2. Select the wizards button

from the floating toolbars. The Wizard Selection dialog box pops up.

3. Select the class of wizard from the list of wizards on the left side of the Wizard Selection dialog. Several classes contain too many devices to fit on one palette and have been broken up into several palettes; for example; Small Faceplates 1 and Small Faceplates 2.
4. Double-click on the desired wizard, then click on the window to place the wizard.
5. Once the wizard has been placed, double-click anywhere on the wizard to open a configuration dialog (if appropriate), and complete any necessary configuration based on the instructions later in this chapter.

The remainder of this chapter is devoted to describing and illustrating the various kinds of wizards included in the PMCS Interface Toolkit.

Page 14 of the GE PMCS 6.11a user manual — Configuration
Page 14 · click to enlarge
Page 14

Small Faceplate Wizards

GE PMCS 6.11a — Small Faceplate Wizards diagram (page 14)
Fig. 3 · Small Faceplate Wizards

Usage

The Small Faceplate wizards are icon-sized graphics typically used to create accurate elevation views and one-line diagrams. These wizards are provided with logic to open another window, typically either a Large Faceplate or Tabular Data Screen wizard. There are two palettes of Small Faceplates to choose from.

Configuration

In development mode, after placing the Small Faceplate, double-click on the icon to open the Small Faceplate Dialog box, as illustrated below. Typically, a Small Faceplate wizard is linked to a window containing either a Large Faceplate or a Tabular Data Screen wizard. You can move or resize Small Faceplate wizards in the window as desired.

Page 15 of the GE PMCS 6.11a user manual — Small Faceplate Wizards
Page 15 · click to enlarge
Page 15

Enter the name of the window to open when the icon is clicked on during runtime.

GE PMCS 6.11a — Small Faceplate Wizards diagram (page 15)
Fig. 4 · Small Faceplate Wizards
Page 16 of the GE PMCS 6.11a user manual — Usage
Page 16 · click to enlarge
Page 16

Large Faceplate Wizards

GE PMCS 6.11a — Large Faceplate Wizards diagram (page 16)
Fig. 5 · Large Faceplate Wizards

Usage

Large Faceplate wizards are three-dimensional representations of device faceplates that can be used to display data from the device. These three-dimensional wizards include extensive logic that provides an accurate reproduction of the actual display and keys of the device. Large Faceplate wizards are typically placed in overlay windows.

Page 17 of the GE PMCS 6.11a user manual — EPM 7700
Page 17 · click to enlarge
Page 17

Configuration

Place the Large Faceplate wizard into an open window, then double-click on it to display the Large Faceplate Dialog box. Configure the wizard by entering the appropriate information into each of the boxes.

The figure shown below is the dialog for a typical wizard. Some wizards have additional features which may be configured. See the section titled Features of GE Large Faceplate Wizards for more details.

Enter the unique eight-character name matching the appropriate Topic in the PMCS DDE Server.

GE PMCS 6.11a — Configuration diagram (page 17)
Fig. 6 · Configuration

Enter the application name of the PMCS DDE Server (GE32MODB or GE32MTCP) for most PMCS devices; ION_LINK for EPM 7700 devices).

Enter the minimum security level for enabling remote command functions.

Enter the name of the window to open when the device display is clicked on during runtime.

You can move and resize Large Faceplate wizards as desired.

Special Considerations

The button controls on the 3-D representation emulate the controls of the actual device. This may be useful for reducing software training time for personnel already familiar with device operation. The detailed features of each of the Large Faceplate wizards are described in the section titled Features of GE Large Faceplate Wizards.

EPM 7700

The EPM 7700 Large Faceplate Dialog box contains an extra field, which must be completed during configuration. The Node Name field requires that you enter the name of the computer running the Communications Server that connects to this particular device. Depending on the configuration of the EPM7700 network, this can be either the Primary node computer, or a computer setup as a "Full Station" Secondary node. Refer to DEH-40035, the GE 7700 Gateway Users Guide, and GEH-6514, PMCS Read This Book First, for more information on network configuration. The Node Name field is required because the EPM7700 does not use the same DDE server as the rest of the standard PMCS devices, and the wizard must be directed to the location of the correct Communications Server for proper configuration of DDE topic names.

Page 18 of the GE PMCS 6.11a user manual — Configuration
Page 18 · click to enlarge
Page 18

Also, the Application Name field must be completed as ION_LINK rather than GE32MODB or GE32MTCP for the EPM7700 device. The ION LINK program is installed during initial PMCS 6.11a setup if the EPM7700 software option is selected.

When configuring Wizards on Secondary nodes, the Application Name field entry does not follow the PMCS wizard convention of “\\RemoteComputer\ION_LINK”. EPM7700 Secondary nodes run a local copy of the ION LINK server, thus the application name for EPM7700 Large Faceplate wizards is always “ION_LINK” whether the wizard is installed on the Primary node or a Secondary node. The Node Name entry determines if the wizard is on a Secondary node.

Finally, the EPM 7700 device type requires special InTouch scripting for the large faceplate wizard. Refer to the section at the end of this chapter titled Special Scripting Considerations for the EPM 7700.

Page 19 of the GE PMCS 6.11a user manual — Configuration
Page 19 · click to enlarge
Page 19

Tabular Data Screen Wizards

GE PMCS 6.11a — Tabular Data Screen Wizards diagram (page 19)
Fig. 7 · Tabular Data Screen Wizards

Usage

Tabular Data Screen wizards contain organized, comprehensive, tabular layouts of device parameters including additional configuration and remote control features. Depending on the device, there may be multiple file-tabs beneath the tabular data section. These switch among various pages relating to data and setpoints.

Each Tabular Data Screen wizard contains buttons for activating the help file, trend window, setup window (if applicable), Event Logger, Waveform Capture, and for closing the window.

You can move and resize Tabular Data Screen wizards as desired.

Configuration

In development mode, after placing a wizard into an open window, double-click on it to display the Tabular Data Dialog box. The figure below shows the dialog box for a typical Tabular Data wizard. Some wizards have additional features which may be configured. See the section titled Features of Tabular Data Screen Wizards for more details.

Page 20 of the GE PMCS 6.11a user manual — EPM 7700
Page 20 · click to enlarge
Page 20

Enter the unique eight- character name matching the appropriate Topic in the PMCS DDE Server.

Use the Group Name field to logically group devices, if desired. Enter the name of the group to which the device belongs.

GE PMCS 6.11a — EPM 7700 diagram (page 20)
Fig. 8

Enter the application name of the PMCS DDE Server (GE32MODB or GE32MTCP).

Enter the minimum security level for enabling remote command and setup functions.

Enter the name of the window to be opened when the Trend button is clicked on during runtime.

Enter the name of the window to be opened when the Setup button is clicked on during runtime.

EPM 7700

The EPM 7700 Tabular Data Dialog box is slightly different from the other PMCS device types, containing two extra fields and requiring minor differences in configuration. The Tabular Data Dialog for the EPM 7700 is shown below, followed by the special configuration requirements.

GE PMCS 6.11a — EPM 7700 diagram (page 20)
Fig. 9

The Node Name field requires that you enter the name of the computer running the Communications Server that connects to this particular device. Depending on the configuration of the EPM7700 network, this can be either the Primary node computer, or a computer setup as a “Full Station” Secondary node. Refer to DEH-

Page 21 of the GE PMCS 6.11a user manual — 369 Motor Management Relay
Page 21 · click to enlarge
Page 21

40035, the GE 7700 Gateway Users Guide, and GEH-6514, PMCS Read This Book First, for more information on network configuration. The Node Name field is required because the EPM7700 does not use the same DDE server as the rest of the standard PMCS devices, and the wizard must be directed to the location of the correct Communications Server for proper configuration of DDE topic names.

Also, the Application Name field must be completed as ION_LINK rather than GE32MODB or GE32MTCP for the EPM7700 device. The ION LINK program is installed during initial PMCS setup if the EPM7700 software option is selected.

When configuring Wizards on Secondary nodes, the Application Name field entry does not follow the PMCS wizard convention of “\\RemoteComputer\ION_LINK”. EPM7700 Secondary nodes run a local copy of the ION LINK server, thus the application name for EPM7700 Tabular Data Wizards is always “ION_LINK” whether the wizard is installed on the Primary node or a Secondary node. The Node Name entry determines if the wizard is on a Secondary node.

The Gateway Name field must be completed with GE77GTWY, the application name of the GE 7700 Gateway Server program. When configuring the EPM7700 Tabular wizard on a Secondary node, the Gateway Name does follow the PMCS wizard convention of “\\RemoteComputer\GE77GTWY” in the Gateway Name field, where ‘RemoteComputer’ is the name of the PC where the GE 7700 Gateway application is running – the Primary Node. The following example shows a Tabular Data Dialog box as it would appear when configuring a Tabular Data wizard on a Secondary node. The Node Name field contains the name of the Primary Node computer, the Application Name field is ION_LINK (as it is for ALL EPM7700 wizards on ANY node) and the Gateway Name field points to the GE 7700 Gateway Server running on the Primary Node PC.

GE PMCS 6.11a — 369 Motor Management Relay diagram (page 21)
Fig. 10 · 369 Motor Management Relay

Finally, the EPM 7700 device type requires special InTouch scripting for the tabular data screen wizard. Refer to the section at the end of this chapter titled Special Scripting Considerations for the EPM 7700.

Refer to DEH-40035 for information on the Communications Server and 7700 Gateway Server.

369 Motor Management Relay

The 369 Motor Management Relay offers an optional Remote RTD module, which can provide support for up to 12 additional RTDs. Accordingly, the 369 Tabular

Page 22 of the GE PMCS 6.11a user manual — 369 Motor Management Relay
Page 22 · click to enlarge
Page 22

Data Dialog box has an extra field for indicating when the RRTD option is installed. Be sure to select the correct RRTD option when completing the 369's Tabular Data Dialog window. If you are not planning to use an RRTD module with your relay, select the "No" button. This minimizes the number of I/O tags created by the wizard, providing better performance.

GE PMCS 6.11a — 369 Motor Management Relay diagram (page 22)
Fig. 11 · 369 Motor Management Relay
Page 23 of the GE PMCS 6.11a user manual — Universal Relay
Page 23 · click to enlarge
Page 23

Universal Relay

The Universal Relay device comes in several different models, and each model supports different capabilities, which are reflected by the various tabs available for each model. When configuring a Universal Relay device, you first select the UR Model, then choose which tabs will be displayed for the particular device.

The UR devices are also capable of communicating with a different type of PMCS DDE Server than the other PMCS Advanced Wizards. By selecting the UCA/MMS checkbox, you indicate that you wish the UR wizard to retrieve its data for display from the MMS Server whose name is entered in the Application Name field.

GE PMCS 6.11a — Universal Relay diagram (page 23)
Fig. 12 · Universal Relay

Complete the Application Name field; typically GE32MODB or GE32MTCP. Special Note: The UCA/MMS is not supported in this version. So don’t Check this checkbox.

Select the Model of UR which you are configuring. This determines the contents of the Available Tabs list.

Highlight the tabs you wish to display on the Tabular Data Screen wizard. Use the control key to select multiple tabs.

Page 24 of the GE PMCS 6.11a user manual — Usage
Page 24 · click to enlarge
Page 24

One-Line Wizards

GE PMCS 6.11a — One-Line Wizards diagram (page 24)
Fig. 13 · One-Line Wizards

Usage

You can use one-line wizards to create animated one-line diagrams that represent an electrical schematic of the devices monitored by the software. These wizards are provided with logic to either open another window or display device status.

One-Line wizards are divided into five functional groups according to the type of animation:

  • Horizontal and Vertical Meter wizards display another window, such as a 3-D faceplate.
  • Transformer, Fuse, Ground Symbol, and Motor Symbol wizards have a discrete color-change animation indicating the On/Off state of the device.
  • Horizontal and Vertical Relay wizards also have discrete color-change animation indicating the On/Off state of the device.
  • Horizontal and Vertical Switch wizards have four discrete animations; two are color changes indicating the On/Off state of the device and two are used for a three-state display (Open, Closed, and Error conditions).
Page 25 of the GE PMCS 6.11a user manual — Meter One-Line Wizards
Page 25 · click to enlarge
Page 25
  • Circuit Breaker wizards have two discrete color-change animations for On/Off status display and one analog animation for a five-state display (Open, Closed, Out, Trip, and Error conditions).
  • Lockout/Tagout symbols have discrete visibility animations for various tags. Refer to the section Using and Configuring PMCS Wizards: Lockout/Tagout Wizard for more information.

Configuration

In development mode, after placing the one-line device icon, double-click on the icon to open its configuration dialog box. All one-line wizards have two configuration items in common:

  • Line Size is a number between 1 and 20 that sets the pixel width of the lines in the wizard.
  • Size configuration consists of three radio buttons ( Small , Medium , and Large ) that determine the overall size of the wizard on the screen.

Use the snap-to-grid feature in InTouch to quickly align One-Line wizards.

Configuration of each of the five classes of One-Line wizards is described below.

Meter One-Line Wizards

After placing a meter wizard in a window, double-click on it to display the dialog box shown below. Configure the wizard by entering the appropriate information into each of the boxes.

GE PMCS 6.11a — Meter One-Line Wizards diagram (page 25)
Fig. 14 · Meter One-Line Wizards

Enter the name of the window to open when the icon is clicked on during runtime.

Select the color of the meter wizard.

Page 26 of the GE PMCS 6.11a user manual — Transformer, Fuse, Ground, and Motor One-Line Wizards
Page 26 · click to enlarge
Page 26

Transformer, Fuse, Ground, and Motor One-Line Wizards

After placing a Fuse, Ground, or Motor wizard in a window, double-click on it to display the dialog box shown below. Configure the wizard by entering the appropriate information into each of the boxes.

Enter the name of the InTouch discrete tag that determines the state of the line colors during runtime.

GE PMCS 6.11a — Transformer, Fuse, Ground, and Motor One-Line Wizards diagram (page 26)
Fig. 15 · Transformer, Fuse, Ground, and Motor One-Line Wizard…

Specify the colors of the lines when the Bus Status is On and Off. The wizard is displayed in the On Color when the Bus Status Tagname = 1, Off Color when the Bus Status Tagname = 0.

The dialog box for the Transformer wizard has an extra check box that specifies either an air-core or iron-core transformer, as shown below.

GE PMCS 6.11a — Transformer, Fuse, Ground, and Motor One-Line Wizards diagram (page 26)
Fig. 16 · Transformer, Fuse, Ground, and Motor One-Line Wizard…

Click on the check box to specify an air-core transformer.

Page 27 of the GE PMCS 6.11a user manual — Horizontal and Vertical Relay One-Line Wizards
Page 27 · click to enlarge
Page 27

Horizontal and Vertical Relay One-Line Wizards

After placing a Horizontal or Vertical Relay wizard in a window, double-click on it to display the dialog box shown below. Configure the wizard by entering the appropriate information into each of the boxes.

Enter the name of the InTouch discrete tag that determines the color of the line to the right (or top) of the relay symbol during runtime.

Enter the name of the InTouch discrete tag that determines the color of the line to the left (or bottom) of the relay symbol during runtime.

GE PMCS 6.11a — Horizontal and Vertical Relay One-Line Wizards diagram (page 27)
Fig. 17 · Horizontal and Vertical Relay One-Line Wizards

Click the check box to display a slash through the contacts (normally closed contact).

Specify the colors of the wizard elements when the contact status and connection discrete tags are On or Off.

Enter the name of the InTouch discrete tag that determines the color of the relay symbol during runtime.

Page 28 of the GE PMCS 6.11a user manual — Horizontal and Vertical Switch One-Line Wizards
Page 28 · click to enlarge
Page 28

Horizontal and Vertical Switch One-Line Wizards

After placing a Horizontal or Vertical Switch wizard in a window, double-click on it to display the dialog box shown below. Configure the wizard by entering the appropriate information into each of the boxes.

Enter the name of the InTouch discrete tag that determines the color of the line to the left (or bottom) of the switch symbol during runtime.

Enter the name of the InTouch discrete tag that determines the color of the line to the right (or top) of the switch symbol during runtime.

GE PMCS 6.11a — Horizontal and Vertical Switch One-Line Wizards diagram (page 28)
Fig. 18 · Horizontal and Vertical Switch One-Line Wizards

Enter the names of the InTouch discrete tags that determine the state of the switch during runtime.

Specify the colors of the wizard elements when the connection and switch discrete tags are On and Off and when there is an Error condition. The switch symbol color is determined by the following logic:

SwOpen SwClosed Color 0 0 error 0 1 on 1 0 off 1 1 error

Page 29 of the GE PMCS 6.11a user manual — Breaker Status Value Text Default Color
Page 29 · click to enlarge
Page 29

Circuit Breaker One-Line Wizards

After placing a Horizontal or Vertical Circuit Breaker wizard in a window, double- click on it to display the dialog box shown below. Configure the wizard by entering the appropriate information into each of the boxes.

Enter the name of the InTouch discrete tag that determines the color of the line to the right (or top) of the breaker symbol during runtime.

Enter text to display next to the breaker graphic during runtime (optional).

GE PMCS 6.11a — Circuit Breaker One-Line Wizards diagram (page 29)
Fig. 19 · Circuit Breaker One-Line Wizards

Enter the name of the InTouch discrete tag that determines the color of the line to the left (or bottom) of the breaker symbol during runtime.

Specify the colors of the wizard elements and status text for the breaker states during runtime. See the table below for default status/color mappings.

Enter the name of the InTouch analog tag that determines the color of the circuit breaker symbol, the state of the breaker, and the status text displayed next to the breaker icon during runtime.

The breaker status values and the associated default colors are listed in the table below. Error status indicates that the breaker status inputs create an indeterminate state for the breaker.

Breaker Status Value Text Default Color

Open 1 OPN Green

Closed 3 CLD Red

Drawn Out 5 OUT Green

Tripped 7 TRP Yellow

Error 9 ERR Flashing Red

Breaker status values & display colors.

Page 30 of the GE PMCS 6.11a user manual — Configuration
Page 30 · click to enlarge
Page 30

Elevation Wizards

GE PMCS 6.11a — Elevation Wizards diagram (page 30)
Fig. 20 · Elevation Wizards

Usage

Elevation wizards are graphical elements that represent switchgear components useful for creating 3-D elevation views. These wizards are not associated with any logic or animation, but are provided to create more visually accurate screens and representations of equipment. Device icon wizards are typically placed on the Elevation wizards to show the breakers, trip units, and meters and provide navigation to device 3-D wizards, tabular displays, or arbitrary windows.

Configuration

After placing an Elevation wizard in an open window, it may be moved or resized, but no other configuration is possible. Elevation wizards are not provided with logic for opening another window.

Page 31 of the GE PMCS 6.11a user manual — Configuration
Page 31 · click to enlarge
Page 31

Floor Plan Wizards

GE PMCS 6.11a — Floor Plan Wizards diagram (page 31)
Fig. 21 · Floor Plan Wizards

Usage

Floor Plan wizards are graphical elements that are useful for creating accurate representations of a facility layout. You can use a floor layout as an overview display of an entire plant, with animated areas for navigation to various switchgear elevation views or one-line diagrams. You can paste miniature elevation views as bitmap objects onto the floor layout, sized to fit, and then animate them as push buttons to display elevation views or one-line diagrams (see Chapter 3).

Configuration

After placing a Floor Plan wizard in an open window, it may be moved or resized, but no other configuration is possible. Floor Plan wizards are not provided with logic for opening another window.

Page 32 of the GE PMCS 6.11a user manual — Configuration
Page 32 · click to enlarge
Page 32

Toolbar Wizard

GE PMCS 6.11a — Toolbar Wizard diagram (page 32)
Fig. 22 · Toolbar Wizard

Usage

The Toolbar wizard is a navigational tool which allows the user to move between recently-used or frequently-used windows, and provides a clock for quick reference.

The first/last arrows jump to the first or last window in the windows list (see Configuration below); the inner forward and back arrows move to the next or previous window in the list. The window buttons to the right of the arrows provide quick access to the windows assigned to each button.

Configuration

The arrow buttons on the Toolbar wizard operate by maintaining a list of windows for access by the toolbar navigational controls. To allow a window to be added to the windows list when viewed by a user, a call to WLAddWindow( ) must be placed in the OnShow window script. This call must be placed in each window that you want to have on the window list.

The eight hot buttons are configured by double clicking on the wizard, and completing the Toolbar Wizard Edit dialog box:

GE PMCS 6.11a — Configuration diagram (page 32)
Fig. 23 · Configuration

For each button, you can set the top and bottom caption, and specify the window to be opened when that button is clicked.

Page 33 of the GE PMCS 6.11a user manual — Annunciator Panel Theory of Operation
Page 33 · click to enlarge
Page 33

Annunciator Panel Wizard

GE PMCS 6.11a — Annunciator Panel Wizard diagram (page 33)
Fig. 24 · Annunciator Panel Wizard

Usage

The Annunciator Panel wizard provides an industrial-style annunciator display panel, consisting of a bank of 48 indicator lights which change colors and blink to indicate various device conditions. For instance, a circuit breaker could be associated with an annunciator panel wizard to display grey when closed and change to red if it trips.

This wizard requires the PMCS Event Logger software to be installed and properly configured before it can be used, because it operates by monitoring special DDE tags which change state based on alarms or events recorded by the Event Logger.

The panel consists of an array of 48 buttons (six columns by eight rows), each of which may be labeled with up to three lines of text, and each of which is associated with a particular device (topic) at the PMCS DDE Server.

The annunciator panel wizard provides buttons for acknowledging alarms, resetting acknowledged alarms, and for viewing an alarm summary via the PMCS Event Logger.

Annunciator Panel Theory of Operation

The Annunciator Panel wizard provides a screen full of indicator tiles, each relating to a particular device, event, or group of events. These tiles are displayed in different colors to indicate different alarm conditions. The Annunciator Panel wizard monitors selected DDE items in the Event Logger and responds to changes of state in these items by changing the colors of individual indicator tiles. For example, you might configure a relay trip event to have a tile in the Annunciator Panel wizard. The wizard monitors a DDE tag at the Event Logger corresponding to the trip status of the relay and displays a grey indicator if the relay is operating properly, and a red indicator if the relay has tripped.

Page 34 of the GE PMCS 6.11a user manual — Annunciator Panel Wizard
Page 34 · click to enlarge
Page 34

From the Event Logger’s perspective, there are two parts to configuring the Annunciator Panel. First, each DDE Item that will be displayed on the Annunciator Panel wizard must be added (using the Add Items dialog). For the example we’re discussing, we’ll assume you’ve created a DDE Item named Trip1. Each DDE item will connect to an individual tile in the Annunciator Panel wizard.

The second part consists of defining events which will turn individual DDE items ON or OFF. Each DDE item (or Annunciator Panel tile) can be turned on or off by any number of device events you define. The events are logically ORed together to determine ON or OFF conditions; i.e., if any of the events occurs, the DDE item is ON; if none of the events have occurred, the DDE item remains OFF.

We’ll continue the relay example we began above. For example, you might configure the Trip1 DDE Item to be ON if any of the following events occurs: the relay is tripped, or the relay reports an error condition, or the relay senses an overvoltage condition. The Annunciator Panel wizard displays a grey indicator tile for the relay for as long as the DDE item remains in the OFF condition. If the Annunciator Panel wizard sees the DDE Item change from OFF to ON, it reacts by changing the indicator tile from grey to red. The Event Logger Annunciator Panel logic will also change the state of a DDE Item in response to actions performed at the Annunciator Panel Wizard. The user can both acknowledge and reset individual Annunciator DDE Items. The following diagram shows the relationship of the Annunciator Panel wizard, the Event Logger, and the PMCS DDE Server.

Page 35 of the GE PMCS 6.11a user manual — Annunciator Panel Wizard
Page 35 · click to enlarge
Page 35

Annunciator Panel Wizard monitors DDE Items at Event Logger

DDE Item NameTrip1 Status: OFF

Configured Events Received Relay Tripped? NO Error Condition? NO Overvoltage Condition? NO

Event Logger tracks events reported by PMCS DDE Server

Annunciator Panel Wizard monitors DDE Items at Event Logger

DDE Item NameTrip1 Status: ON

Configured Events Received Relay Tripped? YES Error Condition? NO Overvoltage Condition? NO

Event Logger tracks events reported by PMCS DDE Server

In the upper illustration, the Event Logger watches for any of the three events configured to cause a change of state to the Trip 1 DDE Item. None of these three events have occurred, so the status of the Trip 1 DDE Item is at OFF. The Annunciator Panel wizard is monitoring the configured DDE Items at the Event Logger, but all DDE Items are “OFF” so the Annunciator Panel displays green indicator tiles.

In the lower illustration, the Event Logger has recorded a “Trip” event for the unit in question, and changed the state of the Trip 1 DDE Item to “ON”. The Annunciator Panel wizard sees this change, and responds by changing the color of the annunciator panel tile for Relay 1 to red.

Show 22 more labels / short text on this page
Relay 1 (green) · Relay 2 · Relay 3 · (green) · (green) · Annunciator Panel Wizard · Event Logger · Relay 1 · PMCS DDE Server · Relay 2 · Relay 3 · Relay 1 · Relay 2 (green) · Relay 3 · (red) · (green) · Annunciator Panel Wizard · Event Logger · Relay 1 · PMCS DDE Server · Relay 2 · Relay 3
Page 36 of the GE PMCS 6.11a user manual — State Tag Value
Page 36 · click to enlarge
Page 36

Each "Alarm indicator" as defined by the Event Logger will appear to InTouch as a DDE Integer item which can have the following values/states:

State Tag Value

Default Color

Normal (no alarm) 10 - 19 Solid Gray

Alarm Active - Unacknowledged 20 - 29 Red Blinking

Alarm Active - Acknowledged 30 - 39 Solid Red

Alarm Reset - Unacknowledged (alarm occurred but later went off before being acknowledged)

40. 49 Solid Yellow

Alarm Disabled (Event Logger has disabled this alarm indicator)

Each panel button displays one of five different colors, based on the states defined above. A fill color animation link controlled by an indirect integer tag is used to change colors. The fill color link is set as follows:

<= 9Dark Grey
10 -> 19Grey
20-> 29Grey (will also have a flashing Red animation link)
30 -> 39Red
>= 40Yellow

0 Dark Gray

Page 37 of the GE PMCS 6.11a user manual — Configuration
Page 37 · click to enlarge
Page 37

Configuration

When the Annunciator Panel wizard is dropped, it appears as a blank panel of 48 indicators:

GE PMCS 6.11a — Configuration diagram (page 37)
Fig. 25 · Configuration
Page 38 of the GE PMCS 6.11a user manual — Configuration
Page 38 · click to enlarge
Page 38

Double-click on the wizard to display the Annunciator Panel Dialog:

GE PMCS 6.11a — Configuration diagram (page 38)
Fig. 26 · Configuration

Complete the Annunciator Panel Name field (up to 8 characters), and the Security Access Level (level of security required to Reset any Acknowledged alarms. The color codes for different alarm states can be modified by clicking on each color. Note that the color codes apply to all 48 indicators on the annunciator panel wizard.

Finally, click on an indicator to display the configuration dialog for that individual button:

Page 39 of the GE PMCS 6.11a user manual — Configuration
Page 39 · click to enlarge
Page 39

Enter the text to display on any of the three lines available for the selected button. It is not necessary to enter text on all three lines. Click OK when you have finished assigning text labels to the button.

As each annunciator panel button is labeled, the Annunciator Panel Dialog reflects these changes by showing the Row/Column coordinates of the labeled buttons:

GE PMCS 6.11a — Configuration diagram (page 39)
Fig. 27 · Configuration

When you have finished labeling your annunciator panel buttons, click OK to close the Annunciator Panel Dialog box. When you close this dialog box, InTouch automatically creates indirect analog tags for each panel button. These tags are named xxx_R1C1 through xxx_R8C6, where xxx is the name assigned to the wizard (for example, Panel1), and R1C1 indicates the row and column position on the annunicator panel.

Page 40 of the GE PMCS 6.11a user manual — Configuration
Page 40 · click to enlarge
Page 40
GE PMCS 6.11a — Configuration diagram (page 40)
Fig. 28 · Configuration

Two steps remain after the wizard has been configured.

First, InTouch DDE Integer tags must be created for the DDE items configured in the Event Logger corresponding to the Alarm Panels. Make sure the DDE Item names created in InTouch match the DDE Item names configured in Event Logger. (If you are unsure of how to create DDE tags in InTouch, please refer to WonderWare’s documentation.) The DDE Access name for the Event Logger should be configured in InTouch as follows:

GE PMCS 6.11a — Configuration diagram (page 40)
Fig. 29 · Configuration

Second, an InTouch script must be written to associate the InTouch indirect tags created by the wizard with the InTouch DDE tags created for DDE Items in Event Logger. Typically, this script is placed in the InTouch “On Startup” application script.

Page 41 of the GE PMCS 6.11a user manual — Configuration
Page 41 · click to enlarge
Page 41

An example of a simple script is shown below:

Panel1_R1C1.Name = ANN_P_1A.Name;

Panel1_R1C2.Name = ANN_P_1B.Name;

Panel1_R1C3.Name = ANN_P_2A.Name;

At run-time, InTouch will receive DDE data from the Event Logger which will control the colors of all indicators that have been configured properly.

Page 42 of the GE PMCS 6.11a user manual — Troubleshooting Tips for the Annunciator Panel Wizard
Page 42 · click to enlarge
Page 42

Troubleshooting Tips for the Annunciator Panel Wizard

  • Make sure that all DDE Items associated with the annunciator panel have been created in the Event Logger.
  • You must create associated InTouch DDE Integer Tags by hand in the InTouch tagname database. The DDE Access name for the tags should use “EVENTLOG” for the Application Name and “SYSTEM” for the Topic Name. Make sure the “Request Initial Data” option is selected for this DDE Access name.
  • Check the WWLogger at runtime for possible DDE errors.
  • Make sure your application script is mapping the proper DDE tags with the proper indirect tags.
  • Make sure the Event Logger is running before starting InTouch Windowviewer.
Page 43 of the GE PMCS 6.11a user manual — Configuration
Page 43 · click to enlarge
Page 43

Custom Table Wizard

GE PMCS 6.11a — Custom Table Wizard diagram (page 43)
Fig. 30 · Custom Table Wizard

Usage

The Tabular Data Screen wizards provide the ability to view extensive device data in tabular form. However, they do not allow you to select the data to view - you must view all the data presented and locate the particular data points you are interested in.

The Custom Table wizard differs from the Tabular Data wizards by providing an easy-to-use, highly-flexible way to view a limited number of registers for a particular device. It presents only the data you are interested in, displaying it in a convenient table format as shown above. Each table consists of 1 to 12 rows of information, one register per row.

Each table takes up approximately one-quarter of an average display, so up to four Custom Table wizards may be placed on a screen.

Configuration

When the Custom Table wizard is dropped, it appears as a blank screen. Double- click on the wizard to display the Custom Table Dialog:

Page 44 of the GE PMCS 6.11a user manual — Field Description
Page 44 · click to enlarge
Page 44
GE PMCS 6.11a — Custom Table Wizard diagram (page 44)
Fig. 31 · Custom Table Wizard

Begin configuring the Custom Table by completing the following fields:

Field Description

Device Name Enter the name of the device (topic). Must exactly match the topic name at the DDE Server.

DDE Server Name Enter the name of the PMCS DDE Server.

Device Description Optionally, enter a brief description of this device, up to 32 characters maximum.

Device Type Select the device type corresponding to this topic.

Page 45 of the GE PMCS 6.11a user manual — Custom Table Wizard
Page 45 · click to enlarge
Page 45

EPM 7700 Users Only: When the EPM 7700 device type is selected, an additional field appears in the Custom Table Dialog box, adjacent to the Device Name (shown below).

GE PMCS 6.11a — Custom Table Wizard diagram (page 45)
Fig. 32 · Custom Table Wizard

The Node Name field requires that you enter the name of the computer on which the meter’s Communications Server is located, either the Primary Node or a Full Station Secondary Node. This field is required because the EPM 7700 does not use the same DDE Server as the rest of the standard PMCS devices, and the wizard must be directed to the location of the correct Communications Server for proper configuration of DDE topic names. For more information on configuring EPM7700 networks, refer to DEH-40035, the GE 7700 Gateway Users Guide, and GEH-6514, PMCS Read This Book First.

Also, the Application name field must be completed as ION_LINK rather than GE32MODB or GE32MTCP for the EPM7700 device. The ION LINK program is installed during initial PMCS setup if the EPM7700 software option is selected.

When configuring Custom Tabular wizards on Secondary nodes, the Application Name field entry does not follow the PMCS wizard convention of “\\RemoteComputer\ION_LINK”. EPM7700 Secondary nodes run a local copy of the ION LINK server; thus the application name is always “ION_LINK” whether the wizard is installed on the Primary node or a Secondary node.

Finally, the EPM 7700 device type requires special InTouch scripting for the custom tabular wizard. Refer to the section at the end of this chapter titled Special Scripting Considerations for the EPM 7700.

Page 46 of the GE PMCS 6.11a user manual — Custom Table Wizard
Page 46 · click to enlarge
Page 46

When these fields are completed, click the Select Multiple Tags button to select several tags at once, or click the Select Tag X button to assign tags one at a time. The Select Device Tags dialog appears:

GE PMCS 6.11a — Custom Table Wizard diagram (page 46)
Fig. 33 · Custom Table Wizard

The Select Device Tags dialog shows a list of all the pre-configured tags which the Custom Table wizard supports for the selected device type, sorted by address, and displaying the tagname and description. Most tags are metering value registers.

Select up to twelve tags from the list by clicking (high-lighting) each one. To de- select a tag, simply click it a second time. When you have selected up to 12 tags, click OK to return to the Custom Table dialog box. The selected tags will now be displayed as shown in the following example:

Page 47 of the GE PMCS 6.11a user manual — Custom Table Wizard
Page 47 · click to enlarge
Page 47
GE PMCS 6.11a — Custom Table Wizard diagram (page 47)
Fig. 34 · Custom Table Wizard

You may select OK to select this table configuration, or you may edit the tags one at a time using the Select Tag X buttons (for instance, if you wish to change the order the tags appear in).

The tag descriptions and units may also be edited (useful for non-English applications), but caution is urged when modifying descriptions or units; it may be difficult to remember what they were originally if needed.

Note for users of the MDP device type: This device uses a memory tag to scale many of the data values displayed in the wizard.: "DeviceName_CTRatio" (where DeviceName is the name entered for the device within the wizard). The wizard creates this tag within InTouch (memory tag with a format type of "Real"). The InTouch application must provide a value for this tag (usually entered by the user at run-time). If no value is entered at runtime, a value of zero will be used as the default value for this tag, and many of the metering data registers (AMPS A, B, C, etc) on this device type will appear as zero as well. See the MDP Tabular Data wizard for additional information. If the application has a Tabular Data Screen Wizard with the same device name as this wizard, then the end user can set the CTRatio tag value via the MDP Tabular Data Screen wizard.

Page 48 of the GE PMCS 6.11a user manual — Configuration
Page 48 · click to enlarge
Page 48

System Statistics Wizard

GE PMCS 6.11a — System Statistics Wizard diagram (page 48)
Fig. 35 · System Statistics Wizard

Usage

The System Statistics wizard is an informational tool which allows the user to view detailed statistics about the system, including port information from the DDE Server and disk information.

The wizard consists of a single screen displaying Port Statistics on the top portion and disk information on the bottom. Statistics on up to eight COM ports are displayed. The user may page forward or backward eight ports at a time by clicking the Prev 8 Ports or Next 8 Ports button.

Whenever a new DDE Server name is entered, the user must click the Refresh button to update the DDE links to correspond to the new parameters.

Configuration

When the wizard is dropped, the following dialog box appears:

Page 49 of the GE PMCS 6.11a user manual — System Statistics Wizard
Page 49 · click to enlarge
Page 49
GE PMCS 6.11a — System Statistics Wizard diagram (page 49)
Fig. 36 · System Statistics Wizard

The System Statistics wizard requires a name itself, and also the name of a DDE Server to access.

By default, the System Statistics wizard assumes that the DDE Server is located locally and is named GE32MODB. You may change this to access a DDE Server located on a networked PC by entering the name as \\NODENAME\SERVER, where NODENAME is the name of the host PC and SERVER is the name of the PMCS DDE Server, which will be GE32MODB.

During runtime, the default drive letter is C, corresponding to the local hard drive. You may change this value to any valid drive letter corresponding to either a fixed local drive or a mapped network drive.

Page 50 of the GE PMCS 6.11a user manual — Supported Devices
Page 50 · click to enlarge
Page 50

Lockout/Tagout Wizard

GE PMCS 6.11a — Lockout/Tagout Wizard diagram (page 50)
Fig. 37 · Lockout/Tagout Wizard

Usage

The Lockout/Tagout provides a method for assigning danger or ground tag graphics to various one-line diagrams or wizards.

On-screen tags and indicators are for informational purposes only and DO NOT represent real-world conditions! Actual lockout status must be verified prior to performing any work. Failure to follow appropriate lockout procedures can result in SEVERE INJURY or DEATH!

The Wizard consists of a single screen (shown above) displaying the presence or absence of danger and ground tags for a particular device. The user installs or removes Danger and/or Ground Tags using the Install/Remove buttons on the Tag Assignment window shown above. Any wizards belonging to the same Status Group will display Danger and/or Ground Tag indicators mirroring the tags installed in the Tag Assignment window.

Supported Devices

Page 51 of the GE PMCS 6.11a user manual — Configuration
Page 51 · click to enlarge
Page 51

Several PMCS breaker management devices support the Lockout/Tagout Wizard in their Large Faceplate and Tabular Data Screen wizards. These devices are:

  • 750 / 760 Feeder Management Relay

Configuration

When Lockout/Tagout wizard is dropped and double-clicked, the following dialog box appears:

GE PMCS 6.11a — Configuration diagram (page 51)
Fig. 38 · Configuration

Complete the following fields to configure the Lockout/Tagout Panel Display:

  • Enter a name for this panel. The Panel Name is used to distinguish the tags used internally by a particular instance of a panel from other panels within an application. Each panel within an application should have a unique Panel Name.
  • Enter the name of the Status Group associated with this Lockout/Tagout Panel. The Status Group is the name that links this panel to Lockout/Tagout Online Symbols and the breaker management device wizards that can support it. It is important to remember the Status Group assignment since it must be used to configure the associated Oneline Symbols and IED wizards.
  • Enter the minimum Security Level required to add and remove Danger or Ground tag symbols within the application.

The second part of the Lockout/Tagout wizard that can be configured is the Oneline Tagout Symbol.

The Oneline Tagout Symbol is a small wizard for placement in oneline diagrams, to be associated with a circuit breaker. It displays the presence or absence of any Danger or Ground tag symbols assigned to the breaker symbol by the PMCS user. After dropping the Oneline Tagout Symbol wizard onto a oneline diagram, associate it with a particular circuit breaker and any other devices you wish to have the tags displayed at by making it a member of a Status Group. The Oneline Tagout Symbol Dialog box is displayed when you double-click the wizard:

Page 52 of the GE PMCS 6.11a user manual — Example of Lockout/Tagout Wizard
Page 52 · click to enlarge
Page 52
GE PMCS 6.11a — Example of Lockout/Tagout Wizard diagram (page 52)
Fig. 39 · Example of Lockout/Tagout Wizard

Complete the following fields:

  • Enter the name of the Status Group associated with this Lockout/Tagout symbol. The Status Group is the name that links this symbol to the Lockout/Tagout panel and the breaker management device wizards that can support it. It is important to remember the Status Group assignment since it must be used to configure the associated panel and IED wizards.
  • Enter the name of the window to open when the Oneline Tagout Symbol wizard is clicked on during runtime. It should be the name of the window in which the Lockout/Tagout Panel is located.

Example of Lockout/Tagout Wizard

The following example may help clarify the use of the Lockout/Tagout wizard.

Suppose that we have a breaker being monitored by a redundant pair of ML 750/760 devices in our system. We wish to be able to display Lockout/Tagout symbols for this breaker.

We create a oneline diagram in InTouch which represents this configuration, placing the circuit breaker wizard, then each of the ML 750/760 small faceplate wizards, then a Lockout/Tagout wizard for each ML 750/760 device. It looks like this:

GE PMCS 6.11a — Example of Lockout/Tagout Wizard diagram (page 52)
Fig. 40 · Example of Lockout/Tagout Wizard

When configuring the Lockout/Tagout wizard in the oneline diagram, we complete the Oneline Tagout Symbol dialog as follows:

Page 53 of the GE PMCS 6.11a user manual — Example of Lockout/Tagout Wizard
Page 53 · click to enlarge
Page 53

Breaker_Group_1 is the name of the Status Group we’ll assign to all wizards associated with this breaker; Tag Window is the name of the window we want to appear when someone clicks on the Oneline Tagout wizard during runtime.

Next, we create separate screens containing Large Faceplate wizards and Tabular Data screen wizards for each ML 750/760 device. While configuring each wizard, we make sure that each one is given the Status Group “Breaker_Group_1”. This ensures that any Danger or Ground tag symbols present will be shown on any large faceplate, tabular data screen, or oneline wizards associated with this group. An example of the Tabular Data configuration dialog box is shown below; note that the Status Group field is assigned to Breaker_Group_1, the same Status Group as our Oneline Tagout Symbol wizard. Do not confuse the Status Group parameter with the Group Name parameter. The Group Name parameter is not used for configuring Lockout/Tagout Status Groups.

GE PMCS 6.11a — Example of Lockout/Tagout Wizard diagram (page 53)
Fig. 41 · Example of Lockout/Tagout Wizard

We drop and configure our Lockout/Tagout Wizard next; double clicking this wizard, the Lockout/Tagout Panel dialog appears:

Page 54 of the GE PMCS 6.11a user manual — Example of Lockout/Tagout Wizard
Page 54 · click to enlarge
Page 54

We name the Lockout/Tagout panel Panel_1. We associate the Panel with the same Status Group as our other wizards, Breaker_Group_1. Finally, we set the minimum security level required to add or remove tags.

Now in Runtime mode, when the Tag Assignments dialog is displayed, it appears as follows:

GE PMCS 6.11a — Example of Lockout/Tagout Wizard diagram (page 54)
Fig. 42 · Example of Lockout/Tagout Wizard

Clicking Install Danger Tag checks our security level, and if we have sufficient access, displays a Danger Tag for the breaker as follows:

Page 55 of the GE PMCS 6.11a user manual — Example of Lockout/Tagout Wizard
Page 55 · click to enlarge
Page 55
GE PMCS 6.11a — Example of Lockout/Tagout Wizard diagram (page 55)
Fig. 43 · Example of Lockout/Tagout Wizard

The Installed By field on the tag shows the name of the current operator who installed the tag; the Installed At field shows the time and date stamp of the tag’s installation.

When we view a wizard which belongs to this group, for example the Large Faceplate wizard of one of our ALPS devices, the Danger tag shows up as a red indicator with a “D” in it, as shown below:

GE PMCS 6.11a — Example of Lockout/Tagout Wizard diagram (page 55)
Fig. 44 · Example of Lockout/Tagout Wizard
Page 56 of the GE PMCS 6.11a user manual — Special Scripting Considerations for the EPM 7700
Page 56 · click to enlarge
Page 56

Special Scripting Considerations for the EPM 7700

This section describes the special InTouch scripting which is required for the EPM 7700 device’s Large Faceplate, Tabular Data Screen, and Custom Tabular wizards. The EPM 7700 is a powerful and highly flexible device, supporting hundreds of discrete data items. This scripting is required due to the large number of DDE items available for this device type. For performance reasons, not all DDE items are kept active simultaneously by the EPM 7700 Tabular Data Screen wizard; at any given moment, DDE items which are not used may be disconnected to save the Server the additional overhead of monitoring unused items. The scripts described in this section automatically configure the DDE links used by the Tabular Data Screen wizard when it is displayed, and enable the Large Faceplate wizard to re-connect to items which may have been disabled by the Tabular Data Screen wizard.

Templates for the required scripts are automatically installed in the InTouch directory when PMCS is installed with the EPM 7700 Software Components option selected. You may use the Notepad accessory program to open the files, then copy the text from the file to InTouch when appropriate.

There are three scripts described in this section. The first script is an InTouch Application Script that is required whenever a Large Faceplate or Tabular Data Screen wizard is installed for a given device. The purpose of this script is to provide communication status indication on the wizard. If the application script is not installed, the “Communications Failed” indicator on the Large Faceplate and Tabular Data wizards will not function. The second script, the EPM 7700 Large Faceplate/Custom Table Script, is an InTouch Window Script that must be applied to each Large Faceplate and Custom Tabular wizard window. This script ensures that any tags which were disabled by the Tabular Data wizard are properly restored when switching to a Large Faceplate or Custom Table screen. The third script, the Tabular Data Screen Script, also an InTouch Window Script, applies only to the EPM 7700 Tabular Data Screen wizard. Its purpose is to automatically initialize the wizard for optimum performance whenever its window is displayed.

Page 57 of the GE PMCS 6.11a user manual — Installing the Application Script
Page 57 · click to enlarge
Page 57

Installing the Application Script

1. After configuring the EPM 7700 Large Faceplate wizard or Tabular Data Screen wizard, select “Special \ Scripts \ Application Scripts…” from the WindowMaker main menu. The Application Script Dialog box opens:
GE PMCS 6.11a — Installing the Application Script diagram (page 57)
Fig. 45 · Installing the Application Script

2. Select “While Running” from the Condition Type drop down list, and enter “30000” in the “Every … Msec” text box next to the Condition Type drop down list. 3. Use Notepad.exe to open the file “EPM7700 Application Script.txt”, located in the Intouch directory of the PC. Select (highlight) all the file text and copy it to the clipboard using the CTRL-C keyboard command. 4. Switch back to WindowMaker and paste the clipboard contents into the Application Script dialog text box, using the CTRL-V keyboard command. 5. From the dialog box menu, select Edit \ Find… to bring up the Replace dialog box as shown in the example below. In the “Find What” field, type in “DeviceNm”. In the “Replace With” field type in the Device Name used to configure the Large Faceplate wizard. Click the “Replace All” button to modify the text, then click the Cancel button to close the Replace dialog.

Page 58 of the GE PMCS 6.11a user manual — Installing the Application Script
Page 58 · click to enlarge
Page 58
GE PMCS 6.11a — Installing the Application Script diagram (page 58)
Fig. 46 · Installing the Application Script
1. Click the OK button to close the Application Script Dialog.

NOTE: The application script text is only needed once for each configured device. If you are installing more than one wizard for a particular EPM7700 device (for example, a Large Faceplate and a Tabular Wizard), you only need to copy the application script once. If you are installing more than one EPM7700 device in your InTouch application, the application script window must contain a copy of the application script text for each configured device. See the example below:

Page 59 of the GE PMCS 6.11a user manual — Installing the Application Script
Page 59 · click to enlarge
Page 59
GE PMCS 6.11a — Installing the Application Script diagram (page 59)
Fig. 47 · Installing the Application Script
Page 60 of the GE PMCS 6.11a user manual — Configuring the Large Faceplate/Custom Table Script
Page 60 · click to enlarge
Page 60

EPM 7700 Large Faceplate or Custom Table Wizard Scripting

Configuring the Large Faceplate/Custom Table Script

1. After configuring the Large Faceplate or Custom Table wizard, and with its window displayed, select “Special \ Scripts \ Window Scripts… from the WindowMaker main menu. The Window Script Dialog box opens:
GE PMCS 6.11a — Configuring the Large Faceplate/Custom Table Script diagram (page 60)
Fig. 48 · Configuring the Large Faceplate/Custom Table Script
2. Select "On Show" from the Condition Type drop down list.
3. Use Notepad.exe to open the file “EPM7700 Non-Tabular Window Script.txt”, located in the Intouch directory of the PC.
4. Select (highlight) all the file text and copy it to the clipboard using the CTRL-C keyboard command.
5. Switch to WindowMaker and paste the clipboard contents into the Window Script dialog text box, using the CTRL-V keyboard command.
6. From the dialog box menu, select Edit \ Find… to bring up the Replace dialog box as shown in the following example. In the “Find What” field, type in “DeviceNm”. In the “Replace With” field, enter the Device Name used to configure the Large Faceplate wizard. Click the “Replace All” button to modify the text. Click the Cancel button to close the Replace dialog. Click the OK button to close the Window Scripts Dialog.
Page 61 of the GE PMCS 6.11a user manual — Configuring the Large Faceplate/Custom Table Script
Page 61 · click to enlarge
Page 61
Page 61 of the GE PMCS 6.11a user manual — Configuring the Large Faceplate/Custom Table Script
Page 62 of the GE PMCS 6.11a user manual — Configuring the Tabular Data Screen Script
Page 62 · click to enlarge
Page 62

EPM 7700 Tabular Data Screen Scripting

All EPM7700 Tabular wizards require the creation of a Window Script in InTouch. The Window Script automatically configures DDE Links used by the Tabular Wizard when it is displayed. The script must first be configured, then installed, per the following procedures.

Configuring the Tabular Data Screen Script

1. After configuring the Tabular wizard, and with its window displayed, select "Special \ Scripts \ Window Scripts… from the WindowMaker main menu. The Window Script Dialog box opens.
2. Select “On Show” from the Condition Type drop down list.
3. Use the Notepad.exe accessory program to open the file “EPM7700 Tabular Window Script.txt”, located in the Intouch directory of the PC. Select (highlight) all the file text and copy it to the clipboard using the CTRL-C keyboard command.
4. Switch back to WindowMaker and paste the clipboard contents into the Window Script dialog text box, using the CTRL-V keyboard command.
5. From the dialog box menu, select Edit \ Find… to bring up the Replace dialog box, as shown in the example below. In the “Find What” field, type in “DeviceNm”. In the “Replace With” field type in the Device Name used to configure the Tabular wizard. Click the “Replace All” button to modify the text. Click the Cancel button to close the Replace dialog. Click the OK button to close the Window Scripts Dialog.
GE PMCS 6.11a — Configuring the Tabular Data Screen Script diagram (page 62)
Fig. 49 · Configuring the Tabular Data Screen Script
Page 63 of the GE PMCS 6.11a user manual — Elevation Views
Page 63 · click to enlarge
Page 63

Creating Floor Plans, Elevation Views, and One-Line Diagrams

Introduction

This chapter illustrates how to use the GE wizards described in Chapter 2 to create animated displays of the facility floor plan, switchgear elevations, and system one- line diagrams. These examples are typical, but are not intended to display the limits of creative system design.

Elevation Views

Elevation views of switchgear and switchboards are typically created first, because miniature bitmaps of the elevations can be conveniently placed in floor plans as navigation items.

To build an elevation view, place GE Elevation and Small Faceplate wizards into the window, as follows:

1. Place the appropriate cabinet.
2. Place panels onto the cabinet.
3. Add nameplates, louvers, handles, and fasteners to create the desired level of detail.
4. Place GE Small Faceplate wizards representing the components installed in the equipment on top of the elevation wizards, as shown in the figure on the following page.
5. Configure each of the Small Faceplate wizards to open a window containing an appropriate Large Faceplate or Tabular Data Screen for the device.
Page 64 of the GE PMCS 6.11a user manual — Creating Floor Plans, Elevation Views, and One-Line Diagrams
Page 64 · click to enlarge
Page 64
GE PMCS 6.11a — Creating Floor Plans, Elevation Views, and One-Line Diagrams diagram (page 64)
Fig. 50 · Creating Floor Plans, Elevation Views, and One-Line…
6. You can add additional navigation buttons (using standard InTouch controls) to open windows containing one-line views or other information.
7. If the switchgear shown in the elevation view is fed from or feeds another lineup, you can add buttons to navigate to elevation views representing those lineups.
Page 65 of the GE PMCS 6.11a user manual — Floor Plans
Page 65 · click to enlarge
Page 65

Floor Plans

A floor plan should be a recognizable overhead representation of a facility. These windows are built using the GE Floor Plan wizards, described in Chapter 2. They can be made as detailed or as simple as desired. The example below shows an overview of a facility, showing all of the areas containing equipment.

GE PMCS 6.11a — Floor Plans diagram (page 65)
Fig. 51 · Floor Plans

You can link each of these areas in the main window to a more detailed window by adding a labeled navigation button (using standard InTouch controls) that is configured to show that window. In this way, you can provide paths to move up and down through a complete floor plan hierarchy.

Floor plans may be as detailed as you desire and may include miniature bitmaps of equipment elevations. The procedure for creating a miniature bitmap in a floor plan view is as follows:

1. In the floor plan window, use the toolbox to create a bitmap object with the desired size of the miniature switchgear.
2. Switch to the desired elevation window.
3. Select and copy the elevation view.
4. Switch back to the floor plan window.
5. In the floor plan window, use the Paste Bitmap command to insert the elevation view into the bitmap object.
6. Double-click on the miniature elevation bitmap to configure a link to the fullsized elevation view window.
7. You can add additional buttons, using standard InTouch controls, to navigate to windows containing one-line views of the switchgear or other information.
Page 66 of the GE PMCS 6.11a user manual — Electrical One-Line Diagrams
Page 66 · click to enlarge
Page 66

Electrical One-Line Diagrams

One-line diagrams are built by placing and linking circuit elements using the One- Line wizards, then creating scripts to provide animation for those wizards whose status can be determined or controlled, such as breakers and switches.

A one-line diagram is drawn by placing GE One-Line wizards into a window. All animated One-Line wizards have at least one discrete tag to indicate the status of the bus feed to the device, while others may have tags for in and out connections and for device status. If you do not require animation, link the wizard’s discrete tags to a constant tag with a value of true.

After the device wizards have been placed and configured, they may be connected by standard InTouch line graphics. Double-click on lines to configure them for animation. You can link a line to a discrete variable, with the colors set to indicate on (typically green) and off (typically red). If several lines are used to indicate one section of bus, animate them together with the Make Symbol toolbox selection.

When a one-line diagram is too large to comfortably fit into a single window, place navigation buttons with links to other windows near each bus line that continues to another screen. This allows intuitive navigation up and down a distribution system hierarchy.

To accurately animate your one-line diagram once all the graphics are in place, condition scripts must be written with the logic for the distribution system. See the InTouch documentation for details of the scripting language. The following example shows a simple double-ended substation with a tie breaker and the scripting that animates it.

GE PMCS 6.11a — Electrical One-Line Diagrams diagram (page 66)
Fig. 52 · Electrical One-Line Diagrams

An example of the scripting for this one-line diagram is shown below:

Page 67 of the GE PMCS 6.11a user manual — Electrical One-Line Diagrams
Page 67 · click to enlarge
Page 67

{ Set values of local discrete variables based on state of integer status of breaker. This section sets the breaker status memory discretes to true if the breaker’s analog status value is 3 (closed).} brk1_s = (brk1 == 3 OR brk1 ==9); brk2_s = (brk2 == 3 OR brk1 ==9); brk3_s = (brk3 == 3 OR brk1 ==9); brk4_s = (brk4 == 3 OR brk1 ==9); brk5_s = (brk5 == 3 OR brk1 ==9); brk6_s = (brk6 == 3 OR brk1 ==9);

Sets the breaker status memory discretes to true if the breaker’s analog status value is 3 (closed).

{ set the bus status for the incoming feeds to the dependent bus above in the

distribution hierarchy. This section sets the dependencies of the bus pieces to other sections of the one-line diagram and resets pieces of the bus located entirely on this screen to false.} bus1 = feed1; bus2 = feed2;

Sets the dependencies of the bus pieces to other sections of the one- line diagram and resets the pieces of the bus located entirely on this screen to false.

{ set the bus status for the incoming feeds to the dependent bus above in the

distribution hierarchy. This section sets the dependencies of the bus pieces to other sections of the one-line diagram and resets pieces of the bus located entirely on this screen to false.} bus1 = feed1; bus2 = feed2;

{ reset internal bus pieces to off for computations } bus3 = 0; bus4 = 0; bus5 = 0;

{ set the bus status for the incoming feeds to the dependent bus above in the

distribution hierarchy. This section sets the dependencies of the bus pieces to other sections of the one-line diagram and resets pieces of the bus located entirely on this screen to false.} bus1 = feed1; bus2 = feed2;

IF…THEN statements traverse the hierarchy from top to bottom, left to right, and then bottom to top, right to left.

{ reset internal bus pieces to off for computations } bus3 = 0; bus4 = 0; bus5 = 0;

Page 68 of the GE PMCS 6.11a user manual — Electrical One-Line Diagrams
Page 68 · click to enlarge
Page 68

{ set the bus status for the incoming feeds to the dependent bus below in the

distribution hierarchy. The IF_THEN statements in this section traverse the hierarchy from top to bottom, left to right, and then bottom to top, right to left.} bus6 = 0; bus7 = 0;

{ two main feeds } IF (bus1 AND brk1_s) THEN bus3 = 1; ENDIF; IF (bus2 AND brk2_s) THEN bus4 = 1; ENDIF;

{ left to right across tie breaker } IF (bus3 AND brk3_s) THEN bus4 = 1; ENDIF; IF (bus4 AND brk4_s) THEN bus5 = 1; ENDIF;

{ two outgoing feeders } IF (bus3 AND brk5_s) THEN bus6 = 1; ENDIF; IF (bus5 AND brk6_s) THEN bus7 = 1; ENDIF;

{ back feed from two outgoing feeds } IF (bus7 AND brk6_s) THEN bus5 = 1; ENDIF; IF (bus6 AND brk5_s) THEN bus3 = 1; ENDIF;

{ right to left across tie breaker } IF (bus5 AND brk4_s) THEN bus4 = 1; ENDIF; IF (bus4 AND brk3_s) THEN bus3 = 1; ENDIF;

{ two incoming feeds } IF (bus5 AND brk2_s) THEN

bus2 = 1; ENDIF; IF (bus3 AND brk1_s) THEN bus1 = 1; ENDIF;

Page 69 of the GE PMCS 6.11a user manual — Sample Application
Page 69 · click to enlarge
Page 69

Sample Application

Creating a basic interface

We’ve learned about the various parts and pieces of the Interface Toolkit; now let’s put it to work.

Suppose we have a very basic power management system installed at our corporate home office. The system consists of four trip units and a PQM (Power Quality Meter). We’d like to set up a computer in the front office to provide a front end to this system, allowing us to monitor all these devices at one station without having to walk back to the individual devices on the plant floor.

We plan the application on paper first so that we know how many screens to create and what each screen will look like. This will help us save time when in development by providing a starting point and a map of what we’re trying to create. This ‘storyboard’ for our application looks something like this:

As shown above, for this basic application, we’ll need 12 screens — an introduction screen, a shot of the panelboard showing all five of our power management devices, and then a large faceplate and tabular screen for each device. We’ll link the Large Faceplate screen for each unit to the Small Faceplate wizard shown on the Panelboard screen, and, from the Large Faceplate, we can click on the device’s display to jump to the Tabular data screen for that device. To make it easier to navigate the screens, we’ll create extra buttons on the bottom of the Faceplate and Tabular screens that will jump back to the Panelboard screen.

With our plan in hand, and after completing the installation procedures described in Chapter 1, we’re ready to begin development. Launch InTouch and select the button to create a new file, then click the Development button.

Show 20 more labels / short text on this page
PQM Faceplate · PQM Tabular · Trip Unit 1 · Trip Unit 1 · Faceplate · Tabular · Intro screen · Panel board · Trip Unit 2 · Trip Unit 2 · Faceplate · Tabular · Trip Unit 3 · Trip Unit 3 · Faceplate · Tabular · Trip Unit 4 · Trip Unit 4 · Faceplate · Tabular
Page 70 of the GE PMCS 6.11a user manual — Sample Application
Page 70 · click to enlarge
Page 70

First, we’ll create all our new windows and name them, then we’ll go back and flesh them out with their contents and add links between them. Create the following twelve windows:

  • Main Screen
  • Trip2_Face
  • Panelboard
  • Trip2_Tab
  • PQM_Face
  • Trip3_Face
  • PQM_Tab
  • Trip3_Tab
  • Trip1_Face
  • Trip4_Face
  • Trip1_Tab
  • Trip4_Tab

Select the window named Main Screen, and use the Wonderware tools to sketch a floorplan of the facility, as shown below.

GE PMCS 6.11a — Sample Application diagram (page 70)
Fig. 53 · Sample Application

In the Manufacturing Floor area, we place a button labeled “Click here to begin…,” and give it an animation link to the window named Panelboard.

Select the Panelboard window. Use the PMCS Elevation wizards to create a mock-up of the panelboard, then use the PMCS Small Faceplate wizards to populate the panelboard with our PQM meter and the four trip units. The Panelboard screen should look like this:

Page 71 of the GE PMCS 6.11a user manual — Sample Application
Page 71 · click to enlarge
Page 71
GE PMCS 6.11a — Sample Application diagram (page 71)
Fig. 54 · Sample Application

We’ll include a note about the panelboard’s location, describing where to find the real panel, and also a note of instruction: “Click a device to see the large faceplate screen.”

Create the links to the device screens by double-clicking on each small faceplate and entering the name of the device’s Large Faceplate screen. For example, double-click on the PQM’s Small Faceplate on the panelboard; then, in the resulting dialog box, type the name of the PQM_Face window. Complete these links for the remaining devices.

Next we’ll develop the device screens. For the purposes of this chapter, we’ll just walk through the two PQM screens. The development of the trip unit screens follows the same procedure.

Select the PQM_Face window, then use the Wonderware Button tool found on the Toolbox to create two new buttons, “HOME” and “Go back to Panel.” Use the Animation Links command to tie these buttons to the Main Screen and Panelboard windows, respectively. Now use the Wizards tool to place the PQM Large Faceplate wizard on the PQM_Face window. The screen should look similar to the following:

Page 72 of the GE PMCS 6.11a user manual — Sample Application
Page 72 · click to enlarge
Page 72
GE PMCS 6.11a — Sample Application diagram (page 72)
Fig. 55 · Sample Application

Now we’ll develop the PQM Tabular data screen. Select the PQM Tab window and use the Wizards tool to place the PQM Tabular Data wizard on the screen. Double click the wizard and fill in the Device Name and the Trending windows as shown below. Click OK.

GE PMCS 6.11a — Sample Application diagram (page 72)
Fig. 56 · Sample Application

Finally, add some navigation buttons to the Tabular screen for returning to the Main Screen (HOME), to the Panelboard (Go to Panel), or to the Large Faceplate screen (Go back to Faceplate). Link each button to the appropriate screen, and you’re all set!

Page 73 of the GE PMCS 6.11a user manual — Sample Application
Page 73 · click to enlarge
Page 73

Complete the application by developing the Faceplate and Tabular screens for each of the four trip units and that’s it — we’ve just developed a PMCS application using the GE Wonderware Wizards.

Page 74 of the GE PMCS 6.11a user manual — Sample Application
Page 74 · click to enlarge
Page 74

(This page left blank intentionally)

Page 75 of the GE PMCS 6.11a user manual — Features of GE Large Faceplate Wizards
Page 75 · click to enlarge
Page 75

Features of GE Large Faceplate Wizards

About the Large Faceplate Wizards

This chapter contains descriptions of the functions available with each of the GE Large Faceplate wizards. While a majority of the most popular data available at each device have been made available in the Wizards, some functions available with the actual devices are not provided in the Large Faceplate representations, such as the following:

  • Test Mode or Simulation Mode on some devices is not fully supported
  • Details on status/alarm/trips other than the information displayed by the front LEDs and a brief text message (see Tabular Data Screens for detailed status/alarm/trip information)
  • Any flashing status messages which may be produced by a device
  • Some actual values are not displayed on the Large Faceplate Wizard, but can be found on Tabular Data Screen Wizards

Users should be aware that not all values displayed by the GE Large Faceplate Wizards are automatically updated. Also, some rapidly changing values, especially those requiring calculation, cannot be displayed as rapidly on the wizard as on the actual device’s screen.

For a more detailed description of the functions of a device, see the user’s guide for that device.

Page 76 of the GE PMCS 6.11a user manual — Click on... Function
Page 76 · click to enlarge
Page 76

POWER LEADER EPM

GE PMCS 6.11a — POWER LEADER EPM diagram (page 76)
Fig. 57

The large faceplate representation of the POWER LEADER EPM provides the following animated functions:

Click on... Function

Display Window Clicking on the display area opens the tabular data window specified during wizard configuration and sets the view to the Normal Metering page.

GE Logo Clicking the GE logo opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

Toggles the display between the normal and alternate lists of metering parameters.

SCROLL Buttons Loop through all metered parameters for the current mode, displaying two values at a time. The down arrow scrolls down through the parameter list, with the new value appearing on the lower line of the display. The up arrow scrolls up through the parameter list with the new value appearing on the display’s upper line. Depending on whether the EPM has been configured as a Delta or Wye device, certain parameters display either line-to-line or line-to-neutral values.

Table 1. PLEPM Faceplate animated functions.

The electrical parameters and status information displayed by the EPM are listed below for both the normal and alternate scrolls. Note that the displayed parameters

SELECT/ENTER Button

Page 77 of the GE PMCS 6.11a user manual — POWER LEADER EPM
Page 77 · click to enlarge
Page 77

differ depending on whether the EPM is configured as Wye or Delta. Please note that the Normal Scroll Delta and Alternate Scroll Delta lists contain several parameters marked with an asterisk; these parameters were included in the wizard for programming reasons, but are not valid for Delta configurations and should not be used.

GE PMCS 6.11a — POWER LEADER EPM diagram (page 77)
Fig. 58

Voltage, RMS Phase A–N Voltage, RMS Phase A–N *

Voltage, RMS Phase B–N Voltage, RMS Phase B–N *

Voltage, RMS Phase C–N Voltage, RMS Phase C–N *

Page 78 of the GE PMCS 6.11a user manual — POWER LEADER EPM
Page 78 · click to enlarge
Page 78
GE PMCS 6.11a — POWER LEADER EPM diagram (page 78)
Fig. 59

Current, Phase A Peak Demand Current, Phase A Peak Demand

Current, Phase B Demand Current, Phase B Demand *

Current, Phase B Peak Demand Current, Phase B Peak Demand *

Current, Phase C Peak Demand Current, Phase C Peak Demand

Watts Demand at Peak VA Demand Watts Demand at Peak VA Demand

Vars, Peak Demand Lag (+) Vars, Peak Demand Lag (+)

Vars, Peak Demand Lead (–) Vars, Peak Demand Lead (–)

Power Factor, Phase C Power Factor, Average Since Reset

Power Factor, Average Since Reset Power Factor, Demand Average

Power Factor, Demand Average Power Factor at Peak VA Demand

Power Factor at Peak VA Demand Number of Demand Resets

Number of Demand Resets Time Left in Demand Subinterval

Time Left in Demand Subinterval Number of Power Outages

Page 79 of the GE PMCS 6.11a user manual — Click on... Function
Page 79 · click to enlarge
Page 79

Spectra MicroVersaTrip Trip Unit

GE PMCS 6.11a — Spectra MicroVersaTrip Trip Unit diagram (page 79)
Fig. 60 · Spectra MicroVersaTrip Trip Unit

The large faceplate representation of the Spectra MicroVersaTrip trip unit provides the following animated functions:

Click on... Function

Opens the tabular data window specified during wizard configuration and sets the view to the Normal Monitoring page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

ENTER Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

VALUE Button Changes phases in appropriate modes, depending on whether the device has been configured as Wye or Delta Phase is indicated by letters in the upper right of the display; press VALUE to display a different phase.

Rotates among six different modes, as shown in the lower left of the display, with units in the lower right.

Table 2. Spectra MVT Faceplate animated functions.

The metering modes available with the SELECT button are as follows:

GE PMCS 6.11a — Click on... Function diagram (page 79)
Fig. 61 · Click on... Function

AMPS Current, with no label in the units area of the display. Phase shifting in both Delta and Wye configurations.

VOLTS Voltage, displayed as line-to-line (VL-L) for Delta and line-to-neutral (VL-N) for Wye. Phase shifting in both configurations.

PWR Real power indicated by non-blinking units symbol (kW). Apparent power indicated by blinking units symbol. Phase shifting in Wye configuration.

FREQ Frequency, displayed in Hz. Phase shifting in both Delta and Wye configurations.

Display Window · FUNCTION Button · SELECT Button

Page 80 of the GE PMCS 6.11a user manual — Click on ... Function
Page 80 · click to enlarge
Page 80

Enhanced MicroVersaTrip-C Trip Unit

GE PMCS 6.11a — Enhanced MicroVersaTrip-C Trip Unit diagram (page 80)
Fig. 62 · Enhanced MicroVersaTrip-C Trip Unit

The large faceplate representation of the Enhanced MicroVersaTrip-C trip unit provides the following animated functions:

Click on ... Function

Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

ENTER Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

VALUE Button Changes phases in appropriate modes, depending on whether the device has been configured as Wye or Delta, Phase is indicated by numbers in the upper right of the display; press VALUE to display a different phase.

Rotates among eight different modes, as shown in the lower left of the display, with units in the lower right.

Table 3. EMVT-C Faceplate animated functions.

Show 4 more labels / short text on this page
Display Window · FUNCTION Button · BATTERY Button · SELECT Button
Page 81 of the GE PMCS 6.11a user manual — Mode Description
Page 81 · click to enlarge
Page 81

The EMVT-C’s metering modes available with the SELECT button are as follows:

Mode Description

AMPS Current, with no label in the units area of the display. Phase shifting in both Delta and Wye configurations.

VOLTS Voltage, displayed as line-to-line (Ph-Ph) for Delta and line-to- neutral (Ph-N) for Wye. Phases shown as 01, 02, or 03 for Wye and 01 02, 01 03, or 02 03 for Delta.

kWh Energy; no phase shifting.

kW Real power; no phase shifting.

kVA Apparent power; no phase shifting.

Demand Power demand, displayed with steady kW symbol. Peak power demand, displayed with blinking kW symbol. No phase shifting.

FREQ Frequency, displayed in Hz. Phase shifting in both Delta and Wye configurations.

Page 82 of the GE PMCS 6.11a user manual — Feature Function
Page 82 · click to enlarge
Page 82

Enhanced MicroVersaTrip-D Trip Unit

GE PMCS 6.11a — Enhanced MicroVersaTrip-D Trip Unit diagram (page 82)
Fig. 63 · Enhanced MicroVersaTrip-D Trip Unit

The large faceplate representation of the Enhanced MicroVersaTrip-D trip unit provides the following animated functions:

Feature Function

Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

ENTER Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

VALUE Button Changes phases in appropriate modes, depending on whether the device has been configured as Wye or Delta Phase is indicated by numbers in the upper right of the display; press VALUE to display a different phase.

Rotates among eight different modes, as shown in the lower left of the display, with units in the lower right.

Table 4. EMVT-D Faceplate animated functions.

Show 4 more labels / short text on this page
Display Window · FUNCTION Button · BATTERY Button · SELECT Button
Page 83 of the GE PMCS 6.11a user manual — Mode Description
Page 83 · click to enlarge
Page 83

The metering modes available with the SELECT button are as follows:

Mode Description

AMPS Current, with no label in the units area of the display. Phase shifting in both Delta and Wye configurations.

VOLTS Voltage, displayed as line-to-line (Ph-Ph) for Delta and line-to- neutral (Ph-N) for Wye. Phases shown as 01, 02, or 03 for Wye and 01 02, 01 03, or 02 03 for delta.

kWh Energy; no phase shifting.

kW Real power; no phase shifting.

kVA Apparent power; no phase shifting.

Demand Power demand, displayed with steady kW symbol. Peak power demand, displayed with blinking kW symbol. No phase shifting.

FREQ Frequency, displayed in Hz. Phase shifting in both Delta and Wye configurations.

Page 84 of the GE PMCS 6.11a user manual — Feature Function
Page 84 · click to enlarge
Page 84

POWER LEADER Meter

GE PMCS 6.11a — POWER LEADER Meter diagram (page 84)
Fig. 64 · POWER LEADER Meter

The large faceplate representation of the POWER LEADER Meter provides the following animated functions:

Feature Function

Display Window Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

GE Logo Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

PHASE Button Rotates among phase readings for appropriate modes, indicated by the phase LEDs below the display window.

SCROLL UP and SCROLL DOWN Buttons

Loop through display modes either down or up the list of parameters. Fourteen modes available with a Delta-configured device; one additional with Wye.

Table 5. PL Meter Faceplate animated functions.

RESET/ENTER Button

Page 85 of the GE PMCS 6.11a user manual — Mode Description
Page 85 · click to enlarge
Page 85

The parameters available with the SCROLL buttons are listed below:

Mode Description

RMS Current Units in Amps; phase shifting among A, B, and C.

RMS Voltage L-N Units in Volts; available only in Wye configuration, with phase shifting among A, B, and C.

RMS Voltage L-L Units in Volts; phase shifting among AB, BC, and CA.

Watts Units in kW; phase shifting among A, B, C, and total.

Vars Units in kVARs; phase shifting among A, B, C, and total.

Volt-Amps Units in kVA; phase shifting among A, B, C, and total.

Power Factor No units; no phase shifting.

Watt-Hours Units in kWH; no phase shifting.

VAR-Hours Units in kVARH; no phase shifting.

Current Demand Units in A; phase shifting among A, B, and C.

Peak Current Units in A; phase shifting among A, B, and C.

Watt Demand Units in kW; no phase shifting.

Peak Watt Demand Units in kW; no phase shifting.

Frequency Units in Hz; no phase shifting.

Harm Distortion Value area of display is blank; degree of harmonic distortion is shown as negligible, mild, moderate, or severe.

Page 86 of the GE PMCS 6.11a user manual — Feature Function
Page 86 · click to enlarge
Page 86

Spectra ECM

GE PMCS 6.11a — Spectra ECM diagram (page 86)
Fig. 65 · Spectra ECM

The large faceplate representation of the Spectra ECM provides the following animated functions:

Feature Function

Display Window Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

Open the tabular data window specified during wizard configuration and sets the view to the Setup page.

Refresh Button Updates the display to the most current readings.

Loop through all selections for each of the valid modes accessed by the SELECT/EXIT button.

Displays the top-line message “Press SELECT for”. Press one of the SCROLL buttons to rotate among the four modes. Press SELECT/EXIT to display the first value of the current mode and the SCROLL buttons for all other values available in that mode. Press again to redisplay the “Press SELECT for” prompt for mode selection.

Table 6. Spectra ECM Faceplate animated functions.

The modes and the parameters available in each mode are as follows:

CONTRAST Buttons · SCROLL Buttons · SELECT/EXIT Button

Page 87 of the GE PMCS 6.11a user manual — Mode Parameters and Units
Page 87 · click to enlarge
Page 87

Mode Parameters and Units

STATUS Motor Status ECM Status Trip Status

SETPOINTS FLA Setting, amps Rating Plug, amps Phase Unbalance, disabled/enabled Ground Fault, disabled/enabled Commnet Address

METERING Phase A Current, amps Phase B Current, amps Phase C Current, amps Average Current, amps Phase Unbalance, percent Ground Current, amps Motor Load, percent

LAST TRIP INFO Last Trip Cause Phase A @ Trip, amps Phase B @ Trip, amps Phase C @ Trip, amps Unbalance @ Trip, percent Ground Current @ Trip, amps

Page 88 of the GE PMCS 6.11a user manual — EPM 3710 Meter
Page 88 · click to enlarge
Page 88

EPM 3710 Meter

GE PMCS 6.11a — EPM 3710 Meter diagram (page 88)
Fig. 66 · EPM 3710 Meter

The large faceplate representation of the EPM 3710 provides the following animated functions:

GE PMCS 6.11a — EPM 3710 Meter diagram (page 88)
Fig. 67 · EPM 3710 Meter

Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

Open the tabular data window specified during wizard configuration and set the view to the Setup page.

Rotates the left side of the display through eight sets of instantaneous values, as described in the table below.

Rotates the right side of the display through 13 accumulated values.

Table 7. EPM 3710 Faceplate animated functions.

The parameters displayed by the PHASE button are listed in the following table.

GE PMCS 6.11a — EPM 3710 Meter diagram (page 88)
Fig. 68 · EPM 3710 Meter

The parameters displayed by the FUNCTION button are listed in the following table. If any of the import or export values are zero, they are not displayed and the next nonzero value is shown. When any of these parameters are displayed, the AMPS portion of the display window is used to allow display of the complete value.

Page 89 of the GE PMCS 6.11a user manual — EPM 3710 Meter
Page 89 · click to enlarge
Page 89
GE PMCS 6.11a — EPM 3710 Meter diagram (page 89)
Fig. 69 · EPM 3710 Meter

A or kVA Current average demand or apparent power demand

Page 90 of the GE PMCS 6.11a user manual — Display Indication Parameters
Page 90 · click to enlarge
Page 90

EPM 3720 Meter

GE PMCS 6.11a — EPM 3720 Meter diagram (page 90)
Fig. 70 · EPM 3720 Meter

The large faceplate representation of the EPM 3720 meter provides the following animated functions:

Feature Function

Display Window Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

GROUP Buttons Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

PHASE Button Rotates the left side of the display through eight sets of instantaneous values, as described in the table below. May also affect the POWER FUNCTIONS portion of the display, depending on the FUNCTION selection.

Rotates the right side of the display through 24 accumulated values, in conjunction with the PHASE button.

Table 8. EPM 3720 Faceplate animated functions.

The parameters displayed by the PHASE button are listed in the following table.

Display Indication Parameters

A Phase A current and line-to-neutral voltage

B Phase B current and line-to-neutral voltage

C Phase C current and line-to-neutral voltage

* Average current and line-to-neutral voltage

A, Phase A current and A-B line-to-line voltage

FUNCTION Button

Page 91 of the GE PMCS 6.11a user manual — EPM 3720 Meter
Page 91 · click to enlarge
Page 91
GE PMCS 6.11a — EPM 3720 Meter diagram (page 91)
Fig. 71 · EPM 3720 Meter

The parameters displayed by the FUNCTION button are listed in the following table. When any of the import, export, or net parameters are displayed, the AMPS portion of the display window is used to allow display of the complete value.

GE PMCS 6.11a — EPM 3720 Meter diagram (page 91)
Fig. 72 · EPM 3720 Meter

kW Real power for phase A, B, or C as set by PHASE button, or total real power if PHASE is set to * or *,.

kVR Reactive power for phase A, B, or C as set by PHASE button, or total reactive power if PHASE is set to * or *,.

kVA Apparent power for phase A, B, or C as set by PHASE button, or total apparent power if PHASE is set to * or *,.

PFLG or PFLD Power factor, lagging or leading, for phase !A, B, or C as set by PHASE button, or total power factor if PHASE is set to * or *,.

Page 92 of the GE PMCS 6.11a user manual — Feature Function
Page 92 · click to enlarge
Page 92

EPM 7700 Meter

GE PMCS 6.11a — EPM 7700 Meter diagram (page 92)
Fig. 73 · EPM 7700 Meter

The large faceplate representation of the EPM 7700 meter provides the following animated functions:

Feature Function

Opens the tabular data window specified during wizard configuration and sets the view to the Metering page.

ESC Opens the displays the main menu on the faceplate as shown above.

Blank Buttons Pressing the keys adjacent to the LCD Display window displays the selected screen. For instance, selecting the Total Power button displays the Total Power screen of data.

Table 9. EPM 7700 Faceplate animated functions.

The parameters displayed by the various data screen buttons are listed in the following table.

LCD display window

Page 93 of the GE PMCS 6.11a user manual — Screen Selected Description
Page 93 · click to enlarge
Page 93

Screen Selected Description

  • 1 - Total Power
  • KW Total
  • KVAR Total
  • KVA Total
  • PF Signed Total 2 - Three-Phase Measurements
  • Vln a; Vln b: n/a when Voltage Mode is DELTA
  • Vln c: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg: n/a when Voltage Mode is DELTA
  • Vll ab
  • Vll bc; Vll ca; Vll avg: n/a when Voltage Mode is SINGLE
  • Ia, Ib, I4, Iavg
  • Ic: n/a when Voltage Mode is SINGLE
  • V unbal
  • I unbal
  • Line Frequency 3 - Per-Phase Power
  • KW a; KW b: n/a when Voltage Mode is DELTA
  • KW c: n/a when Voltage Mode is DELTA or SINGLE
  • KW Total
  • KVAR a; KVAR b: n/a when Voltage Mode is DELTA
  • KVAR c: n/a when Voltage Mode is DELTA or SINGLE
  • KVAR Total
  • KVA a; KVA b: n/a when Voltage Mode is DELTA
  • KVA c: n/a when Voltage Mode is DELTA or SINGLE
  • KVA Total
  • PF Signed a; PF Signed b: n/a when Voltage Mode is DELTA
  • PF Signed c: n/a when Voltage Mode is DELTA or SINGLE
  • 4 - Energy
  • KWh Import; KWh Export; KWh Total; KWh Net
  • KVARh Import; KVARh Export; KVARh Total; KVARh Net
  • KVAh Total
  • KW Total Min; KVAR Total Min; KVA Total Min
  • KW Total Max; KVAR Total Max; KVA Total Max
  • 5 - Symmetrical Components
  • I ZeroSeqMag; I PosSeqMag; I NegSeqMag
  • V ZeroSeqMag; V PosSeqMag; V NegSeqMag
  • I ZeroSeqPhs; I PosSeqPhs; I NegSeqPhs
  • V ZeroSeqPhs; V PosSeqPhs; V NegSeqPhs
6. Digital Inputs • Status Inputs 1 - 8
Page 94 of the GE PMCS 6.11a user manual — Screen Selected Description
Page 94 · click to enlarge
Page 94

Screen Selected Description

  • 7 - Per-Phase Minimums
  • Vln a Min; Vln b Min: n/a when Voltage Mode is DELTA
  • Vln c Min: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg Min: n/a when Voltage Mode is DELTA
  • Vll ab Min
  • Vll bc Min; Vll ca Min; Vll Avg Min: n/a when Voltage Mode is SINGLE
  • Ia Min; Ib Min
  • Ic Min: n/a when Voltage Mode is SINGLE
  • I Avg Min
  • 8 - Per-Phase Maximums
  • Vln a Max; Vln b Max : n/a when Voltage Mode is DELTA
  • Vln c Max: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg Max: n/a when Voltage Mode is DELTA
  • Vll ab Max
  • Vll bc Max; Vll ca Max; Vll Avg Max: n/a when Voltage Mode is SINGLE
  • Ia Max; Ib Max
  • Ic Max: n/a when Voltage Mode is SINGLE
  • I Avg Max
  • 9 - Power & Amp Demand
  • KW SWD; KVAR SWD; KVA SWD**
  • KW PD; KVAR PD; KVA PD**
  • KW Total; KVAR Total; KVA Total
  • 10 - THD and K-Factor
  • V1 THD; V2 THD; V3 THD: n/a when Source is n/a
  • I1 THD; I2 THD; I3 THD; I4 THD: n/a when Source is n/a
  • I1 K Factor; I2 K Factor; I3 K Factor; I4 K Factor: n/a when Source is n/a

**NOTE: If the Sliding Demand Reset is initiated, or a SWD setup register is changed, SWD values are “N/A” in the meter until the number of sub-intervals specified in the #sub intervals setup register have expired. The 3D faceplate and Tabular wizard will display 0 for these values during this state.

Page 95 of the GE PMCS 6.11a user manual — Feature Function
Page 95 · click to enlarge
Page 95

269 Plus Motor Management Relay

GE PMCS 6.11a — 269 Plus Motor Management Relay diagram (page 95)
Fig. 74 · 269 Plus Motor Management Relay

The large faceplate representation of the 269 Plus provides the following animated functions:

Feature Function

Display Window Opens the tabular data window specified during wizard configuration and sets the view to the Monitoring page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

RESET Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

CLEAR Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

VALUE Buttons Open the tabular data window specified during wizard configuration and set the view to the Setup page.

HELP Button Displays a Windows help screen for PMCS.

Brings the meter to an initial setting point and displays ACTUAL VALUES HAS SEVEN PAGES OF DATA.

Updates the display to the current meter reading.

STORE Button Resets the meter at two special points in the display of values. Press STORE to toggle the response on the bottom line.

PAGE Buttons Rotate among seven pages of parameter data. Press one of the arrow keys to display PAGE #: ACTUAL VALUES on the top line, a description on the bottom, and reset to the first parameter value. The seven pages are listed in the table below.

SET POINTS Button · ACTUAL VALUES Button · REFRESH Button

Page 96 of the GE PMCS 6.11a user manual — 269 Plus Motor Management Relay
Page 96 · click to enlarge
Page 96
GE PMCS 6.11a — 269 Plus Motor Management Relay diagram (page 96)
Fig. 75 · 269 Plus Motor Management Relay

LINE Buttons Rotate among parameters within a page. Certain configurations or meter values may prevent display of all parameters within a page. The parameters in each page are listed in the table below.

Display animation that shows the status of the 269 Plus relay. If a trip or alarm has occurred, auxiliary relay 1 or 2 is active. If the meter fails its self-test, the dark red square to the left of the label appears bright red.

Table 10. 269+ Faceplate animated functions.

The following table lists the pages that can be accessed with the PAGE buttons, with the parameters available in each page that can be accessed with the LINE buttons.

GE PMCS 6.11a — 269 Plus Motor Management Relay diagram (page 96)
Fig. 76 · 269 Plus Motor Management Relay

Phase current in amps; --- or RUN based on motor status

3 I(3 Ph avg.)=xxx AMPS Max Stator RTD=xxx C

Units = *.1 if G/F CT ratio = 2000:1

6 ST/HR TIMERS (MIN) xx

2 13 MAX STATOR SINCE LAST ACCESS: RTD #x = xxx DEGREES C

14-17 MAXIMUM RTD #x TEMP SINCE LAST ACCESS: xxx DEGREES C

Page 97 of the GE PMCS 6.11a user manual — 269 Plus Motor Management Relay
Page 97 · click to enlarge
Page 97
GE PMCS 6.11a — 269 Plus Motor Management Relay diagram (page 97)
Fig. 77 · 269 Plus Motor Management Relay

3 3 MOTOR LOAD AS A PERCENT FULL LOAD = xxx PERCENT

Displayed only if MTM unit is installed in 269

4 9 # G/F TRIPS SINCE LAST COMMISSIONING xxx

Page 98 of the GE PMCS 6.11a user manual — 269 Plus Motor Management Relay
Page 98 · click to enlarge
Page 98
GE PMCS 6.11a — 269 Plus Motor Management Relay diagram (page 98)
Fig. 78 · 269 Plus Motor Management Relay

Units = *.1 if G/F CT ratio = 2000:1

5 6 PRE-TRIP MAX STATOR RTD RTD #XX = xxx C

Displayed only if MTM unit is installed in 269

Displayed only if MTM unit is installed in 269

Displayed only if MTM unit is installed in 269

Displayed only if MTM unit is installed in 269

Displayed only if MTM unit is installed in 269

7 LEARNED ACCEL TIME ACCEL TIME = xxx SEC

2 Vab = xxx Vbc = xxx Vac = xxx (VOLTS)

Page 99 of the GE PMCS 6.11a user manual — 7 END OF PAGE SEVEN ACTUAL VALUES
Page 99 · click to enlarge
Page 99

Page Value Text Displayed Description

7 4 3 PHASE KVARS KVAR = xxx

Displayed only if MTM unit is on line

5 POWER FACTOR PF = xxx

Displayed only if MTM unit is on line

6 FREQUENCY HZ = xx.x

Displayed only if MTM unit is on line

7 END OF PAGE SEVEN ACTUAL VALUES

Page footer

Page 100 of the GE PMCS 6.11a user manual — Feature Function
Page 100 · click to enlarge
Page 100

565 Feeder Management Relay

GE PMCS 6.11a — 565 Feeder Management Relay diagram (page 100)
Fig. 79 · 565 Feeder Management Relay

The large faceplate representation of the 565 provides the following animated functions:

Feature Function

Display Window Opens the tabular data window specified during wizard configuration and sets the view to Monitoring page.

Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

RESET Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

CLEAR Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

NEXT CHOICE Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.

0 to 9 Buttons Open the tabular data window specified during wizard configuration and set the view to the Setup page.

HELP Button Displays a Windows help screen for PMCS.

Brings the meter to an initial setting point and displays ACTUAL VALUES HAS NINE PAGES OF DATA.

REFRESH Button Updates the display to the current meter reading.

STORE Button Resets the meter at six special points in the display of values. Press STORE to toggle the response on the bottom line.

PAGE UP Button Rotates among nine pages of parameter data. Press the key to display ACTUAL VALUES on the top line, a description on the bottom, and reset to the first parameter value. The nine pages are listed in the table below.

LINE Buttons Rotate among parameters within a page. Certain configurations or meter values may prevent display of all parameters within a page. The parameters in each page are listed in the table below.

Display animation that shows the status of the 565 relay. The dark red square to the left of the label appears bright red to indicate an active state. The TRIP bar shows the current trip condition. Auxiliary relays 1, 2, and 3 show user-selected function status. The BREAKER CLOSED and BREAKER OPEN bars show the status of the monitored feeder breaker. The SERVICE bar is not animated.

Table 11. 565 Faceplate animated functions.

The following table lists the pages that can be accessed with the PAGE UP button, with the parameters available in each page that can be accessed with the LINE buttons.

SET POINTS Button · ACTUAL VALUES Button · Panel Display Lights

Page 101 of the GE PMCS 6.11a user manual — 9 MAINTENANCE DATA END OF PAGE
Page 101 · click to enlarge
Page 101

Page Value Text Displayed Description

1 ACTUAL VALUES CURRENT

2 PHASE A CURRENT xxx

3 PHASE B CURRENT xxx

1 4 PHASE C CURRENT xxx

5 GROUND CURRENT xxx

6 PHASES A = xxx B = xxx C = xxx

Breaker is closed and current

PHASES A<1% FS B<1% FS C<1% FS

7 CURRENT END OF PAGE

1 ACTUAL VALUES ANALOG INPUT

2 2 xxx

Name entered by user, value given in user- defined units

ANALOG INPUT DISABLED

3 ANALOG INPUT END OF PAGE

1 ACTUAL VALUES MAINTENANCE DATA

2 BRKR mm/dd/yy DATExx/xx/xx

3 BREAKER TRIPS xxx

Number of trips since last reset

4 ACCUMULATED KA PHASE A xxx

3 5 ACCUMULATED KA PHASE B xxx

6 ACCUMULATED KA PHASE C xxx

7 MAINTENANCE DATA CLEAR NO

Press STORE button to reset trip counter

8 DATA CLEARED LASTxx/xx/xx

Date of last reset

9 MAINTENANCE DATA END OF PAGE

1 ACTUAL VALUES OPERATIONS DATA

2 TIMED PHASE O/C TRIPS ###

Show 15 more labels / short text on this page
Page header · Value in amps · Value in amps · Value in amps · Value in amps · Value in amps · or · Page footer · Page header · or · Displayed if disabled · Page footer · Page header · Page footer · Page header
Page 102 of the GE PMCS 6.11a user manual — 10 DATA CLEARED LAST 0/0/0
Page 102 · click to enlarge
Page 102

Page Value Text Displayed Description

3 INST PHASE O/C TRIPS ###

4 TIMED GROUND O/C TRIPS ###

4 5 INST GROUND O/C TRIPS ###

6 OVERVOLTAGE TRIPS ###

7 UNDERVOLTAGE TRIPS ###

8 ANALOG INPUT TRIPS ###

9 CLEAR OPERATIONS DATA? NO

Press STORE button to clear trip counters

10 DATA CLEARED LAST 0/0/0

11 OPERATIONS DATA END OF PAGE

1 ACTUAL VALUES PRE-TRIP DATA

2 ALARM PHASE O/C

3 ALARM: GROUND O/C

4 ALARM: OVERVOLT

5 ALARM: UNDERVOLT

6 ALARM: ANALOG INPUT

7 ALARM: ACCUMULATED KA

8 SWITCH ALARM 1

9 ALARM: AMPS DEMAND

10 ALARM: KW DEMAND

11 ALARM: KVAR DEMAND

12 ALARM: POWER FACTOR

13 ALARM: FREQUENCY

14 ALARM: TRIP COIL

5 15 ALARM: MTM COMM

16 CAUSE OF LAST TRIP:

Page footer · Page header

Page 103 of the GE PMCS 6.11a user manual — 28 PRE-TRIP DATA END OF PAGE
Page 103 · click to enlarge
Page 103

Page Value Text Displayed Description

17 TIME OVERCURRENT PHASE ABC

Only phases in alarm are displayed

TIME OVERCURRENT GROUND

INST OVERCURRENT PHASE ABC

UNDERVOLTAGE FAULT

OVERVOLTAGE FAULT

x is in range 1-4

ANALOG INPUT

POWER FACTOR FAULT

FREQUENCY FAULT

18 PHASE A PRE-TRIP CURRENT xxx A

19 PHASE B PRE-TRIP CURRENT xxx A

20 PHASE C PRE-TRIP CURRENT xxx A

21 GROUND PRE-TRIP CURRENT xxx A

22 PRE -TRIP VOLTAGE A-B xxx.xx kV

If configured as Delta

A-N xxx.xx kV

If configured as Wye

23 PRE -TRIP VOLTAGE B-C xxx.xx kV

If configured as Delta

B-N xxx.xx kV

If configured as Wye

24 PRE -TRIP VOLTAGE C-A xxx.xx kV

If configured as Delta

C-N xxx.xx kV

If configured as Wye

25 FREQUENCY AT TRIP xxx.xx Hz

26 DATE OF TRIP xx/xx/xx

27 TIME OF TRIP xx:xx:xx

hh:mm:ss

28 PRE-TRIP DATA END OF PAGE

Show 21 more labels / short text on this page
or · or · or · or · or · EXTERNAL TRIP #x · or · or · or · Value in amps · Value in amps · Value in amps · Value in amps · or · or · or · or · or · or · mm/dd/yy · Page footer
Page 104 of the GE PMCS 6.11a user manual — KW DEMAND DISABLED
Page 104 · click to enlarge
Page 104

Page Value Text Displayed Description

1 ACTUAL VALUES VOLTAGE

2 VOLTAGE A-B xxx.xx kV

6 3 VOLTAGE B-C xxx.xx kV

4 VOLTAGE C-A xxx.xx kV

5 FREQUENCY OF FEEDER xxx.xx Hz

6 VOLTAGE END OF PAGE

1 ACTUAL VALUES EVENT

2 NO OF EVENTS xxx

Displayed only if enabled

EVENT RECORDING DISABLED

7 3 CLEAR EVENTS? NO

Press STORE button to clear event counter

4 EVENTS CLEARED LASTxx/xx/xx
Date of last resetmm/dd/yy

5 EVENT END OF PAGE

1 ACTUAL VALUES DEMAND DATA

2 PH-A PEAK DEMAND xxx A

AMPS DEMAND DISABLED

Next prompt is CLEAR AMP DEMAND

3 PH-B PEAK DEMAND xxx A

4 PH-C PEAK DEMAND xxx A

5 CLEAR AMP DEMAND DATA? NO

Press STORE button to reset amp data

6 DATA CLEARED LASTxx/xx/xx
Date of last resetmm/dd/yy

8 7 PEAK KW DEMAND xxx kW

KW DEMAND DISABLED

8 CLEAR KW DEMAND DATA? NO

Press STORE button to reset kilowatt data

9 KW DEMAND DATA CL’Dxx/xx/xx
Date of last resetmm/dd/yy
Show 14 more labels / short text on this page
Page header · Page footer · Page header · or · Page footer · Page header · Value in amps · or · or · Value in amps · Value in amps · or · or · Displayed if disabled
Page 105 of the GE PMCS 6.11a user manual — 7 METERING DATA END OF PAGE
Page 105 · click to enlarge
Page 105

Page Value Text Displayed Description

10 PEAK KVAR DEMAND xxx kVAR

KVAR DEMAND DISABLED

11 CLEAR KVAR DEMAND DATA? NO

Press STORE button to reset kVAR data

12 KVAR DEMAND DATA

Date of last resetmm/dd/yy
CL’Dxx/xx/xx

13 DEMAND DATA END OF PAGE

1 METERING DATA DEMAND DATA

2 POWER FACTOR LAGGINGx.xx

If PF < 0

LEADINGx.xx

If PF > 0

3 FREQUENCY MTM x.xx Hz

9 4 REAL POWER xxx kW

5 REACTIVE POWER xxx kVAR

6 ENERGY USED xxx MWHRS

7 METERING DATA END OF PAGE

Show 8 more labels / short text on this page
or · or · Displayed if disabled · Page footer · Page header · or · or · Page footer
Page 106 of the GE PMCS 6.11a user manual — 565 Feeder Management Relay
Page 106 · click to enlarge
Page 106

(This page left blank intentionally)

Page 107 of the GE PMCS 6.11a user manual — Features of Tabular Data Screens
Page 107 · click to enlarge
Page 107

Features of Tabular Data Screen Wizards

Introduction

This chapter describes the features available with tabular data screens. The set of features basic to all tabular data screens is described first, then any unique features are described for each device.

Features of Tabular Data Screens

The upper left-hand area of every tabular data screen contains a 3-D graphic of the device faceplate. This graphic is simply to verify identification and is not animated.

The middle area on the left-hand side displays common information about the device. It provides a quick indication of how the device is configured and contains no animation.

The buttons on the lower-left of the screen provide features described below. Not all devices support all of these buttons, so on some screens one or more of the buttons may be grayed out.

  • The Help button calls up the PMCS help file with regard to the current device.
  • The Exit button closes the tabular data screen.
  • The Events button starts or jumps to the PMCS Event Logger client program and displays its window in the foreground.
  • The Trend button displays the trend window that was specified in the configuration dialog. The button will be disabled if no trend window was specified during configuration of the Wizard.
  • The Wave button runs the PMCS Waveform Capture client program for that device. This button is only enabled for devices supporting waveform capture.
  • The Setup button displays the trend window that was specified in the configuration dialog. The button will be disabled if no setup window was specified during configuration of the Wizard.
Page 108 of the GE PMCS 6.11a user manual — Features of Tabular Data Screen Wizards
Page 108 · click to enlarge
Page 108

The right side of the screen contains a display of the device data. The tabs at the bottom enable you to select among the various data tables which can be displayed. The number of tabs (screens) varies according to the type and amount of data available from the device. The two main types of data are metering, which shows the data being monitored by the device, and setup, which is used to configure the device. Other tabs may be available depending on the device’s capabilities.

Some devices have push buttons that reset events or clear accumulated data; these will be discussed below in the individual device sections. These functions are represented by 3-D push buttons on the tabular data screens. When a button is pressed, a dialog box appears that either asks for confirmation of the action or states that the operator has an insufficient access level to perform the operation. If security is enabled in your InTouch application, the current operator must have an Access level greater than or equal to the Access level configured for each tabular wizard in order to issue device commands. See the Wonderware InTouch documentation for more information on how to use security features within InTouch.

Page 109 of the GE PMCS 6.11a user manual — Tab Button Function
Page 109 · click to enlarge
Page 109

Power Leader EPM

GE PMCS 6.11a — Power Leader EPM diagram (page 109)
Fig. 80 · Power Leader EPM

The Power Leader EPM Tabular Data Screen wizard provides the following command buttons:

Tab Button Function

Setup Meter Initialize Performs a complete meter reset

Clear Errors Clears the event log in the meter

Demand Reset Clears the watt demand register in the meter

Energy Reset Clears the accumulated energy registers in the meter

Table 12. PLEPM Tabular data screen commands.

Another feature to bear in mind when working with the PLEPM tabular wizard is:

  • The Normal Metering screen displays one of two tables depending on whether the meter is configured as Delta or Wye.
Page 110 of the GE PMCS 6.11a user manual — Tab Button Function
Page 110 · click to enlarge
Page 110

Spectra MicroVersaTrip

GE PMCS 6.11a — Spectra MicroVersaTrip diagram (page 110)
Fig. 81 · Spectra MicroVersaTrip

The Spectra MicroVersaTrip Tabular Data Screen wizard provides the following command buttons on the Setup screen:

Tab Button Function

Setup Download Downloads the energy demand interval to the DDE Server

Refresh Loads the energy demand interval from the DDE Server into the screen display

Clear Demand Clears the accumulated energy

Table 13. Spectra MVT Tabular data screen commands.

Another feature to bear in mind when working with the Spectra MicroVersaTrip tabular wizard is:

  • The data entry field for the energy demand interval can be set to values of 5 to 60 minutes in increments of 5 minutes.
Page 111 of the GE PMCS 6.11a user manual — Tab Button Function
Page 111 · click to enlarge
Page 111

Enhanced MicroVersaTrip-C Trip Unit

GE PMCS 6.11a — Enhanced MicroVersaTrip-C Trip Unit diagram (page 111)
Fig. 82 · Enhanced MicroVersaTrip-C Trip Unit

The Enhanced MicroVersaTrip-C Tabular Data Screen provides six push buttons on the Setup screen:

Tab Button Function

Setup Energy Clears the accumulated energy registers in the trip unit

Demand Clears the peak demand register in the trip unit

Inst. Trip Resets the instantaneous trip counter in the trip unit

Short Trip Resets the short-time trip counter in the trip unit

Long Trip Resets the long-time trip counter in the trip unit

Ground Fault Resets the ground fault trip counter in the trip unit

Table 14. EMVT-C Tabular data screen commands.

Page 112 of the GE PMCS 6.11a user manual — Tab Button Function
Page 112 · click to enlarge
Page 112

Enhanced MicroVersaTrip-D Trip Unit

GE PMCS 6.11a — Enhanced MicroVersaTrip-D Trip Unit diagram (page 112)
Fig. 83 · Enhanced MicroVersaTrip-D Trip Unit

The Enhanced MicroVersaTrip-D Tabular Data Screen provides six push buttons on the Setup tab:

Tab Button Function

Setup Energy Clears the accumulated energy registers in the trip unit

Demand Clears the peak demand register in the trip unit

Inst. Trip Resets the instantaneous trip counter in the trip unit

Short Trip Resets the short-time trip counter in the trip unit

Long Trip Resets the long-time trip counter in the trip unit

Ground Fault Resets the ground fault trip counter in the trip unit

Table 15. EMVT-D Tabular data screen commands.

Page 113 of the GE PMCS 6.11a user manual — Tab Button Function
Page 113 · click to enlarge
Page 113

POWER LEADER Meter

GE PMCS 6.11a — POWER LEADER Meter diagram (page 113)
Fig. 84 · POWER LEADER Meter

The POWER LEADER Meter Tabular Data Screen wizard provides three push buttons on the Command screen:

Tab Button Function

Command Energy /VARH Clear Clears the accumulated energy registers in the meter

Peak Current Clear Clears the peak current register in the meter

Peak Watt Demand Clear

Clears the peak demand in the meter

Table 16. PL Meter Tabular data screen commands.

Page 114 of the GE PMCS 6.11a user manual — Tab Button Function
Page 114 · click to enlarge
Page 114

Spectra ECM

GE PMCS 6.11a — Spectra ECM diagram (page 114)
Fig. 85 · Spectra ECM

The Spectra ECM Tabular Data Screen wizard performs the following actions with push buttons on the Command screen:

Tab Button Function

Command Contactor 1 Start Closes contactor 1

Contactor 2 Fast Start Initiates a fast start of contactor 2

Contactor 2 Rev Start Reverse closes contactor 2

Stop 1 & 2 Opens contactors 1 and 2

ECM Reset Completely resets the ECM

Initialize Temperature Resets the temperature memory in the ECM

Trip ECM Contactor Trips the ECM contactors

Table 17. Spectra ECM Tabular data screen commands.

Page 115 of the GE PMCS 6.11a user manual — Monitoring Tab
Page 115 · click to enlarge
Page 115

MDP Digital Overcurrent Relay

The feature to bear in mind when working with the MDP tabular wizard is:

  • On the Setup screen, you must enter a value into the CT Ratio box. This value is multiplied by the values in the amp registers to convert the latter into user units. If you do not enter a value for the CT Ratio, the message “CT Ratio has not been entered” appears on the bottom of the Tabular Data Screen and on the Large Faceplate wizard.

Monitoring Tab

GE PMCS 6.11a — Monitoring Tab diagram (page 115)
Fig. 86 · Monitoring Tab
  • The MDP Monitoring Screen shows the following:
  • Metering values of RMS Current, RMS Trip Current and Phase Trip Status
  • Trip Time
  • Status
  • External Inputs The message “CT Ratios has not been entered!” will appear when no CT Ratio entered on the Setup tab. Click on Setup Screen Tab to enter the CT Ratio.
Page 116 of the GE PMCS 6.11a user manual — Tab Button Function
Page 116 · click to enlarge
Page 116

Command Tab

GE PMCS 6.11a — Command Tab diagram (page 116)
Fig. 87 · Command Tab

The MDP Tabular Data Screen wizard has three command buttons:

Tab Button Function

Command Open Breaker Opens the breaker.

Close Breaker Closes the breaker.

Reset Fault Clears the event table in the MDP

Table 18. MDP Tabular data screen commands.

  • The MDP Command Screen shows 3 buttons:
  • Open Breaker: Opens the Breaker
  • Close Breaker: Closes the Breaker
  • Reset Fault: Clears the Event Table in the MDP The screen also shows the Breaker Status, for example OPEN.
Page 117 of the GE PMCS 6.11a user manual — Setup Tab
Page 117 · click to enlarge
Page 117

Setup Tab

GE PMCS 6.11a — Setup Tab diagram (page 117)
Fig. 88 · Setup Tab

The MDP Setup Screen shows:

  • Phase Settings Configuration
  • Ground Settings Configuration

You must enter CT Ratio in the relevant field.

Page 118 of the GE PMCS 6.11a user manual — PQM (Power Quality Meter)
Page 118 · click to enlarge
Page 118

PQM (Power Quality Meter)

All six function buttons under the Info box are enabled for the PQM.

The PQM Tabular Data Screen wizard has nine command buttons, described below.

GE PMCS 6.11a — PQM (Power Quality Meter) diagram (page 118)
Fig. 89 · PQM (Power Quality Meter)

Reset Device Issues a RESET command to the PQM

Demand Clear Max Demand Values Clears the PQM’s Max Demand values from memory

Clear Frequency Values Clears the PQM's Max Frequency values from memory

I, V Range Clear Current Min/Max Clears the PQM’s Current Min/Max values from memory

Clear Voltage Min/Max Clears the PQM’s Voltage Min/Max values from memory

P Range Clear Power Min/Max Clears the PQM’s Power Min/Max values from memory

Analysis Clear Max THD Values Clears the PQM’s Max THD values from memory

I/O Reset Pulse Counter Resets the PQM’s pulse counter

Table 19. PQM Tabular data screen commands.

See the PQM Instruction Manual (Chapter 5, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.

Page 119 of the GE PMCS 6.11a user manual — Metering Tab
Page 119 · click to enlarge
Page 119

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 119)
Fig. 90 · Metering Tab
  • The Multilin PQM Metering tab shows:
  • Metering values: For A, B, C and 3 Phase
  • Energy: In various values
  • Output Relays: Alarm, Aux 1, Aux 2 and Aux 3

The Clear Energy button, when clicked, will clear all energy values. The Reset Device button, when clicked, will reset the Device.

Page 120 of the GE PMCS 6.11a user manual — Status Tab
Page 120 · click to enlarge
Page 120

Status Tab

GE PMCS 6.11a — Status Tab diagram (page 120)
Fig. 91 · Status Tab

The Multilin Status tab shows the status of Alarms, Aux1, Aux2, Aux3 Relays.

Page 121 of the GE PMCS 6.11a user manual — Demand Tab
Page 121 · click to enlarge
Page 121

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 121)
Fig. 92 · Demand Tab

The Multilin PQM Demand screen shows :

  • Demand Current & Power
  • Peak Demand
  • Minimum and Maximum Frequency and their Time Stamps.

The Clear Max Demand Values button, when clicked, will clear all the maximum demand values. The Clear Frequency Values button, when clicked, will clear all the frequency values.

Page 122 of the GE PMCS 6.11a user manual — IV Range Tab
Page 122 · click to enlarge
Page 122

IV Range Tab

GE PMCS 6.11a — IV Range Tab diagram (page 122)
Fig. 93 · IV Range Tab

The Multilin PQM IV Range tab shows the Minumum and Maximum Current, Voltage Values.

The Clear Current Min/Max button, when clicked, will clear all the minimum and maximum values of the current.

The Clear Voltage Min/Max button, when clicked, will clear all the minimum and maximum values of voltage.

Page 123 of the GE PMCS 6.11a user manual — P Range Tab
Page 123 · click to enlarge
Page 123

P Range Tab

GE PMCS 6.11a — P Range Tab diagram (page 123)
Fig. 94 · P Range Tab

The Multilin PQM Power Range screen shows the Power minimum and maximum values.

The Clear Power Min/Max button, when clicked, will clear all the minimum and maximum values of the power.

Page 124 of the GE PMCS 6.11a user manual — Analysis Tab
Page 124 · click to enlarge
Page 124

Analysis Tab

GE PMCS 6.11a — Analysis Tab diagram (page 124)
Fig. 95 · Analysis Tab

The Multilin PQM Power Analysis screen shows:

  • Power Quality Values
  • Total Harmonic Distortion
  • THD Max

The Clear Max THD Values button, when clicked, will clear all maximum THD values.

Page 125 of the GE PMCS 6.11a user manual — IO Tab
Page 125 · click to enlarge
Page 125

IO Tab

GE PMCS 6.11a — IO Tab diagram (page 125)
Fig. 96 · IO Tab

The Multilin PQM Inputs and Outputs screen shows:

  • Digital Input Switches
  • Output Relays
  • Analog Input
  • Switch Input Pulse Counters

The Reset Pulse Counter button, when clicked, will reset all the pulse counter values.

Page 126 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 126 · click to enlarge
Page 126

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 126)
Fig. 97 · Setpoints Tab

The Multilin PQM System Setpoints screen shows:

  • Current Demand Type
  • Current Demand Time Interval (m)
  • Power Demand Type
  • Power Demand Time Interval (m)
  • Energy Cost Per kWh (cents)
  • Neutral Current Sensing
  • Analog Input Main Relay
  • Analog Input Alt Relay
  • Switch A Function
  • Switch B Function
  • Switch C Function
  • Switch D Function
Page 127 of the GE PMCS 6.11a user manual — Tab Button Function
Page 127 · click to enlarge
Page 127

Motor Manager II (MMII)

GE PMCS 6.11a — Motor Manager II (MMII) diagram (page 127)
Fig. 98 · Motor Manager II (MMII)

Five of the six function buttons under the Info box are enabled for the MMII; the Wave button is not supported for the MMII.

The MMII Tabular Data Screen wizard has four command buttons, described below.

Tab Button Function

Metering Clear Energy Clears the MMII's energy counters

Maintenance Clear Start/Trip Counters Clears the MMII's Start and Trip count values from memory

Clear Timers Clears the MMII's Timer values from memory

Clear Interlock Counter Clears the MMII’s Interlock Counter values from memory

Table 20. MMII Tabular data screen commands.

See the MMII's Instruction Manual (Chapter 5, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.

Page 128 of the GE PMCS 6.11a user manual — EPM 3710 Meter
Page 128 · click to enlarge
Page 128

EPM 3710 Meter

GE PMCS 6.11a — EPM 3710 Meter diagram (page 128)
Fig. 99 · EPM 3710 Meter

The EPM 3710 Tabular Data Screen wizard provides the following special features:

  • The Normal Metering Values screen has a label that displays either kVA Demand or Amps Demand, depending on how the meter is configured.
  • The Setpoints screen has two scroll buttons that determine which setpoint is displayed.
  • The Setup tab contains a field "Iout Key" corresponding to the Iout Key display on the actual device. On the actual device, this field displays text messages such as "Voltage A" or "Current C". In the Tabular Data Screen wizard, these messages are presented as a numeric code and must be referenced against the following table.
GE PMCS 6.11a — EPM 3710 Meter diagram (page 128)
Fig. 100 · EPM 3710 Meter

0 Voltage A 9 KVA A 18 KVA Total

1 Voltage B 10 KVA B 19 KVAR Total

3 Current A 12 KVAR A 21 KW Demand

4 Current B 13 KVAR B 22 Amp Demand

Page 129 of the GE PMCS 6.11a user manual — EPM 3720 Meter
Page 129 · click to enlarge
Page 129

EPM 3720 Meter

GE PMCS 6.11a — EPM 3720 Meter diagram (page 129)
Fig. 101 · EPM 3720 Meter

The EPM 3720 Tabular Data Screen wizard has several special features. You can use the Setup 1, Setup 2, and Setpoints screens to change the meter configuration. Values displayed in white boxes are changeable. Some are changed by clicking on the displayed value, while others provide scroll buttons, and some have both.

  • The Download and Refresh buttons on the Setup 1 and Setup 2 screens upload and download the values for all of the setup parameters.
  • The Download and Refresh buttons on the Setpoints screen upload and download all of the setpoints from the device.
  • The Reset Energy Integrators and Reset All Min/Max buttons on the Setup 1 screen provide the named functions.
  • The Sliding Demand tab supports downloading of up to 10 sliding demand measurements to the device. See Appendix B for information on setting the sliding demand keys.

To change setpoints at the device, first press the Refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired, then press the Download button to send all setpoints to unit.

When you first open the EPM 3720 Tabular Data Screen, you may see values of zero in all fields. The EPM 3720 Tabular Data Screen requires some user interaction (such as pressing a key) to update its values.

Page 130 of the GE PMCS 6.11a user manual — Tab Button Function
Page 130 · click to enlarge
Page 130

EPM 7300 Meter

The EPM 7300 Tabular Data Screen wizard has several special features. You can use the Setup screen to change the meter configuration. Values displayed in white boxes are changeable. Some are changed by clicking on the displayed value, while others are changed by clicking on the associated scroll button. The Download and Refresh buttons on the setup screen upload and download all of the setpoints from the device.

To change setpoints at the device, first press the refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired, then press the download button to send all setpoints to the unit.

The EPM 7300 Tabular Data Screen’s command buttons are described below:

Tab Button Function

Metering Reset Energy Resets all Energy Integrators in the meter.

MIN/MAX Demand Digital Input Labels The user can enter descriptive text (up to 20 characters) for each digital input. These labels are retentive.

Force ON For each digital output, this button will force the output to the ON state.

Force OFF For each digital output, this button will force the output to the OFF state.

Resets all Sliding Demand Values in the device.

Reset Min/Max Resets all Min/Max values in the device.

Table 21. EPM 7300 Tabular data screen commands.

Reset Sliding Demand

Page 131 of the GE PMCS 6.11a user manual — Metering Tab
Page 131 · click to enlarge
Page 131

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 131)
Fig. 102 · Metering Tab

The 7300 ION Normal Metering Values screen shows the metering values:

  • A, B and C
  • Three Phase Values
  • Voltage Imbalance
  • Current Imbalance
  • Frequency (Hz)
  • Phase Reversal
  • Energy

The Reset Energy button will reset the energy.

Page 132 of the GE PMCS 6.11a user manual — Min/Max Tab
Page 132 · click to enlarge
Page 132

Min/Max Tab

GE PMCS 6.11a — Min/Max Tab diagram (page 132)
Fig. 103 · Min/Max Tab

The 7300 ION Min/Max/Demand Values screen shows:

  • Minimum and maximum metering values
  • Digital Outputs
1. By clicking on the Text box provided, a popup box will be appeared where text can be entered.
2. By clicking on Force ON and Force OFF the status can be seen as ON or OFF respectively.
  • Sliding Window Demand and Predicted Windows Demand

The Reset Sliding Demand button, when clicked, will reset all Sliding Demand values in the device.

The Reset Min/Max button, when clicked, will reset all Min/Max values in the device.

Page 133 of the GE PMCS 6.11a user manual — Setup Tab
Page 133 · click to enlarge
Page 133

Setup Tab

GE PMCS 6.11a — Setup Tab diagram (page 133)
Fig. 104 · Setup Tab

The 7300 ION Setup screen shows various setup values of the device such as Volts Mode, Phase Order, PT Secondary and CT Secondary.

The Download button, when clicked, will download all relevant values in the device.

The Refresh button, when clicked, will refresh all the values coming from the device.

Page 134 of the GE PMCS 6.11a user manual — Tab Button Function
Page 134 · click to enlarge
Page 134

EPM 7330 Meter

The EPM 7330 Tabular Data Screen wizard has several special features. You can use the Setup screen to change the meter configuration. Values displayed in white boxes are changeable. Some are changed by clicking on the displayed value, while others are changed by clicking on the associated scroll button. The Download and Refresh buttons on the setup screen upload and download all of the setpoints from the device.

To change setpoints at the device, first press the refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired, then press the download button to send all setpoints to the unit.

The EPM 7330 Tabular Data Screen’s command buttons are described below:

Tab Button Function

Metering Reset Energy Resets all Energy Integrators in the meter.

MIN/MAX Demand Digital Input Labels The user can enter descriptive text (up to 20 characters) for each digital input. These labels are retentive.

Force ON For each digital output, this button will force the output to the ON state.

Force OFF For each digital output, this button will force the output to the OFF state.

Resets all Sliding Demand Values in the device.

Reset Min/Max Resets all Min/Max values in the device.

Table 22. EPM 7330 Tabular data screen commands

Reset Sliding Demand

Page 135 of the GE PMCS 6.11a user manual — Metering Tab
Page 135 · click to enlarge
Page 135

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 135)
Fig. 105 · Metering Tab

The 7330 ION Normal Metering Values screen shows the metering values:

  • A, B and C
  • Three Phase Values
  • Voltage Imbalance
  • Current Imbalance
  • Frequency (Hz)
  • Phase Reversal
  • Energy

The Reset Energy button will reset the energy.

Page 136 of the GE PMCS 6.11a user manual — Min/Max
Page 136 · click to enlarge
Page 136

Min/Max

GE PMCS 6.11a — Min/Max diagram (page 136)
Fig. 106 · Min/Max

The 7330 ION Min/Max/Demand Values screen shows:

  • Minimum and maximum metering values
  • Digital Outputs
1. By clicking on the Text box provided, a popup box will be appeared where text can be entered.
2. By clicking on Force ON and Force OFF the status can be seen as ON or OFF respectively.
  • Sliding Window Demand and Predicted Windows Demand

The Reset Sliding Demand button, when clicked, will reset all Sliding Demand values in the device.

The Reset Min/Max button, when clicked, will reset all Min/Max values in the device.

Page 137 of the GE PMCS 6.11a user manual — Setup Tab
Page 137 · click to enlarge
Page 137

Setup Tab

GE PMCS 6.11a — Setup Tab diagram (page 137)
Fig. 107 · Setup Tab

The 7330 ION Setup screen shows various setup values of the device such as Volts Mode, Phase Order, PT Secondary and CT Secondary.

The Download button, when clicked, will download all relevant values in the device.

The Refresh button, when clicked, will refresh all the values coming from the device.

Page 138 of the GE PMCS 6.11a user manual — Metering Tab
Page 138 · click to enlarge
Page 138

EPM 7500/7600 Meter

The EPM 7500/7600 Tabular Data Screen wizard has several special features. You can use the Setup screen to change the meter configuration. Values displayed in white boxes are changeable. Some are changed by clicking on the displayed value, while others are changed by clicking on the associated scroll button. The Download and Refresh buttons on the setup screen upload and download all of the setpoints from the device.

To change setpoints at the device, first press the refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired, then press the download button to send all setpoints to the unit.

In the following pages, each of the 7500/7600 Meter’s Tabular Data Screen Wizards’ tabs will be displayed and detailed.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 138)
Fig. 108 · Metering Tab

EPM 7500/7600 Meter - Metering Data Screen

The Metering tab displays the following metered values from the EPM 7500/7600.

  • Vln A, B: n/a when Voltage Mode is DELTA
  • Vln C: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg: n/a when Voltage Mode is DELTA
  • Vll AB
  • Vll BC, CA, and Avg: n/a when Voltage Mode is SINGLE
  • I A, B, Neutral, and Avg
Page 139 of the GE PMCS 6.11a user manual — Three-Phase Values
Page 139 · click to enlarge
Page 139
  • I C: n/a when Voltage Mode is SINGLE
  • KW A, B: n/a when Voltage Mode is DELTA
  • KW C: n/a when Voltage Mode is DELTA or SINGLE
  • KW Total
  • KVA A, B: n/a when Voltage Mode is DELTA
  • KVA C: n/a when Voltage Mode is DELTA or SINGLE
  • KVA Total
  • KVAR A, B: n/a when Voltage Mode is DELTA
  • KVAR C: n/a when Voltage Mode is DELTA or SINGLE
  • KVAR Total
  • Power Factor Lead A, B: n/a when Voltage Mode is DELTA or PF is Lagging
  • Power Factor Lead C: n/a when Voltage Mode is DELTA or SINGLE or PF is Lagging
  • Power Factor Lead Total: n/a when PF is Lagging
  • Power Factor Lag A, B: n/a when Voltage Mode is DELTA or PF is Leading
  • Power Factor Lag C: n/a when Voltage Mode is DELTA or SINGLE or PF is Leading
  • Power Factor Lag Total: n/a when PF is Leading
  • Power Factor Total A, B: n/a when Voltage Mode is DELTA
  • Power Factor Total C: n/a when Voltage Mode is DELTA or SINGLE
  • Power Factor Total
  • Total Harmonic Distortion – Voltage A, B, and C: n/a when Source is n/a.
  • Total Harmonic Distortion – Current A, B, C, and Neutral: n/a when Source is n/a.
  • K Factor A, B, C, and Neutral: n/a when Source is n/a.

Three-Phase Values

  • Vab, Vbc, Vca
  • Voltage Unbalance
  • Current Unbalance
  • Frequency
  • Phase Reversal (On, Off) : n/a when Voltage Mode is SINGLE
Page 140 of the GE PMCS 6.11a user manual — Min/Max Tab
Page 140 · click to enlarge
Page 140

Min/Max Tab

GE PMCS 6.11a — Min/Max Tab diagram (page 140)
Fig. 109 · Min/Max Tab

EPM 7500/7600 Meter - Min/Max Tab

The Minimum/Maximum Values tab displays a variety of minimum and maximum values recorded by the EPM 7500/7600. Select Show Minimum or Show Maximum buttons to display either the minimum or maximum values for the displayed parameters. To reset all min/max values, select the Reset Min/Max button.

Min/Max values may be displayed for the following parameters:

  • Phase A, B, C, Neutral and Average Values
  • Vln A, B: n/a when Voltage Mode is DELTA
  • Vln C: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg: n/a when Voltage Mode is DELTA
  • Vll AB
  • Vll BC, CA, and Avg: n/a when Voltage Mode is SINGLE
  • I A, B, Neutral, and Avg
  • I C: n/a when Voltage Mode is SINGLE
  • Total Harmonic Distortion – Voltage A, B, and C: n/a when Source is n/a.
  • Total Harmonic Distortion – Current A, B, C, and Neutral: n/a when Source is n/a.
  • K Factor A, B, C, and Neutral: n/a when Source is n/a.
  • Three-Phase Values
  • Vab, Vbc, Vca
  • Power Factor Lead Total: n/a when PF is Lagging
  • Power Factor Lag Total: n/a when PF is Leading
  • Voltage Unbalance
Page 141 of the GE PMCS 6.11a user manual — Relative Setpoints
Page 141 · click to enlarge
Page 141
  • Frequency

Power Quality Tab

GE PMCS 6.11a — Power Quality Tab diagram (page 141)
Fig. 110 · Power Quality Tab

EPM 7500/7600 Meter - Power Quality Tab

The Power Quality tab displays the following power quality values from the EPM 7500/7600.

Symmetric Components

  • Zero Sequence Phase and Magnitude for Current and Voltage
  • Positive Sequence Phase and Magnitude for Current and Voltage
  • Negative Sequence Phase and Magnitude for Current and Voltage

Disturbance Counts

  • Sag / Swell Counter

Relative Setpoints

  • Over KW Sliding Window Demand Status
  • Over Current Phase A Status
  • Over Current Phase B Status
  • Over Current Phase C Status
  • Over Voltage Unbalance Status *Note: no color code is used for the Relative Setpoint Status.

The Power Quality tab also provides push buttons for performing the following commands:

Reset Sag Swell Disturbance Counter – Resets Sag Swell Counter.

Page 142 of the GE PMCS 6.11a user manual — Demand
Page 142 · click to enlarge
Page 142

Enable/Disable Sag Swell – Enables or Disables Sag Swell Tracking.

Enable/Disable Over KW SWD – Enables or Disables Over Real Power Sliding Window Demand for Relative Setpoint Tracking.

Enable/Disable Over Current – Enables or Disables Over Current for Phases A, B, and C for Relative Setpoint Tracking.

Enable/Disable Over Vunb – Enables or Disables Over Voltage Unbalance for Relative Setpoint Tracking.

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 142)
Fig. 111 · Demand Tab

EPM 7500/7600 Meter - Demand Tab

The Demand tab displays the following demand values from the EPM 7500/7600.

Energy

  • Real Energy Import, Export, Total, and Net
  • Reactive Energy Import, Export, Total, and Net
  • Apparent Energy Total

Demand

  • Real Power Sliding Window Demand, Predicted Demand, and Thermal Demand
  • Reactive Power Sliding Window Demand, Predicted Demand, and Thermal Demand
  • Apparent Power Sliding Window Demand, Predicted Demand, and Thermal Demand
Page 143 of the GE PMCS 6.11a user manual — Digital Inputs
Page 143 · click to enlarge
Page 143
  • Average RMS Current Sliding Window Demand, Predicted Demand, and Thermal Demand

Minimum/Peak Demand

  • Minimum or Peak Real Power Sliding Window Demand, Total Demand, and Thermal Demand
  • Minimum or Peak Reactive Power Sliding Window Demand, Total Demand, and Thermal Demand
  • Minimum or Peak Apparent Power Sliding Window Demand, Total Demand, and Thermal Demand

The Demand tab also provides push buttons for performing the following commands:

Reset Energy – Resets Energy Demand values identified above.

Reset SWD– Resets Sliding Window Demand values identified above.

Reset Thermal – Resets Thermal Demand values identified above.

Reset Peak – Resets Peak Demand values identified above.

The Minimum/Peak panel's Show Maximum and Show Minimum buttons can be used to toggle the display between minimums and peaks.

Inputs Tab

GE PMCS 6.11a — Inputs Tab diagram (page 143)
Fig. 112 · Inputs Tab

EPM 7500/7600 Meter - Inputs Tab

The Inputs tab displays the following values from the EPM 7500/7600.

Digital Inputs

Page 144 of the GE PMCS 6.11a user manual — Transformer Ratio Settings
Page 144 · click to enlarge
Page 144
  • Status (On, Off) for Status Inputs (SI) 1-8. (Color Code: Green – ON, Grey – OFF).
  • Counters for SI1-8.

The Inputs tab also provides push buttons for performing the following commands:

Reset Counters – Resets Digital Input Status Counters for SI1-8.

The Inputs tab also provides retentive memory inputs for the following:

Digital Input Names for SI1-8.

Setup 1 Tab

GE PMCS 6.11a — Setup 1 Tab diagram (page 144)
Fig. 113 · Setup 1 Tab

EPM 7500/7600 Meter - Setup 1 Tab

The Setup 1 tab displays the following demand values from the EPM 7500/7600.

Power Settings

  • Volts Mode
  • Phase Order
  • Voltage Polarity for A, B, and C
  • Current Polarity for A, B, C, and Neutral

Transformer Ratio Settings

  • PT and CT Primary
  • PT and CT Secondary
Page 145 of the GE PMCS 6.11a user manual — Communications
Page 145 · click to enlarge
Page 145
  • Neutral CT Primary and Secondary

Communications

  • Baud Rate for Comm 1, 2, and 3.
  • Unit ID for Comm 1, 2, and 3.
  • Protocol for Comm 1, 2, and 3.
  • Mode for Comm 1.
  • IP Address, Subnet Mask, and Default Gateway.

The Setup 1 tab also provides push buttons for performing the following commands:

Download – Executes a script to check for values that have changed and downloads those values to the device via the GE 7700 Gateway.

Refresh – Executes a script to upload all of the meter values for the settings on the screen.

Page 146 of the GE PMCS 6.11a user manual — Relative Setpoint Settings
Page 146 · click to enlarge
Page 146

Setup 2 Tab

GE PMCS 6.11a — Setup 2 Tab diagram (page 146)
Fig. 114 · Setup 2 Tab

EPM 7500/7600 Meter - Setup 2 Tab

The Setup 2 tab displays the following demand values from the EPM 7500/7600.

Sliding Window Demand Settings

  • Sliding Demand Sub Interval Settings for KW, KVAR, KVA, and Iavg.
  • Sliding Demand Number of Sub Intervals for KW, KVAR, KVA, and Iavg.
  • Sliding Demand Predicted Response for KW, KVAR, KVA, and Iavg.

Waveform Recorder Settings

  • Depth of Waveform Recorder

Sag / Swell / Transient Settings

  • Sag / Swell Nominal
  • Sag Limit
  • Swell Limit
  • Change Criteria

Relative Setpoint Settings

  • Nominal value for Over KW, Over Current, and Over Vunbal.
  • Under Dropout for Over KW, Over Current, and Over Vunbal.
  • Over Dropout for Over KW, Over Current, and Over Vunbal.
  • Under Pickup for Over KW, Over Current, and Over Vunbal.
Page 147 of the GE PMCS 6.11a user manual — Setup 2 Tab
Page 147 · click to enlarge
Page 147
  • Over Pickup for Over KW, Over Current, and Over Vunbal.
  • Time On for Over KW, Over Current, and Over Vunbal.
  • Time Off for Over KW, Over Current, and Over Vunbal.

The Setup 2 tab also provides push buttons for performing the following commands:

Download– Executes a script to check for values that have changed and downloads those values to the device via the GE 7700 Gateway.

Refresh– .Executes a script to upload all of the meter values for the settings on the screen.

Page 148 of the GE PMCS 6.11a user manual — Metering Tab
Page 148 · click to enlarge
Page 148

EPM 7700 Meter

The EPM 7700 Tabular Data Screen wizard has several special features. You can use the Setup screen to change the meter configuration. Values displayed in white boxes are changeable. Some are changed by clicking on the displayed value, while others are changed by clicking on the associated scroll button. The Download and Refresh buttons on the setup screen upload and download all of the setpoints from the device.

To change setpoints at the device, first press the refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired, then press the download button to send all setpoints to the unit.

In the following pages, each of the 7700 ION Meter’s Tabular Data Screen Wizards’ tabs will be displayed and detailed.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 148)
Fig. 115 · Metering Tab

EPM 7700 ION Meter - Metering Data Screen

The Metering tab displays the following metered values from the EPM 7700.

  • Vln A, B: n/a when Voltage Mode is DELTA
  • Vln C: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg: n/a when Voltage Mode is DELTA
  • I A, B, Neutral, and Avg
  • I C: n/a when Voltage Mode is SINGLE
  • Vll AB
  • Vll BC, CA, and Avg: n/a when Voltage Mode is SINGLE
Page 149 of the GE PMCS 6.11a user manual — EPM 7700 Meter
Page 149 · click to enlarge
Page 149
  • KW A, B: n/a when Voltage Mode is DELTA
  • KW C: n/a when Voltage Mode is DELTA or SINGLE
  • KW Total
  • KVAR A, B: n/a when Voltage Mode is DELTA
  • KVAR C: n/a when Voltage Mode is DELTA or SINGLE
  • KVAR Total
  • KVA A, B: n/a when Voltage Mode is DELTA
  • KVA C: n/a when Voltage Mode is DELTA or SINGLE
  • KVA Total
  • Power Factor Lead A, B: n/a when Voltage Mode is DELTA or PF is Lagging
  • Power Factor Lead C: n/a when Voltage Mode is DELTA or SINGLE or PF is Lagging
  • Power Factor Lead Total: n/a when PF is Lagging
  • Power Factor Lag A, B: n/a when Voltage Mode is DELTA or PF is Leading
  • Power Factor Lag C: n/a when Voltage Mode is DELTA or SINGLE or PF is Leading
  • Power Factor Lag Total: n/a when PF is Leading
  • Power Factor Total A, B: n/a when Voltage Mode is DELTA
  • Power Factor Total C: n/a when Voltage Mode is DELTA or SINGLE
  • Power Factor Total
  • Total Harmonic Distortion – Voltage A, B, and C: n/a when Source is n/a.
  • Total Harmonic Distortion – Current A, B, C, and Neutral: n/a when Source is n/a.
  • K Factor A, B, C, and Neutral: n/a when Source is n/a.
  • Voltage Unbalance
  • Current Unbalance
  • Frequency
  • Phase Reversal (On, Off) : n/a when Voltage Mode is SINGLE
Page 150 of the GE PMCS 6.11a user manual — Min/Max Tab
Page 150 · click to enlarge
Page 150

Min/Max Tab

GE PMCS 6.11a — Min/Max Tab diagram (page 150)
Fig. 116 · Min/Max Tab

EPM 7700 ION Meter - Min/Max Tab

The Minimum/Maximum Values tab displays a variety of minimum and maximum values recorded by the EPM 7700. Select Show Minimum or Show Maximum buttons to display either the minimum or maximum values for the displayed parameters. To reset all min/max values, select the Reset Min/Max button.

Min/Max values may be displayed for the following parameters:

  • Vln A, B: n/a when Voltage Mode is DELTA
  • Vln C: n/a when Voltage Mode is DELTA or SINGLE
  • Vln Avg: n/a when Voltage Mode is DELTA
  • I A, B, Neutral, and Avg
  • I C: n/a when Voltage Mode is SINGLE
  • Vll AB
  • Vll BC, CA, and Avg: n/a when Voltage Mode is SINGLE
  • KW Total
  • KVAR Total
  • KVA Total
  • Power Factor Lead Total: n/a when PF is Lagging
  • Power Factor Lag Total: n/a when PF is Leading
  • Power Factor Total Total
  • Total Harmonic Distortion – Voltage A, B, and C: n/a when Source is n/a.
  • Total Harmonic Distortion – Current A, B, C, and Neutral: n/a when Source is n/a.
  • K Factor A, B, C, and Neutral: n/a when Source is n/a.
  • Voltage Unbalance
  • Frequency
Page 151 of the GE PMCS 6.11a user manual — Symmetric Components
Page 151 · click to enlarge
Page 151

Power Quality Tab

GE PMCS 6.11a — Power Quality Tab diagram (page 151)
Fig. 117 · Power Quality Tab

EPM 7700 ION Meter - Power Quality Tab

The Power Quality tab displays the following power quality values from the EPM 7700.

Disturbance Monitoring

  • Sag / Swell Counter
  • Transient Counter
  • Over KW Sliding Window Demand Status
  • Over Current Phase A Status
  • Over Current Phase B Status
  • Over Current Phase C Status
  • Over Voltage Unbalance Status *Note: no color code is used for the Relative Setpoint Status.

Symmetric Components

  • Zero Sequence Magnitude for Current and Voltage
  • Zero Sequence Phase for Current and Voltage
  • Positive Sequence Magnitude for Current and Voltage
  • Positive Sequence Phase for Current and Voltage
  • Negative Sequence Magnitude for Current and Voltage
  • Negative Sequence Phase for Current and Voltage
Page 152 of the GE PMCS 6.11a user manual — Sliding Window Demand (SWD)
Page 152 · click to enlarge
Page 152

The Power Quality tab also provides push buttons for performing the following commands:

Reset Disturbance Counters – Resets Sag Swell and Transient Counters.

Enable/Disable Sag Swell – Enables or Disables Sag Swell Tracking.

Enable/Disable Transient – Enables or Disables Transient Tracking.

Enable/Disable Over KW – Enables or Disables Over Real Power Sliding Window Demand for Relative Setpoint Tracking.

Enable/Disable Over Amps – Enables or Disables Over Current for Phases A, B, and C for Relative Setpoint Tracking.

Enable/Disable Over Vunb – Enables or Disables Over Voltage Unbalance for Relative Setpoint Tracking.

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 152)
Fig. 118 · Demand Tab

EPM 7700 ION Meter - Demand Tab

The Demand tab displays the following demand values from the EPM 7700.

Energy

  • Real Energy Import, Export, Total, and Net
  • Reactive Energy Import, Export, Total, and Net
  • Apparent Energy Total

Sliding Window Demand (SWD)

  • Real Power Sliding Window Demand and Predicted Demand
  • Reactive Power Sliding Window Demand and Predicted Demand
  • Apparent Power Sliding Window Demand and Predicted Demand
Page 153 of the GE PMCS 6.11a user manual — Analog Inputs
Page 153 · click to enlarge
Page 153
  • Average RMS Current Sliding Window Demand and Predicted Demand

Thermal Demand

  • Real Power Thermal Demand
  • Reactive Power Thermal Demand
  • Apparent Power Thermal Demand
  • Average RMS Current Thermal Demand

The Demand tab also provides push buttons for performing the following commands:

Reset Energy – Resets Energy Demand values identified above.

Reset SWD– Resets Sliding Window Demand values identified above.

Thermal Demand – Resets Thermal Demand values identified above.

Inputs Tab

GE PMCS 6.11a — Inputs Tab diagram (page 153)
Fig. 119 · Inputs Tab

EPM 7700 ION Meter - Inputs Tab

The Inputs tab displays the following values from the EPM 7700.

Digital Inputs

  • Status (On, Off) for Status Inputs (SI) 1-8. (Color Code: Green – ON, Grey – OFF).
  • Counters for SI1-8.

Analog Inputs

  • Zero Scale Setting for AI1-4. : n/a when doesn’t exist on the meter
Page 154 of the GE PMCS 6.11a user manual — Transformer Ratio Settings
Page 154 · click to enlarge
Page 154
  • Full Scale Setting for AI1-4. : n/a when doesn’t exist on the meter
  • Scaled Value for AI1-4. : n/a when doesn’t exist on the meter

The Inputs tab also provides push buttons for performing the following commands:

Reset Counters – Resets Digital Input Status Counters for SI1-8.

The Inputs tab also provides retentive memory inputs for the following:

Digital Input Names for SI1-8.

Analog Input Names for AI1-4. : n/a when doesn’t exist on the meter

Setup 1 Tab

GE PMCS 6.11a — Setup 1 Tab diagram (page 154)
Fig. 120 · Setup 1 Tab

EPM 7700 ION Meter - Setup 1 Tab

The Setup 1 tab displays the following demand values from the EPM 7700.

Power Settings

  • Volts Mode
  • Phase Order
  • Voltage Polarity for A, B, and C
  • Current Polarity for A, B, C, and Neutral

Transformer Ratio Settings

  • PT and CT Primary
  • PT and CT Secondary
  • Neutral CT Primary and Secondary
Page 155 of the GE PMCS 6.11a user manual — Communications
Page 155 · click to enlarge
Page 155

Communications

  • Baud Rate for Comm 1, 2, and 3.
  • Unit ID for Comm 1, 2, and 3.
  • Protocol for Comm 1, 2, and 3.
  • Mode for Comm 1.
  • Ethernet Protocol, IP Address, Subnet Mask, and Default Gateway.

The Setup 1 tab also provides push buttons for performing the following commands:

Download – Executes a script to check for values that have changed and downloads those values to the device via the GE 7700 Gateway.

Refresh – Executes a script to upload all of the meter values for the settings on the screen.

Page 156 of the GE PMCS 6.11a user manual — Relative Setpoint Settings
Page 156 · click to enlarge
Page 156

Setup 2 Tab

GE PMCS 6.11a — Setup 2 Tab diagram (page 156)
Fig. 121 · Setup 2 Tab

EPM 7700 ION Meter - Setup 2 Tab

The Setup 2 tab displays the following demand values from the EPM 7700.

Sliding Window Demand Settings

  • Sliding Demand Sub Interval Settings for KW, KVAR, KVA, and Iavg.
  • Sliding Demand Number of Sub Intervals for KW, KVAR, KVA, and Iavg.
  • Sliding Demand Predicted Response for KW, KVAR, KVA, and Iavg.

Waveform Recorder Settings

  • Depth of Waveform Recorder

Sag / Swell / Transient Settings

  • Sag / Swell Nominal
  • Sag Limit
  • Swell Limit
  • Change Criteria
  • Transient Threshold

Relative Setpoint Settings

  • Nominal value for Over KW, Over Current, and Over Vunbal.
  • Under Dropout for Over KW, Over Current, and Over Vunbal.
  • Over Dropout for Over KW, Over Current, and Over Vunbal.
  • Under Pickup for Over KW, Over Current, and Over Vunbal.
Page 157 of the GE PMCS 6.11a user manual — Setup 2 Tab
Page 157 · click to enlarge
Page 157
  • Over Pickup for Over KW, Over Current, and Over Vunbal.
  • Time On for Over KW, Over Current, and Over Vunbal.
  • Time Off for Over KW, Over Current, and Over Vunbal.

The Setup 2 tab also provides push buttons for performing the following commands:

Download– Executes a script to check for values that have changed and downloads those values to the device via the GE 7700 Gateway.

Refresh– .Executes a script to upload all of the meter values for the settings on the screen.

Page 158 of the GE PMCS 6.11a user manual — Universal Relay
Page 158 · click to enlarge
Page 158

Universal Relay

The Universal Relay devices are a highly-flexible family of power management devices based on the concept of a backplane and CPU supporting a wide variety of plug-in modules. These modules provide metering, monitoring, protection and control functions, and other abilities.

A UR tabular wizard can display between one and eight screens of data – the number of screens is determined by the user during wizard configuration. There are a total of Twenty Three screens available, depending on the type of UR device connected. For example, the C30 device does not support any metering functions, so the metering an source tabs are not available for this device.

The UR wizard supports connection to the PMCS Modbus and Ethernet servers and third party MMS servers. A UCA/MMS check box is provided on the wizard configuration dialog to correctly set up the Intouch tag names for use with MMS.

Special Note: UCA/MMS support for PMCS 6.11a is removed. Do not check this checkbox.

Note: If WindowViewer is running when the wizard configuration dialog is called up, a message appears warning that any changes made to the UR wizard configuration will not take effect until WindowViewer is shut down and restarted. For example, if a user elects to change the number of tabs configured for a device, the changes will not be reflected in the runtime environment until WindowViewer is restarted.

In the following pages, each of the Tabular Data Screen Wizards’ tabs will be displayed and described.

·

Page 159 of the GE PMCS 6.11a user manual — Power
Page 159 · click to enlarge
Page 159

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 159)
Fig. 122 · Metering Tab

Universal Relay - Metering Data Screen

The Metering tab displays the following metered values from the B30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 devices: Actual Values for Voltage, Current, Power, Power Factor, and Frequency. These values are detailed below.

Current

RMS Current for each phase, ground, and neutral

Phasor magnitude and angle for each phase, ground and neutral

Voltage

RMS voltage for each phase-to-phase, phase-to-neutral, and auxiliary voltage value.

Phasor magnitude and angle for phase-to-phase, phase-to-neutral and auxiliary voltage value.

Phase-to-neutral voltages are displayed as "N/A" if derived from a source wired in a delta configuration.

Power

Shows Real (Watts), Reactive (VAR), and Apparent (VA) power values per phase and 3-phase.

By default, all power values are displayed in terms of kW, kVAR, and kVA. These values will scale as appropriate to MW, MVAR, and MVA.

Power values derived from a source wired in a delta configuration are displayed as "N/A".

Page 160 of the GE PMCS 6.11a user manual — Current
Page 160 · click to enlarge
Page 160

Power Factor

Shows the signed power factor value in percent.

Power Factor values derived from a source wired in a delta configuration are displayed as "N/A".

Frequency

Frequency is shown in units of hertz.

Frequency is only displayed if the Frequency Tracking Reference setpoint is set to a non-zero value.

Power Quality Tab

GE PMCS 6.11a — Power Quality Tab diagram (page 160)
Fig. 123 · Power Quality Tab

Universal Relay - Quality Tab

The Quality tab provides six buttons labeled S1 – S6. These buttons enable you to select the source (1 – 6) for display. The text in the upper left corner of the tab indicates which source is currently displayed. Buttons are disabled for sources that have not been configured or enabled in the attached device. The Voltage parameters displayed are dependent on CT/VT configuration of the device hardware.

For the selected source, the Quality tab displays actual values for Zero Sequence, Positive Sequence, and Negative Sequence currents and voltages. The following devices are supported: B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60. The displayed values are described below.

Current

Phasor magnitude and angle for negative, positive and zero sequence currents.

Page 161 of the GE PMCS 6.11a user manual — Grouped Protection Settings
Page 161 · click to enlarge
Page 161

Voltage

Phasor magnitude and angle for negative, positive and zero sequence voltages.

Voltage values derived from a source wired in a delta configuration will appear as "N/A".

Protection Control Tab

GE PMCS 6.11a — Protection Control Tab diagram (page 161)
Fig. 124 · Protection Control Tab

Universal Relay - Protection Control Tab

The Protection Control tab is supported for the following devices: B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60. The Protection Control tab provides the features described below.

Grouped Protection Settings

There are eight identical groups of protection settings in the UR - this tab provides an enable/disable status indication of selected protection elements, as well as a pushbutton to change the enable/disable status of those elements in each group. Function availability is determined by the Order Code read from the device – those functions that are not available in the connected device will be grayed out and disabled, as shown below:

Page 162 of the GE PMCS 6.11a user manual — Power System Configuration Tab
Page 162 · click to enlarge
Page 162

The label color indicates the function’s availability on the connected device: gray = not available, black = available.

Button to enable or disable the indicated function.

Status indicator: gray = disabled, amber = enabled.

To use this tab, the user selects one of the eight settings groups for editing using the control labeled "Select Settings Group". The status of the settings in the selected group will then be displayed, and the user can enable/disable functions without affecting settings in the other seven groups. Note that the displayed group may not be the active group currently in use by the relay’s protection algorithms. The pushbuttons are subject to user level security in Intouch.

Phase TOC and IOC Settings

The Phase, Neutral, and Ground buttons in this section may be used to select the display of the TOC and IOC values.

Power System Configuration Tab

GE PMCS 6.11a — Power System Configuration Tab diagram (page 162)
Fig. 125 · Power System Configuration Tab

Universal Relay - Power System Configuration Tab

The Power System Configuration tab supports the B30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows the source CT and VT configuration of the entire relay. The supported UR devices can be configured with one to three DSP cards containing voltage and/or current transformers for measurement purposes.

Page 163 of the GE PMCS 6.11a user manual — Hi-Z Function
Page 163 · click to enlarge
Page 163

Current Transformers (CT)

Primary: indicates the current rating of the CT primary.

Secondary: indicates the output current of the CT secondary, either 1A or 5A.

Displays "N/A" if the Order Code indicates no CT is installed in the affected location.

Voltage Transformers (VT)

Secondary: indicates the output voltage of the VT.

Ratio: the turns ratio of the VT.

Displays "N/A" if the Order Code indicates no VT is installed in the affected location.

Synchrocheck 1/2 Delta

The Delta values for Synchrocheck 1 and 2, voltage frequency, and phase.

IRIG-B Signal Type

Displays the IRIG-B signal type in use, if applicable.

Normal Frequency

The system nominal frequency in hertz.

Phase Rotation

The system phase rotation, ABC or ACB.

Frequency Tracking Reference

A numerical setpoint value associated with a specific source. The indicated source is used by the relay for developing frequency metering information. A value of zero indicates that the relay is not intended to meter frequency.

Hi-Z Function

Enable or Disable the device's High Impedance (Hi-Z) function, if equipped.

Page 164 of the GE PMCS 6.11a user manual — Transformer Winding Reference
Page 164 · click to enlarge
Page 164

Transformer Tab

GE PMCS 6.11a — Transformer Tab diagram (page 164)
Fig. 126 · Transformer Tab

Universal Relay - Transformer Tab

The T60 device alone supports a Transformer Tab on its wizard. This tab is unique to the T60 device type. The following values are shown:

Differential Current

Phasor magnitude and angle.

Phasor magnitude and angle

Phasor magnitude and angle

Restraint Current

Phasor Magnitude and angle

Transformer Winding Reference

Indicates which of the six possible transformer windings will serve as the reference winding.

Differential 2nd Harmonic · Differential 5th Harmonic

Page 165 of the GE PMCS 6.11a user manual — Elements Tab
Page 165 · click to enlarge
Page 165

Elements Tab

GE PMCS 6.11a — Elements Tab diagram (page 165)
Fig. 127 · Elements Tab

Universal Relay - Digital Elements Tab

The Elements tab displays user-defined name and current status of the sixteen digital elements in the UR. The status indicator color is amber if an element is enabled, gray if it is disabled. The B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 devices are supported.

Page 166 of the GE PMCS 6.11a user manual — Digital Counter Tab
Page 166 · click to enlarge
Page 166

Digital Counter Tab

GE PMCS 6.11a — Digital Counter Tab diagram (page 166)
Fig. 128 · Digital Counter Tab

Universal Relay - Digital Counter Tab

The digital counter tab supports B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 device types, showing information about the eight digital counters provided in each UR.

Status – this indicator is amber if the counter is enabled, gray if disabled.

Enable/Disable – this button gives the user the ability to enable or disable the specified counter.

Name – displays the user-defined name assigned to the counter.

Frozen Value – shows the counter’s value when last frozen.

Time Stamp – shows the time and date when the frozen count was acquired.

Page 167 of the GE PMCS 6.11a user manual — Virtual Inputs
Page 167 · click to enlarge
Page 167

Virtual Inputs Tab

GE PMCS 6.11a — Virtual Inputs Tab diagram (page 167)
Fig. 129 · Virtual Inputs Tab

Universal Relay - Virtual Inputs Tab

The Virtual Inputs (VInputs) tab allows the user to enable/disable all configured virtual inputs in the connected device and provides indication of their status. The 32 virtual inputs can be manually operated with the pushbuttons provided at the bottom of the screen. This tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 devices.

Virtual Inputs

The enable/disable controls and status indicators are presented as a series of pages. To view the virtual inputs, the use the Page arrow keys provided to navigate between the pages. The arrow keys are disabled when the virtual inputs are not being displayed.

The state of each virtual input can be controlled with the pushbuttons along the bottom of the screen. Clicking one of these buttons toggles the status of the virtual input, changing its state as shown in the indicator blocks associated with each button. Note that a virtual input must be enabled before the toggling action will take effect in the relay.

Page 168 of the GE PMCS 6.11a user manual — Virtual Outputs
Page 168 · click to enlarge
Page 168

Virtual Outputs Tab

GE PMCS 6.11a — Virtual Outputs Tab diagram (page 168)
Fig. 130 · Virtual Outputs Tab

Universal Relay - Virtual Outputs Tab

The Virtual Outputs (VOutput) tab allows the user to view the status (energized/de- energized) of all available virtual outputs on the device. The user can also assign a textual name to each of the outputs. Up to 64 virtual outputs can be diplayed. This tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 devices.

Virtual Outputs

The outputs and their status indicators are presented as a series of pages. To view the virtual outputs, the use the Page arrow keys provided to navigate between the pages.

To assign a name to a virtual output, click in the text field to the right of the output number label. The field becomes editable; make any desired changes, then press Enter.

Page 169 of the GE PMCS 6.11a user manual — Contact Inputs
Page 169 · click to enlarge
Page 169

Contact Inputs Tab

GE PMCS 6.11a — Contact Inputs Tab diagram (page 169)
Fig. 131 · Contact Inputs Tab

Universal Relay - Contact Input Tab

The Contact Input tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows the contact inputs installed on the selected relay. Up to 96 contact inputs may be displayed.

Contact Inputs

The contacts are presented as a series of pages. To view the contact inputs, use the Prev(ious) and Next keys provided to navigate among the pages. The number of contact inputs available is determined from the Order Code read from the device, and is dependent on the number of digital I/O cards installed in the relay. If a contact input is not available in the connected relay, the associated control button is grayed and disabled, and the input name field shows "N/A". If the corresponding Contact Input State is Energized then the LED is lit with an amber color; otherwise the LED remains gray (un-energized).

Page 170 of the GE PMCS 6.11a user manual — Contact Output
Page 170 · click to enlarge
Page 170

Contact Output Tab

GE PMCS 6.11a — Contact Output Tab diagram (page 170)
Fig. 132 · Contact Output Tab

Universal Relay - Contact Output Tab

The Contact Output tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows the contact outputs installed on the selected relay. Up to 64 contact outputs may be displayed.

Contact Output

The contacts are presented as a series of pages. To view the contact outputs, use the Page arrow keys provided to navigate among the pages. The number of contact outputs available is determined from the Order Code read from the device, and is dependent on the number of digital I/O cards installed in the relay. If a contact output is not available in the connected relay, the associated control button is grayed and disabled, and the output name field shows "N/A".

Page 171 of the GE PMCS 6.11a user manual — DCMA Inputs
Page 171 · click to enlarge
Page 171

DCMA Tab

GE PMCS 6.11a — DCMA Tab diagram (page 171)
Fig. 133 · DCMA Tab

Universal Relay - DCMA Tab

The Direct Current MilliAmperes (DCMA) tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows the state of the relay's DCMA inputs. DCMA inputs are analog inputs used to read external transducer values. An example might be rotational speed on a generator, translated into a 4-20 mA current loop. Up to 24 inputs may be enabled or disabled.

DCMA Inputs

The DCMA inputs and their parameters are presented as a series of pages. To view the inputs, the use the Page arrow keys provided to navigate between the pages.

For each DCMA input, its ID number, value, and units are displayed as read from the device. To enable or disable a selected input, click the Enable button next to its ID number.

Page 172 of the GE PMCS 6.11a user manual — Source Tabs
Page 172 · click to enlarge
Page 172

Source Tabs

GE PMCS 6.11a — Source Tabs diagram (page 172)
Fig. 134 · Source Tabs

Universal Relay - Source Tab Example

Similar in operation to the metering tab (except that frequency information is not displayed), there are five identical "Source" tabs (2 – 6) which display actual values information specific to the indicated source. There is no "Source 1" tab, since the Metering tab serves as the "Source 1" display. The B30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR device types are supported.

The display rules for the metering tab also apply to each Source tab.

Page 173 of the GE PMCS 6.11a user manual — Source (x) Demand, Peak Demand, Peak Demand Date
Page 173 · click to enlarge
Page 173

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 173)
Fig. 135 · Demand Tab

Universal Relay - Demand Tab

The Demand tab supports the B30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows a variety of energy measurements and demand parameters for a selected source.

These values are displayed for up to six sources, which may be toggled between using the S1 - S6 buttons. The Clear Demand button clears the values for the selected source. Note: Energy data is displayed as N/A for the L90 and L60 device types, and data logger data is displayed as N/A for the B30 device type.

Demand Values

The Demand panel shows the Data Logger parameters, which may be cleared using the Clear Data Logger button, the time/date stamps of the oldest and newest samples available, and information on the Demand Current and Demand Power Methods, and Demand Interval (if applicable).

Source (x) Energy

Displays positive and negative Watthour and Varhour values for the selected source.

Source (x) Demand, Peak Demand, Peak Demand Date

Displays Demand, Peak Demand, and Peak Demand Date values for a variety of measurements for the selected source.

Page 174 of the GE PMCS 6.11a user manual — Control Functions
Page 174 · click to enlarge
Page 174

Line Tab

GE PMCS 6.11a — Line Tab diagram (page 174)
Fig. 136 · Line Tab

Universal Relay - Line Tab

The Line tab supports the D60, F30, F60, G60, L60, L90 and UR devices, and shows a variety of energy measurements and demand parameters for a selected source.

These values are displayed for up to six sources, which may be toggled between using the S1 - S6 buttons. The Clear Demand button clears the values for the selected source.

Line Tab

Displays (for Remote 1, Remote 2, Local, and Differential) the magnitude and angle on phase A, B, and C.

Also displays information on various Direct Inputs, L90 Channels 1 and 2, and Line Position and Line Zero values.

Control Functions

The Control Functions panel displays status (enabled/disabled) and allows control of various relay elements, for example 87L and 87PC protection elements. Elements are greyed out if not installed or applicable to the device type. Each element's may be enabled or disabled by clicking the button next to its name.

Page 175 of the GE PMCS 6.11a user manual — Breaker Status
Page 175 · click to enlarge
Page 175

Breaker Tab

GE PMCS 6.11a — Breaker Tab diagram (page 175)
Fig. 137 · Breaker Tab

Universal Relay - Breaker Tab

The Breaker tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows a variety amperage measurements and breaker status, as well as allowing control of breaker functions and auto reclosers.

Arcing

Amperage at Breaker 1 and 2 is displayed for Phases A, B, and C. The Clear Current Arcing functions allow current arcing conditions to be cleared.

Breaker Arcing Current features are available for Breakers 1 and 2. This element calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared passing through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase and compared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an output operand to "1". The accumulated value for each phase can be displayed as an actual value.

Breaker Functions

Breaker control can be enabled or disabled using these controls, and the Breaker Arcing Amp function can be enabled or disabled for Breakers 1 and 2. These controls will be disabled if the connected device does not support breaker control.

Breaker Status

Selecting a settings group changes the display of functions. Up to 8 settings groups are available for display.

Page 176 of the GE PMCS 6.11a user manual — Contact Output Current State
Page 176 · click to enlarge
Page 176

Auto Reclose

If the breaker is so equipped, the status of and reclose count for up to six Auto Reclose functions can be displayed, and each recloser may be enabled or disabled. Click the button next to each ID number to enable/disable the autorecloser.

Contact Output Current States Tab

GE PMCS 6.11a — Contact Output Current States Tab diagram (page 176)
Fig. 138 · Contact Output Current States Tab

Universal Relay - Contact Output Current States Tab

The Contact Output Current State tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and indicates the current state of the contact outputs installed on the selected relay. Up to 64 contact outputs may be displayed.

Contact Output Current State

The Current, Voltage, and Detect buttons enable the user to shift the viewing mode of the contacts displayed.

The contacts are presented as a series of pages. To view the contact outputs, use the Page arrow keys provided to navigate among the pages. The number of contact outputs available is determined from the Order Code read from the device, and is dependent on the number of digital I/O cards installed in the relay. If a contact output is not available in the connected relay, the associated control button is grayed and disabled, and the output name field shows "N/A".

Page 177 of the GE PMCS 6.11a user manual — RTD Tab
Page 177 · click to enlarge
Page 177

Remote Temperature Detection Tab

GE PMCS 6.11a — Remote Temperature Detection Tab diagram (page 177)
Fig. 139 · Remote Temperature Detection Tab

Universal Relay - Contact Output Tab

The RTD tab supports the B30, C30, C60, D60, F30, F35, F60, G60, L60, L90, M60 and T60 UR devices, and shows the RTD sensors installed on the selected relay. Up to 48 input sensors may be displayed.

RTD Tab

Each RTD sensor's status, function (name), and current temperature are shown. Individual RTD's may be disabled or enabled using the control button next to the RTD number.

The sensors are presented as a series of pages. To view each page of RTD's, use the Prev(ious) and Next keys provided to navigate among the pages. The number of parameters displayed is determined from the Order Code read from the device, and is dependent on the number of RTD sensors wired to the relay. If a sensor is not available in the connected relay, the associated control button is grayed and disabled, and the name field shows "N/A".

Page 178 of the GE PMCS 6.11a user manual — Bus Tab
Page 178 · click to enlarge
Page 178

Bus Tab

GE PMCS 6.11a — Bus Tab diagram (page 178)
Fig. 140 · Bus Tab

Universal Relay - Bus Tab

The Bus tab is supported for the B30 UR device only. It displays Phase Magnitude and Angle measurements on Bus 1 and Bus 2 for phases A, B, and C.

Current direction is shown in degrees for each phase, and the Zone function can be enabled or disabled on each Bus.

Page 179 of the GE PMCS 6.11a user manual — Metering tab
Page 179 · click to enlarge
Page 179

239 Motor Protection Relay

The 239 does not support Waveform Capture or Event generation, therefore these buttons are disabled beneath the Info box.

The 239 Tabular Data Screen’s command buttons are described below:

Tab Button Function

Metering Reset Device Issues a RESET command to the 239

External Restart Issues an External Restart command to the 239

Trip Data Clear Trip Data Clears the last 5 trip causes from the 239’s memory

Table 23. 239 Tabular data screen commands.

  • The Status tab displays 35 Pickup LEDs (amber) and 35 Alarm LEDs (red), along with a text string for each alarm condition on the Status tab.

See the 239 Motor Protection Relay Instruction Manual (Chapter 5, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.

Metering tab

GE PMCS 6.11a — Metering tab diagram (page 179)
Fig. 141 · Metering tab
  • The Multilin 239 Metering screen shows:
  • Current
  • RTD Status and Temperature
  • Motor Status
  • Switches
  • Output Relays
Page 180 of the GE PMCS 6.11a user manual — Status Tab
Page 180 · click to enlarge
Page 180

The Reset Device button, when clicked, will issue a RESET command to the 239. The Emergency Restart button, when clicked, will issue a RESTART command to the 239.

Status Tab

GE PMCS 6.11a — Status Tab diagram (page 180)
Fig. 142 · Status Tab
  • The Status tab displays Alarm, Trip, Auxilary Status Pickup is shown in Amber color and Active Alarm shown in Red, along with a text string for each alarm condition.
  • See the 239 Motor Protection Relay Instruction Manual (Chapter 5, Actual Values ) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.
Page 181 of the GE PMCS 6.11a user manual — Trip Data
Page 181 · click to enlarge
Page 181

Trip Data

GE PMCS 6.11a — Trip Data diagram (page 181)
Fig. 143 · Trip Data
  • The Multilin 239 Last Trip Data screen shows:
  • Cause of Last Trip and their corresponding currents and RTD Temperatures at the time of trip.
  • Trip Record

The Clear Trip Data button, when clicked, will clear all the trip data.

Page 182 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 182 · click to enlarge
Page 182

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 182)
Fig. 144 · Setpoints Tab
  • The Multilin 239 System Setpoints screen shows:
  • CT Inputs
  • Motor Data
  • Phase Current Overload
  • Breaker Failure
  • Immediate Overload
  • Mechanical Jam
Page 183 of the GE PMCS 6.11a user manual — Tab Button Function
Page 183 · click to enlarge
Page 183

269 Plus Motor Management Relay

GE PMCS 6.11a — 269 Plus Motor Management Relay diagram (page 183)
Fig. 145 · 269 Plus Motor Management Relay

The 269 Tabular Data Screen wizard provides two reset push buttons on the Setup 6 tab.

Tab Button Function

Status 6 Clear Last RTD Data Clears the RTD last access registers

Clears the commissioning data registers

Table 24. 269+ Tabular data screen commands.

For complete explanations of parameters, refer to the 269+ Users Guide.

Clear Commissioning Data

Page 184 of the GE PMCS 6.11a user manual — Voltage
Page 184 · click to enlarge
Page 184

369 Motor Management Relay

Metering Tab

GE PMCS 6.11a — 369 Motor Management Relay diagram (page 184)
Fig. 146 · 369 Motor Management Relay
369. Metering Data Screen

The Metering tab displays the following metered values from the 369 device: Actual Values for Voltage, Current, Power, Power Factor, and Frequency. These values are detailed below.

  • Current
  • Per phase magnitude and angle
  • Phase average
  • Ground current
  • Motor Load as a percentage of the Full Load Current rating defined in setpoints.
  • Thermal Capacity used in percent
  • Estimated time to trip
  • Current Unbalance ratio

Voltage

Voltage values are only displayed if the Metering or Backspin option is installed in the relay, and if a voltage transformer (VT) connection has been programmed in the relay.

Line - Line voltage magnitude.

Average Line-Line voltage.

Line – Neutral voltage magnitude and angle (only shown for wye configurations)

Page 185 of the GE PMCS 6.11a user manual — Timer Functions & Learned Values
Page 185 · click to enlarge
Page 185

Average Line-Neutral voltage. (only shown for wye configurations)

Power

  • Power values are displayed only if the Metering or Backspin option is installed in the relay and a VT connection has been programmed.
  • Real power
  • Reactive power
  • Apparent power
  • Power Factor

Motor Status

The current status of the motor is shown in a colored indicator block

Timer Functions & Learned Values

The lower right quadrant of the metering tab has two pages – Timer Functions and Learned Values. You can toggle between these two displays by clicking on the button located in the bottom right corner of the metering tab display.

Timer Functions: this section displays the current values of several internal timers within the device. Most of these functions must be programmed in the relay in order to function. Refer to the device manual for specific usage details.

Learned Values: this section displays items tracked by the relay. For full details on their usage, consult the relay manual.

Backspin features – these are only enabled when the Backspin option is installed in the relay.

Learned cool time constants – these are enabled only if the "Enable Learned Cool Times" feature is programmed.

Learned k factor is only enabled by setting the unbalance biasing of thermal capacity to on/learned.

Clearing Motor Data (see control tab) will set all these values to their defaults.

Page 186 of the GE PMCS 6.11a user manual — Trip Counters
Page 186 · click to enlarge
Page 186

Alarms Tab

GE PMCS 6.11a — Alarms Tab diagram (page 186)
Fig. 147 · Alarms Tab

369 Relay - Alarms Tab

The Alarms tab consists of three pages – Status, Trip Data, and Trip Counters. You can navigate between pages by clicking the buttons located along the lower edge of the tab display.

Alarm Status

This page displays the current status of the alarm functions within the relay.

If a function is disabled or not programmed, its label appears as dark gray text, and its associated indicator will be dark gray at all times.

If a function is enabled, its label appears as black text, and its indicator will show the current status of that function.

Trip Data

This page displays information about the last trip event.

Voltage, power, and power factor values are only indicated if the Metering or Backspin option is installed and a VT connection has been programmed in the relay.

Line-Neutral voltages are only displayed when the VT is connected in a wye configuration.

The Hottest Stator RTD field is only shown if a Stator RTD is programmed.

Trip Counters

This page displays information about the accumulated trips experienced by the relay. Data on this page can be cleared using the Clear Last Trip Data button on the Control tab.

Page 187 of the GE PMCS 6.11a user manual — Demand Tab
Page 187 · click to enlarge
Page 187

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 187)
Fig. 148 · Demand Tab

369 Relay - Demand Tab

This tab displays current and power demand metering information.

Current demand is indicated regardless of options/VT settings.

Power demand values are only available when the Metering or Backspin option is installed on the relay and a VT connection is programmed.

Peak demand values may be cleared using the Clear Peak Demand Data button on the Control tab.

Page 188 of the GE PMCS 6.11a user manual — Local RTD Tab
Page 188 · click to enlarge
Page 188

Local RTD Tab

GE PMCS 6.11a — Local RTD Tab diagram (page 188)
Fig. 149 · Local RTD Tab

369 Relay - Local RTD Tab

This tab displays information about any RTD temperature probes connected directly to the device. Information on this tab is only available if the RTD option is installed in the relay.

Information and alarm indication for each RTD is only available when that RTD is programmed for operation. If an RTD’s Application is set to "none" then all fields for that RTD display "N/A".

The hottest Stator RTD indicates which RTD is currently returning the highest temperature. This condition is indicated by red text in the Temperature field.

Only one alarm condition can be displayed at a time – highest priority alarms are displayed in the alarm indicator. For example, if a "High Alarm" was triggered and latched and the RTD value returned to the "Alarm Active" state, the "High Alarm" latched indicator would persist.

Page 189 of the GE PMCS 6.11a user manual — Remote RTD Tab
Page 189 · click to enlarge
Page 189

Remote RTD Tab

GE PMCS 6.11a — Remote RTD Tab diagram (page 189)
Fig. 150 · Remote RTD Tab

369 Relay - Remote RTD Tab

This tab displays information about any RTD temperature probes connected to one or more Remote RTD units. These external accessories connect via Modbus to the 369 relay. A maximum of four RRTD modules can be connected to a 369 relay – each module is assigned a page on this tab. Use the RRTD Selection buttons in the lower left corner of the tab to navigate between pages. Information on this tab is only available if an RRTD module is connected to the relay.

Information and alarm indication for each RTD is only available when that RTD is programmed for operation. If an RTD’s Application is set to "none" then all fields for that RTD display "N/A".

The hottest Stator RTD indicates which RTD is currently returning the highest temperature. This condition is indicated by red text in the Temperature field.

Only one alarm condition can be displayed at a time – highest priority alarms are displayed in the alarm indicator. For example, if a "High Alarm" was triggered and latched and the RTD value returned to the "Alarm Active" state, the "High Alarm" latched indicator would persist.

The Status indicators are dedicated to the indicated RRTD module, except for the Comm. Failure indicator – this will be energized if any configured RRTD module stops communicating.

Page 190 of the GE PMCS 6.11a user manual — Control Tab
Page 190 · click to enlarge
Page 190

Control Tab

GE PMCS 6.11a — Control Tab diagram (page 190)
Fig. 151 · Control Tab

369 Relay - Control Tab

This tab provides limited control functionality over Modbus.

Status – indicates the current status of the output relays and general digital inputs.

Preset Values – shows the current value of the indicated field. Note that these values are only updated when the tab is first displayed – not continuously. To preset a new value, click the white box containing the value you want to change. The Intouch Calculator window appears – type in the new value and click OK. The new value is now displayed in the Control tab, but has not yet been sent to the device. Click the Set button to store the new value in the device.

Control – These buttons are disabled unless the Serial Communications Control setpoint in the relay is programmed to "On". These buttons are subject to Intouch user level security. The security level is set during wizard configuration.

Clear Data – These buttons clear the designated values within the device. All buttons are subject to Intouch user level security which is set during wizard configuration.

Page 191 of the GE PMCS 6.11a user manual — Setup Tab
Page 191 · click to enlarge
Page 191

Setup Tab

GE PMCS 6.11a — Setup Tab diagram (page 191)
Fig. 152 · Setup Tab

369 Relay - Setup Tab

This tab displays selected setpoints from the device. All fields on this tab are read- only. Setpoints may be changed via the relay’s own setup program or manually via the front panel.

Page 192 of the GE PMCS 6.11a user manual — Metering Tab
Page 192 · click to enlarge
Page 192

SR469 Motor Management Relay

All six function buttons under the Info area are enabled for the SR469.

The SR469 Tabular Data Screen wizard has nine command buttons, described below.

Tab Button Function

Metering Reset Device Issues a RESET command to the SR469

Clear MWh and Mvarh Clears these values from the SR469’s memory

Clear Peak Demand Clears this data from memory

Status Motor Start/Motor Stop Issues Motor Start or Motor Stop commands

Clear RTD Maximums Resets the RTD Maximums data

Trip Clear Last Trip Data Clears this data from memory

I/O Clear Analog Input Min/Max Data

Clears this data from memory

Maintenance Preset Digital Counter Allows presetting of digital counters.

Clear Trip Counters Clears the trip count data from memory.

Table 25. SR469 Tabular data screen commands.

See the SR469 Motor Management Relay manual (Chapter 5, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 192)
Fig. 153 · Metering Tab

The Multilin SR469 Metering Values screen shows the metering values, for example, Amps A, Amps B and Amps C; and

Page 193 of the GE PMCS 6.11a user manual — Status Tab
Page 193 · click to enlarge
Page 193

Volts AB, Volts BC and Volts CA. Also shows Power, Energy, Motor Data and RTD information. The Clear Peak Demand button will clear all Peak Demand data The Clear MWh & Mvarh button will clear all MWh and Mvarh values. The RESET Device button will issue a RESET command to the SR469.

Status Tab

GE PMCS 6.11a — Status Tab diagram (page 193)
Fig. 154 · Status Tab

The Multilin SR469 Status screen shows:

  • Start Blocks
  • Motor Status
  • Real Time Clock
  • RTD Maximums

The Clear RTD Maximums button will clear all maximum RTD values.

Page 194 of the GE PMCS 6.11a user manual — Alarms Tab
Page 194 · click to enlarge
Page 194

Alarms Tab

GE PMCS 6.11a — Alarms Tab diagram (page 194)
Fig. 155 · Alarms Tab

The Multilin SR469 Alarm Status screen shows the status of various alarms such as Overload Alarm and Underpower Alarm.

Page 195 of the GE PMCS 6.11a user manual — Trip Tab
Page 195 · click to enlarge
Page 195

Trip Tab

GE PMCS 6.11a — Trip Tab diagram (page 195)
Fig. 156 · Trip Tab

The Multilin SR469 Trip screen shows the values of last trip data. The Clear Last Trip Data button will clear all values of the last trip data.

Page 196 of the GE PMCS 6.11a user manual — IO Tab
Page 196 · click to enlarge
Page 196

IO Tab

GE PMCS 6.11a — IO Tab diagram (page 196)
Fig. 157 · IO Tab
  • The Multilin SR469 Inputs & Outputs screen shows values related to:
  • Output Relays
  • Digital Input Switches
  • Analog Inputs

The Clear Analog I/P Min/Max button will clear all minimum and maximum values of Analog I/P.

Page 197 of the GE PMCS 6.11a user manual — Maintenance Tab
Page 197 · click to enlarge
Page 197

Maintenance Tab

GE PMCS 6.11a — Maintenance Tab diagram (page 197)
Fig. 158 · Maintenance Tab

The Multilin SR469 Maintenance screen shows values related to:

  • Trip Counters
  • Timers
  • General Counters

The Clear Trip Counters button will clear all values of trip counters and the Preset Digital Ctr will preset trip counters.

Page 198 of the GE PMCS 6.11a user manual — Analog Tab
Page 198 · click to enlarge
Page 198

Analog Tab

GE PMCS 6.11a — Analog Tab diagram (page 198)
Fig. 159 · Analog Tab

The Multilin SR469 Analog Input Differential screen shows:

  • Analog Input Diff 1-2
  • Analog Input Diff 3-4
Page 199 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 199 · click to enlarge
Page 199

RTD HI Tab

GE PMCS 6.11a — RTD HI Tab diagram (page 199)
Fig. 160 · RTD HI Tab

The Multilin SR469 HI Alarm Status screen shows various RTD values.

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 199)
Fig. 161 · Setpoints Tab

The Multilin SR469 System Setpoints screen shows values of Thermal Model, Current, Voltage Sensing, Power System

Page 200 of the GE PMCS 6.11a user manual — Metering Tab
Page 200 · click to enlarge
Page 200

SR489 Generator Management Relay

All the SR489’s function buttons below the Info box are enabled.

The SR489 Tabular Data Screen wizard has nine command buttons, described below.

Tab Button Function

Metering Reset Device Issues a RESET command to the device.

Clear Peak Demand Clears the peak demand data from memory.

Clear MWh and Mvarh Clears the MWh and Mvarh data from memory.

Clear Max RTD Data Clears the maximum RTD data from memory.

Trip Data Clear Last Trip Data Clears the last trip data from memory.

I/O Clear Analog I/P Min/Max Data Clears the analog input minimum/maximum data from memory.

Maintenance Clear Trip Counters Clears the trip counter data from memory.

Clear Generator Information Clears the generator data from memory.

Clear Breaker Information Clears the breaker data from memory.

Table 26. SR489 Tabular data screen commands.

See the SR489 Generator Management Relay manual (Chapter 5, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 200)
Fig. 162 · Metering Tab

The Multilin SR489 Metering Values screen shows various metering values:

  • Current
  • Voltage
Page 201 of the GE PMCS 6.11a user manual — CLICK MORE BUTTON TO SEE MORE PICKUPS
Page 201 · click to enlarge
Page 201
  • Demand
  • Power
  • RTD Information
  • Motor Data

The Clear Peak Demand button clears all peak demand values. The Clear MWh & Mvarh button clears all MWh and Mvarh data The Clear Max RTD Data button clears the maximum RTD data and The RESET Device button will issue a RESET command to the device.

Pickup Tab

GE PMCS 6.11a — Pickup Tab diagram (page 201)
Fig. 163 · Pickup Tab

The Multilin SR489 Pickups screen shows:

  • Phase Differential Trip
  • Overvoltage Trip
  • Volts/Hertz Trip

CLICK MORE BUTTON TO SEE MORE PICKUPS

Alarms Tab

Page 202 of the GE PMCS 6.11a user manual — Trip Data Tab
Page 202 · click to enlarge
Page 202
GE PMCS 6.11a — Trip Data Tab diagram (page 202)
Fig. 164 · Trip Data Tab

The Multilin SR489 Alarm Pickups screen shows all the Alarms.

Trip Data Tab

GE PMCS 6.11a — Trip Data Tab diagram (page 202)
Fig. 165 · Trip Data Tab

The Multilin SR489 Last Trip Data screen shows the values of last trip data and the corresponding values at the time of trip. The Clear Last Trip Data button clears all values of the last trip data.

Page 203 of the GE PMCS 6.11a user manual — IO Tab
Page 203 · click to enlarge
Page 203

IO Tab

GE PMCS 6.11a — IO Tab diagram (page 203)
Fig. 166 · IO Tab

The Multilin SR489 Inputs & Outputs screen shows:

  • Digital Input Switches
  • Analog Inputs
  • Output Relays
  • Learned Data Values The Clear Analog I/P Min/Max button clears all the minimum and maximum analog I/P.
Page 204 of the GE PMCS 6.11a user manual — Maintenance Tab
Page 204 · click to enlarge
Page 204

Maintenance Tab

GE PMCS 6.11a — Maintenance Tab diagram (page 204)
Fig. 167 · Maintenance Tab

The Multilin SR489 Maintenance screen shows:

  • General Timers & Counters
  • Trip Counters The Clear Trip Counters button will clear all values of trip counters; the Clear General Info button will clear all general information; and the Clear Breaker Info button will clear all breaker information from the memory.
Page 205 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 205 · click to enlarge
Page 205

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 205)
Fig. 168 · Setpoints Tab

The Multilin SR489 System Setpoints screen shows various values related to the setpoints such as Phase CT Primary, Ground CT Type, VT Connection Type, Voltage Transformer Ratio etc.

Page 206 of the GE PMCS 6.11a user manual — 565 Feeder Management Relay
Page 206 · click to enlarge
Page 206

565 Feeder Management Relay

GE PMCS 6.11a — 565 Feeder Management Relay diagram (page 206)
Fig. 169 · 565 Feeder Management Relay

The 565 Tabular Data Screen wizard has the following buttons on the Command tab:

GE PMCS 6.11a — 565 Feeder Management Relay diagram (page 206)
Fig. 170 · 565 Feeder Management Relay

End of Analog Output Test Ends the analog output test

Test LCD Display Sends a test pattern to the LCD

Table 27. 565 Tabular data screen commands.

The Setup 2 tab has two data input areas. Analog Input Title creates a user label for the analog input used in the device. Analog Input Units performs the same function for the units of the analog input. These labels appear on the Metering tab and on the Large Faceplate wizard when the analog input is displayed. The analog input can be

Page 207 of the GE PMCS 6.11a user manual — 565 Feeder Management Relay
Page 207 · click to enlarge
Page 207

scaled to display any desired units from the front of the device, but these labels are not sent to the DDE Server.

For complete explanations of parameters, refer to the 565 Users Guide.

Page 208 of the GE PMCS 6.11a user manual — Metering Tab
Page 208 · click to enlarge
Page 208

735 Feeder Relay

The Events and Wave function buttons below the Info box are disabled since the 735 does not support Waveform Capture or Event generation.

The 735 Tabular Data Screen wizard has two command buttons, described below.

Tab Button Function

Metering Reset Device Issues a RESET command to the 735

Trip Clear Last Trip Data Clears the trip causes log

Table 28. 735 Tabular data screen commands.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 208)
Fig. 171 · Metering Tab

The 735 Metering screen shows:

  • Current and Output Relays
  • Time Overcurrent Trip and Instantaneous Overcurrent Trip
  • Configuration The RESET/CLEAR Device button will issue a RESET command to 735.
Page 209 of the GE PMCS 6.11a user manual — Trip Data Tab
Page 209 · click to enlarge
Page 209

Trip Data Tab

GE PMCS 6.11a — Trip Data Tab diagram (page 209)
Fig. 172 · Trip Data Tab

The 735 Trip Data screen shows trip data information such as:

  • Last Trip Data
  • Trip Record The Clear Last 5 Trip Causes button will clear values of last 5 trip causes.
Page 210 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 210 · click to enlarge
Page 210

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 210)
Fig. 173 · Setpoints Tab

The 735 System Setpoints screen shows setpoints information such as:

  • Dial Settings
  • Option Switches
Page 211 of the GE PMCS 6.11a user manual — Metering Tab
Page 211 · click to enlarge
Page 211

SR745 Transformer Management Relay

Under the Info area, the SR745’s function buttons are all enabled.

The SR745 Tabular Data Screen wizard has three command buttons:

Tab Button Function

Metering Reset Device Issues a RESET command to the device

Demand Clear Max Demand Data

Clears the maximum demand data from the SR745’s memory

Harmonics Clear Loss-of-Life Data

Clears loss-of-life data from the SR745’s memory

Table 29. SR745 Tabular data screen commands.

See the SR745 Transformer Management Relay Instruction Manual (Chapter 6, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A. When configured for only 2 Windings, the Winding 3 fields on the Tabular Data wizard are not visible.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 211)
Fig. 174 · Metering Tab

The Multilin SR745 Metering Values screen shows:

  • Current
  • Sequence Current
  • Status Flags The RESET Device button will issue a RESET command to the device.
Page 212 of the GE PMCS 6.11a user manual — IO Tab
Page 212 · click to enlarge
Page 212

Flags Tab

GE PMCS 6.11a — Flags Tab diagram (page 212)
Fig. 175 · Flags Tab

The Multilin SR745 Element Flags screen shows the state and phases of various elements.

IO Tab

GE PMCS 6.11a — IO Tab diagram (page 212)
Fig. 176 · IO Tab

The Multilin SR745 Inputs & Outputs screen shows:

Page 213 of the GE PMCS 6.11a user manual — Demand Tab
Page 213 · click to enlarge
Page 213
  • Logic Inputs
  • Virtual Inputs
  • Output Relays
  • Virtual Outputs
  • Analog Input

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 213)
Fig. 177 · Demand Tab

The Multilin SR745 Demand Data screen shows:

  • Configuration
  • Present Values
  • Maximums The Clear Max Demand Data button will clear all maximum values of the demand data.
Page 214 of the GE PMCS 6.11a user manual — Harmonic Tab
Page 214 · click to enlarge
Page 214

Harmonic Tab

GE PMCS 6.11a — Harmonic Tab diagram (page 214)
Fig. 178 · Harmonic Tab

The Multilin SR745 Harmonic & Misc Data screen shows:

  • Harmonic Data
  • Misc

The Reset Loss of Life button will clear loss-of-life data from the SR745’s memory.

Page 215 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 215 · click to enlarge
Page 215

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 215)
Fig. 179 · Setpoints Tab

The Multilin SR745 System Setpoints screen shows information such as Nominal Phase to Phase Voltage, Rated Load (MVA), Transformer Type and Analog Outputs.

Page 216 of the GE PMCS 6.11a user manual — Power Tab
Page 216 · click to enlarge
Page 216

Power Tab

GE PMCS 6.11a — Power Tab diagram (page 216)
Fig. 180 · Power Tab

The Multilin SR745 Power & Energy screen shows:

  • Power
  • Energy
  • Aging Factor
  • Tap Changer
Page 217 of the GE PMCS 6.11a user manual — Tab Button Function
Page 217 · click to enlarge
Page 217

SR750/760 Feeder Management Relay

The SR750 and SR760 are very similar devices and share a common Tabular Data Screen wizard. During wizard configuration, select which type of device the wizard represents (SR750 or SR760) by selecting the corresponding radio button in the Tabular Data Screen Configuration dialog box.

Under the Info area, the SR750/760’s function buttons are all enabled.

The SR750/760 Tabular Data Screen wizard has eight command buttons:

Tab Button Function

Metering Clear Energy Resets the energy counters to zero.

Reset Device Issues a RESET command to the SR750/760.

Demand Reset Max Demand Clears the Max Demand data from the SR750/760’s memory.

Trip Reset Trip Counters Resets the SR750/760’s trip counters to zero.

I/O Open Breaker Issues Open Breaker command.

Close Breaker Issues Close Breaker command.

Reset Count Resets the SR750/760's reclosure counter to zero.

Fault Reset Arcing Current

Resets the arcing current data.

Table 30. SR750/760 Tabular data screen commands.

The SR750/760 Tabular screen offers a tab labeled LOGIC. This tab allows you to access the SR750/760's 20 logic inputs. You can use these logic inputs to operate a variety of logic functions for circuit breaker control, external trips, blocking of protection elements, etc., and use the PCMS Wizard to monitor the status of the logic inputs. For more information, refer to the SR750 or SR760 user manual, in the section titled Setpoints - S3 Logic Inputs.

The SR750/SR760 Tabular Data Screen Wizard supports the Lockout/Tagout wizard. Please refer to the section titled Using and Configuring PMCS Wizards: Lockout/Tagout Wizard for details.

If a Danger or Ground Lockout/Tagout symbol is installed on this wizard, attempts to issue a Breaker Open or Breaker Close command will generate an error message.

See the SR750/760 Feeder Management Relay Instruction Manual (Chapter 5, Actual Values) for information on the display of data values under different device configurations. Values not configured for use are displayed as N/A.

Page 218 of the GE PMCS 6.11a user manual — Metering Tab
Page 218 · click to enlarge
Page 218

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 218)
Fig. 181 · Metering Tab

The SR750/760 Metering screen shows:

  • Current
  • Energy
  • Voltage
  • Power The Clear Energy Data button will clear all values of energy data. The RESET Device button will issue a RESET command to the device.
Page 219 of the GE PMCS 6.11a user manual — Fault Tab
Page 219 · click to enlarge
Page 219

Status Tab

GE PMCS 6.11a — Status Tab diagram (page 219)
Fig. 182 · Status Tab

The SR750/760 Status screen shows Active Conditions.

Fault Tab

GE PMCS 6.11a — Fault Tab diagram (page 219)
Fig. 183 · Fault Tab

The SR750/760 Fault & Maintenance Data screen shows:

Page 220 of the GE PMCS 6.11a user manual — Trip Tab
Page 220 · click to enlarge
Page 220
  • Fault Locations
  • Total Arcing Current

The Reset Arcing Current button will reset all values of the arcing current.

Trip Tab

GE PMCS 6.11a — Trip Tab diagram (page 220)
Fig. 184 · Trip Tab

The SR750/760 Trip Data screen shows:

  • Last Trip Data
  • Trip Counters

The Reset Trip Counters button will reset all values of the trip counters.

Page 221 of the GE PMCS 6.11a user manual — Demand Tab
Page 221 · click to enlarge
Page 221

Demand Tab

GE PMCS 6.11a — Demand Tab diagram (page 221)
Fig. 185 · Demand Tab

The SR750/760 Demand screen shows details of:

  • Configuration
  • Values The Reset Max Demand button will reset all maximum values of demand.
Page 222 of the GE PMCS 6.11a user manual — IO Tab
Page 222 · click to enlarge
Page 222

Logic Tab

GE PMCS 6.11a — Logic Tab diagram (page 222)
Fig. 186 · Logic Tab

The SR750/760 Logic screen shows:

  • Contact Inputs
  • Virtual Inputs
  • Logic Input States

IO Tab

GE PMCS 6.11a — IO Tab diagram (page 222)
Fig. 187 · IO Tab

The SR750/760 Inputs & Outputs screen shows:

Page 223 of the GE PMCS 6.11a user manual — Setpoints Tab
Page 223 · click to enlarge
Page 223
  • Output Relays
  • Analog Input
  • Hardware Input Coils
  • Breaker Operation The Open Breaker button will issue an Open Breaker command. The Close Breaker button will issue a Close Breaker command.

Setpoints Tab

GE PMCS 6.11a — Setpoints Tab diagram (page 223)
Fig. 188 · Setpoints Tab

The SR750/760 System Setpoints screen shows:

  • System Setup
  • Analog Output Configuration
Page 224 of the GE PMCS 6.11a user manual — Fanuc 90/70
Page 224 · click to enlarge
Page 224

Fanuc 90/30

GE PMCS 6.11a — Fanuc 90/30 diagram (page 224)
Fig. 189 · Fanuc 90/30

The Fanuc 90/30 Tabular Data Screen wizard is blank. This allows any desired data to be placed on the screen.

Fanuc 90/70

GE PMCS 6.11a — Fanuc 90/70 diagram (page 224)
Fig. 190 · Fanuc 90/70

The Fanuc 90/70 Tabular Data Screen wizard is blank. This allows any desired data to be placed on the screen.

Page 225 of the GE PMCS 6.11a user manual — Fanuc Micro 90
Page 225 · click to enlarge
Page 225

Fanuc Micro 90

GE PMCS 6.11a — Fanuc Micro 90 diagram (page 225)
Fig. 191 · Fanuc Micro 90

The GE Fanuc Micro 90 Tabular Data Screen is blank. This allows for any desired data to be placed on the screen.

Page 226 of the GE PMCS 6.11a user manual — Metering Tab
Page 226 · click to enlarge
Page 226

MX200

The MX 200 device is an Automatic Transfer Switch. The Tabular Data Screen wizard has several special features. You can use the Setup screen to change the meter configuration. Values displayed in white boxes are changeable. Clicking on the displayed value changes some, while clicking on the box changes others. The Download and Refresh buttons on the setup screen upload and download all of the setpoints from the device.

To change setpoints at the device, first press the refresh button to upload current setpoint values from the device (otherwise the defaults are shown and used for download). Modify setpoints as desired then press the download button to send all setpoints to the unit. In the following pages, each of the MX 200 Meter’s Tabular Data Screen Wizards’ tabs will be displayed and detailed.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 226)
Fig. 192 · Metering Tab

The Metering tab displays the following metered values from the MX 200 device.

Page 227 of the GE PMCS 6.11a user manual — Others
Page 227 · click to enlarge
Page 227

Voltages

Normal and Emergency Voltage values for all the phases.

Timer Functions

  • Timer Active
  • Timer Countdown Value
  • Time on Emergency
  • No. of Transfers
  • Nominal FS Vol. Value
  • ATS Mode
  • Fault Present
  • Exerciser Enabled
  • Load Test Running
  • Load, No Load, Fast Load Status

Communications

  • MX-200 – Modcard – Communication Status Displays communication status, for example, Comm OK

Status

  • Q3 Input
  • Auxiliary 2 Input
  • Auxiliary 1 Input
  • Automatic Transfer Relay
  • SN Limit Switch
  • SE Limit Switch
  • SNO Limit Switch
  • SEO Limit Switch
  • S5 Selector
  • S12 Selector
  • Load Shed Input
  • Q7 Input The status is either ON or OFF. If the relay is ON, the status is displayed in green and if relay is OFF, it is displayed in red.

Others

Page 228 of the GE PMCS 6.11a user manual — Setup Tab
Page 228 · click to enlarge
Page 228

The tab shows frequency and number of phases on source:

  • Position Status
  • Phase Rotation The status for Source is displayed as Available (displayed in green) or Not Available (displayed in red). The Position Status is displayed as Normal (displayed in green) or Emergency (displayed in red). The Phase Rotation is displayed as ON (displayed in green) or OFF (displayed in red).

Setup Tab

GE PMCS 6.11a — Setup Tab diagram (page 228)
Fig. 193 · Setup Tab

The Setup tab displays the following demand values from MX 200 device.

Page 229 of the GE PMCS 6.11a user manual — Voltage (Volts)
Page 229 · click to enlarge
Page 229

Control

  • YE
  • YN
  • No Load Test
  • Load Test
  • Fast Load Test
  • S5
  • S12
  • LS
  • Q7
  • Q3
  • Aux2
  • Aux1 The legend is ON and OFF. If ON, it is indicated by amber and if OFF by gray color.

Options

  • T3 Timer Bypass
  • T3 Timer
  • W3 Timer Bypass
  • W3 Timer
  • T Timer Bypass
  • W Timer Bypass
  • In Ph. Mon/Closed Trans
  • ATS Type
  • S12 Auto/Manual
  • S5 Auto/Manual Bypass
  • Phase Sequence Check
  • Emg Over Frequency
  • Emg Over Voltage
  • Normal Over Frequency
  • Normal Under Frequency
  • Normal Over Voltage The value against each option is displayed as either as Confirmed or Not Confirmed.

Voltage (Volts)

Page 230 of the GE PMCS 6.11a user manual — Time (Seconds)
Page 230 · click to enlarge
Page 230
  • Normal Pickup
  • Normal Dropout
  • Emer Pickup
  • Emer Dropout The user can enter values against each parameter.

Frequency (Hz)

  • Normal Pickup
  • Emer Pickup The user can enter values against each parameter.

Time (Seconds)

  • P Time
  • W Time
  • W3 Time
  • DW Time
  • T Time
  • T3 Time
  • DT Time
  • U Time

The Setup tab also provides push buttons for performing the following commands:

Download – Executes a script to check for values that have changed and downloads those values to the device

Refresh – Executes a script to upload all of the meter values for the settings on the screen.

Page 231 of the GE PMCS 6.11a user manual — Master Tab
Page 231 · click to enlarge
Page 231

GEN PLC

The Generator Programmable Logic Controller (PLC) is a specially programmed PLC with specific number of I/O modules, controlled by a Master PLC program up to maximum number of 16 Generators.

GEN PLC Tabular wizard mainly have 3 tabs as described below.

Master Tab

GE PMCS 6.11a — Master Tab diagram (page 231)
Fig. 194 · Master Tab
  • The Master PLC lists 16 generators displaying status for each generator separately. The status types are:
  • Run/Stop
  • Alarm
  • Shutdown
  • Runtime (in hours)
  • Lead Value If a particular generator is stopped, it is displayed in gray color; if a generator is running, in green; if there is an alarm, in amber; and shutdown of a generator in red.
  • The parameters of generators are:
  • Engine Crank Time (In seconds)
  • No. of Cranks
  • Cool Down Time (In seconds)
Page 232 of the GE PMCS 6.11a user manual — Generator Tab
Page 232 · click to enlarge
Page 232

Generator Tab

GE PMCS 6.11a — Generator Tab diagram (page 232)
Fig. 195 · Generator Tab

This tab displays generator parameters for 16 generators represented as G1 to G16 (buttons). When a button is clicked, the parameters of that generator are displayed on the screen. The parameters are:

  • Status
  • Gen Brkr Aux Contact
  • Breaker Close Ready
  • Not in Auto
  • CPU Running
  • Engine in Cooldown
  • Engine Run Contact If a generator is running, the status is displayed in gray and if it is Status Stop, it is displayed as green. The status Not In Auto is displayed in red.
  • Alarm
  • Undervoltage
  • Hi Water Temp Warn
  • Battery Charger Failure
  • Low Fuel Day Tank
  • Oil Pressure Warning
  • Low Water Temp
  • Low Water Level
  • Day Tank Critically – Low Fuel Level
  • Day Tank Hi Fuel Level
  • Day Tank Fuel Leak
  • Summary Alarm
Page 233 of the GE PMCS 6.11a user manual — PSG
Page 233 · click to enlarge
Page 233

Any alarm in generator’s status is displayed in amber. Otherwise the status is displayed in gray.

  • Shutdown
  • Overcrank
  • Overspeed
  • High Water Temp
  • Oil Pressure
  • Overvoltage
  • Reverse Power
  • Breaker Locked Out
  • Fail to Synchronize
  • General Failure
  • Emergency Stop
  • EMCP Diagnostic Failure
  • Gen Set Breaker
  • Air Damper Switch
  • Lock Out 489 Relay
  • Fail Safe 489 Relay

PSG

GE PMCS 6.11a — PSG diagram (page 233)
Fig. 196

The screen shows Paralleling SwitchGear Status of generators.

Page 234 of the GE PMCS 6.11a user manual — PSG
Page 234 · click to enlarge
Page 234
  • Status
  • Latched Under Frequency
  • Latched Over Frequency
  • Communication Failure
  • Main Tank Low Fuel Level
  • Main Tank Critical Low Fuel Level
  • Main Tank High Fuel Level
  • Main Tank Fuel Leaked
  • Load Bank Breaker Bell Alarm
  • System Not in Auto
  • System Under Test
  • Remote Start Signal Received
  • System in Load Demand Mode
  • System Test With Load Bank
  • Remote Peak Shave Signal Received
  • Load Add Priority
  • Load Add Priority 3
  • Load Add Priority 4
  • Load Shed Priority 2
  • Load Shed Priority 3
  • Load Shed Priority 4
Page 235 of the GE PMCS 6.11a user manual — Current (Amps)
Page 235 · click to enlarge
Page 235

EPM5300P

This device belongs to Electro Industries family, which is tightly integrated device in to PMCS product. This device contains the following tabs.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 235)
Fig. 197 · Metering Tab

The screen explains various parameters of the device:

Current (Amps)

  • Phase (A, B, C and Neutral)
  • Inst
  • Max
Page 236 of the GE PMCS 6.11a user manual — Power
Page 236 · click to enlarge
Page 236

Voltage (Volts)

  • Phase (AN, BN, CN, AB, BC and CA)
  • Inst
  • THD Current
  • THD Voltage

Energy

  • WATT Hour
  • VA Hour
  • VAR Hour

Power

  • Real (WATT)
  • Reactive (VAR)
  • Apparent (VA)
  • PF
Page 237 of the GE PMCS 6.11a user manual — Setup One Tab
Page 237 · click to enlarge
Page 237

Setup One Tab

GE PMCS 6.11a — Setup One Tab diagram (page 237)
Fig. 198 · Setup One Tab

The screen explains various parameters in relation with Relay 1 and Relay 2 such as:

  • Configuration
  • Kilo Volt Inputs
  • Kilo Amp Input
  • Mega Watt Input
  • Phase Reverse Limits
  • Meter Setup
  • Limits Set By
  • Relay 1 / Relay 2
  • Phase Reversal
  • Phase Imbalance
  • Delay On
  • Delay Off
  • Decimal Placement
  • Volts Decimal Placement
  • Amps Decimal Placement
  • WATT Decimal Placement
  • VOLTS Full Scale
  • AMPS Full Scale
  • Lim. Threshold for lmb (%)
Page 238 of the GE PMCS 6.11a user manual — Setup Two Tab
Page 238 · click to enlarge
Page 238
  • Reset
  • WATT Hour
  • VAR Hour
  • VA Hour

If it is kilo volt inputs, the decimal placement is 2 (as shown in the screen); if kilo amp input the decimal placement is 3 and if mega watt input, it is 1. Note: Configured is displayed in green, Enabled in red and Reset in Amber.

Setup Two Tab

GE PMCS 6.11a — Setup Two Tab diagram (page 238)
Fig. 199 · Setup Two Tab

The screen explains various parameters related to Limits and Triggers: Brief explanation of each of the columns is described below

Column Description Limit 1 Limit 1 value for the Associated quantity (For example: Phase A Amps) Trigger - Relay 1 LED display in Amber color : Limit 1 of the associated value will trigger Relay 1. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 1. Trigger - Relay 2 LED display in Amber color : Limit 1 of the associated value will trigger Relay 2. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 2. Limit 2 Limit 2 value for the Associated quantity (For example: Phase A Amps) Trigger - Relay 1 LED display in Amber color : Limit 2 of the associated value will trigger Relay 1. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 1. Trigger - Relay 2 LED display in Amber color : Limit 2 of the associated value will trigger Relay 2. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 2. Set Above/Below Limit 1 LED display in RED color : Limit 1 of the associated value is Set for Above. LED display in Gray color: Limit 1 of the associated value is Set for Below. Set Above/Below Limit 2 LED display in RED color : Limit 2 of the associated value is Set for Above.

Page 239 of the GE PMCS 6.11a user manual — Power
Page 239 · click to enlarge
Page 239

LED display in Gray color: Limit 2 of the associated value is Set for Below. Exceeded Limit 1 LED display in GREEN color : The associated quantity is exceeded the Limit 1 value. LED display in Gray color: The associated quantity is NOT exceeded the Limit 1 value. Exceeded Limit 2 LED display in GREEN color : The associated quantity is exceeded the Limit 2 value. LED display in Gray color: The associated quantity is NOT exceeded the Limit 2 value.

Example 1 Example 2 Limit1 is Set for Above Limit 2 is Set for Below Limit 1 is 100 Amps Limit 2 is 80 Amps The associated Quantity is Phase A Instantaneous value is 397 Amps The associated Quantity is Phase A Instantaneous value is 50 Amps Exceeded Limit 1 will show in GREEN color as 397>100 Exceeded Limit 1 will show in GREEN color as 50

Current

  • Phase A
  • Phase B
  • Phase C
  • Neutral

Voltage

  • AN
  • BN
  • CN
  • AB
  • BC
  • CA

Power

  • VA
  • VAR
  • WATT
  • PF
  • Frequency
Page 240 of the GE PMCS 6.11a user manual — Current (Amps)
Page 240 · click to enlarge
Page 240

EPM5200P

This device belongs to Electro Industries family, which is tightly integrated device in to PMCS product. This device contains the following tabs.

Metering Tab

GE PMCS 6.11a — Metering Tab diagram (page 240)
Fig. 200 · Metering Tab

The screen explains various parameters of the device:

Current (Amps)

  • Phase (A, B, C, Neutral)
  • Inst
  • Max
Page 241 of the GE PMCS 6.11a user manual — Setup One Tab
Page 241 · click to enlarge
Page 241

Voltage (Volts)

  • Phase (AN, BN, CN, AB, BC, CA)
  • Inst

THD Current/THD Voltage

  • Displays Phase A, Phase B and Phase C THD Current and Voltage values.

Energy

  • WATT Hour
  • VA Hour
  • VAR Hour

Power

  • Real (WATT)
  • Reactive (VAR)
  • Apparent (VA)
  • PF

Setup One Tab

GE PMCS 6.11a — Setup One Tab diagram (page 241)
Fig. 201 · Setup One Tab

The screen explains various parameters in relation with Relay 1 and Relay 2 such as:

Page 242 of the GE PMCS 6.11a user manual — Setup One Tab
Page 242 · click to enlarge
Page 242
  • Configuration
  • Kilo Volt Inputs
  • Kilo Amp Input
  • Mega Watt Input
  • Phase Reverse Limits
  • Meter Setup
  • Limits Set By
  • Relay 1 / Relay 2
  • Phase Reversal
  • Phase Imbalance
  • Delay On
  • Delay Off
  • Decimal Placement
  • Volts Decimal Placement This value decides the precision. User can change the values from 1 to 4.
  • Amps Decimal Placement This value decides the precision. User can change the values from 1 to 4.
  • WATT Decimal Placement
  • VOLTS Full Scale If kilo volt inputs value is set then Voltage full-scale value is divided by 1000, showing the value in Kilo Volts.
  • AMPS Full Scale If kilo Amp inputs value is set then Amps full-scale value is divided by 1000, showing the value in Kilo Amps.
  • Reset
  • WATT Hour
  • VAR Hour
  • VA Hour
Page 243 of the GE PMCS 6.11a user manual — Voltage (Volts)
Page 243 · click to enlarge
Page 243

EPM5350P

Special Note: This device supports GE32MTCP Server ONLY.

This device belongs to Electro Industries family, which is tightly integrated device in to PMCS product. This device contains the following tabs.

Metering Tab

The screen explains various parameters of the device:

Current (Amps)

  • Phase (A, B, C and Neutral)
  • Inst
  • Max

Voltage (Volts)

  • Phase (AN, BN, CN, AB, BC and CA)
  • Inst
Page 244 of the GE PMCS 6.11a user manual — Setup One Tab
Page 244 · click to enlarge
Page 244
  • THD Current
  • THD Voltage

Energy

  • WATT Hour
  • VA Hour
  • VAR Hour

Power

  • Real (WATT)
  • Reactive (VAR)
  • Apparent (VA)
  • PF

Setup One Tab

GE PMCS 6.11a — Setup One Tab diagram (page 244)
Fig. 202 · Setup One Tab

The screen explains various parameters in relation with Relay 1 and Relay 2 such as:

  • Configuration
  • Kilo Volt Inputs
  • Kilo Amp Input
  • Mega Watt Input
  • Phase Reverse Limits
Page 245 of the GE PMCS 6.11a user manual — Column Description
Page 245 · click to enlarge
Page 245
  • Meter Setup
  • Limits Set By
  • Relay 1 / Relay 2
  • Phase Reversal
  • Phase Imbalance
  • Delay On
  • Delay Off Decimal Placement
  • Volts Decimal Placement
  • Amps Decimal Placement
  • WATT Decimal Placement
  • VOLTS Full Scale
  • AMPS Full Scale
  • Lim. Threshold for lmb (%) Reset
  • WATT Hour
  • VAR Hour
  • VA Hour

If it is kilo volt inputs, the decimal placement is 2 (as shown in the screen); if kilo amp input the decimal placement is 3 and if mega watt input, it is 1. Note: Configured is displayed in green, Enabled in red and Reset in Amber.

Setup Two Tab

GE PMCS 6.11a — Setup Two Tab diagram (page 245)
Fig. 203 · Setup Two Tab

The screen explains various parameters related to Limits and Triggers: Brief explanation of each of the columns is described below

Column Description

Page 246 of the GE PMCS 6.11a user manual — Power
Page 246 · click to enlarge
Page 246

Limit 1 Limit 1 value for the Associated quantity (For example: Phase A Amps) Trigger - Relay 1 LED display in Amber color : Limit 1 of the associated value will trigger Relay 1. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 1. Trigger - Relay 2 LED display in Amber color : Limit 1 of the associated value will trigger Relay 2. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 2. Limit 2 Limit 2 value for the Associated quantity (For example: Phase A Amps) Trigger - Relay 1 LED display in Amber color : Limit 2 of the associated value will trigger Relay 1. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 1. Trigger - Relay 2 LED display in Amber color : Limit 2 of the associated value will trigger Relay 2. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 2. Set Above/Below Limit 1 LED display in RED color : Limit 1 of the associated value is Set for Above. LED display in Gray color: Limit 1 of the associated value is Set for Below. Set Above/Below Limit 2 LED display in RED color : Limit 2 of the associated value is Set for Above. LED display in Gray color: Limit 2 of the associated value is Set for Below. Exceeded Limit 1 LED display in GREEN color : The associated quantity is exceeded the Limit 1 value. LED display in Gray color: The associated quantity is NOT exceeded the Limit 1 value. Exceeded Limit 2 LED display in GREEN color : The associated quantity is exceeded the Limit 2 value. LED display in Gray color: The associated quantity is NOT exceeded the Limit 2 value.

Example 1 Example 2 Limit1 is Set for Above Limit 2 is Set for Below Limit 1 is 100 Amps Limit 2 is 80 Amps The associated Quantity is Phase A Instantaneous value is 397 Amps The associated Quantity is Phase A Instantaneous value is 50 Amps Exceeded Limit 1 will show in GREEN color as 397>100 Exceeded Limit 1 will show in GREEN color as 50

Current

  • Phase A
  • Phase B
  • Phase C
  • Neutral

Voltage

  • AN
  • BN
  • CN
  • AB
  • BC
  • CA

Power

  • VA
  • VAR
  • WATT
  • PF
  • Frequency
Page 247 of the GE PMCS 6.11a user manual — Metering
Page 247 · click to enlarge
Page 247

EPM5000P

This device belongs to the Electro Industries family, which is a tightly integrated device in to the PMCS product. The device contains the following tabs:

Metering

GE PMCS 6.11a — Metering diagram (page 247)
Fig. 204 · Metering

The screen explains various parameters related to metering and status.

Power (WATT): Instantaneous, Average, Maximum and Negative Maximum.

Relay 1/Relay 2: Positive Limit 1, Negative Limit 1, Positive Limit 2 and Negative Limit 2. Delay On is displayed too. If the relay is on, it is displayed in green. If the relay is off, it remains in gray.

Energy (kWh): WATT Hour and Negative WATT Hour. Interval is displayed.

Power Full Scale: This value internally depends on the Power Displacement Value. Based on this the value the number of decimals will be displayed. For example If the Power Decimal Placement is set to 1, the value will have only one decimal place. If the Power Decimal Placement is set to 2, the value will have two decimal places, and so on and so forth. The maximum value allowed is 4.

Page 248 of the GE PMCS 6.11a user manual — Setup
Page 248 · click to enlarge
Page 248

Setup

GE PMCS 6.11a — Setup diagram (page 248)
Fig. 205 · Setup

The screen explains various parameters related to configuration and setup.

Configuration: Mega WATT, Leading Zero, Reset Protection, Open Delta, KYZ Output for positive WH, KYZ Output for negative WH.

Protocol: Relay 1, Relay 2, Communications and DC Output.

Status/Value: The user can set the values in the Status and Value fields. Under Positive WATT and Negative WATT, the status is shown as Above/Below for Limit 1 and Limit 2. The user can directly set the status to the device by clicking on the arrow buttons on respective fields to change the value from Above to Below or from Below to Above. The user can enter the set values by clicking on the field that contains the rectangular box that filled with White color on respective fields by entering the desired set values. Once the user enters the set value, by clicking on the Set button of the respective field, will set the value in to the device. Against these settings the wizard will prompt user for the conformation.

Legend: The Legend is applicable for Configuration parameters. Enabled status is displayed in red, Otherwise the status is displayed in gray.

Page 249 of the GE PMCS 6.11a user manual — Metering
Page 249 · click to enlarge
Page 249

EPM9450Q/EPM9650Q

This device belongs to the Electro Industries family, which is a tightly integrated device in to the PMCS product. The device comes with 2 versions – EPM9450Q and EPM9650Q. The EPM9450Q device does not support Waveform feature. The EPM9650Q supports Waveform features.

The device offers the following features:

  • Max/Min integration: Offers Maximum and Minimum values for every measured reading.
  • 8 Built-in Digital High-Speed Status Inputs: The device offers 8 High speed digital inputs.
  • Demand: Measures Fixed window, Sliding window, Predictive and Themal demands.
  • 4 Communication Ports: There are 4 ports – Port 1, Port 2, Port 3 and Port 4.

The device contains the following tabs:

Metering

GE PMCS 6.11a — Metering diagram (page 249)
Fig. 206 · Metering
  • The Metering tab shows following various parameters:
  • Voltage Normal/ High Speed: This tab displays the voltage values of AN, BN, CN, AB, BC, CA and Aux.
  • Current Normal/ High Speed: Displays currents of Phase A, B, C, measured and calculated.
  • THD Normal/ High Speed: Displays THD values of Phase A, B, C for Voltage and Current an d K Factor.
  • Power: Displays Phase A, B, C and 3 Phase Power Values for Real (Watt), Reactive (VAR), Apparent (VA) and
Page 250 of the GE PMCS 6.11a user manual — Min/Max
Page 250 · click to enlarge
Page 250

PF. • Frequency Normal/ High Speed: Displays Frequency in Hz.

Min/Max

GE PMCS 6.11a — Min/Max diagram (page 250)
Fig. 207 · Min/Max

The tab displays Maximum and Minimum values of various parameters. The user can get maximum and minimum values by clicking on respective buttons labeled Show Max and Show Min.

  • Voltage: This tab displays the voltage values of AN, BN, CN, AB, BC, CA and Aux.
  • Current: Displays currents of Phase A, B, C, measured and calculated.
  • THD : Displays THD values of Phase A, B, C for Voltage and Current an d K Factor.
  • Power Factor : Displays PF of Phase A, B, C and 3 Phase of 4 Quadrants namely Q1, Q2, Q3 and Q4.
  • Power: Displays Phase A, B, C and 3 Phase Power Values for Positive Watt, Coincendence VAR for Postive Watt, Negative Watt, Coincedance VAR for Negative Watt, Positive VAR, Negative VAR and VA.
Page 251 of the GE PMCS 6.11a user manual — Demand
Page 251 · click to enlarge
Page 251

Demand

GE PMCS 6.11a — Demand diagram (page 251)
Fig. 208 · Demand

The screen explains various parameters related to demand values:

  • Sliding Window Demand: Displays Average and Maximum Sliding window demand for Positive Watt, Coincendence VAR for Maximum Postive Watt, Negative Watt, Coincedance VAR for Maximum Negative Watt, Positive VAR, Negative VAR and VA. User can click on Sliding Window button to see the Sliding window Demand.
  • Fixed Window Demand: Displays Average and Maximum Sliding window demand for Positive Watt, Coincendence VAR for Maximum Postive Watt, Negative Watt, Coincedance VAR for Maximum Negative Watt, Positive VAR, Negative VAR and VA. User can click on Fixed Window button to see the Fixed window Demand.
  • Predictive Sliding Window Demand: Displays Predictive Sliding Window demand for WATT, VAR and VA.
  • Energy : Displays Energy values for the parameters namely Positve kWh, Negative kWh, Positve kVARh, Negative kVARh and kVAh.
Page 252 of the GE PMCS 6.11a user manual — Thermal Average
Page 252 · click to enlarge
Page 252

Thermal Average

GE PMCS 6.11a — Thermal Average diagram (page 252)
Fig. 209 · Thermal Average
  • The screen explains about various parameters related to thermal average:
  • Current (Amps): Displays the current readings for the phases A, B, C, Mea. (measured) and Cal. (calculated).
  • Voltage (Volts): Displays the Voltage readings for the phases AN, BN, CN, AB, BC, CA and Aux.
  • Power: Displays Phase A, B, C and 3 Phase Power Values for Real (Watt), Reactive (VAR) and Apparent (VA).
Page 253 of the GE PMCS 6.11a user manual — Digital Inputs
Page 253 · click to enlarge
Page 253

Digital Inputs

GE PMCS 6.11a — Digital Inputs diagram (page 253)
Fig. 210 · Digital Inputs

The Digital Inputs tab displays the following parameters of 8 digital inputs. They are Name: Displays the name of the Digital Input. The maximum allowed is 16 Character string. Open/Close Label: Based on the Digital input status, the corresponding label will be displayed. For example if the digital input status is OPEN then label for Open condition is displayed or if the digital input status is CLOSED then label for Closed condition is displayed. Status: The status is displayed Open/Closed. Open status showed in green and Closed status in gray. Counter: Displays the corresponding digital input counter value.

Page 254 of the GE PMCS 6.11a user manual — Setup
Page 254 · click to enlarge
Page 254

Setup

GE PMCS 6.11a — Setup diagram (page 254)
Fig. 211 · Setup

The screen explains various parameters related to setup.

  • Current Set Points: Above and Below Current Setpoints are shown for Phase A, B, C, Measured and Calculated. Voltage Set Points: Above and Below Voltage Setpoints are shown AN, BN, CN, AB, BC, CA and Aux. PT Ratio: Displays Phase and Auxiliary values for Numerator and Denominator. CT Ratio: Displays Phase and Neutral values for Numerator and Denominator. Communication Parameters: Displays Port Addresses and Baudrate for each of the 4 Ports. Reset: This wizard allows user to reset the following Parameters.
  • Energy
  • Log
  • Maximum and
  • Minimum Voltage Phase Sequence: Displays Phase sequence as either C-B-A or A-B-C, based on the register value.
Page 255 of the GE PMCS 6.11a user manual — Metering
Page 255 · click to enlarge
Page 255

EPM7430D/EPM7450D

These devices belong to the Electro Industries family, which is a tightly integrated device in to the PMCS product. These devices communicate through EI Protocol (Electro Industries Protocol). The server used for these devices is GE32EIND. The device comes with 2 versions – EPM7430D and EPM7450D. Both the devices does not support Waveform and events features. So these two buttons will be disabled.

Metering

GE PMCS 6.11a — Metering diagram (page 255)
Fig. 212 · Metering

The Metering tab shows following various parameters:

  • Voltage: This tab displays the voltage values of AN, BN, CN, AB, BC and CA.
  • Current: Displays currents of Phase A, B, C and neutral.
  • THD Current/THD Voltage: Displays THD values of Phase A, B and C for current and voltage.
  • Energy: Displays values for Positive kWh, Negative kWh, Positive kVARh, Negative kVARh and kVAh,.
  • Power: Displays Phase A, B, C and 3 Phase Power Values for Real (kW), Reactive (kVAR), Apparent (kVA) and PF. The wizard also displays the parameters Frequency (Hz), Phase Imbalance (%) and Phase Reversal. If Phase Reversal is ON, the wizard shows CBA, if not then shows ABC.
Page 256 of the GE PMCS 6.11a user manual — Min/Max
Page 256 · click to enlarge
Page 256

Min/Max

GE PMCS 6.11a — Min/Max diagram (page 256)
Fig. 213 · Min/Max

The tab displays Maximum and Minimum values of various parameters. The user can get maximum and minimum values by clicking on respective buttons labeled Show Max. Values and Show Min. Values.

  • Voltage: This tab displays the voltage values of AN, BN, CN, AB, BC and CA.
  • Current: Displays currents of Phase A, B, C and Neutral.
  • THD : Displays THD values of Phase A, B, C for Current and Voltage.
  • Power: Displays Phase A, B, C and 3 Phase Power Values for Positive kW, Negative kW, Positive kVAR, Negative kVAR, kVA, Positive PF and Negative PF.
  • Frequency: Displays frequency in Hz.
Page 257 of the GE PMCS 6.11a user manual — Limit 1 Trigger/Limit 2 Trigger (Relay 1, Relay 2 and Relay 3)
Page 257 · click to enlarge
Page 257

Limits

GE PMCS 6.11a — Limits diagram (page 257)
Fig. 214 · Limits

The screen explains various parameters related to Limits and Triggers:

Limit 1 Trigger/Limit 2 Trigger (Relay 1, Relay 2 and Relay 3)

Relay 1, Relay 2 and Relay 3 are triggered depending upon the Limit 1 and Limit 2 values. The screen also displays whether the Limit 1 and Limit 2 are set above or set below.

Relay 1, Relay 2 and Relay 3 of Limit 1 and Limit 2 are displayed either as Not Triggered or Triggered. If the relay is triggered, the LED fills with amber, if not then gray.

If Limit 1 or Limit 2 are set above, then the status is displayed in red, if not gray, meaning the Limits are set below,

The Limit 1 and Limit 2 Parameters that are shown on the tab are

Current: Phase A, Phase B, Phase C and Neutral.

VoltageAN, BN, CN, AB, BC, CA
PowerVA, VAR, WATT, PF and Frequency

Brief explanation of each of the columns is described below

Column Description Limit 1 Limit 1 value for the Associated quantity (For example: Phase A Amps) Trigger - Relay 1 LED display in Amber color : Limit 1 of the associated value will trigger Relay 1. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 1. Trigger - Relay 2 LED display in Amber color : Limit 1 of the associated value will trigger Relay 2. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 2.

Page 258 of the GE PMCS 6.11a user manual — Limits
Page 258 · click to enlarge
Page 258

Trigger - Relay 3 LED display in Amber color : Limit 1 of the associated value will trigger Relay 3. LED display in Gray color: Limit 1 of the associated value will not trigger Relay 3. Limit 2 Limit 2 value for the Associated quantity (For example: Phase A Amps) Trigger - Relay 1 LED display in Amber color : Limit 2 of the associated value will trigger Relay 1. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 1. Trigger - Relay 2 LED display in Amber color : Limit 2 of the associated value will trigger Relay 2. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 2. Trigger - Relay 3 LED display in Amber color : Limit 2 of the associated value will trigger Relay 3. LED display in Gray color: Limit 2 of the associated value will not trigger Relay 3. Set Above/Below Limit 1 LED display in RED color : Limit 1 of the associated value is Set for Above. LED display in Gray color: Limit 1 of the associated value is Set for Below. Set Above/Below Limit 2 LED display in RED color : Limit 2 of the associated value is Set for Above. LED display in Gray color: Limit 2 of the associated value is Set for Below.

Page 259 of the GE PMCS 6.11a user manual — Setup
Page 259 · click to enlarge
Page 259

Setup

GE PMCS 6.11a — Setup diagram (page 259)
Fig. 215 · Setup

The screen shows the following parameters in relation with Relay 1, Relay 2 and Relay 3 such as:

Configuration: The Parameters under configuration are Kilo Volt Inputs, Kilo Amp Input, Mega Watt Input, Phase Reverse Limits. If any of the above parameters are configured the LED shows Green otherwise LED shows Gray in color. Meter Setup: If this parameter is set then text displayed as Open Delta, if not then shows Non Open Delta. Limits Set By: If this parameter is set then text displayed as Average, if not then shows Instantaneous. Relay 1 / Relay 2/ Relay 3: This section shows the parameters Phase Imbalance, Delay On and Delay Off of Realy 1, Relay 2 and Relay 3. The Legend applicable Phase Imbalance is if any of the above parameters are Enabled the LED shows RED otherwise LED shows Gray in color. Full Scale Values: Displays Full Scale Voltage values for phases AN, B and CN; and Full Scale current values for phases A, B and C. Also shows Decimal Placement values of Volts, Amps and Power.

Reset of Min and Max: Resets Minimum and Maximum values. For example: To reset Minimum values, when the button is clicked, a dialog box will appear asking “Reset minimum values?”. The dialog box contains Ok and Cancel buttons. If the Ok button is clicked, all the minimum values of parameters are reset. If the Cancel button is clicked, no Reset will occur. Reset of WATT Hour, VAR Hour and VA Hour: In resetting the above parameters 2 dialog boxes will prompt user to implement the functionality.

For example: Dialog box 1: To reset Watt Hour, when the button is clicked, a dialog box will appear asking “Do you want to reset Watt Hour?”. The dialog box contains Ok and Cancel buttons. If the Ok button is clicked, then another dialog box prompts the user. If Cancel button is clicked the Dialog box 2 will not appear and no Reset will occur. Dialog box 2: Asking “Confirm the reset within 10 seconds”. If the Ok button is clicked the parameter is reset. If Cancel button is clicked no Reset will occur.

Page 260 of the GE PMCS 6.11a user manual — PLEPM – Wrong Metering tab displayed
Page 260 · click to enlarge
Page 260

Troubleshooting

Assertion Error

Q: While switching between InTouch's Runtime and Development modes, the program crashed with an Assertion Error.

A: This is a problem with InTouch Wonderware, not the GE PMCS Wizards. It occurs rarely during the development phase, and is not seen once a stable application has been developed and put into use. Reboot the computer and restart the application.

EPM 3710/EPM 3720 – no data or incorrect data displayed

Q: The values on the EPM 3710/3720 wizards come up showing zeros or incorrect data.

A: The EPM 3710/3720 wizards require you to click the Refresh button on the wizard before the display is updated. Also, the first time the wizard is displayed, it may take a few moments for the DDE conversation to be established and data to be displayed.

EPM 3720 – KVAH import values incorrect

Q: On the EPM 3720 Tabular data screen, the KVAH import value does not equal the value of KVAH total or KVAH net when KVAH export equals zero.

A: Some rapidly changing values and/or values requiring extensive calculations cannot be updated on the wizards quickly enough to reflect the data displayed on the device in real time. Be patient while the software catches up with the device.

Long update when changing setpoints

Q: I attempted to change a device setpoint (such as changing the VT connection type from WYE to DELTA). It took a long time to update the Wizards setpoint tab to reflect the changes.

A: When changing setpoints, which are polled very slowly, the display may take a long time (a minute or more) to update. This means the metering data will be postponed while the display updates. Setpoint changes are a relatively rare change to make - please be patient during the delay.

PLEPM – Wrong Metering tab displayed

Page 261 of the GE PMCS 6.11a user manual — InTouch applications – Windows not displayed properly
Page 261 · click to enlarge
Page 261

Q: When I double-click the display on the PLEPM's Large Faceplate wizard to go to the Tabular data screen, the DELTA metering tab is displayed, even though the PLEPM is configured as WYE.

A: Click another tab and then click back to the Metering tab. The correct configuration will now be displayed.

InTouch applications – Windows not displayed properly

Q: When an InTouch application containing PMCS Wizards has its resolution changed, the fonts in the wizard are not sized correctly. For instance, if I develop an application in 600 x 480 resolution and then convert it to 800 x 600 resolution, the screens look terrible, things extend off the screen, text formatting is changed, etc.

A: First, make sure that the TrueType fonts option is turned on in Windows 2000 SP2. If this option is off, it can cause font display problems even if windows have not been resized. Next, any time you change the resolution of an InTouch application containing PMCS Wizards, you'll need to delete the wizards from any converted Windows, and then add the wizards back in. When you add the wizard back in, it will display correctly.

Page 262 of the GE PMCS 6.11a user manual — PLEPM – Wrong Metering tab displayed
Page 262 · click to enlarge
Page 262
Page 262 of the GE PMCS 6.11a user manual — PLEPM – Wrong Metering tab displayed
Page 263 of the GE PMCS 6.11a user manual — Appendix A: EPM 3720 Sliding Window Demand Keys
Page 263 · click to enlarge
Page 263

Appendix A: EPM 3720 Sliding Window Demand Keys

Downloading Sliding Demand Window Keys to the EPM 3720

The EPM 3720 supports up to 10 sliding demand measurements that are user- programmable via the Tabular Data screen wizard. The Sliding Demand tab offers a set of adjustable fields, into which a user can enter a key (a unique string of values) which, when downloaded to the EPM 3720, will trigger a measurement.

For explanations of what the EPM 3720's various parameters mean, refer to the EPM 3720 Users Guide, in the section titled Sliding Window Demand.

To set the EPM 3720's sliding demand keys, follow the procedure below:

Locate the key code for the parameter you wish to measure in the table below.

1. Open the EPM 3720 Tabular Data screen wizard and select the Sliding Demand tab.
2. Enter the appropriate sliding demand window key by clicking the onscreen thumbwheels up or down until the key code from the table below is displayed.
3. Press the Download button to send the key to the device.
4. Allow several seconds for transmission time, then press the Refresh button to verify that the device has accepted the setup parameter. The values displayed should be those downloaded. When it receives the downloaded key, the meter will perform a sliding demand measurement for the parameter selected by the key.
Page 264 of the GE PMCS 6.11a user manual — 4 3 28 VAUX STD TD SD PD
Page 264 · click to enlarge
Page 264

#1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings

Class Subclass

Instance Measurement Supported Modes

4 3 00 Volts LN Average HS STD TD SD PD

4 3 01 Volts LN Phase A HS STD TD SD PD

4 3 02 Volts LN Phase B HS STD TD SD PD

4 3 03 Volts LN Phase C HS STD TD SD PD

4 3 04 Volts LL Average HS STD TD SD PD

4 3 05 Volts LL Phase AB HS STD TD SD PD

4 3 06 Volts LL Phase BC HS STD TD SD PD

4 3 07 Volts LL Phase CA HS STD TD SD PD

4 3 08 Amps Average HS STD TD SD PD

4 3 09 Amps Phase A HS STD TD SD PD

4 3 0A Amps Phase B HS STD TD SD PD

4 3 0B Amps Phase C HS STD TD SD PD

4 3 0C Amps Neutral HS STD TD SD PD

4 3 0D Reserved

4 3 0E Volts Imbalance (0-100) HS STD TD SD PD

4 3 0F Amps Imbalance (0-100) STD TD SD PD

4 3 10 kW Total HS STD TD SD PD HRS

4 3 11 kW Phase A HS STD TD SD PD

4 3 12 kW Phase B HS STD TD SD PD

4 3 13 kW Phase C HS STD TD SD PD

4 3 14 kVAR Total STD TD SD PD HRS

4 3 15 kVAR Phase A STD TD SD PD

4 3 16 kVAR Phase B STD TD SD PD

4 3 17 kVAR Phase C STD TD SD PD

4 3 18 kVA Total HS STD TD SD PD HRS

4 3 19 kVA Phase A HS STD TD SD PD

4 3 1A kVA Phase B HS STD TD SD PD

4 3 1B kVA Phase C HS STD TD SD PD

4 3 1C PF Total STD TD SD PD

4 3 1D PF Phase A STD TD SD PD

4 3 1E PF Phase B STD TD SD PD

4 3 1F PF Phase C STD TD SD PD

4 3 20 Frequency HS STD TD SD PD

4 3 21-23 Reserved

4 3 24 Phase Reversal (0 or 1) HS STD

4 3 25-27 Reserved

4 3 28 VAUX STD TD SD PD

Page 265 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings
Page 265 · click to enlarge
Page 265

#1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings

Class Subclass

Instance Measurement Supported Modes

4 3 29-2F Reserved

4 3 30 I2T Avg. (0 = Off, 1= On) HS

4 3 31 I2T Phase A (0=Off, 1=On) HS

4 3 32 I2T Phase B (0=Off, 1=On) HS

4 3 33 I2T Phase C (0=Off, 1=On) HS

4 3 34-67 Reserved

4 3 68 V1 HD - K-Factor STD TD SD PD

4 3 69 V2 HD - K-Factor STD TD SD PD

4 3 6A V3 HD - K-Factor STD TD SD PD

4 3 6B VAUX HD - K-Factor STD TD SD PD

4 3 6C I1 HD - K-Factor STD TD SD PD

4 3 6D I2 HD - K-Factor STD TD SD PD

4 3 6E I3 HD - K-Factor STD TD SD PD

4 3 6F I4 HD - K-Factor STD TD SD PD

4 3 70 V1 HD - Total Odd STD TD SD PD

4 3 71 V2 HD - Total Odd STD TD SD PD

4 3 72 V3 HD - Total Odd STD TD SD PD

4 3 73 VAUX HD - Total Odd STD TD SD PD

4 3 74 I1 HD - Total Odd STD TD SD PD

4 3 75 I2 HD - Total Odd STD TD SD PD

4 3 76 I3 HD - Total Odd STD TD SD PD

4 3 77 I4 HD - Total Odd STD TD SD PD

4 3 78 V1 HD - Total Even STD TD SD PD

4 3 79 V2 HD - Total Even STD TD SD PD

4 3 7A V3 HD - Total Even STD TD SD PD

4 3 7B VAUX HD - Total Even STD TD SD PD

4 3 7C I1 HD - Total Even STD TD SD PD

4 3 7D I2 HD - Total Even STD TD SD PD

4 3 7E I3 HD - Total Even STD TD SD PD

4 3 7F I4 HD - Total Even STD TD SD PD

4 3 80 V1 HD - Total STD TD SD PD

4 3 81 V2 HD - Total STD TD SD PD

4 3 82 V3 HD - Total STD TD SD PD

4 3 83 VAUX HD - Total STD TD SD PD

4 3 84 I1 HD - Total STD TD SD PD

4 3 85 I2 HD - Total STD TD SD PD

4 3 86 I3 HD - Total STD TD SD PD

4 3 87 I4 HD - Total STD TD SD PD

Page 266 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings
Page 266 · click to enlarge
Page 266

#1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings

Class Subclass

Instance Measurement Supported Modes

4 3 88 V1 HD - Harmonic #1 STD TD SD PD

4 3 89 V2 HD - Harmonic #1 STD TD SD PD

4 3 8A V3 HD - Harmonic #1 STD TD SD PD

4 3 8B VAUX HD - Harmonic #1 STD TD SD PD

4 3 8C I1 HD - Harmonic #1 STD TD SD PD

4 3 8D I2 HD - Harmonic #1 STD TD SD PD

4 3 8E I3 HD - Harmonic #1 STD TD SD PD

4 3 8F I4 HD - Harmonic #1 STD TD SD PD

4 3 90 V1 HD - Harmonic #2 STD TD SD PD

4 3 91 V2 HD - Harmonic #2 STD TD SD PD

4 3 92 V3 HD - Harmonic #2 STD TD SD PD

4 3 93 VAUX HD - Harmonic #2 STD TD SD PD

4 3 94 I1 HD - Harmonic #2 STD TD SD PD

4 3 95 I2 HD - Harmonic #2 STD TD SD PD

4 3 96 I3 HD - Harmonic #2 STD TD SD PD

4 3 97 I4 HD - Harmonic #2 STD TD SD PD

4 3 98 V1 HD - Harmonic #3 STD TD SD PD

4 3 99 V2 HD - Harmonic #3 STD TD SD PD

4 3 9A V3 HD - Harmonic #3 STD TD SD PD

4 3 9B VAUX HD - Harmonic #3 STD TD SD PD

4 3 9C I1 HD - Harmonic #3 STD TD SD PD

4 3 9D I2 HD - Harmonic #3 STD TD SD PD

4 3 9E I3 HD - Harmonic #3 STD TD SD PD

4 3 9F I4 HD - Harmonic #3 STD TD SD PD

4 3 A0 V1 HD - Harmonic #4 STD TD SD PD

4 3 A1 V2 HD - Harmonic #4 STD TD SD PD

4 3 A2 V3 HD - Harmonic #4 STD TD SD PD

4 3 A3 VAUX HD - Harmonic #4 STD TD SD PD

4 3 A4 I1 HD - Harmonic #4 STD TD SD PD

4 3 A5 I2 HD - Harmonic #4 STD TD SD PD

4 3 A6 I3 HD - Harmonic #4 STD TD SD PD

4 3 A7 I4 HD - Harmonic #4 STD TD SD PD

4 3 A8 V1 HD - Harmonic #5 STD TD SD PD

4 3 A9 V2 HD - Harmonic #5 STD TD SD PD

4 3 AA V3 HD - Harmonic #5 STD TD SD PD

4 3 AB VAUX HD - Harmonic #5 STD TD SD PD

4 3 AC I1 HD - Harmonic #5 STD TD SD PD

4 3 AD I2 HD - Harmonic #5 STD TD SD PD

Page 267 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings
Page 267 · click to enlarge
Page 267

#1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings

Class Subclass

Instance Measurement Supported Modes

4 3 AE I3 HD - Harmonic #5 STD TD SD PD

4 3 AF I4 HD - Harmonic #5 STD TD SD PD

4 3 B0 V1 HD - Harmonic #6 STD TD SD PD

4 3 B1 V2 HD - Harmonic #6 STD TD SD PD

4 3 B2 V3 HD - Harmonic #6 STD TD SD PD

4 3 B3 VAUX HD - Harmonic #6 STD TD SD PD

4 3 B4 I1 HD - Harmonic #6 STD TD SD PD

4 3 B5 I2 HD - Harmonic #6 STD TD SD PD

4 3 B6 I3 HD - Harmonic #6 STD TD SD PD

4 3 B7 I4 HD - Harmonic #6 STD TD SD PD

4 3 B8 V1 HD - Harmonic #7 STD TD SD PD

4 3 B9 V2 HD - Harmonic #7 STD TD SD PD

4 3 BA V3 HD - Harmonic #7 STD TD SD PD

4 3 BB VAUX HD - Harmonic #7 STD TD SD PD

4 3 BC I1 HD - Harmonic #7 STD TD SD PD

4 3 BD I2 HD - Harmonic #7 STD TD SD PD

4 3 BE I3 HD - Harmonic #7 STD TD SD PD

4 3 BF I4 HD - Harmonic #7 STD TD SD PD

4 3 C0 V1 HD - Harmonic #8 STD TD SD PD

4 3 C1 V2 HD - Harmonic #8 STD TD SD PD

4 3 C2 V3 HD - Harmonic #8 STD TD SD PD

4 3 C3 VAUX HD - Harmonic #8 STD TD SD PD

4 3 C4 I1 HD - Harmonic #8 STD TD SD PD

4 3 C5 I2 HD - Harmonic #8 STD TD SD PD

4 3 C6 I3 HD - Harmonic #8 STD TD SD PD

4 3 C7 I4 HD - Harmonic #8 STD TD SD PD

4 3 C8 V1 HD - Harmonic #9 STD TD SD PD

4 3 C9 V2 HD - Harmonic #9 STD TD SD PD

4 3 CA V3 HD - Harmonic #9 STD TD SD PD

4 3 CB VAUX HD - Harmonic #9 STD TD SD PD

4 3 CC I1 HD - Harmonic #9 STD TD SD PD

4 3 CD I2 HD - Harmonic #9 STD TD SD PD

4 3 CE I3 HD - Harmonic #9 STD TD SD PD

4 3 CF I4 HD - Harmonic #9 STD TD SD PD

4 3 D0 V1 HD - Harmonic #10 STD TD SD PD

4 3 D1 V2 HD - Harmonic #10 STD TD SD PD

4 3 D2 V3 HD - Harmonic #10 STD TD SD PD

4 3 D3 VAUX HD - Harmonic #10 STD TD SD PD

Page 268 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings
Page 268 · click to enlarge
Page 268

#1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings

Class Subclass

Instance Measurement Supported Modes

4 3 D4 I1 HD - Harmonic #10 STD TD SD PD

4 3 D5 I2 HD - Harmonic #10 STD TD SD PD

4 3 D6 I3 HD - Harmonic #10 STD TD SD PD

4 3 D7 I4 HD - Harmonic #10 STD TD SD PD

4 3 D8 V1 HD - Harmonic #11 STD TD SD PD

4 3 D9 V2 HD - Harmonic #11 STD TD SD PD

4 3 DA V3 HD - Harmonic #11 STD TD SD PD

4 3 DB VAUX HD - Harmonic #11 STD TD SD PD

4 3 DC I1 HD - Harmonic #11 STD TD SD PD

4 3 DD I2 HD - Harmonic #11 STD TD SD PD

4 3 DE I3 HD - Harmonic #11 STD TD SD PD

4 3 DF I4 HD - Harmonic #11 STD TD SD PD

4 3 E0 V1 HD - Harmonic #12 STD TD SD PD

4 3 E1 V2 HD - Harmonic #12 STD TD SD PD

4 3 E2 V3 HD - Harmonic #12 STD TD SD PD

4 3 E3 VAUX HD - Harmonic #12 STD TD SD PD

4 3 E4 I1 HD - Harmonic #12 STD TD SD PD

4 3 E5 I2 HD - Harmonic #12 STD TD SD PD

4 3 E6 I3 HD - Harmonic #12 STD TD SD PD

4 3 E7 I4 HD - Harmonic #12 STD TD SD PD

4 3 E8 V1 HD - Harmonic #13 STD TD SD PD

4 3 E9 V2 HD - Harmonic #13 STD TD SD PD

4 3 EA V3 HD - Harmonic #13 STD TD SD PD

4 3 EB VAUX HD - Harmonic #13 STD TD SD PD

4 3 EC I1 HD - Harmonic #13 STD TD SD PD

4 3 ED I2 HD - Harmonic #13 STD TD SD PD

4 3 EE I3 HD - Harmonic #13 STD TD SD PD

4 3 EF I4 HD - Harmonic #13 STD TD SD PD

4 3 F0 V1 HD - Harmonic #14 STD TD SD PD

4 3 F1 V2 HD - Harmonic #14 STD TD SD PD

4 3 F2 V3 HD - Harmonic #14 STD TD SD PD

4 3 F3 VAUX HD - Harmonic #14 STD TD SD PD

4 3 F4 I1 HD - Harmonic #14 STD TD SD PD

4 3 F5 I2 HD - Harmonic #14 STD TD SD PD

4 3 F6 I3 HD - Harmonic #14 STD TD SD PD

4 3 F7 I4 HD - Harmonic #14 STD TD SD PD

4 3 F8 V1 HD - Harmonic #15 STD TD SD PD

4 3 F9 V2 HD - Harmonic #15 STD TD SD PD

Page 269 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings
Page 269 · click to enlarge
Page 269
GE PMCS 6.11a — Appendix A: EPM 3720 Sliding Window Demand Keys diagram (page 269)
Fig. 216 · Appendix A: EPM 3720 Sliding Window Demand Keys

#1 #2 #3 & #4 Sliding Window Key Thumbwheel Settings

4 3 FA V3 HD - Harmonic #15 STD TD SD PD

4 3 FB VAUX HD - Harmonic #15 STD TD SD PD

4 3 FC I1 HD - Harmonic #15 STD TD SD PD

4 3 FD I2 HD - Harmonic #15 STD TD SD PD

4 3 FE I3 HD - Harmonic #15 STD TD SD PD

Table A-1. EPM 3720 Sliding Window Demand Keys.

Page 270 of the GE PMCS 6.11a user manual — Appendix A: EPM 3720 Sliding Window Demand Keys
Page 270 · click to enlarge
Page 270

(This page left blank intentionally.)

Page 271 of the GE PMCS 6.11a user manual — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720
Page 271 · click to enlarge
Page 271

Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720

Using a setpoint to trigger waveform capture or record on the EPM 3720

When a Setpoint is programmed from the MMI, the EPM3720 has the ability to automatically capture or record waveforms based on the value of a specified parameter. In order to display a Waveform Capture, the meter takes 128 samples from a full cycle of any single selected channel. For a Waveform Record, the meter takes 16 samples per cycle from multiple cycles on all 8 inputs simultaneously. The device will store 36 cycles of 1 event, 18 cycles of 2 events, or 12 cycles of 3 events, depending on the Record Depth programmed by the user. Please follow the instructions below to use a Setpoint to trigger a waveform capture or record on the EPM3720.

For explanations of what the EPM 3720's various parameters mean, refer to the EPM 3720 Users Guide, in the section titled Sliding Window Demand.

1. In the EPM3720 MMI tabular screen, click on the Setpoints tab.
2. Choose an unassigned setpoint number. Either Standard or High Speed may be used, but High Speed is recommended for quicker response. (See Section 6 of the 3720 ACM Installation & Operation Manual for more details on configuring Setpoints.)
3. Based on the parameter that will be set in the Trigger Key, select the Setpoint Type.
4. Set the Trigger Key. The Trigger Key is a code for the parameter that, when its value passes a set limit, triggers an Action. Refer to the table in this section for a list of Trigger Key codes.
5. Enter the High and Low Limits as well as any Time Delays to operate and release.
6. Select the required Action. To record a waveform, choose Waveform Recorder . For Waveform Capture, remember that the waveform of only one input may be automatically captured. Choose Waveform
Page 272 of the GE PMCS 6.11a user manual — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720
Page 272 · click to enlarge
Page 272

Capture Channel X where X represents an integer between 1 and 8. Following are the Channel assignments for Wye and Delta systems.

7. Press the Download key. This will transmit the values entered into the Setpoints tabular screen for the selected setpoint number to the device. After several seconds press the Refresh button and scroll to the selected setpoint to verify that the device has accepted the setpoint entered parameters.

8. For waveform record, open the Waveform Capture program from within the MMI. On the main screen, select the appropriate Topic or device name and click on the Record radio button. Then, under the menu Waveform>Configure>Record Depth, select a depth of either 1 event x 36 cycles, 2 events x 18 cycles, or 3 events x 12 cycles. Press OK. The Trigger, Arm, and Retrieve buttons will become inactive as the depth is downloaded to the meter. For waveform capture proceed directly to step 9.

9. Once the Trigger , Arm , & Retrieve buttons become active, press the Arm button. The Trigger , Arm , & Retrieve buttons will momentarily become inactive. When the buttons become active, the meter is now ready to record/capture a waveform when the setpoint conditions are reached.
10. Once the waveform has been automatically captured or recorded and the event has been logged, choose the appropriate Topic and function; i.e., in the main screen of the Waveform Capture program, press Retrieve .
11. View and save waveforms as desired.
12. To rearm the meter and clear the waveform data out of the device’s memory, press Arm on the main screen of the Waveform Capture program.
Page 273 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 273 · click to enlarge
Page 273
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 273)
Fig. 217 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

1 2 00-07 Analog Inputs (Voltage & Current Inputs)

1 4 00-05 Digital Inputs (Status Inputs) -- Status

1 8 00-05 Digital Inputs (Status Inputs) -- Counter

1 C 00-05 Digital Inputs (Status Inputs) -- Preset/Reset

1 E 00-03 Digital Inputs (Status Inputs) -- Scale

1 F 00-03 Digital Inputs (Status Inputs) -- Rollover

Page 274 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 274 · click to enlarge
Page 274
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 274)
Fig. 218 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

00 Volts LN Average HS STD TD SD PD

01 Volts LN Phase A HS STD TD SD PD

02 Volts LN Phase B HS STD TD SD PD

03 Volts LN Phase C HS STD TD SD PD

04 Volts LL Average HS STD TD SD PD

05 Volts LL Phase AB HS STD TD SD PD

06 Volts LL Phase BC HS STD TD SD PD

07 Volts LL Phase CA HS STD TD SD PD

09 Amps Phase A HS STD TD SD PD

0A Amps Phase B HS STD TD SD PD

0B Amps Phase C HS STD TD SD PD

0E Volts Imbalance (0-100) HS STD TD SD PD

10 kW Total HS STD TD SD PD HRS

11 kW Phase A HS STD TD SD PD

12 kW Phase B HS STD TD SD PD

13 kW Phase C HS STD TD SD PD

Page 275 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 275 · click to enlarge
Page 275
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 275)
Fig. 219 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

18 kVA Total HS STD TD SD PD HRS

19 kVA Phase A HS STD TD SD PD

1A kVA Phase B HS STD TD SD PD

1B kVA Phase C HS STD TD SD PD

30 I2T Avg. (0 = Off, 1= On) HS

68 V1 HD - K-Factor STD TD SD PD

69 V2 HD - K-Factor STD TD SD PD

6A V3 HD - K-Factor STD TD SD PD

6B VAUX HD - K-Factor STD TD SD PD

6C I1 HD - K-Factor STD TD SD PD

6D I2 HD - K-Factor STD TD SD PD

6E I3 HD - K-Factor STD TD SD PD

6F I4 HD - K-Factor STD TD SD PD

70 V1 HD - Total Odd STD TD SD PD

71 V2 HD - Total Odd STD TD SD PD

72 V3 HD - Total Odd STD TD SD PD

73 VAUX HD - Total Odd STD TD SD PD

74 I1 HD - Total Odd STD TD SD PD

75 I2 HD - Total Odd STD TD SD PD

76 I3 HD - Total Odd STD TD SD PD

77 I4 HD - Total Odd STD TD SD PD

78 V1 HD - Total Even STD TD SD PD

79 V2 HD - Total Even STD TD SD PD

7A V3 HD - Total Even STD TD SD PD

Page 276 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 276 · click to enlarge
Page 276
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 276)
Fig. 220 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

7B VAUX HD - Total Even STD TD SD PD

7C I1 HD - Total Even STD TD SD PD

7D I2 HD - Total Even STD TD SD PD

7E I3 HD - Total Even STD TD SD PD

7F I4 HD - Total Even STD TD SD PD

80 V1 HD - Total STD TD SD PD

81 V2 HD - Total STD TD SD PD

82 V3 HD - Total STD TD SD PD

83 VAUX HD - Total STD TD SD PD

84 I1 HD - Total STD TD SD PD

85 I2 HD - Total STD TD SD PD

86 I3 HD - Total STD TD SD PD

87 I4 HD - Total STD TD SD PD

88 V1 HD - Harmonic #1 STD TD SD PD

89 V2 HD - Harmonic #1 STD TD SD PD

8A V3 HD - Harmonic #1 STD TD SD PD

8B VAUX HD - Harmonic #1 STD TD SD PD

8C I1 HD - Harmonic #1 STD TD SD PD

8D I2 HD - Harmonic #1 STD TD SD PD

8E I3 HD - Harmonic #1 STD TD SD PD

8F I4 HD - Harmonic #1 STD TD SD PD

90 V1 HD - Harmonic #2 STD TD SD PD

91 V2 HD - Harmonic #2 STD TD SD PD

92 V3 HD - Harmonic #2 STD TD SD PD

93 VAUX HD - Harmonic #2 STD TD SD PD

94 I1 HD - Harmonic #2 STD TD SD PD

95 I2 HD - Harmonic #2 STD TD SD PD

96 I3 HD - Harmonic #2 STD TD SD PD

97 I4 HD - Harmonic #2 STD TD SD PD

98 V1 HD - Harmonic #3 STD TD SD PD

99 V2 HD - Harmonic #3 STD TD SD PD

9A V3 HD - Harmonic #3 STD TD SD PD

9B VAUX HD - Harmonic #3 STD TD SD PD

9C I1 HD - Harmonic #3 STD TD SD PD

9D I2 HD - Harmonic #3 STD TD SD PD

9E I3 HD - Harmonic #3 STD TD SD PD

9F I4 HD - Harmonic #3 STD TD SD PD

A0 V1 HD - Harmonic #4 STD TD SD PD

A1 V2 HD - Harmonic #4 STD TD SD PD

Page 277 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 277 · click to enlarge
Page 277
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 277)
Fig. 221 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

A2 V3 HD - Harmonic #4 STD TD SD PD

A3 VAUX HD - Harmonic #4 STD TD SD PD

A4 I1 HD - Harmonic #4 STD TD SD PD

A5 I2 HD - Harmonic #4 STD TD SD PD

A6 I3 HD - Harmonic #4 STD TD SD PD

A7 I4 HD - Harmonic #4 STD TD SD PD

A8 V1 HD - Harmonic #5 STD TD SD PD

A9 V2 HD - Harmonic #5 STD TD SD PD

AA V3 HD - Harmonic #5 STD TD SD PD

AB VAUX HD - Harmonic #5 STD TD SD PD

AC I1 HD - Harmonic #5 STD TD SD PD

AD I2 HD - Harmonic #5 STD TD SD PD

AE I3 HD - Harmonic #5 STD TD SD PD

AF I4 HD - Harmonic #5 STD TD SD PD

B0 V1 HD - Harmonic #6 STD TD SD PD

B1 V2 HD - Harmonic #6 STD TD SD PD

B2 V3 HD - Harmonic #6 STD TD SD PD

B3 VAUX HD - Harmonic #6 STD TD SD PD

B4 I1 HD - Harmonic #6 STD TD SD PD

B5 I2 HD - Harmonic #6 STD TD SD PD

B6 I3 HD - Harmonic #6 STD TD SD PD

B7 I4 HD - Harmonic #6 STD TD SD PD

B8 V1 HD - Harmonic #7 STD TD SD PD

B9 V2 HD - Harmonic #7 STD TD SD PD

BA V3 HD - Harmonic #7 STD TD SD PD

BB VAUX HD - Harmonic #7 STD TD SD PD

BC I1 HD - Harmonic #7 STD TD SD PD

BD I2 HD - Harmonic #7 STD TD SD PD

BE I3 HD - Harmonic #7 STD TD SD PD

BF I4 HD - Harmonic #7 STD TD SD PD

C0 V1 HD - Harmonic #8 STD TD SD PD

C1 V2 HD - Harmonic #8 STD TD SD PD

C2 V3 HD - Harmonic #8 STD TD SD PD

C3 VAUX HD - Harmonic #8 STD TD SD PD

C4 I1 HD - Harmonic #8 STD TD SD PD

C5 I2 HD - Harmonic #8 STD TD SD PD

C6 I3 HD - Harmonic #8 STD TD SD PD

C7 I4 HD - Harmonic #8 STD TD SD PD

C8 V1 HD - Harmonic #9 STD TD SD PD

Page 278 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 278 · click to enlarge
Page 278
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 278)
Fig. 222 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

C9 V2 HD - Harmonic #9 STD TD SD PD

CA V3 HD - Harmonic #9 STD TD SD PD

CB VAUX HD - Harmonic #9 STD TD SD PD

CC I1 HD - Harmonic #9 STD TD SD PD

CD I2 HD - Harmonic #9 STD TD SD PD

CE I3 HD - Harmonic #9 STD TD SD PD

CF I4 HD - Harmonic #9 STD TD SD PD

D0 V1 HD - Harmonic #10 STD TD SD PD

D1 V2 HD - Harmonic #10 STD TD SD PD

D2 V3 HD - Harmonic #10 STD TD SD PD

D3 VAUX HD - Harmonic #10 STD TD SD PD

D4 I1 HD - Harmonic #10 STD TD SD PD

D5 I2 HD - Harmonic #10 STD TD SD PD

D6 I3 HD - Harmonic #10 STD TD SD PD

D7 I4 HD - Harmonic #10 STD TD SD PD

D8 V1 HD - Harmonic #11 STD TD SD PD

D9 V2 HD - Harmonic #11 STD TD SD PD

DA V3 HD - Harmonic #11 STD TD SD PD

DB VAUX HD - Harmonic #11 STD TD SD PD

DC I1 HD - Harmonic #11 STD TD SD PD

DD I2 HD - Harmonic #11 STD TD SD PD

DE I3 HD - Harmonic #11 STD TD SD PD

DF I4 HD - Harmonic #11 STD TD SD PD

E0 V1 HD - Harmonic #12 STD TD SD PD

E1 V2 HD - Harmonic #12 STD TD SD PD

E2 V3 HD - Harmonic #12 STD TD SD PD

E3 VAUX HD - Harmonic #12 STD TD SD PD

E4 I1 HD - Harmonic #12 STD TD SD PD

E5 I2 HD - Harmonic #12 STD TD SD PD

E6 I3 HD - Harmonic #12 STD TD SD PD

E7 I4 HD - Harmonic #12 STD TD SD PD

E8 V1 HD - Harmonic #13 STD TD SD PD

E9 V2 HD - Harmonic #13 STD TD SD PD

EA V3 HD - Harmonic #13 STD TD SD PD

EB VAUX HD - Harmonic #13 STD TD SD PD

EC I1 HD - Harmonic #13 STD TD SD PD

ED I2 HD - Harmonic #13 STD TD SD PD

EE I3 HD - Harmonic #13 STD TD SD PD

EF I4 HD - Harmonic #13 STD TD SD PD

Page 279 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 279 · click to enlarge
Page 279
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 279)
Fig. 223 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

F0 V1 HD - Harmonic #14 STD TD SD PD

F1 V2 HD - Harmonic #14 STD TD SD PD

F2 V3 HD - Harmonic #14 STD TD SD PD

F3 VAUX HD - Harmonic #14 STD TD SD PD

F4 I1 HD - Harmonic #14 STD TD SD PD

F5 I2 HD - Harmonic #14 STD TD SD PD

F6 I3 HD - Harmonic #14 STD TD SD PD

F7 I4 HD - Harmonic #14 STD TD SD PD

F8 V1 HD - Harmonic #15 STD TD SD PD

F9 V2 HD - Harmonic #15 STD TD SD PD

FA V3 HD - Harmonic #15 STD TD SD PD

FB VAUX HD - Harmonic #15 STD TD SD PD

FC I1 HD - Harmonic #15 STD TD SD PD

FD I2 HD - Harmonic #15 STD TD SD PD

FE I3 HD - Harmonic #15 STD TD SD PD

FF I4 HD - Harmonic #15 STD TD SD PD

00 Volts LN Average HS STD TD SD PD

01 Volts LN Phase A HS STD TD SD PD

02 Volts LN Phase B HS STD TD SD PD

03 Volts LN Phase C HS STD TD SD PD

04 Volts LL Average HS STD TD SD PD

05 Volts LL Phase AB HS STD TD SD PD

06 Volts LL Phase BC HS STD TD SD PD

07 Volts LL Phase CA HS STD TD SD PD

09 Amps Phase A HS STD TD SD PD

Page 280 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 280 · click to enlarge
Page 280
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 280)
Fig. 224 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

0A Amps Phase B HS STD TD SD PD

0B Amps Phase C HS STD TD SD PD

0E Volts Imbalance (0-100) HS STD TD SD PD

10 kW Total HS STD TD SD PD HRS

11 kW Phase A HS STD TD SD PD

12 kW Phase B HS STD TD SD PD

13 kW Phase C HS STD TD SD PD

18 kVA Total HS STD TD SD PD HRS

19 kVA Phase A HS STD TD SD PD

1A kVA Phase B HS STD TD SD PD

1B kVA Phase C HS STD TD SD PD

30 I2T Avg. (0 = Off, 1= On) HS

68 V1 HD - K-Factor STD TD SD PD

69 V2 HD - K-Factor STD TD SD PD

6A V3 HD - K-Factor STD TD SD PD

6B VAUX HD - K-Factor STD TD SD PD

6C I1 HD - K-Factor STD TD SD PD

6D I2 HD - K-Factor STD TD SD PD

Page 281 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 281 · click to enlarge
Page 281
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 281)
Fig. 225 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

6E I3 HD - K-Factor STD TD SD PD

6F I4 HD - K-Factor STD TD SD PD

70 V1 HD - Total Odd STD TD SD PD

71 V2 HD - Total Odd STD TD SD PD

72 V3 HD - Total Odd STD TD SD PD

73 VAUX HD - Total Odd STD TD SD PD

74 I1 HD - Total Odd STD TD SD PD

75 I2 HD - Total Odd STD TD SD PD

76 I3 HD - Total Odd STD TD SD PD

77 I4 HD - Total Odd STD TD SD PD

78 V1 HD - Total Even STD TD SD PD

79 V2 HD - Total Even STD TD SD PD

7A V3 HD - Total Even STD TD SD PD

7B VAUX HD - Total Even STD TD SD PD

7C I1 HD - Total Even STD TD SD PD

7D I2 HD - Total Even STD TD SD PD

7E I3 HD - Total Even STD TD SD PD

7F I4 HD - Total Even STD TD SD PD

80 V1 HD - Total STD TD SD PD

81 V2 HD - Total STD TD SD PD

82 V3 HD - Total STD TD SD PD

83 VAUX HD - Total STD TD SD PD

84 I1 HD - Total STD TD SD PD

85 I2 HD - Total STD TD SD PD

86 I3 HD - Total STD TD SD PD

87 I4 HD - Total STD TD SD PD

88 V1 HD - Harmonic #1 STD TD SD PD

89 V2 HD - Harmonic #1 STD TD SD PD

8A V3 HD - Harmonic #1 STD TD SD PD

8B VAUX HD - Harmonic #1 STD TD SD PD

8C I1 HD - Harmonic #1 STD TD SD PD

8D I2 HD - Harmonic #1 STD TD SD PD

8E I3 HD - Harmonic #1 STD TD SD PD

8F I4 HD - Harmonic #1 STD TD SD PD

90 V1 HD - Harmonic #2 STD TD SD PD

91 V2 HD - Harmonic #2 STD TD SD PD

92 V3 HD - Harmonic #2 STD TD SD PD

93 VAUX HD - Harmonic #2 STD TD SD PD

94 I1 HD - Harmonic #2 STD TD SD PD

Page 282 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 282 · click to enlarge
Page 282
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 282)
Fig. 226 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

95 I2 HD - Harmonic #2 STD TD SD PD

96 I3 HD - Harmonic #2 STD TD SD PD

97 I4 HD - Harmonic #2 STD TD SD PD

98 V1 HD - Harmonic #3 STD TD SD PD

99 V2 HD - Harmonic #3 STD TD SD PD

9A V3 HD - Harmonic #3 STD TD SD PD

9B VAUX HD - Harmonic #3 STD TD SD PD

9C I1 HD - Harmonic #3 STD TD SD PD

9D I2 HD - Harmonic #3 STD TD SD PD

9E I3 HD - Harmonic #3 STD TD SD PD

9F I4 HD - Harmonic #3 STD TD SD PD

A0 V1 HD - Harmonic #4 STD TD SD PD

A1 V2 HD - Harmonic #4 STD TD SD PD

A2 V3 HD - Harmonic #4 STD TD SD PD

A3 VAUX HD - Harmonic #4 STD TD SD PD

A4 I1 HD - Harmonic #4 STD TD SD PD

A5 I2 HD - Harmonic #4 STD TD SD PD

A6 I3 HD - Harmonic #4 STD TD SD PD

A7 I4 HD - Harmonic #4 STD TD SD PD

A8 V1 HD - Harmonic #5 STD TD SD PD

A9 V2 HD - Harmonic #5 STD TD SD PD

AA V3 HD - Harmonic #5 STD TD SD PD

AB VAUX HD - Harmonic #5 STD TD SD PD

AC I1 HD - Harmonic #5 STD TD SD PD

AD I2 HD - Harmonic #5 STD TD SD PD

AE I3 HD - Harmonic #5 STD TD SD PD

AF I4 HD - Harmonic #5 STD TD SD PD

B0 V1 HD - Harmonic #6 STD TD SD PD

B1 V2 HD - Harmonic #6 STD TD SD PD

B2 V3 HD - Harmonic #6 STD TD SD PD

B3 VAUX HD - Harmonic #6 STD TD SD PD

B4 I1 HD - Harmonic #6 STD TD SD PD

B5 I2 HD - Harmonic #6 STD TD SD PD

B6 I3 HD - Harmonic #6 STD TD SD PD

B7 I4 HD - Harmonic #6 STD TD SD PD

B8 V1 HD - Harmonic #7 STD TD SD PD

B9 V2 HD - Harmonic #7 STD TD SD PD

BA V3 HD - Harmonic #7 STD TD SD PD

BB VAUX HD - Harmonic #7 STD TD SD PD

Page 283 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 283 · click to enlarge
Page 283
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 283)
Fig. 227 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

BC I1 HD - Harmonic #7 STD TD SD PD

BD I2 HD - Harmonic #7 STD TD SD PD

BE I3 HD - Harmonic #7 STD TD SD PD

BF I4 HD - Harmonic #7 STD TD SD PD

C0 V1 HD - Harmonic #8 STD TD SD PD

C1 V2 HD - Harmonic #8 STD TD SD PD

C2 V3 HD - Harmonic #8 STD TD SD PD

C3 VAUX HD - Harmonic #8 STD TD SD PD

C4 I1 HD - Harmonic #8 STD TD SD PD

C5 I2 HD - Harmonic #8 STD TD SD PD

C6 I3 HD - Harmonic #8 STD TD SD PD

C7 I4 HD - Harmonic #8 STD TD SD PD

C8 V1 HD - Harmonic #9 STD TD SD PD

C9 V2 HD - Harmonic #9 STD TD SD PD

CA V3 HD - Harmonic #9 STD TD SD PD

CB VAUX HD - Harmonic #9 STD TD SD PD

CC I1 HD - Harmonic #9 STD TD SD PD

CD I2 HD - Harmonic #9 STD TD SD PD

CE I3 HD - Harmonic #9 STD TD SD PD

CF I4 HD - Harmonic #9 STD TD SD PD

D0 V1 HD - Harmonic #10 STD TD SD PD

D1 V2 HD - Harmonic #10 STD TD SD PD

D2 V3 HD - Harmonic #10 STD TD SD PD

D3 VAUX HD - Harmonic #10 STD TD SD PD

D4 I1 HD - Harmonic #10 STD TD SD PD

D5 I2 HD - Harmonic #10 STD TD SD PD

D6 I3 HD - Harmonic #10 STD TD SD PD

D7 I4 HD - Harmonic #10 STD TD SD PD

D8 V1 HD - Harmonic #11 STD TD SD PD

D9 V2 HD - Harmonic #11 STD TD SD PD

DA V3 HD - Harmonic #11 STD TD SD PD

DB VAUX HD - Harmonic #11 STD TD SD PD

DC I1 HD - Harmonic #11 STD TD SD PD

DD I2 HD - Harmonic #11 STD TD SD PD

DE I3 HD - Harmonic #11 STD TD SD PD

DF I4 HD - Harmonic #11 STD TD SD PD

E0 V1 HD - Harmonic #12 STD TD SD PD

E1 V2 HD - Harmonic #12 STD TD SD PD

E2 V3 HD - Harmonic #12 STD TD SD PD

Page 284 of the GE PMCS 6.11a user manual — #1 #2 #3 & #4 Trigger Key Thumbwheel Setting
Page 284 · click to enlarge
Page 284
GE PMCS 6.11a — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720 diagram (page 284)
Fig. 228 · Appendix B: Automatic Waveform Capture and Waveform…

#1 #2 #3 & #4 Trigger Key Thumbwheel Setting

E3 VAUX HD - Harmonic #12 STD TD SD PD

E4 I1 HD - Harmonic #12 STD TD SD PD

E5 I2 HD - Harmonic #12 STD TD SD PD

E6 I3 HD - Harmonic #12 STD TD SD PD

E7 I4 HD - Harmonic #12 STD TD SD PD

E8 V1 HD - Harmonic #13 STD TD SD PD

E9 V2 HD - Harmonic #13 STD TD SD PD

EA V3 HD - Harmonic #13 STD TD SD PD

EB VAUX HD - Harmonic #13 STD TD SD PD

EC I1 HD - Harmonic #13 STD TD SD PD

ED I2 HD - Harmonic #13 STD TD SD PD

EE I3 HD - Harmonic #13 STD TD SD PD

EF I4 HD - Harmonic #13 STD TD SD PD

F0 V1 HD - Harmonic #14 STD TD SD PD

F1 V2 HD - Harmonic #14 STD TD SD PD

F2 V3 HD - Harmonic #14 STD TD SD PD

F3 VAUX HD - Harmonic #14 STD TD SD PD

F4 I1 HD - Harmonic #14 STD TD SD PD

F5 I2 HD - Harmonic #14 STD TD SD PD

F6 I3 HD - Harmonic #14 STD TD SD PD

F7 I4 HD - Harmonic #14 STD TD SD PD

F8 V1 HD - Harmonic #15 STD TD SD PD

F9 V2 HD - Harmonic #15 STD TD SD PD

FA V3 HD - Harmonic #15 STD TD SD PD

FB VAUX HD - Harmonic #15 STD TD SD PD

FC I1 HD - Harmonic #15 STD TD SD PD

FD I2 HD - Harmonic #15 STD TD SD PD

FE I3 HD - Harmonic #15 STD TD SD PD

FF I4 HD - Harmonic #15 STD TD SD PD

Table B-1. EPM 3720 Trigger Keys.

Page 285 of the GE PMCS 6.11a user manual — Action Key Setpoint Supported
Page 285 · click to enlarge
Page 285

The action keys specify the instance number for an object to perform an action on. The following action keys are possible:

Action Key Setpoint Supported

Meaning

0. No action

1000-1004 STD HS Clear digital input counter 0-3 (Status input counter 1-4), 4=ALL

1100-1102 STD HS Operate Relay #1 to 3

1C00-1C04 STD HS same as 1000-1004

A400-A407 STD HS Waveform Capture channels #1 to 8

A500 STD HS Waveform Recorder

Action keys marked with STD are supported by Standard Setpoints (1–11), action keys marked with HS are supported by High Speed Setpoints (1–6).

Page 286 of the GE PMCS 6.11a user manual — Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720
Page 286 · click to enlarge
Page 286

(This page left blank intentionally.)

Page 287 of the GE PMCS 6.11a user manual — Memory Discrete Comment Subject to deactivation?
Page 287 · click to enlarge
Page 287

Appendix C: EPM 7700 - Special Considerations

EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizard

This appendix lists the EPM 7700 tags which may be activated or deactivated by the EPM 7700 Tabular Data Screen wizard. This information is of use for developers creating their own wizards to access the EPM 7700’s data. If you wish to use a tag in a custom wizard you are developing, check this table to see if it is subject to deactivation by the Tabular Data Screen wizard. If it is, you may wish to create a duplicate tag with a unique name to access the same register. Otherwise, it is possible that the tag may be deactivated by the Tabular Data Screen wizard, and the data will be unavailable for use by your custom wizard.

Tabular Data Screen Wizard will not work properly with InTouch’s trending features.

Tags which talk to GE77GTWY. All others tags talk to ION_LINK

Memory Discrete Comment Subject to deactivation?

DeviceNm_Min Tag to indicate whether to show min or max on min/max page N

Page 288 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 288 · click to enlarge
Page 288
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 288)
Fig. 229 · Appendix C: EPM 7700 ˚ Special Considerations

DeviceNm_CommFail Comm Fail Indicator for Pegasys DDE Server - ION_LINK N

DeviceNm_24721 External Boolean 3 - Enable Sag Swell Y

DeviceNm_24723 External Boolean 5 - Enable Over SWD KW Y

DeviceNm_24724 External Boolean 6 - Enable Over Current Y

DeviceNm_24725 External Boolean 7 - Enable Over Vunbal Y

Page 289 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 289 · click to enlarge
Page 289
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 289)
Fig. 230 · Appendix C: EPM 7700 ˚ Special Considerations
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 289)
Fig. 231 · Appendix C: EPM 7700 ˚ Special Considerations
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 289)
Fig. 232 · Appendix C: EPM 7700 ˚ Special Considerations
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 289)
Fig. 233 · Appendix C: EPM 7700 ˚ Special Considerations

DeviceNm_23260_Anlg External Numeric 1 - Over Kw Nominal N

DeviceNm_23261_Anlg External Numeric 2 - Over Ia Nominal N

DeviceNm_23262_Anlg External Numeric 3 - Over Ib Nominal N

DeviceNm_23263_Anlg External Numeric 4 - Over Ic Nominal N

DeviceNm_23264_Anlg External Numeric 5 - Over Vunbal Nominal N

Page 290 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 290 · click to enlarge
Page 290
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 290)
Fig. 234 · Appendix C: EPM 7700 ˚ Special Considerations
Page 291 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 291 · click to enlarge
Page 291
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 291)
Fig. 235 · Appendix C: EPM 7700 ˚ Special Considerations
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 291)
Fig. 236 · Appendix C: EPM 7700 ˚ Special Considerations
Page 292 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 292 · click to enlarge
Page 292
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 292)
Fig. 237 · Appendix C: EPM 7700 ˚ Special Considerations
Page 293 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 293 · click to enlarge
Page 293
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 293)
Fig. 238 · Appendix C: EPM 7700 ˚ Special Considerations
Page 294 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 294 · click to enlarge
Page 294
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 294)
Fig. 239 · Appendix C: EPM 7700 ˚ Special Considerations

DeviceNm_23260_GWY External Numeric 1 - Over Kw Nominal N

DeviceNm_23261_GWY External Numeric 2 - Over Ia Nominal N

DeviceNm_23262_GWY External Numeric 3 - Over Ib Nominal N

DeviceNm_23263_GWY External Numeric 4 - Over Ic Nominal N

DeviceNm_23264_GWY External Numeric 5 - Over Vunbal Nominal N

Page 295 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 295 · click to enlarge
Page 295
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 295)
Fig. 240 · Appendix C: EPM 7700 ˚ Special Considerations
Page 296 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 296 · click to enlarge
Page 296
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 296)
Fig. 241 · Appendix C: EPM 7700 ˚ Special Considerations
Page 297 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 297 · click to enlarge
Page 297
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 297)
Fig. 242 · Appendix C: EPM 7700 ˚ Special Considerations
Page 298 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 298 · click to enlarge
Page 298
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 298)
Fig. 243 · Appendix C: EPM 7700 ˚ Special Considerations
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 298)
Fig. 244 · Appendix C: EPM 7700 ˚ Special Considerations
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 298)
Fig. 245 · Appendix C: EPM 7700 ˚ Special Considerations
Page 299 of the GE PMCS 6.11a user manual — Appendix C: EPM 7700 ˚ Special Considerations
Page 299 · click to enlarge
Page 299
GE PMCS 6.11a — Appendix C: EPM 7700 ˚ Special Considerations diagram (page 299)
Fig. 246 · Appendix C: EPM 7700 ˚ Special Considerations
Page 300 of the GE PMCS 6.11a user manual — I/O Message Comment
Page 300 · click to enlarge
Page 300

I/O Message Comment

Show 6 more labels / short text on this page
DeviceNm_31309 Comm2_Baud Y · DeviceNm_31310 Comm3_Baud Y · DeviceNm_31311 Comm1_Protocol Y · DeviceNm_31312 Comm2_Protocol Y · DeviceNm_31313 Comm3_Protocol Y · DeviceNm_31314 Ethernet_Protocol Y
Page 301 of the GE PMCS 6.11a user manual — Table of Contents
Page 301 · Contents
Contents

Contents

Introductionp.9Welcomep.9How should I use this manual?p.10Conventionsp.11About the Interface Toolkitp.11Installationp.11Using and Configuring PMCS Wizardsp.13About the Wizardsp.13Small Faceplate Wizardsp.14Usagep.14Configurationp.14Large Faceplate Wizardsp.16Usagep.16Configurationp.17Special Considerationsp.17EPM 7700p.17Tabular Data Screen Wizardsp.19Usagep.19Configurationp.19EPM 7700p.20369 Motor Management Relayp.21Universal Relayp.23One-Line Wizardsp.24Usagep.24Configurationp.25Meter One-Line Wizardsp.25Transformer, Fuse, Ground, and Motor One-Line Wizardsp.26Horizontal and Vertical Relay One-Line Wizardsp.27Horizontal and Vertical Switch One-Line Wizardsp.28Circuit Breaker One-Line Wizardsp.29Elevation Wizardsp.30Usagep.30Configurationp.30Floor Plan Wizardsp.31Usagep.31Configurationp.31Toolbar Wizardp.32Usagep.32Configurationp.32Annunciator Panel Wizardp.33Usagep.33Annunciator Panel Theory of Operationp.33Configurationp.37Troubleshooting Tips for the Annunciator Panel Wizardp.42Custom Table Wizardp.43Usagep.43Configurationp.43System Statistics Wizardp.48Usagep.48Configurationp.48Lockout/Tagout Wizardp.50Usagep.50Supported Devicesp.51Configurationp.51Example of Lockout/Tagout Wizardp.52Special Scripting Considerations for the EPM 7700p.56Installing the Application Scriptp.57Configuring the Large Faceplate/Custom Table Scriptp.60EPM 7700 Tabular Data Screen Scriptingp.62Configuring the Tabular Data Screen Scriptp.62Creating Floor Plans, Elevation Views, and One-Line Diagramsp.63Introductionp.63Elevation Viewsp.63Floor Plansp.65Electrical One-Line Diagramsp.66Sample Applicationp.69Creating a basic interfacep.69Features of GE Large Faceplate Wizardsp.75About the Large Faceplate Wizardsp.75POWER LEADER EPMp.76Spectra MicroVersaTrip Trip Unitp.79Enhanced MicroVersaTrip-C Trip Unitp.80Enhanced MicroVersaTrip-D Trip Unitp.82POWER LEADER Meterp.84Spectra ECMp.86EPM 3710 Meterp.88EPM 3720 Meterp.90EPM 7700 Meterp.92269 Plus Motor Management Relayp.95565 Feeder Management Relayp.100Features of Tabular Data Screen Wizardsp.107Introductionp.107Features of Tabular Data Screensp.107Power Leader EPMp.109Spectra MicroVersaTripp.110Enhanced MicroVersaTrip-C Trip Unitp.111Enhanced MicroVersaTrip-D Trip Unitp.112POWER LEADER Meterp.113Spectra ECMp.114MDP Digital Overcurrent Relayp.115Monitoring Tabp.115Command Tabp.116Setup Tabp.117PQM (Power Quality Meter)p.118Metering Tabp.119Status Tabp.120Demand Tabp.121IV Range Tabp.122P Range Tabp.123Analysis Tabp.124IO Tabp.125Setpoints Tabp.126Motor Manager II (MMII)p.127EPM 3710 Meterp.128EPM 3720 Meterp.129EPM 7300 Meterp.130Metering Tabp.131Min/Max Tabp.132Setup Tabp.133EPM 7330 Meterp.134Metering Tabp.135Min/Maxp.136Setup Tabp.137EPM 7500/7600 Meterp.138Metering Tabp.138Min/Max Tabp.140Power Quality Tabp.141Demand Tabp.142Inputs Tabp.143Setup 1 Tabp.144Setup 2 Tabp.146EPM 7700 Meterp.148Metering Tabp.148Min/Max Tabp.150Power Quality Tabp.151Demand Tabp.152Inputs Tabp.153Setup 1 Tabp.154Setup 2 Tabp.156Universal Relayp.158Metering Tabp.159Currentp.159Voltagep.159Powerp.159Power Factorp.160Frequencyp.160Power Quality Tabp.160Currentp.160Voltagep.161Protection Control Tabp.161Grouped Protection Settingsp.161Phase TOC and IOC Settingsp.162Power System Configuration Tabp.162Current Transformers (CT)p.163Voltage Transformers (VT)p.163Synchrocheck 1/2 Deltap.163IRIG-B Signal Typep.163Normal Frequencyp.163Phase Rotationp.163Frequency Tracking Referencep.163Hi-Z Functionp.163Transformer Tabp.164Differential Currentp.164Restraint Currentp.164Transformer Winding Referencep.164Elements Tabp.165Digital Counter Tabp.166Virtual Inputs Tabp.167Virtual Inputsp.167Virtual Outputs Tabp.168Virtual Outputsp.168Contact Inputs Tabp.169Contact Inputsp.169Contact Output Tabp.170Contact Outputp.170DCMA Tabp.171DCMA Inputsp.171Source Tabsp.172Demand Tabp.173Demand Valuesp.173Source (x) Energyp.173Source (x) Demand, Peak Demand, Peak Demand Datep.173Line Tabp.174Line Tabp.174Control Functionsp.174Breaker Tabp.175Arcingp.175Breaker Functionsp.175Breaker Statusp.175Auto Reclosep.176Contact Output Current States Tabp.176Contact Output Current Statep.176Remote Temperature Detection Tabp.177RTD Tabp.177Bus Tabp.178239 Motor Protection Relayp.179Metering tabp.179Status Tabp.180Trip Datap.181Setpoints Tabp.182269 Plus Motor Management Relayp.183369 Motor Management Relayp.184Metering Tabp.184Currentp.184Voltagep.184Powerp.185Motor Statusp.185Timer Functions & Learned Valuesp.185Alarms Tabp.186Alarm Statusp.186Trip Datap.186Trip Countersp.186Demand Tabp.187Local RTD Tabp.188Remote RTD Tabp.189Control Tabp.190Setup Tabp.191SR469 Motor Management Relayp.192Metering Tabp.192Status Tabp.193Alarms Tabp.194Trip Tabp.195IO Tabp.196Maintenance Tabp.197Analog Tabp.198RTD HI Tabp.199Setpoints Tabp.199SR489 Generator Management Relayp.200Metering Tabp.200Pickup Tabp.201Alarms Tabp.201Trip Data Tabp.202IO Tabp.203Maintenance Tabp.204Setpoints Tabp.205565 Feeder Management Relayp.206735 Feeder Relayp.208Metering Tabp.208Trip Data Tabp.209Setpoints Tabp.210SR745 Transformer Management Relayp.211Metering Tabp.211Flags Tabp.212IO Tabp.212Demand Tabp.213Harmonic Tabp.214Setpoints Tabp.215Power Tabp.216SR750/760 Feeder Management Relayp.217Metering Tabp.218Status Tabp.219Fault Tabp.219Trip Tabp.220Demand Tabp.221Logic Tabp.222IO Tabp.222Setpoints Tabp.223Fanuc 90/30p.224Fanuc 90/70p.224Fanuc Micro 90p.225MX200p.226Metering Tabp.226Setup Tabp.228GEN PLCp.231Master Tabp.231Generator Tabp.232PSGp.233EPM5000Pp.247Meteringp.247Setupp.248EPM5200Pp.240Metering Tabp.240Setup One Tabp.241EPM5300Pp.235Metering Tabp.235Setup One Tabp.237Setup Two Tabp.238EPM5350Pp.243Metering Tabp.243Setup One Tabp.244Setup Two Tabp.245EPM9450Q/EPM9650Qp.249Meteringp.249Min/Maxp.250Demandp.251Thermal Averagep.252Digital Inputsp.253Setupp.254EPM7430D/EPM7450Dp.255Meteringp.255Min/Maxp.256Limitsp.257Setupp.259Troubleshootingp.260Assertion Errorp.260EPM 3710/EPM 3720 – no data or incorrect data displayedp.260EPM 3720 – KVAH import values incorrectp.260Long update when changing setpointsp.260PLEPM – Wrong Metering tab displayedp.261InTouch applications – Windows not displayed properlyp.261Appendix A: EPM 3720 Sliding Window Demand Keysp.263Downloading Sliding Demand Window Keys to the EPM 3720p.263Appendix B: Automatic Waveform Capture and Waveform Retrieval on EPM3720p.271Using a setpoint to trigger waveform capture or record on the EPM 3720p.271Appendix C: EPM 7700 ˚ Special Considerationsp.287EPM 7700 Tags Subject to Deactivation by Tabular Data Screen Wizardp.287Indexp.301
Page 302 of the GE PMCS 6.11a user manual — W
Page 302 · click to enlarge
Page 302

T

UR, 150

Tabular Data Screen Wizards, 11, 99 Toolbar wizard, 24

W

U

Universal Relay, 150 Universal Relay Devices, 150

294 • Index PMCS Interface Toolkit

waveform capture, 99

Page 303 of the GE PMCS 6.11a user manual — Index
Page 303 · click to enlarge
Page 303

(This page left blank intentionally.)

Page 304 of the GE PMCS 6.11a user manual — GE Industrial Systems
Page 304 · click to enlarge
Page 304

GE Industrial Systems

General Electric Company 41 Woodford Ave., Plainville, CT 06062

GEH-6513 R011 0102 © 2000 - 2002 General Electric Company

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
SP2If this option is off, it can cause font display problems even if windows have not p.261

Ask about the GE PMCS 6.11a

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the GE PMCS 6.11a

Be the first to ask — other owners or our team will answer.

Original document

GE PMCS 6.11a manual PDF

304 pages·2.7 MB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…