LP 33 Series
30 & 40 kVA 208 VAC UL / Series 0 Manufactured by: GE Zenith Controls General Electric Company 2501 Pecan Street Bonham, Texas 75418 T 903 640 7900 T 903 640 7900


Identification No.
COPYRIGHT © 2005 by GE Consumer & Industrial All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Up-dating · Revision Concerns Date

Dear Customer, We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE. We trust that the use of the LP 33 Series Uninterruptible Power Supply system, developed and produced to the highest standards of quality, will give you complete satisfaction. Please carefully read the Installation Guide. It contains all the necessary information about the installation of the UPS. Thank you for choosing GE !
START UP AND COMMISSIONING A GE Global Services Field Engineer must perform start-up and commissioning of the UPS. Please Contact G.E. Global Services at least two weeks prior to schedule start-up and commissioning at 1-800-637-1738, or by E-mail at gedeservices@indsys.ge.com
GE Digital Energy General Electric Company CH – 6595 Riazzino (Locarno)
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Switzerland

Congratulations on your choice of a LP 33 Series Uninterruptible Power Supply (UPS). It will help eliminate load disturbances due to unexpected power problem. This Installation Guide describes how to prepare the installation site, and it provides weight and dimensions and procedures for moving, installing and connecting the UPS. While every care has been taken to ensure the completeness and accuracy of this manual, GE assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
LP 33 Series / 30 & 40 kVA, is a product that needs to be installed by a licensed and knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references. If any problems are encountered with the procedures contained in this manual, please contact your Service Center before you proceed. This document shall not be copied or reproduced without the permission of GE. Some of the information contained in this manual may be changed without notice to reflect technical improvements.
Read the safety instructions contained on the following pages carefully before the installation of the UPS, options and battery system. Pay attention to the rectangular boxes included in the text: They contain important information and warning concerning electrical connections and personnel safety.

When included in the text, this symbol refers to operation needed only for parallel system.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA



With this document, GE gives to the user all the necessary information about the correct use of the UPS. We recommend that this manual be kept next to the UPS for future references. If any problems are encountered with the procedures contained in this manual, please contact the nearest Service Center before you proceed. All UPS installation, maintenance and service work should be performed by qualified service personnel only.
LP 33 Series / 30 & 40 kVA is a FCC Class A-UPS Product. While every care has been taken to ensure the completeness and accuracy of this manual, GE assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

SAVE THESE INSTRUCTIONS This manual contains important instructions for models LP 33 Series / 10 & 20 kVA that should be followed during installation and maintenance of the UPS and battery.
- Move the UPS in an upright position in its original package to the final destination room. - Check for sufficient floor and elevator loading capacity. - Check the integrity of the UPS equipment carefully. If you notice visible damage, do not install or start the UPS. Contact the nearest Service Center immediately. - WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user
serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally
high voltage remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel. The UPS contains its own energy source (battery).
- The field-wiring terminals may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation. The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (55°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time depending on storage temperature).
- The battery-voltage is dangerous for person’s safety. - When replacing the battery, use the same number, voltage (V) and capacity (Ah). - Proper disposal or recycling of the battery is required. Refer to your local codes for disposal requirements. - Never dispose of battery in a fire: They may explode. - Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water. - Avoid charging in a sealed container. - Never short circuit battery. When working with battery, remove watches, rings or other metal objects, and only use insulated tools.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Safety symbols and warnings Safety warnings The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads. The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages. Please pay attention to the meaning of the following warnings and symbols. Throughout this manual the following symbols are defined:
PE (Earth) – GND (Ground) PROTECTIVE GROUNDING TERMINAL: A terminal which must be connected to earth ground prior to making any other connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

The LP 33 Series Uninterruptible Power Supply (UPS) provides the energy supply for critical loads which need a reliable, continuous free from voltage disturbances and frequency fluctuations supply.
In case the mains fails, or it exceeds the permitted tolerances, the energy to supply the load is furnished by the battery with a backup time dependent on its capacity, until the mains recovers.
LP 33 Series is a truly VFI double conversion Uninterruptible Power Supply (UPS), equipped with automatic bypass, where the load is normally supplied by the inverter.
LP 33 Series can be configured, if chosen, for the ECO Mode permitting the maximum energy saving.
The main typical performances of the LP 33 Series system are the following:
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA


Fig. 3.1-1 UPS block diagram The Uninterruptible Power Supply System LP 33 Series / 30 & 40 kVA can be divided into the following main elements: Electronics The UPS is designed with a microprocessor–controlled supervision and diagnostic system. Communication between user and UPS is achieved by the front panel consisting of an LCD screen, displaying the operation modes, the measurements and the events / alarms. Rectifier The rectifier converts the 3-phase mains voltage into a controlled and regulated DC-voltage, in order to supply power to the booster, and to charge the battery through the battery-charger. Inverter The inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and frequency, which is completely independent from the AC-input voltage. Automatic Bypass The automatic bypass consists of a static semiconductor-switch (SSR: Static Switch Relay), used to provide an uninterrupted transfer of the load from inverter to mains when operating in VFI Mode. If chosen the ECO Mode, the SSM transfer the load from mains to inverter in case the utility fails. Back-Feed Protection All LP 33 Series UPS’s are equipped with an automatic system for the protection against voltage back feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1). This protection works automatically by opening contactor K6 (in series with the thyristors of the static switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong manipulations on the maintenance bypass Q2. Manual Bypass The manual bypass consists of a pair of manual switches Q1 and Q2, which allow the isolation of the UPS from the load, while still supplying the load with power directly from the mains. Battery The battery, normally stored by the battery-charger, supplies the DC energy to inverter in the event of mains failure.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

This section describes the different possible operation modes of the UPS explaining the function of the main modules of the UPS. VFI (Voltage Frequency Independent) Mode operation

Under normal conditions the load is permanently powered by the inverter with constant amplitude and frequency. The rectifier, powered by the mains, supplies the inverter and the battery-charger keeps the battery fully charged.
Fig. 3.2-1 Energy flow in VFI Mode operation
The inverter converts the DC voltage in a new AC sine wave voltage with constant amplitude and frequency independently from the input mains power. ECO Mode operation (Intelligent Energy Management) When the ECO Mode is selected, and the mains power is available, the load is normally powered through the automatic bypass. When the mains voltage is detected out of the prescribed tolerances, the load is automatically transferred to the inverter. When the mains recovers, the load returns to the automatic bypass after a variable time defined by the control unit.

Fig. 3.2-2 Energy flow in ECO Mode operation
The ECO Mode can be configured directly by the user for higher efficiency, considering the mains reliability and criticality of the load. The selection between the two operation modes “VFI Mode and ECO Mode”, or switching between operation modes at required time, can be done through the UPS control panel (see Section 6.3.1-5).
In case of parallel system
ECO Mode cannot be enabled for RPA Parallel System.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA


In VFI (Voltage Frequency Independent) operation mode, the load is permanently supplied by the inverter but, in case of trouble on the inverter, or when overload or short-circuit on the output occur, if the mains voltage do not exceed the admitted tolerances, the load is instantly transferred to the mains through the automatic bypass, taking advantage of the higher short circuit power.
Fig. 3.2-3 Energy flow in automatic bypass operation
When the inverter recovers, the load will be re-transferred automatically to the inverter.
In case of parallel system Each unit has its own bypass. All the bypasses in the system work together, their control being managed in the same manner by all units. The units are continuously exchanging information before taking such decision. In case the inverter of one unit fails, its bypass remains operating. It is excluded only if the unit is separated from the common bus by opening its output switch Q1. Mains recovery operation

As soon as the mains recovers, the rectifier starts up automatically supplying the inverter and the battery-charger recharges the battery. In case the inverter has been shut down following a complete discharge of the battery, when the mains recovers the system start up automatically.
Fig. 3.2-4 Energy flow at mains recovery operation
When the energy stored in the battery is sufficient to ensure a minimum time of operation with the actual load, in case of a future mains failure, the load will be retransferred to inverter (if selected VFI Mode).
In case of parallel system When the AC input power recovers, the rectifiers will start up sequentially according to their number in the parallel system in order to avoid an initial inrush current. The inverters will start up automatically, but only when the battery has recharged enough for a minimum runtime with the present load. When enough inverters to supply the load have been restarted, the load will be transferred from the automatic bypass back to the inverter bus-bars.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Automatic bypass operation

The manual bypass circuit consisting of Q1 and Q2 manual switches, permits the transfer of the load directly to the mains without interruption, leaving the UPS galvanically separated from the output load. This type of operation is normally used when the UPS system must be completely turned off for maintenance or reparation.

Fig. 3.2-5 Energy flow in manual bypass operation
In the event of a mains power failure, the rectifier and the battery-charger turn OFF, while the inverter continues to supply the load without interruption using the energy stored in the battery. During the battery discharge, the LCD screen displays the remaining autonomy, based on the battery capacity and the applied load.

Fig. 3.2-6 Energy flow during mains failure operation
In the event of an extended mains failure, before the battery is fully discharged, the alarm “stop operation” warns the user that the UPS will start the shutdown procedures when the indicated time expired (normally 3 minutes).
In case of parallel system With parallel system for power capacity: • With the bypass mains power available as the warning “battery low” occurs on one unit, after timeout (selectable) the load is transferred to mains.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Manual bypass operation · Mains failure operation

The RPA (Redundant Parallel Architecture) allows to extend the unit to a parallel system with 2, 3, or 4 units LP 33 Series connected on the same bus, which ensure the highest reliability rate and increase the power availability. Parallel system for power capacity Two or more units can be paralleled in order to achieve output power superior to the maximum power delivered by a single UPS unit. The maximum total load shared between the n parallel units can achieve the 100% of the installed nominal power system. In the event of one unit fails, the load will be suddenly transferred to the mains by the bypass. Parallel system for redundancy The parallel system can be defined redundant only in case the nominal power rating of n-1 units of n parallel units is sufficient to supply the required load power.
F2 F1 F3 F4
LOAD
Fig. 3.3-1 RPA system diagram
The load in a parallel redundant system, is equally shared by n units connected on the output bars. Should one of the parallel units trip off-line, the remaining (n-1) units will share the load maintaining the applications protected by inverter until the normal situation restores. Load sharing between parallel units The control bus exchanging the data between the microprocessors of the paralleled units provide for a constant proportional load sharing in every load condition. Management and synchronization of the parallel system All the units are identical without master and slaves. One unit is arbitrarily selected as the reference (the first unit connected on power bus) being this unit the first synchronized with the mains voltage, and all the other units synchronize with the first one. In case the reference unit fails or it is excluded from the parallel power bus any other unit will take over the reference role. The AC input power source of all the bypasses must be the same for all the units of the parallel system excluding any phase shift between them. Control bus of the parallel system A high-speed serial bus, guarantees communication, synchronization and load sharing between the UPS modules. Each module controls it’s own function, while the Master (each unit can be Master) controls and commands the status of the system.

OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Usually each UPS Unit runs with its own Battery. In case of parallel units running with a Common Battery (max. 4 UPS - see Fig. 3.4-1), the sharing circuit between the individual UPS is integrated in the communication bus of the system in order to assure an equal sharing of the Rectifiers output currents.

Rectifier Inverter Automatic Bypass Manual Bypass Mains Power Load Bus Bar External Battery Fuse Battery
Fig. 3.4-1 Diagram RPA system with UPS on common battery
Pay attention to the following recommendations:
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA


Stamp of your Dealer or local responsible of the Technical Assistance
For any request of technical support please contact the supplier who provided the system.

The requested data permitting to identify your UPS are marked on the identification label fixed on the front of the cabinet, behind the lower front door. For fast and efficient Technical Support solutions, please mention the data marked on the identification label.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

NOTE !
This product has been designed to respect the environment, using materials and components respecting eco-design rules.
It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen Carbon Fluor Clorid).

GE, in compliance with environment protection recommends to the User that the UPS equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.
Leads contained in the batteries is a dangerous substance for the environment, therefore it must be correctly recycled by specialised companies!
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA



Fig. 4.1-3 Control panel

Fig. 4.1-4 Q1 & Q2 switches
Fig. 4.1-1 General view

CI Customer Interface Board (optional)
Q1 UPS output switch
Q2 Manual bypass switch
SNMP Advanced SNMP Card (optional)
RS232 Serial port RS232
Fig. 4.1-2 General view with open door
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
BC Battery cabinet · F5-6-7 Battery fuses · RC Relay card


Fig. 5.1-1 Control panel LCD screen Shows the UPS system data, events messages and UPS setting. The data is displayed on 4 rows, 20 characters each, allowing the operator to select between 7 languages: English, German, French, Spanish, Italian, Finnish or Polish. If there is no keypad activity during 1 minute the LCD screen will return to default screen. Metering Shows electric parameters, operating statistics and some information screens (see Section 6.1). Alarm Shows in chronological order, all the events occurred (alarms, messages, commands, handling, etc.) and resets general alarm / buzzer (see Section 6.2). Menu Allows the user to adapt certain features of the UPS to his needs, to reset the command total off, to test the LEDs panel, and to command the inverter ON/OFF (see Section 6.3). + Scroll to following screen. Entering in PARAMETER MENU/USER, allows to select the horizontal editable position. - Entering in Alarm and Metering, scroll to previous screen. Entering in menu allows to select the row including the needed command. Enter Confirms the selected command. Entering in PARAMETER MENU/USER allows the user to change the parameters. LED Alarm (red)
When blinking, it means the UPS is in alert condition with the buzzer sounding. The yellow LED will remain lit after pressing the key Alarm. It remains lit also when the output switch Q1 is open or battery disconnected. LED Operation (green)
When lit, it means the UPS is correctly operating and the load is powered by the inverter. When blinking, it means SERVICE REQUIRED
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA


total off Press simultaneously the keys “Alarm” and “-” on the panel. This will cause the opening of all contactors (K4, K6 and K7), shutdown of booster, Inverter, battery- charger and SSM.
In a parallel system pressing total off on one unit all the units will shut down.
Using the command total off, the load will be immediately powered down.
To restart the unit, command total off must be restored entering the screen


OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Shows the UPS system data, events messages and UPS setting. The data is displayed on 4 rows, 20 characters each, allowing the operator to select between 7 languages: English, German, French, Spanish, Italian, Finnish and Polish. If there is no keypad activity during 1 minute the LCD screen will return to default screen. 6.1 METERING SCREENS (Metering)
This menu allows, when the keypad Metering is pressed, to show on the LCD panel a series of screens containing metering information about AC and DC parameters.
LP 33 40kVA P1
Udcp=215V Udcn=215V Ubp=164V Ubn=164V O Charge Level = 100% Autonomy = 15min
Beside the indication of the Battery voltage on the display, a letter shows, according to the table below, the operational status of SBM:
Sigle Status of charger Charter voltage Description
O OFF 0 VDC Battery open circuit voltage
T ON Boost (176 VDC) Boost charge with new Battery
F ON Floating (164 VDC) Battery charged
L ON Floating (164 VDC) Normal charge
B ON Boost (176 VDC) Boost charge
E ON Boost (179 VDC) Battery equalization
Access to the Parameters for setting the SBM mode is password protected. Please call your Service Center.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

MAINS f=60.0Hz U1=120V U2=119V
f=60.0Hz U1=120V U2=119V
LOAD ON PHASE U1=120V I1=56A 50% U2=120V I2=50A 45% U3=120V I3=61A 55%
MISCELLANEOUS Battery Temp. = +25°C UPS Oper Time= 450h INV Oper Time= 430h
MAINS FAULTS STAT. Minor = 100 Major = 150 Overloads = 30
IDENTIFICATION LP 33 40kVA P1 SW Version: x.x S/N: Q0040-0105-0001
Screen containing the statistic evaluation in % (100= good; 0= bad) of the utility, for the ECO Mode operation. 4. The number of fast transients occurred on the bypass utility on the last seven days.
ECO Mode RATE 100% NR FAST TRANSIENT 2ms >5ms >10ms 25 10 7 3
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Each of the following listed alarms or messages can be displayed on the LCD screen or transmitted to a PC through the serial port RS232 or the SNMP card (optional). Entering the Alarm mode, the LCD screen displays a sequence of screens corresponding to the last 256 alarms & events, each screen indicating:
01.01.2005 12:15:45 NR=255 Status=A588 4580: INVERTER AND MAINS SYNCHRONIZED
explicit text description of the event. 6.2.1 Alarms list
Are defined alarms: all the events which activate the LED Warning (yellow) and the buzzer in order to alert the user about an abnormal situation.
Parameters are lost and have been replaced with default values.
Voltage supply +/-15 VDC has been detected out of tolerance on the P1 – Control board or the programmable circuits are defective.
FAILURE
4004 UPS FAILURE
The master unit detected the slave unit missing on the communication bus even though switch Q1 is still closed.
The trip indicator mounted on rectifier input fuses indicates a blown fuse. The rectifier is turned Off (K4 open) and the load will be supplied by the battery.
FAILURE
4102 K4 CLOSING
K4 not closed despite a closing command being done. The rectifier is switched OFF.
4103 K4 OPENING
K4 not open despite an opening command being done. The rectifier is switched OFF.
4110 RECTIFIER MAINS OUT OF TOLERANCE
Rectifier input mains has been detected out of tolerance (voltage, frequency or phase).
The battery has been discharged and reached “stop operation” time-out (default 3 minutes), the inverter will be shut down. It restarts automatically only when the battery has recovered energy to ensure min. a “stop operation” time to the actual load.
VOLTAGE
VOLTAGE
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Alarm Meaning

During battery test the DC voltage falls under the critical level. If the boost voltage has not been reached within 24 hours, then the charge voltage returns to floating voltage. Battery test is stopped.
FAULT
Rectifier and inverter are OFF. The DC power supply is discharging the battery slowly. Rectifier must be restarted or battery must be disconnected in order to avoid damages.
Rectifier voltage hasn’t reached the set value. Probably fault on regulation loop. The DC capacitors are not equally charged (more of 50 VDC of difference). The rectifier is switched OFF.
Inverter output fuses blown. Signaled by electronic detector. Inverter can be started manually after replacement of fuses.
K7 not closed despite a closing command being done. Signaled by auxiliary contact. Load will be supplied by mains.
FAILURE
K7 not open despite an opening command being done. Signaled by auxiliary contact. Load will be supplied by mains.
FAILURE
Inverter output voltage is out of the tolerances defined in respective parameter (±10%). Inverter is switched OFF.
Detection of inverter bridge (Is) current limitation cause inverter OFF and automatic restart (message 320). After 3 times inverter switches OFF for persistent Is max detection in time. Inverter switch OFF, and it can be restarted manually.
4340 INVERTER CONTROL FAILURE
The slave oscillator is not synchronized with the master, thus causing the shutdown of it’s inverter.
Auto calibration of the Inverters free-run frequency was not possible. The oscillator frequency of this unit is out of tolerance.
FAILURE
4402 RECTIFIER CANNOT BE TURNED ON
The rectifier cannot be turned on because the DC link voltage has not reached the requested value.
K6 not closed despite a closing command being done. Signaled by auxiliary contact. The load cannot be supplied by electronic bypass.
FAILURE
4405 K6 OPENING
K6 not open despite an opening command being done. Signaled by auxiliary contact.
The mains bypass voltage is out of the tolerances (±10%). K6 opens, synchronization with mains is inhibited and transfer to mains is blocked.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Alarm Meaning

The load supplied by utility is over 100%. The load remains blocked on utility as long as alarm overload is active.
Load is locked on mains because 3 transfers on mains have been detected in a short time (default 30 seconds). Transfer will be free again after a time defined by respective parameter (default 30 seconds).
ON MAINS
4531 LOAD ON MAINS BY ERROR DETECTOR
Load is transferred to mains because the error detector detected a disturbance on the output voltage.
Alarm after detection of an Emergency Off from an external safety device connected on Customer Interface. Consequently K4, K6 and K7 open and shut down inverter, booster and rectifier.
ACTIVATED
The UPS-System is in an overload condition >125% on inverter, or >150% on mains. A sequence of “stop operation” starts. Time out depending on load quantity.
With mains bypass supply available and load >115%, the load is transferred on mains. Load will be transferred again automatically on inverter when load will be
4581 INVERTER AND MAINS NOT SYNCH.
The voltages of mains and inverter are not synchronized, which causes the opening of K6.
The battery temperature exceeds the value inserted in parameter. Disabled with parameter (service only).
4698 BATTERY POWER
In case of utility failure, with the actual load, the autonomy time would result below “stop operation” time (default 3 minutes).
Battery voltage is at the lowest limit. Shutdown of inverter until the battery voltage reaches the value in respective parameter.
The load is locked on Inverter following 3 load transfers within 30 seconds. After time out of the value in respective parameter (default 30 seconds), bypass will be free.
ON INVERTER
An overtemperature condition has been detected on inverter. Elapsed “stop operation” time, inverter shutdown. With mains available, load is transferred on mains.
4998 LOAD OFF DUE TO EXTENDED OVERLOAD
Load Off after time-out of “stop operation” for overload on inverter or bypass (time depending on the % of overload).
Load Off after time-out of “stop operation” with missing mains due to battery low voltage or overtemperature condition.
UBATT OR TEMP.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Alarm Meaning

Are defined messages: all the recorded events which are referred to the operation status coherent with the normal situation of the UPS.
Rectifier input mains is again within the admitted tolerance (voltage, frequency and phase).
The UPS is in Load OFF status, resulting in Battery supply for the power supply. Should the Battery voltage decrease to a value below of the one set in a parameter, then power supply will shutdown to avoid damage to the Battery
Start of manual or automatic battery test. Rectifier output voltage is decreased to the value defined by respective parameter.
STARTED
End battery test. End of manual or automatic battery test. Rectifier output voltage is restored to floating voltage.
STOPPED
4141 ISMAX DETECTION
Detection of persistent booster (Is) current limitation.
4161 RECTIFIER
Rectifier received the command to switch ON.
4162 RECTIFIER
Rectifier received the command to switch OFF for: input mains out of tolerance / EPO / UDC max.
4163 GENERATOR
Customer Interface (X1 / 11, 22) received a Gen set ON signaling. Operating mode dependent on setting of respective parameters.
Customer Interface (X1 / 11, 22) received a Gen set OFF signaling. Function bypass enabled dependent on setting of respective parameter.
OFF
4303 INVERTER CANNOT BE TURNED OFF
Inverter cannot be switched OFF, because the load cannot be transferred on mains (voltage out of tolerance, not synchronizing, bypass blocked).
The command to start the inverter has been activated on the control panel.
ON
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Message Meaning

The command to switch OFF the inverter has been done by the control panel or automatically for alarm detection.
4411 BYPASS MAINS
Bypass input mains is again within the admitted tolerance (voltage, frequency and phase).
4500 COMMAND
Disconnection of the load by opening K4, K6 and K7 for: EPO / Total Off / Overload / Stop operation.
4521 NO BYPASS
With the load supplied by electronic bypass, a mains failure or K6 opening occurred.
4534 MULTIPLE LOAD
2 transfers inverter-mains have been detected in a short time, defined by respective parameter (default 30 seconds).
4535 BYPASS LOCKED
Transfer on mains not enabled due to settings of respective parameters. Contactor K6 is open.
Settings of respective parameters enable bypass transfer on mains. Contactor K6 can be closed.
FREE
4561 TOTAL
Push-button Total Off behind the front door has been pressed, with the output circuit breaker Q1 closed.
4562 DETOUR
The auxiliary contact indicates that manual bypass Q2 has been closed.
4564 DETOUR
The auxiliary contact indicates that manual bypass Q2 has been opened.
4567 COMMAND LOAD ON MAINS
The control unit received a command to transfer the load on mains.
The control unit received a command to transfer the load on inverter.
End of the overload condition previously detected with alarm 4570.
The voltages of inverter and mains bypass are synchronized.
Command not to synchronize with mains has been done for: mains bypass out of tolerance (4410) or setting respective parameters.
SYNCHRONIZE
4583 COMMAND TO SYNCHRONIZE
Command to synchronize with mains has been done for: mains BP OK (4410) or setting respective parameters.
The ECO Mode function has been disabled or the programmed time is expired. The UPS returns to VFI Mode supplying the load normally by inverter.
UPS ON
The function ECO Mode is enabled, and according to the time program the UPS will run in ECO Mode, supplying the load normally by mains.
STAND BY
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Message Meaning

The auxiliary contact indicates that the output switch Q1 has been opened.
The auxiliary contact indicates that the output switch Q1 has been closed.
IMPOSSIBLE
Inverter can be started or shutdown by remote control. Commands source can be chosen depending on the value of respective parameter (password required): 0 = Only local panel. 1 = Only serial port on CI (TLC). 2 = Both.
ON
Inverter can be started or shutdown by remote control. Commands source can be chosen depending on the value of respective parameter (password required): 0 = Only local panel. 1 = Only serial port on CI (TLC). 2 = Both.
OFF
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Message Meaning

In case of failure or malfunction, before calling the nearest Service Centre please note the most important identification data of your UPS and the most recent events displayed. In order to make the diagnosis easier for our Diagnostic Centre we suggest you make a copy of this page, fill it in with the requested data, and send it by fax.

UPS No.: - - Series:
Date: / / Signature:

Description of repair action taken:
Actual situation:
Remarks:
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Pressing the menu keypad a series of screens will be displayed, permitting the user to set some functions of the UPS, to restore the command total off, to perform the LEDs TEST, and to switch the inverter ON/OFF.
LP 33 40kVA P1 UPS ON
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

This screen allows the user to modify some parameters permitting to adapt some functions of the UPS to his/her needs, described as follows. This screen can be accessed by entering MENU/PARAMETER MENU/LEVEL 1: USER and confirming with the key Enter.
LEVEL 1: USER LEVEL 2: SERVICE
In PARAMETER MENU the buttons + / - / Enter perform the following functions:
+ This key allows to scroll forward to the next screen and, once the key Enter has been pressed, to move the horizontal selection to the next editable position.
- This key allows to move the selection to the next parameter and, once the key Enter has been pressed, to change the value of the selected character by the underscore cursor.
Enter Start the editing for the currently selected parameter. 1. Date and time set-up
DATE AND TIME D M Y Date: 01.01.2005 Hour: 12:15:45
PROTOCOL SETUP Modem enabled = N Init=BEQV1X3&D0S0=2 Alarm=N Delay=30s
It can be 39 characters long and considers that a blank character terminates the string. If no blank character is found then all 39 characters are used
Delay: This parameter controls the delay between the occurrence of a new event and the modem dialing. It is useful because since the events typically do not occur isolated but in certain sequences, you can eliminate the need for multiple dial-outs for such a sequence of events.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Tel1: This parameter specifies a first tel. number to be used for modem dial-out. The telephone number has a maximum of 39 characters and cannot contain intermediate blank. If the desired number is shorter than 39 characters, finish the string with blanks.
Tel1 enabled: this parameter Y/N specifies if the first telephone number will be used for dial-out.
Tel2: it records the second dial-out number.
Tel2 enabled: this parameter Y/N specifies if the second telephone number will be used for dial-out.
Tel3: it records the third dial-out number.
Tel3 enabled: this parameter Y/N specifies if the third telephone number will be used for dial-out.
Tel4: it records the fourth dial-out number.
Tel4 enabled: this parameter Y/N specifies if the fourth telephone number will be used for dial-out. 4. LCD Display
HOURS SELECTED 24 24 12
If the value is Y and the current time is in the interval for the current day, the ECO Mode is active.
The activation / disactivation of ECO Mode is indicated each time in the event list.
In order to check the inverter function, at least 1 minute of VFI Mode must be programmed during the week (the Y / N parameter is automatically disabled if this condition is not satisfied). In case this minimum time in VFI Mode is not respected, the ECO Mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Language = ENGLISH

2. d1 ÷ d7: Enabling time in function of weekdays. For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time intervals when the UPS is operating in ECO Mode. The hour is given in 24-hour format. These intervals are defined by: ECO Mode START: the hour of the day after which the ECO Mode is enabled. The ECO Mode is enabled until the following ECO STOP time is reached (the ECO STOP time of the same day if this is later than the ECO START time, the ECO STOP time of the following day otherwise). ECO Mode STOP: the hour of the day before which the ECO Mode is enabled. The ECO Mode is enabled starting from the preceding ECO START time (the ECO START time of the same day if this is earlier than the ECO STOP time, the ECO START time of the previous day otherwise). Identical times for ECO START and ECO STOP maintain the existing mode only in case the previous command was ECO START and the following command will be ECO STOP. 3. HOURS SELECTED: The number of ECO Mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the operation mode parameter window (ceiling value). To better understand the ECO Mode programming, some typical examples are shown: Example 1: For continuous ECO Mode set the ECO START times to 00:00 and the ECO STOP times to 23:59 for all weekdays, but almost 1 day must have 1 minute of VFI programmation: i.e d2 - Sunday 00:00 to 23:58).

Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
ECO START 00:00
ECO STOP 23:59 23:58 23:59 Example 2: ECO Mode STOP before ECO Mode START. ECO START 18:00, ECO STOP 06:00 for weekday d4 - Tuesday. Means that on d4 - Tuesday the ECO Mode is active between 00:00 and 06:00 and between 18:00 and 23:59.

Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
ECO START 00:00 00:00 00:00 18:00 00:00 00:00 00:00
ECO STOP 23:59 23:59 23:59 06:00 23:59 23:59 23:59 Example 3: ECO Mode during the night and week-end. If the ECO Mode must be enabled all nights (d3 - Monday ÷ d7 - Friday) between 18:00 in the evening and 06:00 of the following morning and during all Saturday (d1) and Sunday (d2), the corresponding parameters are:

Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
ECO START 00:00 00:00 18:00
ECO STOP 23:59 23:59 06:00
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

Example 4: If the ECO Mode must be enabled on Monday (d3) and Tuesday (d4) between 18:00 in the evening and 06:00 of the following morning, on Friday (d7) between 12:00 and 13:00, during all Saturday (d1) and on Sunday (d2) until 20:00, the corresponding parameters are.

Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
ECO START 00:00 00:00 18:00 18:00 00:00 00:00 12:00
ECO STOP 23:59 20:00 23:59 06:00 06:00 00:00 13:00
ECO START ECO STOP In dark colour are displayed the times with ECO Mode operation. The arrows indicate the conditions given by the ECO START and ECO STOP times introduced with the parameters. Note that on day d6 - Tuesday the interval has length 0 (zero), therefore the ECO Mode is not enabled on this day. Example 5: An equivalent set of parameters for Example 4 is.

Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
ECO START 00:00 00:00 18:00 18:00 06:00 09:00 12:00
ECO STOP 23:59 20:00 18:00 06:00 06:00 09:00 13:00
ECO START ECO STOP The ECO Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 - Tuesday (as indicated by the ECO STOP time of weekday d4 - Tuesday). The ECO STOP time of weekday d3 - Monday has no effect as it is followed by the ECO STOP time of weekday d4 - Tuesday. It can be, without change of meaning, any time between 18:00 and 23:59. Similarly, the ECO Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of weekday d5 - Wednesday. The ECO START time of weekday d5 - Wednesday has no effect as it is preceded by the ECO START time of weekday d4 - Tuesday. It can be, without change of meaning, any time between 00:00 and 06:00.

OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

7.1.1 Start-up of the LP 33 Series
Before connecting hazardous voltages, make sure that:
This procedure must be performed for the first start-up following the installation, with the UPS completely switched Off and not powered. This procedure presupposes that the load is not yet supplied by the UPS system.
SELF TEST 00000000000 SELF TEST OK!
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Continue ►

Udcp=215V Udcn=215V Ubp=164V Ubn=164V F Charge level = 100% Autonomy = 800min
Verify, selecting the screen METERING/Udcp and Udcn, that the booster voltage has reached about 215 VDC.
Some seconds later the load will be transferred on inverter and the main screen will display: APPLICATION ON UPS
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

The purpose of this procedure is to supply the load directly by mains through manual bypass Q2. This procedure is normally performed when the UPS must be completely switched OFF for maintenance or service purpose, performed by an authorized Service Center.
The output will be supplied by the mains through the automatic bypass. LP 33 40kVA
APPL. ON MANUAL DEV.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
= 70% · = 70% · Continue ►

Remark: command INVERTER ON will be enabled only when the inverter voltage of each phase decreases below 7 VAC (about 30 seconds).
Udcp= 5V Udcn= 5V Ubp=0V Ubn=0V O Charge level = 0% Autonomy = 0min
Before proceeding to step 7, check on the display panel that the DC link voltage (both polarities) Udcp and Udcn has reached the minimum voltage of 5 VDC (about 30 seconds).
The load is now powered directly by mains through the manual bypass Q2.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Synchronized

This procedure presupposes that the load is powered by the manual bypass switch:
Udcp=215V Udcn=215V Ubp=164V Ubn=164V F Charge level = 100% Autonomy = 800min
Some seconds later the load will be transferred on inverter and the main screen will display: APPLICATION ON UPS LP 33 40kVA
END OF PROCEDURE
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
= 70%

As a result of this procedure the UPS is completely switched OFF and not powered.

Remark: command INVERTER ON will be enabled only when the inverter voltage of each phase decreases below 7 VAC (about 30 seconds).
Udcp= 5V Udcn= 5V Ubp=0V Ubn=0V O Charge level = 0% Autonomy = 0min 5. Switch OFF the inverter by entering the screen: MENU/COMMAND MENU/INVERTER OFF
Before proceeding to step 5, check on the display panel that the DC link voltage (both polarities) Udcp and Udcn has reached the minimum voltage of 5 VDC (about 30 seconds).
COMMAND MENU INVERTER ON INVERTER OFF * 6. Switch OFF the mains power at the AC input distribution panel.

OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

View of the panel after pressing the button “total off”:
= 0% 1. Reset “total off”. Restore the command “total off” by entering the screen: MENU/RESET TOTAL OFF
LED TEST RESET TOTAL OFF * The load is supplied by the mains through the automatic bypass. The booster starts automatically.
LP 33 40kVA APPLICATION ON BYPASS
END OF PROCEDURE
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

View of the panel after pressing the button “EPO”:
= 0% 1. Reset the button “EPO”.
01.01.2005 12:15:45 NR=255 Status=A588 4563: EMERGENCY OFF ACTIVATED
Press Alarm, to reset alarm and buzzer.
The load is supplied by the mains through the automatic bypass. The booster starts automatically.
LP 33 40kVA APPLICATION ON BYPASS
The load will be automatically transferred from mains to the inverter.
END OF PROCEDURE
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

7.2.1 Parallel System start-up of the LP 33 Series
Before connecting hazardous voltages, make sure that:
This procedure must be performed for the first start-up following the installation, with all the units completely switched Off and not powered. This procedure presupposes that the load is not yet supplied by the UPS system.
SELF TEST 00000000000 SELF TEST OK!
The LCD screen will display the number of the unit in the parallel system (P1, P2, P3 or P4).
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Continue ►

LP 33 40kVA P1
Verify, selecting the screen METERING/Udcp and Udcn, that the booster voltage has reached about 215 VDC.
Udcp=215V Udcn=215V Ubp=164V Ubn=164V F Charge level = 100% Autonomy = 800min
Some seconds later the load will be transferred on inverter and the main screen of each unit will display: APPLICATION ON UPS
LP 33 40kVA P1
END OF PROCEDURE
It is recommended to recharge the battery during a few hours in order to provide the complete battery energy stored to the load in the event of mains failure.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
= 70% · = 70%

The purpose of this procedure is to supply the load directly by mains through manual bypass Q2. This procedure is normally performed when the UPS must be completely switched OFF for maintenance or service purpose, performed by an authorized Service Center. 1. Switch OFF the inverter on each unit entering the screen: MENU/COMMAND MENU/INVERTER OFF
The output will be supplied by the mains through all automatic bypass. LP 33 40kVA P1
APPL. ON MANUAL DEV.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
= 70% · = 70% · Continue ►

Remark: command INVERTER ON will be enabled only when the inverter voltage of each phase decreases below 7 VAC (about 30 seconds).
Udcp= 5V Udcn= 5V Ubp=0V Ubn=0V O Charge level = 0% Autonomy = 0min
Before proceeding to step 7, check on the display panel that the DC link voltage (both polarities) Udcp and Udcn has reached the minimum voltage of 5 VDC (about 30 seconds).
The load is now supplied directly from the mains through the manual switches Q2.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Synchronized

This procedure presupposes that the load is powered by the manual bypass switch:
Udcp=215V Udcn=215V Ubp=164V Ubn=164V F Charge level = 100% Autonomy = 800min
The load will be automatically transferred from mains to the inverters as the needed power requested from the applied load is achieved on inverter side. The main screen of each unit will display: APPLICATION ON UPS
LP 33 40kVA P1
END OF PROCEDURE
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
= 70%

With purpose to separate one unit from the parallel system. 1. Switch OFF the inverter only on this unit entering the screen: MENU/COMMAND MENU/INVERTER OFF Attention: to switch OFF permanently the inverter the key Enter must be pressed 2 times.
COMMAND MENU INVERTER ON INVERTER OFF * 2. Switch OFF the output switch Q1 (0) only on this unit. 3. Perform the command total off only on this unit. 4. Remove the battery fuses F5, F6, F7 (and eventual external fuses in case of external battery) only on this unit. 5. In order to discharge the DC link capacitors, start once more the inverter only on this unit through the screen: MENU/COMMAND MENU/INVERTER ON
Remark: command INVERTER ON will be enabled only when the inverter voltage of each phase decreases below 7 VAC (about 30 seconds).
Before proceeding to step 6, check on the display panel that the DC link voltage (both polarities) Udcp and Udcn has reached the minimum voltage of 5 VDC (about 30 seconds).
Udcp= 5V Udcn= 5V Ubp=0V Ubn=0V O Charge level = 0% Autonomy = 0min
COMMAND MENU INVERTER ON INVERTER OFF * 7. Switch OFF the mains power only on this unit at the AC input distribution panel.
WARNING ! In case the unit should be disconnected and removed from the operating system, the operation must be performed by qualified persons. If an intermediate unit must be disconnected from a parallel system pay attention do not open the control bus: keep the plugs J3 and J4 connected to the board “P16 - Connector adapter RPA” (see Section 4.8.4).
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Synchronized


This procedure must be performed when the load is supplied by the other units of the UPS system and an additional unit must be switched ON and connected to the parallel bus in order to share the load with each other. This unit must be completely switched OFF and not powered. 1. Switch ON the mains power at the input distribution pane on this unit. As a result the UPS performs a self-test and the LCD will show the following screen:


Udcp=215V Udcn=215V Ubp=164V Ubn=164V F Charge level = 100% Autonomy = 800min 4. Switch ON the inverter of this unit entering the screen: MENU/COMMAND MENU/INVERTER ON
Verify, selecting the screen METERING/Udcp and Udcn, that the booster voltage has reached about 215 VDC of this unit.
When the inverter will be synchronized, the unit will be automatically connected with the parallel bus-bar and the load will be shared with the other units. The main screen of each unit will display: APPLICATION ON UPS
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

As a result of this procedure the parallel system is completely switched OFF and not powered.

Remark: command INVERTER ON will be enabled only when the inverter voltage of each phase decreases below 7 VAC (about 30 seconds).
Udcp= 5V Udcn= 5V Ubp=0V Ubn=0V O Charge level = 0% Autonomy = 0min 5. Switch OFF the inverter on each unit entering the screen: MENU/COMMAND MENU/INVERTER OFF
Before proceeding to step 5, check on the display panel that the DC link voltage (both polarities) Udcp and Udcn has reached the minimum voltage of 5 VDC (about 30 seconds).
MENU COMANDI INVERTER ON INVERTER OFF * 6. Switch OFF the mains power of each unit at the AC input distribution panel.

OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

View of the panel after pressing the button “total off”:
LP 33 40kVA P1
= 0% 1. Reset “total off” of the parallel system. Restore the command “total off”, on any one of the units, by entering the screen: MENU/RESET TOTAL OFF
LED TEST RESET TOTAL OFF * The load is supplied by the mains through the automatic bypass. The booster starts automatically.
LP 33 40kVA P1 APPLICATION ON BYPASS
The LCD screen must display on all Units the status: APPLICATION ON BYPASS
As soon as the output power of the inverters is sufficient to supply the load, the output of the units with running inverter will transfer to inverter. The LCD screen must display on all Units the status: APPLICATION ON UPS
LP 33 40kVA P1
END OF PROCEDURE
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
= 70% · = 70%


View of the panel after pressing the button “EPO”:
LP 33 40kVA P1
= 0% 1. Reset the button “EPO”.
01.01.2005 12:15:45 NR=255 Status=A588 4563: EMERGENCY OFF ACTIVATED 2. Reset all UPS by entering the screen: MENU/COMMAND MENU/INVERTER OFF The load is supplied by the mains through the automatic bypass.
Press Alarm, to reset alarm and buzzer.

The booster starts automatically.
The LCD screen must display on all Units the status: APPLICATION ON BYPASS

As soon as the output power of the inverters is sufficient to supply the load, the output of the units with running inverter will transfer to inverter. The LCD screen must display on all Units the status: APPLICATION ON UPS
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA


RPA kit Redundant Parallel Architecture
Allows to extend the unit to a parallel system with 2, 3, or 4 units connected on the same bus, which ensure the highest reliability rate and increase the power availability without prior investments.
For battery with extended backup time (max. 15A).
16 15 14 13 12 22 21 20 19 18 17
1 2 3 4 5 6 7 8 9 10 11
Advanced SNMP Card Simple Network Management Protocol
The Advanced SNMP Card is an interface to the Ethernet Network, and provides UPS information via the standard SNMP Protocol (UPS-MIB (RFC-1628); GE Single MIB; GE Parallel MIB). The UPS can therefore be managed by a Network Management System (NMS) or by our applications (for instance JUMP), which uses this information to determine the state of the UPS in order to guarantee safe and orderly shutdown of the server, when needed.


Connectivity Software JUMP Software Suite / IRIS Service, etc.
Software application for the control and monitoring of the UPS.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

All maintenance and service works must be performed by QUALIFIED SERVICE PERSON.
When used properly, the LP 33 Series UPS is virtually maintenance free. Take care of proper environmental conditions (see Installation Guide - Section 3.5 – Ventilation & Cooling) and keep air inlets/outlets free from dust and any other obstacle. 9.2 COOLING FAN MAINTENANCE
The expected operational life of the cooling fans is approximately 40.000 hours of continuous operation. A high ambient temperature will shorten this operational life. 9.3 BATTERY MAINTENANCE
The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the number of discharge cycles. The UPS LP 33 Series offers the possibility of SBM (Superior Battery Management). The function SBM can be activated through a service Parameter. The functionality of SBM reduces the Battery recharging time together with improved lifetime of the Battery. As a healthy battery is essential to the performance of the UPS, an automatic or manual battery test can be performed regularly to ensure failsafe operation, in order to check if the battery can provide the expected backup time in case of mains failure. We recommend the battery test be performed at least every 1 month, especially if the battery is not sufficiently discharged during normal operation. Since the parameter enabling the battery test protected by user password, please contact your Service Center for more information. Please consider that, if you did a full battery test to verify the full runtime of the battery, the charger needs at least 8 hours to recharge the battery up to 90% of its capacity. To guarantee that the battery is fully charged, the UPS system should be in operation for at least 12 hours every 3 months. When the condition of the battery is critical, the warning signal will be activated (general alarm, buzzer and alarm message “4118 - Battery fault”). In this case the battery must be replaced as soon as possible. Please contact your Service Center.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

If this lamp lights up during the normal operation (service parameter with password), the performances of the UPS remain the same, but that means the unit has not been serviced for the last 20.000 hours by a qualified GE Service Engineer.
LP 33 40 kVA
= 70% SERVICE REQUIRED
Some components of the UPS which need periodic maintenance, if not replaced, could cause a reliability reduction of the supply system. We highly recommend that you contact your Service Center for preventive maintenance work.
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc. .
Date Description Done by
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA

RIDER FOR WARRANTY FOR SALE OF SiteProTM, DIGITAL ENERGYTM SG Series and LP Series UPS. This Rider incorporates by reference the Terms and Conditions in GE Industrial Systems (herein called GE) GETC2003, and includes the following additional provisions contained herein. In the event of conflict between this Rider and GETC2003, the Rider shall take precedence. Limitation on use with life support equipment: Customer understands and agrees that the products sold hereunder are not intended for application or use, and shall not be used: (i) in conjunction with or for life support equipment when failure of any product can be reasonably be expected to cause failure of or diminish the effectiveness of such life support Customer represents and warrants that it shall NOT USE THE PRODUCTS FOR ANY SUCH PURPOSES, OR PERMIT OTHERS TO USE THE PRODUCTS FOR ANY SUCH PURPOSES. If, in breach of the foregoing, any such use occurs, Seller shall have no liability for any resulting damage or injury, in addition to any other legal or equitable rights of Seller, Customer shall indemnify Seller against any such liability, whether arising as a result of breach of contract, warranty, indemnity, tort (including negligence),
If reperformance is not practicable, Seller will furnish without charge
services in an amount essentially equal to those that, in the sole judgment of Seller, would have been required for reperformance. Where a failure cannot be corrected by Seller’s reasonable efforts, the parties will negotiate an equitable adjustment in price. In providing a replacement Product or parts, Seller reserves the right to use refurbished circuit boards, which shall be warranted in accordance with this Warranty Provision. The correction of any failure or the supply of repaired or replacement parts or Products pursuant to this Warranty Provision shall not extend the duration of the applicable Warranty Period. Seller does not warrant the following items: (i) computer hardware, (ii) any computer software, including software provided by Seller with any Product, (iii) products or services obtained from others or (iv) any batteries used in conjunction with the products, including those provided by Seller, and in regard to these items, only the warranty of the manufacturer, if any, shall apply. Seller's obligation under this Provision entitled “Warranty” shall terminate immediately upon any modification of the Product by Customer unless made with the approval of Seller. The Warranty Period applicable to each Product can be extended, if Customer purchases an extended warranty from Seller. If Customer purchases an extended warranty from Seller, the terms of such extended warranty shall supersede these warranty provisions. THE PRECEDING PARAGRAPHS OF THIS WARRANTY PROVISION SET FORTH THE EXCLUSIVE CLAIMS (EXCEPT AS TO TITLE) BASED ON DEFECT IN OR FAILURE OF A PRODUCT, WHETHER THE CLAIM IS IN CONTRACT, INDEMNITY, WARRANTY, TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY OR OTHERWISE.
strict liability or otherwise. WARRANTY: Seller warrants to Customer that during the “Warranty Period” applicable for its SitePro, Digital EnergyTM SG Series and LP Series UPS Product furnished hereunder (the “Product”) will be free from defects in material, workmanship and title. The warranty period (“Warranty Period”) for the specified Product begins on the earlier of three (3) months after the delivery date or upon commissioning of the Product (if applicable) and ends at the end of the period as set forth below: The Warranty Period for the specified Product is as follows: SitePro / Digital EnergyTM SG Series UPS 12 Months LP Series UPS 24 Months
Upon the expiration of the applicable Warranty Period, all such liability shall terminate and Customer shall have a reasonable time, not to exceed thirty (30) days after the applicable Warranty Period, to give written notice of any defects that appeared during the Warranty Period. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, IMPLIED OR STATUTORY. NO IMPLIED STATUTORY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL APPLY. INSTALLATION AND COMMISSIONING OF INSTALLABLE SYSTEMS: If the Products cannot be installed immediately after delivery, Customer is responsible for maintaining proper storage conditions according to operating manuals and any other instructions provided by Seller. Installable Products may only be installed by certified electrical installers and must be installed according to Seller’s specifications, appropriate national electrical codes and accepted standards of workmanship. For purposes of these GE Terms and Conditions, “Installable Products” shall mean Products that require the services of a certified electrical installer to be connected to the power grid. The commissioning of installable Products may only be done by a technician authorized by Seller and must be done according to Seller’s specifications. For purposes of these GE Terms and Conditions, “commissioning” shall mean the start-up of the installable Products and the testing of the installable Products in connection with the load. If commissioning is to be performed by Seller, Seller may refuse to commission the installable Products, if the operating conditions at Customer’s site do not allow safe commissioning and operation of the installable Products. Any costs resulting from a delay in commissioning will be charged to Customer.
In no case does this warranty apply to any failure or nonconformance with specifications caused by or attributable to any associated or complementary products not supplied under these Terms and Conditions, nor shall it in any case apply to the quantity or quality of the product of Customer or the process of manufacture on which any products are used. The warranties and remedies set forth herein are conditioned upon (a) proper transportation, handling, storage, installation, commissioning, operation, use and maintenance in conformance with the operation instruction manuals (including revisions thereto) provided by Seller, any applicable recommendations of Seller and any applicable laws, regulations or codes (b) repair or modification pursuant to Seller’s instructions or approval and (c) Customer promptly notifying Seller of any defects and, if required, promptly making the Product available for correction at Customer’s expense. This warranty shall not apply (a) if Customer or any other unauthorized person has made any modifications, alterations or repairs to the Product not authorized by Seller, including Customer’s use of parts in conjunction with the Product (excluding batteries) not admitted or delivered by Seller, (b) to a Product with removed or altered serial numbers, (c) to a Product damaged by acts of God, sources external to the Product, misuse, accident, abuse, neglect, negligence, or use beyond rated capacity, and (d) if GE authorized field service technician does not commission Digital Energyæ SG Series UPS and SitePro UPS.
If any Product or service fails to meet the foregoing warranties (except title), Seller shall thereupon correct any such failure either, at its option, by (i) repairing any defective or damaged part or Product and/or reperforming any defective service or (ii) making available, F.O.B. at Seller’s facility, place of manufacture or other mutually agreed upon point of shipment, any necessary repaired or replacement parts; provided, however, that prior to repairing any defective or damaged part or Product, Seller shall have received, at Customer’s cost, such part or Product in need of repair or replacement.