EN
GE logo
Official user manual

GE Security System Keypad (1019070)

58 pages·1.1 MB·Network Card·PDF·ENDEFRITNLJA
GE Security System Keypad (1019070)
Table of Contents 116 sections 1 INTRODUCTION · 1.1 FEATURES · 1.2 OVERVIEW · 1.3 ARCHITECTURE · … ShowHide
1 INTRODUCTIONp.71.1 FEATURESp.71.2 OVERVIEWp.71.3 ARCHITECTUREp.101.4 SAFETYp.102 CONSOLE INTERFACEp.112.1 INTRODUCTIONp.112.1.1 Local connectionp.112.1.2 Remote connectionp.122.1.3 Log-onp.132.1.4 Saving the settingsp.132.2 COMMAND LISTp.142.2.1 General command groupp.142.2.2 Network command groupp.152.2.3 DNS command groupp.162.2.4 User command groupp.172.2.5 Service command groupp.182.2.6 Time command groupp.192.2.7 Smtp command groupp.202.2.8 Snmp command groupp.212.2.9 Trap command groupp.222.2.10 UPS command groupp.232.2.11 Rccmd command groupp.242.2.12 Events command groupp.252.2.13 Log command groupp.253 WEB INTERFACEp.263.1 INTRODUCTIONp.263.1.1 Supported browsersp.263.1.2 Initial web accessp.263.1.3 Sample pagep.263.1.4 Saving the settingsp.273.2 NAVIGATION BARp.273.3 UPS SECTIONp.273.3.1 UPS Identification pagep.273.3.2 Battery pagep.283.3.3 UPS Status pagep.293.3.4 UPS Alarm pagep.293.3.5 UPS PMAD page (3-ph version ONLY)p.293.3.6 UPS Test pagep.303.3.7 UPS Control page (1-ph/SP units ONLY)p.303.3.8 UPS Config pagep.303.4 SYSTEM SECTIONp.313.4.1 Network pagep.313.4.2 Date&Time pagep.313.4.3 RCCMD pagep.313.4.4 Password pagep.313.4.5 Configuration pagep.323.4.6 Upgrade pagep.323.5 SNMP SECTIONp.323.5.1 SNMP settings pagep.323.5.2 Trap settings pagep.323.5.3 Alarm notification pagep.323.6 SMTP SECTIONp.333.6.1 SMTP configuration pagep.333.6.2 Alarm notification pagep.333.7 LOG SECTIONp.333.8 UTILITY SECTIONp.333.9 SAVE SECTIONp.343.10 USER SECTIONp.344 SNMP AGENTp.35MIB STRUCTUREp.354.2 RFC1628 MIB OBJECTSp.354.3 GE MIB OBJECTSp.375 NETWORK CONFIGURATIONp.395.1 ETHERNET CONNECTIONp.395.2 TCP/IP CONFIGURATIONp.395.2.1 Static IP addressp.395.2.2 BOOTP / DHCPp.395.3 DNS CONFIGURATIONp.405.4 HOSTNAMEp.406 MULTI-SERVER NETWORK SHUTDOWN (RCCMD)p.416.1 NETWORK SHUTDOWN WITH RCCMDp.416.1.1 Set-up and Configuration of controlled Serversp.416.1.2 Configuration of the SNMP/Web adapterp.416.1.3 Network configurationp.426.1.4 RCCMD Shutdownp.426.2 RCCMD CLIENT RELAYp.437 SECURITYp.447.1 USER AUTHENTICATION & AUTHORISATIONp.447.1.1 User Managementp.447.1.2 User classp.447.1.3 Selective service activationp.447.2 SERVICES (ACCESS METHODS)p.457.3 ENCRYPTIONp.457.3.1 SSH and SFTPp.457.3.2 SSL Certificatesp.477.4 CUSTOMER RESPONSIBILITYp.497.4.1 Physical securityp.497.4.2 Changing default configurationp.497.4.3 User & Service managementp.497.4.4 Encryptionp.497.4.5 Firewallsp.498 OTHER FUNCTIONALITIESp.508.1 SYSTEM TIMEp.508.2 SERIAL BY-PASS (1-PH/SP VERSION ONLY)p.508.3 HTTP BASED MONITORING (1-PH/SP VERSION ONLY)p.508.3.1 UPS Load Alertp.519 MAINTENANCEp.529.1 SOFTWARE UPGRADEp.529.2 CONFIGURATION FILEp.529.3 LOGSp.5210 TROUBLESHOOTINGp.5310.1 TROUBLESHOOTING UPS CONNECTIONp.5310.1.1 3-ph SNMP/Web plug-in adapterp.5310.1.2 1-ph SNMP/Web external adapterp.5310.2 TROUBLESHOOTING LOCAL CONNECTIONp.5310.3 TROUBLESHOOTING NETWORK CONNECTIONp.5410.4 TROUBLESHOOTING WEB ACCESSp.5510.5 TROUBLESHOOTING DATE&TIME (NTP)p.5510.6 TROUBLESHOOTING E-MAIL NOTIFICATION (SMTP)p.5610.7 TROUBLESHOOTING NETWORK SHUTDOWNp.5711 CUSTOMER SUPPORTp.5811.1 FIRST LINE SUPPORTp.5811.2 INTERNETp.5811.3 WWW SERVERp.58Unbenanntp.1
Page 1 of the GE Security System Keypad (1019070) user manual — GE imagination at work
Page 1 · click to enlarge
Page 1

GE Digital Energy Power Quality

GE Security System Keypad (1019070) — GE Digital Energy Power Quality diagram (page 1)
Fig. 1 · GE Digital Energy Power Quality
GE Security System Keypad (1019070) — GE Digital Energy Power Quality diagram (page 1)
Fig. 2 · GE Digital Energy Power Quality
GE Security System Keypad (1019070) — GE Digital Energy Power Quality diagram (page 1)
Fig. 3 · GE Digital Energy Power Quality
GE Security System Keypad (1019070) — GE Digital Energy Power Quality diagram (page 1)
Fig. 4 · GE Digital Energy Power Quality

Operating Manual

Digital Energy™ SNMP / WEB ADAPTER

P/N 1018959 3-ph SNMP/Web plug-in adapter P/N 1019070 1-ph SNMP/Web plug-in adapter

P/N 23954 SP SNMP/Web plug-in adapter P/N 1019071 1-ph SNMP/Web external adapter

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44

www.gedigitalenergy.com

GE Security System Keypad (1019070) — Operating Manual diagram (page 1)
Fig. 5 · Operating Manual

GE imagination at work

Page 2 of the GE Security System Keypad (1019070) user manual — P/N 1018959 P/N 1019070 P/N 23954 P/N 1019071
Page 2 · click to enlarge
Page 2

3-ph SNMP/Web plug-in adapter 1-ph SNMP/Web plug-in adapter SP SNMP/Web plug-in adapter 1-ph SNMP/Web external adapter

Model:

Date of issue05.12.2008
File nameOPM_CNT_SNM_BAS_CRD_V012
Revision1.2

P/N 1018959 P/N 1019070 P/N 23954 P/N 1019071

Identification No.

1.0 First Issue 15.02.2008

1.1 Updated for the 3-ph and SP SNMP/Web plug-in adapters 13.05.2008

1.2 Updated following the introduction of the RCCMD functionality 05.12.2008

COPYRIGHT © 2008 by GE Consumer & Industrial SA

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Up-dating · Revision Concerns Date

Page 3 of the GE Security System Keypad (1019070) user manual — Thank you for choosing GE !
Page 3 · click to enlarge
Page 3

Dear Customer, We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE. We trust that the use of the SNMP/Web adapters for our Uninterruptible Power Supply systems, developed and produced to the highest standards of quality, will give you complete satisfaction. Please read carefully the Installation Manual, which contains all the necessary information about the installation of the adapters.

Thank you for choosing GE !

Distributed by: Your service contact: g

GE Digital Energy General Electric Company CH – 6595 Riazzino (Locarno)

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Switzerland

Page 4 of the GE Security System Keypad (1019070) user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

1 INTRODUCTIONp.71.1 FEATURESp.71.2 OVERVIEWp.71.3 ARCHITECTUREp.101.4 SAFETYp.102 CONSOLE INTERFACEp.112.1 INTRODUCTIONp.112.1.1 Local connectionp.112.1.2 Remote connectionp.122.1.3 Log-onp.132.1.4 Saving the settingsp.132.2 COMMAND LISTp.142.2.1 General command groupp.142.2.2 Network command groupp.152.2.3 DNS command groupp.162.2.4 User command groupp.172.2.5 Service command groupp.182.2.6 Time command groupp.192.2.7 Smtp command groupp.202.2.8 Snmp command groupp.212.2.9 Trap command groupp.222.2.10 UPS command groupp.232.2.11 Rccmd command groupp.242.2.12 Events command groupp.252.2.13 Log command groupp.253 WEB INTERFACEp.263.1 INTRODUCTIONp.263.1.1 Supported browsersp.263.1.2 Initial web accessp.263.1.3 Sample pagep.263.1.4 Saving the settingsp.273.2 NAVIGATION BARp.273.3 UPS SECTIONp.273.3.1 UPS Identification pagep.273.3.2 Battery pagep.283.3.3 UPS Status pagep.293.3.4 UPS Alarm pagep.293.3.5 UPS PMAD page (3-ph version ONLY)p.293.3.6 UPS Test pagep.303.3.7 UPS Control page (1-ph/SP units ONLY)p.303.3.8 UPS Config pagep.303.4 SYSTEM SECTIONp.313.4.1 Network pagep.313.4.2 Date&Time pagep.313.4.3 RCCMD pagep.313.4.4 Password pagep.313.4.5 Configuration pagep.323.4.6 Upgrade pagep.323.5 SNMP SECTIONp.323.5.1 SNMP settings pagep.323.5.2 Trap settings pagep.323.5.3 Alarm notification pagep.323.6 SMTP SECTIONp.333.6.1 SMTP configuration pagep.333.6.2 Alarm notification pagep.333.7 LOG SECTIONp.333.8 UTILITY SECTIONp.333.9 SAVE SECTIONp.343.10 USER SECTIONp.344 SNMP AGENTp.35MIB STRUCTUREp.354.2 RFC1628 MIB OBJECTSp.354.3 GE MIB OBJECTSp.375 NETWORK CONFIGURATIONp.395.1 ETHERNET CONNECTIONp.395.2 TCP/IP CONFIGURATIONp.395.2.1 Static IP addressp.395.2.2 BOOTP / DHCPp.395.3 DNS CONFIGURATIONp.405.4 HOSTNAMEp.406 MULTI-SERVER NETWORK SHUTDOWN (RCCMD)p.416.1 NETWORK SHUTDOWN WITH RCCMDp.416.1.1 Set-up and Configuration of controlled Serversp.416.1.2 Configuration of the SNMP/Web adapterp.416.1.3 Network configurationp.426.1.4 RCCMD Shutdownp.426.2 RCCMD CLIENT RELAYp.437 SECURITYp.447.1 USER AUTHENTICATION & AUTHORISATIONp.447.1.1 User Managementp.447.1.2 User classp.447.1.3 Selective service activationp.447.2 SERVICES (ACCESS METHODS)p.457.3 ENCRYPTIONp.457.3.1 SSH and SFTPp.457.3.2 SSL Certificatesp.477.4 CUSTOMER RESPONSIBILITYp.497.4.1 Physical securityp.497.4.2 Changing default configurationp.497.4.3 User & Service managementp.497.4.4 Encryptionp.497.4.5 Firewallsp.498 OTHER FUNCTIONALITIESp.508.1 SYSTEM TIMEp.508.2 SERIAL BY-PASS (1-PH/SP VERSION ONLY)p.508.3 HTTP BASED MONITORING (1-PH/SP VERSION ONLY)p.508.3.1 UPS Load Alertp.519 MAINTENANCEp.529.1 SOFTWARE UPGRADEp.529.2 CONFIGURATION FILEp.529.3 LOGSp.5210 TROUBLESHOOTINGp.5310.1 TROUBLESHOOTING UPS CONNECTIONp.5310.1.1 3-ph SNMP/Web plug-in adapterp.5310.1.2 1-ph SNMP/Web external adapterp.5310.2 TROUBLESHOOTING LOCAL CONNECTIONp.5310.3 TROUBLESHOOTING NETWORK CONNECTIONp.5410.4 TROUBLESHOOTING WEB ACCESSp.5510.5 TROUBLESHOOTING DATE&TIME (NTP)p.5510.6 TROUBLESHOOTING E-MAIL NOTIFICATION (SMTP)p.5610.7 TROUBLESHOOTING NETWORK SHUTDOWNp.5711 CUSTOMER SUPPORTp.5811.1 FIRST LINE SUPPORTp.5811.2 INTERNETp.5811.3 WWW SERVERp.58Unbenanntp.1
Page 5 of the GE Security System Keypad (1019070) user manual — Unbenannt
Page 5 · click to enlarge
Page 5

3.7 LOG SECTION 33 3.8 UTILITY SECTION 33 3.9 SAVE SECTION 34 3.10 USER SECTION 34

4 SNMP AGENT 35 4.1 MIB STRUCTURE 35 4.2 RFC1628 MIB OBJECTS 35 4.3 GE MIB OBJECTS 37

5 NETWORK CONFIGURATION 39 5.1 ETHERNET CONNECTION 39 5.2 TCP/IP CONFIGURATION 39 5.2.1 Static IP address 39 5.2.2 BOOTP / DHCP 39 5.3 DNS CONFIGURATION 40 5.4 HOSTNAME 40

6 MULTI-SERVER NETWORK SHUTDOWN (RCCMD) 41 6.1 NETWORK SHUTDOWN WITH RCCMD 41 6.1.1 Set-up and Configuration of controlled Servers 41 6.1.2 Configuration of the SNMP/Web adapter 41 6.1.3 Network configuration 42 6.1.4 RCCMD Shutdown 42 6.2 RCCMD CLIENT RELAY 43

7 SECURITY 44 7.1 USER AUTHENTICATION & AUTHORISATION 44 7.1.1 User Management 44 7.1.2 User class 44 7.1.3 Selective service activation 44 7.2 SERVICES (ACCESS METHODS) 45 7.3 ENCRYPTION 45 7.3.1 SSH and SFTP 45 7.3.2 SSL Certificates 47 7.4 CUSTOMER RESPONSIBILITY 49 7.4.1 Physical security 49 7.4.2 Changing default configuration 49 7.4.3 User & Service management 49 7.4.4 Encryption 49 7.4.5 Firewalls 49

8 OTHER FUNCTIONALITIES 50 8.1 SYSTEM TIME 50 8.2 SERIAL BY-PASS (1-PH/SP VERSION ONLY) 50 8.3 HTTP BASED MONITORING (1-PH/SP VERSION ONLY) 50 8.3.1 UPS Load Alert 51

9 MAINTENANCE 52 9.1 SOFTWARE UPGRADE 52 9.2 CONFIGURATION FILE 52 9.3 LOGS 52

10 53 TROUBLESHOOTING 10.1 TROUBLESHOOTING UPS CONNECTION 53 10.1.1 3-ph SNMP/Web plug-in adapter 53 10.1.2 53 1-ph SNMP/Web external adapter 10.2 53 TROUBLESHOOTING LOCAL CONNECTION

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 6 of the GE Security System Keypad (1019070) user manual — Unbenannt
Page 6 · click to enlarge
Page 6

10.3 54 TROUBLESHOOTING NETWORK CONNECTION 10.4 TROUBLESHOOTING WEB ACCESS 55 10.5 55 TROUBLESHOOTING DATE&TIME (NTP) 10.6 TROUBLESHOOTING E-MAIL NOTIFICATION (SMTP) 56 10.7 TROUBLESHOOTING NETWORK SHUTDOWN 57

11 CUSTOMER SUPPORT 58 11.1 FIRST LINE SUPPORT 58 11.2 INTERNET 58 11.3 WWW SERVER 58

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 7 of the GE Security System Keypad (1019070) user manual — LAN
Page 7 · click to enlarge
Page 7

1 INTRODUCTION

1.1 FEATURES

Each SNMP/Web adapter provides the following features:

  • 10/100 Mpbs connection speed
  • Use of DHCP / BOOTP or manual configuration for the TCP/IP network settings
  • SNMP Agent
  • Web server
  • Console interface
  • UPS status / alarms / readings, alarm logging over different interfaces
  • Digital outputs (open-collector outputs for relay drive) – 1-ph plug-in version only
  • SNMP Traps and E-mail notification upon UPS alarm
  • Advanced security features 1.2 OVERVIEW

3-ph SNMP/Web plug-in adapter (P/N 1018959)

Front panel / User interface view Site Pro / SG Series LP33 Series

LAN

LAN

RS-232

RS-232

LAN

LAN

RS-232

RS-232

UPS

UPS

UPS

UPS

1 4 3 2

  • 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX
  • 2 – LEDs Ref. specific section
  • 3 – RS-232 port Local console connection (115200-N-8-1)
  • 4 – Reset button HW reset

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 8 more labels / short text on this page
UTP 10/100 Active · UTP 10/100 Active · UTP 10/100 Active · UTP 10/100 Active · Reset · Reset · Reset · Reset
Page 8 of the GE Security System Keypad (1019070) user manual — 1 INTRODUCTION
Page 8 · click to enlarge
Page 8

1-ph SNMP/Web plug-in adapter (P/N 1019070)

GE Security System Keypad (1019070) — 1 INTRODUCTION diagram (page 8)
Fig. 6
  • 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX
  • 2 – LEDs Ref. specific section
  • 3 – RS-232 port Local console connection (115200-N-8-1)
  • 4 – Reset button HW reset
  • 5 – RJ11 Connector Contact interface, open-collector output SP SNMP/Web plug-in adapter (P/N 23954)
GE Security System Keypad (1019070) — 1 INTRODUCTION diagram (page 8)
Fig. 7

Front Panel – User Interface View

  • 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX
  • 2 – LEDs Ref. specific section
  • 3 – RS-232 port Local console connection (115200-N-8-1)
  • 4 – Reset button HW reset 1-ph SNMP/Web external adapter (P/N 1019071)
GE Security System Keypad (1019070) — 1 INTRODUCTION diagram (page 8)
Fig. 8

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

View · Front View

Page 9 of the GE Security System Keypad (1019070) user manual — 1 INTRODUCTION
Page 9 · click to enlarge
Page 9
GE Security System Keypad (1019070) — 1 INTRODUCTION diagram (page 9)
Fig. 9
  • 1 – RJ45 Connector Ethernet connection, 10Base-T or 100Base-TX
  • 2 – LEDs Ref. specific section
  • 3 – RS-232 port Local console connection (115200-N-8-1)
  • 4 – Reset button HW reset
  • 6 – Power-in AC adapter connection
  • 7 – UPS port RS-232 connection to the UPS LEDs The various front panel LEDs have the following meaning:
  • LAN / Netlink
StatusMeaning OffNo LAN connection detected OnLAN connection established, no communication BlinkLAN connection established, receive or transmit active
GE Security System Keypad (1019070) — 1 INTRODUCTION diagram (page 9)
Fig. 10
  • UPS / Fail
StatusMeaning OffOK / No Fault OnNo UPS Connection
  • Active
StatusMeaning OffFault of device BlinkDevice OK / No fault

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 10 of the GE Security System Keypad (1019070) user manual — 1.3 ARCHITECTURE
Page 10 · click to enlarge
Page 10

1.3 ARCHITECTURE

GE Security System Keypad (1019070) — 1.3 ARCHITECTURE diagram (page 10)
Fig. 11

All maintenance and service work should be performed by qualified service personnel only.

Please read carefully the Installation Manual before installing or operating the adapters. For more information on the UPS system, please refer to the applicable Installation and User Manual.

Particularly, refer to Safety Rules, Warnings and Cautions as laid out in the cited document.

The knowledge of (and FULL compliance to) the safety instructions and the warning contained in the cited documents are THE ONLY CONDITION to avoid any dangerous situations during installation, operation, maintenance work, and to preserve the maximum reliability of the UPS system.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 11 of the GE Security System Keypad (1019070) user manual — 2.1 INTRODUCTION
Page 11 · click to enlarge
Page 11

2 CONSOLE INTERFACE

2.1 INTRODUCTION

The console interface provides a simple way to configure the SNMP/Web adapters through a command-line interface. Actually, the console interface provides a full set of commands, extending far beyond the adapter initial configuration and allowing access to all advanced functionalities. Nevertheless, access using the console interface (by means of a local serial connection) is normally needed only for initial configuration, when no DHCP server is available or the IP-address is not known. The console interface can be accessed locally (serial connection) or remotely (Telnet, SSH). 2.1.1 Local connection

Local access requires a local computer connected to the adapter serial port using a straight serial cable:

  • Connect the SNMP adapter to a computer using a standard 1:1 serial communication cable.
  • Run a terminal simulator (e.g. HyperTerminal on a PC running Windows)
  • Configure the terminal simulator as follows: 115,200bps, 8 data bits, 1 stop bit, parity none, flow control none terminal emulation VT-100
GE Security System Keypad (1019070) — 2.1 INTRODUCTION diagram (page 11)
Fig. 12
GE Security System Keypad (1019070) — 2.1 INTRODUCTION diagram (page 11)
Fig. 13
  • Establish the connection and press <enter>
  • The default username (login) and password are ge and ge
  • A command-line configuration interface is entered

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 12 of the GE Security System Keypad (1019070) user manual — 2.1.2 Remote connection
Page 12 · click to enlarge
Page 12

2.1.2 Remote connection

The console interface can also be accessed remotely from any computer on the same subnet using either Telnet or SSH (under the hypothesis that the relevant service is running and enabled for the selected user). TELNET Telnet provides basic user authentication. The SNMP/Web adapter uses the standard telnet port. To start a Telnet session and connect to the adapter:

  • Launch a telnet client (e.g. on a PC running Windows, select Run from the Start menu and type telnet <IP> )
  • The default username (login) and password are ge and ge
  • A command-line configuration interface is entered SSH SSH (Secure SHell) combines user authentication with encryption, to provide a higher degree of communication security. In any case, the user access rights are the same regardless of the service/interface used. Below is a sample SSH session using a popular SSH client ( putty ):
  • Start the SSH client application ( putty.exe )
GE Security System Keypad (1019070) — 2.1.2 Remote connection diagram (page 12)
Fig. 14 · 2.1.2 Remote connection

o In the Host Name section specify the card hostname or the IP address o In the Connection Type section select SSH o Select Open to launch the SSH session

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 13 of the GE Security System Keypad (1019070) user manual — 2.1.3 Log-on
Page 13 · click to enlarge
Page 13
  • Most SSH clients display the host key fingerprint at the start of the session. Make sure the fingerprint shown matches the SNMP/Web adapter fingerprint (see Encryption section for details on figuring out the SSH fingerprint)
GE Security System Keypad (1019070) — 2.1.3 Log-on diagram (page 13)
Fig. 15 · 2.1.3 Log-on
  • A login window should then be available in a few seconds. The default username (login) and password are ge and ge
GE Security System Keypad (1019070) — 2.1.3 Log-on diagram (page 13)
Fig. 16 · 2.1.3 Log-on

2.1.3 Log-on

User authentication requires inputting the username and password. Remember that:

  • Both username and password are case-sensitive, and are always specified in lower case
  • By default, only one user is defined, with username and password set to ge and ge
  • Depending on the user class, not all commands and settings may be available 2.1.4 Saving the settings

Apart from some network parameters, most setting are immediately active. However, the adapter will revert to the last save settings at reboot. Therefore, in order to permanently modify the SNMP/Web adapter setting, remember to save the configuration after every change.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 14 of the GE Security System Keypad (1019070) user manual — 2.2 COMMAND LIST
Page 14 · click to enlarge
Page 14

2.2 COMMAND LIST

The various commands are split in different groups, depending on the involved functionality, and are listed here in accordance with their group classification. The command-line interface includes a command auto-completion feature. Normally, typing a command without any parameter displays usage information on the command. A help command is also available. Note that all commands are case-sensitive. 2.2.1 General command group

The general command group consists of the following commands:

general | network | dns | user | service | time | smtp | snmp | trap | ups | rccmd | events | log

general shows all general commands network shows all network commands etc …

list List all available commands

version Display the board FW version

Change current user password

passwd NOTE: Password length is limited to 8 chars. The command line interface may accept longer passwords, although only the first 8 characters are significant.

Ping IP address or hostname

ping [hostname] | [X.X.X.X]

hostname fully qualified hostname X.X.X.X IP-address

nvdefault Reset the configuration to factory default

nvsave Save changes to non-volatile memory

nvdump Dump configuration file (gedeups.cfg) to FTP area

Update the SNMP/Web configuration with the gedeups.cfg file from the FTP area nvupdate

Start the upgrade with the uploaded firmware

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 9 more labels / short text on this page
Command Parameters Description · Show help information · help · User logout · logout · exit User logout · upgrade · System restart (soft-reset) · reboot
Page 15 of the GE Security System Keypad (1019070) user manual — 2.2.2 Network command group
Page 15 · click to enlarge
Page 15

2.2.2 Network command group

The network command group allows to configure the board for communication over the network.

showip Show the current network settings

arp Show ARP table

Define the network settings at boot-up (*)

manual static IP configuration, the device configuration (ref. setip) is used dhcp network settings retrieved from DHCP server bootp network settings retrieved from BOOTP server

manual | dhcp | bootp

Set static IP/mask/default gateway

[address] IP-address [netmask] Subnet mask [gateway] Default gateway IP-address

Define the full qualified domain name

[hostname] Full qualified domain name

Get the hostname from DHCP server

dhcphost on | off

As most network devices, SNMP/Web adapters use an auto- negotiation protocol to communicate what media technologies they support, and then select the fastest mutually supported media technology. recheck mii-tool

Running this command shows the negotiated media.

As most network devices, SNMP/Web adapters use an auto- negotiation protocol to communicate what media technologies they support, and then select the fastest mutually supported media technology. auto | 100baseTx-FD | 100baseTx-HD | 10baseT-FD | 10baseT-HD

Some passive devices, such as single-speed hubs, are unable to auto-negotiate. To handle such devices, the SNMP/Web adapter can be forced to operate in one mode, instead of auto-negotiating.

Quick network configuration menu menu Running this command lunches an interactive menu – follow the on-screen instructions (*) NOTE: Network settings become effective only after a reboot. Therefore, if these settings must be modified, the following actions shall be performed in sequence:

  • Update the settings, using the applicable command
  • Save the settings – nvsave command. Always remember that unsaved setting are lost in case of reset / reboot
  • Reboot the card – reboot command

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 6 more labels / short text on this page
Command Parameters Description · boot-method · [address] [netmask] [gateway] · setip · hostname [hostname] · speedduplex
Page 16 of the GE Security System Keypad (1019070) user manual — 2.2.3 DNS command group
Page 16 · click to enlarge
Page 16

Setting the boot-method to manual has the side effect that manual-dns is also set to ON. Mind that the reverse is not true (setting boot-method to DHCP does not forced manual-dns to OFF). However, if the boot method is set through the quick network configuration menu, setting the boot-method to DHCP will also force manual-dns to OFF. Unlike network settings, the DNS settings may become immediately active. 2.2.3 DNS command group

The dns command group allows to configure the setting for hostname address resolution.

showdns Show detailed DNS settings

manual-dns on | off

on Use DNS server address specified manually off Obtain DNS server address automatically

Add a DNS Server

[X.X.X.X] DNS server IP-address [X.X.X.X]

Delete a DNS Server

[X.X.X.X] DNS server IP-address [X.X.X.X] deldnssrv

Test DNS settings address resolution

[host] hostname [server] DNS server IP-address (optional)

RESULT: Successful Server: [DNS server hostname] Address: [DNS server IP address] Name: [host] Address: [Resolved IP address for the host] Unsuccessful [host]: No address associated with the name Or [host]: Hostname lookup failure

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 5 more labels / short text on this page
Command Parameters Description · Define DNS configuration · adddnssrv · nslookup · [host] [server]
Page 17 of the GE Security System Keypad (1019070) user manual — 2.2.4 User command group
Page 17 · click to enlarge
Page 17

2.2.4 User command group

The user command group is available only to the supervisor user, the only user who can perform user management.

Change supervisor login name

[name] New supervisor username

showuser Show user settings

[user] username for the new user [telnet] 1 – access allowed / 0 – not allowed [http] 1 – access allowed / 0 – not allowed [ftp] 1 – access allowed / 0 – not allowed [access] ‘ro’ – read-only / ‘rw’ – read/write

[user] [http] [telnet] [ftp] [access]

[name] User to be deleted

Modify services and access rights for a user

[user] [http] [telnet] [ftp] [access]

[user] username for the new user [telnet] 1 – access allowed / 0 – not allowed [http] 1 – access allowed / 0 – not allowed [ftp] 1 – access allowed / 0 – not allowed [access] ‘ro’ – read-only / ‘rw’ – read/write NOTE: The indicated services refer to the following access methods:

Web interface Controls access with both HTTP and HTTPS protocols http

Remote console interface Controls access with both Telnet and SSH (Secure SHell) protocols plus SFTP (Secure FTP)

File transfer Controls access with FTP ftp

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 8 more labels / short text on this page
Command Parameters Description · supername [name] · Add a user · adduser · Delete a user · deluser [name] · moduser · telnet
Page 18 of the GE Security System Keypad (1019070) user manual — 2.2.5 Service command group
Page 18 · click to enlarge
Page 18

2.2.5 Service command group

The service command group allows to enable/disable different services. Note that the local (serial) connection cannot be disabled.

Enable/disable HTTP server (port:80)

on Web server enabled off Web server disabled http-server

Enable/disable HTTPS server (port:443)

on Secure web server enabled off Secure web server disabled https-server

Enable/disable SSH encryption (port:22)

on SSH encryption enabled off SSH encryption disabled

ssh-server on | off

Enable/disable FTP server (port:21)

ftp-server on | off

on FTP server enabled off FTP server disabled

Enable/disable Telnet server (port:23) telnet-server on | off on Telnet server enabled off Telnet server disabled

Create new digital certificate for the HTTPS server (*)

sitename The DNS name / IP address of the adapter sitename

Show the SSH key fingerprint (*) ssh-fingerprint

Show the web server digital certificate fingerprint (also known as thumbnail) (*) ssl-fingerprint

Show the digital certificate fingerprint (also known as thumbnail) for the CA Root Certificate (*) ca-fingerprint

showftp Show FTP server info and connections

showlogin Show detailed telnet/ssh login information (*) Refer to the Encryption section for details.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 4 more labels / short text on this page
Command Parameters Description · on | off · on | off · makecert
Page 19 of the GE Security System Keypad (1019070) user manual — 2.2.6 Time command group
Page 19 · click to enlarge
Page 19

2.2.6 Time command group

The time command group allows to enable/disable different services. Note that the local (serial) connection cannot be disabled.

showtime Show all configured time settings

ntponoff on | off

on NTP client enabled off NTP client disabled

[hostname] hostname or IP-address of the NTP server

Force clock synchronisation with NTP server ntpdate

Set the time-zone.

Set the date & time

MM month DD day hh hour mm minute [CC]YY year ss seconds (*) By running the tmzone command, an interactive menu is launched – follow the on-screen instructions. NOTE: When using the local serial connection, make sure that the terminal emulation is set to VT-100, otherwise the interactive menu may not be rendered correctly.

settime MMDDhhmm[[CC]YY][.ss]

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 5 more labels / short text on this page
Command Parameters Description · Enable/disable NTP client · Define NTP server · ntp-server [hostname] · (*) tmzone
Page 20 of the GE Security System Keypad (1019070) user manual — 2.2.7 Smtp command group
Page 20 · click to enlarge
Page 20

2.2.7 Smtp command group

The smtp command group allows to configure the e-mail sending functionality for e-mail notification of UPS events and alarms:

showsmtp Show detailed e-mail settings

on E-mail alert enabled off E-mail alert disabled email-alert

Set timeout for TCP communication with SMTP server

[seconds] Timeout in seconds (range 5-60 seconds) smtp-timeout

Set SMTP server address

[hostname] hostname/IP-address of the SMTP server

Enable/disable authentication for email server

email-authen on | off

on E-mail server requires authentication off E-mail server does not require authentication

Set email server account

[user] Username for e-mail server authentication

Set email server password

[pwd] Password for e-mail server authentication

Set the 'mail from:' header

[sender] E-mail address (63 chars max)

Add a recipient address

[e-mail] [e-mail] E-mail address (63 chars max) addrcpt

Delete a recipient address

[e-mail] E-mail address (63 chars max)

Send a test mail sendemail [msg]

[msg] Test message to be send

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 10 more labels / short text on this page
Command Parameters Description · Enable/disable email functionality · on | off · [seconds] · smtp-server [hostname] · email-account [user] · email-passwd [pwd] · smtp-sendername · [sender] · delrcpt [e-mail]
Page 21 of the GE Security System Keypad (1019070) user manual — 2.2.8 Snmp command group
Page 21 · click to enlarge
Page 21

2.2.8 Snmp command group

The snmp command group allows to configure the SNMP Agent for UPS monitoring via SNMP and trap notification of UPS events and alarms:

showsnmp Show detailed system information

Set SNMP server listening port (*)

snmp-server on | off

on SNMP Agent enabled off SNMP Agent disabled

Set the system contact

Set the system location

Defines the community name for receiving SNMP information (GET).

[community] community name [community] getcommunity NOTE: The get community name controls access to the SNMP Agent – the community in the request must match the getcommunity parameter. The default value is public.

Defines the community name for writing SNMP information (SET).

(*) Changing the port causes the SNMP Agent to restart. This might have a temporary effect also on trap notification. (**) Both parameters have a maximum length of 63 chars. If these parameters contain blanks or special characters they shall be specified in between double quotation marks (“...”) .

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 10 more labels / short text on this page
Command Parameters Description · snmpport [port] · [port] SNMP port · Enable/disable SNMP Agent · [contact] contact person · syscontact [contact] (**) · [location] location name · syslocation [location] (**) · [community] community name · setcommunity [community]
Page 22 of the GE Security System Keypad (1019070) user manual — 2.2.9 Trap command group
Page 22 · click to enlarge
Page 22

2.2.9 Trap command group

The trap command group allows to configure the trap sending functionality. With SNMP traps various systems can be notified in case of UPS events and alarms.

showtrap Show detailed trap configuration

Enable/disable send trap [RFC1628] function

sendtrap on | off

on Trap sending enabled off Trap sending disabled

Enable/disable send trap [GE-MIB] function

on Trap sending enabled off Trap sending disabled on | off

Add a trap address

[X.X.X.X] IP-address of the trap target v1 | v2 SNMP version (optional – default: v1) [community] community name (optional – default: public) [port] port to which the trap will be sent (optional – default 162)

[X.X.X.X] v1 | v2 [community] [port]

Delete a trap address

[X.X.X.X] IP-address of the trap target [X.X.X.X]

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 4 more labels / short text on this page
Command Parameters Description · sendgetrap · addtraptgt · deltraptgt
Page 23 of the GE Security System Keypad (1019070) user manual — 2.2.10 UPS command group
Page 23 · click to enlarge
Page 23

2.2.10 UPS command group

The UPS command group allows monitoring and configuration of the managed UPS system.

upsinfo (*) Show detailed UPS information

upstest (*) Start/Stop UPS tests

upscontrol (*) Control the UPS (1-ph/SP versions ONLY)

upsconfig (*) Configure UPS parameters

Set UPS attached device

[device] Device which is powered/protected by the UPS NOTE: Maximum length 63 chars. If this parameter contain blanks or special characters it shall be specified in between double quotation marks (“...”)

Set alarm delay time (1-ph/SP version ONLY)

[time] Time in seconds before alarm notification

Set retry delay time (1-ph/SP version ONLY)

[time] Time in seconds between re-connection attempts

Set retry count (1-ph/SP version ONLY)

[count] Number of re-connection attempts

Enable/disable the serialbypass functionality

serialbypass on | off

Show/Set card address on the IMV bus

[address] Card address in the range 0, 54-57

Enable/disable write commands to the UPS

Setting readonlymode to on will stop any write operation towards the UPS (the SNMP/Web adapter will effectively switch to read-only mode). The UPS Test, Control and Config web pages will not be shown in the navigator bar. [on | off] readonlymode

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 6 more labels / short text on this page
Command Parameters Description · attacheddevice [device] · alarmdelay [time] · retrydelay [time] · retrycount [count] · [address] cardaddress
Page 24 of the GE Security System Keypad (1019070) user manual — 2.2.11 Rccmd command group
Page 24 · click to enlarge
Page 24

(*) By running these commands, an interactive menu is launched – follow the on-screen instructions. The menu also provide a complete on-line help section. NOTE: When using the local serial connection, make sure that the terminal emulation is set to VT-100, otherwise the interactive menu may not be rendered correctly.

Caution! Some of these commands (particularly upscontrol and upsconfig) may inject commands and/or alter the UPS configuration with consequences on the UPS operation that may affect the load. Make sure you fully understand the effect on the UPS and on the load before injecting any of these commands. Make sure that it is safe to perform the desired operation for both the UPS and the load. 2.2.11 Rccmd command group

The rccmd command group allows to configure the RCCMD Server embedded in the SNMP/Web adapter.

Command Sub-command Parameters Description

showrccmd Shows the current RCCMD Server configuration

Enable/disable Network Shutdown function on|off on Network Shutdown enabled off Network Shutdown disabled)

Add an RCCMD Client

[ip] IP-address of the trap target [port] Port on which the client is listening [cond] Shutdown condition: aXX after XX minutes on battery bXX at XX min remain batt time

[ip] [port] [cond] rccmd

Send an RCCMD test message to a specific RCCMD client [num] test

[row] RCCMD client reference

Delete an RCCMD Client

[row] RCCMD client reference [num] del

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

add

Page 25 of the GE Security System Keypad (1019070) user manual — 2.2.12 Events command group
Page 25 · click to enlarge
Page 25

2.2.12 Events command group

The events command group controls the alarm notification via traps and/or e-mail.

Show the alarm notification configuration showevents

Configure the alarm notification for a specific event

[row] Alarm ID [e-mail] 0 = no e-mail notification for this alarm 1 = send e-mail on alarm (de)activation [trap] 0 = no trap sent for this alarm 1 = send trap on alarm (de)activation 2.2.13 Log command group

event [row] [e-mail] [trap]

The log command group allows to access the logs maintained by the SNMP/Web adapters.

Dump the System log to the console syslog

Dump the UPS log to the console upslog

Dump the System and UPS log to the FTP area logdump

Clear the UPS event log clearlog

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Command Parameters Description · Command Parameters Description

Page 26 of the GE Security System Keypad (1019070) user manual — 3.1 INTRODUCTION
Page 26 · click to enlarge
Page 26

3 WEB INTERFACE

3.1 INTRODUCTION

The SNMP/Web adapters provide a web interface by implementing an embedded web server. This interface allows to configure the adapter in order to monitor and manage the UPS. 3.1.1 Supported browsers

The use of non-standard / deprecated HTML tags has been avoided in order to guarantee compatibility with the most commonly used browsers. Although the web page rendering may not be identical in different browsers, it should always be visually consistent. The web interface has been tested using the following browsers:

  • Microsoft Internet Explorer 6.0, 7.0
  • Mozilla Firefox 1.5
  • Opera 9.01
  • Netscape browser 8.1 3.1.2 Initial web access

Enter the SNMP/Web adapter address in the web browser URL field to access the web interface. Either the adapter IP address or the hostname can be used (DNS resolution of the hostname must be ensured in the latter case). You will be presented with the web server initial page. Note that authentication (username / password pair) can be required. The only user configured by default is the supervisor with username /password set to ge and ge. In case any problem is encountered during web access refer to the Troubleshooting section. 3.1.3 Sample page

A sample web page is shown in the following picture:

GE Security System Keypad (1019070) — 3.1 INTRODUCTION diagram (page 26)
Fig. 17

Each page features a top navigation bar that directs to the main functionalities of the adapter. Additionally, there can be a side navigation menu that allows accessing different pages dealing with a specific functionality.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 27 of the GE Security System Keypad (1019070) user manual — 3.1.4 Saving the settings
Page 27 · click to enlarge
Page 27

3.1.4 Saving the settings

Apart from some network parameters, most setting are immediately active. However, the adapter will revert to the last save settings at reboot. Therefore, in order to permanently modify the SNMP/Web adapter setting, remember to save the configuration after every change. 3.2 NAVIGATION BAR

The top navigation bar features the following items:

  • Home : is the web server home page, showing basic information on the system and the network settings
  • UPS : access to the UPS section, for UPS monitor, control and configuration
  • System : adapter configuration (network settings, time management, etc.)
  • SMTP : configuration and control of the e-mail notification functionality
  • SNMP : configuration of the SNMP Agent and trap notification
  • Log : UPS log and System log
  • Utility : various utility applications (e.g. DNS lookup, media technology selection and verification) and service enable page
  • Save : save the current settings and/or force a reboot
  • User : user management The following paragraphs will detail each single section 3.3 UPS SECTION

The UPS pages can be split in two different sections: UPS monitoring and UPS control.

The Identification, Battery, Status, Alarms and PMAD pages are part of the UPS monitoring section. These pages allow to remotely access the UPS status and measurements. Please note that each specific UPS model may implement a subset of the available measurement – data not available for the specific UPS is marked as N/A.

The Test, Control and Config pages are part of the UPS control sections. Once again, the supported command and configuration options depend on the specific UPS model. Unsupported option are marked as N/A and cannot be set. It must be stressed that some of the command will affect the UPS and may cause alarms or UPS malfunction and eventually switch off the UPS (as is the case with the shutdown command).

The UPS Identification page shows the following information:

  • UPS Manufacturer
  • UPS Model
  • Serial Number
  • Software Version – the version of the main UPS control board firmware
  • Protocol Version – the version of the serial protocol used to communicate with the UPS
  • UPS Attached Devices – identification of the devices attached to the UPS output (as set by the administrator).

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 28 of the GE Security System Keypad (1019070) user manual — 3.3.2 Battery page
Page 28 · click to enlarge
Page 28

3.3.2 Battery page

The Battery page shows the following information.

The current status of the battery:

1. unknown
2. normal The remaining run-time on batteries is greater than the UPS low battery time (ref. UPS Config page)
3. low The remaining run-time is less than or equal the UPS low battery time (ref. UPS Config page)
4. depleted The battery would be unable to sustain the load, if mains power is lost

Seconds On Battery The time elapsed since the UPS switched to battery power (in seconds)

Estimated Minutes Remaining An estimate of the remaining run-time on batteries, under present load conditions (in minutes)

An estimate of the remaining battery charge (in percentage – 100% is full charge) Estimated Charge Remaining

The present battery voltage (in Volts) Battery Voltage

The battery flowing from/to the battery (in Amperes) Battery Current

The ambient temperature of the UPS batteries (in °C) Battery Temperature

The RSM ripple on the DC link (in Vrms) Battery Ripple

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Parameter Name Description · Battery Status

Page 29 of the GE Security System Keypad (1019070) user manual — 3.3.5 UPS PMAD page (3-ph version ONLY)
Page 29 · click to enlarge
Page 29

3.3.3 UPS Status page

The UPS status page shows the following information for each of the input / output / bypass lines.

Frequency Line frequency (in Hertz)

Voltage Line RMS voltage (in Volts)

Line RMS current (in Amperes) Current

Power / True Power Line True Power (in Watt)

Load % The power capacity presently being used (percentage) [Output only]

Volt min Lowest input voltage in the present time-period (in Volts) [Input only]

Lowest input voltage in the present time-period (in Volts) [Input only] Volt max

Also the following information is presented:

Input Line Bads Number of times the mains input went out-of-tolerance since UPS start-up

The present source of the output power Output Source

Finally, a 3-ph system featuring the PMAD functionality will also show the following:

The present output power factor. A positive value indicates an inductive load; while a negative value indicateS a capacitive load. Power factor

The output peak current Peak current

Share current In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The PMAD functionality detects the amount of share currents in a parallel system. Obviously, single system do not provide this functionality and will show this value as not available (N/A). 3.3.4 UPS Alarm page

This page presents the UPS active alarms (if any) with an indication of the time elapsed since the activation (in seconds). Once again, the supported alarms depend on the specific UPS model.

For the meaning of each specific alarm refer to the relevant UPS documentation.

3.3.5 UPS PMAD page (3-ph version ONLY)

This page presents diagnostic related readings from UPSs implementing the PMAD (Preventive Maintenance and Advanced Diagnostic) functionality. These include the following:

The remaining time before a check of the specific devices / system is required Life Time

Count of failures and transients on mains input and bypass Mains Statistics

Bus Communication Qty of UPSs: Number of UPSs as currently seen in the parallel system. (The reset button forces a refresh of the count and the display) Channel table: The table shows the actual communication status over the two redundant buses between the unit currently selected (in green bold) and other units.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 4 more labels / short text on this page
Parameter Name Description · Parameter Name Description · Parameter Name Description · Parameter Name Description
Page 30 of the GE Security System Keypad (1019070) user manual — 3.3.6 UPS Test page
Page 30 · click to enlarge
Page 30

3.3.6 UPS Test page

This page presents allows to initiate a specific UPS test, and reports the status of the last performed test (if any). The page includes a table with clear explanation of the test result reading. For an explanation of the various test procedures please refer to the applicable UPS documentation. 3.3.7 UPS Control page (1-ph/SP units ONLY)

The UPS control page mainly controls UPS shutdown and reboot behaviour. As previously stated, these commands will impact the UPS and may have effect on any load applied to the UPS. It is therefore important to fully understand the consequences of any settings performed through this page.

Shutdown type The action to be taken when the UPS is commanded to shutdown 1 – output The output of the UPS is switched off 2 – system The entire UPS system is switched off

Shutdown after delay Specifies a time (in seconds) after which the UPS will shutdown -1 disables the procedure 0 immediate shutdown

Specifies a time (in seconds) after which the UPS will start-up Startup after delay

-1 disables the procedure 0 immediate start-up

The UPS will shutdown immediately, and will remain off for the specified time (in seconds), after which the UPS will restart Reboot

-1 disables the procedure

On – the UPS will restart right after the shutdown Auto-Restart

Off – the UPS will not restart after the shutdown Caution! These commands may switch off the UPS output, therefore leaving the load with no power. Make sure you fully understand the effect on the UPS and on the load before injecting any of these commands. Make sure that it is safe to perform the described operation for both the UPS and the load. 3.3.8 UPS Config page

The page lists the main UPS configuration parameters. Normally, these parameters are pre-configured at the factory and there is no need to change them. Furethermore, forcing an incorrect configuration may impair the UPS functionalities and severly affect the load. It is therefore recommended not to alter any configuration settings unless informed and instructed to do so.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Parameter Name Description

Page 31 of the GE Security System Keypad (1019070) user manual — 3.4 SYSTEM SECTION
Page 31 · click to enlarge
Page 31

3.4 SYSTEM SECTION

3.4.1 Network page

Network configuration of the card – refer to the NETWORK CONFIGURATION chapter within this manual. Note that the settings on this page will only take effect after a reboot of the card. 3.4.2 Date&Time page

Through this page it is possible to configure the adapter date and time settings. The SNMP/Web adapter features an internal real-time-clock, and provides different ways to synchronise its clock with the actual time:

  • NTP server : the card will periodically re-synch its internal date and time with the NTP server
  • Manual : the card date and time are set by the user
  • Browser : the card date and time will synch with the browser time Regardless of the chosen configuration, make sure the correct timezone is selected. The timezone setting also affects autocorrection for the daylight saving time. 3.4.3 RCCMD page

This page shows the current configuration for the Network Shutdown (RCCMD) functionality. The various RCCMD clients are listed, with three action buttons:

  • Edit : edit the RCCMD Client configuration
  • Test : send an RCCMD Test Message to the Client
  • Del : delete the RCCMD Client New RCCMD Clients can be added with the Add button. The page to Add/Edit RCCMD clients requires to specify the following information:
  • Client : RCCMD Client IP Address or hostname
  • Port : RCCMD Port on the Client, default is 6003
  • Condition : three different shutdown conditions can be chosen:

o After X minutes on battery o At X minutes remaining of battery autonomy o When the UPS signals a Low Battery condition NOTE: Although the web interface accepts hostnames to identify RCCMD Clients, it is strongly recommended to identify the clients with their IP address. Using symbolic hostnames may cause the network shutdown to fail in case the DNS server is not available, unreachable or mis-configured 3.4.4 Password page

This page allows the currently connected user to modify its password. Clearly, this page only allows modification to the current users. The account of other users can be managed only by the uspervisor users in the User section. NOTE: The password length is limited to 8 chars.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 32 of the GE Security System Keypad (1019070) user manual — 3.5.2 Trap settings page
Page 32 · click to enlarge
Page 32

3.4.5 Configuration page

In this page, the SNMP/Web adapter configuration file is shown in a text area. The configuration file can be exported by pressing the Highlight button and copying the selected text (e.g. CTRL+C) to a separate application. 3.4.6 Upgrade page

This page shall only be accessed when the SNMP/Web adapter SW is to be upgraded. Refer to the section for details on the SW upgrade process. NOTE: Use only GE officially released SW. Only perform the SW upgrade when requested to do so by GE. 3.5 SNMP SECTION

The SNMP section deals with SNMP and trap configuration. 3.5.1 SNMP settings page

The most relevant SNMP settings are the following:

Set SNMP server listening port. Default port is 161. Port Number

Defines the community name for receiving SNMP information (GET). The get community name controls access to the SNMP Agent – the community in the request must match the getcommunity parameter. The default value is public.

Defines the community name for writing SNMP information (SET). The set community name controls access to the SNMP Agent – the community in the request must match the setcommunity parameter. The default value is private.

3.5.2 Trap settings page

This page allows to configure up to 20 recipients of SNMP traps. The most relevant settings are the following:

IP-address of the trap target Trap destination

Community name (optional – default is public) Community

Controls SNMP trap versionIf unchecked, v1 traps are sent (default) If checked, V2 traps are sent

Port to which the trap will be sent (optional – default 162) Port 3.5.3 Alarm notification page

This page is used to configure the alarm notification via trap and/or e-mail. Every alarm is listed, and the user may enable the notification via trap and/or e-mail upon alarm (de)activation.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 4 more labels / short text on this page
Parameter Name Description · Get Community · Set Community · Parameter Name Description
Page 33 of the GE Security System Keypad (1019070) user manual — 3.6 SMTP SECTION
Page 33 · click to enlarge
Page 33

3.6 SMTP SECTION

The SMTP page controls the e-mail notification functionality. 3.6.1 SMTP configuration page

The basic SMTP settings are the following:

SMTP Server Hostname or IP-address of the SMTP server

Sender name The MAIL FROM field of the mail message

The RCPT TO field of the mail message Recipent e-mail address If the SMTP server requires authentication, the following sections shall also be defined.

Username for SMTP server authentication Account

Password for SMTP server authentication Password 3.6.2 Alarm notification page

This page is used to configure the alarm notification via trap and/or e-mail. Every alarm is listed, and the user may enable the notification via trap and/or e-mail upon alarm (de)activation. 3.7 LOG SECTION

This section offers access to the System and the UPS log. The System log collects information on user activity, while the UPS log lists UPS alarms. Both the logs can be exported by copying the relevant text from the page (Highlight button gollowed by CTRL+C). 3.8 UTILITY SECTION

This section includes some useful tools for troubleshooting and configuration:

  • DNS lookup : a tool for verifying DNS server configuration, useful for troubleshooting DNS problems
  • Mii-tool : shows the media technology currently selected / negotiated
  • Speed/Duplex : set the media technology to be used / advertised.
  • As most network devices, SNMP/Web adapters use an auto-negotiation protocol ( Auto setting) to communicate what media technologies they support, and then select the fastest mutually supported media technology. Some passive devices, such as single-speed hubs, are unable to auto-negotiate. To handle such devices, the SNMP/Web adapter can be forced to operate in one of the following modes: 100baseTx-FD , 100baseTx-HD , 10baseT-FD and 10baseT-HD .
  • Service : enable / disable the various service interfaces provided over the network
  • CA Root Certificate : link to the Certification Authority root certificate for download an installation in the Trusted CA repository on the selected browser. Refer to the Encryption section for details.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Parameter Name Description · Parameter Name Description

Page 34 of the GE Security System Keypad (1019070) user manual — 3.9 SAVE SECTION
Page 34 · click to enlarge
Page 34

3.9 SAVE SECTION

This section allows to save the current settings to non-volatile memory (Save) and/or to reboot the adapter (Reboot). Remember that the SNMP/Web adapter will revert to the last saved settings at reboot. Therefore, in order to permanently modify the settings the configuration must be saved. 3.10 USER SECTION

This section offers access to the user management web page. Note that this page becomes operative only for the supervisor user (the only user enabled to perform user management).

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 35 of the GE Security System Keypad (1019070) user manual — 4 SNMP AGENT
Page 35 · click to enlarge
Page 35

4 SNMP AGENT

The SNMP/web adapters implement an SNMP Agent providing access to OIDs according to the MIB structure, and may generate traps at the occurrence of specific events. This allows one or more NMSs (Network Management Systems) to monitor, manage and control the UPS. The SNMP Agent complies with the standard UPS-MIB as specified in RFC1628. Limited to the 3-ph SNMP/Web plug-in adapter, additional information is available with the GESingle and GEParallel MIBs. The SNMP/Web adapter implements both SNMP v1 and SNMP v2 protocols. Always remember that with these protocols the information travel on the network in plain text. It is therefore recommended to disable the SNMP Agent when this functionality is not used. Refer to the “Security” section of this manual for further details. 4.1 MIB STRUCTURE

RFC1628 MIB is available in the upsMIB group. Additional UPS information is available in the GE MIB under the geUPS group (limited to the 3-ph SNMP/Web plug-in adapter). 4.2 RFC1628 MIB OBJECTS

iso(1).org(3).dod(6).internet(1)

iso(1).org(3).dod(6).internet(1)

The SNMP/Web adapters support the following RFC1628 Objects: OIDs TRAPS & ALARMS ==== upsIdent Group ==== upsIdentManufacturer upsIdentModel upsIdentUPSSoftwareVersion upsIdentAgentSoftwareVersion upsIdentName upsIdentAttachedDevices ==== uspBattery Group ==== upsBatteryStatus upsSecondsOnBattery upsEstimatedMinutesRemaining upsEstimatedChargeRemaining upsBatteryVoltage upsBatteryCurrent upsBatteryTemperature

==== upsTrap Group ==== UpsTrapOnBattery UpsTrapTestCompleted UpsTrapAlarmEntryAdded UpsTrapAlarmEntryRemoved ==== upsWellKnownAlarms group ==== UpsAlarmBatteryBad UpsAlarmOnBattery UpsAlarmLowBattery UpsAlarmDepletedBattery UpsAlarmTempBad UpsAlarmInputBad UpsAlarmOutputBad UpsAlarmOutputOverload UpsAlarmOnBypass

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 16 more labels / short text on this page
mgmt(2) · mgmt(2) · mib-2(1) · mib-2(1) · upsMIB(33) · upsMIB(33) · private(4) · private(4) · enterprises(1) · enterprises(1) · imv(818) · imv(818) · geHardware(1) · geHardware(1) · geUPS(1) · geUPS(1)
Page 36 of the GE Security System Keypad (1019070) user manual — 4 SNMP AGENT
Page 36 · click to enlarge
Page 36

OIDs TRAPS & ALARMS ==== upsInput Group ==== upsInputLineBads upsInputNumLines upsInputFrequency upsInputVoltage upsInputCurrent upsInputTruePower ==== upsOutput Group ==== upsOutputSource upsOutputFrequecny upsOutputNumLines upsOutputVoltage upsOutputCurrent upsOutputPower upsOutputPercentLoad ==== upsBypass Group ==== upsBypassFrequency upsBypassNumLines upsBypassLineIndex upsBypassVoltage upsBypassCurrent upsBypassPower ==== upsAlarm Group ==== upsAlarmsPresent ==== upsTest Group ==== upsTestID upsTestSpinLock upsTestResultSummary upsTestResultsDetails upsTestStartTime upsTestElapsedTime ==== upsControl Group ==== upsShutdownType upsShutdownAfterDelay upsStartUpAfterDelay upsRebootWithDuration upsAutoRestart

UpsAlarmBypassBad UpsAlarmOutputOffAsRequested UpsAlarmUpsOffAsRequested UpsAlarmChargerFailed UpsAlarmUpsOutputOff UpsAlarmUpsSystemOff UpsAlarmFanFailure UpsAlarmFuseFailure UpsAlarmGeneralFault UpsAlarmDiagnosticTestFailed UpsAlarmCommunicationsLost UpsAlarmAwaitingPower UpsAlarmShutdownPending UpsAlarmShutdownImminent UpsAlarmTestInProgress UpsAlarmReceptacleOff

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 37 of the GE Security System Keypad (1019070) user manual — 4.3 GE MIB OBJECTS
Page 37 · click to enlarge
Page 37

4.3 GE MIB OBJECTS

GE provides private MIBs, which enhance the UPS information available over SNMP interface. These MIBs are only supported on 3-ph SNMP/Web plug-in adapter. Two different version of the GE private MIB exist:

  • GE Single MIB: to be used for monitoring of a 3-ph UPS is single unit configuration
  • GE Parallel MIB: to be used for monitoring of a 3-ph parallel UPS system The MIB structure is shown in the following picture. The geGenericUPS group provides information on the unit in stand-alone configuration or on the overall system in a parallel configuration. The geFirstUPS … geEightUPS groups provide information on the units that are part of a parallel configuration. For each of these groups the 3-ph SNMP/Web plug-in adapter supports the following objects. (Objects marked with [*] do not have a RFC1628 correspondence) OIDs TRAPS & ALARMS ==== upsIdent Group ==== upsIdentManufacturer upsIdentModel upsIdentUPSSoftwareVersion upsIdentAgentSoftwareVersion upsIdentName upsIdentAttachedDevices upsIdentsUPSSerialNumber [*] upsIdentComProtVersion [*] upsIdentOperatingTime [*] ==== uspBattery Group ==== upsBatteryStatus upsSecondsOnBattery upsEstimatedMinutesRemaining upsEstimatedChargeRemaining upsBatteryVoltage upsBatteryCurrent upsBatteryTemperature upsBatteryRipple [*] ==== upsInput Group ==== upsInputLineBads upsInputNumLines upsInputFrequency

geUPS (1.3.6.1.4.1.818.1.1)

geUPS (1.3.6.1.4.1.818.1.1)

==== geUPSTraps & upsWellKnownAlarms group ==== upsAlarmBatteryBad upsAlarmOnBattery upsAlarmLowBattery upsAlarmDepletedBattery upsAlarmTempBad upsAlarmInputBad upsAlarmOutputBad upsAlarmOutputOverload upsAlarmOnBypass upsAlarmBypassBad upsAlarmOutputOffAsRequested upsAlarmUpsOffAsRequested upsAlarmChargerFailed upsAlarmUpsOutputOff upsAlarmUpsSystemOff upsAlarmFanFailure

upsAlarmFuseFailure upsAlarmGeneralFault upsAlarmDiagnosticTestFailed upsAlarmCommunicationsLost upsAlarmAwaitingPower upsAlarmShutdownPending upsAlarmShutdownImminent

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 12 more labels / short text on this page
geGenericUPS(10) · geGenericUPS(10) · geFirstUPS(11) · geFirstUPS(11) · geSecondUPS(12) · geSecondUPS(12) · Parallel system only · Parallel system only · … · … · geEigthUPS(18) · geEigthUPS(18)
Page 38 of the GE Security System Keypad (1019070) user manual — 4.3 GE MIB OBJECTS
Page 38 · click to enlarge
Page 38

upsInputVoltage upsInputCurrent upsInputTruePower upsInputVoltageMin [*] upsInputVoltageMax [*] ==== upsOutput Group ==== upsOutputSource upsOutputFrequecny upsOutputNumLines upsOutputVoltage upsOutputCurrent upsOutputPower upsOutputPercentLoad upsOutputPowerFactor [*] upsOutputPeakCurrent [*] upsOutputShareCurrent [*] ==== upsBypass Group ==== upsBypassFrequency upsBypassNumLines upsBypassLineIndex upsBypassVoltage upsBypassCurrent upsBypassPower ==== upsAlarm Group ==== upsAlarmsPresent upsAlarmMaskA [*] ==== upsTest Group ==== upsTestID upsTestSpinLock upsTestResultSummary upsTestResultsDetails upsTestStartTime upsTestElapsedTime

upsAlarmTestInProgress upsAlarmReceptacleOff upsAlarmHighSpeedBusFailure [*] upsAlarmHighSpeedBusJACRCFailure [*] upsAlarmConnectivityBusFailure [*] upsAlarmHighSpeedBusJBCRCFailure [*] upsAlarmCurrentSharing [*] upsAlarmDCRipple [*]

Once again, some objects may not be available over the full-range of 3-ph UPSs as these will depend on the UPS model, configuration, enabled features, etc.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 39 of the GE Security System Keypad (1019070) user manual — 5 NETWORK CONFIGURATION
Page 39 · click to enlarge
Page 39

5 NETWORK CONFIGURATION

The SNMP/Web adapter network interface is very flexible and can be configured for operation in various environments. This section details all possible network configuration combinations, while it is recommended to refer to Console/Web interface sections for the specific configuration commands / menus. 5.1 ETHERNET CONNECTION

As most advanced network devices, SNMP/Web adapters use an autonegotiation protocol to communicate what media technologies are supported, and then select the fastest mutually supported media technology. In this context, media refers to a 10baseT/100baseTx Ethernet connection in Half-Duplex (HD) or Full- Duplex (FD) mode. The SNMP/Web adapters advertise and support the following media:

  • 100baseTx-FD
  • 100baseTx-HD
  • 10baseT-FD
  • 10baseT-HD This autonegotiation feature is enabled by default. However, some passive devices, such as singlespeed hubs, are unable to autonegotiate. To handle such devices, the SNMP/Web adapter can be forced to operate in one specific mode, instead of autonegotiating. 5.2 TCP/IP CONFIGURATION

TCP/IP configuration refers to the settings needed by an SNMP/Web adapter to operate in a TCP/IP network. The selection of the boot method is critical for successful SNMP/Web adapter configuration. The SNMP/Web adapters support the following boot methods:

  • Static IP
  • BOOTP
  • DHCP The default configuration is DHCP support. 5.2.1 Static IP address

In this case, the TCP/IP settings are manually configured on the adapter, and stored in non-volatile memory. Particularly, the following need to be specified:

  • IP address : IP address of the SNMP/Web adapter
  • Subnet Mask
  • Default gateway : IP address of the default gateway NOTE : These settings are only available when the boot method is set to Static IP . 5.2.2 BOOTP / DHCP

In this case, the SNMP/Web adapter automatically obtains the TCP/IP settings respectively from a BOOTP or a DHCP server. The default configuration for the SNMP/Web adapters is DHCP support. If the adapter IP-address is used by other network nodes for accessing UPS information (e.g. NMS systems), make sure the DHCP server assigns a fixed IP to the SNMP adapter. NOTE: For details on BOOTP and DHCP protocol refer respectively to RFC951 and RFC2131.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 40 of the GE Security System Keypad (1019070) user manual — 5.3 DNS CONFIGURATION
Page 40 · click to enlarge
Page 40

5.3 DNS CONFIGURATION

DNS configuration affects the SNMP/Web adapter ability to resolve symbolic hostnames to IP addresses, and may impact other functionality (such as e-mail sending, for example): The SNMP/Web adapters can be configured to automatically obtain DNS server address (e.g. Primary and Secondary DNS server as specified in the DHCP response). This is the defaults setting. Alternatively, the IP address of the DNS servers may be specified manually. The adapters also offer a DNS lookup feature, which allows verification of the DNS setting by sending a DNS query.

The SNMP/Web adapter is configured with a hostname: a fully qualified domain name for the adapter. The adapter will always include this information in the relevant communication to the DHCP server (option 12 – host name field). The DHCP server may use this information to update the DNS server, so that the adapter will be accessible using its domain name. The adapter can also be configured to use the hostname as received from the DHCP server. This is NOT the default behaviour and must be explicitly enabled through the console interface using the dhcphost command.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 41 of the GE Security System Keypad (1019070) user manual — 6 MULTI-SERVER NETWORK SHUTDOWN (RCCMD)
Page 41 · click to enlarge
Page 41

6 MULTI-SERVER NETWORK SHUTDOWN (RCCMD)

The SNMP/Web adapters include a module for Multi-Server Network Shutdown. This module allows the configuration of a shutdown strategy for several servers powered by the UPS when the batteries are running low following a prolonged mains failure. 6.1 NETWORK SHUTDOWN WITH RCCMD

RCCMD (Remote Console Command) is a mechanism that allows the execution of commands on remote systems. With the SNMP/Web adapters this mechanism is used to shutdown servers powered by the UPS. The SNMP/Web adapter acts like the master (RCCMD Sender) while the servers and remote systems act as slaves (RCCMD Listener). RCCMD is based on standard TCP/IP network protocols, therefore allowing the shutdown of servers running different operating systems and operating in a heterogeneous network. RCCMD does not include the command that is to be executed in the sending process but instead deposits the command with the receiving process. This provides additional security, as the receiving process may check which network node sent the RCCMD-signal and determine whether to process it. Both the SNMP/Web adapters and the servers need to be correctly configured in order to use the Network Shutdown functionality. 6.1.1 Set-up and Configuration of controlled Servers

The installation on the controller servers of the RCCMD SW (known as RCCMD Listener or RCCMD Client module) is clearly a prerequisite. A detailed description of the installation and configuration steps is out of the scope of this document – for details please refer to the applicable product documentation (User Manual). However, there are a few general recommendations. First of all, the RCCMD Client software is a licensed software. A license code can be used for only one installation. If more servers are to be included in the shutdown process, more licenses are needed. For increased safety, a list of trusted RCCMD Servers can be defined in the RCCMD Client. This way, the RCCMD Client will accept only messages coming from the trusted Servers, and will discard any other RCCMD message. If such functionality is used, the SNMP/Web adapter IP address must be added to the list of trusted RCCMD Servers. Finally, a shutdown routine needs to be defined in each remote system. This may be a batch file, a shell script or other. It shall include all commands for a graceful shutdown of the system. 6.1.2 Configuration of the SNMP/Web adapter

The SNMP/Web adapter can be configured using the web interface or the command-line console. First of all, in order to use the RCCMD Sender embedded in the SNMP/Web adapter the Network Shutdown functionality must be enabled. Then, the various servers must be added to the list of RCCMD Clients on the SNMP/Web adapter. For each client, the Hostname or IP Address and the port on which the RCCMD process will be listening need to be specified (the standard RCCMD port is 6003). NOTE: Although it is possible to identify the servers with their hostname, it is strongly recommended to specify their IP addresses. Using symbolic hostnames may cause the network shutdown to fail in case the DNS server is not available, unreachable or mis-configured.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 42 of the GE Security System Keypad (1019070) user manual — 6.1.3 Network configuration
Page 42 · click to enlarge
Page 42

Finally, it is possible to configure the actual condition that triggers the RCCMD Shutdown command:

  • After X minutes that the UPS is running on battery
  • At X minutes of estimated minutes remaining of battery autonomy
  • When the UPS signals a low battery condition Note that a low battery condition will force the shutdown of the configured RCCMD Clients regardless of the chosen shutdown condition. The configuration of the clients can be tested – the SNMP/Web adapter includes a Test function. This allows to send either a test message to the Client, or to force a shutdown. It is important to monitor both the messages returned from the SNMP/Web adapter and the actual result on the Client. Depending on the configuration, the SNMP/Web adapter may successfully send the message, but this can be ignored by the RCCMD Client. 6.1.3 Network configuration

The RCCMD Shutdown command travels across the network using standard TCP/IP protocols. Therefore, the network configuration may affect the Shutdown process. Particularly:

  • As stated above, the RCCMD Clients allow the definition of a list of trusted RCCMD Servers (that is, RCCMD Servers allowed to send a shutdown command). When this safety feature is used, the SNMP/Web adapter IP address must be added to the list of trusted RCCMD Servers for each RCCMD Client. Therefore, the SNMP/Web adapter should be assigned a static IP address when possible. If a DHCP Server is used, it should be configured so that the SNMP/Web adapter is always assigned the same address.
  • The various servers to be shutdown must be added to the list of RCCMD clients on the SNMP/Web adapter. Although it is possible to identify the servers with their hostname, it is strongly recommended to specify their IP addresses even if DNS hostname resolution is configured. The network shutdown may fail if the DNS server is not available or unreachable.
  • The entire network infrastructure, including routers, switches, hubs, etc. must be powered by the UPS. Otherwise it may not be possible to reach all clients during Network Shutdown. 6.1.4 RCCMD Shutdown

When the configured condition is met, the SNMP/Web adapter will send an RCCMD Shutdown command to the configured RCCMD Clients. This will launch the shutdown routine as configured in the Client. In case of problems with the network communication, the SNMP/Web adapter will attempt to issue the RCCMD Shutdown command multiple times. However, after 30s the SNMP/Web adapter will assume a successful RCCMD Shutdown and further communication to the RCCMD Client will stop.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 43 of the GE Security System Keypad (1019070) user manual — 6.2 RCCMD CLIENT RELAY
Page 43 · click to enlarge
Page 43

6.2 RCCMD CLIENT RELAY

The maximum number of RCCMD Clients that can be managed by the SNMP/Web adapter is limited. In order to reach a higher number of RCCMD Clients, one or more of these clients can be configured to operate as relays. Basically, the RCCMD Client needs to be configured so that it will execute a batch or script file that issues more RCCMD Shutdown commands. The following sample batch file lets the RCCMD Client acts as a relay station:

@ECHO OFF SET PATH=C:\RCCMD\ # RCCMD Relay # This batch sends RCCMD Shutdown commands to the following IP addresses rccmd –s –a 191.168.200.5 rccmd –s –a 191.168.200.6 # … the list can be continued … # At last, force shutdown of the local machine ExitWin.exe shutdown force @CLS This procedure can also be used for a low number of RCCMD servers, as it may be easier to configure the Network Shutdown this way rather than through the SNMP/Web adapter, especially when a number of servers need to be shutdown simultaneously. Clearly, the RCCMD Client acting as Relay becomes an important link in the Network Shutdown process, as it both receives and sends RCCMD Shutdown commands. This node and related network connectivity (routers, switches and hubs) shall therefore be protected by the UPS.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 44 of the GE Security System Keypad (1019070) user manual — 7 SECURITY
Page 44 · click to enlarge
Page 44

7 SECURITY

As any other device connected to a network, the adapters are exposed to security threats. This section details the advanced security features provided by the SNMP/Web adapters. Users should use the information provided in this section to correctly configure the cards and implement all security features deemed appropriate to the installation environment. 7.1 USER AUTHENTICATION & AUTHORISATION

In this context, authentication means establishing the digital identity of anyone attempting to access the adapters though one of the available interfaces. Most of the supported protocols implement a username/password pair as a mean for user identification. This is different from authorisation, which means verifying whether a user is allowed to have access to data or specific services. The SNMP/Web adapters allow making full use of both protection mechanisms. 7.1.1 User Management

The adapters come with a predefined supervisor user, whose default username and password are ge and ge. New users can then be created using either the console or the web interface. NOTE Only the supervisor user can create new users. To create a new user, the following information shall be specified:

  • Username / password
  • User class (access rights)
  • Available services 7.1.2 User class

Users are divided in three separate classes based on access rights. Supervisor Predefined user; it can be renamed but not deleted; it cannot be created (only one supervisor user is allowed). This user has all access rights. It is the only user who can perform user management (creation/deletion of users). Read/write access (rw)

Access with read/write rights. Can access and modify all setting with the exception of user management. These access rights should be restricted to professional users (e.g. Network Administrators). Read-only access (ro)

Access only for reading. Can access most settings but cannot modify them. Most users are expected to be created with this profile. 7.1.3 Selective service activation

The SNMP/Web adapters allow selective service activation – that is, the various interfaces can be enabled on a user basis. For each user, access to the following services can be enabled: http Web interface Controls access with HTTP and HTTPS protocols telnet Remote console interface Controls access with Telnet and SSH (Secure SHell) protocols ftp File transfer Controls access with FTP and SFTP (Secure FTP) protocols

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 45 of the GE Security System Keypad (1019070) user manual — HTTPS (SSL) Authentication via user/pwd pair Encrypted communication 7.3 ENCRYPTION
Page 45 · click to enlarge
Page 45

7.2 SERVICES (ACCESS METHODS)

The table below lists the available services (access methods), highlighting the major security features for each interface.

Interface Access methods Security features Local console interface Serial cable Authentication via user/pwd pair Telnet Authentication via user/pwd pair Plain text Remote console interface

SSH (Secure SHell) Authentication via user/pwd pair Encrypted communication SNMP Agent SNMP Community Name Plain text FTP Authentication via user/pwd pair Plain text File transfer

SFTP (SSH FTP) Authentication via user/pwd pair Encrypted communication HTTP Authentication via user/pwd pair Plain text Web interface

HTTPS (SSL) Authentication via user/pwd pair Encrypted communication 7.3 ENCRYPTION

As stated above, the SNMP/Web adapter offers interfaces providing encryption for protecting data confidentiality and integrity, and particularly the following:

  • SSH (Secure Shell)
  • SFTP (SSH File Transfer Protocol)
  • HTTPS In this context, encryption is based on public-key cryptography schemes. Normally, the SNMP/Web adapters will be delivered already configured with all applicable keys and certificates – should the adapter miss these information it will generate them at first start-up (this operation may take some time). The length of the keys used for encryption is 1024 bits, providing complex encryption and a higher level of security. 7.3.1 SSH and SFTP

SSH allows running terminal sessions to the SNMP/Web adapter over a secure channel. SSH uses public- key cryptography. The SSH server is authenticated using a host key as identification. Most SSH clients display the host key fingerprint at the start of the SSH session. Below is an example from a popular SSH client (putty):

GE Security System Keypad (1019070) — HTTPS (SSL) Authentication via user/pwd pair Encrypted communication 7.3 ENCRYPTION diagram (page 45)
Fig. 18 · HTTPS (SSL) Authentication via user/pwd pair Encrypt…

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 46 of the GE Security System Keypad (1019070) user manual — 7.2 SERVICES (ACCESS METHODS)
Page 46 · click to enlarge
Page 46

The fingerprint may be checked against the information provided by the SNMP/Web adapter to confirm to SSH server identity. On the console interface inject the ssh-fingerprint command. Below is a sample output of the ssh-fingerprint command: GEDE> ssh-fingerprint 1024 6e:07:31:58:16:91:ae:2e:43:6f:03:64:94:57:55:6d ssh_host_rsa_key.pub 1024 06:97:69:97:cd:93:1b:b6:29:ca:34:e5:8c:35:7c:6e ssh_host_dsa_key.pub 1024 d1:9b:50:13:b3:e3:98:8e:8c:76:49:14:be:21:ed:b3 ssh_host_key.pub The output can be interpreted as follows:

Key SSH version Cryptography algorithm

ssh_host_rsa_key.pub v2 RSA

ssh_host_dsa_key.pub v2 DSA

ssh_host_key.pub v1 RSA It can be seen in the above example that the fingerprint shown by SSH matches the RSA key for SSH v2 on the ssh-fingerprint output.

The SNMP/Web adapter supports both version 1 and version 2 of the SSH protocol. It is recommended to use SSH v2 (if possible), as SSH v1 is generally considered obsolete.

On the other hand, SFTP is a file transfer protocol providing secure transfer. It is used in conjunction with the SSH protocol, as SFTP does not provide security by itself but expects the underlying protocol to provide that. Therefore, the key fingerprint can be verified exactly in the same way as with SSH. Below is a sample from a popular SFTP client (sftp):

GE Security System Keypad (1019070) — 7.2 SERVICES (ACCESS METHODS) diagram (page 46)
Fig. 19

It can be seen that the key fingerprint is exactly the same.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 47 of the GE Security System Keypad (1019070) user manual — 7.3.2 SSL Certificates
Page 47 · click to enlarge
Page 47

7.3.2 SSL Certificates

HTTPS is not a protocol itself, but it actually refers to HTTP communication over SSL (Secure Sockets Layer) connection. HTTPS uses public-key cryptography to protect the communication. With HTTPS, the server sends back its identification in the form of a digital certificate. The certificate usually contains the server name, the trusted certificate authority (CA), and the server's public encryption key.

The server certificate includes a digital signature from a certification authority. Each browser is normally equipped with a set of CA root certificates of commercial authorities. The web browsers perform a set of verifications over the digital certificate in order to validate the certificate and start the HTTPS communication. The main checks are substantially the following:

  • The client verifies that the issuing Certificate Authority (CA) is on its list of trusted CAs.
  • The client checks the server's certificate validity period Further to this, the client may compare the actual DNS name of the server to the DNS name on the certificate (though this last point may be browser dependent). Below is a sample of the results of these checks, when browser attempts to establish an HTTP connection to the web server embedded in the SNMP/Web adapter (the sample is take from Internet Explorer, but similar indications can be obtained with the most common browsers):
GE Security System Keypad (1019070) — 7.3.2 SSL Certificates diagram (page 47)
Fig. 20 · 7.3.2 SSL Certificates

First of all, in order to verify the actual certificate, its fingerprint (sometimes also knows as thumbprint) can be checked against the one provided by the SNMP/Web adapter. Particularly, select View Certificate and look for the fingerprint/thumbprint:

GE Security System Keypad (1019070) — 7.3.2 SSL Certificates diagram (page 47)
Fig. 21 · 7.3.2 SSL Certificates

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 48 of the GE Security System Keypad (1019070) user manual — 7.3.2 SSL Certificates
Page 48 · click to enlarge
Page 48

On the console interface inject the ssl-fingerprint command. Below is a sample output of the ssl- fingerprint command:

GEDE> ssl-fingerprint MD5 Fingerprint=8F:A1:CE:8B:B3:04:E7:07:90:6D:02:77:6F:EE:9E:22 SHA1 Fingerprint=F5:D2:CA:27:BF:DA:98:31:39:6F:18:8C:C5:9C:BC:6C:D3:62:15:AC

It can be seen that the thumbprint shown by the web browser (with thumbprint algorithm shown as sha1) matches the SHA1 fingerprint as shown by the ssl-fingerprint command.

Furthermore, the SNMP/Web adapters are provided with two different certificates: the server certificate and the CA Root Certificate (the latter has been used to sign the server certificate). The server certificate does not have the digital signature of a commercial CA, trusted by the browser. By installing the CA Root Certificate in the trusted CA repository, the web browser will not show the security warning about trusting the Certificate Authority.

The CA Root Certificate can be downloaded from the embedded web server (in the Utility section), and then it can be installed in the trusted CA repository.

Finally, the server certificate’s common name will not match the DNS name or the IP address of the SNMP/Web adapter. Although the communication is secure, with the adapter controlling the access to the web interface and the client being able to verify the fingerprint/thumbprint of the certificate, the browser may still issue a warning.

In order to clear this final warning the user may generate a new server certificate so that the common name matches the DNS name / IP address of the SNMP/Web adapter. The server certificate is generated by injecting the makecert <sitename> command over the console interface (this command is available only to the supervisor), when the <sitename> parameter must obviously match the DNS name / IP address of the adapter. In order to start using the new certificate the SNMP/Web adapter must be rebooted.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 49 of the GE Security System Keypad (1019070) user manual — 7.4 CUSTOMER RESPONSIBILITY
Page 49 · click to enlarge
Page 49

7.4 CUSTOMER RESPONSIBILITY

As shown above, the SNMP/Web adapters implement advanced security features. Nevertheless, achieving complete security protection requires the introduction of a comprehensive security program. This section lists some good practices in network security that customers are recommended to adopt. 7.4.1 Physical security

Most of the security features would prove useless if physical access to the equipment is uncontrolled. In fact, physical access is probably the major security hazard for a site. This problem may be efficiently tackled by installing the equipment in a secure area and by implementing access control policies. 7.4.2 Changing default configuration

It is recommended that users change the adapter default configuration at their very first access. Particularly, it is recommended to focus on the following settings:

  • The default username and password for the superuser are ge and ge . It is recommended to change default username and password (by configuring new and unique ones) at the initial card configuration
  • Any service is associated with a specific port. The default configuration uses the standard port for each protocol (e.g. 161 for SNMP). If the user specifies a non-standard port for a service this increases security by hiding the relevant interface to malicious users.
  • Further to this, SNMP access is controlled by read and set community settings. These respectively default to public and private . Once again, changing these settings may help in increasing security. It is clear that username, password and service configuration must remain secret in order to provide an efficient security protection. If this information becomes public the entire authentication method loses effectiveness. 7.4.3 User & Service management

As shown above, the SNMP/Web adapters offer advanced user management features, by offering different access rights and allowing selective activation of services. It must be noted that every running service exposes the system to a possible attack. Minimising the number of running services may increase overall protection. It is therefore recommended to disable unused services. 7.4.4 Encryption

In most network protocols, sensitive information (e.g. username/password pairs) is transmitted over the network as plain text. This may not be a problem in most installations, but it may become critical when malicious users can gain access to the network traffic. The introduction of encryption provides and higher degree of security by ensuring that exchanged data cannot be intercepted. The SNMP/Web adapters provide an encryption-protected alternative for the main access methods:

  • Web interface: use HTTPS (SSL – Secure Socket Layer) protocol
  • Remote console interface: use SSH (Secure Shell) protocol
  • File transfer: use SFTP (Secure FTP) 7.4.5 Firewalls

It should be now clear that although some protocols and some access methods might provide a higher degree of security, every customer is encouraged to implement a comprehensive security scheme, of which the SNMP/Web adapters are only a single node. The partition of the network in sub-networks and the introduction of firewalls with stringent rules are a critical component in the global security program.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 50 of the GE Security System Keypad (1019070) user manual — 8.1 SYSTEM TIME
Page 50 · click to enlarge
Page 50

8 OTHER FUNCTIONALITIES

8.1 SYSTEM TIME

The SNMP/Web adapter provides means to maintain the system time. Particularly, the adapter will maintain an internal clock when powered-up, while an RTC with battery back-up will hold date/time information when off (or during power-cycles). This system offers a sufficient accuracy in the short term. However, in the longer term the time drift may become significant. For best results it is recommended to configure the adapter for communication with an NTP server. This forces the system time to be synchronised with an external source, and it will ensure long-term date/time accuracy. 8.2 SERIAL BY-PASS (1-PH/SP VERSION ONLY)

The SNMP/Web adapter offers some diagnostic and UPS Service functionalities. These features are not targeted to the end user. The serial bypass is one of these features, and it is introduced here only for completeness. With the serial bypass functionality the SNMP/Web adapter are configured in transparent mode. That is, the adapter acts as a relay between its serial port (DB9F local console port) and the serial connection to the UPS control board. This functionality is activated by injecting a serialbypass on command through the console interface (either local or remote). This functionality is only meant to be used for obtaining service access to the UPS, and as such is subject to some limitations. Particularly, it is recommended that the end user does not activate it, as the adapter will signal a Communication Lost alarm. In case the serial bypass is accidentally enabled, it can be disabled (with full adapter operation restored) by injecting a serialbypass off command through the console interface – obviously, only through remote connection, as the local console is not offering console interface access. At start-up the adapter will always configure its local console interface for normal operation. This means that if the adapter is reset (or reboots) it will exit the serial bypass functionality. 8.3 HTTP BASED MONITORING (1-PH/SP VERSION ONLY)

The 1-ph/SP SNMP/Web adapters offer an additional method to monitor the UPS operation. The web interface offers a dynamic page (that is, generated on the fly upon request) picturing the current UPS status. The page is available as a single-line text page, no HTML, no authentication required. The page location is http://<IP or Hostname>/ge_alarm.asp. The single-line text has the following format:

[Date / Time];[Keyword];[Alarm Text] where:

[Date / Time] is the date and time of the instant the web page was created

[Keyword] is NORMAL, INFORMATION, WARNING or CRITICAL, indicating increasing severity of

the UPS condition. [Alarm Text] is a comma separated value (no blanks) of all active alarm conditions

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 51 of the GE Security System Keypad (1019070) user manual — 8.3.1 UPS Load Alert
Page 51 · click to enlarge
Page 51

8.3.1 UPS Load Alert

The SNMP/Web adapter monitors the UPS Output Percent Load and reports a UpsLoadAlert when the load drops of a defined percentage (the actual load step detected is also saved in the UPS log). This functionality warns the user that there has been a drop in the UPS load. This could indicate potential issues with the UPS load (fuse blown, breaker tripped, unit off, etc.). Per current implementation, the alert is only available for HTTP based monitoring. The following commands (available over the command-line interface – local console or telnet) have been introduced to control this functionality.

This command controls the UPS Load Alert. The UPS output percent load is monitored, and when the drops is above the specified threshold is will report a UpsLoadAlert condition.

load_alert_thres [-1 | 5..100]

The parameter is expressed in percentage of the UPS rating: the threshold can be set to a value between 5% and 100%.

Setting it to –1 disables the functionality.

Default value15%

This command controls the time that the SNMP/Web adapter will maintain active the UpsLoadAlert notification. Once the configured time is expired the notification is reset.

The parameter is expressed in minutes: it can be set to a value between 1 and 500 minutes. [-1 | 1..500] load_alert_time

Setting it to –1 means that the notification will never be reset.

Default value15 minutes

This command controls a filtering and averaging mechanism applied on the UPS output percent load measurement. This mechanism aims to prevent reporting false conditions following transient conditions. [1..5] load_alert_filter The parameter can be set to a value between 1 and 5, where 1 is no filtering/averaging and 5 is highest filtering.

Default value3

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Command Parameters Description

Page 52 of the GE Security System Keypad (1019070) user manual — 9.1 SOFTWARE UPGRADE
Page 52 · click to enlarge
Page 52

9 MAINTENANCE

9.1 SOFTWARE UPGRADE

The application software in the SNMP/Web adapter may be upgraded (please note that the upgrade procedure can be performed only by the supervisor and by rw users). The procedure to upgrade the software is described below:

  • Transfer the new software ( gedeappXXX.bin ) to the device using ftp or sftp
  • Start the upgrade by injecting the upgrade command at the console or by pressing the upgrade button in the Upgrade web page (System section)
  • Reboot the system to complete the upgrade procedure NOTE : Make sure to use binary transfer to upload the file (binary transfer is selected with the binary FTP command). Particularly, the FTP client on Windows defaults to ascii transfer – ascii transfer corrupts the binary file during upload, and the upgrade procedure fails. Although the procedure itself may seem trivial, there is a set of advices to be considered. First of all, the upgrade procedure has been tested to be safe. However, any interruption to the procedure (even accidental) may cause an abnormal termination. This means that any access to the adapter may be lost if the upgrade procedure is not completed successfully – at that stage, the only recovery mechanism is the adapter replacement. Therefore:
  • Never power off or un-plug the device during upgrade
  • Use only GE officially released software
  • Avoid unnecessary upgrades (in line of practice, only perform upgrades when recommended to do so by GE) 9.2 CONFIGURATION FILE

The SNMP/Web adapter settings are stored in non-volatile memory. It is possible to store the settings in a file, download it, or even upload a new configuration file. To store the settings in a file, inject the nvdump command at the console. This will create a gedeups.cfg file in the FTP area. The file can then be downloaded via ftp or sftp. Also the web interface offers access to the SNMP/Web adapter configuration: Configuration page in the System section. The configuration is shown in a text area and it can be selected and copied to any text- based editor. Finally, it is also possible to upload a new configuration file. This procedure can be performed only by the supervisor or rw users. Mind that this is not the recommended procedure to change the adapter settings, as the device will not perform any check on the downloaded file – operation of the SNMP/Web adapter may be severely affected by a corrupted configuration file. In any case the procedure is described below:

  • Transfer the new configuration file ( gedeups.cfg ) to the device using ftp or sftp
  • Update the configuration by injecting the nvupdate command at the console
  • Reboot the system to begin using the new configuration 9.3 LOGS

The SNMP/Web adapters maintain a log of the user activity (System log) and a log of UPS alarms (UPS log). The logs can be accessed over the web interface (Log section) or over the console interface (syslog and upslog commands). The logs can also be stored in a file and downloaded from the adapter. In order to download the log files, inject the logdump command at the console. This will create ups.log and sys.log in the FTP area. The files can then be downloaded via ftp or sftp.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 53 of the GE Security System Keypad (1019070) user manual — 10.1 TROUBLESHOOTING UPS CONNECTION
Page 53 · click to enlarge
Page 53

10 TROUBLESHOOTING

10.1 TROUBLESHOOTING UPS CONNECTION

The SNMP/Web adapter front panel features a LED marked ‘UPS’. This LED should be OFF in normal conditions. If the LED is ON then there is a problem in the communication with the UPS. NOTE: It may take up to one minute for the adapter to synchronise the communication with the UPS. Also, the SNMP/Web adapter will signal a Communication Lost alarm if communication with the UPS is lost and cannot be re-established. 10.1.1 3-ph SNMP/Web plug-in adapter

The 3-ph plug-in adapter features a dip-switch to configure the card logical address. This setting is critical when two or more cards are installed in the same UPS system. The address of each card MUST be unique – refer to the Installation section of the Installation Guide for details. NOTE: In case of address collision with other SNMP/Web adapters the UPS alarm web page will show the following notice: “Address collision. Check adapter configuration” 10.1.2 1-ph SNMP/Web external adapter

The 1-ph external adapter connects to the UPS through cables. In case of problems in the communication with the UPS check the cabling. The cable for connecting the adapter to the UPS is normally provided with the UPS. Note that two types of communication are possible:

  • Intelligent (serial) communication: use VIC-23 or IMV-I cable or straight 1:1 serial cable
  • Contact interface communication: use VIC-25 or IMV-C serial cable The actual cable to be used will depend on the actual UPS make and model – refer to applicable UPS documentation and accessories. In any case, make sure the proper cable is used. 10.2 TROUBLESHOOTING LOCAL CONNECTION

For troubleshooting problems in local (serial) console connection to the adapter refer to the following table.

Port already in use – e.g. Windows HyperTerminal reports the following problem:

Close all applications and services that are currently using the port selected for the connection to the device.

GE Security System Keypad (1019070) — 10.1 TROUBLESHOOTING UPS CONNECTION diagram (page 53)
Fig. 22

Attempt a new connection.

Cannot connect to the adapter

Check the serial cable (a straight 1:1 serial cable is required) and its connection. Check the settings of the terminal application: 115,200bps, 8 data bits, 1 stop bit, parity none, flow control none

Cannot login to the local console

Verify username and password used. Verify that the user has been correctly defined and configured by the administrator.

Cannot use interactive menus Check the settings of the terminal application: Terminal emulation VT-100

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Problem Recommended resolution

Page 54 of the GE Security System Keypad (1019070) user manual — 10.3 TROUBLESHOOTING NETWORK CONNECTION
Page 54 · click to enlarge
Page 54

10.3 TROUBLESHOOTING NETWORK CONNECTION

When experiencing difficulties in the network access to the card follow the flowchart below to identify the root-cause of the problem and implement proper corrective actions. (*) If the adapter and the relevant network node belong to different subnets check the gateway settings.

GE Security System Keypad (1019070) — 10.3 TROUBLESHOOTING NETWORK CONNECTION diagram (page 54)
Fig. 23

(**) Credentials are not limited to username and password, but – for example – also include SNMP community name, port, etc. Also, make sure the relevant user configuration allows access to the adapter using the selected interface. Should you consider contacting your support interface for addressing network connection issues pls. attach a of log the network communication (i.e. capture network traffic with a network protocol analyser).

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 55 of the GE Security System Keypad (1019070) user manual — 10.4 TROUBLESHOOTING WEB ACCESS
Page 55 · click to enlarge
Page 55

10.4 TROUBLESHOOTING WEB ACCESS

Refer to the following table for troubleshooting most common problems in accessing the embedded web interface. Please note that proper browser configuration is responsibility of the user – this section aims to give guidance to understanding the common access problems and browser errors.

Browser error: ”Connection refused” ”No page to display” ”Could not connect to server” ”The page cannot be displayed” ”Cannot find server”

Check the correctness of the specified URL. The URL should specify either the adapter IP address or the hostname:

  • Plain HTTP access, example <a href="http://192.168.10.10" rel="nofollow noopener" target="_blank">http://192.168.10.10</a> or <a href="http://SnmpAdapter" rel="nofollow noopener" target="_blank">http://SnmpAdapter</a>
  • HTTPS (SSL) access, example <a href="https://192.168.10.10" rel="nofollow noopener" target="_blank">https://192.168.10.10</a> or <a href="https://SnmpAdapter" rel="nofollow noopener" target="_blank">https://SnmpAdapter</a>

Check that the web interface service has been enabled on the SNMP/Web adapter. If using HTTPS, verify it has been enabled on the adapter.

Verify username and password used. Browser error: ”Unauthorized” Check that the user has been correctly defined and configured by the administrator – that is, web interface access is allowed.

When accessing the web interface using HTTPS, the browser verifies that: Security alert

  • The issuing Certificate Authority (CA) is on its list of trusted CAs.
  • The server's certificate is valid
  • The adapter IP-Address/DNS-name matches the name on the certificate

If one of these checks fails the browser will issue a security alert. The Encryption section explains out to download the CA Root Certificate for installation in the browser trusted CA repository. 10.5 TROUBLESHOOTING DATE&TIME (NTP)

When NTP server connection is configured and enabled, the SNMP/Web adapter will periodically re- synch its internal date and time settings with the NTP server. Should you experience problems with this functionality, perform the following checks:

  • Verify that the NTP server is correctly working in the specified node
  • Force a date/time update either by running an ntpdate command through the command line interface or pressing the ‘Update Now’ button on the Date&Time web page. If unsuccessful, there is a communication problem between the adapter and the NTP server: o Verify that the NTP server can be reached from the adapter. This can be easily verified by

running a ping command through the command-line interface o If a symbolic name is used in place of an IP address for the NTP server, verify that the name

is resolved in the correct IP address through DNS connection. This can be easily verified by running a nslookup command, either through the command-line interface or the web interface. • If the update is successful, but the actual time does not correspond to the expected value, verify that time-zone setting. Note that the time-zone setting also controls the daylight saving setting.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Problem Recommended resolution

Page 56 of the GE Security System Keypad (1019070) user manual — N
Page 56 · click to enlarge
Page 56

10.6 TROUBLESHOOTING E-MAIL NOTIFICATION (SMTP)

When e-mail notification via SMTP is configured and enabled, the SNMP/Web adapter will notify the selected recipients upon UPS alarm activation / deactivation. If problems are experienced with this functionality, follow the flowchart below to identify the root-cause of the problem and implement proper corrective actions.

Please note that proper configuration of the SNMP/Web adapter and the SMTP server set-up and configuration are responsibility of the user. This section aims to give basic troubleshooting guidance. For details on SMTP protocol refer to RFC 821, RFC 1123 and RFC 2821.

Y

Y

OK

OK

N

N

Check SMTP server operation telnet my.smtp.server smtp

Check SMTP server operation telnet my.smtp.server smtp

Server OK ? Resolve SMTP

Server OK ? Resolve SMTP

Y

Y

N

N

Ping SMTP server from the adapter

Ping SMTP server from the adapter

N

N

Y

Y

Send test e-mail GEDE>sendemail test

Send test e-mail GEDE>sendemail test

Y Check adapter /

Y Check adapter /

N

N

SNMP server configuration (**) OK

SNMP server configuration (**) OK

(*)If the adapter and the SMTP server belong to different subnets check the gateway settings. (**) Particularly:

  • If the SMTP server supports logging, enable the log functionality. Server error messages may give useful hints on the nature of the problem
  • Check the SNMP/Web adapter hostname (must be a valid domain name), SMTP sender-name and e-mail recipient (both must be valid e-mail addresses)
  • If the SMTP server requires authentication, verify the account settings on the SNMP/Web adapter. With reference to Authentication, the embedded e-mail client only supports the CRAM-MD5 and LOGIN mechanisms. Make sure the e-mail server supports at least one of these mechanisms.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Show 14 more labels / short text on this page
E-mail notification · E-mail notification · E-mail OK · E-mail OK · server issues · server issues · Ping OK ? · Ping OK ? · Verify TCP/IP settings · Verify TCP/IP settings · (*) · (*) · Email OK ? · Email OK ?
Page 57 of the GE Security System Keypad (1019070) user manual — 10.7 TROUBLESHOOTING NETWORK SHUTDOWN
Page 57 · click to enlarge
Page 57

10.7 TROUBLESHOOTING NETWORK SHUTDOWN

When experiencing difficulties with the Network Shutdown functionality (RCCMD), there are a few diagnostic tools that can be used. The first step is to ensure that the SNMP/Web adapter can reach the RCCMD Client. The actual network connectivity between the two nodes can be checked with the usual ping command. However, the actual RCCMD communication and related configuration can also be tested. The SNMP/Web adapter includes a Test function that sends a test message to the Client. It is important to monitor both the messages returned from the SNMP/Web adapter and the actual result on the Client. Depending on the configuration, the SNMP/Web adapter may successfully send the test message, but this can be ignored by the RCCMD Client. The network configuration of the devices can be critical. It is highly recommended to assign static IP addresses to the involved devices (SNMP/Web adapter and RCCMD Clients). In a DHCP environment, the DHCP Server should be configured to always assign the same address to these devices. It is also recommended to identify the nodes with their IP address rather than their hostname – otherwise, the Network Shutdown may fail when the DNS server is unavailable or unreachable. As the RCCMD Shutdown command is a TCP/IP network message, it is vital that network connectivity devices (such as routers, switches and hubs) are protected by the UPS. Finally, both the SNMP/Web adapter and the RCCMD Clients log their RCCMD activity. The analysis of the logfiles may provide useful hints on the actual RCCMD communication and the eventual root cause of the problem.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Page 58 of the GE Security System Keypad (1019070) user manual — On-line support available on request (Internet access required). 11.3 WWW SERVER
Page 58 · click to enlarge
Page 58

11 CUSTOMER SUPPORT

11.1 FIRST LINE SUPPORT

Please contact your local GE distributor for problems with the installation of the product or its use. 11.2 INTERNET

On-line support available on request (Internet access required). 11.3 WWW SERVER

We have a WWW server running at

www.gedigitalenergy.com

With your favourite web browser you can access the latest information from GE, and download updates and manuals for this product.

OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Port already in use – e.g. Windows HyperTerminal reports the following problem:Close all applications and services that are currently using the port selected for the connection to the device. Attempt a new connection. p.53
Cannot connect to the adapterCheck the serial cable (a straight 1:1 serial cable is required) and its connection. Check the settings of the terminal application: 115,200bps, 8 data bits, 1 stop bit, parity none, flow control none p.53
Cannot login to the local consoleVerify username and password used. Verify that the user has been correctly defined and configured by the administrator. p.53
Cannot use interactive menusCheck the settings of the terminal application: Terminal emulation VT-100 p.53
Browser error: ”Connection refused” ”No page to display” ”Could not connect to server” ”The page cannot be displayed” ”Cannot find server”Check the correctness of the specified URL. The URL should specify either the adapter IP address or the hostname: • Plain HTTP access, example http://192.168.10.10 or http://SnmpAdapter • HTTPS (SSL) access, example https://192.168.10.10 or https://SnmpAdapter Check that the web interface service has been enabled on the SNMP/Web adapter. If using HTTPS, verify it has been enabled on the adapter. p.55
Browser error: ”Unauthorized”Verify username and password used. Check that the user has been correctly defined and configured by the administrator – that is, web interface access is allowed. p.55
Security alertWhen accessing the web interface using HTTPS, the browser verifies that: • The issuing Certificate Authority (CA) is on its list of trusted CAs. • The server's certificate is valid • The adapter IP-Address/DNS-name matches the name on the certificate If one of these checks fails the browser will issue a security alert. The Encryption section explains out to download the CA Root Certificate for installation in the browser trusted CA repository. p.55

Ask about the GE Security System Keypad (1019070)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the GE Security System Keypad (1019070)

Be the first to ask — other owners or our team will answer.

Original document

GE Security System Keypad (1019070) manual PDF

58 pages·1.1 MB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…