GEH–6505A

g

User’s Guide

Page 2 of the GE GEH6505A user manual — GEH–6505
Page 2 · click to enlarge
Page 2

GEH–6505

WARNINGS, CAUTIONS, AND NOTES

AS USED IN THIS PUBLICATION

This document is based on information available at the time of its publication. While efforts have been made to ensure accuracy, the information contained herein does not cover all details or variations in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described herein that are not present in all hardware and software systems. GE Electrical Distribution & Control assumes no obligation of notice to holders of this document with respect to changes subsequently made.

GE Electrical Distribution & Control makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.

REFERENCES POWER LEADER™ is a registered trademark of GE Company.

Modbus RTU is a registered trademark of AEG Schneider Automation.

For details of the Modbus RTU protocol, refer to PI-MBUS-300 Rev. E from Modicon/AEG Schneider Automation.

For details of RS485 communications, refer to the EIA-485 standard.

©Copyright 1996 GE Company

All Rights Reserved

Page 5 of the GE GEH6505A user manual — Chapter 1 – Introduction 1–1 Overview
Page 5 · click to enlarge
Page 5

Chapter 1 – Introduction

Chapter 1 – Introduction 1–1 Overview

DeviceDescription EPM 3710Full-function, three-phase electronic meter with optional pulse initiation, waveform capture, data logging, and protective relay outputs. EPM 3720Full-function, three-phase electronic meter with optional pulse initiation, waveform capture, data logging, protective relay outputs, and harmonic distortion measurements. Multilin 269 Plus Motor Management RelayProtection for medium-voltage industrial motors and associated mechanical systems. Multilin 565 Feeder Management RelayComplete time-overcurrent phase and ground protection by monitoring feeder phase current and ground current. Fanuc 90/30 PLCProgrammable logic controller (PLC) for applications from simple relay replacement to midrange process control. Fanuc 90/70 PLCProgrammable logic controller with multiple processors and programming capabilities for large, high-speed applications. Modbus ConcentratorMaps addresses of up to 32 attached POWER LEADER communications network (commnet) devices to equivalent Modbus addresses for use with the Ethernet Gateway.

The GE POWER LEADER™ Ethernet Gateway (catalog number PLENETG01), shown in Figure 1, is a microprocessor-based device that connects one to four RS485-based Modbus Remote Terminal Unit (RTU) networks to an industry-standard, high- speed Ethernet network. Up to 31 Modbus RTU devices can be connected to each of the Modbus RTU networks.

GE GEH6505A — Chapter 1 – Introduction 1–1 Overview diagram (page 5)
Fig. 1 · Chapter 1 – Introduction 1–1 Overview

Figure 1. POWER LEADER Ethernet Gateway.

The Ethernet Gateway works with GE’s Power Management Control System (PMCS), a comprehensive power management software platform that acts as the ‘host’ to RS485 networks attached to the Ethernet Gateway. A special part of the PMCS called the Dynamic Data Exchange (DDE) server is a database that records the addresses and configurations of all attached devices. The Ethernet Gateway serves as a pass- through device, interpreting the addressing information and routing queries from the host to the Modbus RTU networks and passing answers to those queries from the attached devices back to the host.

Table 1. Examples of Modbus RTU compatible devices.

As mentioned in Table 1, the Modbus Concentrator allows integration of POWER LEADER commnet devices with Modbus RTU-compatible networks for use with the Ethernet Gateway. See Section 3–5 for more details on the integration of commnet devices into Modbus networks.

The Ethernet Gateway strictly conforms to the Modbus RTU protocol, providing the capability to tie the supported Modbus RTU devices into an Ethernet network. Table 1 contains a partial list of devices that are compatible with the Ethernet Gateway and conform to the Modbus RTU standard.

Figure 2 illustrates a typical Modbus RTU network connected to a high-speed Ethernet through an Ethernet Gateway.

Page 6 of the GE GEH6505A user manual — 1–2 Physical Description
Page 6 · click to enlarge
Page 6

POWER LEADER™ Ethernet Gateway Chapter 1 – Introduction

GE GEH6505A — POWER LEADER™ Ethernet Gateway Chapter 1 – Introduction diagram (page 6)
Fig. 2 · POWER LEADER™ Ethernet Gateway Chapter 1 – Introduct…

269+ E P M 3710 E P M 3720

Figure 2. Typical use of Ethernet Gateway.

1–2 Physical Description

many as 31 Modbus devices each and up to 247 Modbus addresses each. RS485 ports are DB-9 (9-pin D shell) connectors with the following pin assignments:

Figure 3 is an outline drawing showing the dimensions of the Ethernet Gateway. Figure 4 is a rear view of the Gateway showing its control power, Ethernet, RS485 and RS232 connections.

Data - Pin 1

The following ports and connections are provided on the Gateway:

Data + Pin 2

  • A pair of Ethernet ports provides input and output connections to the either a 10BaseT or a 10Base2 Ethernet network.
  • One RS232 port (also DB-9 style) allows connection of a dumb terminal for configuration and troubleshooting of the Ethernet Gateway.
  • Four RS485 ports support up to four Modbus RTU networks, labeled Network 1 to Network 4, with as
  • A standard PC-style power connector for AC control power input.
GE GEH6505A — 1–2 Physical Description diagram (page 6)
Fig. 3 · 1–2 Physical Description
GE GEH6505A — 1–2 Physical Description diagram (page 6)
Fig. 4 · 1–2 Physical Description

Com 1 RS232 port for dumb terminal

Com 2 RS232 port not used

keyboard port not used

Length15.5 in. 393.0 mm

10Base2 and 10BaseT Ethernet ports

Figure 3. Front view with dimensions.

Figure 4. Rear view showing ports.

Show 5 more labels / short text on this page
Ground Pin 5 · Status LEDs · Power on/off switch · Control power connection · Four RS485 ports
Page 7 of the GE GEH6505A user manual — SS DD EE NN CC
Page 7 · click to enlarge
Page 7

Chapter 1 – Introduction

1-3 Operational Description

DD Destination device port number – the Gateway RS485 port to which the message should be routed (0 - 3)

The Ethernet Gateway transparently passes message between the host and devices attached to the Gateway. Figure 5 illustrates the stripping or adding of Ethernet headers to the Modbus messages. This section describes the nature of these messages and how the Gateway routes them. The following information is not necessary for configuration and use of the Ethernet Gateway, but is provided for users who may be developing custom applications and need such information.

EE Error status byte (0 = no parity errors, 1 = parity errors encountered)

NN Number of bytes in the Modbus message

CC A one byte checksum calculated by adding the first 14 bytes in the header

The header is stripped off the message by the Gateway and the remainder of the message is sent without changes to the destination device (or interpreted by the Gateway if a configuration message).

Messages sent from the software to RS485 devices via the Ethernet Gateway have a 15-byte header inserted in front of the message. The header tells the Gateway where to send the message, how long the message is, and if parity errors were encountered. This header has the following format:

Messages from the RS485 devices to the host are processed by adding the 15-byte header onto the start of the message. For messages from devices to the host, the byte in the DD position contains the RS485 port from which the message came.

Cyclic redundancy check (CRC) handling is done by the host on the Ethernet and the RS485 device on the Modbus. The Gateway does not check the CRC when receiving messages from the host or from RS485 devices.

SS DD EE NN CC

SS Sequence of ten AA hex bytes indicating the start of a message

Modbus messages from host to device - Ethernet Gateway str ips off header

Modbus message Host PMC S

Message tr aveling on Ethernet Message traveling on RS485

Modbus messages from device to host - Ether net Gateway adds header

Figure 5. Ethernet headers on Modbus messages.

The Gateway uses TCP/IP (Transmission Control Protocol/Internet Protocol) to interface with the host on the Ethernet.

The Gateway initially opens a socket and waits for a host device to attempt to connect with the socket.

Once a connection is established, data messages may be transmitted to the Gateway (and ultimately the RS485 devices) and messages from RS485 devices passed to the host.

Show 13 more labels / short text on this page
Message Format · Ethernet · Ethernet Gateway · Modbus message · header information · RS485 device · Ethernet · Modbus message · header information · Modbus message · Ethernet Gateway · RS485 device · Gateway/Host Interface
Page 8 of the GE GEH6505A user manual — 1–5 Environmental Requirements
Page 8 · click to enlarge
Page 8

POWER LEADER™ Ethernet Gateway Chapter 1 – Introduction

1–4 Specifications

1–6 Terminology

The specifications of the Ethernet Gateway are listed in Table 2.

Following are definitions of some of the terms used in this document.

POWER LEADER – The GE family of comprehensive

GE GEH6505A — 1–4 Specifications diagram (page 8)
Fig. 5 · 1–4 Specifications
ParameterValue Control power90–132 Vac or 180–264 Vac, 47–63 Hz; autoranging Power supply =150 VA min (contact your GE sales representative for additional voltage options.) Modbus communicationsFour RS485 ports, 1200 baud, 2400 baud, 4800 baud, 9600 baud and 19.2 Kbaud. Ethernet communicationsOne PCL-843 16-bit Ethernet card; supports 10BaseT or 10Base2 transport mediums. Standards UL Listed CSA Certified508 & 840 C22.2 No. 14

power management devices and system software used to minimize downtime and overall power cost.

PMCS – Power Management Control System software.

SCADA (supervisory control and data acquisition) – A group

of systems including power management and control systems.

DCS (distributed control system) – A group of systems

including building automation and status monitoring systems.

Ethernet – An open, industry-standard, high-perform-

ance network communications protocol that operates on 10BaseT or 10Base2 transport mediums and yields communications rates up to 10 megabits per second.

Modbus RTU (Remote Terminal Unit) – An open, industry-

standard, high-performance network communica- tions protocol developed by Modicon/AEG Schneider Automation.

Table 2. POWER LEADER Ethernet Gateway specifications.

1–5 Environmental Requirements

Modbus-compatible device – Any device equipped with a

Modbus RTU communications port.

The environmental requirements of the Ethernet Gateway are listed in Table 3.

Modbus master – A host computer running PMCS

software.

RS485/EIA485 – A physical standard for multi-drop,

GE GEH6505A — 1–5 Environmental Requirements diagram (page 8)
Fig. 6 · 1–5 Environmental Requirements
ParameterValue Operating temperature0° C to +50° C Storage temperature–20° C to +80° C Relative humidity10% to 95% noncondensing Vibration response and enduranceIEC 255–21–1 Severity Class 1 Fast transient surgeANSI C37.90.1 Radiated EMI withstandANSI C37.90.2 Electrostatic dischargeIEC 801–2 Severity Class 4

high-speed, noise-tolerant communications over a twisted pair network; often used with the Modbus RTU protocol.

Commnet – A GE proprietary communications network

standard.

Commnet-compatible device – Any meter, relay, trip unit, or

other device equipped with a commnet commu- nications port.

Commnet segment – A group of one to four commnet-

compatible devices (including at most one waveform- capturing meter) with all communication ports wired to a single Concentrator commnet port.

Table 3. POWER LEADER Ethernet Gateway environmental

requirements.

Page 9 of the GE GEH6505A user manual — 2–2 Control Power Connections
Page 9 · click to enlarge
Page 9

Chapter 2 – Installation

Chapter 2 – Installation 2–1 Mounting

GE GEH6505A — Chapter 2 – Installation 2–1 Mounting diagram (page 9)
Fig. 7 · Chapter 2 – Installation 2–1 Mounting

The Ethernet Gateway may be mounted on a horizontal surface or on a wall, preferably inside an enclosure or switchgear lineup. The Gateway should be mounted so that it is spaced from enclosure walls or from other components in the enclosure. A minimum of two inches clearance should be allowed along the long sides of the Gateway, and at least six inches clearance on the ends to allow for ventilation and cable access. To wall mount the Ethernet Gateway, attach the brackets to the chassis using six of the provided screws through the six holes on the inner edges of the mounting brackets. Then use the remaining four screws to secure the chassis to the wall through the holes in the outer edges of the brackets. Be sure that the chassis is mounted securely. The hole pattern for the mounting flanges of the Ethernet Gateway is shown in Figure 6.

Figure 7. Connecting control power to the Ethernet Gateway.

2–3 Ethernet Connection

10BaseT and 10Base2 connections are provided on the back of the Ethernet Gateway to connect the Gateway to the Ethernet network, as shown in Figure 8. The Gateway is equipped with a PCL-843 16-bit Ethernet card.

12 in. 1 in.

305. 0 mm 23.0 mm
GE GEH6505A — 2–3 Ethernet Connection diagram (page 9)
Fig. 8 · 2–3 Ethernet Connection
7. 1/8" 190.6 mm

8 - R5 4 - R2.5

Figure 6. Mounting hole pattern for Ethernet Gateway.

2–2 Control Power Connections

Connect the control power cable included with the Ethernet Gateway to the standard PC-style power outlet on the rear of the enclosure, as shown in Figure 7. See Section 1–4 for appropriate control power voltage ranges.

Figure 8. Making the Ethernet connection to the Gateway.

The ON switch for the Ethernet Gateway is located on the front panel. Make sure the Gateway is mounted in a location where the power switch is not likely to be accidentally hit or switched off.

Page 10 of the GE GEH6505A user manual — 2–6 Wiring Rules – Modbus Networks
Page 10 · click to enlarge
Page 10

POWER LEADER™ Ethernet Gateway Chapter 2 – Installation

2–4 Modbus Connection

2–5 Diagnostic Connection

The Modbus RTU networks should be connected to the RS485 ports on the back of the Ethernet Gateway, as shown in Figure 9.

The RS232 port on the back of the Ethernet Gateway is provided for connection of a dumb terminal to the Gateway. The terminal may be used for configuring the Ethernet Gateway’s settings or for diagnostic purposes. For diagnostic purposes, the Gateway may be set to display all messages and traffic on the terminal so that problems may be tracked down and corrected. To connect a terminal (usually a laptop computer running Windows’ Terminal accessory software) to the Gateway, plug its RS232 cable into the RS232 port on the back of the Ethernet Gateway, as shown in Figure 11.

GE GEH6505A — 2–4 Modbus Connection diagram (page 10)
Fig. 9 · 2–4 Modbus Connection
GE GEH6505A — 2–4 Modbus Connection diagram (page 10)
Fig. 10 · 2–4 Modbus Connection

Figure 9. Connecting an RS485 network to the Ethernet

Gateway.

Per the EIA-485 standard, the RS485 networks must be terminated at both ends. Position the Ethernet Gateway at one end of the RS485 networks, as it is internally terminated. The user must ensure that the final device on each network is terminated correctly, as shown in Figure 10.

Figure 11. Connecting a dumb terminal to the RS232 port.

2–6 Wiring Rules – Modbus Networks

GE GEH6505A — 2–6 Wiring Rules – Modbus Networks diagram (page 10)
Fig. 11 · 2–6 Wiring Rules – Modbus Networks

When wiring Modbus RTU devices to an Ethernet Gateway, follow the wiring rules below to ensure proper configuration. Refer to GEH-6502, the PMCS Network Architecture Guide, for specific examples of correct and incorrect configurations.

1. Up to 31 Modbus devices may be attached to a single Modbus network. RS485 repeaters do not have Modbus addresses, but do count as devices toward the 31 physical devices per network limit.
2. Every device on a single Modbus network must have a unique address. (Devices on different networks may use the same Modbus address, i.e., it is acceptable to have a device addressed as device 10 on Network 1 and another device addressed as device 10 on Network 2.) Use the Modbus address worksheets (at the end of this

Figure 10. Terminating an RS485 network at the last device.

Page 11 of the GE GEH6505A user manual — 2–7 Modbus Equivalent Addresses
Page 11 · click to enlarge
Page 11

Chapter 2 – Installation

manual) to record the devices attached to each network and verify that each device on each network has a unique address.

devices. To the Modbus network, the commnet devices appear as valid Modbus addresses.

To provide seamless integration of commnet- compatible devices into the Modbus RTU network, the Concentrator directly maps commnet addresses to equivalent Modbus addresses. The valid range of commnet addresses recognized by the concentrator is 300–514. These addresses are one-to-one mapped to the equivalent Modbus address range of 33–247.

3. Modbus Concentrators may be used to add POWER LEADER commnet devices to a Modbus network. The Concentrator assigns a Modbus-equivalent address to each commnet device attached to it. See Section 2-7 for a discussion of commnet and Modbus-equivalent addresses.

For a more detailed discussion of commnet devices and the function of the Modbus Concentrator, see GEH-6491, the Modbus Concentrator Users Guide.

Table 4 lists commnet devices supported by the Modbus Concentrator (and the Ethernet Gateway).

DeviceDescription POWER LEADER EPMFull-function, three-phase electronic meter with optional pulse initiation; simple retrofit to existing electromechanical installations. See GEH–6302 for a full description. POWER LEADER MeterFull-function three-phase meter with optional protective relaying and waveform capture. See GEH–5892. POWER LEADER MDP Overcurrent RelayThree-phase and ground protection against overloads and rapid detection of short circuits. See GEK–100682. Spectra ECM™Advanced motor protection in fullvoltage-nonreversing (FVNR) and full-voltage-reversing (FVR) combination starter applications. See GEH–6435. MicroVersaTrip PM™ trip unit in Spectra RMS™ molded-case circuit breakersOvercurrent protection and optional full-function metering and protective relaying. See GEH–5934. MicroVersaTrip PM™ trip unit in AKR, Power Break® and Power Break® II insulated-case circuit breakers.Overcurrent protection and optional full-function metering and protective relaying. See GEH–6273.
4. No connections between Modbus networks are permitted, either directly or through repeaters.
5. Modbus networks are constrained to a maximum 4,000 feet of communication cable without repeaters.
6. RS485 repeaters may be used to extend the wiring length of a Modbus network or to provide isolation between runs of cable in a Modbus network. Refer to GEH-6502 for appropriate wiring lengths with repeaters.

2–7 Modbus Equivalent Addresses

A maximum of 31 Modbus devices can be supported on a single RS485 network of the Ethernet Gateway. However, the Modbus RTU protocol permits up to 247 individual addresses to be recognized. These additional 216 addresses may be utilized by commnet devices attached to a special Modbus device, the Modbus Concentrator.

Commnet is a communications protocol utilized by many of the devices from GE’s POWER LEADER family of power management devices. The Modbus Concentrator is a Modbus RTU device that permits commnet devices to be assigned Modbus-equivalent addresses. Each Modbus Concentrator keeps track of up to 32 commnet devices and directs traffic between the Modbus network and the commnet

Table 4. POWER LEADER commnet devices supported by the

Modbus Concentrator.

Page 12 of the GE GEH6505A user manual — 3–1 Configuration Procedure
Page 12 · click to enlarge
Page 12

POWER LEADER™ Ethernet Gateway Chapter 3 – Configuration

Chapter 3 – Configuration

The Ethernet Gateway needs to be properly configured to communicate with your RS485 networks. Two items are critical to proper performance of your Gateway: the Gateway’s Ethernet address and the RS485 port communication settings. The Gateway’s Ethernet address should be set so that the host software will know how to address messages to the Gateway. You must configure the Ethernet Gateway with the appropriate baud rate and communications settings for each RS485 port to match attached RS485 network. After initial setup, you should only need to make changes to the Gateway’s settings after adding devices or making system changes.

GE GEH6505A — Chapter 3 – Configuration diagram (page 12)
Fig. 12 · Chapter 3 – Configuration

Follow the instructions in Section 3-1 to perform the initial configuration. After the network is operational, you may make configuration changes through the dumb terminal. These procedures are described in the following sections.

Figure 12. Terminal communications settings.

You are now ready to configure the Gateway, as outlined below:

In all cases, be sure to save any configuration changes to the Gateway’s hard drive (option 12) for safe retrieval in the event of a power loss.

1. Type SET (must be typed in capital letters) then press to bring up the configuration menu. If you make an error typing in this string, wait ten seconds and try again.

3–1 Configuration Procedure

Configuration of the Gateway requires a dumb terminal with RS232 port set to 19.2 Kbps, 8 data bits, no parity, and 1 stop bit. The easiest way to do this is to use a portable computer with an RS232 port, and run the Terminal accessory program from Windows.

2. The terminal displays the configuration menu:
GE GEH6505A — 3–1 Configuration Procedure diagram (page 12)
Fig. 13 · 3–1 Configuration Procedure

Use a null modem cable to attach the laptop to the RS232 port of the Gateway, power up the laptop and launch the Terminal program (located in the Accessories program group in the Windows program manager). Click on the Settings menu, then choose Communications. Set your communications options to look like figure 12.

When you have set your communications options, close the options window and power up the Gateway (the ON switch is located on the front panel).

When the Gateway finishes powering up, the following message is transmitted to the terminal:

Figure 13. Ethernet Gateway configuration menu.

Page 13 of the GE GEH6505A user manual — 3–3 Baud Rate Specification
Page 13 · click to enlarge
Page 13

Chapter 3 – Configuration

Enter the setting number you want to change, then press .

3–2 Ethernet Gateway IP Address

Ethernet Gateway’s IP address must be properly set for it to receive messages sent by the host software. Consult your LAN personnel or system administrator for assistance in selecting the correct IP address. Follow Section 3–7 to modify the IP address.

3. At the prompt, enter the new setting, then press . If you enter an invalid value, the following message will be displayed:

3–3 Baud Rate Specification

Pressing returns you to the configuration menu.

You must configure the baud rate and communications settings on each RS485 port to match the baud rate on the attached RS485 network. The Gateway supports RS485 speeds of 1200 baud, 2400 baud, 4800 baud, 9600 baud and 19.2 Kbaud. Default settings are 19.2 Kbaud, 8 data bits, no parity, 1 stop bit.

4. Configure parameters as desired, by repeating steps 2 and 3.

Each network’s baud rate depends on the devices attached to it – see GEH-6502, the PMCS Network Architecture Guide, for more details on this.

5. When you are finished making changes, select option 12, . The configuration file on drive A is modified with the new parameters and the terminal displays the following message:

To configure the baud rate and communications settings for any of the four RS485 ports, follow Section 3-1, referencing the special instructions given below regarding the communications options.

Table 5 lists the valid entries for options 1 through 8 of the Configuration menu, relating to the baud rate and communications settings of RS485 ports.

If an error has been made, select option 13,

The currently displayed settings are discarded and the following message is displayed on the terminal:

Correct the error by repeating steps 1–3.

6. When you have saved the configuration and exited, the Ethernet Gateway is ready for operation. Turn off the unit until the rest of the network is ready for operation.
Page 14 of the GE GEH6505A user manual — 3–5 Ethernet Driver
Page 14 · click to enlarge
Page 14

POWER LEADER™ Ethernet Gateway Chapter 3 – Configuration

3–4 Message Monitoring

GE GEH6505A — 3–4 Message Monitoring diagram (page 14)
Fig. 14 · 3–4 Message Monitoring

For diagnostic purposes, you may want to monitor message traffic across the RS485 ports. This can be done on a terminal connected to the RS232 port. You may monitor messages on any single RS485 port or on all four ports simultaneously.

Data Bits0 = 7 data bits 1 = 8 data bits

Selecting menu item 14 allows you to select whether or not messages are sent to the RS232 port in monitor mode and which RS485 ports are to be monitored. The following prompt appears:

Stop Bits0 = 1 stop bit 1 = 2 stop bits
Parity0 = None 1 = Even 2 = Odd

Table 5. RS485 Port Settings.

1. Follow the procedure outlined in Section 3-1 to configure the Gateway.
2. At the Configuration menu, select the option number, then press . At the prompt, enter the new setting, then press . For options 1, 3, 5, and 7, enter the new setting from the options in Table 5, then press . For options 2, 4, 6, and 8, enter each new parameter as prompted, using the correct entries from Table 5. If you enter an invalid value, the following message display:

Enter your selection from the above choices.

3–5 Ethernet Driver

Menu item 10 permits the Ethernet driver to be selected. Most systems utilize DIX Ethernet; a handful use IEEE Ethernet. The Gateway defaults to the DIX Ethernet driver. If your network does not function under DIX Ethernet and you have eliminated all other potential sources of trouble, change the driver setting to IEEE Ethernet and retry communications. If this does not resolve the problem, contact Customer Service.

Press to return to the Configuration menu.

3. Follow steps 5 and 6 of Section 3-1 to save any changes and exit configuration mode.
Page 15 of the GE GEH6505A user manual — 3–6 Gateway Diagnostics
Page 15 · click to enlarge
Page 15

Chapter 3 – Configuration

3–6 Gateway Diagnostics

Enter the port to be tested: 1, 2, 3, or 4. The following message displays:

Selecting menu item 11 exits the Gateway software and runs the Gateway diagnostics program. The Gateway Diagnostics menu shown in Figure 14 is displayed on the terminal.

(where X is the port being tested).

If the loop-back is successful, the following message will be displayed:

GE GEH6505A — 3–6 Gateway Diagnostics diagram (page 15)
Fig. 15 · 3–6 Gateway Diagnostics

(where Y is the loop-back port).

If the loop-back is unsuccessful, the following message displays:

Default settings on the RS485 ports for the loop- back tests are 115.2 Kbps, 8-N-1.

Figure 14. Gateway Diagnostics menu.

Select menu item 3 to test the Gateway’s internal Ethernet connections. This performs a self-test of the Gateway’s Ethernet card to ensure that it is functioning correctly. The following message displays:

Display Socket, IP Address and Subnet Mask

Select menu item 1 to display the IP address and subnet mask for the Gateway.

If the test passes, the following message displays:

Select menu item 2 to perform a loop-back test on an RS485 port. The loop-back test is useful for identifying the RS485 ports and for testing communications on an RS485 port. To complete this test, you will need a short RS485 cable, available at an electronics retailer.

If the test fails, the following message displays:

In either case, pressing returns you to the diagnostics menu.

The RS485 port being tested is connected to another RS485 port and a test message is transmitted from the port being tested. The following prompt appears:

Select menu item 4 to exit the Gateway diagnostic software and reload the Gateway software.

GE GEH6505A — 3–6 Gateway Diagnostics diagram (page 15)
Fig. 16 · 3–6 Gateway Diagnostics

Ethernet Test · RS485 Loop-back Test · Exit Diagnostics Program

Page 16 of the GE GEH6505A user manual — 3–7 Advanced Options – Technical Support Personnel ONLY
Page 16 · click to enlarge
Page 16

POWER LEADER™ Ethernet Gateway Chapter 3 – Configuration

Network Test – FACTORY USE ONLY

3–7 Advanced Options – Technical Support Personnel ONLY

Ordinarily these options will have been configured by the system integrator or direct from the factory; you should NOT alter any of the settings from the advanced options area of the Configuration menu.

Menu item 5 is for factory testing of the network. End users should NOT select this option. This test attempts to communicate with a host across the Ethernet. To complete this test, you will need an RS232 null modem cable, available at an electronics retailer. Before performing this test, the host PC must be running the client software mentioned above, and must be connected to the Ethernet Gateway via the null modem cable.

Select menu item 15 to modify the Gateway socket identifier. The format is: ####.

When you select menu item 4, the following message is displayed:

Select menu item 16 to modify the Gateway Internet Protocol (IP) address. Enter the IP address in dot notation, e.g., 123.145.51.126.

Select menu item 17 to modify the Gateway subnet mask. Enter the subnetwork mask in dot notation, e.g., 255.255.255.0.

Select menu item 18 to modify the FTP PC/TCP kernal serial number. The number has the following format: 1234-5678-9012.

If the network test passes, the following message is displayed:

Select menu item 19 to modify the FTP PC/TCP kernal authentication key. The number has the fol- lowing format: 1234-5678-9012.

If the network test fails, the following message is displayed:

Select menu item 21 to modify the Gateway Router. This item has the following format: 0.0.0.0, 0.0.0.0, 0.0.0.0 Note that the Router numbers may have multiple digits in each placeholder, and each set of four numbers represents one router; for example, 205.109.43.11, 0.0.0.0, 0.0.0.0 is configured for one router. The Gateway may be configured with a maximum of three routers.

In either case, pressing returns you to the diagnostics menu.

Updating the Gateway Software

Option 20 of the Configuration menu allows updat- ing of the Ethernet Gateway’s operating software and is for use ONLY by factory service personnel.

Page 17 of the GE GEH6505A user manual — Chapter 4 – Operation
Page 17 · click to enlarge
Page 17

Chapter 4 – Operation

Chapter 4 – Operation

The Ethernet Gateway, once properly configured, requires no user intervention for operation.

During normal operation, the Ethernet Gateway passes messages to and from the attached Modbus devices and translates these messages between the Ethernet and Modbus RTU protocols.

Should power to the Ethernet Gateway be inter- rupted, communications between the host and the RS485 networks will resume automatically and immediately when power is restored.

Likewise, if the Ethernet connection or any of the RS485 connections are broken, communications will be immediately resumed when the connections are restored.

Any errors encountered by the Ethernet Gateway will result in a message being sent back to the host, where it will be interpreted and displayed for correc- tive action by the operator.

All processing error messages are sent to the RS232 port. Processing error messages are listed in Section 5-1 of this manual.

Page 18 of the GE GEH6505A user manual — Chapter 5 – Diagnostic Messages and Errors
Page 18 · click to enlarge
Page 18

POWER LEADER™ Ethernet Gateway Chapter 5 – Errors and Diagnostic Messages

Chapter 5 – Diagnostic Messages and Errors

5–1 Monitor Mode

5–2 Processing Error Messages

The Ethernet Gateway can be set to send diagnostic messages to the RS232 port to be displayed on a terminal (see Chapter 3). These diagnostic messages can be very useful in tracking down errors in configuration or device addressing.

Table 7 gives error messages that may be generated by the Gateway and displayed at the PMCS host.

GE GEH6505A — Chapter 5 – Diagnostic Messages and Errors diagram (page 18)
Fig. 17 · Chapter 5 – Diagnostic Messages and Errors

Error - Buffer Overflow One or more buffers have

Diagnostic messages sent to the RS232 port in moni- tor mode have the following format:

E-n (n = 1,2,3 or 4) indicates a message

sent from the Ethernet Gateway to RS485 port number 1,2,3 or 4

RS485 port number 1,2,3 or 4 to the Ethernet Gateway

Table 6. Diagnostic messages key.

Page 19 of the GE GEH6505A user manual — Chapter 6 – Troubleshooting Guide
Page 19 · click to enlarge
Page 19

POWER LEADER™ Ethernet Gateway Chapter 6 – Troubleshooting Guide

Chapter 6 – Troubleshooting Guide

The following guide is provided for troubleshooting and isolating common problems. It does not cover every possible condition. Contact the ED&C Customer Support Center at 800-843-3742 if the problem is not resolved by these procedures.

Symptom Possible Cause Corrective Action 1. No response at either host PC or dumb terminal from the Ethernet Gateway.

Lack of power.

Check that control power cable is working and correctly connected.

Ethernet Gateway internal failure.

Remove and reapply power to the Ethernet Gateway to see if the failure clears itself (possibly caused by external noise). Contact Customer Support if the problem persists.

2. No response at host PC from the Ethernet Gateway, but terminal connection is OK.

Faulty Ethernet wiring between Ethernet Gateway and host PC

Check that the Ethernet connector is properly wired and firmly seated. Test wiring for continuity and polarity to host PC.

Ethernet driver may be incorrect.

Check with your system administrator as to which Ethernet driver is being used (DIX or IEEE). Make sure Gateway is set accordingly (Section 3-5).

3. Ethernet connections OK, but no response from RS485 device(s).

Faulty RS485 wiring between Ethernet Gateway and RS485 networks.

Check that the RS485 connector is properly wired and firmly seated. Test wiring for continuity and polarity on RS485 wiring.

Lack of control power at RS485 device(s).

Check that control power present and correctly connected at device(s).

4. Some devices on RS485 networks not recognized at host.

Addressing problems or too many devices on segment

Refer to Section 5-1 to diagnose the precise problem and correct accordingly.

Page 20 of the GE GEH6505A user manual — RS485 Port Configuration Worksheets
Page 20 · click to enlarge
Page 20

POWER LEADER™ Ethernet Gateway Configuration Worksheets

RS485 Port Configuration Worksheets

Use the following worksheets to record the devices attached to the Ethernet Gateway for reference and troubleshooting. Record the Ethernet Gateway’s Ethernet address on the first page only, then fill in the information on the Modbus devices attached to

each network: device type and physical location, and the Modbus address assigned to it.

Ethernet Gateway Address:

RS485 Port 1 Worksheet

Baud Rate for RS485 Port 1

GE GEH6505A — RS485 Port Configuration Worksheets diagram (page 20)
Fig. 18 · RS485 Port Configuration Worksheets

Device Number Device Type & Physical Location / Notes

1 11 1 12 1 13 1 14 1 15

1 20 1 21 1 22 1 23 1 24

1 27 1 28 1 29 1 30 1 31

Page 21 of the GE GEH6505A user manual — Configuration Worksheets
Page 21 · click to enlarge
Page 21

Configuration Worksheets

RS485 Port 2 Worksheet

Baud Rate for RS485 Port 2

GE GEH6505A — Configuration Worksheets diagram (page 21)
Fig. 19 · Configuration Worksheets

Device Number Device Type & Physical Location / Notes

2 1 2 2 2 3 2 4 2 5

2 10 2 11 2 12 2 13 2 14

2 19 2 20 2 21 2 22 2 23

2 26 2 27 2 28 2 29 2 30 2 31

Page 22 of the GE GEH6505A user manual — POWER LEADER™ Ethernet Gateway Configuration Worksheets
Page 22 · click to enlarge
Page 22

POWER LEADER™ Ethernet Gateway Configuration Worksheets

RS485 Port 3 Worksheet

Baud Rate for RS485 Port 3

GE GEH6505A — POWER LEADER™ Ethernet Gateway Configuration Worksheets diagram (page 22)
Fig. 20 · POWER LEADER™ Ethernet Gateway Configuration Workshe…

Device Number Device Type & Physical Location / Notes

3 1 3 2 3 3 3 4 3 5

3 10 3 11 3 12 3 13 3 14

3 19 3 20 3 21 3 22 3 23

3 26 3 27 3 28 3 29 3 30 3 31

Page 23 of the GE GEH6505A user manual — Configuration Worksheets
Page 23 · click to enlarge
Page 23

Configuration Worksheets

RS485 Port 4 Worksheet

Baud Rate for RS485 Port 4

GE GEH6505A — Configuration Worksheets diagram (page 23)
Fig. 21 · Configuration Worksheets

Device Number Device Type & Physical Location / Notes

4 1 4 2 4 3 4 4 4 5

4 10 4 11 4 12 4 13 4 14

4 19 4 20 4 21 4 22 4 23

4 26 4 27 4 28 4 29 4 30 4 31

Page 24 of the GE GEH6505A user manual — g
Page 24 · click to enlarge
Page 24

g

GE Electrical Distribution & Control

General Electric Company 41 Woodford Ave., Plainville, CT 06062

GEH-6505A 0996 © 1996 General Electric Company

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Check that the Ethernet connector is properly wired and firmly seated. Test wiring for continuity and polarity to host PC. Check with your system administrator as to which Ethernet driver is being used (DIX or IEEE). Make sure Gateway is set accordingly (Section 3-5). p.19
Check that the RS485 connector is properly wired and firmly seated. Test wiring for continuity and polarity on RS485 wiring. Check that control power present and correctly connected at device(s). p.19
Refer to Section 5-1 to diagnose the precise problem and correct accordingly. p.19

Ask about the GE GEH6505A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.