Field Controls Draft Inducer (WML-C)

40 pages·870 KB·Furnace·PDF·ENDEFRITNLJA
Field Controls Draft Inducer (WML-C)
Table of Contents 80 sections Installation, Operation and · Maintenance Manual Oil Fired Warm Air Furnaces · WML-C AND MPL-B (Down-Flow or Horizontal Model) · ALL INSTALLATIONS MUST MEET ALL · … ShowHide
Installation, Operation andp.1Maintenance Manual Oil Fired Warm Air Furnacesp.1WML-C AND MPL-B (Down-Flow or Horizontal Model)p.1ALL INSTALLATIONS MUST MEET ALLp.1LOCAL, PROVINCIAL/STATE, ANDp.1FEDERAL CODES WHICH MAYp.1DIFFER FROM THIS MANUALp.1ECR International Limitedp.1OLSEN Divisionp.1INTRODUCTIONp.3LOCATION OF UNITp.3DOWN-FLOW INSTALLATIONp.3HEAT LOSSp.3Fig 1 Suspended Installationp.4BURNER ELECTRODESp.10PROCEDURE:p.10STACK TEMPERATURE:p.10OIL BURNER SET-UPp.10PREPARATIONS:p.10FURNACE INSTALLATION SETUPp.10SMOKE TEST NOTE :p.10OPERATING INSTRUCTIONSp.12APPENDIX AWML-C AND MPL-B BURNER SET UPp.13Model Nozzle Pump Pressure Flow Rate Head 1 Staticp.13Table A-2 Beckett AFII Oil Burner Set-Upp.13Table A-3 Riello 40F Series Oil Burner Set-Upp.13Model Nozzle Pump Pressure Flow Rate Air Gate Turbulatorp.13Table A-4 Riello Balanced Flue (BF) Burner Set-Upp.14Furnacep.14Output BTU/Hrp.14Burnerp.14Model Nozzle Pump Pressure Flow Rate Turbulatorp.14Modelp.14Settingp.14A.2 BURNER ELECTRODESp.14A.3 START UPp.14x SystemTemperatureRise SystemTemperatureRise Bonnet Outputp.15( ) ( ) CFM Bonnet Outputp.15Table A-8 Direct Drive Blower Characteristicsp.15Table A-6 Direct Drive Blower Set-Upp.15TIP:p.1560 - 90 GT10 ½ HP 7.0 45-75°Fp.1590-130 GT12-10DD ¾ HP 12.5 50-80°Fp.15Model Blowerp.15WML-Cp.15MPL-Bp.15Table A-9 General Dimensions (Inches)p.16WML-C &p.16A Depthp.16Model Widthp.16APPENDIX B: WIRING DIAGRAMSp.17Beckett AF Burner Wiring Diagramp.17Beckett AFII Burner Wiring Diagramp.18Riello 40F3 and F5 Burner Wiring Diagramp.19Riello 40BF3 Burner Wiring Diagramp.20OPERATION OF OIL BURNERp.21APPENDIX C-R7184 TROUBLESHOOTINGp.22R7184 DETAILED SEQUENCE OF OPERATION (FIGURE 7)p.22R7184 INTERRUPTED ELECTRONIC OIL PRIMARY CONTROLp.23FIGURE 7p.23ELECTRONIC FAN TIMER BOARD ON CONTROL PANELp.23FIGURE 8p.23IDLE STATEp.24THERMOSTAT CALLS FOR HEATp.24R7184 SEQUENCE ofp.24SAFETY CHECK FOR FLAME (5 SEC.)p.24REMAINS IN IDLE STATEp.24OPERATIONp.24NO FLAMEp.24FLAMEp.24BURNER MOTOR & IGNITOR STARTp.24SOLENOID VALVE OPENSp.24LOCKOUT STATEp.24TRIAL FOR IGNITIONp.24BURNER FLAME MONITOREDp.24FLAME LOSTp.24TO EXIT LOCKOUTp.24PRESS RESETp.24CARRYOVER TIMER EXPIRESp.24RECYCLE TIMER STARTSp.24
Page 1 of the Field Controls Draft Inducer (WML-C) user manual — Installation, Operation and
Page 1 · click to enlarge
Page 1

Installation, Operation and

Maintenance Manual Oil Fired Warm Air Furnaces

WML-C AND MPL-B (Down-Flow or Horizontal Model)

ALL INSTALLATIONS MUST MEET ALL

LOCAL, PROVINCIAL/STATE, AND

FEDERAL CODES WHICH MAY

DIFFER FROM THIS MANUAL

ECR International Limited

OLSEN Division

Field Controls Draft Inducer (WML-C) — Installation, Operation and diagram (page 1)
Fig. 1 · Installation, Operation and
Field Controls Draft Inducer (WML-C) — Installation, Operation and diagram (page 1)
Fig. 2 · Installation, Operation and

Read this complete manual before beginning installation. These instructions must be kept with the furnace for future reference.

Page 2 of the Field Controls Draft Inducer (WML-C) user manual — Installation, Operation and
Page 2 · click to enlarge
Page 2
Page 2 of the Field Controls Draft Inducer (WML-C) user manual — Installation, Operation and
Page 3 of the Field Controls Draft Inducer (WML-C) user manual — HEAT LOSS
Page 3 · click to enlarge
Page 3

enable proper sizing of the trunk and branch ductwork. In retrofit applications, a building shell (overall) heat loss calculation may be used.

IMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE.

DO NOT USE GASOLINE, CRANKCASE OIL, OR ANY OTHER OIL CONTAINING GASOLINE AS A FUEL FOR THIS FURNACE.

In the United States, Manual J. titled, "Load Calculation" published by the Air Conditioning Contractors of America, (ACCA), describes a suitable procedure for calculating the maximum hourly heat loss.

INTRODUCTION

IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE FUEL SUPPLIER.

Please read these instructions completely and carefully before installing and operating the furnace.

In Canada, the maximum hourly heat loss may be calculated in accordance with the procedures described in the manuals of the Heating, Refrigeration and Air Conditioning Institute (HRAI), or by other method prescribed by authorities having jurisdiction that are suitable for local conditions.

The furnace must be installed and set up by a qualified contractor.

Model WML-C is an oil fired forced air multi-positional furnace, with an output capacity range of 58,000 BTU/Hr. to 85,600 BTU/Hr. The MPL-B is also an oil fired forced air multi-positional furnace with an output capacity range of 85,500 BTU/Hr. to 123,000 BTU/Hr. The WML- C AND MPL-B furnace may be installed in the down-flow position, as well as both left and right horizontal positions.

LOCATION OF UNIT

The furnace should be located such that the flue connection to the chimney is short, direct and consists of as few elbows as possible. When possible, the unit should be centralized with respect to the supply and return air ductwork. A central location minimizes the trunk duct sizing. All models may be installed on combustible floors. Do not install the furnace on carpet or tiled floors.

THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THESE INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING BUT NOT LIMITED TO: BUILDING, ELECTRICAL AND MECHANICAL CODES.

All models are listed with the Canadian Standards Association, (CSA), and comply with the standards of both the United States and Canada for use with No. 1 (Stove) and No. 2 (Furnace) Oil.

In the United States, the installation of the furnace and related equipment shall be installed in accordance with the regulations of NFPA No. 31, Installation of Oil Burning Equipment, as well as in accordance with local codes.

Minimum installation clearances are listed in Table 1.

The furnace area must not be used as a broom closet or for any other storage purposes, as a fire hazard may be created. Never store items such as the following on, near or in contact with the furnace:

In Canada, the installation of the furnace and related equipment shall be installed in accordance with the regulations of CAN/CSA - B139, Installation Code For Oil Burning Equipment, as well as in accordance with local codes.

DOWN-FLOW INSTALLATION

All WML-C AND MPL-B furnace models have been assembled for installation in the down-flow position. Maintain all clearances to combustibles as outlined in Table 1. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot. Use shims made of noncombustible material.

1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners or other cleaning tools.

When installation or application questions arise, regulations prescribed in the National Codes and Local Regulations take precedence over the general instructions provided with this installation manual. When in doubt, please consult your local authorities.

2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners or other painting materials and compounds.

All models are shipped assembled and pre-wired. The furnace should be carefully inspected for damage when being unpacked.

4. Paper bags, boxes, or other paper or cardboard products.

HEAT LOSS

Never operate the furnace with the blower door removed. To do so could result in serious personal injury and/or equipment damage.

To determine the correct furnace and firing rate for an application, it is necessary to calculate the maximum hourly heat loss of the building based on local design conditions. In new construction, the heat loss should be calculated on a room-by-room basis to

Page 4 of the Field Controls Draft Inducer (WML-C) user manual — Fig 1 Suspended Installation
Page 4 · click to enlarge
Page 4
HORIZONTAL INSTALLATION WML-C AND MPL-B furnaces models are assembled and shipped ready for installation in the down-flow position. The furnace may be installed in either of the horizontal positions; warm air discharging left or warm air-discharging right by following these steps: 1. Rotate the furnace 90° to the desired position. 2. Remove the three nut and washer sets fastening the oil burner assembly to the furnace. Rotate the oil burner assembly to be in the normal upright position. 3. Re-align the oil burner assembly to the combustion chamber (fire-pot), and then secure into place with the three nut and washer sets. NON-SUSPENDED INSTALLATION Maintain clearances to combustibles as outlined in Table 1. Installation on a combustible floor requires a clearance of 1 inch. This can be done by using a noncombustible material such as oneinch thick channel iron or similar material. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the event of nozzle drip, install the furnace with an approximate 2-degree slope from the oil burner casing towards the fire pot. UseTable 1: Clearance to Combustible Furnace WML-C Location Down flow Hori Top 0 in. 3 Bottom 1 in. 1 S/A Plenum 1 in. 1 Rear 1 in. 1 Sides 1 in. 1 Front 10 in.1 10 Flue Pipe 9 in. 2 9 Enclosure Closet Cl 1 24 inches is required for servi 2 18 inches required in the Unit shims made of noncombustible material. SUSPENDED INSTALLATION Refer to Figure 1. Maintain clearances to combustibles as outlined in Table 1. The furnace may be suspended by field fabricating a cradle of angle iron and threaded rod. Secure the furnace with 2 inch minimum slotted angle or equivalent, as shown in Figure 1. The furnace must be supported in such a way as to not allow twisting or sagging of the cabinet. Position the supports so as to not interfere with accessing the burner and blower compartments. Suggestion; as a measure to prevent fuel oil from accumulating in locations other than the fire pot, as could be the case in the eventTable 1: Clearance to Combustible Furnace WML-C Location Down flow Hori Top 0 in. 3 Bottom 1 in. 1 S/A Plenum 1 in. 1 Rear 1 in. 1 Sides 1 in. 1 Front 10 in.1 10 Flue Pipe 9 in. 2 9 Enclosure Closet Cl 1 24 inches is required for servi 2 18 inches required in the Units MPL-B zontal Down flow Horizontal in. 0 in. 3 in. in. 1 in. 1 in. in. 1 in. 1 in. in. 1 in. 1 in. in. 1 in. 1 in. in.1 10 in.1 10 in.1 in. 2 9 in. 2 9 in. 2 oset Closet Closet cing. ed States. of nozzle drip, install the furnace with an approximate 2 degree slope from the oil burner casing towards the fire pot. AIR CONDITIONING If the furnace is used in conjunction with air conditioning, the furnace shall be installed in parallel with or upstream from the evaporator coil to avoid condensation in the heat exchanger. In a parallel installation, the dampers or air controlling means must prevent chilled air from entering the furnace. If the dampers are manually operated, there must be a means of control to prevent the operation of either system unless the dampers are in the full heat or full cool position. The air heated by the furnace shall not pass
FurnaceWML-CMPL-B LocationDown flowHorizontalDown flowHorizontal Top0 in.3in.0 in.3 in. Bottom1 in.1in.1 in.1 in. S/A Plenum1 in.1in.1 in.1 in. Rear1 in.1in.1 in.1 in. Sides1 in.1in.1 in.1 in. Front10 in.110in.110 in.110 in.1 Flue Pipe9 in. 29in. 29 in. 29 in. 2 EnclosureClosetClosetClosetCloset
Field Controls Draft Inducer (WML-C) — Fig 1 Suspended Installation diagram (page 4)
Fig. 3 · Fig 1 Suspended Installation

Fig 1 Suspended Installation

Page 5 of the Field Controls Draft Inducer (WML-C) user manual — Fig 1 Suspended Installation
Page 5 · click to enlarge
Page 5
through a refrigeration unit unless the unit is specifically approved for such service. Generally, a six-inch clearance between the air conditioning evaporator coil and the heat exchanger will provide adequate airflow through the evaporator coil. The blower speed must be checked and adjusted to compensate for the pressure drop caused by the evaporator coil. Refer to Appendix B for recommended wiring and electrical connections of the air conditioning controls. COMBUSTION AIR When a furnace is installed in the full basement of a typical frame or brick house, infiltration is normally adequate to provide air for combustion and draft operation. If the furnace is installed in a closet or utility room, two (2) ventilation openings must be provided connecting to a well ventilated space (full basement, living room or other room opening thereto, but not a bedroom or bathroom). One opening shall be located 6" from the top and bottom of the enclosure at the front of the furnace. For furnaces located in buildings of unusually tight construction, such as those with high quality weather stripping, caulking, windows and doors, or storm sashed windows, or where basement windows are well sealed, a permanent opening communicating with a well ventilated attic or with the outdoors shall be provided, using a duct if necessary. Size all of the openings and associated ductwork by the standards provided in the latest Oil Installation Code editions; NFPA 31 in the United States, CAN/CSA B139 in Canada. Take all fuel burning appliances in the area into consideration when calculating combustion and ventilation air requirements. The Model CAS-2B-90E Furnace Boot manufactured by Field Controls, Inc. may be used with the furnace to obtain combustion air from outdoors. Use of this device does not alter the need for ventilation air; however, it does provide a good source of combustion air and is connected to the oil burner. CHIMNEY VENTING The chimney must be sized correctly and be in good repair. If the chimney is oversized, there is a high risk of the flue gases condensing resulting in damage to the chimney and other venting parts. This problem may be corrected by the use of an appropriately sized chimney liner.If the chimney serves the WML-C furnace only, the vent should be sized at 5-inch minimum. The MPL-B should be 6-inch minimum. The data provided in Table 3 is based on dedicated venting. If the furnace is to be co-vented with other appliances, refer to NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, NFPA 31, Standard for the Installation of Oil Burning Equipment or CAN/CSA B139, Installation Code For Oil Burning Equipment for correct sizing information. NOTE: This furnace is approved for use with L-Vent. NOTE: Maximum temperature for LVent is 575°F (300°C). IMPORTANT: The chimney must be capable of providing sufficient draft at all times for the safe removal of the products of combustion. The chimney should be tested under “winter” conditions; doors and windows closed, all other fossil fuel burning appliances on, clothes dryer on, bathroom fans on, etc. If the chimney cannot overcome the competition for air, it will be necessary to access the reason for it, and take corrective action. If the chimney is found to be sized correctly and in good repair, it will probably be necessary to re-evaluate the availability of combustion and ventilation air, and take corrective action. The flue pipe should be as short as possible with horizontal pipes sloping upward toward the chimney at a rate of one-quarter inch to the foot. The flue pipe should not be smaller in cross sectional area than the flue collar on the furnace. The flue pipe should connect to the chimney such that the flue pipe extends into, and terminates flush with the inside surface of the chimney liner. Seal the joint between the pipe and the lining. The chimney outlet should be at least two feet above the highest point of a peaked roof. All unused chimney openings should be closed. Chimneys must conform to local, provincial or state codes, or in the absence of local regulations, to the requirements of the National Building Code. See Figure 2 and Table 2 for common chimney problems and their remedies.THE FURNACE MUST BE CONNECTED TO A FLUE HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE AND PROPER OPERATION OF THE APPLIANCE. The flue pipe must not be routed through concealed space, because it must be visually checked for signs of deterioration during the annual inspection and servicing. The flue pipe must not pass through any floor or ceiling, but may pass through a wall where suitable fire protection provisions have been installed. In the United States, refer to the latest edition of NFPA 31 for regulations governing the installation of oil burning equipment. In Canada, refer to the latest edition of CAN/CSA B139 for rules governing the installation of oil burning equipment. NOTE: THE RECOMMENDED FLUE DRAFT PRESSURE IS -0.02 IN. W.C. (AS MEASURED UPSTREAM OF THE BAROMETRIC DRAFT REGULATOR). SHOWN IN FIGURE 1. DRAFT REGULATOR CONTROL This device is used in conjunction with conventional chimney venting. This control (or draft regulator) automatically maintains a constant negative pressure in the furnace to obtain maximum efficiency. It ensures that proper pressures are not exceeded. If the chimney does not develop sufficient draft, the draft control cannot function properly. The draft regulator, must be installed within the same room or enclosure as the furnace, and should not interfere with the combustion air supplied to the burner. The control should be located a minimum of 3 flue pipe diameters from the furnace breeching and installed in accordance to the instructions supplied with the regulator.
Page 6 of the Field Controls Draft Inducer (WML-C) user manual — Fig 1 Suspended Installation
Page 6 · click to enlarge
Page 6
Fig. 2: Common Chimney Problems Table 2: Common Chimney Problems Refer to Figure 2 Key Trouble Diagnostic Remedy Extend chimney Top of chimney above all lower than A Observation surrounding surrounding objects within objects 30 feet. Chimney Cap B Observation Remove or ventilator. Make opening Coping restricts as large as C Observation opening. inside of chimney.DObstruction in chimneyCan be found by light and mirror reflecting conditions in chimney.Use weight to break and dislodge. EJoist protruding into chimney.Lowering a light on an extension cord.Must be handled by competent masonry contractor. FBreak in chimney lining.Smoke test - build smudge fire blocking off other opening, watching for smoke to escape.Must be handled by competent masonry contractor. GCollection of soot at narrow space in flue opening.Lower light on extension cord.Clean out with weighted brush or bag of loose gravel on end of line. HOffsetLower light on extension cord.Change to straight or to long offset. ITwo or more openings to the same chimney.Found by inspection from basement.The least important opening must be closed, using some other chimney flue. JLoose-seated pipe in flue opening.Smoke test.Leaks should be eliminated by cementing all pipe openings. KSmoke pipe extends into chimney.Measurement of pipe from within or observation of pipe by means of a lowered light.Length of pipe must be reduced to allow end of pipe to be flush with inside of tile. LFailure to extend the length of flue partition to the floor.By inspection or smoke test.Extend partition to floor level. MLoose-fitted clean-out door.Smoke test.Close all leaks with cement.
Field Controls Draft Inducer (WML-C) — Fig 1 Suspended Installation diagram (page 6)
Fig. 4 · Fig 1 Suspended Installation
Refer to Figure 2 KeyTroubleDiagnosticRemedy ATop of chimney lower than surrounding objectsObservationExtend chimney above all surrounding objects within 30 feet. BChimney Cap or ventilator.ObservationRemove CCoping restricts opening.ObservationMake opening as large as inside of chimney.
Page 7 of the Field Controls Draft Inducer (WML-C) user manual — Fig 1 Suspended Installation
Page 7 · click to enlarge
Page 7
OPTIONAL SIDE WALL VENTING Certain WML-C AND MPL-B furnace models are manufactured to be installed as sidewall vented units. Please refer to Direct Venting Instructions, P/N 28888 included with the Vent Kit for details. Sidewall Venting (Direct Venting) requires the use of specific oil burners; the Beckett AFII, or the Riello 40BF. Please refer to Appendix A, Tables A2, and A4. Note: Sidewall venting requires special attention to combustion air supply. There is no natural draft in the venting system between furnace cycles; therefore, if the indoor pressure is negative relative to the outdoors, the vent terminal becomes a point of infiltration. This could lead to oil odour control problems. This problem is rectified by the use of ducted outdoor air for combustion (semi-sealed combustion), using the Beckett AFII or Riello 40BF oil burner. See Direct Vent Instructions supplied with the Vent Kits. Table 3: Minimum Chimney Base Temperatures (°F)In general, the oil tank must be properly supported and remain stable in both empty and full condition. The oil tank must be fitted with vent and supply pipes to the outdoors. Refer to the abovementioned codes for sizing. The vent pipe must be no less than 1¼ inches I.P.S., and terminate with an appropriate vent cap in a location where it will not be blocked. The fill pipe must be no less than 2 inches I.P.S., and terminate with an appropriate cap in a location where debris will not enter the fill pipe during oil delivery. If located indoors, the tank should normally be in the lowest level, (cellar, basement, etc.). It must be equipped with a shut-off valve at the tank outlet used for the oil supply. The oil tank must be located as to not block the furnace / room exit pathway. Observe all clearances specified in the abovementioned codes. PIPING INSTALLATION In the United States, NFPA 31, Standard for the Installation of Oil Burning Equipment, Chapter 2. In Canada, the entire fuel system should be installed in accordance with the requirements of CAN/CSA B139, and local regulations. Use only approved fuel oil tanks piping, fittings and oil filters. Ensure that all fittings used in a copper oil line system are high quality flare fittings. Do not use compression fittings. Do not use Teflon tape on any fittings. Pressurized or gravity feed installations must not exceed 3 PSIG. Pressures greater than 10 PSIG may cause damage to the shaft seal. If the height of the oil stored in a tank above the oil burner exceeds 11½ feet, it may be necessary to use a pressure-regulating device approved for this purpose. The furnace may be installed with a onepipe system with gravity feed or lift. The maximum allowable lift on a single line system is 8 feet. Lift should be measured from the bottom (outlet) of the tank, to the inlet of the burner. Sizing a single line system is complex because of the difficulty estimating the pressure drop through each fitting, bend and component in the line. In general, keep single line systems short as possible. The following chart shows the allowable line lengths (horizontal + vertical) for single and two-line oil piping systems. All distances are in feet.Table 4: Oil Lines Copper Tubing Oil Line Length (Feet) Lift (Feet)Single-Pipe ODTwo-Pipe OD 3/8”1/2”3/8”1/2” 05310068100 14910065100 24510063100 34110060100 43710058100 53310055100 62910053100 7259950100 8218348100 9176845100 10135242100 12- - -- - -37100 14- - -- - -32100 16- - -- - -27100 18- - -- - -2288 In retrofit applications, where an existing oil line system is in place, a vacuum check will help determine the efficacy of the existing oil line system The vacuum in a system should not exceed 6” Hg. for a single pipe system, nor 12” Hg. for a two-pipe system. NOTE: The oil burner requires the use of a bypass plug when converting from single-pipe to two-pipe oil piping systems. See burner manufacturer’s instructions. All fuel systems should include an oil filter between the fuel oil storage tank and the oil burner. For best results, install the oil filter as close to the burner as possible. When using an indoor oil tank, the oil filter may be installed at the tank downstream from the shut-off valve. If firing the furnace under the 0.65 gph rate, a 7 to 10 micron line filter should be installed as close to the oil burner as possible. ELECTRICAL CONNECTIONS The furnace is listed by the Canadian Standards Association (CSA). It is factory wired and requires minimal field wiring. In the United States, the wiring must be in accordance with the National Fire Protection Association NFPA-70, National Electrical Code, and with local codes and regulations. In Canada, all field wiring should conform to CAN/CSA C22.1 Canadian Electrical Code, Part 1, and by local codes, where they prevail. The furnace should be wired to a separate and dedicated circuit in the NozzleChimney Height (ft.) 11202836 Chimney Thermal Resistance < R6 0.50300400535725 0.65275340430535 0.70270330405505 0.75260320380475 0.85250300355430 1.00225300365430 NozzleChimney Height (ft.) 11202836 Chimney Thermal Resistance > R6 0.50185200220250 0.65175185205220 0.70175185195215 0.75175185195210 0.85165185195205 1.00165185195205 < - less than, > - greater than OIL TANK Oil storage tanks must be selected and installed in compliance with applicable codes; in the United States, NFPA 31, Standard for the Installation of Oil Burning Equipment, Chapter 2. and in Canada, CAN/CSA-B139, Installation Code for Oil Burning Equipment, Section 6. Observe all local codes and by-laws.
Page 8 of the Field Controls Draft Inducer (WML-C) user manual — Fig 1 Suspended Installation
Page 8 · click to enlarge
Page 8
main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace circuit. Although a suitably located circuit breaker can be used as a service switch, a separate service switch is advisable. The service switch is necessary if reaching the circuit breaker involves becoming close to the furnace, or if the furnace is located between the circuit breaker and the means of entry to the furnace room. The furnace switch (service switch) should be clearly marked, installed in an easily accessible area between the furnace and furnace room entry, and be located in such a manner to reduce the likelihood that it would be mistaken as a light switch or similar device. The power requirements for all models: 120 VAC, 1 ∅, 60 Hz., 12A. Accessories requiring 120 VAC power sources such as electronic air cleaners and humidifier transformers may be powered from the ST9103 EFT. Do not use the direct drive motor connections as a power source, since there is a high risk of damaging the accessories by exposure to high voltage from the autogenerating windings of the direct drive motor. Thermostat wiring connections and air conditioning contactor low voltage connections are shown in the wiring diagrams. Some micro-electronic thermostats require additional controls and wiring. Refer to the thermostat manufacturer's instructions. The thermostat should be located approximately 5 feet above the floor, on an inside wall where there is good natural air circulation, and where the thermostat will be exposed to average room temperatures. Avoid locations where the thermostat will be exposed to cold drafts, heat from nearby lamps and appliances, exposure to sunlight, heat from inside wall stacks, etc. Normal heat anticipator setting: 0.1 A. For more precise adjustment, the heat anticipator may be adjusted to the amperage draw of the heating control circuit as measured between the "R" and "W" terminals of the thermostat. To reduce the risk of damaging the heat anticipator, do not measure circuit without first removing one of the two wires first. To determine the heating circuit amperage draw: 1. Disconnect one of the “R” or “W” wires from the thermostat terminal.2. Connect an ammeter between the wire and the thermostat terminal to which it was attached. 3. Note the amperage reading when the heating contacts are closed. (System switch must be on “HEAT” if so equipped. 4. Re-connect the thermostat wire. If the thermostat is serving a combination heating and air conditioning system, pay particular attention to polarity. 5. When the thermostat is reconnected and re-plumbed, adjust the heat anticipator setting to match the observed amperage reading. FAN TIMER BOARD AND LIMIT CONTROL The Electronic Fan Timer integrates control of all burner and circulator fan operations. This control is the central wiring point for most of the electrical components in the furnace. The Honeywell ST9103 has a fixed fan delay on time of 30 seconds after the burner ignites. The United Technologies 1158120 has an adjustable fan on time that is set by selecting the dipswitch combination displayed in Table 6. This fan on delay can be set at 30, 60, 90 or 120 seconds. This provides a delay between the burner ignition and blower start-up to eliminate excessive flow of cold air when the blower comes on. The Honeywell ST9103 has an adjustable fan off time of 60, 90, 120 and 150 seconds that is set by selecting a dipswitch combination on the control board displayed in Table 5. Similarly the United Technologies 1158-120 have an adjustable fan off time of 2, 3, 4 or 6 minutes displayed in Table 6. The fan off delay time starts when the burner motor is de-energized at the end of a call for heat. Blower shutdown is delayed to remove any residual heat from the heat exchanger and improve the annual efficiency of the furnace. The electronic fan timer board works in conjunction with snap disc limit controls, which perform a safety function, and breaks power to the oil burner primary control, which shuts off the burner if the furnace over-heats. The limit control is thermally operated and automatically resets. The limit control is factory installed, pre-set and is not adjustable. If a limit control opens, the Honeywell ST9103 will energize the circulating fan. When the limit control closes the burner is re-energized and the heating cycle begins again.If the limit control opens with the United Technologies 1158-120 electronic fan control, the circulating fan will be energized as well. When the limit closes, the control initiates a two minute delay. When this delay is finished, the fan off timer will begin. At the end of the fan off time cycle the burner will be energized, initiating a normal burner cycle. TABLE 5 Honeywell ST9103 Dip Switch Blower Off Delay Position Time 1 2 On On 60 seconds On Off 90 seconds Off On 120 seconds Off Off 150 seconds TABLE 6 United Technologies 1158-120 Dip Switch PositionBlower Delay Times 1234On SecondsOff Minutes OffOff30 OnOff60 OffOn90 OnOn120 OffOff2 OnOff3 OffOn4 OnOn6 Note: It is advisable not to set the fan on delay time for a time period longer than 90 seconds at highest input. Longer fan on delay times may result in nuisance limit trips. CIRCULATING AIR BLOWER All WML-C AND MPL-B furnace models are equipped with a direct drive blower system. Direct drive blower speed adjustments are not normally required in properly sized extended plenum duct systems. The motor RPM and air CFM delivery will vary automatically to accommodate conditions within the usual range of external static pressures typical of residential duct systems. Under-sized duct systems may require a higher blower speed to obtain a reasonable system temperature rise. Some older duct systems were not designed to provide static pressure. They typically feature special reducing fittings at each branch run and lack block ends on the
Dip Switch PositionBlower Off Delay Time 12 OnOn60 seconds OnOff90 seconds OffOn120 seconds OffOff150 seconds
Page 9 of the Field Controls Draft Inducer (WML-C) user manual — Fig 1 Suspended Installation
Page 9 · click to enlarge
Page 9
trunk ducts. These systems may require modification to provide some resistance to the airflow to prevent over-amping of the direct drive blower motor. Selecting a lower blower speed may correct this problem. Direct drive blower speeds are adjusted by changing the "hot" wires to the motor winding connections. Please refer to wiring diagram in Appendix B or the wiring diagram label affixed to the furnace. THE NEUTRAL WIRE (normally the white wire) IS NEVER MOVED TO ADJUST THE BLOWER SPEED.box, tape off both ends of the unused wire.into contact with the furnace heat exchanger. Do not use direct drive motor connections as a source of power for 120 VAC humidifiers and humidifier transformers. OIL BURNER The oil burner must align properly with the cerafelt fiber chamber (firepot). The cerafelt fiber chamber is initially quite soft, but hardens and becomes quite brittle after the first firing. The firepot is held in place by a retaining bracket; however, it is possible for the firepot to shift if subjected to rough handling during transit. BEFORE OPERATING THE FURNACE CHECK BURNER ALIGNMENT WITH COMBUSTION CHAMBER. THE END CONE OF THE AIR TUBE MUST BE CENTRED TO THE ACCOMODATING RING PROVIDED IN THE DESIGN OF THE COMBUSTION CHAMBER. ADJUST ALIGNMENT AS NECESSARY BEFORE THE FIRST FIRING. OIL BURNER NOZZLES WML-C AND MPL-B furnaces are certified for multiple firing rates, ranging from approximately 58,000 to 85,600 BTU/hr. on the WML-C and 85,500 to 123,000 BTU/Hr. on the MPL-B By changing the oil burner nozzle within the specific model range, and temperature rise, the furnace may be fired at an ideal rate for a wide range of structures. ertical Smoke Test Port Location DISCONNECT THE POWER SUPPLY TO THE FURNACE BEFORE OPENING THE BLOWER ACCESS DOOR TO SERVICE THE AIR FILTER, FAN AND MOTOR. FAILURE TO SHUT OFF POWER COULD ALLOW THE BLOWER TO START UNEXPECTEDLY, CREATING A RISK OF DEATH OR PERSONAL INJURY. Do not use the blower speed wires as a source of power to accessories as electronic air cleaners and humidifier transformers. The unused motor taps auto-generate sufficiently high voltages to damage accessory equipment. Use the terminals provided on the electronic fan timer. DO NOT CONNECT POWER LEADS BETWEEN MOTOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYS BE CONNECTED TO THE MOTOR'S DESIGNATED NEUTRAL TERMINAL. It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to connect the wiring from both modes is to use a "piggy-back connector" accommodating both wires on a single motor tap. It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape. If the joining of the blower speed wiring is done in the furnace junction Figure 4: Horizontal Smoke TestDo not start the burner or blower fan unless the blower access door is securely in place. Additional ST9103 Fan Timer Control information is in Appendix A, Tables, and in Appendix B, Wiring Diagrams. HUMIDIFIER A humidifier is an optional accessory available through most heating supplies outlets. Installation should be carried out in accordance with the humidifier manufacturer's installation instructions. Water or water droplets from the humidifier should not be allowed to come Port Location Figure 5: V Figure 4: Horizontal Smoke TestPort LocationFigure 5: Vertical Smoke Test Port Location
Field Controls Draft Inducer (WML-C) — Fig 1 Suspended Installation diagram (page 9)
Fig. 5 · Fig 1 Suspended Installation
Field Controls Draft Inducer (WML-C) — Fig 1 Suspended Installation diagram (page 9)
Fig. 6 · Fig 1 Suspended Installation
Page 10 of the Field Controls Draft Inducer (WML-C) user manual — SMOKE TEST NOTE :
Page 10 · click to enlarge
Page 10

BURNER ELECTRODES

PROCEDURE:

excess air, or contaminated fuel. Do not ignore this indicator.

Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of the burners is essential for smooth light ups and proper operation. The electrode tips should be adjusted to a gap of 5/32”, 1/16” ahead of the nozzle, 5/16” above the centerline of the nozzle. The “Z” dimension (front edge of the burner head to the front face of the nozzle is 1-1/8 inches.

Start the burner and allow it to run at least ten minutes. Set the air shutter to give a good flame visually. The combustion air supply to the burner is controlled by manipulating the air shutter on the left side of the burner, and, if necessary, the bulk air band. To adjust, loosen the bolt on the movable shutter. Move the shutter gradually until a good flame (visually) has been achieved. Re- snug the bolt.

STACK TEMPERATURE:

Stack temperature will vary depending on fuel input, circulating air blower speed, and burner set up, etc. In general, stack temperature should typically range between 380°F to 550°F, assuming that the combustion air is approximately room temperature (65°F - 70°F). In general, lower stack temperature indicates greater efficiency; however, excessively low stack temperature can lead to condensation forming in the chimney and / or venting. Sulphur and similar contaminants in the fuel oil will mix with condensation to form acids. Acids and resultant chemical salts will cause rapid deterioration of the chimney and venting components, and may attack the furnace.

Electrode positioning should be checked before the first firing of the furnace.

Check the initial draft setting as the furnace warms up. The draft may be measured at the test port. The breech draft should be approximately - 0.05” w.c. to obtain an over fire draft reading of - 0.02 inches w.c.

The electrode porcelains should be free of cracks, the electrode tips should be tapered and free of burrs, and the contact rods must be clean and be in firm contact with the ignition transformer contact springs. The electrodes must not come into contact with the burner head.

Check the oil pump pressure. Standard operating pressure is 100 PSIG.

OIL BURNER SET-UP

After reaching steady state, take a smoke test. If not indicating a trace, set the combustion air controls to provide a trace.

If the flue gases are below the range, it may be necessary to slow down the blower fan. If the flue gases are above the range, the blower fan may require speeding up. Stack temperature varies directly with the system temperature rise. System temperature rise is the difference between the furnace outlet temperature and furnace inlet temperature as measured in the vicinity of the connection between the plenum take-offs and the trunk ducts.

The burner air supply is adjusted to maintain the fuel to air ratio to obtain ideal combustion conditions. A lack of air causes "soft" and "sooty" flames, resulting in soot build-up throughout the heat exchanger passages. Excess combustion air causes a bright roaring fire and high stack temperatures resulting in poor fuel efficiency.

Typically, the CO2 reading will range from 11.5% to 13.5%.

After the air adjustments have been completed, and the air shutter or air adjustment plate has been secured, re- check the over fire draft and take another smoke test to ensure that the values have not changed.

PREPARATIONS:

Drill a ¼” test port in the venting, ideally at least 2 flue pipe diameters away from the furnace breeching, if venting horizontally from the furnace, or from the flue pipe elbow if venting vertically before reaching the furnace. (See Figures 4 and 5).

If the venting from the furnace to the chimney is long, or exposed to cold ambient temperatures, it may be necessary to use L-Vent as the vent connector to reduce stack temperature loss to prevent condensation. The venting should be inspected annually to ensure that it is intact.

Field Controls Draft Inducer (WML-C) — PREPARATIONS: diagram (page 10)
Fig. 7

The test port will allow flue gas samples to be taken and stack temperatures to be measured.

FURNACE INSTALLATION SETUP

Before starting the burner, check the burner alignment with the combustion chamber (fire pot), check that the correct nozzle is tightened into place, and that the burner electrodes are properly positioned.

The furnace must be set up as the final step in the installation.

A) The oil burner must be set up following the procedures outlined above.

B) The WML-C models should operate within a temperature rise of 45°F to 75°F. The MPL-B temperature rise range should be 50°F to 80°F. To determine the temperature rise, measure the supply air and return air temperatures when the furnace has reached steady state conditions. This is the point at which the supply air temperature stops increasing relative to the return air temperature. The furnace may have to run 10 to 15 minutes to reach steady state conditions. The measurements may be made with duct thermometers or thermocouples

The Beckett burner bulk air band is should be closed, and the air shutter initial setting should be approximately 7.00.

Field Controls Draft Inducer (WML-C) — FURNACE INSTALLATION SETUP diagram (page 10)
Fig. 8

Figure 6: Checking Over-Fire Draft.

SMOKE TEST NOTE :

If oily or yellow smoke spots are found on the smoke test filter paper, it is usually a sign of unburned fuel. This indicates poor combustion. This type of problem may be caused by excess draft,

Page 11 of the Field Controls Draft Inducer (WML-C) user manual — BURNER ELECTRODES
Page 11 · click to enlarge
Page 11
used in conjunction with multi-meters with temperature measurement capabilities. The return air should be measured at a point where the thermometer will be well within the air stream near the furnace return air inlet. Actual location is not particularly critical; however, avoid locations where the temperature readings could be affected by humidifier bypass ducts, the inside radius of elbows, etc. The supply air temperature should be measured at a point where the thermometer will be well within the air stream near the furnace supply air outlet. Usually, the side mid-point of the supply air plenum take-off is ideal, providing it is out of the line of sight to the heat exchanger. If the thermometer is within the line of sight of the heat exchanger, the supply air readings may be skewed by radiant heat from the heat exchanger. If the plenum take-off is unsuitable, the supply air temperature may be measured within the first 18 inches of the first segment of supply air trunk duct. If the temperature rise is outside the recommended range, it may be adjusted on direct drive equipped units by selecting alternate circulation fan motor speeds. If the temperature rise is too high, speed the fan up. If the temperature rise is too low, slow the fan down. C) Keep in mind that the stack temperature varies directly with the temperature rise. The higher the temperature rise, the higher the stack temperature will be, resulting in lower efficiency. The lower the temperature rise, the lower the stack temperature will be, which, in some cases, may allow condensation to form in the chimney and other vent parts. D) Test the high limit control to ensure that it is operating correctly. This may be done by temporarily removing the circulator fan heating wire or neutral wire. Turn of electrical power to the furnace before working with the motor wires. Be sure to protect any removed wires from shorting out on metal furnace parts. If the high limit test is successful, shut off the electrical power to the furnace, restore the proper motor wiring. Finally, restore power to the furnace. E) Operate the furnace through a minimum of three full heating cycles. During this time, check for fuel oil leaks, gross air leakage from the supply air ductwork, unusual noises originatinganywhere within the heating system which may cause some concern or annoyance to the home owner, etc. F) Be sure that the homeowner is familiar with the furnace. The homeowner should be aware of the location of electrical circuit breaker or fuse, the location of any electrical switches controlling the furnace, the location of the oil tank shut-off valve and how to operate the valve. The homeowner should be informed where the oil tank gauge is located and how to read it. It would be beneficial to review safety issues with the home owner, such as the danger of storing combustibles too close to the furnace, hanging anything on the furnace vent pipe, and especially the dangers of indiscriminately pressing the burner reset button. IMPORTANT: Be sure that the home owner knows where the burner reset switch is located, and is aware that the reset switch is not to be activated more than once without a thorough look for the cause of the problem, (lack of fuel, etc.). Be sure that the homeowner knows when to quit trying to start the furnace during these conditions and who to call for emergency service. MAINTENANCE AND SERVICE A: Routine Maintenance By Home Owner Other than remembering to arrange for the annual professional servicing of the furnace by the service or installation contractor, the most important routine service performed by the homeowner is to maintain the air filter or filters. A dirty filter can cause the furnace to over-heat, fail to maintain indoor temperature during cold weather, increase fuel consumption and cause component failure. The furnace filter(s) should be inspected, cleaned or replaced monthly. The furnace is factory equipped with a semipermanent type filter. If the filter is damaged, replace with filters of the same size and type. During the routine service, inspect the general condition of the furnace watching for signs of oil leaks in the vicinity of the oil burner, soot forming on any external part of the furnace, soot forming around the joints in the vent pipe, etc. If any of these conditions are present, please advice your service or installation contractor.B: Annual Service By Contractor THE COMBUSTION CHAMBER (FIREPOT) IS FRAGILE. USE CARE WHEN INSPECTING AND CLEANING THIS AREA. The heat exchanger should be inspected periodically and cleaned if necessary. If cleaning is necessary, SHUT OFF POWER TO THE FURNACE and remove the burner. Using a stiff brush with a wire handle, brush off scale and soot from inside the drum and flue pipe. To clean the radiator, remove the round cover or covers on the inner radiator access pipes located on the front panel between the oil burner and the flue pipe. Rear breech models have a single front cleanout and front breech models have two front cleanouts. A wire brush can be used to loosen dirt and debris on the inside surfaces of the radiator. Clean out all accumulated dirt, soot and debris with a wire handled brush and an industrial vacuum cleaner. Replace the clean-out covers. Most circulating fan motors are permanently lubricated by the motor manufacturer. These motors will have no oil ports. If the blower motor does contain oil ports, under normal operating conditions it will not require oiling for the first two years. Oil sparingly; a few drops in each oil port with SAE 20 nondetergent oil. Oiling is most easily done with a "tele-spout" oiler. This oiler has a long flexible plastic spout. DO NOT OVER-LUBRICATE. Excess oil may result in premature electric motor failure. Inspect the blower fan. Clean it if necessary. Oil Burner Maintenance: Follow the instructions of the oil burner manufacturer. (See oil burner manufacturer's instructions supplied with furnace). The oil burner nozzle should be replaced annually. We recommend that the oil filter be changed on an annual basis. The venting system should be cleaned and inspected for signs of deterioration. Replace pitted or perforated vent pipe and fittings. The barometric draft regulator should open and close freely. All electrical connections should be checked to ensure tight connections. Safety controls such as the high limit controls should be tested for functionality. The fan control functions
Page 12 of the Field Controls Draft Inducer (WML-C) user manual — OPERATING INSTRUCTIONS
Page 12 · click to enlarge
Page 12

should be checked to ensure that all fan speeds are operating properly.

furnace and set the thermostat above room temperature. After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function test is complete, shut off electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then resume operation and continue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.

OPERATING INSTRUCTIONS

Open all supply and return air registers and grilles.

Open all valves in oil pipes.

Turn on electric power supply

Set the thermostat above room temperature to call for heat. The burner should start. NOTE: It may be necessary to press the RESET button on the primary combustion control relay.

To Shut Down Unit

Set the thermostat to the lowest possible setting.

There will be a fan on time delay before the circulating fan is energized. The Honeywell ST9103 has a fixed fan delay on time of 30 seconds after the burner ignites. The United Technologies 1158- 120 has an adjustable fan on time that is set by selecting the dipswitch combination displayed in Chart 1. This fan on delay can be set at 30, 60, 90 or 120 seconds.

Set the manual switch (if installed) in the Electrical Power Supply Line to "OFF".

Set the thermostat below room temperature. The oil burner should stop.

DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED, WHEN THE FURNACE IS FULL OF VAPOUR, OR WHEN THE COMBUSTION CHAMBER IS VERY HOT. NEVER BURN GARBAGE OR PAPER IN THE FURNACE, AND NEVER LEAVE PAPER OR RAGS AROUND THE UNIT.

The air circulation blower will continue to run until the time off setting selected on the electronic fan timer control times out. The Honeywell ST9103 has an adjustable fan off time of 60, 90, 120 and 150 seconds that is set by selecting a dipswitch combination on the control board. Similarly the United Technologies 1158-120 has an adjustable fan off time of 2, 3, 4 or 6 minutes The fan timer control adjustments may be altered if the air at the room registers is uncomfortably high upon blower start up or shutdown.

The necessary adjustments to the fan control settings should be determined by measuring the temperature of the air in the supply air take-off, or within the first few inches of the supply air trunk. The side mid point of the transition is usually ideal, providing that the thermometer probe is beyond the "line of sight" wherein false readings from radiant heat could be observed. The system temperature rise, the difference in temperature between the supply air and return air, should be within the indicated range on the appliance rating plate.

To check the operation of the limit switch, shut off power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the

Before Lighting · To Light Unit

Page 13 of the Field Controls Draft Inducer (WML-C) user manual — Model Nozzle Pump Pressure Flow Rate Air Gate Turbulator
Page 13 · click to enlarge
Page 13

APPENDIX AWML-C AND MPL-B BURNER SET UP

WML-C AND MPL-B furnaces may be used with the following oil burners.

Please note: The Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only. For sidewall venting applications utilizing outdoor air for combustion, use the Beckett AFII or the Riello 40BF (Balanced Flue) oil burners only.

Table A-1 Beckett AF Oil Burner Set-Up

Field Controls Draft Inducer (WML-C) — APPENDIX AWML-C AND MPL-B BURNER SET UP diagram (page 13)
Fig. 9

Beckett AF Series Oil Burners (For use with chimney vented units only)

Model Nozzle Pump Pressure Flow Rate Head 1 Static

WML-60C 2 58,000 AF76BNHS 0.50 / 80°A 100 PSIG 0.50 USGPH F3 3- ⅜ in.

WML-80C 75,000 AF76BNHS 0.65 / 80°A 100 PSIG 0.65 USGPH F3 3- ⅜ in.

WML-90C 85,600 AF76BNHS 0.75 / 80°A 100 PSIG 0.75 USGPH F3 3- ⅜ in.

MPL-90B 85,500 AF76XN 0.75 / 80°A 100 PSIG 0.75 USGPH F3 2- ¾ in.

MPL-100B 96,000 AF76XN 0.85 / 80°A 100 PSIG 0.85 USGPH F3 2- ¾ in.

MPL-120B 112,000 AF76XN 1.00 / 60°A 100 PSIG 1.00 USGPH F3 2- ¾ in.

MPL-130B 123,000 AF76YB 1.10 / 70°A 100 PSIG 1.10 USGPH F6 2- ¾ in. 1 Head is shielded by ceramic insulator. 2 Low Firing Rate Baffle required when using a 0.50-gallon nozzle.

Table A-2 Beckett AFII Oil Burner Set-Up

Field Controls Draft Inducer (WML-C) — Table A-2 Beckett AFII Oil Burner Set-Up diagram (page 13)
Fig. 10 · Table A-2 Beckett AFII Oil Burner Set-Up

Beckett AFII Series Oil Burners (For use with sidewall vented units using outdoor combustion air)

WML-60CB2 63,500 AFII-85 0.50 / 60°A 145 PSIG 0.55 USGPH FB0

WML-80CB2 75,000 AFII-85 0.60 / 60°A 145 PSIG 0.65 USGPH FB3

WML-90CB2 85,600 AFII-85 0.70 / 60°A 145 PSIG 0.75 USGPH FB3

MPL-90BB2 85,500 AFII-150 0.70 / 60°A 145 PSIG 0.75 USGPH FB0

MPL-100BB2 96,000 AFII-150 0.80 / 60°A 145 PSIG 0.85 USGPH FB3

MPL-120BB2 112,000 AFII-150 0.85 / 70°A 145 PSIG 1.00 USGPH FB3

Table A-3 Riello 40F Series Oil Burner Set-Up

Field Controls Draft Inducer (WML-C) — Table A-3 Riello 40F Series Oil Burner Set-Up diagram (page 13)
Fig. 11 · Table A-3 Riello 40F Series Oil Burner Set-Up

Riello 40F Series Oil Burners (For use with chimney vented units)

Model Nozzle Pump Pressure Flow Rate Air Gate Turbulator

WML-60CRF 59,500 40F3 0.50 / 60°W 105 PSIG 0.51 USGPH 2.6 1.0

WML-80CRF 75,000 40F3 0.60 / 60°W 115 PSIG 0.65 USGPH 2.6 1.5

WML-90CRF 85,600 40F3 0.65 / 60°W 135 PSIG 0.75 USGPH 3.6 2.0

MPL-90BRF 85,500 40F5 0.60 / 60°W 145 PSIG 0.75 USGPH 2.25 0.0

MPL-100BRF 96,000 40F5 0.65 / 60°W 145 PSIG 0.85 USGPH 2.5 0.5

MPL-120BRF 112,000 40F5 0.85 / 60°W 145 PSIG 1.00 USGPH 2.75 1.0

Page 14 of the Field Controls Draft Inducer (WML-C) user manual — A.3 START UP
Page 14 · click to enlarge
Page 14

Table A-4 Riello Balanced Flue (BF) Burner Set-Up

Riello Balanced Flue Series Oil Burners (For use with sidewall vented units using outdoor combustion air)

Furnace

Output BTU/Hr

Burner

Model Nozzle Pump Pressure Flow Rate Turbulator

Model

Setting

WML-60CRB 59,500 40BF3 0.50 / 60°W 105 PSIG 0.51 USGPH 1.0

WML-80CRB 75,000 40BF3 0.60 / 60°W 115 PSIG 0.65 USGPH 1.5

WML-90CRB 85,600 40BF3 0.65 / 60°W 135 PSIG 0.75 USGPH 2.0 NOTE: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve zero smoke. A.1 OIL BURNER AIR ADJUSTMENT

A.2 BURNER ELECTRODES

system temperature rise. System temperature rise is the difference between the furnace outlet temperature and furnace inlet temperature as measured in the vicinity of the connection between the plenum take- offs and the trunk ducts

Adjustment of the electrode tips with respect to each other, the nozzle, and to the rest of the burner is very important to ensure smooth start-ups and to permit efficient combustion.

For complete details, consult the oil burner instruction manual provided in the furnace documents envelope.

Perform a smoke spot test. The smoke spot should not exceed No. 1 on the Bacharach Scale.

Adjust the air shutter by loosening the locking screws and moving the air shutter, and if necessary, the bulk air band.

Electrode gap: 5/32 inch.

Distance above horizontal centerline: 5/16 inch. Older instruction sheets specify 7/16 inch. The current specification is 5/16 inch.

After the air adjustments have been completed, re-check the draft pressure at the test port on the burner mounting plate as shown in Figure #6. The draft should be adjusted to 0.02 inches w.c.

Adjust the burner air supply by first loosening the locking screw located on the black dial to the right of the burner. Turn the black dial clockwise to increase the combustion air and counter-clockwise to decrease the combustion air. Re-tighten the locking screw after obtaining the proper setting.

Distance ahead of nozzle: 1/16 inch.

“Z” dimension, the distance from the front of the end cone (head) to the face of the nozzle should be 1-1/8 inches. If a ceramic head is used, the distance from the end cone to the nozzle face is increased to 1-3/8 inches.

In the United States, the Beckett AF Burner may be equipped with Beckett's "Inlet Air Shut-Off" to increase efficiency. (Beckett Part No. AF/A 5861).

Riello 40 Series (Chimney Vented)

Riello 40F, & BF Burners

Riello burners are factory set with respect to nozzle size; pump pressure, air gate and turbulator adjustments for each model and firing rate. By removing the burner cover and loosening the screws that secure the air adjustment plate, the combustion air can be adjusted. Move the adjusting plate to either increase or decrease combustion air. When the proper air setting is achieved, retighten the fixing screws.

Electrode gap: 5/32 inch.

Distance above horizontal centerline: 13/64 inch.

A.4 SPECIAL INSTRUCTIONS FOR UNITS EQUIPPED WITH RIELLO BURNERS

Distance ahead of nozzle: 5/64 to 7/64 inch.

Riello burners are factory set with respect to nozzle size, pump pressure, air gate and turbulator adjustments for each model and firing rate; therefore, do not use the above listed set up procedures.

A.3 START UP

The furnace should be operated for a minimum of 15 minutes to reach steady state conditions before fine tuning combustion. The warm up time is ideal for testing the oil pump pressure.

Riello Balanced Flue (BF) Series

Riello specifications are listed in Tables A-3 and A-4. Consult the Riello Installation Instructions supplied with the Burner for specific information concerning burner adjustments, operation, and trouble-shooting.

Riello burners are factory set with respect to nozzle size; pump pressure, and turbulator adjustments for each model and firing rate. The combustion air can be adjusted with the burner cover on by first removing the plastic cover on the top right hand side of the burner cover. With a Philips head screw driver, turn the adjustment screw clockwise to increase combustion air or counter-clockwise to decrease combustion air. When the combustion air is set, re-insert the plastic cover.

Drill a 1/4-inch test port in the venting between the furnace flue outlet and draft regulator (barometric damper). Insert a stack thermometer and note the flue gas temperature. The flue gases should be within a range of 350°F to 450°F. If the flue gases are below the range, it may be necessary to slow down the blower fan. If the flue gases are above the range, the blower fan may require speeding up. Stack temperature varies directly with the

Beckett AF Burner · Beckett AF Burner · Beckett AFII Burner

Page 15 of the Field Controls Draft Inducer (WML-C) user manual — Table A-8 Direct Drive Blower Characteristics
Page 15 · click to enlarge
Page 15

x SystemTemperatureRise SystemTemperatureRise Bonnet Output

Field Controls Draft Inducer (WML-C) — x SystemTemperatureRise SystemTemperatureRise Bonnet Output diagram (page 15)
Fig. 12 · x SystemTemperatureRise SystemTemperatureRise Bonnet…
Field Controls Draft Inducer (WML-C) — x SystemTemperatureRise SystemTemperatureRise Bonnet Output diagram (page 15)
Fig. 13 · x SystemTemperatureRise SystemTemperatureRise Bonnet…

( ) ( ) CFM Bonnet Output

x CFM = = 1085 1085 . .

MPL-90B GT12-10DD Low ¾ HP Med-High ¾ HP 3 ¾ HP 1185 – 1553

MPL-100B GT12-10DD Med-High ¾ HP High ¾ HP 3 ¾ HP 1185 – 1553

MPL-120B GT12-10DD High ¾ HP High ¾ HP 3 ¾ HP 1185 – 1553

MPL-130B GT12-10DD High ¾ HP High ¾ HP 3 ¾ HP 1185 – 1553

WML-60C GT10 DD Low ½ HP Med-Low ½ HP 3 ½ HP 763 – 1505

WML-80C GT10 DD Med-Low ½ HP Med-High ½ HP 3 ½ HP 763 – 1505

WML-90C GT10 DD Med-High ½ HP High ½ HP 3 ½ HP 763 – 1505

LOW 813 813 797 763 MED-LOW 1170 1144 1118 1063 MED-HIGH 1423 1381 1291 1220

LOW 1334 1286 1239 1185 MED-LOW 1389 1332 1287 1236 MED-HIGH 1423 1373 1326 1289

These Formulae will assist with the design of the ductwork and the determination of airflow delivery:

Table A-8 Direct Drive Blower Characteristics

Table A-6 Direct Drive Blower Set-Up

TIP:

60 - 90 GT10 ½ HP 7.0 45-75°F

90-130 GT12-10DD ¾ HP 12.5 50-80°F

Model Blower

WML-C

MPL-B

Page 16 of the Field Controls Draft Inducer (WML-C) user manual — Table A-9 General Dimensions (Inches)
Page 16 · click to enlarge
Page 16
Field Controls Draft Inducer (WML-C) — Table A-9 General Dimensions (Inches) diagram (page 16)
Fig. 14 · Table A-9 General Dimensions (Inches)
Field Controls Draft Inducer (WML-C) — Table A-9 General Dimensions (Inches) diagram (page 16)
Fig. 15 · Table A-9 General Dimensions (Inches)

WML-C 22 22-1/8 55-1/4 19 x 19 18 x 18 18 x 18 5 Permanent 20 x 20 x 1 265

MPL-B 22-1/4 22-1/4 62 20-1/2 x 20- 1/2 18 x 18 18 x 18 6 Permanent 20 x 20 x 1 292

Down flow WML-C & MPL-B

Table A-9 General Dimensions (Inches)

WML-C &

MPL-B

A Depth

Model Width

Horizontal

Page 17 of the Field Controls Draft Inducer (WML-C) user manual — APPENDIX B: WIRING DIAGRAMS
Page 17 · click to enlarge
Page 17
Field Controls Draft Inducer (WML-C) — APPENDIX B: WIRING DIAGRAMS diagram (page 17)
Fig. 16

APPENDIX B: WIRING DIAGRAMS

Beckett AF Burner Wiring Diagram

Page 18 of the Field Controls Draft Inducer (WML-C) user manual — Beckett AFII Burner Wiring Diagram
Page 18 · click to enlarge
Page 18
Field Controls Draft Inducer (WML-C) — Beckett AFII Burner Wiring Diagram diagram (page 18)
Fig. 17 · Beckett AFII Burner Wiring Diagram

Beckett AFII Burner Wiring Diagram

Page 19 of the Field Controls Draft Inducer (WML-C) user manual — Riello 40F3 and F5 Burner Wiring Diagram
Page 19 · click to enlarge
Page 19
Field Controls Draft Inducer (WML-C) — Riello 40F3 and F5 Burner Wiring Diagram diagram (page 19)
Fig. 18 · Riello 40F3 and F5 Burner Wiring Diagram

Riello 40F3 and F5 Burner Wiring Diagram

Page 20 of the Field Controls Draft Inducer (WML-C) user manual — Riello 40BF3 Burner Wiring Diagram
Page 20 · click to enlarge
Page 20
Field Controls Draft Inducer (WML-C) — Riello 40BF3 Burner Wiring Diagram diagram (page 20)
Fig. 19 · Riello 40BF3 Burner Wiring Diagram

Riello 40BF3 Burner Wiring Diagram

Page 21 of the Field Controls Draft Inducer (WML-C) user manual — OPERATION OF OIL BURNER
Page 21 · click to enlarge
Page 21

OPERATION OF OIL BURNER

resume operation and continue until the thermostat is satisfied. Restore the thermostat setting to a comfortable temperature.

Once the furnace flue pipe, electrical and oil line connections have been made, use the following instructions to set the burner:

Set the heat anticipator adjustment in the thermostat (if so equipped), by removing the "R" or "W" wire to the thermostat, then reading the amperage draw between the two wires. Failure to remove one of the wires from the thermostat while performing this test could burn out the heat anticipator. Set the heat anticipator to the amperage measured.

Shut off the electrical power to the furnace.

Install an oil pressure gauge to the pressure port on the oil pump. (Refer to the oil pump specification sheet included with the burner instructions).

Restore electrical power to the furnace.

Start the furnace and bleed all air from the fuel oil lines.

Close the purge valve and fire the unit.

Allow the furnace to warm up to normal operating temperatures. During this time, set the pump pressure in accordance with the data provided in Appendix A, Table A-2, and A-5.

When the furnace has reached "steady state" (after approximately 15 minutes). Set combustion air damper to get a TRACE of smoke.

Check the system temperature rise. The temperature rise is the difference between the return air temperature measured at a point near the return air inlet, and the supply air temperature measured near the furnace outlet. If the temperature rise is too high, the airflow must be increased. If the temperature rise is too low, the fan should be slowed down.

Turn off the burner. Observing the duct thermometer in the supply air stream, note the temperature at which the blower fan stops. The fan adjustments can be made by moving the dipswitch settings on the timer control board for fan off delay.

To check the operation of the limit switch, shut off power to the furnace. Temporarily remove the neutral wire from the direct drive blower motor. Restore the electrical power to the furnace and set the thermostat above room temperature. After three or four minutes of burner operation, the limit control should turn the burner off. When the limit function test is complete, shut off electrical power to the furnace, replace the neutral wire to the blower fan motor, and then restore power. The blower fan will start up immediately. Once the temperature has dropped and the limit control has reset, the fan will operate until the fan off time is achieved. The oil burner will then

Page 22 of the Field Controls Draft Inducer (WML-C) user manual — APPENDIX C-R7184 TROUBLESHOOTING
Page 22 · click to enlarge
Page 22

APPENDIX C-R7184 TROUBLESHOOTING

R7184 DETAILED SEQUENCE OF OPERATION (FIGURE 7)

Power is applied to unit. The R7184 completes a self-diagnostic procedure. If no light or flame is present, and unit passes its self-diagnostic procedure, the control enters into the idle mode.

Thermostat calls for heat:

A) Safety check is made for flame (4 second delay).

1. If flame is not present, the R7184 will apply power to the burner motor and igniter.
2. If flame is present, the control remains in the idle state.

B) Unit enters a pre-purge period of 15 seconds.

C) After 10 seconds, control checks for flame presence.

1. If flame is not present, the R7184 enters the trial for ignition state.
2. When flame is present, the control enters lock out mode.

D) Control monitors the burner flame.

1. When flame is present, the control enters ignition carryover state. (Continues to spark for 10 sec.).

a) Provides continuous spark after flame is sensed to assure that burner remains lit.

b) Turns on LED diagnostic light.

c) Starts carryover timer.

(i) Flame and call for heat are monitored.

  • If flame is lost and lockout timer has not expired, R7184 will return to trial for ignition state.
  • If flame is lost and lockout timer has expired, R7184 will enter the recycle state.

♦ Recycle timer starts.

♦ Burner motor and igniter and solenoid valve are turned off.

♦ LED diagnostic light flashes slowly.

E) Carryover timer expires.

1. Enters run state.

a) Igniter turns off.

Combustion continues until thermostat is satisfied, or R7184 detects a loss of flame and enters into Recycle Mode.

F) Thermostat is satisfied - call for heat is terminated:

a) R7184 shuts off burner motor and solenoid valve.

(i) If control utilizes a blower motor off delay, after 30 seconds, flame presence is checked.

  • If flame is not present, the R7184 LED diagnostic light is off and returns to idle state.
  • If flame is presence is detected, the control enters lock out mode.
Page 23 of the Field Controls Draft Inducer (WML-C) user manual — ELECTRONIC FAN TIMER BOARD ON CONTROL PANEL
Page 23 · click to enlarge
Page 23

R7184 INTERRUPTED ELECTRONIC OIL PRIMARY CONTROL

FIGURE 7

Field Controls Draft Inducer (WML-C) — R7184 INTERRUPTED ELECTRONIC OIL PRIMARY CONTROL diagram (page 23)
Fig. 20

ELECTRONIC FAN TIMER BOARD ON CONTROL PANEL

FIGURE 8

Field Controls Draft Inducer (WML-C) — ELECTRONIC FAN TIMER BOARD ON CONTROL PANEL diagram (page 23)
Fig. 21
Page 24 of the Field Controls Draft Inducer (WML-C) user manual — SAFETY CHECK FOR FLAME (5 SEC.)
Page 24 · click to enlarge
Page 24

IDLE STATE

THERMOSTAT CALLS FOR HEAT

R7184 SEQUENCE of

SAFETY CHECK FOR FLAME (5 SEC.)

REMAINS IN IDLE STATE

OPERATION

NO FLAME

FLAME

BURNER MOTOR & IGNITOR START

10 SEC.

SAFETY CHECK FOR FLAME (5 SEC.)

NO FLAME

FLAME

SOLENOID VALVE OPENS

LOCKOUT STATE

TRIAL FOR IGNITION

  • R7184:
  • Shuts off burner motor
  • Shuts off igniter
  • Shuts off Solenoid Valve
  • Fast Flashes LED Diagnostic Light

BURNER FLAME MONITORED

NO FLAME

FLAME

  • CARRYOVER STATE
  • Provides continuous spark
  • LED diagnostic light ON
  • Start Carryover Timer

FLAME LOST

TO EXIT LOCKOUT

PRESS RESET

FLAME

CARRYOVER TIMER EXPIRES

FLAME LOST

FLAME

RUN STATE • Igniter turns off.

FLAME LOST

RECYCLE TIMER STARTS

THERMOSTAT SATISFIED

  • R7184:
  • Shuts off Solenoid Valve
  • Shuts off Igniter
  • Shuts off Burner Motor
  • Slow Flashes LED diagnostic light
  • R7184 SHUTS OFF:
  • Burner Motor
  • Solenoid Valve
  • LED Diagnostic Light

30 SEC.

SAFETY CHECK FOR FLAME (5 SEC.)

RECYCLE TIMER EXPIRES

NO FLAME

(60 SECONDS

FLAME

RETURNS TO IDLE STATE

Page 25 of the Field Controls Draft Inducer (WML-C) user manual — LIMIT
Page 25 · click to enlarge
Page 25

Table C-1: ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF OPERATION

Mode Action System Response

a. EFT closes oil primary control T - T connections). b. Ignition system and R7184 oil primary control start the furnace. Oil flows as long as

Thermostat calls for heat. ("W" terminal is energized).

the oil primary control senses flame. c. Burner motor is energized and heat "fan on" delay timing begins. When timing is

complete, the circulator fan is energized at heat speed.

a. R7184 oil primary control is de-energized, terminating the burner cycle. b. Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch settings. When timing is complete, the circulator fan is de-energized. c. EFT returns to standby mode, (Oil primary control and circulator fan are off, unless continuous fan operation is selected at the thermostat).

Thermostat ends call for heat. ("W" terminal is de-energized).

HEAT

a. Oil primary control locks out within lockout timing, (30 seconds). b. Burner motor is de-energized. (Even though thermostat is still calling for heat). c. If circulator fan has started, it continues through the selected heat “fan off” delay period.

Burner fails to light.

a. Burner motor is de-energized and oil primary control goes into recycle mode. b. If the selected heat “fan off” delay timing is longer than the recycle delay timing, the circulator fan continues to run through the next trial for ignition.

Established flame fails.

Thermostat begins call for cool. (G and Y terminals are energized).

a. Cooling contactor is energized immediately. b. Circulator fan is energized at cool speed. COOL

Thermostat ends call for cool. (G and Y terminals are de- energized).

a. Cooling contactor is de-energized immediately. b. Circulator fan turns off immediately.

Thermostat begins call for fan. (G terminal is energized). a. Circulator fan is energized immediately at cooling speed. FAN

Thermostat ends call for fan. (G terminal is de-energized). a. Circulator fan is de-energized immediately.

a. Oil primary control shuts off burner. b. Circulator fan is energized immediately at heat speed. c. EFT opens oil primary control T - T connections. Circulating fan runs as long as limit string stays open. d. If there is a call for cooling or fan, the circulating fan switches from heating to

Limit switch string opens.

cooling speed.

LIMIT

a. EFT begins heat “fan off” delay sequence. b. Circulating fan turns off after the selected heat “fan off” timing. c. EFT re-closes oil primary control T - T connections. d. Oil primary control is energized, initiating burner light off.

Limit switch string closes (with existing call for heat).

a. Circulator fan turns off when heat “fan off” delay time is complete. b. Normal operation resumes; EFT control is in standby mode awaiting next thermostat command.

Limit switch string closes (without existing call for heat).

a. Circulating fan is energized when there is no call for heat, cool, or fan. b. If fan operation is required by a call for heat, cool, or fan, the EFT switches off the

FAN Continuous circulating fan is connected.

continuous fan speed tap before energizing the other fan speed.

  • Electronic air cleaner (EAC) connections are energized when the heat or cool speed of the circulator fan is energized. EAC connections are not energized when the optional continuous fan terminal is energized.

EAC Electronic Air Cleaner is connected.

HUM Humidity control is connected. • Humidifier connections are energized when the oil burner motor is energized.

Page 26 of the Field Controls Draft Inducer (WML-C) user manual — CHECK OIL PRIMARY CONTROL AND IGNITER
Page 26 · click to enlarge
Page 26

R7184 LED DIAGNOSTIC LIGHT

TROUBLESHOOTING

The LED diagnostic light has several functions. It indicates the state or mode in which the oil burner is operating. It will also indicate fault conditions, and help determine cad cell resistance while the burner is operating.

Electrical Shock Hazard.

Troubleshooting is done with the system powered. Be careful to observe all necessary precautions to prevent electrical shock or equipment damage.

PRELIMINARY STEPS:

NORMAL CONDITIONS :

Check the diagnostic light for indications of burner condition. Refer to R7184 LED DIAGNOSTIC LIGHT section for details.

PRELIMINARY CHECKS :

The LED diagnostic light will turn on when the burner enters the carryover state; the point at which ignition spark is on, and will remain on through the run state, where the ignition spark is terminated but the burner continues to fire.

Make sure that limit switches are closed and those contacts are clean.

Check for line voltage power on the oil primary control black and white lead wires.

WHEN SIMULATING A CALL FOR HEAT AT THE R7184, DISCONNECT AT LEAST ONE THERMOSTAT LEAD WIRE FROM THE T1 - T2 TERMINALS TO PREVENT DAMAGE TO THE THERMOSTAT. NEGLECTING THIS PROCEDURE MAY BURN OUT THE HEAT ANTICIPATOR OF A STANDARD 24 VAC THERMOSTAT, OR CAUSE HARM TO COMPONENTS WITHIN A MICRO-ELECTRONIC THERMOSTAT.

Refer to Table C-4 or C-5 for further troubleshooting information.

The LED diagnostic light will turn off at the end of the burner cycle as the R7184 enters the idle state, and will remain off until the next heating cycle.

FAULT CONDITIONS:

If the LED diagnostic light is flashing quickly; 1 Hz (½ second on / ½ second off), the R7184 is in the lockout state or in restricted mode. To exit the lockout state, press the reset button.

Before checking the oil primary control, perform these preliminary checks, (repair or replace controls as necessary):

If the LED diagnostic light is flashing slowly; ¼ Hz (2 seconds on / 2 seconds off), the R7184 is in the recycle state. This indicates that flame sensing was lost after the lockout timer expired during the ignition carryover state. The R7184 will return to the idle state within 60 seconds.

  • Check the power supply; fuse box or breaker, any service switches, all wiring connections, and burner motor reset button (if equipped).
  • Check the limit switches to ensure that the switch contacts are closed.

CAD CELL CONDITION :

  • Check the electrode gap and position.

If the LED diagnostic light is off, the cad cell is not sensing flame.

  • Check the contacts between the oil primary control and the electrodes.

If the LED diagnostic light is on, the cad cell is sensing flame, or viewing ambient light.

  • Check oil supply (tank gauge).

The resistance of the cad cell may be checked while the R7184 is in the run state by pressing the reset button. The LED diagnostic light will flash the following code:

  • Check the oil nozzle, oil filter, and oil valves.
  • Check the piping or tubing to the oil tank.

TABLE C-2: CAD CELL RESISTANCE

  • Check the oil pump pressure.

CHECK OIL PRIMARY CONTROL AND IGNITER

Flashes Resistance in Ohms

If the trouble does not appear to be in the burner or ignition hardware, check the oil primary control and the igniter by using the following equipment:

1 Less than 400

2 Between 400 - 800

Screwdriver.

3 Between 800 – 1600

Voltmeter (0 - 150 VAC)

Insulated jumper wires with both ends stripped.

4 Between 1600- 5000

Page 27 of the Field Controls Draft Inducer (WML-C) user manual — N/A N/A
Page 27 · click to enlarge
Page 27

Table C-3: R7184 TROUBLESHOOTING Condition: Burner motor does not start when there is a call for heat.

Procedure Status Corrective Action

1. Check that limit switches are closed and contacts are clean. N/A N/A
2. Check for line voltage power at the oil primary control. Voltage should be 120 Vac between the black and white lead wires on the oil primary control.

N/A N/A

3. Check indicator light with burner off, no call for heat (no flame). Indicator light is on. Cad cell is defective, sees external light, or connections have shorted. Go to step 4.

Indicator light turns off. Eliminate external light source or permanently shield cad cell.

  • Replace cad cell with new cad cell and recheck.
  • If indicator light does not turn off, remove yellow lead wires from R7184 and recheck.
  • If indicator light is still on, replace the R7184 control.
  • If the indicator light turns off, replace cad cell bracket assembly.
4. Shield cad cell from external light. Indicator light stays on.
5. Verify that the oil valve is closed during the “valve on delay” period by opening view port and verifying that no flame is present during the 15-second “valve on delay”.

Indicator light is on. If flame is present, replace the oil valve.

Trouble is in thermostat circuit. Check thermostat-wiring connections. If connections are clean and tight, check thermostat wires for continuity.

Burner starts.

6. Jumper thermostat (T -T) terminals on R7184
  • Disconnect line voltage power and open line switch.
  • Check all wiring connections.
  • Tighten any loose connections and recheck.
  • If burner still doesn't start, replace R7184.

Burner does not start.

If burner still doesn't start, check the oil burner motor. It may be seized or burned out.

Condition: Burner starts then locks out on safety with indicator light flashing at 1/2 second on, 1/2 second off.

Procedure Status Corrective Action

Indicator light stops flashing. Go to Step 8. 7. Reset oil primary control by pushing in and releasing red reset button.

Indicator light continues to flash at 1/2 second on, 1/2 second off rate.

Verify that the control is not in restricted mode. (See notes at end of this table.). If not in restricted mode, replace R7184

Page 28 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 28 · click to enlarge
Page 28

Condition: Burner starts then locks out on safety with indicator light flashing at 1/2 second on, 1/2 second off. (Cont.)

Procedure Status Corrective Action

Ignition is off Spark igniter could be defective. Check for line voltage at igniter terminals. If line voltage is present, replace R7484.

Ignition is on. Go to Step 9. 8. Listen for spark after burner turns on (after 2 second delay). Ignition is on but no oil is being sprayed into the combustion chamber.

Wait for “Valve ON” delay to complete. Check oil supply, and oil line valve. Check for filter blockage or seized oil pump.

Indicator light is on until the control locks out and starts flashing during lockout.

Replace R7184 9. Check indicator light after flame is established, but before oil primary control locks out.

Indicator light stays off. Go to step 10.

10. Check cad cell sighting for view of flame. a. Disconnect line voltage power and open line switch. b. Unplug cad cell and clean cad cell face with soft clothe. Check sighting for clear view of flame. Replace cad cell in socket. c. Reconnect line voltage power and close line switch. d. Start burner.

Burner locks out.

Go to step 11.

Burner keeps running. System is OK.

11. Check cad cell. a. Disconnect line voltage power and open line switch. b. Remove existing cad cell and replace with new cad cell. c. Disconnect all wires from thermostat terminals to ensure that there is no call for heat. d. Reconnect line voltage power and close line switch. e. Expose new cad cell to bright light such as a flashlight.

Indicator light is on.

Remount control onto burner housing. Go to step 6.

Indicator light is off. Go to step 12.

12. Check cad cell bracket assembly. a. Disconnect line voltage power and open line switch. b. Remove cad cell wires from quick connect connectors on the R7184 and leave control lead wires open. c. Apply power to device. d. Place jumper across cad cell terminals after burner motor turns on.

Indicator light is on.

Replace cad cell bracket assembly.

Indicator light is off. Replace R7184.

only 3 times, after which, the control locks out. The reset count returns to zero each time a call for heat is successfully completed.

To reset from RESTRICTED MODE: press and hold the reset button for 30 seconds. When the LED flashes twice, the device has reset.

beginning of the normal heat cycle on SAFETY CHECK.

Page 29 of the Field Controls Draft Inducer (WML-C) user manual — TABLE C4: SYSTEM AND GENERAL TROUBLESHOOTING
Page 29 · click to enlarge
Page 29

TABLE C4: SYSTEM AND GENERAL TROUBLESHOOTING

Problem Possible Cause Remedy

Thermostat not calling for heat. Check thermostat and adjust. Also, check thermostat for accuracy; if it is a mercury switch type, it might be off level.

Check furnace switch, main electrical panel furnace fuse or circuit breaker. Also look for any other hand operated switch, such as an old poorly located furnace switch, which was not removed during furnace replacement.

No power to furnace.

Furnace will not start.

Remove thermostat wires from oil primary control terminals T-T. Place a jumper across T-T. If furnace starts, replace thermostat, thermostat sub- base (if equipped), or both.

Thermostat faulty.

Check reset button on oil primary control. Remove thermostat wires from oil primary control terminals T1 - T2. Check for 24v across T -T. If no voltage is present, check for 115v to oil primary control. If 115v is present, go to Table C-3.

Oil primary control faulty.

Check photo cell (cad cell) wiring for short circuits. Also, check for room light leaking into cad cell compartment. Repair light leak if necessary. See Table C-3. Furnace will not start.

Photo Cell wiring shorted or room light leaking into photo cell compartment

Open safety switch. Check for open limit or auxiliary limit. Also, check internal wiring connections; loose connectors, etc.

No fuel oil. Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.

Clogged nozzle. Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.

Clogged oil filter. Replace oil tank filter or in-line filter if used.

Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)

Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.

Low oil pump pressure.

Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.

Check fuel oil lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.

Defective burner motor. Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if necessary.

If cad cell is dirty, clean it. (Determine why cad cell is getting dirty). If cad cell is poorly aimed, realign it. NOTE: The photocell should have a resistance of 100K Ω in absence of light; a maximum of 1500 Ω in the presence of light. Ensure that room light is not leaking into the cad cell compartment. (See diagnostic light section).

Furnace starts, but cuts out requiring manually resetting the oil protector reset button.

Photo Cell (Cad Cell) defective.

No fuel oil. Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary.

Clogged nozzle. Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide.

Clogged oil filter. Replace oil tank filter or in-line filter if used.

Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line.

Low oil pump pressure.

Furnace starts, but cuts out requiring manually resetting the oil protector reset button.

Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.

Check fuel oil lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants.

Defective burner motor. Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if necessary.

Water or contaminants in oil. Drain fuel oil storage tank, replace fuel oil. (Consult with fuel oil supplier).

Frozen oil line. Gently warm oil line. Insulate oil line. (Outdoor piping size may require increased diameter).

Page 30 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 30 · click to enlarge
Page 30
TABLE C-4SYSTEM AND GENERAL TROUBLESHOOTING continued

Problem Possible Cause Remedy

Electrodes out of adjustment or defective.

Check electrode settings. Check electrodes for dirt build-up or cracks in porcelain.

Poor transformer high voltage connections or defective transformer.

Check contacts between the igniter and electrodes. If OK, replace the igniter

Oil burner sputtering at nozzle

Fuel oil filter clogged. Replace fuel oil storage tank filter and / or fuel oil in-line filter.

Defective oil pump. Check burner motor / fuel oil pump coupling. Check oil pump pressure. Replace fuel oil pump if necessary.

Fuel oil line partially clogged or contains air. Bleed air from oil line. If problem persists, replace oil line.

System temperature rise ideally should not exceed 85°F. Check for clogged air filters. Check blower fan for excess dirt build-up or debris. Speed up blower fan if necessary.

System temperature rise too high.

Check “fan off” delay timing setting. Use a duct thermometer in the supply air plenum take-off or first few inches of the supply air trunk duct. Ideally, the fan will shut off at a temperature of 90° - 100°F. Manipulate the dip switch settings to come as close as possible to this “fan off” temperature.

Poor “fan off” delay timing selection, (fan stops too soon).

Excessive fuel oil consumption.

Fuel oil leak. Check fuel oil line for leaks. Repair or replace if necessary.

Stack temperature too high. Check stack temperature. Stack temperatures will normally range from 350° to 450°F. Check draft regulator. Draft should be set to 0.02 in. w.c.

Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If the thermostat is being influenced by drafts, sunlight, duct work, etc., relocate to more suitable location.

Thermostat improperly adjusted or in poor location.

Adjust the oil burner combustion air band and draft regulator to gain the highest practical CO2 or lowest practical O2 content in the flue gases. See Burner Set Up. Too much smoke.

Insufficient combustion air adjustment at oil burner, or improper draft pressure.

Heat exchanger partially clogged. Check for soot build-up in heat exchanger flue passages, especially in the outer radiator.

Check alignment. Blast tube should be centered with fire pot burner opening. Oil burner head should be ¼ inch back from the inside surface of the fire pot.

Poor alignment between oil burner blast tube and fire pot.

Soot building up on blast tube (end coning).

Flame impingement caused by Incorrect nozzle angle.

Check nozzle size and angle. (See Appendix A). Check distance from head to inside surface of the fire pot.

Defective fire-pot Check fire-pot. Repair or replace.

Airflow blocked or dirty air filter. Clean or replace air filter.

Check thermostat heat anticipator setting against measured amperage draw. Increase heat anticipator setting if necessary. If the thermostat is being influenced by drafts, sunlight, duct work, etc., relocate to more suitable location.

Thermostat adjustments or location.

Check all dampers. Open closed dampers including registers in unused rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.

Insufficient airflow.

Furnace will not warm home to desired temperature.

Test high limit function of all limit switches. Use a duct thermometer to assess accuracy of limit control. Check for obstructions to airflow around limit switch bi-metal elements. Replace control if necessary.

Defective high limit control.

Under-sized nozzle. Check nozzle. If problem is not caused by air flow problems, use larger nozzle, if permitted by rating plate.

Blower fan motor stopping intermittently on overload.

Check blower fan motor amperage draw. Check motor ventilation ports, clean if necessary. Replace motor if necessary.

Burner motor stopping intermittently on overload. Check burner motor. Replace if necessary.

Home does not heat evenly Improper distribution of heat. This is not likely to be a furnace problem. Balance duct system.

Page 31 of the Field Controls Draft Inducer (WML-C) user manual — IMPORTANT:
Page 31 · click to enlarge
Page 31
TABLE C-4SYSTEM AND GENERAL TROUBLESHOOTING continued

Problem Possible Cause Remedy

Airflow blocked or dirty air filter. Clean or replace air filter. Supply air temperature too hot. Insufficient airflow.

Check all dampers. Open closed dampers including registers in unused rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan.

Excess airflow. Check system temperature rise. Slow down blower fan if necessary. Supply air temperature too cool. Excessive duct losses. Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary.

Increase "fan on” dipswitch settings on EFT if control has this option.). Register air deflectors may help. Supply air temperature too cool during first moments of furnace cycle. Excessive duct losses. Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary. FINAL CHECK OUT

Fan control "fan on" setting too low.

Where the circuit breaker or fuse is located in the main electrical panel.

How and where to visually inspect the venting system for leaks or other problems.

ENSURE THAT ALL SAFETY DEVICES AND ELECTRICAL COMPONENTS HAVE BEEN SET FOR NORMAL OPERATION. ENSURE THAT ALL ELECTRICAL CONNECTIONS ARE TIGHT AND THAT THE WIRING IS SECURE.

Where the furnace switch is located, and the switch "on" and "off" positions if not obvious.

How to inspect, clean and replace the air filter, and other homeowner maintenance procedures.

Where the oil shut-off valve from the oil storage tank is located.

Who to call for emergency service and routine annual service.

How to operate the thermostat, and other related accessories.

The terms and conditions of the manufacturer's warranty and the contractor's warranty.

IMPORTANT:

How to operate the manual reset button on the primary control, and especially when not to push the reset button.

Please ensure that the homeowner is informed and understands:

Page 32 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 32 · click to enlarge
Page 32

PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: WML C Ref. No. Description PART NO. 1 Right and Left Side Panel 30072L 2 Rear Panel Baffle 27918 3 Rear Panel 30272L 4 Blower Division Panel Assembly 30311 5 Base Panel Assembly 29007 6 Front Panel 30073L 7 Blower Access Door 30074L Door Handle – P2-41 28673 Logo Bezel 28479 Logo Label 28563 8 End Panel 29013L 9 Heat Exchanger Assembly 27876 10 Firepot Retainer Bracket 27068 11 Replacement Combustion Chamber 2700WP 12 Oil Burner Mounting Plate Assembly 29873 13 Flue Pipe Connecting Flange 29005 14 Junction Box Cover 28722 15 Pouch Gasket 2080175 16 Flue Pipe Gasket (2 per Unit) 21994 17 Radiator Cleanout Cover Assembly 1061A Cleanout Cover Gasket 2080176 18 Casing Clean-out Cover 3011325A 19 Filter Frame 21260 20 Filter Frame End Support 21306 21 Air Filter – 20 x 20 x 1 (Permanent) 2180032 22 Junction Box 28723 23 Channel Wire Retainer 30239 24 Limit Control 60T11BOF L180º F 28654 25 Wire Harness Control 30268 26 Wire Harness Blower Direct drive 30265 27 Fan Timer Control: Honeywell ST9103A or UTC 1158-150 29388 28 Draft Regulator 5” 27494 29 Beckett oil Burner AF76BNHS 30288 Burner Motor 1/7 HP 3450 RPM PSC 29689 Beckett Clean-cut Oil Pump 29688 Solid State Igniter 29522 Primary Combustion Control R7184A 29664 Flame Retention Head 11961 (F3) Nozzle 0.65 / 80º A 210086 30 Blower Assembly, Complete, Direct Drive, ½ hp, 4-Speed 30313 Blower Housing and Wheel, GT10 DD 28142 Blower Wheel, GT10 DD 26430 Blower Motor, ½ hp, 4-Speed 26088 Motor Mounting Band – TR6884B 17811 Motor Mount Arms – 10-10 DD Blower (3 per unit) 26251 Motor Run Capacitor, 10 mfd @ 370 vac 27743 Capacitor Strap 27760 Low Fire Kit

Low Firing Rate Baffle Nozzle, .50/80° A

29880 25521101 29389

Page 33 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 33 · click to enlarge
Page 33

PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: WML C Ref. No. Description PART NO. 31 Auxiliary Limit 60T11BOF L140º F 29198 32 Transformer 27738 33 Control Panel 30190 34 Wire Harness, Junction Box to Control 30264 35 Wire Harness, Supply 29366 36 Limit Cover, Left 30240 37 Limit Cover, Right

PARTS LISTING: COUNTERFLOW HORIZONTAL DIRECT VENT MODEL: WML CB2U Ref. No. Description PART NO. All parts are the same as listed on the previous pages for Model WML-C except where noted below.

12 Oil Burner Mounting Plate Assembly 29872 Oil Burner Mounting Plate 29867 Sight Glass Cover Plate 29850 Sight Glass Gasket (2 per unit) 29870 Sight Glass 29876 13 Flue Connector Assembly 6” to 4” 90º Elbow 28952 14 Pouch Gasket (Second gasket required for Direct Vent) 2080175 15 Flue Collar Gasket (Second gasket required for Direct Vent) 21994 34 Beckett Oil Burner AFII 85 30069 Burner Motor 1/7 HP 3450 RPM PSC 28907 Beckett Clean-cut Oil Pump A2EA6520 29688 Solid State Ignitor 10SAY-01 28558

Primary Combustion Control R7184P 29649 Air Tube Combination FBX80HGXS 28561 Flame Retention Head (FB3) Nozzle, .60/60ºA (WML-80CB2U only)

28533 28017 PARTS LISTING: VESTIBULE KIT: WML C Ref. No. Description PART NO. Vestibule Kit 30554 Door Handle 28673 Base Panel 29019 Top Panel 21437L Door Panel 29022L Left Side Panel 30527L Right Side Panel 30528L PARTS LISTING: SUB BASE FOR COMBUSTIBLE FLOOR INSTALLATION: WML C Ref. No. Description PART NO. Sub Base 06000075

Page 34 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 34 · click to enlarge
Page 34
Field Controls Draft Inducer (WML-C) — IDLE STATE diagram (page 34)
Fig. 22
Page 35 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 35 · click to enlarge
Page 35

PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL Ref. No. Description PART NO. 1a 1b Right Side Panel Left Side Panel

30360L 30351L 2 Side Panel Heat Exchanger Support (2 per unit) 27038 3 Rear Panel 30353L 4 Blower Division Panel Assembly 30397 5 Base Heat Exchanger Support 26975 6 Front Panel 30350L 7 Blower Access Door 30363L Door Handle – P2-41 28673 Logo Bezel 28479 Logo Label 28563 8 End Panel 30352 9 Heat Exchanger Assembly 30380 10 Firepot Retainer Bracket 27068 11 Replacement Combustion Chamber 27000WP 12 Oil Burner Mounting Plate Assembly 29873 Inspection Door Gasket 29871 13 Flue Connector 28306 14 Pouch Gasket 2080175 15 Flue Pipe Gasket 21994 16 Radiator Cleanout Cover Assembly 1061A Cleanout Cover Gasket 2080176 17 Casing Clean-out Cover 3011325A 18 Filter Frame 21260 19 Filter Frame End Support 21306 20 Air Filter – 20 x 20 x 1 (Permanent) 2180032 21 Junction Box 28723 22 Channel Wire Retainer 30239 23 Limit Control 60T11BOF L150º F 29197 24 Limit Control 60T11BOF L160º F 29662 25 Wire Harness Junction Box to Control 30392 26 Wire Harness Blower Direct drive 30391 27 Fan Timer Control: Honeywell ST9103A or UTC 1158-150 29388 28 Air Baffle 30364 29 Wire Harness, Supply 29366 30 Limit Cover, Left 30240 31 Limit Cover, Right 30195 32 Draft Regulator 6” 12240 33 Transformer 27738 34 Control Panel 30355 35 Wire Harness Burner to Timer Board 30390 36 Wire Harness Transformer to Timer Board 30393

Page 36 of the Field Controls Draft Inducer (WML-C) user manual — PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL
Page 36 · click to enlarge
Page 36

PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL

Ref. No. Description PART NO. 37 Beckett oil Burner AF76XN 30389 Burner Motor 1/7 HP 3450 RPM PSC 29689 Beckett Clean-cut Oil Pump A2EA6520 29688 Solid State Ignitor FRANCE 10SAY-04 29522 Primary Combustion Control R7184A 29664 Air Tube Combination AF76XN 27610 Flame Retention Head (MPL 80, to 120) 11961 (F3) Flame Retention Head (MPL 130) 12646 (F6) Nozzle 1.00 / 60º A (MPL 120) 27104 Nozzle 1.10 / 70º A (MPL 130) 2100101 38 Blower Assembly, Complete, Direct Drive, ½ hp, 4-Speed 30387 Blower Housing and Wheel, GT12-10 DD 17559 Blower Wheel, GT12-10 DD 29692 Blower Motor, 3/4 hp, 4-Speed 27161 Motor Mounting Band – TR6884B 17811 Motor Mount Arms – 12-12 DD Blower (3 per unit) 17812 Motor Run Capacitor, 20 mfd @ 370 vac 27745 Blower Slide Rail 29026 39 Auxillary Limit L130°F 60T11 BOF 30388 40 Junction Box Cover 28722 PARTS LISTING: COUNTERFLOW HORIZONTAL DIRECT VENT MODEL: MPL BB2U

Ref. No. Description PART NO. All parts are the same as listed on the previous pages for Model MPL-B except where noted below. 12 Oil Burner Mounting Plate Assembly 29872 Oil Burner Mounting Plate 29867 Sight Glass Cover Plate 29850 Sight Glass Gasket (2 per unit) 29870 Sight Glass 29876 13 Flue Connector Assembly 6” to 4” 90º Elbow 28952 14 Pouch Gasket (Second gasket required for Direct Vent) 2080175 15 Flue Collar Gasket (Second gasket required for Direct Vent) 21994 37 Beckett Oil Burner AFII 150 30430 Burner Motor 1/7 HP 3450 RPM PSC 28907 Beckett Clean-cut Oil Pump A2EA6520 29688 Solid State Ignitor 10SAY-01 28558 Primary Combustion Control R7184P 29649 Air Tube Combination FBX80HGXS 28561 Flame Retention Head (FB3) Nozzle, 0.85/70ºA (MPL-120BB2U only)

28533 PARTS LISTING: SUB BASE FOR COMBUSTIBLE FLOOR INSTALLATION: MPL B Ref. No. Description PART NO. Sub Base 006000073

Page 37 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 37 · click to enlarge
Page 37
Field Controls Draft Inducer (WML-C) — IDLE STATE diagram (page 37)
Fig. 23
Page 38 of the Field Controls Draft Inducer (WML-C) user manual — IF DIFFERENT FROM INSTALLATION CONTRACTOR:
Page 38 · click to enlarge
Page 38

HOMEOWNER’S REFERENCE TABLE

Model No.

Serial No.

Telephone No.

After Hours No.

FUEL SUPPLIER

Telephone No.

After Hours No.

IF DIFFERENT FROM INSTALLATION CONTRACTOR:

Service Tech.

Telephone No.

After Hours No.

Show 7 more labels / short text on this page
Date Installed · Contractor · Contact · Address · Postal Code · Fuel Oil Supplier · Contact
Page 39 of the Field Controls Draft Inducer (WML-C) user manual — NOTES:
Page 39 · click to enlarge
Page 39

NOTES:

Page 40 of the Field Controls Draft Inducer (WML-C) user manual — IDLE STATE
Page 40 · click to enlarge
Page 40
Field Controls Draft Inducer (WML-C) — IDLE STATE diagram (page 40)
Fig. 24

6800 Base Line, Wallaceburg, Ontario, N8A 5E5, Can. Tel: (519) 627-0791 Fax: (519) 627-4719 2201 Dwyer Avenue, Utica, New York, 13504, USA. Tel: (315) 797-1310 Fax: (315) 724-9319 85 Middle Road, Dunkirk, New York, 14048, USA Tel: (716) 366-5500 Fax: (716) 366-1209 www.ecrinternational.com

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Nozzle p.7
Chimney Thermal Resistance < R6 p.7
0.50 p.7
0.65 p.7
0.70 p.7
0.75 p.7
0.85 p.7
1.00 p.7
Chimney Thermal Resistance > R6 p.7
< - less than, > - greater than p.7
OIL TANK Oil storage tanks must be selected and installed in compliance with applicable codes; in the United States, NFPA 31, Standard for the Installation of Oil Burning Equipment, Chapter 2. and in Canada, CAN/CSA-B139, Installation Code for Oil Burning Equipment, Section 6. Observe all local codes and by-laws. p.7
DO NOT CONNECT POWER LEADS BETWEEN MOTOR SPEEDS. THE NEUTRAL WIRE MUST ALWAYS BE CONNECTED TO THE MOTOR'S DESIGNATED NEUTRAL TERMINAL. p.9
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to connect the wiring from both modes is to use a "piggy-back connector" accommodating both wires on a single motor tap. It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape. If the joining of the blower speed wiring is done in the furnace junction Figure 4: Horizontal Smoke Test p.9
It is possible and acceptable to use a single blower speed for both heating and cooling modes. The simplest method to connect the wiring from both modes is to use a "piggy-back connector" accommodating both wires on a single motor tap. It is also acceptable to connect the selected motor speed with a pigtail joined to both heating and cooling speed wires with a wire nut. As a safety precaution against accidental disconnection of the wires by vibration, it is advisable to secure the wire nut and wires with a few wraps of electricians tape. If the joining of the blower speed wiring is done in the furnace junction Figure 4: Horizontal Smoke Testertical Smoke Test Port Location p.9
Furnace will not start.Thermostat not calling for heat.Check thermostat and adjust. Also, check thermostat for accuracy; if it is a mercury switch type, it might be off level. p.29
Furnace will not start.No power to furnace.Check furnace switch, main electrical panel furnace fuse or circuit breaker. Also look for any other hand operated switch, such as an old poorly located furnace switch, which was not removed during furnace replacement. p.29
Furnace will not start.Thermostat faulty.Remove thermostat wires from oil primary control terminals T-T. Place a jumper across T-T. If furnace starts, replace thermostat, thermostat sub- base (if equipped), or both. p.29
Furnace will not start.Oil primary control faulty.Check reset button on oil primary control. Remove thermostat wires from oil primary control terminals T1 - T2. Check for 24v across T -T. If no voltage is present, check for 115v to oil primary control. If 115v is present, go to Table C-3. p.29
Furnace will not start.Photo Cell wiring shorted or room light leaking into photo cell compartmentCheck photo cell (cad cell) wiring for short circuits. Also, check for room light leaking into cad cell compartment. Repair light leak if necessary. See Table C-3. p.29
Furnace will not start.Open safety switch.Check for open limit or auxiliary limit. Also, check internal wiring connections; loose connectors, etc. p.29
Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)No fuel oil.Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary. p.29
Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)Clogged nozzle.Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide. p.29
Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)Clogged oil filter.Replace oil tank filter or in-line filter if used. p.29
Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)Low oil pump pressure.Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line. p.29
Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.Check fuel oil lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants. p.29
Furnace will not start without first pushing oil primary control reset button. (Happens on frequent basis)Defective burner motor.Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if necessary. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Photo Cell (Cad Cell) defective.If cad cell is dirty, clean it. (Determine why cad cell is getting dirty). If cad cell is poorly aimed, realign it. NOTE: The photocell should have a resistance of 100K Ω in absence of light; a maximum of 1500 Ω in the presence of light. Ensure that room light is not leaking into the cad cell compartment. (See diagnostic light section). p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.No fuel oil.Check fuel oil supply. Check that all hand operated fuel oil valves are in the open position. Fill oil storage tank if necessary. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Clogged nozzle.Replace nozzle with high quality replacement. Use rating plate or Tables in Appendix A as a guide. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Clogged oil filter.Replace oil tank filter or in-line filter if used. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Low oil pump pressure.Connect pressure gauge to oil pump. Adjust pump pressure, or replace oil pump if necessary. Ensure that erratic pressure readings are not caused by defective fuel oil line. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Air getting into fuel oil lines, or fuel oil line dirty, clogged, or in some manner defective.Check fuel oil lines. Replace any compression fittings found with high quality flared fittings. Check for any signs of oil leaks. Any oil leak is a potential source of air or contaminants. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Defective burner motor.Check burner motor. If burner motor is cutting out on over-load, determine why. Replace if necessary. p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Water or contaminants in oil.Drain fuel oil storage tank, replace fuel oil. (Consult with fuel oil supplier). p.29
Furnace starts, but cuts out requiring manually resetting the oil protector reset button.Frozen oil line.Gently warm oil line. Insulate oil line. (Outdoor piping size may require increased diameter). p.29
Supply air temperature too hot.Airflow blocked or dirty air filter.Clean or replace air filter. p.31
Supply air temperature too hot.Insufficient airflow.Check all dampers. Open closed dampers including registers in unused rooms. Check system temperature rise. If temperature rise is too high, speed up blower fan. p.31
Supply air temperature too cool.Excess airflow.Check system temperature rise. Slow down blower fan if necessary. p.31
Supply air temperature too cool.Excessive duct losses.Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary. p.31
Supply air temperature too cool during first moments of furnace cycle.Fan control "fan on" setting too low.Increase "fan on” dipswitch settings on EFT if control has this option.). Register air deflectors may help. p.31
Supply air temperature too cool during first moments of furnace cycle.Excessive duct losses.Check supply air ductwork. Seal leaky joints and seams. Insulate ductwork if necessary. p.31

Ask about the Field Controls Draft Inducer (WML-C)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Field Controls Draft Inducer (WML-C)

Be the first to ask — other owners or our team will answer.

Original document

Field Controls Draft Inducer (WML-C) manual PDF

40 pages·870 KB·Furnace·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…