FC95HRV*
FC155HRV
FC200HRV*
FC150ERV
Heat Recovery Ventilators
This product earned the ENERGY STAR by meeting strict energy efficiency guidelines set by Natural Resources Canada and the US EPA. It meets ENERGY STAR requirements only when used in Canada.
69-Field 0412


Thank you for purchasing a Field Control Heat/Energy Recovery Ventilator (HRV/ERV). The HRV/ERV provides fresh air to your home while recovering energy from the air it exhausts. There are numerous benefits to a properly installed, operated, and maintained HRV/ERV: • Exhausts the stale, contaminated air, found in today’s tight buildings.
*Refer to the individual control pages of this manual for more information about these controls.
High indoor humidity levels, during the heating season, have become a problem in many well insulated, tight homes. Excessive condensation on the windows is a visual sign of high indoor humidity levels. High indoor humidity levels can result in mold and mildew and the eventual degradation of the building structure itself.
Refer to the main control instructions located in the Operation and Installation Manual for instructions on how to set the dehumidistat. The dehumidistat function on the main control should be set to OFF for all seasons except the heating season, because a dehumidifying effect occurs only when the outdoor air is dryer than the indoor air. Set the RH level to 80 to turn the dehumidistat OFF. (Refer to the control instructions for information on how to set the Dehumidistat). DEHUMIDISTAT DISABLE - automatically disables the dehumidistat function on the main control when outdoor temperatures exceed 15°C (59°F) for a full 24 hour period. All other HRV features and functions operate normally while the dehumidistat function is disabled. DEHUMIDISTAT RE-ENABLE - automatically re-enables the dehumidistat function if either the outdoor temperature drops below 15°C (59°F) for a full 24 hour period or if the HRV is reset (unplugged for 30 seconds).
Your HRV/ERV reduces indoor humidity levels when the outdoor air is drier than the indoor air. These conditions usually occur during the heating season when outdoor temperatures are less than 15°C (59°F). During the heating season, the operation of the HRV/ERV may reduce indoor humidity levels sufficiently to eliminate the need for further dehumidification.
If your home requires further dehumidification, use the dehumidistat feature located on any optional main control (refer to the Operation and Installation Manual for Optional Control information). This feature aggressively addresses high indoor humidity levels by initiating high speed ventilation when the indoor humidity levels rise above the adjustable set point on the control.
DEFROST MODE - To ensure reliable operation during cold weather, the HRV automatically cycles through its defrost mode when the outdoor temperatures drop below freezing.
SELF-TEST - Each time the HRV/ERV is powered/energized, the self-test function automatically initiates. The HRV/ERV cycles through the available speeds and tests the damper motor operation. The HRV/ERV defaults back to the previous operational mode and speed selection after the self-test (approximately 60 seconds in duration).
HRV/ERV - a Heat Recovery Ventilator (HRV/ERV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months, heat recovered from the stale air, before it is exhausted to the outdoors, warms the incoming cold fresh air. During the summer months, when the indoor space is air conditioned, the HRV/ERV helps to cool the incoming fresh air with the cool exhausted stale air.
STANDBY - The HRV/ERV is powered/energized and waiting for ventilation to be initiated by an external control.
TIMERS - These optional controls may be installed at specific exhaust locations (bathrooms etc.) to initiate high speed ventilation.
Heat Recovery Ventilators (HRV) carry a Lifetime Warranty on the heat recovery core and a 5 (five) year replacement parts warranty. Energy Recovery Ventilators (ERV) carry a 5 (five) year warranty
on the energy recovery core and a 5 (five) year replacement parts warranty.

The Healthy Home System Control (HHSC) activates the HRV/ERV automatically to deliver fresh air into your home.

The duration of the ventilation rate is adjustable on the HHSC. Your installer sets up this control during the installation of your system . Refer to the instructions that came with the HHSC for the setup information.
Your HRV/ERV system produces a dehumidifying effect when outdoor humidity levels are lower than indoor humidity levels. These conditions occur normally when outdoor termperatures are below 60°F. An additional dehumidification effect is achievable with the Optional Dehumidistat (Part DH1).
Dehumidistat Indicator LEDs Set to the desired humidity level. High speed ventilation will initiate when the indoor moisture level exceeds the set point on the control.
The Optional DH1 Control may be combined with the Healthy
Home System Control (HHSC). The DH1 will initiate high speed
ventilation when the moisture level in the home exceeds the set
point on the control. Once the humidity in the house is reduced,
the HRV will revert back to the HHSC automatic setting. The
Dehumidistat should be set to OFF for all seasons except the
heating season.
% · Dehumidistat Adjust button

The Dehumidistat Ventilation Control offers ON/OFF, High Speed/Low speed plus an electronic dehumidistat.
Key Features • 2 Speed Fan setting (Low/High)
High Speed Indicator LED
Turning on the Control Press and release the ON/OFF button. The "ON Indicator Light" will illuminate.
Adjusting the Ventilation Speed The unit will normally operate at low speed. Press and release the SPEED button to initiate high speed ventilation. The "High Speed Indicator LED" will illuminate.
Humidity Control Your unit will produce a dehumidifying effect when outdoor humidity levels are lower than indoor humidity levels. Never use the dehumidistat feature when outdoor temperatures are above 59° F (15° C).
*Install a jumper between 2 (ON) and 3 (RED) on the HRV/ERV terminal block to configure the ON/OFF button to ON/STANDBY. Refer to “Setting Standby when using a Main Control” in this manual.
Setting the Dehumidistat Press and release the DEHUMIDISTAT button until the DEHUMIDISTAT LED is at the desired setting. After 5 seconds the dehumidistat light will either flash or be on continuous.
A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation. A continuous light indicates the humidity level is lower than the setting.

The timer will override the Operational Mode (regardless of the setting) and initiate high speed ventilation. Upon completion of the timer cycle, the HRV/ERV returns to your selected Operational Mode and speed setting.
installed, the HRV/ERV Terminal Block must have
a jumper installed between 2 (ON) and 3 (RED).
Control” in this manual.
Lifestyle 20/40/60 Minute Timer Initiates high speed ventilation for 20, 40 or 60 minutes. The 20/40/60 Minute Status Lights indicate high speed operation.
Lockout Mode is useful if you wish to disable the timer. Set lockout by holding the Select Button for 5 seconds. Unlock by holding for 5 seconds.
20/40/60 Minute Status Lights
Select Button

a) simply open access door and slide core out
b) remove filter clips
c) once clips are removed filters can be taken off the core to be
rinsed with water or a combination of mild soap and water. Do not clean in the dishwasher
d) to re-assemble, place clean filter(s) (wet or dry) back into their
positions against the core and return clips to their original position
e) slide core back into its’ original position
b) carefully grip ends of core and pull evenly outward. Core may
(a) through the large opening of the fan assembly and then
be snug, but will slide out of the channel
c) once removed from the cabinet remove filters
(b) through the smaller opening in the end
d) wash core in warm soapy water (do not use dishwasher)
of the fan assembly.
e) install the clean filters
f) install clean core
H channel approximately 1/4” (6mm)
b) mount the left or right side flange of the core guide
approximately 1/4” (6mm) followed by the other side
c) mount the top flange of the core guide into the top H channel
Before attempting this task, thought should be given to having a qualified service technician complete the service work.
approximately 1/4” (6mm).
d) with all four corners in place and the core straight and even,
push hard in the centre of the core until the core stops on the back of the cabinet.
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power unit OFF at disconnect switch(es). Unit may have multiple power supplies.


THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
Performance (HVI certified) Net supply air flow in cfm (L/s) against external static pressure
E.S.P (external static pressure) [cfm (L/s)]
MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. The unit has a 2 speed fan operation.
@ 0.1" (25 Pa) 76 (36)
@ 0.2" (50 Pa) 73 (34)
FILTERS Washable air filters in exhaust and supply air streams.
@ 0.3" (75 Pa) 70 (33)
@ 0.4" (100 Pa) 66 (31)
MOUNTING THE HRV Four threaded inserts at corners of the cabinet designed to accept the “S” hooks and hanging straps supplied with the unit.
@ 0.5" (125 Pa) 60 (29)
Max. Temperature Recovery 88%
Sensible Effectiveness @ 60 cfm (28 L/s) 32°F (0°C) 88% *Sensible Efficiency @ 60 cfm (28 L/s) 32°F (0°C) 75%
DEFROST Recirculating defrost system.
CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD. WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs (25.4 kg)
*Sensible Efficiency @ 61 cfm (29 L/s) -13°F (-25°C) 68%
WATTS / Low speed. 59
WATTS / High speed 150
ELECTRONICS • Built-in Relay for Interfacing to furnace
Amp rating 0.9
*Sensible Efficiency – thermal **Latent Efficiency – moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length
#WH 185 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh
0 0.1 0.2 0.3 0.4 0.5 0.6
Static Pressure (in w.g.)
DIMENSIONS FC95HRV inches (mm)
All units conform to CSA and UL standards.
18.5" (470 mm)
Threaded inserts (4) at corners
WARRANTY Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
18.5" (470 mm)
Stale Air to outside 5" round collar
24.5" (622 mm)
SUPPLY Fresh air from outside 5" round collar
SUPPLY Fresh air to building
Return air from building
6" round (conv. to oval)
6" round (conv. to oval) collar


In order to make the HRV as space efficient as possible, the INDOOR supply and return ports are converted from round to oval shape. Overall size of the port remains the same. Simply bend a standard duct fitting to the correct shape, and attach to the oval port using the same method as for a round port.
FC95HRV Air Flow Stale air enters the FRONT-RIGHT side port. The air passes down the front half of the core, then up the back half of the core and out the RIGHT-REAR port. Fresh outdoor air enters the LEFT-REAR port and passes down the back half of the core. Then the fresh outdoor air passes up the front half of the core and out the LEFT-FRONT port. This configuration allows the air to actually travel through the core twice, which makes the FC95HRV nearly as efficient as a double core unit.

*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
RECIRCULATING
BALANCING DAMPER
DEFROST
DAMPER
All units conform to CSA and UL standards.
BLOWERS
WARRANTY Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
FRESH AIR
TO INSIDE
BALANCING DAMPER 33 5/8" (850mm)
*All Duct Connections 6" (150mm) CONDENSATE DRAINS

19" (483) · 14 3/4" (375)

Static Pressure (in w.g.)
INSTALLER SELECTABLE HIGH SPEED SETTINGS Adjustable DIP switches are located on the circuit board. Hi3 is the factory setting. Refer to the Operation and Installation manual for the adjustment instructions.
RECIRCULATING
FILTERS
BALANCING DAMPER
DEFROST
DAMPER
MOTOR CORE
BLOWERS
All units conform to CSA and UL standards.
of 25 inches (635 mm) is recommended for servicing unit.
WARRANTY Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty. BALANCING DAMPER 33 5/8" (850 mm)
TO INSIDE
14 3/4" (375 mm)
*All Duct Connections 6" (150 mm)
All Duct Connections 6” (160 mm)
Quote#:
inches (mm) · 19" (483 mm)

LATENT RECOVERY/MOISTURE TRANSFER CORE The cross-flow energy recovery core transfers heat and water vapor between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. MOUNTING THE ERV Four threaded inserts at corners of case designed to accept the "S" hooks and hanging straps supplied with the unit. CASE Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Door balancing ports. WEIGHT 75 lbs. (34Kg) SHIPPING WEIGHT 77lbs. (35Kg) ELECTRONICS •Built-in Relay for Interfacing to furnace

Sensible Effectiveness @ 64 cfm (30 L/s) 32°F (0°C) 81% *Sensible Efficiency @ 64 cfm (30 L/s) 32°F (0°C) 69%
Total Efficiency 50% @ 64 cfm (30L/s) 95°F (35°C) 47%
*Sensible Efficiency – thermal **Latent Efficiency – moisture Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100' length

#WH 186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
DIMENSIONS FC150ERV inches (mm)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
*All Duct Connections 6"(150mm)

DAMPER
BALANCING
FILTERS
DAMPER
WARRANTY Units carry a five (5) year warranty on the enthalpic (ERV) core and a 5 year replacement parts warranty.

screen · 19" (483) · 33-5/8" (850)

Installing the Ducting Between the HRV/ERV & Living Areas in the House A well designed and installed ducting system will allow the HRV/ERV to operate at its maximum efficiency. All ducts should be kept short and have as few bends or elbows as possible to maximize airflow. Forty-five degree elbows are preferred to 90° elbows. Use "Y" tees instead of straight tees whenever possible. All duct joints must be fastened with screws, rivets or duct sealant and wrapped with mastic or quality duct tape to prevent leakage. Mastic is preferred but if duct tape is used, we recommend aluminum foil duct tape. Galvanized (rigid) ducting from the HRV/ERV to the living areas in the house is recommended whenever possible although flexible duct can be used in moderation if necessary. A short length (approximately 12 inches or 300mm) of non- metallic flexible insulated duct should be connected between the HRV/ERV and the supply/exhaust duct system to avoid possible noise transfer through the duct system. All ducts running through attics and unheated spaces must be sealed and insulated to code.
Simplified Installations The Simplified Installation draws stale air from the cold air return duct of the air handler/furnace and introduces an equal amount of fresh air farther downstream into the cold air return. Refer to "Simplified Installation Diagrams".
The air handler/furnace blower must be running when the unit is operating for this system to be effective. Refer to "Interlocking the HRV/ERV to an Air Handler/Furnace Blower".
Partially Dedicated Installations The Partially Dedicated Installation draws stale air from specific points in the house and introduces an equal amount of fresh air into the cold air return. Refer to "Partially Dedicated Installation Diagrams".
Stale air ducts should be installed in areas of the home where the poorest indoor air quality exists (bathrooms and kitchen). Each location with a stale air duct should have a timer to initiate high speed ventilation. Refer to "Optional Timers" in this manual.
Applications such as greenhouses, atriums, swimming pools, saunas, etc. have unique ventilation requirements which should be addressed with an isolated ventilation system.
The air handler/furnace blower should be running when the HRV is operating to evenly distribute the fresh air throughout the house. Refer to "Interlocking the HRV/ERV to an Air Handler/Furnace Blower".
Fully Dedicated Installations The Fully Dedicated Installation draws stale air from specific points in the house and delivers fresh air to specific locations of the house. This system is not connected to an air handler/furnace. Refer to "The Fully Dedicated Installation Diagrams" in this manual.
Stale air ducts should be installed in areas of the home where the poorest indoor air quality exists (bathrooms and kitchen). Each location with a stale air duct should have a timer which will initiate high speed ventilation. Refer to "Optional Timers" in this manual. Fresh air ducts should be installed to all bedrooms and living areas, excluding bathrooms, kitchen and utility areas. Grilles should be located high on a wall or in ceiling locations. Grilles that diffuse the air comfortably are recommended. Refer to "Grilles" in this manual. Special care should be taken in locating grilles if the floor is the only option available. Areas such as under baseboard heaters will help to temper the air. Optional in-line duct heaters are available for mounting in the supply duct work to add heat if required.

Simplified Installation (Return/Return Method)
Sizing the Ductwork It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.
The amount of air (cfm) that an HRV/ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work plus the number of fittings used in the duct work.
DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and
DIRECT CONNECTION of the SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN.
EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN
3' min. recommended
Dampers for balancing airflows
Spring-Loaded Backdraft Damper Install the Backdraft Damper with the leaf hinge vertical. The damper is installed on the “Stale Air to Outside Collar”.
4” (102mm) Backdraft Damper Part No. 99-RSK4 5” (127mm) Backdraft Damper Part No. 99-RSK5 6” (152mm) Backdraft Damper Part No. 99-RSK6 8” (203mm) Backdraft Damper Part No. 99-RSK8 The Stale Air to Outside air duct requires a Backdraft Damper.This damper prevents outdoor air from entering the HRV during the operation of the Furnace/ Air Handler while the HRV is in standby, OFF or Recirculate.
two direct connections. • The exhaust air connection should be upstream of the supply air
connection to prevent exhausting any fresh air. • Weatherhood arrangement is for drawing purposes only. Six feet (2m)
minimum separation is recommended. The Weatherhood must also be 18" (460mm) above grade minimum. • The airflow must be confirmed on site using the balancing procedures found in this manual

Partially Dedicated System This installation enables stale air to be drawn from the poorest air quality areas of the home (bathrooms, kitchen).
Sizing the Ductwork It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.
The amount of air (cfm) that an HRV/ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is a measure of resistance imposed on the blower by length of duct work plus the number of fittings used in the duct work.
DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN
(Stale air drawn from key areas of home)
EXHAUST AIR from various parts of home. i.e. bathrooms (if required), kitchens (if required).
3' min. recommended
Dampers for balancing airflows
Spring-Loaded Backdraft Damper Install the Backdraft Damper with the leaf hinge vertical. The damper is installed on the “Stale Air to Outside Collar”.
4” (102mm) Backdraft Damper Part No. 99-RSK4 5” (127mm) Backdraft Damper Part No. 99-RSK5 6” (152mm) Backdraft Damper Part No. 99-RSK6 8” (203mm) Backdraft Damper Part No. 99-RSK8
The Stale Air to Outside air duct requires a Backdraft Damper.This damper prevents outdoor air from entering the HRV during the operation of the Furnace/Air Handler while the HRV is in standby, OFF or Recirculate.
minimum separation is recommended. The Weatherhood must also be 18" (460mm) above grade minimum. • The airflow must be confirmed on site using the balancing procedures
found in this manual.

Fully Dedicated System This is a stand alone HRV/ERV system which is not connected to a force air system. Stale air is drawn from key areas of the home (bathroom, kitchen) while fresh air is supplied to main living areas.
Fresh air to house - main living areas. bedrooms, livingroom, rec. room, etc.
Stale air from various parts of home. i.e. bathrooms (if required) Kitchens (if required)
Dampers for balancing airflows
Key Points · Outdoors

Location Install the unit in a heated space that provides convenient space for service access. A typical location is in either a mechanical room or an area close to the outside wall within close proximity to where the weatherhoods are mounted. If a basement area is inconvenient or non- existent, install the unit in a utility or laundry room.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
Attic installations are not recommended due to:
A) the complexity of work to install
B) freezing conditions in the attic
C) difficulty of access for servicing and cleaning
Leave sufficient clearance at the front of the access door for servicing the air filters and core. The recommended clearance is a minimum of 25" (635 mm) for opening and closing the door. Field Controls provides four straps for hanging the unit from the basement floor joists.
Unit must be installed level to ensure proper condensate drainage. Due to the broad range of installation and operational conditions, consider the possibility of condensation forming on either the unit or connecting ducting. Objects below the installation may be exposed to condensate.
Use 4 screws and 4 washers (not incldued) to attach the hanging straps to the floor joists. The washer must be wider than the eyelet of the grommet on the hanging strap.
By design, the adjustable hanging straps reduce the possibility of noise, resonance, and harmonics.
Pull down on the hand loops while lifting the bottom of the unit.
- Adjust the unit down by lifting up on the buckle. - Adjust the unit up by pulling down vertically on the Hand
Loops while lifting up the bottom of the cabinet.

Drain Connection The HRV may produce some condensation during a defrost cycle. This water should flow into a nearby drain, or be taken away by a condensate pump.
PRE-PUNCHED HOLES (2)
DRAIN PAN DRAIN PAN
CAUTION DRAIN SPOUT
DRAIN SPOUT
The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point or freeze protection must be provided.
TEE CONNECTOR
1/2 " I.D. DRAIN HOSE
The HRV cabinet has prepunched holes for the drain (see below). Insert the drain spout through the hole in the drain pan. Be sure to install the "O ring" which seals each spout to the pan. HAND TIGHTEN the washer and lock nut which hold the drain spout in place.
HARD PIPE PLUMBING
PRE-PUNCHED HOLES (2)
Construct a P-Trap using the plastic tee connector. Cut two lengths of 1/2" drain hose (not included) and connect the other ends to the two drain spouts. Position the "T" fitting to point upward and connect the drain line. Tape or fasten base to avoid any kinks. Pour a cup of water into the drain pan of the HRV after the drain connection is complete. This creates a water seal which will prevent odors from being drawn up the hose and into the fresh air supply of the HRV.
1/2" HARD PIPE
DRAIN SPOUT
DRAIN SPOUT
TEE JOINT
TO DRAIN
Drain trap and tubing MUST be below bottom of door with 1/4" per foot downwards slope away from unit.
Adjustable grilles should be used to balance the flow rates into and out of various rooms. The grilles should not be adjusted after balancing the unit.
The Techgrille The TECHGRILLE is a round, fully adjustable grille, which provides superior, quiet air distribution.
Grilles or diffusers should be positioned high on the wall or in the ceiling. Kitchen Exhaust grilles must never be connected to the range hood. They should be installed at least 4 feet (1.2 m) horizontally away from the stove.
4” (100 mm) Part No. 99-EAG4

Field supplied balancing dampers should be installed external to the unit to balance the amount of stale air being exhausted with the amount of fresh air being brought into the house. Refer to Air flow Balancing section.
5” (125 mm) Part No. 99-EAG5
6” (150 mm) Part No. 99-EAG6


Installing the Ducting from the Weatherhoods to the HRV/ERV The inner and outer liners of the flexible insulated duct must be clamped to the sleeve of the weatherhoods (as close to the outside as possible) and the appropriate port on the HRV/ERV. It is very important that the fresh air intake line be given special attention to make sure it is well sealed. A good bead of high quality caulking (preferably acoustical sealant) will seal the inner flexible duct to both the HRV/ERV port and the weatherhood prior to clamping.
Weatherhoods Fixed covered weatherhoods have a built-in bird screen with a 1/4" (6mm) mesh to prevent foreign objects from entering the ductwork.
5” (125 mm) Part No.WH 185 6” (150 mm) Part No.WH 186
To minimize air flow restriction, the flexible insulated duct that connects the two outside weatherhoods to the HRV/ERV should be stretched tightly and be as short as possible.
IS 100% SEALED TO
WALL PLATE
Twisting or folding the duct will severely restrict air flow.
Hard (rigid) ducting which has been sealed and insulated should be used for runs over 10’ (3.3 m). Refer to your building code.
12" galvanized pipe supplied
1/4" (6 mm) SCREEN (front view)
Exhaust Weatherhood Requirements
36" (1m) recommended min. 36" (1m) recommended min.
6' (2m) recommended min.
When installing the weatherhood, its outside perimeter must be sealed with exterior caulking.
18" (460mm) min. 18" (460mm) min.
CAUTION
Local codes may require greater distances for exhaust and intake.
Weatherhood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) above the ground, or above the depth of expected snow accumulation.
SCREEN (side view)

Standard Series Controls may be installed onto a flush mounted 2" x 4" electrical switch box or it may be surface mounted onto a wall.

Only 1 master control should be installed to a ventilation system (the Face Plate on this illustration may not be exactly the same as yours).
Pay special attention not to damage the Contact Pins when attaching and detaching the Face Plate. (Figure B)
Separate the Face Plate from the Back Plate. Side View

Drill a 1/8” hole for the Top Screw and Anchor
Drill a 1/8” hole for the Bottom Screw and Anchor
Dehumidistat Sensor Openings to room air allow accurate sensor readings.
Red #3 · Yellow #4 · Green #5

Operating your 20/40/60 Minute Timer Press and release the Select Button to activate high speed override. The High Speed Status Light will illuminate and the unit will run on high speed ventilation for 20 minutes.

The 20/40/60 Minute timers provide an extended override time of 20 - 40 additional minutes simply by pressing and releasing the select button.
The High Speed Status Light will dim after 10 seconds of run time.
Select Button initiates high speed ventilation for 20, 40 or 60 minutes.
The High Speed Status Light will flash during the last 5 minutes of the cycle.
All timers connected to the unit will illuminate for the duration of the override when the Select Button is pressed.
Lockout Mode Lockout Mode is used to disable the timers.
The timer can be set to lockout mode by pressing and holding the Select Button for five seconds. After five seconds, the High Speed Status Light will flash; release the Select Button. The timer is now in lockout mode. If the Select Button is pressed during lockout mode the High Speed Status Light will momentarily illuminate but no override will be initiated.
If lockout mode is initiated when the timer is activated, the timer will continue its timed sequence but will not allow any further overrides to be initiated. Lockout mode can be unlocked by pressing and holding the Select Button for five seconds. After five seconds the High Speed Status Light will stop flashing. Release the Select Button and the timer will now operate normally.
Terminal Block Connections (from Timer to Terminal Block) Yellow on timer to YELLOW #4 Red on timer to RED #3 Green on timer to GREEN #5


HRV/ERV control. The HHSC is also typically used to control an FAD fresh air damper. 2. Complete all wiring connections before restoring power to the HVAC system and HRV/ERV.
Choose a Location The HHSC controller can be installed anywhere in your home. To simplify the installation, locate the HHSC control near the HVAC system and/or the HRV/ERV, since the HHSC does not require routine adjustment or occupant interaction.
Programming the HHSC Control 1. Balance the fresh and stale airflows as instructed in this manual. 2. Determine the cfm flow rate as instructed in this manual. 3. To obtain the desired rate of fresh air exchange, refer to the HHSC Control Installation Instructions to determine the On/Off timer settings for the HHSC Control. Use the cfm flow rate determined in step 2 as the computed or
To provide the occupants with direct access to the functions of the controls, install optional accessory controls throughout the house.
How To Install the Controller 1. Separate the HHSC controller cover from the wall plate (mounting base) to expose mounting holes (see illustration). 2. Route wires through large hole in the mounting base. Mount base against wall and mark wall through 3 mounting holes. 3. If mounting on a metal or wood surface, drill three 1/8-in. pilot holes in wall where marked for the supplied mounting screws. If mounting on drywall or other surface, drill appropriate holes for wall anchors or other means of attachment. 4. Secure mounting base to wall with either the 3 screws provided or other fasteners, while ensuring that all wires extend through the hole in mounting base. 5. Adjust length and routing of each wire to reach the proper terminal and connector block on mounting base, while leaving a 1/4 in. length of extra wire. Strip only 1/4 in. of insulation from each wire to prevent adjacent wires from shorting together when connected. 6. Connect wires to their respective terminals on the connector block. (Figure 1) Both (R) and (C) must be connected for proper operation. Improper wiring or installation may damage the controller. Ensure wiring is correct before proceeding with installation or turning the unit on. 7. Push any excess wire into wall and against mounting base. 8. Snap cover onto base, while ensuring pins align with sockets in connector. 9. Once powered the HHSC automatically enters into operating mode.
measured fresh air flow rate (as calculated in the HHSC instructions). To ensure adequate ventilation, ensure that the “Fan On” time is equal to or greater than the “Vent On” time, as programmed in the HHSC Control. 4. For continuous operation of the HRV/ERV, set “Fan On” and “Vent On” to “Un” (unlimited), and “Fan Off” and “Vent Off” to any setting except “Un”. This setting also causes the HVAC fan to run continuously. NOTE: The HHSC Control is factory programmed with the default settings of the two On/Off timer values. No configuration is required to use these factory default settings.
Default settings: FAN OFF 20 minutes FAN ON 10 minutes VENT ON 10 minutes VENT OFF 20 minutes

Complete the Wiring Connections 1. Refer to subsequent wiring diagrams in this manual that correspond to the desired control configuration.

HHSC CONTROL
R C Wt Gt Gf V
HI
FACTORY-INSTALLED JUMPER DO NOT REMOVE
ON
R
NO
Y
NC
G
BK
LO
24C *
HI
HRV/ERV WIRING TERMINALS
R C W Y G R Y W G
12V/24 VAC Field wiring, 20 AWG min. required
* Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period.
Setting up the HHSC Control The duration of the ventilation rate is adjustable on the Healthy Home System™Control (HHSC). Refer to the instructions that accompanied the HHSC for setup information.


Installation of the HHSC with the DH1 and 20/40/60 Minute Timers (test a)
R C W Y G R Y W G
* Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period. ** One DH-1 Dehumidistat and/or one or more VTC timer controls may be connected as shown. Connect all Red, Yellow, and Green control terminals to the corresponding HRV/ERV terminals.


Setting up the HHSC Control The duration of the ventilation rate is adjustable on the Healthy Home System Control™(HHSC). Refer to the instructions that accompanied the HHSC for setup information.

DHVC VENTILATION CONTROL
if the system is configured as fully dedicated (no central HVAC connections).
FACTORY-INSTALLED JUMPER FOR STANDBY-OFF OPERATION. SEE “SETTING STANDBY” SECTION OF INSTALLATION INSTRUCTIONS
HI
HIGH
ON
R
NO
Y
NC
R Y G
G
BK
LO
HI
HRV/ERV WIRING TERMINALS
Y
Y
R C W Y G R Y W G
R
THERMOSTAT FURNACE OR HEAT PUMP
G
G
12V/24 VAC Field wiring, 20 AWG min. required
* Connect V Terminal on the HHSC Control to the Hi Terminal (instead of Lo) for a shorter ventilation period. ** One DH-1 Dehumidistat and/or one or more VTC timer controls may be connected as shown. Connect all Red, Yellow, and Green control terminals to the corresponding HRV/ERV terminals.
VTC VENT TIMER CONTROL (OPTIONAL)**
%

Connecting the HRV/ERV as illustrated will ensure the Air Handler/Furnace Blower Motor is operating whenever the HRV/ERV is ventilating.
The HRV/ERV must be interlocked to the Furnace/Air Handler with a Simplified Installation (Return/Return Installation) and should be interlocked with a Partially Dedicated Installation.
Consideration should be given to competing airflows when connecting the HRV/ERV in conjunction with an Air Handler/Furnace Blower system.
The HRV/ERV will be “fully-off” when the OFF position is selected on the Main Control. Timers and /or other controls will not function when the HRV/ERV is in the OFF position. The “fully-off” feature can be modified to “standby-off” by adding a jumper on the Terminal Block between 2 (ON) and 3 (RED). “Standby” can also be achieved by setting the main control to the ON position and selecting speed 0*. Timers and /or additional controls will initiate high speed ventilation when activated. * Speed 0 is not available on all controls The Terminal Block (located on the HRV/ERV)
off” functionality. Check with your local
building authority before modifying the unit
to “standby -off”.
end user may occur if the unit is modified
from “fully-off” to “standby-off”.
A jumper must be in place between 2 (ON) and 3 (RED) on the Terminal Block to activate the HRV/ERV for timers and/or dry contact controls.
The HRV/ERV must have a Jumper in place between 2 (ON) and 3 (RED) on the Terminal Block when installing the unit without a Main Control.
Adding Dry Contact Controls Low Speed - A jumper between 2 (ON) and 1 (LOW) initiates low speed ventilation. High Speed - A jumper between 2 (ON) and 6 (HI) initiates high speed ventilation. Dehumidistat - A dry contact for a dehumidistat is connected between 2 (ON) and 10 (BLK). The Terminal Block (located on the HRV/ERV)

Balancing the air flows is critical to ensuring that the amount of air introduced from the outside of the building equals the amount of air exhausted to the outside of the building. If these two air flows are not properly balanced, the following issues may occur:
Air Flow Measuring Gauges The magnehelic gauge and the digital manometer are suitable instruments for the balancing of air flows.
Continuous, excessive, positive pressure may drive moist indoor air into the external walls of the building. Once inside the external walls, moist air may condense (in cold weather) and degrade structural components or cause locks to freeze. Continuous, excessive, negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane and radon gas may be drawn into the home through basement or ground contact areas, and may also cause the backdrafting of vented combustion equipment.
A magnehelic gauge with a scale of 0 to .25" w.c. is suitable for accurately measuring air duct velocity. The value on the gauge will be velocity pressure. A digital manometer requires the ability to display differential pressures at 3 digits of resolution.
Gauge Attachments When sampling an air flow, various attachments are available for use on a magnehelic gauge or digital manometer.

The following illustration shows a magnehelic gauge with a scale of 0 to .25" w.c. with a pitot tube attachment. This combination will measure the system air velocity pressure accurately, regardless of the duct size or shape (either round or rectangular).
Magnehelic Gauge with a scale of 0 to .25” w.c.
DUCT
AIR FLOW
MAGNEHELIC
Magnehelic Gauge (scale of 0 to .25” w.c.) with a Pitot Tube Attachment

any elbows or bends and 1 foot upstream of any elbows or bends) in the Fresh Air and Stale air streams.
stream in the Stale Air From Building air stream. Move the Pitot tube around in the duct (facing towards the airflow) and take an average reading. Record the reading.

Stale Air From Building

Drill 3/16” holes in Stale & Fresh Air ducts.
Pitot tube tip facing towards the air stream.
Magnehelic Gauge must be level.
Fresh Air to Building
STEP 4.


B) Upon completion of balancing, seal the holes (foil tape recommended).
Pitot tube tip facing towards the air stream.
Magnehelic Gauge must be level.
A) Review the readings and damper down the duct with the highest duct velocity pressure. Repeat Step 2 and Step 3 until both ducts show indentical readings. For this example, the Fresh Air to Building air stream has the highest duct velocity pressure.
After balancing the air flows, calculate the cfm flow rate. Example This example shows how to determine the air flow for a 6” diameter duct. As shown in the illustration, the duct velocity pressure reads 0.025” w.c. on the magnehelic gauge. Use the chart that came with the magnehelic gauge to determine a duct velocity of 640 feet per minute for a duct

velocity pressure of 0.025” w.c. Cfm Calculation cfm = feet per minute x cross section area of duct
= 640 x 0.196 = 125 Cross Section Area of some common round duct sizes: 0.087 for 4” diameter duct 0.136 for 5” diameter duct 0.196 for 6” diameter duct 0.267 for 7” diameter duct
Magnehelic Gauge reading .025” w.c.
Balancing Damper · Balancing Damper

Door balancing ports (not on all models) are designed to be used in conjunction with a Magnehelic Gauge or Digital Manometer to
Step 4 Close the HRV Door. Initiate power and operate the HRV on high speed. Operate the forced air system on high speed (if the HRV is connected to the forced air system) . Step 5 Insert the 2 rubber fittings from the gauge to the STALE AIR Balancing Ports (upper right and lower left). Seal the FRESH AIR Balancing Ports (upper left and lower right) with tape. Record your reading. Step 6 Insert the 2 rubber fittings from the gauge to the FRESH AIR Balancing Ports (upper left and lower right). Seal the STALE AIR Balancing Ports (upper right and lower left) with tape. Record your reading. Step 7 Refer to the "Airflow Reference Chart" for your model and determine the FRESH AIR and STALE AIR flow rates (the chart is located on the lower portion of this page). Step 8 Damper down the higher airflow and repeat Steps 5 to 7 as required until both airflows are identical (balanced). Step 9 Remove the tape and rubber fittings and reinstall the 4 Door Port Covers.
measure the Stale and Fresh airflows for balancing.

Step 1 Prepare the air flow measuring device (i.e. Magnehelic Gauge or Digital Manometer) by connecting the hoses to the low and high pressure side of the gauge. Step 2 Insert the hoses into the rubber fittings from the optional Door Port Adapter Kit (part # 99-182). Use light pressure and rotate until fitting is snug. Do not extend the hose past the rubber fitting. Step 3 Open the HRV Door. Remove the 4 Door Port Covers by carefully pushing them out from the back side of the door (use the blunt end of a large drill bit etc.).
Magnehelic Gauge hoses connected to STALE AIR balancing ports

FC200HRV FC155HRV
MODEL 200
(CFM)
(CFM)
Fresh Air Stale Air
Fresh Air Stale Air
(in. w.g.)
(in. w.g.)
0.100 93 80 0.105 96 83 0.110 99 86 0.115 102 89 0.120 105 92 0.125 108 96 0.130 111 99 0.135 114 102 0.140 117 105 0.145 120 108 0.150 123 111 0.160 130 117 0.170 136 123 0 180 . 142 129 0.190 148 135 0.200 154 141 0.210 160 147 0.220 166 154 0.230 172 160 0.240 178 166 0.250 184 172 0.260 191 178 0.270 197 184 0.280 203 190 0.290 209 196 0.300 215 202 0.310 221 209
0.100 98 91 0.110 102 96 0.120 107 101 0.130 111 107 0.140 115 112 0.150 120 117 0.160 124 122 0.170 128 127 0.180 133 132 0.190 137 137 0.200 141 142 0.210 145 147 0.220 149 152 0 230 . 153 156 0.240 157 161 0.250 161 166 0.260 165 171 0.270 169 175 0.280 173 180 0.290 177 184 0.300 181 189 0.310 185 193 0.320 189 198 0.330 192 202 0.340 196 207 0.350 200 211 0.360 203 215
Illustration of measuring STALE airflow using a Magnehelic Gauge.
Magnehelic Gauge hoses connected to FRESH AIR balancing ports
0 180 142 129
0 230 153 156

Illustration of measuring FRESH airflow using a Magnehelic Gauge.

The FC155HRV and FC200HRV models have factory installed Balancing Dampers located in the “Fresh Air to Building” and “Stale Air from Building” collars.
Installations where the HRV is ducted directly to the return of the furnace/Air Handler may require additional dampening on the fresh air to building duct. This is due to the high return static pressures found in some furnace installations.
All other units require the installation of balancing dampers (not included) in the “Fresh Air to Building” and “Stale Air from Building” ductwork. Refer to the installation diagrams in this manual for the Simplified, Partially Dedicated, and Fully Dedicated systems.
Observe the location of the screws when connecting ductwork to the collar. Screws should be located no further than 1/2” from the outside edge of the collar and they should be no longer than 3/4”.
Push and turn with slotted screwdriver. Damper automatically locks when pressure is released.
Illustration of Adjusting the Factory Installed Balancing Damper
Illustration of Connecting ductwork to the Balancing Damper Collars
1/2”

SYMPTOM CAUSE SOLUTION
Supply air feels cold
Dehumidistat is not Operating
Humidity Levels are too High Condensation is appearing on the windows
Humidity Levels are too Low
HRV and/or Ducts Frosting up
Condensation or Ice Build Up in Insulated Duct to the Outside
Water in the bottom of the HRV
Poor Air Flows


PIN 1 - BLACK PIN 2 - ORANGE PIN 3 - RED PIN 4 - SPARE
3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SPARE
P3 PIN 1 - BLUE PIN 4 - RED PIN 2 - YELLOW PIN 5 - WHITE PIN 3 - BROWN PIN 6 - BLACK
P6 PIN 1 - GREEN PIN 2 - GREEN