General Information

Important Safety Messages

SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the Smart-UPS and batteries.

Read these instructions carefully and look at the equipment to become familiar with the equipment before attempting to install, operate, service or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.

APC Smart-UPS Rack-Mount — General Information diagram (page 3)
Fig. 2 · General Information

Product Handling Guidelines

18-32 kg 40-70 lb 32-55 kg 70-120 lb >55 kg >120 lb

1 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 4 of the APC Smart-UPS Rack-Mount user manual — Safety and General Information
Page 4 · click to enlarge
Page 4

Safety and General Information

  • Adhere to all national and local electrical codes.
  • All wiring must be performed by a qualified electrician.
  • Changes and modifications to this unit not expressly approved by APC could void the warranty.
  • This UPS is intended for indoor use only.
  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
  • For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
  • The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life.
  • Replace the battery immediately when the UPS indicates battery replacement is necessary.
  • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
  • The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs), in a rack.
  • Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.
  • Always install peripheral equipment above the UPS in rack-mount configurations.
  • Additional safety information can be found in the Safety Guide supplied with this unit.

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 2

Page 5 of the APC Smart-UPS Rack-Mount user manual — Battery
Page 5 · click to enlarge
Page 5

Product Description

The APC by Schneider Electric Smart-UPS™ is a high performance uninterruptible power supply (UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to acceptable levels or the batteries are completely discharged.

This user manual is available on the enclosed Documentation CD. Download the latest version (if any) of the user manual from the APC by Schneider Electric web site, www.apc.com Specifications

For additional specifications, refer to the APC by Schneider Electric Web site at www.apc.com

Weight SpecificationsUPS + Battery PackBattery Pack 24 kg (53 lb)10.5 kg (23 lb) TemperatureOperating0° to 40° C (32° to 104° F) Storage-15° to 45° C (5° to 113° F) charge UPS battery every six months Maximum ElevationOperating3,000 m (10,000 ft) Storage15,000 m (50,000 ft) Humidity0% to 95% relative humidity, non-condensing0° to 40° C (32° to 104° F)

Battery

CAUTION

RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE

  • Replace the battery at least every 5 years.
  • Replace the battery immediately when the UPS indicates battery replacement is necessary.
  • Replace battery at the end of its service life.
  • Replace batteries with the same number and type of batteries as originally installed in the equipment.
  • Replace the battery immediately when the UPS indicates a battery overtemperature condition, or UPS internal overtemperature, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
  • *Replace all battery modules (including the modules in External Battery Packs) which are older than one year, when installing additional battery packs or replacing the battery module(s).

Failure to follow these instructions could result in equipment damage and minor or moderate injury.

*Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.

Maintenance free, sealed lead acidUPS modelReplacement Battery Pack SMT1200RMJ1U SMT1500RM1U SMT1500RMI1UAPCRBC88J APCRBC88 APCRBC88 Replace used batteries with APC by Schneider Electric approved batteries. To order a replacement battery go to the APC by Schneider Electric Web site, www.apc.com. Always recycle used batteries. For information on recycling a used battery, refer to the Battery Disposal Information sheet included with the replacement battery.

3 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 6 of the APC Smart-UPS Rack-Mount user manual — Installation
Page 6 · click to enlarge
Page 6

Product Overview

Front panel features

APC Smart-UPS Rack-Mount — Front panel features diagram (page 6)
Fig. 3 · Front panel features

Rear panel features

1200/1500 VA 100/120 Vac

APC Smart-UPS Rack-Mount — Rear panel features diagram (page 6)
Fig. 4 · Rear panel features

1500 VA 230 Vac

APC Smart-UPS Rack-Mount — 1500 VA 230 Vac diagram (page 6)
Fig. 5 · 1500 VA 230 Vac

Controlled outlet group 1

Controlled outlet group 2

RJ45 connector - serial UPS monitoring port

SmartSlot for optional accessory card

Installation

For UPS installation information, refer to the Smart-UPS 1200/1500 VA 100/120/230 Vac Rack-Mount 1U Installation Guide that is included with the UPS. The Installation Guide is also available on the Documentation CD included with the UPS and on the APC by Schneider Electric Web site, www.apc.com

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 4

Show 8 more labels / short text on this page
Battery · Battery connector · Display interface · Bezel · su0699b su0699c · Circuit breaker/Overload protection · UPS input · USB port
Page 7 of the APC Smart-UPS Rack-Mount user manual — Rear panel features
Page 7 · click to enlarge
Page 7

Operation

Connect Equipment

APC Smart-UPS Rack-Mount — Operation diagram (page 7)
Fig. 6 · Operation
  • Adhere to all local and national electrical codes.
  • Always connect the UPS to a grounded outlet. Failure to follow these instructions can result in minor or moderate injury
1. Connect equipment to the outlets on the rear panel of the UPS.
2. Connect the UPS to the building utility power. Connect the UPS to a two pole, three wire, grounded source only.
3. To use the UPS as a M ASTER O N /O FF switch, turn on equipment that is connected to the UPS.
4. To turn on the UPS and all connected equipment press the ON / OFF button on the front panel of the UPS.
5. Refer to “Switched Outlet Groups” on page 12 for information on switched outlet group configuration. Outlet type and location may vary.
APC Smart-UPS Rack-Mount — Operation diagram (page 7)
Fig. 7 · Operation

Rear panel features

Serial port: Connect a computer to use power management software.

USB port: Connect a computer to use power management software.

5 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 8 of the APC Smart-UPS Rack-Mount user manual — Menu overview
Page 8 · click to enlarge
Page 8

Display Panel

Overview

UP/DOWN arrow buttons

UPS ON/OFF button

Display interface operation

Press either the ESC or ENTER buttons to access the main menu.

Use the UP/DOWN arrow buttons to scroll through menu options.

Press ENTER to view sub menus. Scroll through the list of options. Press ENTER to select an option.

Press ESCAPE to exit a sub menu and return to a main menu.

Menu overview

The display interface has Standard and Advanced menu screens. The preference for Standard or Advanced menu options is made during initial installation and can be changed at any time using the Configuration menu.

Standard menus are the most commonly used menus. The default screen shows Load and Battery Capacity bar graphs.

The Advanced menus include more status information and additional sub menus. The default screen shows scrolling status information.

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 6

Show 8 more labels / short text on this page
Online LED · On Battery LED · Alert LED · Replace Battery LED · Display screen · su0701a · ENTER button · ESCAPE button
Page 9 of the APC Smart-UPS Rack-Mount user manual — Display Panel
Page 9 · click to enlarge
Page 9
Main MenuDisplay DescriptionStandard OptionAdvanced Option Status * Advanced menu Status items displayed as scrolling informationOperating mode*xx Efficiencyxx Load power (W)*xx Load power (VA)*xx Load amperagex Load energy meterx Battery charge state%xx Battery runtime*xx Battery voltagexx Battery temperaturex Input voltage and frequency*xx Output voltage and frequency*xx Last transfer reason*xx Last UPS self test resultxx Outlet group status*x NMC IP address (if applicable)x ControlUPS controlx Outlet Group controlx ConfigurationLanguagexx Output voltage setting (if applicable)x Power qualityxx Menu typexx Audible alarmsxx Display modexx Sensitivityx Low voltage transfer pointsx High voltage transfer pointsx Low battery alert thresholdx Automatic self test intervalx Battery install datexx Reset energy meterx Enter set-up wizardx Perform firmware update (UPS output must be off)x Reset to factory defaultsxx Outlet group configurationx NMC configuration (if applicable)x Test & DiagnosticsUPS self testxx UPS alarms testxx UPS calibration testxx

7 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 10 of the APC Smart-UPS Rack-Mount user manual — Display Panel
Page 10 · click to enlarge
Page 10
Main MenuDisplay DescriptionStandard OptionAdvanced Option LogsLast 10 transfer events (if applicable)x Last 10 alert events (if applicable)x AboutModel identificationxx Part numberxx Serial numberxx UPS manufacture datexx Replace battery part numberxx Battery install datexx Replace battery datexx UPS firmware revisionxx NMC Information - part/serial/version numbers/manufacture date/MAC address/ firmware revision (if applicable)x

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 8

Page 11 of the APC Smart-UPS Rack-Mount user manual — Start up settings
Page 11 · click to enlarge
Page 11

Configuration

UPS Settings

Start up settings

At initial start up use the Setup Wizard to configure the following settings.

FunctionFactory DefaultOptionsDescription LanguageEnglish• English • French • German • Spanish • Italian • Portuguese • JapaneseThe language for the display interface. Language options will vary by model. Output Voltage 230 Vac models only230 Vac• 220 Vac • 230 Vac • 240 VacUPS output must be off to configure this setting. Local Power QualityGood• Good • Fair • PoorSelect the desired utility input power quality. • Good: The UPS will go on battery power more often to provide the cleanest power supply to connected equipment. • Fair: The UPS will tolerate some voltage fluctuations before switching to battery power. • Poor: The UPS will tolerate more voltage fluctuations and will go on battery power less often. The Power Quality setting will automatically change the high and low transfer points and the transfer sensitivity setting. Menu TypeStandard• Standard • AdvancedThe Advanced menus include all parameters. The Standard menus display a limited set of menus and options. DateUPS manufacture date + 90 daysmm-yyyyAt initial start up, enter the current date.

9 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 12 of the APC Smart-UPS Rack-Mount user manual — General settings
Page 12 · click to enlarge
Page 12

General settings

Configure these settings at any time, using the display interface or PowerChute™ software.

FunctionFactory DefaultOptionsDescription High Transfer Point100 Vac models: 108 Vac 120 Vac models: 127 Vac 230 Vac models: 253 Vac100 Vac models: 108-114 Vac 120 Vac models: 127-136 Vac 230 Vac models: 242-276 VacTo avoid unnecessary battery usage, the high and low transfer points can be adjusted. • Set the transfer point higher if the AC voltage is chronically high. • Set the transfer point lower if the AC voltage is chronically low. When the Power Quality setting is changed the high and low transfer points will automatically be adjusted. 230 Vac models only: The transfer point options will change based on the output voltage setting. Low Transfer Point100 Vac models: 92 Vac 120 Vac models: 106 Vac 230 Vac models: 207 Vac100 Vac models: 86-92 Vac 120 Vac models: 97-106 Vac 230 Vac models: 186-216 Vac Transfer SensitivityNormal• Normal • Reduced • LowSet the sensitivity to a level that is appropriate for the connected equipment. • Normal: The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment. • Reduced: The UPS will tolerate some voltage fluctuations before switching to battery power. • Low: The UPS will tolerate more voltage fluctuations and will go on battery power less often. When the Power Quality setting is changed the transfer sensitivity will automatically be adjusted. Low Runtime Alert120 secValue set in secondsThe UPS will emit an audible alarm when the remaining runtime has reached this level. Date of Last Battery ReplacementDate set at factoryReset this date when the battery module is replaced. Audible AlarmOn• On • OffThe UPS will mute all audible alarms if this is set to Off or when any of the display buttons are pressed. Display ModeAuto Dim• Always On • Auto Dim • Auto Off• The display interface remains continuously illuminated. • The display interface illumination will diminish after two minutes of inactivity. • The display interface illumination will extinguish after two minutes of inactivity.

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 10

Page 13 of the APC Smart-UPS Rack-Mount user manual — Function Factory Default Options Description
Page 13 · click to enlarge
Page 13

Function Factory Default Options Description

On start up and 14 days after each self-test.

  • Last test + 14 days
  • Last test + 7 days
  • Start up+ 14 days
  • Start up + 7 days
  • On start up only
  • Never

The interval at which the UPS will execute a self-test.

The batteries must be charged to at least 70% capacity to perform a self-test.

“Start up” on these menus refers to any time the UPS is turned on.

Reset to Factory Default

  • No
  • Yes
  • No Restore the UPS factory default settings.

11 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Auto Self-Test Interval

Page 14 of the APC Smart-UPS Rack-Mount user manual — Configure the Switched Outlet Groups
Page 14 · click to enlarge
Page 14

Switched Outlet Groups

Overview

The UPS has two Switched Outlet Groups. Each can be configured to independently perform the following actions:

  • Turn off: Disconnect from power immediately and restart only with a manual command.
  • Turn on: Connect to power immediately.
  • Shutdown: Disconnect power, and automatically reapply power when utility power becomes available.
  • Reboot: Shut down and restart.
  • Turn on or off in a specified sequence.
  • Automatically turn off or shut down when various conditions occur. Note: If the Switched Outlet Groups are not configured, all of the outlets on the unit will provide battery backup power.

Configure the Switched Outlet Groups

1. Connect equipment to the Switched Outlet Groups.

– Nonessential equipment that should shut off quickly in the event of a power outage to conserve

battery runtime can be added to a short power off delay.

– If equipment has dependent peripherals that must restart or shut down in a specific order, such

as an ethernet switch that must restart before a connected server, connect the devices to separate groups.

– Equipment that needs to reboot independently from other equipment should be added to a

separate group.

2. Use the Configuration menus to configure how the Switched Outlet Group will react in the event of a power outage.

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 12

Page 15 of the APC Smart-UPS Rack-Mount user manual — Customize Switched Outlet Groups
Page 15 · click to enlarge
Page 15

Customize Switched Outlet Groups

Use the Configuration menu to change the Switched Outlet Group settings.

Function Factory Default Options Description

Turn On Delay 0 sec Set the value in seconds

The amount of time the UPS or Switched Outlet Group will wait between receiving the command to turn on and the actual startup.

Turn Off Delay 90 sec Set the value in seconds

The amount of time that the UPS or Switched Outlet Group will wait between receiving the command to turn off and the actual shut down.

Reboot Duration 8 sec Set the value in seconds

The amount of time that the UPS or Switched Outlet Group must remain off before it will restart.

Minimum Return Run Time

0 sec Set the value in seconds

The amount of battery runtime that must be available before the UPS or Switched Outlet Group will turn on.

Load Shed Time On Battery

  • Disabled
  • Enable
  • Disable When the unit switches to battery power, the UPS can disconnect power to the Switched Outlet Group to save runtime.

Load Shed Time On Battery

1800 sec Set the value in seconds

The amount of time the Switched Outlet Group will continue function after the UPS begins operating on battery.

  • Disabled
  • Enable
  • Disable When the battery runtime falls below the specified value, the Switched Outlet Group will turn off.

Load Shed Runtime Remain

120 sec Set the value in seconds

Remaining runtime required for the outlets to stay on.

Load Shed on Overload

  • Disabled
  • Enable
  • Disable In the event of an overload (greater than 100% output), the Switched Outlet Group will immediately turn off to conserve power for critical loads. The Switched Outlet Group will only turn on again with a manual command.

13 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Load Shed · Runtime Remain

Page 16 of the APC Smart-UPS Rack-Mount user manual — Problem and Possible Cause Solution
Page 16 · click to enlarge
Page 16

Troubleshooting

Problem and Possible Cause Solution

The UPS will not turn on or there is no output

The UPS has not been turned on. Press the ON button once to turn on the UPS.

The UPS is not connected to utility power. Ensure that the power cable is securely connected to the unit and to the utility power supply.

The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.

The unit shows very low or no input utility voltage.

Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage.

The UPS has detected an internal fault. Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

The UPS is operating on battery, while connected to utility power

The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.

There is very high, very low, or distorted input line voltage.

Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.

The UPS is beeping

The UPS is in normal operation. None. The UPS is protecting the connected equipment.

UPS does not provide expected backup time

The UPS battery is weak due to a recent outage or is near the end of its service life.

Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated.

The UPS is experiencing an overload condition.

Check the UPS load display. Unplug unnecessary equipment, such as printers.

Display interface LEDs flash sequentially

The UPS has been shut down remotely through software or an optional accessory card.

None. The UPS will restart automatically when AC power returns.

The Alert LED is illuminated, the UPS displays a message and emits a constant beeping

The UPS has detected an internal fault. Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 14

Page 17 of the APC Smart-UPS Rack-Mount user manual — Problem and Possible Cause Solution
Page 17 · click to enlarge
Page 17

Problem and Possible Cause Solution

The replace battery LED is illuminated

The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a Self-Test. If the problem persists after recharging, replace the battery.

The replacement battery is not properly connected.

Ensure that the battery connector is securely connected.

15 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 18 of the APC Smart-UPS Rack-Mount user manual — Transport
Page 18 · click to enlarge
Page 18

Transport

1. Shut down and disconnect all connected equipment.
2. Disconnect the unit from mains power.
3. Disconnect all internal and external batteries (if applicable).
4. Follow the shipping instructions outlined in the Service section of this manual. Service

If the unit requires service, do not return it to the dealer. Follow these steps:

1. Review the Troubleshooting section of the manual to eliminate common problems.
2. If the problem persists, contact APC by Schneider Electric Customer Support through the APC by Schneider Electric web site, www.apc.com.

a. Note the model number and serial number and the date of purchase. The model and serial numbers

are located on the rear panel of the unit and are available through the LCD display on select models.

b. Call Customer Support. A technician will attempt to solve the problem over the phone. If this is not

possible, the technician will issue a Returned Material Authorization Number (RMA#).

c. If the unit is under warranty, the repairs are free.

d. Service procedures and returns may vary internationally. For country specific instructions

refer to the APC by Schneider Electric web site, www.apc.com.

3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty. Note: Before shipping, always disconnect battery modules in a UPS or external battery pack. The disconnected internal batteries may remain inside the UPS or external battery pack.
4. Write the RMA# provided by Customer Support on the outside of the package.
5. Return the unit by insured, prepaid carrier to the address provided by Customer Support.

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 16

Page 19 of the APC Smart-UPS Rack-Mount user manual — Limited Factory Warranty
Page 19 · click to enlarge
Page 19

Limited Factory Warranty

Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period.

This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com.

SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT recommendations or specifications. Further, SEIT shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.

EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.

SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.

SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.

THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.

IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.

NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.

To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the SEIT Web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.

17 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Page 20 of the APC Smart-UPS Rack-Mount user manual — Limited Factory Warranty
Page 20 · click to enlarge
Page 20

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 18

Page 21 of the APC Smart-UPS Rack-Mount user manual — Limited Factory Warranty
Page 21 · click to enlarge
Page 21
Page 21 of the APC Smart-UPS Rack-Mount user manual — Limited Factory Warranty
Page 22 of the APC Smart-UPS Rack-Mount user manual — 0 5 /20 21 EN 990-4324 G
Page 22 · click to enlarge
Page 22

APC by Schneider Electric Worldwide Customer Support

Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:

  • Visit the APC by Schneider Electric Web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests. – <a href="http://www.apc.com" rel="nofollow noopener" target="_blank">www.apc.com</a> (Corporate Headquarters)

Connect to localized APC by Schneider Electric Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/

Global support searching APC by Schneider Electric Knowledge Base and using e-support.

  • Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail. – Local, country-specific centers: go to <a href="http://www.apc.com/support/contact" rel="nofollow noopener" target="_blank">www.apc.com/support/contact</a> for contact information. – For information on how to obtain local customer support, contact the APC by Schneider Electric

representative or other distributors from whom you purchased your APC by Schneider Electric product.

© 2021 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their

respective owners.

0 5 /20 21 EN 990-4324 G

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
The UPS will not turn on or there is no output p.16
The UPS has not been turned on.Press the ON button once to turn on the UPS. p.16
The UPS is not connected to utility power.Ensure that the power cable is securely connected to the unit and to the utility power supply. p.16
The input circuit breaker has tripped.Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker. p.16
The unit shows very low or no input utility voltage.Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage. p.16
The UPS has detected an internal fault.Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately. p.16
The UPS is operating on battery, while connected to utility power p.16
There is very high, very low, or distorted input line voltage.Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity. p.16
The UPS is beeping p.16
The UPS is in normal operation.None. The UPS is protecting the connected equipment. p.16
UPS does not provide expected backup time p.16
The UPS battery is weak due to a recent outage or is near the end of its service life.Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated. p.16
The UPS is experiencing an overload condition.Check the UPS load display. Unplug unnecessary equipment, such as printers. p.16
Display interface LEDs flash sequentially p.16
The UPS has been shut down remotely through software or an optional accessory card.None. The UPS will restart automatically when AC power returns. p.16
The Alert LED is illuminated, the UPS displays a message and emits a constant beeping p.16
The UPS has detected an internal fault.Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately. p.16
The replace battery LED is illuminated p.17
The battery has a weak charge.Allow the battery to recharge for at least four hours. Then, perform a Self-Test. If the problem persists after recharging, replace the battery. p.17
The replacement battery is not properly connected.Ensure that the battery connector is securely connected. p.17

Ask about the APC Smart-UPS Rack-Mount

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the APC Smart-UPS Rack-Mount

Be the first to ask — other owners or our team will answer.

Original document

APC Smart-UPS Rack-Mount manual PDF

22 pages·471 KB·Uninterruptible Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…