Important Safety Messages
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the Smart-UPS and batteries.
Read these instructions carefully and look at the equipment to become familiar with the equipment before attempting to install, operate, service or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning product safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.

18-32 kg 40-70 lb 32-55 kg 70-120 lb >55 kg >120 lb
1 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 2

The APC by Schneider Electric Smart-UPS™ is a high performance uninterruptible power supply (UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to acceptable levels or the batteries are completely discharged.
This user manual is available on the enclosed Documentation CD. Download the latest version (if any) of the user manual from the APC by Schneider Electric web site, www.apc.com Specifications
For additional specifications, refer to the APC by Schneider Electric Web site at www.apc.com
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
Failure to follow these instructions could result in equipment damage and minor or moderate injury.
*Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.
3 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U


1200/1500 VA 100/120 Vac


Controlled outlet group 1
Controlled outlet group 2
RJ45 connector - serial UPS monitoring port
SmartSlot for optional accessory card
For UPS installation information, refer to the Smart-UPS 1200/1500 VA 100/120/230 Vac Rack-Mount 1U Installation Guide that is included with the UPS. The Installation Guide is also available on the Documentation CD included with the UPS and on the APC by Schneider Electric Web site, www.apc.com
Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 4

Connect Equipment


Serial port: Connect a computer to use power management software.
USB port: Connect a computer to use power management software.
5 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

UP/DOWN arrow buttons
UPS ON/OFF button
Press either the ESC or ENTER buttons to access the main menu.
Use the UP/DOWN arrow buttons to scroll through menu options.
Press ENTER to view sub menus. Scroll through the list of options. Press ENTER to select an option.
Press ESCAPE to exit a sub menu and return to a main menu.
The display interface has Standard and Advanced menu screens. The preference for Standard or Advanced menu options is made during initial installation and can be changed at any time using the Configuration menu.
Standard menus are the most commonly used menus. The default screen shows Load and Battery Capacity bar graphs.
The Advanced menus include more status information and additional sub menus. The default screen shows scrolling status information.
Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 6

7 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 8

UPS Settings
At initial start up use the Setup Wizard to configure the following settings.
9 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Configure these settings at any time, using the display interface or PowerChute™ software.
Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 10

On start up and 14 days after each self-test.
The interval at which the UPS will execute a self-test.
The batteries must be charged to at least 70% capacity to perform a self-test.
“Start up” on these menus refers to any time the UPS is turned on.
Reset to Factory Default
11 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U
Auto Self-Test Interval

The UPS has two Switched Outlet Groups. Each can be configured to independently perform the following actions:
– Nonessential equipment that should shut off quickly in the event of a power outage to conserve
battery runtime can be added to a short power off delay.
– If equipment has dependent peripherals that must restart or shut down in a specific order, such
as an ethernet switch that must restart before a connected server, connect the devices to separate groups.
– Equipment that needs to reboot independently from other equipment should be added to a
separate group.
Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 12

Use the Configuration menu to change the Switched Outlet Group settings.
Function Factory Default Options Description
Turn On Delay 0 sec Set the value in seconds
The amount of time the UPS or Switched Outlet Group will wait between receiving the command to turn on and the actual startup.
Turn Off Delay 90 sec Set the value in seconds
The amount of time that the UPS or Switched Outlet Group will wait between receiving the command to turn off and the actual shut down.
Reboot Duration 8 sec Set the value in seconds
The amount of time that the UPS or Switched Outlet Group must remain off before it will restart.
Minimum Return Run Time
0 sec Set the value in seconds
The amount of battery runtime that must be available before the UPS or Switched Outlet Group will turn on.
Load Shed Time On Battery
Load Shed Time On Battery
1800 sec Set the value in seconds
The amount of time the Switched Outlet Group will continue function after the UPS begins operating on battery.
Load Shed Runtime Remain
120 sec Set the value in seconds
Remaining runtime required for the outlets to stay on.
Load Shed on Overload
13 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U
Load Shed · Runtime Remain

The UPS will not turn on or there is no output
The UPS has not been turned on. Press the ON button once to turn on the UPS.
The UPS is not connected to utility power. Ensure that the power cable is securely connected to the unit and to the utility power supply.
The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.
The unit shows very low or no input utility voltage.
Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage.
The UPS has detected an internal fault. Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.
The UPS is operating on battery, while connected to utility power
The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.
There is very high, very low, or distorted input line voltage.
Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.
The UPS is beeping
The UPS is in normal operation. None. The UPS is protecting the connected equipment.
UPS does not provide expected backup time
The UPS battery is weak due to a recent outage or is near the end of its service life.
Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated.
The UPS is experiencing an overload condition.
Check the UPS load display. Unplug unnecessary equipment, such as printers.
Display interface LEDs flash sequentially
The UPS has been shut down remotely through software or an optional accessory card.
None. The UPS will restart automatically when AC power returns.
The Alert LED is illuminated, the UPS displays a message and emits a constant beeping
The UPS has detected an internal fault. Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.
Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 14

The replace battery LED is illuminated
The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a Self-Test. If the problem persists after recharging, replace the battery.
The replacement battery is not properly connected.
Ensure that the battery connector is securely connected.
15 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

If the unit requires service, do not return it to the dealer. Follow these steps:
a. Note the model number and serial number and the date of purchase. The model and serial numbers
are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call Customer Support. A technician will attempt to solve the problem over the phone. If this is not
possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. For country specific instructions
refer to the APC by Schneider Electric web site, www.apc.com.
Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 16

Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation or use of the product contrary to SEIT recommendations or specifications. Further, SEIT shall not be liable for defects resulting from: 1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT’S RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT’S LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support. Customers with warranty claims issues may access the SEIT worldwide customer support network through the SEIT Web site: www.apc.com. Select your country from the country selection drop down menu. Open the Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.
17 Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U

Smart-UPS 1200 VA 100 Vac Rack-Mount 1U / 1500 VA 120/230 Vac Rack-Mount 1U 18



Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:
Connect to localized APC by Schneider Electric Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/
Global support searching APC by Schneider Electric Knowledge Base and using e-support.
representative or other distributors from whom you purchased your APC by Schneider Electric product.
© 2021 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their
respective owners.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| The UPS will not turn on or there is no output | p.16 | ||
| The UPS has not been turned on. | Press the ON button once to turn on the UPS. | p.16 | |
| The UPS is not connected to utility power. | Ensure that the power cable is securely connected to the unit and to the utility power supply. | p.16 | |
| The input circuit breaker has tripped. | Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker. | p.16 | |
| The unit shows very low or no input utility voltage. | Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage. | p.16 | |
| The UPS has detected an internal fault. | Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately. | p.16 | |
| The UPS is operating on battery, while connected to utility power | p.16 | ||
| There is very high, very low, or distorted input line voltage. | Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity. | p.16 | |
| The UPS is beeping | p.16 | ||
| The UPS is in normal operation. | None. The UPS is protecting the connected equipment. | p.16 | |
| UPS does not provide expected backup time | p.16 | ||
| The UPS battery is weak due to a recent outage or is near the end of its service life. | Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated. | p.16 | |
| The UPS is experiencing an overload condition. | Check the UPS load display. Unplug unnecessary equipment, such as printers. | p.16 | |
| Display interface LEDs flash sequentially | p.16 | ||
| The UPS has been shut down remotely through software or an optional accessory card. | None. The UPS will restart automatically when AC power returns. | p.16 | |
| The Alert LED is illuminated, the UPS displays a message and emits a constant beeping | p.16 | ||
| The UPS has detected an internal fault. | Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately. | p.16 | |
| The replace battery LED is illuminated | p.17 | ||
| The battery has a weak charge. | Allow the battery to recharge for at least four hours. Then, perform a Self-Test. If the problem persists after recharging, replace the battery. | p.17 | |
| The replacement battery is not properly connected. | Ensure that the battery connector is securely connected. | p.17 |