6104 BCF3 R02 Page 1 Potential for Fire, Smoke and Asphyxiation Hazards T o the Homeowner or Equipment Owner : Please read and carefully follow all instructions provided in this manual regarding your responsibilities in caring for your heating equipment.
Page 2 6104 BCF3 R02 T able of Contents Before you begin .............................................................................................................................. ....... 2-4 T o the Owner .........................................
6104 BCF3 R02 Page 3 Bef or e y ou be gin . . . The following resources will give you addional information for your installation. W e suggest that you consult these resources whenever possible. Pay particular attention to the appliance manufacturer ’ s instructions.
Page 4 6104 BCF3 R02 Owner ’ s Responsibility: Follow These Instructions Exactly Contact a professional, quali fi ed service agency for the installation, adjustment and service of your oil burning system. Thereafter , have your equipment adjusted and inspected at least annually to ensure reliable operation.
6104 BCF3 R02 Page 5 Combustion air supply The burner requires combustion air and ventilation air for reliable operation. Assure that the building and/or com- bustion air openings comply with National Fire Protec- tion Standard for Oil-Burning Equipment, NFP A 31.
Page 6 6104 BCF3 R02 Figure 1. Min. Combustion Chamber Dimensions V erify fi ring rate Refer to appliance manufacturer ’ s instructions (if available) for fi ring rate and nozzle selection.
6104 BCF3 R02 Page 7 Mount the bur ner Mount fl ange(s) on air tube This section does not apply to burners with welded fl ang- es. Do not install air tube on burner . For non-pressur e fi ring fl ange , refer to Figure 3 : Install gasket (item a ) and fl ange (item d ).
Page 8 6104 BCF3 R02 Set dimension Z Loosen fastener c in Figure 6 . Slide the nozzle line and plate assembly until dimension Z in Figure 5 is 1-1/2” ±1/16” . When dimension Z (from end of air tube to fl at area of front face of head) is correctly set, tighten acorn nut c .
6104 BCF3 R02 Page 9 Install two high-quality shut-off valves in accessible locations on the oil supply line. Locate one valve close to the tank. Locate the other valve close to the burner , upstream of the fuel fi lter . Bur ner fuel fl ow One-pipe systems – See Figure 7 for the fuel fl ow path.
Page 10 6104 BCF3 R02 Keep Service Access Covers Securely Installed These covers must be securely in place to prevent electrical shock, damage from exter- nal elements, and protect against injury from moving parts. All covers or service access plates must be in place at all times except during maintenance and service.
6104 BCF3 R02 Page 1 1 Star t-up chec klist Combustion air supply and venting have been inspected and veri fi ed to be free of obstructions and installed in ac- cordance with all applicable codes. Oil nozzle has been selected correctly and securely in- stalled in the nozzle adapter .
Page 12 6104 BCF3 R02 Star t the Bur ner Do not attempt to start the burner when excess oil has accumulated in the appliance, the appliance is full of vapor , or when the combustion chamber is very hot. Do not attempt to re-establish fl ame with the burner running if the fl ame becomes extinguished during start- up, venting, or adjustment.
6104 BCF3 R02 Page 13 High Ef fi ciency/Positive Pr essure Appliances ; also vary from traditional appliances (see manufacturer ’ s recommendations). Follow these four steps to properly adjust the burner: Step 1: Adjust the air shutter/band until a trace of smoke is achieved.
Page 14 6104 BCF3 R02 Check motor current. The amp draw should not exceed the nameplate. Check all wiring for secure connections or insulation breaks. Check the pump pressure and cutoff function. Check primary control safety lockout timing. Check ignition system for proper operation.
6104 BCF3 R02 Page 15 R eplacement par ts Item Part Name/Description Part Number 1 Air T ube Specify 2 Flange Kit Specify 3 Electrode Assembly Specify 4 Air Shutter 3709 5 Nozzle Line Assembly Specify.
Page 16 6104 BCF3 R02 Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Beckett.
An important point after buying a device Beckett CF375 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Beckett CF375 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Beckett CF375 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Beckett CF375 you will learn all the available features of the product, as well as information on its operation. The information that you get Beckett CF375 will certainly help you make a decision on the purchase.
If you already are a holder of Beckett CF375, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Beckett CF375.
However, one of the most important roles played by the user manual is to help in solving problems with Beckett CF375. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Beckett CF375 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center