INSTALLATION AND MAINTENANCE INSTRUCTIONS

2112/24ATR Photoelectronic Smoke Detector with Fixed Heat and Integral Temp-3 Sounder

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Figure 1. Wiring diagram for the 2112/24ATR detector:

POWER

TO DETECTORS

EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716 12/24V

+ + – A A NC

P W

+ + – A A NC

P W

R

R

ALARM CONTACT

ALARM CONTACT

UL LISTED COMPATIBLE

CONTROL

NC COMMON

A U X

NC COMMON

A U X

EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER

PANEL

(OPTIONAL) RELEASING

C NO

(OPTIONAL) RELEASING

DEVICE

NO

DEVICE

NO

C NO

INITIATING

LOOP

OPTIONAL CLASS A WIRING

Specifications Diameter: 5.5 inches (140 mm) Height (including mounting bracket): 2.05 inches (52 mm) Weight: 7.5 oz. (210 g) Operating Temperature Range: 32° to 100°F (0° to 38°C) Operating Humidity Range: 10% to 93% Relative Humidity, Noncondensing Latching Alarm: Reset by momentary power interruption Audible Signal: 85 dBA minimum when in alarm or with supply polarity reversed Heat Sensor: 135°F Fixed Temperature Electronic Thermistor Electrical Ratings System Voltage (nominal): 12 or 24 VDC Minimum: 10 VDC Maximum: 35 VDC Maximum Ripple Voltage: 30% of nom. Voltage (peak to peak) Standby Current: 50 µA maximum Alarm Current: 49 mA typical, 60 mA max. at 12V 57 mA typical, 65 mA max. at 24V Reset Voltage: 0.8 VDC minimum Reset Time: 1.0 second maximum Start-up Time: 30 seconds maximum (after 60 sec. reset) EOL Relay: A77-716B, 12/24 VDC Alarm Initiation and Auxiliary Relay: 1A @ 30 VAC Contact Ratings, Resistive Load: 1A @ 30 VDC Special Considerations: Due to the built-in temporal pattern, use these detectors only with a non-coded power supply.

Before Installing Please thoroughly read the System Sensor manual I56-407, Guide for Proper Use of System Smoke Detectors, which pro- vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.

D200-84-00 1 I56-1240-02R

+

Page 2 of the System Sensor 24ATR user manual — D200-84-00 2 I56-1240-02R
Page 2 · click to enlarge
Page 2

Figure 2. Surface mounting of 2112/24ATR smoke detector on 31/2-inch and 4-inch octagonal box:

Mounting Each 2112/24ATR detector is supplied with a mounting bracket that permits the detector to be mounted: 1. To a single gang box, or 2. Directly to a 3-1/2 inch or 4 inch octagonal box, or 3. To a 4 inch square electrical box by using a plaster ring. 4. Directly to the ceiling using drywall anchors, if permitted by local codes and/or the authority having jurisdiction. Tamper-resistant Feature This detector includes a tamper-resistant feature that pre- vents its removal from the bracket without the use of a tool. To make the detector tamper-resistant, remove the smaller tab by breaking it at the scribed line on the tamper resistant tab on the detector mounting bracket (see Figure 3), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screw- driver to depress the tamper-resistant tab, located in the slot on the mounting bracket, and turn the detector coun- terclockwise.

General Description Model 2112/24ATR is a 4-wire photoelectronic smoke de- tector that uses a state-of-the-art optical sensing chamber. This detector also provides restorable, 135˚F fixed-tem- perature heat detection. The units have a heat detection unit that is integrated with the photoelectronic sensor. In addition, a piezoelectric horn in each detector produces an interrupted, 85 dBA tone when the individual detector alarms or when the supply voltage polarity is reversed.

NOTE: In order for all detectors on a loop to sound when the panel alarms, the panel must reverse the supply volt- age polarity to that loop upon alarm. For panels that do not reverse the polarity during alarm, a reversing relay, such as Systems Sensor’s RR-2, must be used. The RR-2 is designed to allow all the detectors in the same loop to sound when one of the detectors goes into alarm. Some panels may require the use of programmable outputs. Refer to System Sensor literature for further information on the RR-2.

Wiring Installation Guidelines All wiring must be installed in compliance with the Na- tional Electrical Code, applicable local codes, and any spe- cial requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.

Installation of this detector is simplified by the use of a mounting bracket and a plug-in screw terminal block that can be prewired to the system, allowing the detector to be easily installed or removed for cleaning. The detector’s sensitivity can be tested in place using the MOD400R Test Module.

The screw terminal block accepts 14 – 22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit. Do not mix fire system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against electrical interference.

An LED on the detector provides a local visual indication of the detector’s status. If power is applied to the detector and it is functioning normally in standby within the listed sensi- tivity range, the status LED blinks every ten seconds. The LED also latches on in alarm.

Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance al- lowed for the control panel being used before wiring the detector loops.

If the LED stops blinking, the unit should be removed for maintenance and inspection.

Figure 3. 2112/24ATR smoke detector mounting bracket:

TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER-RESIST FEATURE)

System Sensor 24ATR — D200-84-00 2 I56-1240-02R diagram (page 2)
Fig. 1

D200-84-00 2 I56-1240-02R

Show 14 more labels / short text on this page
· · · · · · · · · · · · ·
Page 3 of the System Sensor 24ATR user manual — D200-84-00 3 I56-1240-02R
Page 3 · click to enlarge
Page 3

Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting the wire into the appropriate terminal, and tightening the screw to secure the wire in place.

2. Press and hold the recessed test switch with a 0.18 inch maximum diameter tool such as an allen wrench or small screwdriver. 3. The detector’s LED should light within 5 seconds. B. Test Module (System Sensor Model No. MOD400R).

The MOD400R test module can be used with a DMM or analog voltmeter to check the detector sensitivity as de- scribed in the test module’s manual. C. Smoke Entry Test

WARNING

Remove power from the control unit or initiating device cir- cuits before installing detectors.

Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the de- tector until the unit alarms. D. Direct Heat Method (Hair dryer of 1000-1500 watts)

1. Wire the plug-in screw terminal block per Figure 1 and plug the terminal block into the detector. 2. Align the arrows on the detector with the arrows on the mounting bracket. 3. Turn the detector clockwise in the mounting bracket un- til it clicks into place. 4. After all detectors have been installed, apply power to the control unit or initiating device circuits. 5. Test the detector as described in TESTING. 6. Reset the detector at the system control panel. 7. Notify the proper authorities the system is in operation.

Direct the heat toward either of the side thermistors. Hold the heat source about 12 inches from the detector in order to avoid damage to the plastic. The detector will reset only after it has had sufficient time to cool and the power source has been momentarily interrupted.

Both smoke and heat detection testing are recommended for verifying system protection capability.

A detector that fails to activate with any of the above tests should first be cleaned as outlined in MAINTENANCE. If the detector still fails to activate, return it for repair.

CAUTION

Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne dust particles from enter- ing the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. Be sure to remove dust covers from any sensors that were left in place during construction as part of returning the system to service.

Notify the proper authorities the system is back in operation.

Maintenance NOTEBefore removing the detector, notify the proper au-

thorities that the smoke detector system is under- going maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. NOTE: Before removing the detector cover, note the posi-

Testing NOTEBefore testing, notify the proper authorities that

the smoke detector system is undergoing mainte- nance and will be temporarily out of service. Dis- able the zone or system undergoing maintenance to prevent unwanted alarms.

tion of the thermistors. Make sure the thermistors are not bent over when the housing is replaced.

Detectors must be tested after installation and following periodic maintenance. Test the 2112/24ATR as follows: A. Test Switch

1. Remove the detector housing by gently prying the four housing tabs on the bottom of the base with a smallbladed screwdriver and pull the housing from the base. Use caution to avoid damaging the thermistors. 2. Vacuum the screen carefully without removing it.
1. A recessed test switch is located on the detector housing (See Figure 4).

Figure 4. Top and side views showing position of test switch:

System Sensor 24ATR — CAUTION diagram (page 3)
Fig. 2

PUSH RECESSED SWITCH WITH A 0.18″ MAX. DIAMETER TOOL

D200-84-00 3 I56-1240-02R

Installation

Page 4 of the System Sensor 24ATR user manual — SENSING CHAMBER
Page 4 · click to enlarge
Page 4

Figure 5. Removal of cover and screen for cleaning: 3. Remove screen assembly, pulling straight out (please

see Figure 5). 4. Remove the sensing chamber cover. 5. Clean the sensing chamber by vacuuming or blowing

out dust and particles. 6. Replace the sensing chamber cover, aligning the arrow

REMOVABLE HOUSING

on the cover top with the arrow on the printed circuit board. 7. Replace the screen by placing the screen assembly over

REMOVABLE SCREEN

the sensing chamber cover and twisting until it snaps into place. 8. Replace the housing by aligning the three triangular

SENSING CHAMBER COVER

slots on the base with their counterparts on the hous- ing. Gently press the housing until it locks in place. Check to make sure that the thermistors are in the up- right position. 9. Reinstall the detector. 10. Notify the proper authorities that the system is back in operation.

SENSING CHAMBER

BASE

Please refer to insert for the Limitations of Fire Alarm Systems

System Sensor warrants its enclosed smoke detector to be free from de- fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or work- manship under normal use and service during the three year period com- mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-

ment, RA # , 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica- tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse- quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

D200-84-00 4 I56-1240-02R ©2001 System Sensor

Show 29 more labels / short text on this page
· yyyyyyyyyyyyyyyy · · yyyyyyyyyyyyyyy · · · yyyyyyyyyyyyyyyy · yyyyyyyyyyyyyyyy · · · yyyyyyyyyyyyyyy · yyyyyyyyyyyyyyy · · · yyyyyyyyyyyyyyyy · yyyyyyyyyyyyyyyy · · · yyyyyyyyyyyyyyy · yyyyyyyyyyyyyyy · · · yyyyyyyyyyyyyyyy · yyyyyyyyyyyyyyyy · · · yyyyyyyyyyyyyyy · yyyyyyyyyyyyyyy · Three-Year Limited Warranty

Ask about the System Sensor 24ATR

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the System Sensor 24ATR

Be the first to ask — other owners or our team will answer.

Original document

System Sensor 24ATR manual PDF

4 pages·137 KB·Smoke Alarm·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…