1400 Direct Wire Ionization Smoke Detector
3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com
Specifications Diameter: 5.5 inches (140 mm) Height: 3.12 inches (80 mm) Weight: 0.7 lb. (310 g) Operating Temperature: 0°C to +49°C (32°F to 120°F) Latching Alarm: Reset by momentary power interruption. Operating Humidity: 10% to 93% Relative Humidity, Noncondensing
Electrical Ratings: System Voltage: 12/24 VDC Maximum Ripple Voltage: 4 Volts peak to peak Start-up Capacitance: 0.02 µA Maximum Standby Ratings: 8.5 VDC Minimum 35 VDC Maximum 100 µA Maximum Alarm Ratings: 4.2 VDC Minimum at 10 mA 6.6 VDC Minimum at 100 mA Alarm current must be limited to 100 mA maximum by the control panel. If used, the
RA400Z Remote Annunciator operates within the specified detector alarm currents. Reset Voltage: 2.5 VDC Minimum Reset Time: 0.3 S Maximum Start-up Time: 35 S Maximum
Before Installing Please thoroughly read the System Sensor manual A05- 1003, Applications Guide for System Smoke Detectors. This manual provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor. (For installation in Canada, refer to CAN/ULC- S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
Each detector includes an LED that provides a local visual indication of the detector’s status. The LED blinks every ten seconds as an indication that power is applied to the detector and lights continuously in alarm. These detectors also have the latching alarm feature. The alarm can be reset only by a momentary power interruption.
The detector also has provision for the connection of an optional Model RA400Z Remote Annunciator. The RA400Z provides a visual indication of an alarm and mounts to a single gang box.
General Description System Sensor 1400 dual-chamber ionization smoke detec- tors utilize state-of-the-art, unipolar sensing chambers. These detectors are designed to provide open area protec- tion, and to be used with compatible UL-listed, 2-wire con- trol panels only. The detector’s operation and sensitivity can be tested in place.
Spacing NFPA 72 defines the spacing requirements for smoke detectors. Typically, this is 30 feet when the detectors are installed on a smooth ceiling. However, ALL installations must comply with NFPA 72 and/or special requirements of the authority having jurisdiction.

Figure 1. Surface mounting of Model 1400 detector on 3-1/2 and 4 inch octagonal box:
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the control panel being used before wiring the detector loops.
Begin electrical connections by stripping about 3⁄8″ insula- tion from the end of the wire. Then, slide the bare end of the wire under the clamping plate and tighten the clamping plate screw. A wiring diagram for a typical 2-wire detector system is shown in Figure 3.
Figure 2. Model 1400 detector mounting bracket:
connections are supervised. Do NOT loop the wire under the terminals.
TAB
System Sensor smoke detectors are marked with a compat- ibility identifier located as the last digit of a five digit code stamped on the back of the product. Connect detectors only to compatible control units as indicated in System Sensor’s compatibility chart which contains a current list of UL-listed control units and detectors. A copy of this list is available from System Sensor upon request.
Tamper-resistant Feature This detector includes a tamper-resistant feature that effec- tively prevents removal of the detector without the use of a tool. To make the detector tamper-resistant, break off the smaller tab at the scribed line on the tamper resistant tab, on the detector mounting bracket (see Figure 2), then install the detector. To remove the detector from the bracket once it has been made tamper resistant, use a small screw- driver to depress the tamper-resistant tab located in the slot on the mounting bracket and turn the detector coun- terclockwise for removal.
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
S0140-00
Mounting Each 1400 detector is supplied with a mounting bracket kit that permits the detector to be mounted: 1. Directly to a 31⁄2 inch or 4 inch octagonal, 11⁄2 inch deep electrical box, or 2. To a 4 inch square electrical box by using a plaster ring with the supplied mounting bracket kit.
Installation Wiring Guidelines All wiring must be installed in compliance with the National Electrical Code and all applicable local codes and any special requirements of the authority having jurisdic- tion, using the proper wire size. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
Disconnect the power to the alarm system control unit before installing detectors.
For signal wiring (the wiring between interconnected detectors), it is recommended that the wire be no smaller than AWG 18. However, the screws and clamping plate can accommodate wire sizes up to AWG 12. The use of twisted pair wiring for the power (+ and –) loop is recommended to minimize the effects of electrical interference.
Installation

Figure 3. Wiring diagram for 1400 smoke detector used with two-wire control panel:
LOOP
EOL RESISTOR
3 2 1 3 2 1
CONTROL
PANEL
REMOTE ANNUNCIATOR
REMOTE ANNUNCIATOR –
S0141-00
CLASS A OPTIONAL WIRING
A. Recessed Test Switch 1. A test switch is located on the detector housing (See
Dust covers can be used to help limit dust entry to the detector, but they are not a substitute for removing the detector during building construction. Remove any dust covers before placing system in service.
Figure 4). 2. Push and hold the recessed test switch with a 0.1 inch
maximum diameter tool. 3. The LED on the detector should light within 5 seconds. B. Test Module (System Sensor Model No. MOD400R) The MOD400R is used with an analog or digital voltme-
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
ter to check the detector sensitivity as described in the test module manual. C. Aerosol Generator (Gemini 501) Set the generator to represent 4%/ft. to 5%/ft. obscuration
Testing Before testing the detector, look for the presence of the flashing LED. If it does not flash, power has been lost to the detector (check the wiring), or it is defective (return for repair – refer to Warranty).
as described in the Gemini 501 manual. Using the bowl shaped applicator, apply aerosol until the unit alarms.
Notify the proper authorities that the system is back on line.
Detectors must be tested after installation and following periodic maintenance. Notify the proper authorities that the system is undergoing testing. The 1400 may be tested as follows:
Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested. If the detectors still fail these tests, they should be returned for repair.
Figure 4. Bottom and side views showing position of test switch:
SOCKET LED
TEST MODULE
PUSH RECESSED TEST SWITCH WITH A 0.1" MAX. DIAMETER TOOL.
D400-07-00 3 I56-279-05R

Figure 5. Removal of cover and screen for cleaning:
the smoke detector system is undergoing mainte- nance and, therefore, will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. The 1400 is cleaned as follows: 1. Remove the detector screen and cover assembly by depressing the three lock prongs on the top of the cover, rotating the cover clockwise, and pulling the screen cover assembly away from the detector (see Figure 5). Use of the System Sensor CRT400 cover removal tool is recommended. 2. Remove the screen from the cover. 3. Use a vacuum cleaner to remove dust from the screen, the cover, and the sensing chamber. 4. After cleaning, snap the screen into the cover, then place the cover and screen assembly on the detector turning clockwise until it is locked in place. 5. Test the detector as described in TESTING. 6. Notify the proper authorities that the system is back on line. S0143-00
REMOVABLE SCREEN
LOCK PRONG
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obliga- tion of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair
Department, RA # , 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s neg- ligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D400-07-00 4 I56-279-05R ©2004 System Sensor
Three-Year Limited Warranty
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.