Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.



1.1 Product Description
The AFI5100 is an Input Point Module used as part of a Siemens integrated access control and security solution. It provides an interface between an Advanced Access Controller (ACC) and up to 32 input devices used to monitor a secure facility.
The AFI5100 continuously monitors the status of all input devices connected; for example, Passive Infrared Detectors (PIRs). Any changes in state are instantly communicated to the ACC and then on to the Host system if necessary.
1.3 Prerequisites
z Input Devices to be connected to the IPM
z Cabling (RS-485)
z Required Tools & Materials
z Medium-duty drill and associated drill-bits (if required)
z 4 mounting screws or standoffs (approx. 4mm)
z Flat-blade terminal screwdriver
z Wire cutters
z Cable strippers

1.5 Mounting Instructions
It is recommended that you wear a grounding strap while carrying out this proce- dure.
Listed end-of-line resistors must be connected to the wiring for each input device if they are to be supervised. If supervised, cable must be shielded and total cable run resistance must not exceed 100 Ohms. Cable shielding must be unconnected at the device end, and connected to the board earth at the IPM end.
Listed end-of-line resistors must be connected to the Fire Over-ride Input wires if you are implement- ing Enhanced Fire Over-ride. Enhanced mode requires the connection of 22Kohm supervision resistor circuits. Cable must be shielded and total cable run resistance must not exceed 100 Ohms.



The following diagram displays the location of the ports on the AFI5100 :

9 4 5 6 7 8



The following table describes the operation of the LEDs located on the AFI5100 :
Each input LED may be in one of two states as indicated by color.

The following table outlines the cable recommended for connection of an inte- grated security system:

The previous table provides a guideline for selecting an appropriate cable type only. Other cable types are also compatible with the system and can be used to achieve the same results.
The AFI5100 is programmed using the host software application via the ACC, or using the FLN Configurator Field Service Tool application. Please refer to the ap- propriate User’s Guide for more Information.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are made.

Siemens Building Technologies A24205-A335-B245.doc



© 2005 Copyright by Siemens Building Technologies AG
Issued by Siemens Building Technologies Fire & Security Products GmbH & Co. oHG D-76181 Karlsruhe
Data and design subject to change without notice.
Supply subject to availability.
Printed in the Federal Republic of Germany on environment-friendly chlorine-free paper.
Document no. A24205-A335-B245