The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 1 of the Siemens 200 user manual — Instruction Manual July 2009
Page 1 · click to enlarge
Page 1

Instruction Manual July 2009

100/200 multiranger

Page 2 of the Siemens 200 user manual
Page 2 · click to enlarge
Page 2

Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.

Qualified Personnel: This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.

Unit Repair and Excluded Liability:

  • The user is responsible for all changes and repairs made to the device by the user or the user’s agent.
  • All new components are to be provided by Siemens Milltronics Process Instruments Inc.
  • Restrict repair to faulty components only.
  • Do not reuse faulty components.
Copyright Siemens Milltronics ProcessDisclaimer of Liability Instruments Inc. 2009. All Rights Reserved This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement. Technical data subject to change.

© Siemens Milltronics Process Instruments Inc. 2009

Page 3 of the Siemens 200 user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 4 of the Siemens 200 user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 5 of the Siemens 200 user manual — Table of contents
Page 5 · click to enlarge
Page 5

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 6 of the Siemens 200 user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 7 of the Siemens 200 user manual — Table of contents
Page 7 · click to enlarge
Page 7

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 8 of the Siemens 200 user manual — Table of contents
Page 8 · click to enlarge
Page 8

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 9 of the Siemens 200 user manual — Table of contents
Page 9 · click to enlarge
Page 9

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 10 of the Siemens 200 user manual — Table of contents
Page 10 · click to enlarge
Page 10

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 11 of the Siemens 200 user manual — Notes:
Page 11 · click to enlarge
Page 11

The MultiRanger 100 and 200

The MultiRanger is available in two models, MultiRanger 100 and MultiRanger 200, and is designed for a variety of applications:

  • water and wastewater
  • storage tanks, for measuring liquids, slurries, and solids
  • hoppers, ore bunkers, flotation cells

MultiRanger 100

MultiRanger 100/200

The MultiRanger 100 is a single or dual-point level, one, three, or six relay measurement device. It is equipped with digital communications and offers the latest in echo processing technology and diagnostic features.

MultiRanger 200

The MultiRanger 200 is a single or dual-point, three or six relay device that offers both level and volume measurement. It has Open Channel Monitoring capabilities, a larger number of advanced pump control algorithms, and is equipped with digital communications. It offers the latest in echo processing technology and diagnostic features.

The Manual

Notes:

  • This product is intended for use in industrial areas. Operation of this equipment

in a residential area may cause interference to several frequency based communications. • Please follow the installation and operating procedures for a quick, trouble-free

installation and to ensure the maximum accuracy and reliability of your MultiRanger.

The manual provides instruction for both MultiRanger 100 and MultiRanger 200 models. For your convenience, the manual uses MultiRanger 100 features as its standard content. Additional MultiRanger 200 features are clearly marked.

The manual is designed to help you get the most out of your MultiRanger, and it provides information on the following:

  • How to program the unit
  • Example applications
  • Principles of operation
  • Parameter values
  • Parameter uses
  • Outline diagrams
  • Wiring diagrams
  • Installation requirements
  • Modbus® 1 register mapping
  • Modem configuration
1. Modbus is a registered trademark of Schneider Electric.
Page 12 of the Siemens 200 user manual — MultiRanger 100/200
Page 12 · click to enlarge
Page 12

If you have any questions, comments, or suggestions about the manual contents, please email us at techpubs.smpi@siemens.com.

For the complete library of Siemens Milltronics manuals, go to www.siemens.com/processautomation

Manual Symbols

Please note their use carefully.

Alternating Current Direct Current Earth (ground) Terminal Protective Conductor Terminal Caution (refer to instructions) Infra-red communication port on front of instrument RJ-11 communications port No co-axial cable connections

MultiRanger 100/200

Configuration Examples

The configuration examples used in this manual illustrate the versatility of the MultiRanger. Because there is often a range of ways to approach an application, other configurations may also apply.

In all examples, substitute your own application details. If the examples do not apply to your application, check the applicable parameter reference for the available options.

Should you require more information, please contact your Siemens Milltronics representative. For a complete list of Siemens Milltronics representatives, go to www.siemens.com/processautomation

Page 13 of the Siemens 200 user manual — Pollution degree
Page 13 · click to enlarge
Page 13

Specifications

Power

AC version

  • 100-230 V AC ± 15%, 50 / 60 Hz, 36 VA (17W) 1
  • fuse: F3: 2 AG, Slow Blow, 0.375A, 250V

DC version

  • 12-30 V DC, 20W 1
  • fuse: F3: 2 AG, Slow Blow, 2A, 250V

Transmitter fuse

  • F1: Belling Lee, L754, 4000A HRC, ceramic type, 100mA, 250V

Temperature Sensor fuse

  • F2: Belling Lee, L754, 4000A HRC, ceramic type, 50mA, 250V

Mounting

Specifications

Location

  • indoor / outdoor

Altitude

  • 2000 m max.

Ambient temperature

  • -20 to 50 °C (-5 to 122 °F)

Relative humidity

  • Wall Mount: suitable for outdoors (Type 4X / Nema 4X, IP65 Enclosure)
  • Panel Mount: suitable for outdoors (Type 3 / Nema 3, IP54 Enclosure)

Installation category

  • II

Pollution degree

1. Power consumption is listed at maximum.

• 4

Page 14 of the Siemens 200 user manual — Sensor
Page 14 · click to enlarge
Page 14

Range

  • 0.3 m (1 ft) to 15 m (50 ft), dependent on transducer

Accuracy

  • 0.25% of maximum range or 6 mm (0.24”), whichever is greater

Resolution

  • 0.1% of program range 1 or 2 mm (0.08”), whichever is greater

Memory

  • 1 MB static RAM with battery backup
  • 512 kB flash EPROM

Programming

Primary

  • handheld programmer

Secondary

Specifications

  • PC running SIMATIC PDM
  • PC running Dolphin Plus software

Display

  • back lit LCD

Temperature Compensation

  • Range: -50 to 150 °C (-58 to 302 °F)

Source

  • integral transducer sensor
  • TS-3 temperature sensor
  • programmable fixed temperature

Temperature Error

Sensor

  • 0.09 % of range
1. Program range is defined as the empty distance from the face of the transducer (P006) plus any range extension (P801).
Page 15 of the Siemens 200 user manual — Optional
Page 15 · click to enlarge
Page 15

Fixed

  • 0.17 % per °C deviation from programmed value

Outputs

Transducer drive

  • 315 V peak

mA Analog

MultiRanger 100/200Single or Dual point versions include two mA outputs
  • 0-20 mA
  • 4-20 mA
  • 750 ohm maximum
  • Resolution of 0.1%
  • Isolated

Relays 1

  • One:
  • 1 control
  • Three:
  • 2 control
  • 1 alarm control
  • Six:
  • 4 control
  • 2 alarm control
  • All relays rated 5A at 250 V AC, non-inductive

Specifications

Control Relays

  • 1, 2 or 4 Form A, NO relays (numbers 1, 2, 4, 5)

Alarm Relay

  • 0, 1 or 2 Form C, NO, or NC relay (numbers 3, 6)

Communication

  • RS-232 running Modbus RTU and ASCII via RJ-11 connector
  • RS-485 running Modbus RTU and ASCII via terminal blocks

Optional

  • SmartLinx ® compatible
1. All relays are certified only for use with equipment that fails in a state at or under the rated maximums of the relays.
Page 16 of the Siemens 200 user manual — Transducer Frequency
Page 16 · click to enlarge
Page 16

Inputs

mA (analog) (1) [MR 200 only]

  • 0-20 or 4-20 mA, from alternate device, scalable

Discrete (2)

  • 10-50 V DC switching level
  • logical 0 = < 0.5 V DC
  • logical 1 = 10 to 50 V DC
  • 3 mA maximum draw

Enclosure

Wall Mount

  • 240 mm (9.5") x 175 mm (6.9"). Width dimension includes hinges.
  • Type 4X / NEMA 4X / IP 65 1
  • Polycarbonate

Panel Mount

  • 278 mm (10.93") x 198 mm (7.8") Width dimension includes flange.
  • Type 3 / Nema 3 / IP54
  • Polycarbonate

Specifications

Weight

  • Wall mount: 1.37 kg (3.02 lb)
  • Panel mount: 1.5 kg (3.3 lb)

Approvals

  • See product nameplate

Compatible Transducers

  • Echomax series and STH series

Transducer Frequency

  • 44 kHz
1. For watertight applications, use only approved, suitable size hubs in the enclosure’s conduit holes.
Page 17 of the Siemens 200 user manual — Specifications
Page 17 · click to enlarge
Page 17

Cable

  • Do not use coaxial cable for transducer (see General Appendix F: Upgrading on page 246 for more information)
  • transducer and mA output signal to be 2 copper conductors, twisted with shield/drain wire, 300 Vrms, 0.324 - 0.823 mm 2 (22 - 18 AWG), nominal capacitance between adjacent conductors @ 1kHz = 62.3 pF/m (19 pF/ft). Nominal capacitance between conductor and shield @ 1kHz = 108.3 pF/m (33 pF/ft) (Belden® 1 8760 is acceptable)
  • 365 m maximum

Specifications

1. Belden is a registered trademark of Belden Wire & Cable Company.
Page 18 of the Siemens 200 user manual — Installation
Page 18 · click to enlarge
Page 18

Installation

  • Installation must only be performed by qualified personnel, and in accordance

with local governing regulations. • This product is susceptible to electrostatic shock. Follow proper grounding

procedures.

All field wiring must have insulation suitable for at least 250 V.

Hazardous voltage present on transducer terminals during operation.

DC terminals shall be supplied from an SELV source in accordance with IEC 1010-1 Annex H.

  • The non-metallic enclosure does not provide grounding between conduit

connections. Use grounding type bushings and jumpers.

Mounting

Mounting Locations

Recommended

  • Ambient temperature is always within -20 to 50 °C (-5 to 122 °F)
  • MultiRanger display window is at shoulder level, unless most interaction is through a SCADA system
  • Easy access for hand programmer is provided
  • Cable length requirements are minimal
  • Mounting surface is free from vibration
  • Leave is sufficient room to swing unit lid open and have clear access.
  • A place for a laptop computer is provided for on-site Dolphin Plus configuration

Installation

Avoid

  • Exposure to direct sunlight. (Provide a sun shield to avoid direct sunlight.)
  • Proximity to high voltage/current runs, contacts, SCR or variable frequency motor speed controllers
Page 19 of the Siemens 200 user manual — Please note:
Page 19 · click to enlarge
Page 19

Mounting Instructions

The wall mount and panel mount units install differently. Please follow the specific instructions for your unit.

Wall Mount

Enclosure Dimensions

14.9 mm (0.58")

160.3 mm (6.325") 130 mm (5.125")

91 mm (3.58")

15.2 mm (0.6")

4.3 mm dia. (0.17") four mounting holes

6.6 mm (0.26")

240 mm (9.45") 227 mm (8.93")

Mounting the Enclosure

Installation

1. Remove the lid screws and open the lid to reveal the mounting screw holes. 2. Mark and drill four holes in the mounting

surface for the four screws (customer supplied). 3. Fasten with a long screwdriver.

Please note:

  • Recommended mounting: directly to wall or to electrical cabinet back panel
  • Recommended mounting screws: #6
  • If alternate mounting surface is used, it MUST be able to support four times the weight of the unit.

lid screws (6) · mounting screw holes

Page 20 of the Siemens 200 user manual — Installation
Page 20 · click to enlarge
Page 20

Cable routed through a conduit:

1. Remove the four mounting screws holding the motherboard to the enclosure. 2. Be careful not to damage the electronics with static electricity. Remove the

motherboard from the enclosure by pulling the board straight out. 3. Drill the required cable entry holes. Make sure conduit holes do not interfere with

the lower areas on the terminal block, circuit board, or SmartLinx card. 4. Attach the conduit to the enclosure using only approved suitable size hubs for

watertight application. 5. Reinstall the motherboard with the mounting screws.

suitable location for conduit entrances

Cable exposed and entering through the cable glands:

1. Unscrew the glands and attach them loosely to the enclosure. 2. Thread the cables through the glands. Ensure the power cable is kept separated

Installation

from the signal cables and then wire the cables to the terminal blocks. 3. Tighten the glands to form a good seal.

Page 21 of the Siemens 200 user manual — Installation
Page 21 · click to enlarge
Page 21

Panel Mount

Installing the panel mount unit requires making a cutout in the panel. The dimensions for the cutout are provided in the illustration below. A full size cutout template is provided with your unit or may be downloaded from www.siemens.com/processautomation

Cutout Dimensions

Siemens 200 — Cutout Dimensions diagram (page 21)
Fig. 1 · Cutout Dimensions

Installation

Cutout Instructions

1. Select a place for the unit and fasten the template onto the panel (use tape or tacks). 2. Drill the four fastener holes. 3. Make the cutout using the appropriate tools. 4. Mount unit according to the instructions in this manual.
Page 22 of the Siemens 200 user manual — Helpful hint:
Page 22 · click to enlarge
Page 22

Panel Mount Dimensions

198 mm (7.80")

97 mm (3.82")

36 mm (1.40")

278 mm (10.93")

Mounting the Enclosure

Once cutout is complete and mounting holes are drilled, follow these steps:

1. Remove lid from unit by undoing the six lid screws and lifting it off its hinges. 2. Remove the four screws holding the motherboard to the enclosure. 3. Be careful not to damage the electronics with static electricity. Remove the

motherboard from the enclosure by pulling the board straight out. 4. Drill the required cable entry holes. Be sure to compensate for panel door

Installation

dimensions and make sure conduit holes do not interfere with the lower areas on the terminal block, circuit board, or SmartLinx card. 5. Replace board and fasten the four screws. 6. Place the unit into the panel and insert hexagonal fasteners through bevel slots and

predrilled panel holes. 7. Fasten with wingnuts and hand tighten. 8. Add conduit or glands and wire as required, then replace the lid.

Helpful hint:

  • Use tape to hold hexagonal heads in slots while attaching wingnuts.
Page 23 of the Siemens 200 user manual — Installation
Page 23 · click to enlarge
Page 23

MultiRanger Board

Siemens 200 — MultiRanger Board diagram (page 23)
Fig. 2 · MultiRanger Board

Female Connector for SmartLinx Card

Installing the Battery

The battery (Rayovac BR2032) has a ten-year life expectancy. Please note the life expectancy may be reduced by ambient temperature. If the unit loses external and battery power, a capacitor will power the RAM for about ten minutes.

Siemens 200 — Installing the Battery diagram (page 23)
Fig. 3 · Installing the Battery

Installation

1. Open the enclosure lid. 2. Slide the battery into the holder. Be sure to

align the + and – terminals correctly. 3. Close and secure enclosure lid.

Show 6 more labels / short text on this page
Battery · RS-232 RJ-11 Connector · Power Supply · SmartLinx Card · Terminals · RS-485 Connections
Page 24 of the Siemens 200 user manual — Installation
Page 24 · click to enlarge
Page 24

Installing SmartLinx Card

SmartLinx cards are generally pre-installed. If unit does not have a SmartLinx card, follow these steps to install one.

1. Align card with the two mounting posts and then press-fit with the female connector. 2. Use the screws supplied with the card to attach it to the mounting posts. 3. Wire in the SmartLinx card according to SmartLinx Manual.

Installation

Page 25 of the Siemens 200 user manual — Wiring
Page 25 · click to enlarge
Page 25

Wiring

Please note:

  • Verify that all system components are installed in accordance with instructions.
  • Connect all cable shields to the MultiRanger Shield Terminals. Avoid differential ground potentials by not connecting cable shields to ground (earth) anywhere.
  • Keep exposed conductors on shielded cables as short as possible to reduce noise on the line caused by stray transmissions and noise pickup.

Siemens Milltronics TS-3 Temperature Sensor

Laptop running Dolphin Plus

Customer Alarm, Pump, or Control Device

Customer Device, digital output

Customer Device, analog output

Customer Network or Modem

Display, PLC, Chart recorder, or other Control Device

Wiring

MultiRanger · Siemens Milltronics Transducer(s) · SmartLinx Card

Page 26 of the Siemens 200 user manual — Wiring
Page 26 · click to enlarge
Page 26

Terminal Board

The terminal board on the MultiRanger allows all inputs and outputs to be connected simultaneously.

  • 0.56 - 0.79 Nm
  • 5 - 7 in.lbs Please do not overtighten the screws.

TB1

TB2

TB1

L2/N L1

TB3

SYNC

12-30 V

SHIELD

RELAY 1

4. 20 mA OUTPUTS

RELAY 2

RELAY 3

TS-3

SHIELD

RELAY 4

2 DISCRETE

INPUTS

RELAY 5

COM

RELAY 6

RS485

A

B

Cables

The MultiRanger transceiver requires a shielded two-wire connection to the transducer.

Connection Cable Type mA input and mA output sync, Temperature sensor, discrete input, dc input Transducer

2 copper conductors, twisted, with shield1/drain wire, 300V 0.324 - 0.823 mm2 (22 - 18 AWG) Maximum length: 365 m

Do not use a coaxial transducer cable extension with the MultiRanger. Electrical noise interference affects performance. Relay output AC input

Wiring

Relay to be copper conductors per local requirements to meet 250 V 5A contact rating.

1. Preferred shielding is braided screen.

mA INPUT · DC Version

Page 27 of the Siemens 200 user manual — Wiring
Page 27 · click to enlarge
Page 27

Transducers

Siemens 200 — Transducers diagram (page 27)
Fig. 4 · Transducers

Run the transducer cable in a grounded metal conduit, separate from other

  • Notes:
  • Do not use coaxial cable because of electrical noise interference
  • Do not connect the shield and white transducer wires together; wire to separate

terminals • Disregard older transducer manuals that recommend these practices

A 0.1 µF (100V or greater) capacitor is included with the MultiRanger for retrofitting old MultiRanger Plus installations. Please see MultiRanger 100/200 Installation (for retrofitting MultiRanger Plus Installations) on page 247.

Relays

Relay contacts are shown in the de-energized position. All relays are handled identically and can be configured as positive or negative logic using P118.

Siemens 200 — Relays diagram (page 27)
Fig. 5 · Relays

Power Failure Relays 1, 2, 4, and 5 are normally open and will fail in the normal state.

  • four Form A, NO relays(1,2,4,5)
  • two Form C, NO or NC relays (3,6)
  • 5A at 250Vac, noninductive

Relays 3 and 6 can be wired either normally open or normally closed, and will fail in their de- energized states.

Wiring

Page 28 of the Siemens 200 user manual — Wiring
Page 28 · click to enlarge
Page 28

Temperature Sensor

Accurate temperature readings are critical to accurate level measurements because the speed of sound changes, depending on air temperature, and all Siemens Milltronics Echomax and ST-H transducers have an internal temperature sensor.

If the following conditions apply, a separate TS-3 temperature sensor will ensure optimum accuracy:

  • the transducer is exposed to direct sunlight (or other radiant heat source)
  • the transducer face and monitored surface temperature differs
  • faster response to temperature changes is required

TEMPERATURE SENSOR

mA Input [MR 200 only]

For more information, consult the Transducer (P004) and mA Input Parameters (P250, P251, and P252) in the parameter reference section.

mA Output

For more information, consult the mA output parameters (P200 to P219) in the parameter reference section.

Wiring

Page 29 of the Siemens 200 user manual — Wiring
Page 29 · click to enlarge
Page 29

Level System Synchronization

When using multiple ultrasonic level monitors, be sure to run the transducer cables in separate grounded metal conduits.

When separate conduits are not possible, synchronize the level monitors so that no unit transmits while another is waiting for echo reception.

MultiRanger Other Siemens Milltronics Transceiver

Synchronizing with another MultiRanger 100/200, or other Siemens Milltron- ics instruments (DPL+, SPL, XPL+, LU01, LU02, LU10, LUC500, Hydro+, EnviroRanger, MiniRanger):

  • Mount the level monitors together in one cabinet
  • Use a common power (mains) supply and ground (earth) for all units
  • Interconnect the SYNC terminals of all level monitors
  • Set parameter P726 Level System Sync on page 190.
  • Contact Siemens Milltronics or your local distributor. Go to <a href="http://www.siemens.com/processautomation" rel="nofollow noopener" target="_blank">www.siemens.com/processautomation</a>

Power

Important!

Before applying power to the MultiRanger for the first time, ensure any connected alarm/control equipment is disabled until satisfactory system operation and performance is verified.

Notes for AC power connections

  • The equipment must be protected by a 15 A fuse, or circuit breaker in the

building installation. • A circuit breaker or switch in the building installation, marked as the disconnect

switch, must be in close proximity to the equipment and within easy reach of the operator.

Wiring

Page 30 of the Siemens 200 user manual — Wiring
Page 30 · click to enlarge
Page 30

connected to a reliable ground.

GND

L2/N

Digital Communications

Wiring the MultiRanger for communications allows it to be integrated into a full SCADA system or an industrial LAN.

The MultiRanger can also be directly connected to a computer running Dolphin Plus.

RS-232 Serial Connection

Siemens 200 — RS-232 Serial Connection diagram (page 30)
Fig. 6 · RS-232 Serial Connection

RS-232 RJ-11

RS-485 Connection (see below)

RS-485 Serial Connection

Siemens 200 — RS-485 Serial Connection diagram (page 30)
Fig. 7 · RS-485 Serial Connection

Wiring

Ground · Connector

Page 31 of the Siemens 200 user manual — Wiring
Page 31 · click to enlarge
Page 31

Discrete Inputs

Discrete inputs have a positive and negative terminal. Requires an external power supply.

Discrete Input (post.) 1

Discrete Input (pos.) 2

Common (neg.) for Discrete Input

Wiring

Page 32 of the Siemens 200 user manual — Indicator Functions
Page 32 · click to enlarge
Page 32
Siemens 200 — Operating the MultiRanger diagram (page 32)
Fig. 8 · Operating the MultiRanger

Operation

The MultiRanger has two modes of operation: RUN and PROGRAM.

In RUN mode, the MultiRanger detects material level and provides control functions. The MultiRanger automatically starts in RUN mode when power is applied.

System status is shown on the unit’s LCD, or on a remote communications terminal.

Display

Siemens 200 — Display diagram (page 32)
Fig. 9 · Display

Indicator Functions

Siemens 200 — Indicator Functions diagram (page 32)
Fig. 10 · Indicator Functions

RUN Mode PROGRAM Mode 1 index type (see below) index type (see next table) 2 index index 3 primary reading parameter value 4 units units 5 hi and hi hi alarm designation auxiliary function 6 level display n/a 7 filling display scroll access tag 8 emptying display scroll access tag 9 lo and lo lo alarm designation n/a 10 relay # programmed relay # programmed 11 relay # activated relay # activated 12 auxiliary reading parameter number 13 normal operation: n/a 14 failsafe operation: n/a

Page 33 of the Siemens 200 user manual — P
Page 33 · click to enlarge
Page 33

Icons indicating index type (Item 1) edited in PROGRAM mode:

Siemens 200 — Icons indicating index type (Item 1) edited in PROGRAM mode: diagram (page 33)
Fig. 11 · Icons indicating index type (Item 1) edited in PROGR…

Operation

Readings in RUN Mode

Change the displayed values with the keys on the hand programmer. All readings are shown in the Auxiliary field, except for the totalizer and P920.

Key Function P# Toggle Readings between percent and units:

P920

  • Level: 0 – 100%
  • Space or Distance: 1 100% – 0

Accumulated pump running hours2 for numbered pump.

P310

Hold number key for five seconds to display the number of accumulated pump starts2 for numbered pump.

P311

[MR 200 only] Eight-digit totalizer, uses index and reading areas, press again to toggle, P737 sets default. Used for OCM and Pumped Volume.

P322 P323 P920

[MR200 only] Head measurement P926

[MR 200 only] Instantaneous flow based on head (OCM) P925

mA Output value P203

Rate of level change P707

Failsafe Time Left (in %). When the Reading is updated, this value (Auxiliary Reading) resets to 100 and begins to decrease until the next valid measurement is made. If the Failsafe Time Left reaches 0, LOE flashes in the display. Hold for four seconds to show echo confidence P805

+ ### Display the value of the entered parameter which is global or indexed by transducer Auxiliary reading displays parameter specified in P731 P731

P

P

1. Distances less than 0.3 m (1 ft) from the transducer face cannot be measured reliably. Therefore, a 0% reading is not possible during Distance operation.
2. If the associated relay is programmed for pump control.
Show 4 more labels / short text on this page
+ · + · Temperature P664 · Distance P923
Page 34 of the Siemens 200 user manual — Operation
Page 34 · click to enlarge
Page 34

Status Parameters

Status parameters give the operating status of the MultiRanger. You can access parameters with the hand programmer (see page 32) or with Dolphin Plus (see page 27). Remote SCADA system access is also possible.

Operation

Parameter Values P203 mA Output Value 0 to 22 – Current mA output P254 [MR 200 only]

Scaled mA Input Value 0 to 9999 – Current mA input after scaling

P275 Scaled Discrete Input Value Shows current value of discrete input,

values vary by DI function P322 [MR 200 only]

LCD Total Low The last four digits of the totalizer

P323 [MR 200 only]

LCD Total High The first four digits of the totalizer

P341 Run Time The number of days the MultiRanger has been operating P342 Start Ups The number of times power has been cycled P664 Temperature Current temperature measured by transducer P707 Rate Value Current rate of material level change P708 [MR 200 only]

Volume Rate Display Current rate of material volume change

P729 Scan Time Seconds since last level scan P806 Echo Strength Strength of primary echo P920 Reading Measurement Current primary reading P921 Material Measurement Current level from P007–Span P922 Space Measurement Empty space above the material level P924 [MR 200 only]

Volume Measurement Current volume value, if programmed

P925 [MR 200 only]

Flow Measurement (OCM) Current flow value, if OCM programmed

P926 [MR 200 only]

Head Measurement (OCM) Current level, if OCM programmed

P927 Distance Measurement Distance from transducer face to material

Page 35 of the Siemens 200 user manual — Auxiliary Reading
Page 35 · click to enlarge
Page 35

Controlling the Display

RUN mode provides numerous parameters and variables that you can track on the display (see Display on page 22).

Operation

The LCD displays EEEE if a value is too long.

Adjusting the primary reading for four-digit LCD readout:

Parameter Action P060 Decimal Position Sets maximum number of decimals P061 Convert Reading Scales the reading to fit P062 Offset Reading Shifts the reading up or down by a fixed amount

Example

To reference the displayed level to sea level, enter the distance in Units (P005), between Empty (P006) and sea level. (Enter a negative value if Empty is below sea level.)

Siemens 200 — Example diagram (page 35)
Fig. 12 · Example

P062 is the distance between sea level and Empty.

Auxiliary Reading

The Auxiliary Reading area of the LCD displays parameter values while leaving the primary reading on screen.

Siemens 200 — Auxiliary Reading diagram (page 35)
Fig. 13 · Auxiliary Reading
Page 36 of the Siemens 200 user manual — Changing Number Scrolling Speed
Page 36 · click to enlarge
Page 36

Setting the Default Auxiliary Reading

To maintain a constant variable display in the auxiliary reading area, set the default.

Example:

Operation

To leave the level reading on the screen and view the echo confidence in the auxiliary reading field, set the following parameter:

Parameter Index Value Description

P730 G 805 Auxiliary field defaults to P805

Setting a Specific Auxiliary Reading

To display a second auxiliary reading, press in RUN mode.

P

ExampleTo set to display current temperature, go to P731:

P

Parameter Index Value Description

P731 G 912 Shows P912–Transducer Temperature

Multiple Readings [MR 200 only]

During differential or average operation (P001 = 4 /5), the display scrolls sequentially through Point Numbers 1, 2, and 3. Point 3 is the difference between (or average of) Points 1 and 2.

Changing Number Scrolling Speed

Parameter Index Value Description

P732 G 5 Hold each value for 5 seconds

See Parameter Indexing on page 37. All the instructions in the following procedures apply to the hand programmer and assume that the MultiRanger is activated.

Page 37 of the Siemens 200 user manual — Operation
Page 37 · click to enlarge
Page 37

PROGRAM Mode

The MultiRanger is programmed by setting its parameters to match your specific application. Most parameters are indexed, allowing you to set the parameter to specific conditions and to more than one input or output. When the MultiRanger is in PROGRAM mode, you can change these parameter values and set operating conditions.

Operation

Please refer to the Parameter Reference section on page 117 for a full listing and explanations of parameter values.

The MultiRanger’s primary programming is by the hand programmer. Other access is available through Dolphin Plus software (purchased separately).

Siemens 200 — Operation diagram (page 37)
Fig. 14 · Operation
  • DISPLAY
  • The display briefly reads ---- while the measurement reading is verified. Reading level and other data is displayed and programmed relays are operated.
  • Placing a programmed unit that is in normal operation into PROGRAM mode de-energizes all control relay outputs. Be sure to bypass the MultiRanger while programming it.
Siemens 200 — Operation diagram (page 37)
Fig. 15 · Operation

The hand programmer gives you direct access to the MultiRanger.

  • Notes:
  • The battery in the programmer is not replacable.
  • The hand programmer is ordered separately from Siemens Milltronics Infrared Port

For your convenience, the programmer has a magnetic mounting strip on the back. Keep programmer nearby for easy access.

Point the programmer at the IR port above the display and press the keys.

Unless otherwise noted, each valid key press should produce a change in the LCD. Verify when programming the unit.

Page 38 of the Siemens 200 user manual — Operation
Page 38 · click to enlarge
Page 38

Programmer Keys

Operation

Siemens 200 — Operation diagram (page 38)
Fig. 16 · Operation

Keys Programming Mode Run Mode 1 8-digit Totalizer (toggle) [MR 200 only] 2 Pump Running Time

3 Head [MR 200 only] 4 Flow based on Head [MR 200] 5 mA Output

Units or % Units or % (Program Mode) (Key 2) Next Display Field Pause Display Toggle

Page 39 of the Siemens 200 user manual — (compatible with product software versions 1.06 and earlier) 1
Page 39 · click to enlarge
Page 39

Dolphin Plus

(compatible with product software versions 1.06 and earlier) 1

Operation

Use Dolphin Plus software to configure, monitor, tune, and diagnose the MultiRanger from a PC or directly in the field with a laptop.

Dolphin Plus is easy to install and easy to use. Just load the software from the CD onto a desktop PC or Laptop and then set up or modify complete parameter configurations in a Windows®2environment.

After configuration, you can edit parameters, upload and download parameter sets to and from disk, and use parameter sets saved from other instruments. You can also work with echo profiles for fine tuning without the need for special instruments. Built-in Quick Start features and Help files guide you through the entire process.

Siemens 200 — (compatible with product software versions 1.06 and earlier) 1 diagram (page 39)
Fig. 17 · (compatible with product software versions 1.06 and…
1. See P900 for Software Revision Number. 2. Windows is a registered trademark of Microsoft Corporation.
Page 40 of the Siemens 200 user manual — Operation
Page 40 · click to enlarge
Page 40

Dolphin Plus Toolbar Buttons

The toolbar buttons provide quick access to Dolphin Plus features.

Operation

Siemens 200 — Operation diagram (page 40)
Fig. 18 · Operation

open the vertical echo profile and tank mimic window

Page 41 of the Siemens 200 user manual — Device Description
Page 41 · click to enlarge
Page 41

SIMATIC Process Device Manager (PDM)

(compatible with product software versions 1.07 and later) 1

Operation

SIMATIC PDM is a software package for parameterizing, commissioning, diagnosing and maintaining process devices. For the MultiRanger 100/200, SIMATIC PDM connects directly to the device using Modbus over Port 1 or Port 2. The MultiRanger 100/200 comes with Port 1 set for communications to SIMATIC PDM.

SIMATIC PDM contains a simple process monitor of the process values, alarms and status signals of the device. Using SIMATIC PDM you can

  • display,
  • set,
  • change,
  • compare,
  • check the plausibility of,
  • manage, and
  • simulate

process device data.

More information about SIMATIC PDM is available at www.siemens.com/processinstrumentation go to Products & Solutions > Products & Systems > Communication and Software > Process Device Manager. Please consult the operating instructions or online help for details on using SIMATIC PDM. An Application Guide on using MultiRanger 100/200 with PDM and Modbus is available on our website: www.siemens.com/processautomation

Device Description

To use Process Device Manager (PDM) with MultiRanger 100/200, you need the Device Description for MultiRanger 100/200, which will be included with new versions of PDM. You can locate the Device Description in Device Catalog, under Sensors/Level/ Echo/ Siemens Milltronics. If you do not see MultiRanger 100/200 under Siemens Milltronics, you can download it from our website: www.siemens.com/processautomation Go to the MultiRanger product page and click Downloads. After downloading the DD file, you need to execute DeviceInstall.

1. See P900 for Software Revision Number.
Page 42 of the Siemens 200 user manual — Helpful Hints
Page 42 · click to enlarge
Page 42

Activating the MultiRanger

All the instructions in the following procedures apply to the hand programmer and assume that the MultiRanger is activated.

Operation

1. Power the MultiRanger.
2. Point the programmer at the unit and press PROGRAM . 3. Press DISPLAY .
Siemens 200 — Operation diagram (page 42)
Fig. 19 · Operation
  • preset to display distance from the face of the transducer to the material
  • transducer selection is preset for the XPS-10
  • empty distance is preset to 5 m
  • Dual Point Model
  • starts in an OFF state and does not take level measurements
  • to set up measurement, the quick start parameters must be configured
  • See Quick Start parameters on page 119

Changing Parameters

Siemens 200 — Changing Parameters diagram (page 42)
Fig. 20 · Changing Parameters
1. Starting in RUN mode, press PROGRAM and then press DISPLAY to put the unit into PROGRAM mode. 2. Press DISPLAY to select the Parameter Number field. 3. Enter the Parameter Number (e.g. 110). After the third digit is entered, the parameter

value is shown. 4. Enter the new value, and press ENTER . The MultiRanger interprets the value, either accepting or replacing it with a valid value.

Helpful Hints

  • For parameters P001 to P009, press a single digit (1–9) and then press DISPLAY to show that parameter.
  • The ? icon indicates that the MultiRanger has accepted the value but that it conflicts with other values entered. Double-check your programming.
  • By default, the SCROLL arrows show only the Quick Start parameters and any that have been changed.
  • P733 sets all parameters to be scroll-accessed.
Page 43 of the Siemens 200 user manual — Global Values
Page 43 · click to enlarge
Page 43

Security

The Lock parameter P000 secures the MultiRanger against parameter changes via the handheld programmer. The unit can still be put into PROGRAM mode when locked, and parameter values can be viewed, but no parameter values can be changed.

Operation

When P000 is set to 1954, programming is enabled. To disable programming, enter another value.

P000 (1954) is a fixed value password. Therefore, you should use other means to secure the MultiRanger if security is a concern.

Simulation

P000 Lock also controls how simulations affect control relays. By default, control relays are unaffected by simulation levels. But if P000 is set to –1, they react to the simulated level. See Parameters P925–P927 on page 220 for running a simulation.

Using Units or Percent (%)

Many parameters can be viewed either in measurement units (P005) or as a percentage. View the parameter and then press MODE to toggle between units and percentage. The LCD shows the selected measurement type, either units (m, ft) or percentage (%).

MR 200 only:

Percentage is also available when showing flow and volume with 100%, based on the parameter that defines the maximum.

Measurement Maximum Volume P051 Flow P604

Parameters Types

View Only Parameters

Parameter values indicating status only. They cannot be altered.

Global Values

Parameter values common to all inputs and outputs on the MultiRanger.

When a global parameter is accessed, the index display automatically disappears. When a non-global parameter is accessed, the index display reappears showing the last index number.

Page 44 of the Siemens 200 user manual — Display Readout
Page 44 · click to enlarge
Page 44

Default Values

Parameter default values are indicated with an * in the parameter tables.

Operation

1954 * OFF: programming permitted -1 Simulation Controls (relays energize based on simulated level) other ON: Lock activated and programming not permitted via the handheld programmer

The asterix identifies 1954 as the default value.

Parameter Reset

Returning a parameter to factory default.

1. Display the appropriate parameter number. 2. Display the appropriate index value (if required). 3. Press CLEAR .
4. Press ENTER .

Master Reset (P999)

Returns all parameters to original values.

Use Conditions:

  • before initial system installation
  • following a software upgrade If complete reprogramming is required, use Dolphin Plus to store and retrieve parameters.

When the dual point option is enabled, P999 is indexed by transducer. Use index 00 to reset the entire MultiRanger.

Display Readout

The following readouts are shown when the MultiRanger cannot display a number.

Display Definition Parameter has not been set

All values not same when viewing index 0

Value too large for four-digit display

P000 Lock · Primary Index Global · Value

Page 45 of the Siemens 200 user manual — Operation
Page 45 · click to enlarge
Page 45

Changing Parameters(Dolphin Plus)

The other method for changing parameter values is with Dolphin Plus software. It lets you access the MultiRanger from a PC or on site with a laptop and change MultiRanger parameters.

Operation

Most examples in this manual use the icons from the hand programmer but nearly all functions are also available through Dolphin Plus.

Siemens 200 — Operation diagram (page 45)
Fig. 21 · Operation
Page 46 of the Siemens 200 user manual — Accessing a Parameter Index
Page 46 · click to enlarge
Page 46

Parameter Indexing

Parameters are indexed when they apply to more than one input or output. The index value defines the input/output for that parameter. Indexed parameters contain a value for each index, even if that index is not used.

Operation

MultiRanger Display

The index number and the index values are displayed above the parameter indicator on the LCD.

Index Value Index Number

Siemens 200 — Operation diagram (page 46)
Fig. 22 · Operation
  • Notes
  • Transducers are always indexed when the dual point option is enabled.
  • An indexed transducer is commonly referred to as a Point (short for ’Measurement Point’). Point Number refers to indexed transducers.
  • To set all indexed values for a parameter to the same value, use index 0.
  • MR 200 only: Transducer parameters are indexed only if Operation (P001) is set to Difference (value=4) or Average (value=5) on a single point MultiRanger.

Accessing a Parameter Index

1. Press DISPLAY once to clear current parameter field. 2. Enter the new parameter number.
3. Press DISPLAY twice. 4. Press the number of the required index. Or press ARROW keys to scroll through the available values.
Page 47 of the Siemens 200 user manual — Accessing a Secondary Index
Page 47 · click to enlarge
Page 47

Primary and Secondary Indexes

Primary Index: relates to direct input or output and can refer to relays, communications ports, and other parameters. In parameters that allow secondary indexes, the primary index is often referred to as a point.

Operation

Secondary Index: relates to previously indexed parameters where the parameter requires a second index, permitting multiple values on an indexed input or output.

Primary Index

Example SettingP111[3] = 52

P111

3 4 5 6 2 1

  • P111 sets the Relay Control Function
  • P111(3) = 52 sets Relay # 3 to a value of 52 .

Secondary Index

Parameters with a secondary index permit multiple values for a primary index (point). For example, a volume calculation based on vessel characterization breakpoints requires a distinct set of breakpoints for each measured point.

Thus the primary index refers to the measurement point, and each secondary index refers to a characterization breakpoint value.

Accessing a Secondary Index

1. Press MODE and then press DISPLAY to activate secondary index. The icon appears under the index field. 2. Enter the secondary index, and then enter the values to set the secondary index.
Page 48 of the Siemens 200 user manual — Single Point Models
Page 48 · click to enlarge
Page 48

Example [MR 200 only] P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpoint) for universal volume calculation. The illustration indicates how you can set secondary indexes to specific functions.

Operation

Siemens 200 — Operation diagram (page 48)
Fig. 23 · Operation

A B C P054 [1,6] = 2m P054 [1,3] = 1.5m P054 [1,1] = .75m P054 [2,6] = 8m P054 [2,3] = 5.5m P054 [2,1] = 2.75m

  • P054 [1,1] = .75m sets breakpoint 1 on transducer 1 to .75m.
  • P054 [2,1] = 8m sets breakpoint 1 on transducer 2 to 2.75m. Starting Measurement

The MultiRanger startup varies between single and dual point models.

Siemens 200 — Operation diagram (page 48)
Fig. 24 · Operation

Note: The number of points is an order option and is set by the factory. On a single point model, the index for P001 is global (G). On a dual point model the index for P001 is 1 or 2. To check the model in use, enter P001 on handheld programmer. For a single point device, parameter P001 will not show an entry for index number on the LCD. (See MultiRanger Display on page 36 for location of index number on the LCD.) Parameter P001 will display an index number for a dual point model.

Single Point Models

The MultiRanger starts in DISTANCE mode with the transducer preset for the XPS-10 and an empty distance of 5 meters. Change the following parameters to reflect your application parameters.

Siemens 200 — Single Point Models diagram (page 48)
Fig. 25 · Single Point Models

Parameter Index Value Description P001 G 1 Operation = level P002 G 1 Material = liquid P003 G 2 Maximum Process Speed = medium P004 G 104 Transducer = XPS-15 P005 G 1 Units = meters P006 G 12 Empty = 12m P007 G 10 Span = 10m

Page 49 of the Siemens 200 user manual — Parameter Index Value Description
Page 49 · click to enlarge
Page 49

Average or Differential [MR 200 only]

For differential or average operation with a single-point MultiRanger, set P001 to 4 (differential) or 5 (average) and connect two transducers of the same type. All of the relevant parameters then become indexed by the correct transducer:

Operation

Ring indicates relay is configured

Dot indicates relay is energized/de- energized

Index Description 2 indexed by Transducer One or Two 3 indexed by level measurement 1 = Transducer One 2 = Transducer Two 3 = Calculated Level (average or difference)

Dual Point Models

The MultiRanger starts in an OFF state and does not take level measurements. For measurement setup, configure these basic parameters:

If the application uses two measurement points, provide the basic information for each measurement point separately:

Parameter Index Value Description

P001 1 1 Operation = level

2 3 Operation = distance

P002 1 1 Material = Liquid 2 1

P003 1 2 Max. Process Speed = medium 2 3 Max. Process Speed = fast

P004 1 104 Transducer = XPS - 15 2 102 Transducer = XPS - 10 P005 G 1 Units = meters

P006 1 12 Empty = 12m 2 4 Empty = 4m

P007 1 11 Span = 11m 2 3.5 Span = 3.5m

Relay Number

Page 50 of the Siemens 200 user manual — Failsafe
Page 50 · click to enlarge
Page 50

Average or Differential [MR 200 only]

For differential or average operation dual-point MultiRanger, set P001 to 4 (differential) or 5 (average) and connect two transducers of the same type.

Operation

All the relevant parameters are then indexed by the correct number:

Index Description 2 indexed by Transducer One or Two 3 indexed by level measurement 1 = Transducer One 2 = Transducer Two 3 = Calculated Level (average or difference)

Measurement Conditions

The following information will help you configure your MultiRanger for optimal performance and reliability.

Response Rate

The response rate of the device influences the measurement reliability. Use the slowest rate possible with the application requirements.

The response rate is also important to functions connected to the filling or emptying indicators.

Dimensions [MR 200 only]

The dimensions of the vessel, wet well, or reservoir (except empty and span) are only important if you require volume.

Volume is required to report the level value in terms of volume. The pumped volume function can also report pumped volume or pump efficiencies.

Failsafe

The failsafe parameters ensure that the devices controlled by the MultiRanger default to an appropriate state when a valid level reading is not available.

  • P070 – Failsafe Timer activates if an error condition is detected. Upon expiration of the timer, relay status defaults to values based on P071.
  • P071 – Failsafe Material Level determines the level reading if the Failsafe Timer expires and the unit is still in an error condition.
  • P129 – Relay Failsafe controls the reaction of each relay. See Relay Failsafe on page 45 for more information. If Failsafe Operation activates frequently, see the Troubleshooting Appendix on page 231.
Page 51 of the Siemens 200 user manual — Rate of Change [MR 200]
Page 51 · click to enlarge
Page 51

Relays

Relays are the primary controls of external devices such as pumps or alarms.

The MultiRanger comes with extensive control and alarm functions.

General Introduction

Depending on the model, up to six onboard multi-purpose relays are provided on the MultiRanger. Each relay may be independently assigned to one function and has a corresponding status icon on the LCD.

The relay functions fall under three modes of operation:

Mode Function alarm alarm ON = LCD Icon ON = relay coil de-energized pump pump ON = LCD Icon ON = relay coil energized miscellaneous contact closed = LCD Icon ON = relay coil energized

Relays

Relay Function

Note: The MultiRanger 100 or 200 can be programmed with relays. The number of relays installed depends on the model. To determine the number of available relays that can be utilized in your MultiRanger 100 or 200, open the lid and count the large white relays to the left of the display. It is important to count the number of on-board relays as the software will allow programming of up to six relays whether they are installed or not.

Alarm

Level

In high alarm, the function goes on when the level rises to the ON setpoint and goes off when the level lowers to the OFF setpoint. In low alarm, the function goes on when the level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint.

In Bounds [MR 200]

The relay will be in alarm if the level is inside the zone between the setpoints.

Out of Bounds [MR 200]

The relay will be in alarm if the level is outside the zone between the setpoints.

Rate of Change [MR 200]

In filling alarm, the function goes on when the rate of filling increases to the ON setpoint and goes off when the rate of filling drops to the OFF setpoint. In emptying alarm, the function goes on when the rate of emptying increases to the ON setpoint and goes OFF when the rate of emptying drops to the OFF setpoint. For emptying alarm, the setpoints must be entered as negative values.

Page 52 of the Siemens 200 user manual — Setpoint - ON / OFF
Page 52 · click to enlarge
Page 52

Temperature [MR 200]

In high alarm, the function goes on when the temperature rises to the ON setpoint and goes off when the temperature lowers to the OFF setpoint. In low alarm, the function goes on when the temperature lowers to the ON setpoint and goes off when the temperature rises to the OFF setpoint.

Loss of Echo

The function goes on when the fail-safe timer expires. The function goes OFF when a valid echo is received (fail-safe timer is reset).

Pump

Level

Relays

In pump down, the function goes on when the level rises to the ON setpoint and goes off when the level lowers to the OFF setpoint. In pump up, the function goes on when the level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint.

Miscellaneous

Totalizer and Samplers [MR 200]

Refer to Totalizing Pumped Volume on page 65. Relays are normally de-energized, contact closure is approximately 200 mSec duration.

Setpoint - ON / OFF

If the ON setpoint is higher than the OFF setpoint, the relay operates as:

  • high alarm
  • pump down control

If the ON setpoint is lower than the OFF setpoint, the relay operates as:

  • low alarm
  • pump up control

The ON and OFF setpoints can not be the same on an individual relay but may be common to other relays. The dead band or hysteresis is the difference between the ON and OFF setpoints. For in and out of bounds level alarms, the hysteresis is set at ± 2 % of span from either boundary.

Page 53 of the Siemens 200 user manual — P111–Alarm Functions
Page 53 · click to enlarge
Page 53

Relay Status – Non Run Modes

When the fail-safe timer expires, pump control relays respond as previously described. However, alarm relays will respond in the following manner:

Fail-Safe Mode Relay Status High Alarm Low Alarm Fail-Safe High ON OFF Fail-Safe Low OFF ON Fail- Safe Hold HOLD HOLD

Upon entering the program mode, all pump control relays will be turned OFF. Alarm relays will hold their prior status.

  • Cautions:
  • If the relay status can affect plant operation or personnel safety, it is advisable to override the relay functions or disconnect the relay wiring during calibration or simulation.
  • Keep power disconnected at main breaker when MultiRanger cover is opened.

Relays

Relay States

The relays on the MultiRanger are completely programmable, allowing for any control scheme.

Relay Types Relay 1,2,4,5 – NO (Form A) Relay 3,6 – NO / NC (Form C)

Relay Related Parameters

Some parameters affect how relays react during normal conditions:

P100–Preset Applications [MR 200 only]

Sets the MultiRanger to a preset application. These preset applications quickly set up the MultiRanger with a minimum number of parameters.

P111–Relay Control Function

Sets the default state differently, depending on whether the relay is programmed as an alarm or a control.

P111–Alarm Functions

The alarm function de-energizes the relay coils. During normal operation (no alarms), the relay coils are energized.

Page 54 of the Siemens 200 user manual — Relay Setpoints and Functionality
Page 54 · click to enlarge
Page 54

P111–Control Functions

The control function energizes the relay coils. When the instrument is at rest (no controls operating) the relay coils are de- energized.

P112–Relay ON Setpoint

Sets the process point at which the relay is tripped.

P113–Relay OFF Setpoint

Sets the process point at which the relay is reset.

P118–Relay Output Logic

Affects relay reaction. Reverses the logic (normally-open to normally-closed or vice versa).

Relays

P129–Relay Failsafe

Changes how individual relays react to a failsafe condition on the instrument.

Relay Wiring Test

P119–Relay Logic Test

Checks the application wiring by forcing a relay control function, such as a level alarm or pump control setpoint. Ensure all the relay programming and wiring works properly.

Please verify that ON and OFF respond correctly. Use P119 as a final test once all of the relay programming is done.

Relay Activation

The flexibility of the relay functions ensures that the MultiRanger can support relay wiring for different systems and applications. Use the following as a guide to the most common parameters.

Relay Setpoints and Functionality

[MR 100]: When a setpoint is reached, the corresponding action is taken. The setpoint can be an ON or OFF setpoint related to a process variable.

[MR 200]: The setpoint can be an ON or OFF setpoint related to a process variable, or a timed setpoint based on interval and duration.

Page 55 of the Siemens 200 user manual — Relays
Page 55 · click to enlarge
Page 55

[MR 100]: Functions affected by setpoint are configured by parameters that determine the application requirements such as timing. P111 Pump and Control functions (see page 134) sets the functions requirements.

[MR 200]: Functions affected by setpoint are configured by parameters that determine the application requirements such as timing. P111 Pump and Control functions (see page 134 sets the function requirements. Other function parameters:

  • P132–Pump Start Delay
  • P133–Pump Power Resumption Delay
  • P645–Relay Duration

Relay Logic is Modified

Normal operating conditions means that alarms are off and pumps are on. This can be reversed using P118–Relay Output Logic.

Relays

Relay Failsafe

P129–Relay Failsafe

Adjusts how individual relays react to a failsafe condition. Relays can be set to:

  • OFF Control is by P071–Failsafe Material Level
  • HOLd Keeps the relay in the current state
  • dE De-energizes the relay (default for pump controls)
  • En Energizes the relay
Page 56 of the Siemens 200 user manual — Relays
Page 56 · click to enlarge
Page 56

Preset Applications

Preset applications set up the relay parameters to predetermined values shown below:

Value # Parameters Affected Off 0 All relays set to OFF Wet Well 1

Pump down with the following settings:

Parameter Relay # 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 70% 80% 90% 10% – – P113 20% 20% 85% 15% – – Wet Well 2

Pump down with the following level and rate settings:

Parameter Relay # 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 70% 80% 90% 10% – – P113 20% 20% 85% 15% – – P121 1 P121 sets the pump relays to accept control by rate of level change once the first ON setpoint is reached. Because the pumps are started by rate, you must change P703 to desired empty rate. Reservoir 1

Relays

Pump up with the following level settings:

Parameter Relay # 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 30% 20% 90% 10% – – P113 80% 80% 85% 15% – – Reservoir 2

Pump up with the following level and rate settings:

Parameter Relay # 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 20% 20% 90% 10% – – P113 80% 80% 85% 15% – – P121 1 P121 sets the pump relays to accept control by rate of level change once the first ON setpoint is reached. Because the pumps are started by rate you must change P702 to desired fill rate. Screen

Differential control of a screen or rake:

Parameter Relay # 1 2 3 4 5 6 P110 3 1 2 3 0 0 P111 50 1(H) 1(L) 1(H) – – P112 80% 90% 10% 90% – – P113 20% 85% 15% 10% – – Alarms

General alarms at four setpoints:

Parameter Relay # 1 2 3 4 5 6 P111 1(H) 1(L) 1(HH) 1(LL) 0 0 P112 80% 20% 90% 10% – – P113 75% 25% 85% 15% – –

Page 57 of the Siemens 200 user manual — P066: Override Time Delay
Page 57 · click to enlarge
Page 57

Backup Level Override

Backup level override provides the option of overriding the ultrasonic input with another contacting point level device, for example, the Pointek CLS200. The ultrasonic reading is fixed at the programmed switch level until the discrete input is released and the ultrasonic device makes its decisions based on the override value.

Backup Level Override Parameters

P064: Reading Override Enable

Sets the discrete input as the source of a level reading override.

P065: Reading Override Value

Substitutes value for current reading when the discrete input (P064) is enabled. Value is added in current units and is valid only for the following:

  • level
  • space
  • distance
  • difference
  • average modes of operation
  • head level in OCM mode

Backup Level Override

Example:

A high level backup switch is connected to Digital Input Two in the same application as Transducer One at level value 4.3 m.

Parameter Index Value P064 1 2 P064 2 0 P065 1 4.3 P065 2 –

When the level rises to 4.3 m and the switch is activated, the reading is forced to 4.3 m where it stays until the switch is de-activated.

P066: Override Time Delay

Sets the time (in seconds) used to calm the override condition input.

Settings

Page 58 of the Siemens 200 user manual — Discrete Inputs
Page 58 · click to enlarge
Page 58

Discrete Inputs

Wiring the Discrete Inputs

Normal state is standard operation, with the MultiRanger sensing the material level and controlling the pumps.

The discrete input contacts are either normally-open or normally-closed when the system state is normal.

Example:

Normal state for a backup high level switch is open, and the contacts on the discrete input are wired as normally-open.

See Discrete Inputs on page 21 for complete details on wiring the discrete inputs. To override a level using a discrete input, see Backup Level Override on page 47.

Programming the Discrete Input Logic

The P270 series of parameters permits control over the discrete input.

DI State P270 Setting Normally Open Normally Closed

P270 = 2 P270 = 3

The current value of the discrete input is reported in P275:

P275 Setting MultiRanger State 0 1 Normal State Exception State

Discrete Inputs

Page 59 of the Siemens 200 user manual — mA I/O
Page 59 · click to enlarge
Page 59

mA I/O

To integrate the MultiRanger with other equipment, use the mA input and outputs.

The mA input can be used as a level measurement or can be passed on to a SCADA system.

mA Input [MR 200]

Level Reading Parameters

Parameter Index Value Description P004 1 250 Transducer = mA input 1 P250 1 2 Scale = 4 to 20 mA P251 1 0 4 mA = 0% of span P252 1 100 20 mA = 100% of span P253 1 0 Do not damp the input signal

To pass the mA input on to a SCADA system, read the value from the appropriate communication registers. For more information, go to the MultiRanger Communications section on page 89.

mA Output

The MultiRanger has two mA outputs, used to send measurements to other devices.

Configuring the mA output to send a 4 to 20 mA signal scaled from 10% to 90% of span of the second transducer:

Parameter Index Value Description P200 1 2 set to 4 to 20 range P201 1 1 send mA proportional to level reading P202 1 2 base mA on level point 2 P210 1 10 set 4 mA at 10% of span1

P211 1 90 set 20 mA at 90% of span2

P219 1 0 set failsafe action as 0 mA

1. If the level reading drops below 10% of span, the mA output drops below 4 mA.
2. If the level reading rises above 90% of span, the mA output rises above 20 mA.

mA I/O

Page 60 of the Siemens 200 user manual — mA LI/O
Page 60 · click to enlarge
Page 60

Calibrating 4 mA Output

1. Connect the mA receiving device to the MultiRanger. 2. Put the MultiRanger into PROGRAM mode. 3. Set P911–mA Output Value to 4.0. 4. View the mA level on the receiving device. 5. If there is a discrepancy,

a.Attach ammeter to MultiRanger mA output. b.Access P214, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and

ENTER . The ammeter should show a value near 4 mA. c.Enter the exact value displayed on the ammeter into P214 (Index 1 or 2). d.The ammeter should then read exactly 4.00 mA. The unit is now calibrated for 4 mA for the receiving device.

Calibrating 20 mA Output

1. Connect the mA receiving device to the MultiRanger. 2. Put the MultiRanger into PROGRAM mode. 3. Set P911–mA Output Value to 20.0. 4. View the mA level on the receiving device. 5. If there is a discrepancy,

a.Attach ammeter to MultiRanger mA output. b.Access P215, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and

ENTER . The ammeter should show a value near 20 mA. c.Enter the exact value displayed on the ammeter into P215 (Index 1 or 2). d.The ammeter should then read exactly 20.00 mA. The unit is now calibrated for 20 mA for the receiving device.

Verifying the mA Range

Checks that the external device can track the entire 4 to 20 mA range sent by the MultiRanger.

1. Use P920 to put the MultiRanger into Simulation mode (see page 85). 2. Run the simulation through one complete fill / empty cycle. 3. View P911–mA Output Value to verify that it tracks to the simulation. 4. View the mA value reported on the external equipment to verify that it also tracks to

the simulation.

mA LI/O

Page 61 of the Siemens 200 user manual — Tank Shape and Dimensions
Page 61 · click to enlarge
Page 61
Siemens 200 — Volume [MR 200] diagram (page 61)
Fig. 26 · Volume [MR 200]

Volume is a feature of the MultiRanger 200 only. Volume is used in two situations:

Volume

1. Calculate and display volume instead of level. For programming all setpoint parameters in terms of volume units rather than level units. 2. Calculate pumped volume to accomplish the following:
  • Totalize the volume of material that is pumped out of the wet well
  • Set an alarm on pump efficiency

If you require this functionality, please contact your local Siemens Milltronics representative at www.siemens.com/processautomation.

Readings

When using volume, readings are given in arbitrary units specified in P051.

The default is 100, which gives a reading in percent of total. Use whatever units you want here. If the value is too large for the four-digit LCD, use a larger unit.

Example

If a wet well has a maximum capacity of 250,000 liters, use the value 250.0 for P051 and set the reading in 1000s of liters.

Tank Shape and Dimensions

There are many common tank shapes to select from. (See P050. If possible, use one of these.) Each tank shape uses the Empty distance (P006) in its calculations of volume.

Some tank shapes also require extra dimensions to calculate the volumes. Do not estimate these values. They must be correct to ensure the accuracy of your volume calculations.

Siemens 200 — Tank Shape and Dimensions diagram (page 61)
Fig. 27 · Tank Shape and Dimensions

To configure volume for a tank with a half-sphere bottom, set the following:

Parameter Index Value Description P050 1 4 selects the correct tank shape P051 1 100 sets maximum volume at 100 (percent) P052 1 1.3 sets A to 1.3m

  • Notes:
  • The default reading changes to a range from 0 to 100 (the value in P051)
  • Empty (P006) is still measured to the bottom of the tank, not the top of A .
Page 62 of the Siemens 200 user manual — MAX VOLUME P051
Page 62 · click to enlarge
Page 62

Characterization Chart [MR 200]

If you cannot use a pre-defined tank, then use one of the universal tank shapes and program the characterization curve.

Volume

1. Plot a volume to height chart. Usually a tank supplier will provide this chart. However, if you have a custom-built wet well then you will need access to complete drawings of the well or accurate measurements. 2. Enter the curve values from this chart into P054 and P055. 3. Ensure extra points are added around sharp transitions in the wet well volume (e.g:

as steps in the well wall).

Example Chart

MAX VOLUME P051

VOLUME (P055)

FLOW

LEVEL (P054) 0,0

Page 63 of the Siemens 200 user manual — P055 1
Page 63 · click to enlarge
Page 63

MultiRanger 200 only

Parameter Transducer Index Value Description

Volume

2 0.8 3 2.0 4 3.5 5 4.1 6 4.7 7 5.1 8 5.2 9 5.3 10 5.4 11 5.5 12 5.6 13 6.0 14 7.2 15 9.0

Determines the Level breakpoints at which the volumes are known.

P054 1

2 2.1 3 4.0 4 5.6 5 5.9 6 6.3 7 6.7 8 7.1 9 7.8 10 8.2 11 8.8 12 9.2 13 10.9 14 13.0 15 15.0

Determines the volumes which correspond to the level breakpoints. The universal calculations interpret between the breakpoints to produce an accurate model of the volume at all level readings.

P055 1

Settings P050 = 9 for linear approximation P050 = 10 for curved approximation

Linear approximation uses a linear algorithm; curved approximation uses a cubic spline algorithm.

Page 64 of the Siemens 200 user manual — Parameter Index 1
Page 64 · click to enlarge
Page 64

Alarms

Level

The level alarm is the most common. Use this alarm to warn you when your process is in danger of being upset due to high or low levels.

Generally, the four alarms used are Hi, Hi Hi, Lo, and Lo Lo.

Set the Common Parameters

Alarms

P006

P007

Prerequisite: You must know the details of your application and substitute the values for the sample values provided. If you are bench testing the unit, then set your test values to be the same as the sample values.

Parameter Index 1

Value Description P001 G 1 Operation = level P002 G 1 Material = liquid P003 G 2 Maximum Process Speed = medium P004 G 102 Transducer = XPS-10 P005 G 1 Units = meters P006 G 1.8 Empty = 1.8m P007 G 1.4 Span = 1.4m

1. This example assumes a base, single measurement unit. If your unit has optional dual point software installed then some parameters are indexed by two.
Show 4 more labels / short text on this page
hi hi · hi · lo · lo lo
Page 65 of the Siemens 200 user manual — P112 5 -10% P113 5 -5%
Page 65 · click to enlarge
Page 65

Setting Simple Level Alarms

To set Relay Five to a standard level alarm (Hi Hi, Hi, Lo, Lo Lo) do the following:

  • Parameter Index Value Description P110 5 1
  • Set P110, indexed to relay, to the value 1 for Transducer One P111 5 1
  • Set P111, indexed to relay, to the value 1 for level alarm
  • Press UNIT to display the Auxiliary Function symbol.
  • Press ARROW keys as required to scroll to the alarm designation (L, LL, H, or HH).
  • Press ENTER to enter the value. P112 5 1.2m
  • Set the ON setpoint P113 5 1.15m
  • Set the OFF setpoint

Alarms

Available designations:

Alarm Designation Hi Hi HH Hi H Lo L Lo Lo LL

Rate [MR 200]

Rate alarms can trigger an alarm if the vessel is filling/emptying too quickly.

Setting a Filling Rate Alarm

Parameter Index Value Description P111 5 4 These settings trip the alarm when the reservoir is filling faster than 1 m per minute and reset it at 0.9m per minute. P112 5 1m P113 5 0.9m

Setting an Emptying Rate Alarm

Parameter Index Value Description P111 5 4 These settings trip the alarm when the reservoir is emptying faster than 10% of span per minute and reset the alarm when emptying falls to 5%.

P112 5 -10% P113 5 -5%

Page 66 of the Siemens 200 user manual — Temperature [MR 200]
Page 66 · click to enlarge
Page 66

In Bounds/ Out of Bounds Range [MR 200]

Use the bounded range alarms to detect when the level is inside or outside of the range. By using a bounded range alarm, you can effectively put two level alarms (high and low) on one relay.

Setting an Out of Bounds Alarm

Parameter Index Value P111 5 3 P112 5 1.3 P113 5 0.3 P116 5 0.05

Results:

Alarms

  • Trips alarm above 1.35 m and below 0.25m
  • Resets alarm below 1.25 m and above 0.35m

Setting an In Bounds Alarm

Parameter Index Value P111 5 2 P112 5 1.3 P113 5 0.3 P116 5 0.05

Results:

  • Trips alarm below 1.25 m and above 0.35 m
  • Resets alarm above 1.35 m and below 0.25 m

Cable Fault

Activates an alarm if transducer cable circuit enters a shorted or opened state.

Parameter Index Value Description P111 5 7 Alarm on transducer cable fault P110 5 1 Alarm on Transducer One

Temperature [MR 200]

Use the temperature alarm to activate an alarm when the temperature reaches the ON setpoint (P112). This alarm uses the same setpoint parameters as the level alarms (P112 and P113).

Page 67 of the Siemens 200 user manual — Alarms
Page 67 · click to enlarge
Page 67

With P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112 < P113).

This shows a high alarm:

Parameter Index Value Description P111 5 5 Alarm on temperature P112 5 45 ON setpoint at 45 °C P113 5 43 OFF setpoint at 43 °C P110 5 1 Take the temperature reading from Transducer One

The temperature source can be the temperature sensor built into the transducer or an external TS-3, as set by P660.

Alarms

Loss of Echo (LOE)

Parameter Index Value Description P110 5 1 Alarm on LOE for Transducer One P111 5 6 Alarm on LOE P070 G 0.5 Trip alarm when 0.5 minutes (30 seconds) pass without detecting a valid echo.

Page 68 of the Siemens 200 user manual — Pump Control
Page 68 · click to enlarge
Page 68

Pump Control

Setting a Pump Down Group

Example: Sewage Wet Well

Setting a group of three pumps to pump down a wet well.

Siemens 200 — Example: Sewage Wet Well diagram (page 68)
Fig. 28 · Example: Sewage Wet Well

Pump Control

Set the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values.

Siemens 200 — Pump Control diagram (page 68)
Fig. 29 · Pump Control

Value Description P001 G 1 Operation = level P002 G 1 Material = liquid P003 G 2 Maximum Process Speed = medium P004 G 102 Transducer = XPS-10 P005 G 1 Units = meters P006 G 1.8 Empty = 1.8m P007 G 1.4 Span = 1.4m

1. Example assumes a single measurement unit. If your MultiRanger has dual point software installed then some parameters are indexed by two.
Page 69 of the Siemens 200 user manual — Pump Control
Page 69 · click to enlarge
Page 69

Set Relays to ALTERNATE DUTY ASSIST

Siemens 200 — Set Relays to ALTERNATE DUTY ASSIST diagram (page 69)
Fig. 30 · Set Relays to ALTERNATE DUTY ASSIST

Parameter Index Value Description P111 1 52 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY ASSIST. P111 2 52 P111 3 52

Set the ON Setpoints

Parameter Index Value Description P112 1 1.0m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.

P112 2 1.1m P112 3 1.2m

Set the OFF Setpoints

Parameter Index Value Description P113 0 0.5m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

Setting a Pump Up (Reservoir) Group

Pump Control

Sets a group of three pumps to pump up a reservoir.

Siemens 200 — Pump Control diagram (page 69)
Fig. 31 · Pump Control
Page 70 of the Siemens 200 user manual — Set the Relay OFF Setpoints
Page 70 · click to enlarge
Page 70

Set the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values.

Parameter Index 1

Value Description P001 G 1 Operation = level P002 G 1 Material = liquid P003 G 2 Maximum Process Speed = medium P004 G 102 Transducer = XPS-10 P005 G 1 Units = meters P006 G 1.8 Empty = 1.8m P007 G 1.4 Span = 1.4m

1. Example assumes a single measurement unit. If your MultiRanger has dual point software installed, some parameters are indexed by two.

Set Relays to ALTERNATE DUTY ASSIST

Parameter Index Value Description P111 1 52 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY ASSIST. P111 2 52 P111 3 52

Pump Control

Set the Relay ON Setpoints

Parameter Index Value Description P112 1 0.4m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.

P112 2 0.3m P112 3 0.2m

Set the Relay OFF Setpoints

Parameter Index Value Description P113 0 1.3m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

For more information, see Appendix D: Pump Control Reference on page 239.

Page 71 of the Siemens 200 user manual — Set the Relay OFF Setpoints
Page 71 · click to enlarge
Page 71

Other Pump Control Algorithms

Set Relays to ALTERNATE DUTY BACKUP [MR 200]

Parameter Index Value Description P111 1 53 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY BACKUP. P111 2 53 P111 3 53

Set the Relay ON Setpoints [MR 200]

Parameter Index Value Description P112 1 0.4m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.

P112 2 0.3m P112 3 0.2m

Set the Relay OFF Setpoints [MR 200]

Parameter Index Value Description P113 0 1.3m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

Pump Control

Set Relays to FIXED DUTY ASSIST

Parameter Index Value Description P111 1 50 Sets the pump relays (index 1, 2, and 3) to FIXED DUTY ASSIST. Multiple pumps can run simultaneously. P111 2 50 P111 3 50

Set the Relay ON Setpoints

Parameter Index Value Description P112 1 0.4m Sets the three setpoints for the pump relays. The setpoints remain attached to the pump relays. P112 2 0.3m P112 3 0.2m

Set the Relay OFF Setpoints

Parameter Index Value Description P113 0 1.3m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

Page 72 of the Siemens 200 user manual — Set the Relay OFF Setpoints [MR 200]
Page 72 · click to enlarge
Page 72

Set Relays to FIXED DUTY BACKUP [MR 200]

Parameter Index Value Description P111 1 51 Sets the pump relays (index 1, 2, and 3) to FIXED DUTY BACKUP. Only one pump will ever run at one time. P111 2 51 P111 3 51

Set the Relay ON Setpoints [MR 200]

Parameter Index Value Description P112 1 0.4m Sets the three setpoints for the pump relays. The setpoints remain attached to the pump relays. P112 2 0.3m P112 3 0.2m

Set the Relay OFF Setpoints [MR 200]

Parameter Index Value Description P113 0 1.3m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

Set Relays to ALTERNATE DUTY SERVICE [MR 200]

Pump Control

Parameter Index Value Description P111 1 54 Sets the pump relays (index 1, 2, and 3) to SERVICE RATIO DUTY ASSIST P111 2 54 P111 3 54 P122 1 25 Sets the ratio to: 25% – Pump One

50% – Pump Two 25% – Pump Three P122 2 50 P122 3 25

Set the Relay ON Setpoints [MR 200]

Parameter Index Value Description P112 1 0.4m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.

P112 2 0.3m P112 3 0.2m

Set the Relay OFF Setpoints [MR 200]

Parameter Index Value Description P113 0 1.3m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

Page 73 of the Siemens 200 user manual — Pump Control
Page 73 · click to enlarge
Page 73

Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]

Parameter Index Value Description P111 1 56 Sets the pump relays (index 1, 2, and 3) to FIFO DUTY ASSIST. P111 2 56 P111 3 56

Set the Relay ON Setpoints [MR 200]

Parameter Index Value Description P112 1 0.4m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.

P112 2 0.3m P112 3 0.2m

Set the Relay OFF Setpoints [MR 200]

Parameter Index Value Description P113 0 1.3m By using index 0 all six relays are set at the same time, including any alarm relays. Use with caution.

Optional Pump Controls

Pump Control

Starting Pumps by Rate of Level Change [MR 200]

Use this function when multiple pumps will be controlled by rate of level change rather than setpoints. Pumping costs can be reduced because only the highest ON setpoint needs to be programmed. This results in a lower difference in head to the next wet well which, in turn, results in less energy being used to pump out the well.

Parameter Index Value Description P112 1 1.35 Starting pumps by rate allows all setpoints to be set higher to save money by pumping from the highest safe level of the wet well.

P112 2 1.35 P112 3 1.35 P113 1 0.5m P113 2 0.5m P113 3 0.5m P121 1 1 P121 2 1 P121 3 1 P132 G 20.0

The pumps will start on 20 second intervals until the rate set in P703 is met.

Page 74 of the Siemens 200 user manual — Pump Control
Page 74 · click to enlarge
Page 74

When the first ON setpoint is reached, the pumps will start, one by one, until the material level rate of change is set at the same value or greater than the value in:

  • P703 – Emptying Indicator (pump down applications)
  • P702 – Filling Indicator (pump up applications)

Set delay between pump starts using P132 – Pump Start Delay.

Single and Dual Point [MR 200]

  • Single Point Mode: one pump by rate control available that affects all pumps.
  • Dual Point Mode: a single pump by rate control can be set up for each of the three available level points. Set Operation for difference or average (P001 = 4 or 5).
  • Notes:
  • Set all pump control relay ON and OFF setpoints to the same value
  • If the level is within 5% of Span (P007) of the OFF setpoint, then the next pump is not started

Rotating Pumps by Service Ratio [MR 200]

Prerequisite: Set pump relays to a service ratio value (P111 = 54 or 55).

Pump Control

Parameter Index Value Description P122 1 1 These values will start Pump Two 50% of the time and Pumps One and Three each 25% of the time. P122 2 2 P122 3 1

  • Notes:
  • The MultiRanger will not sacrifice other pumping strategies to ensure that the ratio is held true
  • If the pump relays are set to the same value, then the ratio equals 1:1 and all pumps are used equally (preset)

When more than one pump is assigned a Pump Service Ratio value (in any time units) and a pump start is required (P112 Relay Setpoint ON), the pump with the fewest running hours (with respect to the assigned ratio values) starts.

Conversely, when a pump stop is required (113 Relay Setpoint OFF), the pump with the most running hours (as compared to the assigned ratio values) stops.

Page 75 of the Siemens 200 user manual — P
Page 75 · click to enlarge
Page 75

Totalizing Pumped Volume [MR 200]

Prerequisite: the volume of the vessel must be known.

Parameter Index Value Description P001 G 7 Operation = pumped volume P002 G 1

P003 G 2 P004 G 102 P005 G 1 P006 G 1.8 P007 G 1.4 P050 G 1 Tank shape is Flat Bottom. P051 G 17.6 Max volume is 17.6m3 or 17,600 liters. P111 1 52 Sets relays 1, 2, and 3 as a pump group using ALTERNATE DUTY ASSIST CONTROL. P111 2 52 P111 3 52 P112 1 1.0 Sets the ON setpoints for the pump group. P112 2 1.2 P112 3 1.4 P113 0 0.2 Sets the OFF setpoints for the pump group.

These parameters are as shown above.

Set in RUN Mode

Pump Control

1. Press PROGRAM for RUN mode.
2. Press TOGGLE to display pumped volume on the totalizer.
3. Press AUXILIARY to display current level in the auxiliary reading area.

P

Setting Independent Failsafe Controls

Independent failsafe controls allow you to vary an individual relay from the global failsafe controls programmed in P070 to P072.

Example:

The global failsafe controls are set to hold and Relay Five is set to trigger an alarm bell.

Parameter Index Value Description P071 G HOLd Keep level at last known value. P129 5 dE De-energize Relay Five, and trigger alarm.

Page 76 of the Siemens 200 user manual — Reducing Wall Cling [MR 200]
Page 76 · click to enlarge
Page 76

Setting a Pump to Run On [MR 200]

When you need to pump below the normal OFF setpoint, use P130 (Pump Run-On Interval) and P131 (Pump Run-On Duration) to control this event.

Example:

The pump connected to Relay Three is set to pump for an extra 60 seconds every 5 hours.

Parameter Index Value Description P130 3 5 Time in hours of run-on interval. P131 3 60 Run-on for 60 seconds.

Setting the Pump Start Delays [MR 200]

The pump start delay ensures that all of the pumps do not start at once to avoid power surges. There are two parameters used here: P132–Pump Start Delay and P133–Pump Power Resumption Delay. The default is 10 seconds but you can increase this if your pumps take longer to spin up.

Pump Control

Example:

The delay between pumps is set to 20 seconds and the delay of the first pump is set to 30 seconds.

Parameter Index Value Description P132 G 20 Wait at least 20 seconds between pump starts. P133 G 30 Wait for 30 seconds when power is restored.

Reducing Wall Cling [MR 200]

Use the Wall Cling parameter to randomly alter the ON and OFF setpoints over a range. This eliminates the ridge of material that builds up at the setpoint that can give false echoes.

This setting may increase the number of days between trips to clean the wet well.

Wall cling reduction is set by P136. The relay setpoints ON and OFF are randomly varied inside a range so the material level does not stop at the same point.

Page 77 of the Siemens 200 user manual — Setting a Flush Valve [MR 200]
Page 77 · click to enlarge
Page 77

Example [MR 200]:

A range of 0.5 meters is used to vary the setpoint. The randomly-selected setpoints are always inside the ON and OFF setpoints.

Siemens 200 — Grouping Pumps [MR 200] diagram (page 77)
Fig. 32 · Grouping Pumps [MR 200]

Grouping Pumps [MR 200]

You can group pumps and use the same pumping algorithm separately on each group. If you specify different pumping algorithms then the pumps are already grouped by algorithm and you do not need to use this parameter.

Pump Control

Group pumps only when four pumps are using the same algorithm and you want to split them into two groups.

Example:

Pumps One and Two can operate as a group and Pumps Three and Four can operate as another group.

Parameter Index Value Description P137 1 1 Groups Pumps One and Two P137 2 1 P137 3 2 Groups Pumps Three and Four P137 4 2

Setting a Flush Valve [MR 200]

A flush valve stirs up the sediment on the bottom of the well during pumping so that it doesn’t accumulate. These parameters will control any relays set with P111 = 64 (Flush Valve).

Most sets of parameters will work with only one or two changes; however, for these parameters to work, all of them must be set to a value.

Show 5 more labels / short text on this page
Level Setpoint ON · Random Setpoint · Wall Cling Value · Range · Level Setpoint OFF
Page 78 of the Siemens 200 user manual — Pump Control
Page 78 · click to enlarge
Page 78

Example:

The flush valve connects to Relay Four and the watched pump is on Relay One.

Parameter Index Value Description P170 G 1 Watch Relay One to count pump cycles. P171 G 3 Open the flush valve for 3 cycles. P172 G 10 Use the flush value every 10 cycles. P173 G 120 Open the flush valve for 120 seconds.

Relay Controlled by Communications

A relay can be controlled directly by a remote system through communications. No other control schemes can then be used with a relay configured this way. Communications can be used to force status of some control relays, such as pumps.

Settings:

Parameter Index Value Description P111 5 65 Sets Relay Five to communications control.

Tracking Pump Usage

Pump Control

You can find out how much an individual pump has been used by viewing the pump records parameters.

Information Available Parameter Access Current RUN time P309 Total pump hours P310 Total pump starts P311 Total pump RUN on occurrences P312 [MR 200 ONLY]

Page 79 of the Siemens 200 user manual — Rake (Screen) Control MR 200
Page 79 · click to enlarge
Page 79

Rake (Screen) Control [MR 200]

This feature is only available on the MultiRanger 200.

Screens or rakes are mounted on the inflow channel of the wastewater treatment plant to prevent debris from clogging the equipment.

When material builds up on the screen, a level differential is created, and the water level is higher in front of the screen than behind it. When this differential reaches the programmed setpoint, the MultiRanger activates a relay to operate mechanical rakes that clean the screen and ensure a steady flow.

Setting a Rake Control

P007 (3) Max differential between Point 1 and Point 2 reading also sets 100% scale for bargraph and mA output.

Siemens 200 — Setting a Rake Control diagram (page 79)
Fig. 33 · Setting a Rake Control

Rake (Screen) Control MR 200

Siemens 200 — Rake (Screen) Control MR 200 diagram (page 79)
Fig. 34 · Rake (Screen) Control MR 200
Point ThreeLevel Distance = h[1] –h[2]
Show 5 more labels / short text on this page
Transducer · Two Transducer · One Rake · Transducer[1] · Water Level h[2]
Page 80 of the Siemens 200 user manual — Rake (Screen) Control
Page 80 · click to enlarge
Page 80

Setting the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values.

Parameter Index Value Description P001 G 4 Operation = Differential P002 G 1 Material = liquid P003 1,2 2 Max. Process Speed = medium P004 1,2 102 Transducer = XPS-10 P005 G 1 Units = meters P006 1 2 1.8 2.2 Empty Empty

= 1.8m = 2.2m P007 1 2 3

1.4 1.4 1.4

Span Span Max Differential

= 1.4m = 1.4m = 1.4m

Set Relay 1 (Operate Rake)

Parameter Index Value Description P110 1 3 Starts the rake when the difference between the two levels rises above 0.4m and stop the rake when the difference falls below 0.1m.

P111 1 50 P112 1 0.4 P113 1 0.1

Set Relays 2 to 4 (Level Alarms)

P110 2 1 Description P110 2 1 Sets Relay Two as a high level alarm for Transducer One with an ON setpoint of 1.3m and an OFF setpoint of 1.2m.

P111 2 1 P112 2 1.3 P113 2 1.2 P110 3 2 Sets Relay Three as a low level alarm for Transducer Two with an ON setpoint of 0.2m and an OFF setpoint of 0.4m.

Rake (Screen) Control

MR 200

P111 3 1 P112 3 0.2 P113 3 0.4 P110 4 3 Sets Relay Four as a rake failure alarm as it uses the differential level point (3) with an ON setpoint of 1.0m and an OFF setpoint of 0.9m.

P111 4 1 P112 4 1.0 P113 4 0.9

Page 81 of the Siemens 200 user manual — Counter Formula
Page 81 · click to enlarge
Page 81

External Totalizers and Flow Samplers [MR 200]

This feature is only available on the MultiRanger 200.

External totalizers are simple counters which count the number of relay clicks produced by the MultiRanger. This is generally used to keep track of OCM or pumped volume totals. Note that both of these values are also stored in the MultiRanger and are available through communications.

Flow samplers are devices which take a sample of liquid when triggered by a relay click. These samples are used to monitor water quality over time. Flow samplers can be driven by OCM volume or by relay click volume settings depending on the application requirements.

Relay Contacts

Pumped volume is calculated at the end of the pump cycle. Totalized volume given through a relay set up for totalizer (P111[r]=40) will be given in bursts at this time.

Both the open and closed times for the relay contact are provided by P645 and are preset to 0.2 seconds. Partial units are added to the next pump cycle.

Example:

Shows a relay set up to make one contact for every cubic metre (m3) of liquid.

P645 P645

4m3 2m3 2m3 3m3 1m3

Totalizer

External Totalizers and Flow Samplers – MR 200

To set the totalizer to provide relay contact to an external counter, use the following:

Counter Formula

1 Contact per 10P640 units P640 is preset to 0 so the default number of contacts for a pumped volume cycle is equivalent to the number of volume units.

Pump Cycle

Page 82 of the Siemens 200 user manual — External Totalizers and
Page 82 · click to enlarge
Page 82

The source of units depends on the operation:

Operation Units Source Parameter OCM (P001=6) P604–Maximum Flow, or P608–Flowrate Units Pumped Volume (P001=7) P051–Max Volume

Flow Sampler

Based on Volume and Time

To trigger a flow sampler relay based on flow, use P111[r]=41 and set the other parameters:

Counter Formula

1 Contact per P641 x 10P642 units

Operation Units Source Parameter OCM (P001=6) P604 – Maximum Flow, or P608 – Flowrate Units

By using a mantissa (P641) and an exponent (P642), the relay contacts can be based on a volume other than a multiple of ten.

During the periods of low flow, the sampler may be idle for lengths of time. Program P115 to a time interval in hours to drive the sampler. The sampler will operate based on the volume of flow or the time interval, whichever comes first.

External Totalizers and

Flow Samplers – MR 200

Page 83 of the Siemens 200 user manual — Common Parameters
Page 83 · click to enlarge
Page 83

Open Channel Monitoring (OCM) [MR 200]

Open Channel Monitoring MR 200

An OCM installation is defined one of three ways, based on the Primary Measuring Device (PMD):

1. Dimensional (P600 = 2,3,6,7)

For some common weir and flume types. PMD dimensions (P602) are entered directly.

  • BS-3680 / ISO 1438/1 Thin plate V notch weir on page 75
  • BS-3680 / ISO 4359 Rectangular Flume on page 76
  • Palmer Bowlus Flume on page 77
  • H Flume on page 78

2. Exponential (P600 = 1)

For most other weir and flume types. PMD exponents provided by the manufacturer are entered. Flow is calculated using the exponent (P601) and the maximum values (P603 and P604).

  • Standard Weirs on page 79
  • Parshall Flume on page 80
  • Leoplod Lagco on page 81
  • Cut Throat Flume on page 82

3. Universal (P600 = 4,5)

For all other PMDs, the head-to-flow curve can be plotted based on known breakpoints, usually supplied by the PMD manufacturer.

  • Typical Flow Characterization on page 83
  • Example Flumes on page 84
  • Example Weirs on page 84

Common Parameters

These Quick Start parameters are required for all installations.

Parameter Index Value Description P001 G 6 Operation = OCM P002 G 1 Material = liquid P003 G 2 Max. Process Speed = medium P004 G 102 Transducer = XPS-10 P005 G 1 Units = meters P006 G 1.8 Empty = 1.8m P007 G 1.0 Span = 1.4m P801 G 0.8 Range Extension to avoid LOE

Page 84 of the Siemens 200 user manual — P006
Page 84 · click to enlarge
Page 84

Setting Zero Head

Open Channel Monitoring

Many PMDs start flowing higher than the traditional empty distance of the application. You can account for the flow in one of two ways:

MR 200

1. Use P605 (Zero Head) to have OCM calculations ignore levels below that value. Possible head = P007 minus P605.

P006

P007

P603

P605

2. Use P801 Range Extension where the Empty level is set to the bottom of the weir,

and above the bottom of the channel. It should be used if the surface monitored can fall past the Empty (P006) level in normal operation without reporting an LOE. The value is added to Empty (P006) and can be greater than the range of the transducer.

P006

P007

P603

P801

The examples on the following pages show both methods.

m

Page 85 of the Siemens 200 user manual — P006
Page 85 · click to enlarge
Page 85

Setting Totalized Volume

Open Channel Monitoring MR 200

To display the totalized volume on the LCD use the following parameters:

Parameter Index Value Description P737 G 2 Show the eight digit totalizer in the primary display

Applications Supported by MultiRanger 200

BS-3680 / ISO 1438/1 Thin plate V notch weir

Siemens 200 — BS-3680 / ISO 1438/1 Thin plate V notch weir diagram (page 85)
Fig. 35 · BS-3680 / ISO 1438/1 Thin plate V notch weir

P006

4 to 5 x hmax (hmax = P007)

Siemens 200 — P006 diagram (page 85)
Fig. 36

Parameter Index Value P600 G 7–ISO 1438/1 V Notch Weir P602 1 Notch angle (view only) 2 Discharge coefficient (Ce) P603 G Maximum Head (preset to P007) P801 G Range Extension P608 G Flowrate Units

Front View

Page 86 of the Siemens 200 user manual — Open Channel Monitoring
Page 86 · click to enlarge
Page 86

BS-3680 / ISO 4359 Rectangular Flume

Open Channel Monitoring

MR 200

Siemens 200 — Open Channel Monitoring diagram (page 86)
Fig. 37 · Open Channel Monitoring

Plan View 4 to 5 x hmax (hmax = P007)

Front View Side View

Siemens 200 — Open Channel Monitoring diagram (page 86)
Fig. 38 · Open Channel Monitoring
Siemens 200 — Open Channel Monitoring diagram (page 86)
Fig. 39 · Open Channel Monitoring

Parameter Index Value P600 G 6–ISO 4359 Rectangular Flume P602 1 Approach width (B) 2 Throat width (b) 3 Hump Height (p) 4 Throat length (L) (view only) 5 Velocity coefficient (Cv) (view only) 6 Discharge coefficient (Cd) (view only) 7 Cross sectional area P605 G Zero Head P608 G Flowrate Units

m · Transducer · P605 (p)

Page 87 of the Siemens 200 user manual — Application Information
Page 87 · click to enlarge
Page 87

Palmer Bowlus Flume

Open Channel Monitoring MR 200

Transducer D/2, point of measurement

P006

P007

P603

P605

Parameter Index Value P600 G 2–Palmer Bowlus Flume P602 1 Flume width (D) P603 G Maximum Head (preset = P007) P604 G Maximum Flow P605 G Zero Head P606 G Time Units

Application Information

  • Sized by pipe diameter D
  • Flume relief is trapezoidal
  • Designed to install directly into pipelines and manholes
  • Head is referenced to bottom of the throat, not bottom of the pipe
  • For rated flows under free flow conditions, the head is measured at a distance of D/2 upstream from the beginning of the converging section
Show 4 more labels / short text on this page
Plan View · Flow · Front View · Side View
Page 88 of the Siemens 200 user manual — Flume Size (Diameter in feet)
Page 88 · click to enlarge
Page 88

H Flume

Open Channel Monitoring

MR 200

P006 P007

D

Front View Side View

Parameter Index Value P600 G 3–H Flume P602 1 Flume height (D) P603 G Maximum Head (preset = P007) P604 G Maximum Flow P606 G Time Units

  • Sized by maximum depth of flume
  • Approach is preferably rectangular, matching width and depth for distance 3 to 5 times the depth of the flume
  • May be installed in channels under partial submergence (ratio of downstream level to head). Typical errors are:
  • 1% @ 30% submergence
  • 3% @ 50% submergence
  • For rated flows under free flow conditions, the head is measured at a point downstream from the flume entrance

Flume Size (Diameter in feet)

Point of Measurement cm inches 0.5 5 1¾ 0.75 7 2¾ 1.0 9 3¾ 1.5 14 5½ 2.0 18 7¼ 2.5 23 9 3.0 28 10¾ 4.5 41 16¼

  • H flumes come with a flat or sloping floor. The same flow table can be used because error is less than 1%.
Show 5 more labels / short text on this page
Transducer · m · Flow · Point of Measurement · Plan View
Page 89 of the Siemens 200 user manual — Applicable Weir Profiles
Page 89 · click to enlarge
Page 89

PMDs with Exponential Flow to Head Function

Open Channel Monitoring MR 200

For Primary Measuring Devices (PMDs) that measure flow by an exponential equation, use these parameters. Ensure that you use the correct exponent for your PMD; the values below are samples only.

Standard Weirs

Siemens 200 — Standard Weirs diagram (page 89)
Fig. 40 · Standard Weirs

Applicable Weir Profiles

Siemens 200 — Applicable Weir Profiles diagram (page 89)
Fig. 41 · Applicable Weir Profiles

Parameter Index Value P600 G 1 - Exponential Function P601 G Weir Type Value1

2.50 1.50 1.50 1.00 P603 G Maximum Head P604 G Maximum Flow P606 G Time Units P801 G Range Extension

V-notch Suppressed rectangular Cipolletti or trapezoidal Sutro or proportional

1. Values are samples only. Consult weir manufacturer’s documentation for correct flow exponent.
Show 6 more labels / short text on this page
Transducer · V-notch or · suppressed rectangular · cipolleti or trapezoidal · sutro or proportional · triangular
Page 90 of the Siemens 200 user manual — C 2 / 3 C
Page 90 · click to enlarge
Page 90

Non-Applicable Weir Profiles

Open Channel Monitoring

MR 200

compound Poebing approximate exponential

Flows through these weirs can be measured using the Universal Flow Calculation P600 = 4 or 5. See Universal Calculation Support on page 83.

Parshall Flume

C 2 / 3 C

P006

Application Information

  • Sized by throat width
  • Set on solid foundation
  • For rated flows under free flow conditions, the head is measured at 2 / 3 the length of the converging section from the beginning of the throat section

Parameter Index Value P600 G 1–Parshall Flume P601 G 1.22–1.607 (consult your flume documentation) P603 G Maximum Head P604 G Maximum Flow (Q) P606 G Time Units

Show 7 more labels / short text on this page
m · contracted rectangular · Plan View · Flow · Front View · Side View · Transducer
Page 91 of the Siemens 200 user manual — Application Information
Page 91 · click to enlarge
Page 91

Leopold Lagco Flume

Open Channel Monitoring MR 200

Parameter Index Value P600 G 1–Leopold Lagco Flume P601 G 1.55 P603 G Maximum Head (preset P007) P604 G Maximum Flow P605 G Zero Head P606 G Time Units

Application Information

  • Designed to be installed directly into pipelines and manholes
  • Leopold Lagco may be classed as a rectangular Palmer-Bowlus flume
  • Sized by pipe (sewer) diameter
  • For rated flows under free flow conditions, the head is measured at a point upstream referenced to the beginning of the converging section. Refer to the following table:
Show 8 more labels / short text on this page
Plan View · Throat · Front View · Diverging Converging · Transducer · Point of Measurement · Side View · 0 Head
Page 92 of the Siemens 200 user manual — MR 200
Page 92 · click to enlarge
Page 92

Open Channel Monitoring

Flume Size (pipe diameter in inches)

Point of Measurement cm inches 4-12 2.5 1 15 3.2 1¼ 18 4.4 1¾ 21 5.1 2 24 6.4 2½ 30 7.6 3 42 8.9 3½ 48 10.2 4 54 11.4 4½ 60 12.7 5 66 14.0 5½ 72 15.2 6

MR 200

Cut Throat Flume

Application Information

  • Similar to Parshall flume except that the floor is flat bottomed and throat has no virtual length.
  • Refer to manufacturer’s specifications for flow equation and point of head measurement.

Parameter Index Value P600 G 1–Cut Throat Flume P601 G 1.55 P603 G Maximum Head (preset P007) P604 G Maximum Flow P606 G Time Units

m · Plan View

Page 93 of the Siemens 200 user manual — Typical Flow Characterization
Page 93 · click to enlarge
Page 93

Universal Calculation Support

Open Channel Monitoring MR 200

When the primary measuring device (PMD) doesn’t fit one of the standard types, it can be programmed using a universal characterization. When Universal is selected as the PMD type (P600), then both P610 and P611 must be entered to define the flow.

Two curve types are supported:

  • P600 = 4–linear (piece wise linear)
  • P600 = 5–curved (cubic spline)

Both are shown in the following chart.

Typical Flow Characterization

Characterization is achieved by entering the head (P610) and corresponding flow (P611), either from empirical measurement or from the manufacturer's specification. Increasing the number of defined breakpoints will increase the accuracy of the flow measurement.

Breakpoints should be concentrated in areas exhibiting the higher degrees of non linear flow. A maximum of 32 breakpoints can be defined. The curve’s end point is always specified by the parameters Maximum Head (P603) and Maximum Flow (P604) for a maximum total of 33 breakpoints.

Max. Flow

Max. Head

Use as many breakpoints as required by the complexity of your PMD. See Volume on page 51 for more information and parameters P610 and P611 for characterization.

Show 9 more labels / short text on this page
Maximums (P603, P604) · Flow (P611) · Linear · Curved · Head (P610) · Flow Breakpoints · Zero Flow · Zero Head · Head Breakpoints
Page 94 of the Siemens 200 user manual — MR 200
Page 94 · click to enlarge
Page 94

Example Flumes

Open Channel Monitoring

These example flumes would both require a universal calculation.

MR 200

Trapezoidal

Dual Range (nested) Parshall

Example Weirs

These weirs could require universal calculation.

compound Poebing approximate exponential

m · contracted rectangular

Page 95 of the Siemens 200 user manual — Starting a (P920, P921, P922, or P923) simulation when level = 0:
Page 95 · click to enlarge
Page 95

Testing the Configuration

After programming the unit, you must test the device to ensure that it performs to your specifications. This test can be run in simulation mode or by varying the level in the application. The latter is preferred as it more accurately represents running conditions. However, if it is not possible to do a physical test, a simulation will ensure that control programming is correct.

Simulation

Testing the Configuration

In simulation mode, the LCD display reacts to the simulated level changes. Alarm relays will also react to the simulation, but any pump or control relays will not react.

To allow pump or control relays to operate on the simulated level, set P000 to –1.

Simulating a Single Measurement

Access the appropriate parameter: (press PROGRAM and then key in the parameter number). Press TRANSDUCER five times to overcome Echo Lock (P711) if applicable: the associated Reading is displayed in the Parameter Value field, and any alarm relays are set accordingly.

To verify Reading calculations (P920 to P926)

1. Go to the parameter to be simulated (P920, P921, P922, P923, P924, P925, or P926), and key in a material level in Units (Units defined in P005), or % of Span (% of Span defined in P007). 2. Press ENTER to display the calculated Reading. [Regardless of setting for P001, the parameter value being simulated will display as the primary reading. The auxiliary reading will always display the level value (P921). See “Display” on page 22 for positions of the primary and auxiliary readings on the LCD.] 3. Verify the calculated Reading. (At this point, the simulation is in Stop state. The

effect of the ARROW key is based on this state. See chart on page 86.)

Simulating a Level Cycle

Starting a (P920, P921, P922, or P923) simulation when level = 0:

1. Go to the parameter to be simulated (P920, P921, P922, or P923).
2. Press ENTER to simulate level rise and fall. At the start of a simulation, the default rate is 1% of Span / second.
Page 96 of the Siemens 200 user manual — To confirm universal flow calculations (P600 = 4, 5) are accurate:
Page 96 · click to enlarge
Page 96
3. Press the ARROW or to adjust the simulated rate of rise or fall, based on the chart on page 86. The maximum rate is 4% of Span / second.

The effect of the ARROW key is determined by the state (rate of rise or fall) immediately before the key is pressed.

Action State (prior to pressing key) Effect

Stop Rise at 1% of Span / second

Rise at 1% of Span / second Rise at 4% of Span / second (max.)

Testing the Configuration

Rise at 4% of Span / second (max.) No effect

Fall at 1% of Span / second Stop

Fall at 4% of Span / second Fall at 1% of Span / second

Stop Fall at 1% of Span / second

Rise at 1% of Span / second Stop

Rise at 4% of Span / second (max.) Rise at 1% of Span / second

Fall at 1% of Span / second Fall at 4% of Span / second (max.)

Fall at 4% of Span / second (max.) No effect

When the level rises to 100% or falls to 0%, it reverses direction at the same rate.

Checking Volume Characterization [MR 200]

To confirm universal volume calculations (P050 = 9, 10) are correct:

1. Go to P920. 2. Key in a level associated with a known volume. 3. Press ENTER . 4. Check the returned volume against the manufacturer’s chart. 5. Change parameters P054 and P055, as required. 6. Repeat steps 2 to 5 until the volume curve is verified.

Checking OCM Flow Characterization [MR 200]

To confirm universal flow calculations (P600 = 4, 5) are accurate:

1. Go to P925. 2. Enter a level with a known flow. 3. Press ENTER . 4. Check the returned flow against the manufacturer’s chart.

Press · Press

Page 97 of the Siemens 200 user manual — Application Test
Page 97 · click to enlarge
Page 97
5. Change parameters P610 and P611, as required. 6. Repeat steps 2 to 5 until the flow curve is verified.

I/O Checkout

After the unit is installed, test to verify the wiring.

Relays

Use P119 to force a state change and verify that the results are as expected (pump starts, alarm sounds, etc.).

Testing the Configuration

Discrete Inputs

Use P270 to force the input value and verify that the results are as expected.

1. Go to P270 [DI] where DI = the discrete input to be tested 2. Set P270 to 0 (forced OFF) 3. Go to P275 [DI] to verify that the value is forced 4. Check the state of outputs to ensure that they respond as expected 5. Go to P270 [DI] 6. Set P270 to 1 (forced ON) 7. Go to P275 [DI] to verify that the value is forced 8. Check the state of outputs to ensure that they respond as expected

For further information see Discrete Inputs section on page 48.

mA Input [MR 200]

Use P254 to test the mA input value against a true level. Use a trusted external mA source to generate the signal required for testing, and verify the incoming signal with P260. Check that the system responds as expected when the mA level is changed.

mA Output

Use an external device to test the mA output against the measured level. Check that the mA value changes to reflect the changes in the measured level.

Application Test

If you are testing the application by varying the material level (the preferred test method) make sure that none of the control devices is connected (or at least that no power is available to them).

If you are testing the application in simulation mode (and P000 is not –1), then control relays are not energized and the control devices can remain connected.

While the level is being cycled, check the results of the discrete inputs either by closing the circuit externally (preferred) or by using P270 Discrete Input Function to force the input ON or OFF. Try all possible combinations to thoroughly test the setup. For each combination, run a complete cycle to verify that the relays operate as expected.

Page 98 of the Siemens 200 user manual — Testing the Configuration
Page 98 · click to enlarge
Page 98

Monitor system performance carefully, under all anticipated operating conditions.

1. When the MultiRanger performs exactly as required, programming is complete.
2. If alternate Reading units, Failsafe action, or relay operation is desired, update the

parameters for the new functionality.

3. If the system performance experiences problems, see General Appendix C:

Troubleshooting, on page 231.

If you cannot observe all possible operating conditions during the System Performance Evaluation, use the level simulation (see page 85) to verify programming.

When a simulation is run, alarm relays will react to the simulated level changes, but control relays will not react. You can set P000 to value –1 to trigger the control relays based on the simulated level.

Testing the Configuration

Retest the system every time you adjust any control parameters.

Page 99 of the Siemens 200 user manual — Optional SmartLinx ® Cards
Page 99 · click to enlarge
Page 99

MultiRanger Communications

MultiRanger Communication Systems

The MultiRanger is an integrated level controller capable of communicating process information to a Supervisory Control and Data Acquisition (SCADA) system, via a serial device such as a radio modem, leased line, or dial-up modem.

Siemens 200 — MultiRanger Communications diagram (page 99)
Fig. 42 · MultiRanger Communications

Communications

Connection via radio modem, dial-up modem, or leased line modem

The standard MultiRanger supports the following two communication protocols:

Modbus

Modbus is an industry standard protocol used by SCADA and HMI systems. The MultiRanger uses Modbus to communicate via the RS-485 port. For a description of the Modbus protocol, contact your local Schneider representative.

Dolphin

Dolphin is a proprietary Siemens Milltronics protocol designed to be used with Dolphin Plus. For more information on Dolphin Plus or to obtain a copy of the software, please go to www.siemens.com/processautomation to contact your Siemens Milltronics representative.

Optional SmartLinx ® Cards

The standard MultiRanger unit may also be enhanced with Siemens Milltronics SmartLinx® communication modules that provide an interface to popular industrial communication systems.

This manual only describes the built-in communications. For more information on SmartLinx, please consult the appropriate SmartLinx manual.

MultiRanger

Page 100 of the Siemens 200 user manual — Modbus
Page 100 · click to enlarge
Page 100

Communication Systems

The MultiRanger is capable of communicating with most SCADA systems, PLCs, and PCs. The supported protocols are:

  • Modbus RTU/ASCII – base unit on RS-232 or RS-485 transport
  • PROFIBUS DP – optional SmartLinx ® module
  • Allen-Bradley® 1 Remote I/O – optional SmartLinx module
  • DeviceNet® – optional SmartLinx module

Communication Ports

The MultiRanger comes with two communication ports on the base unit.

Port Connection Location Interface 1 RJ-11 connector inside enclosure on main board RS-232 2 terminal block terminal block RS-485

RS-232

The RJ-11 jack connects to a laptop computer for the following:

Communications

  • initial setup
  • configuration
  • troubleshooting
  • periodic maintenance

RS-485

The RS-485 port on the terminal blocks connects into industrial communications wiring and has the following advantages:

  • runs communications cable farther
  • allows multiple slave units on the network, addressed by P771 – Network Address

To communicate with equipment requiring RS-485 capability, Siemens Milltronics offers the RS-485 External Modem Kit. For more information, go to www.siemens.com/processautomation

Modbus

The Modbus protocol is supported in the base unit and can be configured using the Communications parameters P770 to P782.

To set up communications with a Modbus RTU master device on port 2 using RS-485, set the following parameters:

1. Allen-Bradley is a registered trademark of Rockwell Automation. DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
Page 101 of the Siemens 200 user manual — Communications
Page 101 · click to enlarge
Page 101

Parameter Index Value Description P770 2 3 Modbus RTU slave P771 2 1 Network address, only used for RS-485 P772 2 9.6 Data rate of 9600 baud P773 2 0 No parity, common setting P774 2 8 8 data bits, common setting P775 2 1 1 stop bit, common setting P778 2 0 No modem connected P782 2 0 Index parameter values globally

SmartLinx

Other protocols are available through optional SmartLinx communications modules. Details on how to install and program these modules are contained in the SmartLinx documentation.

Dolphin Plus

Dolphin Plus software makes it easy to record and compare parameter sets for all the MultiRangers in your company. Dolphin Plus uses a proprietary protocol called Dolphin to communicate with Siemens Milltronics instruments. This protocol is set when P770 = 1.

Communications

By default the settings for port 1 (RJ-11 connection) and Dolphin Plus match. These settings are:

Parameter Index Value Description P770 1 1 Dolphin P772 1 115.2 Data rate of 115.2 Kilo baud P773 1 0 No parity, common setting P774 1 8 8 data bits, common setting P775 1 1 1 stop bit, common setting

Page 102 of the Siemens 200 user manual — Comms Installation
Page 102 · click to enlarge
Page 102

Communications Installation

Wiring Guidelines

  • the RJ-11 cable maximum length is 3 meters
  • RS-485 maximum length is 1,200 meters (4,000 feet)
  • use 24 AWG (minimum)
  • use good quality communication grade (shielded twisted pairs) cable that is recommended for RS-485 for port 2 (Belden 9842)
  • run the communication cable separately from power and control cables (do not tie wrap your RS-232 or RS-485 cable to the power cable or have them in the same conduit)
  • use shielded cable and connect to ground at one end only
  • follow proper grounding guidelines for all devices on the bus

Ports 1 and 2

Siemens 200 — Ports 1 and 2 diagram (page 102)
Fig. 43 · Ports 1 and 2

Port Wall Mount 1 RS-232 port (RJ-11 modular telephone jack) is on the motherboard and is generally used with a laptop computer or modem. 2 Connections for the RS-485 port are on the terminal block.

Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locations

The RJ-11 jack and the RS-485 port are inside the enclosure of the unit.

Comms Installation

Siemens 200 — Comms Installation diagram (page 102)
Fig. 44 · Comms Installation

RJ-11 Jack · RS-485 Port

Page 103 of the Siemens 200 user manual — To connect the unit to an RS-232 modem:
Page 103 · click to enlarge
Page 103

Port 1: RS-232 RJ-11 Jack

To connect the unit to a PC using an RS-232 jack, use the cable as shown:

Siemens 200 — Port 1: RS-232 RJ-11 Jack diagram (page 103)
Fig. 45 · Port 1: RS-232 RJ-11 Jack

Modular cable with RJ-11 plug

To connect the unit to a modem using an RS-232 jack:

Siemens 200 — To connect the unit to a modem using an RS-232 jack: diagram (page 103)
Fig. 46 · To connect the unit to a modem using an RS-232 jack:

Modular cable with RJ-11 plug

Comms Installation

Port 2: RS-485

To connect the unit to an RS-232 modem:

MultiRanger Terminal Block DB 9 DB 9

Siemens 200 — To connect the unit to an RS-232 modem: diagram (page 103)
Fig. 47 · To connect the unit to an RS-232 modem:

Computer DB-9 (male) · RS-232 Modem

Page 104 of the Siemens 200 user manual — P771 Network Address
Page 104 · click to enlarge
Page 104

(Shield to be grounded at one end)

B A C O M

To connect the unit to a modem using an RS-485 port:

COM MultiRanger Terminal Block RS-485 Modem

A

B

Configuring Communication Ports (Parameters)

The 11 parameters listed are indexed to the two communication ports, unless otherwise noted: An asterisk (*) identifies the preset value.

Port Description 1 RS-232 port (RJ-11 modular telephone) 2 The RS-485 port is on the terminal blocks

P770 Port Protocol

The communications protocol used between the MultiRanger and other devices.

Comms Installation

Primary Index Communications Port

0 Communications port disabled 1 * Siemens Milltronics Dolphin protocol (preset for port 1) 2 Modbus ASCII slave serial protocol 3 * Modbus RTU slave serial protocol (preset for port 2)

The MultiRanger supports the Siemens Milltronics Dolphin format (www.siemens.com/ processautomation), and the internationally recognized Modbus standard in both ASCII and RTU formats. Other protocols are available with optional SmartLinx cards.

P771 Network Address

The unique identifier of the MultiRanger on the network.

Primary Index Communications Port Values Range: 0 to 9999 1 * Preset

MultiRanger Terminal Block · Values

Page 105 of the Siemens 200 user manual — Comms Installation
Page 105 · click to enlarge
Page 105

For devices connected with the Siemens Milltronics protocol, this parameter is ignored. For devices connected with a serial Modbus slave protocol, this parameter is a number from 1-247. The network administrator must ensure that all devices on the network have unique addresses. Do not use the value 0 for Modbus communications as this is the broadcast address and is inappropriate for a slave device.

P772 Baud Rate

The communication rate with the master device.

Primary Index Communications Port

4.8 4800 baud 9.6 9600 baud 19.2 * 19,200 baud (preset for port 2) 115.2 * 115,200 baud (preset for port 1)

This specifies the rate of communication in Kbaud. Any value may be entered, but the only values supported are those shown above. The baud rate should reflect the speed of the connected hardware and protocol used.

P773 Parity

The serial port parity.

Primary Index Communications Port

0 * No Parity 1 Odd Parity 2 Even Parity

Ensure that the communications parameters are identical between the MultiRanger and all connected devices, as many modems default to N-8-1.

P774 Data Bits

The number of data bits per character.

Primary Index Communications Port

Range: 5 to 8 8 * Modbus RTU 7 or 8 Modbus ASCII 7 or 8 Dolphin Plus

Comms Installation

P775 Stop Bits

The number of bits between the data bits.

Primary Index Communications Port Values Range: 1 or 2 1 * Preset

Values · Values · Values

Page 106 of the Siemens 200 user manual — Comms Installation
Page 106 · click to enlarge
Page 106

P778 Modem Available

Sets the MultiRanger to use an external modem.

Primary Index Communications Port

0 * No modem connected 1 Answer only

P779 Modem Inactivity Timeout

Sets the time that the unit will keep the modem connected with no activity.

Primary Index Communications Port Values Range: 0-9999 seconds

0 * No timeout

To use this parameter, ensure that P778 (Modem Available) =1. Ensure that the value is low enough to avoid unnecessary delays when an unexpected disconnect occurs but long enough to avoid timeout while you are still legitimately connected. This parameter value is ignored by the Modbus Master Drivers as they automatically disconnect when done communicating.

Hanging Up

If the line is idle and the P779 Modem Inactivity Timeout expires, then the modem is directed to hang up the line. Ensure that P779 is set longer than the standard polling time of the connected master device. Set P779 to 0 to disable the inactivity timer.

P782 Parameter Index Location

Determines where index information is stored for the parameter access area for the Modbus register map.

Primary Index Global Values 0 * Global 1 Parameter-Specific

Comms Installation

For more on Parameter Index Location, see Parameter Access on page 102.

Values

Page 107 of the Siemens 200 user manual — Modbus Register Types
Page 107 · click to enlarge
Page 107

Modbus Register Map

Features affecting volume, mA input, and Average or Difference readings apply to the MultiRanger 200 only. They are clearly marked.

The memory map of the MultiRanger occupies the Modbus holding registers (R40,001 and up). This map is used when the protocol is Modbus RTU slave or Modbus ASCII slave.

Register Map for Most Common Data

Legend Type The type of data held in the group of registers. Start The first register to hold the referenced data. Data Type The possible values of the data in the register. See Data Types on page 107 for more information. Description The type of data held in the individual registers. #R The number of registers used for the referenced data. Read/Write Indicates whether the register is readable, writeable or both.

Data Type Read/ Write Word Order 40,062 0/1 R/W

Type Description Start #R 1

Map ID Register Map Type 40,063 1 0/1 = P782 R/W ID Siemens Milltronics Product Code

40,064 1 4 = Model 200 6 = Model 100 R

Single Parameter Access (SPA) R40,090 7 see Appendix A on page 114

41,010 2 -20,000 to 20,000 R

Volume (2)3[MR 200]

41,020 2 -20,000 to 20,000 R

1. Maximum registers shown; fewer may be used depending on options installed.

2. Varies according to model. MR 100: Available as reading 1 and reading 2 when in either Single or Dual Point Mode. In Dual Point Mode, reading 1 and reading 2 are always available. MR 200: Available as reading 1, reading 2, and Average or Difference when in either Single or Dual Point Mode. In Single Point Mode, point 2 and 3 are only available if P001 = Average or Difference. In Dual Point Mode, reading 1 and reading 2 are always available. Point 3 is only available if P001[3]= Average or Difference.

3. 2 nd volume available in Dual Point Mode only.

Modbus Register Types

Point Data · Reading (3)2

Page 108 of the Siemens 200 user manual — Modbus Register Types
Page 108 · click to enlarge
Page 108

Data Type Read/ Write Point Data

Type Description Start #R 1

Temperature (2) 41,030 2 –50 to 150 R Totalizer for points 1 and 2 [MR 200]

41,040 4 UINT32 R/W

Discrete Inputs (2) 41,070 1 Bit Mapped R Relay Outputs (3 or 6) 41,080 1 Bit Mapped R/W

I/O

mA Input (1) [MR 200]

41,090 1 0000 to 20,000 R

mA Output (2) 41,110 2 0000 to 20,000 R/W

Pump on Setpoint (3 or 6)

41,420 6 0000 to 10,000 R/W

Pump off Setpoint (3 or 6)

41,430 6 0000 to 10,000 R/W

Pumped Volume (2) [MR 200]

41,440 4 UINT32 R

Pump Hours (3 or 6) 41,450 12 UINT32 R Pump Starts (3 or 6) 41,470 6 0000 to 10,000 R

Parameter Access 43,998 to 46999 R/W

1. Maximum registers shown; fewer may be used depending on options installed.

The MultiRanger was designed to make it easy for master devices to get useful information via Modbus. This chart gives an overview of the different sections. A more detailed explanation of each section follows below.

Word Order (R40,062)

This determines the format of unsigned, double-register integers (UINT32).

  • 0 indicates that the most significant word (MSW) is given first
  • 1 indicates that the least significant word (LSW) is given first

See Unsigned Double Precision Integer (UINT32) on page 107 for more information.

Map ID (R40,063)

Modbus Register Types

This value identifies the register map used by the MultiRanger. See P782 Parameter Index Location on page 96.

See also Parameter Access (R43,998 – R46,999) on page 102 for details.

Pump Control

Page 109 of the Siemens 200 user manual — Modbus Register Types
Page 109 · click to enlarge
Page 109

Product ID (R40,064)

This value identifies the Siemens device type:

Device Type Value MultiRanger 100 6 MultiRanger 200 4

Point Data (R41,010 – R41,031)

Measurement point data contain the current instrument readings. These are the values shown for the reading measurement for each measurement point. The reading is based on the setting for P001 (operation). P001 can be set to level, distance, OCM flow, or volume. See Parameter Reference section on page 117 for details.

The measurement registers are 41,010 to 41,012. The MultiRanger uses 41,010 when configured with a single transducer and 41,010 to 41,012 when configured with two transducers (P111=4 or 5 only). Two transducers can create three readings because they can generate an average or differential reading (R41,012) as well as the two level readings (R41,010 and R41,011).

Available registers:

Data Registers Parameter Reading 41,010 to 41,012 P920 Volume [MR 200] 41,020, 41,021 P924 Temperature 41,030 and 41,031 P912

The reading is expressed as a percentage of full scale, multiplied by 100:

Reading Value 0 0.00% 5000 50.00% 7564 75.64% 20,000 200.00%

Totalizer (R41,040 – R41,043)

The totalizers are stored as 32 bit integers using two registers. The totalizers can be read with R41,040 and R41,041 as totalizer for Point 1, and R41,042 and R41,043 as totalizer for Point 2. The totalizer values can be reset to any value by writing that value to the registers. The values can be cleared by writing zero (0) to the registers.

Modbus Register Types

Input/Output (R41,070 – R41,143)

The MultiRanger has discrete inputs, mA inputs, mA outputs and relay outputs. See below for details for each I/O type.

Page 110 of the Siemens 200 user manual — Modbus Register Types
Page 110 · click to enlarge
Page 110

Discrete Inputs (R41,070)

This table shows the current status of the discrete inputs. Only register 41,070 is used.

Discrete Input Data Address 1 41,070, bit 1 2 41,070, bit 2

Relay Outputs (R41,080)

This table shows the current status of the relays. A reading of 0 means that the relay function is not asserted and a 1 means that it is asserted. For example, a 1 for a pump relay means that the pump is running.

Relay Data Address 1 41,080, bit 1 2 41,080, bit 2 3 41,080, bit 3 4 41,080, bit 4 5 41,080, bit 5 6 41,080, bit 6

Values are written to control a relay only if the Relay Control Function (P111) is set to communications (65). See Relay Function Codes (P111 Only) on page 110.

mA Input (R41,090) [MR 200]

The mA input is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). P254 displays the value of the input. This parameter is indexed by the input number.

mA Output (R41,110-41,111)

The mA output is scaled from 0 to 2,000 (0 to 20 mA multiplied by 100). This is displayed in P911.

Pump Control (R41,400 – R41,474)

Only relays set for pump control (P111 = 50 to 52) are available. These registers have no effect on relays programmed for other uses.

Pump ON Setpoint (R41,420 – R41,425)

Modbus Register Types

The ON setpoint level (P112) for the referenced pump relay.

The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is shown in the register as 5402.

Page 111 of the Siemens 200 user manual — Modbus Register Types
Page 111 · click to enlarge
Page 111

Pump OFF Setpoint (R41,430 – R41,435)

The OFF setpoint level (P113) for the referenced pump relay.

The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is shown in the register as 5402.

Pumped Volume (R41,440 – R41,443) [MR 200]

The pumped volume registers hold the current total for all of the pumps associated with a level point. These registers are available only if operation is set to pumped volume (P001 = 7).

These volumes can become very large. Therefore, two registers are used to hold the value. See Unsigned Double Precision Integer (UINT32) on page 107 for more information.

The value in the registers is given as an integer value but must be interpreted as having the number of decimals set in P633 (LCD Totalized Decimal Position): this number can be 0 to 3. Ensure that your software accounts for these decimal places before you report the pumped volume totals.

Pump Hours (R41,450 – R41,461)

The number of running hours for the referenced pump relay. The hours are given to three decimal places, so the integer must be divided by 1000 to get the correct value. For example 12,340 represents 12.34 hours.

This value comes from parameter P310. See page 157 of the Parameter Reference section for details.

Pump Starts (R41,470 – R41,475)

The number of pump starts for the referenced pump relay.

This value comes from parameter P311. See page 157 of the Parameter Reference section for details.

Modbus Register Types

Page 112 of the Siemens 200 user manual — Modbus Register Types
Page 112 · click to enlarge
Page 112

Parameter Access (R43,998 – R46,999)

Parameter values are given as integers in the range of registers from R44,000 to R44,999. The last three numbers of the register correspond to the parameter number.

Parameter Register # Format Register # Parameter # 44,000 46,000 P000 44,001 46,001 P001 44,002 46002 P002 … … … 44,999 46,999 P999

Usually, the parameters are all read / write.

  • Note:
  • Parameters P000 and P999 are read only. If P000 is set to lock activated then all of the parameters are read only via the handheld programmer
  • Parameter P999 (Master Reset) cannot be used via Modbus
  • See Data Types on page 107 for a description of the different types of data associated with different parameters

Each parameter register has a corresponding format register that holds the format information required to interpret the value. See Format Words (R46,000 to R46,999) on page 105.

Parameter Indexing

Many parameters are indexed. There are two possible indexes: a primary index and a secondary index. A secondary index is a sub-address of the primary index. Some indexed parameters affect multiple I/O devices.

The following is an example of a primary index:

P111 is the Relay Control Function. This parameter determines how a relay is controlled by the MultiRanger (used as an alarm, for pump control, etc.). Because there are up to six relays on the MultiRanger, P111 is indexed by six to allow each relay to be programmed independently.

A few parameters also have a secondary index. While a secondary index is important for setting up the MultiRanger, it is almost never needed through remote communications.

Indexing the Parameter Access Area

Each parameter communicates its value to only one register. You must know the index(es) for the parameter in order to interpret the information in the register correctly.

Modbus Register Types

For example, to make use of the value returned in register R44,111 you must know which relay it is referring to. See Relay Function Codes (P111 Only) on page 110 for details on P111 values.

To determine the index values, the primary and secondary index must be read or write. The two possible methods of handling these index values are described in the following paragraphs: Global Index Method and Parameter Specific Index Method.

Page 113 of the Siemens 200 user manual — Modbus Register Types
Page 113 · click to enlarge
Page 113

Reading Parameters

To read parameter values, follow the steps listed in either the Global or the Parameter Specific Index Method that follow. You must be able to program your HMI or SCADA system before completing these methods.

Global Index Method (P782 = 0)

Global format method sets index values for all parameters simultaneously. Use this method to read multiple values set to the same index values.

1. Write the primary index value into R43,999.

This is a value between 0 and 40 which specifies the input or output indexed by the parameter.

Examples are:

  • Transducer 1 is index 1
  • Discrete input 2 is index 2
  • Relay 5 is index 5
2. Write the secondary index value into R43,998.

This is a value between 0 and 40 that specifies the secondary index on the parameter. This value is usually 0.

3. Write the desired format value into the appropriate format register. Because the

primary and secondary indexes are already specified, these portions of the format word are ignored and only the last digit is significant.

See Format Registers on page 115 for details.

4. Read the value from the appropriate parameter register.

Types of values are:

  • Numeric Values, on page 107
  • Bit Values, on page 107
  • Split Values, on page 108
  • Text Messages, on page 109
  • Relay Function Codes (P111 Only), on page 110

A value of 22,222 indicates that an error has occurred. Specify a different format type and try again.

Parameter Specific Index Method (P782 = 1)

The Parameter Specific index method sets the index values for each parameter independently. Use this method to read multiple parameters with different index values.

Modbus Register Types

1. Write the primary index, secondary index, and data format values into the appropriate format register.
  • For example, to read the following information:
  • measured level (P921)
  • in units with three decimal places
Page 114 of the Siemens 200 user manual — Modbus Register Types
Page 114 · click to enlarge
Page 114
  • from Transducer One

Send the integer value 01008 to register 46,921.

2. Read the value from the appropriate parameter register (the example uses 44,921).
  • Types of values are:
  • Numeric Values on page 107
  • Bit Values on page 107
  • Split Values on page 108
  • Text Messages on page 109
  • Relay Function Codes (P111 Only) on page 110

A value of 22,222 indicates that an error occurred. Specify a different format type and try again.

Writing Parameters

The method of writing parameters is similar to the method of reading them. Become familiar with Reading Parameters, page 103, before attempting to write any parameters.

To write parameter values to the MultiRanger, follow these steps:

Global Index Method (P782 = 0)

1. Write the primary index value into R43,999.
2. Write the secondary index value into R43,998.
3. Write the desired format value into the appropriate format register.
4. Write the value to the appropriate parameter register.

Parameter Specific Index Method (P782 = 1)

1. Write the primary index, secondary index, and data format values into the appropriate format register.
2. Write the value to the appropriate parameter register.

Modbus Register Types

Page 115 of the Siemens 200 user manual — Modbus Register Types
Page 115 · click to enlarge
Page 115

Format Words (R46,000 to R46,999)

Format words are unsigned integers that contain up to three values (described below). The number of values used in the format words depends on the Parameter Index Location (P782) that is used.

Parameter P782 Parameter Index Location, described on page 96, determines which of two methods is used to access the format words: Global Index Method or Parameter Specific Index Method.

Global Index Method (P782 = 0)

Only the final digit of the format word determines the decimal offset (below).

Parameter-Specific Index Method (P782 = 1)

All three decimal fields are used to determine the parameter value’s primary index, secondary index, and decimal offset.

Format Registers

Each format register is made up of three decimal fields:

  • decimal offset
  • secondary index
  • primary index

The primary and secondary indices correspond to those that are used by the parameter.

Modbus Register Types

decimal offset (0-9) · secondary index (00-99) · primary index (00-64)

Page 116 of the Siemens 200 user manual — Modbus Register Types
Page 116 · click to enlarge
Page 116

The decimal offset indicates how the remote system must interpret the integer value that is stored in the parameter access register. The following table shows how different parameter values can be shown based on a register value (integer) of 1234.

Decimal Offset Example 0 0 1,234 1 –1 12,340 2 –2 123,400 3 –3 1,234,000 4 –4 12,340,000 5 –5 123,400,000 6 +1 123.4 7 +2 12.34 8 +3 1.234 9 Percent 12.34%

Examples of using the format word for both the index values and the decimal offset value are shown below:

Format Primary Index Secondary Index Decimal

00000 00 00 0 01003 01 00 3 right 02038 02 03 3 left 05159 05 15 percent

To write these values you can use a decimal offset as follows: format word = (primary index x 1000) + (secondary index x 10) + (decimal).

Modbus Register Types

Page 117 of the Siemens 200 user manual — Unsigned Double Precision Integer (UINT32)
Page 117 · click to enlarge
Page 117

Data Types

Data Types

The MultiRanger parameters do not always use integers to hold values. For the convenience of the programmer, those values are converted to and from a 16-bit integer number. This section describes the conversion process. The sections that follow describe where those values are in the discrete I/O and block transfer addresses, and how to get the parameters you need.

Numeric Values

Numeric parameter values are the most common. For example, parameter P920 (Reading) returns a number that represents the current reading (either level or volume, depending on the MultiRanger configuration).

Numeric values are requested or set in units or percent of span, and may be specified with a number of decimal places.

Numeric values must be in the range –20,000 to +20,000 to be valid. If a parameter is requested and its value is more than +20,000, the number 32,767 is returned; if it is less than –20,000, the number –32,768 is returned. If this overflow happens, decrease the number of decimal places.

If a parameter cannot be expressed in terms of percent of span, or has no meaningful value, the number 22,222 is returned. Try requesting the parameter in units, or refer to P005 in the Parameter Reference section on page 122.

Bit Values

Bits are packed into registers in groups of 16 bits (1 word). In this manual, the bits are numbered from 1 to 16, with bit 1 as the least significant bit (LSB) and bit 16 as the most significant bit (MSB).

16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 MSB LSB

Unsigned Double Precision Integer (UINT32)

Large numbers are put into unsigned 32 bit integers. By default, they are set up so that the first word (register) is the most significant word (MSW) and the second word (register) is the least significant word (LSW).

Page 118 of the Siemens 200 user manual — One example is P807, Transducer Noise, where:
Page 118 · click to enlarge
Page 118

For example, if R41,442 is read as a UINT32, the 32 bits would look like this:

R41,442 R41,443

Data Types

16 MSW 1 16 LSW 1

32 32-bit integer value (UINT32) 1

The two registers are read as a 32-bit integer.

The most significant word (MSW) and least significant word (LSW) can be reversed to accommodate some Modbus drivers. See Word Order (R40,062) on page 98 for details.

The position of the decimal place is dependent on the register. For more details see the description of the register.

Split Values

Certain parameters are actually a pair of numbers separated by a colon, using this format: xx:yy.

One example is P807, Transducer Noise, where:

xx = the average noise value in dB

yy = the peak noise in dB

The number which corresponds to xx:yy, either for reading or setting a parameter, is determined by the following formula:

For storing to the device:

value = (xx + 128) x 256 + (yy + 128)

For reading from the device:

xx = (value / 256) – 128 yy = (value % 256) – 128 where % is the modulus operator.

The modulus can be computed by following these steps:

value1 = value / 256 value2 = remainder of value1 value3 = value2 x 256 yy = value3 – 128

It may simplify Parameter to notice:

xx = (most significant byte of value) – 128 yy = (least significant byte of value) – 128

Page 119 of the Siemens 200 user manual — Data Types
Page 119 · click to enlarge
Page 119

Text Messages

If a device parameter returns a text message, that message is converted to an integer and provided in the register. The numbers are shown in the following table:

Data Types

Number Text Message as displayed on LCD 22222 Invalid value 30000 Off 30001 On 30002 ≡ 30003 (parameter does not exist) 30004 Err 30005 Err1 30006 Open 30007 Short 30008 Pass 30009 Fail 30010 Hold 30011 Lo 30012 Hi 30013 De 30014 En 30015 (parameter has not been set) -32768 Value is less than –20,000 32767 Value is greater than 20,000

Page 120 of the Siemens 200 user manual — MultiRanger 200
Page 120 · click to enlarge
Page 120

Relay Function Codes (P111 Only)

Please note that the MultiRanger 200 offers more function codes.

Data Types

If a device parameter returns a relay function code, that message is converted to a number and is then provided in the register. The numbers are shown in the following table:

MultiRanger 100

Control Relay Function Code Number P111 General OFF, relay not used 0 0 Undesignated Level Alarm 1 1 Low-Low Level Alarm 2 1 – LL Low Level Alarm 3 1 – L High Level Alarm 4 1 – H High-High Level Alarm 5 1 – HH Loss of Echo (LOE) Alarm 20 6 Transducer Cable Fault Alarm 16 7 Pump Fixed Duty Assist 25 50 Alternate Duty Assist 30 52 Control Communication 66 65

MultiRanger 200

Control Relay Function Code Number P111 General OFF, relay not used 0 0 Undesignated Level Alarm 1 1 Low-Low Level Alarm 2 1 – LL Low Level Alarm 3 1 – L High Level Alarm 4 1 – H High-High Level Alarm 5 1 – HH In Bounds Alarm 6 2 Out of Bounds Alarm 9 3 Rate of Level Change Alarm 12 4 Temperature Alarm 15 5 Loss of Echo (LOE) Alarm 20 6 Transducer Cable Fault Alarm 16 7 Pump Totalizer 22 40 Flow Sampler 23 41 Fixed Duty Assist 25 50 Fixed Duty Backup 26 51 Alternate Duty Assist 30 52 Pump (con’t)

Alternate Duty Backup 31 53 Service Ratio Duty Assist 35 54 Service Ratio Duty Backup 36 55 First In First Out (FIFO) 40 56 Control Flush Valve 65 64 Communication 66 65

See P111 on page 134 of theParameter Reference section.

Page 121 of the Siemens 200 user manual — OR
Page 121 · click to enlarge
Page 121

Error Handling

Modbus Responses

When polled by a Modbus Master, a slave device will do one of the following:

1. Not reply. This means that something went wrong with the transmission of the message.
2. Echo back the command with the correct response (see the Modbus specification

for more details). This is the normal response.

3. Return an Exception Code. This reflects an error in the message.

Error Handling

MultiRanger uses the following exception codes:

Code Name Meaning 01 Illegal Function The function code received in the query is not an allowable action for the slave. 02 Illegal Data Address The data address received in the query is not an allowable address for the slave. 03 Illegal Data Value A value contained in the query data field is not an allowable value for the slave.

Error Handling

Errors can be traced to two general sources:

1. There is an error in transmission.

OR

2. The host tries to do something that is not a valid action.

In the first case, the MultiRanger does not respond and the master waits for a response time out error, which causes the master to re-send the message.

In the second case, the response depends on what the host tries to do. In general, MultiRanger will not give an error to the host request. Various actions and the expected outcome are as follows:

  • If the host reads an invalid register, the host will get an undetermined value back.
  • If the host writes an invalid register (a non-existing parameter or a read only parameter), the value will be ignored and no error response will be made. However, the current value will not reflect the desired new value.
  • If the host writes a read only register, then the value will be ignored and no error response will be made. However, the current value will not reflect the desired new value.
  • If P000 is activated, then the value will be ignored and no error response will be made. However, the current value will not reflect the desired new value.
Page 122 of the Siemens 200 user manual — Error Handling
Page 122 · click to enlarge
Page 122
  • If the host attempts to write one or more registers that are out of range, an exception response code 2 or 3 is generated, depending if the start address is valid.
  • If the host used an unsupported function code, an exception response code of 01 should be generated. However, this is not guaranteed and there may be no response.

Error Handling

Page 123 of the Siemens 200 user manual — Communications
Page 123 · click to enlarge
Page 123

Communication Troubleshooting

Generally

1. Check the following:
  • There is power at the unit
  • The LCD is showing the relevant data
  • The device can be programmed using the hand programmer
2. Check the wiring pin outs and verify that the connection is correct.
3. Verify that values in the set-up parameters (P770 to P779) match the settings in the

computer used to communicate with the unit.

4. Check that the port on the computer is correct. Sometimes trying a different Modbus

driver will solve the problem. An easy stand-alone driver called ModScan32 is available from Win-Tech at www.win-tech.com This driver is helpful for testing communications.

Specifically

Communications

1. The MultiRanger is set to communicate via a modem but no communication is returning to the master.
  • Check that the parameters are set up correctly and that the correct port is configured
  • Verify the wiring diagram. Note that there is a difference between wiring directly to a computer and wiring to a modem.
  • Verify that the modem is set up correctly. Siemens Milltronics has a series of Application Guides that may help. Please contact your local Siemens Milltronics representative for more information on Application Guides. 2. A MultiRanger parameter is set via remote communications, but the parameter

remains unchanged.

  • Some parameters can only be changed when the device is not scanning. Try putting the device in program mode, using the operating mode function.
  • Try setting the parameter from the keypad. If it can not be set using the keypad, check the lock parameter and set it to 1954.
Page 124 of the Siemens 200 user manual — Communication Appendix A
Page 124 · click to enlarge
Page 124

Communication Appendix A: Single Parameter Access (SPA)

This Appendix is intended to provide someone with advanced communications knowledge the ability to access any parameter value in any available format.

Built into MultiRanger is an advanced handshaking area that can be used to read and write single registers to the MultiRanger. This section performs a similar function to the Parameter access section. The differences are:

1. Advanced section is more powerful and harder to program.
2. Advanced section only gives you access to one parameter at a time.

Mapping

Parameter Read and Write (40,090 – 40,097) is a series of eight registers used for reading and writing parameter values to and from the MultiRanger. The first three registers are always unsigned integers representing parameters and index values. The second five registers are the format and value(s) of the parameter.

All parameters normally accessed through the hand-held programmer are available through these registers.

Address Description 40,090 Parameter (integer) 40,091 Primary Index (integer) 40,092 Secondary Index (integer) 40,093 Format word (bit mapped) 40,094 Read value, word 1 40,095 Read value, word 2 40,096 Write value, word 1 40,097 Write value, word 2

Communication Appendix A

Reading Parameters

To read parameters through Modbus do the following steps:

1. Send the parameter, its primary index, and its secondary index (usually 0), and format to registers 40,090 to 40,093.
2. Wait until you can read the written values from the registers (40,090 to 40,093) to

confirm that the operation is complete.

3. Read the value from registers 40,094 and 40,095.
Page 125 of the Siemens 200 user manual — Communication Appendix A
Page 125 · click to enlarge
Page 125

Writing Parameters

To set parameters through Modbus do the following steps:

1. Send the parameter, its primary index, and its secondary index (usually 0) to registers 40,090, 40,091, and 40,092.
2. Write the value to registers 40,096 and 40,097.
3. Write the desired format word to register 40,093 to enable the MultiRanger to

interpret the value correctly.

Format Register

Bits Values Description 1-8 0-2 Error Code 9-11 0-7 3-bit number representing decimal offset 12 0/1 direction of offset (0 = right, 1 = left) 13 0/1 Numeric format: Fixed (0) or Float (1) 14 0/1 Read or Write of data, Read (0), Write (1) 15 0/1 Word order: Most Significant Word first (0), Least Significant Word first (1) 16 Reserved

For example, to format the level reading so that it is shown in percent with two decimal places shifted left, the format bits would look like this:

Bit Numbers 16 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01

Bit Values 0 1 0

offset direction to right

Communication Appendix A

decimal offset of 2

The value sent to the MultiRanger is 0001001000000000 binary or 512 decimal. The value 512 is sent as an integer to register 40,093 to format the output words 40,094 and 40,095 accordingly.

If the numeric data type is set for integer and the value contains decimal places, they are ignored. In this situation, use the decimal offset to ensure that you have an integer value and then write your code to recognize and handle the decimal offset.

Show 5 more labels / short text on this page
most significant first · no error code · fixed format · reserved · read
Page 126 of the Siemens 200 user manual — Communication Appendix A
Page 126 · click to enlarge
Page 126

Error Codes

The error codes returned in the format area are 8-bit integers found in the lowest eight bits of the format word. This allows for 256 potential error codes.

Currently the MultiRanger has two error codes available.

Values Description 0 No error 1 Data not available as percent (available as units) 2-255 Reserved

Communication Appendix A

Page 127 of the Siemens 200 user manual — Accessing a Secondary Index
Page 127 · click to enlarge
Page 127

Parameter Reference

The MultiRanger is configured through its parameters, and the application determines the parameter values which are entered into the unit.

Please check your value entries carefully before operating the MultiRanger to ensure optimum performance.

MultiRanger 100 and MultiRanger 200

All MultiRanger 100 and MultiRanger 200 parameters are listed in this section. MultiRanger 200 parameters are identified separately. The parameter title includes this marking [MR 200], indicating that parameter applies to the MultiRanger 200 only.

As a general rule, parameters affecting volume apply only to the MultiRanger 200.

Helpful Hints

Please note the following:

  • Default values are always indicated with an asterix (*)
  • Global values are common for all inputs and outputs on the unit
  • Indexed parameters can apply to more than one input or output
  • Primary index relates to an input or output
  • Secondary index allows for multiple values on an indexed point

Accessing a Secondary Index

1. Press MODE , and then press DISPLAY to activate secondary index.

The icon appears under the index field. 2. Enter the secondary index, and then enter the values to set the secondary index.

Page 128 of the Siemens 200 user manual — Table of Contents
Page 128 · Contents
Contents

Contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 129 of the Siemens 200 user manual — Primary Index Single Point Model Dual Point Model
Page 129 · click to enlarge
Page 129

P000 Lock

  • Notes:
  • This lock only applies to the handheld programmer: it does not lock access through communications.
  • A remote master can change configuration if P799 is set to allow this.

Secures the MultiRanger from changes via the handheld programmer.

1954 * OFF (programming permitted)

-1 Simulation Controls (relays energize based on simu- lated level)

other lock activated (programming secured)

Related • Simulation on page 85

Access this parameter directly (type 000) and enter any value (except 1954) to secure programming lock. To unlock the MultiRanger, access this parameter and enter 1954.

Quick Start (P001 to P007)

P001 Operation

Sets the type of measurement required for the application.

Primary Index Single Point Model Dual Point Model

1 Level – how full the vessel is (MR 200: volume – P050)

2 Space – how empty the vessel is (MR 200: ullage – P050)

3 * Distance – distance from transducer to material

4 DPD – dual point difference [MR 200]

5 DPA – dual point average [MR 200]

6 OCM – flow rate in an open channel [MR 200]

7 Pump Totalizer – total pumped volume [MR 200]

Alters • P600 Primary Measuring Device

Show 5 more labels / short text on this page
Primary Index Global · Values · Global Transducer · 0 Out-of-service · Values
Page 130 of the Siemens 200 user manual — Primary Index Single Point Model Dual Point Model
Page 130 · click to enlarge
Page 130

For DPD and DPA Programming [MR 200]

Please note that this feature is only available on the MultiRanger 200.

Single Point Model Use

For Dual Point Difference (DPD) or Dual Point Average (DPA), the unit requires either two transducers of the same type, or one transducer and one mA input. If two transducers are used, all transducer parameters become indexed, and a third level point is calculated.

  • DPD (difference) = Point 1 - Point 2
  • DPA (average) = (Point 1 + Point 2) / 2. The calculated DPD or DPA is always based on level measurements of points 1 and 2. For these operations any of three level points (transducer 1, transducer 2, or the calculated point) can be used to trigger relays (see P110 Level Source on page 134).

The points must be globally set to either 4 or 5 (as required). Point 3 becomes the calculated value as shown above. See Rake Control example on page 69.

Dual Point Model Use

To set a dual point MultiRanger for DPA or DPD functions, Point 3 must be set to either 4 or 5 (as required). Points 1 and 2 cannot be set to 4 or 5, but these points are used to calculate the value in point 3.

This table shows the available functions:

Operation [index] Available Values

P001 [1] 1, 2, 3, 6, 7

P001 [2] 1, 2, 3, 6, 7

P001 [3] 4,5

P002 Material

Specifies material type.

Primary Index Single Point Model Dual Point Model

Values 1 * Liquid or horizontal solid surface

2 Solid or angled surface

Alters • P830 TVT Type

Global Transducer

Page 131 of the Siemens 200 user manual — P004 Transducer
Page 131 · click to enlarge
Page 131

P003 Maximum Process Speed

Determines level change reaction.

1 Slow (0.1 m/min)

2 * Medium (1 m/min)

3 Fast (10 m/min)

  • P070 Failsafe Timer
  • P700 Max Fill Rate
  • P701 Max Empty Rate
  • P702 Filling Indicator
  • P703 Emptying Indicator
  • P704 Rate Filter
  • P710 Fuzz Filter
  • P713 Echo Lock Window
  • P727 Scan Delay
  • P841 Long Shot Number
  • Failsafe (P070 to P072)
  • P121 Pump by Rate
  • Rate (P700 to P708)
  • Measurement Verification (P710 to P713)
  • Transducer Scanning (P726 to P729)
  • P905 Transmit Pulse

Use a setting just fast enough to keep up with your process. Slower settings provide higher accuracy. Faster settings allow for more level fluctuations.

P004 Transducer

Specifies the Siemens Milltronics transducer connected to the unit.

Primary Index Single Point Model Dual Point Model Global Transducer

0 * No transducer attached (preset for Dual Point) 1 ST-25 2 ST-50 100 STH 101 XCT-8 102 * XPS-10 (preset for Single Point Model) 103 XCT-12 104 XPS-15 112 XRS-5 250 mA input [MR 200]

(chart con’t next page)

Show 5 more labels / short text on this page
Primary Index Transducer · Values · Alters · Related · Values
Page 132 of the Siemens 200 user manual — P006 Empty
Page 132 · click to enlarge
Page 132
  • P203 mA Output Value/Transducer
  • mA Input (P250 to P260) (related only to Value 250)
  • P800 Near Blanking
  • P823 Reform Echo
  • P832 TVT Shaper Adjust
  • P840 Short Shot Number
  • P841 Long Shot Number
  • P842 Short Shot Frequency
  • P843 Long Shot Frequency
  • P844 Short Shot Width
  • P845 Long Shot Width
  • P852 Short Shot Range

Related (chart cont’d from previous page)

P005 Units

Specifies measurement units used for dimensional values.

  • P006 Empty
  • P007 Span
  • P603 Maximum Head
  • P605 Zero Head
  • P620 Low Flow Cutoff
  • P921 Material Measurement
  • P926 Head Measurement
  • P927 Distance Measurement

Changing this value automatically changes the units displayed for many parameters. Existing values are converted and do not have to be re-entered.

P006 Empty

Enter distance in units (P005) from the face of the transducer to the process empty point.

Values Range0.000 to 99.000 m (or equivalent depending on units)
Preset5.000 m (or equivalent depending on units)

Alters • P007 Span

Altered By • P005 Units

  • P800 Near Blanking
  • P921 material Measurement
  • P927 Distance Measurement

Setting this value also sets Span (P007) unless Span was already set to another value. For distance operation (P001=3), Span is preset to Empty.

Show 10 more labels / short text on this page
Primary Index Global · 1 * Meters · 2 Centimeters · Values · 3 Millimeters · 4 Feet · 5 Inches · Alters · Primary Index Transducer · Related
Page 133 of the Siemens 200 user manual — Volume (P050 to P055) [MR 200]
Page 133 · click to enlarge
Page 133

P007 Span

Sets the range levels to be measured.

Values Range0.000 to 99.000 m (or equivalent depending on units)
Presetbased on Empty (P006)
  • P605 Zero Head
  • P112 Relay ON Setpoint
  • P113 Relay OFF Setpoint
  • Altered By
  • P005 Units
  • P006 Empty
  • Volume (P050 to P055)
  • P800 Near Blanking
  • P921 Material Measurement
  • P922 Space Measurement
  • P926 Head Measurement

Span is preset for a value close to the maximum available. Enter a value reflecting maximum application range.

Always prevent the monitored surface from approaching within 0.3 m (1 ft) of the transducer face as this is the minimum blanking for most Siemens Milltronics transducers (some require more blanking – see your transducer manual).

Many other parameters are set as a percentage of span (even if they are entered in units). The values of these other parameters may change if the span is altered after installation and the other parameters are measured using a level determined upward from the Empty level toward the transducer face.

MultiRanger 200

All volumes are based on span so it should be set for the maximum volume point if volume calculations are needed.

Volume (P050 to P055) [MR 200]

Please note that the volume parameters apply only to the MultiRanger 200.

Use these parameters to enable the MultiRanger to show readings based on vessel or wet well volume (rather than level)..

Primary Index Level · Alters · Related

Page 134 of the Siemens 200 user manual — P050 Tank Shape [MR 200]
Page 134 · click to enlarge
Page 134

P050 Tank Shape [MR 200]

Enter the Tank Shape value matching the monitored vessel or wet well.

When Operation is LEVEL (P001 = 1), liquid (material) volume is calculated.

Alternatively, when Operation is SPACE (P001 = 2), remaining vessel capacity is calculated. In RUN mode, readings are displayed in percent of maximum volume. To convert readings to volumetric units, see Maximum Volume (P051).

Siemens 200 — P050 Tank Shape [MR 200] diagram (page 134)
Fig. 48 · P050 Tank Shape [MR 200]
Page 135 of the Siemens 200 user manual — P051 Maximum Volume [MR 200]
Page 135 · click to enlarge
Page 135
Siemens 200 — Volume (P050 to P055) [MR 200] diagram (page 135)
Fig. 49 · Volume (P050 to P055) [MR 200]
  • P001 Operation
  • P051 Maximum Volume
  • Pump Efficiency (P180-P186)
  • Pumped Volume Totalizer (P622-P623)
  • P920 Reading Measurement

P051 Maximum Volume [MR 200]

For Readings in volumetric units (rather than percent), enter the equivalent vessel volume for Span (P007).

Siemens 200 — P051 Maximum Volume [MR 200] diagram (page 135)
Fig. 50 · P051 Maximum Volume [MR 200]
  • P006 Empty
  • P007 Span
  • P924 Volume Measurement

Any volume units can be chosen because volume is calculated from empty to maximum span and is scaled according to the Tank Shape (P050) value.

Siemens 200 — P051 Maximum Volume [MR 200] diagram (page 135)
Fig. 51 · P051 Maximum Volume [MR 200]
  • If max. volume = 3650 m 3 , enter 3650
  • If max. volume = 267500 gallons, enter 267.5 (thousands of gallons)
Page 136 of the Siemens 200 user manual — P054 Level Breakpoints (Universal Volume Calculation)
Page 136 · click to enlarge
Page 136

P052 Tank Dimension A [MR 200]

Dimension A as used in P050 Tank Shape.

Values Range0.0 to 99.00 m (or equivalent depending on units)
Preset0.000

Related • P050 Tank Shape

Enter one of the following:

  • height of the tank bottom if P050 = 2,3,4, or 5

OR

  • length of one end section of the tank if P050 = 7, in Units (P005)

P053 Tank Dimension L [MR 200]

Dimension L as used in P050 Tank Shape.

Values Range0.0 to 99.00 m (or equivalent depending on units)
Preset0.000

Related • P050 Tank Shape

Enter the following:

  • tank length (excluding both end sections) if P050 = 7

P054 Level Breakpoints (Universal Volume Calculation)

[MR 200]

When the tank shape is too complex for any of the preconfigured shapes, you can specify the volume based on segments. See “Accessing a Secondary Index” on page 117 for more information.

Values Range0.0 to 99.00 m or Max. volume (P051) (or equivalent depending on units)

Related • P055 Volume Breakpoints

Enter the following:

  • up to 32 level breakpoints (where volume is known) if P050 = 9 or 10 Entering a Level Breakpoint
1. Go to Parameter P054. 2. For each index enter a breakpoint in measurement units. 3. Ensure that each breakpoint corresponds to the same index for P055.
Show 4 more labels / short text on this page
Primary Index Level · Primary Index Level · Primary Index Level · Secondary Index Breakpoint
Page 137 of the Siemens 200 user manual — P060 Decimal Position
Page 137 · click to enlarge
Page 137

P055 Volume Breakpoints and Characterization

(Universal Volume Calculation) [MR 200]

Each segment defined by the level breakpoints (P055) requires a volume so that the MultiRanger can make the level-to-volume calculations.

Siemens 200 — P055 Volume Breakpoints and Characterization diagram (page 137)
Fig. 52 · P055 Volume Breakpoints and Characterization

Typical volume calculations

V = (1/3)πr2h V = πr2h

Entering a Volume Breakpoint

1. Go to Parameter P055. 2. For each index enter a volume. 3. Ensure that each volume corresponds to the same index for P054.

For more on Volume Characterization, go to page 52.

Display and Reading (P060 to P062)

These parameters are used to:

  • Change the number of decimal places displayed
  • Convert the Reading to alternate units
  • Reference measurements to other than Empty (P006) or Span (P007)

P060 Decimal Position

Siemens 200 — P060 Decimal Position diagram (page 137)
Fig. 53 · P060 Decimal Position

Defines the maximum number of decimal places used on the LCD.

3 3 digits after the decimal point (limited by device resolution)

Cone Cylinder

Page 138 of the Siemens 200 user manual — P062 Offset Reading
Page 138 · click to enlarge
Page 138

Alters • P607 Flowrate Decimal

Altered by • P051 Maximum volume

Related • P920 Reading Measurement

In RUN mode, the decimal position adjusts to prevent the number of digits from exceeding the display capabilities. To keep the decimal place from shifting, reduce the number of decimal places to that shown at 100%.

Example:

If 100% is 15m, use two decimal places for sample readings of 15.00 or 12.15.

P061 Convert Reading [MR 200]

Multiplies the current value by the specified amount to allow for scaling.

Values Range-999 to 9999
Preset1.000

Related • P920 Reading Measurement

Examples:

  • If the measured value is in feet, enter 0.3333 to display the number of yards
  • For simple linear, volume conversions set POO5 to 1 (meters) and then enter the volume measurement per unit to get the correct conversion. For example, if the reservoir contains 100 litres per vertical meter, use 100 to get the reading in litres.
  • Notes:
  • This method does not calculate volume. It must not be used in place of the volume parameters if any volume dependent features (such as pump efficiency) are used. To calculate true volumes see Volume (P050 to P055).
  • Avoid entering a value that, when multiplied by the maximum current Reading, exceeds the display capabilities. If value exceeds four digits, EEEE is shown.

P062 Offset Reading

Adds the specified value to the level reading, usually to reference the reading to sea level or another datum level.

Values Range-999 to 9999
Preset0.000

Related • P920 Reading Measurement

The operation of the device is not affected by the Offset Reading. This value is used for display purposes only. All control measurements are still referenced to Empty.

Primary Index Level · Primary Index Level

Page 139 of the Siemens 200 user manual — P065 Reading Override Value
Page 139 · click to enlarge
Page 139

Backup Level Override

Use this feature to override the ultrasonic reading by a discrete input such as a contacting point device. The ultrasonic reading will be fixed at the programmed switch level until the discrete input is released.

The ultrasonic device makes decisions based on the override values.

P064 Reading Override Enable

Sets the discrete input to act as the source for a level reading override.

Values 0 * OFF: No override.

1-2 ONNumber = discrete input of override signal
  • Related
  • P065 Reading Override Value
  • P270 Discrete Input Function

P065 Reading Override Value

This value is substituted for the current reading when the selected discrete input is enabled and activated.

Values Range0.0 to 99.00 m (or equivalent depending on units)
Preset0.00
  • P001 Operation
  • P005 Units
  • P006 Empty
  • P007 Span
  • P064 Override Enable
Show 4 more labels / short text on this page
Primary Index Transducer · Primary Index Transducer · Alters Current reading · Related
Page 140 of the Siemens 200 user manual — P069 Password
Page 140 · click to enlarge
Page 140

Please note the following:

  • enter value in current units (as selected in P005)
  • valid for level, space, and distance
  • volume is calculated based on the Backup level

Example:

Transducer One is configured for a level measurement. Digital Input 2 is connected to a Hi Level Backup switch located a level of 4.3m.

Parameter Index Value

P064 1 2

P065 1 4.3

When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m. The reading stays at 4.3m until the switch is de-activated.

P066 Override Time Delay

Defines the time used to calm (debounce) the override condition input. Set in seconds.

Values Range0.0 to 9999 Preset: 5.0
  • P064 Override Enable
  • P065 Reading Override Value
  • P270 Discrete Input Function

P069 Password

Holds the current password for P000. Select by typing in 069. You cannot scroll to this parameter.

Values Range0 to 9999 Default: 1954

Related • P000 Lock

This parameter is write-only, and can only be selected by entering 069. To change the password, unlock the device by entering the current password into P000. Then enter the new password into P069. To lock the device, enter a password other than the correct one in P000. While the device is unlocked, the password is visible in P000.

Primary Index Transducer · Related · Primary Index Global

Page 141 of the Siemens 200 user manual — P071 Failsafe Material Level
Page 141 · click to enlarge
Page 141

Failsafe (P070 to P072)

P070 Failsafe Timer

The time for invalid measurements to elapse before Failsafe State activates.

Primary Index Single Point Model Dual Point Model

Values Range0 to 15 minutes

Preset 10.00 minutes

Altered by • P003 Maximum Process Speed

Related • P129 Relay Failsafe

Once activated, the Failsafe State initiates the following:

  • 1. The material level is reported based on P071 Failsafe Material Level.
  • The unit responds to the new level as programmed (control and alarm relays activate as defined by the programming).
  • Individual relays can have independent failsafe responses. See P129 Relay Failsafe. 2. The appropriate error is displayed:
  • LOE for loss of echo from the transducer
  • Short for a shorted transducer cable
  • Open for a cut transducer cable
  • Error for all other problems

When modifying the preset value, set it short enough to protect the process but long enough to avoid false alarms. Only use No Delay (0.0 Minutes) for testing.

P071 Failsafe Material Level

The material level reported when a Failsafe State is initiated.

Range-4999

Value in units or % (-50% to 150% of span)

HI Level goes to maximum span

LO Level goes to 0 span (Empty)

HOLd * Level remains at last reading

  • P001 Operation
  • P006 Empty
  • P007 Span
  • P111 Relay Control Function
  • P112 Relay ON Setpoint
  • P113 relay OFF Setpoint
  • P129 Relay Failsafe

Select the Failsafe Material Level based upon the relay operation required during failsafe operation.

Show 5 more labels / short text on this page
Global Transducer · Primary Index Level · to 9999 · Values · Related
Page 142 of the Siemens 200 user manual — Preset Applications (P100)
Page 142 · click to enlarge
Page 142

Selecting HI, LO, or HOLd

1. Press FUNCTION to display the Auxiliary Function symbol.
2. Press ARROWS to scroll to the desired option.
3. Press ENTER to set the value.

Entering a Measurement

To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units (P005).

Relay reaction

The way in which relay programming reacts to the failsafe level depends on P129 Relay Failsafe (page 140). By default:

  • Alarm relays have P129 = OFF and so react to the Failsafe Material Level.
  • Control relays have P129 = dE and so de-energize the relay when the unit enters Failsafe mode regardless of the Failsafe Material Level.

P072 Failsafe Level Advance

Sets the speed the MultiRanger advances to and returns from the Failsafe Material Level.

1 * Restricted Advances to/from Failsafe Material Level as set by P003, P700 and P701.

2 Immediate Failsafe Material Level assumed right away

3 Fast Back Failsafe Level Advance is restricted, return is immediate

  • P003 Maximum Process Speed
  • P070 Failsafe Timer
  • P071 Failsafe Material Level
  • P700 Max Fill rate
  • P701 Max Empty rate

Relays (P100 to P119)

The MultiRanger has three or six relays (or digital outputs) used to control devices and alarms. While the number of devices is limited by the relays, all control functions are accessible through software and each parameter is indexed to the three or six relays. See the Relay section on page 41.

Preset Applications (P100)

The MultiRanger makes standard applications easier to program by providing an extensive list of presets.

Primary Index Level · Values · Related

Page 143 of the Siemens 200 user manual — 0 * OFF
Page 143 · click to enlarge
Page 143

Control Functions (P111)

Each relay can be configured independently to take advantage of the MultiRanger’s advanced features and flexibility. Start with a preset application and then change the required parameters to make the task more efficient.

Setpoints (P112, P113)

Each relay is triggered by one or more setpoints. The setpoints can be based on absolute level (P112, P113) or rate of change (P702, P703). Each control function specifies which setpoints are required.

P100 Preset Applications [MR 200]

Six preset applications to configure or bench test the unit.

0 * OFF

1 Wet Well 1

2 Wet Well 2

  • P110 Level Source
  • P111 Relay Control Function
  • P112 Relay On Setpoint
  • P113 Relay OFF Setpoint
  • P121 Pump by Rate

Related • P001 Operation

Select an application that is similar to yours and change the parameters required. If none suit, then refer to P111 Relay Control Function on page 134.

Show 7 more labels / short text on this page
Primary Index Global · Values · 3 Reservoir 1 · 4 Reservoir 2 · 5 Screen · 6 Alarms · Alters
Page 144 of the Siemens 200 user manual — P111 Relay Control Function
Page 144 · click to enlarge
Page 144

P110 Level Source

Sets the level source on which the indexed relay is assigned to a measurement point.

Please note that Difference and Average settings are MultiRanger 200 features.

Range1 to 3

1 * Point # 1 = Transducer One

2 Point # 2 = Transducer Two

3 [MR 200]

Point # 3 = Difference (P001=4) or Average (P001=5) [MR 200]

  • P003 Maximum Process Speed
  • P700 Max Fill rate
  • P701 Max Empty rate
  • P070 Failsafe Timer
  • P071 Failsafe Material Level

Altered by:

MultiRanger 200

Please note that these features are only available on the MultiRanger 200.

In Single Point Mode (standard):

Points 2 and 3 are available only if Operation is set for difference or average (P001 = 4 or 5).

In Dual Point Mode (optional):

Point 2 is always available, and Point 3 is available only if Operation is set for difference or average (P001 = 4 or 5).

P111 Relay Control Function

Sets the control algorithm used to trip the relay.

Please note that parameter P111 values vary between the MultiRanger 100 and the MultiRanger 200.

Values See chart below

Altered by • P100 Preset Applications

Use zero 0 (preset) to disable control of the indexed relay.

Primary Index Relay · Values · Primary Index Relay

Page 145 of the Siemens 200 user manual — MultiRanger 200
Page 145 · click to enlarge
Page 145

MultiRanger 100

Values For P111 Control Type # 1

Relay Control

OFF 0* Relay set off, no action (preset) Level 1 Based on level setpoints ON and OFF Loss of Echo (LOE) 6 When echo is lost Cable Fault 7 When the circuit to a transducer is opened

Pump Fixed Duty Assist 50 At fixed ON and OFF setpoints and allows multiple pumps to run Alternate Duty Assist 52 At rotating ON and OFF setpoints and allows multiple pumps to run

Communication 65 Based on input from external communications. See Communications section on page 89 for further refer- ence.

1. When reading and setting this parameter through Modbus or SmartLinx communications the parameter values are mapped to different numbers. See MultiRanger Communications on page 89 for Modbus information or the relevant SmartLinx ® manual.

MultiRanger 200

Values For P111 Control Type # 1 Relay Control

Off 0* Relay set off, no action (preset) Level 1 Based on level setpoints ON and OFF

In Bounds 2 When level enters the range between ON and OFF setpoints

Out of Bounds 3 When level exits the range between ON and OFF set- points Rate of Change 4 Based on rate setpoints ON and OFF Temperature 5 Based on temperature setpoints ON and OFF Loss of Echo (LOE) 6 When echo is lost Cable Fault 7 When the circuit to a transducer is opened

Flow Totalizer 40 Every 10y units (P641-P645) Flow Sampler 41 Every y x 102 units (P641-P645) or time duration (P115)

General · General

Page 146 of the Siemens 200 user manual — P112 Relay ON Setpoint
Page 146 · click to enlarge
Page 146

Values For P111 Control Type # 1 Relay Control

Fixed Duty Assist 50 At fixed ON and OFF setpoints and allows multiple pumps to run or for rake control

Fixed Duty Backup 51 At fixed ON and OFF setpoints and allows only one pump to run Alternate Duty Assist 52 At rotating ON and OFF setpoints and allows multiple pumps to run Alternate Duty Backup 53 At rotating ON and OFF setpoints and allows only one pump to run Service Ratio Duty Assist 54 On service ratio at ON and OFF setpoints and allows multiple pumps to run Service Ratio Duty Backup 55 On service ratio at ON and OFF setpoints and allows only one pump to run First In First Out (FIFO) 56 As Alternate Duty Assist, resets the relay from stag- gered OFF setpoints

Flush Valve 64 Used to control a pump flushing device based on Flush Systems (P170 to P173)

Communication 65 Based on input from external communications. See Communications section on page 89 for further refer- ence.

1. When reading and setting this parameter through Modbus or SmartLinx communications the parameter values are mapped to different numbers. See the MultiRanger Communications section on page 89 for Modbus information or the relevant SmartLinx ® manual.

P112 Relay ON Setpoint

Sets the process point at which the relay changes from its NORMAL state.

Values Range-999 to 9999
Preset----

Altered by • P007 Span

  • P100 Preset Applications
  • P111 Relay Control Function
  • P113 Relay OFF Setpoint

For most applications, the relay is tripped at this point. For IN-BOUNDS and OUT-OF- BOUNDS alarms, it is the high point in the specified range. This parameter is set according to Span (P007) even when another reading, such as volume, is shown on the LCD.

Show 4 more labels / short text on this page
Pump · Control · Primary Index Relay · Related
Page 147 of the Siemens 200 user manual — P116 Dead Band [MR 200]
Page 147 · click to enlarge
Page 147

P113 Relay OFF Setpoint

Sets the process point at which the relay returns to its NORMAL state.

Values Range-999 to 9999
Preset----

Altered by • P007 Span

  • P100 Preset Applications
  • P111 Relay Control Function
  • P112 Relay ON Setpoint

For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF- BOUNDS alarms, it is the low point in the specified range. This parameter is set to Span (P007), even when another reading, such as volume, is shown on the LCD.

P115 Relay Interval Setpoint [MR 200]

The length of time in hours between starts.

Values Range0 to 9000 hours
Preset0.000

Altered by • P100 Preset Applications

Related • P111 Relay Control Function

P116 Dead Band [MR 200]

The distance above and below the bound alarm setpoints.

Values Range0.000 to Span Value (P007), or equivalent depending on units
Preset2% of span
  • P111 Relay Control Function
  • P112 Relay ON Setpoint
  • P113 Relay OFF Setpoint
Show 5 more labels / short text on this page
Primary Index Relay · Related · Primary Index Relay · Primary Index Relay · Related
Page 148 of the Siemens 200 user manual — Relay States
Page 148 · click to enlarge
Page 148

For IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a dead band prevents relay chatter due to material level fluctuations at both the upper and lower setpoints.

Enter the dead band in either percent of span or units of measure (P005). The dead band value is applied both above and below the upper and lower bound setpoints as shown in the fig- ure.

Actual ON or OFF setpoint

P116

Setpoint set in P112 or P113

P116

Actual OFF or ON setpoint

P118 Relay Output Logic

The logic applied to relays to determine the contact open or closed state.

Value Logic Alarm Contact

Pump or Control

Contact

2 * Positive Normally Closed Normally Open

3 Negative Normally Open Normally Closed

Related • P111 Relay Control Function

The relay contact operation is NORMALLY CLOSED for alarms and NORMALLY OPEN for controls. See P111 Relay Control Function for more information.

Power Failure

When power is cut to the MultiRanger, its relays fail to the following states:

Relay States

3,6 Open or Closed1

1. Relays 3 and 6 are Form C types, so you can wire it either NORMALLY OPEN or NORMALLY CLOSED. Check the wiring before programming.

To use relays 3 or 6 as general alarm indicators, set P118 to 3 – negative logic and wire the alarm for normally open operation. When an alarm event occurs (see below) or when power is cut, the circuit closes and the alarm activates.

Show 4 more labels / short text on this page
Primary Index Relay · Values · Relay Fail State · 1,2,4,5 Open
Page 149 of the Siemens 200 user manual — Primary Index Single Point Model Dual Point Model
Page 149 · click to enlarge
Page 149

Positive Logic

In software, all relays are programmed the same way, with ON setpoints indicating when to change the relay contact state (open or closed). This parameter allows the reversal of the operation so that relay contacts can be NORMALLY CLOSED or NORMALLY OPEN. P118 is preset to 2 which is positive logic.

Negative Logic

When P118 = 3 (negative logic), the operation for the indexed relay is reversed from normal.

P119 Relay Logic Test

Forces the relay control logic into an ACTIVATED or DE-ACTIVATED state.

0 * OFF - Control from MultiRanger algorithms

1 Activate relay control

2 De-activate relay control

  • Related
  • P111 Relay Control Function
  • P910 Toggle Relays

This parameter tests site wiring and control logic programming. Forcing the relay to an activated or de-activated state is similar to the MultiRanger detecting an event and responding to it. Helpful in testing new installations and diagnosing control problems.

Pump Setpoint Modifiers (P121 and P122) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

These parameters provide alternate ways of starting the pumps in the pump group. See the Pump Control section on page 58 for descriptions of the pump control algorithms.

P121 Pump by Rate [MR 200]

Sets the pump relays to accept control by rate of level change once the first ON setpoint is reached.

Primary Index Single Point Model Dual Point Model

Values 0 * OFF (pump by level)

1 ON (pump by rate)

  • P007 Span
  • P111 Relay Control Function
  • P132 Pump Start Delay
  • Rate (P700 to P708)

Use this function when multiple pumps are to be controlled by rate of level change rather than by setpoints.

Show 4 more labels / short text on this page
Primary Index Relay · Values · Transducer Level · Related
Page 150 of the Siemens 200 user manual — Independent Relay Failsafe (P129)
Page 150 · click to enlarge
Page 150

The delay between pump starts is set by P132 Pump Start Delay.

This only applies to any relays set to pump control (P111 = 50 to 56).

  • Notes:
  • All pump control relay ON and OFF setpoints must be the same value
  • If the level is within 5% of Span (P007) of the OFF setpoint, the next pump is not started

P122 Pump Service Ratio [MR 200]

Selects pump usage based on the RUN time ratio rather than last used.

Values Range0.000 to 9999
Preset20.00

Related • P111 Relay Control Function

This parameter only relates to relays with P111 = 54 or 55.

To make this parameter useful, assign it to all of the pump relays. The number assigned to each pump relay represents the ratio applied to decide the next pump to start or stop.

  • Notes:
  • The MultiRanger will not sacrifice other pumping strategies to ensure that the ratio is held true
  • If the pump relays are set to the same value then the ratio equals 1:1 and all pumps are used equally (preset)

Independent Relay Failsafe (P129)

P129 Relay Failsafe

Sets how individual relays react to a failsafe condition, to allow for more flexible programming.

OFF * Response governed by P071 Failsafe Material Level

HOLd For LAST KNOWN relay state retention

dE To have the relay de-energize immediately on failsafe

En To have the relay energize immediately on failsafe

Altered by • P071 Failsafe Material Level

  • P070 Failsafe Timer
  • P111 Relay Control Function

Use this for operations independent of the Failsafe Material Level (P071).

Primary Index Relay · Primary Index Relay · Values

Page 151 of the Siemens 200 user manual — P130 Pump Run-On Interval [MR 200]
Page 151 · click to enlarge
Page 151

Relay Failsafe is only available for the following relay functions (P111) and is not used for any other relay control function.

Relay Function (P111) Preset (P129)

1. level alarm
2. in bounds alarm
3. out of bounds alarm

OFF

4. rate of change alarm
5. temperature alarm

50 to 56 – all pump controls dE

To select an independent Relay Failsafe value:

1. Press FUNCTION to display the Auxiliary Function symbol.
2. Press ARROWS to scroll through the failsafe options. 3. Select option and press ENTER .

Advanced Pump Control Modifiers (P130 to P137) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

These parameters only affect relays set to pump operation (P111 = 50 to 56).

P130 Pump Run-On Interval [MR 200]

Sets the number of hours between pump run-on occurrences.

Values Range0.000 to 1000
Preset0.000

Related • Advanced Pump Control Modifiers (P130 to P136)

To clear sediment in a pump-down wet well, run the pump after the normal OFF setpoint is reached to force some solid material through. This parameter sets the time between such events. Only the last pump running can run-on.

Primary Index Global

Page 152 of the Siemens 200 user manual — P133 Pump Power Resumption Delay [MR 200]
Page 152 · click to enlarge
Page 152

P131 Pump Run-On Duration [MR 200]

Sets the number of seconds that the pump runs on.

Range0.0 to 9999
Preset0.000

Related • Advanced Pump Control Modifiers (P130 to P136)

Your pump capacity determines the amount of material that can be removed. Choose a value long enough to clean out the vessel bottom, yet short enough not to run the pump dry. Also be sure that this value does not overlap with P130 (Interval). The timing should look something like this:

P131 P132 P130 (Pump Run-On)

P132 Pump Start Delay [MR 200]

Sets the minimum delay (in seconds) between pump starts.

Range0.0 to 9999
Preset10 seconds

Value is divided by 10 in simulation mode.

  • Related
  • Advanced Pump Control Modifiers (P130 to P136)
  • P121 Pump by Rate

Use this feature to reduce a power surge from all pumps starting at the same time. This delay determines when the next pump is permitted to start.

P133 Pump Power Resumption Delay [MR 200]

Sets the minimum delay before the first pump restarts after power failure.

Range0.000 to 9999
Preset10 seconds
  • Related
  • Advanced Pump Control Modifiers (P130 to P136)
  • P132 Pump Start Delay

This reduces the surge from the first pump starting immediately on power resumption. When this delay expires, other pumps will start as per P132.

Show 6 more labels / short text on this page
Primary Index Relay · Values · Primary Index Global · Values · Primary Index Global · Values
Page 153 of the Siemens 200 user manual — P137 Pump Group [MR 200]
Page 153 · click to enlarge
Page 153

P136 Wall Cling Reduction [MR 200]

Varies the upper and lower setpoints to reduce material buildup on the walls.

Siemens 200 — P136 Wall Cling Reduction [MR 200] diagram (page 153)
Fig. 54 · P136 Wall Cling Reduction [MR 200]

This value is the range in which the setpoints are allowed to deviate in percent or units. The Relay Setpoints ON and OFF values are randomly varied inside the range to ensure that the material level does not consistently stop at the same point.

Siemens 200 — P136 Wall Cling Reduction [MR 200] diagram (page 153)
Fig. 55 · P136 Wall Cling Reduction [MR 200]

P137 Pump Group [MR 200]

Puts pumps into groups for multiple pump rotations on one transducer.

Siemens 200 — P137 Pump Group [MR 200] diagram (page 153)
Fig. 56 · P137 Pump Group [MR 200]

Alters • P111 Relay Control Function when P111=52 (Alternate duty assist) or 53 (Alternate duty backup)

This feature groups pumps (relay points 1 - 6) into groups 1 or 2. It is applied to pump rotation and occurs independently within each group.

Siemens 200 — P137 Pump Group [MR 200] diagram (page 153)
Fig. 57 · P137 Pump Group [MR 200]
Show 4 more labels / short text on this page
Level Setpoint ON · Wall Cling Value · Random Setpoint Range · Level Setpoint OFF
Page 154 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 154 · click to enlarge
Page 154

Flush Systems (P170 to P173) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

Use this feature to control an electrically operated flush valve on a pump to divert some pump output back into the wet well to stir up sediment.

  • Notes:
  • If any of the following parameters are set to 0 , this feature will not work.
  • In Dual Point mode, a flush valve can be set up for each of the three available level inputs (P001 = 4 or 5 ).

Single Point Mode

Enter the MultiRanger relay number of the pump with the flush valve. The activation of this pump relay drives the usage of the flush system. Both P172 Flush Interval and P171 Flush Cycles are based on the operation of this relay and control any relay set to P111 = 64, Flush Valve.

Dual Point Mode

The indexed relay is the one that controls the flush device. The value is the pump relay that is watched by the flush system. Enter the pump relay value into the parameter at the flush relay index.

Example

If you need to watch pump Relay One to control a flush valve on Relay Two you would set P170[2]=1.

P170 Flush Pump [MR 200]

Picks the number of the pump relay which triggers the flushing device.

Single Point Model Dual Point Model

Range0 to 6
Preset0

Related • P111 = 64, Flush Valve

Enter the MultiRanger relay number of the pump with the flush valve. The activation of this pump relay drives the usage of the flush system. Both P172 Flush Interval [MR 200] and P171 Flush Cycles [MR 200] are based on the operation of this relay and controls any relay set to P111 = 64, Flush Valve.

Primary Index · Global Relay · Values

Page 155 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 155 · click to enlarge
Page 155

P171 Flush Cycles [MR 200]

Sets the number of pump cycles requiring flush control.

Single Point Model Dual Point Model

Range0 to 9999
Preset0

Related • P111 = 64, Flush Valve

If three flush cycles are required after every ten pump cycles then:

P172 (Flush Interval) = 10 P171 (Flush Cycles) = 3

P172 Flush Interval [MR 200]

Sets the number of pump cycles before flush control is enabled.

Single Point Model Dual Point Model

Range0 to 9999
Preset0

Related • P111 = 64, Flush Valve

To start a new flush cycle every ten times the pumps are run, set this to 10.

P173 Flush Duration [MR 200]

The length of time for each flush cycle that the flush control is active.

Single Point Model Dual Point Model

Range0.000 to 9999 s
Preset0.000

Related • P111 = 64, Flush Valve

Show 9 more labels / short text on this page
Primary Index · Global Relay · Values · Primary Index · Global Relay · Values · Primary Index · Global Relay · Values
Page 156 of the Siemens 200 user manual — 0 OFF
Page 156 · click to enlarge
Page 156

mA Output (P200 to P219)

P200 mA Output Range

Determines the mA output range.

Primary Index mA output

1 0 to 20 mA

2 * 4 to 20 mA

3 20 to 0 mA

4 20 to 4 mA

Related • P911 mA Output Value

If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If either 3 or 4 is selected, then the output is inversely proportional. After setting P200, verify that P212 has a valid entry for mA Output Min Limit, as P212 is not changed automatically by a change to P200.

P201 mA Output Function

Alters the mA output/measurement relationship.

Please note that parameter P201 values vary between the MultiRanger 100 and the MultiRanger 200.

MultiRanger 100

Primary Index mA output

value mA function Operation (P001)

0 OFF

  • Related
  • P202 mA Output Allocation
  • P911 mA Output Value

Altered By • P001 Operation

Show 6 more labels / short text on this page
0 off · Values · Values · 1 level level · 2 space space · 3 distance distance
Page 157 of the Siemens 200 user manual — MultiRanger 200
Page 157 · click to enlarge
Page 157

MultiRanger 200

Primary Index mA output

value mA function Operation (P001)

0 OFF

1 level level, differential, or average

4 volume level or space

  • Related
  • P202 mA Output Allocation
  • P911 mA Output Value

Altered By • P001 Operation

P202 mA Output Allocation

Sets the input source from which the mA output is calculated.

Please note that parameter P202 values vary between the MultiRanger 100 and the MultiRanger 200. MultiRanger 100

Primary Index mA output

1 * Point 1

1:2 Average of readings from Point 1 and Point 2

Related • P201 mA Output Function

MultiRanger 200

Primary Index mA output

Values 1 * Point 1

1:2 Average of readings from Point 1 and Point 2

Related • P201 mA Output Function

Show 12 more labels / short text on this page
2 space space · 3 distance distance · Values · 5 flow OCM · 6 head · 7 volume rate · 8 mA input · 9 comms input · Values · 2 Point 2 · 2 Point 2 · 3 Point 3
Page 158 of the Siemens 200 user manual — P203 mA Output Value / Transducer
Page 158 · click to enlarge
Page 158

Enter the Point Number the mA output is based on. This value depends on whether mA function (P201) is set as transducer or mA input.

For a single point device, if P201 uses a transducer, parameter P202 can only be altered if P001 (Operation) is set for DPD or DPA.

P202 can be set to a particular point or range of points. When set to a range of points, the mA output will be the average of the readings from all in service transducers in the range. Out of service transducers will be ignored.

If P202 mA Output Allocation End contains the value 0, then only 1 transducer has been assigned to the mA output.

P203 mA Output Value / Transducer

Displays current mA output value for the Point Number.

Values Range0.000 to 22.00 (view only)

This displays as an Auxiliary Reading when key is pressed in the RUN mode and does not include adjustments made using Trim features (P214 / P215).

P203 holds the mA value associated with a transducer. This value is used for run mode display of the mA output. When only one mA output is associated with a transducer, this parameter holds the value of that mA output. When more than one transducer is associated with a mA output (set via P202), P203 holds the mA output calculated from the resulting average of the associated transducer readings. When more than one mA output is associated with a transducer, P203 holds the value of the first mA output associated with the transducer.

Primary Index Level

Page 159 of the Siemens 200 user manual — mA Output Limits (P212 and P213)
Page 159 · click to enlarge
Page 159

Independent mA Setpoints (P210 and P211)

Use these features to reference the minimum and/or maximum mA output to any point in the measurement range.

P201—mA Function

Settings Action

Level, Space, or Distance Enter the material level in Units (P005) or percent of Span (P007) as referenced to Empty (P006).

Volume [MR 200] Enter the volume in Max Volume (P051) units or as a per- cent of Max Volume.

Flow [MR 200] Enter the flowrate in OCM Max Flow (P604) units or as a percent of OCM Max Flow.

Head [MR 200] Enter the head in level units (P005) or percent of Max Head (P603).

Volume Rate [MR 200] Enter the volume rate in volume/min. Ensure the % sym- bol is displayed before attempting to enter a % value.

mA input or Communications Input Not Applicable

P210 0/4 mA Output Setpoint

Sets the process level corresponding to the 0 or 4mA value.

Primary Index mA output

Values Range-999 to 9999

Related • P211 20 mA Output Setpoint

Enter the value (in applicable units or %) to correspond to 0 or 4 mA.

P211 20 mA Output Setpoint

Sets the process level that corresponds to the 20 mA value.

Primary Index mA output

Values Range-999 to 9999

Related • P210 0/4 mA Output Setpoint

Enter the value (in applicable units or %) to correspond to 20 mA.

mA Output Limits (P212 and P213)

Use these features to adjust the minimum and/or maximum mA output values, which should suit the input limit requirements of the external device.

Page 160 of the Siemens 200 user manual — P214 4 mA Output Trim
Page 160 · click to enlarge
Page 160

P212 mA Output Min Limit

Sets the minimum mA output value (in mA) to be produced.

Primary Index mA output

Range0.000 to 22.00
Preset3.8
  • Related
  • P200 mA Output Range
  • P213 mA Output Max Limit

P213 mA Output Max Limit

Sets the maximum mA output value (in mA) to be produced.

Primary Index mA output

Range0.000 to 22.00
Preset20.2 mA

Related • P200 mA Output Range / P212 mA Output Min LImit

mA Output Trim (P214 to P215)

This does not affect the P203 value shown, and is used when recalibration of an external device is impractical.

To adjust the value so that the device correctly indicates 4.00 (when P214 is accessed) or 20.00 mA (when P215 is accessed):

1. Attach ammeter to MultiRanger 4 to 20 mA output. 2. Access P214, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and

ENTER . The ammeter should show a value near 4 mA. 3. Enter the exact value displayed on the ammeter into P214 (Index 1 or 2). 4. The ammeter should then read exactly 4.00 mA. 5. Repeat steps 1 to 4 to set P215, using 20 mA as the desired value.

P214 4 mA Output Trim

Calibrates the 4 mA output.

Primary Index mA output

Values Preset4.00

Related • P215 20 mA Output Trim

Adjust this value so the device indicates 4.000 mA when P214 is accessed.

Values · Values

Page 161 of the Siemens 200 user manual — mA Input (P250 to P260) [MR 200]
Page 161 · click to enlarge
Page 161

P215 20 mA Output Trim

Calibrates the 20 mA output.

Primary Index mA output

Values Preset20.00

Related • P214 4mA Output Trim

Adjust this value so the device indicates 20.00 mA when P215 is accessed.

mA Output Failsafe (P219) [MR 200]

Please note that this parameter applies to the MultiRanger 200 only.

P219 mA Output Failsafe [MR 200]

Use for failsafe operation, independent of the Failsafe Material Level (P071).

Primary Index mA output

Range0.000 to 22.00

OFF * mA output responds to Failsafe Material Level (P071).

HOLd last known value is held until normal operation resumes

LO produce the Empty mA output immediately

HI produce the Span mA output immediately

Related • P201 mA Output Function

Selecting an independent mA Failsafe option:

1. Press MODE to display the Auxiliary Function symbol.
2. Press ARROWS to scroll access the failsafe options.
3. Press ENTER when the desired option displayed.

Or, to produce an mA output at a specific value, enter the value required. This is used only if mA output is allocated to a transducer (P201 = 1 to 7).

mA Input (P250 to P260) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

Values

Page 162 of the Siemens 200 user manual — P252 20 mA Input Level [MR 200]
Page 162 · click to enlarge
Page 162

P250 mA Input Range [MR 200]

Shows the mA input range of the connected mA device.

1 0 to 20 mA

2 * 4 to 20 mA

Ensure this range corresponds to the output range of the external device. All level measurements will equate % of Span with the % of the mA range.

P251 0 or 4 mA Input Level [MR 200]

Shows the process level corresponding to the 0 or 4 mA value.

Range-999 to 9999%
Preset0%
  • Related
  • P006 Empty
  • P007 Span

When using an external mA signal to determine level, the input range must be scaled to give accurate results.

P252 20 mA Input Level [MR 200]

Shows the process level corresponding to the 20 mA value.

Range-999 to 9999%
Preset100%
  • Related
  • P006 Empty
  • P007 Span

Input range is scaled for accuracy if an external mA signal calculates level.

Show 6 more labels / short text on this page
Primary Index Global · Values · Primary Index Global · Values · Primary Index Global · Values
Page 163 of the Siemens 200 user manual — Discrete Input Functions (P270 to P275)
Page 163 · click to enlarge
Page 163

P253 Input Filter Time Constant [MR 200]

Shows the time constant used in the mA input filter to dampen signal fluctuations.

Range0 to 9999
Preset1

This number in seconds is used in the damping calculations. Larger values damp more than smaller values and 0 disables the signal filter.

P254 Scaled mA Input Value [MR 200]

Shows the resulting level value after scaling.

Range-999 to 9999% (view only)
Presetcalculated from the input mA signal

This parameter is calculated from the input mA signal.

P260 mA Raw Input [MR 200]

Shows the raw mA input supplied by the external device.

Primary Index mA input

Values Range0.000 to 20.00 (view only)

Discrete Input Functions (P270 to P275)

Discrete inputs can be used for the following:

  • Passing other information to a remote system through communications
  • Backup level override

Use the parameters listed above to have discrete inputs modify the unit’s operation.

Use the following parameters to configure the discrete input itself.

See also the Pump Control section on page 58 for a description of the MultiRanger’s pump control algorithms, including how the discrete inputs alter its operation.

Show 4 more labels / short text on this page
Primary Index Global · Values · Primary Index Global · Values
Page 164 of the Siemens 200 user manual — Record Temperatures (P300 to P303)
Page 164 · click to enlarge
Page 164

P270 Discrete Input Function

Sets how discrete signals are interpreted by the MultiRanger.

Primary Index Discrete input

2 * Normally Open – 0 (DI open), 1 (DI closed)

3 Normally Closed – 0 (DI closed), 1 (DI open)

Related • Pump Control section

P275 Scaled Discrete Input Value

Shows the current value of the discrete input after any scaling is applied.

Primary Index Discrete input

Displayview only
Valuesdependent on the function of the discrete input

Range of Values Function (P270)

0 (DI open), 1 (DI closed) Normally Open

0 (DI closed), 1 (DI open) Normally Closed

Readings are updated continuously even in PROGRAM mode. The value signals a level override event.

Standard Data Logging (P300 to P321)

All records can be reset by pressing the CLEAR keys.

Record Temperatures (P300 to P303)

These features display the high and/or low temperatures in °C. When a parameter relating to a TS-3 Temperature Sensor is accessed, the Point Type display changes to the TS-3 symbol .

If the unit is powered up without a temperature sensor connected, the value –50°C is displayed. This information can help trace problems with both built in and external temperature sensors.

Show 6 more labels / short text on this page
0 Forced OFF · 1 Forced ON · Values · Values · 1 Forced ON · 0 Forced OFF
Page 165 of the Siemens 200 user manual — P302 Temperature, Sensor Maximum
Page 165 · click to enlarge
Page 165

P300 Temperature, Transducer Maximum

Shows the highest temperature encountered, as measured by the temperature sensor in the transducer (if applicable).

Range- 50 to 150°C (view only)
Preset- 50°C

Related • P301 Temperature, Transducer Min

Press CLEAR keys to reset the log after a short circuit on the transducer wiring.

P301 Temperature, Transducer Minimum

View the lowest temperature encountered, as measured by the temperature sensor in the transducer (if applicable).

Range- 50 to 150°C (view only)
Preset150°C

Related • P300 Temperature, Transducer Max

Press CLEAR keys to reset the log after an open circuit on the transducer wiring.

P302 Temperature, Sensor Maximum

View the highest temperature encountered, as measured by the TS-3 Temperature Sensor (if applicable).

Range- 50 to 150°C (view only)
Preset- 50°C

Related • P303 Temperature, Sensor Min

Press CLEAR keys to reset the log after a short circuit on the transducer wiring.

Show 6 more labels / short text on this page
Primary Index Transducer · Values · Primary Index Transducer · Values · Primary Index Global · Values
Page 166 of the Siemens 200 user manual — Pump Records (P309 to P312)
Page 166 · click to enlarge
Page 166

P303 Temperature, Sensor Minimum

Shows the lowest temperature encountered, as measured by the TS-3 Temperature Sensor (if applicable).

Range- 50 to 150°C (view only)
Preset150°C

Related • P302 Temperature, Sensor Max

Press CLEAR keys to reset the log after an open circuit on the transducer wiring.

Record Readings (P304 and P305)

This identifies the occurrence of the record high and low level readings. Press CLEAR

keys to reset these values once the installation is working correctly.

P304 Reading Max

Shows the highest Reading calculated (in normal Reading units or %).

Values Range-999 to 9999 (view only)

Related • P305 Reading Min

P305 Reading Min

Shows the lowest Reading calculated (in normal Reading units or %).

Values Range-999 to 9999 (view only)

Related • P304 Reading Max

Pump Records (P309 to P312)

These features to identify pump usage and if the associated Relay Function (P111) is set for any pump control feature. The value is that of the pump connected to the associated terminals.

Enter a value to set the current record to that value. Use this if a pump is added with a known number of hours logged, or the value can be reset to zero 0 after maintenance.

Show 4 more labels / short text on this page
Primary Index Global · Values · Primary Index Level · Primary Index Level
Page 167 of the Siemens 200 user manual — P312 Pump Run Ons [MR 200]
Page 167 · click to enlarge
Page 167

P309 Pump RUN Time

Displays the amount of time in minutes since a relay was last activated.

Values Range0 to 9999 minutes (view only)

Related • Relay Function (P111) set for any pump control feature

Parameter measures the length of time since a relay was asserted, most often to determine how long a pump has been running. Alternatively, it can monitor a relay to show how long it has been in a state of alarm. It resets every time the relay is activated.

P310 Pump Hours

View or reset the accumulate ON time for the displayed Relay Number.

Values Range0.000 to 9999

Related • Relay Function (P111) set for any pump control feature

Value is displayed with a floating decimal point (the more figures displayed before the decimal, the fewer displayed after). It is the value displayed when key is pressed in the RUN mode.

P311 Pump Starts

View or reset the accumulated number of times the Relay Number has been ON.

Values Range0 to 9999

Related • Relay Function (P111) set for any pump control feature

This value is displayed when key is pressed and held for five seconds in RUN mode.

P312 Pump Run Ons [MR 200]

View or reset the accumulated number of times the displayed Relay Number has been held ON via Run On Interval (P130).

Please note that this parameter applies to the MultiRanger 200 only.

Values Range0 to 9999

Related • Relay Function (P111) set for any pump control feature

Show 4 more labels / short text on this page
Primary Index Relay · Primary Index Relay · Primary Index Relay · Primary Index Relay
Page 168 of the Siemens 200 user manual — Example
Page 168 · click to enlarge
Page 168

Flow Records (P320 and P321) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

These features are enabled if Operation is set for OCM (P001 = 6), or an OCM device is defined (P600 ≠ 0). Use them to identify the occurrence of the record high and low flow rates as displayed in OCM Max Flow (P604) units, or as a percent of OCM Max Flow. Press CLEAR keys to reset values once the installation is working correctly.

P320 Flow Max [MR 200]

View the highest flow rate calculated (in units or %).

Single Point Model Dual Point Model

Values Range-999 to 9999 (view only)

Related • P604 Maximum Flow

P321 Flow Min [MR 200]

View the lowest flow rate calculated (in units or %).

Single Point Model Dual Point Model

Values Range-999 to 9999 (view only)

Related • P604 Maximum Flow

LCD Totalizer (P322 and P323) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

Use these features to view, reset, or preset the eight-digit display totalizer when Operation is set for OCM or Pumped Volume (P001 = 6 or 7). The eight-digit totalizer is divided into two groups of four digits. The four least significant totalizer digits are stored in P322, and the four most significant digits are stored in P323. Adjust these values separately to set a new total.

Example

P323 = 0017 P322 = 6.294 Totalizer Display = 00176.294

Show 4 more labels / short text on this page
Primary Index · Global Transducer · Primary Index · Global Transducer
Page 169 of the Siemens 200 user manual — Profile Records (P330 to P337)
Page 169 · click to enlarge
Page 169

Totalizer units are dependent upon programming. Enter zero 0 (if required) to reset the totalizer to zero. Alternatively, enter any other (applicable) value, to preset the totalizer to the necessary value.

P322 LCD Total Low [MR 200]

View and/or alter the four least significant digits of the totalizer value.

Single Point Model Dual Point Model

Values Range0.000 to 9999
  • P630 LCD Totalized Multiplier
  • P633 LCD Totalized Decimal Position
  • P737 Primary Reading

P323 LCD Total High [MR 200]

View and/or alter the four most significant digits of the totalizer value.

Single Point Model Dual Point Model

Values Range0.000 to 9999
  • P630 LCD Totalized Multiplier
  • P633 LCD Totalized Decimal Position
  • P737 Primary Reading

Profile Records (P330 to P337)

These features can record up to ten Echo profiles, initiated manually (P330), or automatically (P331 et al). If ten Profiles are already saved, addresses 1 through 10 are filled, the oldest automatically initiated record is overwritten. Manually initiated records are not automatically overwritten. All records are automatically deleted in the event of a power interruption.

When a record is displayed, results are based on current programming (which may have been altered since the record was saved). This permits the effect on the echo profile to be observed when changing an echo parameter.

Show 6 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index · Global Transducer · Related
Page 170 of the Siemens 200 user manual — To delete a record
Page 170 · click to enlarge
Page 170

P330 Profile Record

Records profiles for later viewing.

Primary Index Echo profile

Code Description

A1 automatically recorded profile from Transducer One

A2 automatically recorded profile from Transducer Two

U1 manually recorded profile from Transducer One

U2 manually recorded profile from Transducer Two

In addition to being a profile records library, this provides two functions:

  • manually records and saves echo profiles
  • displays an echo profile, recorded manually or automatically

To select a record address

1. Enter PROGRAM mode and press DISPLAY twice to highlight the index field. The field shows two underscores _ _ . 2. Type the index number. The profile record information is shown. 3. Use ARROWS to scroll through the records.

To manually record a profile

Press TRANSDUCER to fire the transducer and record the echo profile into the internal buffer for display.

MultiRanger 100 and MultiRanger 200 Features

To save a manual record

Press ENTER to copy the echo profile record in the buffer and save it in the selected address in the record library. The parameter value field displays the new record information.

To display a record

Press key to enter display auxiliary mode and then:

  • Press TRANSDUCER to copy the current echo profile into the buffer for display on Dolphin Plus

To delete a record

Press CLEAR and then ENTER to delete the echo profile record in the selected address. The value returns to -.

no record · Values

Page 171 of the Siemens 200 user manual — P333 Auto Record Interval
Page 171 · click to enlarge
Page 171

P331 Auto Record Enable

Use to enable/disable the Auto Profile Record function.

Range0 to 1

P332 Auto Record Transducer

Specifies the Transducer Point Number for which Auto Profile Records are saved.

Please note that Differential and Average operation is a MultiRanger 200 feature.

Range0 to 2

1 * Transducer One

Altered By • P001 Operation = 4 or 5

MultiRanger 200

This feature is preset to Point Number 1. (Alteration is only required if differential or average Operation [P001 = 4 or 5] is selected.)

P333 Auto Record Interval

Enter the time to elapse after an Auto Profile Record is saved before another Auto Profile Record can be saved (subject to all other restrictions).

Range0.0 to 166.6 (minutes)
Preset120
Show 10 more labels / short text on this page
Primary Index Global · Values · 0 * Off · 1 On · Primary Index Global · 0 Any transducer · Values · 2 Transducer Two · Primary Index Global · Values
Page 172 of the Siemens 200 user manual — P335 Auto Record OFF Setpoint
Page 172 · click to enlarge
Page 172

Auto Record ON and OFF Setpoints (P334 to P337)

Use Auto Record ON Setpoint (P334) and Auto Record OFF Setpoint (P335) to define the boundaries within which the level must be, for the resultant Echo Profile to be considered for an Auto Profile Record.

If is displayed for either P334 or P335, Auto Profile Records are saved regardless of current level (subject to all other restrictions).

Enter the level value in Units (P005) or percent of Span (P007) as referenced to Empty (P006).

P334 Auto Record ON Setpoint

Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the boundaries for Auto Profile Records to be saved.

Values Range-999 to 9999
  • P335 Auto Record OFF Setpoint
  • P336 Auto Record Filling / Emptying
  • P337 Auto Record LOE Time

P335 Auto Record OFF Setpoint

Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the boundaries for Auto Profile Records to be saved.

Values Range-999 to 9999
  • P334 Auto Record ON Setpoint
  • P336 Auto Record Filling / Emptying
  • P337 Auto Record LOE Time
Show 4 more labels / short text on this page
Primary Index Global · Related · Primary Index Global · Related
Page 173 of the Siemens 200 user manual — P337 Auto Record LOE Time
Page 173 · click to enlarge
Page 173

P336 Auto Record Filling / Emptying

Use this feature to restrict Auto Profile Records from being saved unless the level is rising, falling or either.

0 * Auto Profile Record on filling or emptying

1 Auto Profile Record on filling only

2 Auto Profile Record on emptying only

  • P334 Auto Record ON Setpoint
  • P335 Auto Record OFF Setpoint
  • P337 Auto Record LOE Time
  • P702 Filling Indicator
  • P703 Emptying Indicator

If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator (P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile Record restrictions.

P337 Auto Record LOE Time

Limits Auto Profile Records from being saved unless extended LOE occurs.

Range0.0 to 9999 (seconds)
Preset0.0
  • P334 Auto Record ON Setpoint
  • P335 Auto Record OFF Setpoint
  • P336 Auto Record Filling / Emptying

If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0 LOE is not required for an Auto Profile Record to be saved.

Show 6 more labels / short text on this page
Primary Index Global · Values · Related · Primary Index Global · Values · Related
Page 174 of the Siemens 200 user manual — P342 Start Ups
Page 174 · click to enlarge
Page 174

Installation Records (P340 to P342)

P340 Date of Manufacture

View the date of manufacture of this MultiRanger unit.

Values FormatYY:MM:DD (view only)
  • Related
  • P340 Date of Manufacture
  • P342 Start Ups

P341 RUN Time

View the number of days this MultiRanger has been in operation.

Values Range0.000 to 9999 (view only)
  • Related
  • P340 Date of Manufacture
  • P342 Start Ups

The RUN Time value is updated once a day, and cannot be reset. However, in the event of a power interruption, the counter won’t advance. Therefore, a unit that is powered down on a regular basis will not have an accurate value.

P342 Start Ups

The number of times power has been applied since the Date Of Manufacture.

Values Range1 to 9999 (view only)
  • Related
  • P340 Date of Manufacture
  • P342 Run Time

Primary Index Global · Primary Index Global · Primary Index Global

Page 175 of the Siemens 200 user manual — Single Point Model Dual
Page 175 · click to enlarge
Page 175

Open Channel Monitoring (P600 to P621) [MR 200]

Open Channel Monitoring (OCM) operation is a MultiRanger 200 feature only.

If the MultiRanger is used to monitor open channel flow, alter the following parameters as required and run a calibration as described in P621.

The MultiRanger measures head as referenced to Empty (P006) or OCM Zero Offset (P605), when Operation is set for OCM (P001 = 6). Flowrate, based on head (at the point of measure specified by the Primary Measuring Device fabricator) is also calculated and displayed on the LCD.

Some Primary Measuring Devices require a longer Range Extension (P801) to avoid entering the LOE failure state if the water level falls below the zero point of the Primary Measuring Device. See P801 Range Extension on page 200 for more information.

P600 Primary Measuring Device [MR 200]

The type of primary measuring device (PMD) used.

Single Point Model Dual

0 * off (no calculation)

1 Exponential (see P601)

2 Palmer-Bowlus Flume (see P602)

3 H-Flume (see P602)

4 Universal Linear Flow Calculation (see P610, P611)

5 Universal Curved Flow Calculation (see P610, P611)

6 BS-3680/ISO 4359 Rectangular Flume (see P602)

7 BS-3680/ISO 1438/1 Thin Plate V-Notch Weir (see P602)

  • P601 Flow Exponent
  • P602 Primary Measuring Device Dimensions
  • P608 Flowrate Units

Altered By • P001 Operation

  • P603 Maximum Head
  • P604 Maximum Flow
  • P605 Zero Head
  • P610 Head Breakpoints
  • P611 Breakpoint
Show 5 more labels / short text on this page
Primary Index · Global Transducer · Values · Alters · Related
Page 176 of the Siemens 200 user manual — (P603)
Page 176 · click to enlarge
Page 176

The MultiRanger is pre-programmed for common PMD flow calculations. If your PMD is not listed, select the appropriate Universal Flow Calculation.

Associated parameters Max Head (P603), Max Flow (P604), and Min Head (P605) may be scroll accessed. If Operation is not set for OCM (P001 = 6), this value is preset to 0. If Operation is set for OCM, it is preset to 1.

P601 Flow Exponent [MR 200]

The Exponent for the flow calculation formula.

Single Point Model Dual

Range-999 to 9999
Preset1.55

Altered By • P600 Primary Measuring Device

  • P603 Maximum Head
  • P604 Maximum Flow
  • P605 Zero Head

Use this parameter if the Primary Measuring Device (P600) is set to 1 (exponential). It creates an exponential curve with end points set by Max Head (P603) and Zero Head (P604) and with the curve based on the specified exponent.

If P601 = 1, the flow characteristic is a straight line

Max. Flow

A Word on Exponents

(P604)

The exponential equation is

Q = KH P601

WhereQ = flow K = internal constant H = head

Max. Head

(P603)

Use the exponent specified by the PMD manufacturer, if available, or the sample value given below.

Show 6 more labels / short text on this page
Primary Index · Global Transducer · Values · Related · Zero Flow · Zero Head
Page 177 of the Siemens 200 user manual — ISO 1438/1
Page 177 · click to enlarge
Page 177

Example Exponents

PMD Type Exponent (sample only)

Suppressed Rectangular Weir 1.50

Cipolletti Weir 1.50

Venturi Flume 1.50

Parshall Flume 1.22 to 1.607

Leopold Lagco 1.547

V-Notch Weir 2.50

P602 Primary Measuring Device Dimensions [MR 200]

The dimensions of the Primary Measuring Device (PMD).

Single Point Model Dual Point Model

Global Transducer and Dimension

ISO 1438/1

ISO 4359

Index Values for Supported PMDs

Altered By • P600 Primary Measuring Device

Use this parameter if the Primary Measuring Device is directly supported (P600=2,3,6,7). The dimensions required for each PMD vary.

For more information on PMD, see page 73.

Show 14 more labels / short text on this page
Primary Index · Secondary Index Dimension · 1 Notch Angle · 2 Discharge Coefficient · 1 Approach width · 2 Throat width · 3 Hump Height · 4 Throat Length · 5 Velocity coefficient · 6 Discharge coefficient · Palmer Bowlus · 1 Flume width · H Flume · 1 Flume height
Page 178 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 178 · click to enlarge
Page 178

P603 Maximum Head [MR 200]

The level value associated with Maximum Flow, in Units (P005).

Single Point Model Dual Point Model

Range-999 to 9999
PresetSpan (P007) value
  • Altered By
  • P005 Units
  • P600 Primary Measuring Device
  • Related
  • P604 Maximum Flow
  • P605 Zero Head

This represents the highest head level supported by the PMD and works in conjunction with Maximum Flow (P604) to define the highest point in the exponential curve. Use it when the Primary Measuring Device (PMD) requires a maximum head and flow reference point. This would include Exponential, Palmer Bowlus Flume, H-Flume, and Universal breakpoints.

P604 Maximum Flow [MR 200]

The maximum flowrate associated with Maximum Head (P603).

Single Point Model Dual Point Model

Range-999 to 9999
Preset1000

Altered By • P600 Primary Measuring Device

  • P603 Maximum Head
  • P606 Time Units
  • P925 Flow Measurement

This represents the flow at the highest head level supported by the PMD. and works in conjunction with Maximum Head (P603) to define the highest point in the exponential curve. Use it when the Primary Measuring Device (PMD) requires a maximum head and flow reference point. This would include Exponential, Palmer Bowlus Flume, H-Flume, and Universal breakpoints.

Also use this parameter with Time Units (P606) to define the flowrate units. The limitation of four digits is for the LCD only, and the flowrate value is available with greater precision through communications.

Show 7 more labels / short text on this page
Primary Index · Global Transducer · Values · Primary Index · Global Transducer · Values · Related
Page 179 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 179 · click to enlarge
Page 179

Example

Conditions Enter

  • Flowrate display: millions of gallons/day,
  • Maximum flowrate is 376,500,000 gallons/ day
  • 376.5 for Maximum Flow (P604)
  • and 4 for Time Units (P606).

P605 Zero Head [MR 200]

The distance above Empty (P006) in Units (P005) representing zero head (and zero flow).

Single Point Model Dual Point Model

Range-999 to 9999
Preset0.000
  • Altered By
  • P005 Units
  • P007 Span
  • P006 Empty
  • P801 Range Extension
  • P926 Head Measurement

This feature can be used for most weirs and some flumes (e.g. Palmer Bowlus) where the zero reference is at a higher elevation than the channel bottom.

Material level at zero flow

Show 8 more labels / short text on this page
Primary Index · Global Transducer · Values · Related · Transducer · Empty (P006) · PMD base · Zero Head (P605)
Page 180 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 180 · click to enlarge
Page 180

P606 Time Units [MR 200]

Determines the units used to display current flow and logging flow values.

Primary Index Single Point Model Dual Point Model

Altered By • P608 Flowrate Units

This is used when the Primary Measuring Device is Ratiometric (P608=0).

Example

Conditions Enter

  • Flowrate display: millions of gallons/day,
  • Maximum flowrate is 376,500,000 gallons/day
  • 376.5 for Maximum Flow (P604)
  • and 4 for Time Units (P606).

P607 Flowrate Decimal [MR 200]

The maximum number of decimal places to be displayed.

Single Point Model Dual Point Model

0 no digits after the decimal point

1 1 digit after the decimal point

2 2 digits after the decimal point

3 3 digits after the decimal point

Altered By • P060 Decimal Position

In RUN mode, the number of decimal places displayed is automatically adjusted (if necessary) to prevent the number of Flowrate digits from exceeding display capabilities.

The maximum number of head decimal places is controlled by Decimal Position (P060).

Show 10 more labels / short text on this page
Global Transducer · 1 seconds · 2 minutes · Values · 3 hours · 4 * days · Alters • · Primary Index · Global Transducer · Values
Page 181 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 181 · click to enlarge
Page 181

P608 Flowrate Units [MR 200]

The volume units used to display total flow.

Single Point Model Dual Point Model

0 * Ratiometric calculation (units defined by P604)

1 litres / second

2 cubic metres / hour

3 cubic metres / day

4 cubic feet / second

5 gallons / minute – Imperial

6 million gallons / day – Imperial

7 gallons / minute – U.S.

8 million gallons / day – U.S.

Alters • P606 Time Units

Altered By • P600 Primary Measuring Device

Related • P608 Flowrate Units

This parameter is enabled only if the primary measuring device (PMD) supports absolute calculations (P600=6,7). For absolute PMDs (P600=6,7) volume units can be specified using this parameter. If needed, absolute PMDs can still use ratiometric (P608=0) to accommodate other units.

Show 6 more labels / short text on this page
Primary Index · Global Transducer · Ratiometric (P600=all) · Absolute (P600=6,7 only) · Values · Values
Page 182 of the Siemens 200 user manual — Head vs. Flowrate (P610 and P611)
Page 182 · click to enlarge
Page 182

P610 Head Breakpoints [MR 200]

The head breakpoints for which flowrate is known. See “Accessing a Secondary Index” on page 117 for more information..

Single Point Model Dual Point Model

Values Range0.000 to 9999

Related • P611 Breakpoint Flowrates

The values in the Span for which flowrates are known. See Universal Calculation Support on page 83 for how to specify universal flows.

P611 Breakpoint Flowrates [MR 200]

The flowrate corresponding to each Head Breakpoint entered.

Single Point Model Dual Point Model

Values Range0.000 to 9999

Related • P610 Head Breakpoints

These are the flowrates for the related breakpoints. See Universal Calculation Support on page 83 for how to specify universal flows.

Head vs. Flowrate (P610 and P611)

Max. Flow

Max. Head

Show 10 more labels / short text on this page
Primary Index · Global Transducer · Secondary Index Breakpoint · Primary Index · Global Transducer · Secondary Index Breakpoint · Flow Breakpoints · Zero Flow · Zero Head · Head Breakpoints
Page 183 of the Siemens 200 user manual — Procedure, with “head” steady
Page 183 · click to enlarge
Page 183

P620 Low Flow Cutoff [MR 200]

Eliminates totalizer activity for flows at or below the cutoff value.

Single Point Model Dual Point Model

Range0.000 to 9999

Preset = 5.000 %, or equivalent units

Altered By • P005 Units

Related • P007 Span

Use this to enter the minimum head in units (P005) or as a percent of span.

P621 Auto Zero Head [MR 200]

Calibrates Zero Head (P605) based on actual head measurements.

Single Point Model Dual Point Model

Values Range-999 to 9999
  • P006 Empty
  • P062 Offset Reading
  • P605 Zero Head
  • P664 Temperature

Use this parameter when the reported head is consistently high or low by a fixed amount.

Before using this feature, verify the following parameters are correct:

  • Empty (P006)
  • Temperature (P664)
  • Offset Reading (P062=0)
  • Zero Head Offset (P605)

Procedure, with “head” steady

1. Press TRANSDUCER to display the calculated head. 2. Repeat step ONE at least FIVE times to verify repeatability. 3. Measure the actual head (with a tape measure or solid rule). 4. Enter the actual head value.

The deviation between the entered Empty (P006) value and the calibrated Empty value is stored in Offset Correction (P652). Alternatively, the Empty parameter (P006) can be corrected directly.

Show 6 more labels / short text on this page
Primary Index · Global Transducer · Values · Primary Index · Global Transducer · Related
Page 184 of the Siemens 200 user manual — P622 Inflow / Discharge Adjust [MR 200]
Page 184 · click to enlarge
Page 184

Pumped Volume Totalizer (P622) [MR 200]

The Pumped Volume Totalizer is a MultiRanger 200 feature only.

If the eight-digit totalizer display or a remote totalizer contact closure are desired, alter the following parameters.

P622 Inflow / Discharge Adjust [MR 200]

The method used to calculate the volume pumped, for pumped total Operation (P001 = 7).

Primary Index Single Point Model Dual Point Model Global Transducer

1 = inflow * / pump cycle When the pump is off, the MultiRanger estimates the volume of inflow by recording the rate at which the liquid level changes. When the pump is operating, the estimated inflow volume is added to the pumped volume total. When the pump stops, the pumped volume of the previous pump cycle is added to the total volume pumped in the totalizer. 2 = inflow * ignored Inflow is assumed to be 0 while pumps are running. 3 = inflow * / rate (preset) Volume pumped is adjusted for inflow. Inflow rate is estimated by assuming that the rate calculated (P708) just prior to the start of the pump cycle remained constant during the pump cycle. Inflow rate is averaged using rate filter (P704), rate update time (P705) and rate update distance (P706) to control how the average rate is calculated.

  • P001 Operation
  • P704 Rate Filter
  • P705 Rate Update Time
  • P706 Rate Update Distance
  • P708 Volume Rate Display

Values · Related · * or discharge

Page 185 of the Siemens 200 user manual — Example:
Page 185 · click to enlarge
Page 185

Totalizer (P630 to P645) [MR 200]

The Totalizer features apply to MultiRanger 200 only.

P630 LCD Totalized Multiplier [MR 200]

Use this feature if the LCD Total increments by too large (or too small) an amount.

Single Point Model Dual Point Model

-3 .001

Related • LCD Totalizer (P322 and P323)

Enter the factor (powers of 10 only) by which actual volume is divided, prior to display on the LCD. Use a value such that the eight-digit totalizer doesn’t roll over between readings.

Example:

For an LCD Total display in 1000s of volume units, enter 3.

Show 9 more labels / short text on this page
Primary Index · Global Transducer · Values · 0 * 1 · 4 10,000 · 5 100,000 · Values · 6 1,000,000 · 7 10,000,000
Page 186 of the Siemens 200 user manual — Primary Index Single Point Model Dual Point Model
Page 186 · click to enlarge
Page 186

P633 LCD Totalized Decimal Position [MR 200]

Enter the maximum number of decimal places to be displayed.

Primary Index Single Point Model Dual Point Model

0 no digits after the decimal point

1 1 digit after the decimal point

2 * 2 digits after the decimal point

3 3 digits after the decimal point

Related • LCD Totalizer (P322 and P323)

In RUN mode, the number of decimal places displayed is not automatically adjusted. When the LCD Total value is so large as to exceed display capabilities, the total rolls over to 0 and continues incrementing.

P640 Remote Totalized Multiplier [MR 200]

Use this feature if the remote totalizer (device connected to the relay set for totalizer operation [relay Function, P111 = 40]), updates too slowly or rapidly.

Primary Index Single Point Model Dual Point Model

-3 .001

  • P001 Operation
  • P111 Relay Control Function
  • P114 Relay Duration Setpoint
  • P115 Relay Interval Setpoint
  • P645 Relay Duration

Parameter is relevant only if Operation is set to OCM or Pumped Volume (P001 = 6 or 7). The relays on the MultiRanger have a maximum frequency of 2.5 Hz.

Show 11 more labels / short text on this page
Global Transducer · Values · Global Transducer · Values · 0 * 1 · Values · 4 10,000 · 5 100,000 · 6 1,000,000 · 7 10,000,000 · Related
Page 187 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 187 · click to enlarge
Page 187

Enter the factor (powers of 10 only) by which actual volume is divided, prior to Remote Totalizer count increment.

Example:

For a Remote Totalizer update by 1000s of volume units, enter 3.

P641 Flow Sampler Mantissa [MR 200]

Use this feature in conjunction with Flow Sampler Exponent (P642) to establish the number of flow units required to increment the Flow Sampler (device connected to the MultiRanger relay set for the flow sampler operation Relay Function, P111 = 41).

Single Point Model Dual Point Model

Range0.001 to 9999

Preset = 1.000

  • P001 Operation
  • P111 Relay Control Function
  • OCM (P600 to P621)
  • P642 Flow Sampler Exponent

This parameter is relevant only if Operation is set to OCM (P001 = 6). Enter the mantissa (Y) for the exponent (Z) in the formula:

Flow Sampler Increment = Y x 10Z Flow units.

ExampleTo count once every 4310 (4.31 x 10 3 ) flow units:
  • set P641 to 4.31 and P642 to 3

P642 Flow Sampler Exponent [MR 200]

Use this feature in conjunction with Flow Sampler Mantissa (P641) to establish the number of flow units required to increment the Flow Sampler (device connected to the MultiRanger relay set for the flow sampler operation Relay Function, P111 = 41).

Single Point Model Dual Point Model

Range-3 to +7 (integers only)
  • P001 Operation
  • P111 Relay Control Function
  • OCM (P600 to P621)
  • P641 Flow Sampler Mantissa
Show 9 more labels / short text on this page
Primary Index · Global Transducer · Values · Related · Primary Index · Global Transducer · Values · Preset = 0 · Related
Page 188 of the Siemens 200 user manual — Range Calibration (P650 to P654)
Page 188 · click to enlarge
Page 188

This parameter is relevant only if Operation is set to OCM (P001 = 6).

Enter the exponent (Z) for the mantissa (Y) in the formula:

Flow Sampler Increment = Y x 10Z Flow units.

P645 Relay Duration [MR 200]

Use this feature (if desired) to adjust the minimum contact closure duration of a relay set as a totalizer, flow sampler, time (control), or aeration (P111 = 40, 41, 60 or 62)

Range0.1 to 1024

Preset = 0.2 (sec)

Related • P111 Relay Control Function

Enter minimum contact closure duration (in seconds) required by the device connected.

For the flow sampler function this value is used for both the ON time of the relay and the OFF time between contacts.

P645 OFF time P645 on time relay contact closed

Range Calibration (P650 to P654)

There are two types of calibration possible:

Offset: Adjusts the measurements by a fixed amount.

Sound Velocity: Adjusts speed of sound and changes the measurement calculations.

Do Offset calibration at any steady level unless a Sound Velocity calibration is also done. If both calibrations are done then do Offset at a known high level and Sound Velocity at a known low level.

Primary Index Global · Values · relay contact open

Page 189 of the Siemens 200 user manual — Condition for use of this feature
Page 189 · click to enlarge
Page 189

P650 Offset Calibration

Calibrates Empty (P006) if the reported level is consistently high or low by a fixed amount.

Single Point Model Dual Point Model

Values Range-999 to 9999
  • P006 Empty
  • P062 Offset Reading
  • P605 Zero Head
  • P652 Offset Correction
  • P664 Temperature

Before using this feature, verify the following parameters are correct:

  • Empty (P006)
  • Temperature (P664)
  • Offset Reading (P062)
  • Zero Head Offset (P605), if using OCM

Offset Calibration

Begin with a steady level.

1. Press TRANSDUCER to display the calculated reading. 2. Repeat Step One at least five times to verify repeatability. 3. Measure the actual reading (use tape measure). 4. Enter the actual value. The deviation between the entered Empty (P006) value and the calibrated Empty value is stored in Offset Correction (P652).

P651 Sound Velocity Calibration

Changes the speed of sound constant.

Single Point Model Dual Point Model

Values Range-999 to 9999
  • Related
  • P653 Velocity
  • P654 Velocity at 20°C

Condition for use of this feature

  • The acoustic beam atmosphere is other than air
  • The acoustic beam atmosphere temperature is unknown
  • The Reading accuracy is acceptable at higher material levels only

For best results, calibrate with the level at a known value near empty.

Show 5 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index · Global Transducer
Page 190 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 190 · click to enlarge
Page 190

Using Sound Velocity Calibration

Ensure a steady level at some low value (P653 and P654 adjusted accordingly)

1. Allow sufficient time for the vapor concentration to stabilize. 2. Press TRANSDUCER to display the calculated reading. 3. Repeat Step Two at least five times to verify repeatability. 4. Measure the actual reading (e.g. with a tape measure). 5. Enter the actual value. Repeat this procedure if the atmosphere type, concentration, or temperature conditions are different from when the last sound velocity calibration was performed.

P652 Offset Correction

The value altered when an Offset Calibration is performed.

Single Point Model Dual Point Model

Values Range-999 to 999.0

Related • P650 Offset Calibration

Alternatively, if the amount of Offset Correction required is known, enter the amount to be added to the Reading before display.

P653 Velocity

The value adjusted based on the Sound Velocity at 20 °C (P654) vs. Temperature (P664) characteristics of air.

Single Point Model Dual Point Model

Values Range50.3 to 20011.9 m/s (165 to 6601 ft/s)
  • Related
  • P651 Sound Velocity Calibration
  • P654 Velocity at 20°C

Alternatively, enter the current sound velocity (if known), or perform a Sound Velocity Calibration (P651). The units used are m/s if P005 = 1, 2, or 3 (ft/s if P005 = 4 or 5).

Show 4 more labels / short text on this page
Primary Index · Global Transducer · Primary Index · Global Transducer
Page 191 of the Siemens 200 user manual — 1 * AUTO
Page 191 · click to enlarge
Page 191

P654 Velocity at 20°C

This value is used to automatically calculate Sound Velocity (P653).

Single Point Model Dual Point Model

Values Range50.0 to 2000.0 m/s (164 to 6562 ft/s)
  • P005 Units
  • P651 Sound Velocity Calibration
  • P653 Velocity

After performing a Sound Velocity Calibration, check this value to verify the acoustic beam atmosphere is air (344.1 m/s or 1129 ft/s).

Alternatively, if the acoustic beam atmosphere sound velocity at 20°C (68 °F) is known, and the sound velocity vs. temperature characteristics are similar to that of air, enter the sound velocity.

The units used are m/s if P005 = 1, 2, or 3 (or ft/s if P005 = 4 or 5).

Temperature Compensation (P660 to P664)

P660 Temp Source

Source of the temperature reading used to adjust the speed of sound.

1 * AUTO

4 TS-3 Temperature Sensor

5 Average (TS-3 and transducer)

Alters • P664 Temperature

  • P651 Sound Velocity
  • P653 Velocity
  • P654 Velocity at 20°C
  • P661 Temp Fixed

The MultiRanger uses the TS-3 temperature sensor assigned to the transducer. If one is not connected, the ultrasonic/temperature transducer is used. If the transducer does not have an internal temperature sensor, the Temp Fixed (P661) value is used.

If the acoustic beam atmosphere temperature varies with distance from the transducer, connect a TS-3 Temperature Sensor and ultrasonic / temperature transducers, and select average.

Show 8 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index Transducer · 2 Temp Fixed · Values · 3 Ultrasonic/Temperature Transducer · Related
Page 192 of the Siemens 200 user manual — P663 Temperature Transducer Allocation
Page 192 · click to enlarge
Page 192

In gasses other than air, the temperature variation may not correspond with the speed of sound variation. In these cases turn off the temperature sensor and use a fixed temperature.

P661 Temp Fixed

Use this feature if a temperature sensing device is not used.

Values Range-199 to 199 (preset = 20 °C)
  • P651 Sound Velocity Calibration
  • P653 Velocity
  • P654 Velocity at 20°C
  • P660 Temp Source

Enter the temperature (in °C) of the atmosphere within the transducer acoustic beam. If the temperature varies with distance from the transducer, enter the average temperature.

P663 Temperature Transducer Allocation

This feature may only be used for differential or average Operation (P001 = 4 or 5).

1 * Transducer One

1:2 Transducer One and Two average [MR200]

  • P651 Sound Velocity Calibration
  • P653 Velocity
  • P654 Velocity at 20°C

As preset, the temperature measurements of Ultrasonic / Temperature Transducer One and Two are allocated to Points 1 and 2 respectively.

Use this feature if the temperature measurement from both transducers should be identical, but one is located close to a radiant heat source. Allocate the temperature measurement of the other transducer to both transducer Point Numbers.

Enter the number of the Transducer whose temperature measurement will be used for the distance calculation of the Point Number displayed. When both transducers are allocated to a Point Number, the temperature measurements from each are averaged.

Show 6 more labels / short text on this page
Primary Index Transducer · Related · Primary Index Transducer · 2 Transducer Two · Values · Related
Page 193 of the Siemens 200 user manual — P003 Value Meters/Minute
Page 193 · click to enlarge
Page 193

P664 Temperature

View the transducer temperature in °C.

Values Range-50 to 150 (view only)

Altered By • P660 Temp Source

  • P651 Sound Velocity Calibration
  • P653 Velocity
  • P654 Velocity at 20°C
  • P661 Temp Fixed

Value is displayed when is pressed in RUN mode (see Readings in Run Mode on page 23).

If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.

Rate (P700 to P708)

These parameters determine how material level changes are reported.

P700 Max Fill Rate

Adjusts the MultiRanger response to increases in the actual material level (or advance to a higher Failsafe Material Level, P071).

Single Point Model Dual Point Model

Values Range0.000 to 99.00 m (or equivalent depending on units)

Altered by • P003 Maximum Process Speed

  • P005 Units
  • P007 Span
  • P071 Failsafe Material Level

Enter a value slightly greater than the maximum vessel filling rate. This value, in Units (P005) or % of Span (P007) per minute, is automatically altered when Maximum Process Speed (P003) is altered.

P003 Value Meters/Minute

Show 5 more labels / short text on this page
Primary Index Transducer · Related · Primary Index · Global Transducer · Related
Page 194 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 194 · click to enlarge
Page 194

P701 Max Empty Rate

Adjusts the MultiRanger response to decreases in the actual material level (or advance to a lower Failsafe Material Level, P071).

Single Point Model Dual Point Model

Values Range0.000 to 99.00 m (or equivalent depending on units)

Altered by • P003 Maximum Process Speed

  • P005 Units
  • P007 Span
  • P071 Failsafe Material Level

Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units (P005) or % of Span (P007) per minute, is automatically altered when Maximum Process Speed (P003) is altered.

P003 Value Meters / Minute

P702 Filling Indicator

The fill rate required to activate the LCD Filling indicator ( ).

Single Point Model Dual Point Model

Values Range0.000 to 99.00 m (or equivalent depending on units)

Altered by • P003 Maximum Process Speed

  • P005 Units
  • P007 Span
  • P700 Max Fill Rate

This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of the Max Fill Rate (P700).

Show 6 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index · Global Transducer · Related
Page 195 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 195 · click to enlarge
Page 195

P703 Emptying Indicator

The empty rate required to activate the LCD Emptying indicator ( ).

Single Point Model Dual Point Model

Values Range0.000 to 99.00 m (or equivalent depending on units)

Altered by • P003 Maximum Process Speed

  • P005 Units
  • P007 Span
  • P701 Max Empty Rate

This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of the Max Empty Rate (P701).

P704 Rate Filter

Damps Rate Value (P707) fluctuations.

Single Point Model Dual Point Model

0 Rate display not required

1 Continuously filtered and updated

2 1 minute or 50 mm (2 in)

3 5 minutes or 100 mm (3.9 in)

4 10 minutes or 300 mm (11.8 in)

5 10 minutes or 1000 mm (39.4 in)

Alters • P707 Rate Value

Altered by • P003 Maximum Process Speed

Related • P705 Rate Update Time/ P706 Rate Update Distance

Enter the time or distance interval over which the Rate Value is to be calculated before the display updates.

This is automatically altered along with Maximum Process Speed (P003).

This value automatically alters the Rate Update Time (P705) and / or Rate Update Distance (P706). Alternatively, these parameter values may be altered independently.

Show 8 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index · Global Transducer · Filtered Output · Interval Output · Values
Page 196 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 196 · click to enlarge
Page 196

P705 Rate Update Time

The time period (in seconds) over which the material level rate of change is averaged before Rate Value update.

Single Point Model Dual Point Model

Values Range0.000 to 9999

Related • P707 Rate Value

P706 Rate Update Distance

The material level change (in metres) to initiate a Rate Value update.

Single Point Model Dual Point Model

Values Range0.000 to 9999

Related • P707 Rate Value

P707 Rate Value

The rate of material level change (in Units (P005) or % of Span (P007) per minute).

Single Point Model Dual Point Model

Values Range-999 to 9999 (view only)

Altered By • P704 Rate Filter

  • Related
  • P005 Units
  • P007 Span

A negative rate indicates the vessel is emptying.

This is the value displayed when is pressed in the RUN mode as described in the Readings in RUN Mode chart on page 23.

Show 6 more labels / short text on this page
Primary Index · Global Transducer · Primary Index · Global Transducer · Primary Index · Global Transducer
Page 197 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 197 · click to enlarge
Page 197

P708 Volume Rate Display [MR 200]

The rate of change of volume in percent of maximum volume per minute.

Please note that this feature applies to the MultiRanger 200 only.

Single Point Model Dual Point Model

Values Range-999 to 9999 (view only)

Related • P622 Inflow / Discharge Adjust

This value is used internally to calculate inflow in pumped volume applications (P622=3).

Press READING to toggle between percent and volume.

Measurement Verification (P710 to P713)

P710 Fuzz Filter

Use this to stabilize the reported level, due to level fluctuations (such as a rippling or splashing liquid surface) within the Echo Lock Window (P713).

Single Point Model Dual Point Model

Values Range0 to 100 (0 = off)

Altered by • P003 Maximum Process Speed

  • Related
  • P007 Span
  • P713 Echo Lock Window

This value (in % of Span, P007) is automatically altered when Maximum Process Speed (P003) is altered. The higher the value entered, the greater the fluctuation stabilized.

Show 4 more labels / short text on this page
Primary Index · Global Transducer · Primary Index · Global Transducer
Page 198 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 198 · click to enlarge
Page 198

P711 Echo Lock

Use this feature to select the measurement verification process.

Single Point Model Dual Point Model

2 * Material agitator

  • P700 Max Fill Rate
  • P701 Max Empty Rate
  • P712 Echo Lock Sampling
  • P713 Echo Lock Window
  • P820 Algorithm

If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for maximum verification or material agitator to avoid agitator blade detection. Ensure the agitator is always ON while the MultiRanger is monitoring the vessel to avoid stationary blade detection.

When set for max verification or material agitator, a new measurement outside of the Echo Lock Window (P713) must meet the sampling criterion (P712).

For total lock, Echo Lock Window (P713) is preset to zero 0. The MultiRanger continuously searches for the best echo according to the algorithm chosen (P820). If the selected echo is within the window, the window is then centered about the echo. If not, the window widens with each successive shot until the selected echo is within the window. The window then returns to its normal width.

When Echo Lock is OFF , the MultiRanger responds immediately to a new measurement as restricted by the Max Fill / Empty Rate (P700 / P701); however, measurement reliability is affected.

Show 7 more labels / short text on this page
Primary Index · Global Transducer · 0 Off · 1 Maximum verification · Values · 3 Total lock · Related
Page 199 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 199 · click to enlarge
Page 199

P712 Echo Lock Sampling

The sampling criterion sets the number of consecutive echoes appearing above or below the echo currently locked onto, that must occur before the measurements are validated as the new reading (for Echo Lock P711 values: 1 or 2).

Single Point Model Dual Point Model

Range1:1 to 50:50
Formatx:y

x = the number of above echoes

y = the number of below echoes

Related • P711 Echo Lock

P711 value P712 preset value

1, max verification 5:5

2, material agitator 5:2

Example:

  • P711 = 2, material agitator
  • P712 = 5:2
  • a new reading will not be validated unlessfive consecutive measurements higher or two consecutive measurements lower than the current reading occur
  • Resetting P711 returns P712 to the respective preset values

P713 Echo Lock Window

Adjusts the size of the Echo Lock Window.

Single Point Model Dual Point Model

Range0.000 to 99.00 m (or equivalent depending on units), nearest acceptable value is returned
Preset0.000

Altered by • P003 Maximum Process Speed

  • Related
  • P005 Units
  • P711 Echo Lock
Show 8 more labels / short text on this page
Primary Index · Global Transducer · Values · Setting · Result · Primary Index · Global Transducer · Values
Page 200 of the Siemens 200 user manual — P727 Scan Delay
Page 200 · click to enlarge
Page 200

The Echo Lock Window is a distance window (units P005) centred on the echo and used to derive the Reading. When a new measurement is in the window, it is re-centred and the new Reading calculated. Otherwise, the new measurement is verified by Echo Lock (P711) before the reading is updated.

When 0 is entered the window is automatically calculated after each measurement. For slower P003 Maximum Process Speed values the window is narrow, for faster P003 values the window becomes wider.

Transducer Scanning (P726 to P729)

P726 Level System Sync

Enables the System Sync on the terminal block.

1 * synchronize level monitors

Use this if another level measurement system is mounted nearby, and they are wired together on the Sync terminal.

P727 Scan Delay

The delay, in seconds, between measurements from transducer points (dual point model only).

Range0 to 60 seconds
Preset5.0

Altered by • P003 Maximum Process Speed

Related • P001 Operation

This feature may only be used to adjust the delay before the next point is scanned. Enter the amount of delay in seconds. This value is automatically altered when Maximum Process Speed (P003) is altered.

Show 5 more labels / short text on this page
Primary Index Global · 0 not required · Values · Primary Index Global · Values
Page 201 of the Siemens 200 user manual — Selecting the Auxiliary Reading operation
Page 201 · click to enlarge
Page 201

P728 Shot Delay

The delay, in seconds, between transducer shots.

Range0.1 to 4.0
Preset0.5

Use this if transient acoustic noise within the vessel is causing measurement difficulties due to echoes from one shot being received on the next. If more than one ultrasonic unit is installed for redundancy, this value should be 0.

P729 Scan Time

View the elapsed time (in seconds) since the point displayed was last scanned.

Values Range0.000 to 9999 (view only)

Related • P001 Operation

This may be viewed as an Auxiliary Reading in the RUN mode.

Display (P730 to P739)

P730 Auxiliary Reading

Use this feature to display operator selected Auxiliary Readings temporarily or indefinitely (as desired).

Range000 to 999
DisplayOFF, HOLd

Select OFF to display Auxiliary Readings temporarily. Select HOLd to display Auxiliary Readings until another Auxiliary Reading is selected or programming mode is entered. See the Hand Programmer section on page 27 for RUN mode auxiliary readings.

Selecting the Auxiliary Reading operation

1. Press READING to display the Auxiliary Function symbol.
2. Press ARROWS to access the OFF or HOLd option desired.
3. Press ENTER
Show 5 more labels / short text on this page
Primary Index Transducer · Values · Primary Index Level · Primary Index Global · Values
Page 202 of the Siemens 200 user manual — P733 Scroll Access
Page 202 · click to enlarge
Page 202

If necessary, enter the Parameter Number to default in the Auxiliary Reading display. That value will show in the auxiliary reading area by default. Other values are available but will reset to the parameter defined here.

P731 Auxiliary Reading Key

Enter the Parameter Number whose value is to be displayed in the Auxiliary Reading field

Range000 to 999
PresetMaterial Reading, P921

is pressed in the RUN mode. See the Hand Programmer section on page 27 for RUN mode auxiliary readings.

P

P732 Display Delay

Adjusts the Point Number display scroll speed.

Range0.5 to 10
Preset1.5 seconds
  • Related
  • P001 Operation
  • P737 Primary Reading

Use this feature to adjust the delay before the display advances to the next Point Number. Display scrolling is independent from transducer scanning.

P733 Scroll Access

Use this feature to select the parameter scroll access option desired.

0 Off to scroll to all parameters (P001 to P999)

1 * Smart for Quick Start, altered, and tagged parameters

2 Tagged to scroll to operator tagged parameters only

Press READING and to tag / untag any accessed parameter. is displayed to indicate the parameter accessed is tagged.

Show 6 more labels / short text on this page
Primary Index Global · Values · Primary Index Global · Values · Primary Index Global · Values
Page 203 of the Siemens 200 user manual — P741 Communications Timeout
Page 203 · click to enlarge
Page 203

P735 Backlight

Controls the LCD backlighting.

The backlight can be forced on or off, or be controlled by a programmer, in which case it will turn OFF 30 seconds after the last key is pressed.

P737 Primary Reading [MR 200]

The reading shown on the primary reading display when in RUN mode.

Range0 to 3

1 * Default reading (P920) based on operation (P001)

2 LCD totalizer (P322, P323)

3 Automatically toggle between 1 and 2

  • LCD Totalizer (P322 and P323)
  • P732 Display Delay
  • P920 Reading Measurement

When this value indicates TOGGLE, then both readings (default and totalizer) are shown in the time specified in display delay (P732).

P741 Communications Timeout

The maximum time allowed between receiving a request and transmitting the response.

Range0 to 60 000 milliseconds
Preset5 000 ms

If the maximum time is exceeded, no response will be transmitted, and the action required may not be completed.

Show 10 more labels / short text on this page
Primary Index Global · 0 Off · Values · 1 * On · 2 Keypad activated · Primary Index Global · Values · Related · Primary Index Port · Values
Page 204 of the Siemens 200 user manual — P771 Network Address
Page 204 · click to enlarge
Page 204

SmartLinx Reserved (P750 to P769)

These parameters are reserved for optional SmartLinx communications cards and vary by card. Refer to the SmartLinx documentation to determine if any of them are used.

Communications (P770 to P782)

The MultiRanger communication ports are configured by a series of parameters that are indexed by port. See the Communications section on page 89 for a complete description of communications set-up.

Communication parameters are indexed to these communication ports, unless otherwise noted:

Port Description

1 RS-232 port (RJ-11 modular telephone)

2 RS 485 port on terminal block

P770 Port Protocol

The communications protocol used between the MultiRanger and other devices.

Primary Index Communications Port

0 Communications port disabled

1 Siemens Milltronics Dolphin protocol

2 Modbus ASCII slave serial protocol

3 * Modbus RTU slave serial protocol (preset for ports 1 and 2)

The MultiRanger supports the internationally recognized Modbus standard in both ASCII and RTU formats. Other protocols are available with optional SmartLinx cards.

P771 Network Address

The unique identifier of the MultiRanger on the network.

Primary Index Communications Port

Range0 to 9999

1 * Preset:

For devices connected with the Siemens Milltronics protocol this parameter is ignored. For devices connected with a serial Modbus slave protocol, this parameter is a number from 1-247. The network administrator must ensure that all devices on the network have unique addresses. Do not use the value 0 for Modbus communications as this is the broadcast address and is inappropriate for a slave device.

Values · Values

Page 205 of the Siemens 200 user manual — P774 Data Bits
Page 205 · click to enlarge
Page 205

P772 Baud Rate

The communication rate with the master device.

Primary Index Communications Port

4.8 4800 baud

9.6 9600 baud

19.2 * 19,200 baud (preset for port 2)

115.2 * 115,200 baud (preset for port 1)

This specifies the rate of communication in Kbaud. Any value may be entered but only the values shown above are supported. The baud rate should reflect the speed of the connected hardware and protocol used.

P773 Parity

The serial port parity.

Primary Index Communications Port

0 * No Parity

Ensure that the communications parameters are identical between the MultiRanger and all connected devices. For example, many modems default to N-8-1 which is No parity, 8 data bits, and 1 stop bit.

P774 Data Bits

The number of data bits per character.

Primary Index Communications Port

Range5 to 8

8 * Modbus RTU

7 or 8 Modbus ASCII

7 or 8 Dolphin Plus

Show 5 more labels / short text on this page
Values · 1 Odd Parity · Values · 2 Even Parity · Values
Page 206 of the Siemens 200 user manual — Hanging Up
Page 206 · click to enlarge
Page 206

P775 Stop Bits

The number of bits between the data bits.

Primary Index Communications Port

Range1 or 2

1 * Preset:

P778 Modem Available

Sets the MultiRanger to use an external modem..

Primary Index Communications Port

0 * No modem connected

P779 Modem Inactivity Timeout

Sets the time that the unit will keep the modem connected with no activity.

Primary Index Communications Port

Range0-9999 seconds

0 * No timeout

  • Related
  • P778 Modem Available
  • P779 Modem Inactivity Timeout

To use this parameter, ensure that P778 (Modem Available) = 1. Ensure that the value is low enough to avoid unnecessary delays when an unexpected disconnect occurs but long enough to avoid timeout while you are still legitimately connected. This parameter value is ignored by the Modbus Master Drivers, as they automatically disconnect when done.

Hanging Up

If the line is idle and the P779 Modem Inactivity Timeout expires, then the modem is directed to hang up the line. Ensure that P779 is set longer than the standard polling time of the connected master device. 0 disables the inactivity timer.

Show 4 more labels / short text on this page
Values · Values · 1 Answer only · Values
Page 207 of the Siemens 200 user manual — P790 Hardware Error
Page 207 · click to enlarge
Page 207

P782 Parameter Index Location

Determines where index information is stored for the parameter access area.

Altered By • P770 Port Protocol

Global (0)

  • The primary and secondary index values are global (they affect all of the parameter access area at once) and stored in:
  • primary index – R43,999
  • secondary index – R43,998

Parameter-Specific (1)

The primary and secondary index values are encoded into the format words found between R46,000 and R46,999. Each format work corresponds with the R44,000 series number in the parameter access map. For example, the format register R46,111 corresponds to the parameter P111 and the value is stored in R44,111. If the Modbus protocol (P770 = 2 or 3) is not used this parameter is ignored.

SmartLinx Hardware Testing (P790 to P795)

P790 Hardware Error

The results of ongoing hardware tests in the communications circuitry.

PASS * No errors

FAIL Error occurred communicating with card; commu- nications should resume.

ERR1 No module installed, or module not supported; SmartLinx communications have been disabled

  • Related
  • P791 Hardware Error Code
  • P792 Hardware Error Count

If FAIL or ERR1 is displayed in P790 (Hardware Error), go to P791 (Hardware Error Code) and P792 (Hardware Error Count) for information about the error.

Show 6 more labels / short text on this page
Primary Index Global · 0 * Global · Values · 1 Parameter-Specific · Primary Index Global · Values
Page 208 of the Siemens 200 user manual — P795 SmartLinx Protocol
Page 208 · click to enlarge
Page 208

P791 Hardware Error Code

Indicates the precise cause of Fail or ERR1 condition from P790.

0 * No error

8 No SmartLinx card installed

Error code; provide this code to your Siemens Milltronics representative for troubleshooting

Related • P790 Hardware Error

P792 Hardware Error Count

A count that increments by 1 each time Fail is reported in P790 (Hardware Error).

Range0 to 9999

Error count; provide this number to your Siemens Milltronics repre- sentative for troubleshooting.

Related • P790 Hardware Error

P794 SmartLinx Module Type

This parameter is used to identify the module type when SmartLinx is used. If you are not using SmartLinx, this parameter is not functional. Please see the associated SmartLinx instruction manual for a full description of this parameter.

P795 SmartLinx Protocol

This parameter is used to identify the protocol when SmartLinx is used. If you are not using SmartLinx, this parameter is not functional. Please see the associated SmartLinx instruction manual for a full description of this parameter.

Show 5 more labels / short text on this page
Primary Index Global · Values · Any other value · Primary Index Global · Values
Page 209 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 209 · click to enlarge
Page 209

P799 Communications Control

Enables the read/write access to parameters via remote communications.

Protocol (Index 1 controls the Modbus Master (RS-485 or RS-232); Index 2 controls the Fieldbus Master (PROFIBUS DP, DeviceNet, or Allen Bradley Remote I/O)

2 Restricted Access – read only except for P799 which is read/write

  • Notes:
  • P799 controls the lock access via communications.
  • P000 controls the lock access via the Siemens handheld programmer.

Echo Processing (P800 to P807)

P800 Near Blanking

The space near the transducer face which cannot be measured.

Single Point Model Dual Point Model

Range0.000 to 99.00 m (or equivalent depending on units)
Preset0.300m (Most transducers)

0.450m (XCT-8, XCT-12)

  • P006 Empty
  • P007 Span
  • P833 TVT Start Min

Use this feature if the surface is reported to be near the transducer face but is in fact much further away. Extend this value when changing transducer location, mounting, or aiming.

Please note that changing the Near Blanking cannot correct measurement problems. Ensure that Span (P007) < Empty (P006) minus Near Blanking (P800)

Show 8 more labels / short text on this page
Primary Index · 0 Read Only · 1 * Read/Write · Values · Primary Index · Global Transducer · Values · Related
Page 210 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 210 · click to enlarge
Page 210

P801 Range Extension

Allows the material level to fall below the Empty setting without reporting LOE.

Single Point Model Dual Point Model

Range0.000 to 99.00 m, or max. span (P007), or equivalent depending on units
Preset20% of Span (P007)
  • P005 Units
  • P006 Empty
  • P007 Span
  • P004 Transducer

This feature is useful in OCM applications where the Empty level is set to the bottom of the weir, and above the bottom of the channel, and should be used if the surface monitored can fall past the Empty (P006) level in normal operation. The value is added to Empty (P006) and can be greater than the range of the transducer. If the surface monitored can extend beyond Empty (P006), increase Range Extension (in Units (P005) or % of Span) such that Empty plus Range Extension is greater than the transducer face to furthest surface to be monitored distance. This is often the case with OCM when using weirs and some flumes.

P802 Transducer with Submergence Shield

Used when the transducer is expected to be submerged on occasion.

Single Point Model Dual Point Model

  • P006 Empty
  • P071 Failsafe Material Level
  • Relays

When a transducer with a submergence shield is submerged, the shield traps an air pocket that creates a special echo. The MultiRanger recognizes the echo and advances the reading to the highest level and operates displays and outputs accordingly. This feature is effective for when power is returned while the transducer is submerged.

Show 10 more labels / short text on this page
Primary Index · Global Transducer · Values · Related · Primary Index · Global Transducer · 0 * Off · Values · 1 Submergence transducer · Related
Page 211 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 211 · click to enlarge
Page 211

P803 Shot / Pulse Mode

Determines what type of ultrasonic shots are fired.

Single Point Model Dual Point Model

2 * Short and long

  • P006 Empty
  • P805 Echo Confidence
  • P804 Confidence Threshold
  • P852 Short Shot Range

Increases MultiRanger response when the monitored surface is close to the transducer face. Select short and long to have short and long acoustic shots fired for each measurement, regardless of the transducer to surface distance. Select short to have only short shots fired if the Echo Confidence (P805) produced by a short shot exceeds the short Confidence Threshold (P804) and the monitored surface is always within the Short Shot Range (P852).

P804 Confidence Threshold

Determines which echoes are evaluated by software.

Single Point Model Dual Point Model

Range0 to 99:0 to 99
Preset10:5

Related • P805 Echo Confidence

The short and long shot Confidence Thresholds are preset to 10 and 5 respectively. When Echo Confidence (P805) exceeds the Confidence Threshold, the echo is evaluated by Sonic Intelligence®. Values are entered as two numbers separated by a decimal point. The first number is the short shot confidence and the second number is the long shot confidence.

Show 8 more labels / short text on this page
Primary Index · Global Transducer · 1 Short · Values · Related · Primary Index · Global Transducer · Values
Page 212 of the Siemens 200 user manual — P807 Noise
Page 212 · click to enlarge
Page 212

P805 Echo Confidence

Displays the echo confidence of the measurement echo from the last shot.

Formatx:y (view only)

x = short (0 to 99)

y = long (0 to 99)

  • Related
  • P804 Confidence Threshold
  • P830 TVT Type

Use this feature to monitor the effect of transducer aiming, location, and mechanical transducer / mounting isolation.

Both short and long shot Echo Confidence is displayed. (To display this value in the

auxiliary display while the unit is running, press for 4 seconds.)

Display Description x:-- short shot confidence value, (long shot not used). --:y long shot confidence value, (short shot not used). x:y short and long shot confidence values (both used). E transducer cable is open or short circuited. --:-- no shots were processed for Sonic Intelligence® evaluation.

P806 Echo Strength

Displays the strength (in dB above 1 uV RMS) of the echo which was selected as the measurement echo.

Values Format0 to 99 (view only)

P807 Noise

Displays the average and peak ambient noise (in dB above 1 uV RMS) being processed.

Formatx:y (view only)

x = average (-99 to 99)

y = peak (-99 to 99)

The noise level is a combination of transient acoustic noise and electrical noise (induced into the transducer cable or receiving circuitry). See Noise Problems in the Troubleshooting Section on page 232.

Show 5 more labels / short text on this page
Primary Index Transducer · Values · Primary Index Transducer · Primary Index Transducer · Values
Page 213 of the Siemens 200 user manual — P816 Echo Time Raw
Page 213 · click to enlarge
Page 213

Advanced Echo Processing (P815 to P825)

The following parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques.

P815 Echo Time Filtered

The time (in ms) from the transmission of the pulse, to when it is processed.

Values Range0.0 to 9999 (view only)

Related • P816 Echo Time Raw

P816 Echo Time Raw

The time (in ms) from the transmit pulse to the processed echo.

Values Range0.0 to 9999 (view only)

Related • P815 Echo Time Filtered

Primary Index Transducer · Primary Index Transducer

Page 214 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 214 · click to enlarge
Page 214

P820 Algorithm

Chooses the algorithm to generate the measured value from the profile.

Single Point Model Dual Point Model

Values 1 ALF = flat Area, Largest, and First average

2 A = flat Area only

3 L = flat Largest only

4 F = flat First only

5 AL = flat Area and Largest average

6 AF = flat Area and First average

7 LF = flat Largest and First average

8 * bLF = smooth Largest or First

9 bL = smooth Largest only

10 bF = smooth First only

12 tF = true First only

  • P805 Echo Confidence
  • P821 Spike Filter
  • P822 Narrow Echo Filter
  • P823 Reform Echo
  • P825 Echo Marker Trigger

Use this to select the algorithm(s) the Sonic Intelligence® echo selection is based on. Use P805 Echo Confidence (page 202) to determine which algorithm gives the highest confidence under all level conditions. If the wrong echo is processed, observe the echo processing displays and select an alternate algorithm, either by entering the numeric value desired, or as below:

1. Press MEASURE to display the Auxiliary Function symbol.
2. Press ARROWS to access the desired Reading display symbols.
3. Press ENTER when the required algorithm is displayed.

Primary Index · Global Transducer · Related

Page 215 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 215 · click to enlarge
Page 215

P821 Spike Filter

Dampens spikes in the echo profile to reduce false readings.

Single Point Model Dual Point Model

  • P820 Algorithm
  • P822 Narrow Echo Filter
  • P823 Reform Echo
  • P825 Echo Marker Trigger

Use P821 if interference spikes are on the long shot Echo Profile display.

P822 Narrow Echo Filter

Filters out echoes of a specific width.

Single Point Model Dual Point Model

0 = OFF (preset), nearest acceptable value returned

  • P820 Algorithm
  • P821 Spike Filter
  • P823 Reform Echo
  • P825 Echo Marker Trigger

Use this for transducer acoustic beam interference (e.g. ladder rungs). Enter the width of false echoes (in ms) to be removed from the long shot Echo Profile. When a value is keyed in, the nearest acceptable value is entered.

Show 11 more labels / short text on this page
Primary Index · Global Transducer · 0 Off · Values · 1 * On · Related · Primary Index · Global Transducer · Values · greater = wider · Related
Page 216 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 216 · click to enlarge
Page 216

P823 Reform Echo

Smoothes jagged peaks in the echo profile.

Single Point Model Dual Point Model

0 = OFF (preset)

greater = wider, nearest acceptable value returned

  • P002 Material
  • P820 Algorithm
  • P821 Spike Filter
  • P822 Narrow Echo Filter
  • P825 Echo Marker Trigger

Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates slightly, though the monitored surface is still. Enter the amount (in ms) of long shot Echo Profile smoothing required. When a value is keyed in, the nearest acceptable value is entered.

P825 Echo Marker Trigger

The point on the primary echo on which the measured value is based.

Single Point Model Dual Point Model

Range5 to 95%
Preset50%
  • P820 Algorithm
  • P821 Spike Filter
  • P822 Narrow Echo Filter
  • P823 Reform Echo

Use this feature if the reported material level fluctuates slightly, due to a variable rise in the leading edge of the true echo on the Echo Profile.

Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo. This value is preset to 50%.

Show 8 more labels / short text on this page
Primary Index · Global Transducer · Values · Related · Primary Index · Global Transducer · Values · Related
Page 217 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 217 · click to enlarge
Page 217

Advanced TVT Adjustment (P830 to P835)

The following parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques.

Advanced TVT control applies to long shots only.

P830 TVT Type

Selects the TVT Curve used.

Single Point Model Dual Point Model

1 * TVT Short Curved

2 TVT Short Flat

3 TVT Long Flat

4 TVT Long Smooth Front

5 TVT Long Smooth

Altered By • P002 Material

  • Related
  • P805 Echo Confidence
  • P835 TVT Slope Min

Select the TVT type which gives the highest confidence (P805) under all level conditions. Use this parameter with caution, and do not use TVT Slopes with the bF or bLF Algorithm (P820).

P831 TVT Shaper

Turns the TVT Shaper ON or OFF.

Single Point Model Dual Point Model

Related • P832 TVT Shaper Adjust

Turn the TVT Shaper ON before using P832 and afterwards. Turn the TVT Shaper ON and OFF while monitoring the effect to pick up the true echo.

Show 9 more labels / short text on this page
Primary Index · Global Transducer · Values · 6 TVT Slopes · Primary Index · Global Transducer · 0 * Off · Values · 1 On
Page 218 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 218 · click to enlarge
Page 218

P832 TVT Shaper Adjust

Allows manual adjustment of the TVT curve. Use this parameter in conjunction with Dolphin Plus PC Software.

Single Point Model Dual Point Model

Breakpoint Transducer and Breakpoint

Range-50 to 50
Preset0

Related • P831 TVT Shaper

Use this feature to bias the shape of the TVT curve to avoid selecting false echoes from fixed objects.

Adjustment to this parameter is best done while viewing the echo profile with Dolphin Plus. Refer to the Dolphin Plus online help for details.

The TVT curve is divided into 40 breakpoints, accessible by enabling the point number as the breakpoint index field. Each breakpoint is normalized to a value of 0, as displayed in the parameter value field. By changing the breakpoint value, up or down, the intensity of the bias applied to that breakpoint of the curve is respectively changed. By changing the value of adjacent breakpoints, the effective bias to the shaper can be broadened to suit the desired correction. In the case of multiple false echoes, shaping can be applied along different points of the curve. Shaping should be applied sparingly in order to avoid missing the true echo.

P833 TVT Start Min

Use this feature to adjust the TVT Curve height to ignore false echoes (or pick up true echoes) near the start of the Echo Profile.

Single Point Model Dual Point Model

Range-30 to 225
Preset50
  • Related
  • P800 Near Blanking
  • P834 TVT Start Duration

Enter the minimum TVT Curve start point (in dB above 1 uV RMS).

This feature should only be used if increased Near Blanking (P800) would extend farther than desired into the measurement range.

Show 5 more labels / short text on this page
Primary Index · Values · Primary Index · Global Transducer · Values
Page 219 of the Siemens 200 user manual — Primary Index Single Point Model Dual Point Model
Page 219 · click to enlarge
Page 219

P834 TVT Start Duration

Use this feature in conjunction with TVT Start Min (P833) to ignore false echoes (or pick up true echoes) near the start of the Echo Profile.

Single Point Model Dual Point Model

Range0 to 9999
Preset30
  • Related
  • P833 TVT Start Min
  • P835 TVT Slope Min

Enter the time (in ms) for the TVT Curve to decrease from the TVT Start Min (P833) point to the TVT Curve baseline.

P835 TVT Slope Min

Enter the minimum slope (in dB/s) for the middle of the TVT Curve.

Primary Index Single Point Model Dual Point Model

Values Range0 to 9999
Preset200
  • Related
  • P830 TVT Type
  • P834 TVT Start Duration

Use this feature to adjust the slope declination, and use it in conjunction with TVT Start Duration (when a long flat TVT Type is selected) to ensure the TVT Curve remains above the false echoes in the middle of the Echo Profile. Alternatively, if TVT Type is set for TVT Slopes (P830 = 6), preset is 2000.

Show 4 more labels / short text on this page
Primary Index · Global Transducer · Values · Global Transducer
Page 220 of the Siemens 200 user manual — Values
Page 220 · click to enlarge
Page 220

P837 Auto False-Echo Suppression

Use P837 and P838 together, to set MultiRanger 100/200 to ignore false echoes. Use P838 to set the Auto TVT distance first.

  • Notes:
  • This function works best when the vessel is empty or nearly empty: use it only if there is a minimum distance of 2 meters from the transducer face to the material.
  • Set P837 and P838 during start up, if possible.
  • If the vessel contains an agitator, the agitator should be running.

If MultiRanger 100/200 displays a full level, or if the reading fluctuates between a false high level and a correct level, set P837 to elevate the TVT in this region and to de- sensitize the receiver from any ‘base noise’ caused by internal transducer reflections, nozzle echoes, or other vessel false echoes. Set P838 and then P837 (detailed instructions follow P838).

1 Use ’learned’ TVT. (See ’learned TVT curve’ in Display after Auto False Echo Suppression on page 211.)

Values

Display before Auto False Echo Suppression

(or when P837 = 0)

Siemens 200 — Values diagram (page 220)
Fig. 58 · Values
Show 8 more labels / short text on this page
0 * Off · 2 Learn · default TVT · true echo · P839 Hover Level · Level (db) · false echo · Distance (meters)
Page 221 of the Siemens 200 user manual — P839 TVT Hover Level
Page 221 · click to enlarge
Page 221

P838 Auto False-Echo Suppression Distance

Defines the range of Auto False-Echo Suppression (P837) to use for ignoring false echoes. (Units are defined in P005.)

Range (depends on model)

Maximum range0.000 to 15 m (50 ft)

Values

Default 1.000 m (3.28 ft)

Determine the actual distance from the transducer face to the material surface. Subtract 0.5 m from this distance, and enter the result.

Set Up:

1. Perform this function when the vessel is empty or nearly empty. 2. Determine actual distance from transducer face to material level. 3. Select P838 and key in [distance to material level minus 0.5 m].
4. Press ENTER . 5. Select P837.
6. Press 2 and then press ENTER . P837 will revert to 1 (use Learned TVT) automatically after a few seconds.

Display after Auto False Echo Suppression

Siemens 200 — Display after Auto False Echo Suppression diagram (page 221)
Fig. 59 · Display after Auto False Echo Suppression

TVT curve (learned) material level

P839 TVT Hover Level

Defines (in percent) how high the TVT curve is placed above the profile, relative to the largest echo. When MultiRanger 100/200 is located in the center of the vessel, lower this parameter to prevent multiple echo detections.

Values Range 0 to 100%

Show 4 more labels / short text on this page
Level (db) · false echo · Distance (meters) · Default 33 (%)
Page 222 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 222 · click to enlarge
Page 222

Advanced Shot Adjustment (P840 to P852)

These parameters are for Siemens Milltronics service personnel only. P840 Short Shot Number

The number of short shots to be fired (and results averaged) per transmit pulse.

Single Point Model Dual Point Model

Range0 to 100
Preset1
  • P841 Long Shot Number
  • P842 Short Shot Frequency
  • P844 Short Shot Width
  • P850 Short Shot Bias
  • P851 Short Shot Floor
  • P852 Short Shot Range

P841 Long Shot Number

Enter the number of long shots to be fired (and results averaged) per transmit pulse.

Single Point Model Dual Point Model

Range0 to 200
Preset5

Altered By • P003 Maximum Process Speed

  • P840 Short Shot Number
  • P843 Long Shot Frequency
  • P845 Long Shot Width

This value is automatically altered by Maximum Process Speed (P003).

Show 8 more labels / short text on this page
Primary Index · Global Transducer · Values · Related · Primary Index · Global Transducer · Values · Related
Page 223 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 223 · click to enlarge
Page 223

P842 Short Shot Frequency

Adjust the short shot transmit pulse frequency (in kHz).

Single Point Model Dual Point Model

Values Range41 to 46 kHz, nearest acceptable value is returned

Altered By • P004 Transducer

  • P840 Short Shot Number
  • P844 Short Shot Width
  • P850 Short Shot Bias
  • P851 Short Shot Floor
  • P852 Short Shot Range

This feature is automatically altered when Transducer (P004) is altered. P843 Long Shot Frequency

Adjust the long shot transmit pulse frequency (in kHz).

Single Point Model Dual Point Model

Values Range41 to 46 kHz, nearest acceptable value is returned

Altered By • P004 Transducer

  • P841 Long Shot Number
  • P842 Short Shot Frequency
  • P843 Long Shot Frequency
  • P845 Long Shot Width

This feature is automatically altered when Transducer (P004) is altered. P844 Short Shot Width

Adjust the width (in ms) of the short shot transmit pulse.

Single Point Model Dual Point Model

Values Range0.000 to 5.000

Altered By • P004 Transducer

  • P840 Short Shot Number
  • P842 Short Shot Frequency
  • P845 Long Shot Width
  • P850 Short Shot Bias
  • P851 Short Shot Floor
  • P852 Short Shot Range

This feature is automatically altered when Transducer (P004) is altered.

Show 9 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index · Global Transducer · Related · Primary Index · Global Transducer · Related
Page 224 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 224 · click to enlarge
Page 224

P845 Long Shot Width

Adjust the width (in ms) of the long shot transmit pulse.

Single Point Model Dual Point Model

Values Range0.000 to 5.000

Altered By • P004 Transducer

  • P841 Long Shot Number
  • P844 Short Shot Width
  • P843 Long Shot Frequency

This feature is automatically altered when Transducer (P004) is altered.

P850 Short Shot Bias

Use this feature to slant the echo evaluation in favour of the short shot echo when both short and long shots are evaluated (see Shot Mode, P803).

Single Point Model Dual Point Model

Range0 to 100
Preset20
  • P803 Shot / Pulse Mode
  • P840 Short Shot Number
  • P842 Short Shot Frequency
  • P844 Short Shot Width
  • P851 Short Shot Floor
  • P852 Short Shot Range

P851 Short Shot Floor

Enter the minimum echo strength (in dB above 1 uV) derived from a short shot to be considered for evaluation.

Single Point Model Dual Point Model

Range30 to 100
Preset50
  • P840 Short Shot Number
  • P842 Short Shot Frequency
  • P844 Short Shot Width
  • P850 Short Shot Bias
  • P852 Short Shot Range
Show 11 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index · Global Transducer · Values · Related · Primary Index · Global Transducer · Values · Related
Page 225 of the Siemens 200 user manual — F1 RAM
Page 225 · click to enlarge
Page 225

P852 Short Shot Range

Enter the maximum distance in Units (P005) to be measured using short shot echoes.

Single Point Model Dual Point Model

Values Range0 to 10 m, or equivalent depending on units

Altered By • P004 Transducer

  • P840 Short Shot Number
  • P842 Short Shot Frequency
  • P844 Short Shot Width
  • P850 Short Shot Bias
  • P851 Short Shot Floor

This feature is automatically altered when Transducer (P004) is altered.

Test (P900 to P913)

Test Parameters are intended for use by Siemens Milltronics Service personnel.

P900 Software Revision Number

View the EPROM Rev. #.

Values Range00.00 to 99.99 (view only)

P901 Memory

Press ENTER to activate the MultiRanger memory test.

Displayview only

PASS (memory test successful)

F1 RAM

Show 8 more labels / short text on this page
Primary Index · Global Transducer · Related · Primary Index Global · Primary Index Global · Values · F3 FLASH data · F4 FLASH code
Page 226 of the Siemens 200 user manual — P906 RS-232 Port
Page 226 · click to enlarge
Page 226

P902 Watchdog

Press ENTER to put the CPU into an infinite loop to test the watchdog timer.

On successful completion (10 seconds) the RUN mode is entered and the MultiRanger is reset. Programming is kept and the unit responds as if there had been a power failure.

P903 Display

Press ENTER to activate the display test.

All LCD segments and symbols are temporarily displayed.

P904 Keypad

Press ENTER , then press each keypad key in the following sequence:

P P

As each key is pressed, the associated keypad number is displayed. On successful test completion, PASS is displayed. FAIL is displayed if a key is pressed out of sequence or the programmer keypad malfunctions.

P905 Transmit Pulse

Press ENTER to supply repeated transmit pulses, at the frequency entered, to the transducer and / or view the transducer operating frequency (automatically altered by P004 Transducer) for the Point Number displayed.

Siemens 200 — P905 Transmit Pulse diagram (page 226)
Fig. 60 · P905 Transmit Pulse

P906 RS-232 Port

Siemens 200 — P906 RS-232 Port diagram (page 226)
Fig. 61 · P906 RS-232 Port

Press ENTER to test the RS-232 port on the RJ-11.

An external device must be connected to the RS-232 port for this test. On successful completion, PASS is displayed, otherwise it is FAIL.

Page 227 of the Siemens 200 user manual — P912 Transducer Temperature
Page 227 · click to enlarge
Page 227

P908 Scanner

Press ENTER to cycle the scanner relay while firing the transmitter.

Use this parameter to ensure that both transducers are being stimulated.

P910 Toggle Relays

Used to energize and de-energize relays directly.

Values 0 to 6

Related • P119 mA Relay Logic Test

Enter the relay number and then toggle between energized and de-energized, as required. Enter 0 to toggle all relays at once.

Applies only to relays with P119 = 0 (algorithm control). Use this parameter to confirm that relay contacts are opening and closing.

This feature is helpful when P119 does not give expected results even though programming was verified.

P911 mA Output Value

Access this parameter to display the current value of the mA output.

Primary Index mA output

Values Range0.10 to 25.00
  • Related
  • P200 mA Output Range
  • P201 mA Output Function

Additionally, this feature may be used to enter a desired value. The mA output immediately assumes the value entered regardless of any restrictions programmed.

P912 Transducer Temperature

Use this feature to display the temperature in °C (as monitored by the connected transducer).

Values Range-50 to 150

Err is displayed if the transducer is not equipped with an internal temperature sensor.

Primary Index Global · Primary Index Transducer

Page 228 of the Siemens 200 user manual — P920 Reading Measurement
Page 228 · click to enlarge
Page 228

P913 Sensor Temperature

Access this parameter to display the temperature in °C (as monitored by the TS-3).

Values Range-50 to 150

OPEn is displayed if a TS-3 is not connected.

P914 mA Input [MR 200]

Use this feature to display the mA input value (in mA).

Primary Index mA input

Values Range0.000 to 24.00

Measurement (P920 to P927)

All of these parameters are available in RUN mode and used to verify programming. See Readings in RUN Mode on page 23.

The range and values shown for each of these parameters depends on the Operation (P001) chosen. The readings for each operation are listed below.

To Access in RUN Mode

1. Ensure the device is in RUN mode.
2. Press .The Auxiliary Reading field becomes underscores P_ _ _

P

3. Type the parameter number. The field changes to the value of the specified

parameter. These parameters are also available in simulation mode. See the Testing the Configuration section page 85 for instructions on how to control the simulation direction and rate.

P920 Reading Measurement

Corresponds to the final reading after all programming is applied.

Please note that the following features apply only to the MultiRanger 200: Difference, Average, OCM, and Pump Totalizer.

Values Range-999 to 9999

In general this means that: P920 = (Reading x P061) + P062.

Primary Index Global · Primary Index Level

Page 229 of the Siemens 200 user manual — P923 Distance Measurement
Page 229 · click to enlarge
Page 229

Reading Measurements by Operation

P001 P050 = 0 P050 ≠ 0

0. OFF -
1. Level P921 P924
2. Space P922 100% - P924
3. Distance P927 P927
4. Difference [MR 200] P921 (indexed) P921 (indexed)
5. Average [MR 200] P921 (indexed) P921 (indexed)

6 – OCM [MR 200] P925 P925

7. Pump Totalizer [MR 200] P924 P924

P921 Material Measurement

The distance in Units (P005) or % of Span (P007) between Empty (P006) and the monitored surface.

Values Range-999 to 9999 (view only)
  • P005 Units
  • P006 Empty
  • P007 Span

P922 Space Measurement

The distance between the monitored surface and Span (P007).

Values Range0.000 to 9999 (view only)

Related • P007 Span

P923 Distance Measurement

The distance between the monitored surface and the transducer face.

Values Range0.000 to 9999 (view only)
Show 4 more labels / short text on this page
Primary Index Level · Related · Primary Index Transducer · Primary Index Transducer
Page 230 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 230 · click to enlarge
Page 230

P924 Volume Measurement [MR 200]

The calculated vessel capacity in Max Volume (P051) or % of Max Volume.

Please note that Volume Measurement is a MultiRanger 200 feature only.

Values Range0.000 to 9999 (view only)

Related • P051 Maximum Volume

P925 Flow Measurement [MR 200]

The calculated flowrate in Max Flow (P604) units or % of Max Flow.

Please note that Flow Measurement is a MultiRanger 200 feature only.

Single Point Model Dual Point Model

Values Range0.000 to 9999 (view only)

Related • P604 Maximum Flow

P926 Head Measurement [MR 200]

Corresponds to Head (the distance from Zero Head (P605) to the monitored surface in Units (P005) or % of Span (P007).

Please note that Head Measurement is a MultiRanger 200 feature only.

Single Point Model Dual Point Model

Values Range-999 to 9999 (view only)
  • P005 Units
  • P007 Span
  • P605 Zero Head
Show 6 more labels / short text on this page
Primary Index Level · Primary Index · Global Transducer · Primary Index · Global Transducer · Related
Page 231 of the Siemens 200 user manual — Single Point Model Dual Point Model
Page 231 · click to enlarge
Page 231

P927 Distance Measurement

The distance between the surface and the transducer face (displays only as % of Empty).

Values Range0.000 to 9999% (Displays as % of Empty) (view only)
  • Related
  • P005 Units
  • P006 Empty

Use P923 unless the distance information is required in percent.

Master Reset (P999)

This feature resets all parameters to original values.

Single Point Model Dual Point Model

Values See below.

Use this feature prior to initial programming if arbitrary Parameter Values were used during a bench test, or after upgrading the software. Following a Master Reset, complete reprogramming is required.

To perform a Master Reset, access P999 and press CLEAR . C.ALL displays until the reset is complete.

In dual point units, both points can be reset at the same time by setting the index to 00

and pressing the CLEAR keys.

Primary Index Transducer · Primary Index · Global Transducer

Page 232 of the Siemens 200 user manual — Notes:
Page 232 · click to enlarge
Page 232

Notes:

Page 234 of the Siemens 200 user manual — Dolphin Plus Display
Page 234 · click to enlarge
Page 234

Appendix B: Technical Reference

Transmit Pulse

The transmit pulse consists of one or more electrical “shot” pulses, which are supplied to the transducer connected to the MultiRanger terminals. The transducer fires an acoustic “shot” for each electrical pulse supplied. After each shot is fired, sufficient time is provided for echo (shot reflection) reception before the next (if applicable) shot is fired. After all shots of the transmit pulse are fired, the resultant echoes are processed. The transmit pulse shot number, frequency, duration, delay, and associated measurement range are defined by parameters P803 and P840 to P852.

Appendix BTech Reference

Echo Processing

Echo processing consists of echo enhancement, true echo selection, and selected echo verification.

Echo Enhancement is achieved by filtering (P821 and P822) and reforming (P823) the echo profile. The true echo (echo reflected by the intended target) is selected when that portion of the echo profile meets the evaluation criteria of Sonic Intelligence®. Insignificant portions of the echo profile outside of the measurement range (Span P006 + Range Extension P801), below the TVT Curve (P830, and P832 to P835), and less than the Confidence Threshold (P804) and Short Shot Floor (P851) are automatically disregarded. The remaining portions of the Echo Profile are evaluated using the Algorithm (P820) and Short Shot Bias (P850). The Echo Profile portion providing the best Echo Confidence (P805) is selected.

True echo verification is automatic. The position (relation in time after transmit) of the new echo is compared to that of the previously accepted echo. When the new echo is within the Echo Lock Window (P713), it is accepted and displays, outputs, and relays are updated per the Fuzz Filter (P710) and Rate Parameters (P700 to P703). If the new echo is outside of the Window, it is not accepted until Echo Lock (P711) requirements are satisfied.

Dolphin Plus Display

Siemens 200 — Dolphin Plus Display diagram (page 234)
Fig. 62 · Dolphin Plus Display
Show 4 more labels / short text on this page
Cursor · Echo Marker · TVT Curve · Echo Profile
Page 235 of the Siemens 200 user manual — Display before Auto False Echo Suppression
Page 235 · click to enlarge
Page 235

TVT (Time Varying Threshold) curves

A TVT curve describes a threshold below which any echoes will be ignored. The default TVT curve is used, until P837 and P838 are used to create a new ’learned TVT curve’.

Auto False-Echo Suppression

False echoes can be caused by an obstruction in the beam path (pipes, ladders, chains, and such). Such false echoes may rise above the default TVT curve.

P838 allows you to set a distance, and P837 then instructs the MultiRanger to ’learn’ where the obstructions/false echoes are within that distance. The new TVT curve is set above the false echoes, screening them out.

Appendix BTech Reference

Display before Auto False Echo Suppression

(or when P837 = 0)

Display after Auto False Echo Suppression

TVT curve (learned) material level

Show 9 more labels / short text on this page
default TVT · true echo · P839 Hover Level · Level (db) · false echo · Distance (meters) · Level (db) · false echo · Distance (meters)
Page 236 of the Siemens 200 user manual — Sound Velocity
Page 236 · click to enlarge
Page 236

Distance Calculation

To calculate the transducer to material level (object) distance, the transmission medium (atmosphere) sound velocity (P653) is multiplied by the acoustic transmission to reception time period. This result is divided by 2 to calculate the one way distance.

Distance = Sound Velocity x Time / 2

The Reading displayed is the result of performing any additional modification to the calculated distance (as determined by Operation P001, Units P005, Volume Conversion, P050 to P054, Reading, P060 to P063, OCM, P600 to P611, and/or Totalizer P622 to P633 parameters).

Appendix BTech Reference

Sound Velocity

The sound velocity of the transmission medium is affected by the type, temperature, and vapor pressure of the gas or vapor present. As preset, the MultiRanger assumes the vessel atmosphere is air at 20°C (68°F). Unless altered, the sound velocity used for the distance calculation is 344.1 m / s (1129 ft / s).

Variable air temperature is automatically compensated when a Siemens Milltronics ultrasonic / temperature transducer is used. If the transducer is exposed to direct sunlight, use a sunshield or a separate TS-3 temperature sensor.

Also, if the temperature varies between the transducer face and the liquid monitored, use a TS-3 temperature sensor (submerged in the liquid) in combination with an ultrasonic / temperature transducer. Set Temp Source (P660) for both, to average the transducer and TS-3 measurements.

Atmosphere composition other than air can pose a challenge for ultrasonic level measurement. However, excellent results may be obtained by performing a Sound Velocity Calibration (P651) if the atmosphere is homogeneous (well mixed), at a fixed temperature, and under consistent vapor pressure.

The MultiRanger automatic temperature compensation is based on the sound velocity / temperature characteristics of “air” and may not be suitable for the atmosphere present. If the atmosphere temperature is variable, perform frequent Sound Velocity Calibrations to optimize measurement accuracy.

Sound Velocity calibration frequency may be determined with experience. If the sound velocity in two or more vessels is always similar, future calibrations may be performed on one vessel and the resultant Velocity (P653) entered directly for the other vessel(s).

If the sound velocity of a vessel atmosphere is found to be repeatable at specific temperatures, a chart or curve may be developed. Then, rather than performing a Sound Velocity Calibration each time the vessel temperature changes significantly, the anticipated Velocity (P653) may be entered directly.

Page 237 of the Siemens 200 user manual — Volume Calculation [MR 200]
Page 237 · click to enlarge
Page 237

Scanning

MultiRanger 100/200

When echo processing is complete (if more than 1 vessel is monitored) the scanning relay changes state to supply the transmit pulse to the other transducer after the Scan Delay (P727).

Scan Delay is automatically set by Maximum Process Speed (P003). When high speed scanning is required (sometimes the case for equipment position monitoring), the Scan Delay may be reduced. Reduce the Scan Delay only as required, otherwise premature scanning relay fatigue could occur.

Appendix BTech Reference

MultiRanger 200

When two transducers are connected and configured in a dual point unit, the MultiRanger will scan each in turn via the scanner relay. When a single point MultiRanger is programmed for differential or average level Operation (P001 = 4 or 5), two transducers of the same type must be used.

Volume Calculation [MR 200]

Please note that the Volume Calculation feature is only available on the MultiRanger 200.

The unit provides a variety of volume calculation features (P050 to P055).

If the vessel does not match any of the eight preset Tank Shape calculations, a Universal Volume calculation may be used. Use the level/volume graph or chart provided by the vessel fabricator (or create one based on the vessel dimensions). Based on the graph, choose the Universal Volume calculation, and select the level vs. volume breakpoints to be entered (32 max). Generally, the more breakpoints entered, the greater the accuracy.

Universal, Linear (P050 = 9)

This volume calculation creates a piece-wise linear approximation of the level/volume curve. This option provides best results if the curve has sharp angles joining relatively linear sections.

Enter a Level Breakpoint at each point where the level/volume curve bends sharply (2 minimum).

For combination curves (mostly linear but include one or more arcs), enter numerous breakpoints along the arc, for best volume calculation accuracy.

Page 238 of the Siemens 200 user manual — Flow Calculation
Page 238 · click to enlarge
Page 238

Universal, Curved [MR 200]

Please note that the Universal, Curved feature is only available on the MultiRanger 200.

Set P050 = 10

This calculation creates a cubic spline approximation of the level/volume curve, providing best results if the curve is non-linear, and there are no sharp angles.

Siemens 200 — Universal, Curved [MR 200] diagram (page 238)
Fig. 63 · Universal, Curved [MR 200]
Appendix BTech Reference

Select at least enough breakpoints from the curve to satisfy the following:

  • two breakpoints very near the minimum level
  • one breakpoint at the tangent points of each arc
  • one breakpoint at each arc apex
  • two breakpoints very near the maximum level For combination curves, enter at least two breakpoints immediately before and after any sharp angle (as well as one breakpoint exactly at the angle) on the curve.

Flow Calculation

Please note that the Flow Calculation feature is only available on the MultiRanger 200.

The MultiRanger provides numerous OCM flow calculation features (P600 to P611).

If the PMD (primary measuring device) does not match any of the eight preset PMD calculations, or if a PMD is not used, select a Universal Volume calculation. Use the head/ flow graph or chart provided by the PMD fabricator (or create one based on the PMD or channel dimensions).

Based on the graph, choose the Universal Flow calculation, and select the head versus flow breakpoints to be entered (32 max). Generally, the more breakpoints entered, the greater the flow calculation accuracy.

Page 239 of the Siemens 200 user manual — Select at least enough breakpoints from the curve to satisfy the following:
Page 239 · click to enlarge
Page 239

Universal, Linear [MR 200]

Please note that the Universal, Linear feature is only available on the MultiRanger 200.

Set P600 = 4.

This flow calculation creates a piece-wise linear approximation of the head/flow curve. This option provides best results if the curve has sharp angles joining relatively linear sections.

Appendix BTech Reference

Enter a Head Breakpoint at each point where the head/flow curve bends sharply (2 minimum). For combination curves (mostly linear but include 1 or more arcs), enter numerous breakpoints along the arc, for best flow calculation accuracy.

See also Typical Flow Characterization on page 83.

Universal, Curved [MR 200]

Please note that the Universal, Curved feature is only available on the MultiRanger 200.

This calculation creates a cubic spline approximation of the head/flow curve, providing best results if the curve is non-linear, and there are no sharp angles.

Select at least enough breakpoints from the curve to satisfy the following:

  • two breakpoints very near the minimum head
  • one breakpoint at the tangent points of each arc
  • one breakpoint at each arc apex
  • two breakpoints very near the maximum head
Page 240 of the Siemens 200 user manual — Parameter Values Dependent on Maximum Process
Page 240 · click to enlarge
Page 240

For combination curves, enter at least 2 breakpoints immediately before and after any sharp angle (as well as 1 breakpoint exactly at the angle) on the curve. For more information, go to Typical Flow Characterization on page 83.

Maximum Process Speed

The MultiRanger’s ability to respond to material level changes is designed to exceed even the most demanding installation requirements.

The Maximum Process Speed setting automatically presets various parameters affecting the MultiRanger response to material level changes as follows:

Appendix BTech Reference

Parameter Values Dependent on Maximum Process

Speed (P003) (units) 1 (slow) 2 (medium) 3 (fast) P070 Failsafe Timer (min) 100 10 1 P700 Max Fill Rate (m/min) 0.1 1 10 P701 Max Empty Rate (m/min) 0.1 1 10 P702 Filling Indicator (m/min) 0.01 0.1 1 P703 Emptying Indicator (m/min) 0.01 0.1 1 P704 Rate Filter (option) 4 2 2 P710 Fuzz Filter (% of Span) 100 50 10 P713 Echo Lock Window (per P701 / P702 and time since last valid measurement) P727 Scan Delay (seconds) 5 5 3 P841 Long Shot Number 10 5 2

If any of these parameters are independently altered, a Maximum Process Speed (P003) parameter alteration automatically resets the independently altered value.

Slower Maximum Process Speed (P003) provides greater measurement reliability. Faster, independently set Max Fill (P700) and Max Empty (P701). Rates may be impeded by Echo Lock (P711), Scan Delay (P727), and Shot Delay (P728) values.

Page 241 of the Siemens 200 user manual — Appendix C: Troubleshooting
Page 241 · click to enlarge
Page 241

Appendix C: Troubleshooting

If the setup becomes too confusing use P999 to reset and start again. Common Problems Chart

Symptom Cause Action Display blank, transducer not pulsing. No power. Check power supply, wiring, or power fuse.

Check programmer usage: 15 cm (6”) from faceplate pointed at upper target.

No response to program- mer.

Obstructed infrared interface, defective programmer.

Short circuited transducer cable, or defective transducer at indi- cated terminal block number.

Displays Short and tb:(#).

Repair or replace as necessary.

Transducer not connected or con- nection reversed.

Check connection to displayed ter- minal blocks. Open circuited transducer cable, or defective transducer at indi- cated terminal block number.

Appendix CTroubleshooting

Displays Open and tb:(#).

Repair or replace as necessary.

Relocate and/or re-aim transducer at material. Proceed to Measurement Difficul- ties.

Displays LOE. Weak or non-existent echo.

Wrong transducer selected (P004).

Verify transducer type and re-enter value. Transducer connected in “two wire” method.

Do not tie white and shield together. Use all three terminal blocks. Transducer connected back- wards.

Displays Error and tb:(#).

Reverse black and white wires on terminal block.

Displays EEEE Value too large to display in 4 or 5 characters.

Select larger Units (P005), or lower Convert Reading (P061). Reading fluctuates while material level is still (or vice versa).

Alter Maximum Process Speed (P003) or damping (P704) accord- ingly. See Maximum Process Speed.

Incorrect measurement stabiliza- tion.

Relocate and / or re-aim transducer at material level or object. Proceed to Measurement Difficul- ties below. See also: Transducer Ringing. Material level reported is always incorrect by the same amount.

Transducer acoustic beam obstructed, standpipe too nar- row, or transducer ringing (reads over 100%).

Reading is fixed, regard- less of the actual mate- rial level.

Incorrect Empty (zero) reference for level operation (P001 = 1).

See Empty (P006), Reading Offset (P063), Offset Calibration (P650), & Offset Correction (P652).

Measurement accuracy improves as level nears transducer.

Use a transducer with a built-in tem- perature sensor or a TS-3 tempera- ture sensor. See Sound Velocity.

Incorrect Sound Velocity used for distance calculation.

Reading is erratic, with little or no relation to material level.

Relocate and / or re-aim transducer at material. Check noise parameters. See Noise Problems.

True echo too weak or wrong echo being processed.

Page 242 of the Siemens 200 user manual — Acoustical Noise
Page 242 · click to enlarge
Page 242

Noise Problems

Incorrect readings can be the result of noise problems, either acoustic or electrical, in the application.

The noise present at the input to the ultrasonic receiver can be determined by viewing parameter P807. The display reads ##:##, where the first number is the average noise and the second is the peak noise. In general, the most useful value is the average noise.

With no transducer attached the noise is under 5 dB. This is often called the noise floor. If the value with a transducer attached is greater than 5 dB, then signal processing problems can occur. High noise decreases the maximum distance that can be measured. The exact relationship between noise and maximum distance is dependent on the transducer type and the material being measured. Any average noise level greater than 20 dB is probably cause for concern unless the distance is much shorter than the maximum for the transducer.

Determine the Noise Source

Disconnect the transducer from the MultiRanger. If the measured noise is below 5 dB, then continue here. If the measured noise is above 5 dB go to Non-Transducer Noise Sources below.

Appendix CTroubleshooting
1. Connect only the shield wire of the transducer to the MultiRanger. If the measured noise is below 5 dB, continue with the next step. If the noise is above 5 dB, go to Common Wiring Problems. 2. Connect the white and black transducer wires to the MultiRanger. Record the

average noise. 3. Remove the positive wire of the transducer. Record the average noise. 4. Re-connect the positive wire and remove the negative wire. Record the average

noise. Using the table below, determine the appropriate next step. The terms higher, lower and unchanged refer to the noise recorded in the previous steps.

These are guidelines only. If the suggested solution does not solve the problem, try the other options also.

- removed + removed Go to:

higher Reducing Electrical Noise unchanged Common Wiring Problems lower Reducing Acoustical Noise

higher Reducing Electrical Noise unchanged Contact Siemens Milltronics lower Reducing Acoustical Noise

higher Common Wiring Problems unchanged Common Wiring Problems lower Reducing Acoustical Noise

Acoustical Noise

To confirm that the problem is acoustical, place several layers of cardboard over the face of the transducer. If the noise is reduced, the noise is definitely acoustical.

Show 4 more labels / short text on this page
higher · noise · unchanged · lower
Page 243 of the Siemens 200 user manual — Reducing Acoustical Noise
Page 243 · click to enlarge
Page 243

Non-Transducer Noise Sources

Remove all input and output cables from the MultiRanger individually while monitoring the noise. If removing a cable reduces the noise, that cable may be picking up noise from adjacent electrical equipment. Check that low voltage cables are not being run adjacent to high voltage cables or near to electrical noise generators such as variable speed drives.

Filtering cables is an option but is not recommended unless all other options have been exhausted.

The MultiRanger is designed to work near heavy industrial equipment such as variable speed drives. Even so, it should not be located near high voltage wires or switch gear.

Try moving the electronics to a different location. Often moving the electronics a few meters farther from the source of noise will fix the problem. Shielding the electronics is also an option, but it should be a last resort. Proper shielding is expensive and is difficult to install properly–the shielding box must enclose the MultiRanger electronics completely, and all wires must be brought to the box through grounded metal conduit.

Common Wiring Problems

  • Make sure that the transducer shield wire is connected at the electronics end only. Do not ground it at any other location.
  • Do not connect the transducer shield wire to the white wire.
  • The exposed transducer shield wire must be as short as possible.
  • Connections between the wire supplied with the transducer, and any customer installed extension wire should be done in grounded metal junction boxes. On Siemens Milltronics transducers the white wire is negative and the black wire is positive. If the extension wire is colored differently, make sure that it is wired consistently.
Appendix CTroubleshooting

Extension wire must be shielded twisted pair. Older MultiRanger products may have included recommendations to use co-axial cable for noise reduction purposes. This is no longer the case. Use shielded twisted pair. See the installation section for specifications.

Reducing Electrical Noise

  • Ensure that the transducer cable does not run parallel to other cables carrying high voltage or current.
  • Move the transducer cable away from noise generators like variable speed drives.
  • Put the transducer cable in grounded metal conduit.
  • Filter the noise source.

Reducing Acoustical Noise

  • Move the transducer away from the noise source.
  • Use a stilling well.
  • Install a rubber or foam bushing or gasket between the transducer and the mounting surface.
  • Relocate or insulate the noise source.
  • Change the frequency of the noise. The MultiRanger is only sensitive to noise between 25 KHz and 65 KHz.
Page 244 of the Siemens 200 user manual — Displaying Echoes
Page 244 · click to enlarge
Page 244

Measurement Difficulties

If the Failsafe Timer (P070) expires due to a measurement difficulty, LOE flashes alternately with the last known Reading. In rare cases, the MultiRanger may lock on to a false echo and report a fixed or wrong reading.

Flashing LOE Display

The loss of echo (LOE) display appears when the echo confidence is below the threshold value set in P805 Echo Confidence.

LOE occurs when:

  • The echo is lost and no echo is shown above the ambient noise. See low echo confidence (P805) and low echo strength (P806).
  • Two echoes are too similar to differentiate. See low echo confidence (P805) and low echo strength (P806).

If LOE is displayed, check the following:

  • Surface monitored is within the transducer maximum range
  • Transducer model (P004) matches the transducer used
  • Transducer is located and aimed properly
  • Transducer is not submerged without a submergence shield
Appendix CTroubleshooting

Adjust Transducer Aiming

See the transducer manual for range, mounting, and aiming details. For optimum performance, adjust transducer aiming to provide the best Echo Confidence (P805) and Echo Strength (P806) for all material levels within the measurement range.

The most efficient method of checking echoes is with Siemens Milltronics Dolphin Plus software.

Displaying Echoes

Editing Parameters

Siemens 200 — Displaying Echoes diagram (page 244)
Fig. 64 · Displaying Echoes

Use Dolphin Plus to graphically display the echo profile at the installation. Interpret the echo profile and change relevant parameters.

Edit the parameter values. Use F1 to get online help at any time.

Page 245 of the Siemens 200 user manual — Obstructions in the Sound Beam
Page 245 · click to enlarge
Page 245

To display Echo Confidence in the RUN mode

Press and hold for four seconds (Failsafe Time Left changes to the Short:Long Confidence display).

To display Echo Confidence in the program mode, access the Echo Confidence (P805) parameter.

To update the value displayed after each aiming adjustment..

Press (five times or more to verify stability and overcome any echo lock P711).

Increase Failsafe Timer Value

Increase the Failsafe Timer (P070) value, if failsafe operation will not be compromised by the larger value.

Try this only if LOE shows for short periods of time.

Install a Transducer with a Narrower Beam

Sometimes the interference echoes from the sides of a vessel can cause the MultiRanger to lock onto a consistent, incorrect level. Try installing a longer range (narrower beam) transducer, enter the new transducer model (P004), and (if necessary) optimize aiming and frequency again.

Always contact your Siemens Milltronics service personnel before selecting a transducer to solve this type of problem.

Appendix CTroubleshooting

Use Dolphin Plus to Debug Echo

If a narrower beam transducer is not available, use Dolphin Plus to view live sonic profiles and make adjustments to the Advanced Echo Processing parameters. Fixed Reading

If the Reading is a fixed value, regardless of the transducer to material surface distance, ensure the:

1. Transducer acoustic beam is free from obstruction. 2. Transducer is properly aimed 3. Transducer is not in contact with any metal object. 4. Material mixer (if used) is operating while the MultiRanger is operating. If it is

stopped, ensure that the mixer blade is not stopped under the transducer.

Obstructions in the Sound Beam

Check for (and remove if present) any acoustic beam obstruction, or relocate the transducer.

If an obstruction cannot be removed or avoided, adjust the Time Varying Threshold (TVT) Curve to reduce the Echo Confidence derived from the sound reflected by the obstruction. Use Dolphin Plus to adjust the TVT curve. (See P832: TVT Shaper.) Nozzle Mountings

If the transducer is mounted on or in a nozzle, grind smooth any burrs or welds on the inside or open end (the end that opens into the vessel). If the problem persists, install a

Page 246 of the Siemens 200 user manual — Set the MultiRanger to Ignore the Bad Echo
Page 246 · click to enlarge
Page 246

larger diameter or shorter length nozzle, bevel the inside of the bottom end, or cut the open end of the nozzle at a 45° angle.

See the transducer manual for complete mounting instructions.

For ST-series and XPS-10 transducers use the plastic conduit / flange adapter supplied with the unit.

If the mounting hardware is over tightened, loosen it. Over tightening changes the resonance characteristics of the transducer and can cause problems. Set the MultiRanger to Ignore the Bad Echo

If the preceding remedies have not fixed the problem, the false echo has to be ignored.

If the Echo is Close to the Transducer If there is a static, incorrect, high level reading from the MultiRanger there is probably something reflecting a strong echo back to the transducer. If the material level never reaches that point extend the Near Blanking (P800) to a distance to just past the obstruction.

Adjust the TVT to Ignore the Echo Use Auto False Echo Suppression (P837-P839) to automatically shape around false echoes. Wrong Reading

Appendix CTroubleshooting

If the Reading is erratic, or jumps to some incorrect value periodically, ensure the:

1. Surface monitored is not beyond the MultiRanger’s programmed range or the transducer’s maximum range. 2. Material is not falling into the transducer’s acoustic beam. 3. Material is not inside the blanking distance of the transducer. Types of Wrong Readings

If a periodic wrong Reading is always the same value, see Fixed Reading.

If the wrong Reading is random, ensure the material surface to transducer distance is less than the Empty value entered plus 20%. If the material/object monitored is outside this distance, increase Range Extension (P801) as required. This error is most common in OCM applications using weirs. Liquid Splashing

If the material monitored is a liquid, check for splashing in the vessel. Enter a lower Maximum Process Speed (P003) value to stabilize the Reading, or install a stilling well. (Contact Siemens Milltronics or your local distributor.) Adjust the Echo Algorithm

Use Dolphin Plus to view live sonic profiles and make adjustments to the P820 Algorithm parameter. See P820 on page 204 for details.

If the “Area” algorithm is used and narrow noise spikes are evident on the (long shot) Echo Profile, turn the Spike Filter (P821) on and/or widen the Narrow Echo Filter (P822). Also, if the true echo has jagged peaks, use Reform Echo (P823).

Page 247 of the Siemens 200 user manual — Poor Ring Down
Page 247 · click to enlarge
Page 247

If multiple echoes appear on the Echo Profile, typical of a flat material profile (especially if the vessel top is domed), use the “first” Algorithm.

If the Echo Profile repeatedly switches from short to long, adjust the Short Shot Range (P852) to stabilize the “shot” mode used for the echo evaluation. Also, adjust the Short Shot Bias to increase (or decrease the amount of preference given to short shot echoes over long shot echoes.

Should a stable measurement still not be attainable, contact Siemens Milltronics or your local distributor. Transducer Ringing

If the transducer is mounted too tightly, or if it is mounted so that its side touches something, its resonance characteristics change and this can cause problems.

Siemens 200 — Transducer Ringing diagram (page 247)
Fig. 65 · Transducer Ringing
Appendix CTroubleshooting

Poor Ring Down

Siemens 200 — Poor Ring Down diagram (page 247)
Fig. 66 · Poor Ring Down

Normal Ring Down

Page 248 of the Siemens 200 user manual — Unit Repair and Excluded Liability
Page 248 · click to enlarge
Page 248

Ring down times that extend past the near blanking area can be interpreted by the MultiRanger as the material level and are characterized by a steady high level being reported.

Unit Repair and Excluded Liability

All changes and repairs must be done by qualified personnel and applicable safety regulations must be followed. Please note the following:

  • The user is responsible for all changes and repairs made to the device.
  • All new components must be provided by Siemens Milltronics Process Instruments Inc.
  • Restrict repair to faulty components only
  • Do not re-use faulty components.
Appendix CTroubleshooting
Page 249 of the Siemens 200 user manual — MultiRanger 200
Page 249 · click to enlarge
Page 249

Appendix D: Pump Control Reference

Please note that some pump control features apply to the MultiRanger 200 only.

The MultiRanger has the pump control strategies to solve nearly any water / wastewater application. This section details these strategies for engineers requiring in-depth knowledge of the system and how it operates.

Pump Control Options

The various methods of pump control are made up of a combination of two control variables:

Pump Duty

The pump duty indicates in what sequence pumps are started.

Pump Start Method

The start method indicates whether new pumps start and run with any currently running pumps (most common) or whether new pumps start and shut off currently running pumps.

Pump Groups

The MultiRanger groups pumps that use identical pumping strategies based on the value of Relay Control Function (P111). Generally, one group of pumps corresponds to one wet well or reservoir.

Pump by Rate [MR 200]

Appendix DPump Control

Please note that this feature applies to the MultiRanger 200 only.

To trigger pump starts by the rate of change in material level use P121–Pump by Rate (P121). New pumps are started, one at a time, until the rate setpoint (Filling Indicator (P702), or Emptying Indicator(P703)) is reached.

Pump Control Algorithms

Please note that the MultiRanger 100 and the MultiRanger 200 use this feature differently.

MultiRanger 100

All of these algorithms can be used to start multiple pumps (assist).

MultiRanger 200

Page 250 of the Siemens 200 user manual — Relay Table
Page 250 · click to enlarge
Page 250

All of these algorithms can be used to start multiple pumps (assist) or one pump at a time (backup).

The MultiRanger 100 and MultiRanger 200 have three main methods of pump control:

Fixed

Starts pumps based on individual setpoints and always starts the same pumps in the same sequence.

Alternate

Starts pumps based on the duty schedule and always leads with a new pump.

Service Ratio

Starts pumps based on user-defined ratio of running time.

Fixed Duty Assist (P111 = 50)

Ties the indexed pump relay directly to the indexed setpoint.

Relay Operation (for P118 = 2)

The relay contact closes at the ON setpoint and opens at the OFF setpoint. Multiple relay contacts in the pump group can be closed at the same time.

Relay Table

The following table shows relay status when each setpoint is reached.

Relays

Index 1 2 3 On 3 On 2 On On Off On 1 On Off Off Off 0 Off Off Off

Appendix DPump Control

Setpoints

Fixed Duty Backup (P111 = 51) [MR 200]

Ties the indexed pump relay directly to the indexed setpoint.

Please note that this feature applies to the MultiRanger 200 only.

Relay Operation (for P118 = 2)

The relay contact closes at the ON setpoint and opens at the OFF setpoint. When a new relay trips the previously closed relay contact opens to shut down the running pump.

Only one relay contact in the pump group can be closed at any one time.

Relay Table

Page 251 of the Siemens 200 user manual — Relay Operation (for P118 = 2)
Page 251 · click to enlarge
Page 251

The following table shows relay status when each setpoint is reached.

Relays

Index 1 2 3 On 3 Off Off On On 2 Off On Off On 1 On Off Off Off 0 Off Off Off

Setpoints

Alternate Duty Assist (P111 = 52)

Alternates the lead pump each time the material level cycles and runs all pumps together.

Relay Operation (for P118 = 2)

The setpoints associated with the relays are grouped so that they can be rotated.

Setpoint one does not relate directly to relay one. The pumping algorithm manages the mapping of setpoints to relays.

When pumps are run, they RUN in parallel.

Relay Table

Cycle 1 Relays

Setpoints

On 3 On 2 On On Off On 1 On Off Off Off 0 Off Off Off Cycle 2 Relays

Setpoints

On 3 On 2 Off On On On 1 Off On Off Off 0 Off Off Off Cycle 3 Relays

Appendix DPump Control

Setpoints

On 3 On 2 On Off On On 1 Off Off On Off 0 Off Off Off

Alternate Duty Backup (P111 = 53) [MR 200]

Alternates the lead pump each time the material level cycles.

Please note that this feature applies to the MultiRanger 200 only.

Relay Operation (for P118 = 2)

The setpoints associated with the relays are grouped so that they can be rotated. Setpoint one does not relate directly to relay one. The pumping algorithm manages the mapping of setpoints to relays. When pumps are run, they can RUN only one at a time.

Page 252 of the Siemens 200 user manual — Relay Operation (for P118 = 2) [MR 200]
Page 252 · click to enlarge
Page 252

Relay Table

Cycle 1 Relays 1 2 3

Setpoints

On 3 Off Off On On 2 Off On Off On 1 On Off Off 0ff 0 Off Off Off

Cycle 2 Relays 1 2 3

Setpoints

On 3 On Off Off On 2 Off Off On On 1 Off On Off Off 0 Off Off Off Cycle 3 Relays 1 2 3

Setpoints

On 3 Off On Off On 2 On Off Off On 1 Off Off On Off 0 Off Off Off

Service Ratio Duty Assist (P111 = 54) [MR 200]

Selects the lead pump based on number of hours each pump has run and the specified ratios that each pump requires. Multiple pumps can run at one time.

Please note that this feature applies to the MultiRanger 200 only.

Relay Operation (for P118 = 2) [MR 200]

Please note that this feature applies to the MultiRanger 200 only.

Appendix DPump Control

The setpoints associated with the relays are grouped so they can be redistributed based on pump RUN time ratios. The next pump to start or stop is the one with the required time to actual time ratio.

Over time the number of hours demanded of each pump will conform to the ratios specified. Usually, the ratios are specified in percent values.

To create a grouping of pumps where two pumps make up 50% of the run time and the third pump makes up the other 50%.

P122 is set to these values:

P122 Index Value 1 25 2 25 3 50

Page 253 of the Siemens 200 user manual — Pump Group (P137)
Page 253 · click to enlarge
Page 253

Service Ratio Duty Backup (P111 = 55) [MR 200]

Selects the lead pump based on number of hours each pump has RUN and the specified ratios that each pump requires. Only one pump can RUN at a time.

Please note that this feature applies to the MultiRanger 200 only.

This algorithm is the same as Service Ratio Duty Assist except that it will only RUN one pump at a time. When the next pump in the sequence starts, the previous pump stops.

First In First Out (FIFO) (P111 = 56) [MR 200]

Selects the lead pump based on the Alternate duty but uses staggered off setpoints and shuts down pumps based on the first in, first out rule.

Please note that this feature applies to the MultiRanger 200 only.

This algorithm starts pumps in the same way as Alternate Duty Assist but uses staggered OFF setpoints to shut the pumps down. When the first OFF setpoint is reached the FIFO rule shuts down the first pump started. If the pumps started in sequence 2,3,1 then they would be shut down in sequence 2,3,1.

Pump by Rate (P121) [MR 200]

Starts pumps until the level is changing at the rate specified in P702 or P703.

Please note that this feature applies to the MultiRanger 200 only.

Pumping costs can be less because only the highest ON setpoint needs to be programmed and this results in a lower difference in head to the next wet well which, in turn, results in less energy being used to pump out the well.

Other Pump Controls [MR 200]

Appendix DPump Control

Please note that these features apply to the MultiRanger 200 only.

There are a number of other controls available to modify pump behaviour.

Pump Run-On (P130, P131)

Extends the RUN period for a pump based on a set time interval. This allows for the wet well to be pumped lower than usual and reduces sludge build-up on the well bottom.

Wall Cling Reduction (P136)

Varies the ON and OFF setpoints to keep a fat ring from forming around the walls of the wet well.

Pump Group (P137)

Allows for two different Alternate Duty Assist or Alternate Duty Backup pump groups in the same application.

Page 254 of the Siemens 200 user manual — Flush Device (P170 to P173)
Page 254 · click to enlarge
Page 254

Flush Device (P170 to P173)

Operates a flush valve or special flush device based on the number of pump starts, usually to aerate wet well wastewater.

Appendix DPump Control
Page 255 of the Siemens 200 user manual — Appendix E: Updating Software
Page 255 · click to enlarge
Page 255

Appendix E: Updating Software

Updating Software

To update the software in the MultiRanger, please contact your Siemens Milltronics representative to obtain the software. For a complete list of representatives, go to www.siemens.com/processautomation

To install the software, please complete the following:

1. Connect your PC or laptop to the MultiRanger RJ-11 RS-232 port. 2. Run the .exe Downloader program in the software. Use this to set the RS-232

settings to match your MultiRanger. Please note that the software default settings will already match the default settings of the unit. Changes are only necessary if the RS-232 settings in the unit have been changed. 3. Complete the Downloader program steps. 4. Verify that Downloader confirms a succesful upgrade before exiting. 5. Complete a Master Reset (P999) after a successful upgrade, before re-entering

Appendix EUpdating Software
Page 256 of the Siemens 200 user manual — Coaxial Transducer Extention
Page 256 · click to enlarge
Page 256

Appendix F: Upgrading

Appendix FUpgrading

The following procedure will assist you if you are upgrading from a MultiRanger Plus to a MultiRanger 100 or MultiRanger 200.

If the application is unchanged, copy down the parameters in the MultiRanger Plus before de-commissioning the unit.

Mounting a MultiRanger 100/200

Please read the MultiRanger Installation section on page 8 before mounting the new MultiRanger 100/200.

Make sure the power is OFF to the unit before following these steps:

1. Remove the old MultiRanger Plus. 2. Mount the new MultiRanger 100/200 using the same mounting holes.

Connecting the Transducer

If this is not practical, please refer to the Coaxial Transducer Extension section below.

Coaxial Transducer Extention

The MultiRanger 100/200 uses a new differential input receiver that works either directly connected to the transducer lead or with a screened twisted pair extension cable via a field junction box. This arrangement, using two conductors and a screen, gives considerably better electrical noise immunity than the previous coaxial arrangement (up to 20dB) and will give reliable operation in applications where the proximity of power cables, variable speed drives etc. would have caused problems.

If you are installing a new MultiRanger system we strongly recommend that you use a good quality screened, twisted pair cable if an extension is required. If the integral transducer cable is used you need only connect to the MultiRanger and benefit from the superior performance.

Transducer

Page 257 of the Siemens 200 user manual — MultiRanger 100/200 Installation (for retrofitting MultiRanger Plus Installations)
Page 257 · click to enlarge
Page 257

Connecting a transducer with RG62 coaxial extension cable

Appendix FUpgrading

If you are replacing an older Siemens Milltronics Ultrasonic Level Controller with a new MultiRanger where an RG62 coaxial extension is fitted and you are unable to replace the extension with a new cable, please refer to connection diagram below. Please note that the noise immunity performance will be similar to our older model ultrasonic level controllers if you use coaxial cable.

Existing installation

RG62 coaxial cable has been used to make the extension. The level controller might be a MultiRanger Plus, HydroRanger, HydroRanger Plus or one of our other level controllers.

MultiRanger 100/200 Installation (for retrofitting MultiRanger Plus Installations)

Connect with a 0.1µF (100v or greater) capacitor (included with MultiRanger) between the shield and negative terminals. Connect centre core of the coaxial to the positive terminal and the screen to the negative terminal.

Transducer · Transducer

Page 258 of the Siemens 200 user manual — MultiRanger Plus
Page 258 · click to enlarge
Page 258

MultiRanger Plus to MultiRanger 100/200 Parameters

Appendix FUpgrading

The MultiRanger 100/200 uses the current Siemens Milltronics standard parameter set which is different than the parameter numbers used in the MultiRanger Plus.

The MultiRanger Plus parameters numbers are sequential (P-0 to P-99). The MultiRanger 100/200 parameters number are also sequential; however, some of the parameters are indexed.

Parameters are indexed when they apply to more than one input or output. The index value defines the input/output for that parameter. Indexed parameters contain a value for each index, even if that index is not used.

Example

In the MultiRanger Plus each relay had a dedicated parameter number for its function, ON and OFF points.

MultiRanger Plus Relay One

  • P-8: Function
  • P-9 : ON setpoint
  • P-10: OFF setpoint

MultiRanger 100/200 uses P111 for all relays and indexes these parameters.

  • P-111: Function
  • P-112: ON
  • P-113: OFF

The following tables show the differences between the MultiRanger Plus and the MultiRanger 100/200. They each show one relay programmed as a high alarm, and two relays programmed for pump control with alternating pump starts:

MultiRanger Plus

MultiRanger 100/200

Relay Parameter Value

Relay Parameter Value

1 P-8 (relay function) 1 (alarm)

1 P111 [1] (relay function) 1

1 P-9 (ON setpoint) 4 m

1 P112 [1] (ON setpoint) 4 m

1 P10 (OFF setpoint) 3.5 m

1 P113[1] (OFF setpoint) 3.5 m

2 P-11 (relay function) 9

2 P111[2] (relay function) 52

2 P-12 (ON setpoint) 3.2 m

2 P112[2] (ON setpoint) 3.2 m

2 P-13 (OFF setpoint) 0.5 m

2 P113[2] (OFF setpoint) 0.5 m

3 P-14 (relay function) 9

3 P111[3] (relay function) 52

3 P-15 (ON setpoint) 3.4 m

3 P112[3] (ON setpoint) 3.4 m

3 P-16 (OFF setpoint) 0.6 m

3 P113[3] (OFF setpoint) 0.6 m

Page 259 of the Siemens 200 user manual — Appendix G
Page 259 · click to enlarge
Page 259

Appendix G: Conduit Entry for Class 1, Div 2 Applications

Siemens 200 — Appendix G: Conduit Entry for Class 1, Div 2 Applications diagram (page 259)
Fig. 67 · Appendix G: Conduit Entry for Class 1, Div 2 Applica…

Appendix G

7ML19981FBO6 MultiRanger 100/200 – INSTRUCTION MANUAL Page 249

Page 260 of the Siemens 200 user manual — Appendix G: Conduit Entry for Class 1, Div 2 Applications
Page 260 · click to enlarge
Page 260
Siemens 200 — Appendix G: Conduit Entry for Class 1, Div 2 Applications diagram (page 260)
Fig. 68 · Appendix G: Conduit Entry for Class 1, Div 2 Applica…

Page 250 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FBO6

Page 261 of the Siemens 200 user manual — Software
Page 261 · click to enlarge
Page 261

Appendix H: Software Revision History

MultiRanger 100

Software

Date Changes

Rev.

1.00 Aug. 15, 2005 • Pilot Release.

1.01 Sept. 21, 2005 • Internal Release.

1.02 Dec. 12, 2001 • Initial Release.

  • 1.03 Aug. 27, 2002
  • Clarified return message for factory RS232 test.
  • Prevent entering of strings with invalid fields in Dolphin Plus.
  • Properly convert ft/sec to m/sec in P654.
  • Eliminated rogue watchdog resets from repeatedly pressing hand programmer enter while in P901-P90.
  • Allow 32 bit read/write as seconds.
  • Factory mode lock is written to flash.
  • Cleaned up compiler errors and Lint warnings.
  • Modified handling of non-quick start parameters.
  • Modifications for Production Testing.
  • Users may now configure the SmartLinx memory map.

Appendix H: Software Rev.

Page 262 of the Siemens 200 user manual — Software
Page 262 · click to enlarge
Page 262

Software

Date Changes

Rev.

  • Product enhancements to eliminate relay chatter on software download.
  • Improved functionality of receiver saturation during calibration.
  • Added relay functionality through P118 to coincide with manual.
  • Improved product security with addition of P069.
  • Backup level override behaviour improvement.
  • Improved mA control with P210 - P213.
  • Improved temperature calibration in factory mode.
  • Improved Production Testing support.
  • Improved reset behaviour.
  • Changed default mA trim values.
  • Improved functionality of downloading breakpoints in Dolphin Plus.

Feb. 11, 2003

Feb. 23, 2003

1.06 May 27, 2004 • RCVR offset limits are no longer handled in the code.

Appendix H: Software Rev.

  • 1.07 Aug. 30, 2004
  • P060, P005 Dependancy removed.
  • Split Values - Parameters with the "xx:yy" format now being limited properly.
  • Temperature Spike - Temperature readings now being protected from other units’ transmit pulse.
  • TVT Shift - A rounding error in the number of samples, caused the TVT position to shift.
  • Auto False Echo Suppression - Device learns the shape of an empty tank to automatically suppress false echos.
  • SIMATIC PDM Compatability - Device uses Modbus to communicate with SIMATIC PDM. DDs required.
Page 263 of the Siemens 200 user manual — Software
Page 263 · click to enlarge
Page 263

Software

Date Changes

Rev.

  • 1.08 Nov. 11, 2004
  • Improvements made as a result of Siemens systems testing:
  • SIMATIC PDM related: TVT display improvement to prevent it from going negative. MLFB number includes SMPI as well as Siemens numbering. Change of some enumerations in the Device Description.
  • Device related: mA output no longer resets when PAR_MA_FUNCTION (P201) is written to. mA trims (P214, P215) now have the property no Reset.
  • Enhancement: Device Identification command allows Tag, Description, Message, and Date.
  • 1.09 Nov. 28, 2005
  • Correction for manual Shaper TVT shift due to change in velocity.
  • Resolved issue of reading some floats as decimal shifted integers.
  • The submergence algorithm now implemented with the thresholds defined.
  • Changes to support single DUART.

Appendix H: Software Rev.

1.10 not released

  • 1.11 Apr. 20, 2006
  • Software modified to support replacement component.
  • Supports SIMATIC PDM version 6.02.
  • Added support for true First echo processing algorithm
  • Support for 3rd Point Volume has been added on P001 = DPA or DPD.
  • 1.12 Aug. 15, 2008
  • Many parameter ranges improved to match product function and SIMATIC PDM.
  • P110 = OFF removed from SIMATIC PDM
  • Improved text labels for P770
Page 264 of the Siemens 200 user manual — Software
Page 264 · click to enlarge
Page 264

MultiRanger 200

Software

Date Changes

Rev.

1.00 Nov. 09, 2001 • Pilot Release.

1.01 Dec. 02, 2001 • Initial Release.

  • 1.02 Aug. 20, 2002
  • P602 functions reduced point limit from 10 to 6.
  • Changed P132 to global.
  • P640 now accepts negative values.
  • Changed access mode of dialer parameters so they cannot be scrolled.
  • Clarified return message for factory RS232 test.
  • Prevent entering strings with invalid fields in Dolphin Plus.
  • Properly convert ft/sec to m/sec in P654.
  • Eliminated rogue watchdog resets when repeatedly pressing hand programmer enter while in P901-P903.
  • Allow 32 bit read/write as seconds.
  • Factory mode lock is written to flash.
  • Cleaned up compiler errors and Lint warnings.
  • Modified handling of non-quick start parameters.
  • Modifications for Production Testing.
  • Users may now configure the SmartLinx memory map.
  • Improved Preset Application values.

Appendix H: Software Rev.

1.03 Sept. 25, 2002 • Allow files to be downloaded to the product using Dolphin+.

Page 265 of the Siemens 200 user manual — Software
Page 265 · click to enlarge
Page 265

Software

Date Changes

Rev.

  • Product enhancements to eliminate relay chatter on software download.
  • Improved functionality of receiver saturation during calibration.
  • Added relay functionality thru P118 to coincide with manual.
  • Improved product security with addition of P069.
  • Backup level override behaviour improvement.
  • Improved mA control with P210 - P213.
  • Improved temperature calibration in factory mode.
  • Improved Production Testing support.
  • Improved reset behaviour.
  • Changed default mA trim values.
  • Improved functionality of downloading downloading in Dolphin +.

Feb. 11, 2003

Feb. 21, 2003

1.06 May 27, 2004 • RCVR offset limits are no longer handled in the code.

Appendix H: Software Rev.

  • 1.07 Aug. 30, 2004
  • OCM Time Units improvement.
  • Totalizer enhancement to prevent a rounding error puting the totalizer into an unstable "mode."
  • Totalizer - Access to totalizer in OCM mode from Modbus map (reg 41040).
  • P060, P005 Dependancy removed.
  • Split Values - Parameters with the "xx:yy" format now being limited properly.
  • Temperature Spike - Temperature readings now being protected from other units’ transmit pulse.
  • TVT Shift - A rounding error in the number of samples caused the TVT to shift position.
  • Auto False Echo Suppression - Device learns the shape of an empty tank to automatically suppress false echos.
  • SIMATIC PDM Compatability - Device uses Modbus to communicate with SIMATIC PDM. DDs required.
Page 266 of the Siemens 200 user manual — Software
Page 266 · click to enlarge
Page 266

Software

Date Changes

Rev.

  • 1.08 Aug. 30, 2004
  • Improvements made as a result of Siemens systems testing:
  • SIMATIC PDM related: TVT display improvement to prevent it from going negative. MLFB number includes SMPI as well as Siemens numbering. Change of some enumerations in the Device Description.
  • Device related: mA output no longer resets when PAR_MA_FUNCTION (P201) is written to. mA trims (P214, P215) now have the property noReset.
  • Enhancement: Device Identification command allows Tag, Description, Message, and Date.
  • 1.09 Nov. 28, 2005
  • Correction for manual Shaper TVT shift due to change in velocity.
  • Reading some floats as decimal shifted integers would return a value off by 1 in some cases.
  • The submergence algorithm now implemented with the thresholds defined.
  • Changes to support single DUART.

Appendix H: Software Rev.

1.10 not released

  • 1.11 Apr. 20, 2006
  • Software modified to support replacement component.
  • Supports SIMATIC PDM version 6.02.
  • Added support for true First echo processing algorithm
  • Support for 3rd Point Volume has been added on P001 = DPA or DPD.

1.12 Aug. 01, 2006 • Internal Release.

  • 1.13 Aug. 15, 2008
  • Many parameter ranges improved to match product function and SIMATIC PDM.
  • P110 = OFF removed from SIMATIC PDM
  • Improved volume calculation for 3rd point volume
  • Improved text labels for P770
Page 267 of the Siemens 200 user manual — Parameter Charts
Page 267 · click to enlarge
Page 267

Programming Charts

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P003 Max. Process Speed

P052 Tank Dimension A

P053 Tank Dimension L

P054 Level Breakpoints record values on a separate sheet.

P055 Volume Breakpoints record values on a separate sheet.

P064 Reading Override Enable

Parameter Charts

P065 Reading Override Value

P066 Override Time Delay

P071 Failsafe Material Level

P072 Failsafe Level Advance

P100 Preset Applications [MR200]

P111 Relay Control Function

P112 Relay ON Setpoint

Show 21 more labels / short text on this page
Security · P000 Lock (G) · Quickstart · P001 Operation · P002 Material · P004 Transducer · P005 Units (G) · P006 Empty · P007 Span · Volume · P050 Tank Shape · P051 Max Volume · Reading Value · P060 Decimal Position · P061 Convert Reading · P062 Offset Reading · P069 Password · Failsafe · P070 Failsafe Timer · Relays · P110 Level Source
Page 268 of the Siemens 200 user manual — Parameter Charts
Page 268 · click to enlarge
Page 268

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P113 Relay OFF Setpoint

P115 Relay Interval Setpoint [MR 200]

P118 Relay Output Logic

P119 Relay Logic Test

P121 Pump by Rate [MR 200]

P122 Pump Service Ratio [MR 200]

Advanced Pump Control Modifiers

P130 Pump Run-On Interval [MR 200]

P131 Pump Run-On Duration [MR 200]

P132 Pump Start Delay [MR 200]

P133 Pump Power Resumption Delay

[MR 200]

P136 Wall Cling Reduction [MR 200]

P137 Pump Group [MR 200]

P170 Flush Pump [MR 200]

P171 Flush Cycles [MR 200]

P172 Flush Interval [MR 200]

P173 Flush Duration [MR 200]

Parameter Charts

P200 mA Output Range

P201 mA Output Function

P202 mA Output Allocation

P203 mA Output Value / Transducer

P210 0/4 mA Output Setpoint

P211 20 mA Output Setpoint

P212 mA Output Min Limit

P213 mA Output Max limit

P214 4 mA Output Trim

P215 20 mA Output Trim

Show 9 more labels / short text on this page
P116 Deadband · Pump Setpoint Modifiers · Independent Relay Failsafe · P129 Relay Failsafe · Flush Systems · mA Output · Independent mA Setpoints · mA Output Limits · mA Output Trim
Page 269 of the Siemens 200 user manual — Parameter Charts
Page 269 · click to enlarge
Page 269

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P219 mA Output Failsafe[MR 200]

P250 mA Input Range [MR 200]

P251 0 to 4 mA Input Level [MR 200]

P252 20 mA Input Level [MR 200]

P253 Input Filter Time Constant [MR 200]

P254 Scaled mA Input Value[MR 200]

P260 mA Raw Input [MR 200]

P270 Discrete Input Function

P275 Scaled Discrete Input Value

P300 Temp, Transducer max

P301 Temp, Transducer min

P302 Temperature, Sensor max

P303 Temperature, Sensor min

P309 Pump RUN Time

P312 Pump Run Ons [MR 200]

Parameter Charts

P320 Flow Max [MR 200]

P321 Flow Min [MR 200]

P322 LCD Total Low [MR 200]

P323 LCD Total High [MR 200]

P331 Auto Record Enable

P332 Auto Record Transducer

P333 Auto Record Interval

Auto Record ON and OFF Setpoints

Show 13 more labels / short text on this page
mA Input · Discrete Input Functions · Record Temperatures · Record Readings · P304 Reading Max · P305 Reading Min · Pump Records · P310 Pump Hours · P311 Pump Starts · Flow Records · LCD Totalizer · Profile Records · P330 Profile Record
Page 270 of the Siemens 200 user manual — Parameter Charts
Page 270 · click to enlarge
Page 270

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P334 Auto Record ON Setpoint

P335 Auto Record OFF Setpoint

P336 Auto Record Filling/Emptying

P337 Auto Record LOE Time

P340 Date of Manufacture

P600 Primary Measuring Device [MR 200]

P601 Flow Exponent [MR 200]

P602 Primary Measuring Device Dimensions [MR200]

P603 Maximum Head [MR 200]

P604 Maximum Flow [MR 200]

P605 Zero Head [MR 200]

P606 Time Units [MR 200]

P607 Flowrate Decimal [MR 200]

P608 Flowrate Units [MR 200]

P610 Head Breakpoints [MR 200]

P611 Breakpoint Flowrates [MR 200]

P620 Low Flow Cutoff [MR 200]

P621 Auto Zero Head [MR 200]

Parameter Charts

P622 Inflow / Discharge Adjust [MR 200]

P630 LCD Totalized Multiplier [MR 200]

P633 LCD Totalized Decimal Postion [MR 200]

P640 Remote Totalized Multiplier [MR 200]

P641 Flow Sampler Mantissa [MR 200]

P642 Flow Sampler Exponent [MR 200]

P645 Relay Duration [MR 200]

Show 6 more labels / short text on this page
Installation Records · P341 RUN Time · P342 Start Ups · Open Channel Monitoring · Pumped Volume Totalizer · Totalizer
Page 271 of the Siemens 200 user manual — Parameter Charts
Page 271 · click to enlarge
Page 271

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P651 Sound Velocity Calibration

P654 Velocity @ 20° C

P663 Temp Transducer Allocation

P700 Max Fill Rate

P701 Max Empty Rate

P705 Rate Update Time

P706 Rate Update Distance

P708 Volume Rate Display [MR 200]

Parameter Charts

P712 Echo Lock Sampling

P713 Echo Lock Window

P726 Level System Sync

P731 Auxiliary Reading Key

Show 25 more labels / short text on this page
Range Calibration · P650 Offset Calibration · P652 Offset Correction · P653 Velocity · Temperature Compensation · P660 Temp Source · P661 Temp Fixed · P664 Temperature · Rate · P702 Filling Indicator · P703 Emptying Indicator · P704 Rate Filter · P707 Rate Value · Measurement Verification · P710 Fuzz Filter · P711 Echo Lock · Transducer Scanning · P727 Scan Delay · P728 Shot Delay · P729 Scan Time · Display · P730 Auxiliary Reading · P732 Display Delay · P733 Scroll Access · P735 Backlight
Page 272 of the Siemens 200 user manual — Parameter Charts
Page 272 · click to enlarge
Page 272

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P737 Primary Reading [MR 200]

P779 Modem Inactivity Timeout

P782 Parameter Index Location

P791 Hardware Error Code

P792 Hardware Error Count

P794 SmartLinx Module Type

P802 Transducer with Submergence Shield

Parameter Charts

P803 Shot / Pulse Mode

P815 Echo Time Filtered

P816 Echo Time Raw

P822 Narrow Echo Filter

Show 25 more labels / short text on this page
P741 Communications Timeout · SmartLinx Reserved · Communications · P770 Port Protocol · P771 Network Address · P772 Baud Rate · P773 Parity · P774 Data Bits · P775 Stop Bits · P778 Modem Available · SmartLinx Hardware Testing · P790 Hardware Error · P795 SmartLinx Protocol · P799 Communications Control · Echo Processing · P800 Near Blanking · P801 Range Extension · P804 Confidence Threshold · P805 Echo Confidence · P806 Echo Strength · P807 Noise · Advanced Echo Processing · P820 Algorithm · P821 Spike Filter · P823 Reform Echo
Page 273 of the Siemens 200 user manual — Parameter Charts
Page 273 · click to enlarge
Page 273

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P825 Echo Marker Trigger

P832 TVT Shaper Adjust

P833 TVT Start Min

P834 TVT Start Duration

P835 TVT Slope Min

P837 Auto-False Echo Suppression

P838 Auto-False Echo Suppression- Distance

P839 TVT Hover Level

P840 Short Shot Number

P841 Long Shot Number

P842 Short Shot Frequency

P843 Long Shot Frequency

P844 Short Shot Width

P845 Long Shot Width

P850 Short Shot Bias

P851 Short Shot Floor

P852 Short Shot Range

P900 Software Revision Number

Parameter Charts

P911 mA Output Value

P914 mA Input [MR 200]

Show 16 more labels / short text on this page
P824 (reserved) · Advanced TVT Adjustment · P830 TVT Type · P831 TVT Shaper · Advanced Shot Adjustment · P901 Memory · P902 Watchdog · P903 Display · P904 Keypad · P905 Transmit Pulse · P906 RS-232 Port · P908 Scanner · P910 Toggle Relays · P912 Transducer Temperature · P913 Sensor Temperature · Measurement
Page 274 of the Siemens 200 user manual — Parameter Charts
Page 274 · click to enlarge
Page 274

Parameter Altered Values for Indices/Point Numbers

# Name 1 2 3

P924 Volume Measurement [MR 200]

P925 Flow Measurement [MR 200]

P926 Head Measurement [MR 200]

Parameter Charts

Show 6 more labels / short text on this page
P920 Reading Measurement · P921 Material Measurement · P922 Space Measurement · P923 Distance Measurement · P927 Distance Measurement · P999 Master Reset
Page 276 of the Siemens 200 user manual — Table of contents
Page 276 · click to enlarge
Page 276

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 277 of the Siemens 200 user manual — Table of contents
Page 277 · click to enlarge
Page 277

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 278 of the Siemens 200 user manual — Table of contents
Page 278 · click to enlarge
Page 278

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 279 of the Siemens 200 user manual — Table of contents
Page 279 · click to enlarge
Page 279

Table of contents

The MultiRanger 100 and 200p.11MultiRanger 100p.11MultiRanger 200p.11The Manualp.11Manual Symbolsp.12Configuration Examplesp.12Specificationsp.13Installationp.18Mountingp.18Mounting Locationsp.18Mounting Instructionsp.19Wall Mountp.19Cable routed through a conduit:p.20Panel Mountp.21Mounting the Enclosurep.22MultiRanger Boardp.23Installing the Batteryp.23Installing SmartLinx Cardp.24Wiringp.25Terminal Boardp.26Cablesp.26Transducersp.27Relaysp.27Temperature Sensorp.28mA Input [MR 200 only]p.28mA Outputp.28Level System Synchronizationp.29Powerp.29Digital Communicationsp.30RS-232 Serial Connectionp.30RS-485 Serial Connectionp.30Discrete Inputsp.31Operating the MultiRangerp.32RUN Modep.32Readings in RUN Modep.33Status Parametersp.34Controlling the Displayp.35Adjusting the primary reading for four-digit LCD readout:p.35Auxiliary Readingp.35Multiple Readings [MR 200 only]p.36PROGRAM Modep.37Starting PROGRAM Modep.37Hand Programmerp.37Programmer Keysp.38Dolphin Plusp.39Dolphin Plus Toolbar Buttonsp.40SIMATIC Process Device Manager (PDM)p.41Device Descriptionp.41Activating the MultiRangerp.42Changing Parametersp.42Securityp.43Using Units or Percent (%)p.43Parameters Typesp.43Parameter Resetp.44Display Readoutp.44Changing Parameters(Dolphin Plus)p.45Parameter Indexingp.46Primary and Secondary Indexesp.47Primary Indexp.47Secondary Indexp.47Starting Measurementp.48Single Point Modelsp.48Average or Differential [MR 200 only]p.49Dual Point Modelsp.49Average or Differential [MR 200 only]p.50Measurement Conditionsp.50Response Ratep.50Dimensions [MR 200 only]p.50Failsafep.50Relaysp.51General Introductionp.51Relay Functionp.51Alarmp.51Pumpp.52Miscellaneousp.52Relay Status – Non Run Modesp.53Relay Statesp.53Relay Related Parametersp.53Relay Wiring Testp.54Relay Activationp.54Relay Failsafep.55Preset Applicationsp.56Backup Level Overridep.57Backup Level Override Parametersp.57Discrete Inputsp.58Wiring the Discrete Inputsp.58Programming the Discrete Input Logicp.58mA I/Op.59mA Input [MR 200]p.59mA Outputp.59Volume [MR 200]p.61Readingsp.61Tank Shape and Dimensionsp.61Characterization Chart [MR 200]p.62Example Chartp.62MultiRanger 200 onlyp.63Alarmsp.64Levelp.64Setting Simple Level Alarmsp.65Rate [MR 200]p.65In Bounds/ Out of Bounds Range [MR 200]p.66Cable Faultp.66Temperature [MR 200]p.66Loss of Echo (LOE)p.67Pump Controlp.68Setting a Pump Down Groupp.68Setting a Pump Up (Reservoir) Groupp.69Other Pump Control Algorithmsp.71Set Relays to ALTERNATE DUTY BACKUP [MR 200]p.71Set Relays to FIXED DUTY ASSISTp.71Set Relays to FIXED DUTY BACKUP [MR 200]p.72Set Relays to ALTERNATE DUTY SERVICE [MR 200]p.72Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]p.73Optional Pump Controlsp.73Starting Pumps by Rate of Level Change [MR 200]p.73Rotating Pumps by Service Ratio [MR 200]p.74Totalizing Pumped Volume [MR 200]p.75Setting Independent Failsafe Controlsp.75Setting a Pump to Run On [MR 200]p.76Setting the Pump Start Delays [MR 200]p.76Reducing Wall Cling [MR 200]p.76Grouping Pumps [MR 200]p.77Setting a Flush Valve [MR 200]p.77Relay Controlled by Communicationsp.78Tracking Pump Usagep.78Rake (Screen) Control [MR 200]p.79Setting a Rake Controlp.79Setting the Common Parametersp.80Set Relay 1 (Operate Rake)p.80Set Relays 2 to 4 (Level Alarms)p.80External Totalizers and Flow Samplers [MR 200]p.81Relay Contactsp.81Totalizerp.81Flow Samplerp.82Based on Volume and Timep.82Open Channel Monitoring (OCM) [MR 200]p.83Common Parametersp.83Setting Zero Headp.84Setting Totalized Volumep.85Applications Supported by MultiRanger 200p.85BS-3680 / ISO 1438/1 Thin plate V notch weirp.85BS-3680 / ISO 4359 Rectangular Flumep.86Palmer Bowlus Flumep.87H Flumep.88PMDs with Exponential Flow to Head Functionp.89Applicable Weir Profilesp.89Non-Applicable Weir Profilesp.90Parshall Flumep.90Leopold Lagco Flumep.91Cut Throat Flumep.92Universal Calculation Supportp.93Typical Flow Characterizationp.93Example Flumesp.94Example Weirsp.94Testing the Configurationp.95Simulationp.95Simulating a Single Measurementp.95Simulating a Level Cyclep.95Checking Volume Characterization [MR 200]p.96Checking OCM Flow Characterization [MR 200]p.96I/O Checkoutp.97Application Testp.97MultiRanger Communicationsp.99MultiRanger Communication Systemsp.99Optional SmartLinx®Cardsp.99Communication Systemsp.100Communication Portsp.100Modbusp.100SmartLinxp.101Dolphin Plusp.101Communications Installationp.102Wiring Guidelinesp.102Ports 1 and 2p.102Ports 1 and 2: RS-232 RJ-11 Jack and RS-485 Locationsp.102Port 1: RS-232 RJ-11 Jackp.103Port 2: RS-485p.103Configuring Communication Ports (Parameters)p.104Modbus Register Mapp.107Word Order (R40,062)p.108Map ID (R40,063)p.108Product ID (R40,064)p.109Point Data (R41,010 – R41,031)p.109Totalizer (R41,040 – R41,043)p.109Input/Output (R41,070 – R41,143)p.109Discrete Inputs (R41,070)p.110Relay Outputs (R41,080)p.110mA Input (R41,090) [MR 200]p.110mA Output (R41,110-41,111)p.110Pump Control (R41,400 – R41,474)p.110Pump ON Setpoint (R41,420 – R41,425)p.110Pump OFF Setpoint (R41,430 – R41,435)p.111Pumped Volume (R41,440 – R41,443) [MR 200]p.111Pump Hours (R41,450 – R41,461)p.111Pump Starts (R41,470 – R41,475)p.111Parameter Access (R43,998 – R46,999)p.112Parameter Indexingp.112Indexing the Parameter Access Areap.112Reading Parametersp.113Global Index Method (P782 = 0)p.113Parameter Specific Index Method (P782 = 1)p.113Writing Parametersp.114Global Index Method (P782 = 0)p.114Parameter Specific Index Method (P782 = 1)p.114Format Words (R46,000 to R46,999)p.115Global Index Method (P782 = 0)p.115Parameter-Specific Index Method (P782 = 1)p.115Format Registersp.115Data Typesp.117Numeric Valuesp.117Bit Valuesp.117Unsigned Double Precision Integer (UINT32)p.117Split Valuesp.118Text Messagesp.119Relay Function Codes (P111 Only)p.120Error Handlingp.121Modbus Responsesp.121Error Handlingp.121Communication Troubleshootingp.123Generallyp.123Specificallyp.123Communication Appendix A: Single Parameter Access (SPA)p.124Mappingp.124Reading Parametersp.124Writing Parametersp.125Format Registerp.125Error Codesp.126Parameter Referencep.127MultiRanger 100 and MultiRanger 200p.127Helpful Hintsp.127Index typesp.128Quick Start (P001 to P007)p.129For DPD and DPA Programming [MR 200]p.130Volume (P050 to P055) [MR 200]p.133Display and Reading (P060 to P062)p.137Backup Level Overridep.139Failsafe (P070 to P072)p.141Relays (P100 to P119)p.142MultiRanger 200p.144Pump Setpoint Modifiers (P121 and P122) [MR 200]p.149Independent Relay Failsafe (P129)p.150Advanced Pump Control Modifiers (P130 to P137) [MR 200]p.151Flush Systems (P170 to P173) [MR 200]p.154mA Output (P200 to P219)p.156Independent mA Setpoints (P210 and P211)p.159mA Output Limits (P212 and P213)p.159mA Output Trim (P214 to P215)p.160mA Output Failsafe (P219) [MR 200]p.161mA Input (P250 to P260) [MR 200]p.161Discrete Input Functions (P270 to P275)p.163Standard Data Logging (P300 to P321)p.164Record Temperatures (P300 to P303)p.164Record Readings (P304 and P305)p.166Pump Records (P309 to P312)p.166Flow Records (P320 and P321) [MR 200]p.168LCD Totalizer (P322 and P323) [MR 200]p.168Profile Records (P330 to P337)p.169Auto Record ON and OFF Setpoints (P334 to P337)p.172Installation Records (P340 to P342)p.174Open Channel Monitoring (P600 to P621) [MR 200]p.175Example Exponentsp.177Pumped Volume Totalizer (P622) [MR 200]p.184Totalizer (P630 to P645) [MR 200]p.185Range Calibration (P650 to P654)p.188Temperature Compensation (P660 to P664)p.191Rate (P700 to P708)p.193Measurement Verification (P710 to P713)p.197Transducer Scanning (P726 to P729)p.200Display (P730 to P739)p.201SmartLinx Reserved (P750 to P769)p.204Communications (P770 to P782)p.204SmartLinx Hardware Testing (P790 to P795)p.207Echo Processing (P800 to P807)p.209Advanced Echo Processing (P815 to P825)p.213Advanced TVT Adjustment (P830 to P835)p.217Advanced Shot Adjustment (P840 to P852)p.222Test (P900 to P913)p.225Measurement (P920 to P927)p.228Master Reset (P999)p.231Appendix A: Index Typesp.233Index typesp.233Appendix B: Technical Referencep.234Transmit Pulsep.234Echo Processingp.234TVT (Time Varying Threshold) curvesp.235Auto False-Echo Suppressionp.235Distance Calculationp.236Sound Velocityp.236Scanningp.237Volume Calculation [MR 200]p.237Universal, Curved [MR 200]p.238Flow Calculationp.238Universal, Linear [MR 200]p.239Universal, Curved [MR 200]p.239Maximum Process Speedp.240Appendix C: Troubleshootingp.241Common Problems Chartp.241Noise Problemsp.242Determine the Noise Sourcep.242Non-Transducer Noise Sourcesp.243Common Wiring Problemsp.243Reducing Electrical Noisep.243Reducing Acoustical Noisep.243Measurement Difficultiesp.244Flashing LOE Displayp.244Adjust Transducer Aimingp.244Increase Failsafe Timer Valuep.245Install a Transducer with a Narrower Beamp.245Use Dolphin Plus to Debug Echop.245Fixed Readingp.245Obstructions in the Sound Beamp.245Nozzle Mountingsp.245Set the MultiRanger to Ignore the Bad Echop.246Wrong Readingp.246Types of Wrong Readingsp.246Liquid Splashingp.246Adjust the Echo Algorithmp.246Transducer Ringingp.247Unit Repair and Excluded Liabilityp.248Appendix D: Pump Control Referencep.249Pump Control Optionsp.249Pump Groupsp.249Pump by Rate [MR 200]p.249Pump Control Algorithmsp.249Fixed Duty Assist (P111 = 50)p.250Fixed Duty Backup (P111 = 51) [MR 200]p.250Alternate Duty Assist (P111 = 52)p.251Alternate Duty Backup (P111 = 53) [MR 200]p.251Service Ratio Duty Assist (P111 = 54) [MR 200]p.252Service Ratio Duty Backup (P111 = 55) [MR 200]p.253First In First Out (FIFO) (P111 = 56) [MR 200]p.253Pump by Rate (P121) [MR 200]p.253Other Pump Controls [MR 200]p.253Appendix E: Updating Softwarep.255Updating Softwarep.255Appendix F: Upgradingp.256Mounting a MultiRanger 100/200p.256Connecting the Transducerp.256Coaxial Transducer Extentionp.256Connecting a transducer with RG62 coaxial extension cablep.257MultiRanger Plus to MultiRanger 100/200 Parametersp.258Appendix G: Conduit Entry for Class 1, Div 2 Applicationsp.259Appendix H: Software Revision Historyp.261MultiRanger 100p.261MultiRanger 200p.264Programming Chartsp.267Indexp.275Ap.275Bp.275Cp.275Dp.275Ep.275Fp.275Gp.276Hp.276Ip.276Lp.276Mp.276Np.276Op.276Pp.276Qp.277Rp.277Sp.278Tp.278Up.278Vp.278Wp.279
Page 280 of the Siemens 200 user manual — Notes
Page 280 · click to enlarge
Page 280

Notes

Page 281 of the Siemens 200 user manual — W
Page 281 · click to enlarge
Page 281
Siemens 200 — W diagram (page 281)
Fig. 69
Page 282 of the Siemens 200 user manual — *7ml19981FB06* Rev. 6.1
Page 282 · click to enlarge
Page 282

www.siemens.com/processautomation

Siemens Milltronics Process Instruments Inc. 1954Technology Drive, P.O. Box 4225 Peterborough, ON, Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 Email: techpubs.smpi@siemens.com

Siemens Milltronics Process Instruments Inc. 2009 Subject to change without prior notice

*7ml19981FB06* Rev. 6.1

Printed in Canada

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
P070Failsafe Timer activates if an error condition is detected. Upon expiration of p.50
P071Failsafe Material Level determines the level reading if the Failsafe Timer p.50
P129Relay Failsafe controls the reaction of each relay. See Relay Failsafe on page p.50
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Display blank, transducer not pulsing.No power.Check power supply, wiring, or power fuse. p.241
No response to program- mer.Obstructed infrared interface, defective programmer.Check programmer usage: 15 cm (6”) from faceplate pointed at upper target. p.241
Displays Short and tb:(#).Short circuited transducer cable, or defective transducer at indi- cated terminal block number.Repair or replace as necessary. p.241
Displays Open and tb:(#).Transducer not connected or con- nection reversed.Check connection to displayed ter- minal blocks. p.241
Displays Open and tb:(#).Open circuited transducer cable, or defective transducer at indi- cated terminal block number.Repair or replace as necessary. p.241
Displays LOE.Weak or non-existent echo.Relocate and/or re-aim transducer at material. p.241
Displays LOE.Proceed to Measurement Difficul- ties. p.241
Displays Error and tb:(#).Wrong transducer selected (P004).Verify transducer type and re-enter value. p.241
Displays Error and tb:(#).Transducer connected in “two wire” method.Do not tie white and shield together. Use all three terminal blocks. p.241
Displays Error and tb:(#).Transducer connected back- wards.Reverse black and white wires on terminal block. p.241
Displays EEEEValue too large to display in 4 or 5 characters.Select larger Units (P005), or lower Convert Reading (P061). p.241
Reading fluctuates while material level is still (or vice versa).Incorrect measurement stabiliza- tion.Alter Maximum Process Speed (P003) or damping (P704) accord- ingly. See Maximum Process Speed. p.241
Reading is fixed, regard- less of the actual mate- rial level.Transducer acoustic beam obstructed, standpipe too nar- row, or transducer ringing (reads over 100%).Relocate and / or re-aim transducer at material level or object. p.241
Reading is fixed, regard- less of the actual mate- rial level.Proceed to Measurement Difficul- ties below. p.241
Reading is fixed, regard- less of the actual mate- rial level.See also: Transducer Ringing. p.241
Material level reported is always incorrect by the same amount.Incorrect Empty (zero) reference for level operation (P001 = 1).See Empty (P006), Reading Offset (P063), Offset Calibration (P650), & Offset Correction (P652). p.241
Measurement accuracy improves as level nears transducer.Incorrect Sound Velocity used for distance calculation.Use a transducer with a built-in tem- perature sensor or a TS-3 tempera- ture sensor. p.241
Measurement accuracy improves as level nears transducer.See Sound Velocity. p.241
Reading is erratic, with little or no relation to material level.True echo too weak or wrong echo being processed.Relocate and / or re-aim transducer at material. p.241
Reading is erratic, with little or no relation to material level.Check noise parameters. See Noise Problems. p.241

Ask about the Siemens 200

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Siemens 200

Be the first to ask — other owners or our team will answer.

Original document

Siemens 200 manual PDF

282 pages·3 MB·Network Card·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…