1 © Copyright Para Systems, Inc., 2003 PRO-E Series User's Manual 1 . Introduction 2 2 . Controls and Indicators 5 3. Installation 7 4. Operation 9 5 . T roubleshooting 12 6 . Replacing the Battery 13 7 . Obtaining Service 16 8 . Specifications 17 9 .
2 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ! English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service.
3 W ARNING: Risk of Electrical Shock. Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected. T o de-energize the outputs of the UPS: 1. If the UPS is on press and release the On/Off/T est button.
4 English Para Systems Life Support Policy As a general policy , Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or mal- f.
5 On-Line On-Battery Buck Boost English On-Line/On-Battery/Boost/Buck LED Overload LED Weak/Bad Battery LED On/Off/T est Button Fault LED Press and release the ON/OFF/T est Button after 1 beep to turn the UPS ON or OFF (see section 4).
6 REAR P ANEL English 5 4 3 2 1 10 8 6 7 9 5 4 3 2 1 8 6 7 9 1. The Information/Rating Label. 2. The Battery Backup and Surge output power receptacles are NEMA 5-15R type (IEC 320 C13 sockets for 230V models). 3. The USB Communications Interface Port is for UPS monitoring and control.
7 INST ALLA TION PLACEMENT The PRO-E series is intended to be install in a temperature controlled environ- ment that is free of conductive contaminants.
8 English DO NOT plug Power Strips or Surge Protection Devices into the ”Battery Backup” Receptacles on the UPS. Plugging Power Strips or Surge Protection Devices into the “Battery Backup” Receptacles may cause internal damage to the UPS, the Power Strip, or the Surge Protection Device.
9 English TURNING THE UNIT ON/OFF ON / OFF / T est Button SELF TEST Press and release the ON/OFF/T est Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a two-second self test. Press and release the ON/OFF/T est Button after one beep to turn the UPS OFF .
10 English ALARMS ON BA TTER Y When the UPS is operating on the batteries, the On-Battery LED will blink and the audible alarm will sound once every 10-seconds. The alarm will stop once the UPS returns to the On-Line operation. UPS F AUL T When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will sound a constant alarm.
11 COMMUNICA TIONS PORTS (RS232 and USB) The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability . The PRO-E series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port.
12 English Possible Cause Symptom What T o Do Press and release the On/Off/ T est button to start UPS On/Of f/T est button not pushed UPS will not turn on Reset circuit breaker by pressing the plunger back in.
13 REPLACING THE BA TTER Y W ARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond battery replacement procedures below . This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by AUTHORIZED SERVICE PERSONNEL ONL Y .
14 English BA TTER Y REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system.
15 9. Disconnect the positive (red) wire from the battery positve terminal. 10. Disconnect the battery negative (black) wire from the battery negative terminal. NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire. 1 1.
16 English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem.
17 Default 120V (230V) / User selectable at 120/127V , (208/230V) 3-5 years, depending on discharge cycles and ambient temp 500V A 350W 700V A 490W 1500V A 1050W 1 100V A 770W 500 J (440 J) 0 ns (instantaneous) normal mode; <5 ns common mode <5% Normal and common mode EMI/RFI suppression 1-12V9Ah 2-12V7Ah 3-12V7Ah Audible noise at 1 m (3 ft.
18 English (These items may require optional software or hardware) Function Factory Default Description User Choices Set inverter output voltage Shut- down T ype Set audible alarm state Enable/ Disabl.
19 English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase.
20 English EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUEN- TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
21 DECLARA TION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 73/23/EEC Standard(s) to which Conformity is declared: EN50091-1-1, EN50091-2 Manufacturer’s Name: Para Systems, Inc.
22 English Notes:.
Rackmount Solutions, Ltd. 915 S. J upiter Road Garland, TX 75042 www .rackmountsolutions .net sales@rac kmountsolutions.net 1-866-207-6631 | F ax 972-276-6484 GSA Contract # GS-35F-0208R f or IT 70 Ap.
An important point after buying a device Rackmount Solutions PRO700iE (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Rackmount Solutions PRO700iE yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Rackmount Solutions PRO700iE - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Rackmount Solutions PRO700iE you will learn all the available features of the product, as well as information on its operation. The information that you get Rackmount Solutions PRO700iE will certainly help you make a decision on the purchase.
If you already are a holder of Rackmount Solutions PRO700iE, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Rackmount Solutions PRO700iE.
However, one of the most important roles played by the user manual is to help in solving problems with Rackmount Solutions PRO700iE. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Rackmount Solutions PRO700iE along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center