Operating Manual


IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
Please read and save these instructions. This manual contains important instructions for Chloride models:
Follow these instructions during installation and maintenance of the UPS and batteries.
If you have a problem with the UPS, please refer to this manual before calling the Technical Support Department. The Troubleshooting section on pages 20 and 53 address most UPS-related issues.
This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial environment. The UPS generates, uses, and can radiate radio frequency energy. If installation and use is not in accordance with the instruction manual, it may cause harmful interference to radio communications.
Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 USA Telephone: (847) 990-3228 Toll Free: (800) 239-2257 Facsimile: (800) 833-6829
UPLIT039 Rev. 0 4/03
Active and E-Series UPS User Manual i



Thank you for selecting this uninterruptible power supply (UPS). Chloride’s Active UPS offers the most reliable protection from the harmful effects of electrical line disturbances for your computing and communications equipment.
To ensure that your Active model and serial number are registered, complete and mail the enclosed postage- paid warranty card.
Chloride offers 24-hour technical support. To contact Chloride Technical Services:
Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.
UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode. Unplugging the UPS does not remove the electrical charge. To ensure that the UPS is off, push BYPASS (for a minimum of 1 second) before unplugging the UPS from the mains.
Do not use AC adaptors with only two conductors to connect the input line cord to the wall socket as this will not connect the earth ground to the equipment.
This device complies with the relevant safety regulations for uninterruptible power supplies for use in a controlled office environment. If you have any questions, please contact Chloride Technical Service at 1- 800-879-5011.

(see chapter 2, “Display and Operation Elements (Active)” on page 3) does not isolate the device (UPS) from the mains. To isolate completely from the mains, the main switch must be switched off and the power plug disconnected.
Chloride Active UPS is UL listed under UL1778 for North American units.

The Uninterruptible Power System (UPS) is connected between AC power and the load. It protects the load against mains disturbances, especially power failures.
Its operation is based on the on-line principle. The connected load is supplied power through the UPS’s inverter. Power disturbances from the mains are suppressed which increases the loads’ operational security (PC, network server, multi-user systems etc.)
In the event of a mains failure, maintenance-free batteries provide an uninterrupted supply of energy. In practice, mains failures are of relatively short duration, dependent on the mains quality. Therefore, the UPS’ energy is in most cases sufficient to ensure continuous operation of the connected systems, until the mains is reestablished. In the event of a longer lasting mains failure it allows for controlled shutdown of connected systems.
The UPS indicates by acoustical (buzzer) and optical (LED) alarms that a mains failure has occurred and is still persistent. Battery runtimes vary depending upon load, number of batteries and environmental conditions.
The following chart shows the approximate values of the emergency runtime (assuming fully charged battery at the onset of the mains failure.)
Load in % A700 A1000 A2000 A3000 OVERLOAD >105 95-105 6 min 7 min 10 min 6 min LOAD 75-95 7 min 8 min 11 min 7 min 55-75 10 min 11 min 16 min 10 min 35-55 15 min 17 min 24 min 15 min 1-35 28 min 33 min 37 min 28 min
The most reliable method for determining actual battery runtime is the application of Chloride MopUPS® software. With this software, the prospective remaining battery capacity is indicated before and during an AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application program, operating system and computer hardware, it can be ensured that in the event of a power failure the application programs are automatically closed, the subscribers logged in at the server are logged out, the data is stored and the operating systems are shut down. For further information please refer to our publication about the Chloride ManageUPS™NET SNMP Adapter.
After return of the mains voltage, the UPS automatically initiates a restart. The connected systems are restarted according to their specifications.
In the event of overload or internal failure, the load is supplied from the mains via an automatic bypass. As soon as the normal status is reestablished, automatic switchover to inverter operation is performed.
This operation manual contains all relevant information to install and operate the UPS.

The OVERLOAD indicator is on when the UPS is overloaded.

The LED-chain LOAD indicates the load state of the UPS.
The BYPASS indicator is on when the UPS supplies a voltage via the bypass.
The INVERTER indicator is on when the inverter is in operation.
The LED-chain BATTERY indicates the battery’s charge state (normal operation) or the % of battery time remaining when mains fail.
The LINE indicator is on when there is mains voltage at the UPS
input.
The ALARM indicator is on when the UPS is faulty. Simulta- neously, an acoustical signal is given, which can be reset by pressing the BYPASS switch.
The switch switches the inverter off and the bypass on. The UPS still has output voltage.
Operating the switch | activates the inverter. After a delay of approximately 5 seconds the BYPASS indicator extinguishes and the INVERTER indicator illuminates.


Selector switch Interface COM A Interface COM B (optional)
Selector switch - for output voltage. The selection of the output voltage must be made with the UPS switched off and unplugged.*
Input fuse - the fuse may only be changed when the device is switched off and unplugged.

Selector switch - for output voltage. The selection of the output voltage must be made with the UPS switched off and unplugged.*
Interface COM B (optional)
Connection for additional bat-
Input fuse - the fuse may only be changed when the device is switched off and unplugged.
* Call Chloride Technical Services for information on setting output voltages (1-800-879-5011).

Selector switch - for output voltage. The selection of the output voltage must be made with the UPS switched off and unplugged.*

Selector switch Interface COM A Interface COM B (optional)
Connection for additional batteries Fans Output Receptacle Output Receptacle Fuses Input circuit breaker
Selector Swith - for output voltage The selection of the output voltage must be made with the UPS switched off and unplugged.*

Selector switch Interface COM A Interface COM B (optional) Connection for additional bat- teries
* Call Chloride Technical Services for information on setting output voltages (1-800-879-5011)

The technical data of the Active Rackmount UPS corresponds to the standard unit series Active, except for the details which are explained below. The Active Rackmount consists of the following types:
The above listed units with a mounting height of 2 U (2 U = 3.50 inches) are designed for installation in a standard 19-inch industrial rack.
This system, called “unit” in the following text, serves as an uninterruptible power supply of connected loads in a 19-inch rack. In certain configurations battery packs are part of the unit. These battery packs may only be connected electrically with the corresponding base unit.
The Active Rackmount units are designed to be mounted in a 19-inch rack. When installing the UPS, please consider the heavy weight of some components. Preferably, they should be installed in the lower section of the rack. UPS systems consisting of several components must be installed so that the battery packs are mounted in the lower section with the UPS mounted directly above them.

The units must be attached in the rack on both sides. When using the attached mounting rails, the single unit can easily be inserted into a 2 U mounting space or removed from it. In order to attach the unit in the horizontal position, the front-plate has to be attached to the 19-inch rack at the indicated points on both sides of the unit.
Do not attach the unit only at the front-plate. This may damage the unit and/or other mounted units.

Fig. 5: Mounting the rails at the body of the UPS or Battery-Pack.
The following table shows the maximum configuration.
Table 1. Battery Cabinets

3.3.1 Active 700-19 and Active 1000-19
The following figures show the Active700-19, Active1000-19, Active2000-19 and Active 3000-19 with battery extensions.



To connect the battery pack to the unit, use the separate cable supplied.





Upon receipt of your UPS, carefully examine the packing containers for any sign of physical damage. Notify the carrier immediately if damage is present. Carefully unpack the UPS. Retain the packaging for reuse or disposal.
UPS includes:

The following table shows the designations of the battery cabinets which are available for the UPS devices.
Table 2. External Battery Packs

Active 1000 BPActive1000-19 2x (3 x 7. 2 Ah)
Active 2000 BPActive3000-19 2x (8 x 7. 2 Ah)
Active 3000 BPActive3000-19 2x (8 x 7. 2 Ah)
Disconnect the UPS from the mains and the loads from the UPS.
Connect the battery cabinet types BP1000, BP3000 to the UPS using the supplied cable. The connection scheme is shown in the figures below. Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.

Battery Plug 1 · Circuit Breaker · Battery Plug 2

5.1 Ready for Operation Check
To check the emergency supply feature of the UPS, it must be disconnected from the mains.
When correctly functioning with charged batteries, an acoustical signal in intervals of 4 seconds will be heard. The LED “LINE” (line voltage) indicator disappears. When the interval between the acoustical signals is reduced to 1 second, the UPS will supply energy for a maximum of 3 more minutes before it is automatically switched off.
The load will be supplied from the batteries during the specified emergency supply period. If this is not so, then please check in chapter 8 “Troubleshooting (Active)” on page 20.
Reconnect the UPS with the mains.
The UPS is now again ready for normal operation. Please note, that the batteries have to be recharged before the complete emergency supply period is again available.
The self test is a LED test.
With the UPS connected to the AC power, switch | has to be operated for at least 1 second.

There are three modes of operation, when the UPS is switched on.

The loads are supplied through the inverter, the energy is taken from the mains.

Lights Illuminated During Power Failure
In the event of a mains failure, the inverter continues to supply the loads without interruption, the energy is taken from the battery.
In this operation mode, an acoustical signal is given in intervals of approximately 4 seconds. When reaching the battery’s energy minimum, this signal is given at one second intervals.
Lights Illuminated


Lights Illuminated in BYPASS Operation
In the event of large overload (> 140%) switch-over to bypass is initiated and the inverter is blocked. The energy is taken from the mains.
This is not a normal operating status. In the event of mains failure the loads will no longer be supplied (no UPS operation).

The Active UPS has a standard interface COM A and an optional interface COM B. Protocol data transfer signal exchange is through COM A RS232 interface or the optional interface (COM B).
These interfaces can be used for:
The necessary communication software packages and interface cables are available as accessories.
The 9-pin SUB-D connector (pin contacts) contains the RS 232 signals, 5 output signals and 1 input signal. The RS232 signal RXD can also be used as input signal, when the sequential interface is not used.
The 5 alarm outputs are open-collector outputs.

The interface COM A is galvanically separated from all other circuits.

Table 3. Interface COM A
SGN at pin 5 This connection point serves as a reference for all signals.
RXD at pin 2 and TXD at pin 3 In conforms standard RS232 configuration.
This input (pin 2: High signal +5V...+12V, tŠ 1 second, pin 5: 0V) enables the control processor to switch off the UPS in the event of a mains failure. After the mains has been reestablished, the UPS starts again independent of this signal status.
INV SHUTDOWN at pin 2
BATTERY LOW at pin 1 This output goes low, when the battery can supply current for approximately 3 more minutes at nominal load.
Pin 9 goes low and pin 6 goes high for mains voltage failure at the UPS input for a minimum of 10 seconds or when the mains voltage moves beyond the tolerance band. The signal is reset 850 ms after the mains have been reestablished.
AC FAIL at pin 9 and AC FAIL at pin 6
BYPASS ACTIVE at pin 7 This signal goes low after switching over to bypass, blocking the inverter and the energy being supplied by the mains
This output is low, when one of the alarms “BATTERY LOW”, “AC FAIL” or “BYPASS ACTIVE” is given.
SUM ALARM at pin 8
The optional interface COM can be equipped with various interface cards. The designation beside the plug then depends on the type of interface card.
In Figure 18, the function of the interface signals for version COM B is described. The optional interface COM B provides potential-free signalling contacts and a shutdown input and an insulated auxiliary supply.

Troubleshooting Optional Interface COM
Pin Number Condition

This input (pin 3) is enabled with a high signal (+5 V to +12 V with respect to pin 4 (0 V)) and when enabled, switches off the UPS after a mains failure has occurred. After the mains has been reestablished, the UPS starts again independent of this signal status. This input must be high for one (1) second before shut off will occur.
This output provides an N/O (Normally Open) contact between pins 9 and 5, and an N/C (Normally Closed) contact between pins 8 and 5. the 9-5 contact closes when the mains voltage fails at the UPS input or when the mains voltage falls below the lower limit for a minimum of 10 seconds. This contact opens approximately 850 ms after the mains have been reestablished. The 8-5 contact provides a mirror function, opening when the mains voltage fails and closing when mains power returns.
This output provides a N/O contact between pins 6 and 5 and an N/C contact between pins 7 and 5. The 6- 5 contact closes when the battery has been depleted to the point that it can only supply current for approximately three (3) more minutes at nominal load. The 7-5 contact provides a mirror function opening when the battery is low.
This output provides an N/O contact between pins 1 and 5. The 1-5 contact closes after switching to the bypass mode. In the bypass mode, energy to the output of the UPS is being supplied by the mains power and not through the inverter.
This output provides an N/O contact between pins 2 and 5. The 2-5 contact closes when one of the alarms “AC FAIL,” “LOW BATT” or “BYPASS ACTIVE” is active or when the indication “ALARM” at the front- panel is on.

The UPS does not require maintenance by the user. When the battery expires, the UPS or the battery must be replaced by qualified electrical personnel.
The typical battery’s lifetime is 4 years at an ambient temperature of 25 °C. This may vary greatly depending upon load conditions, number of outages, and environmental factors.
For extended storage in moderate climates, the batteries should be charged for 8 hours every three months. Repeat it every two months in high temperature locations.
switch on the front panel and pull the plug out of the mains receptacle.
Do not use scouring powder or plastic-dissolving solutions to clean the UPS.
Do not allow liquid to get inside the UPS.
Make sure that the air vents on the UPS are not obstructed.
Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.

If a problem occurs in spite of the high reliability of the device, please review the following checks before calling Chloride Technical Services.
Please note the following information when you call for service:
Full description of problem (connected loads, does the problem occur regularly or sporadically, display indicators/alarm etc.)
Table 4. Troubleshooting
Problem Possible Cause Action to Take
Main switch is OFF. Switch on main switch.
No mains voltage available.
Have mains checked by qualified electrical personnel.
No indication. No alarm.
Replace fuse by identical type or switch on circuit breaker. If the problem persists, then call Technical Services.
Input fuse has blown or input circuit breaker has tripped.
External batteries are not connected when powered.
Unit will not run without batteries. Confirm proper battery connection.
LINE Indicator is not on, acoustical alarm is given in intervals.
Normal UPS operation (see also “Operational Characteristics (Active)” on page 13).
Mains failure.
LINE Indicator is not on, although mains voltage is available, acoustical alarm is given in intervals.
Input fuse has blown or input circuit breaker has tripped.
Replace fuse with identical type or switch on circuit breaker. If the problem persists, then call Technical Services.
Press BYPASS switch, then ON switch. If normal operation does not occur, call Technical Services.
ALARM Indicator is on, continuous acoustical alarm.
UPS failure.
Over temperature. Reduce ambient temperature.
Batteries are not completely charged. Charge batteries (“Active Installation and Commissioning” on page 11) and test emergency supply time. If problem persists, then call Technical Services.
Emergency supply time is shorter than specified.
Batteries are defective or reached the end of its useful life.
Charging device is faulty.
OVERLOAD LED indicator is on. Overload at the UPS output. Reduce load to the permissible value.

9.1 Chloride Technical Support
Chloride offers 24-hour technical support. To contact Chloride Technical Services:
Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.

Table 5. Chloride Active UPS North America
UPS Model Active 700 Active 1000 Active 2000 Active 3000
Rating 700 VA 1 kVA 2 kVA 3 kVA
Voltage 120 VAC single-phase
Voltage range A 80 - 138 VAC
Frequency 50/60Hz ± 0.5%
Power factor (lambda) >0.95
Integrated battery type Lead-calcium, maintenance-free
Battery voltage (V) 24 36 96 96
Runtimes (min.) (half load/full load) 10/5 15/6 18/7 10/5
Runtimes (min.),1 battery cabinet (half load/full load) NA 70/30 100/30 60/30
Runtimes (min.), 2 battery cabinets (half load/full load) NA 130/60 200/80 120/50
Voltage 100/110/120 VAC, single-phase
Voltage tolerance ± 3%
Frequency with mains control see input frequency
Frequency with internal control 50/60 Hz, ±0. 5%
Distortion factor (linear/non-linear load) max. 4%/max. 7%
Permissible crest factor 3
Overload capability 130% for 1.5 sec., 110% for 10 sec. output short-circuit proof
Radio interference level FCC Part 15 Class A
Interference immunity IEC 801-2,level 4 / IEC 801-3,level 3; IEC 801-4,level 4 / IEC 801-5,level 2)

Table 5. Chloride Active UPS North America
UPS Model Active 700 Active 1000 Active 2000 Active 3000
Protection class IP 20
Noise level mains operation < 41 dBa < 41 dBa < 50 dBa < 50 dBa
Noise level battery operation < 45 dBa
Operating temperature (ambient) + 50°F to +105°F (10°C to + 40°C) recommended +59°F to +89°F (+15°C to + 32°C)
Storage temperature +5°F to +104°F (-15°C to +40°C)
Relative humidity 20% to 90%,non-condensation
max. 10,000 ft. (3000m), above 5,000 ft. (1500m) max ambient temperature = 95°F
UPS
Weight - lbs. (kg) 28.6 (13) 35.3 (16) 75 (34) 75 (34)
Dimensions - HxWxD in. (mm) 8.9 x 5.7 x 16 (225 x 145 x 405) 13.8 x 7.9 x 18.5 (350 x 200 x 470)
Weight lbs (kg) None 42 (19) 106 (48) 106 (48)
8.9 x 5.7 x 16 (225x145x4
13.8 x 7.9 x 18.5 (350 x 200 x 470)
Dimensions - HxWxD in. (mm) None
Visual LED-indication at the front side
RS232 interface Alarm contacts +5V...+12 V
Signal input +5V...+12 V

Table 5. Chloride Active UPS North America
UPS Model Active 700 Active 1000 Active 2000 Active 3000
Type 5-15P 5-15P L5-20P L5-30P
Fusing mains / CB 10 A 15 A 20 A 30 A
Quantity 3 3 3/1 3/1
Type 5-15R 5-15R 5-15R/L5- 20R 5-15R/L5- 30R
Maximum current (at 120 VAC, pf = 0.7) 5.8 A 8.3 A 16.7 25 A
Interfaces COM A 9-pin SUB-D (pin contact)
Interfaces COM B (optional) Optional contact or ethernet card
External battery cabinet none keyed plug, 3-pole
Connections · Mains connections · Load connection

Table 6. Active Rackmount Technical Data for North American Models
Type Active700-19 Active1000-19 Active2000-19 Active3000-19
Unit dimensions - WxHxD - in. (mm)
19 x 3.5 x 17.6 19 x 3.5 x 17.6 19 x 3.5 x 18.8 19 x 3.5 x 18.8
Body dimensions - WxHxD - in. (mm)
16.1 x 3.5 x 16.1 16.1 x 3.5 x 16.1 16.1 x 3.5 x 17.3 16.1 x 3.5 x 17.3
Weight - lbs 33 (15) 40 (18) 27 (12) 30 (13.5)
Ambient temperature +50°F to 104°F (+10°C to +40°C) 5000 ft to 10000 ft: 50°F to 95°F (1500 m to 3000 m: +10°C to +35°C)
Storage temperature +5°F to +104°F (-15°C to +40°C)
Relative Humidity 20% to 90%, non-condensing
Type of cooling Fan
RFI class FCC part 15 Class A
Efficiency > 83% > 83% > 83% > 83%
Noise level 42 dBa 42 dBa 50 dBa 50 dBa
Mains connections 5-15P 5-15P L5-20P L5-30P
Electrical load (output) (3) 5-15R (3) 5-15R (2) 5-20R (1) L5-30R
Minimum fuse protecting of mains 10 A 15 A 20 A 30 A
Battery pack - external — BPActive1000-
Battery voltage — 36 V 96 V 96 V
Net weight (kg) — 47.5 (21.5) 59.5 (27) 59.5 (27)
Dimensions — same as UPS

10 20 30 40 50 C 50 68 86 104 122 F
Figure 19 shows the typical lifetime of the batteries which are used in the UPS devices, depending on the devices’ ambient temperature.
0,1 · Ambient Temperature

Thank you for selecting this uninterruptible power supply (UPS). Chloride’s E-Series UPS offer the most reliable protection from the harmful effects of electrical line disturbances for your computing and communications equipment.
To ensure that your E-Series model and serial number are registered, complete and mail the enclosed postage-paid warranty card.
Chloride offers 24-hour technical support. To contact Chloride Technical Services:
Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.
UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode. Unplugging the UPS does not remove the electrical charge. To ensure that the UPS is off, push BYPASS (for a minimum of 1 second) before unplugging the UPS from the mains.
Do not use AC adaptors with only two conductors to connect the input line cord to the wall socket as this will not connect the earth ground to the equipment.
This device complies with the relevant safety regulations for uninterruptible power supplies for use in a controlled office environment. If you have any questions, please contact Chloride Technical Service at (800) 388-4234 or (847) 990-3229.

(see chapter 12, “Display and Operation Elements (E-Series)” on page 29) does not isolate the device (UPS) from the mains. To isolate completely from the mains, the main switch must be switched off and the power plug disconnected.
Chloride Active and E-Series UPSs are UL listed under UL1778 for North American units.
This product may only be sold to users with qualified personnel. In order to avoid RF, restrictions for installation or additional precautions may apply.

The Uninterruptible Power System (UPS) is connected between AC power and the load. It protects the load against mains disturbances, especially power failures.
Its operation is based on the on-line principle. The connected load is supplied power through the UPS’s inverter. Power disturbances from the mains are suppressed which increases the loads’ operational security (PC, network server, multi-user systems etc.)
In the event of a mains failure, maintenance-free batteries provide an uninterrupted supply of energy. In practice, mains failures are of relatively short duration, dependent on the mains quality. Therefore, the UPS’ energy is in most cases sufficient to ensure continuous operation of the connected systems, until the mains is reestablished. In the event of a longer lasting mains failure it allows for controlled shutdown of connected systems.
The UPS indicates by acoustical (buzzer) and optical (LED) alarms that a mains failure has occurred and is still persistent. Battery runtimes vary depending upon load, number of batteries and environmental conditions.
The following chart shows the approximate values of the emergency runtime (assuming fully charged battery at the onset of the mains failure.)
Load in % E61 E101 E203 OVERLOAD >105 w/BPE101 95-105 9 min 9 min 15 min LOAD 75-95 10 min 10 min 20 min 55-75 13 min 13 min 25 min 35-55 21 min 21 min 45 min 1-35 40 min 40 min 90 min
The most reliable method for determining actual battery runtime is the application of Chloride MopUPS® software. With this software, the prospective remaining battery capacity is indicated before and during an AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application program, operating system and computer hardware, it can be ensured that in the event of a power failure the application programs are automatically closed, the subscribers logged in at the server are logged out, the data is stored and the operating systems are shut down. For further information please refer to our publication about the Chloride ManageUPS™NET SNMP Adapter.
After return of the mains voltage, the UPS automatically initiates a restart. The connected systems are restarted according to their specifications.
In the event of overload or internal failure, the load is supplied from the mains via an automatic bypass. As soon as the normal status is reestablished, automatic switchover to inverter operation is performed.

This operation manual contains all relevant information to install and operate the UPS.
The OVERLOAD indicator is on when the UPS is overloaded.
The LED-chain LOAD indicates the load state of the UPS.
The BYPASS indicator is on when the UPS supplies a voltage via the bypass.
The INVERTER indicator is on when the inverter is in operation.
The LED-chain BATTERY indicates the battery’s charge state (normal operation) or the % of battery time remaining when mains fail.
The LINE indicator is on when there is mains voltage at the UPS
input.
The ALARM indicator is on when the UPS is faulty. Simulta- neously, an acoustical signal is given, which can be reset by pressing the BYPASS switch.
The switch switches the inverter off and the bypass on. The UPS still has output voltage.
Operating the switch | activates the inverter. After a delay of approximately 5 seconds the BYPASS indicator extinguishes and the INVERTER indicator illuminates.


Selector switch Interface COM A Interface COM B (optional)
Selector switch - for output voltage The selection of the output voltage must be made with the UPS switched off.*
(E61 with optional PDU shown)
Output circuit breaker External battery connector
Fans · Input circuit breaker · Optional PDU


Selector switch Interface COM A Interface COM B (optional)
Selector switch - for output voltage The selection of the output voltage must be made with the UPS switched off.*
(E101 with optional PDU shown)
Output circuit breaker Input circuit breaker
Mains fuse and Battery switch
* Call Chloride Technical Services for information on setting output voltages ((800) 388-4234 or (847) 990-3228)
Selector switch - for output voltage The selection of the output voltage must be made with the UPS switched off.*
Selector switch (must be set to 230 V) EPO connection Interface COM A Interface COM B (optional)

Output circuit breaker Input circuit breaker
Wiring box cover (or optional PDU)
* Call Chloride Technical Services for information on setting output voltages at (800) 388-4234 or (847) 990-3229

Upon receipt of your UPS, carefully examine the packing containers for any sign of physical damage. Notify the carrier immediately if damage is present. Carefully unpack the UPS. Retain the packaging for reuse or dispose. Check the packing for damages.
UPS includes:
1. Unpack and move E-Series UPS and battery cabinet(s), if supplied, into desired installation location. 2. Adjust leveling jacks under the UPS and battery cabinet(s) to remove wheels of the units from the floor and avoid movement of connections. 3. Turn off input and output breakers on the back of the UPS and any battery cabinets to be used. 4. Turn off and isolate the power source to be used for the UPS input using proper lock-out/tag-out procedures. 5. Confirm that the power source to be used for the UPS is 208 V (208/120 3 φ for E203). 6. Remove the connection plate on the back of the UPS to expose connection terminals. 7. Wire input of the UPS by first connecting ground (earth) wire to GND (ground) terminal. Next, connect the input power leads to L1/N and L2 (for E61 and E101) or L1, L2, and L3 (for E203). See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gauge, wire temperature and screw torque requirements.
For model E61 (if using an external battery cabinet), first remove the connection plate from the rear of the battery cabinet, then connect the battery cable (supplied with the battery cabinet) from the battery connector on the UPS to the terminals on the battery cabinet. Confirm that (+), (-) and GND terminals are connected to proper wires. Connect any additional battery cabinets in a “daisy-chain”

manner until all GND terminals, (-) terminals and (+) terminals are connected together. See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gage, wire temperature and screw torque requirements.
For models E101 and E203, first remove the connection plate from the rear of the battery cabinet. Next, connect the wires from GND terminal on the UPS to GND wire on the battery cabinet, and then from (-) terminal on the UPS to the (-) terminal on the battery cabinet. Finally, connect (+) terminal on the UPS to the (+) terminal on the battery cabinet. Connect any additional battery cabinets in a “daisy-chain” manner until all GND terminals, (-) terminals and (+) terminals are connected together. See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gage, wire temperature and screw torque requirements. 10. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires are pinched or damaged. 11. Confirm that all input and output breakers on the UPS and battery cabinet(s) are in the OFF position. 12. Restore power source to the UPS.

Table 7. Minimum Requirements for E-Series UPS Installation
Min. Wire Gaug
Min. Wire Gaug
Min. Wire Gaug
Min. Wire Temp
Min. Wire Temp . (°C)*
Min. Wire Temp . (°C)*
GND Chassis Ground ** 40 75 ** 45 75 ** 45 90
L1/N Line 1 8 40 75 6 45 75 4 45 90
L2 Line 2 8 40 75 6 45 75 4 45 90
L3 Line 3 N/A 4 45 90
120A 120 V from Neutral 10 35 75 6 45 75 4 45 90
0 Neutral 10 35 75 6 45 75 4 45 90
88B 208 V from 120A 10 35 75 6 45 75 4 45 90
120B 120 V from Neutral 10 35 75 6 45 75 4 45 90
GND Chassis Ground opt 35 75 opt 45 75 opt 45 90
+ +240 VDC to - N/A N/A N/A 4 45 75 4 45 75
- Battery Common N/A N/A N/A 4 45 75 4 45 75
GND Chassis Ground N/A N/A N/A 4 45 75 4 45 75
* Use insulated copper wire rated 75 C minimum. ** Must be no smaller than wire connected to L1/N and L2 (for E61 and E101) or L1, L2, L3 (for E203).






When connected to the mains, the batteries automatically begin charging. The UPS may be used immediately, however, full run time will not be available until the batteries are fully charged.
The “LINE” and “BYPASS” indicators and the “LOAD” (output load) indicator are illuminated. After a few seconds the “INVERTER” indicator illuminates and the “BYPASS” indicator turns off. The UPS is now in ON-LINE operation.
An overload alarm signal (1 signal per second) is heard.
The “LINE” and “BYPASS” LED indicators are illuminated.

dryers, vacuum cleaners).
The “LINE” and “BYPASS” indicators and the “LOAD” (output load) indicator are illuminated. After a few seconds the “INVERTER” indicator illuminates and the “BYPASS” indicator turns off. The UPS is now in ON-LINE operation.
An overload alarm signal (1 signal per second) is heard.

The following table shows the designations of the battery cabinets which are available for the UPS devices.
Table 8. External Battery Packs
E61 (E41) BPE61 2x (20 x 7. 2 Ah)
E101 (E81)/ E203 (E153) BPE101 1x (20 x 38 Ah)
Disconnect the UPS from the mains and the loads from the UPS.
Connect the battery cabinet types BP1000, BP3000 and BPE61 to the UPS using the supplied cable. The connection scheme is shown in the figures below. With type BPE101, make the hard-wired connection between UPS and the battery cabinet (see figures 28 and 29 on page 40).
Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.

Battery Plug for Connection of an Additional Battery Extension
Model Cabinet Batteries



Table 9. Technical data of the connection cable
Minimum permissible cable cross section 6 mm2, 8 AWG 4 AWG
Maximum permissible cable cross section 20 mm2, 4 AWG 4 AWG
Nominal operating voltage 240 VDC 240 VDC
Hardwire

14.1 Ready for Operation Check
To check the emergency supply feature of the UPS, it must be disconnected from the mains.
When correctly functioning with charged batteries, an acoustical signal in intervals of 4 seconds will be heard. The LED “LINE” (line voltage) indicator disappears. When the interval between the acoustical signals is reduced to 1 second, the UPS will supply energy for a maximum of 3 more minutes before it is automatically switched off.
The load will be supplied from the batteries during the specified emergency supply period. If this is not so, then please check in chapter 17 “Troubleshooting (E-Series)” on page 48.
Reconnect the UPS with the mains.
The UPS is now again ready for normal operation. Please note, that the batteries have to be recharged before the complete emergency supply period is again available.
The self test is a LED test.
With the UPS connected to the AC power, switch | has to be operated for at least 1 second.

There are three modes of operation, when the UPS is switched on.
The loads are supplied through the inverter, the energy is taken from the mains.
Lights Illuminated During Power Failure
In the event of a mains failure, the inverter continues to supply the loads uninterruptedly, the energy is taken from the battery.
In this operation mode, an acoustical signal is given in intervals of approximately 4 seconds. When reaching the battery’s energy minimum, this signal is given every second.
Lights Illuminated

Lights Illuminated in BYPASS Operation
In the event of large overload (> 140%) switch-over to bypass is initiated and the inverter is blocked. The energy is taken from the mains.
This is not a normal operating status. In the event of mains failure the loads will no longer be supplied (no UPS operation).

The E-Series UPS has a standard interface COM A and an optional interface COM B. Protocol data transfer signal exchange is through COM A RS232 interface or the optional interface (COM B).
These interfaces can be used for:
The necessary communication software packages and interface cables are available as accessories.
The 9-pin SUB-D connector (pin contacts) contains the RS 232 signals, 5 output signals and 1 input signal. The RS232 signal RXD can also be used as input signal, when the sequential interface is not used.
The 5 alarm outputs are open-collector outputs.

The interface COM A is galvanically separated from all other circuits.

Table 10. Interface COM A
SGN at pin 5 This connection point serves as a reference for all signals.
RXD at pin 2 and TXD at pin 3 In conforms standard RS232 configuration.
This input (pin 2: High signal +5V...+12V, > 1 second, pin 5: 0V) enables the control processor to switch off the UPS in the event of a mains failure. After the mains has been reestablished, the UPS starts again independent of this signal status.
INV SHUTDOWN at pin 2
BATTERY LOW at pin 1 This output goes low, when the battery can supply current for approximately 3 more minutes at nominal load.
Pin 9 goes low and pin 6 goes high for mains voltage failure at the UPS input for a minimum of 10 seconds or when the mains voltage moves beyond the tolerance band. The signal is reset 850 ms after the mains have been reestablished.
AC FAIL at pin 9 and AC FAIL at pin 6
BYPASS ACTIVE at pin 7 This signal goes low after switching over to bypass, blocking the inverter and the energy being supplied by the mains
This output is low, when one of the alarms “BATTERY LOW”, “AC FAIL” or “BYPASS ACTIVE” is given.
SUM ALARM at pin 8
The optional interface COM can be equipped with various interface cards. The designation beside the plug then depends on the type of interface card.
In the following the function of the interface signals for version COM B is described. The optional interface COM B provides potential-free signalling contacts and a shutdown input and an insulated auxiliary supply.
Pin Number Condition

Troubleshooting Optional Interface COM
This input (pin 3) is enabled with a high signal (+5 V to +12 V with respect to pin 4 (0 V)) and when enabled, switches off the UPS after a mains failure has occurred. After the mains has been reestablished, the UPS starts again independent of this signal status. This input must be high for one (1) second before shut off will occur.
This output provides an N/O (Normally Open) contact between pins 9 and 5, and an N/C (Normally Closed) contact between pins 8 and 5. the 9-5 contact closes when the mains voltage fails at the UPS input or when the mains voltage falls below the lower limit for a minimum of 10 seconds. This contact opens approximately 850 ms after the mains have been reestablished. The 8-5 contact provides a mirror function, opening when the mains voltage fails and closing when mains power returns.
This output provides a N/O contact between pins 6 and 5 and an N/C contact between pins 7 and 5. The 6- 5 contact closes when the battery has been depleted to the point that it can only supply current for approximately three (3) more minutes at nominal load. The 7-5 contact provides a mirror function opening when the battery is low.
This output provides an N/O contact between pins 1 and 5. The 1-5 contact closes after switching to the bypass mode. In the bypass mode, energy to the output of the UPS is being supplied by the mains power and not through the inverter.
This output provides an N/O contact between pins 2 and 5. The 2-5 contact closes when one of the alarms “AC FAIL,” “LOW BATT” or “BYPASS ACTIVE” is active or when the indication “ALARM” at the front- panel is on.
(E-Series Models E153X and E203X only)
The external connection to the EPO circuit is located next to the 9-pin SUB-D (interface com A) connector in the upper right of the back of the unit. If the circuit between the two EPO connector pins is “opened,” the output of the UPS is immediately switched off. To restart the UPS, the procedures outlined in section 13.3 on page 37 must be followed. The EPO circuit may be extended by connecting normally closed switches in series between the EPO connector pins. Activating (opening) any of the series switches will cause the UPS to shut off its output.

The UPS does not require maintenance by the user. When the battery expires, the UPS or the battery must be replaced by qualified electrical personnel.
The typical battery’s lifetime is 4 years at an ambient temperature of 25 °C. This may vary greatly depending upon load conditions, number of outages, and environmental factors.
For extended storage in moderate climates, the batteries should be charged for 8 hours every three months. Repeat it every two months in high temperature locations.
switch on the front panel, switch off the input circuit breaker, isolate the source and secure it against reclosing.
Do not use scouring powder or plastic-dissolving solutions to clean the UPS.
Do not allow liquid to get inside the UPS.
Make sure that the air vents on the UPS are not obstructed.
Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.

If a problem occurs in spite of the high reliability of the device, please review the following checks before calling Chloride Technical Services.
Please note the following information when you call for service:
Full description of problem (connected loads, does the problem occur regularly or sporadically, display indicators/alarm etc.)
Table 11. Troubleshooting
Problem Possible Cause Action to Take
Main switch is OFF. Switch on main switch.
No mains voltage available.
Have mains checked by qualified electrical personnel.
No indication. No alarm.
Replace fuse by identical type or switch on circuit breaker. If the problem persists, then call Technical Services.
Input fuse has blown or input circuit breaker has tripped.
External batteries are not connected when powered.
Unit will not run without batteries. Confirm proper battery connection.
LINE Indicator is not on, acoustical alarm is given in intervals.
Normal UPS operation (see also “Operational Characteristics (E- Series)” on page 41).
Mains failure.
LINE Indicator is not on, although mains voltage is available, acoustical alarm is given in intervals.
Input fuse has blown or input circuit breaker has tripped.
Replace fuse with identical type or switch on circuit breaker. If the problem persists, then call Technical Services.
Press BYPASS switch, then ON switch. If normal operation does not occur, call Technical Services.
ALARM Indicator is on, continuous acoustical alarm.
UPS failure.
Over temperature. Reduce ambient temperature.
Batteries are not completely charged. Charge batteries (“E-Series Installation and Commissioning” on page 33) and test emergency supply time. If problem persists, then call Technical Services.
Emergency supply time is shorter than specified.
Batteries are defective or reached the end of its useful life.
Charging device is faulty.
OVERLOAD LED indicator is on. Overload at the UPS output. Reduce load to the permissible value.

18.1 Chloride Technical Support
Chloride offers 24-hour technical support. To contact Chloride Technical Services:
Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.

Table 12. Chloride E-Series UPS North America
UPS Model E61XA (E41XA*)
E203XA (E153XA*)
(E81*)
* Models may be upgraded to base kVA of UPS shown.
Rating 6 kVA 10 kVA 20 kVA
Voltage 208 VAC single-phase 208/120 three- phase
Voltage range 170 V to 276 V 176 to 276 V 177 to 240 V
Frequency 50/60Hz ± 5%
Power factor (lambda) >0.97 >0.95
Integrated battery type Lead-calcium, maintenance-free None
Battery voltage (V) 240
Runtimes (min.) (half load/full load) 25/8 30/12 N/A
Runtimes (min.),1 battery cabinet (half load/full load) 94/38 100/40 40/15
Voltage - North American 120, 208, 240 VAC, single-phase
Voltage tolerance ± 3%
Frequency with mains control see input frequency
Frequency with internal control 50/60 Hz, ± 0.5%
Distortion factor (linear/non-linear load) max. 4%/max. 7% max. 5%/ max.
Permissible crest factor 3
Overload capability 130% for 2 sec., 110% for 10 sec. output short-circuit proof
Radio interference level FCC Part 15 Class A

Table 12. Chloride E-Series UPS North America
UPS Model E61XA (E41XA*)
E203XA (E153XA*)
(E81*)
Interference immunity IEC 801-2,level 4 / IEC 801-3,level 3 IEC 801-4,level 4 / IEC 801-5,level 2
Efficiency > 86% >90% >85%
Noise level mains operation < 50 dBa < 55 dBa
Noise level battery operation < 55 dBa
Operating temperature + 50°F to +105°F (+10°C to + 40°C) recommended +59°F to +89°F (+15°C to + 32°C)
Storage temperature +5°F to +104°F (-15°C to +40°C)
Relative humidity 20% to 90%, non-condensing
max. 10,000 ft. (3,000m), above 5,000 ft. (1,500m) max ambient temperature = 95°F
UPS
Weight - lbs. 347 580 787
46.5 x 16.5 x 31.5 (1180 x 420 x
Dimensions - HxWxD in. (mm) 27.8 x 10.6 x 22.5 (705 x 270 x 570)
38 x 13.4 x 25 (965 x 340 x 670)
Weight lbs 337 894
Dimensions - HxWxD in. (mm) 27.8 x 10.6 x 22.5 (705 x 270 x 570)
38 x 15 x 26.4 (965 x 380 x 670)
Visual LED-indication at the front side
RS232 interface Alarm contacts +5V...+12V
Signal input +5V...+12V

Table 12. Chloride E-Series UPS North America
UPS Model E61XA (E41XA*)
E203XA (E153XA*)
(E81*)
hardwired min 10 AWG/6
hardwired min 6 AWG/10
hardwired 4 AWG/20 mm2
Fusing of the mains supply 35 A 63 A 60 A x 5 poles
hardwired min 10 AWG/6
hardwired min 6 AWG/10
hardwired 4 AWG/20 mm2
Interfaces COM A 9-pin SUB-D, pin contacts
Interfaces COM B (optional) 9-pin SUB-D, outlet
hardwired Min 8 AWG/6
External battery cabinet keyed plug, 3-
hardwired 4 AWG/20 mm2
hardwired removable terminal block

10 20 30 40 50 C 50 68 86 104 122 F
Figure 19 shows the typical lifetime of the batteries which are used in the UPS devices, depending on the devices’ ambient temperature.
19.2 Optional Power Distribution Units (PDU) available 4 -10 kVA.

0,1 · Ambient Temperature

Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 United States Toll Free: (800) 239-2257 Tel: (847) 990-3228 Fax: (800) 833-6829
© 2003, UP Systems, Inc.
All other trademarks, product and corporatate names are all property of their respected owners. Specifications contained in this document are subject to change without notice.
UPLIT039 Rev. 0
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| No indication. No alarm. | Main switch is OFF. | Switch on main switch. | p.24 |
| No indication. No alarm. | No mains voltage available. | Have mains checked by qualified electrical personnel. | p.24 |
| No indication. No alarm. | Input fuse has blown or input circuit breaker has tripped. | Replace fuse by identical type or switch on circuit breaker. If the problem persists, then call Technical Services. | p.24 |
| No indication. No alarm. | External batteries are not connected when powered. | Unit will not run without batteries. Confirm proper battery connection. | p.24 |
| LINE Indicator is not on, acoustical alarm is given in intervals. | Mains failure. | Normal UPS operation (see also “Operational Characteristics (Active)” on page 13). | p.24 |
| LINE Indicator is not on, although mains voltage is available, acoustical alarm is given in intervals. | Input fuse has blown or input circuit breaker has tripped. | Replace fuse with identical type or switch on circuit breaker. If the problem persists, then call Technical Services. | p.24 |
| ALARM Indicator is on, continuous acoustical alarm. | UPS failure. | Press BYPASS switch, then ON switch. If normal operation does not occur, call Technical Services. | p.24 |
| ALARM Indicator is on, continuous acoustical alarm. | Over temperature. | Reduce ambient temperature. | p.24 |
| Emergency supply time is shorter than specified. | Batteries are not completely charged. | Charge batteries (“Active Installation and Commissioning” on page 11) and test emergency supply time. If problem persists, then call Technical Services. | p.24 |
| Emergency supply time is shorter than specified. | Batteries are defective or reached the end of its useful life. | p.24 | |
| Emergency supply time is shorter than specified. | Charging device is faulty. | p.24 | |
| OVERLOAD LED indicator is on. | Overload at the UPS output. | Reduce load to the permissible value. | p.24 |
| Emergency supply time is shorter than specified. | Batteries are not completely charged. | Charge batteries (“E-Series Installation and Commissioning” on page 33) and test emergency supply time. If problem persists, then call Technical Services. | p.52 |
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.