Rackmount Solutions VA 6000

58 pages·1.7 MB·Power Supply·PDF·ENDEFRITNLJA
Rackmount Solutions VA 6000
Table of Contents 183 sections UPLIT039 Front Page.pdf · important safety instructions · save these instructions. · Please read and save these instructions. This manual contains important instructions for Chloride models: · … ShowHide
UPLIT039 Front Page.pdfp.1important safety instructionsp.2save these instructions.p.2Please read and save these instructions. This manual contains important instructions for Chloride models:p.2Follow these instructions during installation and maintenance of the UPS and batteries.p.2If you have a problem with the UPS, please refer to this manual before calling the Technical Support Department. The Troubleshooting section on pages 20 and 53 address most UPS-related issues.p.2This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules. These lim...p.2Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 USA Telephone: (847) 990-3228 Toll Free: (800) 239-2257 Facsimile: (800) 833-6829p.2UPLIT039 TOC.pdfp.1Chapter 1 Chloride Introduction 1p.3Chapter 2 Display and Operation Elements (Active) 3p.3Chapter 3 Active Rackmount Series 7p.3Chapter 4 Active Installation and Commissioning 11p.3Chapter 5 Operational Characteristics (Active) 13p.3Chapter 6 Description of the Interface (Active) 16p.3Chapter 7 Maintenance (Active) 19p.3Chapter 8 Troubleshooting (Active) 20p.3Chapter 9 Technical Support for your Active UPS 21p.3Chapter 10 Active Tower and Rackmount Specifications 22p.3Chapter 11 Chloride Introduction 27p.3Chapter 12 Display and Operation Elements (E-Series) 29p.3Chapter 13 E-Series Installation and Commissioning 33p.3Chapter 14 Operational Characteristics (E-Series) 41p.4Chapter 15 Description of the Interface (E-Series) 44p.4Chapter 16 Maintenance (E-Series) 47p.4Chapter 17 Troubleshooting (E-Series) 48p.4Chapter 18 Technical Support for your E-Series UPS 49p.4Chapter 19 E-Series Specifications 50p.4UPLIT039 Active and ESeries Rev 0.pdfp.1Chapter 1 Chloride Introductionp.51.1 Registering your Chloride Active UPSp.51.2 Technical Support and Service (Active)p.51.3 Safety Notesp.5Chapter 2 Display and Operation Elements (Active)p.72.1 Frontp.82.2 Rearp.92.2.1 Active 700 and 1000p.9Fig. 1: Active 700 Rear Viewp.9Fig. 2: Active 1000 Rear Viewp.92.2.2 Active 2000 and 3000p.10Fig. 3: Active 2000 Rear Viewp.10Fig. 4: Active 3000 Rear Viewp.10Chapter 3 Active Rackmount Seriesp.113.1 Safetyp.113.1.1 Intended usep.113.1.2 Further safety notesp.113.2 Installation and operating notesp.113.2.1 Selection of the mounting locationp.113.2.2 Mechanical Attachmentp.12Fig. 5: Mounting the rails at the body of the UPS or Battery-Pack.p.12Table 1. Battery Cabinetsp.123.2.3 Connection of a battery packp.123.3 Unit Rear View and Connectionsp.133.3.1 Active 700-19 and Active 1000-19p.13Fig. 6: Active700-19p.13Fig. 7: Active1000-19p.13Fig. 8: Battery Pack - BPActive1000-19p.133.3.2 Active 2000-19 and Active 3000-19p.14Fig. 9: Active2000-19p.14Fig. 10: Battery Pack - BPActive3000-19p.143.3.3 Active3000-19p.14Fig. 11: Active3000 -19p.14Fig. 12: BPActive3000-19p.14Chapter 4 Active Installation and Commissioningp.154.1 Commissioning of an External Battery Cabinetp.16Table 2. External Battery Packsp.16Fig. 13: Connection of Battery Extensions for devices Active 1000p.16Chapter 5 Operational Characteristics (Active)p.175.1 Ready for Operation Checkp.175.2 Self Testp.175.3 Modes of Operationp.185.3.1 Normal Operation, Inverter On (Mains Available)p.18Fig. 14: Front Display Panel During Normal Operations (Mains Available)p.185.3.2 Battery Operation, Inverter On (Mains Failure)p.18Fig. 15: Front Display Panel During Battery Operation (Mains Failure)p.185.3.3 Bypass Operation, Inverter OFF (Overload > 140%)p.19Fig. 16: Front Display Panel During Bypass Operation (Overload > 140%)p.19Chapter 6 Description of the Interface (Active)p.206.1 Standard Interface COM Ap.20Fig. 17: COM A signal Definition and Connectionp.20Table 3. Interface COM Ap.216.2 Optional Interface COM Bp.21Fig. 18: Simplified Schematic of Interface Connectionsp.21Chapter 7 Maintenance (Active)p.237.1 Storagep.231. Connect the UPS to a grounded receptacle.p.232. Pull out the mains plug after 8 hours.p.233. Note the date of charging on the packing.p.237.2 Cleaningp.23Chapter 8 Troubleshooting (Active)p.24Table 4. Troubleshootingp.24Chapter 9 Technical Support for your Active UPSp.259.1 Chloride Technical Supportp.25Chapter 10 Active Tower and Rackmount Specificationsp.26Table 5. Chloride Active UPS North Americap.26Table 6. Active Rackmount Technical Data for North American Modelsp.2910.1 Battery Lifetimep.30Fig. 19: Typical lifetime of the batteriesp.30Chapter 11 Chloride Introductionp.3111.1 Registering your Chloride E-Series UPSp.3111.2 Technical Support and Service (E-Series)p.3111.3 Safety Notesp.3111.4 Warning for E-Series E61, E101 and E203p.32Chapter 12 Display and Operation Elements (E-Series)p.3312.1 Frontp.3412.2 Rearp.3512.2.1 E-Series E61 and E101p.35Fig. 20: E41 or E61p.35Fig. 21: E81 or E101p.3612.2.2 E-Series E203p.36Fig. 22: E203p.36Chapter 13 E-Series Installation and Commissioningp.3713.1 Installation of the E-Series (Hardwired)p.371. Unpack and move E-Series UPS and battery cabinet(s), if supplied, into desired installation location.p.372. Adjust leveling jacks under the UPS and battery cabinet(s) to remove wheels of the units from the floor and avoid movement of connections.p.373. Turn off input and output breakers on the back of the UPS and any battery cabinets to be used.p.374. Turn off and isolate the power source to be used for the UPS input using proper lock-out/tag-out procedures.p.375. Confirm that the power source to be used for the UPS is 208 V (208/120 3 f for E203).p.376. Remove the connection plate on the back of the UPS to expose connection terminals.p.377. Wire input of the UPS by first connecting ground (earth) wire to GND (ground) terminal. Next, connect the input power leads t...p.378. If the UPS does not have an attached Power Distribution Unit (PDU), wire the output of the UPS to appropriate load as follows:p.379. Connect the UPS to the battery cabinet(s) (if required)p.3710. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires are pinched or damaged.p.3811. Confirm that all input and output breakers on the UPS and battery cabinet(s) are in the OFF position.p.3812. Restore power source to the UPS.p.38Table 7. Minimum Requirements for E-Series UPS Installationp.39Fig. 23: Wiring Diagram for the E61p.39Fig. 24: Wiring Diagram for the E101p.40Fig. 25: Wiring Diagram for the E153 and E203p.40Fig. 26: E203 Power Systemp.4013.2 Commissioning of the E-Seriesp.411. Before using the device, charge the batteries for 8 hours.p.412. After charging, connect the loads to the UPS.p.413. When the signal interface is used, then the connection cable (accessories) is linked between UPS and computer system. Please see instructions in the documentation for the accessories.p.414. Switch on the loads.p.415. Switch on the UPS by operating the switch | on the front panel.p.4113.3 Starting Up the E-Seriesp.411. Switch on the input circuit breaker on the back of the UPS.p.412. When connected to the mains, the batteries automatically begin charging. The UPS may be used immediately, however, full run time will not be available until the batteries are fully chargedp.413. Before using the device, charge the batteries for 8 hours.p.414. After battery charging is completed, switch on the output circuit breaker at the rear side of the UPS. The loads are now supplied by the UPS.p.415. If a signal interface cable is used, connect the cable (accessory) between the UPS and the computer system. Please observe further instructions in the documentation for the accessory.p.426. Switch on the loads.p.427. Switch on the UPS by operating the switch | at the front plate.p.4213.4 Commissioning of an External Battery Cabinetp.43Table 8. External Battery Packsp.43Fig. 27: Connection of an External Battery Cabinet to Type E61p.43Fig. 28: Connection of an External Battery Cabinet to Type E101p.44Fig. 29: Connection of an External Battery cabinet to Type E203p.44Table 9. Technical data of the connection cablep.44Chapter 14 Operational Characteristics (E-Series)p.4514.1 Ready for Operation Checkp.4514.2 Self Testp.4514.3 Modes of Operationp.4614.3.1 Normal Operation, Inverter On (Mains Available)p.46Fig. 30: Front Display Panel During Normal Operations (Mains Available)p.4614.3.2 Battery Operation, Inverter On (Mains Failure)p.46Fig. 31: Front Display Panel During Battery Operation (Mains Failure)p.4614.3.3 Bypass Operation, Inverter OFF (Overload > 140%)p.47Fig. 32: Front Display Panel During Bypass Operation (Overload > 140%)p.47Chapter 15 Description of the Interface (E-Series)p.4815.1 Standard Interface COM Ap.48Fig. 33: COM A signal Definition and Connectionp.48Table 10. Interface COM Ap.4915.2 Optional Interface COM Bp.49Fig. 34: Simplified Schematic of Interface Connectionsp.4915.3 Emergency Power Off (EPO)p.50Chapter 16 Maintenance (E-Series)p.5116.1 Storagep.511. Install the hard-wire connections according to chapter 13 “E-Series Installation and Commissioning” on page 33 at an appropriate source. Switch on the input circuit breaker at the rear of the device for hardwired connection.p.512. Switch off the input circuit breaker of the UPS. Then remove the connections of the UPS in an inverted sequence to what is described in chapter 13 “E-Series Installation and Commissioning” on page 33.p.513. Note the date of charging on the packing.p.5116.2 Cleaningp.51Chapter 17 Troubleshooting (E-Series)p.52Table 11. Troubleshootingp.52Chapter 18 Technical Support for your E-Series UPSp.5318.1 Chloride Technical Supportp.53Chapter 19 E-Series Specificationsp.54Table 12. Chloride E-Series UPS North Americap.5419.1 Battery Lifetimep.57Fig. 35: Typical lifetime of the batteriesp.5719.2 Optional Power Distribution Units (PDU) available 4 -10 kVA.p.57Fig. 36: Optional Power Distribution Unitsp.57
Page 1 of the Rackmount Solutions VA 6000 user manual — Active and E-Series Uninterruptible Power Supply
Page 1 · click to enlarge
Page 1
Rackmount Solutions VA 6000 — UPLIT039 Front Page.pdf diagram (page 1)
Fig. 1 · UPLIT039 Front Page.pdf

Active and E-Series Uninterruptible Power Supply

Operating Manual

  • 700 VA
  • 700 VA Rackmount
  • 1000 VA
  • 1000 VA Rackmount
  • 2000 VA Rackmount
  • 2000 VA
  • 3000 VA
  • 3000 VA Rackmount
  • 6000 VA
  • 10000 VA
  • 20000 VA
Page 2 of the Rackmount Solutions VA 6000 user manual — FCC Compliance
Page 2 · click to enlarge
Page 2
Rackmount Solutions VA 6000 — important safety instructions diagram (page 2)
Fig. 2 · important safety instructions

Active™ and E-Series™ User Instruction Manual

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS.

Please read and save these instructions. This manual contains important instructions for Chloride models:

  • Active700
  • Active1000
  • Active2000
  • Active3000
  • BPActive1000
  • BPActive3000
  • Active700-19
  • Active1000-19
  • Active2000-19
  • Active3000-19
  • BPActive1000-19
  • BPActive3000-19
  • E61XA (E41XA)
  • E101XA (E81XA)
  • E203XA (E153XA)
  • BPE61
  • BPE101

Follow these instructions during installation and maintenance of the UPS and batteries.

If you have a problem with the UPS, please refer to this manual before calling the Technical Support Department. The Troubleshooting section on pages 20 and 53 address most UPS-related issues.

FCC Compliance

This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial environment. The UPS generates, uses, and can radiate radio frequency energy. If installation and use is not in accordance with the instruction manual, it may cause harmful interference to radio communications.

Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 USA Telephone: (847) 990-3228 Toll Free: (800) 239-2257 Facsimile: (800) 833-6829

UPLIT039 Rev. 0 4/03

Active and E-Series UPS User Manual i

Page 3 of the Rackmount Solutions VA 6000 user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

UPLIT039 Front Page.pdfp.1important safety instructionsp.2save these instructions.p.2Please read and save these instructions. This manual contains important instructions for Chloride models:p.2Follow these instructions during installation and maintenance of the UPS and batteries.p.2If you have a problem with the UPS, please refer to this manual before calling the Technical Support Department. The Troubleshooting section on pages 20 and 53 address most UPS-related issues.p.2This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules. These lim...p.2Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 USA Telephone: (847) 990-3228 Toll Free: (800) 239-2257 Facsimile: (800) 833-6829p.2UPLIT039 TOC.pdfp.1Chapter 1 Chloride Introduction 1p.3Chapter 2 Display and Operation Elements (Active) 3p.3Chapter 3 Active Rackmount Series 7p.3Chapter 4 Active Installation and Commissioning 11p.3Chapter 5 Operational Characteristics (Active) 13p.3Chapter 6 Description of the Interface (Active) 16p.3Chapter 7 Maintenance (Active) 19p.3Chapter 8 Troubleshooting (Active) 20p.3Chapter 9 Technical Support for your Active UPS 21p.3Chapter 10 Active Tower and Rackmount Specifications 22p.3Chapter 11 Chloride Introduction 27p.3Chapter 12 Display and Operation Elements (E-Series) 29p.3Chapter 13 E-Series Installation and Commissioning 33p.3Chapter 14 Operational Characteristics (E-Series) 41p.4Chapter 15 Description of the Interface (E-Series) 44p.4Chapter 16 Maintenance (E-Series) 47p.4Chapter 17 Troubleshooting (E-Series) 48p.4Chapter 18 Technical Support for your E-Series UPS 49p.4Chapter 19 E-Series Specifications 50p.4UPLIT039 Active and ESeries Rev 0.pdfp.1Chapter 1 Chloride Introductionp.51.1 Registering your Chloride Active UPSp.51.2 Technical Support and Service (Active)p.51.3 Safety Notesp.5Chapter 2 Display and Operation Elements (Active)p.72.1 Frontp.82.2 Rearp.92.2.1 Active 700 and 1000p.9Fig. 1: Active 700 Rear Viewp.9Fig. 2: Active 1000 Rear Viewp.92.2.2 Active 2000 and 3000p.10Fig. 3: Active 2000 Rear Viewp.10Fig. 4: Active 3000 Rear Viewp.10Chapter 3 Active Rackmount Seriesp.113.1 Safetyp.113.1.1 Intended usep.113.1.2 Further safety notesp.113.2 Installation and operating notesp.113.2.1 Selection of the mounting locationp.113.2.2 Mechanical Attachmentp.12Fig. 5: Mounting the rails at the body of the UPS or Battery-Pack.p.12Table 1. Battery Cabinetsp.123.2.3 Connection of a battery packp.123.3 Unit Rear View and Connectionsp.133.3.1 Active 700-19 and Active 1000-19p.13Fig. 6: Active700-19p.13Fig. 7: Active1000-19p.13Fig. 8: Battery Pack - BPActive1000-19p.133.3.2 Active 2000-19 and Active 3000-19p.14Fig. 9: Active2000-19p.14Fig. 10: Battery Pack - BPActive3000-19p.143.3.3 Active3000-19p.14Fig. 11: Active3000 -19p.14Fig. 12: BPActive3000-19p.14Chapter 4 Active Installation and Commissioningp.154.1 Commissioning of an External Battery Cabinetp.16Table 2. External Battery Packsp.16Fig. 13: Connection of Battery Extensions for devices Active 1000p.16Chapter 5 Operational Characteristics (Active)p.175.1 Ready for Operation Checkp.175.2 Self Testp.175.3 Modes of Operationp.185.3.1 Normal Operation, Inverter On (Mains Available)p.18Fig. 14: Front Display Panel During Normal Operations (Mains Available)p.185.3.2 Battery Operation, Inverter On (Mains Failure)p.18Fig. 15: Front Display Panel During Battery Operation (Mains Failure)p.185.3.3 Bypass Operation, Inverter OFF (Overload > 140%)p.19Fig. 16: Front Display Panel During Bypass Operation (Overload > 140%)p.19Chapter 6 Description of the Interface (Active)p.206.1 Standard Interface COM Ap.20Fig. 17: COM A signal Definition and Connectionp.20Table 3. Interface COM Ap.216.2 Optional Interface COM Bp.21Fig. 18: Simplified Schematic of Interface Connectionsp.21Chapter 7 Maintenance (Active)p.237.1 Storagep.231. Connect the UPS to a grounded receptacle.p.232. Pull out the mains plug after 8 hours.p.233. Note the date of charging on the packing.p.237.2 Cleaningp.23Chapter 8 Troubleshooting (Active)p.24Table 4. Troubleshootingp.24Chapter 9 Technical Support for your Active UPSp.259.1 Chloride Technical Supportp.25Chapter 10 Active Tower and Rackmount Specificationsp.26Table 5. Chloride Active UPS North Americap.26Table 6. Active Rackmount Technical Data for North American Modelsp.2910.1 Battery Lifetimep.30Fig. 19: Typical lifetime of the batteriesp.30Chapter 11 Chloride Introductionp.3111.1 Registering your Chloride E-Series UPSp.3111.2 Technical Support and Service (E-Series)p.3111.3 Safety Notesp.3111.4 Warning for E-Series E61, E101 and E203p.32Chapter 12 Display and Operation Elements (E-Series)p.3312.1 Frontp.3412.2 Rearp.3512.2.1 E-Series E61 and E101p.35Fig. 20: E41 or E61p.35Fig. 21: E81 or E101p.3612.2.2 E-Series E203p.36Fig. 22: E203p.36Chapter 13 E-Series Installation and Commissioningp.3713.1 Installation of the E-Series (Hardwired)p.371. Unpack and move E-Series UPS and battery cabinet(s), if supplied, into desired installation location.p.372. Adjust leveling jacks under the UPS and battery cabinet(s) to remove wheels of the units from the floor and avoid movement of connections.p.373. Turn off input and output breakers on the back of the UPS and any battery cabinets to be used.p.374. Turn off and isolate the power source to be used for the UPS input using proper lock-out/tag-out procedures.p.375. Confirm that the power source to be used for the UPS is 208 V (208/120 3 f for E203).p.376. Remove the connection plate on the back of the UPS to expose connection terminals.p.377. Wire input of the UPS by first connecting ground (earth) wire to GND (ground) terminal. Next, connect the input power leads t...p.378. If the UPS does not have an attached Power Distribution Unit (PDU), wire the output of the UPS to appropriate load as follows:p.379. Connect the UPS to the battery cabinet(s) (if required)p.3710. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires are pinched or damaged.p.3811. Confirm that all input and output breakers on the UPS and battery cabinet(s) are in the OFF position.p.3812. Restore power source to the UPS.p.38Table 7. Minimum Requirements for E-Series UPS Installationp.39Fig. 23: Wiring Diagram for the E61p.39Fig. 24: Wiring Diagram for the E101p.40Fig. 25: Wiring Diagram for the E153 and E203p.40Fig. 26: E203 Power Systemp.4013.2 Commissioning of the E-Seriesp.411. Before using the device, charge the batteries for 8 hours.p.412. After charging, connect the loads to the UPS.p.413. When the signal interface is used, then the connection cable (accessories) is linked between UPS and computer system. Please see instructions in the documentation for the accessories.p.414. Switch on the loads.p.415. Switch on the UPS by operating the switch | on the front panel.p.4113.3 Starting Up the E-Seriesp.411. Switch on the input circuit breaker on the back of the UPS.p.412. When connected to the mains, the batteries automatically begin charging. The UPS may be used immediately, however, full run time will not be available until the batteries are fully chargedp.413. Before using the device, charge the batteries for 8 hours.p.414. After battery charging is completed, switch on the output circuit breaker at the rear side of the UPS. The loads are now supplied by the UPS.p.415. If a signal interface cable is used, connect the cable (accessory) between the UPS and the computer system. Please observe further instructions in the documentation for the accessory.p.426. Switch on the loads.p.427. Switch on the UPS by operating the switch | at the front plate.p.4213.4 Commissioning of an External Battery Cabinetp.43Table 8. External Battery Packsp.43Fig. 27: Connection of an External Battery Cabinet to Type E61p.43Fig. 28: Connection of an External Battery Cabinet to Type E101p.44Fig. 29: Connection of an External Battery cabinet to Type E203p.44Table 9. Technical data of the connection cablep.44Chapter 14 Operational Characteristics (E-Series)p.4514.1 Ready for Operation Checkp.4514.2 Self Testp.4514.3 Modes of Operationp.4614.3.1 Normal Operation, Inverter On (Mains Available)p.46Fig. 30: Front Display Panel During Normal Operations (Mains Available)p.4614.3.2 Battery Operation, Inverter On (Mains Failure)p.46Fig. 31: Front Display Panel During Battery Operation (Mains Failure)p.4614.3.3 Bypass Operation, Inverter OFF (Overload > 140%)p.47Fig. 32: Front Display Panel During Bypass Operation (Overload > 140%)p.47Chapter 15 Description of the Interface (E-Series)p.4815.1 Standard Interface COM Ap.48Fig. 33: COM A signal Definition and Connectionp.48Table 10. Interface COM Ap.4915.2 Optional Interface COM Bp.49Fig. 34: Simplified Schematic of Interface Connectionsp.4915.3 Emergency Power Off (EPO)p.50Chapter 16 Maintenance (E-Series)p.5116.1 Storagep.511. Install the hard-wire connections according to chapter 13 “E-Series Installation and Commissioning” on page 33 at an appropriate source. Switch on the input circuit breaker at the rear of the device for hardwired connection.p.512. Switch off the input circuit breaker of the UPS. Then remove the connections of the UPS in an inverted sequence to what is described in chapter 13 “E-Series Installation and Commissioning” on page 33.p.513. Note the date of charging on the packing.p.5116.2 Cleaningp.51Chapter 17 Troubleshooting (E-Series)p.52Table 11. Troubleshootingp.52Chapter 18 Technical Support for your E-Series UPSp.5318.1 Chloride Technical Supportp.53Chapter 19 E-Series Specificationsp.54Table 12. Chloride E-Series UPS North Americap.5419.1 Battery Lifetimep.57Fig. 35: Typical lifetime of the batteriesp.5719.2 Optional Power Distribution Units (PDU) available 4 -10 kVA.p.57Fig. 36: Optional Power Distribution Unitsp.57
Page 4 of the Rackmount Solutions VA 6000 user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

UPLIT039 Front Page.pdfp.1important safety instructionsp.2save these instructions.p.2Please read and save these instructions. This manual contains important instructions for Chloride models:p.2Follow these instructions during installation and maintenance of the UPS and batteries.p.2If you have a problem with the UPS, please refer to this manual before calling the Technical Support Department. The Troubleshooting section on pages 20 and 53 address most UPS-related issues.p.2This equipment was tested and complies with the limits for a Class A digital device, pursuant to Part 15 of FCC Rules. These lim...p.2Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 USA Telephone: (847) 990-3228 Toll Free: (800) 239-2257 Facsimile: (800) 833-6829p.2UPLIT039 TOC.pdfp.1Chapter 1 Chloride Introduction 1p.3Chapter 2 Display and Operation Elements (Active) 3p.3Chapter 3 Active Rackmount Series 7p.3Chapter 4 Active Installation and Commissioning 11p.3Chapter 5 Operational Characteristics (Active) 13p.3Chapter 6 Description of the Interface (Active) 16p.3Chapter 7 Maintenance (Active) 19p.3Chapter 8 Troubleshooting (Active) 20p.3Chapter 9 Technical Support for your Active UPS 21p.3Chapter 10 Active Tower and Rackmount Specifications 22p.3Chapter 11 Chloride Introduction 27p.3Chapter 12 Display and Operation Elements (E-Series) 29p.3Chapter 13 E-Series Installation and Commissioning 33p.3Chapter 14 Operational Characteristics (E-Series) 41p.4Chapter 15 Description of the Interface (E-Series) 44p.4Chapter 16 Maintenance (E-Series) 47p.4Chapter 17 Troubleshooting (E-Series) 48p.4Chapter 18 Technical Support for your E-Series UPS 49p.4Chapter 19 E-Series Specifications 50p.4UPLIT039 Active and ESeries Rev 0.pdfp.1Chapter 1 Chloride Introductionp.51.1 Registering your Chloride Active UPSp.51.2 Technical Support and Service (Active)p.51.3 Safety Notesp.5Chapter 2 Display and Operation Elements (Active)p.72.1 Frontp.82.2 Rearp.92.2.1 Active 700 and 1000p.9Fig. 1: Active 700 Rear Viewp.9Fig. 2: Active 1000 Rear Viewp.92.2.2 Active 2000 and 3000p.10Fig. 3: Active 2000 Rear Viewp.10Fig. 4: Active 3000 Rear Viewp.10Chapter 3 Active Rackmount Seriesp.113.1 Safetyp.113.1.1 Intended usep.113.1.2 Further safety notesp.113.2 Installation and operating notesp.113.2.1 Selection of the mounting locationp.113.2.2 Mechanical Attachmentp.12Fig. 5: Mounting the rails at the body of the UPS or Battery-Pack.p.12Table 1. Battery Cabinetsp.123.2.3 Connection of a battery packp.123.3 Unit Rear View and Connectionsp.133.3.1 Active 700-19 and Active 1000-19p.13Fig. 6: Active700-19p.13Fig. 7: Active1000-19p.13Fig. 8: Battery Pack - BPActive1000-19p.133.3.2 Active 2000-19 and Active 3000-19p.14Fig. 9: Active2000-19p.14Fig. 10: Battery Pack - BPActive3000-19p.143.3.3 Active3000-19p.14Fig. 11: Active3000 -19p.14Fig. 12: BPActive3000-19p.14Chapter 4 Active Installation and Commissioningp.154.1 Commissioning of an External Battery Cabinetp.16Table 2. External Battery Packsp.16Fig. 13: Connection of Battery Extensions for devices Active 1000p.16Chapter 5 Operational Characteristics (Active)p.175.1 Ready for Operation Checkp.175.2 Self Testp.175.3 Modes of Operationp.185.3.1 Normal Operation, Inverter On (Mains Available)p.18Fig. 14: Front Display Panel During Normal Operations (Mains Available)p.185.3.2 Battery Operation, Inverter On (Mains Failure)p.18Fig. 15: Front Display Panel During Battery Operation (Mains Failure)p.185.3.3 Bypass Operation, Inverter OFF (Overload > 140%)p.19Fig. 16: Front Display Panel During Bypass Operation (Overload > 140%)p.19Chapter 6 Description of the Interface (Active)p.206.1 Standard Interface COM Ap.20Fig. 17: COM A signal Definition and Connectionp.20Table 3. Interface COM Ap.216.2 Optional Interface COM Bp.21Fig. 18: Simplified Schematic of Interface Connectionsp.21Chapter 7 Maintenance (Active)p.237.1 Storagep.231. Connect the UPS to a grounded receptacle.p.232. Pull out the mains plug after 8 hours.p.233. Note the date of charging on the packing.p.237.2 Cleaningp.23Chapter 8 Troubleshooting (Active)p.24Table 4. Troubleshootingp.24Chapter 9 Technical Support for your Active UPSp.259.1 Chloride Technical Supportp.25Chapter 10 Active Tower and Rackmount Specificationsp.26Table 5. Chloride Active UPS North Americap.26Table 6. Active Rackmount Technical Data for North American Modelsp.2910.1 Battery Lifetimep.30Fig. 19: Typical lifetime of the batteriesp.30Chapter 11 Chloride Introductionp.3111.1 Registering your Chloride E-Series UPSp.3111.2 Technical Support and Service (E-Series)p.3111.3 Safety Notesp.3111.4 Warning for E-Series E61, E101 and E203p.32Chapter 12 Display and Operation Elements (E-Series)p.3312.1 Frontp.3412.2 Rearp.3512.2.1 E-Series E61 and E101p.35Fig. 20: E41 or E61p.35Fig. 21: E81 or E101p.3612.2.2 E-Series E203p.36Fig. 22: E203p.36Chapter 13 E-Series Installation and Commissioningp.3713.1 Installation of the E-Series (Hardwired)p.371. Unpack and move E-Series UPS and battery cabinet(s), if supplied, into desired installation location.p.372. Adjust leveling jacks under the UPS and battery cabinet(s) to remove wheels of the units from the floor and avoid movement of connections.p.373. Turn off input and output breakers on the back of the UPS and any battery cabinets to be used.p.374. Turn off and isolate the power source to be used for the UPS input using proper lock-out/tag-out procedures.p.375. Confirm that the power source to be used for the UPS is 208 V (208/120 3 f for E203).p.376. Remove the connection plate on the back of the UPS to expose connection terminals.p.377. Wire input of the UPS by first connecting ground (earth) wire to GND (ground) terminal. Next, connect the input power leads t...p.378. If the UPS does not have an attached Power Distribution Unit (PDU), wire the output of the UPS to appropriate load as follows:p.379. Connect the UPS to the battery cabinet(s) (if required)p.3710. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires are pinched or damaged.p.3811. Confirm that all input and output breakers on the UPS and battery cabinet(s) are in the OFF position.p.3812. Restore power source to the UPS.p.38Table 7. Minimum Requirements for E-Series UPS Installationp.39Fig. 23: Wiring Diagram for the E61p.39Fig. 24: Wiring Diagram for the E101p.40Fig. 25: Wiring Diagram for the E153 and E203p.40Fig. 26: E203 Power Systemp.4013.2 Commissioning of the E-Seriesp.411. Before using the device, charge the batteries for 8 hours.p.412. After charging, connect the loads to the UPS.p.413. When the signal interface is used, then the connection cable (accessories) is linked between UPS and computer system. Please see instructions in the documentation for the accessories.p.414. Switch on the loads.p.415. Switch on the UPS by operating the switch | on the front panel.p.4113.3 Starting Up the E-Seriesp.411. Switch on the input circuit breaker on the back of the UPS.p.412. When connected to the mains, the batteries automatically begin charging. The UPS may be used immediately, however, full run time will not be available until the batteries are fully chargedp.413. Before using the device, charge the batteries for 8 hours.p.414. After battery charging is completed, switch on the output circuit breaker at the rear side of the UPS. The loads are now supplied by the UPS.p.415. If a signal interface cable is used, connect the cable (accessory) between the UPS and the computer system. Please observe further instructions in the documentation for the accessory.p.426. Switch on the loads.p.427. Switch on the UPS by operating the switch | at the front plate.p.4213.4 Commissioning of an External Battery Cabinetp.43Table 8. External Battery Packsp.43Fig. 27: Connection of an External Battery Cabinet to Type E61p.43Fig. 28: Connection of an External Battery Cabinet to Type E101p.44Fig. 29: Connection of an External Battery cabinet to Type E203p.44Table 9. Technical data of the connection cablep.44Chapter 14 Operational Characteristics (E-Series)p.4514.1 Ready for Operation Checkp.4514.2 Self Testp.4514.3 Modes of Operationp.4614.3.1 Normal Operation, Inverter On (Mains Available)p.46Fig. 30: Front Display Panel During Normal Operations (Mains Available)p.4614.3.2 Battery Operation, Inverter On (Mains Failure)p.46Fig. 31: Front Display Panel During Battery Operation (Mains Failure)p.4614.3.3 Bypass Operation, Inverter OFF (Overload > 140%)p.47Fig. 32: Front Display Panel During Bypass Operation (Overload > 140%)p.47Chapter 15 Description of the Interface (E-Series)p.4815.1 Standard Interface COM Ap.48Fig. 33: COM A signal Definition and Connectionp.48Table 10. Interface COM Ap.4915.2 Optional Interface COM Bp.49Fig. 34: Simplified Schematic of Interface Connectionsp.4915.3 Emergency Power Off (EPO)p.50Chapter 16 Maintenance (E-Series)p.5116.1 Storagep.511. Install the hard-wire connections according to chapter 13 “E-Series Installation and Commissioning” on page 33 at an appropriate source. Switch on the input circuit breaker at the rear of the device for hardwired connection.p.512. Switch off the input circuit breaker of the UPS. Then remove the connections of the UPS in an inverted sequence to what is described in chapter 13 “E-Series Installation and Commissioning” on page 33.p.513. Note the date of charging on the packing.p.5116.2 Cleaningp.51Chapter 17 Troubleshooting (E-Series)p.52Table 11. Troubleshootingp.52Chapter 18 Technical Support for your E-Series UPSp.5318.1 Chloride Technical Supportp.53Chapter 19 E-Series Specificationsp.54Table 12. Chloride E-Series UPS North Americap.5419.1 Battery Lifetimep.57Fig. 35: Typical lifetime of the batteriesp.5719.2 Optional Power Distribution Units (PDU) available 4 -10 kVA.p.57Fig. 36: Optional Power Distribution Unitsp.57
Page 5 of the Rackmount Solutions VA 6000 user manual — 1.3 Safety Notes
Page 5 · click to enlarge
Page 5

Chapter 1 Chloride Introduction

Thank you for selecting this uninterruptible power supply (UPS). Chloride’s Active UPS offers the most reliable protection from the harmful effects of electrical line disturbances for your computing and communications equipment.

1.1 Registering your Chloride Active UPS

To ensure that your Active model and serial number are registered, complete and mail the enclosed postage- paid warranty card.

1.2 Technical Support and Service (Active)

Chloride offers 24-hour technical support. To contact Chloride Technical Services:

  • Phone: (800) 879-5011
  • email: usa.service@<a href="http://chloridepower.com" rel="nofollow noopener" target="_blank">chloridepower.com</a>.

Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.

1.3 Safety Notes

UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode. Unplugging the UPS does not remove the electrical charge. To ensure that the UPS is off, push BYPASS (for a minimum of 1 second) before unplugging the UPS from the mains.

Do not use AC adaptors with only two conductors to connect the input line cord to the wall socket as this will not connect the earth ground to the equipment.

This device complies with the relevant safety regulations for uninterruptible power supplies for use in a controlled office environment. If you have any questions, please contact Chloride Technical Service at 1- 800-879-5011.

Page 6 of the Rackmount Solutions VA 6000 user manual — Chapter 1 Chloride Introduction
Page 6 · click to enlarge
Page 6
  • Transport the unit only in suitable packaging (protect against jolts and shocks).
  • If the equipment is moved indoors from a cold environment, condensation may occur. Before you place the equipment in service it must be absolutely dry. An acclimatization period of at least two hours is required.
  • This equipment must be installed in an indoor, temperature controlled environment that is free of conductive contaminants. See chapter 10, “Active Tower and Rackmount Specifications” on page 22 for specific environmental limits.
  • The Active equipment has a safety-tested power cable and may only be connected to a properly grounded receptacle.
  • The switch

(see chapter 2, “Display and Operation Elements (Active)” on page 3) does not isolate the device (UPS) from the mains. To isolate completely from the mains, the main switch must be switched off and the power plug disconnected.

  • In case of interruption of the mains voltage, the integrated battery maintains the power supply to the connected equipment.
  • Lay all cables so that nobody can stand on them or trip over them. When connecting the device to the power supply, follow the instructions in the chapter on “Active Installation and Commissioning” on page 11.
  • No data transmission lines should be connected or disconnected during a thunderstorm.
  • Make sure that no objects (e.g. pins, necklaces, paper clips, etc.) get inside the device.
  • In emergencies (e.g. damaged case, controls or power cables, penetration of liquids or foreign matter) put the device into BYPASS, disconnect the power plug and contact Chloride Technical Services at 1-800-879-5011.
  • Do not connect equipment that will overload the UPS (e.g. laser printers or vacuum cleaners) or demand DC-current (e.g. half-wave rectifiers or hair dryers).
  • When cleaning the unit, follow the instructions in chapter 7, “Maintenance (Active)” on page 19.
  • The sum of the leakage currents (protective conductor current) of the UPS and the connected devices must not exceed 3.5 mA for the types Active 700, 1000, 2000 and 3000.

Chloride Active UPS is UL listed under UL1778 for North American units.

Page 7 of the Rackmount Solutions VA 6000 user manual — Chapter 2 Display and Operation Elements (Active)
Page 7 · click to enlarge
Page 7

Chapter 2 Display and Operation Elements (Active)

The Uninterruptible Power System (UPS) is connected between AC power and the load. It protects the load against mains disturbances, especially power failures.

Its operation is based on the on-line principle. The connected load is supplied power through the UPS’s inverter. Power disturbances from the mains are suppressed which increases the loads’ operational security (PC, network server, multi-user systems etc.)

In the event of a mains failure, maintenance-free batteries provide an uninterrupted supply of energy. In practice, mains failures are of relatively short duration, dependent on the mains quality. Therefore, the UPS’ energy is in most cases sufficient to ensure continuous operation of the connected systems, until the mains is reestablished. In the event of a longer lasting mains failure it allows for controlled shutdown of connected systems.

The UPS indicates by acoustical (buzzer) and optical (LED) alarms that a mains failure has occurred and is still persistent. Battery runtimes vary depending upon load, number of batteries and environmental conditions.

The following chart shows the approximate values of the emergency runtime (assuming fully charged battery at the onset of the mains failure.)

Load in % A700 A1000 A2000 A3000 OVERLOAD >105 95-105 6 min 7 min 10 min 6 min LOAD 75-95 7 min 8 min 11 min 7 min 55-75 10 min 11 min 16 min 10 min 35-55 15 min 17 min 24 min 15 min 1-35 28 min 33 min 37 min 28 min

  • The actual battery capacity can be read from the LED-”battery” chain (see table below). Battery Capacity Battery 1 - 35% 35 - 55% 55 - 75% 75 - 95% 95 - 100%

The most reliable method for determining actual battery runtime is the application of Chloride MopUPS® software. With this software, the prospective remaining battery capacity is indicated before and during an AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application program, operating system and computer hardware, it can be ensured that in the event of a power failure the application programs are automatically closed, the subscribers logged in at the server are logged out, the data is stored and the operating systems are shut down. For further information please refer to our publication about the Chloride ManageUPS™NET SNMP Adapter.

After return of the mains voltage, the UPS automatically initiates a restart. The connected systems are restarted according to their specifications.

In the event of overload or internal failure, the load is supplied from the mains via an automatic bypass. As soon as the normal status is reestablished, automatic switchover to inverter operation is performed.

This operation manual contains all relevant information to install and operate the UPS.

Page 8 of the Rackmount Solutions VA 6000 user manual — 2.1 Front
Page 8 · click to enlarge
Page 8

2.1 Front

The OVERLOAD indicator is on when the UPS is overloaded.

Rackmount Solutions VA 6000 — 2.1 Front diagram (page 8)
Fig. 3 · 2.1 Front

The LED-chain LOAD indicates the load state of the UPS.

The BYPASS indicator is on when the UPS supplies a voltage via the bypass.

The INVERTER indicator is on when the inverter is in operation.

The LED-chain BATTERY indicates the battery’s charge state (normal operation) or the % of battery time remaining when mains fail.

The LINE indicator is on when there is mains voltage at the UPS

input.

The ALARM indicator is on when the UPS is faulty. Simulta- neously, an acoustical signal is given, which can be reset by pressing the BYPASS switch.

The switch switches the inverter off and the bypass on. The UPS still has output voltage.

Operating the switch | activates the inverter. After a delay of approximately 5 seconds the BYPASS indicator extinguishes and the INVERTER indicator illuminates.

Page 9 of the Rackmount Solutions VA 6000 user manual — 2.2.1 Active 700 and 1000
Page 9 · click to enlarge
Page 9

2.2 Rear

2.2.1 Active 700 and 1000

Rackmount Solutions VA 6000 — 2.2.1 Active 700 and 1000 diagram (page 9)
Fig. 4 · 2.2.1 Active 700 and 1000

Selector switch Interface COM A Interface COM B (optional)

Selector switch - for output voltage. The selection of the output voltage must be made with the UPS switched off and unplugged.*

Input fuse - the fuse may only be changed when the device is switched off and unplugged.

Fig. 1Active 700 Rear View
Rackmount Solutions VA 6000 — 2.2.1 Active 700 and 1000 diagram (page 9)
Fig. 5 · 2.2.1 Active 700 and 1000

Selector switch - for output voltage. The selection of the output voltage must be made with the UPS switched off and unplugged.*

Interface COM B (optional)

Connection for additional bat-

Input fuse - the fuse may only be changed when the device is switched off and unplugged.

Fig. 2Active 1000 Rear View

* Call Chloride Technical Services for information on setting output voltages (1-800-879-5011).

Show 11 more labels / short text on this page
Fan · Input fuse · Mains connection · Output receptacles · Selector switch · Interface COM A · teries · Fan · Input fuse · Mains (input) connection · Output receptacles
Page 10 of the Rackmount Solutions VA 6000 user manual — 2.2.2 Active 2000 and 3000
Page 10 · click to enlarge
Page 10

2.2.2 Active 2000 and 3000

Selector switch - for output voltage. The selection of the output voltage must be made with the UPS switched off and unplugged.*

Rackmount Solutions VA 6000 — 2.2.2 Active 2000 and 3000 diagram (page 10)
Fig. 6 · 2.2.2 Active 2000 and 3000

Selector switch Interface COM A Interface COM B (optional)

Connection for additional batteries Fans Output Receptacle Output Receptacle Fuses Input circuit breaker

Fig. 3Active 2000 Rear View

Selector Swith - for output voltage The selection of the output voltage must be made with the UPS switched off and unplugged.*

Rackmount Solutions VA 6000 — 2.2.2 Active 2000 and 3000 diagram (page 10)
Fig. 7 · 2.2.2 Active 2000 and 3000

Selector switch Interface COM A Interface COM B (optional) Connection for additional bat- teries

Fig. 4Active 3000 Rear View

* Call Chloride Technical Services for information on setting output voltages (1-800-879-5011)

Show 5 more labels / short text on this page
Linecord Output receptacles · Fans · Output Receptacle · Input circuit breaker · Linecord
Page 11 of the Rackmount Solutions VA 6000 user manual — 3.2.1 Selection of the mounting location
Page 11 · click to enlarge
Page 11

Chapter 3 Active Rackmount Series

The technical data of the Active Rackmount UPS corresponds to the standard unit series Active, except for the details which are explained below. The Active Rackmount consists of the following types:

  • Active700-19, with 700 VA nominal rating
  • Active1000-19, with 1000 VA nominal rating
  • Active2000-19, with 2000 VA nominal rating
  • Active3000-19, with 3000 VA nominal rating,
  • BPActive1000-19
  • BPActive3000-19

The above listed units with a mounting height of 2 U (2 U = 3.50 inches) are designed for installation in a standard 19-inch industrial rack.

3.1 Safety

3.1.1 Intended use

This system, called “unit” in the following text, serves as an uninterruptible power supply of connected loads in a 19-inch rack. In certain configurations battery packs are part of the unit. These battery packs may only be connected electrically with the corresponding base unit.

3.1.2 Further safety notes

  • When mounting the unit into a rack, it has to be attached on both sides and the front plate of the unit has to be fixed to the rack by screws.
  • There may be connected: - up to 2 battery packs to the Active1000-19. - up to 5 battery packs to the Active2000-19 or Active3000-19.
  • The vents for air intake and outlet at the front and rear side must not be obstructed.

3.2 Installation and operating notes

3.2.1 Selection of the mounting location

The Active Rackmount units are designed to be mounted in a 19-inch rack. When installing the UPS, please consider the heavy weight of some components. Preferably, they should be installed in the lower section of the rack. UPS systems consisting of several components must be installed so that the battery packs are mounted in the lower section with the UPS mounted directly above them.

Page 12 of the Rackmount Solutions VA 6000 user manual — 3.2.3 Connection of a battery pack
Page 12 · click to enlarge
Page 12

3.2.2 Mechanical Attachment

The units must be attached in the rack on both sides. When using the attached mounting rails, the single unit can easily be inserted into a 2 U mounting space or removed from it. In order to attach the unit in the horizontal position, the front-plate has to be attached to the 19-inch rack at the indicated points on both sides of the unit.

Do not attach the unit only at the front-plate. This may damage the unit and/or other mounted units.

Rackmount Solutions VA 6000 — 3.2.2 Mechanical Attachment diagram (page 12)
Fig. 8 · 3.2.2 Mechanical Attachment

Fig. 5: Mounting the rails at the body of the UPS or Battery-Pack.

The following table shows the maximum configuration.

Table 1. Battery Cabinets

UPSType of Battery PacksMaximum Number of Packs Active700-19NoneNone Active1000-19BPActive1000-192 units Active2000-19BPActive3000-195 units Active3000-19BPActive3000-195 units

3.2.3 Connection of a battery pack

Page 13 of the Rackmount Solutions VA 6000 user manual — 3.3 Unit Rear View and Connections
Page 13 · click to enlarge
Page 13

3.3 Unit Rear View and Connections

3.3.1 Active 700-19 and Active 1000-19

The following figures show the Active700-19, Active1000-19, Active2000-19 and Active 3000-19 with battery extensions.

Rackmount Solutions VA 6000 — 3.3 Unit Rear View and Connections diagram (page 13)
Fig. 9 · 3.3 Unit Rear View and Connections
Fig. 6Active700-19
Rackmount Solutions VA 6000 — 3.3 Unit Rear View and Connections diagram (page 13)
Fig. 10 · 3.3 Unit Rear View and Connections
Fig. 7Active1000-19
Rackmount Solutions VA 6000 — 3.3 Unit Rear View and Connections diagram (page 13)
Fig. 11 · 3.3 Unit Rear View and Connections
Fig. 8Battery Pack - BPActive1000-19

To connect the battery pack to the unit, use the separate cable supplied.

Page 14 of the Rackmount Solutions VA 6000 user manual — 3.3.3 Active3000-19
Page 14 · click to enlarge
Page 14

3.3.2 Active 2000-19 and Active 3000-19

Rackmount Solutions VA 6000 — 3.3.2 Active 2000-19 and Active 3000-19 diagram (page 14)
Fig. 12 · 3.3.2 Active 2000-19 and Active 3000-19
Fig. 9Active2000-19
Rackmount Solutions VA 6000 — 3.3.2 Active 2000-19 and Active 3000-19 diagram (page 14)
Fig. 13 · 3.3.2 Active 2000-19 and Active 3000-19
Fig. 10Battery Pack - BPActive3000-19

3.3.3 Active3000-19

Rackmount Solutions VA 6000 — 3.3.3 Active3000-19 diagram (page 14)
Fig. 14 · 3.3.3 Active3000-19
Fig. 11Active3000-19
Fig. 12BPActive3000-19
Page 15 of the Rackmount Solutions VA 6000 user manual — Chapter 4 Active Installation and Commissioning
Page 15 · click to enlarge
Page 15

Chapter 4 Active Installation and Commissioning

Upon receipt of your UPS, carefully examine the packing containers for any sign of physical damage. Notify the carrier immediately if damage is present. Carefully unpack the UPS. Retain the packaging for reuse or disposal.

UPS includes:

  • UPS device
  • Connection cable for the UPS input
  • Output receptacles are on the UPS
Page 16 of the Rackmount Solutions VA 6000 user manual — WARNING:
Page 16 · click to enlarge
Page 16

4.1 Commissioning of an External Battery Cabinet

The following table shows the designations of the battery cabinets which are available for the UPS devices.

Table 2. External Battery Packs

Rackmount Solutions VA 6000 — 4.1 Commissioning of an External Battery Cabinet diagram (page 16)
Fig. 15 · 4.1 Commissioning of an External Battery Cabinet

Active 1000 BPActive1000-19 2x (3 x 7. 2 Ah)

Active 2000 BPActive3000-19 2x (8 x 7. 2 Ah)

Active 3000 BPActive3000-19 2x (8 x 7. 2 Ah)

Disconnect the UPS from the mains and the loads from the UPS.

Connect the battery cabinet types BP1000, BP3000 to the UPS using the supplied cable. The connection scheme is shown in the figures below. Switch the circuit breaker on the battery cabinet to the ON position.

The UPS is now ready for operation.

WARNING:

Rackmount Solutions VA 6000 — WARNING: diagram (page 16)
Fig. 16
Fig. 13Connection of Battery Extensions for devices Active 1000

Battery Plug 1 · Circuit Breaker · Battery Plug 2

Page 17 of the Rackmount Solutions VA 6000 user manual — 5.2 Self Test
Page 17 · click to enlarge
Page 17

Chapter 5 Operational Characteristics (Active)

5.1 Ready for Operation Check

To check the emergency supply feature of the UPS, it must be disconnected from the mains.

When correctly functioning with charged batteries, an acoustical signal in intervals of 4 seconds will be heard. The LED “LINE” (line voltage) indicator disappears. When the interval between the acoustical signals is reduced to 1 second, the UPS will supply energy for a maximum of 3 more minutes before it is automatically switched off.

The load will be supplied from the batteries during the specified emergency supply period. If this is not so, then please check in chapter 8 “Troubleshooting (Active)” on page 20.

Reconnect the UPS with the mains.

The UPS is now again ready for normal operation. Please note, that the batteries have to be recharged before the complete emergency supply period is again available.

5.2 Self Test

The self test is a LED test.

With the UPS connected to the AC power, switch | has to be operated for at least 1 second.

  • Acknowledgment of the input is given by a single acoustical signal.
  • The elements of the LED “BATTERY” chain are illuminated according to the battery’s load status. The “LINE” and “BYPASS” indicators are illuminated.
  • Initially all elements of the LED “LOAD” chain are illuminated. Beginning with the top indicator, all elements of this chain will extinguish one after the other. Thereafter the elements are on according to the UPS load status.
  • The “BYPASS” indicator turns off after approximately 5 seconds and the “Inverter” indicator illuminates. The load is supplied through the inverter, the energy is taken from the mains.
Page 18 of the Rackmount Solutions VA 6000 user manual — 5.3.2 Battery Operation, Inverter On (Mains Failure)
Page 18 · click to enlarge
Page 18

5.3 Modes of Operation

There are three modes of operation, when the UPS is switched on.

5.3.1 Normal Operation, Inverter On (Mains Available)

Rackmount Solutions VA 6000 — 5.3.1 Normal Operation, Inverter On (Mains Available) diagram (page 18)
Fig. 17 · 5.3.1 Normal Operation, Inverter On (Mains Available…
Fig. 14Front Display Panel During Normal Operations (Mains Available)

The loads are supplied through the inverter, the energy is taken from the mains.

5.3.2 Battery Operation, Inverter On (Mains Failure)

Rackmount Solutions VA 6000 — 5.3.2 Battery Operation, Inverter On (Mains Failure) diagram (page 18)
Fig. 18 · 5.3.2 Battery Operation, Inverter On (Mains Failure)

Lights Illuminated During Power Failure

Fig. 15Front Display Panel During Battery Operation (Mains Failure)

In the event of a mains failure, the inverter continues to supply the loads without interruption, the energy is taken from the battery.

In this operation mode, an acoustical signal is given in intervals of approximately 4 seconds. When reaching the battery’s energy minimum, this signal is given at one second intervals.

Lights Illuminated

Page 19 of the Rackmount Solutions VA 6000 user manual — 5.3.3 Bypass Operation, Inverter OFF (Overload > 140%)
Page 19 · click to enlarge
Page 19

5.3.3 Bypass Operation, Inverter OFF (Overload > 140%)

Rackmount Solutions VA 6000 — 5.3.3 Bypass Operation, Inverter OFF (Overload > 140%) diagram (page 19)
Fig. 19 · 5.3.3 Bypass Operation, Inverter OFF (Overload > 140…

Lights Illuminated in BYPASS Operation

Fig. 16Front Display Panel During Bypass Operation (Overload > 140%)

In the event of large overload (> 140%) switch-over to bypass is initiated and the inverter is blocked. The energy is taken from the mains.

This is not a normal operating status. In the event of mains failure the loads will no longer be supplied (no UPS operation).

Page 20 of the Rackmount Solutions VA 6000 user manual — 6.1 Standard Interface COM A
Page 20 · click to enlarge
Page 20

Chapter 6 Description of the Interface (Active)

The Active UPS has a standard interface COM A and an optional interface COM B. Protocol data transfer signal exchange is through COM A RS232 interface or the optional interface (COM B).

These interfaces can be used for:

  • Direct communication between UPS and a computer.
  • Integration of the UPS as client into a network with centralized monitoring.
  • Transfer of operational states to external alarm systems.

The necessary communication software packages and interface cables are available as accessories.

6.1 Standard Interface COM A

The 9-pin SUB-D connector (pin contacts) contains the RS 232 signals, 5 output signals and 1 input signal. The RS232 signal RXD can also be used as input signal, when the sequential interface is not used.

The 5 alarm outputs are open-collector outputs.

Rackmount Solutions VA 6000 — 6.1 Standard Interface COM A diagram (page 20)
Fig. 20 · 6.1 Standard Interface COM A
Fig. 17COM A signal Definition and Connection

The interface COM A is galvanically separated from all other circuits.

Page 21 of the Rackmount Solutions VA 6000 user manual — 6.2 Optional Interface COM B
Page 21 · click to enlarge
Page 21

Table 3. Interface COM A

SGN at pin 5 This connection point serves as a reference for all signals.

RXD at pin 2 and TXD at pin 3 In conforms standard RS232 configuration.

This input (pin 2: High signal +5V...+12V, tŠ 1 second, pin 5: 0V) enables the control processor to switch off the UPS in the event of a mains failure. After the mains has been reestablished, the UPS starts again independent of this signal status.

INV SHUTDOWN at pin 2

BATTERY LOW at pin 1 This output goes low, when the battery can supply current for approximately 3 more minutes at nominal load.

Pin 9 goes low and pin 6 goes high for mains voltage failure at the UPS input for a minimum of 10 seconds or when the mains voltage moves beyond the tolerance band. The signal is reset 850 ms after the mains have been reestablished.

AC FAIL at pin 9 and AC FAIL at pin 6

BYPASS ACTIVE at pin 7 This signal goes low after switching over to bypass, blocking the inverter and the energy being supplied by the mains

This output is low, when one of the alarms “BATTERY LOW”, “AC FAIL” or “BYPASS ACTIVE” is given.

SUM ALARM at pin 8

6.2 Optional Interface COM B

The optional interface COM can be equipped with various interface cards. The designation beside the plug then depends on the type of interface card.

In Figure 18, the function of the interface signals for version COM B is described. The optional interface COM B provides potential-free signalling contacts and a shutdown input and an insulated auxiliary supply.

Rackmount Solutions VA 6000 — 6.2 Optional Interface COM B diagram (page 21)
Fig. 21 · 6.2 Optional Interface COM B
Fig. 18Simplified Schematic of Interface Connections

Troubleshooting Optional Interface COM

Pin Number Condition

Page 22 of the Rackmount Solutions VA 6000 user manual — SUM ALARM
Page 22 · click to enlarge
Page 22

INV SHUTDOWN

This input (pin 3) is enabled with a high signal (+5 V to +12 V with respect to pin 4 (0 V)) and when enabled, switches off the UPS after a mains failure has occurred. After the mains has been reestablished, the UPS starts again independent of this signal status. This input must be high for one (1) second before shut off will occur.

AC FAIL

This output provides an N/O (Normally Open) contact between pins 9 and 5, and an N/C (Normally Closed) contact between pins 8 and 5. the 9-5 contact closes when the mains voltage fails at the UPS input or when the mains voltage falls below the lower limit for a minimum of 10 seconds. This contact opens approximately 850 ms after the mains have been reestablished. The 8-5 contact provides a mirror function, opening when the mains voltage fails and closing when mains power returns.

LOW BATT

This output provides a N/O contact between pins 6 and 5 and an N/C contact between pins 7 and 5. The 6- 5 contact closes when the battery has been depleted to the point that it can only supply current for approximately three (3) more minutes at nominal load. The 7-5 contact provides a mirror function opening when the battery is low.

BYPASS ACTIVE

This output provides an N/O contact between pins 1 and 5. The 1-5 contact closes after switching to the bypass mode. In the bypass mode, energy to the output of the UPS is being supplied by the mains power and not through the inverter.

SUM ALARM

This output provides an N/O contact between pins 2 and 5. The 2-5 contact closes when one of the alarms “AC FAIL,” “LOW BATT” or “BYPASS ACTIVE” is active or when the indication “ALARM” at the front- panel is on.

Page 23 of the Rackmount Solutions VA 6000 user manual — 7.2 Cleaning
Page 23 · click to enlarge
Page 23

Chapter 7 Maintenance (Active)

The UPS does not require maintenance by the user. When the battery expires, the UPS or the battery must be replaced by qualified electrical personnel.

The typical battery’s lifetime is 4 years at an ambient temperature of 25 °C. This may vary greatly depending upon load conditions, number of outages, and environmental factors.

7.1 Storage

For extended storage in moderate climates, the batteries should be charged for 8 hours every three months. Repeat it every two months in high temperature locations.

1. Connect the UPS to a grounded receptacle. 2. Pull out the mains plug after 8 hours. 3. Note the date of charging on the packing.

7.2 Cleaning

switch on the front panel and pull the plug out of the mains receptacle.

Do not use scouring powder or plastic-dissolving solutions to clean the UPS.

Do not allow liquid to get inside the UPS.

Make sure that the air vents on the UPS are not obstructed.

Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.

Page 24 of the Rackmount Solutions VA 6000 user manual — Chapter 8 Troubleshooting (Active)
Page 24 · click to enlarge
Page 24

Chapter 8 Troubleshooting (Active)

If a problem occurs in spite of the high reliability of the device, please review the following checks before calling Chloride Technical Services.

  • Is the UPS plugged into a correctly working grounded receptacle
  • Has the fuse blown or have circuit breakers tripped?

Please note the following information when you call for service:

  • Information about the device (model number, serial number from serial plate)

Full description of problem (connected loads, does the problem occur regularly or sporadically, display indicators/alarm etc.)

Table 4. Troubleshooting

Problem Possible Cause Action to Take

Main switch is OFF. Switch on main switch.

No mains voltage available.

Have mains checked by qualified electrical personnel.

No indication. No alarm.

Replace fuse by identical type or switch on circuit breaker. If the problem persists, then call Technical Services.

Input fuse has blown or input circuit breaker has tripped.

External batteries are not connected when powered.

Unit will not run without batteries. Confirm proper battery connection.

LINE Indicator is not on, acoustical alarm is given in intervals.

Normal UPS operation (see also “Operational Characteristics (Active)” on page 13).

Mains failure.

LINE Indicator is not on, although mains voltage is available, acoustical alarm is given in intervals.

Input fuse has blown or input circuit breaker has tripped.

Replace fuse with identical type or switch on circuit breaker. If the problem persists, then call Technical Services.

Press BYPASS switch, then ON switch. If normal operation does not occur, call Technical Services.

ALARM Indicator is on, continuous acoustical alarm.

UPS failure.

Over temperature. Reduce ambient temperature.

Batteries are not completely charged. Charge batteries (“Active Installation and Commissioning” on page 11) and test emergency supply time. If problem persists, then call Technical Services.

Emergency supply time is shorter than specified.

Batteries are defective or reached the end of its useful life.

Charging device is faulty.

OVERLOAD LED indicator is on. Overload at the UPS output. Reduce load to the permissible value.

Page 25 of the Rackmount Solutions VA 6000 user manual — Chapter 9 Technical Support for your Active UPS
Page 25 · click to enlarge
Page 25

Chapter 9 Technical Support for your Active UPS

9.1 Chloride Technical Support

Chloride offers 24-hour technical support. To contact Chloride Technical Services:

  • Phone: (800) 879-5011
  • email: usa.service@<a href="http://chloridepower.com" rel="nofollow noopener" target="_blank">chloridepower.com</a>

Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.

Page 26 of the Rackmount Solutions VA 6000 user manual — Chapter 10 Active Tower and Rackmount Specifications
Page 26 · click to enlarge
Page 26

Chapter 10 Active Tower and Rackmount Specifications

Table 5. Chloride Active UPS North America

UPS Model Active 700 Active 1000 Active 2000 Active 3000

Rating 700 VA 1 kVA 2 kVA 3 kVA

Voltage 120 VAC single-phase

Voltage range A 80 - 138 VAC

Frequency 50/60Hz ± 0.5%

Power factor (lambda) >0.95

Integrated battery type Lead-calcium, maintenance-free

Battery voltage (V) 24 36 96 96

Runtimes (min.) (half load/full load) 10/5 15/6 18/7 10/5

Runtimes (min.),1 battery cabinet (half load/full load) NA 70/30 100/30 60/30

Runtimes (min.), 2 battery cabinets (half load/full load) NA 130/60 200/80 120/50

Voltage 100/110/120 VAC, single-phase

Voltage tolerance ± 3%

Frequency with mains control see input frequency

Frequency with internal control 50/60 Hz, ±0. 5%

Distortion factor (linear/non-linear load) max. 4%/max. 7%

Permissible crest factor 3

Overload capability 130% for 1.5 sec., 110% for 10 sec. output short-circuit proof

Radio interference level FCC Part 15 Class A

Interference immunity IEC 801-2,level 4 / IEC 801-3,level 3; IEC 801-4,level 4 / IEC 801-5,level 2)

Show 6 more labels / short text on this page
Electrical Data · Input · Battery · Output · Common Data · Electrical safety UL1778
Page 27 of the Rackmount Solutions VA 6000 user manual — (35 °C)
Page 27 · click to enlarge
Page 27

Table 5. Chloride Active UPS North America

UPS Model Active 700 Active 1000 Active 2000 Active 3000

Protection class IP 20

Noise level mains operation < 41 dBa < 41 dBa < 50 dBa < 50 dBa

Noise level battery operation < 45 dBa

Operating temperature (ambient) + 50°F to +105°F (10°C to + 40°C) recommended +59°F to +89°F (+15°C to + 32°C)

Storage temperature +5°F to +104°F (-15°C to +40°C)

Relative humidity 20% to 90%,non-condensation

max. 10,000 ft. (3000m), above 5,000 ft. (1500m) max ambient temperature = 95°F

(35 °C)

UPS

Weight - lbs. (kg) 28.6 (13) 35.3 (16) 75 (34) 75 (34)

Dimensions - HxWxD in. (mm) 8.9 x 5.7 x 16 (225 x 145 x 405) 13.8 x 7.9 x 18.5 (350 x 200 x 470)

Weight lbs (kg) None 42 (19) 106 (48) 106 (48)

8.9 x 5.7 x 16 (225x145x4

13.8 x 7.9 x 18.5 (350 x 200 x 470)

Dimensions - HxWxD in. (mm) None

Visual LED-indication at the front side

RS232 interface Alarm contacts +5V...+12 V

Signal input +5V...+12 V

Show 13 more labels / short text on this page
Efficiency > 83% · Cooling Fan · Altitude · Mechanical Data · Battery extension · Type None BPActive · 1000 BPActive · 3000 BPActive · 05) · Signals · Audible Acoustical alarm · Communications · Ethernet (optional)
Page 28 of the Rackmount Solutions VA 6000 user manual — Chapter 10 Active Tower and Rackmount Specifications
Page 28 · click to enlarge
Page 28

Table 5. Chloride Active UPS North America

UPS Model Active 700 Active 1000 Active 2000 Active 3000

Type 5-15P 5-15P L5-20P L5-30P

Fusing mains / CB 10 A 15 A 20 A 30 A

Quantity 3 3 3/1 3/1

Type 5-15R 5-15R 5-15R/L5- 20R 5-15R/L5- 30R

Maximum current (at 120 VAC, pf = 0.7) 5.8 A 8.3 A 16.7 25 A

Interfaces COM A 9-pin SUB-D (pin contact)

Interfaces COM B (optional) Optional contact or ethernet card

External battery cabinet none keyed plug, 3-pole

Connections · Mains connections · Load connection

Page 29 of the Rackmount Solutions VA 6000 user manual — Table 6. Active Rackmount Technical Data for North American Models
Page 29 · click to enlarge
Page 29

Table 6. Active Rackmount Technical Data for North American Models

Type Active700-19 Active1000-19 Active2000-19 Active3000-19

Unit dimensions - WxHxD - in. (mm)

19 x 3.5 x 17.6 19 x 3.5 x 17.6 19 x 3.5 x 18.8 19 x 3.5 x 18.8

Body dimensions - WxHxD - in. (mm)

16.1 x 3.5 x 16.1 16.1 x 3.5 x 16.1 16.1 x 3.5 x 17.3 16.1 x 3.5 x 17.3

Weight - lbs 33 (15) 40 (18) 27 (12) 30 (13.5)

Ambient temperature +50°F to 104°F (+10°C to +40°C) 5000 ft to 10000 ft: 50°F to 95°F (1500 m to 3000 m: +10°C to +35°C)

Storage temperature +5°F to +104°F (-15°C to +40°C)

Relative Humidity 20% to 90%, non-condensing

Type of cooling Fan

RFI class FCC part 15 Class A

Efficiency > 83% > 83% > 83% > 83%

Noise level 42 dBa 42 dBa 50 dBa 50 dBa

Mains connections 5-15P 5-15P L5-20P L5-30P

Electrical load (output) (3) 5-15R (3) 5-15R (2) 5-20R (1) L5-30R

Minimum fuse protecting of mains 10 A 15 A 20 A 30 A

Battery pack - external — BPActive1000-

Battery voltage — 36 V 96 V 96 V

Net weight (kg) — 47.5 (21.5) 59.5 (27) 59.5 (27)

Dimensions — same as UPS

Show 6 more labels / short text on this page
Dimensions · Operating Data · Safety class UL1778 · Installation · 19 BPActive3000- · 19 BPActive3000-
Page 30 of the Rackmount Solutions VA 6000 user manual — 10.1 Battery Lifetime
Page 30 · click to enlarge
Page 30

10.1 Battery Lifetime

10 20 30 40 50 C 50 68 86 104 122 F

Fig. 19Typical lifetime of the batteries

Figure 19 shows the typical lifetime of the batteries which are used in the UPS devices, depending on the devices’ ambient temperature.

0,1 · Ambient Temperature

Page 31 of the Rackmount Solutions VA 6000 user manual — 11.3 Safety Notes
Page 31 · click to enlarge
Page 31

Chapter 11 Chloride Introduction

Thank you for selecting this uninterruptible power supply (UPS). Chloride’s E-Series UPS offer the most reliable protection from the harmful effects of electrical line disturbances for your computing and communications equipment.

11.1 Registering your Chloride E-Series UPS

To ensure that your E-Series model and serial number are registered, complete and mail the enclosed postage-paid warranty card.

11.2 Technical Support and Service (E-Series)

Chloride offers 24-hour technical support. To contact Chloride Technical Services:

  • Phone: (800) 388-4234 or (847)-990-3229
  • email: usa.service@<a href="http://chloridepower.com" rel="nofollow noopener" target="_blank">chloridepower.com</a>.

Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.

11.3 Safety Notes

UPSs present a different safety issue than most electrical equipment because unplugging the UPS puts it into backup mode. Unplugging the UPS does not remove the electrical charge. To ensure that the UPS is off, push BYPASS (for a minimum of 1 second) before unplugging the UPS from the mains.

Do not use AC adaptors with only two conductors to connect the input line cord to the wall socket as this will not connect the earth ground to the equipment.

This device complies with the relevant safety regulations for uninterruptible power supplies for use in a controlled office environment. If you have any questions, please contact Chloride Technical Service at (800) 388-4234 or (847) 990-3229.

  • Transport the unit only in suitable packaging (protect against jolts and shocks).
  • If the equipment is moved indoors from a cold environment, condensation may occur. Before you place
Page 32 of the Rackmount Solutions VA 6000 user manual — 11.4 Warning for E-Series E61, E101 and E203
Page 32 · click to enlarge
Page 32
  • the equipment in service it must be absolutely dry. An acclimatization period of at least two hours is required.
  • This equipment must be installed in an indoor, temperature controlled environment that is free of conductive contaminants. See chapter 19, “E-Series Specifications” on page 50 for specific environmental limits.
  • The special conditions for installing the hard-wired devices E61, E101 and E203 in chapter 13, “ESeries Installation and Commissioning” on page 33 must be observed.
  • The switch

(see chapter 12, “Display and Operation Elements (E-Series)” on page 29) does not isolate the device (UPS) from the mains. To isolate completely from the mains, the main switch must be switched off and the power plug disconnected.

  • In case of interruption of the mains voltage, the integrated battery maintains the power supply to the connected equipment.
  • Lay all cables so that nobody can stand on them or trip over them. When connecting the device to the power supply, follow the instructions in the chapter on “E-Series Installation and Commissioning” on page 33.
  • No data transmission lines should be connected or disconnected during a thunderstorm.
  • Make sure that no objects (e.g. pins, necklaces, paper clips, etc.) get inside the device.
  • In emergencies (e.g. damaged case, controls or power cables, penetration of liquids or foreign matter) put the device into BYPASS, disconnect the power plug and contact Chloride Technical Services at 1-800-388-4234 or 1-847-990-3229. The special conditions for installing the hardwired devices, E61, E101 and E203 are in chapter 13, “E-Series Installation and Commissioning” on page 33.
  • Do not connect equipment that will overload the UPS (e.g. laser printers or vacuum cleaners) or demand DC-current (e.g. half-wave rectifiers or hair dryers).
  • When cleaning the unit, follow the instructions in chapter 16, “Maintenance (E-Series)” on page 47.
  • The sum of the leakage currents (protective conductor current) of the UPS and the connected devices must not exceed 3.5 mA for the types Active 700, 1000, 2000 and 3000.

Chloride Active and E-Series UPSs are UL listed under UL1778 for North American units.

11.4 Warning for E-Series E61, E101 and E203

This product may only be sold to users with qualified personnel. In order to avoid RF, restrictions for installation or additional precautions may apply.

Page 33 of the Rackmount Solutions VA 6000 user manual — Chapter 12 Display and Operation Elements (E-Series)
Page 33 · click to enlarge
Page 33

Chapter 12 Display and Operation Elements (E-Series)

The Uninterruptible Power System (UPS) is connected between AC power and the load. It protects the load against mains disturbances, especially power failures.

Its operation is based on the on-line principle. The connected load is supplied power through the UPS’s inverter. Power disturbances from the mains are suppressed which increases the loads’ operational security (PC, network server, multi-user systems etc.)

In the event of a mains failure, maintenance-free batteries provide an uninterrupted supply of energy. In practice, mains failures are of relatively short duration, dependent on the mains quality. Therefore, the UPS’ energy is in most cases sufficient to ensure continuous operation of the connected systems, until the mains is reestablished. In the event of a longer lasting mains failure it allows for controlled shutdown of connected systems.

The UPS indicates by acoustical (buzzer) and optical (LED) alarms that a mains failure has occurred and is still persistent. Battery runtimes vary depending upon load, number of batteries and environmental conditions.

The following chart shows the approximate values of the emergency runtime (assuming fully charged battery at the onset of the mains failure.)

Load in % E61 E101 E203 OVERLOAD >105 w/BPE101 95-105 9 min 9 min 15 min LOAD 75-95 10 min 10 min 20 min 55-75 13 min 13 min 25 min 35-55 21 min 21 min 45 min 1-35 40 min 40 min 90 min

  • The actual battery capacity can be read from the LED-”battery” chain (see table below). Battery Capacity Battery 1 - 35% 35 - 55% 55 - 75% 75 - 95% 95 - 100%

The most reliable method for determining actual battery runtime is the application of Chloride MopUPS® software. With this software, the prospective remaining battery capacity is indicated before and during an AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application program, operating system and computer hardware, it can be ensured that in the event of a power failure the application programs are automatically closed, the subscribers logged in at the server are logged out, the data is stored and the operating systems are shut down. For further information please refer to our publication about the Chloride ManageUPS™NET SNMP Adapter.

After return of the mains voltage, the UPS automatically initiates a restart. The connected systems are restarted according to their specifications.

In the event of overload or internal failure, the load is supplied from the mains via an automatic bypass. As soon as the normal status is reestablished, automatic switchover to inverter operation is performed.

Page 34 of the Rackmount Solutions VA 6000 user manual — 12.1 Front
Page 34 · click to enlarge
Page 34

This operation manual contains all relevant information to install and operate the UPS.

12.1 Front

The OVERLOAD indicator is on when the UPS is overloaded.

The LED-chain LOAD indicates the load state of the UPS.

The BYPASS indicator is on when the UPS supplies a voltage via the bypass.

The INVERTER indicator is on when the inverter is in operation.

The LED-chain BATTERY indicates the battery’s charge state (normal operation) or the % of battery time remaining when mains fail.

The LINE indicator is on when there is mains voltage at the UPS

input.

The ALARM indicator is on when the UPS is faulty. Simulta- neously, an acoustical signal is given, which can be reset by pressing the BYPASS switch.

The switch switches the inverter off and the bypass on. The UPS still has output voltage.

Operating the switch | activates the inverter. After a delay of approximately 5 seconds the BYPASS indicator extinguishes and the INVERTER indicator illuminates.

Page 35 of the Rackmount Solutions VA 6000 user manual — 12.2.1 E-Series E61 and E101
Page 35 · click to enlarge
Page 35

12.2 Rear

12.2.1 E-Series E61 and E101

Rackmount Solutions VA 6000 — 12.2.1 E-Series E61 and E101 diagram (page 35)
Fig. 22 · 12.2.1 E-Series E61 and E101

Selector switch Interface COM A Interface COM B (optional)

Selector switch - for output voltage The selection of the output voltage must be made with the UPS switched off.*

(E61 with optional PDU shown)

Output circuit breaker External battery connector

Fig. 20E41 or E61

Fans · Input circuit breaker · Optional PDU

Page 36 of the Rackmount Solutions VA 6000 user manual — E-Series E203
Page 36 · click to enlarge
Page 36
Rackmount Solutions VA 6000 — Fig. 21: E81 or E101 diagram (page 36)
Fig. 23 · Fig. 21: E81 or E101

Selector switch Interface COM A Interface COM B (optional)

Selector switch - for output voltage The selection of the output voltage must be made with the UPS switched off.*

(E101 with optional PDU shown)

Output circuit breaker Input circuit breaker

Mains fuse and Battery switch

Fig. 21E81 or E101

* Call Chloride Technical Services for information on setting output voltages ((800) 388-4234 or (847) 990-3228)

E-Series E203

Selector switch - for output voltage The selection of the output voltage must be made with the UPS switched off.*

Selector switch (must be set to 230 V) EPO connection Interface COM A Interface COM B (optional)

Rackmount Solutions VA 6000 — E-Series E203 diagram (page 36)
Fig. 24 · E-Series E203

Output circuit breaker Input circuit breaker

Wiring box cover (or optional PDU)

Fig. 22E203

* Call Chloride Technical Services for information on setting output voltages at (800) 388-4234 or (847) 990-3229

Show 4 more labels / short text on this page
Fans · Optional PDU · Fans · Maintenance bypass switch
Page 37 of the Rackmount Solutions VA 6000 user manual — 13.1 Installation of the E-Series (Hardwired)
Page 37 · click to enlarge
Page 37

Chapter 13 E-Series Installation and Commissioning

Upon receipt of your UPS, carefully examine the packing containers for any sign of physical damage. Notify the carrier immediately if damage is present. Carefully unpack the UPS. Retain the packaging for reuse or dispose. Check the packing for damages.

UPS includes:

  • UPS device
  • A recharging cable is connected to external battery cabinets BPE61.

13.1 Installation of the E-Series (Hardwired)

1. Unpack and move E-Series UPS and battery cabinet(s), if supplied, into desired installation location. 2. Adjust leveling jacks under the UPS and battery cabinet(s) to remove wheels of the units from the floor and avoid movement of connections. 3. Turn off input and output breakers on the back of the UPS and any battery cabinets to be used. 4. Turn off and isolate the power source to be used for the UPS input using proper lock-out/tag-out procedures. 5. Confirm that the power source to be used for the UPS is 208 V (208/120 3 φ for E203). 6. Remove the connection plate on the back of the UPS to expose connection terminals. 7. Wire input of the UPS by first connecting ground (earth) wire to GND (ground) terminal. Next, connect the input power leads to L1/N and L2 (for E61 and E101) or L1, L2, and L3 (for E203). See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gauge, wire temperature and screw torque requirements.

8. If the UPS does not have an attached Power Distribution Unit (PDU), wire the output of the UPS to appropriate load as follows: Wire 208 V load between terminals marked 120A (x1) and 88B (x3). Wire 120 V loads between terminals marked 0 (x2) and 120A (x1) or 0 (x2) and 120B (x4).
9. Connect the UPS to the battery cabinet(s) (if required) See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gage, wire temperature and screw torque requirements.

For model E61 (if using an external battery cabinet), first remove the connection plate from the rear of the battery cabinet, then connect the battery cable (supplied with the battery cabinet) from the battery connector on the UPS to the terminals on the battery cabinet. Confirm that (+), (-) and GND terminals are connected to proper wires. Connect any additional battery cabinets in a “daisy-chain”

Page 38 of the Rackmount Solutions VA 6000 user manual — 10. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires are pinched or damaged.
Page 38 · click to enlarge
Page 38

manner until all GND terminals, (-) terminals and (+) terminals are connected together. See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gage, wire temperature and screw torque requirements.

For models E101 and E203, first remove the connection plate from the rear of the battery cabinet. Next, connect the wires from GND terminal on the UPS to GND wire on the battery cabinet, and then from (-) terminal on the UPS to the (-) terminal on the battery cabinet. Finally, connect (+) terminal on the UPS to the (+) terminal on the battery cabinet. Connect any additional battery cabinets in a “daisy-chain” manner until all GND terminals, (-) terminals and (+) terminals are connected together. See Table 10, “Minimum Requirements for E-Series UPS Installation,” on page 40 for minimum wire gage, wire temperature and screw torque requirements. 10. Carefully replace the connection plate(s) on the battery cabinet and the UPS, making sure that no wires are pinched or damaged. 11. Confirm that all input and output breakers on the UPS and battery cabinet(s) are in the OFF position. 12. Restore power source to the UPS.

Page 39 of the Rackmount Solutions VA 6000 user manual — . (°C)*
Page 39 · click to enlarge
Page 39

Table 7. Minimum Requirements for E-Series UPS Installation

E61 (E41) E101 (E81) E203 (E153)

Min. Wire Gaug

Min. Wire Gaug

Min. Wire Gaug

Min. Wire Temp

Min. Wire Temp . (°C)*

Min. Wire Temp . (°C)*

. (°C)*

GND Chassis Ground ** 40 75 ** 45 75 ** 45 90

L1/N Line 1 8 40 75 6 45 75 4 45 90

L2 Line 2 8 40 75 6 45 75 4 45 90

L3 Line 3 N/A 4 45 90

120A 120 V from Neutral 10 35 75 6 45 75 4 45 90

0 Neutral 10 35 75 6 45 75 4 45 90

88B 208 V from 120A 10 35 75 6 45 75 4 45 90

120B 120 V from Neutral 10 35 75 6 45 75 4 45 90

GND Chassis Ground opt 35 75 opt 45 75 opt 45 90

+ +240 VDC to - N/A N/A N/A 4 45 75 4 45 75

- Battery Common N/A N/A N/A 4 45 75 4 45 75

GND Chassis Ground N/A N/A N/A 4 45 75 4 45 75

* Use insulated copper wire rated 75 C minimum. ** Must be no smaller than wire connected to L1/N and L2 (for E61 and E101) or L1, L2, L3 (for E203).

Rackmount Solutions VA 6000 — . (°C)* diagram (page 39)
Fig. 25
Fig. 23Wiring Diagram for the E61
Show 14 more labels / short text on this page
Term · Term Torqu · Term Torqu · Term Torqu · ID Description · e (awg) · e (in- · e (awg) · e (in- · e (awg) · e (in- · lbs) · lbs) · lbs)
Page 40 of the Rackmount Solutions VA 6000 user manual — Fig. 24: Wiring Diagram for the E101
Page 40 · click to enlarge
Page 40
Rackmount Solutions VA 6000 — Fig. 24: Wiring Diagram for the E101 diagram (page 40)
Fig. 26 · Fig. 24: Wiring Diagram for the E101
Fig. 24Wiring Diagram for the E101
Rackmount Solutions VA 6000 — Fig. 24: Wiring Diagram for the E101 diagram (page 40)
Fig. 27 · Fig. 24: Wiring Diagram for the E101
Fig. 25Wiring Diagram for the E153 and E203
Rackmount Solutions VA 6000 — Fig. 24: Wiring Diagram for the E101 diagram (page 40)
Fig. 28 · Fig. 24: Wiring Diagram for the E101
Fig. 26E203 Power System
Page 41 of the Rackmount Solutions VA 6000 user manual — 13.3 Starting Up the E-Series
Page 41 · click to enlarge
Page 41

13.2 Commissioning of the E-Series

When connected to the mains, the batteries automatically begin charging. The UPS may be used immediately, however, full run time will not be available until the batteries are fully charged.

1. Before using the device, charge the batteries for 8 hours. 2. After charging, connect the loads to the UPS.
3. When the signal interface is used, then the connection cable (accessories) is linked between UPS and computer system. Please see instructions in the documentation for the accessories. 4. Switch on the loads. 5. Switch on the UPS by operating the switch | on the front panel.

The “LINE” and “BYPASS” indicators and the “LOAD” (output load) indicator are illuminated. After a few seconds the “INVERTER” indicator illuminates and the “BYPASS” indicator turns off. The UPS is now in ON-LINE operation.

An overload alarm signal (1 signal per second) is heard.

13.3 Starting Up the E-Series

1. Switch on the input circuit breaker on the back of the UPS.

The “LINE” and “BYPASS” LED indicators are illuminated.

2. When connected to the mains, the batteries automatically begin charging. The UPS may be used immediately, however, full run time will not be available until the batteries are fully charged 3. Before using the device, charge the batteries for 8 hours. 4. After battery charging is completed, switch on the output circuit breaker at the rear side of the UPS. The loads are now supplied by the UPS.
Page 42 of the Rackmount Solutions VA 6000 user manual — 5. If a signal interface cable is used, connect the cable (accessory) between the UPS and the computer system. Please observe further instructions in the documentation for the accessory.
Page 42 · click to enlarge
Page 42

dryers, vacuum cleaners).

5. If a signal interface cable is used, connect the cable (accessory) between the UPS and the computer system. Please observe further instructions in the documentation for the accessory. 6. Switch on the loads. 7. Switch on the UPS by operating the switch | at the front plate.

The “LINE” and “BYPASS” indicators and the “LOAD” (output load) indicator are illuminated. After a few seconds the “INVERTER” indicator illuminates and the “BYPASS” indicator turns off. The UPS is now in ON-LINE operation.

An overload alarm signal (1 signal per second) is heard.

Page 43 of the Rackmount Solutions VA 6000 user manual — 13.4 Commissioning of an External Battery Cabinet
Page 43 · click to enlarge
Page 43

13.4 Commissioning of an External Battery Cabinet

The following table shows the designations of the battery cabinets which are available for the UPS devices.

Table 8. External Battery Packs

E61 (E41) BPE61 2x (20 x 7. 2 Ah)

E101 (E81)/ E203 (E153) BPE101 1x (20 x 38 Ah)

Disconnect the UPS from the mains and the loads from the UPS.

Connect the battery cabinet types BP1000, BP3000 and BPE61 to the UPS using the supplied cable. The connection scheme is shown in the figures below. With type BPE101, make the hard-wired connection between UPS and the battery cabinet (see figures 28 and 29 on page 40).

Switch the circuit breaker on the battery cabinet to the ON position.

The UPS is now ready for operation.

Rackmount Solutions VA 6000 — 13.4 Commissioning of an External Battery Cabinet diagram (page 43)
Fig. 29 · 13.4 Commissioning of an External Battery Cabinet

Battery Plug for Connection of an Additional Battery Extension

Fig. 27Connection of an External Battery Cabinet to Type E61

Model Cabinet Batteries

Page 44 of the Rackmount Solutions VA 6000 user manual — E101 E203
Page 44 · click to enlarge
Page 44
Rackmount Solutions VA 6000 — Fig. 28: Connection of an External Battery Cabinet to Type E101 diagram (page 44)
Fig. 30 · Fig. 28: Connection of an External Battery Cabinet t…
Fig. 28Connection of an External Battery Cabinet to Type E101
Rackmount Solutions VA 6000 — Fig. 28: Connection of an External Battery Cabinet to Type E101 diagram (page 44)
Fig. 31 · Fig. 28: Connection of an External Battery Cabinet t…
Fig. 29Connection of an External Battery cabinet to Type E203

Table 9. Technical data of the connection cable

E101 E203

Minimum permissible cable cross section 6 mm2, 8 AWG 4 AWG

Maximum permissible cable cross section 20 mm2, 4 AWG 4 AWG

Nominal operating voltage 240 VDC 240 VDC

Hardwire

Page 45 of the Rackmount Solutions VA 6000 user manual — 14.2 Self Test
Page 45 · click to enlarge
Page 45

Chapter 14 Operational Characteristics (E-Series)

14.1 Ready for Operation Check

To check the emergency supply feature of the UPS, it must be disconnected from the mains.

When correctly functioning with charged batteries, an acoustical signal in intervals of 4 seconds will be heard. The LED “LINE” (line voltage) indicator disappears. When the interval between the acoustical signals is reduced to 1 second, the UPS will supply energy for a maximum of 3 more minutes before it is automatically switched off.

The load will be supplied from the batteries during the specified emergency supply period. If this is not so, then please check in chapter 17 “Troubleshooting (E-Series)” on page 48.

Reconnect the UPS with the mains.

The UPS is now again ready for normal operation. Please note, that the batteries have to be recharged before the complete emergency supply period is again available.

14.2 Self Test

The self test is a LED test.

With the UPS connected to the AC power, switch | has to be operated for at least 1 second.

  • Acknowledgment of the input is given by a single acoustical signal.
  • The elements of the LED “BATTERY” chain are illuminated according to the battery’s load status. The “LINE” and “BYPASS” indicators are illuminated.
  • Initially all elements of the LED “LOAD” chain are illuminated. Beginning with the top indicator, all elements of this chain will extinguish one after the other. Thereafter the elements are on according to the UPS load status.
  • The “BYPASS” indicator turns off after approximately 5 seconds and the “Inverter” indicator illuminates. The load is supplied through the inverter, the energy is taken from the mains.
Page 46 of the Rackmount Solutions VA 6000 user manual — 14.3.2 Battery Operation, Inverter On (Mains Failure)
Page 46 · click to enlarge
Page 46

14.3 Modes of Operation

There are three modes of operation, when the UPS is switched on.

14.3.1 Normal Operation, Inverter On (Mains Available)

Fig. 30Front Display Panel During Normal Operations (Mains Available)

The loads are supplied through the inverter, the energy is taken from the mains.

14.3.2 Battery Operation, Inverter On (Mains Failure)

Lights Illuminated During Power Failure

Fig. 31Front Display Panel During Battery Operation (Mains Failure)

In the event of a mains failure, the inverter continues to supply the loads uninterruptedly, the energy is taken from the battery.

In this operation mode, an acoustical signal is given in intervals of approximately 4 seconds. When reaching the battery’s energy minimum, this signal is given every second.

Lights Illuminated

Page 47 of the Rackmount Solutions VA 6000 user manual — 14.3.3 Bypass Operation, Inverter OFF (Overload > 140%)
Page 47 · click to enlarge
Page 47

14.3.3 Bypass Operation, Inverter OFF (Overload > 140%)

Lights Illuminated in BYPASS Operation

Fig. 32Front Display Panel During Bypass Operation (Overload > 140%)

In the event of large overload (> 140%) switch-over to bypass is initiated and the inverter is blocked. The energy is taken from the mains.

This is not a normal operating status. In the event of mains failure the loads will no longer be supplied (no UPS operation).

Page 48 of the Rackmount Solutions VA 6000 user manual — 15.1 Standard Interface COM A
Page 48 · click to enlarge
Page 48

Chapter 15 Description of the Interface (E-Series)

The E-Series UPS has a standard interface COM A and an optional interface COM B. Protocol data transfer signal exchange is through COM A RS232 interface or the optional interface (COM B).

These interfaces can be used for:

  • Direct communication between UPS and a computer.
  • Integration of the UPS as client into a network with centralized monitoring.
  • Transfer of operational states to external alarm systems.

The necessary communication software packages and interface cables are available as accessories.

15.1 Standard Interface COM A

The 9-pin SUB-D connector (pin contacts) contains the RS 232 signals, 5 output signals and 1 input signal. The RS232 signal RXD can also be used as input signal, when the sequential interface is not used.

The 5 alarm outputs are open-collector outputs.

Rackmount Solutions VA 6000 — 15.1 Standard Interface COM A diagram (page 48)
Fig. 32 · 15.1 Standard Interface COM A
Fig. 33COM A signal Definition and Connection

The interface COM A is galvanically separated from all other circuits.

Page 49 of the Rackmount Solutions VA 6000 user manual — 15.2 Optional Interface COM B
Page 49 · click to enlarge
Page 49

Table 10. Interface COM A

SGN at pin 5 This connection point serves as a reference for all signals.

RXD at pin 2 and TXD at pin 3 In conforms standard RS232 configuration.

This input (pin 2: High signal +5V...+12V, > 1 second, pin 5: 0V) enables the control processor to switch off the UPS in the event of a mains failure. After the mains has been reestablished, the UPS starts again independent of this signal status.

INV SHUTDOWN at pin 2

BATTERY LOW at pin 1 This output goes low, when the battery can supply current for approximately 3 more minutes at nominal load.

Pin 9 goes low and pin 6 goes high for mains voltage failure at the UPS input for a minimum of 10 seconds or when the mains voltage moves beyond the tolerance band. The signal is reset 850 ms after the mains have been reestablished.

AC FAIL at pin 9 and AC FAIL at pin 6

BYPASS ACTIVE at pin 7 This signal goes low after switching over to bypass, blocking the inverter and the energy being supplied by the mains

This output is low, when one of the alarms “BATTERY LOW”, “AC FAIL” or “BYPASS ACTIVE” is given.

SUM ALARM at pin 8

15.2 Optional Interface COM B

The optional interface COM can be equipped with various interface cards. The designation beside the plug then depends on the type of interface card.

In the following the function of the interface signals for version COM B is described. The optional interface COM B provides potential-free signalling contacts and a shutdown input and an insulated auxiliary supply.

Fig. 34Simplified Schematic of Interface Connections

Pin Number Condition

Page 50 of the Rackmount Solutions VA 6000 user manual — 15.3 Emergency Power Off (EPO)
Page 50 · click to enlarge
Page 50

Troubleshooting Optional Interface COM

INV SHUTDOWN

This input (pin 3) is enabled with a high signal (+5 V to +12 V with respect to pin 4 (0 V)) and when enabled, switches off the UPS after a mains failure has occurred. After the mains has been reestablished, the UPS starts again independent of this signal status. This input must be high for one (1) second before shut off will occur.

AC FAIL

This output provides an N/O (Normally Open) contact between pins 9 and 5, and an N/C (Normally Closed) contact between pins 8 and 5. the 9-5 contact closes when the mains voltage fails at the UPS input or when the mains voltage falls below the lower limit for a minimum of 10 seconds. This contact opens approximately 850 ms after the mains have been reestablished. The 8-5 contact provides a mirror function, opening when the mains voltage fails and closing when mains power returns.

LOW BATT

This output provides a N/O contact between pins 6 and 5 and an N/C contact between pins 7 and 5. The 6- 5 contact closes when the battery has been depleted to the point that it can only supply current for approximately three (3) more minutes at nominal load. The 7-5 contact provides a mirror function opening when the battery is low.

BYPASS ACTIVE

This output provides an N/O contact between pins 1 and 5. The 1-5 contact closes after switching to the bypass mode. In the bypass mode, energy to the output of the UPS is being supplied by the mains power and not through the inverter.

SUM ALARM

This output provides an N/O contact between pins 2 and 5. The 2-5 contact closes when one of the alarms “AC FAIL,” “LOW BATT” or “BYPASS ACTIVE” is active or when the indication “ALARM” at the front- panel is on.

15.3 Emergency Power Off (EPO)

(E-Series Models E153X and E203X only)

The external connection to the EPO circuit is located next to the 9-pin SUB-D (interface com A) connector in the upper right of the back of the unit. If the circuit between the two EPO connector pins is “opened,” the output of the UPS is immediately switched off. To restart the UPS, the procedures outlined in section 13.3 on page 37 must be followed. The EPO circuit may be extended by connecting normally closed switches in series between the EPO connector pins. Activating (opening) any of the series switches will cause the UPS to shut off its output.

Page 51 of the Rackmount Solutions VA 6000 user manual — 16.2 Cleaning
Page 51 · click to enlarge
Page 51

Chapter 16 Maintenance (E-Series)

The UPS does not require maintenance by the user. When the battery expires, the UPS or the battery must be replaced by qualified electrical personnel.

The typical battery’s lifetime is 4 years at an ambient temperature of 25 °C. This may vary greatly depending upon load conditions, number of outages, and environmental factors.

16.1 Storage

For extended storage in moderate climates, the batteries should be charged for 8 hours every three months. Repeat it every two months in high temperature locations.

1. Install the hard-wire connections according to chapter 13 “E-Series Installation and Commissioning” on page 33 at an appropriate source. Switch on the input circuit breaker at the rear of the device for hardwired connection. 2. Switch off the input circuit breaker of the UPS. Then remove the connections of the UPS in an inverted sequence to what is described in chapter 13 “E-Series Installation and Commissioning” on page 33. 3. Note the date of charging on the packing.

16.2 Cleaning

switch on the front panel, switch off the input circuit breaker, isolate the source and secure it against reclosing.

Do not use scouring powder or plastic-dissolving solutions to clean the UPS.

Do not allow liquid to get inside the UPS.

Make sure that the air vents on the UPS are not obstructed.

Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.

Page 52 of the Rackmount Solutions VA 6000 user manual — Chapter 17 Troubleshooting (E-Series)
Page 52 · click to enlarge
Page 52

Chapter 17 Troubleshooting (E-Series)

If a problem occurs in spite of the high reliability of the device, please review the following checks before calling Chloride Technical Services.

  • Is the UPS plugged into a correctly working grounded receptacle (or for hardwired to confirmed 208 VAC input)?
  • Has the fuse blown or have circuit breakers tripped?

Please note the following information when you call for service:

  • Information about the device (model number, serial number from serial plate)

Full description of problem (connected loads, does the problem occur regularly or sporadically, display indicators/alarm etc.)

Table 11. Troubleshooting

Problem Possible Cause Action to Take

Main switch is OFF. Switch on main switch.

No mains voltage available.

Have mains checked by qualified electrical personnel.

No indication. No alarm.

Replace fuse by identical type or switch on circuit breaker. If the problem persists, then call Technical Services.

Input fuse has blown or input circuit breaker has tripped.

External batteries are not connected when powered.

Unit will not run without batteries. Confirm proper battery connection.

LINE Indicator is not on, acoustical alarm is given in intervals.

Normal UPS operation (see also “Operational Characteristics (E- Series)” on page 41).

Mains failure.

LINE Indicator is not on, although mains voltage is available, acoustical alarm is given in intervals.

Input fuse has blown or input circuit breaker has tripped.

Replace fuse with identical type or switch on circuit breaker. If the problem persists, then call Technical Services.

Press BYPASS switch, then ON switch. If normal operation does not occur, call Technical Services.

ALARM Indicator is on, continuous acoustical alarm.

UPS failure.

Over temperature. Reduce ambient temperature.

Batteries are not completely charged. Charge batteries (“E-Series Installation and Commissioning” on page 33) and test emergency supply time. If problem persists, then call Technical Services.

Emergency supply time is shorter than specified.

Batteries are defective or reached the end of its useful life.

Charging device is faulty.

OVERLOAD LED indicator is on. Overload at the UPS output. Reduce load to the permissible value.

Page 53 of the Rackmount Solutions VA 6000 user manual — Chapter 18 Technical Support for your E-Series UPS
Page 53 · click to enlarge
Page 53

Chapter 18 Technical Support for your E-Series UPS

18.1 Chloride Technical Support

Chloride offers 24-hour technical support. To contact Chloride Technical Services:

  • Phone: (800) 388-4234 or (847) 990-3229
  • email: usa.service@<a href="http://chloridepower.com" rel="nofollow noopener" target="_blank">chloridepower.com</a>.

Please check with Chloride Technical Services before attempting to repair or return any Chloride product. If a Chloride unit needs repair or replacement, Chloride Technical Services issues a Return Material Authorization (RMA) number along with instructions on how to return the unit.

Page 54 of the Rackmount Solutions VA 6000 user manual — E101XA
Page 54 · click to enlarge
Page 54

Chapter 19 E-Series Specifications

Table 12. Chloride E-Series UPS North America

UPS Model E61XA (E41XA*)

E101XA

E203XA (E153XA*)

(E81*)

* Models may be upgraded to base kVA of UPS shown.

Rating 6 kVA 10 kVA 20 kVA

Voltage 208 VAC single-phase 208/120 three- phase

Voltage range 170 V to 276 V 176 to 276 V 177 to 240 V

Frequency 50/60Hz ± 5%

Power factor (lambda) >0.97 >0.95

Integrated battery type Lead-calcium, maintenance-free None

Battery voltage (V) 240

Runtimes (min.) (half load/full load) 25/8 30/12 N/A

Runtimes (min.),1 battery cabinet (half load/full load) 94/38 100/40 40/15

Voltage - North American 120, 208, 240 VAC, single-phase

Voltage tolerance ± 3%

Frequency with mains control see input frequency

Frequency with internal control 50/60 Hz, ± 0.5%

Distortion factor (linear/non-linear load) max. 4%/max. 7% max. 5%/ max.

Permissible crest factor 3

Overload capability 130% for 2 sec., 110% for 10 sec. output short-circuit proof

Radio interference level FCC Part 15 Class A

Show 7 more labels / short text on this page
Electrical Data · Input · Battery · Output Voltage · 8% · Common Data · Electrical safety UL1778
Page 55 of the Rackmount Solutions VA 6000 user manual — (35 °C)
Page 55 · click to enlarge
Page 55

Table 12. Chloride E-Series UPS North America

UPS Model E61XA (E41XA*)

E101XA

E203XA (E153XA*)

(E81*)

Interference immunity IEC 801-2,level 4 / IEC 801-3,level 3 IEC 801-4,level 4 / IEC 801-5,level 2

Efficiency > 86% >90% >85%

Noise level mains operation < 50 dBa < 55 dBa

Noise level battery operation < 55 dBa

Operating temperature + 50°F to +105°F (+10°C to + 40°C) recommended +59°F to +89°F (+15°C to + 32°C)

Storage temperature +5°F to +104°F (-15°C to +40°C)

Relative humidity 20% to 90%, non-condensing

max. 10,000 ft. (3,000m), above 5,000 ft. (1,500m) max ambient temperature = 95°F

(35 °C)

UPS

Weight - lbs. 347 580 787

46.5 x 16.5 x 31.5 (1180 x 420 x

Dimensions - HxWxD in. (mm) 27.8 x 10.6 x 22.5 (705 x 270 x 570)

38 x 13.4 x 25 (965 x 340 x 670)

Weight lbs 337 894

Dimensions - HxWxD in. (mm) 27.8 x 10.6 x 22.5 (705 x 270 x 570)

38 x 15 x 26.4 (965 x 380 x 670)

Visual LED-indication at the front side

RS232 interface Alarm contacts +5V...+12V

Signal input +5V...+12V

Show 11 more labels / short text on this page
Cooling Fan · Common Data (continued) · Altitude · Mechanical Data · 800) · Battery extension · Type BPE61 BPE101 · Signals · Audible Acoustical alarm · Communications · ethernet
Page 56 of the Rackmount Solutions VA 6000 user manual — EPO N/A N/A
Page 56 · click to enlarge
Page 56

Table 12. Chloride E-Series UPS North America

UPS Model E61XA (E41XA*)

E101XA

E203XA (E153XA*)

(E81*)

hardwired min 10 AWG/6

hardwired min 6 AWG/10

hardwired 4 AWG/20 mm2

Fusing of the mains supply 35 A 63 A 60 A x 5 poles

hardwired min 10 AWG/6

hardwired min 6 AWG/10

hardwired 4 AWG/20 mm2

Interfaces COM A 9-pin SUB-D, pin contacts

Interfaces COM B (optional) 9-pin SUB-D, outlet

hardwired Min 8 AWG/6

External battery cabinet keyed plug, 3-

hardwired 4 AWG/20 mm2

hardwired removable terminal block

EPO N/A N/A

Show 20 more labels / short text on this page
Connections · mm2 · mm2 · Mains connections · max 6 AWG/16 · max 4 AWG/20 · mm2 · mm2 · Load connection · mm2 · mm2 · max 6 AWG/16 · max 4 AWG/20 · mm2 · mm2 · Connections (continued) · mm2 · pole · Max 4 AWG/20 · mm2
Page 57 of the Rackmount Solutions VA 6000 user manual — SPDU-2-8 SPDU-2-4 SPDU-3-4
Page 57 · click to enlarge
Page 57

19.1 Battery Lifetime

10 20 30 40 50 C 50 68 86 104 122 F

Fig. 35Typical lifetime of the batteries

Figure 19 shows the typical lifetime of the batteries which are used in the UPS devices, depending on the devices’ ambient temperature.

19.2 Optional Power Distribution Units (PDU) available 4 -10 kVA.

Rackmount Solutions VA 6000 — 19.1 Battery Lifetime diagram (page 57)
Fig. 33 · 19.1 Battery Lifetime

SPDU-2-8 SPDU-2-4 SPDU-3-4

Fig. 36Optional Power Distribution Units

0,1 · Ambient Temperature

Page 58 of the Rackmount Solutions VA 6000 user manual — Visit our website at www.chlorideups.com
Page 58 · click to enlarge
Page 58

Chloride Power Protection 28430 N Ballard Drive Lake Forest, IL 60045 United States Toll Free: (800) 239-2257 Tel: (847) 990-3228 Fax: (800) 833-6829

Visit our website at www.chlorideups.com

© 2003, UP Systems, Inc.

All other trademarks, product and corporatate names are all property of their respected owners. Specifications contained in this document are subject to change without notice.

UPLIT039 Rev. 0

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
No indication. No alarm.Main switch is OFF.Switch on main switch. p.24
No indication. No alarm.No mains voltage available.Have mains checked by qualified electrical personnel. p.24
No indication. No alarm.Input fuse has blown or input circuit breaker has tripped.Replace fuse by identical type or switch on circuit breaker. If the problem persists, then call Technical Services. p.24
No indication. No alarm.External batteries are not connected when powered.Unit will not run without batteries. Confirm proper battery connection. p.24
LINE Indicator is not on, acoustical alarm is given in intervals.Mains failure.Normal UPS operation (see also “Operational Characteristics (Active)” on page 13). p.24
LINE Indicator is not on, although mains voltage is available, acoustical alarm is given in intervals.Input fuse has blown or input circuit breaker has tripped.Replace fuse with identical type or switch on circuit breaker. If the problem persists, then call Technical Services. p.24
ALARM Indicator is on, continuous acoustical alarm.UPS failure.Press BYPASS switch, then ON switch. If normal operation does not occur, call Technical Services. p.24
ALARM Indicator is on, continuous acoustical alarm.Over temperature.Reduce ambient temperature. p.24
Emergency supply time is shorter than specified.Batteries are not completely charged.Charge batteries (“Active Installation and Commissioning” on page 11) and test emergency supply time. If problem persists, then call Technical Services. p.24
Emergency supply time is shorter than specified.Batteries are defective or reached the end of its useful life. p.24
Emergency supply time is shorter than specified.Charging device is faulty. p.24
OVERLOAD LED indicator is on.Overload at the UPS output.Reduce load to the permissible value. p.24
Emergency supply time is shorter than specified.Batteries are not completely charged.Charge batteries (“E-Series Installation and Commissioning” on page 33) and test emergency supply time. If problem persists, then call Technical Services. p.52

Ask about the Rackmount Solutions VA 6000

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Rackmount Solutions VA 6000

Be the first to ask — other owners or our team will answer.

Original document

Rackmount Solutions VA 6000 manual PDF

58 pages·1.7 MB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…