Tape Drive Installation Instructions
Tape Drive Numbering 3
Scalar 50 Tape Drive Upgrade Kits 4
Required Tools 6
Unpacking the Tape Drive 6
Installing the Tape Drives 6
Cabling the Tape Drives 7
Setting the Tape Drive SCSI ID 11
Setting the SCSI ID Using the OCP 11
Setting the SCSI ID from the Remote Management Pages 12
Determining the WWNs World Wide Names 15
Verifying Library Connectivity 18
SCSI ID Assignment with Native Fibre Channel Tape Drives 21
Document 81-81769-01 B01, September 2007 1
Introduction 3

Made in the USA.
Quantum Corporation provides this publication “as is” without warranty of any kind, either express or implied, including but not limited to the implied warranties of merchantability or fitness for a particular purpose. Quantum Corporation may revise this publication from time to time without notice.
© Copyright 2007 by Quantum Corporation. All rights reserved.
Your right to copy this document is limited by copyright law. Making copies or adaptations without prior written authorization of Quantum Corporation is prohibited by law and constitutes a punishable violation of the law.
Capacity on Demand (CoD), Crosslink Mechanism, DLT, DLTSage, DLTtape, Super DLTtape, Performance on Demand, (PoD), PRISM, PRISM Storage Architecture logo, SiteCare, StackLink, StorageCare, SuperLoader, and ValueLoader are all trademarks of Quantum Corporation. Quantum, the Quantum logo, and the DLTtape logo are all registered trademarks of Quantum Corporation.
Other trademarks may be mentioned herein which belong to other companies.

This document provides instructions for adding a tape drive to an Scalar 50 tape library. The tape drive upgrade procedure consists of the following steps:
Tape Drive Numbering 0 The Scalar 50 tape library may contain up to 4 tape drives depending on the tape drive type. Refer to the following figures:
Figure 1 Scalar 50 Cable Configuration (Full Height Drives)

Back of Library · Introduction 3


Scalar 50 Tape Drive Upgrade Kits 0 The tape drive upgrade kit differs depending on the tape drive type needed for the library. Refer to the following tables:
Table 1 Tape Drive Upgrade Kits (SDLT) SDLT Part Number PC-UUAQA-YF (DLT-S4, SCSI) PC-UU8QC-YF (DLT-S4, Native Fibre)
4 Introduction


Table 2 Tape Drive Upgrade Kits (LTO)
Introduction 5

Required Tools 0 The following tools are required to perform the tape drive upgrade procedure:
To unpack the tape drive:
1 Open the shipping carton.
2 Remove the tape drive from the carton.
The tape drive is protected by two pieces of foam and an antistatic bag.
3 Remove the foam from the wrapped tape drive. Remove the tape drive from the antistatic bag.
To install tape drives in a Scalar 50 Series library:
Note: Each tape drive ships from Quantum with a version of library firmware as well as drive firmware on the tape drive interface PWA. When you install the tape drive, the library will check the version of library firmware on the tape drive and verify if the firmware is newer than the version currently running. If the library firmware on the tape drive is newer than the version currently running on the library, the OCP will prompt you with the option to upgrade the library firmware.
1 At the back of the library, use a flat blade screwdriver to loosen the captive screws that secure the cover plate to the empty drive bay.
2 Set the cover plate aside.
6 Unpacking the Tape Drive

3 Insert the tape drive into the drive bay slowly until the connectors are seated (see figure 3).

4 Tighten the tape drive captive screws using a flat blade screwdriver.
5 Repeat steps 1 through 4 to install another tape drive in a different location, if desired.
Proceed to Cabling the Tape Drives.
After the tape drive(s) have been installed, you must connect SCSI or Fibre Channel cables to each drive.
Refer to the following figures to cable the tape drives:
Cabling the Tape Drives 7

Figure 4 Scalar 50 Cable Configuration (SCSI Full Height Drives)

Figure 5 Scalar 50 Cable Configuration (Native Fibre Channel Full Height Drives)
Back of Library Ethernet

LTO Tape drives shown. SDLT drives have a single FC port

Figure 6 Scalar 50 Cable Configuration (SCSI Half- Height Drives)
Power · Power


Figure 7 Scalar 50 Cable Configuration (Native Fibre Channel Half-Height Drives)
Cabling the Tape Drives 9

Figure 8 Scalar 50 Cable Configuration (Stacked)

The library host and Ethernet network are connected only to the Master library.
10 Cabling the Tape Drives
Ethernet

The next step in the installation procedure is to set the required SCSI ID for the new tape drive.
There are two ways to set the tape drive SCSI ID:
Setting the SCSI ID Using the OCP 0 To set the tape drive SCSI ID on an Scalar 50 Series library with an LCD:
1 From the operator control panel (OCP), press Setup from the Home screen. The OCP displays the Setup screen (see figure 9):
Figure 9 Setup Screen

2 Use the up and down arrows to highlight Cabinet and press Enter.
The Cabinet screen displays (see figure 10):
Figure 10 Library Options Screen

3 Use the up and down arrows to highlight Host bus and press Enter.
The Host bus screen displays (see figure 11):
Setting the Tape Drive SCSI ID 11
Enter

Figure 11 Host Bus Options Screen

4 Use the up and down arrows to highlight the tape drive receiving the new SCSI ID and press Enter.
5 Use the up and down arrows to select a SCSI ID and press Enter to set the ID.
6 When you have completed setting the SCSI IDs, press Exit to return to the Cabinet screen.
7 From the Ops screen, use the up and down arrows to highlight Drive Operations and press Enter.
The Drive Operations screen displays (see figure 12):
Figure 12 Drive Operations Screen

8 Use the up and down arrows to select a tape drive and press Enter.
9 Use the up and down arrows to select Off and press Enter.
The tape drive powers down and returns to the Drive Operations screen.
10 Use the up and down arrows to select On and press Enter.
The tape drive powers on and is ready for use. The tape drive installation is complete.
To set the tape drive SCSI ID on a Scalar 50 Series library from the remote management pages:
1 On the host computer, open the internet browser software.
2 In the Address field, type http://IPaddress/ where IP address is the IP address for the Quantum Scalar 50 Series library.
12 Setting the Tape Drive SCSI ID

3 Enter the username and password and click OK.
The Overview page displays (see figure 13):
Figure 13 Overview Page

4 Click the Setup tab.
The Setup tab displays.
5 Click on the SCSI tab at the top of the Setup tab.
The SCSI page displays (see figure 14).
Figure 14 SCSI Page

Setting the Tape Drive SCSI ID 13

6 To change a SCSI ID, enter the ID number in the field next to the device and click Apply.
7 From the Operations page, click on the Drives tab.
The Drives page displays (see figure 15):
Figure 15 Drives Page

8 Enter the new tape drive number
9 Select shutdown and click Apply.
The tape drive powers down.
10 Enter the new tape drive number
11 Select Power on and click Apply.
The tape drive powers on. The tape drive installation is complete.
Note: The firmware revision on the new tape drive(s) must match the firmware revision on the currently installed tape drives (of the same tape drive type). If the new tape drive has a different revision, you must download the appropriate tape drive firmware from Quantum and update the drive. All tape drives in the library must contain the same firmware revision. You can view the tape drive firmware revision on the OCP under Drive Operations.
After native Fibre Channel tape drives are installed, additional information must be gathered to complete the installation and verify connectivity. Competing the native Fibre Channel tape drive installation consists of the following steps:
Drive operations

The media changer (robot) and tape drives within the library have WWNs World Wide Names assigned to them by the system controller board (SCB). The WWNs must be determined and recorded both for the customer and for Quantum customer support. This information is important when replacing the Fibre Channel SCB and tape drives. Using the following procedures, complete table 3 and retain a copy of the table for your records. Have this table available when contacting Quantum Customer Support for any library or tape drive connectivity issues.
Table 3 Library World Wide Names
Library/Tape Drive World Wide Name (e.g. 50:05:08:40:00:16:47:00)
Using the Remote Management to Determine the WWNs 0
To determine the WWNs from the library remote management pages:
1 On the host computer, open the internet browser software.
2 In the Address field, type http://IPaddress/ where IP address is the IP address for the Quantum Scalar 50 series library.
3 Enter the username and password and click OK.
The Overview page displays (see figure 16):

Figure 16 Overview Page
4 Click Setup from the contents frame.
The management frame displays the Setup page (see figure 17).

Figure 17 Setup Page
5 Click on the SCSI/Fibre tab.
The SCSI/Fibre page displays (see figure 18).

Figure 18 SCSI/Fibre Page

6 For the Media Changer and Tape Drives, click Fibre under the Connectivity type.
The Media Changer (see figure 19) and Tape Drive Configuration (see figure 20) screen displays.
Figure 19 Media Changer Configuration Screen


Figure 20 Tape Drive Configuration Screen

World wide names (port 0 and port 1)
7 Record the WWNs for the media changer and tape drives in table 3.
Example: Drive 0 WWN is 50:05:08:40:16:6B:00, Drive 1 WWN will be 50:05:08:40:16:6B:04, Drive 2 WWN will be 50:05:08:40:16:6B:08.
8 To determine the WWN for the media changer, subtract 01h from the next to last hex byte of the WWN for Drive 0.
Example: Drive 0 WWN is 50:05:08:40:16:6B:00, Media Changer WWN will be 50:05:08:40:16:6A:00.
Verifying Library Connectivity 0 To verify the tape drive installation, you should verify that the library and tape drives are recognized from the host or from the SAN switch.
If the SAN switch is available, it is possible to verify connectivity by connecting to the switch. There are two ways to directly access the SAN switch:
or

Connect Via a Telnet Session 0
To connect via a Telnet session to a SAN switch:
1 Connect the service laptop to the SAN switch using an Ethernet cross- over cable, or by connecting to the LAN (if available).
2 On the service laptop, open a command prompt window.
3 From the command prompt, enter the following command and press :
telnet
The SAN switch login prompt displays.
4 Enter the username and password and press .
5 For Brocade switches, at the command prompt, type nsshow and press .
The nsshow command displays (see figure 21).
Figure 21 Nsshow Command

WWN for the library
WWN for the second Native Fibre channel drive
WWN for the first Native Fibre channel drive

If the world wide names are visible from the nsshow command, the connectivity is verified.
Connect Via a Web Browser 0
To connect via a web browser:
1 Connect the service laptop to the SAN switch using an Ethernet cross- over cable.
2 On the service laptop, launch a web browser such as Internet Explorer.
3 In the Address field, type http://IPaddress/ where IP address is the IP address for the SAN switch and press .
The SAN switch web based utility displays.
4 Examine the Name Server table for the status of the switch ports and the WWNs of the connected devices.
If the WWNs for the library and all tape drives are visible, the connectivity is verified.
Refer to the following sections Fibre Channel connectivity troubleshooting:
Fibre Channel Connectivity Troubleshooting 0 The following section provides Fibre Channel connectivity problems and resolutions when connecting via Fibre Channel to the SAN switch, or directly to the library and drives.
1 Medium changer and drives are not visible in the device manager
a Check all cable connections.
b Check the SAN switch port LEDs for connection status to the library Fibre Channel HBA and tape drives.
c If you are connected to the SAN switch, verify that you are connected to the same zone as the library and tape drives. If you are unsure, try one of the ports on the SAN switch that a tape drive is connected to.
d Verify that the SAN switch is powered on and operating normally.

e If you are still unable to view the Fibre Channel devices, launch the SANsurfer SANblade manager and click Connect. Accept the default “localhost” entry.
The SANblade manager displays (see figure 22).

Figure 22 SANblade Manager
The SANblade manager should display all connected Fibre Channel devices. If the library and tape drives do NOT display, check the cabling and connection status.
SCSI ID Assignment with Native Fibre Channel Tape Drives 0
With native Fibre Channel tape drives, each tape drive is it’s own Fibre Channel target with a dedicated WWN and on LUN 0. The host (including the laptop using MAGMA box) will pick up the devices and assign local SCSI IDs in the order that the SAN devices are discovered. This will in almost every case NOT match the order of the devices as they are installed in the library. This is not a problem from the customer point of view, as long as drive serialization is enabled on the library and serialization is supported by the customers ISV application. This will allow the ISV application to put the drives in the correct order within the application.
In some rare cases it may be necessary to re-map the local SCSI ID assignments so that the library changer is at SCSI ID 0 and the drive SCSI ID assignments follow in order. The important thing to remember is that the order of the SCSI IDs on your system will probably not match the order of the drives in the library. Make sure to check the SCSI ID that is assigned to the WWN of the drive you want to communicate with or you may be communicating to the wrong drive

To display the SCSI ID assignments:
1 From the SANblade manager program, click Configure.
The port configuration screen displays (see figure 23).

Figure 23 Port Configuration Screen
The port configuration screen allows you to change the SCSI ID order if the Fibre Channel HBA drive supports persistent bindings.
Click on the drop down ID box to change the SCSI ID assignment as desired.
assignment